84
California’s Energy Codes and Standards Now and Next sdf The California Energy Commission with California Lighting Technology Center & Energy Code Ace April 26, 2016 | 2 pm

California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

California’s Energy Codes and StandardsNow and Next

sdf

The California Energy Commission with

California Lighting Technology Center &Energy Code Ace

April 26, 2016   | 2 pm

Page 2: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

California Energy Commission, Daniel WongAppliances and Outreach & Education

California Lighting Technology Center, Nicole GraeberResearch Development & Demonstration

Energy Code Ace, PG&E, Kelly CunninghamCompliance Improvement 

Page 3: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,
Page 4: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

A Little CEC History• Section 25402 of the Public Resources Code 

(known as the Warren Alquist Act)

• The act created the Energy Commission in 1974 and gave it authority to develop and maintain Building Energy Efficiency Standards

• Requires the Standards and new requirements to be cost effective over the economic life of the structure

• Requires the Energy Commission to update the Standards periodically (about every 3 years)

Page 5: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

CLTC, UC Davis MissionTo accelerate the development, deployment and commercialization of energy‐efficient lighting and daylighting technologies in partnership with utilities, manufacturers, end users, builders, designers, researchers, academics, and governmental agencies.

Mission‐driven Activities:Research & Development ▪ Demonstration & Outreach ▪ Education & Training

Page 6: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

♠ Assist in reaching statewide energy goals by improving compliance through outreach and education

♠ Part of the California Investor Owned Utility Statewide Codes and Standards program

© 2016 Pacific Gas and Electric Company, San Diego Gas and Electric, Southern California Gas Company and Southern California Edison. All rights reserved, except that this document may be used, copied, and distributed without modification. Neither PG&E, Sempra, nor SCE — nor any of their employees makes any warranty, express of implied; or assumes any legal liability or responsibility for the accuracy, completeness or usefulness of any data, information, method, product, policy or process disclosed in this document; or represents that its use will not infringe any privately‐owned rights including, but not limited to patents, trademarks or copyrights.

Page 7: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

• Why energy standards?• What are the policy drivers?• Where does lighting fit in the big picture?• What is the regulation development process?

History of California’s Regulations

Page 8: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

California’s Energy Efficiency Standards

CA Governor Ronald Reagan signing Warren‐Alquist Act in 1974

Page 9: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Supporting Agencies:

California’s Policy Goals

1. California’s Long Term Energy Efficiency Strategic Plan. 2. Executive Order B‐18‐123. Assembly Bill 758; Existing Buildings Action Plan4. Assembly Bill 32 for 2020; Executive Order  B‐30‐15 for 2030 and 20505. Executive Order B‐29‐15

Page 10: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

How Standards are Updated

The code cycle can be divided into four phases: • Proposals• Pre‐Rulemaking• Rulemaking• Post‐Adoption

Page 11: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Standards Development Obligations

• Technically feasible• Cost‐effective • Performance‐based and prescriptive compliance paths

Page 12: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Impact of 2016 Energy Standards• First Year Energy Savings over 2013 Standards

– Electricity Savings – 537 GWh– Demand Reduction – 195 MW– Gas Savings – 30.1 MTherms

• Energy savings avoid the need to build nearly 12 (500 MW) power plants over 30 year period

Page 13: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

• Nonresidential What’s New?• Mandatory Lighting Controls• Prescriptive Lighting Requirements• Acceptance Test Technician Certification Provider• Certification of Lighting Controls

2016 Nonresidential Lighting Standards

Page 14: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

When does Title 24, Part 6 2016 go into effect?

