buildings with double brick wall onstructions: impact of thermal bridges on the energy demand

Embed Size (px)

Citation preview

  • 7/27/2019 buildings with double brick wall onstructions: impact of thermal bridges on the energy demand

    1/7

    The impact of thermal bridges on the energy demand of buildings with double

    brick wall constructions

    T.G. Theodosiou a,*, A.M. Papadopoulos b,1

    a Department of Engineering and Management of Energy Resources, University of Western Macedonia, GR-50100 Kozani, Greeceb Laboratory of Heat Transfer and Environmental Engineering, Department of Mechanical Engineering, Aristotle University Thessaloniki, GR-54124 Thessaloniki, Greece

    1. Introduction

    The European Directive 2002/91/EC on the Energy Performance

    of Buildings (EPBD) [1] is probably the most important single

    action towards the improvement of energy efficiency in the

    building sector throughout Europe since the 1970s when, in the

    aftermath of the energy crisis, most national building regulations

    introduced mandatory thermal insulation requirements. The

    implementation of the Directive 2002/91/EC in the form of

    national laws by each member state, gradually leads to the need

    to adopt advanced standards, techniques and technologies while

    designing and constructing new buildings, but also in applying

    energy renovation measures in existing ones, in order to comply

    with the updated energy efficiency requirements. The features of

    the urban built environment in many European countries impose

    limitations, or at least restrictions, on implementing other

    advanced renovation measures like the use of passive or active

    solar systems, passive cooling techniques, etc. This is mostly due to

    factors like the overshadowing of buildings in winter, the

    unfavourable orientation and the architectural typology of

    buildings facades [2]. Still, even in cases where such measures

    can be implemented, it is still rather impossible to achieve a

    satisfactory degree of energy efficiency, as long as the buildings

    present high thermal losses trough their external envelope. In that

    sense, the less glamorous but still most effective measures, such as

    the buildings envelope thermal insulation and the heating

    systems upgrading remain prerequisites for a realistic approach

    towards the improvement of the buildings energy efficiency.

    Contemporary national regulations throughout the world

    specify requirements for the insulation of the various buildings

    elements, according to specific thermophysical properties and the

    calculation procedures adopted, based on various standards,

    varying from simple one-dimensional steady state considerations

    to more sophisticated two-dimensional dynamic ones, which

    inevitably lead to executing building simulation procedures. Still,

    the problem of thermal bridges, appearing for example at the

    junction between two separately insulated elements, or between a

    vertical and a horizontal element, is not always dealt with

    properly. This leads to underestimated thermal losses during the

    design process, the insulation study or the various calculation

    Energy and Buildings 40 (2008) 20832089

    A R T I C L E I N F O

    Article history:

    Received 11 April 2007

    Received in revised form 7 April 2008

    Accepted 2 June 2008

    Keywords:

    Thermal bridges

    Insulation

    Double brick walls

    Thermal facade

    A B S T R A C T

    The implementation of the European Directive on the Energy Performance of Buildings (EPBD) is a

    milestone towards the improvement of energy efficiency in the building sector. However, even in cases

    where impressive measures can be implemented in the densely built urban environment, the less

    glamorous measure of buildings envelope thermal insulation remains a prerequisite towards the

    improvement of the buildings energy efficiency. Despite the insulation requirements specified by

    national regulations, thermal bridges in the buildings envelope remain a weak spot in the constructions.

    Moreover, in many countries construction practices tend to implement only partially the insulation

    measures foreseen by regulations. As a result, thermal losses are in practice greater than those predicted

    during the design stage. This paper presents a study on representative wall thermal insulation

    configurations used in Greek buildings, in order to investigate the impact of the thermal bridges on the

    energy consumption. The double wall construction, used widely in Greece and not only there, is rather

    susceptible to the occurrence of thermal bridges, in contrast to a typical thermal insulating facade, like

    the one applied in Central Europe. The analysis of the thermal bridges impact will in that sense also

    highlight the potential for energy renovation measures in older buildings.

