  • Cutler-HammerTransfer Switches Product Focus

    Delayed TransitionOpen TransitionClosed Transition

    ManualNon-automaticBypass Isolation

    Contactor and Breaker-basedTransfer Switches

  • A History of Experience,Innovation and Reliability

    As a premier industrial manufacturer, Eatons electricalbusiness is one of the worldsleading suppliers of electricalcontrol products and powerdistribution equipment withyearly sales of over $2.5 billion.Eatons electrical productsinclude a complete line of lowand medium voltage assemblies from substations,switchgear and panelboards toloadcentres, transformers andsafety switches. These products are used whereverthere is a demand for electricalpower in residences, high-riseapartment and office buildings,commercial sites, hospitals and factories.

    Built With Experience

    For over a century, Eaton hasfocused on providing qualitypower-centric products andservices. In todays businessenvironment, customers likeyou are driving our transformation from a leadingglobal electrical componentsprovider into a customer-centric solutions partner whounderstands your business.We do this through in-depthcollaboration with customersand subject matter expertsstudying the issues inherent to the electrical power distribution and control systems.

    Eaton is one of the pioneeringelectrical manufacturers andhas been focused on providingreliable backup power systemswith transfer switchequipment for over 75 years.

    Powered With Innovation

    Eaton continues to meetchanging industry needs by providing a broad range of automatic transfer switches.These switches may begrouped into a basic, enhanced or premium set offeatures that will meet yourapplication requirements. Eaton has used industry-leading breaker based designsfor years and now has a line ofcontactor based designs.

    These designs can be matchedto a family of automatic transfer switch controllers thatwill meet your specific needs.Identify your application,define your needs, and selectthe solution from Eaton.

    Delivered With Reliability

    Power outages due to badweather or utility failure havegrown increasingly costly andmore disruptive to businessesand homeowners. A backuppower system will keep yourcomputers, security system,heating or refrigeration system, cash registers, homehealth care equipment, or anysystem that uses electricpower, energized and operational. The demands forreliability have increased.Eaton meets thoseexpectations by the stringentCSA C22.2 No. 178 andUL1008 automatic transferswitches with a world-classproduct delivery system.Eaton will provide the individual transfer switch builtto exacting standards or supply the same transferswitch in an integratedlineup with other Eaton gear.For startup service, applicationsupport, and emergency support, call Eaton ElectricalServices and Systems at 1-800-498-2678.

    Built with years of experiencePowered with innovationDelivered with reliability

    2

  • Eatons Cutler-Hammer

    automatic transfer switchesare designed to provide youwith a full offering of transferswitches to solve your industryand application needs. Eatonoffers the industrys mostcomplete line of contactor-based, breaker-based, and Magnum stored energybased transfer switches. This wide range of selectionsenables you to identify yourapplication needs and thebenefits you expect to realize,and then choose the solutionbest for you. The corner stoneof all of these offerings is theproven design experience and reliability built into all Cutler-Hammer transferswitches.

    Basic Solution

    The Basic Solution offers atransfer switch that meets themost basic and cost-effectiverequirement needs for an automatic, manual or non-automatic transfer switch.This solution set allows youto choose from either acontactor-based or a breaker based design andmatch that power-switchingdevice with our basic transferswitch controller.

    Enhanced Solution

    The Enhanced Solution meetsall of the basic automatictransfer switch needs. In addition to meeting themost basic transfer switchrequirement, the EnhancedSolution allows for optimalcontrol and improved flexibility.This solution set allows you to choose from either a contactor based or breaker-based design.

    Premium Solution

    The Premium Solution isoffered for those applicationsrequiring continuity of powerduring the transfer and routinetest. This solution set offersboth contactor-based andbreaker-based designs withdrawout capability.

    Switch Types Available

    Open Transition Closed Transition Delayed Transition Bypass Isolation Non-Automatic Manual

    TRANSFER SWITCH STANDARDS

    CSA C22.2 No. 178-1978 Canadian Standards Association

    UL 991 UL Standards for Safety Tests for Safety-RelatedControls Employing Solid-State Devices

    UL 1008 UL Standards for Transfer Switches

    NEMA ICS 109.21 Impulse Withstand Test

    IEEE 472 (ANSI C37.90A) Ringing Wave Immunity/Voltage Surge Test

    EN55022 (CISPR11): Conducted and Radiated Emissions

    EN61000-4-2 Class B Level 4 ESD Immunity Test

    EN61000-4-3 (ENV50140) Radiated RF, Electromagnetic FieldImmunity Test

    EN61000-4-4 Electrical Fast Transient/Burst Immunity Test

    EN61000-4-5 IEEE C62.41: Surge Immunity Test

    EN61000-4-6 (ENV50141) Conducted Immunity Test

    EN61000-4-11 Voltage Dips and Interruption Immunity

    FCC Part 15 Conducted/Radiated Emissions (Class A)

    CISPR 11 Conducted/Radiated Emissions (Class A)

    IEC 1000-2 Electrostatic Discharge Test

    IEC 1000-3 Radiated Susceptibility Tests

    IEC 1000-4 Fast Transient Tests

    IEC 1000-5 Surge Withstand Tests

    CSA Conformance C22.2 No. 178-1978 (Reaffirmed 1992)

    UL 869A Reference Std for Service Equipment

    UL 50/508 Enclosures

    NEMA ICS 1 General Standards for Industrial Control Systems

    NEMA ICS 2 Standards for Industrial Control Devices,Controllersand Assemblies

    NEMA ICS 6 Enclosures for Industrial Controls and Systems

    NEMA ICS 10-1993 AC Automatic Transfer Switches

    ANSI C33.76 Enclosures

    NEC 517, 700, 701 and 702 National Electrical Code

    NFPA 70 National Electrical Code

    NFPA 99 Health Care Facilities

    NFPA 101 Life Safety Code

    NFPA 110 Emergency and Standby Power Systems

    EGSA 100S Standard for Transfer Switches

    Solutions Overview

    3

  • Greater Reliability to Avoid Lost Revenue and Production Time Soft Load Ramping Continuity of Power Through Synchronization of Sources 30 Cycle, 85 kA Short-Time Ratings Lower Energy Costs Realized through Managing Demand Charges Integral Overcurrent Protection Available No Power Interruption During Switch Inspection or Testing Drawout Design