Page 15: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

2016 Nonresidential: What’s New?

Page 16: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Mandatory Indoor Lighting Controls

Section Control

§130.1(a) Area Controls

§130.1(b) Multi‐Level Lighting Control

§130.1(c) Shut‐OFF Control

§130.1(d) Automatic Daylighting Control

§130.1(e) Demand Responsive Control

Page 17: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Area Controls 130.1(a)• Must have manual ON/OFF control for all indoor lighting. Each enclosed space must be controlled separately.– Controls must be readily accessible– General lighting separately controlled from 

other lighting types

Page 18: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Multi‐Level Lighting Control §130.1(b)• Multi‐level lighting controls required for:

– Enclosed spaces ≥ 100 ft2; and– LPD > 0.5 W/ft2

– General lighting only– Dimmable luminaires must be controlled by 

a dimmer

• Exception for spaces which require partial‐OFF occupancy sensor (new):– Aisle ways, open areas in warehouse– Library book stack aisles– Corridors and stairwells– Parking garages

Page 19: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Shut‐OFF Control §130.1(c)• All Indoor lighting must have an automatic shutoff 

control (§130.1(c)1)– Occupant sensing or automatic time‐switch– No more than 5,000 ft2 of lighting controlled together

• Occupant sensors are required for (§130.1(c)5):– Offices ≤ 250 ft2

– Multipurpose rooms ≤ 1,000 ft2

– Classrooms, conference rooms– Require partial‐ON or vacancy sensor 

if also meeting multi‐level lighting control req. (new)

Page 20: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Case Study: Adaptive Corridor LightingLatham Square, (Oakland, CA)

• Adaptive (bi‐level) lighting controls installed on 12 floors of corridors the Latham Square office building

• 174 T8 Luminaires retrofitted with 64 Watt T8 fluorescents and occupancy based controls

• Energy savings: 86% 

Page 21: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Case Study: Adaptive Corridor LightingBainer Hall, UC Davis

• Existing 4‐lamp T8 fluorescent luminaires updated with three adaptive corridor lighting solutions from different manufacturers

• Average energy savings: 73% • Average occupancy rate: 18%

Page 22: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Daylighting & Demand Response Control §130.1(d), §130.1(e) 

• Automatic daylighting controls required for:– Spaces with ≥ 24 ft2 of glazing and ≥ 120 W lighting in the 

daylit zone– Open parking garages with ≥ 36 ft2 of glazing or opening and 

≥ 60 W lighting in the daylit zone– General lighting within daylit zone only– Control steps listed in TABLE 130.1‐A

• Demand responsive controls are required for:– Buildings over 10,000 ft2, excluding spaces with 

LPD of ≤ 0.5 W/ft2

– Must be capable of receiving a DR signal and reducing total lighting power by 15% minimum

Page 23: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

An 80,000 ft2 building is being constructed containing ten tenant spaces, each 8,000 ft2 in size. 

Do these tenant spaces need to comply with the requirements for automatic demand response?

Page 24: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Mandatory Outdoor Lighting Controls and Equipment

Section Control

§130.2(a) Incandescent Lighting(no change)

§130.2(b) Cutoff Requirements(no change)

§130.2(c) Controls(new requirements)

Page 25: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Controls for Outdoor Lighting §130.2(c)• All outdoor luminaires (§130.2(c)1):

– Controlled by photocontrol and time‐switch, or– Astronomical time‐switch control

• Outdoor lighting mounted ≤ 24 feet above the ground (§130.2(c)3): – Motion sensor that automatically reduces lighting power 

by 40 ‐ 90% (new)– Outdoor sales  lots and sales canopies (new)– Exceptions: 

• poles with max of 75W• non‐poles with max 30 W• linear lighting with max of 4 W/ft

Page 26: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Case Study: Wall Packs At UC Davis• UC Davis replaced 101 HPS and MH wall packs with 

adaptive LED with networked controls and PIR motion sensors

• Retrofit cut energy consumption by 89%• $76,000 in energy costs will be saved over the 

life of the new wall packs

Page 27: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Prescriptive Lighting Measures §140.6, §140.7

Section Control

§140.6(a)2 Power Adjustment Factors

§140.6(b), §140.6(c) Lighting Power Allowance

§140.7 Outdoor Lighting

Page 28: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Prescriptive Indoor Lighting Req. §140.6

New for 2016:• New Power Adjustment Factors (PAFs) added for: 

