    BIOGAS FLARE STACKS

    HT-S Type are high-performance enclosed ground flare stacks where biogas combustion temperature,

    flame retention time and destruction efficiency are the results to be achieved. Combustion occurs inside

    the base refractory combustion chamber and is completed in the upper cylindrical chamber lined with

    fiberceramic, under a controlled environment. Air flow is admitted into the combustion chamberthrough a motorized damper, depending on the combustion temperature set-point. An outer shield

    provides additional protection against radiant heat loss. The flare stack is supplied complete with gas

    train, control box fitted with touch-screen panel for operation setting and control, flame arrestor, safety

    devices, automatic air damper, thermocouple and combustion temperature control system. Operation is

    fully automatic.

    BIOGAS FILTER

    Condensate/sediment traps are designed to remove liquids and solids from biological gas, and are

    installed immediately downstream from each digester to remove the large volume of condensed water,

    and upstream from energy recovery plants. First-stage removal is accomplished by a combination ofcentrifugal force and a sharp drop in velocity as the gas enters the trap. Second-stage removal takes

    place in a stainless steel mesh where smaller size particles are separated from biological gas flow. An

    external water trap device allows for continuous disposal of condensate water

  • 7/29/2019 Biogas Flare Stacks

    3/11

    BIOGAS DRYING

    Biogas from anaerobic digestion is saturated with water vapour that has a significant negative impact on

    the performance of energy recovery units. Removal of moisture is achieved by means of cooling down

    the biogas flow so that moisture turns into condensate water that can be easily separated, collected and

    discharged. The system is based on an air-cooled fully automatic water chiller and a water/biogas heat

    exchanger. The two units are connected by a recirculating water+glicole hydraulic circuit. Condensate

    water separated in the heat exchanger is collected inside a knock-out drum from which is automatically

    disposed. The system is designed as package unit; chiller is supplied separately, for installation in non-hazardous area.

  • 7/29/2019 Biogas Flare Stacks

    4/11

    SCRUBBER

    Scrubber units UTB are the basic option for removal of biogas typical contaminants like hydrogen

    sulphyde (H2S) and are characterized by simple design and operation. Biogas is washed with a water-

    NaOH solution. In order to achieve a high purification efficiency, the washing solution and biogas are

    kept mixed as long as possible: in the first stage inside a venture jet, in the second stage through the

    layer of filling bodies which are continuously sprayed by nozzles with the washing solution. The system is

    designed as package unit and the standard version is supplied fitted with on mount electric control

    panel.

  • 7/29/2019 Biogas Flare Stacks

    5/11

    BIOGAS ANALYSIS EQUIPMENT

    Biogas analysis assists process control and can help to optimise digester operation and maximize

    methane production. It can also ensure newly installed biogas plant is operating to design specification.

    PROGECO includes in its scope of supply hand held portable instruments and fixed continuous and

    automated equipment for analysis of methane (CH4), oxygen (O2), carbon dioxide (CO2), hydrogen

    sulphyde (H2S) in biogas. Data can be stored or sent to remote PC / SCADA system.

    INSTRUMENTS SCOPE METHANE CAPTURE PROJECT

  • 7/29/2019 Biogas Flare Stacks

    6/11

  • 7/29/2019 Biogas Flare Stacks

    7/11

    General

    The Scope represents a complete design and supply comprising instruments,control panels,power

    supplies, all connecting cables, including UPS, Voltage Spike protection, data loggers and panel displays

    The scope of supply covers :

    1. Quantity 3 of remote mounted Magnetic Flow Meter DMH KOBOLD size DN 100

    2. Quantity 2 of Gas Volume Flow Meters DOG KOBOLD a flow pulsation measurement principle, with

    temperature TWL KOBOLD and Pressure Transmitter PAS KOBOLD compensation

    3. Gas Composition meters,ideally one meter with automatic gas supply switching between two gas

    sources

    4. PLC for Valve operation

    5. Data Logging

    6. Gas Conditioning

  • 7/29/2019 Biogas Flare Stacks

    8/11

    7. Electrical Panel

    The Panels are to be self - contained and sealed against the ingress of H2S that may be in the

    environment at a low level. The Scope of supply shall be point - to point tested and simulated prior to

    shipment. Key spare part are to be nominated and included. All instruments to be provided with

    calibration test certificate. Equipment for gas composition analysis that may contain gas or leak gasshould be separate from other panels to keep gas away from electronics component

    INSTALLATION

    Physical installation of field items will be by pipe fitters. Electrical installation will be by electricians as

    may be expected to be present in a palm oil mill or equipment. There shall be clear installation

    instructions in English and diagrams, annotated photographs or similiar illustrations where - ever

    possible. Installation is to be limited to physical placement and the panel, and the supply of power

    All field devices installed in pipe - work shall have a specified JIS Flange connection. Pipe spools is

    stainless steel shall contain the set of instruments required for flow measurement and sampling