    Greater Reliability to Avoid Lost Revenue and Production Time 30 Cycle, 85 kA Short-Time Ratings Safe Preventative Maintenance without Power Interruption Integral Overcurrent Protection Available No Power Interruption During Switch Inspection or Testing Integrated Service Entrance Solution

    Interchangeable Bypass and Switch Devices Drawout Design

    Greater Reliability to Avoid Lost Revenue and Production Time Interchangeable Bypass and Switch Devices Safe Preventative Maintenance without Power Interruption Drawout Design Standard No Power Interruption During Switch Inspection or Testing Front Access Standard

    Dual ATS

    Greater Reliability to Avoid Lost Revenue and Production Time 30 Cycle, 85 kA Short-Time Ratings Lower Energy Costs Realized from Managing Demand Charges Integral Overcurrent Protection Available No Power Interruption During Generator Set Testing Integrated Service Entrance Solution

    Drawout Design Available

    Greater Reliability to Avoid Lost Revenue and Production Time Paralleled in Less than 100 ms Lower Energy Costs Realized from Managing Demand Charges Programmable Field Settings No Power Interruption During Generator Set Testing Communication Capability

    Ability to Transfer Large Motor or Inductive Loads 30 Cycle, 85 kA Short-Time Ratings on Power Circuit Breaker Allows Loads to Re-Energize after Transfer at Normal Inrush Currents Integral Overcurrent Protection Available Avoid Higher Starting Currents which Increase Energy Costs Integrated Service Entrance Solution

    Ability to Transfer Large Motor or Inductive Loads Multi Tap Transformer Voltage Selection Available Allows Loads to Re-Energize after Transfer at Normal Inrush Currents Easily Adjustable Time Delays for the Neutral Position Avoid Higher Starting Currents which Increase Energy Costs

    Ability to Transfer Large Motor or Inductive Loads 30 Cycle, 85 kA Short-Time Ratings on Power Circuit Breaker Allows Loads to Re-Energize after Transfer at Normal Inrush Currents Integral Overcurrent Protection Available Avoid Higher Starting Currents which Increase Energy Costs Integrated Service Entrance Solution

    Drawout Design Available

    Simplest of Transfer Switching Solution Equal Withstand, Interrupting and Closing Ratings Open Transition Safe Manual Transfer Under Load Integral Overcurrent Protection Available Breaker-Based

    Integrated Service Entrance Solution (100 1000 A)

    Most Simple Operation Most Compact Offering Open Transition Most Cost-Effective Multi Tap Transformer Voltage Selection Available Contactor-Based Application Flexibility (100 600 A)

    Permits Safe and Convenient Non-auto Transfer Under Load 30 Cycle, 85 kA Short-Time Ratings on Power Circuit Breaker Integral Overcurrent Protection Available Drawout Design Available

    Permits Safe and Convenient Manual Transfer Under Load Equal Withstand, Interrupting and Closing Ratings Most Cost-Effective Manual Transfer Integral Overcurrent Protection Available

    Deadfront Design

    Continuity of Power for UPS Applications Required UPS Bypass Signal Prevents Unauthorized Bypass High Interrupting Ratings Reliable Manually Initiated Electrical Operation

    Identify Your Application Define Your Needs Determine Your Right Solution Select Eaton

    Make the right decision

    KEY FEATURES AGRICULTURECUSTOMER BENEFITS

    PREMIUMSOLUTION

    Continuity of PowerDuring Retransfer

    Critical Load TransferApplications

    Maximum Control andUltimate Flexibility

    Maximum Investment

    ENHANCEDSOLUTION

    Momentary Loss of Power AcceptableDuring Retransfer

    Optimal Control andImproved Flexibility

    Moderate Investment

    BASIC SOLUTION

    Momentary Loss of Power AcceptableDuring Retransfer

    Least Critical LoadTransfer Applications

    Basic Controland Flexibility

    Minimum Investment

    SPECIAL SOLUTION

    ATS SOLUTION GUIDE: Highlighting Contactor-Based Designs

    4

  • Soft Load Soft Load Soft Load Soft Load Soft LoadMagnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based(600 5000 A) (600 5000 A) (600 5000 A) (600 5000 A) (600 5000 A)

    Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed TransitionBypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass IsolationMagnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based(200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A)

    Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed TransitionBypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass Isolation Bypass IsolationContactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based(100 1200 A) (100 1200 A) (100 1200 A) (100 1200 A) (100 1200 A) (100 1200 A) (100 1200 A)

    Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed TransitionMagnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based(200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A)

    Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed Transition Closed TransitionContactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based(40 1200 A) (40 1200 A) (40 1200 A) (40 1200 A) (40 1200 A) (40 1200 A) (40 1200 A)

    Delayed Transition Delayed Transition Delayed Transition Delayed Transition Delayed Transition Breaker-Based Breaker-Based Breaker-Based Breaker-Based Breaker-Based(30 5000 A) (30 5000 A) (30 5000 A) (30 5000 A) (30 5000 A)

    Delayed Transition Delayed Transition Delayed Transition Delayed Transition Delayed Transition Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based(40 1200 A) (40 1200 A) (40 1200 A) (40 1200 A) (40 1200 A)

    Open Transition Open Transition Open Transition Open Transition Open Transition Magnum-Based Magnum-Based Magnum-Based Magnum-Based Magnum-Based(200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A) (200 5000 A)

    Open Transition Open Transition Open Transition Open Transition Open Transition Breaker-Based Breaker-Based Breaker-Based Breaker-Based Breaker-Based(30 1000 A) (30 1000 A) (30 1000 A) (30 1000 A) (30 1000 A)

    Open Transition Open Transition Open Transition Open Transition Open Transition Contactor-Based Contactor-Based Contactor-Based Contactor-Based Contactor-Based(40 1200 A) (40 1200 A) (40 1200 A) (40 1200 A) (40 1200 A)

    Non-Auto Non-Auto Magnum-Based Magnum-Based(200 5000 A) (200 5000 A)

    Manual or Non-Auto Manual or Non-Auto Breaker-Based Breaker-Based(30 1000 A) (30 1000 A)

    Maintenance Bypass Maintenance Bypass Maintenance Bypass Maintenance Bypass Maintenance Bypass Maintenance Bypass Maintenance BypassBreaker-Based Breaker-Based Breaker-Based Breaker-Based Breaker-Based Breaker-Based Breaker-Based(100 1000 A) (100 1000 A) (100 1000 A) (100 1000 A) (100 1000 A) (100 1000 A) (100 1000 A)

    COMMERCIAL INDUSTRIAL UTILITIES INSTITUTIONS GOVERNMENT COMMUNICATIONS DATA CENTRE

    5

  • Product Description

    Eatons Cutler-Hammer Automatic Transfer Switch is designed to provide unmatched performance, reliability and versatility forcritical standby power applications. The switches can beequipped with the ATC-300 or ATC-800 controllers to match yourapplication needs. All the controllers offer rock-solid monitoring,status reporting and transfer control operation. Superior designand robust construction make Eatons Cutler-Hammer transferswitch the industry benchmark for critical and distributedpower systems.

