Packaged Cooling with Electric Heat Rooftop Units Voyager™ 3 through 25Tons - 60 HZ RT-PRC002-EN May 2000

Cat

Embed Size (px)

Citation preview

Page 1: Cat

Packaged Cooling withElectric Heat Rooftop Units

Voyager™

3 through 25 Tons - 60 HZ

RT-PRC002-ENMay 2000

Page 2: Cat

©American Standard Inc. 2000 RP-PRC002-EN

Introduction

VoyagerTM . . . One of the mostcomplete lines of packaged unitson the market today. Built toprovide not only ultimate indoorcomfort, but also comfort in knowingthat our packaged units are easy toinstall and maintain.

Trane was the first to introduce theMicro and has continued to improve itsperformance. Together the Voyagerand the Micro provide the higheststandards in quality and reliability,comfort, ease of service, and theperformance of Trane light commercialproducts.

To increase their ability to win jobs,contractors want a unit that saves timeand money. Engineers want a unit thatmeets their design criteria and coversspecial applications. Voyager deliversall of this and more!

Trane Quality and Reliability. . .Building a superior packaged unitmeans not only knowing what to put in-- but also what to leave out. Wedesigned the Voyager unit leaving inthe tried and true components. We leftout those parts and components thatcause failures and require service.

SM

Page 3: Cat

RP-PRC002-EN 3

Contents

Introduction

Features and Benefits

Application Considerations

Selection Procedure

Model Number Description

General Data

Performance Data

Cooling PerformanceFan PerformanceHeat Performance

Controls

Electric Power

Dimension and Weights

Mechanical Specifications

2

4

9

101112

2020355456

57

78

98

Page 4: Cat

4 RT-PRC002-EN

Features andBenefits

Compressors

• Voyager contains the bestcompressor technology available, inorder to achieve the highestperformance possible. Ourcompressor line includes Trane builtClimatuff®, Model H and 3-D®Scrolls, along with CopelandCompressors.

• Our Compressor designs are testedin Trane’s SEET (System ExtremeEnvironmental Test) facility in Tyler,Texas where five years of operationare simulated in a sixteen week test.

• The dual compressors in the 7½-25ton units provide system back-up.

• Quality is improved in the Micro unitsdue to built-in reliabilityenhancements. Features like timedelay relay and anti-short cycle timersare built into the circuit board on allVoyager Micro units.

Micro

• For many years Trane has workedwith micro-processor controls in theapplied equipment markets. Thesedesigns provided the technology forVoyager™ with micro-processorcontrols.

• The Micro provides unit control forheating, cooling and ventilatingutilizing input from sensors thatmeasure outdoor and indoortemperature.

• The Micro improves quality andreliability through the use of time-tested micro-processor controls andlogic. The Micro now:

—prevents the unit from short cycling,considerably improving compressor life.

—ensures that the compressor will runfor a specific amount of time whichallows oil to return for better lubrication,enhancing the reliability of thecompressor.

• The Voyager with the Micro reducesthe number of components required tooperate the unit, thereby reducingpossibilities for component failure.

Weather Tight Top And Cabinet

• Voyager units incorporate either a onepiece top or the Trane-Tite-Top (T3).Each part of the top (either two or threepieces) overlaps in such a way thatwater cannot leak into the unit. Theseoverlapped edges are gasketed andsealed to ensure superior waterintegrity.

• Quick-Sess (3-7½ tons) and Quick-Access (8½-25 tons) panels reduce thenumber of possiblewater entry points.

• For added water integrity, Voyager hasa raised 11/8" lip around the supply andreturn of the downflow units toprevent water blowing into theductwork, in the event water shouldget into the unit.

Quality And Reliability Testing

•The fan and idler arm assemblydesigns have been tested to over300,000 cycles each. Our combinedcycle testing is now over 7,000,000cycles.

• All of Voyager’s designs wererigorously rain tested at the factory toensure water integrity.

• Actual shipping tests are performed todetermine packaging requirements.Units are test shipped around thecountry to determine the bestpackaging. Factory shake and droptests are used as part of the packagedesign process to help assure that theunit will arrive at your job site in topcondition.

• Rigging tests include lifting a unit intothe air and letting it drop one foot,assuring that the lifting lugs and railshold up under stress.

• All parts are inspected at the point offinal assembly. Substandard parts areidentified and rejected immediately.

• We perform a 100% coil leak test at thefactory. The evaporator and condensercoils are leak tested at 200 psig andpressure tested to 450 psig.

• Every unit receives a 100% unit run testbefore leaving the production line tomake sure it lives up to rigorous Tranerequirements.

Our designs are tested at thefactory, not on the jobsite!

Page 5: Cat

RT-PRC002-EN 5

Features andBenefits

Ease Of Installation

Contractors look for lower installation(jobsite) costs. Voyager’s conversionlessunits provide many time and moneysaving features.

Conversionless Units

• The dedicated design units are eitherdownflow or horizontal and require nopanel removal and alteration time toconvert in the field — a major costsavings during installation.

• Horizontal units come complete withduct flanges so the contractor doesn’thave to field fabricate them. These ductflanges are a time and cost saver.

Improved Airflow

U-shaped airflow allows for improvedstatic capabilities.

Single Side Access

Access to all of Voyager’s components isaccomplished through the Quick-Sessand Quick-Access panels. No more thanthree screws must be removed toaccess components.

Micro

The function of the Micro replaces theneed for field installed anti-short-cycletimer and time delay relays. The Microensures that the controls are integral tothe unit. The contractor no longer has topurchase these options and pay to havethem installed.

Easy Access Low Voltage Terminal Board

• Voyager’s low voltage terminal boardis external to the electrical controlcabinet. It is extremely easy to locateand attach the thermostat wire. This isanother cost and time-savinginstallation feature.

• The wiring of the low voltage to theunit and the zone sensors is as easy as1-1, 2-2, and 3-3.

Trane’s Idler Arm Assembly

Our idler pulley provides quick-adjustment for belt or motor sheaves on8½ - 25 ton units. No longer does thecontractor have to adjust the motor totighten the belt or change the motorsheave setting. A real time-saver inservicing and installing.

Single Point Power

A single electrical connection powersthe unit.

Page 6: Cat

6 RT-PRC002-EN

Serviceability

Today’s owners are more conscious ofthe cost of service and maintenance.Voyager was designed with input fromservice contractors. Their informationhelped us design a unit that would getthe serviceman off the job quicker andsave the owner money. Here is whyVoyager can save money in service.

Single-Side Service

Single-side service is standard on allVoyager units.

Quick-Sess 3-7½ ton and Quick-AccessPanels 8½-25 Ton Units

Remove three or fewer screws for accessto the standardized internal componentsand wiring.

Micro

• The Micro unit requires no specialtools to run the Voyager unit through itspaces. Simply place a jumper betweenTest 1 and Test 2 on the Low VoltageTerminal Board and the unit will walkthrough its operational stepsautomatically.

The unit automatically returns control tothe zone sensor after stepping throughthe test mode a single time, even if thejumper is left on the unit.

• As long as the unit has power and theLED is lit, the Micro is operational. Thelight indicates that the Micro isfunctioning properly.

• The Micro features expandeddiagnostic capabilities when utilizedwith Trane’s Integrated ComfortTM

Systems.

• One Zone Sensor option has centralcontrol panel lights which indicate themode the unit is in and possiblediagnostic information (dirty filters forexample).

Voyager’s Simpler Design

• The Voyager design uses up to 42%fewer parts than previous units. Sinceit is simpler in design, it is easier todiagnose.

• The Micro unit’s built-in diagnosticshelp the serviceman to identify anyproblem quickly.

Standardized Components

• Components are placed in the samelocation for all Voyager units.Familiarize yourself with one Voyagerand you are familiar with all Voyagerunits.

• One single Micro board is used on allVoyager Packaged Gas/Electrics,Cooling with Electric Heat, and HeatPump models. This providesstandardization of parts for thecontractors. Less money is tied up ininventory using the Micro.

• Contractors/owners can stock fewerparts due to standardized componentsthroughout the Voyager product line.

Colored And Numbered Wiring

You save time and money tracing wiresand diagnosing the unit.

StandardizedComponents

Colored andNumbered Wiring

Easy Access Low VoltageTerminal Board

Quick-Adjust Idler Arm

On all 8½-25 ton units, the belt andsheaves can be quickly adjusted withoutmoving the mounted fan motor. This isdone with our idler arm pulley. TheQuick-Adjust Idler Arm is a major savingsof time and money.

Features andBenefits

Page 7: Cat

RT-PRC002-EN 7

Voyager Helps Win Jobs And EngineerSpecifications

The Voyager units are built utilizingimportant input from our consultingengineers. Engineers want a unit thatperforms to their rigorous standards in avariety of applications. They want a unitthat lives up to their customers’expectations after giving their stamp ofapproval. Here is how Voyager performsto that standard.

Capacity Modulation

Voyager features dual compressors onunits 7½ thru 25 tons. The dualcompressor models are outstanding forhumidity control, light load coolingconditions and system back-upapplications.

Flexible Applications

• Only five factory-built roof curbs for theentire Voyager line. . .simplifies curbselection.

• Airflow is outstanding. The Voyagercan replace an older machine with oldductwork and, in some cases, improvethe comfort through better airdistribution.

• Factory Installed Options (FIOPs). .wide variety of options available.

Micro

• Some of the benefits of the Micro arethe built-in anti-short-cycle timer, thetime delay relay and the minimum‘’on’’ time controls. These controls arefunctions of the Micro and are factorytested to assure proper operation.

• As an energy benefit, the Micro softenselectrical ‘’spikes’’ by staging on fans,compressors and heaters.

• Another benefit is the IntelligentFallback or Adaptive Control. This is abenefit to the occupant if a componentgoes astray, the unit will continue tooperate at pre-determined temperatureset point.

• Intelligent Anticipation is a standardfeature of the Micro. It occursconstantly as the Micro and the zonesensor work together in harmony toprovide tighter comfort control thanconventional electro-mechanicalthermostats.

Micro

TraneCommunicationInterface

Features andBenefits

Page 8: Cat

8 RT-PRC002-EN

VariTrac

Trane’s outstanding changeover VAVSystem for light commercialapplications. When coupled withVoyager, it provides the latest intechnological advances in comfortmanagement systems and can allowthermostat control in every zoneserved by VariTrac.

Low Ambient Cooling

All 3-25 ton units have coolingcapabilities down to 0 F as standard.

Power Exhaust Option

This option offered by Trane isavailable on the 6¼-25 ton downflowunits. It provides exhaust of thereturn air when using a downfloweconomizer to maintain properbuilding pressurization. Great forrelieving most buildingoverpressurization problems.

Downflow And HorizontalEconomizers

The economizers come with threecontrol options — dry bulb isstandard, enthalpy and differentialenthalpy are field installed options.

INPUT/STATUSPANEL

TIMECLOCK

EDITTERMINAL

Central Control Panel

VariTrac®

High Static Drive Accessory

Available on some models, the highstatic drive accessory allows for theoptimization of the standard motor.Avoid expensive motors and operationcosts by installing this optimized sheaveaccessory.

Trane Communication Interface orTCI is available factory or field installed.This module when applied with theMicro easily interfaces with Trane’sIntegrated ComfortTM System.

Factory built roof curbs are availablefor the downflow units.

An assortment of zone sensors fromprogrammable to automatic and manualare available.

The following options round-out thecomplete line of Voyager accessories:

— 0 - 25% manual outside air hood

— Motorized outside air for 6¼-25 ton

One Of Our Finest Assets:

Trane Sales Representatives are aSupport group that can assist you with:

—Product

—Application

—Service

—Training

—Special Applications

—Specifications

—Computer Programs and much more

Voyager has the features and benefitsthat make it second to none. It wasdesigned with input from contractorsand engineers in the field. The U-shapedairflow performance is outstanding.

If all of your customers knew aboutVoyager, all would insist on it.

Voyager 3 - 25 tons . . .

SIMPLY THE BEST VALUE!!!!

Features andBenefits

Page 9: Cat

RT-PRC002-EN 9

Application of this product should bewivhin the cataloged airflow andcooling considerations. The UPGComputer Performance Program willsimulate product performance for a setof given conditions. It is recommendedthat the program be run for the worstdesign scenario for a particular unit. Formore information on the UPGComputer Product Performanceprogram contact your local TraneRepresentative.

Low Ambient Cooling

This Voyager line features, as standard,low ambient cooling down to 0F.Contact your local Trane Representativefor more assistance with low ambientcooling applications.

Barometric Relief

This product line offers an optionalbarometric relief damper included in thedownflow economizer accessory. Thisaccessory consists of gravity damperswhich open with increased pressure. Asthe building air pressure increases, thepressure in the unit return air sectionalso increases, opening the dampersand relieving the conditioned space.

NOTE: THE EFFECTIVENESS OFBAROMETRIC RELIEF DAMPERDURING ECONOMIZING OPERATIONIS SYSTEM RELATED.

PRESSURE DROP OF THE RETURN AIRSYSTEM SHOULD BE CONSIDERED TOCONTROL BUILDING PRESSURIZA-TION.

Power Exhaust Accessory

The power exhaust accessory isavailable on all 6¼-25 ton downflowunits. This accessory can be fieldinstalled and will assist the barometricrelief damper in relieving buildingpressurization.

Condensate Trap

The evaporator is a draw-thruconfiguration. A trap must be fieldprovided prior to start-up on the coolingcycle.

Clearance Requirements

The recommended clearances identifiedwith unit dimensions should bemaintained to assure adequateserviceability, maximum capacity andpeak operating efficiency. Actualclearances which appear inadequateshould be reviewed with the local Tranesales personnel.

Unit Pitch

These units have sloped condensatedrain pans. Units must be installed level,any unit slope must be toward accessside of unit.

ApplicationConsiderations

Page 10: Cat

10 RT-PRC002-EN

Cooling Capacity

Step 1Calculate the building’s total and sensiblecooling loads at design conditions. Usethe Trane calculation methods or anyother standard accepted method.

Factors used in unit selection:ATotal Cooling Load: 85 MBhBSensible Cooling Load: 60 MBhCAirflow: 3000 cfmDElectrical Characteristics: 460/60/3ESummer Design Conditions: EnteringEvaporator Coil: 80 DB, 67 WB OutdoorAmbient: 95FExternal Static Pressure: 0.52 in. wgGRooftop - downflow configurationHAccessories• Roof curb• Economizer• Electric HeatIHeating• Capacity 70 MBh• 460 volt/3 phase Electric Heat —3000

cfm

Step 2As a starting point, a roughdetermination must be made of the sizeof the unit. The final selection will bemade after examining the performanceat the given conditions. Divide the totalcooling load by nominal BTUH per ton(12 MBh per ton); then round up to thenearest unit size.

85 MBh / 12 MBh = 7.08 Tons or 7½ Tons

Step 3Table PD-7 shows that a TCD090C4 has agross cooling capacity of 90 MBh and65.0 MBh sensible capacity at 3000 cfmand 95 DB outdoor ambient with 80 DB,67 WB air entering the evaporator.

To Find Capacity at IntermediateConditions Not in the Table

When the design conditions arebetween two numbers that are in thecapacity table, interpolation is requiredto approximate the capacity. Note:Extrapolation outside of the tableconditions is not recommended.

Step 4In order to select the correct unit whichmeets the building’s requirements, thefan motor heat must be deducted fromthe gross cooling capacity. The amountof heat that the fan motor generates isdependent on the effort by the motor -cfm and static pressure. To determine thetotal unit static pressure:

External Static (duct system)0.52 wg

Standard Filter 1 in. 0.10 wgfrom Table PD-57

Economizer 0.03 wg

(100% Return Air) from Table PD-57

Electric Heater Size 36 kw 0.05 wgfrom Table PD-57

Total Static Pressure 0.70 wg

Note: The Evaporator Fan PerformanceTable PD-31 has deducted the pressuredrop for a 1 in. filter already in the unit(see note below Table PD-31). Therefore,the actual total static pressure is 0.70 -0.10 (from Table PD-57) = 0.60 wg.

With 3000 cfm and 0.60 wg.Table PD-31 shows 1.42 bhp for this unit.Note below the table gives a formula tocalculate Fan Motor Heat,3.53 x bhp = MBH.3.53 x 1.42 = 5.01 MBH.

Now subtract the fan motor heat fromthe gross cooling capacity of the unit:Net Total Cooling Capacity= 90 MBH - 5.01 = 84.99 MBH.

Net Sensible Cooling Capacity= 64.9 MBH - 5.01 = 59.89 MBH.

Step 5If the performance will not meet therequired load of the building -total orsensible cooling load, try a selection atthe next higher size unit.

Heating Capacity

Step 1Calculate the building heating loadusing the Trane calculation form or otherstandard accepted method.

Step 2Size the system heating capacity tomatch the calculated building heatingload. The following are building heatingrequirements:A Total heating load of 70.0 MBHB 3000 cfmC460 volt/3 phase Power Supply

The electric heat accessory capacitiesare listed in Table PD-58. From the table,a 27 kw heater will deliver 92.1 MBH at480 volts. In order to determine capacityat 460 volts, the heater voltagecorrection factor from Table PD-59 mustbe used. Therefore, 92.1 MBH x .92(voltage correction factor) = 84.73 MBH.

Air Delivery Selection

External static pressure drop throughthe air distribution system has beencalculated to be 0.60 inches of water.From Table PD-57 static pressure dropthrough the economizer is 0.03 and the36 kw heater is 0.05 inches of water(0.52 + 0.03 + 0.05). Enter Table PD-31 fora TCD090C4 at 3000 cfm and 0.60 staticpressure. The standard motor at 1015rpm will give the desired airflow at arated bhp of 1.42.

SelectionProcedure

Page 11: Cat

RT-PRC002-EN 11

ModelNumberDescription

Digit 8 - Electrical Characteristics

1 = 208-230/60/13 = 208-230/60/34 = 460/60/3W= 575/60/3

Packaged Cooling with Electric Heat Unit Typical Model Nomenclature

Digits 1, 2 - Product Type

TC = Packaged Cooling, ElectricHeat

Digits 4, 5, 6 - Nominal Gross Cooling

Capacity (MBh)

036 = 3 Tons Standard Efficiency037 = 3 Tons High Efficiency048 = 4 Tons Standard Efficiency049 = 4 Tons High Efficiency060 = 5 Tons Standard Efficiency061 = 5 Tons High Efficiency074 = 6 Tons High Efficiency075 = 6¼ Tons Standard Efficiency086 = 7 Tons High Efficiency090 = 7½ Tons Standard Efficiency091 = 7½ Tons High Efficiency102 = 8½ Tons Standard Efficiency103 = 8½ Tons High Efficiency120 = 10 Tons Standard Efficiency121 = 10 Tons High Efficiency150 = 12½ Tons Standard Efficiency151 = 12½ Tons High Efficiency180 = 15 Tons Standard Efficiency181 = 15 Tons High Efficiency210 = 17½ Tons Standard Efficiency211 = 17½ Tons High Efficiency240 = 20 Tons Standard Efficiency241 = 20 Tons High Efficiency300 = 25 Tons Standard Efficiency301 = 25 Tons High Efficiency

Digit 7- Major Development Sequence

Digit 11- Minor Design Sequence

T C D 0 9 0 C 3 0 0 A A

1 2 3 4 5 6 7 8 9 10 11 12

Digit 3 - Airflow Configuration

D = DownflowH = Horizontal

Digit 10 - Factory-Installed Options

0 = No Factory-installed OptionsA = Factory-installed EconomizerB = Oversized MotorC = Downflow Economizer and Oversized

MotorF = Trane Communications Interface (TCI)G = Downflow Economizer and TCI

Digit 12- Service Digit

Page 12: Cat

12 RT-PRC002-EN

GeneralData

(3, 4 , 5 Ton)Standard Efficiency

Table GD-1 — General Data

3 Ton Downflow Units 4 Ton Downflow and Horizontal Units 5 Ton Downflow and Horizontal UnitsTCD036C1, C3, C4 TCR048C1 TCR048C3, C4, CW TCR060C1 TCR060C3, C4, CW

Cooling Performance1

Gross Cooling Capacity 37,400 49,900 48,900 64,000 62,500SEER2 10.00 10.007 10.007 9.85 10.00Nominal CFM / ARI Rated CFM 1,200/1,200 1,600/1,600 1,600/1,600 2,000/2,000 2,000/2,000ARI Net Cooling Capacity 36,000 48,000 47,000 61,500 60,000System Power (KW) 4.016 5.34 5.26 6.95 6.71

CompressorNo./Type 1/Climatuff® 1/Climatuff 1/Climatuff 1/Climatuff 1/Climatuff

Sound Rating (BELS)3 8.2 8.6 8.6 8.6 8.6Outdoor Coil — Type Hi-Performance Hi-Performance Hi-Performance Hi-Performance Hi-Performance

Tube Size (in.) O.D. .375 .375 .375 .375 .375Face Area (sq ft) 5.87 7.43 5.83 11.32 9.76Rows/FPI 2/16 2/16 2/16 2/16 2/16

Indoor Coil — Type Hi-Performance Hi-Performance Hi-Performance Hi-Performance Hi-PerformanceTube Size (in.) .375 .375 .375 .375 .375Face Area (sq ft) 3.67 4.83 4.83 6.33 6.33Rows/FPI 2/15 2/15 2/15 2/15 2/15Refrigerant Control Short Orifice Short Orifice Short Orifice Short Orifice Short OrificeDrain Connection No./Size (in.) 1/¾ PVC 1/¾ PVC 1/¾ PVC 1/¾ PVC 1/¾ PVC

Outdoor Fan — Type Propeller Propeller Propeller Propeller PropellerNo. Used/Diameter (in.) 1/24 1/24 1/24 1/24 1/24Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 Direct/1CFM 3,150 3,940 3,630 4,900 4,270No. Motors/HP 1/.25 1/.33 1/.33 1/.50 1/.40Motor RPM 850 850 1,075 975 1,075

Indoor Fan — Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal FC CentrifugalNo. Used 1 1 1 1 1Diameter x Width (in.) 9 x 9 12 x 9 12 x 9 12 x 9 12 x 9Drive Type/No. Speeds Direct/2 Direct/2 Direct/2 Direct/2 Direct/2No. Motors 1 1 1 1 1Motor HP (Standard/Oversized) .33/.40 .50/.75 .50/.75 .60/.75 .60/.75Motor RPM(Standard/Oversized) 1075/1400 850/1040 850/1040 850/1040 850/1040Motor Frame Size(Standard/Oversized) 48/48 48/48 48/48 48/48 48/48

Filters — Type/Furnished? Throwaway/Yes Throwaway/Yes Throwaway/Yes Throwaway/Yes Throwaway/Yes(No.) Size Recommended (in.) (2) 20 x 25 x 1 (2) 20 x 25 x 15 (2) 20 x 25 x 15 (2) 20 x 25 x 1 (2) 20 x 25 x 1

Refrigerant Charge (Lbs of R-22)4 5.6 6.6 5.6 8.4 7.9

NOTES:1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is

net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipmentcertification program, which is based on ARI Standard 210/240.

2. SEER is rated at ARI conditions and in accordance with DOE test procedures.3. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.5. TCH048 models require (2) 16 x 25 x 1 filters6. TCD036C3, C4 system power KW 3.99.6. Hoizontal models have 8.95 SEER.

RIndicates both downflow and horizontal units.

Page 13: Cat

RT-PRC002-EN 13

GeneralData

(6¼, 7½ Ton)Standard Efficiency

Table GD-2 — General Data

6¼ Ton Downflow and Horizontal Units 7½ Ton Downflow and Horizontal UnitsSingle Compressor Dual Compressor

TCR075C3, C4, CW TCR090C3, C4, CW TCR090D3, D4, DWCooling Performance1

Gross Cooling Capacity 75,000 92,000 90,000EER2 9.00 9.00 9.00Nominal CFM / ARI Rated CFM 2,500/2,188 3,000/2,625 3,000/2,625ARI Net Cooling Capacity 72,000 88,000 86,000Integrated Part Load Value3 — — 9.40System Power (KW) 8.00 9.78 9.56

CompressorNo./Type 1/Climatuff® 1/Trane H 2/Climatuff

Sound Rating (BELS)4 8.8 8.8 8.8Outdoor Coil — Type Hi-Performance Hi-Performance Hi-Performance

Tube Size (in.) O.D. .375 .375 .375Face Area (sq ft) 11.32 12.09 14.00Rows/FPI 2/16 2/16 2/16

Indoor Coil — Type Hi-Performance Hi-Performance Hi-PerformanceTube Size (in.) .375 .375 .375Face Area (sq ft) 7.00 7.88 7.88Rows/FPI 2/15 3/15 2/15Refrigerant Control Short Orifice Short Orifice Short OrificeDrain Connection No./Size (in.) 1/¾ PVC 1/¾ PVC 1/¾ PVC

Outdoor Fan — Type Propeller Propeller PropellerNo. Used/Diameter (in.) 1/24 1/24 1/24Drive Type/No. Speeds Direct/1 Direct/1 Direct/1CFM 4,870 5,450 5,620No. Motors/HP 1/.50 1/.50 1/.50Motor RPM 1,075 1,075 1,075

Indoor Fan — Type FC Centrifugal FC Centrifugal FC CentrifugalNo. Used 1 1 1Diameter x Width (in.) 12 x 9 12 x 9 12 x 9Drive Type/No. Speeds Belt/1 Belt/1 Belt/1No. Motors 1 1 1Motor HP (Standard/Oversized) 1.0/2.0 1.0/2.0 1.0/2.0Motor RPM (Standard/Oversized) 1,725/1,725 1,725/1,725 1,725/1,725Motor Frame Size (Standard/Oversized) 56/56 56/56 56/56

Filters — Type/Furnished? Throwaway/Yes Throwaway/Yes Throwaway/Yes(No.) Size Recommended (in.) (3) 16 x 25 x 1 (3) 16 x 25 x 1 (3) 16 x 25 x 1

Refrigerant Charge (Lbs of R-22)5 9.1 10.6 6.3/Circuit

NOTES:1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is

net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipmentcertification program, which is based on ARI Standard 340/360-93.

2. EER is rated at ARI conditions and in accordance with DOE test procedures.3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at

ARIrated cfm.

4. Sound Rating shownis tested in accordance with ARI Standard 270 or 370.5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

RIndicates both downflow and horizontal units.

Page 14: Cat

14 RT-PRC002-EN

(8½, 10 Ton)Standard Efficiency

GeneralData

Table GD-3 — General Data

8½ Ton Downflow and Horizontal Units 10 Ton Downflow and Horizontal UnitsTCR102C3, C4, CW TCR120C3, C4, CW

Cooling Performance1

Gross Cooling Capacity 107,000 125,000EER2 9.2 9.26

Nominal CFM / ARI Rated CFM 3,400/3,000 4,000/3,500ARI Net Cooling Capacity 102,000 118,000Integrated Part Load Value3 9.4 9.16

System Power (KW) 11.09 12.836

CompressorNo./Type 2/Climatuff® 2/ClimatuffSound Rating (BELS)4 9.2 9.2Outdoor Coil — Type Hi-Performance Hi-Performance

Tube Size (in.) O.D. .375 .375Face Area (sq ft) 16.03 18.67Rows/FPI 2/16 2/16

Indoor Coil — Type Hi-Performance Hi-PerformanceTube Size (in.) .375 .375Face Area (sq ft) 10.50 10.50Rows/FPI 2/15 3/15Refrigerant Control Short Orifice Short OrificeDrain Connection No./Size (in.) 1/0.75 PVC 1/0.75 PVC

Outdoor Fan — Type Propeller PropellerNo. Used/Diameter (in.) 1/26 1/26Drive Type/No. Speeds Direct/1 Direct/1CFM 7,000 7,700No. Motors/HP 1/1.0 1/1.0Motor RPM 1,125 1,125

Indoor Fan — Type FC Centrifugal FC CentrifugalNo. Used 1 1Diameter x Width (in.) 15 x 11 15 x 11Drive Type/No. Speeds Belt/1 Belt/1No. Motors 1 1Motor HP (Standard/Oversized) 2.0/3.0 3.0/5.0Motor RPM (Standard/Oversized) 1,740/1,740 1,740/3,450Motor Frame Size (Standard/Oversized) 145T/145T 145T/145T

Filters — Type/Furnished? Throwaway/Yes Throwaway/Yes(No.) Size Recommended (in.)Downflow (2) 20 x 20 x 2, (2) 16 x 20 x 2 (2) 20 x 20 x 2, (2) 16 x 20 x 2Horizontal (2) 20 x 25 x 2, (2) 16 x 25 x 2 (2) 20 x 25 x 2, (2) 16 x 25 x 2

Refrigerant Charge (Lbs of R-22)5 7.1/Circuit 8.5/Circuit

NOTES:1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is

net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipmentcertification program, which is based on ARI Standard 340/360-93.

2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at

ARI rated cfm.4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.6. Horizontal models EER 9.4, IPLV 9.3, system power KW 12.55.

RIndicates both downflow and horizontal units.

Page 15: Cat

RT-PRC002-EN 15

(12½, 15 Ton)Standard Efficiency

GeneralData

12½ Ton Downflow and Horizontal Units 15 Ton Downflow and Horizontal UnitsTCR150C3, C4, CW TCR180B3, B4, BW

Cooling Performance1

Gross Cooling Capacity 150,000 180,000EER2 9.2 9.06

Nominal CFM / ARI Rated CFM 5,000/4,400 6,000/5,300ARI Net Cooling Capacity 142,000 170,000Integrated Part Load Value3 8.9 8.9System Power (KW) 15.44 18.906

CompressorNo./Type 2/Climatuff® Scroll 2/Trane 3-D® Scroll/Climatuff® Scroll

Sound Rating (BELS)4 9.2 9.2Outdoor Coil — Type Hi-Performance Hi-Performance

Tube Size (in.) O.D. .375 .375Face Area (sq ft) 23.93 24.18Rows/FPI 2/16 2/16

Indoor Coil — Type Hi-Performance Hi-PerformanceTube Size (in.) .375 .375Face Area (sq ft) 12.637 17.50Rows/FPI 3/15 2/15Refrigerant Control Short Orifice Short OrificeDrain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT

Outdoor Fan — Type Propeller PropellerNo. Used/Diameter (in.) 1/26 2/26Drive Type/No. Speeds Direct/1 Direct/1CFM 7,800 10,800No. Motors/HP 1/1.00 2/.50Motor RPM 1,125 1,100

Indoor Fan — Type FC Centrifugal FC CentrifugalNo. Used 1 1Diameter x Width (in.) 15 x 15 15 x 15Drive Type/No. Speeds Belt/1 Belt/1No. Motors 1 1Motor HP (Standard/Oversized) 3.0/5.0 3.0/5.0Motor RPM (Standard/Oversized) 1,740/3,450 1,740/3,450Motor Frame Size (Standard/Oversized) 145T/145T 145T/145T

Filters — Type/Furnished? Throwaway/Yes Throwaway/Yes(No.) Size Recommended (in.)Downflow (3) 20 x 20 x 2, (3) 16 x 20 x 2 (2) 20 x 20 x 2, (4) 20 x 25 x 2Horizontal (4) 20 x 25 x 2 (2) 20 x 20 x 2, (4) 20 x 25 x 2

Refrigerant Charge (Lbs of R-22)5

Downflow 8.4/9.1/Circuit 13.4/7.7/CircuitHorizontal 8.6/Circuit 13.4/7.7/Circuit

NOTES:1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is

net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipmentcertification program, which is based on ARI Standard 340/360-93.

2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at

ARI rated cfm.4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.6. Horizontal models EER 9.1, system power KW 18.68.7. Face area for Indoor Coil on horizontal models is 12.36.

RIndicates both downflow and horizontal units.

Table GD-4 — General Data

Page 16: Cat

16 RT-PRC002-EN

(17½, 20, 25 Ton)Standard Efficiency

GeneralData

Table GD-5 — General Data

17½ Ton 20 Ton 25 TonDownflow and Horizontal Units Downflow and Horizontal Units Downflow and Horizontal Units

TCR210C3, C4, CW TCR240B3, B4, BW TCR300B3, B4, BWCooling Performance1

Gross Cooling Capacity 208,000 246,000 290,000EER2 8.8 9.2 9.7Nominal CFM / ARI Rated CFM 7,000/5,800 8,000/7,000 10,000/8,750ARI Net Cooling Capacity 192,000 232,000 272,000Integrated Part Load Value3 8.5 9.3 9.8System Power (KW) 21.81 25.22 28.05

CompressorNo./Type 2/Trane 3-D® Scroll/Climatuff® Scroll 2/Trane 3-D®Scroll 2/Trane 3-D Scroll

Sound Rating (BELS)4 9.4 9.4 9.4Outdoor Coil — Type Hi-Performance Hi-Performance Hi-Performance

Tube Size (in.) O.D. .375 .375 .375Face Area (sq ft) 28.21 32.57 36.43Rows/FPI 2/16 2/16 2/16

Indoor Coil — Type Hi-Performance Hi-Performance Hi-PerformanceTube Size (in.) .375 .375 .375Face Area (sq ft) 17.50 26.00 26.00Rows/FPI 3/15 2/15 3/15Refrigerant Control Short Orifice Short Orifice Short OrificeDrain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT 1/1.00 NPT

Outdoor Fan — Type Propeller Propeller PropellerNo. Used/Diameter (in.) 2/26 2/26 2/28Drive Type/No. Speeds Direct/1 Direct/1 Direct/1CFM 14,100 14,800 16,700No. Motors/HP 2/1.0 2/1.0 2/1.0Motor RPM 1,125 1,125 1,125

Indoor Fan — Type FC Centrifugal FC Centrifugal FC CentrifugalNo. Used 1 1 1Diameter x Width (in.) 15 x 15 18 x 18 18 x 18Drive Type/No. Speeds Belt / 1 Belt / 1 Belt / 1No. Motors 1 1 1Motor HP (Standard/Oversized) 5.0/7.5 5.0/7.5 7.5/NAMotor RPM (Standard/Oversized) 3,450/3,470 3,450/3,470 3,470/NAMotor Frame Size (Standard/Oversized) 145T/184T 145T/184T 184T/NA

Filters — Type/Furnished? Throwaway/Yes Throwaway/Yes Throwaway/Yes(No.) Size Recommended (in.)Downflow (2) 20 x 20 x 2, (4) 20 x 25 x 2 (4) 20 x 20 x 2, (4) 20 x 25 x 2 (4) 20 x 20 x 2, (4) 20 x 25 x 2Horizontal (2) 20 x 20 x 2, (4) 20 x 25 x 2 (8) 20 x 25 x 2 (8) 20 x 25 x 2

Refrigerant Charge (Lbs of R-22)5 14.0/8.5/Circuit6 13.8/Circuit 17.0/Circuit

NOTES:1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is

net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. 17½ and 20 ton model ratings shown are certified in accordancewith the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARIStandard 340/360-93.

2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at

ARI rated cfm.4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.6. Refrigerant charge for horizontal models is 14.4/8.7 per circuit.

RIndicates both downflow and horizontal units.

Page 17: Cat

RT-PRC002-EN 17

GeneralData

(3, 4, 5, 6, 7 Ton)High Efficiency

Table GD-6 — General Data

3 Ton 4 Ton 5 Ton 6 Ton 7 TonDownflow Units Downflow and Horizontal Units Downflow and Horizontal UnitsTCR037C3,C4 TCR049C3,C4 TCR061C3,C4 TCR074C3,C4 TCR086C3,C4

Cooling Performance1

Gross Cooling Capacity 42,400 51,400 60,500 72,000 82,000SEER / EER2 12.00/— 12.00/— 12.00/— —/10.00 —/9.50

Nominal CFM / ARI Rated CFM 1,200/1,200 1,600/1,600 2,000/2,000 2,500/2,188 2,500/2,188ARI Net Cooling Capacity 41,000 49,500 58,000 68,000 78,000System Power (KW) 3.78 4.61 5.38 6.80 8.21

CompressorNo./Type 1/Climatuff® 1/Climatuff 1/Climatuff 1/Climatuff 1/Climatuff

Sound Rating (BELS)3 8.2 8.2 8.2 8.2 8.8Outdoor Coil — Type Hi-Performance Hi-Performance Hi-Performance Hi-Performance Hi-Performance

Tube Size (in.) O.D. 0.375 0 .375 0 .375 0.375 0.375Face Area (sq ft) 11.32 11.32 12.09 11.32 14.00Rows/FPI 2/16 2/16 2/16 2/16 2/16

Indoor Coil — Type Hi-Performance Hi-Performance Hi-Performance Hi-Performance Hi-PerformanceTube Size (in.) 0.375 0.375 0.375 0.375 0.375Face Area (sq ft) 6.33 6.33 7.00 7.88 7.88Rows/FPI 2/15 3/15 3/15 3/15 3/15Refrigerant Control Short Orifice Short Orifice Short Orifice Short Orifice Short OrificeDrain Connection No./Size (in.) 1 / ¾ PVC 1/¾ PVC 1/¾ PVC 1/¾ PVC 1/¾ PVC

Outdoor Fan — Type Propeller Propeller Propeller Propeller PropellerNo. Used/Diameter (in.) 1/24 1/24 1/24 1/24 1/24Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 Direct/1CFM 4,100 4,100 4,150 4,100 5,620No. Motors/HP 1/.25 1/.25 1/.25 1/.25 1/.50Motor RPM 850 850 850 850 1,075

Indoor Fan — Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal FC CentrifugalNo. Used 1 1 1 1 1Diameter x Width (in.) 9 x 9 12 x 9 12x 9 12 x 9 12 x 9Drive Type/No. Speeds Direct/2 Direct/2 Direct/2 BELT/1 BELT/1No. Motors 1 1 1 1 1Motor HP (Standard/Oversized) .33/.40 .50/.75 .60/.75 1.0/2.0 1.0/2.0Motor RPM(Standard/Oversized) 1075/1400 850/1040 850/1040 1725/1725 1725/1725Motor Frame Size(Standard/Oversized) 48/48 48/48 48/48 56/56 56/56

Filters — Type/Furnished? Throwaway/Yes Throwaway/Yes Throwaway/Yes Throwaway/Yes Throwaway/Yes(No.) Size Recommended (in.) (2) 20 x 25 x 1 (2) 20 x 25 x 1 (3) 16 X 25 X 1 (3)16 X 25 X 1 (3) 16 X 25 X 1

Refrigerant Charge (Lbs of R-22)4 8.3 8.9 10.2 10.0 11.6

NOTES:1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is

net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. 3 - 5 ton models are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240. 6 and 7 ton models are certified in accordance with the Unitary Large Equipmentcertification program, which is based on ARI Standard 340/360-93.

