Upload
rajendran-srn
View
223
Download
2
Embed Size (px)
Citation preview
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
1/46
1
Boiler Internal Cycle Chemistry
Indonesia Customer Seminar
June 13 & 14 2012
Jakarta Indonesia
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
2/46
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
3/46
High Pressure Boiler Definition
Terminology:
Boilers in which steamproduced at or above 70 bar
(1000 psi) Sub-critical, below critical pressure(225 kg/cm2). Drum type boilers.
Supercritical, mostly operate at 245
kg/cm2. Highest is 350 kg/cm2.Once-through boilers
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
4/46
Factors Affecting Chemistry in HP Boiler
Smaller densitydifference and greatervolatility
High Cycle ofConcentration
ConcentratingMechanisms
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
5/46
5
Higher pressure =greater volatility ofdissolved solids
Higher pressure =smaller difference ofliquid and vapor
density
SiO2NaOH
NH4Cl
(NH4)2SO4
CuO NaCl
Na3PO4
Volatile Mechanical
Fe3O4
#1 Boiler Pressure and Carry Over
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
6/46
#2 High Cycle of Concentration
Make-up water cost for HPboiler is high
Energy loss from blow down inHP boiler is also high
HP boiler running with highcycle compare (50- >100 cycles
or 2-1% BD)to save the costfrom blow down and make-up
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
7/46
Higher solids accumulation inthe boiler higher potentialfor deposition problem
Longer holding timeLimiting effectiveness of chemicaldispersant that commonly use tominimize deposition
#2 High Cycle of Concentration
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
8/46
Iron Transport and Boiler Deposition
The majority of iron entering the boiler remains inthe boiler (even when dispersants are used)
Cycle % Fe Transport
(with dispersant)
25-50 20-30
75-100 5
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
9/46
Pressure, Temperature and Deposits
Deposit will retard the heattransfer and increase the tubemetal temperature
High tube metal temperature inHP boiler makes its tolerancefor water deposit is reduce
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
10/46
#3 Concentrating Mechanisms
The concentration of TDSin the film is higher thanthe bulk
The higher thetemperature difference, thegreater TDS concentrationin film (tube surfaces)
High concentration ofagressive ions could leadto localized corrosion
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
11/46
#3 Concentrating Mechanisms
Concentrating mechanismslead to localized corrosionstype that only found in HPBoiler
Critical Factors: DNB,Deposition & Evaporation inwater line
Deposit will enhanceconcentrating mechanisms andincrease potential for underdeposit corrosion
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
12/46
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
13/46
Chemical Cleaning Guide Line
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
14/46
ObjectivesHP Boiler Internal Cycle Chemistry
Prevent Internal
Corrosion
Prevent Deposition
Promote Production of
Pure Steam
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
15/46
Achieinge non-corrosive boiler water pH levels
Providing adequatebuffer to deal with BFWcontamination
Providing minimumsolids contribution to theboiler water
15
Boiler Internal Treatment Chemistry
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
16/46
Why pH Control is Important ?
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
17/46
Caustic Corrosion
Causes: DepositionFree NaOH > 1 ppm
- Na contamination- Caustic overfeed
Solution
Minimize NaOHconcentrationNa:PO 4 = 2.3-2.6(Congruent PO 4)
17
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
18/46
Acid Phosphate Corrosion18
CausesDepositionPhosphate Hide Out
Control Na:PO 4 < 3:1Solution
Control PO 4 residual atlower rangeControl Na:PO 4 > 3:1Equilibrium PO 4 (EPT)
HideoutLoad
PO4
pH
Hideout Return
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
19/46
Hydrogen Damage
Causes: Deposition Acidic condition