    Electrical Ratings

    Ratings 40, 100, 150, 200, 225, 260, 400, 600, 800,1000 and 1200 amperes

    2, 3 or 4-poles Up to 600 Vac, 50/60 Hz. NEMA 1, 3R, Open UL 1008 listed CSA C22.2 No. 178 certified

    Industrial Design Highlights

    Double-throw, mechanically interlocked transfer mechanism,preventing connection of both sources

    Field-selectable multi-tap transformer panel permits operationon a wide range of system voltages

    High withstand and closing ratings Compact design

    1200 Ampere ATS with ATC-300 Controller

    Contactor-basedTransfer Switches

    Switch Type - Open TransitionDelayed TransitionClosed Transition

    Standard Features (ATC-300)

    Switch position contacts: Source 1 Position 1NO and 1NC Source 2 Position 1NO and 1NC

    Source 1 and Source 2 sensing: Undervoltage/underfrequency Overvoltage/overfrequency 3-phase rotation protection 3-phase voltage unbalance/loss

    Pre-transfer signal contacts 1NO/1NC Go to Emergency (Source 2) Seven field-programmable time delays LCD-based display for programming, system diagnostics

    and Help message display Mimic diagram with source available and connected

    LED indication Time-stamped history log System test pushbutton Programmable plant exerciser OFF, daily, 7, 14, 28-day

    interval selectable run time 0 600 minutes no load/load with fail-safe

    Optional Features

    Available surge suppression device for power/controller,engine start circuit, phone and cable connections

    Space heater with thermostat Ammeter load side Power quality metering 2 and 4 position switch Stainless steel cover for controller Open in-phase transition or time delay neutral transition

    Optional Features (ATC 800 only)

    Closed transition Remote communications Load shed from emergency Selected automatic or non-automatic operation

    6

  • Type

    AT = AutomaticCT = Closed

    Transition

    Orientation

    C = Contactor

    Mechanism

    C2 = 2-PositionC3 = 3-Position

    Logic

    3 = ATC-3008 = ATC-800

    Mounting

    X = Fix Mount

    AT C 3 C2 X 3 0400 X S C

    Certification

    U = UL ListedC = CSA certified

    Number of poles

    2 = 2-Pole3 = 3-Pole4 = 4-Pole

    Enclosure

    K = OpenS = NEMA 1J = NEMA 12R = NEMA 3R

    Amperes

    0040 = 40 A0080 = 80 A0100 = 100 A0150 = 150 A0200 = 200 A0225 = 225 A0260 = 260 A0400 = 400 A0600 = 600 A0800 = 800 A1000 = 1000 A1200 = 1200 A

    Voltage

    A = 120 V, 60 HzB = 208 V, 60 HzE = 600 V, 60 HzG = 220 V, 50 HzH = 380 V, 50 HzK = 600 V, 50 HzM = 230 V, 50 HzN = 401 V, 50 HzO = 415 V, 50 HzW = 240 V, 60 HzX = 480 V, 60 HzZ = 365 V, 50 Hz

    100 Ampere ATS with ATC-300 Controller

    Contactor-based Automatic Transfer Switch Catalogue Numbering System

    Automatic, Non-Automatic up to 400 Amps Wall Mount. Automatic, Non-Automatic600 to 1200 Amps Floor Standing (Height "A" Includes Bottom Bracket).

    CONTACTOR-BASED TRANSFER SWITCH 40 1200 AMPERES - DIMENSIONS IN INCHES (MM) AND APPROXIMATE SHIPPING IN LBS. (KG)

    Enclosure Bolt Pattern Standard Terminals

    A (Height) B (Width) C (Depth) G (Horizontal) H (Vertical) Load Side, Normal Neutral WeightAmperes and Standby Source Connection Lbs. (kg)

    40 100 @ 480 V 38.68 (982.5) 18.31 (465.1) 13.34 (338.8) 10.25 (260.4) 37.38 (949.5) (1) #14 2/0 (1) #14 1/0 164 (74)

    40 100 @ 600 V 38.68 (982.5) 18.31 (465.1) 13.34 (338.8) 10.25 (260.4) 37.38 (949.5) (1) #14 2/0 (1) #14 1/0 164 (74)

    150 200 @ 480 V 38.68 (982.5) 18.31 (465.1) 13.34 (338.8) 10.25 (260.4) 37.38 (949.5) (1) #6 300 kcmil (3) 1/0 250 kcmil 164 (74)

    150 200 @ 600 V 48.74 (1238.0) 18.31 (465.1) 13.84 (351.5) 13.00 (330.2) 47.84 (1215.1) (1) #6 300 kcmil (3) 1/0 250 kcmil 260 (118)

    225 400 @ 480 V 48.74 (1238.0) 18.31 (465.1) 13.84 (351.5) 13.00 (330.2) 47.84 (1215.1) (2) #3 /0 250 kcmil (6) 250 500 kcmil 260 (118)

    225 1200 @ 600 V 79.41 (2017.0) 29.19 (741.4) 22.46 (570.5) N/A N/A (4) 1/0 750 kcmil (12) 1/0 750 kcmil 600 (272) 3-Pole 650 (295) 4-Pole

    600 1200 @ 480 V 79.41 (2017.0) 25.25 (641.4) 3-Pole 22.46 (570.5) N/A N/A (4) 1/0 750 kcmil (12) 1/0 750 kcmil 600 (272)29.19 (741.4) 4-Pole

    Wall Mount Floor Standing Height Dimension Includes the Bottom Bracket

    WITHSTAND AND CLOSE-ON RATINGS (KA)

    Ampere Rating 480 Volts 600 Volts

    Any Specific Any SpecificBreaker Breaker Breaker Breaker

    100, 200 10,000 30,000 10,000 22,000

    260, 320, 400 35,000 50,000 35,000 42,000

    600, 800, 1000,1200 50,000 65,000 50,000 65,000

    1

    1

    1

    1

    1

    1

    2

    2

    2

    7

  • Product Description

    Eatons Cutler-Hammer Automatic Transfer Switch is designed to provide unmatched performance,reliability and versatility forcritical standby power applications. The switches can beequipped with the ATC-300 or ATC-800 controllers to match yourapplication needs. A Bypass Isolation Transfer Switch may beused to provide emergency power to life safety and other criticalloads where maintenance of the main transfer switch, withoutinterruption of power to the load, is either desirable or required.