2. EER and SEER are rated at ARI conditions and in accordance with DOE test procedures.3. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

RIndicates both downflow and horizontal units.

Page 18: Cat

18 RT-PRC002-EN

(7½, 8½, 10, 12½, Ton)High Efficiency

GeneralData

7½ Ton 8½ Ton 10 Ton 12½ TonDownflow and Horizontal Models Downflow and Horizontal Models

TCR091D3, D4 TCR103C3,C4,CW TCR121C3,C4,CW TCR151C3,C4,CWCooling Performance1

Gross Cooling Capacity 86,000 106,000 127,000 154,000EER 2 10.00 11.00 11.5 11.3Nominal CFM / ARI Rated CFM 3,000/2,625 3,400/3,000 4,000/3,500 5,000/4,400ARI Net Cooling Capacity 81,000 101,000 120,000 147,000Integrated Part Load Value 3 10.10 11.9 12.4 11.5System Power KW 8.1 9.18 10.43 13.01

CompressorNo./Type 2/Climatuff® 2/Copeland Scroll 2/Climatuff 2/Copeland Scroll

Sound Rating (BELS)4 8.8 9.0 9.2 9.2Outdoor Coil — Type Hi-Performance Hi-Performance Hi-Performance Hi-Performance

Tube Size (in.) O.D. 0.375 0 .375 0 .375 0.375Face Area (sq ft) 14.00 23.93 28.21 27.12Rows/FPI 2/16 2/16 2/16 3/16

Indoor Coil — Type Hi-Performance Hi-Performance Hi-Performance Hi-PerformanceTube Size (in.) 0.375 0.375 0.375 0.375Face Area (sq ft) 7.88 12.636 17.50 17.50Rows/FPI 3/15 3/15 3/15 3/15Refrigerant Control Short Orifice Short Orifice Short Orifice Short OrificeDrain Connection No./Size (in.) 1 / ¾ PVC 1/1.0 NPT 1/1.0 NPT 1/1.0 NPT

Outdoor Fan — Type Propeller Propeller Propeller PropellerNo. Used/Diameter (in.) 1/24 1/26 2/26 2/26Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1CFM 5,620 7,100 10,800 10,400No. Motors/HP 1/.50 1/1.00 2/.50 2/.50Motor RPM 1075 1125 1100 1100

Indoor Fan — Type FC Centrifugal FC Centrifugal FC Centrifugal FC CentrifugalNo. Used 1 1 1 1Diameter x Width (in.) 12 x 9 15 x 11 15 x 15 15 x 15Drive Type/No. Speeds BELT/1 BELT/1 BELT/1 BELT/1No. Motors 1 1 1 1Motor HP (Standard/Oversized) 1.0/2.0 2.0/3.0 2.0/3.0 3.0/5.0Motor RPM(Standard/Oversized) 1725/1725 1740/1740 1740/1740 1740/3450Motor Frame Size(Standard/Oversized) 56/56 145T/145T 145T/145T 145T/145T

Filters — Type/Furnished? Throwaway/Yes Throwaway/Yes Throwaway/Yes Throwaway/Yes(No.) Size Recommended (in.) (3)16 X 25 X 1 (3)20 X 20 X 2/ (2)20 X 20 X 2/ (2)20 X 20 X 2/

(3)16 X 20 X 27 (4)20 X 25 X 2 (4)20 X 25 X 2Refrigerant Charge (Lbs of R-22) 5/Circuit 6.4/6.4 9.1/9.58 11.0/11.0 15.0/13.8

NOTES:1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is

net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipmentcertification program, which is based on ARI Standard 340/360-93.

2. EER is rated at ARI conditions and in accordance with DOE test procedures.3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb

at ARI rated cfm.4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.6. Face area for Indoor Coil on horizontal models is 12.36.7. Horizontal models have 4 - 20 x 25 x 2 filters.8. The refrigerant charge for 8½ ton horizontal models is 7.8/8.1 per circuit.

RIndicates both downflow and horizontal units.

Table GD-7 — General Data

Page 19: Cat

RT-PRC002-EN 19

GeneralData

(15, 17½, 20, 25 Ton)High Efficiency

RIndicates both downflow and horizontal units.

Table GD-8 — General Data

15 Ton 17½ Ton 20 Ton 25 TonDownflow and Horizontal Models

TCR181C3,C4,CW TCR211C3,C4,CW TCR241C3,C4,CW TCR301C3,C4,CWCooling Performance1

Gross Cooling Capacity 189,000 220,000 268,000 300,000EER 2 11.5 11.0 10.6 10.4Nominal CFM / ARI Rated CFM 6,000/5,300 7,000/6,200 8,000/7,000 10,000/8,750ARI Net Cooling Capacity 180,000 208,000 250,000 278,000Integrated Part Load Value 3 13.3 12.0 11.2 11.0System Power KW 15.65 18.91 23.58 26.73

CompressorNo./Type 2/Trane 3-D®Scroll/Climatuff® Scroll 2/Trane3-D Scroll/Copeland Scroll 2/Trane 3-D Scroll 2/Trane 3-D Scroll

Sound Rating (BELS)4 9.2 9.4 9.4 9.4Outdoor Coil — Type Hi-Performance Hi-Performance Hi-Performance Hi-Performance

Tube Size (in.) O.D. 0.375 0 .375 0.375 0.375Face Area (sq ft) 35.30 35.30 35.30 35.30Rows/FPI 3/16 3/16 3/16 3/16

Indoor Coil — Type Hi-Performance Hi-Performance Hi-Performance Hi-PerformanceTube Size (in.) 0.375 0.375 0.375 0.375Face Area (sq ft) 26.00 26.000 26.00 26.00Rows/FPI 3/15 4/15 4/15 4/15Refrigerant Control Short Orifice Short Orifice Short Orifice Short OrificeDrain Connection No./Size (in.) 1/1.0 NPT 1 /1.0 NPT 1/1.0 NPT 1/1.0 NPT

Outdoor Fan — Type Propeller Propeller Propeller PropellerNo. Used/Diameter (in.) 2/26 2/26 2/26 2/26Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1CFM 11,000 12,800 13,700 13,700No. Motors/HP 2/.50 2/1.00 2/1.00 2/1.00Motor RPM 1100 1125 1125 1125

Indoor Fan — Type FC Centrifugal FC Centrifugal FC Centrifugal FC CentrifugalNo. Used 1 1 1 1Diameter x Width (in.) 18 x 18 18 x 18 18 x 18 18 x 18Drive Type/No. Speeds BELT/1 BELT/1 BELT/1 BELT/1No. Motors 1 1 1 1Motor HP (Standard/Oversized) 3.0/5.0 5.0/7.5 5.0/7.5 7.5/NA

Motor RPM(Standard/Oversized) 1740/3450 3450/3470 3450/3470 3470/NAMotor Frame Size(Standard/Oversized) 145T/145T 145T/184T 145T/184T 184T/NA

Filters — Type/Furnished? Throwaway/Yes Throwaway/Yes Throwaway/Yes Throwaway/Yes(No.) Size Recommended (in.) (4/4)20 X 20 X 2/20 X 25 X 26 (4/4)20 X 20 X 2/20 X 25 X 26 (4/4)20 X 20 X 2/20 X 25 X 26 (4/4)20X20X2/20X25X26

Refrigerant Charge (Lbs of R-22) 5 / Circuit 25/13 25.7/12.5 21.8/21.8 24.5/24.5

NOTES:1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is

net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. 15, 17½ and 20 ton models are certified in accordance with theUnitary Large Equipment certification program, which is based on ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/360-93.

2. EER is rated at ARI conditions and in accordance with DOE test procedures.3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb

at ARIrated cfm.

4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.6. Horizontal models have 8 - 20 x 25 x 2 filters.

Page 20: Cat

20 RT-PRC002-EN

PerformanceData

(3, 4 Ton)Standard Efficiency

Ambient Temperature (F)85 95 105 115

Enter.Dry Entering Wet Bulb (F)

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 34.5 26.9 38.8 22.1 41.3 14.6 31.7 25.3 36.6 20.9 39.7 13.6 28.6 23.5 33.5 19.4 37.6 12.4 25.5 21.8 30.1 16.6 34.9 11.180 34.9 32.0 39.0 26.1 41.6 19.8 32.2 30.4 36.8 24.9 39.9 18.7 29.3 28.7 33.7 23.3 37.8 17.4 26.2 26.2 30.2 21.5 35.0 16.0

1080 85 35.9 35.9 39.3 30.9 41.9 24.2 33.6 33.6 36.9 29.8 40.2 23.4 31.2 31.2 33.9 28.3 37.9 22.3 28.5 28.5 30.5 26.5 35.2 21.090 38.2 38.2 39.6 35.7 42.3 28.5 36.1 36.1 37.3 34.8 40.5 27.9 33.6 33.6 34.6 33.4 38.2 27.1 31.0 31.0 31.1 31.1 35.4 25.975 35.5 28.5 39.5 22.1 41.5 14.8 32.6 26.8 37.3 20.8 40.0 13.8 29.5 25.1 34.5 19.3 38.0 12.6 26.2 23.3 30.9 17.5 35.4 11.380 36.0 34.0 39.7 27.3 41.9 20.5 33.2 32.4 37.4 26.2 40.3 19.4 30.0 30.0 34.6 24.7 38.2 18.1 27.4 27.4 31.0 22.9 35.5 16.8

1200 85 37.5 37.5 40.0 32.4 42.3 26.0 35.2 35.2 37.7 31.5 40.7 24.2 32.6 32.6 34.9 30.2 38.5 23.3 29.9 29.9 31.4 28.5 35.7 22.190 39.4 39.4 40.4 37.5 42.8 29.4 37.5 37.5 38.2 36.8 41.1 29.0 35.2 35.2 35.3 35.3 38.8 28.4 32.5 32.5 32.6 32.6 35.9 27.475 36.3 30.0 39.9 22.9 41.8 15.0 33.3 28.2 37.8 21.6 40.3 14.0 30.2 26.5 35.1 20.1 38.3 12.9 26.9 24.8 31.5 18.4 35.8 11.580 37.0 36.0 40.2 28.2 42.2 21.2 33.8 33.8 38.0 27.3 40.7 20.1 31.2 31.2 35.2 26.0 38.6 18.8 28.4 28.4 31.6 24.3 35.9 17.4

1320 85 38.6 38.6 40.5 33.7 42.6 27.1 36.5 36.5 38.3 33.0 41.0 26.0 33.9 33.9 35.6 32.0 38.9 24.1 31.1 31.1 32.2 30.3 36.2 23.190 40.4 40.4 41.1 39.1 43.2 30.1 38.6 38.6 39.0 38.7 41.5 30.0 36.3 36.3 36.4 36.4 39.2 29.5 33.8 33.8 33.9 33.9 36.5 28.775 37.0 31.4 40.3 23.6 41.9 15.2 34.0 29.7 38.2 22.3 40.5 14.2 30.8 28.0 35.6 20.9 38.5 13.1 27.4 26.1 32.0 19.2 36.0 11.780 37.4 37.4 40.6 29.1 42.4 21.8 35.0 35.0 38.4 28.4 40.9 20.7 32.3 32.3 35.7 27.2 38.8 19.5 29.4 29.4 32.2 25.5 36.3 18.1

1440 85 39.5 39.5 41.0 34.9 42.9 25.8 37.5 37.5 38.8 34.4 41.3 25.4 35.0 35.0 36.2 33.5 39.2 24.9 32.1 32.1 33.0 32.1 36.5 24.090 41.2 41.2 41.6 40.5 43.5 30.8 39.4 39.4 39.5 39.5 41.8 30.8 37.3 37.3 37.3 37.3 39.6 30.5 34.8 34.8 34.9 34.9 36.9 30.0

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

Table PD-2 — Gross Cooling Capacities (MBH) 4 Ton Single Phase TCR048C1

Ambient Temperature (F)85 95 105 115

Enter.Dry Entering Wet Bulb (F)

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 45.9 35.7 51.4 29.9 54.5 19.6 42.5 33.7 48.8 28.5 52.7 18.4 38.9 31.7 45.2 26.7 50.2 17.1 35.0 29.6 41.1 24.8 47.0 15.680 46.2 42.1 51.7 34.5 54.9 26.4 42.9 40.2 49.0 33.1 53.0 25.1 39.5 38.3 45.4 31.3 50.4 23.6 35.6 35.6 41.3 29.2 47.2 21.9

1440 85 47.4 47.4 51.9 40.7 55.3 31.9 44.7 44.7 49.2 39.5 53.3 31.0 41.8 41.8 45.6 37.7 50.6 29.8 38.7 38.7 41.5 35.6 47.3 28.390 50.3 50.3 52.2 46.9 55.8 37.5 47.8 47.8 49.5 45.9 53.7 36.8 44.9 44.9 46.2 44.2 51.0 35.9 41.8 41.8 41.9 41.9 47.5 34.675 47.1 37.6 52.2 29.3 54.9 19.8 43.6 35.7 49.7 27.8 53.1 18.7 39.9 33.6 46.4 26.1 50.7 17.4 36.0 31.5 42.2 24.0 47.6 15.880 47.6 44.7 52.5 35.9 55.4 27.2 44.2 42.8 49.9 34.7 53.5 25.9 40.4 40.4 46.5 33.0 51.0 24.5 37.2 37.2 42.3 31.0 47.8 22.8

1600 85 49.4 49.4 52.8 42.5 55.8 34.3 46.6 46.6 50.1 41.6 53.9 32.0 43.6 43.6 46.7 40.0 51.3 31.0 40.4 40.4 42.6 38.0 48.0 29.790 51.9 51.9 53.2 49.1 56.5 38.6 49.6 49.6 50.6 48.4 54.4 38.2 46.9 46.9 47.5 47.2 51.7 37.5 43.6 43.6 43.7 43.7 48.3 36.475 48.2 39.5 52.8 30.3 55.2 20.1 44.6 37.5 50.3 28.8 53.5 19.0 40.8 35.4 47.2 27.1 51.1 17.7 36.8 33.3 43.0 25.1 48.1 16.180 48.8 47.2 53.1 37.1 55.7 28.0 45.4 45.3 50.6 36.1 53.9 26.8 41.8 41.8 47.3 34.7 51.5 25.3 38.6 38.6 43.1 32.6 48.3 23.7

1760 85 50.8 50.8 53.5 44.1 56.2 35.7 48.3 48.3 50.8 43.4 54.4 34.4 45.2 45.2 47.6 42.2 51.8 32.0 41.9 41.9 43.5 40.3 48.6 30.990 53.2 53.2 54.0 51.1 57.0 39.5 51.0 51.0 51.5 50.7 55.0 39.4 48.3 48.3 48.4 48.4 52.3 38.9 45.3 45.3 45.4 45.4 48.9 38.075 49.0 41.2 53.2 31.2 55.5 20.4 45.4 39.3 50.9 29.7 53.8 19.3 41.6 37.2 47.8 28.1 51.4 17.9 37.5 35.1 43.7 26.1 48.4 16.380 49.8 49.5 53.6 38.2 56.0 28.8 46.4 46.4 51.1 37.4 54.3 27.5 43.2 43.2 47.9 36.1 51.8 26.1 39.8 39.8 43.8 34.2 48.7 24.4

1920 85 51.9 51.9 54.1 45.6 56.6 34.0 49.6 49.6 51.5 45.1 54.8 33.6 46.7 46.7 48.3 44.2 52.3 32.9 43.3 43.3 44.4 42.5 49.1 31.990 54.2 54.2 54.7 52.8 57.3 40.3 52.1 52.1 52.1 52.1 55.4 40.4 49.5 49.5 49.5 49.5 52.8 40.2 46.5 46.5 46.5 46.5 49.4 39.5

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

RIndicates both downflow and horizontal units.

Table PD-1 — Gross Cooling Capacities (MBH) 3 Ton Single/Three Phase TCD036C1, C3, C4

Page 21: Cat

RT-PRC002-EN 21

(4, 5 Ton)Standard Efficiency

PerformanceData

Table PD-3 — Gross Cooling Capacities (MBH) 4 Ton Three Phase TCR048C3, C4, CW

Ambient Temperature (F)85 95 105 115

Enter.Dry Entering Wet Bulb (F)

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 45.0 35.2 50.6 29.5 54.0 19.4 41.6 33.3 47.8 28.0 51.9 18.1 38.0 31.4 44.3 26.3 49.1 16.7 34.2 29.3 40.2 24.4 45.8 15.280 45.3 41.7 50.8 34.2 54.4 26.1 42.1 39.8 48.0 32.7 52.2 24.7 38.7 37.9 44.5 30.9 49.3 23.2 35.0 35.0 40.4 28.9 46.0 21.5

1440 85 46.7 46.7 51.1 40.4 54.7 31.8 44.0 44.0 48.2 39.1 52.4 30.7 41.1 41.1 44.6 37.3 49.6 29.4 38.0 38.0 40.6 35.3 46.2 27.990 49.6 49.6 51.4 46.6 55.2 37.4 47.1 47.1 48.6 45.5 52.8 36.5 44.2 44.2 45.3 43.9 49.9 35.5 41.1 41.1 41.2 41.2 46.4 34.175 46.2 37.2 51.4 29.0 54.5 19.6 42.7 35.3 48.7 27.4 52.3 18.4 39.0 33.3 45.3 25.6 49.7 17.0 35.1 31.2 41.2 23.6 46.4 15.480 46.7 44.3 51.7 35.7 54.9 27.0 43.4 42.5 48.9 34.3 52.7 25.6 39.7 39.7 45.5 32.6 49.9 24.1 36.5 36.5 41.3 30.6 46.6 22.4

1600 85 48.7 48.7 51.9 42.3 55.3 34.0 45.9 45.9 49.1 41.2 53.1 31.7 42.9 42.9 45.7 39.6 50.2 30.6 39.7 39.7 41.7 37.7 46.8 29.290 51.2 51.2 52.4 49.0 55.9 38.5 48.9 48.9 49.7 48.0 53.6 38.0 46.1 46.1 46.2 46.2 50.6 37.1 43.0 43.0 43.1 43.1 47.1 35.575 47.2 39.1 52.0 29.9 54.8 19.9 43.7 37.1 49.3 28.4 52.7 18.7 39.9 35.1 46.1 26.7 50.1 17.3 35.9 33.0 42.0 24.7 46.9 15.780 47.9 46.8 52.3 36.9 55.3 27.8 44.3 44.3 49.6 35.8 53.2 26.4 41.2 41.2 46.2 34.3 50.4 24.9 37.9 37.9 42.1 32.3 47.1 23.3

1760 85 50.1 50.1 52.7 44.0 55.8 35.5 47.6 47.6 49.8 43.1 53.6 34.1 44.5 44.5 46.5 41.8 50.8 31.6 41.2 41.2 42.6 40.0 47.4 30.490 52.5 52.5 53.3 51.0 56.4 39.6 50.2 50.2 50.6 50.3 54.1 39.2 47.5 47.5 47.5 47.5 51.2 38.5 44.4 44.4 44.5 44.5 47.7 37.575 48.1 40.8 52.5 30.9 55.1 20.2 44.5 38.9 49.9 29.4 53.0 19.0 40.7 36.8 46.6 27.7 50.4 17.5 36.6 34.8 42.7 25.8 47.2 15.980 48.6 48.6 52.9 38.0 55.6 28.6 45.7 45.7 50.2 37.1 53.5 27.3 42.5 42.5 46.8 35.7 50.8 25.7 39.1 39.1 42.8 33.9 47.5 24.0

1920 85 51.2 51.2 53.3 45.5 56.2 34.0 48.8 48.8 50.5 44.8 54.0 33.4 45.9 45.9 47.2 43.8 51.2 32.6 42.5 42.5 43.5 42.1 47.9 31.590 53.5 53.5 54.0 52.8 56.9 40.5 51.3 51.3 51.3 51.3 54.6 40.3 48.6 48.6 48.7 48.7 51.7 39.8 45.5 45.5 45.6 45.6 48.2 39.0

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

Table PD-4 — Gross Cooling Capacities (MBH) 5 Ton Single Phase TCR060C1

Ambient Temperature (F)85 95 105 115

Enter.Dry Entering Wet Bulb (F)

CFM Bulb 6 1 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 58.9 45.9 65.7 36.5 69.6 25.3 54.8 43.6 62.8 34.6 67.8 24.0 50.4 41.3 58.4 34.7 64.9 22.6 45.8 38.8 53.2 32.4 61.0 20.880 59.4 54.1 65.9 44.4 70.1 33.8 55.5 51.9 62.9 42.7 68.1 32.4 51.3 49.6 58.6 40.6 65.1 30.8 46.4 46.4 53.5 38.1 61.2 28.9

1800 85 60.7 60.7 66.2 52.1 70.5 41.0 57.5 57.5 63.0 50.8 68.3 40.2 54.0 54.0 58.9 48.7 65.3 38.9 50.2 50.2 53.9 46.3 61.4 37.090 64.2 64.2 66.7 59.9 71.1 48.0 61.4 61.4 63.6 58.8 68.8 47.6 58.0 58.0 59.7 57.0 65.6 46.6 54.1 54.1 55.0 54.7 61.5 45.075 60.5 48.3 66.7 37.6 70.2 25.5 56.3 46.1 63.8 36.0 68.4 24.4 51.8 43.7 59.9 34.0 65.6 23.0 47.0 41.2 54.6 31.5 61.8 21.180 61.2 57.4 66.9 46.1 70.7 34.9 57.2 55.2 64.0 44.8 68.8 33.5 53.0 52.9 60.0 42.8 65.9 31.9 48.4 48.4 54.8 40.3 62.0 30.0

2000 85 63.2 63.2 67.3 54.4 71.2 42.1 60.0 60.0 64.2 53.4 69.1 41.5 56.4 56.4 60.3 51.7 66.1 40.4 52.4 52.4 55.3 49.3 62.2 38.890 66.2 66.2 67.9 62.8 71.9 49.5 63.7 63.7 65.0 62.1 69.7 49.4 60.5 60.5 61.4 60.8 66.6 48.7 56.5 56.5 56.6 56.6 62.5 47.475 61.8 50.7 67.4 38.8 70.6 25.9 57.5 48.4 64.6 37.2 68.8 24.8 53.0 46.0 60.9 35.3 66.1 23.3 48.1 43.5 55.7 32.9 62.5 21.580 62.6 60.5 67.7 47.6 71.2 35.9 58.7 58.4 64.8 46.6 69.3 34.6 54.2 54.2 61.0 44.9 66.5 33.0 50.1 50.1 55.8 42.5 62.7 31.1

2200 85 64.9 64.9 68.2 56.5 71.8 45.6 62.1 62.1 65.2 55.9 69.8 42.6 58.4 58.4 61.5 54.5 66.8 41.8 54.3 54.3 56.6 52.2 62.9 40.490 67.8 67.8 68.9 65.3 72.5 50.7 65.4 65.4 66.2 65.1 70.4 51.0 62.3 62.3 62.4 62.4 67.3 50.6 58.7 58.7 58.8 58.8 63.3 49.575 62.8 52.9 67.9 39.7 70.9 26.2 58.6 50.7 65.3 38.4 69.2 25.1 54.0 48.3 61.6 36.6 66.6 23.6 49.0 45.8 56.6 34.2 63.0 21.880 63.7 63.2 68.4 49.0 71.6 36.9 59.7 59.7 65.6 48.3 69.6 35.0 55.9 55.9 61.8 46.8 67.0 34.0 51.7 51.7 56.8 `44.5 63.3 32.2

2400 85 66.3 66.3 68.9 58.4 72.2 47.3 63.6 63.6 66.1 58.1 70.3 43.6 60.3 60.3 62.4 57.0 67.4 43.0 56.1 56.1 57.8 55.0 63.6 41.990 69.0 69.0 69.8 67.5 73.0 51.8 66.8 66.8 66.8 66.8 71.0 52.4 63.8 63.8 63.8 63.8 68.0 52.3 60.3 60.3 60.4 60.3 64.0 51.6

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

RIndicates both downflow and horizontal units.

Page 22: Cat

22 RT-PRC002-EN

PerformanceData

(5, 6¼ Ton)Standard Efficiency

Table PD-5 — Gross Cooling Capacities (MBH) 5 Ton Three Phase TCR060C3, C4, CW

Ambient Temperature (F)85 95 105 115

Enter.Dry Entering Wet Bulb (F)

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 57.5 44.8 64.1 37.4 68.0 24.7 53.5 42.6 61.2 35.8 66.2 23.5 49.2 40.3 57.0 33.9 63.4 22.0 44.7 37.9 52.1 29.3 59.6 20.380 58.0 52.8 64.4 43.3 68.5 33.0 54.2 50.7 61.4 41.7 66.5 31.6 50.1 48.4 57.3 39.6 63.5 30.0 45.3 45.3 52.2 37.2 59.8 28.2

1800 85 59.3 59.3 64.6 50.9 68.8 40.1 56.1 56.1 61.6 49.5 66.7 39.3 52.7 52.7 57.5 47.5 63.8 38.0 49.0 49.0 52.6 45.2 59.9 36.190 62.7 62.7 65.1 58.5 69.4 46.9 60.0 60.0 62.1 57.5 67.2 46.5 56.5 56.5 58.3 55.7 64.1 45.5 52.8 52.8 53.7 53.4 60.1 43.975 59.0 47.2 65.1 36.7 68.5 24.9 54.9 45.0 62.3 35.1 66.8 23.8 50.5 42.7 58.5 33.2 64.1 22.4 45.9 40.2 53.3 30.8 60.4 20.680 59.7 56.0 65.3 45.0 69.1 34.1 55.8 53.9 62.5 43.7 67.2 32.7 51.7 51.7 58.6 41.8 64.3 31.1 47.2 47.2 53.5 39.4 60.6 29.3

2000 85 61.7 61.7 65.7 53.2 69.6 42.8 58.5 58.5 62.7 52.2 67.5 40.5 55.0 55.0 58.9 50.5 64.7 39.8 51.1 51.1 54.0 48.1 60.8 38.090 64.7 64.7 66.3 61.3 70.2 48.3 62.2 62.2 63.5 60.7 68.1 48.2 59.0 59.0 59.9 59.4 65.0 47.5 55.1 55.1 55.2 55.2 61.0 46.375 60.3 49.5 65.8 37.9 68.9 25.3 56.2 47.3 63.1 36.3 67.2 24.2 51.7 44.9 59.4 34.5 64.6 22.7 46.9 42.5 54.3 32.1 61.0 21.080 61.2 59.1 66.2 46.5 69.5 35.1 57.3 57.0 63.3 45.5 67.7 33.7 52.9 52.9 59.6 43.8 64.9 32.2 48.9 48.9 54.5 41.5 61.2 30.4

2200 85 63.4 63.4 66.6 55.2 70.1 44.5 60.6 60.6 63.7 54.6 68.2 43.2 57.0 57.0 60.0 53.2 65.3 41.6 53.0 53.0 55.3 51.0 61.5 39.890 66.2 66.2 67.3 63.8 70.8 49.5 63.8 63.8 64.6 63.6 68.8 49.8 60.8 60.8 60.9 60.9 65.8 49.4 57.2 57.2 57.3 57.3 61.8 48.475 61.3 51.6 66.4 39.1 69.2 25.6 57.2 49.5 63.8 37.5 67.6 24.5 52.8 47.1 60.2 35.7 65.0 23.0 47.9 44.7 55.3 33.4 61.5 21.380 62.2 61.8 66.8 47.9 69.9 36.0 58.3 58.3 64.1 47.2 68.2 34.7 54.5 54.5 60.3 45.7 65.4 33.2 50.4 50.4 55.4 43.4 61.8 31.4

2400 85 64.7 64.7 67.3 57.0 70.5 46.2 62.1 62.1 64.5 56.8 68.7 44.8 58.8 58.8 60.9 55.7 65.9 43.3 54.7 54.7 56.4 53.7 62.1 40.990 67.4 67.4 68.2 66.0 71.3 50.6 65.2 65.2 65.2 65.2 69.4 51.2 62.3 62.3 62.3 62.3 66.4 51.1 58.9 58.9 58.9 58.9 62.5 50.4

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

Table PD-6 — Gross Cooling Capacities (MBH) 6¼ Ton Three Phase TCR075C3, C4, CW

Ambient Temperature (F)85 95 105 115

Enter.Dry Entering Wet Bulb (F)

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 70.2 55.7 77.3 45.8 81.3 29.6 65.2 53.0 73.6 43.9 78.7 28.0 60.0 50.2 68.9 41.6 75.2 26.0 54.5 47.3 63.0 38.9 70.8 24.080 70.8 66.1 77.7 53.1 81.9 40.2 66.1 63.4 73.9 51.4 79.3 38.4 61.1 60.7 69.1 49.0 75.6 36.3 55.9 55.9 63.3 46.2 71.0 34.1

2250 85 73.1 73.1 78.1 62.8 82.6 48.5 69.2 69.2 74.2 61.4 79.7 47.5 64.9 64.9 69.4 59.2 75.9 46.0 60.4 60.4 63.8 56.5 71.3 44.190 76.7 76.7 78.7 72.4 83.4 57.0 73.4 73.4 74.9 71.4 80.4 56.5 69.5 69.5 70.5 69.6 76.5 55.5 65.0 65.0 65.1 65.1 71.6 53.975 71.8 58.8 78.3 44.9 81.8 29.8 66.8 56.0 74.7 42.9 79.3 28.3 61.5 53.2 70.2 40.6 75.9 26.5 55.9 50.3 64.5 37.8 71.5 24.380 72.6 70.1 78.7 55.1 82.5 41.5 68.0 67.5 75.0 53.7 79.9 39.7 62.8 62.8 70.4 51.6 76.3 37.7 58.2 58.2 64.7 48.9 71.8 35.5

2500 85 75.4 75.4 79.2 65.5 83.2 52.7 71.8 71.8 75.4 64.5 80.5 48.9 67.6 67.6 70.8 62.8 76.8 47.7 62.9 62.9 65.3 60.2 72.2 46.190 78.8 78.8 80.0 75.7 84.2 58.6 75.6 75.6 76.4 75.2 81.3 58.5 71.8 71.8 71.9 71.9 77.4 57.9 67.5 67.5 67.6 67.6 72.6 56.775 73.1 61.5 79.0 46.5 82.2 30.3 68.1 58.9 75.6 44.5 79.8 28.8 62.7 56.0 71.1 42.1 76.4 26.9 57.0 53.1 65.6 39.5 72.1 24.780 74.1 73.7 79.5 56.9 83.0 42.8 69.4 69.4 75.9 55.9 80.4 41.0 64.9 64.9 71.3 54.1 76.9 39.0 60.1 60.1 65.8 51.5 72.5 36.8

2750 85 77.1 77.1 80.1 67.9 83.8 50.6 73.8 73.8 76.4 67.3 81.2 50.1 69.7 69.7 71.9 66.0 77.6 49.3 65.0 65.0 66.6 63.7 72.9 47.990 80.3 80.3 81.1 78.6 84.8 60.1 77.3 77.3 77.4 77.4 82.0 60.3 73.6 73.6 73.7 73.7 78.2 60.1 69.4 69.4 69.5 69.5 73.4 59.275 74.0 64.1 79.6 47.9 82.5 30.7 69.3 61.7 76.2 45.7 80.1 29.2 63.8 58.8 71.8 43.6 76.8 27.2 58.1 55.8 66.4 41.0 72.6 25.180 75.0 75.0 80.2 58.4 83.3 44.0 71.3 71.3 76.7 57.8 80.9 42.3 66.8 66.8 72.1 56.3 77.4 40.3 61.9 61.9 66.6 53.9 72.9 37.7

3000 85 78.6 78.6 80.9 70.0 84.3 51.5 75.3 75.3 77.3 69.9 81.7 51.2 71.4 71.4 72.9 68.9 78.1 50.6 66.8 66.8 67.7 67.1 73.5 49.590 81.6 81.6 82.0 81.2 85.3 61.3 78.7 78.7 78.7 78.7 82.6 61.9 75.1 75.1 75.2 75.2 78.8 62.0 70.9 70.9 71.0 71.0 74.1 61.5

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

RIndicates both downflow and horizontal units.

Page 23: Cat

RT-PRC002-EN 23

PerformanceData

(7½ Ton)Standard Efficiency

Table PD-7 — Gross Cooling Capacities (MBH) 7½ Ton Three Phase TCR090C3, C4, CW

Ambient Temperature (F)85 95 105 115

Enter.Dry Entering Wet Bulb (F)

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 86.3 68.4 95.3 55.9 100.0 36.3 79.3 64.6 90.2 53.2 96.9 34.3 72.0 60.8 83.7 50.1 92.2 31.7 64.7 57.0 75.6 46.5 86.3 29.180 87.1 81.1 95.7 65.3 101.0 49.6 80.4 77.4 90.6 63.0 97.6 47.2 72.8 72.8 84.0 59.7 92.7 44.5 66.8 66.8 75.9 55.9 86.6 41.5

2700 85 89.8 89.8 96.3 77.0 102.0 59.5 84.4 84.4 90.9 75.2 98.1 58.3 78.6 78.6 84.4 72.3 93.0 56.5 72.5 72.5 76.6 68.6 86.9 54.190 94.3 94.3 97.1 88.8 103.0 69.9 89.8 89.8 91.8 87.4 99.0 69.4 84.4 84.4 85.8 85.1 93.7 68.2 78.3 78.3 78.6 78.6 87.2 66.175 88.4 72.2 96.6 55.4 101.0 36.9 81.3 68.4 91.7 52.6 97.7 34.8 72.9 64.6 85.5 49.5 93.1 32.4 66.3 60.7 77.4 45.7 87.4 29.580 89.5 86.1 97.1 67.7 102.0 51.3 82.9 82.6 92.0 65.9 98.2 48.5 75.9 75.9 85.7 63.1 93.7 46.2 69.7 69.7 77.6 59.3 87.7 43.3

3000 85 92.7 92.7 97.7 80.3 103.0 65.1 87.9 87.9 92.5 79.1 99.2 62.7 82.0 82.0 86.2 76.8 94.2 58.7 75.7 75.7 78.6 73.2 88.0 56.690 97.0 97.0 98.7 92.8 104.0 71.8 92.7 92.7 93.8 92.2 100.0 71.8 87.6 87.6 87.7 87.7 94.9 71.2 81.8 81.8 82.0 82.0 88.5 69.775 90.0 75.6 97.5 57.3 102.0 37.5 83.1 72.1 92.8 54.5 98.3 35.4 75.5 68.2 86.7 51.4 93.8 33.0 67.9 64.3 78.8 47.8 88.2 30.180 91.3 90.4 98.1 69.8 103.0 53.0 84.8 84.8 93.2 68.6 99.0 49.4 78.6 78.6 86.9 66.1 94.3 47.5 72.2 72.2 79.1 62.6 88.6 45.0

3300 85 95.0 95.0 98.9 83.1 104.0 67.9 90.4 90.4 93.9 82.6 100.0 65.5 84.9 84.9 87.7 80.8 95.2 60.6 78.4 78.4 80.4 77.8 89.0 58.990 99.0 99.0 100.0 96.2 105.0 73.5 95.0 95.0 95.0 95.0 101.0 74.0 90.0 90.0 90.2 90.2 96.0 73.9 84.3 84.3 84.5 84.5 89.6 72.975 91.3 78.7 98.2 59.2 102.0 38.0 84.7 75.6 93.7 56.4 98.9 35.9 77.0 71.7 87.6 53.3 94.4 33.4 69.3 67.8 80.1 49.8 88.8 30.680 92.4 92.4 99.0 71.7 103.0 54.5 87.4 87.4 94.2 71.0 99.6 50.2 81.1 81.1 87.9 69.0 95.0 48.5 74.4 74.4 80.4 65.7 89.2 46.3

3600 85 96.9 96.9 99.9 85.7 104.0 70.6 92.4 92.4 95.1 85.8 101.0 62.9 87.1 87.1 89.0 84.6 95.9 62.3 80.9 80.9 81.2 81.2 89.9 61.190 101.0 101.0 101.0 99.3 106.0 75.0 96.8 96.8 96.8 96.8 102.0 75.9 91.0 92.0 92.1 92.1 96.8 76.4 86.4 86.4 86.5 86.5 90.6 75.9

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

Table PD-8 — Gross Cooling Capacities (MBH) 7½ Ton Three Phase - Dual Compressor TCR090D3, D4, DW

Ambient Temperature (F)85 95 105 115

Enter.Dry Entering Wet Bulb (F)

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 83.7 66.2 92.5 54.6 97.1 35.5 77.8 62.9 88.3 52.4 94.3 33.7 71.6 59.6 82.8 49.8 90.5 31.7 64.9 56.2 75.7 46.6 85.4 29.380 84.5 78.3 92.9 63.2 97.9 48.0 78.9 75.2 88.6 61.2 95.0 46.0 72.6 71.3 83.1 58.5 90.9 43.7 66.4 66.4 76.0 55.2 85.7 41.2

2700 85 87.0 87.0 93.4 74.4 98.6 57.7 82.3 82.3 88.9 72.9 95.5 56.6 77.3 77.3 83.4 70.4 91.3 55.0 71.9 71.9 76.5 67.2 85.9 52.990 91.4 91.4 94.2 85.7 99.6 67.6 87.6 87.6 89.8 84.6 96.4 67.1 82.9 82.9 84.2 82.2 91.9 66.1 77.4 77.4 78.4 77.9 86.4 64.375 85.8 69.8 93.7 53.7 97.7 35.8 79.8 66.5 89.7 51.3 95.0 34.1 73.4 63.2 84.4 48.7 91.3 32.1 66.6 59.7 77.5 45.4 86.3 29.780 86.9 83.0 94.2 65.5 98.5 49.5 80.8 79.3 90.0 64.0 95.8 47.6 75.2 75.0 84.6 61.6 91.8 45.3 69.1 69.1 77.7 58.4 86.7 42.8

3000 85 89.8 89.8 94.8 77.5 99.4 62.7 85.7 85.7 90.5 76.5 96.5 58.2 80.6 80.6 85.1 74.6 92.4 57.0 74.9 74.9 78.5 71.5 87.1 55.290 93.9 93.9 95.8 89.4 101.0 69.4 90.3 90.3 91.7 89.0 97.4 69.4 85.9 85.9 86.6 85.9 93.1 68.8 80.7 80.7 80.9 80.9 87.6 67.575 87.4 73.0 94.5 55.4 98.1 36.3 81.5 69.9 90.7 53.2 95.5 34.6 75.0 66.5 85.6 50.5 91.8 32.6 68.0 63.0 78.9 47.4 87.0 30.280 88.3 86.6 95.2 67.5 99.0 51.0 83.3 82.8 91.2 66.4 96.4 49.1 77.3 77.3 85.8 64.4 92.5 46.8 71.6 71.6 79.1 61.4 87.5 44.3

3300 85 92.0 92.0 95.9 80.3 100.0 62.3 88.2 88.2 91.8 79.8 97.2 61.2 83.3 83.3 86.5 78.3 93.2 58.7 77.6 77.6 80.2 75.8 88.0 57.390 95.8 95.8 97.1 92.7 101.0 70.9 92.4 92.4 93.0 91.7 98.3 71.3 88.2 88.2 88.3 88.3 94.0 71.2 83.3 83.3 83.3 83.3 88.6 70.475 88.7 76.0 95.2 57.1 98.4 36.7 83.0 73.2 91.5 54.7 95.9 35.1 76.4 69.8 86.5 52.3 92.3 33.1 69.4 66.3 80.1 49.3 87.6 30.680 90.0 89.3 96.0 69.3 99.4 52.5 85.2 85.2 92.1 68.7 96.8 50.5 79.7 79.7 86.8 67.0 93.1 48.3 73.8 73.8 80.3 64.3 88.1 45.6

3600 85 93.8 93.8 96.8 82.7 100.0 64.0 90.1 90.1 92.8 82.7 97.8 60.8 85.5 85.5 87.7 81.7 93.9 60.2 80.0 80.0 81.2 79.2 88.7 59.190 97.3 97.3 98.1 95.6 102.0 72.3 94.1 94.1 94.5 94.1 98.9 73.1 90.0 90.0 90.1 90.1 94.8 73.4 85.2 85.2 85.2 85.2 89.5 73.0

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

RIndicates both downflow and horizontal units.

