Upload
yihtyngyong
View
30
Download
1
Tags:
Embed Size (px)
DESCRIPTION
Integration of Building Science Elements to Studio 5 Project
Citation preview
SCHOOL OF ARCHITECTURE, BUILDING & DESIGN
Modern Architecture Studies in Southeast Asia (MASSA) Research Unit
Bachelor of Science (Honours) (Architecture)
BUILDING SCIENCE 2 [ARC 3413]
Project 2
Lighting and Acoustic Performance
Integration with Design Studio 5
Student Name:
Yong Yih Tyng
Student ID:
0312764
Tutor:
Mr Edwin
Content Page
1. Project Introduction and Methodology
2. Project Objectives
3. Building Background
4. Light Performance
a. Day lighting – Balcony
1. Position on Plan, Space function, lux and standard requirements
2. Rendering
3. Calculation
4. Proposal
b. Artificial lighting – Mechanical Room
1. Position on Plan, Space function, lux and standard requirements
2. Calculation
3. Proposal
4. Comparison Rendering
c. PSALI – Discussion Room
1. Position on Plan, Space function, lux and standard requirements
2. Pre- rendering
2. Proposal
3. Calculation
4. Proposal Reflected Ceiling Plan
5. End – product Rendering
5. Acoustics Performance
a. Reverberation – Discussion Room
1. Position on Plan, Space function, lux and standard requirements
2. Calculation
3. Proposal
b. Transmission Loss (STC) – Mechanical Room
1. Position on Plan, Space function, lux and standard requirements
2. Calculation
3. Proposal
c. External Noise
1. Position on Plan, Space Function and Issue
2. Solution – Passive Design
6. Reference
1. Project Introduction and Methodology
This is a research integration report of light and acoustic elements within the proposed
community building in studio 5. The building is a community library which serve its function to
provide a local gathering space for knowledge sharing, artwork creation and communication. The
total built up functional space for the library is 2000 meter square.
The research project is divided into two categories: Light and Acoustics Integration Design.
For light integration design, three spaces are selected for the study, as tabulated below.
TYPE OF LIGHTING SPACE
Day Light Balcony Reading
Artificial Light Mechanical Room
PSALI Discussion Room
TYPE OF ACOUSTICS SPACE
Reverberation Discussion Room
Transmission Loss (STC) Mechanical Room Wall
External Noise Source a. Back Alley
b. Road In Front
c. Junction
d. Shop around
In the light research integration project, Autodesk Eco-tech is the software that is being
used as a research tool for the project.
2. Project Objectives
The main intention of the project is to test our ability to integrated and apply pre-design decision
in light and acoustics in final design through problem-solving.
3. Site/ Building Background
Site Location (GPS: 3⁰07’58.5’’N 101⁰41’24.5’’E)
Site Map Existing Building On Site
Proposed Building On Site
Floorplans
Ground Floor First Floor
Second Floor Third Floor
4.0 LIGHT PERFORMANCE
4. Light Performance
a. Day lighting – Balcony
1. Position on Plan, Space function, lux and standard requirements
Space Function:
Contain light duty machine –
book binding, card making machine, 3D printer
(detail work)
Lux requirement/ Standard:
Malaysian sky is classified as intermediate mean
sky and overcast sky with illumination between
60,000 to 80,000 lux at the noon during the
months when solar radiation is highest.
Space Dimension (m²): 53.77
a b
c
d
0 1 2 3 4 5 M
2. Calculation
Daylight factor
Daylight factor is measured as the ratio of illumination at the working plane inside a room to the total
light available outside. (%)
DF – ratio of internal light level to external light level
DF = 𝑬𝒊
𝑬𝒐𝑿 𝟏𝟎𝟎%
Ei = illuminance due to daylight at a point on the indoors working plane
Eo = simultaneous outdoor illuminance on a horizontal plane from an unobstructed hemisphere of sky
Ei 300 lux
Eo (from rendering) 18000 lux
DF = (Ei/Eo) X 100% 1.67
3. Rendering
3D light Values (from outside to inside)
Daylight Contour Map
4. Proposal
Adjustable louvers to control amount of light enter the interior space.