    Electrical Ratings

    Ratings 100, 150, 225, 260, 400, 600, 800, 1000 and 1200 amperes

    2, 3 or 4-poles Up to 600 Vac, 50/60 Hz. NEMA 1, 3R UL 1008 listed CSA C22.2 No. 178 certified

    Industrial Design Highlights

    Front access is a standard feature on all ratings Entry:

    Top, bottom or both Isolated compartments

    Improved safety: Isolated compartments with barriers Single motion rack-out with doors closed Ability to test powerswitching elements during

    draw-out process Dual ATS capability Bypass contactor can be controlled

    by the ATS controller in the bypass mode of operation Installation flexibility:

    Field Entry/Exit locations can be modified in the field Interchangeable drawout contactors

    Field-selectable multi-tap transformer panel permits operation on a wide range of system voltages

    Contactor-basedTransfer Switches

    Switch Type - Bypass Isolation

    Standard Features

    Draw-out cassette design on both ATS and Bypass No service interruption in Bypass to the same source Switch position contacts:

    Source-1 Position 1-N.O. and 1-N.C. Source-2 Position 1-N.O. and 1-N.C.

    Source-1 and Source-2 sensing: Undervoltage/underfrequency Overvoltage/overfrequency 3-phase rotation protection* 3-phase voltage unbalance/loss* Pre-transfer signal contacts1-N.O. and 1-N.C. Go to Source-2 (EMERGENCY)

    Field-programmable time delays: Time Delay Engine Start: 0 1200 seconds Time Delay Normal to Emergency: 0 1800 seconds Time Delay Emergency to Normal: 0 1800 seconds Time Delay Engine Cooldown: 0 1800 seconds Time Delay Emergency Failure: 0 6 seconds LCD-based display for programming, system diagnostics

    and Help Menu display Mimic diagram with Source Available and Connected

    LED indication Time-stamped history log System TEST pushbutton Programmable plant exerciser OFF, daily, 7, 14*, 28-day*

    interval selectable run time 0 600 minutes no load/loadwith failsafe

    *Note: ATC-300 only.

    Optional Features

    Available Surge Protection Device (SPD) for power/controller,engine start circuit, phone and cable connections

    Automatic transfer operation with selectable (via programming)non-automatic or automatic retransfer with failsafe

    Space heater with thermostat Digital multi-function power quality metering Stainless steel cover for controller Load sequencing contacts

    1200 Amp 3-Pole Bypass Isolation Switch

    8

  • Front Access

    Front access is a standardfeature. Source-1 (NORMAL)Source and Load connectionsare set up as standard topentry and Source-2(EMERGENCY) Source connections as bottom entry.These connections are locatedin their own separate compartments. These connections can be relocatedin the field if necessary.

    Multi-Tap Transformer

    The industry-exclusiveMulti-Tap system voltageselector allows the transferswitch to be applied on mostsystem voltages by properinsertion of the selector plug.

    Draw-out Contactors

    The ATS and the Bypassdraw-out cassette powercontactor designs are identicaland interchangeable. Thisstandard feature allows theuser the ability to withdraw,maintain or swap contactorassemblies, providingredundancy of ATS and Bypassfunctions from one contactorassembly to the other.

    Improved Safety

    The unique Eaton designincludes separation betweencontrol and power components. The ATS andBypass isolation contactors aremounted in separatecompartments with protectivebarriers between them. Thisdesign prevents the possibilityof contact with the rear-mounted power connections to the contactors.In addition, the top and bottomentry have separate compartment doors.

    Ease of Maintenance

    Transfer to the Bypass powercontactor is easily initiated andcontrolled via door-mountedcontrols. Once the transfer tothe Bypass contactor iscomplete, the ATS contactor is easily racked out with thecompartment door closed. The ATS contactor may thenbe tested in the racked outposition.

    Ease of Transfer

    The Eaton design allows theoperator to make a quick andsimple transfer from the ATSpower contactor to the Bypasscontactor by initiating theelectrically operated transfervia a 2-position switch. Doormounted indicating lightsconfirm that a successfultransfer has taken place.

    Dual ATS Capability

    The controller on conventionalBypass Isolation Switches onlycontrols the ATS contactor.The Eaton design allows theswitch controller to remainactive in both the ATS andBypass modes, thus providingcontrol to either contactor.This ability of the controller toremain active and control theBypass isolation contactorprovides "N+1" redundancyof a second fully functioningATS, a feature unique to Eaton.

    Bypass Isolation Switch Components

    9

  • Bypass Isolation Contactor-Based Design NEMA 1

    CONTACTOR-BASED TRANSFER SWITCH 100 1200 AMPERES DIMENSIONS IN INCHES (MM) AND APPROXIMATE SHIPPING IN LBS. (KG)

    SwitchRating Enclosure Standard Terminals WeightAmperes Height Width Depth Line Side (Normal Load Neutral Lbs. (kg)

    and Standby Source) Connection Connection

    100 200 90.00 (2286.0) 40.00 (1016.0) 28.97 (735.8) (1) #6 300 Cu/Al (1) #6 300 Cu/Al (3) #6 300 Cu/Al 1800 (817) NEMA 1

    100 200 90.00 (2286.0) 40.00 (1016.0) 44.47 (1129.5) (1) #6 300 Cu/Al (1) #6 300 Cu/Al (3) #6 300 Cu/Al 1850 (840) NEMA 3R

    400 1200 90.00 (2286.0) 40.00 (1016.0) 28.97 (735.8) (4) 3/0 750 Cu/Al (4) 3/0 750 Cu/Al (12) 3/0 750 Cu/Al 1800 (817) NEMA 1