Page 24: Cat

24 RT-PRC002-EN

PerformanceData

(8½, 10 Ton)Standard Efficiency

Table PD-9 — Gross Cooling Capacities (MBH) 8½ Three Phase TCR102C3, C4, CW

Ambient Temperature85 95 105 115

EnterDry Entering Wet Bulb

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Air Flow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 98.2 78.0 110.0 61.6 115.0 42.2 89.7 73.5 105.0 58.7 112.0 40.3 81.5 69.3 96.8 54.8 108.0 38.0 73.5 65.2 87.2 54.4 102.0 35.53060 80 99.0 92.2 110.0 74.7 116.0 57.0 91.0 87.9 105.0 72.4 113.0 54.4 82.5 82.5 96.9 68.5 108.0 51.9 76.2 76.2 87.4 64.1 103.0 49.1

85 102.0 102.0 111.0 87.6 116.0 67.6 96.2 96.2 105.0 85.9 113.0 66.7 89.4 89.4 97.2 82.3 109.0 65.1 82.9 82.9 88.0 78.0 103.0 62.790 108.0 108.0 112.0 101.0 118.0 78.7 103.0 103.0 106.0 99.4 114.0 78.6 96.8 96.8 96.8 96.8 109.0 77.7 89.9 89.9 90.6 89.9 103.0 75.875 101.0 82.3 111.0 63.6 116.0 42.5 92.4 77.9 107.0 61.0 113.0 40.7 83.8 73.5 99.5 57.5 109.0 38.6 75.5 69.4 89.6 53.1 104.0 36.1

3400 80 102.0 97.9 112.0 77.2 117.0 58.1 93.0 93.0 107.0 75.7 114.0 56.2 86.2 86.2 99.6 72.4 110.0 53.8 79.5 79.5 89.7 68.0 104.0 51.085 106.0 106.0 113.0 91.0 117.0 69.3 101.0 101.0 107.0 90.2 115.0 68.4 93.7 93.7 100.0 87.5 110.0 67.4 86.8 86.8 90.6 83.2 104.0 65.590 111.0 111.0 114.0 105.0 118.0 80.4 107.0 107.0 109.0 105.0 116.0 81.0 101.0 101.0 101.0 101.0 111.0 80.8 94.2 94.2 94.2 94.2 105.0 79.675 103.0 86.4 112.0 65.0 116.0 43.0 94.8 82.1 108.0 63.1 114.0 41.3 85.8 77.6 102.0 59.9 110.0 39.3 77.4 73.4 91.6 55.5 104.0 36.6

3740 80 103.0 103.0 113.0 79.4 117.0 59.0 96.8 96.8 108.0 78.6 114.0 57.0 89.5 89.5 102.0 76.0 111.0 55.5 82.6 82.6 91.7 71.6 105.0 52.885 109.0 109.0 114.0 93.9 118.0 70.8 104.0 104.0 109.0 94.0 115.0 69.9 97.6 97.6 102.0 92.3 111.0 69.3 90.2 90.2 93.0 88.2 105.0 67.990 113.0 113.0 115.0 108.0 119.0 81.9 110.0 110.0 110.0 110.0 117.0 83.0 105.0 105.0 105.0 105.0 112.0 83.4 98.1 98.1 98.0 98.0 106.0 82.875 105.0 90.0 113.0 66.2 116.0 43.5 97.0 86.1 109.0 64.9 114.0 41.9 87.7 81.5 103.0 62.1 110.0 39.8 77.6 77.6 93.2 57.8 105.0 37.2

4080 80 106.0 106.0 114.0 81.2 118.0 59.6 100.0 100.0 110.0 81.1 115.0 57.8 92.6 92.6 103.0 79.2 111.0 56.3 85.3 85.3 93.5 75.2 106.0 54.585 111.0 111.0 115.0 96.4 119.0 71.9 107.0 107.0 110.0 97.3 116.0 71.0 101.0 101.0 104.0 96.3 112.0 70.9 93.3 93.3 93.3 93.3 106.0 70.090 115.0 115.0 116.0 111.0 120.0 83.3 112.0 112.0 112.0 112.0 117.0 84.7 107.0 107.0 107.0 107.0 113.0 85.7 101.0 101.0 101.0 101.0 107.0 85.8

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Cooling Capacity3. SHC = Sensible Heat Capacity

Table PD-10 — Gross Cooling Capacities (MBH) 10 Ton Three Phase TCR120C3, C4, CW

Ambient Temperature85 95 105 115

EnterDry Entering Wet Bulb

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 115.0 96.2 129.0 74.8 136.0 49.8 106.0 91.1 123.0 70.8 132.0 47.2 95.4 85.9 113.0 66.2 126.0 44.2 85.5 80.9 101.0 63.2 118.0 40.73600 80 116.0 116.0 130.0 91.3 137.0 67.8 108.0 107.0 123.0 88.8 133.0 65.8 99.7 99.7 113.0 84.3 127.0 62.4 91.5 91.5 101.0 79.0 119.0 58.8

85 124.0 124.0 130.0 108.0 138.0 81.4 117.0 117.0 124.0 107.0 134.0 81.0 109.0 109.0 114.0 103.0 127.0 79.4 100.0 100.0 103.0 97.4 119.0 76.590 130.0 130.0 132.0 125.0 139.0 96.3 124.0 124.0 124.0 124.0 135.0 96.8 117.0 117.0 117.0 117.0 128.0 96.1 109.0 109.0 109.0 109.0 119.0 94.075 118.0 102.0 131.0 76.6 137.0 50.5 109.0 96.9 125.0 73.9 133.0 48.0 98.1 91.6 115.0 69.6 127.0 45.0 86.9 86.9 104.0 64.4 120.0 41.7

4000 80 121.0 120.0 132.0 94.8 138.0 69.2 113.0 113.0 125.0 93.3 134.0 67.9 104.0 104.0 116.0 89.4 128.0 64.8 95.6 95.6 104.0 84.2 120.0 61.485 128.0 128.0 133.0 113.0 139.0 83.4 122.0 122.0 126.0 113.0 135.0 83.3 114.0 114.0 117.0 110.0 129.0 82.6 105.0 105.0 105.0 105.0 121.0 80.590 133.0 133.0 134.0 131.0 141.0 98.9 128.0 128.0 128.0 128.0 136.0 100.0 122.0 122.0 122.0 122.0 130.0 101.0 114.0 114.0 114.0 114.0 121.0 99.375 121.0 107.0 132.0 78.6 137.0 51.2 111.0 103.0 126.0 76.8 134.0 48.8 101.0 97.2 117.0 72.8 128.0 45.9 90.0 90.0 106.0 67.7 121.0 42.5

4400 80 124.0 124.0 133.0 97.8 139.0 70.0 117.0 117.0 127.0 97.4 135.0 69.9 108.0 108.0 118.0 94.3 129.0 66.5 99.2 99.2 106.0 89.2 122.0 63.985 131.0 131.0 134.0 117.0 140.0 85.1 125.0 125.0 128.0 118.0 136.0 85.6 118.0 118.0 120.0 116.0 130.0 85.4 109.0 109.0 109.0 108.0 122.0 84.090 136.0 136.0 136.0 136.0 142.0 101.0 131.0 131.0 131.0 131.0 137.0 103.0 125.0 125.0 125.0 125.0 131.0 104.0 118.0 118.0 118.0 118.0 123.0 104.075 123.0 112.0 133.0 80.3 138.0 51.9 114.0 108.0 127.0 79.1 134.0 49.6 102.0 102.0 119.0 75.9 129.0 46.7 92.8 92.8 107.0 70.8 122.0 43.3

4800 80 127.0 127.0 134.0 101.0 139.0 70.7 121.0 121.0 128.0 101.0 136.0 71.2 112.0 112.0 120.0 98.9 130.0 68.0 102.0 102.0 108.0 94.1 122.0 65.985 133.0 133.0 135.0 121.0 140.0 86.3 128.0 128.0 130.0 122.0 137.0 87.5 121.0 121.0 121.0 121.0 131.0 87.9 112.0 112.0 112.0 112.0 123.0 87.390 137.0 137.0 137.0 137.0 142.0 103.0 133.0 133.0 133.0 133.0 138.0 106.0 128.0 128.0 128.0 128.0 132.0 108.0 120.0 120.0 120.0 120.0 124.0 109.0

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Cooling Capacity3. SHC = Sensible Heat Capacity

RIndicates both downflow and horizontal units.

Page 25: Cat

RT-PRC002-EN 25

PerformanceData

(12½, 15 Ton)Standard Efficiency

RIndicates both downflow and horizontal units.

Table PD-11 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase TCR150C3, C4, CW

Ambient Temperature85 95 105 115

EnterDry Entering Wet Bulb

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 139 116 155 89.6 161 59.5 128 110 148 85.5 158 56.9 118 105 138 80.9 152 53.8 108 99.8 127 76.1 144 50.24500 80 141 138 156 110 162 82.4 130 130 148 107 159 78.8 122 122 138 103 152 75.4 114 114 127 97.6 144 71.7

85 148 148 156 131 163 99.9 141 141 148 128 160 97.3 132 132 139 124 153 95.5 124 124 129 119 145 92.590 156 156 158 151 165 118 149 149 150 150 161 116 142 142 142 142 154 115 134 134 134 134 145 11375 142 122 157 92.5 162 60 132 117 150 89 159 57.6 121 112 141 84.6 153 54.7 111 106 130 79.9 145 51.1

5000 80 144 144 157 114 163 85.7 136 136 151 112 160 82 127 127 141 108 154 78.3 119 119 130 103 146 74.685 153 153 158 136 165 104 146 146 152 135 161 101 138 138 142 132 155 98.9 129 129 132 127 146 96.490 159 159 160 157 167 118 154 154 153 153 162 120 147 147 147 147 156 120 139 139 139 139 147 11875 145 128 158 94.4 163 60.9 135 123 152 92.3 159 58.5 124 118 143 88.1 154 55.6 113 113 132 83.4 146 51.9

5500 80 149 149 159 118 165 83.3 141 141 152 117 160 82.8 132 132 143 113 155 79.9 123 123 132 109 147 7785 156 156 160 141 167 102 150 150 153 141 162 102 142 142 145 139 156 102 134 134 134 134 148 99.990 162 162 162 162 168 120 157 157 157 157 164 123 150 150 150 150 157 124 143 143 143 143 149 12375 147 134 159 96.3 164 61.8 137 129 153 95 160 59.3 127 124 144 91.5 155 56.4 115 115 134 86.8 147 52.8

6000 80 152 152 160 121 165 84.3 144 144 154 121 161 82.9 136 136 145 118 156 81.4 127 127 134 114 148 78.985 159 159 162 145 167 104 153 153 155 146 162 105 146 146 147 145 157 105 137 137 137 137 149 10390 164 164 164 164 169 122 159 159 159 159 164 125 153 153 153 153 159 128 145 145 145 145 150 127

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Cooling Capacity3. SHC = Sensible Heat Capacity

Table PD-12 — Gross Cooling Capacities (MBH) 15 Ton Three Phase TCR180B3, B4, BW

Ambient Temperature85 95 105 115

Enter.Dry Entering Wet Bulb

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73

Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC75 164 131 184 103 195 71.5 154 125 177 99.7 190 68.9 143 120 167 94.4 183 65.4 131 114 155 88.9 174 61.4

5400 80 160 160 185 126 196 95.9 155 146 177 122 191 92.5 146 139 167 117 183 88.6 135 133 155 112 174 84.385 171 171 185 148 197 116 163 163 177 145 191 114 154 154 167 140 184 111 145 145 155 135 174 10790 181 181 186 170 199 135 174 174 174 174 193 134 166 166 169 159 185 131 157 157 159 153 175 12875 169 138 187 107 196 72.4 158 132 179 103 191 69.7 146 126 170 98.3 184 66.2 135 120 158 92.9 176 62.3

6000 80 166 166 187 131 197 98.3 161 154 180 128 193 95.5 151 147 170 123 185 91.6 140 140 158 118 176 87.385 177 177 188 154 199 118 170 170 180 152 194 117 161 161 171 148 186 114 152 152 159 143 177 11190 186 186 186 186 201 139 180 180 179 179 195 138 172 172 174 167 188 136 163 163 164 162 178 13475 172 144 188 110 198 73.5 161 139 182 107 193 70.7 150 133 172 102 186 67.3 133 133 161 96.6 177 63.3

6600 80 175 167 190 135 199 99.8 165 161 182 132 193 97.3 155 155 173 128 186 94.2 145 145 161 123 178 90.285 182 182 191 159 201 121 175 175 183 158 195 119 167 167 174 155 188 117 157 157 157 157 179 11490 190 190 190 190 203 142 184 184 186 178 197 142 176 176 178 174 190 141 168 168 168 168 180 13975 175 150 190 112 199 74.5 164 145 183 110 194 71.7 153 139 174 105 187 68.3 137 137 163 100 178 64.2

7200 80 178 173 191 138 200 102 170 168 184 136 195 98.8 159 159 175 133 188 96 149 149 163 129 179 92.585 186 186 193 164 202 124 179 179 185 163 197 122 171 171 171 171 190 120 162 162 162 162 180 11890 193 193 195 185 204 145 188 188 189 183 199 145 180 180 181 180 191 145 172 172 172 172 181 145

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

Page 26: Cat

26 RT-PRC002-EN

PerformanceData

(17½, 20 Ton)Standard Efficiency

RIndicates both downflow and horizontal units.

Table PD-14 — Gross Cooling Capacities (MBH) 20 Ton Three Phase TCR240B3, B4, BW

Ambient Temperature (F)85 95 105 115

Enter.Dry Entering Wet Bulb (F)

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 228 183 249 141 260 95.9 209 173 241 135 260 92.7 190 162 222 126 253 87.6 170 152 200 115 235 79.680 230 216 250 171 263 130 212 207 242 168 262 126 193 193 222 159 253 120 177 177 200 148 235 112

7200 85 237 237 252 201 267 149 224 224 242 201 263 156 208 208 223 192 254 153 192 192 202 181 235 14590 248 248 254 231 270 175 240 240 245 233 265 186 224 224 228 226 254 185 208 208 208 208 235 17775 233 192 251 145 262 96.7 215 183 246 141 262 93.9 195 172 227 132 256 89.3 175 162 204 121 239 81.480 236 228 253 177 265 132 217 217 246 177 264 131 201 201 228 168 257 125 184 184 205 157 240 117

8000 85 244 244 255 209 268 159 234 234 247 211 266 161 218 218 229 204 257 160 200 200 207 194 240 15390 254 254 258 240 271 187 248 248 250 246 268 192 234 234 234 234 258 194 217 217 217 217 241 18875 237 200 254 148 264 98.1 220 192 249 146 264 95.5 199 182 232 138 258 90.8 179 171 208 127 243 83.380 240 238 256 181 267 134 225 225 249 184 265 133 208 208 232 176 259 130 191 191 209 166 244 122

8800 85 249 249 258 215 270 162 241 241 251 221 268 165 226 226 235 216 260 166 208 208 212 205 244 16090 258 258 261 248 273 190 254 254 254 254 270 198 243 243 242 242 262 202 225 225 225 225 245 19875 240 208 255 151 265 99.4 224 202 251 151 266 97.1 203 191 236 143 260 92.1 183 180 212 132 246 84.980 243 243 258 185 268 135 232 232 252 190 268 143 215 215 236 185 262 134 197 197 212 174 247 126

9600 85 253 253 260 220 271 164 247 247 254 229 270 169 233 233 239 227 263 172 214 214 217 217 247 16790 261 261 263 254 274 194 259 259 259 259 272 203 249 249 249 249 264 210 233 233 232 232 248 208

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

Table PD-13 — Gross Cooling Capacities (MBH) 17½ Ton Three Phase TCR210C3, C4, CW

Ambient Temperature85 95 105 115

EnterDry Entering Wet Bulb

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73

Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC75 189 149 213 118 227 82.8 177 142 204 113 221 79.3 163 135 192 107 213 75.1 149 128 178 100 202 70.5

6300 80 190 175 213 144 228 110 177 168 204 139 222 106 165 161 192 133 213 101 152 152 178 126 203 96.185 196 196 214 168 229 133 186 186 205 164 222 130 176 176 192 159 214 126 165 165 178 152 203 12290 207 207 215 193 231 155 199 199 206 190 224 153 189 189 194 185 215 150 178 178 178 178 204 14675 195 157 216 122 229 83.6 181 150 208 117 223 80.2 168 142 196 112 215 76.3 153 135 182 105 205 71.6

7000 80 196 185 217 149 230 113 183 178 208 145 224 109 169 169 197 140 216 105 158 158 183 133 206 99.685 203 203 218 175 232 136 194 194 209 172 225 134 183 183 197 167 217 131 172 172 183 161 206 12790 214 214 219 201 234 159 206 206 210 199 227 158 197 197 197 197 218 156 186 186 186 186 207 15375 199 164 219 126 230 84.8 185 157 210 121 225 81.6 171 149 200 116 217 77.7 157 142 186 109 207 72.7

7700 80 200 195 220 153 231 117 187 187 211 151 225 112 176 176 200 146 218 108 164 164 186 139 208 10385 209 209 221 181 234 138 201 201 212 179 228 137 190 190 201 175 219 135 179 179 187 169 209 13190 219 219 223 209 236 162 212 212 214 208 230 162 203 203 203 203 221 161 193 193 192 192 210 15975 202 170 220 129 231 86.1 189 164 213 125 226 82.9 175 156 202 120 218 78.7 160 149 189 113 209 73.8

8400 80 203 203 222 157 232 118 193 193 214 155 227 114 181 181 203 151 219 110 170 170 189 145 210 10685 214 214 223 186 234 143 206 206 215 186 229 140 196 196 204 183 221 138 185 185 190 178 211 13590 223 223 225 215 238 166 216 216 216 216 232 166 208 208 208 208 223 166 198 198 198 198 213 164

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Cooling Capacity3. SHC = Sensible Heat Capacity

Page 27: Cat

RT-PRC002-EN 27

PerformanceData

(25 Ton)Standard Efficiency

Table PD-15 — Gross Cooling Capacities (MBH) 25 Ton Three Phase TCR300B3, B4, BW

Ambient Temperature (F)85 95 105 115

Enter.Dry Entering Wet Bulb (F)

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 266 224 299 174 319 118 247 215 285 167 309 113 228 205 266 172 297 108 209 196 244 163 280 99.980 270 268 300 215 321 161 252 252 285 209 311 155 237 237 266 200 297 149 221 221 244 190 280 142

9000 85 286 286 301 255 323 196 272 272 286 250 312 194 256 256 267 242 298 189 240 240 246 233 281 18390 301 301 304 295 326 232 289 289 289 289 314 231 275 275 275 275 300 229 259 259 259 259 282 22475 272 237 303 180 322 120 253 227 290 174 312 115 234 218 271 165 300 109 214 208 249 156 284 10280 277 277 304 223 324 171 262 262 290 219 314 161 246 246 271 211 301 155 229 229 249 201 284 147

10000 85 294 294 306 266 327 208 282 282 291 263 316 200 266 266 273 257 302 197 249 249 253 248 285 19290 308 308 310 309 329 239 297 297 297 297 318 240 284 284 284 284 304 239 268 268 268 268 286 23575 275 243 305 183 323 122 256 233 291 177 314 117 236 223 273 188 301 111 216 214 251 178 285 10380 282 282 306 227 325 174 267 267 292 223 315 162 250 250 273 216 302 157 233 233 251 206 286 150

10500 85 298 298 308 272 328 216 286 286 294 270 317 203 270 270 276 264 304 200 253 253 256 255 286 19690 312 312 311 311 330 256 301 301 301 301 320 244 288 288 288 288 306 244 273 273 272 272 288 24175 278 248 306 185 324 123 258 239 293 181 315 118 239 229 275 172 302 113 217 217 253 184 286 10480 286 286 308 231 325 160 271 271 294 228 316 163 254 254 276 221 304 160 237 237 253 212 287 153

11000 85 301 301 310 277 327 224 289 289 296 276 319 205 274 274 278 271 305 204 257 257 257 257 288 20090 314 314 314 314 330 266 304 304 304 304 321 248 291 291 291 291 307 249 276 276 276 276 289 246

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity4. Table is for 460 volt capacity. For capacity at 230 volt, multiply table capacity by 101%.

Page 28: Cat

28 RT-PRC002-EN

PerformanceData

(3, 4 Ton)High Efficiency

R Indicates both downflow and horizontal units.

Table PD-16 — Gross Cooling Capacities (MBH) 3 Ton Three Phase TCD037C3, C4

Ambient Temperature (F)85 95 105 115

Enter.Dry Entering Wet Bulb (F)

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 39.0 29.9 43.8 23.8 45.9 16.4 36.0 28.1 41.5 22.3 45.1 15.5 32.7 26.3 38.3 21.6 42.8 14.3 29.3 24.4 34.7 19.8 39.9 12.91080 80 39.2 35.3 44.0 29.0 46.3 22.0 36.2 33.5 41.6 27.6 45.3 21.0 33.1 31.7 38.4 25.9 43.0 19.6 29.9 29.9 34.8 2 4.1 40.0 18.1

85 40.0 40.0 44.2 34.0 46.6 26.5 37.5 37.5 41.7 32.8 45.5 26.0 35.0 35.0 38.5 31.1 43.2 24.8 32.3 32.3 35.0 29.3 40.2 23.390 42.5 42.5 44.4 39.1 47.1 30.9 40.2 40.2 41.9 38.0 45.8 30.8 37.6 37.6 38.9 36.4 43.3 29.7 34.9 34.9 35.5 34.7 40.3 28.475 40.2 31.6 44.5 24.6 46.3 16.6 37.0 29.9 42.3 23.3 45.6 15.8 33.7 28.0 39.4 21.7 43.4 14.6 30.2 26.1 35.7 19.9 40.6 13.2

1200 80 40.4 37.5 44.7 30.2 46.6 22.9 37.4 35.8 42.4 29.0 45.9 21.8 34.3 34.0 39.5 27.5 43.6 20.4 31.1 31.1 35.8 25.6 40.7 18.985 41.8 41.8 45.0 35.6 47.0 27.1 39.3 39.3 42.6 34.7 46.2 26.9 36.7 36.7 39.6 33.2 43.8 25.9 33.9 33.9 36.0 31.4 40.9 24.590 44.0 44.0 45.3 41.1 47.6 31.7 42.0 42.0 43.0 40.3 46.6 32.0 39.5 39.5 40.1 39.0 44.1 31.2 36.7 36.7 36.6 36.6 41.1 30.075 41.1 33.3 45.0 25.5 46.5 16.9 37.9 31.5 43.0 24.2 46.0 16.1 34.5 29.6 40.1 22.7 43.8 14.9 31.0 27.7 36.5 20.9 41.0 13.5

1320 80 41.5 39.7 45.3 31.1 47.0 23.9 38.5 38.0 43.1 30.3 46.4 22.5 35.3 35.3 40.2 28.9 44.1 21.2 32.4 32.4 36.6 27.1 41.3 19.785 43.1 43.1 45.6 37.0 47.5 27.7 40.9 40.9 43.3 36.3 46.7 27.7 38.2 38.2 40.4 35.1 44.4 26.8 35.3 35.3 36.9 33.3 41.5 25.690 45.2 45.2 46.0 42.7 48.0 32.4 43.3 43.3 43.8 42.4 47.2 33.0 40.9 40.9 40.9 40.9 44.8 32.5 38.2 38.2 38.1 38.1 41.7 31.475 41.9 34.8 45.2 25.9 46.8 17.1 38.7 33.1 43.5 25.1 46.1 16.3 35.3 31.2 40.7 23.5 44.2 15.2 31.7 29.3 37.2 21.8 41.4 13.7

1440 80 42.4 41.7 45.7 32.0 47.3 24.1 39.4 39.4 43.7 31.5 46.5 22.7 36.5 36.5 40.8 30.2 44.5 21.8 33.6 33.6 37.3 28.5 41.7 20.485 44.2 44.2 46.1 38.1 48.0 28.3 42.1 42.1 44.0 37.9 47.0 28.3 39.6 39.6 41.1 36.8 44.9 27.6 36.6 36.6 37.7 35.3 42.0 26.690 46.1 46.1 46.6 44.1 48.4 33.0 44.3 44.3 44.6 44.2 47.6 33.9 42.0 42.0 42.0 42.0 45.3 33.6 39.3 39.3 39.3 39.3 42.3 32.8

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

Table PD-17 — Gross Cooling Capacities (MBH) 4 Ton Three Phase TCR049C3, C4

Ambient Temperature85 95 105 115

Enter.Dry Entering Wet Bulb

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73

Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC75 47.6 38.7 53.0 30.0 55.7 20.2 43.9 36.6 50.4 28.4 54.3 19.1 40.0 34.5 46.6 27.6 51.9 17.8 35.9 32.3 42.2 25.6 48.5 16.1

1440 80 48.1 46.1 53.2 36.8 56.2 27.5 44.6 44.1 50.5 35.6 54.7 26.5 41.0 41.0 46.7 33.7 52.2 25.0 37.6 37.6 42.3 31.5 48.6 23.385 50.4 50.4 53.5 43.7 57.0 33.7 47.5 47.5 50.7 42.7 55.0 32.8 44.3 44.3 46.9 40.9 52.3 31.9 40.9 40.9 42.6 38.8 48.7 30.490 52.9 52.9 53.9 50.5 57.3 39.2 50.6 50.6 51.2 49.9 55.5 39.3 47.6 47.6 47.6 47.6 52.6 38.6 44.2 44.2 44.2 44.2 48.9 37.375 48.8 40.9 53.5 30.8 56.1 20.5 45.0 38.9 51.2 29.6 54.5 19.4 41.0 36.8 47.7 27.9 52.6 18.1 36.8 34.5 43.2 25.7 49.1 16.5

1600 80 49.5 49.2 53.9 38.2 56.7 28.0 46.0 46.0 51.4 37.4 54.9 27.0 42.7 42.7 47.8 35.7 52.8 26.0 39.2 39.2 43.3 33.6 49.3 24.385 52.0 52.0 54.2 45.6 57.4 34.3 49.5 49.5 51.6 45.1 55.5 33.7 46.2 46.2 48.1 43.6 53.1 33.3 42.7 42.7 43.8 41.5 49.5 32.090 54.3 54.3 54.8 52.8 57.7 40.1 52.3 52.3 52.2 52.2 56.1 40.6 49.5 49.5 49.5 49.5 53.4 40.5 46.2 46.2 46.2 46.2 49.7 39.575 49.8 43.1 53.9 31.6 56.5 20.9 46.0 41.1 51.9 30.8 54.9 19.7 42.0 38.9 48.5 29.1 53.1 18.5 37.7 36.7 44.0 27.0 49.7 16.8

1760 80 50.7 50.7 54.4 39.3 57.1 28.5 47.7 47.7 52.1 39.1 55.4 28.9 44.3 44.3 48.6 37.6 53.3 26.8 40.7 40.7 44.1 35.5 49.9 25.485 53.3 53.3 54.8 47.1 57.8 34.9 51.0 51.0 52.5 47.4 55.9 34.5 47.9 47.9 49.0 46.2 53.7 34.5 44.3 44.3 44.8 44.2 50.1 33.490 55.3 55.3 55.5 54.6 58.2 41.0 53.6 53.6 53.6 53.6 56.5 41.6 50.9 50.9 50.9 50.9 54.1 42.3 47.7 47.7 47.7 47.7 50.4 41.575 50.6 45.1 54.4 32.3 56.8 21.2 46.9 43.2 52.5 31.9 55.3 20.1 42.8 41.0 49.1 30.2 53.5 18.9 38.3 38.3 44.7 28.2 50.1 17.2

1920 80 51.9 51.9 54.9 40.4 57.5 28.8 49.2 49.2 52.8 40.6 55.7 29.2 45.7 45.7 49.2 39.4 53.8 27.5 42.0 42.0 44.9 37.4 50.3 26.285 54.2 54.2 55.4 48.5 58.2 35.5 52.2 52.2 53.2 49.4 56.3 35.3 49.3 49.3 49.8 48.5 54.3 35.6 45.8 45.8 45.8 45.8 50.7 34.790 56.0 56.0 56.0 56.0 58.6 41.9 54.7 54.7 54.7 54.7 56.9 42.7 52.1 52.1 52.1 52.1 54.7 43.8 48.9 48.9 48.9 48.9 51.0 43.3

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

Page 29: Cat

RT-PRC002-EN 29

PerformanceData

(5, 6 Ton)High Efficiency

Table PD-18 — Gross Cooling Capacities (MBH) 5 Ton Three Phase TCR061C3, C4

Ambient Temperature85 95 105 115

Enter.Dry Entering Wet Bulb

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 56.5 46.0 62.7 35.6 66.3 23.9 52.0 43.6 59.3 33.5 64.0 22.4 47.3 41.0 54.6 33.0 61.3 20.8 42.4 38.4 49.4 30.6 56.8 18.71800 80 57.0 55.0 63.0 43.9 66.8 33.4 52.8 52.6 59.5 42.2 64.4 31.2 48.5 48.5 54.8 39.8 61.5 29.4 44.5 44.5 49.7 37.3 56.9 27.3

85 59.8 59.8 63.3 52.2 67.4 39.8 56.3 56.3 59.7 50.8 64.8 39.0 52.4 52.4 55.1 48.5 61.7 37.9 48.3 48.3 50.1 46.0 57.1 35.890 62.8 62.8 63.8 60.5 68.0 47.1 59.8 59.8 60.4 59.4 65.3 46.8 56.3 56.3 56.2 56.2 62.0 46.2 52.2 52.2 52.1 52.1 57.3 44.275 57.8 48.7 63.5 36.8 66.8 24.3 53.3 46.2 60.3 35.0 64.5 22.8 48.5 43.6 55.9 32.7 62.0 21.2 43.5 41.0 50.6 30.2 57.5 19.1

2000 80 58.7 58.6 63.9 45.7 67.3 34.9 54.5 54.5 60.5 44.3 64.9 32.0 50.5 50.5 56.0 42.2 62.3 30.6 46.3 46.3 50.7 39.6 57.7 28.585 61.6 61.6 64.3 54.6 68.0 40.8 58.5 58.5 60.8 53.6 65.5 40.2 54.6 54.6 56.5 51.7 62.5 39.7 50.3 50.3 51.4 49.2 57.9 37.790 64.5 64.5 65.0 63.5 68.8 48.5 61.7 61.7 61.7 61.7 66.1 48.6 58.3 58.3 58.4 58.4 62.9 48.6 54.5 54.5 54.3 54.3 58.2 46.875 58.9 51.2 64.2 37.8 67.2 24.7 54.3 48.7 61.0 36.3 65.0 23.2 49.5 46.1 56.9 34.2 62.5 21.6 44.5 43.5 51.5 31.6 58.0 19.5

2200 80 60.0 60.0 64.6 47.3 67.8 36.0 56.4 56.4 61.3 46.3 65.4 32.7 52.3 52.3 57.0 44.5 62.9 31.8 47.9 47.9 51.6 41.9 58.3 29.785 63.1 63.1 65.1 56.8 68.7 41.8 60.1 60.1 61.7 56.3 66.1 41.3 56.5 56.5 57.7 54.9 63.3 41.2 52.2 52.2 52.6 52.4 58.6 39.490 65.8 65.8 66.0 66.0 69.3 49.7 63.2 63.2 63.2 63.2 66.8 50.2 59.9 59.9 60.1 60.1 63.7 50.8 56.1 56.1 56.2 56.2 59.0 49.275 59.8 53.5 64.7 38.7 67.5 25.0 55.3 51.2 61.6 37.5 65.3 23.6 50.5 48.6 57.7 35.6 63.0 21.9 45.2 45.2 52.2 33.0 58.5 19.8

2400 80 61.3 61.3 65.2 48.7 68.2 36.3 58.0 58.0 61.9 48.1 66.1 33.3 53.9 53.9 57.8 46.6 63.3 32.6 49.4 49.4 52.5 44.1 58.8 30.785 64.3 64.3 65.8 58.8 69.3 42.8 61.4 61.4 62.5 58.6 66.6 42.3 58.0 58.0 58.6 57.8 63.8 42.6 53.8 53.8 53.7 53.7 59.2 41.090 66.8 66.8 66.8 66.8 69.8 50.8 64.3 64.3 64.3 64.3 67.3 51.6 61.2 61.2 61.5 61.5 64.3 52.7 57.5 57. 5 57.6 57.6 59.6 51.3

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

Table PD-19 — Gross Cooling Capacities (MBH) 6 Ton Three Phase TCR074C3, C4

Ambient Temperature85 95 105 115

Enter.Dry Entering Wet Bulb

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73

Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC75 68.1 57.0 74.7 43.2 78.7 28.8 62.9 54.2 70.8 41.1 75.7 27.0 57.3 51.2 65.8 38.5 71.9 25.0 51.5 48.2 59.3 38.3 67.4 22.6

2250 80 69.1 68.4 75.0 53.4 79.4 43.0 64.0 64.0 71.0 51.8 76.1 37.7 59.4 59.4 66.0 49.5 72.3 35.8 54.5 54.5 59.5 46.4 67.6 33.585 72.2 72.2 75.5 63.7 80.7 48.8 68.6 68.6 71.3 62.5 76.8 47.1 64.0 64.0 66.4 60.4 72.7 45.9 59.1 59.1 60.2 57.5 67.8 44.390 75.5 75.5 76.3 73.9 80.8 56.9 72.2 72.2 72.2 72.2 77.4 56.7 68.2 68.2 68.2 68.2 73.1 56.0 63.6 63.6 63.5 63.5 68.1 54.975 69.5 60.2 75.5 44.5 79.3 29.1 64.3 57.4 71.7 42.8 76.3 27.4 58.7 54.4 66.8 40.3 72.5 25.4 52.7 51.3 60.5 37.4 68.2 23.1

2500 80 70.6 70.6 76.0 55.5 80.2 43.9 66.4 66.4 72.0 54.3 76.8 38.6 61.7 61.7 67.0 52.3 72.9 37.0 56.6 56.6 60.7 49.3 68.5 35.085 74.1 74.1 76.5 66.5 81.1 49.7 70.6 70.6 72.5 65.8 77.6 48.6 66.3 66.3 67.6 64.2 73.5 47.7 61.3 61.3 61.7 61.5 68.7 46.690 77.3 77.3 77.6 77.3 81.6 58.6 74.1 74.1 74.0 74.0 78.3 58.8 70.2 70.2 70.2 70.2 74.1 58.5 65.7 65.7 65.8 65.8 69.1 58.075 70.5 63.1 76.2 45.7 79.7 29.7 65.5 60.5 72.4 44.3 76.8 28.0 59.8 57.5 67.7 42.0 73.1 25.8 53.6 53.6 61.4 39.2 68.9 23.6

2750 80 72.3 72.3 76.8 57.3 80.8 44.8 68.4 68.4 72.8 56.6 77.5 39.4 63.6 63.6 67.9 54.8 73.5 38.0 58.4 58.4 61.7 52.1 69.2 36.585 75.7 75.7 77.4 69.0 81.6 50.6 72.3 72.3 73.5 68.8 78.2 49.8 68.1 68.1 68.7 67.6 74.2 49.3 63.3 63.3 63.1 63.1 69.5 48.790 78.6 78.6 78.6 78.6 82.2 60.0 75.5 75.5 75.5 75.5 79.0 60.6 71.7 71.7 71.7 71.7 74.8 60.8 67.3 67.3 67.5 67.5 69.9 61.075 71.4 65.7 76.8 46.7 80.1 30.1 66.7 63.5 73.1 45.6 77.2 28.4 60.9 60.5 68.3 43.6 73.5 26.3 55.0 55.0 62.2 40.9 69.4 24.1

3000 80 73.6 73.6 77.4 59.0 81.0 45.8 69.9 69.9 73.5 58.6 78.3 40.3 65.4 65.4 68.6 57.3 74.0 38.8 60.0 60.0 62.6 54.8 69.7 37.785 76.9 76.9 78.2 71.3 82.1 51.5 73.6 73.6 74.4 71.6 78.8 51.0 69.5 69.5 69.5 69.5 74.8 50.8 64.8 64.8 64.9 64.9 70.1 50.790 79.7 79.7 79.6 79.6 82.8 61.4 76.7 76.7 76.7 76.7 79.6 62.3 73.0 73.0 73.0 73.0 75.4 62.9 68.6 68.6 68.9 68.9 70.7 63.7

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

R Indicates both downflow and horizontal units.

