Cat-CMP Cable Gland

Embed Size (px)

Citation preview

  • 8/17/2019 Cat-CMP Cable Gland

    1/64

  • 8/17/2019 Cat-CMP Cable Gland

    2/64

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    cmp

    ATEX 95

    • Cable Gland & Accessories• Meeting The Atex Hazardous

    Area Directive

    TRITON CDS• Cable Gland & Accessories• Cable Gland Selection Programme• Unique Design Features

    ontheweb

  • 8/17/2019 Cat-CMP Cable Gland

    3/64

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    As a leading manufacturer of metallic cable glands and

    electrical mining products for global applications CMP

    Products is committed to ensuring it remains the

    number one choice in its markets.

    CMP will retain status as the number one supplier by

    continually striving to achieve standards of excellence

    in our company through the continuous improvement

    of our processes and functions. It is only by achieving

    this that CMP will continue to offer unrivaled customer

    service throughout the globe.

    In order to reach these goals CMP Products has set

    itself the following targets for the medium term;

    To broaden, re-design and enhance its product

    range to bring to the market an upgraded product

    offering which will position CMP as the first

    choice of Clients, and to continue this develop-ment process over the next five years.

    To incur substantial investment in manufacturing

    techniques, IT systems and training in order to

    ensure CMP Products can offer unparalleled levels

    of quality and customer service.

    To develop strategic alliances with distributors and

    end-users across the globe in order to provide

    our products with access to a world class global

    distribution network.

    CMP ONLINEAs a leading manufacturer of metallic cable

    glands and electrical mining products for

    global applications CMP Products is

    committed to ensuring it remains the

    number one choice in its markets.

     w w w. c m p - p r o d u c t s . c o m

    MISSION STATEMENT

    INVESTOR IN PEOPLE

    VISION STATEMENT

    To elevate the customer to the Centre of our activities and to employ

    our endeavour to bring about a positive experience for everyone

  • 8/17/2019 Cat-CMP Cable Gland

    4/64

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    Introduction

    Gland Selection Guideline

    CMP Displacement Seal Concept

    Guide To Hazardous Area Cable Selection

    Introduction To ATEX Directives

    Ingress Protection

    IndustrialIntroduction to CMP Industrial Cable Glands

    A2 Unarmoured Cable Glands

    SS2K (GP) Sureseal 2000 Unarmoured

    A2RC Unarmoured - Conduit Connection

    V-TEC (A2P) Industrial

    A4 Armoured - S.T.A (Tape Armour) Outer Seal

    BW Armoured Cable Glands

    BWL Armoured Cable Glands

    CW Armoured - S.W.A Outer Seal

    CX/ Z Armoured - Braided or S.T.A (Tape Armour) Outer Seal

    E1W Armoured - S.W.A Inner/ Outer Seal

    E2W Armoured - S.W.A -L.C. (Lead Sheathed) Inner/Outer Seal

    E1X/Z Armoured - Braided or S.T.A (Tape Armour) Inner/Outer Seal

    CWAL Armoured - A.W.A Outer Seal

    Hazardous Area

    Introduction to CMP Hazardous Area Cable Glands

    A2F Unarmoured Outer Seal

    SS2K Sureseal 2000 Unarmoured

    A2FRC Unarmoured - Conduit Connection Outer Seal

    V-TEC (A2Pe)- Hazardous Area

    A4e Armoured - S.T.A (Tape Armour)

    C2K Armoured - Multiple Armour Outer Seal

    CWe Armoured - S.W.A Outer Seal

    Cxe Armoured - Braided or S.T.A (Tape Armour) Outer Seal

    TRITON (T3CDS) - Multiple Armour Inner/Outer Seal

    E1FW Armoured - S.W.A Inner/ Outer SealE2FW Armoured - S.W.A - L.C. (Lead Sheathed) Inner/ Outer Seal

    E1FX/Z Armoured - Braided or S.T.A (Tape Armour) Inner/Outer Seal

    E2FX/Z Armoured - Braided or S.T.A (Tape Armour) Lead Sheathed Inner/Outer Seal

    PX2K PROTEX 2000 - Armoured - Braided, S.W.A or S.T.A Outer Seal/Comp Barrier 

    Protex WR Armoured - S.W.A Outer Seal/Comp Barrier 

    Protex X/ZR Armoured - Braided Outer Seal/Comp Barrier 

    Protex SS2K Protex Sureseal 2000 Unarmoured Outer Seal/Comp Barrier 

    North America Specification Cable Connectors

    Introduction to CMP North American Glands

    PXSS2K Unarmoured Cable

    C2KX Armoured & Jacketed - Wet Locations Outer Seal

    PXB2KX Armoured CablePX2KX Armoured & Jacketed - Class 1 Div 1 Compound Barrier/ Outer Seal

    MCRA

    MCXA

    Cable Gland Options & Accessories

    Cable Gland Options

    Accessories And Tools

    Standard Selection Table For Adaptors & Reducers

    Stopper Plugs & Insulated Adaptors

    Cable Selector Charts

    XLPE / EPR / SWA / PVC Cables BS5467

    PVC / SWA / PVC Cables BS6346Unarmoured XLPE / PVC Cable To BS6883:9X (DRAFT)

    3

    4

    5

    6 - 7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    2122

    23

    24

    25

    26

    27

    28

    29

    30

    31

    32

    3334

    35

    36

    37

    38

    39

    40

    41

    42

    43

    4445

    46

    47

    48 - 49

    50 - 51

    52 - 53

    54 - 55

    56

    5758 - 59

  • 8/17/2019 Cat-CMP Cable Gland

    5/64

    3

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    CableNPT or NPS M P.G. PF / BSP(JIS) Imperial

    Gland ISO Metric(E.T.)

    Size Preferred Option Preferred Option Preferred Option

    16 M16 1/2” 3/4” 11 9, 13.5 - - -

    20/16 M20 1/2” 3/4” 11 9, 13.5 1/2” - 3/4”

    20S M20 1/2” 3/4” 13.5 11, 16 1/2” - 3/4”

    20 M20 1/2” 3/4” 16 11, 13.5, 21 1/2” 3/4” 3/4”25 M25 3/4” 1” 21 - 3/4” 1” 1”

    32 M32 1” 1-1/4” 29 - 1” 1-1/4” 1-1/4”

    40 M40 1-1/4” 1-1/2” 36 29 1-1/4” 1-1.2” 1-1/2”

    50S M50 1-1/2” 2” 36 42 1-1/2” - 2”

    50 M50 2” 2-1/2” 42 48 2” - 2”

    63S M63 2” 2-1/2” 48 - 2” - 2-1/2”

    63 M63 2-1/2” 3” - - 2-1/2” - 2-1/2”

    75S M75 2-1/2” 3” - - 2-1/2” - 3”

    75 M75 3” 3-1/2” - - 3” 3-1/2” 3”

    90 M90 3” 3-1/2” - - 3” 3-1/2” 3-1/2”

    ENTRY THREAD OPTIONS

    GLAND SELECTION GUIDELINES

    The following is an extract from BS6121:Part 1, with edited additions to assist in gland selection :-

    • Select the type of cable and identify a corresponding cable gland type from this catalogue.

    • Check the type, size & voltage rating of the cable. Note for cables of 3.3kV & above the CMP-CIEL Gland is recommended.

    • Check ACTUAL size of cable over the inner sheath / lead sheath against this catalogue.

    • Check ACTUAL size of overall cable diameter against this catalogue.

    • Check the size and type of armour or braiding, if any, against this catalogue.

    • Check any special environment conditions including enclosure material in relation to corrosion.

    • Check whether installation is in Hazardous Areas, & consider an environmental seal on the cable sheath for indoor/outdoor use.

    • Check whether an entry thread seal is required for IP66 (or IP67/IP68) conditions.

    • Check whether accessories, (ie. shrouds, slip on earth tags, locknuts etc) are required.

    KEY to Hazardous Area Cable Glands = Increased Safety Type ‘e’ Dual Certified Type ‘d’ & ‘e’ Flameproof Type ‘d’■   ◆   ▲

    NOTE :The table above details Standard (Preferred) and Optional Thread sizes which are available on all CMP ‘Double Seal’ Cable Gland types andSingle Seal Cable Glands for unarmoured cables (e.g.A2,A2F,A2RC,A2FRC). Please consult CMP for any requirements not covered by this table.