b. Artificial lighting – Mechanical Room
1. Position on Plan, Space function, lux and standard requirement
Space Function:
Contain light duty machine –
book binding, card making machine, 3D printer
(detail work)
Illuminance level required (lux):
750 Lux
Foot Candles
50 – 75 -100
Mechanical Room (Ground floor)
Space Dimension (m²): 20.75
0 1 2 3 4 5 M
a
b
c
d
e
2. Calculation
Luman Method (Formula):
𝑵 = 𝑬 𝑿 𝑨
𝑭 𝑿 𝑼𝑭 𝑿 𝑴𝑭
N = number of lamps required
E = illuminance level required (lux)
A = area at working plan height (m²)
F = average luminous flux from each lamp (lm)
UF = utilization factor, an allowance for the light distribution of the luminaire and the room
surfaces
MF = maintenance factor, an allowance for reduced light output because of deterioration and dirt
Maintenance Factor (MF)
MF = LLMF X LSF X LMF X RSMF
LLMF – lamp lumen maintenance factor
LSF – lamp survival factor
LMF – luminaire maintenance factor
RSMF – room surface maintenance factor
Room Index (K)
Room Index = 𝐊 = 𝑳 𝑿 𝑾
(𝑳+𝑾)𝒉𝒎
Utilization Factor (UF) (should always less than 1 for effectiveness)
𝑼𝑭 = 𝑬𝒇𝒇𝒆𝒄𝒕𝒊𝒗𝒆 𝒍𝒖𝒎𝒊𝒏𝒐𝒖𝒔 𝒇𝒍𝒖𝒙
𝑻𝒐𝒕𝒂𝒍 𝒍𝒖𝒎𝒊𝒏𝒐𝒖𝒔 𝒇𝒍𝒖𝒙 𝒐𝒇 𝒂𝒍𝒍 𝒕𝒉𝒆 𝒔𝒖𝒓𝒇𝒂𝒄𝒆𝒔
Reflectance Chart
Colour Reflectance
White, off-white, light shades of gray, brown,
blue
75% - 90%
Medium green, yellow, brown, gray 30% - 60%
Dark gray, medium blue 10% - 20%
Dark blue, green, wood panelling 5% - 10%
For Uniform Illumination
Achieve uniform lighting spacing between the luminaires should be less than 1.5times the mounting
height.
Luminaire Spacing < 1.5Hm
The (SHR) spacing to mounting height ratio is 3:2
Proposed Light Specifications
Type BPS680
Light Source Philips Fortimo LED Line 3R
Power LED 24: 25W
Beam Angle 80 - 100⁰ (depending on configuration)
Luminous flux 1650 – 4050 lm (depending on configuration) min 1750 lux – 4300 lux
Correlated Color
Temperature
4000 K
Color rendering ≥ 80
Median useful
life L70B50
70,000 hours
Driver failure
rate
1% per 5000 hours
Average
ambient
temperature
+ 25 ̊ C
Operating
temperature
range
+ 10 to + 40 ̊C
Driver Built - in
Mains voltage 230 or 240 V / 50-60Hz
Material Housing: natural anodized aluminum
End caps: die-cast aluminum
Optical Cover OLC micro-lens optic in polycarbonate cover (LIN-PC)
Installation Individual; suspended mounting with a set of two single steel-wire suspensions
(SM2), with metal-like or white power cord, 150 cm, and ceiling caps Fast fine
adjustment with clutch device (Reutlinger) Through-wiring possible Installation
without removing LED module and optic/cover
Room Dimension (L X W) 20.75
Reflectance 75 –
90%
Utilization Factor (UF) 0.85
Illuminance Level Required (lux) 750
Lamp Maintenance Factor 0.90
Room Index (K) 2.789
Maximum Lux (X 0.7) 1275
Mounting Height (m) 1.5
Working Plan Height (m) 0.85
Spacing Distance (center to center) (m) 3.008
Maintenance factor 0.90
Utilization Factor (UF)
𝑼𝑭 = 𝟎. 𝟖𝟓
Room Index (K)
𝐊 = 𝑳 𝑿 𝑾
(𝑳+𝑾)𝒉𝒎
K = 𝟐𝟎.𝟕𝟓
( 𝟑.𝟗+𝟓.𝟒)𝑿 𝟎.𝟖𝟎
= 2.789
Luman Method (Formula):
N = number of lamps required
E = illuminance level required (lux)
A = area at working plan height (m²)
F = average luminous flux from each lamp (lm)
UF = utilization factor, an allowance for the light distribution of the luminaire and the room
surfaces
MF = maintenance factor, an allowance for reduced light output because of deterioration and dirt
Value refer table above:
𝑵 = 𝑬 𝑿 𝑨
𝑭 𝑿 𝑼𝑭 𝑿 𝑴𝑭
N = 𝟕𝟓𝟎 𝑿 𝟐𝟎.𝟕𝟓
𝟒𝟎𝟓𝟎 𝑿 𝟎.𝟖𝟓 𝑿 𝟎.𝟗𝟎
N = 3.817
N = 4 (Round off)
3. Proposal Reflected Ceiling Plan
Taking N = 13
By formula, (SHR) spacing to mounting height ratio is 3:2
The mounting height = 1.5m
3: 2 = Spacing: 1.5m
1.5 X 1.5 = 2.25metres
The number of rows of lamps is calculated by dividing the width of the room (3.9m)
3.9 m / 2.25 m = 1.73 (2 rows)
Note: Half the spacing (1.125m) is used for the ends of rows
Hence, 1 row = N/2 = 4/2 = 2
Longitudinal spacing between lamps can be calculated by dividing the length of the building by the no of
lamps per row,
Length of the building:
5.4m / 2 = 2.7
Half the spacing at both ends = 2.7 / 2
= 1.35m
Proposed Reflected Ceiling Plan
4. Rendering
Before Light Application (Solely Daylight rendering)
ON GROUND LEVEL
Outdoor Value 79 – 92%
Indoor Value 64 - 57.18%
ON WORKING PLAN
Outdoor Value 79 – 92 %
Indoor Value 57 – 61%
After Light Improvement Application
Light rendering At Working Plan 850cm height, Electrical Light Analysis, Light Arrangement
refer to proposed reflected ceiling plan.