Page 30: Cat

30 RT-PRC002-EN

(7, 7½ Ton)High Efficiency

PerformanceData

R Indicates both downflow and horizontal units.

Table PD-21 — Gross Cooling Capacities (MBH) 7½ Ton Three Phase TCR091D3, D4

Ambient Temperature85 95 105 115

Enter.Dry Entering Wet Bulb

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73

Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC75 80.5 66.3 89.2 50.9 93.5 34.3 74.3 62.9 84.5 48.4 90.8 32.5 67.8 59.5 78.5 45.5 86.3 30.2 61.1 56.0 71.1 45.7 80.8 27.5

2700 80 81.5 79.1 89.5 62.8 95.0 45.5 75.0 75.0 84.7 60.7 91.4 45.0 69.8 69.8 78.7 57.9 86.8 42.5 64.2 64.2 71.4 54.4 81.0 39.885 85.2 85.2 89.9 74.6 95.1 56.4 80.6 80.6 85.0 72.9 92.0 55.7 75.3 75.3 79.1 70.3 87.1 54.1 69.7 69.7 72.1 66.9 81.3 51.990 89.3 89.3 90.8 86.3 96.1 66.6 85.3 85.3 86.2 85.1 92.7 66.6 80.6 80.6 80.6 80.6 87.7 65.5 75.2 75.2 75.2 75.2 81.6 63.775 82.3 69.9 90.2 52.7 94.1 34.6 76.1 66.6 85.7 50.4 91.6 33.0 69.5 63.1 79.9 47.5 87.2 30.7 62.7 59.6 72.7 44.2 81.7 28.0

3000 80 83.1 83.1 90.7 65.2 95.3 46.5 77.9 77.9 86.0 63.6 92.1 46.0 72.5 72.5 80.1 61.0 87.7 44.2 66.7 66.7 72.9 57.7 82.0 41.585 87.7 87.7 91.3 77.8 95.8 57.6 83.4 83.4 86.5 76.7 92.9 57.4 78.3 78.3 80.7 74.6 88.2 56.1 72.5 72.5 74.0 71.4 82.4 54.390 91.6 91.6 92.4 90.2 96.8 68.2 87.8 87.8 87.8 87.8 93.8 69.0 83.2 83.2 83.1 83.1 88.8 68.4 77.9 77.9 77.9 77.9 82.8 67.075 83.8 73.3 91.1 54.1 94.5 35.2 77.6 70.1 86.7 52.3 92.1 33.5 71.0 66.6 81.0 49.5 87.8 31.2 64.1 63.1 73.9 46.2 82.4 28.6

3300 80 85.3 85.3 91.8 67.3 95.7 47.6 80.5 80.5 87.1 66.2 92.7 46.9 74.9 74.9 81.2 64.0 88.3 45.2 69.0 69.0 74.2 60.8 82.8 43.185 89.6 89.6 92.4 80.7 96.6 58.8 85.5 85.5 87.8 80.1 93.7 58.9 80.6 80.6 82.1 78.4 89.1 58.0 74.9 74.9 74.9 74.9 83.3 56.490 93.4 93.4 93.8 93.5 97.5 69.6 89.7 89.7 89.7 89.7 94.6 71.1 85.2 85.2 85.2 85.2 89.8 70.9 80.0 80.0 80.0 80.0 83.9 70.075 84.9 76.4 91.8 55.3 94.9 35.7 79.1 73.4 87.5 53.8 92.4 34.0 72.3 70.0 81.9 51.3 88.4 31.7 64.9 64.9 75.0 48.1 83.0 29.0

3600 80 87.1 87.1 92.6 69.2 96.1 48.7 82.6 82.6 88.0 68.5 93.5 47.5 77.1 77.1 82.2 66.7 89.0 46.2 71.0 71.0 75.3 63.7 83.4 44.285 91.2 91.2 93.4 83.2 97.3 60.0 87.3 87.3 88.9 83.2 94.3 60.0 82.5 82.5 83.3 82.0 89.8 59.6 76.9 76.9 76.9 76.9 84.0 58.490 94.7 94.7 94.7 94.7 98.0 71.0 91.2 91.2 91.2 91.2 95.3 72.9 86.9 86.9 86.8 86.8 90.6 73.3 81.8 81.8 81.7 81.7 84.7 72.8

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

Table PD-20 — Gross Cooling Capacities (MBH) 7 Ton Three Phase TCR086C3, C4

Ambient Temperature85 95 105 115

Enter.Dry Entering Wet Bulb

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 76.9 60.9 84.3 47.2 87.7 32.1 71.6 58.0 80.5 45.0 86.2 30.6 65.9 54.9 75.7 42.4 82.6 28.7 60.0 51.7 69.3 42.0 77.8 26.42250 80 77.4 72.1 84.6 57.6 88.5 43.4 72.3 69.2 80.7 55.8 86.8 41.8 66.9 66.2 75.8 53.3 82.9 39.6 61.3 61.3 69.6 50.3 78.0 37.2

85 79.7 79.7 85.0 67.9 89.2 54.3 75.6 75.6 81.0 66.4 87.2 51.5 71.0 71.0 76.0 64.1 83.2 50.0 66.1 66.1 69.9 61.1 78.3 47.990 83.4 83.4 85.6 78.2 89.9 60.6 80.0 80.0 81.6 77.1 87.9 61.1 75.9 75.9 76.9 75.2 83.7 60.0 71.0 71.0 71.0 71.0 78.5 58.275 78.6 64.1 85.4 48.9 88.3 32.4 73.3 61.3 81.7 46.8 86.6 31.0 67.5 58.2 77.0 44.3 83.4 29.2 61.4 55.0 70.9 41.3 78.7 26.9

2500 80 79.3 76.3 85.8 59.8 89.3 44.2 74.4 73.6 82.0 58.4 87.1 42.8 68.8 68.8 77.2 56.1 83.9 41.1 63.8 63.8 71.1 53.2 79.0 38.785 82.1 82.1 86.3 70.8 90.0 61.4 78.5 78.5 82.4 69.8 88.1 52.9 73.9 73.9 77.5 67.9 84.3 51.9 68.8 68.8 71.6 65.1 79.3 50.190 85.6 85.6 87.1 81.7 90.8 62.1 82.4 82.4 83.3 81.2 88.9 63.2 78.4 78.4 78.4 78.4 84.9 62.6 73.8 73.8 73.8 73.8 79.7 61.2 75 79.8 67.1 85.9 49.9 88.8 32.9 74.8 64.4 82.7 48.5 86.8 31.4 68.9 61.3 78.0 46.0 84.1 29.7 62.8 58.1 72.2 43.2 79.4 27.3

2750 80 80.8 80.0 86.7 61.5 89.8 44.8 76.0 76.0 83.1 60.6 87.7 45.6 71.2 71.2 78.2 58.7 84.5 42.3 66.0 66.0 72.3 56.0 79.8 40.185 84.0 84.0 87.4 73.3 90.9 54.3 80.5 80.5 83.5 72.9 88.6 54.0 76.3 76.3 78.7 71.3 85.2 53.5 71.2 71.2 73.1 68.9 80.2 52.090 87.4 87.4 88.3 84.8 91.5 63.5 84.3 84.3 84.3 84.3 89.6 64.8 80.5 80.5 80.4 80.4 85.8 65.0 75.9 75.9 75.9 75.9 80.7 64.075 80.8 69.7 86.4 50.8 89.2 33.4 76.1 67.4 83.4 49.8 87.1 31.8 70.2 64.3 78.9 47.6 84.7 30.2 64.0 61.1 73.1 44.9 80.1 27.8

3000 80 81.8 81.8 87.3 62.9 90.3 45.3 78.1 78.1 83.9 62.7 88.0 45.9 73.3 73.3 79.1 61.1 85.2 43.2 67.9 67.9 73.3 58.6 80.4 41.385 85.6 85.6 88.1 75.3 91.3 61.4 82.3 82.3 84.5 75.7 89.0 54.0 78.2 78.2 79.8 74.6 85.9 55.0 73.3 73.3 74.3 72.6 81.0 53.990 88.7 88.7 89.2 87.2 92.1 64.6 85.9 85.9 85.9 85.9 90.0 66.1 82.2 82.2 82.2 82.2 86.6 67.1 77.7 77.7 77.6 77.6 81.5 66.5

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

Page 31: Cat

RT-PRC002-EN 31

(8½ Ton)High Efficiency

PerformanceData

Table PD-22— Gross Cooling Capacities (MBH) 8½ Ton Three Phase TCD103C3, C4, CW

Ambient Temperature85 95 105 115

EnterDry Entering Wet Bulb

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73

Air Flow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC75 95.4 82.2 109.0 63.4 115.0 42.0 88.0 78.3 104.0 60.8 112.0 40.0 80.3 74.3 96.3 57.3 108.0 37.6 72.6 70.4 87.3 54.0 103.0 35.0

3060 80 97.6 97.6 109.0 78.7 116.0 57.6 91.7 91.7 104.0 76.8 113.0 56.3 85.5 85.5 96.5 73.3 109.0 53.9 79.2 79.2 87.6 69.2 103.0 51.285 105.0 105.0 110.0 94.0 117.0 70.5 99.9 99.9 105.0 92.8 114.0 69.4 93.7 93.7 97.6 89.7 109.0 68.5 87.2 87.2 89.2 85.7 103.0 66.890 111.0 111.0 112.0 109.0 119.0 83.7 107.0 107.0 107.0 107.0 115.0 83.3 102.0 102.0 102.0 102.0 110.0 83.2 95.6 95.6 95.6 95.6 104.0 82.075 98.3 87.7 110.0 65.6 116.0 42.8 90.8 83.8 106.0 63.7 113.0 40.7 82.8 79.7 98.7 60.4 109.0 38.4 74.8 74.8 89.7 56.4 104.0 35.9

3400 80 102.0 102.0 111.0 82.1 117.0 58.5 96.3 96.3 106.0 81.0 114.0 57.6 89.7 89.7 99.0 78.1 110.0 55.8 83.0 83.0 90.1 74.2 104.0 53.685 109.0 109.0 112.0 98.4 118.0 72.1 104.0 104.0 107.0 98.2 115.0 71.4 98.4 98.4 100.0 96.1 110.0 71.2 91.7 91.7 91.7 91.7 105.0 70.190 113.0 113.0 113.0 113.0 120.0 85.9 110.0 110.0 110.0 110.0 116.0 86.1 105.0 105.0 105.0 105.0 111.0 86.9 99.9 99.9 99.9 99.9 106.0 86.575 101.0 93.0 111.0 67.5 116.0 43.5 93.3 89.1 107.0 66.3 113.0 41.4 84.5 84.5 101.0 63.3 110.0 39.2 77.9 77.9 91.7 59.5 105.0 36.6

3740 80 106.0 106.0 112.0 85.0 117.0 63.0 100.0 100.0 108.0 84.8 115.0 58.6 93.6 93.6 101.0 82.7 111.0 57.4 86.5 86.5 92.4 78.9 105.0 55.485 111.0 111.0 113.0 102.0 119.0 73.3 107.0 107.0 109.0 103.0 116.0 73.1 102.0 102.0 103.0 102.0 111.0 73.4 95.7 95.7 95.7 95.7 106.0 73.090 115.0 115.0 115.0 115.0 120.0 87.8 112.0 112.0 112.0 112.0 117.0 88.6 108.0 108.0 108.0 108.0 113.0 90.1 103.0 103.0 103.0 103.0 107.0 90.575 103.0 98.0 112.0 69.0 117.0 44.1 95.7 94.3 108.0 68.5 114.0 42.2 87.6 87.6 102.0 66.3 110.0 39.9 80.6 80.6 93.4 62.5 105.0 37.4

4080 80 108.0 108.0 113.0 87.5 118.0 65.3 103.0 103.0 109.0 88.2 115.0 59.5 97.1 97.1 103.0 87.0 112.0 58.8 89.8 89.8 94.4 83.6 106.0 57.085 113.0 113.0 115.0 105.0 120.0 74.5 110.0 110.0 110.0 107.0 116.0 74.7 105.0 105.0 105.0 105.0 112.0 75.4 99.0 99.0 99.0 99.0 107.0 75.690 117.0 117.0 117.0 117.0 121.0 89.5 114.0 114.0 114.0 114.0 118.0 90.8 110.0 110.0 110.0 110.0 113.0 92.9 105.0 105.0 105.0 105.0 108.0 94.1

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Cooling Capacity3. SHC = Sensible Heat Capacity

Table PD-23 — Gross Cooling Capacities (MBH) 8½ Ton Three Phase TCH103C3, C4, CW

Ambient Temperature85 95 105 115

Enter.Dry Entering Wet Bulb

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73

Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC75 95.7 82.2 108.0 62.8 112.0 41.4 88.4 78.3 104.0 60.5 111.0 39.5 80.8 74.3 96.6 57.0 107.0 37.3 73.0 70.3 87.9 54.0 102.0 34.5

3060 80 97.7 97.7 109.0 77.8 114.0 56.1 91.9 91.9 104.0 76.6 112.0 55.5 85.8 85.8 96.7 73.1 108.0 53.6 79.4 79.4 88.2 69.1 102.0 50.785 105.0 105.0 110.0 92.9 115.0 68.3 100.0 100.0 105.0 92.5 112.0 67.8 93.9 93.9 97.7 89.5 109.0 68.0 87.4 87.4 89.6 85.6 103.0 66.190 110.0 110.0 111.0 108.0 116.0 80.6 107.0 107.0 107.0 107.0 114.0 81.6 101.0 101.0 101.0 101.0 110.0 82.6 95.5 95.5 95.5 95.5 103.0 81.375 98.6 87.6 110.0 64.8 113.0 42.0 91.1 83.7 106.0 63.4 111.0 40.3 83.4 79.7 98.8 60.1 108.0 38.0 75.0 75.0 90.2 56.2 103.0 35.3

3400 80 102.0 102.0 110.0 80.6 114.0 56.7 96.3 96.3 106.0 80.6 113.0 56.5 89.9 89.9 99.0 77.9 109.0 55.0 83.3 83.3 90.6 74.0 104.0 53.185 108.0 108.0 111.0 96.7 115.0 69.3 104.0 104.0 107.0 97.7 113.0 69.8 98.3 98.3 100.0 95.8 110.0 70.3 91.9 91.9 91.8 91.8 104.0 69.290 112.0 112.0 112.0 112.0 117.0 82.1 110.0 110.0 110.0 110.0 115.0 84.0 105.0 105.0 105.0 105.0 111.0 85.8 99.5 99.5 99.5 99.5 105.0 85.675 101.0 92.9 111.0 66.4 113.0 42.6 93.5 89.0 107.0 65.7 112.0 40.9 85.8 85.0 101.0 63.0 109.0 38.7 78.1 78.1 92.1 59.3 104.0 36.1

3740 80 106.0 106.0 111.0 83.0 114.0 62.3 100.0 100.0 107.0 84.1 113.0 57.3 93.7 93.7 101.0 82.3 110.0 56.4 86.8 86.8 92.7 78.7 104.0 54.785 110.0 110.0 112.0 99.8 116.0 70.1 107.0 107.0 109.0 102.0 114.0 71.1 102.0 102.0 103.0 101.0 111.0 72.2 95.6 95.6 95.6 95.6 105.0 72.090 114.0 114.0 114.0 114.0 117.0 83.3 112.0 112.0 112.0 112.0 115.0 86.0 108.0 108.0 108.0 108.0 112.0 88.6 102.0 102.0 102.0 102.0 106.0 89.475 103.0 97.7 111.0 67.7 113.0 43.2 95.8 94.1 108.0 67.7 112.0 41.5 87.9 87.9 102.0 65.8 109.0 39.4 80.8 80.8 93.7 62.2 105.0 36.9

4080 80 108.0 108.0 112.0 85.0 114.0 64.5 103.0 103.0 109.0 87.2 113.0 57.8 97.0 97.0 102.0 86.3 111.0 57.8 90.0 90.0 94.5 83.2 105.0 56.285 112.0 112.0 113.0 102.0 116.0 70.9 109.0 109.0 110.0 106.0 114.0 72.1 104.0 104.0 104.0 104.0 111.0 73.9 98.6 98.6 98.5 98.5 106.0 74.590 115.0 115.0 115.0 115.0 118.0 84.4 113.0 113.0 113.0 113.0 116.0 87.3 110.0 110.0 110.0 110.0 113.0 90.9 105.0 105.0 105.0 105.0 108.0 92.8

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

R Indicates both downflow and horizontal units.

Page 32: Cat

32 RT-PRC002-EN

(10, 12½ Ton)High Efficiency

PerformanceData

RIndicates both downflow and horizontal units.

Table PD-24— Gross Cooling Capacities (MBH) 10 Ton Three Phase TCR121C3, C4, CW

Ambient Temperature85 95 105 115

EnterDry Entering Wet Bulb

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 117.0 99.3 131.0 76.4 137.0 50.5 106.0 93.7 124.0 72.8 134.0 48.0 95.1 88.5 112.0 68.1 129.0 45.0 81.1 81.1 100.0 62.7 120.0 41.53600 80 119.0 119.0 131.0 93.6 139.0 68.7 110.0 110.0 125.0 91.9 136.0 67.2 101.0 101.0 113.0 86.6 130.0 64.3 92.6 92.6 101.0 81.2 120.0 60.7

85 127.0 127.0 132.0 111.0 140.0 83.6 120.0 120.0 125.0 111.0 137.0 84.3 110.0 110.0 114.0 106.0 130.0 82.5 101.0 101.0 102.0 101.0 120.0 79.590 133.0 133.0 134.0 129.0 142.0 98.8 128.0 128.0 128.0 128.0 138.0 101.0 120.0 120.0 120.0 120.0 131.0 100.0 110.0 110.0 110.0 110.0 121.0 98.475 120.0 106.0 132.0 78.6 138.0 51.3 109.0 100.0 127.0 76.2 136.0 48.9 97.8 94.8 116.0 71.5 130.0 45.9 90.6 90.6 102.0 65.8 123.0 42.7

4000 80 124.0 124.0 133.0 97.2 140.0 69.7 115.0 115.0 127.0 96.9 137.0 69.2 106.0 106.0 116.0 92.6 131.0 67.2 96.7 96.7 103.0 87.0 123.0 63.885 130.0 130.0 134.0 116.0 141.0 85.4 125.0 125.0 128.0 117.0 138.0 86.9 116.0 116.0 118.0 114.0 132.0 86.2 106.0 106.0 106.0 106.0 123.0 84.690 136.0 136.0 136.0 134.0 143.0 101.0 132.0 132.0 132.0 132.0 140.0 105.0 125.0 125.0 125.0 125.0 133.0 105.0 116.0 116.0 116.0 116.0 124.0 105.075 123.0 112.0 134.0 80.8 139.0 52.2 112.0 107.0 128.0 79.5 136.0 49.8 99.9 99.9 118.0 75.3 132.0 46.9 91.1 91.1 104.0 69.4 124.0 43.7

4400 80 127.0 127.0 135.0 100.0 141.0 75.6 120.0 120.0 129.0 102.0 138.0 70.6 110.0 110.0 119.0 98.4 133.0 69.5 100.0 100.0 105.0 92.6 125.0 66.785 133.0 133.0 136.0 120.0 142.0 87.0 128.0 128.0 130.0 123.0 139.0 89.2 121.0 121.0 121.0 121.0 133.0 89.3 110.0 110.0 110.0 110.0 125.0 89.090 138.0 138.0 138.0 138.0 144.0 104.0 134.0 134.0 134.0 134.0 141.0 108.0 129.0 129.0 129.0 129.0 134.0 110.0 121.0 121.0 121.0 121.0 126.0 111.075 125.0 118.0 135.0 82.6 140.0 53.1 115.0 113.0 130.0 82.1 137.0 50.7 103.0 103.0 120.0 78.9 132.0 47.8 94.0 94.0 106.0 72.9 125.0 44.5

4800 80 130.0 130.0 136.0 103.0 141.0 78.3 124.0 124.0 130.0 106.0 139.0 71.7 114.0 114.0 121.0 104.0 134.0 71.4 104.0 104.0 108.0 98.2 126.0 69.385 135.0 135.0 137.0 124.0 143.0 88.4 131.0 131.0 132.0 129.0 140.0 91.2 125.0 125.0 125.0 125.0 134.0 92.2 115.0 115.0 115.0 115.0 126.0 92.990 139.0 139.0 139.0 139.0 145.0 106.0 137.0 137.0 137.0 137.0 142.0 111.0 132.0 132.0 132.0 132.0 136.0 114.0 125.0 125.0 125.0 125.0 128.0 116.0

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Cooling Capacity3. SHC = Sensible Heat Capacity

Table PD-25 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase TCR151C3, C4, CW

Ambient Temperature85 95 105 115

EnterDry Entering Wet Bulb

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73

Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC75 137.0 116.0 157.0 90.2 166.0 60.8 127.0 110.0 151.0 87.1 163.0 58.5 116.0 105.0 140.0 82.3 158.0 55.8 106.0 99.7 128.0 80.6 152.0 52.8

4500 80 140.0 139.0 158.0 111.0 167.0 82.9 130.0 130.0 151.0 109.0 164.0 80.8 122.0 122.0 141.0 104.0 159.0 77.8 114.0 114.0 128.0 98.5 152.0 74.685 149.0 149.0 158.0 132.0 169.0 100.0 142.0 142.0 151.0 131.0 165.0 99.4 133.0 133.0 141.0 126.0 159.0 98.2 125.0 125.0 130.0 121.0 152.0 96.090 158.0 158.0 160.0 153.0 170.0 118.0 152.0 152.0 154.0 152.0 166.0 118.0 145.0 145.0 145.0 145.0 160.0 118.0 137.0 137.0 137.0 137.0 153.0 117.075 141.0 123.0 159.0 93.4 167.0 61.6 131.0 117.0 154.0 90.9 164.0 59.4 120.0 112.0 144.0 86.6 159.0 56.8 109.0 107.0 132.0 81.0 153.0 53.7

5000 80 145.0 145.0 160.0 116.0 168.0 84.1 136.0 136.0 154.0 114.0 165.0 82.4 128.0 128.0 144.0 110.0 161.0 80.9 119.0 119.0 132.0 105.0 154.0 77.585 155.0 155.0 161.0 138.0 170.0 103.0 148.0 148.0 155.0 138.0 166.0 102.0 140.0 140.0 145.0 135.0 161.0 102.0 131.0 131.0 134.0 129.0 154.0 100.090 162.0 162.0 163.0 160.0 172.0 121.0 157.0 157.0 157.0 157.0 168.0 122.0 151.0 151.0 151.0 151.0 163.0 123.0 143.0 143.0 143.0 143.0 155.0 122.075 145.0 129.0 161.0 95.8 168.0 62.6 134.0 124.0 156.0 94.4 165.0 60.4 123.0 119.0 147.0 90.4 161.0 57.8 112.0 112.0 135.0 85.1 154.0 54.6

5500 80 150.0 150.0 162.0 119.0 169.0 85.2 142.0 142.0 156.0 119.0 167.0 84.0 133.0 133.0 147.0 116.0 162.0 82.4 124.0 124.0 135.0 111.0 155.0 80.185 158.0 158.0 163.0 143.0 172.0 104.0 153.0 153.0 157.0 144.0 168.0 104.0 146.0 146.0 149.0 143.0 163.0 105.0 137.0 137.0 137.0 137.0 156.0 104.090 165.0 165.0 165.0 165.0 173.0 123.0 161.0 161.0 161.0 161.0 170.0 126.0 156.0 156.0 156.0 156.0 164.0 127.0 149.0 149.0 149.0 149.0 157.0 127.075 148.0 136.0 162.0 97.9 168.0 63.5 137.0 131.0 157.0 97.1 166.0 61.4 126.0 125.0 150.0 94.3 162.0 58.9 116.0 116.0 138.0 89.0 155.0 55.6

6000 80 154.0 154.0 163.0 123.0 170.0 86.2 147.0 147.0 158.0 124.0 168.0 85.8 138.0 138.0 150.0 122.0 162.0 83.3 128.0 128.0 138.0 117.0 156.0 82.285 161.0 161.0 165.0 147.0 172.0 106.0 157.0 157.0 160.0 150.0 169.0 106.0 151.0 151.0 152.0 150.0 164.0 107.0 142.0 142.0 142.0 142.0 158.0 107.090 167.0 167.0 167.0 167.0 174.0 126.0 164.0 164.0 164.0 164.0 171.0 128.0 159.0 159.0 159.0 159.0 166.0 131.0 153.0 153.0 153.0 153.0 159.0 132.0

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Cooling Capacity3. SHC = Sensible Heat Capacity

Page 33: Cat

RT-PRC002-EN 33

(15, 17½ Ton)High Efficiency

Table PD-27 — Gross Cooling Capacities (MBH)17½ Ton Three Phase TCR211C3, C4, CW

Ambient Temperature85 95 105 115

EnterDry Entering Wet Bulb

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73

Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC75 200.0 169.0 224.0 130.0 233.0 86.2 184.0 162.0 215.0 125.0 231.0 83.3 169.0 154.0 199.0 118.0 226.0 79.3 147.0 147.0 180.0 113.0 214.0 74.2

6300 80 202.0 202.0 225.0 161.0 236.0 118.0 190.0 190.0 216.0 158.0 234.0 117.0 177.0 177.0 200.0 151.0 227.0 112.0 164.0 164.0 181.0 142.0 214.0 107.085 216.0 216.0 227.0 191.0 239.0 143.0 206.0 206.0 217.0 190.0 236.0 146.0 193.0 193.0 202.0 184.0 228.0 144.0 180.0 180.0 185.0 176.0 215.0 139.090 227.0 227.0 230.0 221.0 242.0 169.0 220.0 220.0 220.0 220.0 239.0 175.0 209.0 209.0 209.0 209.0 229.0 174.0 196.0 196.0 195.0 195.0 217.0 171.075 205.0 180.0 226.0 134.0 234.0 87.6 190.0 172.0 219.0 131.0 233.0 84.8 174.0 164.0 204.0 124.0 228.0 80.8 155.0 155.0 184.0 116.0 218.0 76.0

7000 80 210.0 210.0 228.0 167.0 237.0 119.0 198.0 198.0 220.0 167.0 236.0 120.0 185.0 185.0 205.0 160.0 229.0 117.0 171.0 171.0 186.0 152.0 218.0 112.085 223.0 223.0 230.0 199.0 241.0 145.0 215.0 215.0 222.0 202.0 238.0 150.0 202.0 202.0 209.0 197.0 231.0 150.0 188.0 188.0 191.0 189.0 219.0 147.090 232.0 232.0 233.0 230.0 244.0 173.0 227.0 227.0 227.0 227.0 241.0 180.0 218.0 218.0 218.0 218.0 232.0 182.0 205.0 205.0 204.0 204.0 221.0 181.075 210.0 190.0 228.0 138.0 235.0 88.9 195.0 183.0 222.0 137.0 234.0 86.0 179.0 175.0 208.0 130.0 229.0 82.4 161.0 161.0 188.0 122.0 220.0 77.7

7700 80 217.0 217.0 231.0 173.0 239.0 120.0 206.0 206.0 223.0 174.0 237.0 121.0 192.0 192.0 209.0 169.0 231.0 121.0 178.0 178.0 190.0 161.0 221.0 116.085 228.0 228.0 232.0 206.0 242.0 148.0 221.0 221.0 226.0 211.0 240.0 153.0 210.0 210.0 214.0 209.0 234.0 156.0 196.0 196.0 195.0 195.0 222.0 154.090 235.0 235.0 235.0 235.0 245.0 176.0 232.0 232.0 232.0 232.0 243.0 185.0 224.0 224.0 224.0 224.0 235.0 189.0 213.0 213.0 212.0 212.0 224.0 191.075 214.0 200.0 230.0 141.0 236.0 90.3 200.0 193.0 224.0 141.0 235.0 87.4 181.0 181.0 211.0 136.0 230.0 83.8 166.0 166.0 191.0 128.0 222.0 79.2

8400 80 222.0 222.0 232.0 177.0 239.0 133.0 213.0 213.0 226.0 181.0 238.0 123.0 199.0 199.0 213.0 178.0 233.0 124.0 184.0 184.0 194.0 170.0 223.0 121.085 231.0 231.0 234.0 211.0 243.0 149.0 226.0 226.0 229.0 220.0 241.0 155.0 216.0 216.0 216.0 216.0 235.0 161.0 203.0 203.0 202.0 202.0 224.0 162.090 238.0 238.0 238.0 238.0 246.0 178.0 235.0 235.0 235.0 235.0 244.0 189.0 229.0 229.0 229.0 229.0 237.0 195.0 219.0 219.0 219.0 219.0 227.0 199.0

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Cooling Capacity3. SHC = Sensible Heat Capacity

RIndicates both downflow and horizontal units.

Table PD-26 — Gross Cooling Capacities (MBH) 15 Ton Three Phase TCR181C3, C4, CW

Ambient Temperature85 95 105 115

Enter.Dry Entering Wet Bulb

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 172 144 194 112 205 75.2 159 138 185 107 200 71.9 147 131 172 101 193 68 130 130 158 97 183 63.45400 80 175 169 195 138 207 103 164 162 186 134 202 99.7 153 153 173 128 194 95.4 142 142 158 122 183 90.5

85 185 185 196 164 209 126 176 176 186 161 203 124 165 165 174 156 195 122 155 155 155 155 184 11790 195 195 195 195 211 149 188 188 190 184 204 148 178 178 179 179 196 147 168 168 167 167 184 14475 177 153 197 116 207 76 164 147 189 112 202 73.2 151 140 176 106 195 69.3 138 131 162 99.8 185 64.8

6000 80 181 180 198 144 209 105 170 170 189 142 204 103 159 159 177 136 196 99.4 148 148 162 130 186 94.685 192 192 199 172 211 129 183 183 190 171 206 129 173 173 173 173 197 127 162 162 162 162 186 12490 201 201 200 200 214 153 194 194 195 194 208 155 185 185 185 185 199 154 175 175 175 175 187 15275 181 162 198 123 208 76.6 168 155 191 117 204 74.4 152 152 180 111 197 70.6 142 139 165 105 187 66.2

6600 80 186 186 200 151 210 107 177 177 192 148 206 105 166 166 180 144 198 102 154 154 166 137 188 98.685 197 197 202 179 213 131 189 189 194 180 208 132 179 179 183 173 199 132 168 168 170 166 189 12990 204 204 205 202 215 157 199 199 199 199 209 159 191 191 191 191 201 160 181 181 181 181 190 16075 184 170 200 127 209 79.1 168 168 193 121 206 76.4 156 156 182 116 198 71.9 145 145 168 110 189 67.4

7200 80 191 191 202 153 211 108 182 182 194 154 207 107 171 171 183 151 199 105 159 159 169 145 190 10285 200 200 204 185 214 134 194 194 194 194 209 136 185 185 187 181 201 135 174 174 174 174 191 13490 207 207 208 207 217 160 203 203 203 203 211 163 195 195 195 195 203 166 186 186 186 186 192 167

NOTES:1 All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

Page 34: Cat

34 RT-PRC002-EN

RIndicates both downflow and horizontal units.

Table PD-28 — Gross Cooling Capacities (MBH) 20 Ton Three Phase TCR241C3, C4, CW

Ambient Temperature (F)85 95 105 115

Enter.Dry Entering Wet Bulb (F)

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 246 205 273 158 284 105 228 196 263 152 280 101 208 186 246 145 273 96.5 191 176 222 136 261 91.57200 80 250 245 274 192 287 142 232 232 264 190 283 141 216 216 246 183 274 135 201 201 223 172 261 130

85 263 263 275 227 290 171 251 251 265 228 285 173 236 236 248 221 275 170 219 219 225 211 262 16890 274 274 278 262 293 201 266 266 268 265 288 206 254 254 254 254 277 205 239 239 237 237 262 20575 253 218 275 163 285 107 234 209 267 159 282 103 214 199 252 152 275 98.3 194 189 228 142 266 93.6

8000 80 257 257 277 199 289 144 243 243 268 199 285 143 227 227 252 194 277 140 210 210 228 184 266 13685 270 270 279 236 292 174 261 261 270 240 288 177 247 247 255 237 278 177 230 230 232 226 266 17790 280 280 282 273 295 205 274 274 274 274 291 212 264 264 264 264 280 214 250 250 248 248 267 21875 258 230 278 167 287 109 240 221 270 164 284 105 219 211 256 159 277 100 199 199 232 149 269 95.5

8800 80 264 264 280 204 290 155 252 252 271 208 287 145 236 236 257 205 279 144 218 218 233 195 269 14185 276 276 282 244 293 177 268 268 274 250 290 181 256 256 260 251 281 182 240 240 238 238 269 18590 285 285 286 281 297 209 280 280 280 280 293 217 271 271 271 271 283 221 258 258 258 258 271 22975 262 240 280 169 288 110 246 233 273 169 285 106 225 223 260 166 278 102 205 205 236 156 271 97.1

9600 80 270 270 282 209 291 161 260 260 274 215 288 147 245 245 261 215 281 147 226 226 237 205 271 14685 280 280 284 250 295 179 274 274 277 260 291 184 263 263 265 263 282 186 248 248 246 246 272 19390 288 288 288 288 298 212 284 284 284 284 294 222 276 276 276 276 285 228 264 264 265 265 275 240

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

(20, 25 Ton)High Efficiency

PerformanceData

Table PD-29 — Gross Cooling Capacities (MBH)25 Ton Three PhaseTCR301C3, C4, CW

Ambient Temperature (F)85 95 105 115

Enter.Dry Entering Wet Bulb (F)

CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73

Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC75 277 243 306 187 316 117 258 234 295 178 314 115 238 224 276 169 305 110 218 214 253 163 292 104

9000 80 284 284 307 225 321 169 269 269 295 225 317 161 252 252 277 217 307 158 235 235 254 207 293 15185 300 300 309 269 325 198 289 289 298 271 320 202 273 273 280 266 308 201 256 256 259 256 293 19890 312 312 313 312 329 236 305 305 305 305 321 240 293 293 293 293 310 245 277 277 277 277 295 24475 284 258 310 188 319 121 264 249 299 185 316 117 244 239 282 178 308 112 224 224 259 168 295 106

10000 80 294 294 310 233 323 175 280 280 300 236 319 170 263 263 283 230 309 163 245 245 260 221 296 15885 307 307 313 280 327 202 298 298 303 286 322 207 284 284 287 284 312 208 267 267 267 267 297 20890 318 318 318 318 331 241 312 312 312 312 324 248 301 301 301 301 314 255 287 287 287 287 299 25775 286 265 311 190 320 122 267 256 300 189 316 118 247 246 284 182 309 113 228 228 261 172 296 107

10500 80 297 297 312 237 324 178 285 285 302 241 320 174 267 267 285 237 310 165 249 249 262 227 298 16285 310 310 315 285 328 204 302 302 305 293 323 210 289 289 289 289 313 212 272 272 272 272 299 21390 320 320 320 320 332 244 314 314 314 314 325 251 305 305 305 305 316 260 292 292 292 292 301 26475 289 272 312 192 321 123 270 264 302 192 317 119 249 249 286 186 309 114 231 231 263 176 297 108

11000 80 300 300 313 240 324 181 289 289 304 246 321 177 272 272 287 243 311 170 253 253 265 234 299 16585 312 312 316 289 329 205 305 305 307 299 324 212 293 293 293 293 314 215 276 276 276 276 300 21790 322 322 321 321 332 246 317 317 317 317 326 255 308 308 308 308 317 265 295 295 295 295 303 270

NOTES:1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.2. MBH = Total Gross Capacity3. SHC = Sensible Heat Capacity

Page 35: Cat

RT-PRC002-EN 35

PerformanceData

RIndicates both downflow and horizontal units.

