Bushings 20 kV for montage outdoor/indoor (3 pcs)Item 2.Technical specificationRequirementsOffered Requirements
Type:
-
Nominal Voltage:
24 kV
Rated impulse overvoltage withstand on dry conditions:
125 kV
Temporary short time overvoltage in wet conditions:
50 kV
Nominal frequency:
50 Hz
Materials:
Porcelain C 120, according to IEC 60672-3/Silicon IEC 62231
Sealant:
Portland cement
Overall height of the insulator:
305 mm
Minimum creepage distance:
380 mm
minimum breaking force:
8000 N
minimum torsion torque:
0,8 kNm
Fitting:
Cast iron, hot zinc
Holes for mounting insulator
-Hole numbers:2-axial hole span:240mm-hole diameter:M16
-hole numbers:4-axial hole span:76mm-hole diameter: M12
Standards:
IEC 60272
Tests:
According to IEC 60168
Technical documents with offer:
-detailed dimensions drawing-Complete protocols of type test (not older than 10 years)*
Technical documents with equipment delivery:
protocols of routine tests
2. BUSHINGS 20 kVGeneral
Bushings for passage of flat busbars, inner wall has a conductive layer galvanic linked with busbars. The insulators are equipped with aluminum plates that are used as a carrier of busbars. The plates are secured from falling with clamping rings, which also used as electrical connection of the inner surface and busbars.
* - Type test protocols should be issued by accredited laboratories. Laboratory accreditation should be in accordance with ISO / IEC 17025 and should be issued by the national accreditations. The same must be submitted with the offer.- ISO 9001 should be submitted with offer
Note: The supplier is required to completely fulfill each item of these technical specifications, in otherwise the offer will be rejected as incomplete.