- Condenser in-leakage- Pretreatment upsets
- Un-proper cleaningInadequate buffer
SolutionBetter BFW quality
Control Na:PO 4 3:1 to 1 ppm NaOHContinuum PO 4
19
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
20/46
20
SolidTreatment
Phosphate Continuum(PC)
Caustic Treatment (CT)
All VolatileTreatment
All Volatile (AVT)- Oxidizing- Reducing
Oxygenated Treatment(OT)
ContinuumEPRI New Cycle Chemistry Guide Line 2004
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
21/46
Phosphate Continuum (PC)
Control at Na:PO4 = 3: 0 to 1 ppm NaOHTSP and NaOH only no Phosphate with ratio < 3: 1
Tight boiler water pH control required
Transition from PC (Low) to PC (High) at approximately 3ppm PO 4
Advantages:Better pH control and bufferingGreater tolerance of FW contaminationReduced potential for acid phosphate corrosion if hideout occursEasier to stay in specification
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
22/46
Phosphate Continuum Control Chart
8.6
8.8
9.0
9.2
9.4
9.6
9.8
10.0
10.2
0 1 2 3 4 5 6 7 8 9 10
mg/L PO4
p H
a t 2 5 d e g
C
Na/PO4 = 3.0
TSP + 1 PPM NaOH
TSP + 2 PPM NaOH
PC
Na/PO4 = 2.6
Note:Minimum PO4 > 0.2 mg/L
Na/PO4 = 2.8
Na/PO4 = 4.0
PC (L) PC (H)
Na/PO4 = 3.4
Phosphate Continuum Control Chart
NaOHTSP
BD
23
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
23/46
23
PC(L) CC BFW : < 0.15 S/cm Phosphate : 0.3 3 ppm pH : 9.0 9.7
PC(H)
CC BFW : < 0.20 mS/cm Phosphate : 3 10 ppm pH : 9.5 10.1
Phosphate Continuum Control Chart
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
24/46
Phosphate Continuum Control Chart
8.6
8.8
9.0
9.2
9.4
9.6
9.8
10.0
10.2
0 1 2 3 4 5 6 7 8 9 10
mg/L PO4
p H
a t 2 5 d e g
C
Na/PO4 = 3.0
TSP + 1 PPM NaOH
TSP + 2 PPM NaOH
PC
Na/PO4 = 2.6
Note:Minimum PO4 > 0.2 mg/L
Na/PO4 = 2.8
Na/PO4 = 4.0
PC (L) PC (H)
Na/PO4 = 3.4
Phosphate Continuum Product Options
Na:PO4 = 4:1
Na:PO4 = 3.4 :1
Na:PO4 = 3 :1
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
25/46
Chemical Product Options
Dry TSP (Nalco 444) plus Caustic
Liquid TSP (BT 3000) plus diluteCaustic
Blended Na:PO4 ratio productsNalco BT-3400 (3.4:1)
Nalco BT-4000 (4.0:1)
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
26/46
Caustic Treatment
Candidates are boilers with severe phosphate hideout, condenserleaks, and saline cooling water.Would not be able to use AVT under these conditions.
Maintain to EPRI specifications
Cl- allowed varies by pressure (0.3 ppm @ 2500 psi)
NaOH = 2.5 x Cl -
SO 4 < 2 x Cl -
Provides more buffering capacity for SO 4 or Cl contaminant ingress
than PC(L), less than PC(H).
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
27/46
Boiler Chemistry Guidelines
Parameter Units psi 900 1500 1900 2300 2700 < 136 bar > 136 bar MPa 6.2 10.3 13.1 15.8 18.6 < 13.6 > 13.6
Na mg/L 3.50 2.70 2.10 1.60 1.30 PO4 mg/L 5.00 3.50 2.90 2.30 1.70 < 6 pH 9.68 9.53 9.45 9.35 9.23 9.8 - 10.2 Cl mg/L 1.70 1.20 0.90 0.70 0.52 SO4 mg/L 3.40 2.40 1.80 1.40 1.10 SiO2 mg/L 2.80 0.90 0.45 0.25 0.12 pressure Conductivity uS/cm 40 28 21 17 14 Cation Cond uS/cm 75 48 37 28 22 < 50
Na mg/L 2.30 1.80 1.50 1.20 0.95 PO4 mg/L 3.00 2.40 2.00 1.60 1.20 < 3 pH 9.52 9.38 9.30 9.20 9.09 9.3 - 9.7 Cl mg/L 0.90 0.45 0.30 0.19 0.12 SO4 mg/L 1.80 0.90 0.60 0.37 0.24 SiO2 mg/L 2.80 0.90 0.45 0.25 0.12 pressure Conductivity uS/cm 24 15 12 9 7 Cation Cond uS/cm 38 25 17 12 8 < 50
Na mg/L 2.20 1.60 1.20 0.90 0.70 NaOH mg/L 2.60 1.80 1.40 1.10 0.90 pH 9.80 9.65 9.55 9.45 9.35 9.3 - 9.7 Cl mg/L 0.90 0.58 0.44 0.34 0.27 SO4 mg/L 1.80 1.20 0.90 0.68 0.55 SiO2 mg/L 2.80 0.90 0.45 0.25 0.12 pressure Conductivity uS/cm 27 18 13 10 8 Cation Cond uS/cm 27 18 13 10 8 < 50
Phosphate Continuum - Low
Caustic Treatment
EPRI Guideline VGB Std Drum Pressure
Phosphate Continuum - High
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
28/46
All Volatile Treatment
Only use volatile chemicals. No solid chemicals.
Excellent program:For systems with condensate polishers and/or tight condensers
For once through boilers
Default program during steam blows and commissioning
Requires very high purity feedwater at all times!