c. PSALI – Discussion Room
1. Position on Plan, Space function, lux and standard requirements
Space Function:
For Discussion
Lux requirement/ Standard:
300 lux
Discussion Room (Third floor)
Space Dimension (m²): 14.62
0 1 2 3 4 5 M
a
b
c
d
2. Pre - rendering
Before
ON FLOOR LEVEL
Outdoor Value 82 - 94%
Indoor Value 53 - 81%
ON WORKING PLAN
Outdoor Value 82 - 94%
Indoor Value 53 - 81%
Observation:
Space on left (refer to blue hatched space) – needs improvement in luminosity during the day.
A controllable light system is needed for this room
3. Proposed Light Specifications
Type SP526P
Light Source Philips LED module PP
Power (+/-10%) 38W, 40W
Luminous flux 4000lm in total, 2000lm for each ellipse (1501 lux)
Correlated Color
Temperature
3000 or 4000 K
Color Rendering
Index
≥ 80
Median useful
life L80B50
50,000 hours
Driver failure
rate
1% per 5000 hours
Average
ambient
temperature
+ 25 ̊ C
Operating
temperature
range
+ 10 to 40 ̊C
Mains voltage 220 – 240 V / 50 – 60 Hz
Dimming Dimmable
Controls system
input
DALI
Material Housing and optics: polycarbonate
Color White (WH) and light grey (GR)
Optic Poly-carbonate LED cup
Connection Push – in connector with pull relief
Installation SP520P and SP522P, connection with clips to an exposed T-bar ceiling with
two triangular steel-wire suspensions (SMTT), both with metal-like power cord,
150cm, driver in separate driver box, SP524P and SP526P, decorative ceiling
bar with integrated driver, screw mounting to ceiling Through-wiring possible:
no
4. Calculation
Luman Method (Formula):
𝑵 = 𝑬 𝑿 𝑨
𝑭 𝑿 𝑼𝑭 𝑿 𝑴𝑭
N = number of lamps required
E = illuminance level required (lux)
A = area at working plan height (m²)
F = average luminous flux from each lamp (lm)
UF = utilization factor, an allowance for the light distribution of the luminaire and the room
surfaces
MF = maintenance factor, an allowance for reduced light output because of deterioration and dirt
Maintenance Factor (MF)
MF = LLMF X LSF X LMF X RSMF
LLMF – lamp lumen maintenance factor
LSF – lamp survival factor
LMF – luminaire maintenance factor
RSMF – room surface maintenance factor
Room Index (K)
Room Index = 𝐊 = 𝑳 𝑿 𝑾
(𝑳+𝑾)𝒉𝒎
Utilization Factor (UF) (should always less than 1 for effectiveness)
𝑼𝑭 = 𝑬𝒇𝒇𝒆𝒄𝒕𝒊𝒗𝒆 𝒍𝒖𝒎𝒊𝒏𝒐𝒖𝒔 𝒇𝒍𝒖𝒙
𝑻𝒐𝒕𝒂𝒍 𝒍𝒖𝒎𝒊𝒏𝒐𝒖𝒔 𝒇𝒍𝒖𝒙 𝒐𝒇 𝒂𝒍𝒍 𝒕𝒉𝒆 𝒔𝒖𝒓𝒇𝒂𝒄𝒆𝒔
Reflectance Chart
Colour Reflectance
White, off-white, light shades of gray, brown,
blue
75% - 90%
Medium green, yellow, brown, gray 30% - 60%
Dark gray, medium blue 10% - 20%
Dark blue, green, wood panelling 5% - 10%
For Uniform Illumination
Achieve uniform lighting spacing between the luminaires should be less than 1.5times the mounting
height.