    2008 Elsevier B.V. All rights reserved.

    * Corresponding author. Tel.: +30 2461 056695; fax: +30 2461 056601.

    E-mail addresses: [email protected] (T.G. Theodosiou), [email protected]

    (A.M. Papadopoulos).1 Tel.: +30 2310 996015; fax: +30 2310 996012.

    Contents lists available at ScienceDirect

    Energy and Buildings

    j o u r n a l h o m e p a g e : w w w . e l s e v i e r . c o m / l o c a t e / e n b u i l d

    0378-7788/$ see front matter 2008 Elsevier B.V. All rights reserved.

    doi:10.1016/j.enbuild.2008.06.006

    mailto:[email protected]:[email protected]://www.sciencedirect.com/science/journal/03787788http://dx.doi.org/10.1016/j.enbuild.2008.06.006http://dx.doi.org/10.1016/j.enbuild.2008.06.006http://www.sciencedirect.com/science/journal/03787788mailto:[email protected]:[email protected]
  • 7/27/2019 buildings with double brick wall onstructions: impact of thermal bridges on the energy demand

    2/7

    methods in general, and, consequently, to higher (in comparison to

    the estimates) energy requirements in practice. Moreover, in many

    countries actual construction practices tend to only partially

    implement the insulation foreseen by regulations, because of

    construction difficulties, the conflicting stability issues of the

    various building elements, the lack of properly trained/qualified

    personnel and, finally, because of minimal or inefficient controls on

    behalf of the authorities. The aforementioneddiscrepancy between

    estimated and actual thermal losses appears despite the fact that

    both analytical and simulative methods enable the designing

    engineer to achieve a very good approximation of the thermal

    losses [3,4].

    Nowadays, more than ever in thepast,the need forconvergence

    between the predicted and the actual buildings energy consump-

    tion has proven to be an essential factor in the design and

    construction processes. The energy performance certificate intro-

    duced by theEPBD,which will be mandatory fornew constructions

    and for existing ones in order to be sold or rented, is going to affect

    the building sector in a variety of ways. The certification

    introduced, be it asset or rating-based, raises, from the earliest

    design stages already, the necessity for accurate prediction of

    thermal losses through the buildings envelope, if the actual

    consumption is expected to reasonably converge with thepredicted one. Unfortunately, many European countries still base

    their thermal insulation requirements and legislations on simpli-

    fied calculation methods that neglect or reduce the impact of

    thermal bridges. This, in many cases, may lead to significant

    deviation between predicted and actual thermal losses through the

    buildings envelope, depending on the thermal insulation solution

    opted for. Consequently, the design process is likely to provide an

    underestimation of the actual energy demand compared to the

    values to be later on identified and reported in an energy audit,

    carried out in the frame of EPBD.

    The study discussed in the present paper looks into the typical,

    representative buildings thermal insulation configurations used in

    wall structures in Greece. In particular, this study examines how

    and to what extent the inclusion of the thermal bridges effects, as

    they occur in vertical building elements, affects the calculations

    during the design process and also the actual energy efficiency of a

    building, as this can be measured during an energy audit. The main

    reason for focusing on vertical building elements is that the double

    wall construction, which is used in Greece but also in other

    Mediterranean countries, is rather susceptible to allowing thermal

    bridges, in contrast to a typical thermal insulating facade, like the

    one applied in Central and Western Europe. At the same time, the

    analysis of the thermal bridges impact aims to shed light on the

    potential for energy renovation measures to be applied in older

    buildings. Last but not least, the efficiency of each thermal

    insulation configuration is examined with respect both to its

    economic feasibility and to its environmental impact.

