Cutler-HammerTransfer Switches Product Focus
Delayed TransitionOpen TransitionClosed Transition
ManualNon-automaticBypass Isolation
Contactor and Breaker-basedTransfer Switches
A History of Experience,Innovation and Reliability
As a premier industrial manufacturer, Eatons electricalbusiness is one of the worldsleading suppliers of electricalcontrol products and powerdistribution equipment withyearly sales of over $2.5 billion.Eatons electrical productsinclude a complete line of lowand medium voltage assemblies from substations,switchgear and panelboards toloadcentres, transformers andsafety switches. These products are used whereverthere is a demand for electricalpower in residences, high-riseapartment and office buildings,commercial sites, hospitals and factories.
Built With Experience
For over a century, Eaton hasfocused on providing qualitypower-centric products andservices. In todays businessenvironment, customers likeyou are driving our transformation from a leadingglobal electrical componentsprovider into a customer-centric solutions partner whounderstands your business.We do this through in-depthcollaboration with customersand subject matter expertsstudying the issues inherent to the electrical power distribution and control systems.
Eaton is one of the pioneeringelectrical manufacturers andhas been focused on providingreliable backup power systemswith transfer switchequipment for over 75 years.
Powered With Innovation
Eaton continues to meetchanging industry needs by providing a broad range of automatic transfer switches.These switches may begrouped into a basic, enhanced or premium set offeatures that will meet yourapplication requirements. Eaton has used industry-leading breaker based designsfor years and now has a line ofcontactor based designs.
These designs can be matchedto a family of automatic transfer switch controllers thatwill meet your specific needs.Identify your application,define your needs, and selectthe solution from Eaton.
Delivered With Reliability
Power outages due to badweather or utility failure havegrown increasingly costly andmore disruptive to businessesand homeowners. A backuppower system will keep yourcomputers, security system,heating or refrigeration system, cash registers, homehealth care equipment, or anysystem that uses electricpower, energized and operational. The demands forreliability have increased.Eaton meets thoseexpectations by the stringentCSA C22.2 No. 178 andUL1008 automatic transferswitches with a world-classproduct delivery system.Eaton will provide the individual transfer switch builtto exacting standards or supply the same transferswitch in an integratedlineup with other Eaton gear.For startup service, applicationsupport, and emergency support, call Eaton ElectricalServices and Systems at 1-800-498-2678.
Built with years of experiencePowered with innovationDelivered with reliability
2
Eatons Cutler-Hammer
automatic transfer switchesare designed to provide youwith a full offering of transferswitches to solve your industryand application needs. Eatonoffers the industrys mostcomplete line of contactor-based, breaker-based, and Magnum stored energybased transfer switches. This wide range of selectionsenables you to identify yourapplication needs and thebenefits you expect to realize,and then choose the solutionbest for you. The corner stoneof all of these offerings is theproven design experience and reliability built into all Cutler-Hammer transferswitches.
Basic Solution
The Basic Solution offers atransfer switch that meets themost basic and cost-effectiverequirement needs for an automatic, manual or non-automatic transfer switch.This solution set allows youto choose from either acontactor-based or a breaker based design andmatch that power-switchingdevice with our basic transferswitch controller.
Enhanced Solution
The Enhanced Solution meetsall of the basic automatictransfer switch needs. In addition to meeting themost basic transfer switchrequirement, the EnhancedSolution allows for optimalcontrol and improved flexibility.This solution set allows you to choose from either a contactor based or breaker-based design.
Premium Solution
The Premium Solution isoffered for those applicationsrequiring continuity of powerduring the transfer and routinetest. This solution set offersboth contactor-based andbreaker-based designs withdrawout capability.
Switch Types Available
Open Transition Closed Transition Delayed Transition Bypass Isolation Non-Automatic Manual
TRANSFER SWITCH STANDARDS
CSA C22.2 No. 178-1978 Canadian Standards Association
UL 991 UL Standards for Safety Tests for Safety-RelatedControls Employing Solid-State Devices
UL 1008 UL Standards for Transfer Switches
NEMA ICS 109.21 Impulse Withstand Test
IEEE 472 (ANSI C37.90A) Ringing Wave Immunity/Voltage Surge Test
EN55022 (CISPR11): Conducted and Radiated Emissions
EN61000-4-2 Class B Level 4 ESD Immunity Test
EN61000-4-3 (ENV50140) Radiated RF, Electromagnetic FieldImmunity Test
EN61000-4-4 Electrical Fast Transient/Burst Immunity Test
EN61000-4-5 IEEE C62.41: Surge Immunity Test
EN61000-4-6 (ENV50141) Conducted Immunity Test
EN61000-4-11 Voltage Dips and Interruption Immunity
FCC Part 15 Conducted/Radiated Emissions (Class A)
CISPR 11 Conducted/Radiated Emissions (Class A)
IEC 1000-2 Electrostatic Discharge Test
IEC 1000-3 Radiated Susceptibility Tests
IEC 1000-4 Fast Transient Tests
IEC 1000-5 Surge Withstand Tests
CSA Conformance C22.2 No. 178-1978 (Reaffirmed 1992)
UL 869A Reference Std for Service Equipment
UL 50/508 Enclosures
NEMA ICS 1 General Standards for Industrial Control Systems
NEMA ICS 2 Standards for Industrial Control Devices,Controllersand Assemblies
NEMA ICS 6 Enclosures for Industrial Controls and Systems
NEMA ICS 10-1993 AC Automatic Transfer Switches
ANSI C33.76 Enclosures
NEC 517, 700, 701 and 702 National Electrical Code
NFPA 70 National Electrical Code
NFPA 99 Health Care Facilities
NFPA 101 Life Safety Code
NFPA 110 Emergency and Standby Power Systems
EGSA 100S Standard for Transfer Switches
Solutions Overview
3
Greater Reliability to Avoid Lost Revenue and Production Time Soft Load Ramping Continuity of Power Through Synchronization of Sources 30 Cycle, 85 kA Short-Time Ratings Lower Energy Costs Realized through Managing Demand Charges Integral Overcurrent Protection Available No Power Interruption During Switch Inspection or Testing Drawout Design
Greater Reliability to Avoid Lost Revenue and Production Time 30 Cycle, 85 kA Short-Time Ratings Safe Preventative Maintenance without Power Interruption Integral Overcurrent Protection Available No Power Interruption During Switch Inspection or Testing Integrated Service Entrance Solution