Luminaire Spacing < 1.5Hm
The (SHR) spacing to mounting height ratio is 3:2
Proposed lighting Calculation
Room Dimension (L X W) 14.62
Reflectance 75- 90%
Daylight Average Lux (20’ /600 cm from
window) Obtain from rendering
9900 lm
Luminous Flux from lamp 4000 lm
Utilization Factor (UF) 0.85
Illuminance Level Required (lux) 300.00
Lamp Maintenance Factor 0.90
Room Index (K) 1.603
Maximum Lux (X 0.7) 510
Mounting Height (m) 1.20
Working Plan Height (m) 0.85
Spacing Distance (center to center)
Utilization Factor (UF)
𝑼𝑭 = 𝟎. 𝟖𝟓
Room Index (K)
𝐊 = 𝑳 𝑿 𝑾
(𝑳+𝑾)𝒉𝒎
K = 𝟏𝟒.𝟔𝟐
( 𝟒.𝟐+𝟑.𝟒)𝑿 𝟏.𝟐𝟎
= 1.603
Luman Method (Formula):
N = number of lamps required
E = illuminance level required (lux)
A = area at working plan height (m²)
F = average luminous flux from each lamp (lm)
UF = utilization factor, an allowance for the light distribution of the luminaire and the room
surfaces
MF = maintenance factor, an allowance for reduced light output because of deterioration and dirt
Value refer table above:
𝑵 = 𝑬 𝑿 𝑨
𝑭 𝑿 𝑼𝑭 𝑿 𝑴𝑭
N = 𝟑𝟎𝟎 𝑿 𝟏𝟒.𝟔𝟐
𝟒𝟎𝟎𝟎 𝑿 𝟎.𝟖𝟓 𝑿 𝟎.𝟗𝟎
N = 1.43
N = 2 (Round off)
Taking N = 2
By formula, (SHR) spacing to mounting height ratio is 3:2
The mounting height = 1.2m
3: 2 = Spacing: 1.2m
1.5 X 1.2 = 1.8 metres
The number of rows of lamps is calculated by dividing the width of the room (4.2 m)
4.2 m / 1.8 m = 2.3 (2 rows)
Note: Half the spacing (0.9 m) is used for the ends of rows
Hence, 1 row = N/2 = 2/2 = 1
Longitudinal spacing between lamps can be calculated by dividing the length of the building by the no of
lamps per row,
Length of the building:
3.4m / 1 = 3.4
Half the spacing at both ends = 3.4 / 2
= 1.7m
5. Proposal of Reflected Ceiling Plan with controllable lighting system
6. End-product Rendering
After
Electrical Light rendering ON WORKING PLAN
Electrical Light rendering ON Ground Plan
5.0 ACOUSTICS PERFORMANCE
5. Acoustics Performance
a. Reverberation – Discussion Room
1. Position on Plan, Space function, Acoustics and standard requirements
Space Function:
For Discussion
Acoustics requirement/ Standard:
0.6 – 1.0, NC 25- 35
(Reference
http://www.acoustics.com/conference_room.asp)
RT 0.7, Maximum Noise 35dBA, NC 28
(Reference based on table 1. Maximum ambient
noise levels and optimum reverberation times
(RT) for good speech intelligibility)
Octave Band Center Frequency 500 – 1000 HZ
(Reference http://www.engineeringtoolbox.com/nc-noise-
criterion-d_725.html)
Discussion Room (Third floor)
Space Dimension (m²): 14.62
Wall Dimension (mm):
a. 4217 (length) X 50 (Width) X 3000 (Height)
= 0.63 m³
b. 3416 (length) X 50 (Width) X 3000 (Height)
= 0.51m³
c. 4217 (length) X 50 (Width) X 3000 (Height)
= 0.63 m³
d. 3416 (length) X 50 (Width) X 3000 (Height)
= 0.51m³
0 1 2 3 4 5 M
a
b
c
d
2. Calculation
*Absorption of a surface = surface area (S) X absorption coefficient (a)
Total room absorption (A) = sum of above *
A = 𝑺𝟏𝒂𝟏 + 𝑺𝟐𝒂𝟐 + 𝑺𝟑𝒂𝟑 + 𝑺𝟒𝒂𝟒 + ⋯ … … 𝑺𝒏𝒂𝒏
Where 𝑺𝟏 … … . . 𝑺𝒏 Area of each surface 1 to n
𝒂𝟏 … … . . 𝒂𝒏 Absorption coefficient of each surface 1 to n
Reverberation time Calculation
RT = 𝟎.𝟏𝟔 𝑿 𝑽𝒐𝒍𝒖𝒎𝒆 𝒐𝒇 𝒔𝒑𝒂𝒄𝒆
𝑺𝒖𝒎 𝒐𝒇 𝑺𝑨
Wall A
Surface Area (m²) Absorption Sa
Wooden Strip 31pcs 31 X 0.5 X 3 = 46.5 0.055 2.558
Glass Strip 26 pcs 26 X 0.5 X 3 = 39 0.02 0.780
Glass Panel 1 pcs 0.35 X 3 = 1.05 0.5 0.525
Glass Door 1 pcs 2.2 X 1 = 2.2 0.5 1.10
Glass Panel above door 0.8 X 0.9 = 0.72 0.5 0.360