    400 1200 90.00 (2286.0) 40.00 (1016.0) 44.47 (1129.5) (4) 3/0 750 Cu/Al (4) 3/0 750 Cu/Al (12) 3/0 750 Cu/Al 1850 (840) NEMA 3R

    NEMA 3R dimensions If seismic mounting brackets are required, then the width will be 46.00 (1168.4)1

    1

    1

    2

    10

  • WITHSTAND AND CLOSE-ON RATINGS (KA)

    Ampere Rating 480 Volts 600 Volts

    Any Specific Any SpecificBreaker Breaker Breaker Breaker

    100 10,000 30,000 10,000 22,000

    200 10,000 30,000 10,000 22,000

    260 35,000 50,000 35,000 42,000

    320 35,000 50,000 35,000 42,000

    400 35,000 50,000 35,000 42,000

    600 50,000 65,000 42,000 65,000

    800 50,000 65,000 42,000 65,000

    1000 50,000 65,000 42,000 65,000

    1200 50,000 65,000 42,000 65,000

    Type

    BI = BypassIsolationOpen Transition

    CB = BypassIsolationClosed Transition

    Orientation

    C = Contactor

    Mechanism

    C3 = 3-Position

    Logic

    3 = ATC-3008 = ATC-800

    Mounting

    E = Draw-outX = Fixed Mount

    BI C 3 C3 E 3 1200 W S C

    Certification

    U = UL ListedC = CSA certified

    Number of poles

    2 = 2-Pole3 = 3-Pole4 = 4-Pole

    Enclosure

    S = NEMA 1R = NEMA 3R

    Amperes

    0100 = 100 A0150 = 150 A0225 = 225 A0260 = 260 A0400 = 400 A0600 = 600 A0800 = 800 A1000 = 1000 A1200 = 1200 A

    Voltage

    B = 208 V, 60 HzE = 600 V, 60 HzG = 220 V, 50 HzH = 380 V, 50 HzK = 600 V, 50 HzM = 230 V, 50 HzN = 401 V, 50 HzO = 415 V, 50 HzW = 240 V, 60 HzX = 480 V, 60 HzZ = 365 V, 50 Hz

    Automatic Bypass Isolation Contactor-based Transfer Switch Catalogue Numbering System

    11

  • Standard Features (ATC300)

    Switch position contacts: Source 1 Position 1NO and 1NC Source 2 Position 1NO and 1NC

    Programmable Micro-processor based control Normal/Standby source monitoring Plant Exerciser with Failsafe (programmable) High Withstand, Closing and Interrupting Ratings Manual Transfer Under Load Engine Start Contacts Time Delay Normal to Emergency Time Delay Engine Start Time Delay Emergency to Normal Time Delay Engine Cooldown LED indicators switch position LED indicators source available Emergency source undervoltage/underfrequency sensing Normal source undervoltage sensing

    Time Delay Neutral Go to Emergency Contact (Area Protection) Pre-Transfer Signal Contacts Pushbutton Bypass Time Delays

    Optional Features

    Available surge suppression device for power/controller, engine start circuit, phone and cable connections

    Space heater with thermostat Ammeter load side Power quality metering Stainless steel cover for controller

    Optional Features (ATC 600)

    Remote communications Load shed from emergency Selected automatic or non-automatic operation

    Product Description

    An economical line of transfer switches with micro-processorbased logic, offering a standard feature package, for basicpower applications on 30-1000 ampere systems up to 600volts, 2, 3 or 4 pole.

    Electrical Ratings

    Ratings 40, 100, 150, 200, 225, 260, 400, 600, 800 and 1000 amperes

    2, 3 or 4-poles Up to 600 Vac, 50/60 Hz. NEMA 1, 3R, Open, 12, 4, 4x UL 1008 listed CSA C22.2 No. 178 certified

    Breaker-basedTransfer Switches

    Switch Type - Automatic, Manual and Electrically Operated 30A-1000A

    ATHM Automatic Transfer Switch

    12

  • TRANSFER SWITCH ENCLOSURE DIMENSIONS

    Frame size Rating Figure Height Width Depth

    30A - 150A, 600VF 30A - 200A, 240V A 32.63 (829) 24 (610) 9 (229)

    K, L, M 225A - 600A B 55 (1397) 32 (813) 15 (381)

    N 800A - 1200A B 65 (1651) 38 (965) 16 (406)

    Type

    AT = AutomaticMT = Non-Auto

    ManualNT = Non-Auto

    Electric

    Orientation

    H = Horizontal

    Switch Frame

    Type 240Vac 480Vac 600Vac

    FD = F Frame 30-225A* 30-150A 30-150AKD = K Frame 400A 200-300A 200-300ALD = L Frame 600A 400A 400AMD = M Frame 800A 600A** 600A**NB = N Frame 800-1000A 800-1000A 800-1000A

    Logic

    3 = ATC-300I = ATC-600X = No logic

    Mounting

    A = Source1 (MCS), Source 2 (MCS)B = Source1 (MCCB), Source 2 (MCCB)C = Source1 (MCCB), Source 2 (MCS)D = Source1 (MCS), Source 2 (MCCB)

    AT H 3 FD A 3 0100 E S C

    Certification

    U = UL ListedC = CSA certified

    Number of poles

    2 = 2-Pole3 = 3-Pole4 = 4-Pole

    Enclosure

    S = NEMA 1R = NEMA 3RJ = NEMA 12L = NEMA 4D = NEMA 4XK = OpenP = Sprinklerproof

    Amperes

    0030 = 30 A0070 = 70 A0100 = 100 A0150 = 150 A0200 = 200 A0300 = 300 A0400 = 400 A0600 = 600 A0800 = 800 A1000 = 1000 A

    Voltage

    A = 120 V, 60 HzB = 208 V, 60 HzE = 600 V, 60 HzG = 220 V, 50 HzH = 380 V, 50 HzK = 600 V, 50 HzM = 230 V, 50 HzN = 401 V, 50 HzO = 415 V, 50 HzW = 240 V, 60 HzX = 480 V, 60 HzZ = 365 V, 50 Hz

    Automatic Breaker-based Transfer Switch Catalogue Numbering System

    Notes: *225A single phase applications only**4 pole 600Vac 600A Use N Frame

    13

  • Product Description

    The Cutler-Hammer Bypass/Isolation Transfer Switch is designedfor applications where preventative maintenance, inspection andtesting must be accomplished while maintaining continuityof power to the load. Proven Cutler-Hammer switch designsensure reliable transfer from normal to auxiliary power sources for rapid restoration of essential power in critical applications.Now available in a compact 100 - 600A fully bussed design forboth Single and Double Sided Applications. (800A to 4000A alsoavailable. Contact your local Cutler-Hammer sales representativefor information).