    2. Methodology

    In order to conduct this study, a typical three-storey apartment

    building with an open ground-floor space (pilotis), normally used

    as a parking lot, and a flat roof was chosen as a representative

    urban residential building type. Each storey consists of two

    identical apartments with a total area of 200 m2 (Fig. 1). All

    apartments are equipped with autonomous heating and cooling

    systems. The building is located in the city of Thessaloniki, in

    northern Greece. The main climatic data for this area, which are

    summarised in Table 1, are similar to those prevailing in Southern

    France, Northern Italy and the Mediterranean coastal area of Spain.

    During the heating period, each apartments indoor tempera-

    ture is thermostatically kept to 21 8C, with a night set back

    temperature of 19 8C (00:0008:00). During the cooling period

    each apartments indoor temperature is thermostatically kept to

    24 8C at day-time (08:0024:00), whilst natural ventilation is

    opted for at night, or when the ambient temperature drops below

    24 8C. The latter policy seems to be the most reasonable and

    realistic one for the case of partially air-conditioned buildings [5].

    All simulative calculations were carried out using the TRNSYS 16

    simulation software, which has an established reliability for

    calculating two-dimensional heat fluxes through building ele-

    Fig. 1. Plan view of the building.

    T.G. Theodosiou, A.M. Papadopoulos / Energy and Buildings 40 (2008) 208320892084

  • 7/27/2019 buildings with double brick wall onstructions: impact of thermal bridges on the energy demand

    3/7

    ments and also of HVAC systems [6,7]. These calculations are in

    accordance with the relevant standards concerning the thermal

    bridge heat flows [810]. This approach can therefore highlight the

    discrepancy between the typical analysis method and the 2Danalysis for thermal bridging. The complexity of various envelope

    details further exacerbates the inaccuracy of using simple methods

    and requires 3D analysis to truly account for all the heat flow paths

    [11,12].

    Four different scenarios are examined (Fig. 2). The first three

    scenarios represent typical wall constructions in Greek buildings.

    The forth scenario (D) represents, as far as the Greek context is

    concerned, a novel approach, applied after 2004, which may well

    constitute the main renovation strategy in order to apply

    additional thermal insulation to existing buildings envelopes. In

    detail, scenario A represents a large proportion of the Greek

    building stock constructed during the 1980s, after the introduction

    of the Thermal Insulation Regulation (TIR) in 1979. Although

    thermal insulation of all external envelope elements is, accordingto TIR, mandatory, theapplicationof thermal insulation during this

    period has proven to be problematic, mainly because of the lacking

    construction experience and the absence of adequate and

    appropriate insulation materials in the Greek market. The outlined

    situation led to only a partial application of insulation, namely in

    the cavity between the two brick walls, leaving, as a rule, the load-

    bearing structure, consisting of armed concrete elements, unpro-

    tected. Whilst the insulation materials dominating the market inthe 1980s were expanded polystyrene and, initially, glass wool, in

    the mid-1990s, when armed concrete elements were insulated

    more systematically, extruded polystyrene became very popular

    and glass wool almost disappeared from the market, and was

    substituted by expanded polystyrene. Since 2003, when the

    production of stone wool began in Greece, this inorganic material

    is increasingly becoming popular. The aforementioned develop-

    ments are reflected in the following figures for the year 2006,

    whereby extruded polystyrene accounted for 35%, expanded

    polystyrene for 45% and stone wool for 15% of the market, with

    the last one rising and largely replacing expanded polystyrene

    mainly in the double brick masonry construction. The remaining

    5% of themarket is covered by other materialsand insulating bricks

    [13]. In addition to these elements, double-glazed windows andthermal insulation of the flat roof and pilotis have been found to be

    applied in most cases during the construction process or after-

    wards as a refurbishment action. Unfortunately, even nowadays,

    buildings of similar, poor quality of thermal protection are still

    Table 1

    Climatic data for Thessaloniki

    Month Mean daily ambient temperature (8C) Mean relative humidity (%) Total horizontal radiation (kWh/m2) Heating degree days (18 8C)

    Minimum Mean Maximum

    January 2 5 10 75 45 367

    February 1 7 13 72 54 319

    March 4 10 16 72 87 263

    April 8 14 20 68 125 143May 14 20 25 64 159 35

    June 20 24 28 57 172 0

    July 22 27 30 53 175 0

    August 22 26 30 55 159 0

    September 17 22 26 62 120 0

    October 9 16 22 69 78 76

    November 4 11 17 77 48 208

    December 1 7 14 77 37 330

    Total 1259 1741

    Fig. 2. Insulation configuration among the examined scenarios.

