BIOGAS
7/29/2019 Biogas Flare Stacks
2/11
BIOGAS FLARE STACKS
HT-S Type are high-performance enclosed ground flare stacks where biogas combustion temperature,
flame retention time and destruction efficiency are the results to be achieved. Combustion occurs inside
the base refractory combustion chamber and is completed in the upper cylindrical chamber lined with
fiberceramic, under a controlled environment. Air flow is admitted into the combustion chamberthrough a motorized damper, depending on the combustion temperature set-point. An outer shield
provides additional protection against radiant heat loss. The flare stack is supplied complete with gas
train, control box fitted with touch-screen panel for operation setting and control, flame arrestor, safety
devices, automatic air damper, thermocouple and combustion temperature control system. Operation is
fully automatic.
BIOGAS FILTER
Condensate/sediment traps are designed to remove liquids and solids from biological gas, and are
installed immediately downstream from each digester to remove the large volume of condensed water,
and upstream from energy recovery plants. First-stage removal is accomplished by a combination ofcentrifugal force and a sharp drop in velocity as the gas enters the trap. Second-stage removal takes
place in a stainless steel mesh where smaller size particles are separated from biological gas flow. An
external water trap device allows for continuous disposal of condensate water
7/29/2019 Biogas Flare Stacks
3/11
BIOGAS DRYING
Biogas from anaerobic digestion is saturated with water vapour that has a significant negative impact on
the performance of energy recovery units. Removal of moisture is achieved by means of cooling down
the biogas flow so that moisture turns into condensate water that can be easily separated, collected and
discharged. The system is based on an air-cooled fully automatic water chiller and a water/biogas heat
exchanger. The two units are connected by a recirculating water+glicole hydraulic circuit. Condensate
water separated in the heat exchanger is collected inside a knock-out drum from which is automatically
disposed. The system is designed as package unit; chiller is supplied separately, for installation in non-hazardous area.
7/29/2019 Biogas Flare Stacks
4/11
SCRUBBER
Scrubber units UTB are the basic option for removal of biogas typical contaminants like hydrogen
sulphyde (H2S) and are characterized by simple design and operation. Biogas is washed with a water-
NaOH solution. In order to achieve a high purification efficiency, the washing solution and biogas are
kept mixed as long as possible: in the first stage inside a venture jet, in the second stage through the
layer of filling bodies which are continuously sprayed by nozzles with the washing solution. The system is
designed as package unit and the standard version is supplied fitted with on mount electric control
panel.
7/29/2019 Biogas Flare Stacks
5/11
BIOGAS ANALYSIS EQUIPMENT
Biogas analysis assists process control and can help to optimise digester operation and maximize
methane production. It can also ensure newly installed biogas plant is operating to design specification.
PROGECO includes in its scope of supply hand held portable instruments and fixed continuous and
automated equipment for analysis of methane (CH4), oxygen (O2), carbon dioxide (CO2), hydrogen
sulphyde (H2S) in biogas. Data can be stored or sent to remote PC / SCADA system.
INSTRUMENTS SCOPE METHANE CAPTURE PROJECT
7/29/2019 Biogas Flare Stacks
6/11
7/29/2019 Biogas Flare Stacks
7/11
General
The Scope represents a complete design and supply comprising instruments,control panels,power
supplies, all connecting cables, including UPS, Voltage Spike protection, data loggers and panel displays
The scope of supply covers :
1. Quantity 3 of remote mounted Magnetic Flow Meter DMH KOBOLD size DN 100
2. Quantity 2 of Gas Volume Flow Meters DOG KOBOLD a flow pulsation measurement principle, with
temperature TWL KOBOLD and Pressure Transmitter PAS KOBOLD compensation
3. Gas Composition meters,ideally one meter with automatic gas supply switching between two gas
sources
4. PLC for Valve operation
5. Data Logging
6. Gas Conditioning
7/29/2019 Biogas Flare Stacks
8/11
7. Electrical Panel
The Panels are to be self - contained and sealed against the ingress of H2S that may be in the
environment at a low level. The Scope of supply shall be point - to point tested and simulated prior to
shipment. Key spare part are to be nominated and included. All instruments to be provided with
calibration test certificate. Equipment for gas composition analysis that may contain gas or leak gasshould be separate from other panels to keep gas away from electronics component
INSTALLATION
Physical installation of field items will be by pipe fitters. Electrical installation will be by electricians as
may be expected to be present in a palm oil mill or equipment. There shall be clear installation
instructions in English and diagrams, annotated photographs or similiar illustrations where - ever
