BMS Point Schedule
AI DI AO DO Type/description Model No QTY TypePackage Units 2
Return Air Temp/RH 4 Duct Temp Sensor TB/TI-S 2 Single twisted pair-22AWG
Cooling Coil off Temp 2 Duct Temp Sensor TB/TI-S 2 Single twisted pair-22AWG
Heater coil off Temp 2 Duct Temp Sensor TB/TI-S 2 Single twisted pair-22AWG
Room Air Temp/RH 8 Space Temp sensor TB/TS 8 Single twisted pair-22AWG
Supply fan run status 2 ADPS DPSA-400 2 Single twisted pair-22AWG
Supply fan trip status 2 VFC from PACU Ctrl Pannel Single twisted pair-22AWG
Filter status 2 ADPS DPSA-400 2 Single twisted pair-22AWG
Stage 01 Run status 2 VFC from PACU Ctrl Pannel
Stage 02 Run Status 2 VFC from PACU Ctrl PannelStage 03 Run status 2 VFC from PACU Ctrl Pannel
Stage 04 Run Status 2 VFC from PACU Ctrl Pannel
Stage 01 Trip status 2 VFC from PACU Ctrl Pannel
Stage 02 Trip Status 2 VFC from PACU Ctrl Pannel
Stage 03 Trip status 2 VFC from PACU Ctrl Pannel
Stage 04 Trip Status 2 VFC from PACU Ctrl Pannel
Stage-01 high pressure status 2 VFC from PACU Ctrl Pannel
stage-01 low pressure status 2 VFC from PACU Ctrl Pannel
Stage-02 high pressure status 2 VFC from PACU Ctrl Pannel
stage-02 low pressure status 2 VFC from PACU Ctrl PannelStage-03 high pressure status 2 VFC from PACU Ctrl Pannel
stage-03 low pressure status 2 VFC from PACU Ctrl Pannel
Stage-04 high pressure status 2 VFC from PACU Ctrl Pannel
stage-04 low pressure status 2 VFC from PACU Ctrl Pannel
Packaged A/C Stage01 On/Off Ctrl 2 relay output from DDC
Packaged A/C Stage02 On/Off Ctrl 2 relay output from DDC
Packaged A/C Stage03 On/Off Ctrl 2 relay output from DDC
Packaged A/C Stage04 On/Off Ctrl 2 relay output from DDC
Duct Heater Stage01 On/Off Ctrl 2 relay output from DDC
Duct Heater Stage02 On/Off Ctrl 2 relay output from DDC
Duct Heater Stage03 On/Off Ctrl 2 relay output from DDC
Cables
Twisted, twin pair - 22AWG
Twisted, twin pair - 22AWG
Twisted, twin pair - 22AWG
S/N DESCRIPTION
DMS 600x2
I/O POINTS PERIPHERAL DEVICES
Twisted, twin pair - 22AWG
Twisted, twin pair - 22AWG
Twisted, twin pair - 22AWG
Twisted, twin pair - 22AWG
Twisted, twin pair - 22AWG
1.5mm2Single core flexib
1.5mm2Single core flexib
1.5mm2Single core flexib
1.5mm2Single core flexib
1.5mm2Single core flexib
1.5mm2Single core flexib
1.5mm2Single core flexib
1/4
8/12/2019 BMS point schedule
2/4
BMS Point Schedule
AI DI AO DO Type/description Model No QTY Type
CablesS/N DESCRIPTION
I/O POINTS PERIPHERAL DEVICES
Duct Heater Stage04 On/Off Ctrl 2 relay output from DDC
Freez Stat 8 Twisted, twin pair - 22AWG
Exhaust fan A/M 2 Twisted, twin pair - 22AWG
Exhaust fan trip status 2 VFC from Exh.Fan Ctrl Pannel Single twisted pair-22AWG
Exhaust fan Run status 2 VFC from Exh.Fan Ctrl Pannel Single twisted pair-22AWG
Exhaust Fan On/Off Ctrl 2 relay output from DDC
Total 16 46 0 8 2650
1.5mm2Single core flexib
1.5mm2Single core flexib
2/4
8/12/2019 BMS point schedule
3/4
BMS Point Schedule
Model
Beldon - 8761/Eqv.
Beldon - 8761/Eqv.
Beldon - 8761/Eqv.
Beldon - 8761/Eqv.
Beldon - 8761/Eqv.
Beldon - 8761/Eqv.
Beldon - 8761/Eqv.
Beldon - 8723/Eqv.
Beldon - 8723/Eqv.
Beldon - 8723/Eqv.
Beldon - 8723/Eqv.
Beldon - 8723/Eqv.
Beldon - 8723/Eqv.
Beldon - 8723/Eqv.
Beldon - 8723/Eqv.
le cables - 2 nrs
le cables - 2 nrs
le cables - 2 nrs
le cables - 2 nrs
le cables - 2 nrs
le cables - 2 nrs
le cables - 2 nrs
3/4
8/12/2019 BMS point schedule
4/4
BMS Point Schedule
Model
Beldon - 8723/Eqv.
Beldon - 8723/Eqv.
Beldon - 8761/Eqv.
Beldon - 8761/Eqv.
le cables - 2 nrs
le cables - 2 nrs
4/4