       G   L   A   N   D    S

       E   L   E   C   T   I   O   N    G

       U   I   D   E   L   I   N   E   S

    BW

    BWL

    CW

    Braided Unarmoured

    CABLETYPECable Gland

    Type SWA STASWA Lead

    Sheathed

    APPLICATIONSEALING CONFIGURATION

    No Seal Inner SealDouble Outer 

    SealOuter Seal Outdoor  Indoor  Hazardous

    ●   ●●

    ●●

    C2KX

    CWAL

    E1W

    E2W

    CX

    E1X/Z

    A4

    A2

    SS2K GP

    CWe

    CXe

    C2K

    A4e

    A2F

    SS2K

    E1FW

    E2FW

    E1FX/Z

    WR

    XR

    PXB2KX

    PX2K

    PX2KXPXSS2K

    ●   ● ● ●

    ●   ●   ●

    ●   ●

    ●   ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●

    ● ●●   ●

    ● ●●   ●

    ●   ●

    ●   ●

    ●   ●

    ●   ●

    ●   ●

    ●   ●

    ● ●

    ● ●●   ●   ◆

    ●   ●●   ●

    ● ●   ◆

    Areas

    A2RC

    A2FRC

    A2Pe

    T3CDS

    A2P

  • 8/17/2019 Cat-CMP Cable Gland

    6/64

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

      C  M  P  D  I  S  P  L  A  C  M  E  N  T  S  E  A

      L  C  O  N  C  E  P  T

    As it will be seen from the detailed technical datacontained within this catalogue the method of cablesealing in the CMP range of cable glands is fundamentally

    different from that of it’s competitors. CMP has pioneeredthe use of displacement type seals which afford a largedegree of control in the tightening of the seals onto thecable sheath as opposed to conventional compressionseals which usually require the cable gland to be fullytightened on installation.The information below sets outto demonstrate the difference between the different sealtypes adopted and the reasons why CMP utilise thedisplacement seal very effectively in its Cable Gland range.

    It has long been recognised that the difference in reactionpressure between the inner seal of a cable gland and thepolymeric material of the cable sheath can result in‘cold flow’ under load cycling. Soft bedded cables areparticularly prone to cold flow’. The latest EuropeanStandard EN60079 requires the user to install CableGlands which do not cause an adverse ‘cold flow’ reactionto the inner cable bedding,which would otherwise breachthe integrity of the form of the hazardous area protectionof the electrical apparatus. This is a particular problemwhen using cable glands fitted with conventionalcompression seals.To overcome this problem, the CMP cable gland design

    incorporates a unique seal arrangement whereby the sealis displaced as the gland is tightened, virtually eliminatingany damage to the cable sheath. Additionally the CMP

    design enables the user to control the level of displacement of the seal, and this level of control is afeature not found in other traditional cable glands.Duringdevelopment, tests were carried out on soft beddedcables, comparing these ‘displacement’ seals with thetraditional, ‘compression’ type seals. Significantly lessdistortion or damage to the cable sheath of soft beddedcables occurred when displacement seals were used.Obviously in hazardous area installations, the ongoingeffectiveness of the inner seal of the cable gland representsa critical link in the chain of safety. In recognition of this,the CMP cable glands enable the effectiveness of thecritical inner seal to be easily checked on an ongoing basisin a way that no other cable gland types allow.

    The CMP displacement seal concept has been proven overmany years in service and has been endorsed by majorusers globally as the preferred solution for explosionproof and industrial installations

    (See also TRITON CDS - compensating DisplacementSeal System on Pg 32)

    DISPLACEMENT SEALS COMPRESSION SEALS

    Relaxed Compressed With Controlled Compression

    Inner Outer 

    RELATIVE EFFECTS ON CABLE SHEATH

    Note : Cable performance can be affected by Compression Type Seals employed on either the Inner Sheath or the Outer Sheath

     With Displacement Seal With Compression Seal

    CRUCIAL CABLE CARE - THE DISPLACEMENT SEAL CONCEPTYET ANOTHER ORIGINAL FROM CMP

    4

  • 8/17/2019 Cat-CMP Cable Gland

    7/64

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

       G

       U   I   D   E   T   O    H

       A   Z   A   R   D   O   U   S   A   R   E   A   G

       L   A   N   D

       S   E   L   E   C   T   I   O   N 

    INTERPRETATION OF HAZARDOUS AREA CODE OF PRACTICE FOR

    SELECTION OF COMPOUND BARRIER TYPE CABLE GLANDS

    Direct entry into

    Flameproof

    Type ‘d’ enclosure

    Indirect entry into

    Flameproof

    Type ‘d’ enclosure

    For cables entering FlameproofType ‘d’ enclosures indirectly,

    a Compound BarrierCable Gland need not be used.

    Ex ‘d’ TerminalCompartment

    Conventional CableGland with Sealing

    Rings (e.g. P2K)Line

    Barriers

    For cables entering directly intoFlameproof Type ‘d’ enclosures, a

    Compound Barrier Cable Glandis sometimes required.

    ✝ If in doubt consult with the

    cable supplier or cable manufacturer.

    Compound BarrierGland (e.g. PX2K) 5

    Selection process for cables directly

    entering Ex ‘d’ enclosures.

  • 8/17/2019 Cat-CMP Cable Gland

    8/64

    Directive 99/92/EC requires employers to protect workers from the risk of explosive atmospheres. An explosive atmosphere is definedas a mixture with air, under atmospheric conditions, of dangerous substances in the form of gases, vapours,mist or dust in which afterignition has occurred, combustion spreads to the entire unburned mixture. ATEX 137 implemented in the UK as DSEAR:

    Dangerous Substances and Explosive Atmosphere Regulations 2002Statutory Instrument 2002 No.2776 (Mandatory from 9th December 2002)

    SurfaceIndustries

    Risk Assessment

    Risk Assessment

    Risk assessment does not include:a) Likelyhood that an explosive

    atmosphere will occur,b) Ignition source,c) Scale of explosion, andd) any places connected via

    opening to the explosive atmosphere

    Risk assessment does not include:a) Likelyhood that an explosive

    atmosphere will occur,b) Ignition source,c) Scale of explosion, and

    d) any places connected viaopening to the explosive atmosphere

    Medical areasGas appliances

    (domestic)Gas Fittings

    Manufacture,handling,storage of explosives.

    Borehole SiteMeans of transport bylandor seas (does not

    include transportintended for use inhazardous)

    MODEstablishment

    No

    Yes

    Yes

    No

    ATEX 99/92/EC does not apply

    Yes

    No

    Mines &Quarries

    Reduce therisk fromdangerous

    substances

    Classification of workplaces intoHazardous/non-Hazardous Area

    (mandatory1st July 2003)

    Procedures onaccidents,incidents

    emergencies

    InformationInstruction and

    Training

    Procedures onaccidents,incidents

    emergencies

    InformationInstruction and

    Training

    Procedures on accidents, incidentsemergencies. 8(1)(d)-(In explosive

    conditions audible and visual alarmsrequired) not applicable

    InformationInstruction and

    Training

    DSEAR doesNOT apply

    DSEAR doesNOT apply

    Reduce therisk fromdangerous

    substances

    Offshore Oil &Gas platforms

    Ships

    Secretary of Statesissues certification

    of exemption

    ExemptionsGeneral Safety Measures• Workplace and Work ProcessessThe following do not apply:a) UPS backupb) manual override shutdown

    buttonsc) energy to be dissipated after

    operation of emergency shutdown

    • Systems of Work a) need for written instructions

    for carrying out the work;b) permits to work 

    HM Navy

    Summary of the main requirement for DSEAR is given below:

    • Carry out a risk assessment of any work activities involvingdangerous substances;

    • Provide technical and organisational measures to eliminate or

    reduce to, as far as is reasonably practical, the identified risks;• Provide equipment and procedures to deal with accidents and

    emergencies;• Provide information and training to employees;

    • Classify places where explosive atmospheres may occur into zones,and mark the zones where necessary.

    Other than for certain maritime activities, DSEAR applies whenever the

    following conditions have been satisfied:

    1) There is work being carried out by an employer or self-employed person;

    2) A dangerous substance is present or liable to be present at the workplace;

    3) The dangerous substance presents a risk to the safety of persons

    (as opposed to a risk to health).

    The requirements of DSEAR concerning zoning and co-ordination of safety

    measures in shared workplaces (Regulation 7 & 11 of DSEAR) do not apply to

    all workplaces where other legislation is in place.

    Typical Cable Gland Marking for ATEXCable Glands carrying ATEX approval will typically be marked thus:

    Cable Gland MarkingExample of additional Cable Gland marking according to Form of Protection

    CertificateHolder

    ATEXGeneration

    ApparatusGroup

    Form of 

    Protection 1

    Form of 

    Protection 2

    ApprovedGas Group

    Ex StatusG=GasD=Dust

    Postcode SignifiesAddress of 

    ManufacturerSpecial Condition

    Temperature RatingQA Notified

    Body Number

    ‘X’ - Denotes thatSpecial ConditionsFor Safe Use Exit

    Year of 1stApproval

    SpecificApproval No.