Interchangeable Bypass and Switch Devices Drawout Design
Greater Reliability to Avoid Lost Revenue and Production Time Interchangeable Bypass and Switch Devices Safe Preventative Maintenance without Power Interruption Drawout Design Standard No Power Interruption During Switch Inspection or Testing Front Access Standard
Dual ATS
Greater Reliability to Avoid Lost Revenue and Production Time 30 Cycle, 85 kA Short-Time Ratings Lower Energy Costs Realized from Managing Demand Charges Integral Overcurrent Protection Available No Power Interruption During Generator Set Testing Integrated Service Entrance Solution
Drawout Design Available
Greater Reliability to Avoid Lost Revenue and Production Time Paralleled in Less than 100 ms Lower Energy Costs Realized from Managing Demand Charges Programmable Field Settings No Power Interruption During Generator Set Testing Communication Capability
Ability to Transfer Large Motor or Inductive Loads 30 Cycle, 85 kA Short-Time Ratings on Power Circuit Breaker Allows Loads to Re-Energize after Transfer at Normal Inrush Currents Integral Overcurrent Protection Available Avoid Higher Starting Currents which Increase Energy Costs Integrated Service Entrance Solution
Ability to Transfer Large Motor or Inductive Loads Multi Tap Transformer Voltage Selection Available Allows Loads to Re-Energize after Transfer at Normal Inrush Currents Easily Adjustable Time Delays for the Neutral Position Avoid Higher Starting Currents which Increase Energy Costs
Ability to Transfer Large Motor or Inductive Loads 30 Cycle, 85 kA Short-Time Ratings on Power Circuit Breaker Allows Loads to Re-Energize after Transfer at Normal Inrush Currents Integral Overcurrent Protection Available Avoid Higher Starting Currents which Increase Energy Costs Integrated Service Entrance Solution
Drawout Design Available
Simplest of Transfer Switching Solution Equal Withstand, Interrupting and Closing Ratings Open Transition Safe Manual Transfer Under Load Integral Overcurrent Protection Available Breaker-Based
Integrated Service Entrance Solution (100 1000 A)
Most Simple Operation Most Compact Offering Open Transition Most Cost-Effective Multi Tap Transformer Voltage Selection Available Contactor-Based Application Flexibility (100 600 A)
Permits Safe and Convenient Non-auto Transfer Under Load 30 Cycle, 85 kA Short-Time Ratings on Power Circuit Breaker Integral Overcurrent Protection Available Drawout Design Available
Permits Safe and Convenient Manual Transfer Under Load Equal Withstand, Interrupting and Closing Ratings Most Cost-Effective Manual Transfer Integral Overcurrent Protection Available
Deadfront Design
Continuity of Power for UPS Applications Required UPS Bypass Signal Prevents Unauthorized Bypass High Interrupting Ratings Reliable Manually Initiated Electrical Operation
Identify Your Application Define Your Needs Determine Your Right Solution Select Eaton
Make the right decision
KEY FEATURES AGRICULTURECUSTOMER BENEFITS
PREMIUMSOLUTION
Continuity of PowerDuring Retransfer
Critical Load TransferApplications
Maximum Control andUltimate Flexibility
Maximum Investment
ENHANCEDSOLUTION
Momentary Loss of Power AcceptableDuring Retransfer
Optimal Control andImproved Flexibility
Moderate Investment
BASIC SOLUTION
Momentary Loss of Power AcceptableDuring Retransfer
Least Critical LoadTransfer Applications
Basic Controland Flexibility
Minimum Investment
SPECIAL SOLUTION
ATS SOLUTION GUIDE: Highlighting Contactor-Based Designs
4
Soft Load Soft Load Soft Load Soft Load Soft LoadMagnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based(600 5000 A) (600 5000 A) (600 5000 A) (600 5000 A) (600 5000 A)
Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed TransitionBypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass IsolationMagnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based(200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A)
Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed TransitionBypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass IsolationContactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based(100 1200 A) (100 1200 A) (100 1200 A) (100 1200 A) (100 1200 A) (100 1200 A) (100 1200 A)
Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed TransitionMagnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based(200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A)
Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed TransitionContactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based(40 1200 A) (40 1200 A) (40 1200 A) (40 1200 A) (40 1200 A) (40 1200 A) (40 1200 A)
Delayed Transition Delayed Transition Delayed Transition Delayed Transition Delayed Transition Breaker-Based Breaker-Based Breaker-Based Breaker-Based Breaker-Based(30 5000 A) (30 5000 A) (30 5000 A) (30 5000 A) (30 5000 A)
Delayed Transition Delayed Transition Delayed Transition Delayed Transition Delayed Transition Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based(40 1200 A) (40 1200 A) (40 1200 A) (40 1200 A) (40 1200 A)
Open Transition Open Transition Open Transition Open Transition Open Transition Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based(200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A)
Open Transition Open Transition Open Transition Open Transition Open Transition Breaker-Based Breaker-Based Breaker-Based Breaker-Based Breaker-Based(30 1000 A) (30 1000 A) (30 1000 A) (30 1000 A) (30 1000 A)
Open Transition Open Transition Open Transition Open Transition Open Transition Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based(40 1200 A) (40 1200 A) (40 1200 A) (40 1200 A) (40 1200 A)
Non-Auto Non-Auto Magnum-Based Magnum-Based(200 5000 A) (200 5000 A)
Manual or Non-Auto Manual or Non-Auto Breaker-Based Breaker-Based(30 1000 A) (30 1000 A)
Maintenance Bypass Maintenance Bypass Maintenance Bypass Maintenance Bypass Maintenance Bypass Maintenance Bypass Maintenance BypassBreaker-Based Breaker-Based Breaker-Based Breaker-Based Breaker-Based Breaker-Based Breaker-Based(100 1000 A) (100 1000 A) (100 1000 A) (100 1000 A) (100 1000 A) (100 1000 A) (100 1000 A)
COMMERCIAL INDUSTRIAL UTILITIES INSTITUTIONS GOVERNMENT COMMUNICATIONS DATA CENTRE
5
Product Description
Eatons Cutler-Hammer Automatic Transfer Switch is designed to provide unmatched performance, reliability and versatility forcritical standby power applications. The switches can beequipped with the ATC-300 or ATC-800 controllers to match yourapplication needs. All the controllers offer rock-solid monitoring,status reporting and transfer control operation. Superior designand robust construction make Eatons Cutler-Hammer transferswitch the industry benchmark for critical and distributedpower systems.