(3, 4, 5 Ton)Standard Efficiency

Table PD-30— Evaporator Fan Performance 3, 4 and 5 Ton TCD036C, TCR048C, TCR060C

External Static Pressure (Inches of Water) & Motor Power (Bhp)1

Standard Motor Oversized Motor

UnitHigh Speed Low Speed

Tons Model No. CFM ESP BHP ESP BHP ESP BHP

1000 .72 .30 .60 .28 1.48 .611100 .63 .32 .52 .30 1.34 .631200 .56 .34 .40 .33 1.16 .66

3 TCD036C1

1300 .49 .36 .25 .38 .97 .691400 .38 .38 — — .75 .731500 .27 .40 — — .50 .771300 .85 .49 .77 .37 1.62 .741400 .83 .50 .70 .39 1.53 .771500 .80 .52 .63 .42 1.46 .801600 .75 .54 .55 .44 1.39 .83

TCD048C1

1700 .71 .56 .42 .49 1.31 .861800 .65 .58 — — 1.23 .901900 .60 .60 — — 1.16 .932000 .55 .62 — — 1.08 .97

41300 .82 .46 .70 .34 1.59 .771400 .78 .48 .65 .36 1.52 .791500 .73 .49 .60 .39 1.45 .811600 .69 .50 .52 .41 1.38 .83

TCH048C1

1700 .64 .52 .44 .43 1.31 .861800 .60 .54 .32 .47 1.23 .901900 .53 .56 .16 .52 1.16 .932000 .47 .58 — — 1.08 .961700 .80 .59 .72 .48 1.40 .861800 .75 .61 .66 .50 1.32 .901900 .70 .63 .60 .52 1.25 .932000 .65 .66 .52 .55 1.19 .96

TCD060C1

2100 .60 .69 .45 .59 1.12 1.012200 .53 .71 .35 .62 1.03 1.052300 .47 .73 .23 .67 .92 1.092400 .40 .76 — — .78 1.13

51700 .75 .59 .68 .48 1.36 .861800 .71 .62 .60 .50 1.28 .901900 .66 .64 .57 .52 1.21 .932000 .60 .66 .48 .56 1.14 .97

TCH060C1

2100 .56 .68 .40 .59 1.07 1.012200 .48 .70 .29 .63 .98 1.052300 .40 .73 .17 .67 .85 1.092400 .33 .76 — — .71 1.13

Fan motor heat (MBH) = 4.39 x Fan Bhp.Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designedand tested to operate reliably and continuously at all cataloged conditions.Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisancetripping or premature motor failure. Our product’s war ranty will not be affected.

NOTE:1. Data includes pressure drop due to wet coil and filters.

Page 36: Cat

36 RT-PRC002-EN

PerformanceData

(6¼-7½ Ton)Standard Efficiency

External Static Pressure (Inches of Water)Unit .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.25 1.50

Tons Model No. CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1 HP Standard Motor & Field Supplied Low Static Drive11111 1 HP Standard Motor & Sheaves

2000 597 .39 646 .44 692 .50 739 .55 782 .60 825 .66 868 .71 907 .76 947 .81 986 .86 1082 .98 — —2250 659 .53 705 .59 745 .65 787 .72 829 .78 867 .84 905 .90 944 .96 982 1.02 1017 1.08 1104 1.22 1190 1.35

6¼TCD075C

2500 723 .71 765 .78 802 .85 839 .92 877 .99 914 1.05 950 1.12 984 1.19 1019 1.26 1054 1.32 1134 1.49 1213 1.64TCH075C

2750 789 .93 826 1.01 862 1.08 895 1.15 928 1.23 963 1.31 997 1.38 1030 1.45 1061 1.53 1092 1.60 1171 1.79 1244 1.973000 855 1.19 887 1.27 922 1.36 953 1.44 983 1.52 1014 1.60 1046 1.68 1078 1.76 1108 1.85 1137 1.93 1209 2.13 — —

2 HP Oversized Motor & Sheaves

1 HP Standard Motor & Sheaves2400 721 .62 760 .66 801 .71 840 .76 879 .80 916 .85 952 .89 988 .92 1025 .96 1058 .99 1142 1.05 1226 1.10

7½ TCD090C 2700 802 .86 836 .92 872 .97 908 1.03 943 1.08 977 1.13 1011 1.17 1043 1.22 1075 1.27 1108 1.31 1186 1.40 1259 1.47TCH090C 3000 884 1.17 915 1.23 946 1.29 979 1.35 1011 1.41 1042 1.47 1073 1.52 1104 1.57 1134 1.63 1163 1.68 1236 1.80 — —

3300 966 1.54 994 1.60 1022 1.67 1051 1.73 1081 1.80 1111 1.87 1139 1.93 1167 1.99 1195 2.05 1223 2.11 — — — —3600 1048 1.98 1075 2.06 1101 2.12 1126 2.20 1153 2.27 1181 2.34 1208 2.42 1234 2.49 1260 2.55 — — — — — —

2 HP Oversized Motor & Sheaves

1 HP Standard Motor & Sheaves2400 698 0.59 739 0.64 779 0.69 819 0.74 857 0.78 895 0.82 931 0.86 967 0.90 1004 0.94 1039 0.97 1121 1.04 1203 1.09

7½ TCD090D 2700 775 0.82 813 0.88 848 0.93 884 0.99 919 1.04 953 1.09 987 1.14 1020 1.19 1052 1.23 1084 1.28 1164 1.38 1237 1.45TCH090D 3000 853 1.11 888 1.18 920 1.24 952 1.30 984 1.36 1016 1.42 1047 1.47 1077 1.53 1108 1.58 1137 1.63 1209 1.76 — —

3300 932 1.46 963 1.53 994 1.60 1023 1.67 1052 1.74 1081 1.80 1110 1.87 1138 1.93 1166 1.99 1194 2.05 1261 2.20 — —3600 1011 1.88 1040 1.96 1069 2.04 1096 2.11 1122 2.18 1148 2.26 1176 2.33 1203 2.40 1229 2.47 1254 2.54 — — — —

2 HP Oversize Motor & Sheaves

Data includes pressure drop due to filters and wet coil.Fan motor heat (MBH) = 3.53 x Fan Bhp.

NOTE:1. Requires a field supplied Browning sheave AL74 and Belt A48.

Trane’s factory supplied motors, in commercial equipment, are definite purpose motors,specifically designed and tested to operate reliably and continuously at all catalogedconditions. Using the full horsepower range of our fan motors as shown in our tabulardata will not result in nuisance tripping or premature motor failure. Our product’swarranty will not be affected.

1 HP Standard Motor & Field Supplied Low Static Drive11111

Table PD-31— Evaporator Fan Performance 6¼ And 7½ Ton TCR075C, TCR090C,D

RIndicates both downflow and horizontal units.

Page 37: Cat

RT-PRC002-EN 37

(8½ Ton)Standard Efficiency

PerformanceData

RIndicates both downflow and horizontal units.

External Static Pressure (Inches of Water).10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Field Supplied Low

Static Drive (1) 2 HP Standard Motor & Drive2720 553 0.61 586 0.68 623 0.77 658 0.86 690 0.95 721 1.04 752 1.14 781 1.24 809 1.35 836 1.45 863 1.57 889 1.68 914 1.793060 614 0.84 643 0.92 675 1.01 707 1.11 738 1.21 767 1.31 795 1.42 823 1.52 849 1.63 875 1.75 900 1.87 925 1.99 949 2.113400 676 1.13 703 1.22 729 1.31 758 1.41 787 1.53 815 1.64 842 1.76 868 1.87 893 1.98 917 2.10 941 2.22 964 2.35 987 2.483740 738 1.49 763 1.58 787 1.67 812 1.78 838 1.90 865 2.03 890 2.15 915 2.28 939 2.40 962 2.52 984 2.65 1007 2.78 1028 2.91

4080 800 1.91 823 2.01 846 2.11 868 2.2 891 2.34 916 2.47 940 2.61 963 2.75 986 2.88 1009 3.02 1030 3.15 1051 3.29 1072 3.433 HP Oversized Motor 3 HP Oversized Motor & Drive

& Field Supplied Drive (2)

External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP2 HP Standard Motor & High Static Drive

Accessory 3 HP Oversized Motor & Drive 2720 938 1.91 962 2.02 986 2.14 1009 2.26 1031 2.38 1053 2.5 1075 2.62

3060 973 2.24 996 2.36 1018 2.49 1040 2.62 1062 2.75 1083 2.88 1104 3.013400 1010 2.61 1032 2.75 1053 2.89 1075 3.03 1095 3.17 1116 3.31 1136 3.453740 1050 3.05 1071 3.19 1092 3.34 — — — — — — — —4080 — — — — — — — — — — — — — —

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.NOTES:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils andfilters1. Field Supplied Fan Sheave AK94 Required. Field

Supplied Belt may be necessary.2. 3 HP Motor with Field Supplied Motor Sheave

IVP44 required.

Trane’s factory supplied motors, in commercial equipment, are definitepurpose motors, specifically designed and tested to operate reliably andcontinuously at all cataloged conditions. Using the full horsepower rangeof our fan motors as shown in our tabular data will not result in nuisancetripping or premature motor failure. Our product’s warranty will not beaffected.

Table PD-32 — Evaporator Fan Performance 8½ Ton TCD102C

Table PD-32 Continued

External Static Pressure (Inches of Water).10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2 HP Standard Motor & Field Supplied Low Static Drive (1)

2 HP Standard Motor & Drive2 HP Standard

Motor & High Static Drive Accessory

2720 490 0.45 531 0.53 572 0.61 612 0.70 649 0.78 684 0.87 718 0.97 749 1.07 780 1.17 809 1.27 837 1.37 865 1.48 891 1.593060 542 0.62 578 0.70 615 0.79 651 0.89 686 0.98 719 1.08 751 1.18 782 1.28 811 1.39 840 1.50 867 1.61 893 1.73 919 1.843400 594 0.83 627 0.91 660 1.01 693 1.11 725 1.22 757 1.33 787 1.44 817 1.55 845 1.66 872 1.77 899 1.89 924 2.01 949 2.143740 647 1.08 677 1.17 707 1.27 737 1.38 767 1.50 797 1.62 825 1.74 853 1.85 880 1.97 907 2.10 932 2.22 957 2.35 981 2.484080 700 1.38 728 1.48 756 1.59 783 1.70 811 1.82 838 1.95 865 2.08 892 2.21 917 2.34 943 2.47 967 2.60 991 2.73 1015 2.87

2 HP Standard Motor & Drive3 HP Oversized Motor & Field

Supplied Drive (2)3 HP Oversized Motor & Drive

External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP2 HP Standard Motor & High Static Drive Accessory

2720 917 1.70 942 1.81 967 1.92 991 2.03 1014 2.14 1037 2.26 1059 2.373060 944 1.96 968 2.08 992 2.20 1015 2.32 1038 2.45 1061 2.57 1082 2.703400 973 2.26 997 2.39 1020 2.52 1043 2.65 1065 2.78 1086 2.92 1108 3.053740 1005 2.61 1028 2.74 1050 2.88 1072 3.02 1093 3.16 1114 3.30 1135 3.454080 1038 3.01 1060 3.15 1082 3.29 1103 3.44 1124 — — — — —

3 HP Oversized Motor & Drive

Table PD-33— Evaporator Fan Performance 8½ Ton TCH102C

NOTES:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils andfilters1. Field Supplied Fan Sheave AK94 Required. Field

Supplied Belt may be necessary.2. 3 HP Motor with Field Supplied Motor Sheave

IVP44 required.

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.

Trane’s factory supplied motors, in commercial equipment, are definitepurpose motors, specifically designed and tested to operate reliably andcontinuously at all cataloged conditions. Using the full horsepower rangeof our fan motors as shown in our tabular data will not result in nuisancetripping or premature motor failure. Our product’s warranty will not beaffected.

Table PD-33 Continued

Page 38: Cat

38 RT-PRC002-EN

PerformanceData

(10 Ton)Standard Efficiency

Table PD-34� Evaporator Fan Performance 10 Ton TCD120CExternal Static Pressure (Inches of Water)

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3 HP Standard Motor & Field Supplied Low Static Drive (1) 3 HP Standard Motor & Drive3200 649 0.93 681 1.02 713 1.12 742 1.23 769 1.31 794 1.40 820 1.49 847 1.59 873 1.7 899 1.81 924 1.92 948 2.03 972 2.133600 723 1.30 751 1.40 780 1.51 807 1.62 833 1.74 857 1.84 880 1.93 903 2.03 926 2.13 950 2.25 973 2.37 996 2.49 1019 2.624000 798 1.76 822 1.86 848 1.98 874 2.11 898 2.24 922 2.36 944 2.48 965 2.59 985 2.69 1006 2.79 1027 2.91 1048 3.04 1069 3.174400 873 2.32 895 2.43 918 2.55 942 2.69 965 2.83 987 2.97 1008 3.11 1029 3.24 1048 3.36 1067 3.48 1086 3.59 1104 3.71 1123 3.834800 948 2.99 969 3.11 989 3.24 1011 3.38 1033 3.53 1054 3.68 1074 3.83 1094 3.99 1113 4.14 1131 4.28 1149 4.40 1166 4.53 1183 4.65

3 HP Standard Motor & Drive 5 HP Oversize Motor & Drive

External Static Pressure (Inches of Water)1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3 HP Standard Motor & Drive3 HP Standard Motor & High

Static Drive Accessory3200 995 2.24 1017 2.35 1039 2.46 1061 2.58 1082 2.69 1103 2.81 1124 2.943600 1041 2.74 1062 2.86 1084 2.98 1104 3.10 1125 3.23 1145 3.35 1164 3.474000 1090 3.31 1111 3.45 1131 3.59 1151 3.72 1170 3.85 1190 3.99 1209 4.124400 1142 3.97 1162 4.11 1181 4.26 1200 4.41 1219 4.56 1238 4.72 1256 4.874800 1200 4.78 1217 4.91 1235 5.05 1252 5.21 1270 5.36 1287 5.52 1305 5.69

5 HP Oversize Motor & Drive

Trane�s factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested to operatereliably and continuously at all cataloged conditions. Using the fullhorsepower range of our fan motors as shown in our tabular data willnot result in nuisance tripping or premature motor failure. Ourproduct�s warranty will not be affected.

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.

NOTE:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils and

filters1. Field Supplied Fan Sheave BK90 Required. Field

Supplied Belt may be necessary. Table PD-34 Continued

External Static Pressure (Inches of Water).10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP3 HP Standard Motor & Field Supplied Low Static Dr. (1) 3 HP Standard Motor & Drive

3200 — — — — 651 0.95 684 1.04 718 1.14 750 1.25 782 1.35 812 1.47 842 1.58 870 1.69 897 1.81 923 1.93 949 2.043600 640 1.04 676 1.15 708 1.26 738 1.37 768 1.47 798 1.59 827 1.70 856 1.82 883 1.94 910 2.07 937 2.20 962 2.32 987 2.454000 704 1.39 736 1.52 767 1.64 795 1.76 822 1.88 849 2.00 876 2.12 902 2.25 928 2.38 954 2.51 979 2.65 1003 2.79 1027 2.934400 768 1.82 798 1.96 827 2.10 853 2.23 878 2.36 903 2.49 927 2.62 952 2.76 976 2.90 1000 3.04 1024 3.18 1047 3.33 1070 3.484800 833 2.34 860 2.48 887 2.64 913 2.79 936 2.93 959 3.07 982 3.21 1004 3.36 1027 3.50 1049 3.65 1071 3.80 1093 3.96 1115 4.11

3 HP Standard Motor & Drive 5 HP Oversize Motor & Drive

External Static Pressure (Inches of Water)1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3 HP Standard Motor & Drive3 HP Standard Motor &

High Static Drive Accessory

3200 974 2.16 998 2.28 1021 2.40 1043 2.52 1066 2.65 1087 2.77 1108 2.903600 1011 2.58 1035 2.71 1057 2.85 1079 2.98 1101 3.11 1123 3.25 1143 3.384000 1051 3.07 1073 3.21 1096 3.36 1117 3.50 1139 3.65 1160 3.79 1180 3.944400 1092 3.63 1114 3.78 1136 3.94 1157 4.09 1178 4.25 1198 4.41 1218 4.574800 1136 4.27 1157 4.44 1178 4.60 1198 4.77 1218 4.94 1238 5.10 1258 5.28

5 HP Oversize Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.NOTE:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils and filters1. Field Supplied Fan Sheave BK90 Required. Field Supplied Belt may be necessary.

Table PD-35 Continued

Trane�s factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested to operatereliably and continuously at all cataloged conditions. Using the fullhorsepower range of our fan motors as shown in our tabular datawill not result in nuisance tripping or premature motor failure. Ourproduct�s warranty will not be affected.

Table PD-35� Evaporator Fan Performance 10 Ton TCH120C

Page 39: Cat

RT-PRC002-EN 39

(12½ Ton)Standard Efficiency

PerformanceData

Table PD-36� Evaporator Fan Performance 12 1/2 Ton TCD150CExternal Static Pressure (Inches of Water)

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3 HP Standard Motor & Field Supplied Low Static

3 HP Standard Motor & Drive (2)

4000 591 1.09 628 1.23 663 1.4 698 1.52 732 1.68 764 1.84 796 2.00 827 2.16 857 2.33 886 2.50 914 2.67 942 2.85 969 3.044500 655 1.51 689 1.67 721 1.8 753 1.98 783 2.15 813 2.32 843 2.50 871 2.69 899 2.87 927 3.05 953 3.24 980 3.43 1005 3.625000 721 2.03 752 2.20 781 2.4 810 2.55 838 2.73 866 2.91 893 3.11 920 3.31 946 3.51 971 3.71 997 3.91 1021 4.11 1046 4.325500 786 2.65 815 2.85 842 3 869 3.23 895 3.42 920 3.62 946 3.82 971 4.03 995 4.25 1019 4.47 1043 4.69 1066 4.91 1089 5.136000 853 3.40 879 3.62 905 3.8 930 4.03 954 4.24 977 4.45 1001 4.66 1024 4.88 1047 5.11 1070 5.35 1092 5.58 — — — —

5 HP Oversize Motor & Drive

External Static Pressure (Inches of Water)1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP3 HP Standard Motor & Field Supplied High Static Drive (2)

5 HP Oversize Motor & Drive

4000 995 3.23 1021 3.43 1046 3.63 1071 3.84 1095 4.05 1118 4.27 1141 4.484500 1030 3.82 1055 4.02 1079 4.23 1103 4.45 1126 4.66 1149 4.89 1171 5.115000 1069 4.53 1093 4.74 1116 4.96 1138 5.18 1161 5.40 1183 5.63 — —5500 1112 5.36 1134 5.58 — — — — — — — — — —6000 — — — — — — — — — — — — — —

5 HP Motor & High Static Drive (3)

Trane�s factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested to operatereliably and continuously at all cataloged conditions. Using the fullhorsepower range of our fan motors as shown in our tabular datawill not result in nuisance tripping or premature motor failure. Ourproduct�s warranty will not be affected.

NOTES:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils and filters1. Field Supplied Fan Sheave BK90 Required. Field Supplied

Belt may be necessary.2. Field Supplied Motor Sheave IVP44 Required. Field

Supplied Belt may be necessary.3. Field Supplied Motor Sheave IVP50 Required. Field

Supplied Belt may be necessary.

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.

Table PD-36 Continued

Table PD-37 � Evaporator Fan Performance 12 1/2 Ton TCH150CExternal Static Pressure (Inches of Water)

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3 HP Standard Motor & Field Supplied Low Static

Drive (1)3 HP Standard Motor & Drive

4000 — — 576 1.19 613 1.34 649 1.49 684 1.65 717 1.83 750 2.00 781 2.19 812 2.38 842 2.58 872 2.78 901 2.99 929 3.214500 597 1.46 630 1.61 664 1.77 697 1.93 728 2.11 759 2.29 789 2.48 819 2.68 847 2.88 875 3.09 903 3.30 930 3.52 957 3.755000 656 1.96 686 2.13 717 2.30 747 2.48 776 2.66 804 2.86 832 3.06 860 3.27 886 3.48 913 3.70 939 3.92 964 4.15 989 4.395500 715 2.57 743 2.75 771 2.94 798 3.13 826 3.33 852 3.53 878 3.74 904 3.96 929 4.19 953 4.42 978 4.66 1002 4.90 1025 5.146000 776 3.29 801 3.49 826 3.70 852 3.90 877 4.11 902 4.33 926 4.55 950 4.78 974 5.02 997 5.26 1020 5.51 — — — —

5 HP Oversize Motor & Hi Drive

(2) 5 HP Oversize Motor & Drive

External Static Pressure (Inches of Water)1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP5 HP Oversize Motor & Drive

4000 956 3.43 984 3.65 1010 3.88 1036 4.11 1061 4.35 1086 4.59 1110 4.834500 983 3.98 1008 4.21 1034 4.45 1058 4.70 1083 4.95 1107 5.20 1130 5.465000 1014 4.63 1038 4.88 1062 5.13 1085 5.38 1108 5.64 — — — —5500 1049 5.40 1071 5.65 — — — — — — — — — —6000 — — — — — — — — — — — — — —

Trane�s factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested to operatereliably and continuously at all cataloged conditions. Using the fullhorsepower range of our fan motors as shown in our tabular data willnot result in nuisance tripping or premature motor failure. Ourproduct�s warranty will not be affected.

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.

NOTES:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils and filters1. Field Supplied Fan Sheave BK90 Required. Field Supplied Belt may be necessary.2. 5 HP Oversize Motor with Field Supplied Motor Sheave IVL40 Required. Field

Supplied Belt may be necessary.Table PD-37 Continued

Page 40: Cat

40 RT-PRC002-EN

(15 and 17½Ton)Standard Efficiency

PerformanceData

Table PD-38 — Evaporator Fan Performance 15 Ton TCR180B

External Static Pressure (Inches of Water).10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP3 HP Standard Motor & Field Supplied Low Static Drive (1)

3 HP Standard Motor & Drive

4800 — — 563 1.17 596 1.29 626 1.41 656 1.52 685 1.63 714 1.76 742 1.90 768 2.04 794 2.18 819 2.30 844 2.43 871 2.575400 585 1.47 618 1.60 648 1.72 676 1.86 703 1.99 729 2.12 756 2.25 782 2.38 807 2.52 832 2.68 855 2.84 878 3.00 901 3.156000 643 1.99 673 2.12 701 2.26 727 2.41 752 2.56 777 2.71 801 2.85 825 2.99 848 3.13 871 3.27 894 3.43 916 3.61 938 3.796600 701 2.61 729 2.76 755 2.91 780 3.07 804 3.23 827 3.39 849 3.56 871 3.72 892 3.88 914 4.03 935 4.18 956 4.34 977 4.517200 760 3.35 786 3.52 810 3.69 834 3.85 856 4.02 878 4.20 899 4.38 919 4.56 939 4.74 959 4.91 979 5.08 999 5.25 1018 5.41

(2) 5 HP Oversize Motor & Drive

External Static Pressure (Inches of Water)1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP3 HP Standard Motor & High Static Drive Accessory

4800 898 2.70 923 2.83 946 2.96 970 3.09 994 3.23 1018 3.39 1041 3.545400 923 3.29 945 3.43 969 3.58 993 3.73 1016 3.88 1038 4.03 1060 4.176000 959 3.97 980 4.15 1000 4.31 1019 4.46 1040 4.62 1061 4.78 1082 4.956600 997 4.70 1018 4.90 1037 5.10 1056 5.30 1075 5.49 1093 5.67 — —7200 1038 5.58 1057 5.77 — — — — — — — — — —

5 HP Oversize Motor & Drive

5 HP OS Motor & Field Supplied Drive (3)

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.

Trane’s factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested tooperate reliably and continuously at all cataloged conditions.Using the full horsepower range of our fan motors as shown in ourtabular data will not result in nuisance tripping or premature motorfailure. Our product’s warranty will not be affected.

NOTES:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils and filters1. Field Supplied Fan Sheave BK105 Required. Field Supplied Belt

may be necessary.2. 5 HP Oversize Motor with Field Supplied Fan Sheave BK160

Required.Field Supplied Belt may be necessary.

3. 5 HP Oversize Motor with Field Supplied Motor Sheave IVP50Required. Field Supplied Belt may be necessary.

Table PD-38 Continued

Table PD-39 Evaporator Fan Performance 17½ Ton TCR210C

External Static Pressure (Inches of Water).10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP5 HP Standard Motor with Low Static Drive Accessory 5 HP Standard Motor & Drive

5600 — — — — 718 2.26 742 2.38 765 2.50 789 2.63 813 2.78 836 2.92 857 3.06 879 3.21 903 3.37 927 3.53 949 3.706300 745 2.84 768 2.98 791 3.11 812 3.24 833 3.37 854 3.51 875 3.65 897 3.82 918 3.98 937 4.14 957 4.30 976 4.46 997 4.637000 822 3.86 843 4.01 864 4.16 884 4.31 904 4.46 923 4.60 941 4.75 960 4.90 979 5.08 999 5.26 1018 5.44 1036 5.61 1053 5.797700 900 5.11 920 5.27 939 5.44 957 5.60 976 5.77 993 5.93 1010 6.09 1027 6.24 1044 6.41 1061 6.59 1079 6.78 1097 6.98 1114 7.188400 979 6.59 997 6.78 1014 6.96 1031 7.14 1048 7.32 1065 7.49 1081 7.67 1097 7.84 1113 8.02 1128 8.19 1143 8.37 1159 8.57 — —

7.5 HP Oversize Motor & Drive

External Static Pressure (Inches of Water)1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP5 HP Standard Motor & Drive

5600 971 3.88 993 4.06 1014 4.24 1036 4.42 1058 4.60 1079 4.79 1101 4.976300 1018 4.81 1039 4.99 1059 5.19 1079 5.38 1098 5.58 1117 5.78 1136 5.987000 1070 5.97 1088 6.15 1106 6.34 1125 6.54 1144 6.74 1163 6.95 1181 7.177700 1131 7.37 1147 7.56 1163 7.76 1179 7.95 1194 8.15 1211 8.36 1228 8.588400 — — — — — — — — — — — — — —

7.5 HP Oversize Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-56.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.NOTE:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils and filters

Table PD-39 Continued

Trane’s factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested to operatereliably and continuously at all cataloged conditions. Using the fullhorsepower range of our fan motors as shown in our tabular data willnot result in nuisance tripping or premature motor failure. Ourproduct’s warranty will not be affected.

RIndicates both downflow and horizontal units.

Page 41: Cat

RT-PRC002-EN 41

PerformanceData

(20 Ton)Standard Efficiency

RIndicates both downflow and horizontal units.

External Static Pressure (Inches of Water).10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP5 HP Standard Motor & Field Supplied

Low Static Drive (1)5 HP Standard Motor & Drive

6400 — — 514 1.69 546 1.88 574 2.05 599 2.21 624 2.37 648 2.54 671 2.71 695 2.90 720 3.11 744 3.32 768 3.52 790 3.727200 527 2.08 562 2.29 592 2.50 619 2.71 644 2.91 667 3.09 689 3.26 711 3.45 732 3.64 752 3.83 773 4.04 795 4.27 817 4.508000 578 2.79 610 3.03 639 3.26 666 3.50 690 3.73 712 3.96 733 4.16 753 4.35 773 4.55 792 4.75 811 4.96 830 5.18 848 5.408800 629 3.65 659 3.93 687 4.18 712 4.43 736 4.69 758 4.96 778 5.20 797 5.43 816 5.65 834 5.86 852 6.08 869 6.30 887 6.539600 681 4.67 709 4.99 735 5.27 759 5.54 782 5.82 804 6.11 824 6.39 843 6.67 861 6.92 878 7.16 895 7.40 911 7.63 928 7.86

5 HP Standard Motor & Drive (2) 7.5 HP Oversize Motor & Drive

External Static Pressure (Inches of Water)1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP5 HP

Standard Motor & Drive

5 HP Standard Motor & High Static Drive Accessory

6400 811 3.91 833 4.13 855 4.36 877 4.59 897 4.82 917 5.05 936 5.297200 839 4.74 860 4.96 880 5.19 898 5.41 917 5.64 937 5.88 957 6.148000 867 5.64 887 5.90 907 6.16 927 6.42 946 6.68 964 6.93 982 7.188800 904 6.77 921 7.01 938 7.26 955 7.52 973 7.81 991 8.09 — —9600 944 8.11 960 8.36 976 8.61 — — — — — — — —

7.5 HP Oversize Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.

Table PD-40 Evaporator Fan Performance 20 Ton TCR240B

Table PD-40 Continued

Trane’s factory supplied motors, in commercial equipment, are definitepurpose motors, specifically designed and tested to operate reliably andcontinuously at all cataloged conditions. Using the full horsepower rangeof our fan motors as shown in our tabular data will not result in nuisancetripping or premature motor failure. Our product’s warranty will not beaffected.

NOTES:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils and filters1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be

necessary.2. 7.5 HP Standard Motor with Field Supplied Motor Sheave IVP50 Required.

Field Supplied Belt may be necessary.

Page 42: Cat

42 RT-PRC002-EN

Table PD-41 — Evaporator Fan Performance 25 Ton TCQ300B

PerformanceData

(25 Ton)Standard Efficiency

External Static Pressure (Inches of Water).10 .20 .30 .40 .50 .60 .70 .80 .90 1.00

CFM RPM BHP RPM BHP RPM BHP RPM BHPRPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP7.5 HP Standard Motor & Low Static Drive Accy 7.5 HP Standard

Motor & Drive7000 — — — — 593 2.42 619 2.62 643 2.80 667 2.98 690 3.16 712 3.35 733 3.53 754 3.737500 — — 595 2.66 624 2.88 649 3.10 673 3.31 695 3.50 717 3.68 738 3.88 759 4.08 779 4.288000 595 2.92 627 3.16 655 3.39 679 3.63 702 3.86 724 4.07 745 4.28 766 4.48 786 4.68 805 4.908500 628 3.47 659 3.73 686 3.97 710 4.23 732 4.47 754 4.71 774 4.94 794 5.15 813 5.36 832 5.589000 661 4.08 691 4.36 717 4.62 741 4.89 763 5.15 784 5.41 803 5.66 822 5.89 841 6.12 859 6.359500 695 4.76 723 5.06 749 5.34 772 5.62 794 5.90 814 6.18 833 6.45 852 6.71 870 6.95 887 7.19

10000 729 5.52 755 5.84 781 6.13 804 6.42 825 6.72 844 7.01 863 7.31 881 7.59 899 7.86 916 8.1110500 762 6.35 788 6.69 812 7.00 835 7.31 856 7.62 875 7.93 894 8.24 911 8.54 — — — —11000 796 7.27 821 7.63 844 7.96 867 8.3 887 8.60 — — — — — — — — — —

7.5 HP Standard Motor & Drive7.5 HP Standard Motor & High Static Drive

Accessory

External Static Pressure (Inches of Water)1.10 1.20 1.30 1.40 1.50

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP7.5 HP Standard Motor & Drive

7000 776 3.95 798 4.18 820 4.40 841 4.62 862 4.847500 798 4.48 818 4.71 839 4.95 860 5.19 880 5.428000 824 5.11 842 5.32 860 5.55 880 5.80 899 6.068500 850 5.81 868 6.03 885 6.26 902 6.49 920 6.749000 877 6.58 894 6.81 911 7.05 928 7.29 944 7.539500 904 7.43 921 7.67 938 7.92 954 8.17 970 8.42

10000 933 8.36 949 8.62 — — — — — —10500 — — — — — — — — — —11000 — — — — — — — — — —

7.5 HP Standard Motor & High Static Drive Accessory

Trane’s factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested to operatereliably and continuously at all cataloged conditions. Using the fullhorsepower range of our fan motors as shown in our tabular datawill not result in nuisance tripping or premature motor failure. Ourproduct’s warranty will notbe affected.

Table PD-41 Continued

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & High Static Drive Accessory Fan Speed(RPM), reference Table PD-54.For Standard Motor & Low Static Drive Accessory Fan Speed(RPM), reference Table PD-56.

NOTES:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils andfilters

RIndicates both downflow and horizontal units.

Page 43: Cat

RT-PRC002-EN 43

(3, 4, 5 Ton)High Efficiency

PerformanceData

RIndicates both downflow and horizontal units.

Table PD-42— Evaporator Fan Performance 3, 4 And 5 Ton TCD037C, TCR049C, TCR061C

External Static Pressure (Inches of Water) & Motor Power (Bhp)1

Standard Motor Oversized Motor

UnitHigh Speed Low Speed

Tons Model No. CFM ESP BHP ESP BHP ESP BHP

900 0.83 0.28 0.74 0.26 — —1000 0.78 0.30 0.67 0.28 1.57 0.611100 0.72 0.32 0.61 0.30 1.43 0.63

3 1200 0.65 0.34 0.50 0.33 1.26 0.661300 0.59 0.36 0.36 0.38 1.08 0.691400 0.50 0.38 — — 0.88 0.731500 0.40 0.40 — — 0.63 0.77

1200 0.91 0.48 0.83 0.35 — —1300 0.88 0.49 0.77 0.37 1.63 0.741400 0.85 0.50 0.72 0.39 1.55 0.771500 0.83 0.52 0.65 0.42 1.48 0.801600 0.78 0.54 0.58 0.44 1.41 0.831700 0.74 0.56 0.45 0.49 1.34 0.861800 0.69 0.58 — — 1.27 0.901900 0.64 0.60 — — 1.20 0.932000 0.60 0.62 — — 1.12 0.97

1200 0.88 0.45 0.77 0.32 1.68 0.751300 0.84 0.46 0.72 0.34 1.61 0.771400 0.80 0.48 0.68 0.36 1.55 0.791500 0.76 0.49 0.64 0.39 1.47 0.811600 0.72 0.50 0.55 0.41 1.42 0.831700 0.68 0.52 0.47 0.43 1.34 0.861800 0.64 0.54 0.36 0.47 1.27 0.901900 0.57 0.56 0.20 0.52 1.20 0.932000 0.51 0.58 — — 1.13 0.96

1600 0.77 0.58 0.70 0.46 1.42 0.821700 0.72 0.59 0.64 0.48 1.35 0.861800 0.67 0.61 0.56 0.50 1.29 0.901900 0.61 0.63 0.48 0.52 1.23 0.932000 0.55 0.66 0.39 0.55 1.18 0.962100 0.48 0.69 0.29 0.59 1.09 1.012200 0.40 0.71 0.16 0.62 1.01 1.052300 0.31 0.73 — 0.67 0.88 1.092400 0.23 0.76 — — 0.78 1.13

1600 0.79 0.58 0.73 0.46 1.46 0.831700 0.75 0.59 0.68 0.48 1.42 0.861800 0.71 0.62 0.63 0.50 1.37 0.901900 0.66 0.64 0.58 0.52 1.31 0.932000 0.61 0.66 0.50 0.56 1.25 0.972100 0.55 0.68 0.42 0.59 1.18 1.012200 0.48 0.70 0.31 0.63 1.10 1.052300 0.40 0.73 0.19 0.67 1.00 1.092400 0.31 0.76 — — 0.90 1.13

Fan motor heat (MBH) = 4.39 x Fan Bhp.Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed andtested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fanmotors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’swarranty will not be affected.

NOTE:1. Data includes pressure drop due to wet coil and filters.

4

5

TCD037C*

TCD049C*

TCH049C*

TCD061C*

TCH061C*

Page 44: Cat

44 RT-PRC002-EN

PerformanceData

(6 - 7½ Ton)High Efficiency

Table PD-43 — Evaporator Fan Performance 6-7½ Ton TCR074C - 086C,TCR091D

External Static Pressure (Inches of Water)Unit .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.25 1.50Model No. CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1 HP Standard Motor & Field SuppliedLow Static Drive1

2000 615 0.37 663 0.41 710 0.45 756 0.49 799 0.52 843 0.55 884 0.58 924 0.60 965 0.62 1006 0.63 — — — —2250 681 0.52 723 0.56 766 0.61 807 0.65 848 0.69 886 0.73 925 0.76 964 0.79 1000 0.82 1035 0.84 1126 0.90 1209 0.92

TCD074C2500 748 0.69 785 0.74 824 0.79 862 0.84 899 0.89 936 0.93 971 0.98 1005 1.02 1041 1.06 1075 1.09 1154 1.16 1237 1.22

TCH074C2750 816 0.91 849 0.96 884 1.02 920 1.08 954 1.13 988 1.18 1021 1.23 1053 1.28 1084 1.32 1116 1.37 1195 1.46 1266 1.543000 884 1.17 915 1.23 946 1.29 979 1.35 1011 1.41 1042 1.47 1073 1.52 1104 1.57 1134 1.63 1163 1.68 1236 1.80 — —

1 HP Standard Motor & Sheaves 2 HP Oversize Motor & Sheaves

1 HP Standard Motor & Field SuppliedLow Static Drive1

2000 615 0.37 663 0.41 710 0.45 756 0.49 799 0.52 843 0.55 884 0.58 924 0.60 965 0.62 1006 0.63 — — — —2250 681 0.52 723 0.56 766 0.61 807 0.65 848 0.69 886 0.73 925 0.76 964 0.79 1000 0.82 1035 0.84 1126 0.90 1209 0.92

TCD0862500 748 0.69 785 0.74 824 0.79 862 0.84 899 0.89 936 0.93 971 0.98 1005 1.02 1041 1.06 1075 1.09 1154 1.16 1237 1.22

TCH0862750 816 0.91 849 0.96 884 1.02 920 1.08 954 1.13 988 1.18 1021 1.23 1053 1.28 1084 1.32 1116 1.37 1195 1.46 1266 1.543000 884 1.17 915 1.23 946 1.29 979 1.35 1011 1.41 1042 1.47 1073 1.52 1104 1.57 1134 1.63 1163 1.68 1236 1.80 — —

1 HP Standard Motor & Sheaves 2 HP Oversize Motor & Sheaves

1 HP Standard Motor & Sheaves2400 721 0.62 760 0.66 801 0.71 840 0.76 879 0.80 916 0.85 952 0.89 988 0.92 1025 0.96 1058 0.99 1142 1.05 1226 1.102700 802 0.86 836 0.92 872 0.97 908 1.03 943 1.08 977 1.13 1011 1.17 1043 1.22 1075 1.27 1108 1.31 1186 1.40 1259 1.47

TCD091D3000 884 1.17 915 1.23 946 1.29 979 1.35 1011 1.41 1042 1.47 1073 1.52 1104 1.57 1134 1.63 1163 1.68 1236 1.80 — —

TCH091D3000 966 1.54 994 1.60 1022 1.67 1051 1.73 1081 1.80 1111 1.87 1139 1.93 1167 1.99 1195 2.05 1223 2.11 1289 2.26 — —3600 1048 1.98 1075 2.06 1101 2.12 1126 2.20 1153 2.27 1181 2.34 1208 2.42 1234 2.49 1260 — — — — — — —

2 HP Oversize Motor & Sheaves

Data includes pressure drop due to filters and wet coil.Fan motor heat (MBH) = 3.53 x Fan Bhp.