    EquipmentCategory

    Country of Manufacture

    CE Mark Signifies Full Compliancewith EN Standards

    SIRA 00 ATEX 1148 X II 2 GD

    EEx d IIC EEx e II Type 4X Oil Res II

    NE6 1BS UK -60˚C + -130˚C 0518

    Additional

    Approval Mark 

    Oil Resistance

    Rating

    ApprovedGas Group

    AdditionalNEMA Rating

    99/92/EC

    Doc Ref : TPC 164 issue 04 2005

      I  N  T  R  O  D  U  C  T  I  O  N   T  O   A  T  E

      X

      D  I  R  E  C  T  I  V  E  S

    6

  • 8/17/2019 Cat-CMP Cable Gland

    9/64

       A   T   E   X    D

       I   R   E   C   T

       I   V   E

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    Directive 94/9/EC (ATEX 95) Equipment and Protective Systems for use in potentially explosive atmospheres.Covers electrical andnon-electrical products intended for use in hazardous areas (gas, vapours or dust atmospheres).ATEX 95 implemented in the UK as :

    The Equipment and Protective Systems Intended for USE in PotentiallyExplosive Atmosphere Regulations 1996 Statutory instrument 1996 No. 192

    Zoning Definitions

    94/9/EC

    Zones

    EN60079-10 EN50281-3

    Definitions

    Zone IP RatingATEX Category

    BSEN 50281-1-1/2

    Gas

    0 20

    A place in which an explosive atmosphere is likely to occur innormal operation occasionally.

    Type of Protection

    Intrinsic Safety

    Increased Safety

    Flameproof 

    Pressurisation

    Powder Filling

    Encapsulation

    Oil Immersion

    Type n

    EEx is & ib

    EEx e

    EEx d

    EEx p

    EEx q

    EEx m

    EEx o

    EEx n

    EN 50020

    EN 50019

    EN 50018

    EN 50016

    EN 50017

    EN 50028

    EN 50015

    EN 50021

    Dusts

    20

    21

    22

    IP6X

    IP6X

    IP5X

    Requires 1D equipment

    Requires 1D or 2D equipment

    Requires 3D, 2D, 1D equipment

    *Must be IP6X if dust is electrically conductive

    A place in which an explosive atmosphere is not likely to occurin normal operation, but if it does only occurs for short periods.

    1 21

    2 22

    Dust

    Zoning Definitions

    ATEX

    Cat.

    Typical Zone

    Suitability

    1G1D

    2G2D

    2G2D

    Equip. suitable for zones 0Equip. suitbale for zones 20

    Equip. suitable for zones 1Equip. suitbale for zones 21

    Equip. suitable for zones 2Equip. suitbale for zones 22

    A place in which an explosive atmosphere is continuily present.

    Type of Protection

    CENELECCode

    ENStandard

    Non-electrical equipment (concepts)

    EN 13463-1

    EN 13463-2

    EN 13463-3

    EN 13463-4

    EN 13463-5

    EN 13463-6

    EN 13463-7

    EN 13463-8

    Basic methods & requirements

    Flow restricting enclosure

    Flame-proof enclosure

    Inherent safety

    Constructional Safety

    Control of ignition sources

    Pressurisation

    Liquid immersion

    fr 

    d

    g

    c

    b

    p

    Conformity Assessment ‘Quality Modules’

    Design Phase

    EC-Type Examination

    Internal Control of Production

    Unit Vertification

    Production Phase

    Production Quality Assurance

    Product Quality Assurance

    Product Verification

    Conformity to Type

    Internal Control of Production

    Unit Verification

    *Notes:1 “Global Approach” OJEC No. L220, 19932 ATEX Directive 94/9/EC3 Suffix (E) refers to electrical equipment and internal combustion engines

    Suffix (N) refers to non-electrical equipment4 Technical Files to be deposited with a notified body

    KEY= mandatory unless Unit Verification is used= optional as an alternative to other modules

    Y = one of two production phase modules for the equipment category tobe chosen by the manufacturer

    Module

    *1

    B

    A

    G IX

    D IV

    E VII

    F V

    C VI

    A VIII

    G IX

    VIII

    III

    Y

    Y

    Y

    Y Y Y

    Y

    Y

    Y Y

    O OOOOOO O

    O OOOOOO O

    O

    AnnexM1 M2

    (E)M2(N)

    1 2(E)

    2(N)

    3Prodective

    System

    Equipment Category *3

    *2

    Enclosed break device CNon-incendive component CHermetically sealed device CSealed device CEncapsulated device CEnergy limited apparatus and circuits LRestricted breathing enclosure RSimplified pressurisation PNon sparking A

    T1

    T2

    T3

    T4

    T5

    T6

    450

    300

    200

    135

    100

    85

    Type n equipmentcontaining:

    Additionalcode letter  TClass

    Maxsurface

    temp in˚C

    *4 *4

    7

  • 8/17/2019 Cat-CMP Cable Gland

    10/64

      I  N  G  R  E  S  S

      P  R  O  T  E

      C  T  I  O  N

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    DEGREE OF INGRESS PROTECTION (IP CODE) IN ACCORDANCE WITH EN 60529 : 1991

    CMP cable glands comply with the requirements of EN60529:1991 (IEC 529) in respect of I.P. ratings. Some cable glandtypes have been tested to IP66, whilst other types have been tested to IP66, IP67 & IP68, to a depth of 10 metres. *

    Protected against access

    to hazardous parts with

    the back of a hand

    0 0 Non-protected

    1 1Protected against

    drops of water

    falling vertically

    2 2Protected againstdrops of water

    falling at up to 15º

    from the vertical

    3 3

    Protected against

    spraying water at

    up to 60º from

    the vertical

    4 4Protected againstsplashing water

    from all directions

    5 5

    Protected against

     jet of water from

    all directions

    Protected against

     jet of water of

    similar force to

    heavy seas

    Protected against

    the effects of 

    immersion

    Protected against

    prolonged effects

    of immersion

    under pressure toa specified depth

    6 6

    50mm

    12mm

    2.5mm

    1mm

    Protected against solid

    foreign objects of

    50mm diameter

    and greater

    PROTECTION AGAINST SOLID FOREIGN OBJECTSAND ACCESS TO HAZARDOUS PARTS

    PROTECTION AGAINSTLIQUIDS

    Protected against solidforeign objects of

    12.5mm diameter

    and greater

    Protected against solid

    foreign objects of

    2.5mm diameter

    and greater

    Protected against solidforeign objects of

    1.0mm diameter

    and greater

    Dust-protected

    Non-protected

       F   i  r  s   t   D

       i  g   i   t

        S   e   c   o   n    d    D   i   g   i   t

    Non-protected

    Dust-tight

    Protected against accessto hazardous parts with

    a finger

    Protected against access

    to hazardous parts with

    a tool

    Protected against accessto hazardous parts with

    a wire

    Protected against access

    to hazardous parts with

    a wire

    Protected against accessto hazardous parts with

    a wire

    1m

    m

    7

    8

         1     5   c   m

         (   m     i   n     )

    * Please refer to appropriate catalogue pages for specific ratingsaccording to their design and construction.

    In addition to the Ingress Protection tests carried out as standard on theCMP range of Cable Glands, selected products have additionally beentested to meet the requirements of NEMA 4X in accordance with NorthAmerican standards. Please refer to catalogue pages for specific productcompliance.

    8

  • 8/17/2019 Cat-CMP Cable Gland

    11/64

     APPL ICAT ION

    The CMP range of Industrial Cable Glands embraces products used in a

     wide and diverse variety of market sectors, in conjunction with virtually 

    every kind of industrial cable. With a wealth of experience in terminating

    all types of armoured and unarmoured cables CMP have discovered that 

     when it comes to such critical installations, quality really does count.

    PRODUCTS

    Cable Gland options for all types of cable

    SPECIFICATIONS & APPROVALS

    Largely based around the BS6121 & BS7394 standards CMP deliver

    product produced strictly under ISO9001 controls.CMP Cable glands also conform to BSEN50262.

    R A N G E

    CMP PRODUCTS

    © BP Amoco p.l.c. 1997

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

  • 8/17/2019 Cat-CMP Cable Gland

    12/64

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    10

      U  N  A  R  M  O  U  R  E  D

      C  A  B  L  E

    A

    B

    C

    D

     A2 GLAND

    Minimum Across Ordering PVC

    Gland SizeStandard Entry Threads ‘B’

    ThreadCable Dia ‘A’

    Corners Reference Shroud

    Metric NPT PG Length ‘C’ Min Max Dia ‘D’ Max (Metric) Ref.

