mkelectric.co.uk
632
CA
BLE
MA
NA
GE
ME
NT
PERI
MET
ER A
ND
DIST
RIBU
TION
TECHNICAL SPECIFICATION
ELECTRICAL
VOLTAGE RATING63A, 250V a.c.
VOLTAGE DROPL to N = 3.47 mV/A/metre run L to E = 3.47 mV/A/metre run N to E = 3.47 mV/A/metre run
EARTH FAULT LOOP IMPEDANCEL to E = 3.47 mΩ/m run.
CONDITIONAL SHORT CIRCUIT RATING(Fuse links BS 88 – 100A and BS 1361 100A). Prospective current 16.5 KA Mechanical withstand 10.0 KA peak min
MATERIALSPVCu materials used in the manufacture of MK products are self extinguishing non-flame propagating in accordance with BS 4678 Part 4
Extrusion material has been tested by a UKAS accredited laboratory in accordance with the requirements of BS476: part 7 and has achieved a Class 1Y
Moulding material has been tested by a UKAS accredited laboratory and conforms with IEC 695-2-1 at a severity of 650°C
IET WIRING REGULATIONSDesigned and manufactured to comply in all respects with BS 7671:2008 (IET Wiring Regulations 17th Edition: 2008)
QUALITY ASSURANCEThe system is manufactured to BS EN ISO 9001
Tested to BS EN 61534-1:2011 & BS EN 61534-21:2006
For a full range of corresponding products,
see pages 321-331 in the product selector.
Powerlink PlusTechnicalSkirting and Dado Trunking System
DescriptionPowerlink Plus is a trunking distribution system which contains within its profile a 63A single phase set of busbars and facilities for carrying telecommunications and data services cables.
Co-ordinated within the system is a wide variety of electrical and extra low voltage (ELV) outlets.
On the mains side these include specially designed sockets, both switched and unswitched, nonstandard switchsockets, switches, connection units and, via a simple interface, facilities for mounting all standard MK outlets.
ELV outlets include a master telephone socket outlet, an isolated co-axial socket outlet, “handset” telephone linejack outlet, computer sockets, a blank box and cover to accommodate other ELV requirements and, via a simple interface, facilities for mounting all single gang, standard MK ELV outlets. Also available are BNC type, LJU6C/RJ45 outlets, Euro Outlets and a blank to accommodate other ELV requirements. Incorporates a ‘Stay-set’ mechanism and is mains failure proof, ie it will function under all the normal conditions expected of an RCD and will not trip in the event of a power cut. This makes it suitable for use with freezers or in inaccessible or unmanned locations.
FEATURES
l Wide variety of visually and physically compatible mains and ELV outlets
l Complete segregation between mains and ELVl Stylish and elegant appearancel Easy to assemble, extend and modifyl Durable and impact resistantl Attractive stylingl Suitable for skirting or dado mountingl 3 compartment trunkingl Manufactured to high precision standardsl All extrusions manufactured from 100%
recycled material*
*Based on 2014 consumption
Technical Hotline +44 (0)1268 563720
633
CA
BLE
MA
NA
GE
ME
NT
PERIMETER AND
DISTRIBUTION
WALL THICKNESS
Trunking base 2.4mm
Centre compartment cover 2.5mm
Curved cover 1.5mm
WEIGHT (KG)
TYPE
NUMBER OF COMPARTMENTSWITH SCREENING
1 2
Dado trunking without busbar (K1903)
2.4 3.0 3.6
Dado trunking with busbar (K1963)
3.0 3.6 4.2
POWERLINK PLUS CABLE CAPACITY
TYPE OF CONDUCTOR SIZE CABLE
FACTOR
COMPARTMENT 1(CURVED)
COMPARTMENT 2(WITH BUSBAR)
COMPARTMENT 2(WITH BUSBAR)
COMPARTMENT 3(SQUARE)
Full Term CSA 100% Fill (MM2)
943 2968 2528 1044
TERM AT 45% FILL (MM2)
424 1335 1137 469
POWER CABLES NUMBER OF CABLES AT 45% FILL
PVCstranded
1.5mm2 8.6 49 155 132 54
2.5mm2 12.6 33 105 90 37
4mm2 16.6 25 80 68 28
6mm2 21.2 20 62 53 22
DATA CABLESNUMBER OF CABLES AT 45% FILL (A) AND FULL CAPACITY (B)
A B A B A B A B
Cat 5E UTP 5.5mm dia. 30.2 14 31 44 98 0 0 15 34
Cat 6 UTP 6.5mm dia. 42.2 10 22 31 70 0 0 11 24
Cat 6 STP 7.0mm dia. 49.0 8 19 27 60 0 0 9 21
Powerlink Plus Technical
Dimensions (mm)The dado trunking is divided into three compartments. Two identical outer compartments are mainly for ELV cables with a third central compartment containing the busbars with a cableway above.
50
170
1
1
2
50
170
1
3
2
CROSS SECTION THROUGH DADO TRUNKING
CROSS SECTION THROUGH SKIRTING AND DADO TRUNKING
Skirting and Dado Trunking System
mkelectric.co.uk
634
CA
BLE
MA
NA
GE
ME
NT
PERI
MET
ER A
ND
DIST
RIBU
TION
DIMENSIONS (MM)
FLAT ANGLE A B
DADO 270 170
SKIRTING 270 170
DIMENSIONS (MM)
FLAT TEE A B
DADO 270 170
Powerlink PlusTechnical
A
A
B
B
C
B
A
D
Flat Angles and TeesThese components are fabricated sections and space must be allowed for their inclusion in runs of trunking. All other components snap on over standard trunking profiles.