NOTE:1. Requires a field supplied Browning sheave AL74 and Belt A48.

Trane’s factory supplied motors, in commercial equipment, are definite purposemotors, specifically designed and tested to operate reliably and continuously at allcataloged conditions. Using the full horsepower range of our fan motors as shownin our tabular data will not result in nuisance tripping or premature motor failure.Our product’s warranty will not be affected.

RIndicates both downflow and horizontal units.

Page 45: Cat

RT-PRC002-EN 45

(8½ Ton)High Efficiency

PerformanceData

External Static Pressure (Inches of Water).10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor & Field Supplied Low Static Drive (1) 2 HP Standard Motor & Drive

2720 — — 497 0.52 534 0.59 572 0.67 612 0.75 645 0.82 677 0.90 709 0.98 741 1.1 772 1.17 801 1.27 829 1.37 855 1.473060 494 0.61 537 0.70 575 0.78 607 0.86 642 0.94 677 1.03 708 1.12 737 1.20 765 1.3 794 1.38 823 1.49 851 1.60 877 1.703400 540 0.81 578 0.91 616 1.00 648 1.09 677 1.18 707 1.27 740 1.37 770 1.47 796 1.6 822 1.66 848 1.75 874 1.86 899 1.973740 587 1.06 621 1.17 657 1.27 689 1.37 717 1.47 743 1.56 771 1.67 800 1.78 829 1.9 855 1.99 879 2.09 902 2.19 925 2.304080 634 1.35 666 1.47 698 1.59 730 1.70 759 1.80 784 1.91 807 2.01 832 2.12 859 2.2 886 2.36 911 2.48 935 2.59 957 2.71

3 HP Oversized Motor & Drive

External Static Pressure (Inches of Water) 1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP2 HP Standard Motor

& Drive2 HP Standard Motor & High Static Drive

Accessory2720 881 1.58 906 1.69 932 1.80 956 1.92 981 2.05 1005 2.18 1028 2.313060 903 1.81 928 1.92 952 2.04 975 2.15 998 2.28 1020 2.40 1042 2.533400 925 2.09 950 2.21 974 2.33 997 2.45 1020 2.57 1041 2.70 1063 2.823740 949 2.41 972 2.53 996 2.65 1019 2.79 1041 2.92 1063 3.05 — —4080 978 2.81 999 2.92 1021 3.04 1042 3.17 1064 3.30 — — — —

3 HP Oversized Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.

Table PD-44 — Continued

Table PD-44 — Evaporator Fan Performance 8½ Ton TCR103C

NOTE:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils and filters1. Field Supplied Fan Sheave AK89 Required. Field Supplied Belt

may be necessary.

Trane’s factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested to operatereliably and continuously at all cataloged conditions. Using the fullhorsepower range of our fan motors as shown in our tabular datawill not result in nuisance tripping or premature motor failure. Ourproduct’s warranty will not be affected.

RIndicates both downflow and horizontal units.

Page 46: Cat

46 RT-PRC002-EN

External Static Pressure (Inches of Water).10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP2 HP Standard Motor &

Field Supplied Low Static Drive (1)

2 HP Standard Motor & Drive

2 HP Standard Motor & High Static Drive Accessory

3200 — — 444 0.48 500 0.60 549 0.72 592 0.84 632 0.95 669 1.06 703 1.17 735 1.28 766 1.38 795 1.48 823 1.61 851 1.733600 402 0.44 469 0.60 524 0.75 572 0.88 615 1.02 654 1.15 690 1.28 725 1.40 757 1.53 787 1.65 816 1.77 844 1.89 871 2.004000 430 0.56 495 0.74 549 0.91 596 1.07 638 1.22 677 1.37 713 1.52 746 1.66 778 1.80 809 1.94 838 2.08 865 2.21 892 2.354400 459 0.71 521 0.91 574 1.10 620 1.27 662 1.45 700 1.62 735 1.78 769 1.94 801 2.10 831 2.26 859 2.41 887 2.56 913 2.714800 488 0.87 548 1.10 599 1.31 645 1.51 686 1.70 723 1.89 759 2.07 792 2.25 823 2.43 853 2.60 881 2.78 909 2.95 935 3.11

2 HP Standard Motor & Drive 3 HP Oversize Motor & Drive

External Static Pressure (Inches of Water)1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP2 HP Standard Motor & High

Static Drive Accessory 3 HP Oversize Motor & Drive

3200 879 1.85 906 1.98 932 2.13 956 2.28 980 2.44 1004 2.60 1026 2.753600 897 2.12 922 2.26 946 2.40 971 2.54 996 2.68 1020 2.83 1043 2.994000 918 2.48 943 2.61 967 2.73 990 2.87 1013 3.01 1035 3.17 1057 3.334400 939 2.86 964 3.01 988 3.16 1011 3.31 1033 3.45 — — — —4800 961 3.28 985 3.45 — — — — — — — — — —

(10 Ton)High Efficiency

PerformanceData

Table PD-45 — Evaporator Fan Performance 10 Ton TCD121C

Table PD-46 — Evaporator Fan Performance 10 Ton TCH121C

External Static Pressure (Inches of Water).10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2 HP Standard Motor & Field Supplied Low Static Drive (1)

2 HP Standard Motor & Drive

3200 — — 411 0.51 450 0.61 487 0.71 523 0.82 558 0.93 591 1.06 623 1.18 653 1.31 682 1.43 710 1.57 737 1.70 763 1.853600 406 0.58 444 0.67 479 0.78 513 0.88 546 1.00 578 1.12 609 1.25 640 1.38 669 1.52 697 1.66 724 1.80 750 1.95 775 2.094000 442 0.76 477 0.87 510 0.98 541 1.10 572 1.22 602 1.35 631 1.48 659 1.62 687 1.76 714 1.91 740 2.07 766 2.23 791 2.384400 479 0.98 512 1.10 542 1.22 572 1.35 600 1.48 628 1.61 655 1.75 682 1.90 708 2.05 733 2.20 758 2.36 783 2.53 807 2.704800 515 1.25 548 1.39 576 1.51 603 1.64 630 1.79 656 1.93 682 2.07 707 2.22 731 2.38 755 2.54 779 2.70 802 2.87 825 3.05

3 HP Oversize Motor & Drive

External Static Pressure (Inches of Water)1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP2 HP Standard Motor & High

Static Drive Accessory 3 HP Oversize Motor & Drive

3200 789 2.00 814 2.15 838 2.31 862 2.47 884 2.63 906 2.79 927 2.953600 800 2.24 824 2.40 848 2.56 871 2.72 894 2.89 916 3.06 938 3.244000 814 2.54 838 2.70 860 2.86 883 3.02 905 3.19 926 3.37 — —4400 831 2.87 853 3.04 876 3.21 897 3.39 — — — — — —4800 848 3.23 870 3.42 — — — — — — — — — —

NOTES:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils and filters1. Field Supplied Fan Sheave AK89 Required. Field Supplied Belt may

be necessary.2. 3 HP Oversize Motor with Field Supplied Fan Sheave BK85 Required

Field Supplied belt may be necessary.

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.

Trane’s factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested to operatereliably and continuously at all cataloged conditions. Using the fullhorsepower range of our fan motors as shown in our tabular datawill not result in nuisance tripping or premature motor failure. Ourproduct’s warranty will not be affected.

Table PD-45 — Continued

Table PD-46 — Continued

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.

Trane’s factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested to operatereliably and continuously at all cataloged conditions. Using the fullhorsepower range of our fan motors as shown in our tabular datawill not result in nuisance tripping or premature motor failure. Ourproduct’s warranty will not be affected.

NOTES:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils and filters1. Field Supplied Fan Sheave AK89 Required. Field Supplied Belt may

be necessary.2. 3 HP Oversize Motor with Field Supplied Motor Sheave BK85 Required.

Field Supplied Belt may be necessary.

Page 47: Cat

RT-PRC002-EN 47

(12½ Ton)High Efficiency

PerformanceData

Table PD-47 � Evaporator Fan Performance 12½ Ton TCD151C

External Static Pressure (Inches of Water).10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3 HP Standard Motor & Field Supplied Low Static Drive (1)

3 HP Standard Motor & Drive3 HP Stnd Motor & High Static Drive

Accessory4000 — — — — 549 0.91 596 1.07 638 1.22 677 1.37 713 1.52 746 1.66 778 1.80 809 1.94 838 2.08 865 2.21 892 2.354500 — — 528 0.95 580 1.15 626 1.33 668 1.51 706 1.68 741 1.85 775 2.02 806 2.18 836 2.34 865 2.50 892 2.66 919 2.815000 503 0.96 562 1.20 613 1.42 657 1.63 698 1.83 735 2.03 770 2.23 803 2.42 835 2.60 864 2.79 893 2.97 920 3.15 946 3.325500 540 1.22 597 1.49 646 1.74 689 1.98 729 2.21 766 2.43 800 2.65 833 2.86 864 3.07 893 3.28 921 3.49 948 3.69 974 3.896000 578 1.53 633 1.82 680 2.10 722 2.37 761 2.62 797 2.87 831 3.12 863 3.36 893 3.59 922 3.82 950 4.05 977 4.28 1002 4.50

5 HP Oversize Motor & Drive

External Static Pressure (Inches of Water)1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP3 HP Standard Motor & High Static Drive Accessory

4000 918 2.48 943 2.61 967 2.73 990 2.87 1013 3.01 1035 3.17 1057 3.334500 944 2.97 969 3.12 993 3.27 1016 3.42 1039 3.57 1061 3.72 1082 3.855000 971 3.50 996 3.67 1020 3.85 1043 4.02 1065 4.19 1087 4.36 1108 4.525500 999 4.09 1023 4.28 1047 4.48 1070 4.67 1092 4.86 1114 5.05 1135 5.246000 1027 4.72 1051 4.94 1075 5.16 1098 5.38 1120 5.59 — — — —

5 HP Oversize Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.NOTE:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils and filters1. Field Supplied Fan Sheave BK115 Required. Field Supplied

Belt may be necessary. Table PD-47 � Continued

Trane�s factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested to operatereliably and continuously at all cataloged conditions. Using the fullhorsepower range of our fan motors as shown in our tabular data willnot result in nuisance tripping or premature motor failure. Ourproduct�s warranty will not be affected.

NOTE:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils and filters1. Field Supplied Fan Sheave BK115 Required. Field Supplied Belt

may be necessary.

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.

External Static Pressure (Inches of Water).10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP3 HP Standard Motor & Field Supplied Low Static

Drive (1)3 HP Standard Motor & Drive

4000 — — — — 510 0.98 541 1.10 572 1.22 602 1.35 631 1.48 659 1.62 687 1.76 714 1.91 740 2.07 766 2.23 791 2.384500 — — 521 1.17 551 1.29 579 1.42 607 1.56 635 1.68 662 1.82 688 1.98 713 2.13 738 2.28 763 2.44 787 2.61 811 2.785000 534 1.40 566 1.54 593 1.67 620 1.81 645 1.95 671 2.11 696 2.25 720 2.40 744 2.56 767 2.73 790 2.90 812 3.07 835 3.245500 581 1.83 611 1.99 637 2.13 661 2.28 685 2.43 709 2.59 732 2.76 754 2.92 777 3.08 799 3.25 820 3.43 842 3.61 862 3.806000 628 2.34 657 2.51 682 2.68 704 2.83 727 3.00 749 3.16 770 3.33 791 3.52 812 3.70 833 3.87 853 4.04 874 4.23 893 4.43

5 HP Oversize Motor & Drive

External Static Pressure (Inches of Water)1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP3 HP Standard Motor & Drive

3 HP Standard Motor & High Static Drive Accessory

4000 814 2.54 838 2.70 860 2.86 883 3.02 905 3.19 926 3.37 948 3.554500 835 2.96 858 3.13 880 3.31 901 3.48 922 3.66 943 3.84 963 4.025000 857 3.42 879 3.61 901 3.81 922 4.00 942 4.20 962 4.39 982 4.595500 883 3.98 904 4.17 924 4.37 944 4.57 964 4.78 984 4.99 1003 5.206000 913 4.63 932 4.83 951 5.03 970 5.24 988 5.45 1007 5.66 — —

5 HP Oversize Motor & Drive

Trane�s factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested to operatereliably and continuously at all cataloged conditions. Using the fullhorsepower range of our fan motors as shown in our tabular datawill not result in nuisance tripping or premature motor failure. Ourproduct�s warranty will not be affected.

Table PD-48 � Evaporator Fan Performance 12½ Ton TCH151C

Table PD-48 � Continued

Page 48: Cat

48 RT-PRC002-EN

PerformanceData

(15, 17 ½ Ton)High Efficiency

✲Indicates both downflow and horizontal units.

External Static Pressure (Inches of Water).10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP5 HP Standard Motor & Field Supplied Low Static Drive (1)

5 HP Standard Motor & Drive

5600 — — — — 518 1.45 547 1.60 575 1.75 602 1.91 629 2.08 656 2.26 683 2.43 710 2.63 736 2.83 761 3.03 785 3.236300 — — 532 1.76 561 1.94 588 2.10 614 2.26 639 2.43 663 2.60 687 2.79 711 2.99 735 3.19 759 3.38 783 3.59 807 3.827000 546 2.11 578 2.31 606 2.52 631 2.71 655 2.89 678 3.07 701 3.25 723 3.44 744 3.64 766 3.85 788 4.07 810 4.29 831 4.517700 594 2.75 625 2.98 651 3.21 675 3.43 698 3.64 720 3.84 741 4.03 761 4.23 782 4.44 801 4.65 821 4.87 841 5.10 861 5.348400 642 3.52 671 3.78 697 4.03 720 4.27 741 4.51 762 4.73 782 4.95 802 5.16 821 5.38 840 5.60 858 5.82 876 6.06 894 6.30

5 HP Standard Motor & Drive5 HP Standard Motor & High

Static Drive Accessory7.5 HP Oversize Motor & Drive

External Static Pressure (Inches of Water)1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP5 HP Standard Motor & Drive

5 HP Standard Motor & High Static Drive Accessory

5600 807 3.43 829 3.64 851 3.86 872 4.09 893 4.32 914 4.56 935 4.806300 830 4.04 853 4.27 874 4.49 894 4.72 913 4.95 933 5.19 952 5.437000 852 4.74 874 4.97 895 5.22 917 5.47 937 5.72 957 5.97 975 6.227700 881 5.59 900 5.83 919 6.07 939 6.32 958 6.58 978 6.85 997 7.128400 912 6.55 930 6.81 949 7.08 967 7.34 984 7.60 1002 7.87 — —

7.5 HP Oversize Motor & Drive

Table PD-50 � Evaporator Fan Performance 17½ Ton TCR211C

Table PD-50 � Continued

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.

Trane�s factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested to operatereliably and continuously at all cataloged conditions. Using the fullhorsepower range of our fan motors as shown in our tabular datawill not result in nuisance tripping or premature motor failure. Ourproduct�s warranty will not be affected.

Table PD-49 � Evaporator Fan Performance 15 Ton TCR181CExternal Static Pressure (Inches of Water)

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3 HP Standard Motor & Field Supplied Low Static Drive (1)

3 HP Standard Motor & Drive

4800 — — 444 0.84 472 0.99 503 1.14 535 1.29 566 1.44 598 1.60 629 1.77 658 1.94 684 2.11 710 2.29 735 2.48 760 2.685400 445 1.04 474 1.19 506 1.33 536 1.47 564 1.62 592 1.78 621 1.95 648 2.12 676 2.30 704 2.49 730 2.68 755 2.88 778 3.076000 479 1.38 513 1.55 543 1.72 571 1.87 597 2.03 623 2.19 648 2.36 673 2.55 699 2.74 723 2.93 749 3.13 774 3.34 798 3.566600 519 1.79 552 1.98 580 2.17 606 2.35 632 2.52 656 2.69 679 2.87 702 3.05 725 3.25 748 3.46 771 3.7 794 3.88 816 4.097200 560 2.28 591 2.49 618 2.70 643 2.91 667 3.09 690 3.27 712 3.46 734 3.65 755 3.85 776 4.06 797 4.29 818 4.51 839 4.74

3 HP Standard Motor & Drive 5 HP Oversize Motor & Drive

3 HP Standard Motor & High Static Drive Accessory

Field Supplied Belt may be necessary.

External Static Pressure (Inches of Water)1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP3 HP Standard Motor & High

Static Drive Accessory 5 HP Oversize Motor & Drive4800 785 2.88 809 3.09 832 3.29 854 3.49 876 3.69 898 3.90 919 4.105400 800 3.28 823 3.49 845 3.71 867 3.94 889 4.17 910 4.40 931 4.626000 821 3.77 842 3.99 863 4.20 884 4.43 904 4.66 924 4.90 944 5.156600 839 4.32 862 4.56 884 4.80 904 5.03 924 5.27 943 5.51 961 5.757200 860 4.96 881 5.20 902 5.45 923 5.70 — — — — — —

5 HP Oversize Motor & Drive

Trane�s factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested to operatereliably and continuously at all cataloged conditions. Using the fullhorsepower range of our fan motors as shown in our tabular data willnot result in nuisance tripping or premature motor failure. Ourproduct�s warranty will not be affected.

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.NOTE:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils and filters1. Field Supplied Fan Sheave BK120 Required. Field Supplied Belt may

be necessary. Field Supplied Belt may be necessary.

Table PD-49 � Continued

NOTE:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils and filters1. Field Supplied Fan Sheave BK190 Required. Field

Supplied Belt may be necessary.

✲Indicates both downflow and horizontal units.

Page 49: Cat

RT-PRC002-EN 49

PerformanceData

(20 Ton)High Efficiency

Table 45-2 Evaporator Fan Performance 25 Ton TCQ301C

Table 45-1 Continued

Table PD-51 — Evaporator Fan Performance 20 Ton TCR241C

External Static Pressure (Inches of Water).10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10 1.20 1.30

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP5 HP Standard Motor & Field Supplied Low Static Drive (1)

5 HP Standard Motor & Drive5 HP Standard Motor & High

Static Drive Accessory6400 506 1.64 540 1.84 570 2.03 595 2.19 620 2.34 644 2.51 669 2.69 693 2.89 717 3.09 741 3.29 765 3.49 788 3.70 810 3.917200 560 2.28 592 2.50 620 2.72 646 2.92 668 3.10 690 3.27 711 3.45 733 3.65 755 3.86 777 4.08 799 4.31 820 4.53 841 4.768000 616 3.07 645 3.31 672 3.56 696 3.80 719 4.02 739 4.22 759 4.41 778 4.60 797 4.81 817 5.03 837 5.26 857 5.51 876 5.768800 671 4.04 698 4.29 724 4.55 747 4.83 769 5.10 790 5.34 808 5.56 826 5.77 844 5.98 861 6.20 879 6.43 897 6.67 915 6.939600 728 5.19 753 5.46 776 5.74 799 6.04 820 6.34 840 6.63 859 6.90 876 7.14 893 7.37 909 7.59 925 7.83 941 8.07 958 8.32

(2) 7.5 HP Oversize Motor & Drive

External Static Pressure (Inches of Water)1.40 1.50 1.60 1.70 1.80 1.90 2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP5 HP Standard Motor & High Static Drive Accessory

6400 832 4.12 854 4.34 875 4.57 896 4.80 916 5.04 936 5.29 955 5.547200 862 4.99 883 5.22 902 5.46 922 5.69 942 5.94 961 6.19 980 6.448000 896 6.01 915 6.26 934 6.52 953 6.77 971 7.03 989 7.29 — —8800 933 7.19 951 7.46 969 7.74 986 8.01 — — — — — —9600 974 8.58 — — — — — — — — — — — —

7.5 HP Oversize Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.

NOTES:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils and filters1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may

be necessary.2. 7.5 HP Standard Motor with Field Supplied Motor Sheave 1VP50

Required. Field Supplied Belt may be necessary.

Trane’s factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested to operatereliably and continuously at all cataloged conditions. Using the fullhorsepower range of our fan motors as shown in our tabular datawill not result in nuisance tripping or premature motor failure. Ourproduct’s warranty will not be affected.

Table PD-51 — Continued

RIndicates both downflow and horizontal units.

Page 50: Cat

50 RT-PRC002-EN

Table PD-52 — Evaporator Fan Performance 25 Ton TCR301C

External Static Pressure (Inches of Water).10 .20 .30 .40 .50 .60 .70 .80 .90 1.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP7.5 HP Standard Motor & Low 7.5 HP Standard Motor & Drive

7000 — — — — 608 2.54 633 2.73 656 2.89 678 3.06 700 3.25 723 3.44 745 3.65 768 3.877500 — — 611 2.78 640 3.02 665 3.24 687 3.43 708 3.61 729 3.79 749 3.98 770 4.19 792 4.418000 616 3.07 645 3.31 672 3.56 696 3.80 719 4.02 739 4.22 759 4.41 778 4.60 797 4.81 817 5.038500 650 3.66 678 3.90 704 4.16 728 4.43 750 4.68 771 4.90 790 5.10 808 5.31 826 5.52 844 5.749000 685 4.31 712 4.56 737 4.83 760 5.12 782 5.39 802 5.65 821 5.88 839 6.09 856 6.30 873 6.539500 721 5.04 746 5.30 770 5.58 792 5.88 814 6.18 834 6.46 853 6.72 870 6.96 887 7.18 903 7.41

10000 756 5.85 780 6.12 803 6.41 825 6.72 846 7.04 866 7.35 884 7.64 902 7.90 918 8.14 934 8.3810500 791 6.74 814 7.03 836 7.33 858 7.64 878 7.98 898 8.31 916 8.62 — — — — — —11000 827 7.71 849 8.02 870 8.33 891 8.63 — — — — — — — — — — — —

7.5 HP Standard Motor & Drive — — — — — — — — — — — —

7.5 HP Standard Motor & High Static Drive

External Static Pressure (Inches of Water)1.10 1.20 1.30 1.40 1.50

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP7.5 HP Standard Motor & Drive

7000 790 4.09 812 4.31 833 4.53 854 4.76 875 4.997500 813 4.65 833 4.88 854 5.12 874 5.36 894 5.598000 837 5.26 857 5.51 876 5.76 896 6.01 915 6.268500 863 5.97 881 6.21 900 6.46 919 6.73 937 6.999000 890 6.76 908 7.00 925 7.25 943 7.52 961 7.799500 919 7.64 936 7.88 952 8.13 969 8.40 985 8.67

10000 949 8.62 — — — — — — — —10500 — — — — — — — — — —11000 — — — — — — — — — —

7.5 HP Standard Motor & High Static Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.For Standard Motor & High Static Drive Accessory Fan Speed(RPM), reference Table PD-54.For Standard Motor & Low Static Drive Accessory Fan Speed(RPM), reference Table PD-56.

Trane’s factory supplied motors, in commercial equipment,are definite purpose motors, specifically designed and testedto operate reliably and continuously at all catalogedconditions. Using the full horsepower range of our fanmotors as shown in our tabular data will not result innuisance tripping or premature motor failure. Our product’swarranty will not be affected.

NOTE:Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop due to wet coils andfilters

Table PD-52 — Continued

PerformanceData

(25 Ton)High Efficiency

7.5 HP Std Mtr & Low Static Drive

RIndicates both downflow and horizontal units.

Page 51: Cat

51RT-PRC002-EN

(6-25 Ton)PerformanceData

Table PD-53— Standard Motor & Sheave/Fan Speed (RPM)1

Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 TurnTons Model No. Open Open Open Open Open Open Closed

6, 6¼ TCR074,075 N/A 735 805 875 945 1015 10857, 7½ TCR086,090,091 N/A 722 791 860 929 998 1066

TCD102 N/A 725 773 822 870 919 9678½ TCH102 N/A 604 652 701 749 798 846

TCR103 N/A 649 701 753 805 857 909

10 TCR120 807 857 908 958 1009 1059 N/ATCR121 N/A 519 571 623 675 779 N/A

12½TCR150 706 756 807 857 908 958 N/ATCR151 640 680 720 760 800 840 N/A

TCR180 679 721 764 806 849 891 N/A15

TCR181 560 600 640 680 720 760 N/A

17½TCR210 869 923 978 1032 1087 1141 N/ATCR211 615 659 703 747 791 835 N/A

20 TCR240,TCR241 615 659 703 747 791 835 N/A

25 TCR300,TCR301 705 742 779 817 854 891 N/A

Table PD-54 — Standard Motor & High Static Drive Accessory Fan Speed (RPM)

Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 TurnTons Model No. Open Open Open Open Open Open Closed

8½ TCR102 N/A 870 918 967 1015 1064 1112TCR103 N/A 779 831 883 935 987 1039TCR120 958 1008 1059 1109 1160 1210 N/A

10 TCR121 N/A 779 831 883 935 987 1039

12½ TCR151 807 857 908 958 1009 1059 N/A

15 TCR180 806 849 891 934 976 1019 N/ATCR181 640 680 720 760 800 840 N/A

17½ TCR211 835 879 923 967 1011 1055 N/A20 TCR240/TCR241 835 879 923 967 1011 1055 N/A

25 TCR300/TCR301 816 853 890 928 965 1002 N/A

Table PD-55 — Oversize Motor & Sheave/Fan Speed (RPM)

Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 TurnTons Model No. Open Open Open Open Open Open Closed

6, 6¼,7 TCR074,075,086 N/A 923 992 1060 1129 1197 12657½ TCR090,TCR091 N/A 923 992 1060 1129 1197 1265

8½TCR102 958 1008 1059 1109 1160 1210 N/ATCR103 807 857 908 958 1009 1059 N/A

10TCR120 1032 1086 1141 1195 1250 1304 N/ATCR121 807 857 908 958 1009 1059 N/A

12½TCR150 869 923 978 1032 1087 1141 N/ATCR151 869 923 978 1032 1087 1141 N/A

TCR180 806 856 907 957 1008 1058 N/A15 TCR181 705 755 806 856 907 957 N/A

17½TCR210 949 1008 1068 1127 1187 1246 N/ATCR211 816 853 890 928 965 1002 N/A

20 TCR240,TCR241 816 853 890 928 965 1002 N/ATable PD-56 — Standard Motor & Low Static Fan Drive

Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 TurnTons Model No. Open Open Open Open Open Open Closed

17½ TCR210 705 755 806 856 907 957 N/A25 TCR300/TCR301 594 631 668 705 742 779 N/A

NOTE:1. Factory set at 3 turns open.

RIndicates both downflow and horizontal units.

Page 52: Cat

52 RT-PRC002-EN

(3-17½ Ton)PerformanceData

RIndicates both downflow and horizontal units.

Table PD-57 — Static Pressure Drops Through Accessories (Inches Water Column)

Economizer with Electric Heater

Unit StandardOA/RA Dampers2 Accessory (KW)3

Tons Model No. CFM Filters1 100% OA 100% RA 5-12 14-23 36 54 72

960 .03 .05 .01 .01 .01 — — —3

TCR036C1200 .04 .06 .01 .01 .02 — — —TCR037C1440 .04 .07 .01 .02 .03 — — —

1280 .04 .06 .01 .01 .02 — — —4

TCR048C1600 .06 .02 .08 .02 .04 — — —TCR049C1920 .09 .10 .03 .03 .06 — — —

1600 .04 .08 .02 .02 .04 — — —TCR060C 2000 .06 .10 .03 .03 .07 — — —

5 2400 .08 .12 .06 .05 0.11 — — —

TCR061C 1600 .02 .08 .01 .01 .01 — — —2000 .04 .10 .01 .01 .01 — — —2400 .06 .12 .02 .01 .02 — — —

TCR075C 2000 .04 .10 .01 — .01 .02 — —6, 6¼, 7 TCR074C 2500 .07 .13 .02 — .02 .04 — —

TCR086C 3000 0.10 .15 .03 — .03 .05 — —

2400 .06 .12 .02 — .02 .03 — —7½ TCR090C, D 3000 .10 .15 .03 — .03 .05 — —

TCR091D 3600 .15 .20 .03 — .04 .07 — —

2720 .08/.05 .13 .07/.03 — .06/.05 .07 — —TCD/TCH102C 3400 .13/.08 .16 .11/.04 — .08 .11/.12 — —

4080 .18/.12 .19 .16/.07 — .11 .15/.16 — —8½

2720 .04/.04 .13 .04 — .02 .03 .03 —TCD/TCH103C 3400 .06/.07 .16 .06 — .03 .04 .05 —

4080 .08/.09 .19 .08 — .04 .06 .07 —

3200 .11/.07 .15 .10/.04 — .07/.08 0.10 — —TCD/TCH120C 4000 .17/.11 .19 .15/.06 — .11 .15/.16 — —

4800 .25/.16 .22 .22/.10 — .14/.18 .19/.23 — —10

3200 .03 .13 .01 — .03 .03 .04 —TCR121C 4000 .05 .19 .02 — .04 .05 .06 —

4800 .07 .25 .03 — .06 .07 .09 —

4000 .08/.09 .19 .07 — .07/.05 .09/.07 0.11/.08 —TCD/TCH150C 5000 .12/.14 .23 .12 — .10/.08 .13/.11 0.16/0.13 —

6000 .17/.20 .28 .17 — .14/.11 .18/.15 .22/.19 —12½

4000 .05 .19 .02 — .03 .03 .04 —TCR151C 5000 .07 .26 .03 — .04 .05 .06 —

6000 .10 .33 .04 — .06 .07 .09 —

4800 .07 .25 .03 — .04 .04 .05 —TCR180B 6000 .10 .33 .04 — .06 .07 .08 —

7200 .15 .40 .05 — .09 .10 .12 —15

4800 .04/.03 .14 .03 — 04 .04 .05 —TCD/TCH181C 6000 .06/.05 .20 .04 — 06 .07 .08 —

7200 .09/.07 .27 .05 — 09 .10 .12 —

5600 .09 .30 .04 — — .06 .07 —TCR210C 7000 .14 .39 .05 — — .10 .11 —

8400 .20 .47 .06 — — .15 .17 —17½

5600 .06/.05 .18 .04 — — .05 .06 .07TCD/TCH211C 7000 .09/.07 .26 .04 — — .08 .09 .11

8400 .12/.10 .35 .06 — — .12 .13 .16

NOTES:1. Tested with: 1" filters 3-7½ tons, 2" filters 8½-25 tons2. OA = Outside Air and RA = Return Air.3. Nominal KW ratings at 240, 480, 600 volts.

Page 53: Cat

53RT-PRC002-EN

(20, 25 Ton)PerformanceData

Economizer with Electric Heater

Unit StandardOA/RA Dampers2 Accessory (KW)3

Tons Model No. CFM Filters1 100% OA 100% RA 5-12 14-23 36 54 72

6400 .07 .22 .04 — — .06 .08 .09TCD240B8000 .11 .32 .05 — — .10 .12 .14TCD241C9600 .16 .44 .07 — — .14 .17 .20

206400 .06 .22 .04 — — .06 .08 .09TCH240B8000 .09 .32 .05 — — .10 .12 .14TCH241C9600 .13 .44 .07 — — .14 .17 .20

7000 .09 .26 .04 — — .08 .10 .11TCD300B 9000 .14 .40 .07 — — .13 .15 .18TCD301C 11000 .21 .57 .10 — — .18 .22 .26

25TCH300B 7000 .07 .26 .04 — — .08 .10 .11

TCH301C 9000 .11 .40 .07 — — .13 .15 .1811000 .17 .60 .10 — — .18 .22 .26

NOTES:1. Tested with: 1" filters 3-7½ tons, 2" filters 8½-25 tons2. OA = Outside Air and RA = Return Air.3. Nominal KW ratings at 240, 480, 600 volts.

RIndicates both downflow and horizontal units.

Table PD-57 — Static Pressure Drops Through Accessories (Inches Water Column) Continued

Page 54: Cat

54 RT-PRC002-EN

(3-25 Ton)PerformanceData

Table PD-58 — Auxiliary Electric Heat Capacity

Total2 Stage1 Stage 2

Unit KW MBH No. of KW MBH KW MBHTons Model No. Input1 Output1 Stages Input1 Output1 Input1 Output1

5.00 17.07 1 5.00 17.07 — —TCD036C1 10.00 34.14 2 5.00 17.07 5.00 17.07

13.80 47.10 2 8.80 30.03 5.00 17.073

6.00 20.48 1 6.00 20.48 — —TCD036C3, C4

12.00 40.96 2 6.00 20.48 6.00 20.48TCD037C3, C4

17.40 59.39 2 8.70 29.69 8.70 29.69

5.00 17.07 1 5.00 17.07 — —10.00 34.14 2 5.00 17.07 5.00 17.07

TCR048, 060C113.80 47.10 2 8.80 30.03 5.00 17.0717.60 60.07 2 8.80 30.03 8.80 30.036.00 20.48 1 6.00 20.48 — —

TCR048, 060C3, C4, CW 12.00 40.96 2 6.00 20.48 6.00 20.48TCR049C3, C4 17.40 59.39 2 8.70 29.69 8.70 29.69

23.00 78.50 2 14.30 48.81 8.70 29.69

9.003 30.72 1 9.00 30.7 — —TCR061C3,C4 17.303, 4 59.04 1 17.30 59.0 — —TCR074, 75C3, C4, CW 18.00 61.43 1 18.00 61.4 — —

5,6, 6¼, 7, 7½TCR090C3, D3, C4, D4, CW, DW 27.004 92.15 2 18.00 61.4 9.00 30.7TCR086C,TCR091D 36.003, 4 122.87 2 18.00 61.4 18.00 61.4

TCR102, 120, 150C3, C4, CW 18.00 61.47 1 18.00 61.47 — —8½-15 TCR180B3, B4, BW 36.00 122.94 2 18.00 61.47 18.00 61.47

TCR103, 121, 151 or 181C3, C4,CW 54.005 184.41 2 36.00 122.94 18.00 61.47

TCR210C3, C4, CW, 36.00 122.94 2 18.00 61.47 18.00 61.4717½, 20, 25 240, 300B3, B4, BW 54.00 184.41 2 36.00 122.94 18.00 61.47

TCR211, 241, 301C3,C4,CW 72.006 245.88 2 36.00 122.94 36.00 122.94

4, 5

NOTES:1. Does not include indoor fan power or heat.2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP = x rated cap.3. Not available for TCR075, 090CW.4. Not available for TCR061C3,C4.5. Not available on TCR102, 120C.6. Not available on TCR210C.

( )Voltage 2

Rated Voltage

RIndicates both downflow and horizontal units.

Table PD-59— Electric Heater Voltage

Correction Factors (Applicable to Auxiliary

Heat Capacity)

Nominal Distribution CapacityVoltage Voltage Multiplier

208 0.75240 230 0.92

240 1.00

440 0.84480 460 0.94

480 1.00

540 0.81600 575 0.92

600 1.00

Page 55: Cat

55RT-PRC002-EN

(3-25 Ton)PerformanceData

RIndicates both downflow and horizontal units.

3 Ton 4 Ton 5 Ton 1200 CFM 1600 CFM 2000 CFM

Single Phase Three Phase Single Phase Three Phase Single Phase Three PhaseTCD036C3, C4 TCR048C3,C4 TCR060C3, C4

KW Stages TCD036C1 TCD037C3, C4 TCR048C1 TCR049C3,C4 TCR060C1 TCR061C3, C4

5.00 1 13.2 — 9.9 — 7.9 —6.00 1 — 15.8 — 11.9 — 9.5

10.00 2 26.4 — 19.8 — 15.8 —12.00 2 — 31.6 — 23.7 — 19.013.80 2 36.4 — 27.3 — 21.8 —17.40 2 — 45.9 — 34.4 — 27.517.60 2 — — 34.8 — 27.8 —23.00 2 — — — 45.5 — 36.4

For minimum design airflow, see airflow performance table for each unit.To calculate temp rise at different air flow, use following formula:

Temp. Rise across Elect. Htr = KW x 34131.08 x CFM

NOTE:1. TCR061C3,C4, 23 KW not available.

Table PD-60 Continued

6¼ Ton 7½ Ton 8½ Ton 10 Ton 12½ Ton 15 Ton 17½ Ton 20 Ton 25 Ton2500 CFM 3000 CFM 3400 CFM 4000 CFM 5000 CFM 6000 CFM 7000 CFM 8000 CFM 9000 CFM

Three Phase Three Phase Three Phase Three Phase Three Phase Three Phase Three Phase Three Phase Three PhaseTCR075 TCR090 TCR102 TCR120 TCR150 TCR180 TCR210 TCR240 TCR300

KW Stages TCR074C TCR086C,91D TCR103 TCR121 TCR151 TCR181 TCR211 TCR241 TCR301

9.00 1 11.4 9.5 — — — — — — —17.30 1 21.9 18.2 — — — — — — —18.00 1 22.8 19.0 17.8 14.2 11.4 9.5 — — —27.00 2 34.2 28.5 — — — — — — —36.00 2 45.5 37.9 35.6 28.5 22.8 19.0 16.3 14.2 12.654.001 2 — — 53.4 42.7 34.1 28.5 24.4 21.3 19.072.002 2 — — — — — — 32.5 28.5 25.3

For minimum design airflow, see airflow performance table for each unit.To calculate temp rise at different air flow, use following formula:

Temp. Rise across Elect. Htr = KW x 34131.08 x CFM

NOTES:1. Not available on TCR102, 120 models.2. Not available on TCR210 model.

Table PD-60 — Air Temperature Rise Across Electric Heaters (Degree F)

Page 56: Cat

56 RT-PRC002-EN

Controls

Programmable Night Setback —Auto or manual changeover withseven-day programming. Keyboardselection of Heat, Cool, Fan, Auto, or On.All programmablesensors haveSystemOn, Heat, Cool,Service LED/indicators asstandard.NightSetbackSensorshave one(1) Occupied,one (1)Unoccuped,and two (2)Overrideprograms perday.

Integrated ComfortTM System —Sensor(s) available with optionaltemperatureadjustment andoverride buttonsto providecentral controlthrough a TraneIntegratedComfortTM

system.

