Upload
mohammad-zehab
View
215
Download
0
Embed Size (px)
Citation preview
7/27/2019 buildings with double brick wall onstructions: impact of thermal bridges on the energy demand
1/7
The impact of thermal bridges on the energy demand of buildings with double
brick wall constructions
T.G. Theodosiou a,*, A.M. Papadopoulos b,1
a Department of Engineering and Management of Energy Resources, University of Western Macedonia, GR-50100 Kozani, Greeceb Laboratory of Heat Transfer and Environmental Engineering, Department of Mechanical Engineering, Aristotle University Thessaloniki, GR-54124 Thessaloniki, Greece
1. Introduction
The European Directive 2002/91/EC on the Energy Performance
of Buildings (EPBD) [1] is probably the most important single
action towards the improvement of energy efficiency in the
building sector throughout Europe since the 1970s when, in the
aftermath of the energy crisis, most national building regulations
introduced mandatory thermal insulation requirements. The
implementation of the Directive 2002/91/EC in the form of
national laws by each member state, gradually leads to the need
to adopt advanced standards, techniques and technologies while
designing and constructing new buildings, but also in applying
energy renovation measures in existing ones, in order to comply
with the updated energy efficiency requirements. The features of
the urban built environment in many European countries impose
limitations, or at least restrictions, on implementing other
advanced renovation measures like the use of passive or active
solar systems, passive cooling techniques, etc. This is mostly due to
factors like the overshadowing of buildings in winter, the
unfavourable orientation and the architectural typology of
buildings facades [2]. Still, even in cases where such measures
can be implemented, it is still rather impossible to achieve a
satisfactory degree of energy efficiency, as long as the buildings
present high thermal losses trough their external envelope. In that
sense, the less glamorous but still most effective measures, such as
the buildings envelope thermal insulation and the heating
systems upgrading remain prerequisites for a realistic approach
towards the improvement of the buildings energy efficiency.
Contemporary national regulations throughout the world
specify requirements for the insulation of the various buildings
elements, according to specific thermophysical properties and the
calculation procedures adopted, based on various standards,
varying from simple one-dimensional steady state considerations
to more sophisticated two-dimensional dynamic ones, which
inevitably lead to executing building simulation procedures. Still,
the problem of thermal bridges, appearing for example at the
junction between two separately insulated elements, or between a
vertical and a horizontal element, is not always dealt with
properly. This leads to underestimated thermal losses during the
design process, the insulation study or the various calculation
Energy and Buildings 40 (2008) 20832089
A R T I C L E I N F O
Article history:
Received 11 April 2007
Received in revised form 7 April 2008
Accepted 2 June 2008
Keywords:
Thermal bridges
Insulation
Double brick walls
Thermal facade
A B S T R A C T
The implementation of the European Directive on the Energy Performance of Buildings (EPBD) is a
milestone towards the improvement of energy efficiency in the building sector. However, even in cases
where impressive measures can be implemented in the densely built urban environment, the less
glamorous measure of buildings envelope thermal insulation remains a prerequisite towards the
improvement of the buildings energy efficiency. Despite the insulation requirements specified by
national regulations, thermal bridges in the buildings envelope remain a weak spot in the constructions.
Moreover, in many countries construction practices tend to implement only partially the insulation
measures foreseen by regulations. As a result, thermal losses are in practice greater than those predicted
during the design stage. This paper presents a study on representative wall thermal insulation
configurations used in Greek buildings, in order to investigate the impact of the thermal bridges on the
energy consumption. The double wall construction, used widely in Greece and not only there, is rather
susceptible to the occurrence of thermal bridges, in contrast to a typical thermal insulating facade, like
the one applied in Central Europe. The analysis of the thermal bridges impact will in that sense also
highlight the potential for energy renovation measures in older buildings.
2008 Elsevier B.V. All rights reserved.
* Corresponding author. Tel.: +30 2461 056695; fax: +30 2461 056601.
E-mail addresses: [email protected] (T.G. Theodosiou), [email protected]
(A.M. Papadopoulos).1 Tel.: +30 2310 996015; fax: +30 2310 996012.