< 0.2 uS/cm Cation ConductivityDissolved O 2 at CPD < 10 ppb
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
29/46
Source: Albert Busik, Drum Boiler on All Volatile Treatment - The pH Pitfall, Power Plant Chemistry, 2004
AVT Feed Water Purity is EssentialBoiler Water pH @Temperature with Contaminants
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
30/46
Source: Albert Busik, Drum Boiler on All Volatile Treatment - The pH Pitfall, Power Plant Chemistry, 2004
AVT Feed Water Purity is EssentialBoiler Water pH (9.5) @Temperature with Chloride 10-50 ppb
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
31/46
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
32/46
Oxygenated Treatment (OT)
Most preferred programfor Once Through Boiler
All steel metallurgy
Very high purity boilerBFW
CC < 0.15 mS/cmDO @CPD < 10 ppb
Full flow polisher is a mustNo oxygen scavengers
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
33/46
Disadvantages of OT
Very high purity ofBFW is required
Upset of cationconductivity will leadto serious corrosionproblem
Source:, EPRI, Cycle Chemistry Guidelines forFossil Plants: Oxygenated Treatment, 1994
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
34/46
Continuum Program Selection
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
35/46
Feedwater and Steam Quality Limits
0
0.5
1
1.5
2
2.5
3
3.5
4
OT AVT PC(L) PC(H) CT
p p b
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
u S / c m
Na, Cl, SO4 Cat Cond
Continuum: Feed Water Quality
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
36/46
Boiler Water Quality Limits @ 2500 psi
0
200
400
600
800
1000
1200
1400
OT AVT PC(L) PC(H) CT
p p b
0
4
8
12
16
20
24
28
u S / c m
Cl ppb SO4 ppb Cat Cond uS/cm
Continuum: Boiler Water Quality
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
37/46
Action Levels
EPRI developed Action Levels to specify how long and howfar chemistry could be safely out of the normal controlspecification.
Action Level 1:
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
38/46
Drum Normal Level 1 Level 2 Level 3Parameter Min Max Min Max Min Max Min MaxpH Consistent with selected PC programS. Cond (uS/cm) 28 > 28 < 56 > 56 < 112 > 112Cat. Cond (uS/cm) 48 > 48 < 96 > 96 < 192 > 192
Silica (mg/L) 0.9 > 0.9 < 1.8 > 1.8 < 3.6 > 3.6PO4 (mg/L) Consistent with selected PC programNa:PO4 Ratio Consistent with selected PC programSodium (mg/L) 2.7 > 2.7 < 5.4 > 5.4 < 10.8 > 10.8Chloride (mg/L) 1.2 > 1.2 < 2.4 > 2.4 < 4.8 > 4.8
Sulfate (mg/L) 2.4 > 2.4 < 4.8 > 4.8 < 9.6 > 9.6NaOH (mg/L) 1.0 > 1.0 < 2.0 > 2.0Note: Recommend immediate shutdown if pH < 8.0 or > 10.5
Action Levels: PC Program
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
39/46
39
Why Boiler Lay Up?
Oxygen corrosion found in a boileris generally occurred during theboiler in the idle condition andresult of improper lay up procedure
Factors that need to beconsidered:
What is the duration of downtime Need to provide backup steam capacity ?
Superheater? Drainable ? Can the boiler drained and left drywithout affecting plant operation ?
Can the boiler be sealed ? Do the valveshold ?
40
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
40/46
Boiler Lay Up
Wet Lay Up
Idle < 3 weeks
pH & O2 Scavenger atoptimum level
Pressurized blanket of inertgas to prevent air ingress
Method:
Short Term (Bottle Up) 72 hrs
Dry Lay Up
Best lay up method
Idle > 3 weeks
Method Nitrogen Blanketing Dessicant Vapor Corrosion Inhibitor
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
41/46
41
Boiler Lay-up Decision Tree
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
42/46
42
Short Term Wet Lay UpWater Chemistry Control Range
Lay-up Method Short-term Wet Lay-up
Time Period (After Shutdown) < 72 Hours (as long asretains heat and pressure)
pH Target Range (All-steel) 9.5-9.6 (High in normalrange)
pH Target Range (Cu Alloys) 9.2-9.3 (High in normal
range)Dissolved Oxygen (ug/L)
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
43/46
Wet Lay Up with N 2 Blanketing
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
44/46
Wet Lay Up with Steam Sparging
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
45/46
45
Lay-up Method Long-term Wet Lay-upTime Period (After Shutdown) > 72 Hours or when unit cools to
ambient pressure and temperaturepH Target Range (All-steel) 10.0-10.5pH Target Range (Cu Alloys) 10.0-10.5Dissolved Oxygen (ug/L)
8/10/2019 C. Boiler Internal Cycle Chemistry & Control
46/46
Thank You !