Sub- Total absorption (SA) 5.323 Reference: Sound Absorption Coefficients of General Building Materials Table from “Acoustical Ceilings – Use and Practice”,
Ceilings and Interior Systems Contractors Association (1978), p. 18
Wall B
Surface Area (m²) Absorption Sa
Wooden Strip 33 X 0.5 = 16.5 0.055 0.908
Glass Strip 35 X 0.5 = 17.5 0.02 0.350
Sub- Total absorption (SA) 1.258 Reference: Sound Absorption Coefficients of General Building Materials Table from “Acoustical Ceilings – Use and Practice”,
Ceilings and Interior Systems Contractors Association (1978), p. 18
Wall C
Surface Area (m²) Absorption Sa
Glass wall 1 pcs 4.217 X 3 = 12.6 0.5 6.3
Sub- Total absorption (SA) 6.3 Reference: Sound Absorption Coefficients of General Building Materials Table from “Acoustical Ceilings – Use and Practice”,
Ceilings and Interior Systems Contractors Association (1978), p. 18
Wall D
Surface Area (m²) Absorption Sa
Wooden Strip 20 pcs 20 X 0.5 X 3 =30 0.055 1.65
Glass Strip 19 pcs 19 X 0.5 X 3 = 28.5 0.02 0.570
Glass Panel 1pcs 1.47 X 3 = 4.41 0.5 2.205
Sub- Total absorption (SA) 4.425 Reference: Sound Absorption Coefficients of General Building Materials Table from “Acoustical Ceilings – Use and Practice”,
Ceilings and Interior Systems Contractors Association (1978), p. 18
Grand Total of SA: 17.306
RT = 𝟎.𝟏𝟔 𝑿 𝟒𝟑.𝟖𝟔
𝑺𝒖𝒎 𝒐𝒇 𝑺𝑨 =
𝟕.𝟎𝟏𝟕𝟔
𝟏𝟕.𝟑𝟎𝟔 = 0.405
Requirement: 0.7 RT. The RT for existing is lower than requirement.
Hence,
0.7 – 0.405 = 0.295
0.295 = 0.16 𝑋 43.86
𝑋
0.295 x = 7.0176
X = 23.788 (total SA required to meet the criteria) - Proposal
3. Proposal
By taking total STC lacking in the room: 23.788 SA
Proposed,
Acoustics Panels
FABRIC WRAPPED ACOUSTIC PANELS INSTALLATION
b. Transmission Loss (STC) – Mechanical Room
1. Position on Plan, Space function, Acoustics and standard requirements
Space Function:
Contain light duty machine –
book binding, card making machine, 3D printer
(detail work)
Acoustics requirement/ Standard Relation to its
surrounding:
Purpose:
To stop noise from spreading from mechanical room
To its surrounding area
Mechanical Room (Ground floor)
Space Dimension (m²): 20.75
Wall Dimension:
a. 3905.6 (length) X 322.6 (Width) X 3000 (Height)
= 3.51 m³
b. 5384.3 (length) X 200 (Width) X 3000 (Height)
= 3.24 m³
c. 2428 (length) X 220 (Width) X 3000 (Height)
= 1.602 m³
d. 3028.7 (length) X 220 (Width) X 3000 (Height)
= 1.998 m³
e. 2529.5 (length) X 220 (Width) X 3000 (Height)
= 1.669 m³
0 1 2 3 4 5 M
a
b
c
d
e
Building Code of Australia Requires
The Building Code of Australia (BCA) requires a wall separating sole occupancy units, or between a sole occupancy
unit and a public corridor, plant room, lift shaft, stairway, hallway or the like, to have a Weighted Sound Reduction
Index (Rw) not less than 45.
Where a habitable room such as a living room, dining room, family room, bedroom, study and the like, but not
including the kitchen, in one sole occupancy unit is situated next to a bathroom, sanitary compartment, kitchen or
laundry in an adjoining unit, the wall separating the units must have an Rw not less than 50. In addition, the dividing
wall construction must provide a “satisfactory” level of impact sound isolation.
Soil and waste pipes which serve or pass through more than one sole occupancy unit must be separated by a
construction which provides a minimum of Rw 45 if adjacent to a habitable room (other than a kitchen), or Rw 30 if
the adjacent room is a kitchen, bathroom, laundry or the like.