    T.G. Theodosiou, A.M. Papadopoulos / Energy and Buildings 40 (2008) 20832089 2085

  • 7/27/2019 buildings with double brick wall onstructions: impact of thermal bridges on the energy demand

    4/7

    constructed. In many cases, parts of the load-bearing structure are

    still left un-insulated and so result in excessive thermal losses

    during the winter [14]. As far as the applied thicknesses are

    concerned, and despite the fact that in the coldest climatic zone of

    Greece a minimum of 5 cm of insulation thickness is required

    (scenario C), in practice thinner insulation layers (3 cm or thinner)

    are used on concrete elements during the construction, mostly

    because of stability reasons of masonry wall and in order to

    simplify the construction demands. This practice is represented by

    scenario B, whilst external envelope insulation, by means of the

    thermal insulating facade is represented by scenario D. This

    insulation approach has the advantageof significantlyreducing theeffect of thermal bridges andis applicable to both new andexisting

    buildings when energy renovation works take place.

    With the exception of scenario A, where thermal insulation is

    obviously insufficient,simulation of the other cases was performed

    twice, considering and not considering the effects of thermal

    bridges. This was done, because the thermal insulation regulation,

    still valid in Greece, does not address the thermal bridges effect.

    Consequently, it is of interest to estimate the approximation error

    resulting from this oversimplification, as well as the extent to

    which the existing methodology leads to underestimating the

    actual thermal losses through the buildings envelope. The mean U-

    value for a 1-m-long wall construction in every scenario for both

    methodologies examined is shown in Table 2. It is obvious that

    ignoring the thermal bridges effect has a great impact on most ofthe examined wall constructions, with the exception of scenario D,

    whereas in the latter case D, where the facade is not interrupted by

    an overhang, the U-value is the same for both methodologies.

    For all the examined scenarios double-glazed insulated

    windows were assumed to be the case of all openings of the

    buildings envelope. This assumption is in accordance with most

    Greek buildings reality, since even older buildings have been

    retrofitted with this type of windows. In addition, insulation of

    both the flat roof and the pilotis is regarded as identical in every

    scenario, according to the requirements of the prevailing regula-

    tion [15].

    3. Results

    Theresults discussedfocus on both theheating andcooling load

    requirements and on the corresponding power demand for each

    storey of the building, as well as for the entire building.

    3.1. Heating load

    The specific heating load requirements for each examined

    scenario are shown in Fig. 3. It becomes obvious that in every case

    the intermediate floor apartments present the smaller heating

    requirements. The first and the last floor of the building, whichhave more exposed surfaces to the ambience (floor of the first

    storey to the pilotis and the last floor to the flat roof) suffer from

    higher thermal losses and consequently feature a higher heating

    consumption than the intermediate ones. Moreover, the first

    storey is in a more disadvantageous position, since, on the one

    hand, it does notreceive solar irradiation and, on theotherhand,its

    thermal transmittance is higher than that of the last storey,

    because of the more demanding U-value requirements for the flat

    roof foreseen by the regulations. Due to the thermostatic control of

    the apartments internal air temperature, there are no significant

    vertical heat fluxes among them, despite the lack of horizontal

    insulation in the intermediate floors.

    The absence of thermal protection on the load-bearing

    elements on scenario A, results in high heating requirements(153 W/m2 and 131 W/m2 for the cases of including or neglecting

    thermal bridge calculations, respectively) especially in the lower

    storey where the insulation is restricted to the masonry walls and

    is obviously inadequate, even for the relatively mild Greek climate.