    16 16 1/2” PG11 10 3.1 8.6 24.4 16A2 PVC02

    20/16 20 1/2” PG11 15 3.1 8.6 24.4 20/16A2 PVC02

    20S 20 1/2” PG13.5 10 6.1 11.6 26.5 20SA2 PVC04

    20 20 1/2” PG16 10 6.5 13.9 30.0 20A2 PVC05

    25 25 3/4” PG21 10 11.1 19.9 39.9 25A2 PVC09

    32 32 1” PG29 10 17.0 26.2 45.5 32A2 PVC10

    40 40 1-1/4” PG36 15 22.0 32.1 55.4 40A2 PVC13

    50S 50 1-1/2” PG36 15 29.5 38.1 61.0 50SA2 PVC14

    50 50 2” PG42 15 35.6 44.0 66.5 50A2 PVC17

    63S 63 2” PG48 15 40.1 49.9 77.6 63SA2 PVC20

    63 63 2-1/2” - 15 47.2 55.9 83.2 63A2 PVC22

    75S 75 2-1/2” - 15 52.8 61.9 88.7 75SA2 PVC24

    75 75 3” - 15 59.1 67.9 94.2 75A2 PVC2690 90 3” - 15 66.6 79.3 120.7 90A2 PVC31

    All Dimensions in Millimetres

    A2 Industrial Cable Gland

    Brass indoor and outdoor cable gland for all types of unarmoured cable

    providing a seal on the outer sheath.

    TECHNICAL DATA

    TYPE A2

    DESIGN SPECIFICATION BSEN50262

    INGRESS PROTECTION IP66, I P67 & IP68 (10M DEPTH)

    GLAND MATERIAL BRASS

    SEAL MATERIAL CMP SOLO LSF

    CABLE TYPE UNARMOURED

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA OUTER SHEATH

    * SOLO Option with LSF Seals & LSF Shrouds also AvailableIntegral Entry Thread Seal Option also available, For this Option prefixgland type with ‘R’, e.g. 25RA2Also available in Brass with Nickel Plated Finish

    ADDITIONAL APPROVALS

    MARINE APPROVALS LLOYDS,ABS

    GOST CERTIFICATE OF CONFORMITY 5318856

    OPTIONAL ACCESSORIES SHROUD, LOCKNUT, SERRATED WASHER

    ENTRY THREAD SEAL, ADAPTOR/REDUCER

  • 8/17/2019 Cat-CMP Cable Gland

    13/64

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    TYPE SS2K GP (SS2KPB GP FOR LEAD

    SHEATHED CABLES).

    DESIGN SPECIFICATION BSEN50262

    INGRESS PROTECTION IP66, IP67 & IP68 (10M DEPTH )

    GLAND MATERIAL BRASS

    SEAL MATERIAL THERMOPLASTIC ELASTOMER

    CABLE TYPE UNARMOURED

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA(S) OUTER SHEATH (DOUBLE SEAL)

    OPTIONAL ACCESSORIES LOCKNUT, E ARTH TAG, SERRATED WASHER

    ENTRY THREAD SEAL, ADAPTOR/REDUCER

    * SOLO Option with LSF Seals also AvailableIntegral Entry Thread Seal Option Available(for this option pre-fix gland type with ‘R’, e.g. 25RSS2KGP)

    Standard Entry Minimum Cable Dia ‘A’ / ‘B’ Across Ordering

    Gland Size Threads ‘C’ Thread Millimetres Corners Reference

    Metric NPT PG Length ‘D’ Min Max Dia ‘E’ Max (Metric)

    16 16 1/2” PG11 10 3.1 8.6 24.4 16SS2KGP

    20/16 20 1/2” PG11 15 3.1 8.6 24.4 20/16SS2KGP

    20S 20 1/2” PG13.5 10 6.1 11.6 26.5 20SSS2KGP

    20 20 1/2” PG16 10 6.5 13.9 30.0 20SS2KGP

    25 25 3/4” PG21 10 11.1 19.9 39.9 25SS2KGP

    32 32 1” PG29 10 17.0 26.2 45.5 32SS2KGP

    40 40 1-1/4” PG36 15 22.0 32.1 55.4 40SS2KGP

    50S 50 1-1/2” PG36 15 29.5 38.1 61.0 50SSS2KGP

    50 50 2” PG42 15 35.6 44.0 66.5 50SS2KGP

    63S 63 2” PG48 15 40.1 49.9 77.6 63SSS2KGP

    63 63 2-1/2” - 15 47.2 55.9 83.2 63SS2KGP

    75S 75 2-1/2” - 15 52.8 61.9 88.7 75SSS2KGP

    75 75 3” - 15 59.1 67.9 94.2 75SS2KGP90 90 3” - 15 66.6 79.3 120.7 90SS2KGP

    All Dimensions in Millimetres

    A

    B

    C

    D

    E

    SS2K (GP) GLANDSURESEAL 2000 GP Industrial Cable Gland

    Indoor and Outdoor Brass Cable Gland for all types of Unarmored Cables,

    providing an environmental seal on the cable inner and outer sheaths, or a

    double seal to the cable outer sheath. Suitable for applications where superior

    cable pull out resistance and stability is required.Type SS2KPB GP available for

    unarmoured cables with lead sheath.

    TECHNICAL DATA

       U   N   A   R   M   O   U   R   E   D

       C   A   B   L   E

    11

  • 8/17/2019 Cat-CMP Cable Gland

    14/64

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    TECHNICAL DATA

    TYPE A2RC

    DESIGN SPECIFICATION BSEN50262

    INGRESS PROTECTION IP66, IP67 & IP68 (10M DEPTH)

    GLAND MATERIAL BRASS

    SEAL MATERIAL THERMOPLASTIC ELASTOMER

    CABLE TYPE UNARMOURED

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA (S) OUTER SHEATH

    OPTIONAL ACCESSORIES LOCKNUT, E ARTH TAG, S ERRATED

    WASHER ENTRY THREAD SEAL,

    ADAPTOR/REDUCER

    * SOLO Option with LSF Seals also Available

    A2RC Industrial Cable Gland for Conduit Connection

    Standard Male Entry Minimum ✝ Standard AcrossOrdering

    Gland Size Connection Threads ‘B’ Thread Female NPTCable Dia ‘A’

    CornersReference

    Metric NPT PG Length ‘C’ Threads Min Max Dia ‘D’ Max

    20/16 20 1/2” PG11 15 1/2” 3.1 8.6 30.0 20/16A2RC20S 20 1/2” PG13.5 10 1/2” 6.1 11.6 30.0 20SA2RC

    20 20 1/2” PG16 10 1/2” 6.5 13.9 30.0 20A2RC

    25 25 3/4” PG21 10 3/4” 11.1 19.9 39.9 25A2RC

    32 32 1” PG29 10 1” 17.0 26.2 45.5 32A2RC

    40 40 1-1/4” PG36 15 1-1/4” 22.0 32.1 55.4 40A2RC

    50S 50 1-1/2” PG36 15 1-1/2” 29.5 38.1 61.0 50SA2RC

    50 50 2” PG42 15 2” 35.6 44.0 72.1 50A2RC

    63S 63 2” PG48 15 2” 40.1 49.9 77.6 63SA2RC

    63 63 2-1/2” - 15 2-1/2” 47.2 55.9 88.7 63A2RC

    75S 75 2-1/2” - 15 2-1/2” 52.8 61.9 88.7 75SA2RC

    75 75 3” - 15 3” 59.1 67.9 105.3 75A2RC

    90 90 3” - 15 3” 66.6 79.3 120.7 90A2RC

    All Dimensions in Millimetres

    ✝ Female connection threads in NPT, other thread forms manufactured to order. When ordering please confirm Male & Female Threads required.

    Brass indoor and outdoor conduit connection cable gland for all types of 

    unarmoured cables housed in rigid or flexible conduit systems.The gland

    is equipped with a rotating male or female connection for ease of conduit

    installation.

    12

      U  N  A  R  M  O  U  R  E  D  C  A  B  L  E  S

      I  N  C  O  N  D  U  I  T

    A

    B

    C

    D

     A2RC GLAND

    Female Connection

    Threads Illustrated

  • 8/17/2019 Cat-CMP Cable Gland

    15/64

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

       U   N   A   R   M   O   U   R   E   D

       C   A   B   L   E

    13

    V-Tec (A2P) Industrial

    *Sealing range based upon strain relief & twist protection to VDE 0619 - Available colours: Black, Light Grey (RAL 7001) & Silver Grey (RAL 7035).For colour options please add the folowing suffix to the ordering codes above: B= Black. G= Light Grey. S= Silver GreyOther colours and other non-metallic products in the V-TEC range are also available, please consult CMP Products for further information.