Note: Rating of sound insulation in buildings and of building elements now refer to a “Weighted Sound Reduction
Index (Rw )” to replace “ Sound Transmission Class (STC)”. This was changed in amendment No. 6 to BCA 96.
The International Building Code (ref. 4)
contains requirements to regulate sound transmission through interior partitions separating adjacent
dwelling units and separating dwelling units from adjacent public areas, such as hallways, corridors,
stairs or service areas. Partitions serving the above purposes must have a sound transmission class of at
least 50 dB for airborne noise when tested in accordance with ASTM E90. If field tested, an STC of 45
must be achieved. In addition, penetrations and openings in these partitions must be sealed, lined or
otherwise treated to maintain the STC. Guidance on achieving this for masonry walls is contained below
in Design and Construction. The International Residential Code (ref. 5) contains similar requirements,
but with a minimum STC rating of 45 dB when tested in accordance with ASTM E90 for walls and
floor/ceiling assemblies separating dwelling units.
2. Calculation
Sound pressure is a measure of the pressure on the eardrum
𝐒𝐩𝐥 = 𝟏𝟎𝒍𝒐𝒈𝟏𝟎
𝒑²
𝒑𝒐𝟐
p = root mean squared pressure (n/m²)
Po = reference pressure ( 2 X 10−5 N/𝑚2)
Sound Reduction Index SRI or Transmission Loss TL/ Transmission Coefficient
T = transmission loss
TL = 10 X 𝒍𝒐𝒈𝟏𝟎 [𝟏
𝑻𝒂𝒗]
𝑻𝒂𝒗 = (𝑺𝟏 𝑿 𝑻𝒄𝟏+ 𝑺𝟐 𝑿 𝑻𝒄𝟐+ …… 𝑺𝒏 𝑻𝒄𝒏
𝑻𝒐𝒕𝒂𝒍 𝑺𝒖𝒓𝒇𝒂𝒄𝒆 𝑨𝒓𝒆𝒂)
𝑻𝒄𝒏 = The Transmission Coefficient of Material
𝑺𝒏 = The surface area of material n
Wall A
Surface STC Rating
(DB)
Area (m²) Transmission
Coefficient, ( 𝑻𝒄𝒏)
ST
Brick Wall
(Clay Brick Systems)
4" Brick 2" Air space
50 3.9 X 3 = 11.7 6.738 X 10 ̄ ³ 0.079
Sub- Total of ST 0.079 Reference: http://www.maconline.org/tech/materials/sstoc/sswalls12/sswalls12.html
Sub- Total surface area: 11.7 m²
Wall B
Surface STC Rating
(DB)
Area (m²) Transmission
Coefficient, ( 𝑻𝒄𝒏)
ST
Concrete Wall
(Cavity Wall – Interior) 4" Split Face Block 3.5" airspace 2.5" Fiberglass Insulation 4" C.M.U.
79 5.4 X 3 – 4 X
1.5 = 10.2 3.7074 X 𝟏𝟎−𝟒 3.7816 X 10−3
Glass Window Panel Soundproof windows over a
single pane window
51 4 X 1.5 = 6 6.097 X 𝟏𝟎−𝟑 0.0366
Sub- Total of ST 0.04038 Reference: http://www.maconline.org/tech/materials/sstoc/sswalls12/sswalls12.html
Sub - Total surface area: 16.2 m²
Wall C
Surface STC Rating
(DB)
Area (m²) Transmission
Coefficient, ( 𝑻𝒄𝒏)
ST
Concrete Wall
(Cavity Wall – Interior) 4" Split Face Block 3.5" airspace 2.5" Fiberglass Insulation 4" C.M.U.
79 2.4 X 3 = 7.2 3.7074 X 𝟏𝟎−𝟒 2.669 X 𝟏𝟎−𝟑
Sub- Total of ST 0.002669 Reference: http://www.maconline.org/tech/materials/sstoc/sswalls12/sswalls12.html
Sub - Total surface area: 7.2 m²
Wall D
Surface STC Rating
(DB)
Area (m²) Transmission
Coefficient, ( 𝑻𝒄𝒏)
ST
Concrete Wall
(Cavity Wall – Interior) 4" Split Face Block 3.5" airspace 2.5" Fiberglass Insulation 4" C.M.U.