– Daylight dimming plus OFF– Institutionalized Tuning

• PAFs removed:– Partial‐ON occupancy sensors– Manual Dimming/Multiscene programmable control– Combined manual dimming plus partial‐ON occ. sensor

• Approximately half of lighting power density (LPD) values reduced

Page 29: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Prescriptive Outdoor Lighting Req.§140.7

New for 2016: • General Hardscape LPDs reduced• Lighting for ATMs, tunnels, and bridges is no longer 

exempt, included in power allowance calculations

Page 30: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Prescriptive Outdoor Lighting Req.§140.7

New for 2016: • New Lighting Zone 0 

– No lighting allowance– One luminaire ≤ 15 W for entrances to parking area, trail head, 

toilet facility, etc.

Page 31: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Nonres. Indoor Lighting Alterations §141.0(b)2

Section Control

§141.0(b)2I Entire Luminaire Alteration

§141.0(b)2J Luminaire ComponentModification

Page 32: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Nonres. Indoor Lighting Alterations §141.0(b)2I, J

• Entire Luminaire Alteration (§141.0(b)2J)– Removing and reinstalling luminaires ≥ 10% existing– Replacing/adding entire luminaires– Adding, removing, replacing walls along with redesign of 

lighting system– Exception: replacing or reinstalling ≤ 2 luminaires– Exception: Acceptance testing not required when controls 

are added for 20 or fewer luminaires

Page 33: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Nonres. Indoor Lighting Alterations §141.0(b)2I, J

• Luminaire Component Modification (§141.0(b)2K)– Replacing ballast/driver and lamps– Changing the light source, or optical system– ≥ 70 existing luminaires modified– Exception: Acceptance testing not required when controls 

are added for 20 or fewer luminaires

Page 34: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Nonres. Indoor Lighting Alterations §141.0(b)2I, J

Two options for meeting power and control req.1. Meet LPD and controls 

per TABLE 141.0‐E− Area control− Multilevel lighting control− Shutoff control− Automatic daylight control− Demand responsive control

Similar to 2013

2. Reduce existing lighting power by 50% or 35% and controls− Area control− Shutoff Control

New for 2016

Page 35: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Nonres. Indoor Lighting Alterations §141.0(b)2I, J

Page 36: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Is installing tubular LEDs that require the removal of the ballast (tube connects direct to line voltage) in 148 luminaires an alteration or a repair?

Page 37: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Acceptance Testing§130.4

• Acceptance Testing ‐ §10‐103(a), §130.4(a)– Ensure that controls are installed and operating as required– Consists of visual inspection, review of requirements, and 

functional tests– 2013 Standards introduced requirements for Certified 

Acceptance Test Technicians (ATT)– Certified ATTs must complete training from an approved 

Acceptance Test Technician Certification Provider (ATTCP)– http://www.energy.ca.gov/title24/attcp/

Page 38: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Who Can Be An ATT?Including (but not limited to):

– Electrical Contractors– Certified General Electricians– Professional Engineers– Controls Installation & Setup Contractors– Certified Commissioning Professionals– HVAC Installers– Mechanical Contractors

Participation in the ATT program is limited to persons who have at least three years of verifiable professional experience and expertise in lighting controls and electrical systems.

Page 39: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

SECTION 2

Page 40: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

SECTION 2

Page 41: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,
Page 42: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Under the 2016 standards, an ATT is not required to perform acceptance testing if a permitted project adds lighting controls to control ____ or fewer luminaires.

Page 43: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

• Residential What’s New?• High Efficacy Requirements• Lighting Control Requirements• JA8 Requirements

2016 Residential Lighting Standards

Page 44: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Residential What’s New?

Page 45: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Luminaire Efficacy §150.0(k)1A• All installed luminaires must be high efficacy:

– High efficacy by source type listed in TABLE 150.0‐A; or– Must be certified and labeled per JA8 to qualify as high 

efficacy– No low efficacy allowed!