    Electrical Ratings

    Ratings 40, 100, 150, 200, 225, 260, 400, 600, 800 and 1000 amperes

    2, 3 or 4-poles Up to 600 Vac, 50/60 Hz. NEMA 1, 3R UL 1008 listed CSA C22.2 No. 178 certified

    Superior Main Contact Structure

    The Cutler-Hammer Combination Bypass and AutomaticTransfer Switch is listed to CSA specifications C22.2 No. 178 and C22.2 No. 31.

    As an added plus the switching devices are listed under CSAC22.2 No. 5. Completely enclosed contacts provide both safetyand reliability. They also ensure the integrity of the contactassemblies and minimize the need for periodic maintenance ofthe contacts, reducing the need for downtime and maintenance time.

    Breaker-basedTransfer Switches

    Switch Type - Bypass Isolation

    Transfer Switch Is Easy To Maintain And Test

    The Cutler-Hammer Bypass/Isolation Switch is designed torequire minimum maintenance even under the most strenuousof operating conditions. Due to the use of moulded caseswitches and their inherent self-protection capability, the contactstructure and mechanism is extremely long lived.

    Our experience has shown that through normal operating conditions, the moving and stationary contacts will maintaintheir integrity for the full expected life of the transfer switch.

    When isolating and bypassing the transfer switch, a short term(less than 3 second) power interruption results. However, thisis less than when transferring power after a power outageusing a standard transfer switch. Also, with a double-sidedbypass the transfer switch can be bypassed to either sourcequickly and easily regardless of the position or condition of the transfer switch.

    Safety To Maintenance Personnel

    In most instances, the Bypass/Isolation Switch will be in theBypass Mode only during a maintenance or testing period.During this time, there could be operating personnel close tothe equipment. The self protection capability of theCutler-Hammer switch would give these operators an extrameasure of safety during a rare coincidental fault condition.

    Features

    The Cutler-Hammer Bypass Isolation Switch is available with all the options and features of our standard Transfer Switch product line. Proven, microprocessor based programmablecontrollers are supplied as standard on all Bypass TransferSwitches.

    Double Sided Bypass Isolation Switch

    14

  • Type

    4BI = SingleSidedBypass

    5BI = DoubleSidedBypass

    Orientation

    H = Horizontal

    Switch Frame

    Type 240Vac 480Vac 600Vac

    FD = F Frame 30-225A* 30-150A 30-150AKD = K Frame 400A 200-300A 200-300ALD = L Frame 600A 400A 400AMD = M Frame 800A 600A** 600A**NB = N Frame 800-1000A 800-1000A 800-1000A

    Logic

    3 = ATC-300I = ATC-600X = No logic

    Mounting

    A = Source1 (MCS), Source 2 (MCS)B = Source1 (MCCB), Source 2 (MCCB)C = Source1 (MCCB), Source 2 (MCS)D = Source1 (MCS), Source 2 (MCCB)

    4BI H 3 FD A 3 0100 E S C

    Certification

    U = UL ListedC = CSA certified

    Number of poles

    2 = 2-Pole3 = 3-Pole4 = 4-Pole

    Enclosure

    S = NEMA 1R = NEMA 3RJ = NEMA 12L = NEMA 4D = NEMA 4XK = OpenP = Sprinklerproof

    Amperes

    0030 = 30 A0070 = 70 A0100 = 100 A0150 = 150 A0200 = 200 A0300 = 300 A0400 = 400 A0600 = 600 A0800 = 800 A1000 = 1000 A

    Voltage

    A = 120 V, 60 HzB = 208 V, 60 HzE = 600 V, 60 HzG = 220 V, 50 HzH = 380 V, 50 HzK = 600 V, 50 HzM = 230 V, 50 HzN = 401 V, 50 HzO = 415 V, 50 HzW = 240 V, 60 HzX = 480 V, 60 HzZ = 365 V, 50 Hz

    Automatic Bypass Isolation Breaker-based Transfer Switch Catalogue Numbering System

    Notes: *225A single phase applications only**4 pole 600Vac 600A Use N Frame

    Typical Double Sided Bypass Transfer Switch

    BYPASS ISOLATION ATS (2 & 3 POLE) ENCLOSURE DIMENSIONS

    Max Max Switch CSA Dimensions (inches/mm)Amps Volts Frame Bypass Frame A H I J

    150 480 F F 21/533 30/965 79.5/2019 18/457150 600 F F 21/533 30/965 79.5/2019 18/457

    200 240 F F 21/533 30/965 79.5/2019 18/457

    225* 240 F F 21/533 30/965 79.5/2019 18/457

    300 480 K K 21/533 38/965 79.5/2019 18/457300 600 K K 21/533 38/965 79.5/2019 18/457

    400 240 K K 21/533 38/965 79.5/2019 18/457400 480 L K 21/533 38/965 79.5/2019 18/457400 600 L K 21/533 38/965 79.5/2019 18/457

    600 240 L L 21/533 38/965 79.5/2019 18/457600 480 M L 21/533 38/965 79.5/2019 18/457600 600 M L 21/533 38/965 79.5/2019 18/457

    800 240 NB MD 27.12/689 38/965 91.5/2324 24/610800 480 NB MD 27.12/689 38/965 91.5/2324 24/610800 600 NB MD 27.12/689 38/965 91.5/2324 24/610

    1000 240 NB ND 27.12/689 38/965 91.5/2324 24/6101000 480 NB ND 27.12/689 38/965 91.5/2324 24/6101000 600 NB ND 27.12/689 38/965 91.5/2324 24/610

