    TENDER ENQUIRY NO. BHE/FP/CVL/026

    Particulars Technical Specification

    1 Under ground 11KV grade 95 sq.mm approx.

    1Km. Cable laying

    Supply and cable trench making as per drawing details 95 sq.mm XLPE 3 core Alu

    and installed route marker.

    2 11 KV grade 21 KA - 400 Amp. RMU Unit OneIncoming + Two Out going VCB

    IP-54 category 11KV grade indoor type front opening floor mounted

    3 Transformer outdoor type 750KVA 11/0.40KV Transformer 750KVA - 11/0.40KV outdoor type copper wound oil filled HT/LT side

    required. (Details in section-V i.e technical specifications

    4 DG Set 160KVA - 0.40KV grade with AMFpanel and super slient type

    DG Set 160 KVA 0.40 KV super slient type noise level 0.75 db

    5 End Termination Kit For 11 KV 95 Sq.mm x 3

    core Heat Shrinkable type 6 Indoor type +1

    Outdoor type

    Heat sink cable type outdoor and indoor in termination kit

    6 PCC Panel as details of Single l ine Diagram- ,

    detai ls as per SLD - (Panel with all incommingand outgoing feeder with AMF connection

    provision)

    PCC factory fabricated and wired metal clad dust and vermin proof mounting instrumen

    shall be separate and shall comprise of flush type a meter volt meter selector switchmetering class the board shall have suitable electrolytic Al. bus bar 1250 AMP 3.5 p

    IS 8623 insulated with heat shrink sleaving and mounted on non hygroscopic supporDMC/CMC the panel shall be fabricated with CRCA sheet with a minimum t

    1.6mm/2mm switch board shall be of cat IP-54.

    Interlock DC source ACB 1250Amp. EDO, power source transformer no. 1 (7501250Amp. EDO, transformer no. 2 (750KVA) power source ACB 1250Amp. EDO bus cinterlocked electrical and mechanical to be required.

    Interlock Motive At a time one source ACB shall be in on

    Outgoing feeder- MCCB 50K 4 pole - 250A =7Nos., 200Amp = 3Nos. and 125Amp= 2

    Equipment Details

    (a) ACB - EDO type 1250Amp, 3 Pole- 50 KA with

    Micro Processor release

    Micro processor protection . O/L, S/C, E/F with time delay.

    (b) ACB EDO type 1250 Amp, 4 Pole - 50 KA

    without release

    Micro processor protection . O/L, S/C, E/F with time delay.

    (c ) Out going MCCB Type 400Amp, 4 Pole -50KA

    with Micro Processor Release

    Micro processor protection . O/L, S/C, E/F with time delay.

    7 Chemical earthing electrode with backfillcompound 70L

    3m long dia. 70mm pipe in pipe GI earthing electrode

    TE NO.- BHE/FP/CVL/026

    ENHANCING THE 11 KV POWER SUPPLY AND ITS DISTRIBUTION INCLUDING PROVIDING, INSTALLING,COMMISSIONING

    SL NO.

    CENTRALISED STAMPING UNIT & FABRICATION PL

    BILL OF QUANTITIES (BOQ) AND PRICE S

    SUPPLY , INSTALLATION , ENGINEERING ,TESTING AND COMMISSIONING OF FOLLOWING ITEMS TENDER FOR ENHANCING THE 11

    DISTRIBUTION INCLUDING PROVIDING, INSTALLING,COMMISSIONING OF SUB STATION AND ITS EQUIPMENTS ON TURNKEY BASIS A

    ALL ITEMS TO INCLUDE PROVIDING ALL MATERIALS AND IT'S ASSEMBLY AT SITE , LABOUR, T&Ps, CONSUMABLES ETC REQUIRE

    SPECIFICATIONS AND DRAWINGS AND AS DIRECTED BY ENGINEER-IN-CHARGE FOR TYPE- A, B, C & D BLOCKS AND UTILITIES AND

    INCLUDING TRANSIT INSURANCE AND STORAGE INSURANCE AT SITE TILL HANDING OVER . BIDDER SHALL PROVIDE NOC AND INSP

    POLLUTION CONTROL BOARD OF THE GOVT./ STATUTARY BODY.

    DESCRIPTION OF ITEMS

    Page 1

  • 7/30/2019 BOQ- Sub Stn

    2/2

    TENDER ENQUIRY NO. BHE/FP/CVL/026

    TE NO.- BHE/FP/CVL/026

    ENHANCING THE 11 KV POWER SUPPLY AND ITS DISTRIBUTION INCLUDING PROVIDING, INSTALLING,COMMISSIONING O

    SL NO.

    CENTRALISED STAMPING UNIT & FABRICATION PLA

    BILL OF QUANTITIES (BOQ) AND PRICE SC

    DESCRIPTION OF ITEMS

    8 APFC 300 KVAR MPPH Capacitor Bank Ratio

    1:2:3:4:8 . Microprocessor based APFC 12

    stage relay. Custom build . CRCA 2 mm sheet.Including 630 amp ACB

    As per technical specs.

    9 Replacement of following items in the existing

    source sub station pannel for 11 KV supply:

    (a) 11 KV VCB incoming CTR 400/200/5A, 250

    MVA 63 A

    As per technical specs.

    (b) 11 KV VCB outgoing FDR CTR 200/100/5A,250 MVA

    As per technical specs.

    (a)

    (b)

    (c )

    NOTE :

    Installation of supplied equipments = 5 % of all item nos.

    Testing and commissioning of installed equipments and handing over = 5% of all item nos.

    Note : Service tax including edu. cess and SAH edu. cess at applicable rate on grand total as per SCC Clause 8.3 shall be payable extra

    Special Provisions under bidder's scope : Supplier shall provide suitable skilled, unskilled services manpower with spares and necess

    period of 24 months from the date of handing over of equipments at Jagdishpur (UP) for uninturrupted operation of the equipments and re

    provide suitable office cum storage space for the maintenance staff at si te of work during the guarantee period.

    (1) Value of the work actually executed on site in terms of Cl 16 of SCC i.e terms of payment shall be arrieved at upon completion of follo(a), (b) and (c ) defined below:

    (2) Billing breakup for payment purpose shall be as per following

    Supply at site of above equipments duly verified by BHEL/ consultant as per Bill of material = 90% of all above item nos.

    Page 2