DESCRIPTION

Booster Bias Supply Upgrade. November 30 th , 2011. Three new Ferrite Bias Supplies Built Two are complete – for NOvA One is fully tested and operational The other runs but needs further troubleshooting for odd slewing problem Third one is 40% complete - Booster spare - PowerPoint PPT Presentation

Citation preview

Page 1: Booster Bias Supply Upgrade

Booster Bias Supply UpgradeNovember 30th, 2011

Page 2: Booster Bias Supply Upgrade

Three new Ferrite Bias Supplies Built Two are complete – for NOvA

One is fully tested and operational The other runs but needs further troubleshooting for odd slewing

problem Third one is 40% complete - Booster spare

Finished in the next 3-4 weeks

There are 10 “Ling” MK I supplies that will need upgrading – Booster West Gallery only

Replace main rectifier Transformer – marginal power rating for 15 Hz operation.

Replace PVC SCR heat sinks – prone to LCW water leaks with any pressure surge.

Upgrade can be done one at a time by changing out supply with spare.

Page 3: Booster Bias Supply Upgrade

Ling transformer test, November 15th, 2011

2250A @ 1Hz 2250A @ 15Hz

1100 1200 1300 1400 1500 16002030405060708090

100110120

Time

Deg

C

1600 1620 1640 1660 1680 1700 17202030405060708090

100110120

outer winding center windingupper corelower core

Time

Deg

C

Page 4: Booster Bias Supply Upgrade

Ling transformer test, November 16th, 2011

2250A @ 15Hz

800 900 1000 1100 1200 1300 1400 1500 1600 1700 18000

20

40

60

80

100

120

140

outer winding center windingupper corelower core

Time

Deg

C

Page 5: Booster Bias Supply Upgrade

Ling transformer test, November 17th and 18th, 2011

2250A @ 15Hz with fans 2250A @ 15Hz with fansand top plate lifted 3.5 inches

1000110012001300140015001600170018000

20

40

60

80

100

120

Time

Deg

C

1000

1100

1200

1300

1400

1500

1600

1700

1800

0

20

40

60

80

100

120

outer winding center windingupper corelower core

Time

Deg

C

Page 6: Booster Bias Supply Upgrade

MK I Bias Supply SCR Packages – PVC cased heat sinks

Page 7: Booster Bias Supply Upgrade

New Style SCR Packages with Larger Transformer

Page 8: Booster Bias Supply Upgrade

MK I Bias Supply

Main Rectifier Transformer

Page 9: Booster Bias Supply Upgrade

MK I Bias Supply

SCR Packages with Main Rectifier Transformer - Behind

Page 10: Booster Bias Supply Upgrade

Last transformer order was in 2007. The vender was NWL and they provided six units at a cost of $16,474 ea.