    TYPE DESIGNATION V-TEC, L & M (A2P)

    CABLE GLAND MATERIAL POLYAMIDESEAL MATERIAL CMP SOLO LSF

    FLAME RETARDANCY SPECIFICATION VDE 0471/IEC 695 PART 2-1

    WITHSTAND TEMPERATURE TESTED +750˚C

    CERTIFIED CONTINUOUS OPERATING -20˚C TO +70˚C

    TEMPERATURE RANGE

    INGRESS PROTECTION IP68(AT 5 BAR) TO VDE 0619 / IEC529 ETS

    CABLE TYPE UNARMOURED

    SEALING AREA OUTER SHEATH

    SEALING TECHNIQUE CONTROLLED SEAL WITH STRAIN RELIEF

    OPTIONAL ACCESSORIES LOCKNUT

    TECHNICAL DATA

    CMP V-TEC - & L Cable Glands (A2P) - General Purpose Industrial Type

    A2P1 / A2LP1 Pg 7 8.0 15.0 2.5 6.5 3.0 6.5 18.0 23.0 15.0 16.5 0.41 50

    A2P2 / A2LP2 Pg 9 8.0 15.0 2.5 8.0 3.5 8.0 21.0 27.0 19.0 21.0 0.67 50

    A2P3 / A2LP3 Pg 11 8.0 15.0 3.5 10.0 4.5 10.0 22.0 29.0 22.0 25.0 0.93 50

    A2P4 / A2LP4 Pg 13.5 9.0 15.0 5.0 12.0 6.0 12.0 23.0 30.0 24.0 27.0 1.09 50

    A2P5 / A2LP5 Pg 16 10.0 15.0 7.0 14.0 7.0 14.0 25.0 33.0 27.0 30.0 1.49 25

    A2P6 / A2LP6 Pg 21 11.0 15.0 9.0 18.0 12.0 18.0 28.0 38.0 33.0 37.5 2.33 25

    A2P7 / A2LP7 Pg 29 11.0 15.0 14.0 25.0 17.0 25.0 32.0 43.0 42.0 47.5 3.86 20

    A2P8 / A2LP8 Pg 36 13.0 18.0 18.0 32.0 20.0 32.0 39.0 54.0 53.0 60.0 7.75 10

    A2P9 / A2LP9 Pg 42 13.0 18.0 24.0 38.0 26.0 38.0 42.0 57.0 60.0 68.5 10.07 5

    A2P10 / A2LP10 Pg 48 14.0 18.0 30.0 44.0 30.0 44.0 42.0 58.0 65.0 74.0 10.73 5

    Size Ref.Thread

    Size ‘A’

    Cable Acceptance Range ‘C’

    Min MaxSTD L

    Across

    FlatsAcross

    CornersWeight

    (KG/100)

    Pack QTY.

    Thread

    Length ‘B’

    Min Max

    Standard Reduced*Overall Length ‘D’

    Min Max

    CMP V-TEC M Cable Glands (A2P) - General Purpose Industrial Type

    A2MP1 M12 8.0 2.5 6.5 3.0 6.5 18.0 23.0 15.0 16.5 0.36 50

    A2MP2 M16 8.0 2.5 8.0 3.5 8.0 21.0 27.0 19.0 21.0 0.63 50

    A2MP3 M20 9.0 5.0 12.0 6.0 12.0 23.0 30.0 24.0 27.0 1.00 50

    A2MP4 M25 11.0 9.0 18.0 12.0 18.0 28.0 38.0 33.0 37.5 2.35 25

    A2MP5 M32 11.0 14.0 25.0 17.0 25.0 32.0 43.0 42.0 47.5 3.90 20

    A2MP6 M40 13.0 18.0 32.0 20.0 32.0 39.0 54.0 53.0 60.0 7.50 10

    A2MP7 M50 13.0 24.0 38.0 26.0 38.0 42.0 57.0 60.0 68.5 9.20 5

    A2MP8 M63 14.0 30.0 44.0 30.0 44.0 42.0 58.0 65.0 74.0 9.66 5

    Size Ref.Thread

    Size ‘A’

    Cable Acceptance Range ‘C’

    Min Max

    Across

    FlatsAcross

    Corners

    Weight

    (KG/100)

    Pack QTY.

    Thread

    Length ‘B’Min Max

    Standard Reduced*Overall Length ‘D’

    Min Max

    Plastic gland for use with unarmoured cables

    V-Tec Ordering References

  • 8/17/2019 Cat-CMP Cable Gland

    16/64

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    14

      A  R  M  O  U  R  E  D  C  A  B  L  E  S  T  A

    A

    B

    C

    D

    E

     A4 GLAND

    Brass indoor and outdoor cable gland for all types of Steel Tape Armour

    Cable providing a seal on the cable outer sheath and a continuity seal on

    the Tape Armour.

    TECHNICAL DATA

    TYPE A4

    DESIGN SPECIFICATION BSEN50262

    INGRESS PROTECTION IP66

    GLAND MATERIAL BRASS

    SEAL MATERIAL CMP SOLO LSF

    CABLE TYPE STEEL TAPE ARMOUR

    ARMOUR TERMINATION METALLIC CONTINUITY SEAL

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA OUTER SHEATH

    OPTIONAL ACCESSORIES SHROUD, LOCKNUT, EARTH TAG,

    SERRATED WASHER, ENTRY THREAD SEAL,

    ADAPTOR/REDUCER

    A4 Industrial Cable Gland

    Minimum Across Ordering PVC

    Gland SizeStandard Entry Threads ‘C’

    ThreadCable Dia ‘A’ Cable Dia ‘B’

    Corners Reference Shroud

    Metric NPT PG Length ‘D’ Min Max Min Max Dia ‘E’ Max (Metric) Ref.

    20S 20 1/2” PG13.5 10 6.5 11.6 6.1 11.6 26.5 20SA4 PVC0420 20 1/2” PG16 10 10.0 13.9 6.5 13.9 30.0 20A4 PVC05

    25 25 3/4” PG21 10 11.6 19.9 11.1 19.9 39.9 25A4 PVC09

    32 32 1” PG29 10 19.0 26.2 17.0 26.2 45.5 32A4 PVC10

    40 40 1-1/4” PG36 15 25.0 32.1 22.0 32.1 55.4 40A4 PVC13

    50S 50 1-1/2” PG36 15 27.5 38.1 29.5 38.1 61.0 50SA4 PVC15

    50 50 2” PG42 15 33.1 44.0 35.6 44.0 66.5 50A4 PVC18

    63S 63 2” PG48 15 40.1 49.9 40.1 49.9 77.6 63SA4 PVC21

    63 63 2-1/2” - 15 47.2 55.9 47.2 55.9 83.2 63A4 PVC23

    75S 75 2-1/2” - 15 43.5 61.9 52.8 61.9 88.7 75SA4 PVC24

    75 75 2-1/2” - 15 49.8 67.9 59.1 67.9 94.2 75A4 PVC26

    90 90 3” - 15 64.0 79.3 66.6 79.3 120.7 90A4 PVC31

    All Dimensions in Millimetres

  • 8/17/2019 Cat-CMP Cable Gland

    17/64

       A   R   M   O   U   R   E   D   C   A   B

       L   E   S   W   A

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    15

    BW GLAND / PACK 

    A

    B

    C

    D

    E

    BW Industrial Cable Gland

    BW Industrial Gland Kits

    Brass indoor gland for use with all types of SWA cable, providing mechanicalcable retention and electrical continuity via armour wire termination.

    TECHNICAL DATA

    TYPE BW

    DESIGN SPECIFICATION BS6121 : PART 1 : 1989

    INGRESS PROTECTION IP2X

    GLAND MATERIAL BRASS

    CABLE TYPE STEEL WIRE ARMOUR

    ARMOUR CLAMPING TWO PART ARMOUR LOCK

    OPTIONAL ACCESSORIES SHROUD, LOCKNUT, EARTH TAG,

    SERRATED WASHER,ADAPTOR/REDUCER

    ADDITIONAL APPROVALS

    MARINE APPROVALS LLOYDS,ABS

    * SOLO Option with LSF Shrouds also Available

    Also available in Brass with Nickel Plated Finish

    Gland kit for use with all types of SWA cable, including 2 Brass Glands, 2 SteelLocknuts, 2 Brass Earth Tags and 2 PVC Shrouds for sizes up to and including32mm. For sizes 40mm and above each kit includes 1 off each component

    ✝ For Gland Packs change the ordering code reference above accordingly. eg. 20SBWKIT

    Gland SizeMetric Minimum Cable Cable Armour Across Ordering PVC

    Entry Thread Dia ‘A’ Dia ‘B’ Wire Corners Reference Shroud

    Thread ‘C’ Length ‘D’ Max Max Dia Dia ‘E’ Max (Gland Only) Ref.