Auto High Efficacy per TABLE 150.0‐A(No JA8 certification Required)

Pin‐based linear or Compact Fluorescent

GU‐24 Sockets rated for CFLs/Induction

Pulse‐Start Metal Halide

High Pressure Sodium

Luminaires with high frequency generator and induction lamp

Inseparable SSL for outdoor or colored decorative

Page 46: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Luminaire Efficacy §150.0(k)1A

JA8 Certification Required

All light sources installed in ceiling recessed downlights

Non decorative indoor LEDs

All others not listed in TABLE 150.1‐A

Page 47: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Screw Based Luminaires §150.0(k)1G

New for 2016:• Shall contain lamps that comply with JA8

– Lamps shall be marked with “JA8‐2016” or “JA8‐2016‐E”

• Shall not be recessed downlight luminaires in ceilings• Exception: Luminaires with hard‐wired ballasts for 

high intensity discharge lamps (HID)• Screw base luminaires can be considered high 

efficacy if the installed light source is JA8 certified

Page 48: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Enclosed Luminaire Req. §150.0(k)1H

New for 2016:• Enclosed Luminaires must contain light sources 

marked “JA8‐2016‐E”• Indoor and outdoor• Enclosed is defined as having ventilation 

openings < 3 in2 per lamp

Page 49: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Interior Lighting Controls §150.0(k)2

• Forward phase cut LED dimmers shall comply with NEMA SSL 7A (§150.0(k)2A) (new)

• Bathroom/Laundry/Garage/Utility (§150.0(k)2J)– At least one luminaire controlled by vacancy sensor (new)

• All luminaires with JA8 sources must be controlled by a dimmer or vacancy sensor (§150.0(k)2K) (new)– Not required in closets 

< 70 ft2, hallways

Page 50: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Outdoor Lighting Controls §150.0(k)3• All outdoor lighting must be high efficacy (new)• Must have manual ON/OFF control • Must be controlled by either:

1. Photocell and motion sensor (6 hour override allowed); or 2. Astronomical time clock (6 hour override allowed)3. EMCS with same functionality as astronomical time clock 

(no override allowed)

Page 51: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

JA8 ‐ Qualification Req. for High Efficacy Light Sources

JA8-2016 RequirementsCategory Requirements

Color Rendering Index (CRI) 90 (Same as 2013)

Luminous Efficacy 45 Lumens per Watt across board

Power Factor Min of 0.90 when tested at full output

Start Time Must turn on within 0.5s

Correlated Color Temp (CCT)Inseparable SSL light engines &

GU24 LED Lamps, < 4000 KelvinOthers: < 3000 Kelvin

Page 52: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

JA8 ‐ Qualification Req. for High Efficacy Light Sources

JA8-2016 Requirements (cont.)Category Requirements

R9 < 50Rated Life > 15,000 Hours

Minimum Dimming Levels < 10%

Flicker < 30% for frequencies of 200 Hz or below

Audible Noise < 24 dBa at 1 meter from light source

Elevated Temperature(for enclosed and recessed

luminaires)

EnergyStar testing procedure to ensure life and quality of light

lasts at higher temps

Page 53: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Can an LED A‐19 installed in a downlight be considered compliant if it is certified to the Energy Commission as appropriate for enclosed luminaires? (JA8‐2016‐E)

Page 54: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Available ResourcesBlueprint Newsletter

– Published every other month– Receive by e‐mail– http://www.energy.ca.gov/

efficiency/blueprint

Energy Standards Hotline– Monday ‐ Friday– 800‐772‐3300 (In CA)– 916‐654‐5106 (Outside)– [email protected]

Training– http://www.energy.ca.gov/

title24/training/

Page 55: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Indoor Lighting38%

HVAC Nonresidential14%

Electrical PDS Nonresidential

8%

Title 24, General Information Nonresidential

6%

Forms ‐ Applicability Nonresidential

5%

Outdoor Lighting Nonresidential5%

Forms ‐ Location Nonresidential5%

Fenestration/Skylighting Nonresidential

4%

ATTCP Nonresidential5%

Modeling Nonresidential4%

Forms ‐ Assistance Nonresidential

3%Roofs Nonresidential

3%

Indoor Lighting

HVAC Nonresidential

Electrical PDS Nonresidential

Title 24, General Information Nonresidential

Forms ‐ Applicability Nonresidential

Outdoor Lighting Nonresidential

Forms ‐ Location Nonresidential

Fenestration/Skylighting Nonresidential

ATTCP Nonresidential

Modeling Nonresidential

Forms ‐ Assistance Nonresidential

Roofs Nonresidential

Hotline Data7/1/14 to 3/11/16

Page 56: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

♠ Various Modalities: Traditional Classroom Virtual Classroom Online Self-Studies “Decoding Talk” Series