    Included in the panel is to be a PLC with program according to a functional description provided. The PLC

    shall operate numbers of butterfly valves on time basis

    Multicore cable suitable for connection to valve solenoid shall be included

    MAGNETIC FLOW METERS

    Type : Magnetic Flow Meter

    Size : DN 100

    Requirement : Displays instantaneous and integrated flow capable of 4 - 20 mA output ( but currently

    this is not required) Maximum Flow 75 m3/hr, may be operated at 80 Deg C

    A grounding Ring is required as the pipe is HDPE

    Protection Class : IP67

    Each flow meter should come as a package in ne stainless steel pipe spool, so that there is a flanged pipe

    connection using JIS Flange specifications at the meter should be present in the stainless pipe that

    exaclymatches the meter bore

    The power supply to the meter shall be provided in a panel. 4 - 20 mA signal from Magnetic Flow Meter

    is not required

    GAS FLOW METERS

    Type : Volume flow flow pulsation measurement principle with temperature and preesure

    compensation

  • 7/29/2019 Biogas Flare Stacks

    9/11

    Size : DN 150 operating at about 20 - 800 mbar

    Gas quality : Wet unclean biogas containing up to 4000 mg/litre H2S, nomally 60% Methane,2% Oxygen,

    balance carbon dioxide and nitrogen

    Flow : up 3000 m3/hr

    Ex-Proof Class : Suitable for biogas service

    Protections Class : IP67

    Pressure Rating : PN 16

    Process Temperature : 30 - 55 C

    Output Requirement : Instantaneous display of Nm3/hr, pressure and temperature

    Data Logged recording recording of normalised flow pressure and temperature flow pressure transducer

    and temperaure transmitter output 4 - 20 mA Signals

    Each gas flow meter with temperature and pressure sensing should come as a complete package in one

    stainless steel pipe spool so that there is only a flanged pipe connection using JIS flange specifications at

    the meter pipe size.

    The minimum straight length of pipe upstream /downstream of the meter should be present in the

    stainless pipe that exactly macthes the meter bore

    GAS COMPOSITIONS MONITOR

    A multi -channel gas monitor will monitor two gas streams. one stream will be raw biogas where the

    H2S would be arround 2.500 ppm and saturated humidity. the other stream a scrubbed dehumidified

    biogas where the humidity would usually be about 40% and the H2S about 150 ppm If is necessary to

    switch to an air flow for a ime to refresh the sensors ( especially the H2Sinstruments) then that facility

    must be included

    All tagged streams shall be individually monitored and data logged

    The Gas composition monitor will contain the following component

    Gas suction pump, condensate trap, electronic flow rate monitoring , flame arrester

    Gas cooler

    Silica gel- bassed water trap or smiliar to indicate the gas drier is working WT 20,5 for 4/6 mm hose

    connection isteated of silica gel

    Switched to change between gas flows ( stream 1 and stream 2 or between a gas stream and air )

  • 7/29/2019 Biogas Flare Stacks

    10/11

    Sensors :

    Methane , 0 to 100% v/v

    Hydrogen Sulphide 0 to 3000 ppm

    Hydrogen Sulphide 0 to 500 ppm

    Oxygen 0 - 25%

    Carbon Doxide 0 to 100%

    PROGRAMMABLE LOGIC CONTROLLER

    It is required to operate valves ( provided by others) The PLC shall be provided with Relay output so that

    the valve solenoid may be of either 24 VDC or 24 VAC types

    PLC shall have a touch screen interface. The PLC should allow for 100 Digital outputs and will be

    programmed according to a functional description provided

    The PLC will be protected by surge suppression an a UPS

    PANEL - GAS HANDLING

    Stainless Steel outdoor type meeting IP 65 standard containing :

    Lighting Surge Arrester

    Switch Power Supply 24 VDC 120 Watt 5A

    Lighting

    UPS 1 KVA

    Power Plug for Service Porpose 16P+PE

    Circuit Breaker for each instrument 2P 2A

    Indicator Lamps

    Gas Instrumentation

    PANEL LIQUID FLOW

    Stainless Steel outdoor type meeting IP 65 standard containing :

  • 7/29/2019 Biogas Flare Stacks

    11/11

    Lighting Surge Arrester

    Switch Power Supply 24 VDC 120 Watt 5A

    Lighting

    UPS 1 KVA

    The gas flow meters shall a display at the panel one display per tag. USB interface downloading of the

    data be available without opening the panel door. Data logging may be provided from a separate (

    control room) panel i preparred be the supplier

    CABLE

    All field items shall have power supplies provide from their respective panels, Assume an average

    distance from the panel 0f 80 meter per instrument

    Valve operated by the PLC required a signal cable

    Please provide for 1000 meter of multicore and with 12 or 16 pairs in the multicore

    REFERENCE GAS

    A bottle of dry reference gas suitable for checking the instruments is to be provided. The reference gas

    proposed to contain 60% CH4,1%O2,500 ppm H2S, Balanced CO2. It must be accompanied by a

    certificate specifiying the composition and accuracy limits of the composition