Electrical Ratings
Ratings 40, 100, 150, 200, 225, 260, 400, 600, 800,1000 and 1200 amperes
2, 3 or 4-poles Up to 600 Vac, 50/60 Hz. NEMA 1, 3R, Open UL 1008 listed CSA C22.2 No. 178 certified
Industrial Design Highlights
Double-throw, mechanically interlocked transfer mechanism,preventing connection of both sources
Field-selectable multi-tap transformer panel permits operationon a wide range of system voltages
High withstand and closing ratings Compact design
1200 Ampere ATS with ATC-300 Controller
Contactor-basedTransfer Switches
Switch Type - Open TransitionDelayed TransitionClosed Transition
Standard Features (ATC-300)
Switch position contacts: Source 1 Position 1NO and 1NC Source 2 Position 1NO and 1NC
Source 1 and Source 2 sensing: Undervoltage/underfrequency Overvoltage/overfrequency 3-phase rotation protection 3-phase voltage unbalance/loss
Pre-transfer signal contacts 1NO/1NC Go to Emergency (Source 2) Seven field-programmable time delays LCD-based display for programming, system diagnostics
and Help message display Mimic diagram with source available and connected
LED indication Time-stamped history log System test pushbutton Programmable plant exerciser OFF, daily, 7, 14, 28-day
interval selectable run time 0 600 minutes no load/load with fail-safe
Optional Features
Available surge suppression device for power/controller,engine start circuit, phone and cable connections
Space heater with thermostat Ammeter load side Power quality metering 2 and 4 position switch Stainless steel cover for controller Open in-phase transition or time delay neutral transition
Optional Features (ATC 800 only)
Closed transition Remote communications Load shed from emergency Selected automatic or non-automatic operation
6
Type
AT = AutomaticCT = Closed
Transition
Orientation
C = Contactor
Mechanism
C2 = 2-PositionC3 = 3-Position
Logic
3 = ATC-3008 = ATC-800
Mounting
X = Fix Mount
AT C 3 C2 X 3 0400 X S C
Certification
U = UL ListedC = CSA certified
Number of poles
2 = 2-Pole3 = 3-Pole4 = 4-Pole
Enclosure
K = OpenS = NEMA 1J = NEMA 12R = NEMA 3R
Amperes
0040 = 40 A0080 = 80 A0100 = 100 A0150 = 150 A0200 = 200 A0225 = 225 A0260 = 260 A0400 = 400 A0600 = 600 A0800 = 800 A1000 = 1000 A1200 = 1200 A
Voltage
A = 120 V, 60 HzB = 208 V, 60 HzE = 600 V, 60 HzG = 220 V, 50 HzH = 380 V, 50 HzK = 600 V, 50 HzM = 230 V, 50 HzN = 401 V, 50 HzO = 415 V, 50 HzW = 240 V, 60 HzX = 480 V, 60 HzZ = 365 V, 50 Hz
100 Ampere ATS with ATC-300 Controller
Contactor-based Automatic Transfer Switch Catalogue Numbering System
Automatic, Non-Automatic up to 400 Amps Wall Mount. Automatic, Non-Automatic600 to 1200 Amps Floor Standing (Height "A" Includes Bottom Bracket).
CONTACTOR-BASED TRANSFER SWITCH 40 1200 AMPERES - DIMENSIONS IN INCHES (MM) AND APPROXIMATE SHIPPING IN LBS. (KG)
Enclosure Bolt Pattern Standard Terminals
A (Height) B (Width) C (Depth) G (Horizontal) H (Vertical) Load Side, Normal Neutral WeightAmperes and Standby Source Connection Lbs. (kg)
40 100 @ 480 V 38.68 (982.5) 18.31 (465.1) 13.34 (338.8) 10.25 (260.4) 37.38 (949.5) (1) #14 2/0 (1) #14 1/0 164 (74)
40 100 @ 600 V 38.68 (982.5) 18.31 (465.1) 13.34 (338.8) 10.25 (260.4) 37.38 (949.5) (1) #14 2/0 (1) #14 1/0 164 (74)
150 200 @ 480 V 38.68 (982.5) 18.31 (465.1) 13.34 (338.8) 10.25 (260.4) 37.38 (949.5) (1) #6 300 kcmil (3) 1/0 250 kcmil 164 (74)
150 200 @ 600 V 48.74 (1238.0) 18.31 (465.1) 13.84 (351.5) 13.00 (330.2) 47.84 (1215.1) (1) #6 300 kcmil (3) 1/0 250 kcmil 260 (118)
225 400 @ 480 V 48.74 (1238.0) 18.31 (465.1) 13.84 (351.5) 13.00 (330.2) 47.84 (1215.1) (2) #3 /0 250 kcmil (6) 250 500 kcmil 260 (118)
225 1200 @ 600 V 79.41 (2017.0) 29.19 (741.4) 22.46 (570.5) N/A N/A (4) 1/0 750 kcmil (12) 1/0 750 kcmil 600 (272) 3-Pole 650 (295) 4-Pole
600 1200 @ 480 V 79.41 (2017.0) 25.25 (641.4) 3-Pole 22.46 (570.5) N/A N/A (4) 1/0 750 kcmil (12) 1/0 750 kcmil 600 (272)29.19 (741.4) 4-Pole
Wall Mount Floor Standing Height Dimension Includes the Bottom Bracket
WITHSTAND AND CLOSE-ON RATINGS (KA)
Ampere Rating 480 Volts 600 Volts
Any Specific Any SpecificBreaker Breaker Breaker Breaker
100, 200 10,000 30,000 10,000 22,000
260, 320, 400 35,000 50,000 35,000 42,000
600, 800, 1000,1200 50,000 65,000 50,000 65,000
1
1
1
1
1
1
2
2
2
7
Product Description
Eatons Cutler-Hammer Automatic Transfer Switch is designed to provide unmatched performance,reliability and versatility forcritical standby power applications. The switches can beequipped with the ATC-300 or ATC-800 controllers to match yourapplication needs. A Bypass Isolation Transfer Switch may beused to provide emergency power to life safety and other criticalloads where maintenance of the main transfer switch, withoutinterruption of power to the load, is either desirable or required.