    The more effective approach of the thermal protection of the entire

    envelope (scenarioB) even when therequirements of thethermal

    insulation regulations in terms of thickness are not fully adopted

    is obviously an important step towards reducing heating energy

    requirements. This is true even in the case where the thermal

    bridge effect is included in the calculations. Still, this reduced/

    restricted insulation (scenario B), which is the case for the

    Table 2

    Average U-value for a 1-m-long external wall construction for both the examined methodologies

    Scenario Average U-value for a 1-m-long wall construction (W/m2 K)

    Excluding thermal

    bridge effect

    Including thermal bridge effect

    (in the place of overhangs)

    Including thermal bridge effect

    (without obstruction by overhangs)

    A 0.64 3.64 3.91

    B 0.56 3.56 3.83

    C 0.49 3.49 3.77D 0.52 1.07 0.52

    Fig. 3. Specific annual heating load requirements for each examined scenario.

    T.G. Theodosiou, A.M. Papadopoulos / Energy and Buildings 40 (2008) 208320892086

  • 7/27/2019 buildings with double brick wall onstructions: impact of thermal bridges on the energy demand

    5/7

    majority of the existing buildings, leads to an increase of actual

    heating consumption by almost 15% compared to a full adoption of

    the insulation requirements, as represented by scenario C

    (109 kWh/m2 year instead of 92 kWh/m2 year when including

    thermal bridge effects and 87 kWh/m2 year instead of 71 kWh/

    m2 year when ignoring thermal bridge effects). The results of the

    partially adopted thermal insulation case, combined with the fact

    that thermal bridges are not included in the insulation calculation

    procedure, clearly indicate that the actual thermal losses are 35%

    higher more than the estimated ones, according to the existing

    requirements (109 kWh/m2 year compared to 71 kWh/m2 year in

    scenarios B and C, respectively). Considering the fact that, even

    nowadays, this deviation applies to the majority of the newly

    constructed buildings in Greece, it becomes obvious that currently

    applied thermal insulation measures are rather inadequate and fail

    to contribute, to the expected extent, to energy conservation in

    buildings. When it comes to the reduction of thermal losses,

    external insulation as represented by scenario D is approximately

    identicalwith theone in the previouscase (scenarioC). Theslightly

    higher heating requirements in scenario D are due to the higher

    thermal transmittance of the masonry wall elements. According to

    a more accurate calculation scheme, which includes the 2D

    thermal bridge effect, this configuration proves to be the mostefficient one, as external insulation enables the reduction of

    thermal bridges located at the junction between different

    structural elements. Given that the shape of Greek buildings leads

    to a large number of such junctions, due to the presence of

    balconies and overhangs, this configuration can be efficiently

    adopted in such constructionpractices. This last remarkshowsthat

    the calculation methods currently used in Greece lead to

    misleading results, since a highly effective insulation configura-

    tion, as this of external insulation, is considered to be less efficient

    than cavity insulation.

    The deviation between the two calculation methods highly

    depends on the buildings insulation efficiency, as it is shown in

    Fig. 4. Thermallybetter protectedbuildings show a wider deviation

    between the two approaches, since thermal bridges losses accountfor a larger proportion of the total conductive thermal losses. In

    that sense, the existing calculation methodology becomes less

    accurate,the betterinsulateda building is. In thecase of scenario C,

    the underestimation of the heating requirements is significant,

    reaching approximately 30%, whilst in the case of the poorly

    insulated building of scenario A the error is not exceeding 16%

    approximately.

    It is worth mentioning that these types of calculation errors are

    not limited to simple calculation methods but can also appear in

    advanced calculation methods, like FEM or nodal based energy

    simulations, when thermal bridge effects are not included in the

    calculation model. In the process of an energy audit, this would

    mean that more efficient buildings will prove to have bigger

    deviation between estimated and actual heating consumption

    values. Obviously, the current regulations and their effects greatly

    contradict the target of designing and constructing more energy

    efficient buildings, since the more efficient the building is, the

    more misleading and erroneous the results become.