    20S 20 10 11.6 16.1 0.9/1.25 24.0 20SBW PVC02

    20 20 10 13.9 21.1 0.9/1.25 30.0 20BW PVC05

    25 25 10 19.9 27.4 1.25/1.6 36.0 25BW PVC07

    32 32 10 26.2 34.4 1.6/2.0 44.5 32BW PVC10

    40 40 15 32.1 42.4 1.6/2.0 56.3 40BW PVC13

    50S 50 15 38.1 50.1 2.0/2.5 63.4 50SBW PVC16

    50 50 15 44.0 55.7 2.0/2.5 72.1 50BW PVC19

    63S 63 15 50.0 62.4 2.5 83.0 63SBW PVC22

    63 63 15 55.9 68.2 2.5 88.7 63BW PVC24

    75S 75 15 61.9 76.8 2.5 99.8 75SBW PVC27

    75 75 15 67.9 82.9 2.5/3.15 105.3 75BW PVC29

    Dimensions in Millimetres

  • 8/17/2019 Cat-CMP Cable Gland

    18/64

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

      A  R  M  O  U  R  E  D  C  A  B

      L  E  S  W  A

    A

    B

    C

    D

    E

    BWL GLAND

    16

    Brass indoor gland for use with all types of SWA cable providing mechanical

    cable retention and electrical continuity via armour wire termination.

    BWL Heavy Duty Industrial Cable Gland

    TECHNICAL DATA

    TYPE BWL

    DESIGN SPECIFICATION BS6121 : PART 1 : 1989

    INGRESS PROTECTION IP2X

    MATERIAL BRASS

    CABLE TYPE STEEL WIRE ARMOUR

    ARMOUR CLAMPING TWO PART ARMOUR LOCK

    OPTIONAL ACCESSORIES LOCKNUT, EARTH TAG, SHROUD,

    ENTRY THREAD SEAL, SERRATED WASHER

    * SOLO Option with LSF Shrouds also Available

    Also available in Brass with Nickel Plated Finish

    ADDITIONAL APPROVALS

    MARINE APPROVALS LLOYDS,ABS

    Gland SizeMetric Minimum Cable Cable Armour Across

    OrderingPVC

    Entry Thread Dia ‘A’ Dia ‘B’ Wire CornersReference

    Shroud

    Thread ‘C’ Length ‘D’ Max Max Dia Dia ‘E’ Max Ref.

    20/16 20 15 8.6 13.4 0.9 24.4 20/16BWL PVC02

    20S 20 10 11.6 15.9 0.9/1.25 26.6 20SBWL PVC04

    20 20 10 13.9 20.9 0.9/1.25 33.3 20BWL PVC06

    25 25 10 19.9 27.4 1.25/1.6 39.9 25BWL PVC09

    32 32 10 26.2 33.9 1.6/2.0 51.0 32BWL PVC11

    40 40 15 32.1 40.4 1.6/2.0 56.3 40BWL PVC13

    50S 50 15 38.1 46.7 2.0/2.5 66.5 50SBWL PVC17

    50 50 15 44.0 53.1 2.0/2.5 77.6 50BWL PVC20

    63S 63 15 50.0 62.4 2.5 83.0 63SBWL PVC22

    63 63 15 55.9 68.2 2.5 88.7 63BWL PVC25

    75S 75 15 61.9 72.1 2.5 99.8 75SBWL PVC28

    75 75 15 67.9 78.5 2.5/3.15 111.1 75BWL PVC30

    90 90 15 79.3 90.4 3.15 128.6 90BWL PVC32

    Dimensions in Millimetres

  • 8/17/2019 Cat-CMP Cable Gland

    19/64

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

       A   R   M   O   U   R   E   D   C   A   B

       L   E   S   W   A

    D

    A

    B

    C

    E

    CW GLAND

    17

    CW Industrial Cable Gland

    CW Industrial Gland Kits

    Brass indoor and outdoor gland for all types of SWA cable, providingenvironmental seal on the cable outer sheath.The gland also providesmechanical cable retention and electrical continuity via armour wiretermination.

    TECHNICAL DATA

    TYPE CW

    DESIGN SPECIFICATION BSEN50262

    INGRESS PROTECTION IP66

    GLAND MATERIAL BRASS

    SEAL MATERIAL CMP SOLO LSF

    CABLE TYPE STEEL WIRE ARMOUR

    ARMOUR CLAMPING TWO PART ARMOUR LOCK

    (THREE PART OPTION AVAILABLE)

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA OUTER SHEATH

    OPTIONAL ACCESSORIES SHROUD, LOCKNUT, EARTH TAG,

    ENTRY THREAD SEAL, SERRATED WASHER

    ADAPTOR/REDUCER

    ADDITIONAL APPROVALS

    MARINE APPROVALS ABS

    * SOLO Option with LSF Shrouds also Available

    Also available in Brass with Nickel Plated Finish

    Gland kit for use with all types of SWA cable, including 2 Brass Glands, 2 SteelLocknuts, 2 Brass Earth Tags and 2 PVC Shrouds for sizes up to and including32mm. For sizes 40mm and above each kit includes 1 off each component

    Gland SizeMetric Minimum Cable Cable Armour Across Ordering PVC

    Entry Thread Dia ‘A’ Dia ‘B’ Wire Corners Reference Shroud

    Thread ‘C’ Length ‘D’ Max Min Max Dia Dia ‘E’ Max (Gland Only) Ref.

    20/16 20 15 8.6 6.0 13.4 0.9 24.4 20/16CW PVC02

    20S 20 10 11.6 9.5 15.9 0.9/1.25 26.6 20SCW PVC04

    20 20 10 13.9 12.5 20.9 0.9/1.25 33.3 20CW PVC06

    25 25 10 19.9 17.0 26.2 1.25/1.6 40.5 25CW PVC09

    32 32 10 26.2 22.9 33.9 1.6/2.0 51.0 32CW PVC11

    40 40 15 32.1 26.0 40.4 1.6/2.0 61.0 40CW PVC15

    50S 50 15 38.1 35.0 46.7 2.0/2.5 66.5 50SCW PVC18

    50 50 15 44.0 38.0 53.1 2.0/2.5 77.7 50CW PVC21

    63S 63 15 50.0 45.6 59.4 2.5 83.2 63SCW PVC23

    63 63 15 55.9 54.6 65.9 2.5 88.7 63CW PVC25

    75S 75 15 61.9 57.0 72.1 2.5 101.6 75SCW PVC28

    75 75 15 67.9 60.4 78.5 2.5/3.15 111.1 75CW PVC30

    90 90 15 79.3 69.2 90.4 3.15 128.6 90CW PVC32

    All Dimensions in Millimetres

    ✝ For Gland Kits change the ordering code reference above accordingly. eg. 20SCWKIT

  • 8/17/2019 Cat-CMP Cable Gland

    20/64

    18

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

      B  R  A  I  D  E  D  O  R  S  T  A  C  A  B  L  E

    CX/Z GLAND CX / Z Industrial Cable Gland

    * SOLO Option with LSF Shrouds also Available

    Also available in Brass with Nickel Plated Finish

    ADDITIONAL APPROVALS

    MARINE APPROVALS LLOYDS,ABS

    GOST CERTIFICATE OF CONFORMITY 5318856

    Brass indoor and outdoor cable gland for all types of braided or steel tape

    armour (S.T.A.) cables providing environmental seal on the cable outer sheath.

    The gland also provides mechanical cable retention and electrical continuity via

    wire braid or steel tape armour termination.

    TECHNICAL DATA

    TYPE CX/Z

    DESIGN SPECIFICATION BSEN50262

    INGRESS PROTECTION IP66

    GLAND MATERIAL BRASS

    SEAL MATERIAL CMP SOLO LSF

    CABLE TYPE WIRE BRAID OR STEEL TAPE ARMOUR

    ARMOUR CLAMPING THREE PART ARMOUR LOCK

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA OUTER SHEATH

    OPTIONAL ACCESSORIES SHROUD, LOCKNUT, EARTH TAG,

    ENTRY THREAD SEAL, SERRATED WASHER,

    ADAPTOR/REDUCER

    ✝ Note : Gland size 20/16 suitable for Wire Braid Armour only.

    Gland SizeMetric Minimum Cable Cable Braid/STA Across

    OrderingPVC

    Entry Thread Dia ‘A’ Dia ‘B’ Thickness CornersReference

    Shroud

    Thread ‘C’ Length ‘D’ Max Min Max Max Dia ‘E’ Max Ref.