Electrical Ratings
Ratings 100, 150, 225, 260, 400, 600, 800, 1000 and 1200 amperes
2, 3 or 4-poles Up to 600 Vac, 50/60 Hz. NEMA 1, 3R UL 1008 listed CSA C22.2 No. 178 certified
Industrial Design Highlights
Front access is a standard feature on all ratings Entry:
Top, bottom or both Isolated compartments
Improved safety: Isolated compartments with barriers Single motion rack-out with doors closed Ability to test powerswitching elements during
draw-out process Dual ATS capability Bypass contactor can be controlled
by the ATS controller in the bypass mode of operation Installation flexibility:
Field Entry/Exit locations can be modified in the field Interchangeable drawout contactors
Field-selectable multi-tap transformer panel permits operation on a wide range of system voltages
Contactor-basedTransfer Switches
Switch Type - Bypass Isolation
Standard Features
Draw-out cassette design on both ATS and Bypass No service interruption in Bypass to the same source Switch position contacts:
Source-1 Position 1-N.O. and 1-N.C. Source-2 Position 1-N.O. and 1-N.C.
Source-1 and Source-2 sensing: Undervoltage/underfrequency Overvoltage/overfrequency 3-phase rotation protection* 3-phase voltage unbalance/loss* Pre-transfer signal contacts1-N.O. and 1-N.C. Go to Source-2 (EMERGENCY)
Field-programmable time delays: Time Delay Engine Start: 0 1200 seconds Time Delay Normal to Emergency: 0 1800 seconds Time Delay Emergency to Normal: 0 1800 seconds Time Delay Engine Cooldown: 0 1800 seconds Time Delay Emergency Failure: 0 6 seconds LCD-based display for programming, system diagnostics
and Help Menu display Mimic diagram with Source Available and Connected
LED indication Time-stamped history log System TEST pushbutton Programmable plant exerciser OFF, daily, 7, 14*, 28-day*
interval selectable run time 0 600 minutes no load/loadwith failsafe
*Note: ATC-300 only.
Optional Features
Available Surge Protection Device (SPD) for power/controller,engine start circuit, phone and cable connections
Automatic transfer operation with selectable (via programming)non-automatic or automatic retransfer with failsafe
Space heater with thermostat Digital multi-function power quality metering Stainless steel cover for controller Load sequencing contacts
1200 Amp 3-Pole Bypass Isolation Switch
8
Front Access
Front access is a standardfeature. Source-1 (NORMAL)Source and Load connectionsare set up as standard topentry and Source-2(EMERGENCY) Source connections as bottom entry.These connections are locatedin their own separate compartments. These connections can be relocatedin the field if necessary.
Multi-Tap Transformer
The industry-exclusiveMulti-Tap system voltageselector allows the transferswitch to be applied on mostsystem voltages by properinsertion of the selector plug.
Draw-out Contactors
The ATS and the Bypassdraw-out cassette powercontactor designs are identicaland interchangeable. Thisstandard feature allows theuser the ability to withdraw,maintain or swap contactorassemblies, providingredundancy of ATS and Bypassfunctions from one contactorassembly to the other.
Improved Safety
The unique Eaton designincludes separation betweencontrol and power components. The ATS andBypass isolation contactors aremounted in separatecompartments with protectivebarriers between them. Thisdesign prevents the possibilityof contact with the rear-mounted power connections to the contactors.In addition, the top and bottomentry have separate compartment doors.
Ease of Maintenance
Transfer to the Bypass powercontactor is easily initiated andcontrolled via door-mountedcontrols. Once the transfer tothe Bypass contactor iscomplete, the ATS contactor is easily racked out with thecompartment door closed. The ATS contactor may thenbe tested in the racked outposition.
Ease of Transfer
The Eaton design allows theoperator to make a quick andsimple transfer from the ATSpower contactor to the Bypasscontactor by initiating theelectrically operated transfervia a 2-position switch. Doormounted indicating lightsconfirm that a successfultransfer has taken place.
Dual ATS Capability
The controller on conventionalBypass Isolation Switches onlycontrols the ATS contactor.The Eaton design allows theswitch controller to remainactive in both the ATS andBypass modes, thus providingcontrol to either contactor.This ability of the controller toremain active and control theBypass isolation contactorprovides "N+1" redundancyof a second fully functioningATS, a feature unique to Eaton.