    Amongst all the insulation configurations examined, the case of

    external insulation (scenario D) results in the minimum deviation

    (5.5%), dueto the limited length of thermal bridges. In this case, the

    decision whether to include or not the thermal bridge losses in the

    calculation method becomes less important. With the exception of

    the external insulation configuration, whereby the majority of

    thermal bridges are located in the pilotis ceiling, the calculation

    error is more evident in the case of the intermediate storey, in

    which thermal losses occur only through the external envelope.

    Apparently, in the case of multi-storey buildings, or of buildings

    with a high ratio of vertical to horizontal external surfaces in

    general, the deviation shown in Fig. 4 is expected to be of greater

    importance.

    The maximum heating power the heating system has to provide

    is another important factor affected by the insulation configuration.In partially insulated buildings, the need for maintaining the air

    temperature at 21 8C, especiallyin the early morning orlate at night,

    results in an increasedrating of the heating system, whencompared

    toan adequately insulated building(this canbe seen in Fig.5).Inthe

    casewhere thermal bridges are ignored, the requiredheatingpower

    is similaramongall theadequatelyinsulatedbuilding scenarios. This

    holdsnot true in the case of themoreaccurate approach,i.e. theone

    including the calculation of thermal bridge effects, where external

    insulation configuration leads to a decrease in required heating

    power by up to 21% compared to the most common type of

    insulation configuration presented by scenario B (26.5 kW in

    scenario D compared to 33.4 kW in scenario B).

    3.2. Cooling load

    In the case of cooling load requirements differences among the

    examined scenarios appear to be less significant (see Fig. 6). The

    main reason being that during the cooling season heat flows,

    caused by conduction through the building envelope, contribute to

    a lesserextent to thebuildings energy balance andhave, therefore,

    a smaller effect on the cooling load demands.

    In almost every case it is the buildings last storey which

    presents the higher energy demands, because the flat roof accepts

    high values of solar irradiation during summer. Despite the small

    differences, external insulation still provides an efficient solution

    Fig. 4. Deviation of calculated heating load demand with and without the inclusion

    of thermal bridge effects. Fig. 5. Maximum heating power requirement during the heating season.

    T.G. Theodosiou, A.M. Papadopoulos / Energy and Buildings 40 (2008) 20832089 2087

  • 7/27/2019 buildings with double brick wall onstructions: impact of thermal bridges on the energy demand

    6/7

    in terms of energy conservation, because of the decreased heat

    flows through the opaque elements of the buildings envelope. Onthewhole, considering the seasonal cooling demand, it is of limited

    importance whether to include or not the thermal bridge effect in

    the calculation method.

    In contrast to the case of the annual cooling demand, the

    thermal insulation effect on the required cooling power of the

    cooling system is more evident (Fig. 7). A comparison of scenarios

    A and D indicates that the difference varies between 21% (15.5

    19.6 kW) and 16% (15.218.2 kW), depending on whether the

    thermal bridge effects are included or not.

    4. Energy cost and carbon dioxide emissions

    The primary energy consumption for each examined scenario

    was calculated for the cases of two different heating systems, anoil-fired and a gas-fired boiler distributing the heat to hydronic

    radiators. The former is the traditional heating system installed in

    the majority of current building stock and the latter is a rather new

    option introduced in the late 1990s in many Greek cities, with a

    rapid retrofitting takingplace since 2003. Thenominal efficiency of

    the boiler is 85% and 90% for each fuel type, respectively. When it

    comes to cooling, an air to air heat pump, with an average seasonal

    coefficient of performance (COP) equal to 2.7, is typical for Greek

    climatic conditions. On the basis of these assumptions, the annual

    consumption for each type of fuel is presented in Table 3. For the

    calculation of the annual heating and cooling costs, data for the

    year 2006 were considered with respect to fuel prices and the

    national energy mixture as presented in Table 4 [16]. The results

    are presented in Table 5. All values reflect energy consumption

    resulting from thermal losses calculations including thermal

    bridge effects, since this was proven to be a more accurateapproach.