79 0.55 X 3 +
0.48 X 3 =
3.09
3.7074 X 𝟏𝟎−𝟒 1.1456 X 𝟏𝟎−𝟑
Door Panel 2 Pcs
Fire rated door
48 2 X 0.8 X 2.2
= 3.52 8.229 X 𝟏𝟎−𝟑 0.0289
Door Frame
Fire rated
48 2 X 0.05 X 2.7
+ 1.7 X 0.05 =
0.355
8.229 X 𝟏𝟎−𝟑 2.9215 X 𝟏𝟎−𝟑
Sub- Total of ST 0.032955 Reference: http://www.maconline.org/tech/materials/sstoc/sswalls12/sswalls12.html
Sub - Total surface area: 6.965 m²
Wall E
Surface STC Rating
(DB)
Area (m²) Transmission
Coefficient, ( 𝑻𝒄𝒏)
ST
Concrete Wall
(Cavity Wall – Interior) 4" Split Face Block 3.5" airspace 2.5" Fiberglass Insulation 4" C.M.U.
79 2.5 X 3 = 7.5 3.7074 X 𝟏𝟎−𝟒 2.7805 X
𝟏𝟎−𝟑
Sub- Total of ST 0.0027805 Reference: http://www.maconline.org/tech/materials/sstoc/sswalls12/sswalls12.html
Sub – Total surface area: 7.5 m²
Grand Total of Surface Area: 11.7 + 16.2 + 7.2 + 6.965 + 7.5 = 49.565 m²
Grand Total of ST: 0.15778
𝑻𝒂𝒗 = (𝑺𝟏 𝑿 𝑻𝒄𝟏+ 𝑺𝟐 𝑿 𝑻𝒄𝟐+ …… 𝑺𝒏 𝑻𝒄𝒏
𝑻𝒐𝒕𝒂𝒍 𝑺𝒖𝒓𝒇𝒂𝒄𝒆 𝑨𝒓𝒆𝒂)
𝑻𝒂𝒗 =
𝟎.𝟏𝟓𝟕𝟕𝟖
𝟒𝟗.𝟓𝟔𝟓
= 3.1834 X 𝟏𝟎−𝟑
SRI overall = 10 log 𝟏
𝟑.𝟏𝟖𝟑𝟒 𝑿 𝟏𝟎−𝟑
= 24.97 DB (25 DB) = not full filling requirement of 45 DB
3. Proposal
Hence, 45DB – 25DB = 20 DB
a. Glazing assembly for sound control
b. Panel Absorber
Pacific Sound Absorption Panels
Pacific Sound Absorption Panels consist of particle board sheet, one face of which is factory-
machined with a proprietary slot pattern. The panel is categorized as a Helmholtz absorber.
A range of factory or site applied finishes are available for the panels, including timber veneer,
fabrics, paint or lacquer.
Decorative slot patterns are possible which can be customized to clients’ requirements for special
architectural or corporate image effects.
Standard Height (mm) Standard Width (mm) Panel weight (kg/m2) Panel Thickness (mm) NRC Rating
1840 1200 18.9 35 0.55
Notes:
1. Other larger panel sizes up to 3660 x 1820mm may be possible provided appropriate handling, transport and storage
are allowed for.
APPLICATIONS
Sound Absorption Panels are used to control acoustics in spaces such as theatres, concert
chambers, lecture theatres, music studios, gymnasia, conference rooms, boardrooms, executive
offices, school halls, churches, computer rooms and industrial noise isolation rooms.
Panels are used for wall or ceiling applications.
BENEFITS
Range of surface finishes including timber veneer.
High impact resistance.
Customised decorative slot patterns available.
High wall STC.
No imported materials.
EARLY FIRE HAZARD DATA
Tests to AS1530.3 for uncoated Particle Board (Fletcher Wood Panels Ltd).
Ignitability 14
Spread of Flame 7
Heat Evolved 6
Smoke Developed 4
Special surface coatings are available for improving Early Fire Hazard indices if required.
CONDITIONS OF USE
Pacific Sound Absorption Panels are intended for conditions of dry internal use where there is
adequate ventilation consistent with the recommended environments for Superflake Particle
Board (Fletcher Wood Panels Ltd).
Panels should be stored flat with at least 3 full-width packers per sheet underneath.
Site applied paint coatings should be to the outer surface of the panel only. Light overspray is
permitted inside surface grooving.
Fabric claddings must be discussed with Pacific Doors prior to final specification.
If panels are cleaned then aqueous cleaning solutions should be applied to the outer panel
surfaces only, or non-aqueous cleaning products could be used.
TECHNICAL COMPLIANCE STATEMENT
Testing was carried out at Acoustic Research Centre (Auckland, New Zealand) To test Standard
ISO 354 (1985) and ASTM C423-849. Acoustic Research Centre was TELARC registered for
the test.