Contents lists available at ScienceDirect
Energy and Buildings
j o u r n a l h o m e p a g e : w w w . e l s e v i e r . c o m / l o c a t e / e n b u i l d
0378-7788/$ see front matter 2008 Elsevier B.V. All rights reserved.
doi:10.1016/j.enbuild.2008.06.006
mailto:[email protected]:[email protected]://www.sciencedirect.com/science/journal/03787788http://dx.doi.org/10.1016/j.enbuild.2008.06.006http://dx.doi.org/10.1016/j.enbuild.2008.06.006http://www.sciencedirect.com/science/journal/03787788mailto:[email protected]:[email protected]7/27/2019 buildings with double brick wall onstructions: impact of thermal bridges on the energy demand
2/7
methods in general, and, consequently, to higher (in comparison to
the estimates) energy requirements in practice. Moreover, in many
countries actual construction practices tend to only partially
implement the insulation foreseen by regulations, because of
construction difficulties, the conflicting stability issues of the
various building elements, the lack of properly trained/qualified
personnel and, finally, because of minimal or inefficient controls on
behalf of the authorities. The aforementioneddiscrepancy between
estimated and actual thermal losses appears despite the fact that
both analytical and simulative methods enable the designing
engineer to achieve a very good approximation of the thermal
losses [3,4].
Nowadays, more than ever in thepast,the need forconvergence
between the predicted and the actual buildings energy consump-
tion has proven to be an essential factor in the design and
construction processes. The energy performance certificate intro-
duced by theEPBD,which will be mandatory fornew constructions
and for existing ones in order to be sold or rented, is going to affect
the building sector in a variety of ways. The certification
introduced, be it asset or rating-based, raises, from the earliest
design stages already, the necessity for accurate prediction of
thermal losses through the buildings envelope, if the actual
consumption is expected to reasonably converge with thepredicted one. Unfortunately, many European countries still base
their thermal insulation requirements and legislations on simpli-
fied calculation methods that neglect or reduce the impact of
thermal bridges. This, in many cases, may lead to significant
deviation between predicted and actual thermal losses through the
buildings envelope, depending on the thermal insulation solution
opted for. Consequently, the design process is likely to provide an
underestimation of the actual energy demand compared to the
values to be later on identified and reported in an energy audit,
carried out in the frame of EPBD.
The study discussed in the present paper looks into the typical,
representative buildings thermal insulation configurations used in
wall structures in Greece. In particular, this study examines how
and to what extent the inclusion of the thermal bridges effects, as
they occur in vertical building elements, affects the calculations
during the design process and also the actual energy efficiency of a
building, as this can be measured during an energy audit. The main
reason for focusing on vertical building elements is that the double
wall construction, which is used in Greece but also in other
Mediterranean countries, is rather susceptible to allowing thermal
bridges, in contrast to a typical thermal insulating facade, like the
one applied in Central and Western Europe. At the same time, the
analysis of the thermal bridges impact aims to shed light on the
potential for energy renovation measures to be applied in older
buildings. Last but not least, the efficiency of each thermal
insulation configuration is examined with respect both to its
economic feasibility and to its environmental impact.
2. Methodology
In order to conduct this study, a typical three-storey apartment
building with an open ground-floor space (pilotis), normally used
as a parking lot, and a flat roof was chosen as a representative
urban residential building type. Each storey consists of two
identical apartments with a total area of 200 m2 (Fig. 1). All
apartments are equipped with autonomous heating and cooling
systems. The building is located in the city of Thessaloniki, in
northern Greece. The main climatic data for this area, which are
summarised in Table 1, are similar to those prevailing in Southern
France, Northern Italy and the Mediterranean coastal area of Spain.
During the heating period, each apartments indoor tempera-
ture is thermostatically kept to 21 8C, with a night set back
temperature of 19 8C (00:0008:00). During the cooling period
each apartments indoor temperature is thermostatically kept to
24 8C at day-time (08:0024:00), whilst natural ventilation is
opted for at night, or when the ambient temperature drops below
24 8C. The latter policy seems to be the most reasonable and
realistic one for the case of partially air-conditioned buildings [5].
All simulative calculations were carried out using the TRNSYS 16
simulation software, which has an established reliability for
calculating two-dimensional heat fluxes through building ele-
Fig. 1. Plan view of the building.