Bypass Isolation Switch Components
9
Bypass Isolation Contactor-Based Design NEMA 1
CONTACTOR-BASED TRANSFER SWITCH 100 1200 AMPERES DIMENSIONS IN INCHES (MM) AND APPROXIMATE SHIPPING IN LBS. (KG)
SwitchRating Enclosure Standard Terminals WeightAmperes Height Width Depth Line Side (Normal Load Neutral Lbs. (kg)
and Standby Source) Connection Connection
100 200 90.00 (2286.0) 40.00 (1016.0) 28.97 (735.8) (1) #6 300 Cu/Al (1) #6 300 Cu/Al (3) #6 300 Cu/Al 1800 (817) NEMA 1
100 200 90.00 (2286.0) 40.00 (1016.0) 44.47 (1129.5) (1) #6 300 Cu/Al (1) #6 300 Cu/Al (3) #6 300 Cu/Al 1850 (840) NEMA 3R
400 1200 90.00 (2286.0) 40.00 (1016.0) 28.97 (735.8) (4) 3/0 750 Cu/Al (4) 3/0 750 Cu/Al (12) 3/0 750 Cu/Al 1800 (817) NEMA 1
400 1200 90.00 (2286.0) 40.00 (1016.0) 44.47 (1129.5) (4) 3/0 750 Cu/Al (4) 3/0 750 Cu/Al (12) 3/0 750 Cu/Al 1850 (840) NEMA 3R
NEMA 3R dimensions If seismic mounting brackets are required, then the width will be 46.00 (1168.4)1
1
1
2
10
WITHSTAND AND CLOSE-ON RATINGS (KA)
Ampere Rating 480 Volts 600 Volts
Any Specific Any SpecificBreaker Breaker Breaker Breaker
100 10,000 30,000 10,000 22,000
200 10,000 30,000 10,000 22,000
260 35,000 50,000 35,000 42,000
320 35,000 50,000 35,000 42,000
400 35,000 50,000 35,000 42,000
600 50,000 65,000 42,000 65,000
800 50,000 65,000 42,000 65,000
1000 50,000 65,000 42,000 65,000
1200 50,000 65,000 42,000 65,000
Type
BI = BypassIsolationOpen Transition
CB = BypassIsolationClosed Transition
Orientation
C = Contactor
Mechanism
C3 = 3-Position
Logic
3 = ATC-3008 = ATC-800
Mounting
E = Draw-outX = Fixed Mount
BI C 3 C3 E 3 1200 W S C
Certification
U = UL ListedC = CSA certified
Number of poles
2 = 2-Pole3 = 3-Pole4 = 4-Pole
Enclosure
S = NEMA 1R = NEMA 3R
Amperes
0100 = 100 A0150 = 150 A0225 = 225 A0260 = 260 A0400 = 400 A0600 = 600 A0800 = 800 A1000 = 1000 A1200 = 1200 A
Voltage
B = 208 V, 60 HzE = 600 V, 60 HzG = 220 V, 50 HzH = 380 V, 50 HzK = 600 V, 50 HzM = 230 V, 50 HzN = 401 V, 50 HzO = 415 V, 50 HzW = 240 V, 60 HzX = 480 V, 60 HzZ = 365 V, 50 Hz
Automatic Bypass Isolation Contactor-based Transfer Switch Catalogue Numbering System
11
Standard Features (ATC300)
Switch position contacts: Source 1 Position 1NO and 1NC Source 2 Position 1NO and 1NC
Programmable Micro-processor based control Normal/Standby source monitoring Plant Exerciser with Failsafe (programmable) High Withstand, Closing and Interrupting Ratings Manual Transfer Under Load Engine Start Contacts Time Delay Normal to Emergency Time Delay Engine Start Time Delay Emergency to Normal Time Delay Engine Cooldown LED indicators switch position LED indicators source available Emergency source undervoltage/underfrequency sensing Normal source undervoltage sensing
Time Delay Neutral Go to Emergency Contact (Area Protection) Pre-Transfer Signal Contacts Pushbutton Bypass Time Delays
Optional Features
Available surge suppression device for power/controller, engine start circuit, phone and cable connections
Space heater with thermostat Ammeter load side Power quality metering Stainless steel cover for controller
Optional Features (ATC 600)
Remote communications Load shed from emergency Selected automatic or non-automatic operation
Product Description
An economical line of transfer switches with micro-processorbased logic, offering a standard feature package, for basicpower applications on 30-1000 ampere systems up to 600volts, 2, 3 or 4 pole.
Electrical Ratings
Ratings 40, 100, 150, 200, 225, 260, 400, 600, 800 and 1000 amperes
2, 3 or 4-poles Up to 600 Vac, 50/60 Hz. NEMA 1, 3R, Open, 12, 4, 4x UL 1008 listed CSA C22.2 No. 178 certified
Breaker-basedTransfer Switches
Switch Type - Automatic, Manual and Electrically Operated 30A-1000A
ATHM Automatic Transfer Switch
12
TRANSFER SWITCH ENCLOSURE DIMENSIONS
Frame size Rating Figure Height Width Depth
30A - 150A, 600VF 30A - 200A, 240V A 32.63 (829) 24 (610) 9 (229)
K, L, M 225A - 600A B 55 (1397) 32 (813) 15 (381)
N 800A - 1200A B 65 (1651) 38 (965) 16 (406)
Type
AT = AutomaticMT = Non-Auto
ManualNT = Non-Auto
Electric
Orientation
H = Horizontal
Switch Frame
Type 240Vac 480Vac 600Vac
FD = F Frame 30-225A* 30-150A 30-150AKD = K Frame 400A 200-300A 200-300ALD = L Frame 600A 400A 400AMD = M Frame 800A 600A** 600A**NB = N Frame 800-1000A 800-1000A 800-1000A
Logic
3 = ATC-300I = ATC-600X = No logic
Mounting
A = Source1 (MCS), Source 2 (MCS)B = Source1 (MCCB), Source 2 (MCCB)C = Source1 (MCCB), Source 2 (MCS)D = Source1 (MCS), Source 2 (MCCB)
AT H 3 FD A 3 0100 E S C
Certification
U = UL ListedC = CSA certified
Number of poles
2 = 2-Pole3 = 3-Pole4 = 4-Pole
Enclosure
S = NEMA 1R = NEMA 3RJ = NEMA 12L = NEMA 4D = NEMA 4XK = OpenP = Sprinklerproof
Amperes
0030 = 30 A0070 = 70 A0100 = 100 A0150 = 150 A0200 = 200 A0300 = 300 A0400 = 400 A0600 = 600 A0800 = 800 A1000 = 1000 A
Voltage
A = 120 V, 60 HzB = 208 V, 60 HzE = 600 V, 60 HzG = 220 V, 50 HzH = 380 V, 50 HzK = 600 V, 50 HzM = 230 V, 50 HzN = 401 V, 50 HzO = 415 V, 50 HzW = 240 V, 60 HzX = 480 V, 60 HzZ = 365 V, 50 Hz
Automatic Breaker-based Transfer Switch Catalogue Numbering System
Notes: *225A single phase applications only**4 pole 600Vac 600A Use N Frame
13
Product Description
The Cutler-Hammer Bypass/Isolation Transfer Switch is designedfor applications where preventative maintenance, inspection andtesting must be accomplished while maintaining continuityof power to the load. Proven Cutler-Hammer switch designsensure reliable transfer from normal to auxiliary power sources for rapid restoration of essential power in critical applications.Now available in a compact 100 - 600A fully bussed design forboth Single and Double Sided Applications. (800A to 4000A alsoavailable. Contact your local Cutler-Hammer sales representativefor information).