    BYPASS ISOLATION ATS (4 POLE) ENCLOSURE DIMENSIONS

    Max Max Switch CSA Dimensions (inches/mm)Amps Volts Frame Bypass Frame A H I J

    150 480 F F 21/533 30/965 79.5/2019 18/457150 600 F F 21/533 30/965 79.5/2019 18/457

    200 240 F F 21/533 30/965 79.5/2019 18/457

    300 480 K K 21/533 38/965 79.5/2019 18/457300 600 K K 21/533 38/965 79.5/2019 18/457

    400 240 K K 21/533 38/965 79.5/2019 18/457400 480 L K 21/533 38/965 79.5/2019 18/457400 600 L K 21/533 38/965 79.5/2019 18/457

    600 240 L L 21/533 48/1219 79.5/2019 18/457600 480 NB ND 21/533 48/1219 91.5/2324 24/610600 600 NB ND 21/533 48/1219 91.5/2324 24/610

    800 240 NB ND 27.12/689 48/1219 91.5/2324 24/610800 480 NB ND 27.12/689 48/1219 91.5/2324 24/610800 600 NB ND 27.12/689 48/1219 91.5/2324 24/610

    1000 240 NB ND 27.12/689 48/1219 91.5/2324 24/6101000 480 NB ND 27.12/689 48/1219 91.5/2324 24/6101000 600 NB ND 27.12/689 48/1219 91.5/2324 24/610

    * Single Phase Only

    15

  • 16

    BREAKER-BASED TRANSFER SWITCH WITHSTAND/CLOSING RATINGS

    When protected by any manufacturers' breaker or Cutler-Hammer circuit breaker upstream as shown, the transfer switch is rated for use on a circuit capable ofdelivering not more than the RMS Symmetrical amps at the voltage shown below.

    25kA 35kA 42kA 50kA 65kA 100kA 200kA

    30 - 200 2,3,4 Any* Any* Any* Any* Any* Any* FDC,JDC,KDC

    225 2 Any* Any* Any* Any* Any* Any* FDC,JDC,KDC

    300 2,3,4 Any* Any* Any* Any* Any* Any* KDC

    400 2,3,4 Any* Any* Any* Any* Any* Any* KDC

    600 2,3,4 Any* Any* Any* Any* Any* Any* LDC

    800 - 1000 2,3,4 Any* Any* Any* Any* Any* Any* ---

    30 - 150 2,3,4 Any* Any* Any* Any* Any* (FDB/FD)+LFD 150kAFDC,JDC,KDC FCL***,LCL***

    200 - 300 2,3,4 Any* Any* Any* Any* Any* KDC,NB-TP** LCL***

    400 2,3,4 Any* Any* Any* Any* Any* --- ---

    600 2,3 Any* Any* Any* Any* Any* NB-TP ---

    800 2,3 Any* Any* Any* Any* --- NB-TP ---

    600 - 1000 4 Any* Any* Any* Any* --- --- ---

    1000 2,3 Any* Any* Any* Any* --- --- ---

    30 - 150 2,3,4 Any* Any* (FD/FDB)+LFD (FD/FDB)+LFD (FD/FDB)+LFD (FD/FDB)+LFD ---KDC KDC KDC LCL

    200 - 300 2,3,4 Any* Any* Any* KDC KDC LCL ---

    400 2,3,4 Any* Any* Any* KDC KDC --- ---

    600 2,3 Any* Any* Any* LDC --- --- ---

    600 4 Any* --- --- --- --- --- ---

    800 - 1000 2,3,4 Any* --- --- --- --- --- ---

    *Any manufacturers breaker **with P12 limiter *** 150kA maximum

    Transfer SwitchAmpere Rating

    Voltage

    120/240 and 240, 208Y/120

    480Y/277 and 480

    600Y/347 and 600

    Number of PolesSwitched

    Maximum fault level available at upstream device (kA symmetrical)Upstream any manufacturers' breaker or Cutler-Hammer circuit breaker type

    BREAKER-BASED TRANSFER SWITCH WITHSTAND/CLOSING RATINGS

    When protected by an upstream fuse type shown, the transfer switch is rated for use on a circuit capable of delivering notmore than the RMS Symmetrical amps at the voltage shown below.

    30 - 225 2,3,4

    300 2,3,4

    400 2,3,4

    600 2,3,4

    800 - 1000 2,3,4

    30 - 150 2,3,4

    200 - 300 2,3,4

    400 2,3,4

    600 2,3

    600 4

    800 - 1000 2,3,4

    Transfer SwitchAmpere Rating

    Voltage

    120/240 and 240, 208Y/120

    480Y/277,480,

    600Y/347 and 600

    Number of PolesSwitched Max. Fuse Amperes

    Maximum fault level available at upstream device (kA symmetrical)

    Upstream Fuse Type

    100kA 200kA--- J, T 200AJ,T --- 400AR J,T 400A

    J,T --- 600AJ,T R 600AL --- 1200AL --- 800A

    --- L 1600A

    --- L 1600A

    --- J,T 200AJ,T --- 400A

    R J,T 400AJ,T --- 600AJ,T R 600AL --- 1200AL --- 800A

    --- L 1600A

    --- L 1600A

    --- L 1600A

  • Product Description

    The automatic transfer switch controller is a key componentwithin the automatic transfer switch. It provides the intelligenceto sense the proper conditions to initiate a transfer and aretransfer of the contactor. Eatons Cutler-Hammer automatictransfer switches come with the design flexibility of beingapplied with one of three controllers. All three controllers providethe basic functions needed to perform an automatic transfer.

    Design Highlights Mimic diagram with source available and connected LED

    indications Field selectable fixed time delays Permits system testing via a front screen test pushbutton Complies with UL 1008/CSA 22.2 No. 178 Generator Test Selectable OFF, 7, 14, 28-day interval

    General Description (ATC-300 Controller)

    From installation to programming to usage, the ATC-300 opentransition controller was designed with operational simplicity inmind. The user friendly front panel interface simplifies routineoperation, programming, data presentation and settingadjustments. An LCD-based display provides the flexibility of a back-lit display for enhanced visibility.

    Design Highlights LCD-based display for programming, system diagnostic and

    Help Message display Mimic diagram with source available and connected

    LED indications Stores customer/factory established parameters in

    nonvolatile memory Field programmable time delays Displays real time and historical information with a

    time-stamped history log Permits system testing via a front screen test pushbutton Programmable plant exerciser OFF, daily, 7, 14, 28-day

    interval programmable run times Complies with UL 1008/CSA 22.2 No. 178

    General Description (ATC-600 and ATC-800 Controllers)

    The ATC-600 and ATC-800 controllers were designed with operational simplicity in mind. The user-friendly front panel interface simplifies routine operation, programming, data presentation and setting adjustments. An LCD-based display provides the flexibility of a back-lit display for enhanced visibility.

