valori limita ale coeficientilor de calcul conform EC2 pentru calculul sectiunilor de beton armat, relatia lui omega este eronata, este 1-sqrt(1-2*miu)
Citation preview
CARACTERISTICI DE CALCUL
cdfdb
Med
**2
=µ Momentul redus
µω *211 −+= sau
ξηλω **= sau
DIN TABELE
Coeficientul de armare mecanic
yd
cdnecs
f
fdbA ***, ω=
Aria de armătură necesară
d
x=ξ
CARACTERISTICILE ARMATURILOR PENTRU BETON ARMAT
TIPUL
OTELULUI OB37 PC52 PC60 Bst400S Bst500S B60.50
MARCA S 255 235 355 345 335 420 405 395 400 500 490
DIAMETRE
(mm) 6..12 14..40 6..14 16..28 32..40 6..14 16..28 32..40 6..28 6..28 10..40
fyk (MPa) 255 235 355 345 335 420 405 395 400 500 490
fyu (MPa) 360 510 590 450 550 590
Es (MPa) 200000
γs 1.15
εyd (%) 0.111 0.102 0.154 0.150 0.146 0.183 0.176 0.172 0.174 0.217 0.213
εcu2 (‰) 3.5
ξlim 0.759 0.774 0.694 0.700 0.706 0.657 0.665 0.671 0.668 0.617 0.622
µlim 0.423 0.428 0.401 0.403 0.405 0.388 0.391 0.393 0.392 0.372 0.374