Electrical Ratings
Ratings 40, 100, 150, 200, 225, 260, 400, 600, 800 and 1000 amperes
2, 3 or 4-poles Up to 600 Vac, 50/60 Hz. NEMA 1, 3R UL 1008 listed CSA C22.2 No. 178 certified
Superior Main Contact Structure
The Cutler-Hammer Combination Bypass and AutomaticTransfer Switch is listed to CSA specifications C22.2 No. 178 and C22.2 No. 31.
As an added plus the switching devices are listed under CSAC22.2 No. 5. Completely enclosed contacts provide both safetyand reliability. They also ensure the integrity of the contactassemblies and minimize the need for periodic maintenance ofthe contacts, reducing the need for downtime and maintenance time.
Breaker-basedTransfer Switches
Switch Type - Bypass Isolation
Transfer Switch Is Easy To Maintain And Test
The Cutler-Hammer Bypass/Isolation Switch is designed torequire minimum maintenance even under the most strenuousof operating conditions. Due to the use of moulded caseswitches and their inherent self-protection capability, the contactstructure and mechanism is extremely long lived.
Our experience has shown that through normal operating conditions, the moving and stationary contacts will maintaintheir integrity for the full expected life of the transfer switch.
When isolating and bypassing the transfer switch, a short term(less than 3 second) power interruption results. However, thisis less than when transferring power after a power outageusing a standard transfer switch. Also, with a double-sidedbypass the transfer switch can be bypassed to either sourcequickly and easily regardless of the position or condition of the transfer switch.
Safety To Maintenance Personnel
In most instances, the Bypass/Isolation Switch will be in theBypass Mode only during a maintenance or testing period.During this time, there could be operating personnel close tothe equipment. The self protection capability of theCutler-Hammer switch would give these operators an extrameasure of safety during a rare coincidental fault condition.
Features
The Cutler-Hammer Bypass Isolation Switch is available with all the options and features of our standard Transfer Switch product line. Proven, microprocessor based programmablecontrollers are supplied as standard on all Bypass TransferSwitches.
Double Sided Bypass Isolation Switch
14
Type
4BI = SingleSidedBypass
5BI = DoubleSidedBypass
Orientation
H = Horizontal
Switch Frame
Type 240Vac 480Vac 600Vac
FD = F Frame 30-225A* 30-150A 30-150AKD = K Frame 400A 200-300A 200-300ALD = L Frame 600A 400A 400AMD = M Frame 800A 600A** 600A**NB = N Frame 800-1000A 800-1000A 800-1000A
Logic
3 = ATC-300I = ATC-600X = No logic
Mounting
A = Source1 (MCS), Source 2 (MCS)B = Source1 (MCCB), Source 2 (MCCB)C = Source1 (MCCB), Source 2 (MCS)D = Source1 (MCS), Source 2 (MCCB)
4BI H 3 FD A 3 0100 E S C
Certification
U = UL ListedC = CSA certified
Number of poles
2 = 2-Pole3 = 3-Pole4 = 4-Pole
Enclosure
S = NEMA 1R = NEMA 3RJ = NEMA 12L = NEMA 4D = NEMA 4XK = OpenP = Sprinklerproof
Amperes
0030 = 30 A0070 = 70 A0100 = 100 A0150 = 150 A0200 = 200 A0300 = 300 A0400 = 400 A0600 = 600 A0800 = 800 A1000 = 1000 A
Voltage
A = 120 V, 60 HzB = 208 V, 60 HzE = 600 V, 60 HzG = 220 V, 50 HzH = 380 V, 50 HzK = 600 V, 50 HzM = 230 V, 50 HzN = 401 V, 50 HzO = 415 V, 50 HzW = 240 V, 60 HzX = 480 V, 60 HzZ = 365 V, 50 Hz
Automatic Bypass Isolation Breaker-based Transfer Switch Catalogue Numbering System
Notes: *225A single phase applications only**4 pole 600Vac 600A Use N Frame
Typical Double Sided Bypass Transfer Switch
BYPASS ISOLATION ATS (2 & 3 POLE) ENCLOSURE DIMENSIONS
Max Max Switch CSA Dimensions (inches/mm)Amps Volts Frame Bypass Frame A H I J
150 480 F F 21/533 30/965 79.5/2019 18/457150 600 F F 21/533 30/965 79.5/2019 18/457
200 240 F F 21/533 30/965 79.5/2019 18/457
225* 240 F F 21/533 30/965 79.5/2019 18/457
300 480 K K 21/533 38/965 79.5/2019 18/457300 600 K K 21/533 38/965 79.5/2019 18/457
400 240 K K 21/533 38/965 79.5/2019 18/457400 480 L K 21/533 38/965 79.5/2019 18/457400 600 L K 21/533 38/965 79.5/2019 18/457
600 240 L L 21/533 38/965 79.5/2019 18/457600 480 M L 21/533 38/965 79.5/2019 18/457600 600 M L 21/533 38/965 79.5/2019 18/457
800 240 NB MD 27.12/689 38/965 91.5/2324 24/610800 480 NB MD 27.12/689 38/965 91.5/2324 24/610800 600 NB MD 27.12/689 38/965 91.5/2324 24/610
1000 240 NB ND 27.12/689 38/965 91.5/2324 24/6101000 480 NB ND 27.12/689 38/965 91.5/2324 24/6101000 600 NB ND 27.12/689 38/965 91.5/2324 24/610
BYPASS ISOLATION ATS (4 POLE) ENCLOSURE DIMENSIONS
Max Max Switch CSA Dimensions (inches/mm)Amps Volts Frame Bypass Frame A H I J
150 480 F F 21/533 30/965 79.5/2019 18/457150 600 F F 21/533 30/965 79.5/2019 18/457
200 240 F F 21/533 30/965 79.5/2019 18/457
300 480 K K 21/533 38/965 79.5/2019 18/457300 600 K K 21/533 38/965 79.5/2019 18/457
400 240 K K 21/533 38/965 79.5/2019 18/457400 480 L K 21/533 38/965 79.5/2019 18/457400 600 L K 21/533 38/965 79.5/2019 18/457
600 240 L L 21/533 48/1219 79.5/2019 18/457600 480 NB ND 21/533 48/1219 91.5/2324 24/610600 600 NB ND 21/533 48/1219 91.5/2324 24/610
800 240 NB ND 27.12/689 48/1219 91.5/2324 24/610800 480 NB ND 27.12/689 48/1219 91.5/2324 24/610800 600 NB ND 27.12/689 48/1219 91.5/2324 24/610
1000 240 NB ND 27.12/689 48/1219 91.5/2324 24/6101000 480 NB ND 27.12/689 48/1219 91.5/2324 24/6101000 600 NB ND 27.12/689 48/1219 91.5/2324 24/610
* Single Phase Only
15
16
BREAKER-BASED TRANSFER SWITCH WITHSTAND/CLOSING RATINGS
When protected by any manufacturers' breaker or Cutler-Hammer circuit breaker upstream as shown, the transfer switch is rated for use on a circuit capable ofdelivering not more than the RMS Symmetrical amps at the voltage shown below.