♠ Audiences/Subjects: Building Dept. Personnel Energy Consultants Contractors/Installers Architects/Designers Manufacturers Lighting HVAC Refrigeration Modeling Software

♠ EnergyCodeAce.com♠ E-Newsletter♠ Press♠ Presentations♠ Partnerships

On-going Needs Assessments Inform Offerings

Page 57: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

EnergyCodeAce.com/content/reference‐ace/

Page 58: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

EnergyCodeAce.com/content/reference‐ace/

Page 59: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,
Page 60: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Prior to sale, regulated appliances within the scope of Title 20 requiring the submission of certification data must meet all the applicable requirements found in Sections 1601‐1609 of the California Appliance Efficiency Regulations  and be listed in the appliance efficiency database.

Appliance Efficiency Regulations (Title 20)

Page 61: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

cacertappliances.energy.ca.gov

Page 62: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Certify Your Products• Account management 

allows for self‐registration and maintenance

• Electronic submittal of appliance data, delegations of authority, test lab applications, and 3rd‐party certifier applications

• Multiple search engines to query submittals, active and archived appliances, 3rd‐party certifiers, manufacturers, and approved test labs

Access MAEDBS

Register New Account

Log in to Existing Account

Manage Documentation

Manage Company Info 

& Users

Manage Appliances

Page 63: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Certify Your Productsenergycodeace.com/content/title‐20‐ondemandenergy.ca.gov/appliances/forms/index.html#webdocs

Page 64: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Enforcement: Energy Commission • Administrative civil penalties under Title 20 (monetary fines)

• Responsible parties: ManufacturerRetailerWholesaler

ImporterDistributorAll supply chain actors

Page 65: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

T20 Regulated Lighting Products

Page 66: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Also certified and listed in the MAEDBS: under Title 24, Part 6

• Permanently‐installed high‐efficacy LED luminaires for residential applications

• JA8 compliant screw‐base lamps COMING SOON

• Lamps eligible for rebates through the voluntary California Quality Specification COMING SOON

Page 67: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Could this luminaire be considered high‐efficacy under the 2016 standards? 

Page 68: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

General Service LED Lamps 

Effective Date Minimum Compliance Score

Minimum EfficacyLumens per Watt

January 1, 2018(Tier 1) 282 68

July 1, 2019(Tier 2) 297 80

1605.3(k)(2): All state‐regulated LED lamps

Compliance score: 

Efficacy + (2.3 x CRI)

Page 69: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

• Base: E12, E17, E26, or GU‐24• Output: less than 2,600 lumens • CCT: between 2200 K and 7000 K• Duv: between ‐0.012 and 0.012

State‐regulated LED lamps

Page 70: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Selected Spec Comparison: A19 LampsEnergy Star 2.0 JA8, T24 2016 Title 20 CA Quality Spec

Effective date June 1, 2016 January 1, 2017 Tier 1: January 1, 2018Tier 2: July 1, 2019

November 21, 2014

CRI CRI ≥ 80 CRI ≥ 90 Lamps ≥ 150 lumens: CRI ≥ 82

CRI ≥ 90

R1 – R8 ‐ ‐ Minimum score of 72 for each individual color sample R1‐R8.

R9 > 0 ≥50 > 50

Flicker No minimum  flicker performance requirement

Percent flicker <30% at frequencies less than 200Hz, when tested at 100% and 20% light output, with test method

Dimmability not required for all lamps. Products claiming incandescent equivalency must be dimmable. Products claiming dimmability must comply with JA10.