ComponentsThese components are fabricated sections and space must be allowed for their inclusion in runs of trunking. All other components snap on over standard trunking profiles.
Skirting and Dado Trunking System
K1903 (DADO TRUNKING
WITHOUT BUSBARS)
Technical Hotline +44 (0)1268 563720
635
CA
BLE
MA
NA
GE
ME
NT
PERIMETER AND
DISTRIBUTION
TRUNKING END CAP
K1963 K1904
K1903 K1904
K1962 K1944
CABLE LINK ASSEMBLY
1919
TRUNKINGFLAT
ANGLE UP
FLAT ANGLE DOWN
K1963 K1992 K1992
K1903 K1992 K1992
K1962 K1957 K1958
CABLE TERMINATION
10mm2 1923WHI
25mm2 1924WHI
TRUNKINGEXT
CORNER
K1963 K1906
K1903 K1906
K1962 K1912
TRUNKINGINT
CORNER
K1963 K1905
K1903 K1905
K1962 K1911
PLUG IN BUSBAR COUPLER
K1925WHI
TRUNKING COUPLER
K1963 K1908
K1903 K1908
K1962 K1945
TRUNKING FLAT TEE UP FLAT TEE DOWN
K1963 K1992 K1992
K1903 K1992 K1992
Powerlink Plus Technical
Component Selection Guide
20mm*
15mm* to wall
13mm*
13mm*
13mm*
70mm*
130mm*
20
70
13
13
20
70
13
13
TRUNKING
K1963
K1903
20
70
13
13
20
70
13
13
* Minimum distance
Skirting and Dado Trunking System
mkelectric.co.uk
636
CA
BLE
MA
NA
GE
ME
NT
PERI
MET
ER A
ND
DIST
RIBU
TION Powerlink Plus
Technical
GENERAL NOTES
Prior to installation strike a line of trunking using a plumb and chalk line for vertical, and spirit levels for horizontal runs.
Surface track accommodates 63 amp busbar with an integral duct directly above mains.
Data and Telecom cables.
Pre cut slots and circular holes at 100mm centres permit fi xing holes to be drilled and a wallplug with screw inserted after the surface track has been positioned.
When fi xing trunking use bushes provided and No. 8 wood screws.
Ensure trunking base is secured within 100mm from the end and a maximum of 500mm apart on either side along the length.
Check levels frequently – particularly at corners.
Debur all cut ends using a fi le or a sharp knife.
For mini trunking adaptors drill a 20mm diameter hole through the wall of the centre compartment using drill guide. Insert the tunnel and fi x with two screws provided.
Bridging busbar compartment – if required to take cables from top compartment to bottom or vice versa – drill holes to align with top and bottom holes of the centre compartment. Cut out 85mm from the busbar at the required position. Install cable link (1919) to the busbar and snap fi t cable crossing barrier (K1937CHA) over cables.
Commence installation at cable entry position. Route cables into the central section, wire in to the selected cable termination and plug into adjacent busbar and secure with screws supplied.
Installation Guide
1
2
4
3
8
7
9
10
1
2
3
4
5
6
8
Skirting and Dado Trunking System
5
6
Technical Hotline +44 (0)1268 563720
637
CA
BLE
MA
NA
GE
ME
NT
PERIMETER AND
DISTRIBUTIONPowerlink Plus
Technical
7
9
10
Skirting and Dado Trunking System
mkelectric.co.uk
638
CA
BLE
MA
NA
GE
ME
NT
PERI
MET
ER A
ND
DIST
RIBU
TION Powerlink Plus
Technical
Installation Guide Continued Cut central cover to length to fi t exactly between the exposed frontplates of accessories. At coupling positions leave expansion gaps by cutting the central cover to the same length as the trunking base.
Secure centre covers to the main base with the screws provided every 500mm max, top and bottom and within 150mm of accessories and fi ttings.
At the junction of two adjacent lengths of trunking busbar plug in the coupler to maintain electrical continuity. It is fi tted over a protector in the coupler carrier.
Data / Telecoms Devices – Secure enclosure box over centre compartment with screws supplied.
Run cabling into enclosure and terminate onto outlet on frontplate. Secure front cover to enclosure box with screws provided.
Internal and external corners – Connect the lengths of busbar using the cable link assembly (1919) and
secure trunking using the screws provided.
12
13
14
16
15
12
13
14
16
Skirting and Dado Trunking System
Technical Hotline +44 (0)1268 563720
639
CA
BLE
MA
NA
GE
ME
NT
PERIMETER AND
DISTRIBUTIONPowerlink Plus
Technical
17 Moulded corner and coupler shields should be fi tted before fi tting any covers. They are secured by the central covers overlapping each side of the component and do not require additional fi xing.
Powerlink Plus Sockets – Plug the socket onto the busbars in the required region ensuring that the socket clips fully locate fi rmly on to their corresponding busbars. Secure with screws provided. Note – do not tamper with busbar clips.
Plug on connection units – Connect the load conductors which are either routed through the centre compartment of the trunking or enter through the fl ex outlet. Plug connection unit onto busbar where required and secure as described above.
Outer Covers – For central covers and end cap retainers, leave a gap of 8-10mm and snap fi t onto
trunking.
Snap fi t end caps then other trims after fi tting all central and outer covers.18
19
20
17
18
19
20
15
Skirting and Dado Trunking System