25kA 35kA 42kA 50kA 65kA 100kA 200kA
30 - 200 2,3,4 Any* Any* Any* Any* Any* Any* FDC,JDC,KDC
225 2 Any* Any* Any* Any* Any* Any* FDC,JDC,KDC
300 2,3,4 Any* Any* Any* Any* Any* Any* KDC
400 2,3,4 Any* Any* Any* Any* Any* Any* KDC
600 2,3,4 Any* Any* Any* Any* Any* Any* LDC
800 - 1000 2,3,4 Any* Any* Any* Any* Any* Any* ---
30 - 150 2,3,4 Any* Any* Any* Any* Any* (FDB/FD)+LFD 150kAFDC,JDC,KDC FCL***,LCL***
200 - 300 2,3,4 Any* Any* Any* Any* Any* KDC,NB-TP** LCL***
400 2,3,4 Any* Any* Any* Any* Any* --- ---
600 2,3 Any* Any* Any* Any* Any* NB-TP ---
800 2,3 Any* Any* Any* Any* --- NB-TP ---
600 - 1000 4 Any* Any* Any* Any* --- --- ---
1000 2,3 Any* Any* Any* Any* --- --- ---
30 - 150 2,3,4 Any* Any* (FD/FDB)+LFD (FD/FDB)+LFD (FD/FDB)+LFD (FD/FDB)+LFD ---KDC KDC KDC LCL
200 - 300 2,3,4 Any* Any* Any* KDC KDC LCL ---
400 2,3,4 Any* Any* Any* KDC KDC --- ---
600 2,3 Any* Any* Any* LDC --- --- ---
600 4 Any* --- --- --- --- --- ---
800 - 1000 2,3,4 Any* --- --- --- --- --- ---
*Any manufacturers breaker **with P12 limiter *** 150kA maximum
Transfer SwitchAmpere Rating
Voltage
120/240 and 240, 208Y/120
480Y/277 and 480
600Y/347 and 600
Number of PolesSwitched
Maximum fault level available at upstream device (kA symmetrical)Upstream any manufacturers' breaker or Cutler-Hammer circuit breaker type
BREAKER-BASED TRANSFER SWITCH WITHSTAND/CLOSING RATINGS
When protected by an upstream fuse type shown, the transfer switch is rated for use on a circuit capable of delivering notmore than the RMS Symmetrical amps at the voltage shown below.
30 - 225 2,3,4
300 2,3,4
400 2,3,4
600 2,3,4
800 - 1000 2,3,4
30 - 150 2,3,4
200 - 300 2,3,4
400 2,3,4
600 2,3
600 4
800 - 1000 2,3,4
Transfer SwitchAmpere Rating
Voltage
120/240 and 240, 208Y/120
480Y/277,480,
600Y/347 and 600
Number of PolesSwitched Max. Fuse Amperes
Maximum fault level available at upstream device (kA symmetrical)
Upstream Fuse Type
100kA 200kA--- J, T 200AJ,T --- 400AR J,T 400A
J,T --- 600AJ,T R 600AL --- 1200AL --- 800A
--- L 1600A
--- L 1600A
--- J,T 200AJ,T --- 400A
R J,T 400AJ,T --- 600AJ,T R 600AL --- 1200AL --- 800A
--- L 1600A
--- L 1600A
--- L 1600A
Product Description
The automatic transfer switch controller is a key componentwithin the automatic transfer switch. It provides the intelligenceto sense the proper conditions to initiate a transfer and aretransfer of the contactor. Eatons Cutler-Hammer automatictransfer switches come with the design flexibility of beingapplied with one of three controllers. All three controllers providethe basic functions needed to perform an automatic transfer.
Design Highlights Mimic diagram with source available and connected LED
indications Field selectable fixed time delays Permits system testing via a front screen test pushbutton Complies with UL 1008/CSA 22.2 No. 178 Generator Test Selectable OFF, 7, 14, 28-day interval
General Description (ATC-300 Controller)
From installation to programming to usage, the ATC-300 opentransition controller was designed with operational simplicity inmind. The user friendly front panel interface simplifies routineoperation, programming, data presentation and settingadjustments. An LCD-based display provides the flexibility of a back-lit display for enhanced visibility.
Design Highlights LCD-based display for programming, system diagnostic and
Help Message display Mimic diagram with source available and connected
LED indications Stores customer/factory established parameters in
nonvolatile memory Field programmable time delays Displays real time and historical information with a
time-stamped history log Permits system testing via a front screen test pushbutton Programmable plant exerciser OFF, daily, 7, 14, 28-day
interval programmable run times Complies with UL 1008/CSA 22.2 No. 178
General Description (ATC-600 and ATC-800 Controllers)
The ATC-600 and ATC-800 controllers were designed with operational simplicity in mind. The user-friendly front panel interface simplifies routine operation, programming, data presentation and setting adjustments. An LCD-based display provides the flexibility of a back-lit display for enhanced visibility.