"Flicker free" from 10% to 100%,no specific test method or criteria

Page 71: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Small Diameter Directional Lamps (SDDLs)

Sections 1605.3 (k)– Effective January 1, 2018

– Minimum rated life: 25,000 hours based on lumen maintenance and time to failure test procedure

– Meet one of the following requirements:

• Luminous efficacy of ≥ 80 lumens per watt.

• Luminous efficacy ≥ 70 lumens per watt and CRI + Efficacy ≥  165

Page 72: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Why These Lamps Were Chosen• No Federal or CA Standards for SDDL• ~15 million SDDLs installed in residential & commercial 

buildings, consuming more than 2500 GWh/year• More than 90% of the installed SDDL stock is comprised of 

incandescent, halogen and halogen infrared lamps; only about 10% are LED lamps

• 65% of the stock is commercial • 35% of the stock is residential• Commercial duty cycle of SDDLs is 3720 hours a year whereas 

residential duty cycle is about 840 hours a year

Page 73: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

When does Tier 1 of the recent Title 20 rulemaking regarding general service LED lamps go into effect?

Page 74: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Appliance Required Information Permissible AnswersState-regulated small diameter directional lamps

Base TypeGU 11, GU 5.3, GUX 5.3, GU8, GU 4 and medium screw base

Lamp Type (examples PAR-16, MR-11, MR-16, or R)Lamp Power (Watts)Lamp Output (Lumens)Beam AngleCenter Beam Candle Power (CBCP)Lumens Per WattMinimum lamp efficacy (LPW)Color Rendering Index (CRI)Combined CRI + EfficacyCorrelated Color TemperatureRated Life (hours)

Certification Requirements

Page 75: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Recorded online presentations:http://www.energy.ca.gov/appliances/forms/index.html#webdocs

Title 20 Appliance Efficiency Hotline or email inbox– Inside California (888) 838‐1467– Outside of California (916) 651‐7100– [email protected]

CEC Resources

♠ EnergyCodeAce.com♠ General Information: [email protected]♠ Request a Classroom Training at Your Location: 

Energycodeace.com/content/training‐request/

Page 76: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Energy Commission Building Standards Office – Planning sessions

IOU Codes and Standards Enhancement activities– Indoor: lower LPDs, evaluate additional controls 

opportunities, simplify alterations language– Outdoor: sensors at higher pole heights, lower LPAs– Participate: http://title24stakeholders.com/

CLTC Research and Demonstration projects

What’s Next: Title 24, Part 6 2019

Page 77: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

2019 Code Cycle Timeline

Milestone DatesCEC Develops 2019 TDV  Now – Q2 2016 Draft of CASE Reports to CEC  May 2017 Final CASE Reports to CEC  Sep/Oct 2017 CEC Pre‐rulemaking  July 2017 – Nov 2017 CEC Rulemaking  Nov 2017 – March 2018 2019 Standards Adopted  March 2018 2019 ACM Reference Manuals and Compliance Manuals Approved 

Nov 2018 

2019 Standards Effective  January 1, 2020 

Page 78: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

City of DavisOccupancy Sensing in Outdoor Applications over 24 Feet

• Emerging Technology: Microwave motion sensor • Detection range: 60 feet (pedestrians) and 110 feet (vehicles)

• Baseline: PIR motion sensor• Detection range: ~50 feet (all occupant types)

Page 79: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,
Page 80: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,
Page 81: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,
Page 82: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Can you name a light source performance metric that is calculated based on an integrating sphere measurement?

Page 83: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,
Page 84: California’s Energy Codes and Standards · 4/26/2016  · Controls for Outdoor Lighting §130.2(c) • All outdoor luminaires (§130.2(c)1): – Controlled by photocontroland time‐switch,

Complete your evaluations. Thank you!

California Energy Commission, Daniel WongAppliances and Outreach & [email protected]

California Lighting Technology Center, Nicole GraeberResearch Development & [email protected]

Energy Code Ace, PG&E, Kelly CunninghamCompliance [email protected]