    20/16 * 20 15 8.6 6.0 13.4 0.85 24.4 20/16CX/Z PVC02

    20S 20 10 11.6 9.5 15.9 0.85 26.6 20SCX/Z PVC04

    20 20 10 13.9 12.5 20.9 0.9 33.3 20CX/Z PVC06

    25 25 10 19.9 17.0 26.2 1.25 40.5 25CX/Z PVC09

    32 32 10 26.2 22.9 33.9 1.4 51.0 32CX/Z PVC11

    40 40 15 32.1 26.0 40.4 1.4 61.0 40CX/Z PVC15

    50S 50 15 38.1 35.0 46.7 1.4 66.5 50SCX/Z PVC18

    50 50 15 44.0 38.0 53.1 1.4 77.7 50CX/Z PVC21

    63S 63 15 50.0 45.6 59.4 1.5 83.2 63SCX/Z PVC23

    63 63 15 55.9 54.6 65.9 1.5 88.7 63CX/Z PVC25

    75S 75 15 61.9 57.0 72.1 1.5 101.6 75SCX/Z PVC28

    75 75 15 67.9 60.4 78.5 1.5 111.1 75CX/Z PVC30

    90 90 15 79.3 69.2 90.4 1.6 128.6 90CX/Z PVC32

    All Dimensions in Millimetres

    A

    B

    C

    D

    E

  • 8/17/2019 Cat-CMP Cable Gland

    21/64

    E1W GLAND

       A   R   M   O   U   R   E   D   C   A   B

       L   E   S   W   A

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    19

    Brass indoor and outdoor cable gland for all types of SWA cable, providing

    environmental seal on both the cable inner and outer sheaths.The gland also

    provides mechanical cable retention and electrical continuity via armour wire

    termination.

    TECHNICAL DATA

    TYPE E1W

    DESIGN SPECIFICATION BSEN50262

    INGRESS PROTECTION IP66

    GLAND MATERIAL BRASS

    SEAL MATERIAL CMP SOLO LSF

    CABLE TYPE STEEL WIRE ARMOUR

    ARMOUR CLAMPING TWO PART ARMOUR LOCK

    (THREE PART OPTION AVAILABLE)

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA (S) INNER & OUTER SHEATH

    OPTIONAL ACCESSORIES SHROUD, LOCKNUT, EARTH TAG

    ENTRY THREAD SEAL, SERRATED WASHER

    ADAPTOR/REDUCER

    * Integral Entry Thread Seal Option Available

    (for this option pre-fix gland type with ‘R’, e.g. 25RE1W)Also available in Brass with Nickel Plated finish.

    Minimum Armour Across Ordering PVCGland Standard Entry Threads ‘C’

    ThreadCable Dia ‘A’ Cable Dia ‘B’

     Wire Corners Reference ShroudSize

    Metric NPT PG Length ‘D’ Min Max Min Max Dia Dia ‘E’ Max (Metric) Ref.

    20/16 20 1/2” PG11 15 3.1 8.6 6.0 13.4 0.9 24.4 20/16E1W PVC0220S 20 1/2” PG13.5 10 6.1 11.6 9.5 15.9 0.9/1.25 26.6 20SE1W PVC04

    20 20 1/2” PG16 10 6.5 13.9 12.5 20.9 0.9/1.25 33.3 20E1W PVC06

    25 25 3/4” PG21 10 11.1 19.9 17.0 26.2 1.25/1.6 40.5 25E1W PVC09

    32 32 1” PG29 10 17.0 26.2 22.9 33.9 1.6/2.0 51.0 32E1W PVC11

    40 40 1-1/4” PG36 15 22.0 32.1 26.0 40.4 1.6/2.0 61.0 40E1W PVC15

    50S 50 1-1/2” PG36 15 29.5 38.1 35.0 46.7 2.0/2.5 66.5 50SE1W PVC18

    50 50 2” PG42 15 35.6 44.0 38.0 53.1 2.0/2.5 77.7 50E1W PVC21

    63S 63 2” PG48 15 40.1 49.9 45.6 59.4 2.5 83.2 63SE1W PVC23

    63 63 2-1/2” - 15 47.2 55.9 54.6 65.9 2.5 88.7 63E1W PVC25

    75S 75 2-1/2” - 15 52.8 61.9 57.0 72.1 2.5 101.6 75SE1W PVC28

    75 75 3” - 15 59.1 67.9 60.4 78.5 2.5/3.15 111.1 75E1W PVC30

    90 90 3” - 15 66.6 79.3 69.2 90.4 3.15 128.6 90E1W PVC32

    All Dimensions in Millimetres

    E1W Industrial Cable Gland

    ADDITIONAL APPROVALS

    MARINE APPROVALS LLOYDS,ABS

    GOST CERTIFICATE OF CONFORMITY 5318856 REIW version colour coded with red

    ferrule for ease of identification

    A

    B

    C

    D

    E

  • 8/17/2019 Cat-CMP Cable Gland

    22/64

    20

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

      L  E  A  D  C  O  V  E  R  E  D  A  R  M  O  U  R  E  D  C  A  B  L  E  S  W  A

    RE2W version colour coded with redferrule for ease of identification

    E2W GLAND

    Brass indoor and outdoor cable gland for all types of Lead Covered SWA

    cable providing environmental seal on both the cable inner and outer sheaths.

    The gland also provides mechanical cable retention, and electrical continuity

    via armour wire termination and earth bonding of Lead Sheath.

    TECHNICAL DATA

    TYPE E2W

    DESIGN SPECIFICATION BSEN50262

    INGRESS PROTECTION IP66

    GLAND MATERIAL BRASS

    SEAL MATERIAL CMP SOLO LSF

    CABLE TYPE LEAD COVERED STEEL WIRE ARMOUR

    ARMOUR CLAMPING TWO PART ARMOUR LOCK

    (THREE PART OPTION AVAILABLE)

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA (S) INNER & OUTER SHEATH

    OPTIONAL ACCESSORIES SHROUD, LOCKNUT, EARTH TAG

    ENTRY THREAD SEAL, SERRATED WASHER

    ADAPTOR/REDUCER

    * Integral Entry Thread Seal Option Available(for this option pre-fix gland type with ‘R’, e.g. 25RE2W)

    Minimum Armour Across Ordering PVCGland Standard Entry Threads ‘C’

    ThreadCable Dia ‘A’ Cable Dia ‘B’

     Wire Corners Reference ShroudSize

    Metric NPT PG Length ‘D’ Min Max Min Max Dia Dia ‘E’ Max (Metric) Ref.

    20S 20 1/2” PG13.5 10 6.1 11.6 9.5 15.9 0.9/1.25 26.6 20SE2W PVC0420 20 1/2” PG16 10 6.5 13.9 12.5 20.9 0.9/1.25 33.3 20E2W PVC06

    25 25 3/4” PG21 10 11.1 19.9 17.0 26.2 1.25/1.6 40.5 25E2W PVC09

    32 32 1” PG29 10 17.0 26.2 22.9 33.9 1.6/2.0 51.0 32E2W PVC11

    40 40 1-1/4” PG36 15 22.0 32.1 26.0 40.4 1.6/2.0 61.0 40E2W PVC15

    50S 50 1-1/2” PG36 15 29.5 38.1 35.0 46.7 2.0/2.5 66.5 50SE2W PVC18

    50 50 2” PG42 15 35.6 44.0 38.0 53.1 2.0/2.5 77.7 50E2W PVC21

    63S 63 2” PG48 15 40.1 49.9 45.6 59.4 2.5 83.2 63SE2W PVC23

    63 63 2-1/2” - 15 47.2 55.9 54.6 65.9 2.5 88.7 63E2W PVC25

    75S 75 2-1/2” - 15 52.8 61.9 57.0 72.1 2.5 101.6 75SE2W PVC28

    75 75 3” - 15 59.1 67.9 60.4 78.5 2.5/3.15 111.1 75E2W PVC30

    90 90 3” - 15 66.6 79.3 69.2 90.4 3.15 128.6 90E2W PVC32

    All Dimensions in Millimetres

    E2W Industrial Cable Gland

    ADDITIONAL APPROVALS

    MARINE APPROVALS LLOYDS,ABS

    GOST CERTIFICATE OF CONFORMITY 5318856

    A

    B

    C

    D

    E

  • 8/17/2019 Cat-CMP Cable Gland

    23/64

       B   R   A   I   D   E   D   O   R   S   T   A

       C   A   B   L   E

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    21

    RE1X/Z version colour coded with redferrule for ease of identification

    E1X/Z GLAND

    Brass indoor and outdoor cable gland for all types of braided or steel tape

    armour (S.T.A.) cables, providing environmental seal on both the cable inner

    and outer sheaths.The gland also provides mechanical cable retention and

    electrical continuity via wire braid or tape armour termination.

    TECHNICAL DATA

    TYPE E1X / Z

    DESIGN SPECIFICATION BSEN50262

    INGRESS PROTECTION IP66

    GLAND MATERIAL BRASS

    SEAL MATERIAL CMP SOLO LSF

    CABLE TYPE WIRE BRAID OR STEEL TAPE ARMOUR

    ARMOUR CLAMPING THREE PART ARMOUR LOCK

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA (S) INNER & OUTER SHEATH

    OPTIONAL ACCESSORIES SHROUD, LOCKNUT, EARTH TAG

    ENTRY THREAD SEAL, SERRATED WASHER

    ADAPTOR/REDUCER

    Minimum Braid Across Ordering PVCGland Standard Entry Threads ‘C’

    ThreadCable Dia ‘A’ Cable Dia ‘B’

    Thickness Corners Reference ShroudSize

    Metric NPT PG Length ‘D’ Min Max Min Max Max Dia ‘E’ Max (Metric) Ref.