T.G. Theodosiou, A.M. Papadopoulos / Energy and Buildings 40 (2008) 208320892084
7/27/2019 buildings with double brick wall onstructions: impact of thermal bridges on the energy demand
3/7
ments and also of HVAC systems [6,7]. These calculations are in
accordance with the relevant standards concerning the thermal
bridge heat flows [810]. This approach can therefore highlight the
discrepancy between the typical analysis method and the 2Danalysis for thermal bridging. The complexity of various envelope
details further exacerbates the inaccuracy of using simple methods
and requires 3D analysis to truly account for all the heat flow paths
[11,12].
Four different scenarios are examined (Fig. 2). The first three
scenarios represent typical wall constructions in Greek buildings.
The forth scenario (D) represents, as far as the Greek context is
concerned, a novel approach, applied after 2004, which may well
constitute the main renovation strategy in order to apply
additional thermal insulation to existing buildings envelopes. In
detail, scenario A represents a large proportion of the Greek
building stock constructed during the 1980s, after the introduction
of the Thermal Insulation Regulation (TIR) in 1979. Although
thermal insulation of all external envelope elements is, accordingto TIR, mandatory, theapplicationof thermal insulation during this
period has proven to be problematic, mainly because of the lacking
construction experience and the absence of adequate and
appropriate insulation materials in the Greek market. The outlined
situation led to only a partial application of insulation, namely in
the cavity between the two brick walls, leaving, as a rule, the load-
bearing structure, consisting of armed concrete elements, unpro-
tected. Whilst the insulation materials dominating the market inthe 1980s were expanded polystyrene and, initially, glass wool, in
the mid-1990s, when armed concrete elements were insulated
more systematically, extruded polystyrene became very popular
and glass wool almost disappeared from the market, and was
substituted by expanded polystyrene. Since 2003, when the
production of stone wool began in Greece, this inorganic material
is increasingly becoming popular. The aforementioned develop-
ments are reflected in the following figures for the year 2006,
whereby extruded polystyrene accounted for 35%, expanded
polystyrene for 45% and stone wool for 15% of the market, with
the last one rising and largely replacing expanded polystyrene
mainly in the double brick masonry construction. The remaining
5% of themarket is covered by other materialsand insulating bricks
[13]. In addition to these elements, double-glazed windows andthermal insulation of the flat roof and pilotis have been found to be
applied in most cases during the construction process or after-
wards as a refurbishment action. Unfortunately, even nowadays,
buildings of similar, poor quality of thermal protection are still
Table 1
Climatic data for Thessaloniki
Month Mean daily ambient temperature (8C) Mean relative humidity (%) Total horizontal radiation (kWh/m2) Heating degree days (18 8C)
Minimum Mean Maximum
January 2 5 10 75 45 367
February 1 7 13 72 54 319
March 4 10 16 72 87 263
April 8 14 20 68 125 143May 14 20 25 64 159 35
June 20 24 28 57 172 0
July 22 27 30 53 175 0
August 22 26 30 55 159 0
September 17 22 26 62 120 0
October 9 16 22 69 78 76
November 4 11 17 77 48 208
December 1 7 14 77 37 330
Total 1259 1741
Fig. 2. Insulation configuration among the examined scenarios.
T.G. Theodosiou, A.M. Papadopoulos / Energy and Buildings 40 (2008) 20832089 2085
7/27/2019 buildings with double brick wall onstructions: impact of thermal bridges on the energy demand
4/7
constructed. In many cases, parts of the load-bearing structure are
still left un-insulated and so result in excessive thermal losses
during the winter [14]. As far as the applied thicknesses are
concerned, and despite the fact that in the coldest climatic zone of
Greece a minimum of 5 cm of insulation thickness is required
(scenario C), in practice thinner insulation layers (3 cm or thinner)
are used on concrete elements during the construction, mostly
because of stability reasons of masonry wall and in order to
simplify the construction demands. This practice is represented by
scenario B, whilst external envelope insulation, by means of the
thermal insulating facade is represented by scenario D. This
insulation approach has the advantageof significantlyreducing theeffect of thermal bridges andis applicable to both new andexisting
buildings when energy renovation works take place.
With the exception of scenario A, where thermal insulation is
obviously insufficient,simulation of the other cases was performed
twice, considering and not considering the effects of thermal
bridges. This was done, because the thermal insulation regulation,
still valid in Greece, does not address the thermal bridges effect.