EconomizerControls — Thestandardequipmentoffering is a fixeddry bulbchangeovercontrol. In addition, there are twooptional controls, Enthalpy andDifferential Enthalpy Control.

Enthalpy Control — Replaces the drybulb control with a wet bulb changeovercontroller which has a fully adjustableset point. Enthalpy control offers ahigher level of comfort control, alongwith energy savings potential, than thestandard dry bulb control. This is due tothe additional wet bulb sensingcapability.

Differential Enthalpy — Replaces thestandard dry bulb control with twoenthalpy sensors that compare total heatcontent of the indoor air and outdoor airto determine the most efficient airsource. This control option offers thehighest level of comfort control, plusenergy efficiency, available.

Remote Potentiometer — Minimumposition setting of economizer can beremotely adjusted with this accessory.

Trane Communication Interface(TCI) — This factory or field-installedmicro-processor interface allows the unitto communicate to Trane’s IntegratedComfortTM system.

Conventional Thermostat Interface(CTI) — This factory or field-installedoption will allow the Micro units tointerface with most conventional electro-mechanical thermostats.

Differential Pressure Switches —This factory or field-installed optionallows individual fan failure and dirtyfilter indication. The fan failure switchwill disable all unit functions and “flash”the Service LED on the zone sensor. Thedirty filter switch will light the ServiceLED on the zone sensor and will allowcontinued unit operation.

Input / Output Expansion Accessory— This factory or field-installed optionallows Integrated ComfortTM Sytems toread Supply Air Temperature, Return AirTemperature, Return Air Humidity, anddirect indication of fan failure withoutthe use of an economizer or motorizedoutside air accessory.

Electronic Time Clock — This fieldinstalled accessory allows up to 4 unitsnight set-back and unoccupied functionswhen using a standard (Dual Setpoint)zone sensor module.

Field Installed Control Options

Zone Sensors are the buildingoccupant’s comfort control devices. Theyreplace the conventional electro-mechanical thermostats. The followingzone sensor options are available forVoyager units with the Micro control:

Manual Changeover — Heat, Cool orOff System Switch. Fan Auto or OffSwitch. Onetemperaturesetpoint lever.

Manual/Automatic Changeover —Auto, Heat, Cool or Off System Switch.Fan Auto or OffSwitch. Twotemperaturesetpointlevers. OptionalStatus IndicationLED lights,System On,Heat, Cool, orService.

Remote Sensor — Sensor(s) availablefor all zone sensors to provideremote sensing capabilities.

Page 57: Cat

57RT-PRC002-EN

RIndicates both downflow and horizontal units.

ElectricalData

Table ED-1 — Unit Wiring Standard Efficiency

Standard Indoor Fan Motor Oversize Indoor Fan MotorUnit Minimum Maximum Fuse Minimum Maximum Fuse

Unit Operating Circuit Size Or Maximum Circuit Size Or MaximumTons Model No. Voltage Range Ampacity2 Circuit Breaker1 Ampacity2 Circuit Breaker1

TCD036C1 187-253 27.1 40 28.3 453 TCD036C3 187-253 18.6 25 19.8 30

TCD036C4 414-506 9.4 15 9.7 15

TCR048C1 187-253 36.3 60 38.7 60TCR048C3 187-253 24.8 35 27.2 40

4TCR048C4 414-506 11.9 15 13.0 20TCR048CW 517-633 9.5 15 10.3 15

TCR060C1 187-253 46.5 60 47.8 60TCR060C3 187-253 31.3 45 32.6 50

5TCR060C4 414-506 16.3 25 16.9 25TCR060CW 517-633 11.9 15 12.0 15

TCR075C3 187-253 36.6 50 39.5 606¼ TCR075C4 414-506 17.7 25 18.9 25

TCR075CW 517-633 14.2 20 14.7 20

TCR090C3 / D3 187-253 43.1/41.7 60/50 46.0/44.6 60/507½ TCR090C4 / D4 414-506 20.9/20.8 30/25 22.1/22.0 30/25

TCR090CW / DW 517-633 16.7/16.0 25/20 17.2/16.5 25/20

TCR102C3 187-253 49 60 53 608½ TCR102C4 414-506 29 35 31 40

TCR102CW 517-633 19 20 20 25

TCR120C3 187-253 55 60 59 7010 TCR120C4 414-506 31 40 34 40

TCR120CW 517-633 22 25 24 30

TCR150C3 187-253 71 80 77 9012½ TCR150C4 414-506 32 40 35 45

TCR150CW 518-633 25 30 27 35

TCR180B3 187-253 85 100 91 10015 TCR180B4 414-506 38 50 41 50

TCR180BW 517-633 31 40 34 45

TCR210C3 187-253 101 125 109 12517½ TCR210C4 414-506 45 60 49 60

TCR210CW 517-633 37 45 40 50

TCR240B3 187-253 123 150 130 15020 TCR240B4 414-506 53 60 57 70

TCR240BW 517-633 42 50 45 50

TCR300B3 187-253 132 150 N/A N/A25 TCR300B4 414-506 57 70 N/A N/A

TCR300BW 517-633 45 50 N/A N/A

NOTE:1. HACR breaker per NEC.2. Values do not include power exhaust accessory.

Page 58: Cat

58 RT-PRC002-EN

ElectricalData

RIndicates both downflow and horizontal units.

Table ED-2 — Unit Wiring High Efficiency

Standard Indoor Fan Motor Oversize Indoor Fan MotorUnit Minimum Maximum Fuse Minimum Maximum Fuse

Unit Operating Circuit Size Or Maximum Circuit Size Or MaximumTons Model No. Voltage Range Ampacity2 Circuit Breaker1 Ampacity2 Circuit Breaker1

TCD037C3 187-253 19.6 30 20.8 303

TCD037C4 414-506 9.9 15 10.2 15

TCR049C3 187-253 24.7 35 27.1 404

TCR049C4 414-506 11.8 15 12.9 15

TCR061C3 187-253 30.6 45 31.9 505

TCR061C4 414-506 15.9 25 16.5 25

TCR074C3 187-253 35.2 50 38.1 506

TCR074C4 414-506 16.6 25 17.8 25

TCR086C3 187-253 38.1 60 41.0 607

TCR086C4 414-506 18.1 25 19.3 25

TCR091D3 187-253 41.7 50 44.6 507½

TCR091D4 414-506 21.6 25 22.8 25

TCR103C3 187-253 45 50 48 608½

TCR103C4 414-506 24 30 25 30TCR103CW 517-633 19 20 20 25

TCR121C3 187-253 49 60 52 6010

TCR121C4 414-506 30 35 31 40TCR121CW 517-633 22 25 23 25

TCR151C3 187-253 61 80 67 8012½

TCR151C4 414-506 31 40 34 40TCR151CW 517-633 25 30 27 30

TCR181C3 187-253 81 100 87 10015

TCR181C4 414-506 38 50 40 50TCR181CW 517-633 30 40 33 45

TCR211C3 187-253 94 110 102 12517½

TCR211C4 414-506 46 60 49 60TCR211CW 517-633 36 45 39 50

TCR241C3 187-253 123 150 130 15020

TCR241C4 414-506 53 60 56 70TCR241CW 517-633 42 50 45 50TCR301C3 187-253 130 150 N/A N/A

25 TCR301C4 414-506 56 70 N/A N/ATCR301CW 517-633 45 50 N/A N/A

NOTE:1. HACR breaker per NEC.2. Values do not include power exhaust accessory.

Page 59: Cat

59RT-PRC002-EN

RIndicates both downflow and horizontal units.

Table ED-4 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency

Standard Indoor Motor Oversize Indoor Motor

To Use Heater Heater Control Max Fuse Size Or Max Fuse Size OrTons With Model No. KW Rating1 Stages MCA Max Circuit Breaker2 MCA Max Circuit Breaker2

208/230 Volts Single Phase

BAYHTRP105A 3.7/5.0 1 27.1/29.3 40/40 28.3/30.8 45/453 TCD036C1 BAYHTRP110A 7.5/10.0 2 48.3/55.3 50/60 49.9/56.8 50/60

BAYHTRP114A 10.3/13.8 2 65.5/75.1 70/80 67.0/76.6 70/80

BAYHTRP105A 3.7/5.0 1 36.3/36.3 60/60 38.7/38.7 60/60BAYHTRP110A 7.5/10.0 2 50.4/57.3 60/60 53.4/60.3 60/70

4 TCR048C1BAYHTRP114A 10.3/13.8 2 67.5/77.1 70/80 70.5/80.1 80/90BAYHTRP118A 13.2/17.6 2 84.7/96.9 90/100 87.7/99.9 90/100

BAYHTRP105A 3.7/5.0 1 46.5/46.5 60/60 47.8/47.8 60/60BAYHTRP110A 7.5/10.0 2 51.8/58.7 60/60 53.4/60.3 60/70

5 TCR060C1BAYHTRP114A 10.3/13.8 2 68.9/78.5 70/80 70.5/80.1 80/90BAYHTRP118A 13.2/17.6 2 86.1/98.3 90/100 87.7/99.9 90/100

208/230 Volts Three Phase

BAYHTRP306A 4.5/6.0 1 18.9/21.3 25/25 20.4/22.8 30/303 TCD036C3 BAYHTRP312A 9.0/12.0 2 34.5/39.3 35/40 36.0/40.8 40/45

BAYHTRP318A 13.0/17.4 2 48.6/55.6 50/60 50.1/57.1 60/60

BAYHTRP306A 4.5/6.0 1 24.8/24.8 35/35 27.2/27.2 40/40BAYHTRP312A 9.0/12.0 2 36.5/41.3 40/45 39.5/44.3 40/45

4 TCR048C3BAYHTRP318A 13.0/17.4 2 50.6/57.6 60/60 53.6/60.6 60/70BAYHTRP323A 17.2/23.0 2 65.2/74.4 70/80 68.2/77.4 70/80

BAYHTRP306A 4.5/6.0 1 31.3/31.3 45/45 32.6/32.6 50/50BAYHTRP312A 9.0/12.0 2 37.9/42.7 45/45 39.5/44.3 50/50

5BAYHTRP318A 13.0/17.4 2 52.0/59.0 60/60 53.6/60.6 60/70BAYHTRP323A 17.2/22.0 2 66.6/75.8 70/80 68.2/77.4 70/80

AYRHTRA309BA 6.75/9.0 1 36.6/36.6 50/50 39.5/39.5 60/60AYRHTRA318BA 12.9/17.3 1 52.5/59.4 60/60 56.1/63.0 60/70

6¼AYRHTRA327BA 20.2/27.0 2 77.7/88.6 80/90 81.4/92.2 90/100AYRHTRA336BA 27.0/36.0 2 101.2/115.6 110/125 104.8/119.3 110/125

NOTES:1. Heater kw ratings are at 208/240 for 208/230V unit2. HACR type circuit breaker per NEC.

TCR060C3

TCR075C3

ElectricalData

Table ED-3 — Electrical Characteristics — Power Exhaust Accessory

AccessoryAccessory Operating

Amps

Tons Model Number Voltage Phase HP RPM FLA LRA

BAYPWRX013 208-230 1 .75 1100 6.6 13.5

6, 6¼, 7, 7½ BAYPWRX015 460 1 .75 1100 3.1 6.4

BAYPWRX014 575 1 .75 1100 2.4 5.2

BAYPWRX016 208-230 1 3/4 1040 6.6 13.5

8½, 101, 12½1 BAYPWRX017 460 1 3/4 1040 3.2 8.4

BAYPWRX018 575 1 3/4 1040 2.1 5.2

102, 12½2 BAYPWRX019 208-230 1 3/4 1040 6.6 13.5

15, 17½ BAYPWRX020 460 1 3/4 1040 3.2 8.4

20, 25 BAYPWRX021 575 1 3/4 1040 2.1 5.2

NOTES:1. 10 and 12½ Ton Standard Unit.2. 10 and 12½ Ton High Efficiency Unit.

Page 60: Cat

60 RT-PRC002-EN

Table ED-4 Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency Continued

Standard Indoor Motor Oversize Indoor Motor

To Use Heater Heater Control Max Fuse Size Or Max Fuse Size OrTons With Model No. KW Rating1 Stages MCA Max Circuit Breaker2 MCA Max Circuit Breaker2

208/230 Volts Three Phase

AYRHTRA309BA 6.75/9.0 1 43.1/43.1 60/60 46.0/46.0 60/60AYRHTRA318BA 12.9/17.3 1 52.5/59.4 60/60 56.1/63.0 60/70

TCR090C3AYRHTRA327BA 20.2/27.0 2 77.7/88.6 80/90 81.4/92.2 90/100AYRHTRA336BA 27.0/36.0 2 101.2/115.6 110/125 104.8/119.3 110/125

7½AYRHTRA309BA 6.75/9.0 1 41.7/41.7 50/50 44.6/44.6 50/50AYRHTRA318BA 12.9/17.3 1 52.5/59.4 60/60 56.1/63.0 60/70

TCR090D3AYRHTRA327BA 20.2/27.0 2 77.7/88.6 80/90 81.4/92.2 90/100AYRHTRA336BA 27.0/36.0 2 101.2/115.6 110/125 104.8/119.3 110/125

AYRHTRJ318A 13.5/18.0 1 57/64 60/70 61/68 70/708½ TCR102C3

AYRHTRJ336A 27.0/36.0 2 104/118 110/125 108/122 110/125

AYRHTRJ318A 13.5/18.0 1 59/66 60/70 64/71 70/8010 TCR120C3

AYRHTRJ336A3 27.0/36.0 2 106/121 110/125 N/A N/A

AYRHTRF318A 13.5/18.0 1 71/71 80/80 77/77 90/9012½ TCR150C3 AYRHTRF336A 27.0/36.0 2 108/122 110/125 115/130 125/150

AYRHTRF354A 40.5/54.0 2 154/176 175/200 162/184 175/200

AYRHTRF318A 13.5/18.0 1 85/85 100/100 91/91 100/10015 TCR180B3 AYRHTRF336A 27.0/36.0 2 108/122 110/125 115/130 125/150

AYRHTRF354A 40.5/54.0 2 154/176 175/200 162/184 175/200

AYRHTRH336A 27.0/36.0 2 115/130 125/150 125/139 125/15017½ TCR210C3

AYRHTRH354A 40.5/54.0 2 162/184 175/200 171/193 175/200

AYRHTRH336A 27.0/36.0 2 123/130 150/150 130/139 150/15020 TCR240B3 AYRHTRH354A 40.5/54.0 2 162/184 175/200 171/193 175/200

AYRHTRH372A 54.0/72.0 2 209/238 225/250 218/247 225/250

AYRHTRH336A 27.0/36.0 2 130/139 150/150 — —25 TCR300B3 AYRHTRH354A 40.5/54.0 2 171/193 175/200 — —

AYRHTRH372A 54.0/72.0 2 218/247 225/250 — —

460 Volts Three Phase

BAYHTRP406A 6.0 1 11.0 15 11.4 153 TCD036C4 BAYHTRP412A 12.0 2 20.0 25 20.4 25

BAYHTRP418A 17.4 2 28.2 30 28.5 30

BAYHTRP406A 6.0 1 11.9 15 13.0 20BAYHTRP412A 12.0 2 20.5 25 21.9 25

4 TCR048C4BAYHTRP418A 17.4 2 28.7 30 30.0 35BAYHTRP423A 23.0 2 37.1 40 38.5 40

BAYHTRP406A 6.0 1 16.3 25 16.9 25BAYHTRP412A 12.0 2 21.2 25 21.9 25

5 TCR060C4BAYHTRP418A 17.4 2 29.3 30 30.0 35BAYHTRP423A 23.0 2 37.7 40 38.5 40

AYRHTRA409BA 9.0 1 17.7 25 19.0 25AYRHTRA418BA 18.0 1 31.1 35 32.6 35

6¼ TCR075C4AYRHTRA427BA 27.0 2 44.6 45 46.1 50AYRHTRA436BA 36.0 2 58.1 60 59.6 60

NOTES:1. Heater kw ratings are at 208/240 for 208/230V unit2. HACR type circuit breaker per NEC.3. Do not use in conjunction with oversized motor.

RIndicates both downflow and horizontal units.

ElectricalData

Page 61: Cat

61RT-PRC002-EN

RIndicates both downflow and horizontal units.

ElectricalData

Table ED-4 Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency Continued

Standard Indoor Motor Oversize Indoor Motor

To Use Heater Heater Control Max Fuse Size Or Max Fuse Size OrTons With Model No. KW Rating1 Stages MCA Max Circuit Breaker2 MCA Max Circuit Breaker2

460 Volts Three Phase

AYRHTRA409BA 9.0 1 20.9 30 22.1 30AYRHTRA418BA 18.0 1 31.1 35 32.6 35

7½ TCR090C4AYRHTRA427BA 27.0 2 44.6 45 46.1 50AYRHTRA436BA 36.0 2 58.1 60 59.6 60

AYRHTRA409BA 9.0 1 20.8 25 22.0 25AYRHTRA418BA 18.0 1 31.1 35 32.6 35

TCR090D4AYRHTRA427BA 27.0 2 44.6 45 46.1 50AYRHTRA436BA 36.0 2 58.1 60 59.6 60

AYRHTRJ418A 18.0 1 32 35 34 408½ TCR102C4

AYRHTRJ436A 36.0 2 59 60 61 70

AYRHTRJ418A 18.0 1 34 40 37 4010 TCR120C4

AYRHTRJ436A 36.0 2 61 70 64 70

AYRHTRE418A3 18.0 1 34 40 37 4512½ TCR150C4 AYRHTRE436A 36.0 2 61 70 64 70

AYRHTRE454A 54.0 2 88 90 91 100

AYRHTRE418A3 18.0 1 38 50 41 5015 TCR180B4 AYRHTRE436A 36.0 2 61 70 64 70

AYRHTRE454A 54.0 2 88 90 91 100

AYRHTRG436A 36.0 2 64 70 68 7017½ TCR210C4

AYRHTRG454A 54.0 2 91 100 95 100

AYRHTRG436A 36.0 2 64 70 68 7020 TCR240B4 AYRHTRG454A 54.0 2 91 100 95 100

AYRHTRH472A 72.0 2 118 125 123 125

AYRHTRG436A 36.0 2 68 70 — —25 TCR300B4 AYRHTRG454A 54.0 2 95 100 — —

AYRHTRH472A 72.0 2 123 125 — —

575 Volts Three Phase

BAYHTRPW06A 6.0 1 9.5 15 10.3 15BAYHTRPW12A 12.0 2 16.6 20 17.6 20

4 TCR048CWBAYHTRPW18A 17.4 2 23.1 25 24.1 25BAYHTRPW23A 23.0 2 29.8 35 30.8 35

BAYHTRPW06A 6.0 1 11.9 15 12.0 15BAYHTRPW12A 12.0 2 17.4 20 17.6 20

5 TCR060CWBAYHTRPW18A 17.4 2 23.9 25 24.1 25BAYHTRPW23A 23.0 2 30.7 35 30.8 35

AYRHTRAW18BA 18.0 1 24.9 25 25.5 306¼ TCR075CW

AYRHTRAW27BA 27.0 2 35.7 40 36.4 40

AYRHTRAW18BA 18.0 1 24.9 25 25.5 307½ TCR090CW,DW

AYRHTRAW27BA 27.0 2 35.7 40 36.4 40

AYRHTRJW18A 18.0 1 26 30 27 308½ TCR102CW

AYRHTRJW36A 36.0 2 48 50 49 50

NOTES:1. Heater kw ratings are at 480V for 460 unit and 600V for 575V unit.2. HACR type circuit breaker per NEC.3. Heater model number for horizontal is AYHHTRC418A.

Page 62: Cat

62 RT-PRC002-EN

ElectricalData

Table ED-4 Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency Continued

Standard Indoor Motor Oversize Indoor Motor

To Use Heater Heater Control Max Fuse Size Or Max Fuse Size OrTons With Model No. KW Rating1 Stages MCA Max Circuit Breaker2 MCA Max Circuit Breaker2

575 Volts Three Phase

AYRHTRJW18A 18.0 1 27 30 30 3010 TCR120CW

AYRHTRJW36A 36.0 2 49 50 51 60

AYRHTRDW18A4 18.0 1 27 30 30 3512½ TCR150CW AYRHTRGW36A4 36.0 2 49 50 51 60

AYRHTREW54A 54.0 2 70 70 73 80

AYRHTRDW18A4 18.0 1 31 40 34 4515 TCR180BW AYRHTRGW36A4 36.0 2 49 50 51 60

AYRHTREW54A 54.0 2 70 70 73 80

AYRHTRGW36A3 36.0 2 51 60 55 6017½ TCR210CW

AYRHTRGW54A 54.0 2 73 80 77 80

AYRHTRGW36A3 36.0 2 51 60 55 6020 TCR240BW AYRHTRGW54A 54.0 2 73 80 77 80

AYRHTRHW72A 72.0 2 95 100 98 100

AYRHTRGW36A3 36.0 2 55 60 — —25 TCR300BW AYRHTRGW54A 54.0 2 77 80 — —

AYRHTRHW72A 72.0 2 98 100 — —

NOTES:1. Heater kw ratings are at 600V for 575V unit2. HACR type circuit breaker per NEC.3. The heater model number for horizontal is AYHHTRCW36A.4. The heater model number for horizontal is AYHHTRCW18A, AYHHTRCW36A.

RIndicates both downflow and horizontal units.

Page 63: Cat

63RT-PRC002-EN

ElectricalData

Table ED-5 — Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency

Standard Indoor Motor Oversize Indoor Motor

To Use Heater Heater Control Max Fuse Size Or Max Fuse Size OrTons With Model No. KW Rating1 Stages MCA Max Circuit Breaker2 MCA Max Circuit Breaker2

208/230 Volts Three Phase

BAYHTRP306A 4.5/6.0 1 19.6/21.3 30/30 20.8/22.8 30/303 TCD037C3 BAYHTRP312A 9.0/12.0 2 34.5/39.3 35/40 36.0/40.8 40/45

BAYHTRP318A 13.0/17.4 2 48.5/55.6 50/60 50.1/57.1 60/60

BAYHTRP306A 4.5/6.0 1 24.7/24.7 35/35 27.1/27.1 40/40BAYHTRP312A 9.0/12.0 2 36.5/41.3 40/45 39.5/44.3 40/45

4 TCR049C3BAYHTRP318A 13.0/17.4 2 50.6/57.6 60/60 53.6/60.6 60/70BAYHTRP323A 17.2/23.0 2 65.2/74.4 70/80 68.2/77.4 70/80

AYRHTRA309B 6.7/9.0 1 30.6/33.7 45/45 31.9/35.3 50/505

TCR061C3AYRHTRA318B 12.9/17.3 1 51.7/58.6 60/60 53.3/60.3 60/70

AYRHTRA309B 6.7/9.0 1 35.2/35.2 50/50 38.1/38.1 50/50AYRHTRA318B 12.9/17.3 1 52.5/59.4 60/60 56.1/63.0 60/70

6 TCR074C3AYRHTRA327B 20.2/27.0 2 77.7/88.6 80/90 81.4/92.2 90/100AYRHTRA336B 27.0/36.0 2 101.2/115.6 110/125 104.8/119.3 110/125

AYRHTRA309B 6.7/9.0 1 38.1/38.1 60/60 41.0/41.0 60/60AYRHTRA318B 12.9/17.3 1 52.5/59.4 60/60 56.1/63.0 60/70

7 TCR086C3AYRHTRA327B 20.2/27.0 2 77.7/88.6 80/90 81.4/92.2 90/100AYRHTRA336B 27.0/36.0 2 101.2/115.6 110/125 104.8/119.3 110/125

AYRHTRA309B 6.7/9.0 1 41.7/41.7 50/50 44.6/44.6 50/50AYRHTRA318B 12.9/17.3 1 52.5/59.4 60/60 56.1/63.0 60/70

7½ TCR091D3AYRHTRA327B 20.2/27.0 2 77.7/88.6 80/90 81.4/92.2 90/100AYRHTRA336B 27.0/36.0 2 101.2/115.6 110/125 104.8/119.3 110/125

AYRHTRD318A 13.5/18.0 1 57/64 60/70 61/68 70/708½ TCR103C3 AYRHTRD336A 27.0/36.0 2 104/118 110/125 108/122 110/125

AYRHTRD354A 40.5/54.0 2 151/172 175/175 154/176 175/200

AYRHTRD318A 13.5/18.0 1 57/64 60/70 61/68 70/7010 TCR121C3 AYRHTRD336A 27.0/36.0 2 104/118 110/125 108/122 110/125

AYRHTRD354A 40.5/54.0 2 151/172 175/175 154/176 175/200

AYRHTRF318A 13.5/18.0 1 72/72 80/80 78/78 90/9012½ TCR151C3 AYRHTRF336A 27.0/36.0 2 108/122 110/125 115/130 125/150

AYRHTRF354A 40.5/54.0 2 154/176 175/200 162/184 175/200

AYRHTRF318A 13.5/18.0 1 81/81 100/100 87/87 100/10015 TCR181C3 AYRHTRF336A 27.0/36.0 2 108/122 110/125 115/130 125/150

AYRHTRF354A 40.5/54.0 2 154/176 175/200 162/184 175/200

AYRHTRH336A 27.0/36.0 2 115/130 125/150 125/139 125/15017½ TCR211C3 AYRHTRH354A 40.5/54.0 2 162/184 175/200 171/193 175/200

AYRHTRH372A 54.0/72.0 2 209/238 225/250 218/247 225/250

AYRHTRH336A 27.0/36.0 2 123/130 150/150 130/139 150/15020 TCR241C3 AYRHTRH354A 40.5/54.0 2 162/184 175/200 171/193 175/200

AYRHTRH372A 54.0/72.0 2 209/238 225/250 218/247 225/250AYRHTRH336A 27.0/36.0 2 132/139 150/150 — —

25 TCR301C3 AYRHTRH354A 40.5/54.0 2 171/193 175/200 — —AYRHTRH372A 54.0/72.0 2 218/247 225/250 — —

NOTES:1. Heater kw ratings are at 208/240 for 208/230V unit2. HACR type circuit breaker per NEC.

RIndicates both downflow and horizontal units.

Page 64: Cat

64 RT-PRC002-EN

Table ED-5 Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency Continued

Standard Indoor Motor Oversize Indoor Motor

To Use Heater Heater Control Max Fuse Size Or Max Fuse Size OrTons With Model No. KW Rating1 Stages MCA Max Circuit Breaker2 MCA Max Circuit Breaker12

460 Volts Three Phase

BAYHTRP406A 6.0 1 11.0 15 11.4 153 TCD037C4 BAYHTRP412A 12.0 2 20.0 25 20.4 25

BAYHTRP418A 17.4 2 28.2 30 28.5 30

BAYHTRP406A 6.0 1 11.8 15 12.9 20BAYHTRP412A 12.0 2 20.5 25 21.9 25

4 TCR049C4BAYHTRP418A 17.5 2 28.7 30 30.0 35BAYHTRP423A 23.0 2 37.1 40 38.5 40

AYRHTRA409B 9.0 1 16.7 25 17.4 25AYRHTRA418B 18.0 1 30.2 35 30.9 35

AYRHTRA409B 9.0 1 17.5 25 19.0 25AYRHTRA418B 18.0 1 31.1 35 32.6 35

6 TCR074C4AYRHTRA427B 27.0 2 44.6 45 46.1 50AYRHTRA436B 36.0 2 58.1 60 59.6 60

AYRHTRA409B 9.0 1 18.1 25 19.3 25AYRHTRA418B 18.0 1 31.1 35 32.6 35

7 TCR086C4AYRHTRA427B 27.0 2 44.6 45 46.1 50AYRHTRA436B 36.0 2 58.1 60 59.6 60

AYRHTRA409B 9.0 1 21.6 25 22.8 25AYRHTRA418B 18.0 1 31.1 35 32.6 35

7½ TCR091D4AYRHTRA427B 27.0 2 44.6 45 46.1 50AYRHTRA436B 36.0 2 58.1 60 59.6 60

AYRHTRC418A 18.0 1 32 35 34 358½ TCR103C4 AYRHTRD436A4 36.0 2 59 60 61 70

AYRHTRD454A4 54.0 2 86 90 88 90

AYRHTRC418A 18.0 1 32 35 34 4010 TCR121C4 AYRHTRD436A4 36.0 2 59 60 61 70

AYRHTRD454A4 54.0 2 86 90 88 90

AYRHTRF418A3 18.0 1 34 40 37 4512½ TCR151C4 AYRHTRF436A 36.0 2 61 70 64 70

AYRHTRF454A 54.0 2 88 90 91 100

AYRHTRE418A3 18.0 1 38 50 40 5015 TCR181C4 AYRHTRE436A 36.0 2 61 70 64 70

AYRHTRE454A 54.0 2 88 90 91 100

AYRHTRG436A 36.0 2 64 70 68 7017½ TCR211C4 AYRHTRG454A 54.0 2 91 100 95 100

AYRHTRH472A 72.0 2 118 125 122 125

AYRHTRG436A 36.0 2 64 70 68 7020 TCR241C4 AYRHTRG454A 54.0 2 91 100 95 100

AYRHTRH472A 72.0 2 118 125 122 125AYRHTRG436A 36.0 2 68 70 — —

25 TCR301C4 AYRHTRG454A 54.0 2 95 100 — —AYRHTRH472A 72.0 2 122 125 — —

NOTES:1. HACR type circuit breaker per NEC.2. Values do not include power exhaust accessory.3. Horizontal model heater number is AYHHTRC418A.4. Horizontal model heater numbers are AYHHTRE436A and AYHHTRE454A.

5 TCR061C4

ElectricalData

RIndicates both downflow and horizontal units.

Page 65: Cat

65RT-PRC002-EN

ElectricalData

Table ED-5 Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency Continued

Standard Indoor Motor Oversize Indoor Motor

To Use Heater Heater Control Max Fuse Size Or Max Fuse Size OrTons With Model No. KW Rating1 Stages MCA Max Circuit Breaker2 MCA Max Circuit Breaker12

575 Volts Three Phase

TCR103CW AYRHTRCW18A 18.0 1 32 35 34 358½ TCR103CW AYRHTRDW36A 36.0 2 48 50 49 50

TCD103CW AYDHTRCW54A 54.0 2 69 70 70 70TCH103CW AYHHTREW54A 54.0 2 69 70 70 70

TCR121CW AYRHTRCW18A 18.0 1 26 30 27 3010 TCR121CW AYRHTRCW36A 36.0 2 48 50 49 50

TCD121CW AYDHTRCW54A 54.0 2 69 70 70 70TCH121CW AYHHTREW54A 54.0 2 69 70 70 70

TCD151CW AYDHTRDW18A 18.0 1 27 30 30 35TCH151CW AYHHTRCW18A 18.0 1 27 30 30 35

12½ TCD151CW AYDHTRGW36A 36.0 2 49 50 51 60TCH151CW AYHHTRCW36A 36.0 2 49 50 51 60TCR151CW AYRHTREW54A 54.0 2 70 70 73 80

TCD181CW AYDHTRDW18A 18.0 1 30 40 33 45TCH181CW AYHHTRCW18A 18.0 1 30 40 33 45

15 TCD181CW AYDHTRGW36A 36.0 2 49 50 51 60TCH181CW AYHHTRCW36A 36.0 2 49 50 51 60TCR181CW AYRHTREW54A 54.0 2 70 70 73 80

TCD211CW AYDHTRGW36A 36.0 2 51 60 55 60TCH211CW AYHHTRCW36A 36.0 2 51 60 55 60

17½ TCR211CW AYRHTRGW54A 54.0 2 73 80 77 80TCR211CW AYRHTRHW72A 72.0 2 95 100 98 100

TCD241CW AYDHTRGW36A 36.0 2 51 60 55 60TCH241CW AYHHTRCW36A 36.0 2 51 60 55 60

20 TCR241CW AYRHTRGW54A 54.0 2 73 80 77 80TCR241CW AYRHTRHW72A 72.0 2 95 100 98 100

TCD301CW AYDHTRGW36A 36.0 2 55 60 — —TCH301CW AYHHTRCW36A 36.0 2 55 60 — —

25 TCR301CW AYRHTRGW54A 54.0 2 77 80 — —TCR301CW AYRHTRHW72A 72.0 2 98 100 — —

NOTE:1. HACR type circuit breaker per NEC.2. Values do not include power exhaust accessory.

RIndicates both downflow and horizontal units.

Page 66: Cat

66 RT-PRC002-EN

ElectricalData

RIndicates both downflow and horizontal units.

Table ED-6 — Electrical Characteristics — Evaporator Fan Motor — 60 Cycle

Standard Evaporator Fan Motor Oversized Evaporator Fan Motor

UnitAmps Amps

Tons Model No. No. Volts Phase HP FLA LRA No. Volts Phase HP FLA LRA

TCD036C1 1 208-230 1 .33 2.4 7.2 1 208-230 1 .40 3.8 6.93 TCD036C3, TCD037C3 1 208-230 1 .33 2.4 7.2 1 208-230 1 .40 3.8 6.9

TCD036C4, TCD037C4 1 460 1 .33 1.1/1.6 2.2 1 460 1 .40 1.9 3.1

TCR048C1 1 208-230 1 .50 4.2 9.2 1 208-230 1 .75 6.6 13.5TCR048C3, TCR049C3 1 208-230 1 .50 4.2 9.2 1 208-230 1 .75 6.6 13.5

4TCR048C4, TCR049C4 1 460 1 .50 2.0 4.3 1 460 1 .75 3.1 6.4TCR048CW 1 575 1 .50 1.9 3.4 1 575 1 .75 2.4 5.2

TCR060C1 1 208-230 1 .60 5.3 11.1 1 208-230 1 .75 6.6 13.5TCR060C3, TCR061C3 1 208-230 1 .60 5.3 11.1 1 208-230 1 .75 6.6 13.5

5TCR060C4, TCR061C4 1 460 1 .60 2.5 5.6 1 460 1 .75 3.1 6.4TCR060CW 1 575 1 .60 2.4 4.7 1 575 1 .75 2.5 5.2

TCR075C3, TCR074C3 1 208-230 3 1.00 5.9 32.2 1 208-230 3 2.00 8.8 53.06, 6¼ TCR075C4, TCR074C4 1 460 3 1.00 3.2 16.1 1 460 3 2.00 4.4 26.5

TCR075CW 1 575 3 1.00 2.6 13.2 1 575 3 2.00 3.1 18.4

TCR090C3,D3,TCR086C3,091D3 1 208-230 3 1.00 5.9 32.2 1 208-230 3 2.00 8.8 53.0

7, 7½ TCR090C4,D4,TCR086C4,091D4 1 460 3 1.00 3.2 16.1 1 460 3 2.00 4.4 26.5TCR090CW,DW 1 575 3 1.00 2.6 13.2 1 575 3 2.00 3.1 18.4

TCR102C3, TCR103C3 1 208-230 3 2.00 7.5 47.2 1 208-230 3 3.00 10.6 81.08½ TCR102C4, TCR103C4 1 460 3 2.00 3.4 23.6 1 460 3 3.00 4.8 40.5

TCR102CW, TCR103CW 1 575 3 2.00 3.0 22.8 1 575 3 3.00 3.9 31.0

TCR120C3 1 208-230 3 3.00 9.4 81.0 1 208-230 3 5.00 13.4 109.8TCR120C4 1 460 3 3.00 4.8 40.5 1 460 3 5.00 7.6 54.9

10 TCR120CW 1 575 3 3.00 3.9 31.0 1 575 3 5.00 6.1 41.6TCR121C3 1 208-230 3 2.00 7.5 47.2 1 208-230 3 3.00 10.6 81.0TCR121C4 1 460 3 2.00 3.4 23.6 1 460 3 3.00 4.8 40.5TCR121CW 1 575 3 2.00 3.0 22.8 1 575 3 3.00 3.9 31.0

TCR150C3, TCR151C3 1 208-230 3 3.00 10.6 81.0 1 208-230 3 5.00 16.7 109.812½ TCR150C4, TCR151C4 1 460 3 3.00 4.8 40.5 1 460 3 5.00 7.6 54.9

TCR150CW, TCR151CW 1 575 3 3.00 3.9 31.0 1 575 3 5.00 6.1 41.6

TCR180B3, TCR181C3 1 208-230 3 3.00 10.6 81.0 1 208-230 3 5.00 16.7 109.815 TCR180B4, TCR181C4 1 460 3 3.00 4.8 40.5 1 460 3 5.00 7.6 54.9

TCR180BW, TCR181CW 1 575 3 3.00 3.9 31.0 1 575 3 5.00 6.1 41.6

TCR210C3, TCR211C3 1 208-230 3 5.00 16.7 109.8 1 208-230 3 7.50 17.6 120.417½ TCR210C4, TCR211C4 1 460 3 5.00 7.6 54.9 1 460 3 7.50 8.6 74.0

TCR210CW, TCR211CW 1 575 3 5.00 6.1 41.6 1 575 3 7.50 7.0 60.0

TCR240B3, TCR241C3 1 208-230 3 5.00 16.7 109.8 1 208-230 3 7.50 17.6 120.420 TCR240B4, TCR241C4 1 460 3 5.00 7.6 54.9 1 460 3 7.50 8.6 74.0

TCR240BW, TCR241CW 1 575 3 5.00 6.1 41.6 1 575 3 7.50 7.0 60.0

TCR300B3, TCR301C3 1 208-230 3 7.50 17.6 120.4 — — — — — —25 TCR300B4, TCR301C4 1 460 3 7.50 8.6 74.0 — — — — — —

TCR 300BW, TCR301CW 1 575 3 7.50 7.0 60.0 — — — — — —

Page 67: Cat

67RT-PRC002-EN

ElectricalData

RIndicates both downflow and horizontal units.