Testing was carried out at Acoustic Research Centre (Auckland, New Zealand) to test Standard
ISO 140/III (1978) and ASTM E413-87. Acoustic Research Centre was TELARC registered for
the test. Transmission loss of an equivalent wall with the Pacific Sound Absorption Panel
replaced by standard Gib Board® 9.5mm was STC = 36 (“Gib® Sound Control Systems”, 1992,
Winstone Wallboards Ltd).
c. STC 42 – 50
d. doubling the walls mass
e. Acoustic Fire Rated Door
Frame materials available:
EGZ - 1.6mm
Cold rolled galvanized - 1.6mm
Stainless Steel - 1.5mm
Fasteners:
Jamb fixing at 600mm centres minimum
Expansion anchors eg. M10 countersunk 'Ramset' Dynabolts
M12 countersunk masonry screwbolts
Head Fixing (minimum):
Single door - none required
Paired door - single central fastener required
Wedging Gap:
0-10mm
Reference: http://www.pacificdoors.co.nz/acoustic/acoustic-doors
Product Details AD300 Acoustic Fire Rated Door
The AD300 is a tested acoustic door set designed to reduce sound transmission within buildings.
The AD300 is a hinged flush panel door that is suitable for interior use. It is available as a single
door or as a pair of doors. The AD300 can also be supplied as a Hospital door with features
suited to that application.
The thickness of the AD300 door leaf is 47mm with an approximate leaf weight of 35kg/m2
Wall Type Acoustic Rating Door Application Max Leaf
Height (mm)
Max Leaf
Width (mm)
Steel Stud Wall
Timber Stud Wall
Masonry Wall
STC/Rw 40
Single 2700 1200
Pair 2700 1200
SEALS
The perimeter frame seals are self-adhesive seals mounted in the frame rebate, so are hidden when the door is
closed.
The bottom seal (Type L) is an automatic door seal that lifts clear of the floor when the door is opened. The seal is
fully mortised in a groove in the bottom edge of the door.
The bottom seal must close onto a smooth, flat and level surface in order to seal as intended.
HARDWARE
The AD300 requires suitable latching in order for the frame seals to fully seal the gap between door leaf and frame.
Practically any standard door hardware can be used on the AD300, however the proposed hardware must be advised
to Pacific Door Systems Ltd to assess the suitability, before manufacture.
Product Options LEAF FACINGS
The facings listed below are available for the AD300 door set
MDF
Timber Veneer
HPL decorative laminate (e.g. Formica)
Sheet Vinyl
Notes:
1. Of the above facings only those marked * may extend around the door edge.
2. Other facings may be available, please contact Pacific Doors to discuss further options.
LEAF EDGES
Paint quality doors have unclashed edges.
Timber veneer faced doors are clashed on the vertical edges with solid timber.
Doors faced with decorative laminate or vinyl (e.g. Hospital doors) are capped on the vertical edges with an
aluminium extrusion capping with natural anodised finish.
FRAME TYPES & PROFILES
Timber Frame
The timber frame profiles listed below are available for the AD300 door set
Steel Frame
The steel frame profiles listed below are available for the AD300 door set
Steel frames require packing of the frame during installation with fibrous insulation material (e.g. fibreglass, mineral
wool or polyester batts).
For more in depth information on frame profiles and sizes, please see our Installation Instructions.
MEETING STILES
The meeting stiles listed below are applicable to pair door sets only.
WALL TYPES
Door sets must be installed carefully with particular attention to the sealing of gaps, including around the frame to wall
junction.
Complete door sets are tested to ISO 140-3 in a purpose-built facility that meets the requirements
of ISO 140-1.
The AD300 can be supplied with a vision panel of maximum height 1000mm.
Glazing Type Maximum Glazed Area Max Height (mm) Max Width (mm) Glazing Bead
STC/Rw Rating Timber Aluminum
Soundstop 0.16m2 1000 860 √ √ 40
Soundstop 0.45m2 1000 860 √ √ 38
Notes:
1. Please note that the height and width of the vision panel must still fall within the maximum glazed area.
2. Maximum glazed area is measured per door leaf.
CIRCULAR VISION PANELS
Size allowance Standard Cross Section
STANDARD VISION PANEL CROSS SECTIONS
Aluminium Bead
c. External Noise
1. Position on Plan, Space Function and Issue
2. Solution – Passive Design
6. Reference
Journal/ Articles
J. S. Lamancusa, 2000, Noise Control, Penn State
Article retrieved from http://www.me.psu.edu/lamancusa/me458/9_trans.pdf
Online Research
Anderson Net Zero Energy Classroom, 2015, Autodesk, retrieved from
http://sustainabilityworkshop.autodesk.com/project-gallery/anderson-anderson-net-zero-energy-
classroom
http://www.pacificdoors.co.nz/acoustic/acoustic-doors/ad300
http://www.maconline.org/tech/materials/sstoc/sswalls12/sswalls12.html