Consequently, it is of interest to estimate the approximation error
resulting from this oversimplification, as well as the extent to
which the existing methodology leads to underestimating the
actual thermal losses through the buildings envelope. The mean U-
value for a 1-m-long wall construction in every scenario for both
methodologies examined is shown in Table 2. It is obvious that
ignoring the thermal bridges effect has a great impact on most ofthe examined wall constructions, with the exception of scenario D,
whereas in the latter case D, where the facade is not interrupted by
an overhang, the U-value is the same for both methodologies.
For all the examined scenarios double-glazed insulated
windows were assumed to be the case of all openings of the
buildings envelope. This assumption is in accordance with most
Greek buildings reality, since even older buildings have been
retrofitted with this type of windows. In addition, insulation of
both the flat roof and the pilotis is regarded as identical in every
scenario, according to the requirements of the prevailing regula-
tion [15].
3. Results
Theresults discussedfocus on both theheating andcooling load
requirements and on the corresponding power demand for each
storey of the building, as well as for the entire building.
3.1. Heating load
The specific heating load requirements for each examined
scenario are shown in Fig. 3. It becomes obvious that in every case
the intermediate floor apartments present the smaller heating
requirements. The first and the last floor of the building, whichhave more exposed surfaces to the ambience (floor of the first
storey to the pilotis and the last floor to the flat roof) suffer from
higher thermal losses and consequently feature a higher heating
consumption than the intermediate ones. Moreover, the first
storey is in a more disadvantageous position, since, on the one
hand, it does notreceive solar irradiation and, on theotherhand,its
thermal transmittance is higher than that of the last storey,
because of the more demanding U-value requirements for the flat
roof foreseen by the regulations. Due to the thermostatic control of
the apartments internal air temperature, there are no significant
vertical heat fluxes among them, despite the lack of horizontal
insulation in the intermediate floors.
The absence of thermal protection on the load-bearing
elements on scenario A, results in high heating requirements(153 W/m2 and 131 W/m2 for the cases of including or neglecting
thermal bridge calculations, respectively) especially in the lower
storey where the insulation is restricted to the masonry walls and
is obviously inadequate, even for the relatively mild Greek climate.
The more effective approach of the thermal protection of the entire
envelope (scenarioB) even when therequirements of thethermal
insulation regulations in terms of thickness are not fully adopted
is obviously an important step towards reducing heating energy
requirements. This is true even in the case where the thermal
bridge effect is included in the calculations. Still, this reduced/
restricted insulation (scenario B), which is the case for the
Table 2
Average U-value for a 1-m-long external wall construction for both the examined methodologies
Scenario Average U-value for a 1-m-long wall construction (W/m2 K)
Excluding thermal
bridge effect
Including thermal bridge effect
(in the place of overhangs)
Including thermal bridge effect
(without obstruction by overhangs)
A 0.64 3.64 3.91
B 0.56 3.56 3.83
C 0.49 3.49 3.77D 0.52 1.07 0.52
Fig. 3. Specific annual heating load requirements for each examined scenario.
T.G. Theodosiou, A.M. Papadopoulos / Energy and Buildings 40 (2008) 208320892086
7/27/2019 buildings with double brick wall onstructions: impact of thermal bridges on the energy demand
5/7
majority of the existing buildings, leads to an increase of actual
heating consumption by almost 15% compared to a full adoption of
the insulation requirements, as represented by scenario C
(109 kWh/m2 year instead of 92 kWh/m2 year when including
thermal bridge effects and 87 kWh/m2 year instead of 71 kWh/
m2 year when ignoring thermal bridge effects). The results of the
partially adopted thermal insulation case, combined with the fact
that thermal bridges are not included in the insulation calculation
procedure, clearly indicate that the actual thermal losses are 35%
higher more than the estimated ones, according to the existing
requirements (109 kWh/m2 year compared to 71 kWh/m2 year in
scenarios B and C, respectively). Considering the fact that, even
nowadays, this deviation applies to the majority of the newly
constructed buildings in Greece, it becomes obvious that currently
applied thermal insulation measures are rather inadequate and fail
to contribute, to the expected extent, to energy conservation in
buildings. When it comes to the reduction of thermal losses,
external insulation as represented by scenario D is approximately
identicalwith theone in the previouscase (scenarioC). Theslightly
higher heating requirements in scenario D are due to the higher
thermal transmittance of the masonry wall elements. According to
a more accurate calculation scheme, which includes the 2D
thermal bridge effect, this configuration proves to be the mostefficient one, as external insulation enables the reduction of
thermal bridges located at the junction between different
structural elements. Given that the shape of Greek buildings leads
to a large number of such junctions, due to the presence of
balconies and overhangs, this configuration can be efficiently
adopted in such constructionpractices. This last remarkshowsthat
the calculation methods currently used in Greece lead to
misleading results, since a highly effective insulation configura-
tion, as this of external insulation, is considered to be less efficient
than cavity insulation.