StandardEfficiency

Table ED-7 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Standard Efficiency

Compressor Motors Condenser Fan Motors

UnitAmps1 Amps1

Tons Model No. No. Volts Phase HP2 RPM RLA LRA No. Phase HP FLA LRA

TCD036C1 1 208-230 1 3.00 3450 18.0 92 1 1 .25 2.0 5.33 TCD036C3 1 208-230 3 3.00 3450 11.2 101 1 1 .25 2.0 5.3

TCD036C4 1 460 3 3.00 3450 5.5 51 1 1 .25 .9 2.1

TCR048C1 1 208-230 1 4.00 3450 24.0 119 1 1 .33 2.1 4.84 TCR048C3 1 208-230 3 4.00 3450 14.8 101 1 1 .33 2.1 4.8

TCR048C4 1 460 3 4.00 3450 7.1 51 1 1 .33 1.0 2.6TCR048CW 1 575 3 4.00 3450 5.5 41 1 1 .33 .9 2.1

TCR060C1 1 208-230 1 5.00 3450 28.8 142 1 1 .50 5.2 6.55 TCR060C3 1 208-230 3 5.00 3450 18.6 118 1 1 .40 2.7 7.8

TCR060C4 1 460 3 5.00 3450 10.0 71 1 1 .40 1.3 3.2TCR060CW 1 575 3 5.00 3450 6.7 43 1 1 .40 1.1 2.4

TCR075C3 1 208-230 3 6.25 3450 21.8 124 1 1 .50 3.4 10.86¼ TCR075C4 1 460 3 6.25 3450 9.7 64 1 1 .50 2.4 5.4

TCR075CW 1 575 3 6.25 3450 7.8 51 1 1 .50 1.8 4.1

TCR090C3 1 208-230 3 7.50 3450 27.0 164 1 1 .50 3.4 10.8TCR090C4 1 460 3 7.50 3450 12.2 79 1 1 .50 2.4 5.4TCR090CW 1 575 3 7.50 3450 9.8 63 1 1 .50 1.8 4.1

7½TCR090D3 2 208-230 3 4.00/3.50 3450 14.4 101 1 1 .50 3.4 10.8TCR090D4 2 460 3 4.00/3.50 3450 7.1 51 1 1 .50 2.4 5.4TCR090DW 2 575 3 4.00/3.50 3450 5.4 41 1 1 .50 1.8 4.1TCR102C3 2 208-230 3 4.30/4.30 3450 16.0 118 1 1 1.00 5.5 18.3

8½ TCR102C4 2 460 3 4.30/4.30 3450 10.0 71 1 1 1.00 2.9 9.3TCR102CW 2 575 3 4.30/4.30 3450 5.9 43 1 1 1.00 2.0 5.7

TCR120C3 2 208-230 3 5.00/4.30 3450 19.0/16.0 118 1 1 1.00 5.5 18.310 TCR120C4 2 460 3 5.00/4.30 3450 10.0 71 1 1 1.00 2.9 9.3

TCR120CW 2 575 3 5.00/4.30 3450 6.9 43 1 1 1.00 2.0 5.7

TCR150C3 2 208-230 3 6.00 3450 24.3 156 1 1 1.00 5.5 18.3TCR150C4 2 460 3 6.00 3450 10.6 70 1 1 1.00 2.9 9.3

12½ TCR150CW 2 575 3 6.00 3450 8.4 54 1 1 1.00 2.0 5.7

TCR180B3 2 208-230 3 9.30/5.10 3450 38.2/19.5 253/128 2 1 .50 3.2 8.815 TCR180B4 2 460 3 9.30/5.10 3450 16.6/8.5 118/63 2 1 .50 1.6 3.8

TCR180BW 2 575 3 9.30/5.10 3450 13.8/7.1 97/49 2 1 .50 1.3 3.2

TCR210C3 2 208-230 3 10.0/6.80 3450 37.4/26.1 253/164 2 1 1.00 5.5 18.317½ TCR210C4 2 460 3 10.0/6.80 3450 16.2/11.3 118/100 2 1 1.00 2.9 9.3

TCR210CW 2 575 3 10.0/6.80 3450 13.5/9.4 97/72 2 1 1.00 2.0 5.7

TCR240B3 2 208-230 3 9.30 3450 42.1 247 2 1 1.00 5.5 18.320 TCR240B4 2 460 3 9.30 3450 17.4 95 2 1 1.00 2.9 9.3

TCR240BW 2 575 3 9.30 3450 13.9 76 2 1 1.00 2.0 5.7

TCR300B3 2 208-230 3 10.00 3450 42.8 247 2 1 1.00 5.5 18.325 TCR300B4 2 460 3 10.00 3450 17.7 95 2 1 1.00 2.9 9.3

TCR300BW 2 575 3 10.00 3450 14.2 76 2 1 1.00 2.0 5.7

NOTES:1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.2. HP for each compressor.

Page 68: Cat

68 RT-PRC002-EN

ElectricalData

Compressor Motors Condenser Fan Motors

UnitAmps1 Amps1

Tons Model No. No. Volts Phase HP2 RPM RLA LRA No. Phase HP FLA LRA

TCD037C3 1 208-230 3 3.00 3450 12.0 101 1 1 .25 2.0 5.33 TCD037C4 1 460 3 3.00 3450 5.9 51 1 1 .25 .9 2.1

TCR049C3 1 208-230 3 3.50 3450 14.8 101 1 1 .25 2.0 5.34 TCR049C4 1 460 3 3.50 3450 7.1 51 1 1 .25 .9 2.1

TCR061C3 1 208-230 3 4.30 3450 18.6 118 1 1 .25 2.0 5.35

TCR061C4 1 460 3 4.30 3450 10.0 71 1 1 .25 .9 2.1

TCR074C3 1 208-230 3 5.00 3450 21.0 118 1 1 .25 2.0 5.36 TCR074C4 1 460 3 5.00 3450 10.0 71 1 1 .25 .9 2.1

TCR086C3 1 208-230 3 6.25 3450 23.0 124 1 1 .50 3.4 10.87 TCR086C4 1 460 3 6.25 3450 10.0 64 1 1 .50 2.4 5.4

TCR091D3 2 208-230 3 3.00 3450 14.4 101 1 1 .50 3.4 10.87½

TCR091D4 2 460 3 3.00 3450 7.1 51 1 1 .50 2.4 5.4TCR103C3 2 208-230 3 3.80 3450 14.0 91 1 1 1.00 5.5 18.3

8½ TCR103C4 2 460 3 3.80 3450 7.5 46 1 1 1.00 2.9 9.3TCR103CW 2 575 3 3.80 3450 5.9 37 1 1 1.00 2.0 5.7

TCR121C3 2 208-230 3 4.30 3450 15.4 118 2 1 .50 3.2 8.810 TCR121C4 2 460 3 4.30 3450 10.0 71 2 1 .50 1.6 3.8

TCR121CW 2 575 3 4.30 3450 6.9 43 2 1 .50 1.3 3.2

TCR151C3 2 208-230 3 5.70 3450 19.4 156 2 1 .50 3.2 8.812½ TCR151C4 2 460 3 5.70 3450 10.0 70 2 1 .50 1.6 3.8

TCR151CW 2 575 3 5.70 3450 7.8 54 2 1 .50 1.3 3.2TCR181C3 2 208-230 3 9.30/4.50 3450 37.0/16.9 253/124 2 1 .50 3.2 8.8

15 TCR181C4 2 460 3 9.30/4.50 3450 17.4/7.4 118/60 2 1 .50 1.6 3.8TCR181CW 2 575 3 9.30/4.50 3450 13.9/6.1 97/49 2 1 .50 1.3 3.2

TCR211C3 2 208-230 3 9.30/5.70 3450 37.0/20.0 253/156 2 1 1.00 5.5 18.317½ TCR211C4 2 460 3 9.30/5.70 3450 17.4/10.0 118/70 2 1 1.00 2.9 9.3

TCR211CW 2 575 3 9.30/5.70 3450 13.9/8.0 97/54 2 1 1.00 2.0 5.7

TCR241C3 2 208-230 3 9.30 3450 42.1 253 2 1 1.00 5.5 18.320 TCR241C4 2 460 3 9.30 3450 17.4 118 2 1 1.00 2.9 9.3

TCR241CW 2 575 3 9.30 3450 13.9 97 2 1 1.00 2.0 5.7

TCR301C3 2 208-230 3 10.00 3450 42.1 253 2 1 1.00 5.5 18.325 TCR301C4 2 460 3 10.00 3450 17.4 118 2 1 1.00 2.9 9.3

TCR301CW 2 575 3 10.00 3450 13.9 97 2 1 1.00 2.0 5.7

NOTES:1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.2. HP for each compressor.

Table ED-8 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — High Efficiency

RIndicates both downflow and horizontal units.

HighEfficiency

Page 69: Cat

69RT-PRC002-EN

JobsiteConnections

For specific wiring information, see the installation instructions.All wiring except power wires is low voltage.All customer supplied wiring to be copper and must conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the customer.

NOTE:1. Conventional Thermostat Interface - CTI is a field or factory-installed accessory and is required to operate all Micro-processor units with a conventional thermostat. For

accurate wiring requirements, refer to the accessory installation instructions.

DISCONNECTSWITCH

(BY OTHERS)

ROOFTOPUNIT

ZONE SENSORS

Zone Sensors —Typical Number Of Wires

A— Manual Changeover ...................................... 4Manual/Auto Changeover ............................. 5Manual/Auto Changeover with

Status Indication LED’s .......................... 10Programmable Night Setback with

Status Indication LED’s ............................ 7

B— 3 Power Wires + 1 Ground Wire (three phase)2 Power Wires + 1 Ground Wire (single phase)

Page 70: Cat

70 RT-PRC002-EN

TypicalWiring

(3-7½ Ton)

Page 71: Cat

71RT-PRC002-EN

TypicalWiring

(3-7½ Ton)

Typical wiring diagram. For specificwiring, see individual Service Facts.

PRINTED FROM: 2307-0211

Page 72: Cat

72 RT-PRC002-EN

TypicalWiring

(3-7½ Ton)

Page 73: Cat

73RT-PRC002-EN

Typical wiring diagram. For specificwiring, see individual Service Facts.

PRINTED FROM: 2307-0222

TypicalWiring

(3-7½ Ton)

Page 74: Cat

74 RT-PRC002-EN

TypicalWiring

(8½-25 Ton)

Page 75: Cat

75RT-PRC002-EN

Typical wiring diagram. For specificwiring, see individual Service Facts.

PRINTED FROM: 2307-0307

(8½-25 Ton)TypicalWiring

Page 76: Cat

76 RT-PRC002-EN

(8½-25 Ton)TypicalWiring

Page 77: Cat

77RT-PRC002-EN

Typical wiring diagram. For specificwiring, see individual Service Facts.

PRINTED FROM: 2307-5513

(8½-25 Ton)TypicalWiring

Page 78: Cat

78 RT-PRC002-EN

DimensionalData

(3-5 Ton) Standard Efficiency

(3-4 Ton) High Efficiency

See page 94 for condensatedrain size and location

All dimensions are in inches.

Page 79: Cat

79RT-PRC002-EN

DimensionalData

(3-5 Ton) Standard Efficiency

(3-4 Ton) High Efficiency

All dimensions are in inches.

Downflow Duct Connections — Field Fabricated

Horizontal Unit Supply/Return(4 and 5 Ton Models Only)

See page 94 for condensatedrain size and location

Page 80: Cat

80 RT-PRC002-EN

(6¼, 7½ Ton) Std. Efficiency

(5-7½ Ton) High Efficiency

DimensionalData

&

All dimensions are in inches.

See page 94 for condensatedrain size and location

Page 81: Cat

81RT-PRC002-EN

(6¼, 7½ Ton) Std. Efficiency

(5-7½ Ton) High Efficiency

DimensionalData

All dimensions are in inches.

Downflow Duct Connections — Field Fabricated

Horizontal Unit Supply/Return

See page 94 for condensatedrain size and location

Page 82: Cat

82 RT-PRC002-EN

(8½, 10 Ton) Std . EfficiencyDimensionalData

All dimensions are in inches.

See page 94 for condensatedrain size and location

Page 83: Cat

83RT-PRC002-EN

DimensionalData

(8½, 10 Ton) Std. Efficiency

All dimensions are in inches.

Downflow Duct Connections — Field Fabricated

See page 94 for condensatedrain size and location

Horizontal Unit Supply/Return

Page 84: Cat

84 RT-PRC002-EN

(8½ Ton) High Efficiency

(12½ Ton) Std, Efficiency

DimensionalData

All dimensions are in inches.

NOTE:Duct flanges mount 7-7/16" downinside the curb on the 1½" curbflanges. See recommended ductdimensions on the next page.

Page 85: Cat

85RT-PRC002-EN

(8½ Ton) High Efficiency

(12½ Ton) Std. Efficiency

DimensionalData

All dimensions are in inches.

Downflow Duct Connections — Field Fabricated

NOTE:Duct flanges mount 7-7/16" downinside the curb on the 1½" curbflanges.

Horizontal Unit Supply/Return

RETURN

SUPPLY

1 1\2"1 1\2"PERIMETERPERIMETERCURB FLANGECURB FLANGE

51 7/8"51 7/8"

16 3/16"16 3/16"

22 5/16"22 5/16"44 1/2"44 1/2" 1"1"

14 1/16"14 1/16"

7 7/16"7 7/16"

1"1"

Page 86: Cat

86 RT-PRC002-EN

DimensionalData

(10, 12½ Ton) High Efficiency

(15, 17½ Ton) Std. Efficiency

All dimensions are in inches.

NOTE:Duct flanges mount 7-7/16" downinside the curb on the 1½" curbflanges. See recommended ductdimensions on the next page.

Page 87: Cat

87RT-PRC002-EN

DimensionalData

(10, 12½ Ton) High Efficiency

(15, 17½ Ton) Std. Efficiency

RETURN

SUPPLY

1 1\2"PERIMETERCURB FLANGE

59 7/16"

17 7/8"

26 5/16"52 1/2" 1"

14 1/16"

7 7/16"

1"All dimensions are in inches.

Downflow Duct Connections — Field Fabricated

NOTE:Duct flanges mount 7-7/16" downinside the curb on the 1½" curbflanges.

Horizontal Unit Supply/Return

Page 88: Cat

88 RT-PRC002-EN

DimensionalData

(15-25 Ton) High Efficiency

(20, 25 Ton) Std. Efficiency

All dimensions are in inches.

NOTE:Duct flanges mount 7-7/16" downinside the curb on the 1½" curbflanges. See recommended ductdimensions on the next page.

Page 89: Cat

89RT-PRC002-EN

DimensionalData

(15-25 Ton) High Efficiency

(20, 25 Ton) Std. Efficiency

Downflow Duct Connections — Field Fabricated

All dimensions are in inches.

Horizontal Unit Supply/Return

RETURN

RETURN

SUPPLY

SUPPLY

1 1\2"PERIMETERCURB FLANGE

73 7/16"

19 5/16"

26 5/16"66 1/2" 1"

14 1/16"

7 7/16"

1"

NOTE:Duct flanges mount 7-7/16" downinside the curb on the 1½" curbflanges.

Page 90: Cat

90 RT-PRC002-EN

DimensionalData

All dimensions are in inches.

Note:When applying economizer to horizontal units,connecting ductwork must be run full size to allowproper operation of Economizer Damper.

(3-7½ Ton)Accessories

Page 91: Cat

91RT-PRC002-EN

DimensionalData

(8½-25 Ton)Accessories

All dimensions are in inches.

Note:When applying economizer to horizontal units,connecting ductwork must be run full size toallow proper operation of Economizer Damper.

UnitModel # A B1 C2

TCR102-120, 150 141/4 33½ 33½TCR121, 151-180, 210 171/2 53¾ 36TCR181, 211-301 191/2 64¾ 39

NOTES:1. Horizontal dimension only. Downflow economizer is

width of end panel.2. Power exhaust is applied on downflow economizer

only.

Table DD-1

Page 92: Cat

92 RT-PRC002-EN

DimensionalData

Factory InstalledOptions (FIOPS)

All dimensions are in inches.

UnitModel # A B C

TCD036-060 311/4 511/8 25½TCD061-090

331/4 531/8 25½TCD090-091TCD102, 120 32 531/8 287/8

Table DD-2

UnitModel # A B C

TCD103, 150 333/8 393/8 31TCD121, 151, 180, 210 423/8 483/8 31TCD181, 211-301 291/2 56 381/2

Table DD-3

Page 93: Cat

93RT-PRC002-EN

DimensionalData

Factory InstalledOptions (FIOPS)

Hinged Access Door

Hinged Access Door

Fan Failure Switch

Clogged Filter Switch

Black Epoxy CoatedOutdoor Coils

Powered Or UnpoweredConvenience Outlet

Trane Communication Interface

Supply and/or ReturnSmoke Detectors

Through the BaseElectrical

Disconnect Switch or Circuit Breaker

High Pressure Cut Out

Page 94: Cat

94 RT-PRC002-EN

DimensionalData

(3-25 Ton)

Table DD-4 — Standard Efficiency Units

A B C D F G H E J E K

3, 4, 5 133/16 223/16 111/4 27/8 33/8 397/8 321/4 3/4 PVC 19¾ — 20 ½ —6¼, 7½ 153/16 221/2 1215/16 31/4 33/8 427/8 351/4 3/4 PVC 22¼ — — 2 3/16

8½, 10 153/16 221/2 1215/16 43/16 33/8 427/8 351/4 3/4 PVC 23 — 28 3/16 —12½ 227/16 141/2 1711/16 41/4 41/4 5413/16 473/16 1 NPT — 24 5/8 — 1615, 17½ 267/16 221/2 1811/16 41/4 41/4 627/16 5411/16 1 NPT — 25 5/8 — 620, 25 267/16 283/4 1915/16 41/4 41/4 765/16 6811/16 1 NPT — 26 3/4 — 5 3/8

Condensate Drain LocationCondensate Drain LocationCondensate Drain LocationCondensate Drain LocationCondensate Drain Location Condensate Condensate Condensate Condensate Condensate Drain Size Drain Size Drain Size Drain Size Drain SizeDownflow OnlyDownflow OnlyDownflow OnlyDownflow OnlyDownflow OnlyTonsTonsTonsTonsTons DownflowDownflowDownflowDownflowDownflow Horizontal Horizontal Horizontal Horizontal Horizontal

Table DD-5 — High Efficiency Units

A B C D F G H E J E K

3, 4 133/16 223/16 111/4 27/8 33/8 397/8 321/4 3/4 PVC 19½ — 20 3/8 —5,6,7,7½ 153/16 221/2 1215/16 31/4 33/8 427/8 351/4 3/4 PVC 22 — — 2 3/16

8½ 227/16 141/2 1711/16 41/4 41/4 5413/16 473/16 1 NPT — 24 5/8 — 1610, 12½ 267/16 221/2 1811/16 41/4 41/4 627/16 5411/16 1 NPT — 25 5/8 — 615-25 267/16 283/4 1915/16 41/4 41/4 765/16 6811/16 1 NPT — 26 3/4 — 5 3/8

Condensate Drain LocationCondensate Drain LocationCondensate Drain LocationCondensate Drain LocationCondensate Drain Location Condensate Condensate Condensate Condensate Condensate Drain Size Drain Size Drain Size Drain Size Drain SizeDownflow OnlyDownflow OnlyDownflow OnlyDownflow OnlyDownflow OnlyTonsTonsTonsTonsTons DownflowDownflowDownflowDownflowDownflow HorizontalHorizontalHorizontalHorizontalHorizontal

Page 95: Cat

95RT-PRC002-EN

Weights (3-25 Ton)

RIndicates both downflow and horizontal units.

Table W-1 — Accessory Net Weights (Lbs)1, 8

Oversized High6 Low6

Economizer Outside Air DamperPower Roof Motor Static Static

Model No. Net Manual Motorized Exhaust4 Curb4 Adder Drive Drive

TCR036,048,060CTCR037,049

40 32 — — 80 5 — —

TCR075,090C,090DTCR061,074,086C,091D, 40 32 35 65 82 5 2 —TCR102C, 120C

TCD103CTCD150C

40 32 35 75 165 5 2 —

TCD180BTCD121,151C, TCD210C

65 32 60 95 205 5 2 2

TCD240BTCD181,211,241C

80 32 75 95 235 5 2 —

TCD300B.301C 80 32 75 95 235 N/A N/A 2

TCH103, 150C 35 32 35 — — 5 2 —

TCH180B, 210CTCH121,151C

50 32 60 — — 5 2 2

TCH240BTCH181,211,241C

65 32 75 — — 5 2 —

TCH300B,301C 65 32 75 — — N/A N/A 2

Table W-1 Continued

Electric Heaters

Unit All Zone 6-23 KW 27-36 KW 54 KW 72 KWModel No. Sensors 240/480V2 3 240/480V2 3 240/480V2 3 240/480V2 3

TCR036, 048, 060C 1 20/20 — — —TCR037,049

TCR075, 090C, 090D 1 26/26 26/265 — —TCR061,074,086C,091D, 102C, 120C

TCD103, 150C 1 28/21 31/27 38/32 —

TCD180B, 210C 1 28/217 31/27 38/32 —TCD121,151,181C

TCD240B 1 — 33/27 40/32 43/34TCD211,241C

TCD300B,301C 1 — 33/27 40/32 43/34

TCH103, 121C, 150C 1 28/21 31/27 38/32 —

TCH180B, 210C 1 28/217 31/27 38/32 —TCH121,151,181C

TCH240B 1 — 33/27 40/32 43/34TCH211, 241C

TCH300B, 301C 1 — 33/27 40/32 43/34

NOTES:1. Net weight should be added to unit weight when ordering factory installed accessories.2. For 600V heaters net weights are same as 480V heaters.3. To estimate shipping weight add 5 lbs to net weight.4. Downflow only.5. 27 - 36 KW Heaters not available for TCR061C.6. Not available on all models (See Fan Performance tables for specific models).7. 9 - 23 KW Heaters not available for TCR210C.8. TC102-300 factory installed options for economizers, multiply net capacity x .99, EER x .97. For oversized motors, multiply net capacity x .98, EER x .93.

This is provided in compliance with ARI certification program.

Page 96: Cat

96 RT-PRC002-EN

Weights

Table W-3— Maximum Unit And Corner Weights (Lbs) And Center Of Gravity Dimensions (In.)

UnitMaximum Weights (Lbs) Corner Weights (Lbs)1 Center of Gravity (In.)

Tons Model No. Shipping2 Net A B C D Length Width

3 TCD036C/TCD037C 702/731 541/571 184/192 137/139 99/107 120/133 36/36 19/204 TCR048C/TCR049C 731/765 559/592 190/196 138/147 106/114 123/135 36/37 19/205 TCR060C/TCR061C 751/821 579/633 194/284 143/156 109/121 134/152 36/38 20/216, 6¼ TCR075C/TCR074C 819/852 630/663 196/207 162/173 123/130 150/153 39/40 21/21

TCR090C/TCR086CSingle Compressor

878/861 689/673 229/213 177/173 130/130 153/156 39/39 20/21

7, 7½TCR090D/TCR091DDual Compressor

940/953 751/765 264/265 182/188 130/135 175/176 36/37 20/20

8½ TCR102C/TCR103C 1064/1393 857/1094 298/353 217/291 144/203 197/246 37/43 20/2610 TCR120C/TCR121C 1086/1753 879/1385 302/468 225/357 150/242 202/317 38/46 20/2912½ TCR150C/TCR151C 1460/1776 1161/1408 389/474 307/349 205/248 260/337 42/45 26/3015 TCR180B/TCR181C 1739/2309 1371/1850 482/635 350/464 227/317 312/434 45/52 28/3517½ TCR210C/TCR211C 1820/2380 1452/1921 500/643 378/495 247/341 327/442 46/53 28/3520 TCR240B/TCR241C 2309/2470 1850/2011 654/692 487/523 303/343 406/453 52/53 33/3425 TCR300B/ TCR301C 2365/2475 1906/2016 661/695 507/524 320/343 454/454 53/53 33/34

NOTES:1. Corner weights are given for information only. 8½-25 ton models must be supported continuously by a curb or equivalent frame support.2. Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.

RIndicates both downflow and horizontal units.

Page 97: Cat

97RT-PRC002-EN

Weights

Table W-3 — Factory Installed Options (FIOPS) Net Weights (Lbs)1,2,3

ModelAccessory Number Weight

FIYHEMT001,002 15High Efficiency Motors FIYHEMT003-005 49

FIYHEMT006-008 36

Hinged DoorsFIYHNGE001,002 10FIYHNGE003-009 27

Powered Convenience Outlet FIYCOPO101-206 38

Through the Base ElectricalFIYTBUE101-111 16FIYTBUE201-216 23

Unit Mounted Circuit BreakerFIYUCB4015-4150 5FIYUCB3175-3250 10

Unit Mounted DisconnectFIYUDC4150,6100 5FIYUDC3250 10

NOTES:1. Weights for FIOP accessories not listed are >5 lbs.2. Net weight should be added to unit weight when ordering factory installed accessories.3. See Table W-1 for standard factory installed economizer, electric heater and oversized motor.

Page 98: Cat

98 RT-PRC002-EN

MechanicalSpecifications

GeneralThe units shall be dedicated downflowor horizontal airflow. The operatingrange shall be between 115 F and 0 F incooling as standard from the factory forall units. Cooling performance shall berated in accordance with ARI testingprocedures. All units shall be factoryassembled, internally wired, fullycharged with R-22 and 100% run testedto check cooling operation, fan andblower rotation and control sequencebefore leaving the factory. Wiringinternal to the unit shall be colored andnumbered for simplified identification.Units shall be UL listed and labeled,classified in accordance to UL 1995/CAN/CSA No. 236-M90 for CentralCooling Air Conditioners. Canadianunits shall be CSA Certified.

CasingUnit casing shall be constructed of zinccoated, heavy gauge, galvanized steel.All components shall be mounted in aweather resistant steel cabinet with apainted exterior. Cabinet constructionshall allow for all maintenance on oneside of the unit. Service panels shallhave lifting handles and shall beremoved and reinstalled by removingnot more than three screws whileproviding a water and air tight seal. Allexposed vertical panels and top coversin the indoor air section shall beinsulated with fire-resistant,permanent, ordorless glass fibermaterial. The base of the downflowunit is insulated with a foil-faced,closed-cell material. The downflowunits base pan shall have nopenetrations within the perimeter ofthe curb other than the raised 11/8" highsupply/return openings to provide anadded water integrity precautionshould the condensate drain back up.Each unit has a sloped condensatedrain pan. The base of the unit shallhave provisions for forklift and cranelifting.

FiltersOne inch, throwaway filters shall bestandard on all 3-7½ ton units. Filter rackcan be converted to two inch capability.Two inch filters shall be factory suppliedon all units above 7½ tons.

CompressorsAll 3-10 ton standard, 3-7½ and 10 tonhigh efficiency units shall have direct-drive hermetic, reciprocating typecompressors. The reciprocating typecompressors have a centrifugal oil pumpproviding positive lubrication to movingparts. Motor shall be suction gas-cooledand shall have a voltage utilization rangeof plus or minus 10 percent of unitnameplate voltage. Crankcase heater,internal temperature and current-sensitive motor overloads shall beincluded for maximum protection. Shallhave internal spring isolation and soundmuffling to minimize vibrationtransmission and noise. Low pressureswitches shall be standard.

8½ ton high efficiency and 12½ to 25 tonstandard and high efficiency units shallhave direct-drive, hermetic, scroll typecompressors with centrifugal type oilpumps. Motor shall be suction gas-cooled and shall have a voltageutilization range of plus or minus 10percent of unit nameplate voltage.Internal overloads shall be provided withthe scroll compressors. The scrolls usedon the 12½, 15 and 17½ ton highefficiency and 15, 17½, and 25 tonstandard efficiency units have crankcaseheaters.

Refrigerant CircuitsEach refrigerant circuit shall haveindependent fixed orifice expansiondevices, service pressure ports andrefrigerant line filter driers factory-installed as standard. An area shall beprovided for replacement suction linedriers.

Evaporator and Condenser CoilsInternally finned 3/8" copper tubesmechanically bonded to configuredaluminum plate fin shall be standard.Coils shall be leak tested at the factory toensure the pressure integrity. Theevaporator coil and condenser coil shallbe leak tested to 200 psig and pressuretested to 450 psig. On all dualcompressor models, the evaporator coilshall be intermingled configuration.

Outdoor FansThe outdoor fan shall be direct-drive,statically and dynamically balanced,draw through in the vertical dischargeposition. The fan motor(s) shall bepermanently lubricated and have built-inthermal overload protection.

Indoor FanUnits 5 and below shall have direct-drive, FC, centrifugal fans. Units above 5tons shall have belt driven, FC,centrifugal fans with adjustable motorsheaves. 8½-25 ton units shall have anadjustable idler-arm assembly for quickadjustment of fan belts and motorsheaves. All motors shall be thermallyprotected. Oversized motors will beavailable for high static operations. Allindoor fan motors meet the U.S. EnergyPolicy Act of 1992 (EPACT).

Page 99: Cat

99RT-PRC002-EN

ControlsUnit shall be completely factory wiredwith necessary controls and contactorpressure lugs or terminal block forpower wiring. Units shall provide anexternal location for mounting fuseddisconnect device. Micro-processorcontrols shall be provided for all 24 voltcontrol functions. The resident controlalgorithms shall make all heating,cooling and/or ventilating decisions inresponse to electronic signals fromsensors measuring indoor and outdoortemperatures. The control algorithmmaintains accurate temperature control,minimizes drift from set point andprovides better building comfort. Acentralized Micro-processor shall provideanti-short cycle timing and time delaybetween compressors to provide ahigher level of machine protection.

Accessories

Electric Heaters — Electric heatmodules shall be available forinstallation within basic unit. Electricheater elements shall be constructed ofheavy-duty nickel chromium elementsinternally delta connected for 240 volt,wye connected for 480 and 600 volt.Staging shall be achieved through theunitary control processor (UCP). Eachheater package shall have automaticallyreset high limit control operatingthrough heating element contactors. Allheaters shall be individually fused fromfactory, where required, and meet allNEC and CEC requirements whenproperly installed. Power assembliesshall provide single-point connection.Electric heat modules shall be UL listedor CSA certified.

Roof Curb - Downflow — The roofcurb shall be designed to mate with thedownflow unit and provide support anda water tight installation when installedproperly. The roof curb design shallallow field-fabricated rectangular supply/return ductwork to be connected directlyto the curb. Curb design shall complywith NRCA requirements. Curb shallship knocked down for field assemblyand include wood nailer strips.

MechanicalSpecifications

Economizer - Downflow — Thisaccessory shall be either field or factoryinstalled. The assembly includes: fullymodulating 0-100 percent motor anddampers, barometric relief, minimumposition setting, preset linkage, wiringharness with plug, and fixed dry bulbcontrol. The barometric relief dampershall be standard with the downfloweconomizer and shall provide a pressureoperated damper that shall be gravityclosing and prohibit entrance of outsideair during the equipment “off” cycle.Solid state enthalpy and differentialenthalpy control shall be factorysupplied, field installed option.

Economizer - Horizontal — Thisaccessory shall be field installed only.The horizontal economizer shall beavailable and contain the same featuresas the downflow economizer with theexception of barometric relief.

Remote Potentiometer — Theminimum position setting of theeconomizer shall be adjusted with thisaccessory.

Powered Exhaust — Shall be availableon units above 5 tons. The accessoryshall assist the barometric relief damperin the economizer in relieving buildingpressurization.

Manual Outside Air Damper — Fieldinstalled rain hood and screen shallprovide up to 25 percent outside air.

Motorized Outside Air Dampers —Manually set outdoor air dampers shallprovide up to 50 percent outside air.Once set, outdoor air dampers shallopen to set position when indoor fanstarts. The damper shall close to the fullclosed position when indoor fan shutsdown. This option shall be available forthe 6¼-25 ton models.

High Static Drive — Field installedhigh static drive option shall allow thestandard motor to operate withimproved external static capabilities.(See Fan Performance tables).

Low Static Drive — Field installed lowstatic drive option shall allow thestandard motor to operate at lower staticperformance. (See Fan Performancetables).

Oversized Motors — Factory or fieldinstalled oversized motors shall beavailable for high static applications.

Control Options

Trane Communication Interface(TCI) — Shall be provided to interfacewith the Trane Integrated ComfortTM

System.

Zone Sensors — Shall be provided tointerface with the Micro equippedVoyagers and shall be available in eithermanual, automatic programmable withnight setback, with system malfunctionlights or remote sensor options.

Conventional Thermostat Interface(CTI) — This field installed circuit boardshall provide interface with electro-mechanical thermostats or automationsystems.

Differential Pressure Switches —This field installed option allowsindividual fan failure and dirty filterindication. The fan failure switch willdisable all unit functions and “flash” theService LED on the zone sensor. The dirtyfilter switch will light the Service LED onthe zone sensor and will allow continuedunit operation.

Input/Output Expansion Accessory— This kit allows Integrated Comfort™Systems to read Supply Air Temperature,Return Air Temperature, Return AirHumidity, and direct indication of fanfailure without the use of an economizeror motorized outside air accessory.

Electronic Time Clock — This fieldinstalled accessory allows up to 4 unitsnight set-back and unoccupied functionswhen using a standard (Dual Setpoint)zone sensor module.

Page 100: Cat

100 RT-PRC002-EN

Additional Factory InstalledOptions (FIOPS)

Electric Heaters — Factory installedand wired electric heaters are availablefor all 3 phase horizontal and downflow3 - 25 ton models. If ordering theThrough the Base Electrical option withan Electric Heater, the heater must befactory installed

Through the Base Electrical WithDisconnect Switch — Factory installed3-pole, molded case disconnect switchwith provisions for through the baseelectrical connections are available. Thedisconnect switch will be installed in theunit in a water tight enclosure withaccess through a swinging door. Factorywiring will be provided from the switchto the unit high voltage terminal block.The switch will be UL/CSA agencyrecognized. Note: The disconnect switchwill be sized per NEC and UL guidelinesbut will not be used in place of unitovercurrent protection. This option isavailable on all 3-25 ton downflowmodels.

Through the Base Electrical withCircuit Breaker — This option is afactory installed thermal magnetic,molded case, HACR Circuit Breaker withprovisions for through the base electricalconnections. The circuit breaker will beinstalled in a water tight enclosure in theunit with access through a swingingdoor. Factory wiring will be providedfrom the switch to the unit high voltageterminal block. The circuit breaker willprovide overcurrent protection, be sizedper NEC and UL guidelines, and beagency recognized by UL/CSA. Thisoption is available on all 3-25 tondownflow models.

Powered or UnpoweredConvenience Outlet — This option is aGFCI, 120v/15amp, 2 plug, convenienceoutlet, either powered or unpowered.When the convenience outlet ispowered, a service receptacle disconnectwill be available. The convenience outletis powered from the line side of thedisconnect or circuit breaker, andtherefore will not be affected by theposition of the disconnect or circuitbreaker. This option can only be orderedwhen the Through the Base Electricalwith either the Disconnect Switch, orCircuit Breaker, option is ordered. Thisoption is available on all 3-25 tondownflow models.

Clogged Filter/Fan Failure Switch —A dedicated differential pressure switchis available to achieve active fan failureindication and/or clogged filterindication. These indications will beregistered with either a zone sensor withstatus indication lights or an IntegratedComfort™ System.

Reference or Comparative Enthalpy— Reference or Comparative Enthalpyoption shall be available when a factoryinstalled Downflow Economizer isordered. This option is available on all 3-25 ton downflow models.

Input/Output Expansion Module —This factory installed option will allow anIntegrated Comfort System to readSupply Air Temperature, Return AirTemperature, Return Air Humidity, anddirect indication of fan failure without theuse of an economizer or motorizedoutside air accessory.

High Pressure Cutout — This option isoffered for units that do not have HighPressure cutout as standard. The unitsWITH High Pressure Cutout as standardare: TC*090C, TC*180-301B,C

Hinged Access Doors — Sheet metalhinges are available factory installed onthe Filter/Evaporator Access Door andthe Compressor/Control Access Door.This option is available on all 3-25 tondownflow models.

Trane Communications Interface(TCI) — An option for a factory installedTrane Communication Interface isavailable to allow twisted wire paircommunication with an IntegratedComfort ™ System. Order this optionwhen a combination of TCI andoversized motor is desired.

Discharge Air Sensing Kit — Providestrue discharge air sensing in heatingmodels. This sensor is a status indicatorreadable through Tracer® or Tracker®.Functional only with the TCI andEconomizer or TCI and Generic Input/Output Module options.

High Efficiency Motors — Availablewith efficiency ratings from 86.5 up to91.0. Not available for all models.

Supply and/or Return Air SmokeDetector — With this option installed, ifsmoke is detected, all unit operation willbe shut down. Reset will be manual atthe unit. Return Air Smoke Detectorsrequire minimum allowable airflowwhen used with certain models. See theInstallation, Operation, and Maintenance(IOM) manual for the models affectedand the minimum allowable airflowrequired. This option is available on all 3-25 ton downflow models.

Conventional Thermostat Interface— This option is a circuit board mountedin the unit control box to the right of theUnitary Control Processor board. Itallows the unit to be operated by anelecto-mechanical thermostat or throughdry contact closure type controls.

Black Epoxy Coated Condenser Coil— Provides corrosion protection tocondenser coils for seacoast application.The protection is a factory appliedthermoset vinyl coating, bonded tonormal aluminum fin stock. The uniformthickness of the bonded vinyl layerexhibits excellent corrosion protection insalt spray tests performed in accordancewith ASTM B117.

MechanicalSpecifications

Page 101: Cat

RT-PRC002-EN

Page 102: Cat

The Trane CompanyUnitary Products Group2701 Wilma Rudolph Blvd.Clarksville, TN 37040www.trane.com

An American Standard CompanySince The Trane Company has a policy of continuous product and product data improvement, it reserves theright to change design and specifications without notice.

Literature Order Number

File Number

Supersedes

Stocking Location

RT-PRC002-EN

PL-UN-RT-TCD/TCH 3-25 TONS-PRC002-EN-05-00

TC-D-5 (22-1352-10, Tab 3)