Design Highlights LCD-based display for programming, system diagnostic
and Help Message display Mimic diagram with source available and connected
LED indications Stores customer/factory established parameters in
nonvolatile memory Field programmable time delays Displays real time and historical information with a
time-stamped history log Permits system testing via a front screen test pushbutton Programmable plant exerciser OFF, daily, 7, 14, 28-day
interval selectable run times Communicate via Modbus communication protocol Complies with UL 1008/CSA 22.2 No. 178 Load monitoring, delayed, in-phase and closed transition
Automatic TransferSwitch Controllers
Controller Features
Contactor-Based Design ATS Showing Optional Controllers Available
17
18
AUTOMATIC TRANSFER SWITCH CONTROLLERS
Description ATC-300 ATC-600 / ATC-800
System Application Voltage Up to 600 Vac Up to 600 Vac
Voltage SpecificationsVoltage Measurements of: Source 1 and 2 VAB, VBC and VCA Source 1, 2 and Load VAB, VBC and VCAVoltage Measurement Range 0 790 Vac rms 0 700 Vac rms
Operating Power 65 Vac 145 Vac 65 Vac 145 Vac
Frequency SpecificationsFrequency Measurements of: Source 1 and 2 Source 1 and 2Frequency Measurement Range 40 70 Hz 40 80 Hz
Environmental SpecificationsOperating Temperature Range -20 to +70C -20 to +70CStorage Temperature Range -30 to +85C -30 to +85C
Operating Humidity 0 to 95% Relative Humidity (Non-condensing) 0 to 90% Relative Humidity (Non-condensing)
Operating Environment Resistant to Ammonia, Methane, Nitrogen, Resistant to Ammonia, Methane, Nitrogen, HydrogenHydrogen and Hydrocarbons and Hydrocarbons
Front Panel IndicationMimic Diagram with LED Indication Unit Status. Source 1 and 2 Available and Automatic, Test and Program Mode.
Connected (5 Total) Source 1 and 2 Available, Connected and Preferred. Load Energized (10 Total) Preferred. Load Energized (10 Total)
Main Display LCD-Based Display LED DisplayDisplay Language English, French English
Communications Capable N/A PONI/INCOM
Enclosure Compatibility NEMA 1, 12 and 3R, NEMA 1, 12, 3R and 4X UVUV Resistant Faceplate Resistant Faceplate
Programming SelectionsTime Delay Normal to Emergency 0 1800 Seconds 0 1800 SecondsTime Delay Emergency to Normal 0 1800 Seconds 0 1800 SecondsTime Delay Engine Cooldown 0 1800 Seconds 0 1800 SecondsTime Delay Engine Start 0 120 Seconds 0 120 SecondsTime Delay Neutral 0 120 Seconds 0 120 Seconds or Based on
Load Voltage Decay of 2% 30% of NominalTime Delay Source 2 Fail 0 6 Seconds 0 6 SecondsTime Delay Voltage Unbalance 10 30 Seconds N/AVoltage Unbalance 3-Phase 0 or 1 (1 = Enabled) % of Unbalanced Voltage Dropout 5% 20% (DO) Dropout -2% 3% (PU) N/APhase Reversal 3-Phase OFF, ABC, CBA N/AIn-Phase 0 or 1 (1 = Enabled) N/ALoad Sequencing N/A Up to 10 Devices (via Sub-network)Pre-Transfer Signal 1 120 Seconds (Form C Contact) 0 120 Seconds Up to 10 Devices (via Sub-network)Plant Exerciser Selectable Off, Daily or 7, 14, 28 Selectable Disabled or 7
Day Intervals, 0 600 Minutes, Load or No Load Day Interval, 0 600 Minutes, Load or No LoadPreferred Source Selection N/A Source 1 or 2 or NoneCommitment to Transfer in TDNE N/A Enabled or DisabledRe-transfer Mode N/A Automatic or ManualAuto Daylight Savings Time Adjustment 0 or 1 (1 = Enabled) System Selection Utility/Generator or Dual Utility Utility/Generator or Dual Utility or Dual GeneratorClosed Transition Frequency Difference N/A 0.0 3.0 HzClosed Transition Voltage Difference N/A 1 5%
Note: Features are order specific. Not all features are supplied as standard.
Integrated Solutions
Minimize initial equipment costs, reduce installation time, andincrease system reliability. These are goals of all involved inplacing electrical distribution equipment in service from thedesign engineer, to the electrical contractor, and especially withthe end user of the equipment.
Eaton believes the transfer switch equipment is an integral partof the distribution equipment. This fundamental belief is whyEaton offers various types of transfer switches for the designengineer, electrical contractor and the user to choose from.Eaton offers Contactor-Based, Moulded Case and Circuit Breakerstyle switches.
All Eaton transfer switches are designed to meet the requirementsset forth by CSA C22.2 No.178, however, all transfer switches arenot created equal. You can be assured of safe and reliable operationfrom all types of transfer switches that Eaton offers.
Integrated Solutions
Automatic Transfer Switch Integrated Into a Switchboard Lineup
19
Eaton Corporation is a diversifiedpower management companyranked among the largestFortune 500 companies. Theelectrical sector is Eatons largestdivision and is a global leaderin electrical control, powerdistribution, power quality,automation, and monitoringproducts and services.Eatons global electrical productlines, including Cutler-Hammer,MGE Office ProtectionSystems, Powerware,Holec, MEM, Santak andMoeller, provide customer-drivenPowerChain Management
solutions to serve the powersystem needs of the industrial,institutional, government,utility, commercial, residential,IT, mission critical and OEMmarkets worldwide.
PowerChain Managementsolutions help enterprisesachieve sustainable andcompetitive advantages throughproactive management of thepower system as a strategic,integrated asset throughoutits life cycle. With Eatonsdistribution, generation andpower quality equipment;full-scale engineering services;and information managementsystems, the power systemis positioned to deliverpowerful results: greaterreliability, operating costefficiencies, effective use ofcapital, enhanced safety, andrisk mitigation.
Eaton5050 MainwayBurlington, OntarioL7L 5Z1www.eatoncanada.ca1-800-268-3578
2009 Eaton CorporationAll Rights ReservedPrinted in CanadaPublication No. BR01602001K
PowerChain Management is a registeredtrademark of Eaton Corporation.
fsc symbol