The deviation between the two calculation methods highly
depends on the buildings insulation efficiency, as it is shown in
Fig. 4. Thermallybetter protectedbuildings show a wider deviation
between the two approaches, since thermal bridges losses accountfor a larger proportion of the total conductive thermal losses. In
that sense, the existing calculation methodology becomes less
accurate,the betterinsulateda building is. In thecase of scenario C,
the underestimation of the heating requirements is significant,
reaching approximately 30%, whilst in the case of the poorly
insulated building of scenario A the error is not exceeding 16%
approximately.
It is worth mentioning that these types of calculation errors are
not limited to simple calculation methods but can also appear in
advanced calculation methods, like FEM or nodal based energy
simulations, when thermal bridge effects are not included in the
calculation model. In the process of an energy audit, this would
mean that more efficient buildings will prove to have bigger
deviation between estimated and actual heating consumption
values. Obviously, the current regulations and their effects greatly
contradict the target of designing and constructing more energy
efficient buildings, since the more efficient the building is, the
more misleading and erroneous the results become.
Amongst all the insulation configurations examined, the case of
external insulation (scenario D) results in the minimum deviation
(5.5%), dueto the limited length of thermal bridges. In this case, the
decision whether to include or not the thermal bridge losses in the
calculation method becomes less important. With the exception of
the external insulation configuration, whereby the majority of
thermal bridges are located in the pilotis ceiling, the calculation
error is more evident in the case of the intermediate storey, in
which thermal losses occur only through the external envelope.
Apparently, in the case of multi-storey buildings, or of buildings
with a high ratio of vertical to horizontal external surfaces in
general, the deviation shown in Fig. 4 is expected to be of greater
importance.
The maximum heating power the heating system has to provide
is another important factor affected by the insulation configuration.In partially insulated buildings, the need for maintaining the air
temperature at 21 8C, especiallyin the early morning orlate at night,
results in an increasedrating of the heating system, whencompared
toan adequately insulated building(this canbe seen in Fig.5).Inthe
casewhere thermal bridges are ignored, the requiredheatingpower
is similaramongall theadequatelyinsulatedbuilding scenarios. This
holdsnot true in the case of themoreaccurate approach,i.e. theone
including the calculation of thermal bridge effects, where external
insulation configuration leads to a decrease in required heating
power by up to 21% compared to the most common type of
insulation configuration presented by scenario B (26.5 kW in
scenario D compared to 33.4 kW in scenario B).
3.2. Cooling load
In the case of cooling load requirements differences among the
examined scenarios appear to be less significant (see Fig. 6). The
main reason being that during the cooling season heat flows,
caused by conduction through the building envelope, contribute to
a lesserextent to thebuildings energy balance andhave, therefore,
a smaller effect on the cooling load demands.
In almost every case it is the buildings last storey which
presents the higher energy demands, because the flat roof accepts
high values of solar irradiation during summer. Despite the small
differences, external insulation still provides an efficient solution
Fig. 4. Deviation of calculated heating load demand with and without the inclusion
of thermal bridge effects. Fig. 5. Maximum heating power requirement during the heating season.
T.G. Theodosiou, A.M. Papadopoulos / Energy and Buildings 40 (2008) 20832089 2087
7/27/2019 buildings with double brick wall onstructions: impact of thermal bridges on the energy demand
6/7
in terms of energy conservation, because of the decreased heat
flows through the opaque elements of the buildings envelope. Onthewhole, considering the seasonal cooling demand, it is of limited
importance whether to include or not the thermal bridge effect in
the calculation method.