possible. Installation is to be limited to physical placement and the panel, and the supply of power
All field devices installed in pipe - work shall have a specified JIS Flange connection. Pipe spools is
stainless steel shall contain the set of instruments required for flow measurement and sampling
Included in the panel is to be a PLC with program according to a functional description provided. The PLC
shall operate numbers of butterfly valves on time basis
Multicore cable suitable for connection to valve solenoid shall be included
MAGNETIC FLOW METERS
Type : Magnetic Flow Meter
Size : DN 100
Requirement : Displays instantaneous and integrated flow capable of 4 - 20 mA output ( but currently
this is not required) Maximum Flow 75 m3/hr, may be operated at 80 Deg C
A grounding Ring is required as the pipe is HDPE
Protection Class : IP67
Each flow meter should come as a package in ne stainless steel pipe spool, so that there is a flanged pipe
connection using JIS Flange specifications at the meter should be present in the stainless pipe that
exaclymatches the meter bore
The power supply to the meter shall be provided in a panel. 4 - 20 mA signal from Magnetic Flow Meter
is not required
GAS FLOW METERS
Type : Volume flow flow pulsation measurement principle with temperature and preesure
compensation
7/29/2019 Biogas Flare Stacks
9/11
Size : DN 150 operating at about 20 - 800 mbar
Gas quality : Wet unclean biogas containing up to 4000 mg/litre H2S, nomally 60% Methane,2% Oxygen,
balance carbon dioxide and nitrogen
Flow : up 3000 m3/hr
Ex-Proof Class : Suitable for biogas service
Protections Class : IP67
Pressure Rating : PN 16
Process Temperature : 30 - 55 C
Output Requirement : Instantaneous display of Nm3/hr, pressure and temperature
Data Logged recording recording of normalised flow pressure and temperature flow pressure transducer
and temperaure transmitter output 4 - 20 mA Signals
Each gas flow meter with temperature and pressure sensing should come as a complete package in one
stainless steel pipe spool so that there is only a flanged pipe connection using JIS flange specifications at
the meter pipe size.
The minimum straight length of pipe upstream /downstream of the meter should be present in the
stainless pipe that exactly macthes the meter bore
GAS COMPOSITIONS MONITOR
A multi -channel gas monitor will monitor two gas streams. one stream will be raw biogas where the
H2S would be arround 2.500 ppm and saturated humidity. the other stream a scrubbed dehumidified
biogas where the humidity would usually be about 40% and the H2S about 150 ppm If is necessary to
switch to an air flow for a ime to refresh the sensors ( especially the H2Sinstruments) then that facility
must be included
All tagged streams shall be individually monitored and data logged
The Gas composition monitor will contain the following component
Gas suction pump, condensate trap, electronic flow rate monitoring , flame arrester
Gas cooler
Silica gel- bassed water trap or smiliar to indicate the gas drier is working WT 20,5 for 4/6 mm hose
connection isteated of silica gel
Switched to change between gas flows ( stream 1 and stream 2 or between a gas stream and air )
7/29/2019 Biogas Flare Stacks
10/11
Sensors :
Methane , 0 to 100% v/v
Hydrogen Sulphide 0 to 3000 ppm
Hydrogen Sulphide 0 to 500 ppm
Oxygen 0 - 25%
Carbon Doxide 0 to 100%
PROGRAMMABLE LOGIC CONTROLLER
It is required to operate valves ( provided by others) The PLC shall be provided with Relay output so that
the valve solenoid may be of either 24 VDC or 24 VAC types
PLC shall have a touch screen interface. The PLC should allow for 100 Digital outputs and will be
programmed according to a functional description provided
The PLC will be protected by surge suppression an a UPS
PANEL - GAS HANDLING
Stainless Steel outdoor type meeting IP 65 standard containing :
Lighting Surge Arrester
Switch Power Supply 24 VDC 120 Watt 5A
Lighting
UPS 1 KVA
Power Plug for Service Porpose 16P+PE
Circuit Breaker for each instrument 2P 2A
Indicator Lamps
Gas Instrumentation
PANEL LIQUID FLOW
Stainless Steel outdoor type meeting IP 65 standard containing :
7/29/2019 Biogas Flare Stacks
11/11
Lighting Surge Arrester
Switch Power Supply 24 VDC 120 Watt 5A
Lighting
UPS 1 KVA
The gas flow meters shall a display at the panel one display per tag. USB interface downloading of the
data be available without opening the panel door. Data logging may be provided from a separate (
control room) panel i preparred be the supplier
CABLE
All field items shall have power supplies provide from their respective panels, Assume an average
distance from the panel 0f 80 meter per instrument
Valve operated by the PLC required a signal cable
Please provide for 1000 meter of multicore and with 12 or 16 pairs in the multicore
REFERENCE GAS
A bottle of dry reference gas suitable for checking the instruments is to be provided. The reference gas
proposed to contain 60% CH4,1%O2,500 ppm H2S, Balanced CO2. It must be accompanied by a
certificate specifiying the composition and accuracy limits of the composition