CanalPondsSiteSummary(PVMDF)
Thereisapproximately5,330sq.ft.ofunusedfloorspace,excludingstandardaccessareaandaisles;unusedfloorareaincludingaccessandaisleareas=~8,500sq.ft.;excludingthewastetreatmentroomsjustbuiltasapartofPVMDFproject.Thetworoomsaddanadditional2,200sq.ft.ofspacethatcouldbeutilizedforfurtherdevelopment,eitherproductionorfacilitiessupport.ThelabspaceinSEsectionofthebuildingwouldbeavailableforsupportservicespacewithanadditional4,300sq.ft.ofspace.
Expansionatthesitebeyondthecurrentfootprintislimitedtoapproximately20,000sq.ft.onthesouthernsideoftheproperty(theexistinggrassareabetweenthebuildingandtheparkinglot).
Siteutilities:Asummarysheetofthecurrentutilitiescapacitiesisattached.
Attachments:BuildingmapwithavailablespaceSitepropertymapSiteutilitiessummary
CanalPondsSiteUtilitiesSummary
Electricaldistribution• 4.2MWavailablepoweratthesite
Backupemergencygenerator• Caterpillar#D-150-8,Dfordiesel,150for150KW• Redundantpadandconductplaceforfutureexpansion
Boilers/Lowpressuresteam
• Fultonboilerlowpressuresteam• Five(5)gasfurnacesusedfordomestichotwater;200,000BTU/hr
Chilledwater
• 300tonTranecentrifugalchillerwithroofmountedtower,indoorsump,chillerwaterpumps,towerpumps,condenserpumps,circulationfilterunit,andaleasedwatertreatmentsystem
• 300tonMcQuaysircooledreciprocatingchillero Repairneeded
• ChilledwaterexpansionreportcompletedaspartofconstructioninQ42014.
Nitrogen• 900gallontank
Processvacuum• Lowandhighvacuumsystems(25”Hgand5”Hg)
RO/DIWater
• HighpuritywatersystemthatrequiresaROmaker;DIwatersystemispresent• QuotedevelopedforthisupgradeaspartofPVMDFconstructionwithEvoquaWaterSystems
WastewaterPre-treatmentSystem
• Thereisnopre-treatmentsysteminplace;aquotewasdevelopedspecifictothePVMDFcapacityandtreatmentneedsthatwouldneedtobere-evaluatedwhenthedevelopmentcontinues
CleanroomExhaust
• Generalexhaust:capacity• ScrubbedExhaust:capacity
o ScrubbedhasbeenplacedbutnothookedupatthistimeCompressedair
• Cleandryair,redundantsystem;AtlasCopcounits
Naturalgas• 10inchfeed
Domesticwater• 10inchmain;80psi
SewerCapacity• 6inchmain
AirHandling
• Cleanroombuildoutdataforproductionarea
BMS • AutoMatrixDDCBMSsysteminplace;upgradesneededtosupporttheconstructionchanges;
notimplementedatthistime.• BMSmatrixwasdevelopedasapartofthePVMDFconstructionproject;notimplementedat
thistime.
FireSystem• Simplex4100 • MonitoringisonUPSpowerwithbatteryback-up • 100%Fullysprinklered(wet) • Risersystem
Security• Camerasystemandbadgingsystemarebeinginstalled;byQ22015
TGM • TGMmatrixwasdevelopedasapartofthePVMDFconstructionproject;notimplementedat
thistime.
EnvironmentalPermitting• PhaseIEnvironmentalSiteAssessmentcompletedin2013