In contrast to the case of the annual cooling demand, the
thermal insulation effect on the required cooling power of the
cooling system is more evident (Fig. 7). A comparison of scenarios
A and D indicates that the difference varies between 21% (15.5
19.6 kW) and 16% (15.218.2 kW), depending on whether the
thermal bridge effects are included or not.
4. Energy cost and carbon dioxide emissions
The primary energy consumption for each examined scenario
was calculated for the cases of two different heating systems, anoil-fired and a gas-fired boiler distributing the heat to hydronic
radiators. The former is the traditional heating system installed in
the majority of current building stock and the latter is a rather new
option introduced in the late 1990s in many Greek cities, with a
rapid retrofitting takingplace since 2003. Thenominal efficiency of
the boiler is 85% and 90% for each fuel type, respectively. When it
comes to cooling, an air to air heat pump, with an average seasonal
coefficient of performance (COP) equal to 2.7, is typical for Greek
climatic conditions. On the basis of these assumptions, the annual
consumption for each type of fuel is presented in Table 3. For the
calculation of the annual heating and cooling costs, data for the
year 2006 were considered with respect to fuel prices and the
national energy mixture as presented in Table 4 [16]. The results
are presented in Table 5. All values reflect energy consumption
resulting from thermal losses calculations including thermal
bridge effects, since this was proven to be a more accurateapproach.
The total annual carbon dioxide emissions for the apartments
heating and cooling are presented in Fig. 8. The most representa-
tive case among the current building stock-fired of scenario B is
compared to an oil-fired boiler, which is the typical heating
equipment over the last decades and is therefore considered to be
the reference case.
In the cases of a buildings construction or renovation, the
combination of external insulation and a state of the art gas-fired
boiler would result in an almost 50% annual running cost
reduction, compared to the most common combination of cavity
insulation with oil-fired boiler (22294508s, respectively). This is
mainly due to the heating consumption reduction, since the
cooling demands are not significantly affected by the thermalinsulation configuration. The environmental impact of this
optimum combination is also significant since an approximately
Fig. 6. Specific annual cooling load requirements for each examined scenario.
Fig. 7. Maximum cooling power demand during the cooling season for the entire
building and for each storey.
Table 3
Annual consumption for each type of fuel
Fuel type Annual consumption for each scenario
A B C D
Heating
Fuel oil (kg) 9130 6513 5514 4515
Natural gas (m3) 7432 5302 4489 3676
Cooling
Electricity (kWh) 7362 7307 7435 6684
Table 5
Total annual running costs for heating and cooling
Fuel type Annual running cost for each scenario (s/
year)
A B C D
Heating
Fuel oil 5478 3908 3309 2709
Natural gas 3398 2424 2052 1680
Cooling
Electricity 604 600 610 549
Total
Fuel-fired boiler and heat pump 6083 4508 3919 3258
Gas-fired boiler and heat pump 4003 3024 2663 2229
The scenarios presented here were calculated by taking into account the thermal
bridge effects.
Table 4
Fuel and electricity tariffs and emission factors
Energy source Tariffs Emission factor (kg/kWh)
Natural gas 0.0456s/kWh 0.181
Fuel oil 0.600s/lt 0.247
Electricity 0.08211s/kWh 0.368
T.G. Theodosiou, A.M. Papadopoulos / Energy and Buildings 40 (2008) 208320892088
7/27/2019 buildings with double brick wall onstructions: impact of thermal bridges on the energy demand
7/7
27% reduction in carbon dioxide emissions can be achieved on an
annual basis (3.124.29 t/year).
5. Conclusions
The study of representative wall insulation configurations inGreek buildings, applying both the currently valid calculation
methodology and the more accurate approach which takes the
thermal bridge effect into consideration, shows that the existing
legislative frame is inadequate, leading to a significant under-
estimation of actual energy consumption, especially in the case of
cavity insulation.
Considering the fact that the majority of the buildings
constructed in the last twenty years are partially insulated and
that thermal bridges are not considered by the calculation
procedure, actual thermal losses in the cases of such buildings
are by up to 35% higher than the initially estimated ones. The
double brick wall construction used widely in Greece is
particularly susceptible to allowing thermal bridges. Even when
the actual construction fully implements the insulation study,heating requirements are in reality by 30% higher than the ones
calculated by the current methodology which does not take
thermal bridge effects into account. Interestingly enough, the
underestimation of thermal losses is more misleading in the cases
of fully insulated buildings than in the cases of partially insulated
ones. It was also shown, that the current legislation disfavours the
more effective configuration of external insulation, when com-
pared to the cavity insulation, despite the fact that the former can
minimise thermal losses in thethermal bridges andis also themost
appealing solution when it comes to renovating existing buildings.