    The total annual carbon dioxide emissions for the apartments

    heating and cooling are presented in Fig. 8. The most representa-

    tive case among the current building stock-fired of scenario B is

    compared to an oil-fired boiler, which is the typical heating

    equipment over the last decades and is therefore considered to be

    the reference case.

    In the cases of a buildings construction or renovation, the

    combination of external insulation and a state of the art gas-fired

    boiler would result in an almost 50% annual running cost

    reduction, compared to the most common combination of cavity

    insulation with oil-fired boiler (22294508s, respectively). This is

    mainly due to the heating consumption reduction, since the

    cooling demands are not significantly affected by the thermalinsulation configuration. The environmental impact of this

    optimum combination is also significant since an approximately

    Fig. 6. Specific annual cooling load requirements for each examined scenario.

    Fig. 7. Maximum cooling power demand during the cooling season for the entire

    building and for each storey.

    Table 3

    Annual consumption for each type of fuel

    Fuel type Annual consumption for each scenario

    A B C D

    Heating

    Fuel oil (kg) 9130 6513 5514 4515

    Natural gas (m3) 7432 5302 4489 3676

    Cooling

    Electricity (kWh) 7362 7307 7435 6684

    Table 5

    Total annual running costs for heating and cooling

    Fuel type Annual running cost for each scenario (s/

    year)

    A B C D

    Heating

    Fuel oil 5478 3908 3309 2709

    Natural gas 3398 2424 2052 1680

    Cooling

    Electricity 604 600 610 549

    Total

    Fuel-fired boiler and heat pump 6083 4508 3919 3258

    Gas-fired boiler and heat pump 4003 3024 2663 2229

    The scenarios presented here were calculated by taking into account the thermal

    bridge effects.

    Table 4

    Fuel and electricity tariffs and emission factors

    Energy source Tariffs Emission factor (kg/kWh)

    Natural gas 0.0456s/kWh 0.181

    Fuel oil 0.600s/lt 0.247

    Electricity 0.08211s/kWh 0.368

    T.G. Theodosiou, A.M. Papadopoulos / Energy and Buildings 40 (2008) 208320892088

  • 7/27/2019 buildings with double brick wall onstructions: impact of thermal bridges on the energy demand

    7/7

    27% reduction in carbon dioxide emissions can be achieved on an

    annual basis (3.124.29 t/year).

    5. Conclusions

    The study of representative wall insulation configurations inGreek buildings, applying both the currently valid calculation

    methodology and the more accurate approach which takes the

    thermal bridge effect into consideration, shows that the existing

    legislative frame is inadequate, leading to a significant under-

    estimation of actual energy consumption, especially in the case of

    cavity insulation.

    Considering the fact that the majority of the buildings

    constructed in the last twenty years are partially insulated and

    that thermal bridges are not considered by the calculation

    procedure, actual thermal losses in the cases of such buildings

    are by up to 35% higher than the initially estimated ones. The

    double brick wall construction used widely in Greece is

    particularly susceptible to allowing thermal bridges. Even when

    the actual construction fully implements the insulation study,heating requirements are in reality by 30% higher than the ones

    calculated by the current methodology which does not take

    thermal bridge effects into account. Interestingly enough, the

    underestimation of thermal losses is more misleading in the cases

    of fully insulated buildings than in the cases of partially insulated

    ones. It was also shown, that the current legislation disfavours the

    more effective configuration of external insulation, when com-

    pared to the cavity insulation, despite the fact that the former can

    minimise thermal losses in thethermal bridges andis also themost

    appealing solution when it comes to renovating existing buildings.

    Thus, there is an obvious contradiction between the target of

    designing more energy efficient buildings and the current

    legislative framework, which needs to be addressed and redeve-

    loped and which was still debated in April 2008.