    Design Highlights LCD-based display for programming, system diagnostic

    and Help Message display Mimic diagram with source available and connected

    LED indications Stores customer/factory established parameters in

    nonvolatile memory Field programmable time delays Displays real time and historical information with a

    time-stamped history log Permits system testing via a front screen test pushbutton Programmable plant exerciser OFF, daily, 7, 14, 28-day

    interval selectable run times Communicate via Modbus communication protocol Complies with UL 1008/CSA 22.2 No. 178 Load monitoring, delayed, in-phase and closed transition

    Automatic TransferSwitch Controllers

    Controller Features

    Contactor-Based Design ATS Showing Optional Controllers Available

    17

  • 18

    AUTOMATIC TRANSFER SWITCH CONTROLLERS

    Description ATC-300 ATC-600 / ATC-800

    System Application Voltage Up to 600 Vac Up to 600 Vac

    Voltage SpecificationsVoltage Measurements of: Source 1 and 2 VAB, VBC and VCA Source 1, 2 and Load VAB, VBC and VCAVoltage Measurement Range 0 790 Vac rms 0 700 Vac rms

    Operating Power 65 Vac 145 Vac 65 Vac 145 Vac

    Frequency SpecificationsFrequency Measurements of: Source 1 and 2 Source 1 and 2Frequency Measurement Range 40 70 Hz 40 80 Hz

    Environmental SpecificationsOperating Temperature Range -20 to +70C -20 to +70CStorage Temperature Range -30 to +85C -30 to +85C

    Operating Humidity 0 to 95% Relative Humidity (Non-condensing) 0 to 90% Relative Humidity (Non-condensing)

    Operating Environment Resistant to Ammonia, Methane, Nitrogen, Resistant to Ammonia, Methane, Nitrogen, HydrogenHydrogen and Hydrocarbons and Hydrocarbons

    Front Panel IndicationMimic Diagram with LED Indication Unit Status. Source 1 and 2 Available and Automatic, Test and Program Mode.

    Connected (5 Total) Source 1 and 2 Available, Connected and Preferred. Load Energized (10 Total) Preferred. Load Energized (10 Total)

    Main Display LCD-Based Display LED DisplayDisplay Language English, French English

    Communications Capable N/A PONI/INCOM

    Enclosure Compatibility NEMA 1, 12 and 3R, NEMA 1, 12, 3R and 4X UVUV Resistant Faceplate Resistant Faceplate

    Programming SelectionsTime Delay Normal to Emergency 0 1800 Seconds 0 1800 SecondsTime Delay Emergency to Normal 0 1800 Seconds 0 1800 SecondsTime Delay Engine Cooldown 0 1800 Seconds 0 1800 SecondsTime Delay Engine Start 0 120 Seconds 0 120 SecondsTime Delay Neutral 0 120 Seconds 0 120 Seconds or Based on

    Load Voltage Decay of 2% 30% of NominalTime Delay Source 2 Fail 0 6 Seconds 0 6 SecondsTime Delay Voltage Unbalance 10 30 Seconds N/AVoltage Unbalance 3-Phase 0 or 1 (1 = Enabled) % of Unbalanced Voltage Dropout 5% 20% (DO) Dropout -2% 3% (PU) N/APhase Reversal 3-Phase OFF, ABC, CBA N/AIn-Phase 0 or 1 (1 = Enabled) N/ALoad Sequencing N/A Up to 10 Devices (via Sub-network)Pre-Transfer Signal 1 120 Seconds (Form C Contact) 0 120 Seconds Up to 10 Devices (via Sub-network)Plant Exerciser Selectable Off, Daily or 7, 14, 28 Selectable Disabled or 7

    Day Intervals, 0 600 Minutes, Load or No Load Day Interval, 0 600 Minutes, Load or No LoadPreferred Source Selection N/A Source 1 or 2 or NoneCommitment to Transfer in TDNE N/A Enabled or DisabledRe-transfer Mode N/A Automatic or ManualAuto Daylight Savings Time Adjustment 0 or 1 (1 = Enabled) System Selection Utility/Generator or Dual Utility Utility/Generator or Dual Utility or Dual GeneratorClosed Transition Frequency Difference N/A 0.0 3.0 HzClosed Transition Voltage Difference N/A 1 5%

    Note: Features are order specific. Not all features are supplied as standard.

  • Integrated Solutions

    Minimize initial equipment costs, reduce installation time, andincrease system reliability. These are goals of all involved inplacing electrical distribution equipment in service from thedesign engineer, to the electrical contractor, and especially withthe end user of the equipment.

    Eaton believes the transfer switch equipment is an integral partof the distribution equipment. This fundamental belief is whyEaton offers various types of transfer switches for the designengineer, electrical contractor and the user to choose from.Eaton offers Contactor-Based, Moulded Case and Circuit Breakerstyle switches.

    All Eaton transfer switches are designed to meet the requirementsset forth by CSA C22.2 No.178, however, all transfer switches arenot created equal. You can be assured of safe and reliable operationfrom all types of transfer switches that Eaton offers.

    Integrated Solutions

    Automatic Transfer Switch Integrated Into a Switchboard Lineup

    19

  • Eaton Corporation is a diversifiedpower management companyranked among the largestFortune 500 companies. Theelectrical sector is Eatons largestdivision and is a global leaderin electrical control, powerdistribution, power quality,automation, and monitoringproducts and services.Eatons global electrical productlines, including Cutler-Hammer,MGE Office ProtectionSystems, Powerware,Holec, MEM, Santak andMoeller, provide customer-drivenPowerChain Management

    solutions to serve the powersystem needs of the industrial,institutional, government,utility, commercial, residential,IT, mission critical and OEMmarkets worldwide.

    PowerChain Managementsolutions help enterprisesachieve sustainable andcompetitive advantages throughproactive management of thepower system as a strategic,integrated asset throughoutits life cycle. With Eatonsdistribution, generation andpower quality equipment;full-scale engineering services;and information managementsystems, the power systemis positioned to deliverpowerful results: greaterreliability, operating costefficiencies, effective use ofcapital, enhanced safety, andrisk mitigation.