Thus, there is an obvious contradiction between the target of
designing more energy efficient buildings and the current
legislative framework, which needs to be addressed and redeve-
loped and which was still debated in April 2008.
Apart from the improved heating and cooling demands of
buildings, there are two further benefits to be considered, namely
the not negligible environmental impact and the reduction of the
buildings running costs. Such aspects should not be overlooked
when revising the existing building codes.
References
[1] European Commission, Directive 2002/91/EC of the European Parliament and oftheCouncil of 16th December 2002 on theenergyperformanceof buildings, OJEC,L1/65, 04/01/2003.
[2] T. Theodosiou, N. Chrisomallidou, Shading and solar availability in the urbanEnvironment, in: Proceedings of PLEA2005The 22nd Conference on Passive andLow Energy Architecture, Beirut, Lebanon, November 1316, 2005.
[3] A.B. Larbi, Statistical modelling of heat transfer for thermal bridges of buildings,Energy and Buildings 37 (2005) 945951.
[4] F. Deque, F. Ollivier, J.J. Roux, Effect of 2D modelling of thermal bridges on theenergy performance of buildings: numerical application on the Matisse apart-ment, Energy and Buildings 33 (2001) 583587.
[5] V. Geros, M. Santamouris, S. Karatasou, A. Tsangrassoulis, N. Papanikolaou, On the
cooling potential of night ventilation techniques in the urban environment,Energy and Buildings 37 (2005) 243257.
[6] J. Neymark, R. Judkoff, G. Knabe, H.-T. Le, M. Durig, A. Glass, G. Zweifel, Applyingthe building energysimulation test(BESTEST) diagnosticmethod to verificationofspace conditioning equipment models used in whole-building energy simulationprograms, Energy and Buildings 34 (2002) p.917931.
[7] TRNSYS, A Transient System Simulation Program, Solar Energy Laboratory,University of Wisconsin, Madison, WI, 2006.
[8] EN ISO 10211-1, Thermal Bridges in Building Construction: Heat Flows andSurface Temperatures. Part 1. General Calculation Methods, 1995.
[9] EN ISO 10211-2, Thermal Bridges in Building Construction: Heat Flows andSurface Temperatures. Part 2. Linear Thermal Bridges, 2001.
[10] EN ISO 14683, Thermal Bridges in Building Construction: Linear Thermal Trans-mittance. Simplified Methods and Default Values, 2000.
[11] J. Kosny, E. Kossecka, Multi-dimensional heat transfer through complex buildingenvelope assembliesin hourly energysimulation programs, Energyand Buildings34 (2002) 445454.
[12] I. Doebber, M. Ellis, Thermal performance benefits of precast concrete panel andinsulated concrete form technologies for residential construction, ASHRAE Trans
111 (2005) 340352.[13] SAPPEK, Development of innovative insulation elements based on stone wool,
Project report, vol. 1, Lab. of Heat Transfer and Environmental Engineering,Aristotle University Thessaloniki, 2007 (in Greek).
[14] S. Chadiarakou, M. Santamouris, A. Papadopoulos, The importance of insulationon the buildings thermal losses, in: Proceedings of the CLIMAMED Congress,Lyon, November 2021, 2006, (2006), pp. 325332.
[15] A.M. Papadopoulos, T. Theodosiou, K. Karatzas, Feasibility of energy savingrenovation measures in urban buildings: the impact of energy prices andthe acceptable pay back time criterion, Energy and Buildings 34 (2002) 455466.
[16] A.M. Papadopoulos, S. Oxizidis, G. Papandritsas, Energy, economic and environ-mental performance of heating systems used in Greek buildings, Energy andBuildings 40 (2008) 224230.
Fig. 8. Annual carbon dioxide emissions and percentage CO2 reduction for each fuel
type and for each insulation configuration scenario. Scenario B with oil-fired boiler
is the reference case.
T.G. Theodosiou, A.M. Papadopoulos / Energy and Buildings 40 (2008) 20832089 2089