    Apart from the improved heating and cooling demands of

    buildings, there are two further benefits to be considered, namely

    the not negligible environmental impact and the reduction of the

    buildings running costs. Such aspects should not be overlooked

    when revising the existing building codes.

    References

    [1] European Commission, Directive 2002/91/EC of the European Parliament and oftheCouncil of 16th December 2002 on theenergyperformanceof buildings, OJEC,L1/65, 04/01/2003.

    [2] T. Theodosiou, N. Chrisomallidou, Shading and solar availability in the urbanEnvironment, in: Proceedings of PLEA2005The 22nd Conference on Passive andLow Energy Architecture, Beirut, Lebanon, November 1316, 2005.

    [3] A.B. Larbi, Statistical modelling of heat transfer for thermal bridges of buildings,Energy and Buildings 37 (2005) 945951.

    [4] F. Deque, F. Ollivier, J.J. Roux, Effect of 2D modelling of thermal bridges on theenergy performance of buildings: numerical application on the Matisse apart-ment, Energy and Buildings 33 (2001) 583587.

    [5] V. Geros, M. Santamouris, S. Karatasou, A. Tsangrassoulis, N. Papanikolaou, On the

    cooling potential of night ventilation techniques in the urban environment,Energy and Buildings 37 (2005) 243257.

    [6] J. Neymark, R. Judkoff, G. Knabe, H.-T. Le, M. Durig, A. Glass, G. Zweifel, Applyingthe building energysimulation test(BESTEST) diagnosticmethod to verificationofspace conditioning equipment models used in whole-building energy simulationprograms, Energy and Buildings 34 (2002) p.917931.

    [7] TRNSYS, A Transient System Simulation Program, Solar Energy Laboratory,University of Wisconsin, Madison, WI, 2006.

    [8] EN ISO 10211-1, Thermal Bridges in Building Construction: Heat Flows andSurface Temperatures. Part 1. General Calculation Methods, 1995.

    [9] EN ISO 10211-2, Thermal Bridges in Building Construction: Heat Flows andSurface Temperatures. Part 2. Linear Thermal Bridges, 2001.

    [10] EN ISO 14683, Thermal Bridges in Building Construction: Linear Thermal Trans-mittance. Simplified Methods and Default Values, 2000.

    [11] J. Kosny, E. Kossecka, Multi-dimensional heat transfer through complex buildingenvelope assembliesin hourly energysimulation programs, Energyand Buildings34 (2002) 445454.

    [12] I. Doebber, M. Ellis, Thermal performance benefits of precast concrete panel andinsulated concrete form technologies for residential construction, ASHRAE Trans

    111 (2005) 340352.[13] SAPPEK, Development of innovative insulation elements based on stone wool,

    Project report, vol. 1, Lab. of Heat Transfer and Environmental Engineering,Aristotle University Thessaloniki, 2007 (in Greek).

    [14] S. Chadiarakou, M. Santamouris, A. Papadopoulos, The importance of insulationon the buildings thermal losses, in: Proceedings of the CLIMAMED Congress,Lyon, November 2021, 2006, (2006), pp. 325332.

    [15] A.M. Papadopoulos, T. Theodosiou, K. Karatzas, Feasibility of energy savingrenovation measures in urban buildings: the impact of energy prices andthe acceptable pay back time criterion, Energy and Buildings 34 (2002) 455466.

    [16] A.M. Papadopoulos, S. Oxizidis, G. Papandritsas, Energy, economic and environ-mental performance of heating systems used in Greek buildings, Energy andBuildings 40 (2008) 224230.

    Fig. 8. Annual carbon dioxide emissions and percentage CO2 reduction for each fuel

    type and for each insulation configuration scenario. Scenario B with oil-fired boiler

    is the reference case.

    T.G. Theodosiou, A.M. Papadopoulos / Energy and Buildings 40 (2008) 20832089 2089