    ✝ 20/16 20 1/2” PG11 15 3.1 8.6 6.0 13.4 0.85 24.4 20/16E1X/Z PVC0220S 20 1/2” PG13.5 10 6.1 11.6 9.5 15.9 0.85 26.6 20SE1X/Z PVC04

    20 20 1/2” PG16 10 6.5 13.9 12.5 20.9 0.9 33.3 20E1X/Z PVC06

    25 25 3/4” PG21 10 11.1 19.9 17.0 26.2 1.25 40.5 25E1X/Z PVC09

    32 32 1” PG29 10 17.0 26.2 22.9 33.9 1.4 51.0 32E1X/Z PVC11

    40 40 1-1/4” PG36 15 22.0 32.1 26.0 40.4 1.4 61.0 40E1X/Z PVC15

    50S 50 1-1/2” PG36 15 29.5 38.1 35.0 46.7 1.4 66.5 50SE1X/Z PVC18

    50 50 2” PG42 15 35.6 44.0 38.0 53.1 1.4 77.7 50E1X/Z PVC21

    63S 63 2” PG48 15 40.1 49.9 45.6 59.4 1.5 83.2 63SE1X/Z PVC23

    63 63 2-1/2” - 15 47.2 55.9 54.6 65.9 1.5 88.7 63E1X/Z PVC25

    75S 75 2-1/2” - 15 52.8 61.9 57.0 72.1 1.5 101.6 75SE1X/Z PVC28

    75 75 3” - 15 59.1 67.9 60.4 78.5 1.5 111.1 75E1X/Z PVC30

    90 90 3” - 15 66.6 79.3 69.2 90.4 1.6 128.6 90E1X/Z PVC32

    All Dimensions in Millimetres

    * Integral Entry Thread Seal Option Available

    (for this option pre-fix gland type with ‘R’, e.g. 25RE1X/Z)Also available in Brass with Nickel Plated finish & Aluminium

    ✝ Note size 20/16 suitable for braid armour only.

    E1X / Z Industrial Cable Gland

    ADDITIONAL APPROVALS

    MARINE APPROVALS LLOYDS,ABS

    GOST CERTIFICATE OF CONFORMITY 5318856

    D

    A

    B

    C

    E

  • 8/17/2019 Cat-CMP Cable Gland

    24/64

    22

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

      A  R  M  O  U  R  E  D  C  A  B

      L  E  A  W  A

    D

    A

    B

    C

    E

    CW AL GLAND

    Aluminium indoor and outdoor cable gland for all types of AWA cable,

    providing environmental seal on the cable outer sheath.The gland also

    provides mechanical cable retention and electrical continuity via armour

    wire termination.

    TECHNICAL DATA

    TYPE CW ALUMINIUM

    DESIGN SPECIFICATION BSEN50262

    INGRESS PROTECTION IP66

    GLAND MATERIAL ALUMINIUM

    SEAL MATERIAL CMP SOLO LSF

    CABLE TYPE ALUMINIUM WIRE ARMOUR

    ARMOUR CLAMPING TWO PART ARMOUR LOCK

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA (S) OUTER SHEATH

    OPTIONAL ACCESSORIES SHROUD, LOCKNUT, EARTH TAG

    ENTRY THREAD SEAL, SERRATED WASHER

    ADAPTOR/REDUCER

    Gland SizeMetric Minimum Cable Cable Armour Across Ordering PVC

    Entry Thread Dia ‘A’ Dia ‘B’ Wire Corners Reference Shroud

    Thread ‘C’ Length ‘D’ Max Min Max Dia Dia ‘E’ Max (Gland Only) Ref.

    20S 20 10 11.6 9.5 15.9 0.9/1.25 26.6 20SCW AL PVC04

    20 20 10 13.9 12.5 20.9 0.9/1.25 33.3 20CW AL PVC06

    25 25 10 19.9 17.0 26.2 1.25/1.6 40.5 25CW AL PVC09

    32 32 10 26.2 22.9 33.9 1.6/2.0 51.0 32CW AL PVC11

    40 40 15 32.1 26.0 40.4 1.6/2.0 61.0 40CW AL PVC15

    50S 50 15 38.1 35.0 46.7 2.0/2.5 66.5 50SCW AL PVC18

    50 50 15 44.0 38.0 53.1 2.0/2.5 78.6 50CW AL PVC21

    63S 63 15 50.0 45.6 59.4 2.5 83.2 63SCW AL PVC23

    63 63 15 55.9 54.6 65.9 2.5 89.0 63CW AL PVC25

    75S 75 15 61.9 57.0 72.1 2.5 101.6 75SCW AL PVC28

    All Dimensions in Millimetres

    CW Aluminium Industrial Cable Gland

    ADDITIONAL APPROVALS

    GOST CERTIFICATE OF CONFORMITY 5318856

  • 8/17/2019 Cat-CMP Cable Gland

    25/64

     APPL ICAT ION

    The CMP range of Hazardous Area Cable Glands offers the user solutions which are highly cost effective in their design, and installation process. The

    CMP philosophy of delivering client and end user specific requirements can beseen from a number of significant developments in this range. Given the level

    of experience gained in this field CMP are able to provide a high degree of technical support and advice on the use of cable Glands in Hazardous Area

    applications

    PRODUCTS

    Cable Gland options for all types of cable.

    SPECIFICATIONS & APPROVALS

    Derived from the BS6121 standard which was the original ‘flameproof’standard for Cable Glands CMP Hazardous Area Cable Glands comply with

    a number of international standards including CENELEC (EN50014 & EN60079), IEC (IEC 79) UL & CSA.

    CMP PRODUCTS

    RANGE FOR IEC TYPE CABLES

    ‘© BP Amoco p.l.c. 1997

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

  • 8/17/2019 Cat-CMP Cable Gland

    26/64

    24

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    Dual Certified Flameproof (Type 'd') and Increased Safety (Type 'e') indoor and

    outdoor cable gland for use in Zone 1,Zone 2, Zone 21 and Zone 22 Hazardous

    Areas with all types of unarmoured cable, providing a Flameproof seal on the cable

    outer sheath.

    TECHNICAL DATA

    TYPE A2F

    CENELEC (ATEX) CERTIFICATION SIRA02ATEX1057X

    CODE OF PROTECTION CATEGORY ATEX II 2 GD EEx d IIC & EEx e II,

    EQUIPMENT ZONE 1,ZONE 2, ZONE 21, &

    ZONE 22 - GAS GROUPS IIA, IIB, IIC

    COMPLIANCE STANDARDS EN50014,EN50018,EN50019,EN50281-1-1

    CONTINUOUS OPERATING TEMP.RANGE -60°C TO +130°C

    INGRESS PROTECTION IP66, IP67 & IP68 (10M DEPTH)

    DELUGE PROTECTION TO DTS 01:1991

    GLAND MATERIAL BRASS

    SEAL MATERIAL CMP SOLO LSFCABLE TYPE UNARMOURED

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA(S) OUTER SHEATH

    OPTIONAL ACCESSORIES SHROUD, LOCKNUT, EARTH TAG,

    ENTRY THREAD SEAL, SERRATED WASHER,

    ADAPTOR/REDUCER

    Minimum Across Ordering PVC

    Gland SizeStandard Entry Threads ‘B’

    ThreadCable Dia ‘A’

    Corners Reference Shroud

    Metric NPT PG Length ‘C’ Min Max Dia ‘D’ Max (Metric) Ref.

    16 16 1/2” PG11 15 3.1 8.6 24.4 16A2F PVC0120/16 20 1/2” PG11 15 3.1 8.6 24.4 20/16A2F PVC01

    20S 20 1/2” PG13.5 15 6.1 11.6 26.5 20SA2F PVC03

    20 20 1/2” PG16 15 6.5 13.9 30.0 20A2F PVC05

    25 25 3/4” PG21 15 11.1 19.9 39.9 25A2F PVC08

    32 32 1” PG29 15 17.0 26.2 45.5 32A2F PVC10

    40 40 1-1/4” PG36 15 22.0 32.1 55.4 40A2F PVC12

    50S 50 1-1/2” PG36 15 29.5 38.1 61.0 50SA2F PVC14

    50 50 2” PG42 15 35.6 44.0 66.5 50A2F PVC17

    63S 63 2” PG48 15 40.1 49.9 77.6 63SA2F PVC20

    63 63 2-1/2” - 15 47.2 55.9 83.2 63A2F PVC22

    75S 75 2-1/2” - 15 52.8 61.9 88.7 75SA2F PVC24

    75 75 3” - 15 59.1 67.9 94.2 75A2F PVC26

    90 90 3” - 15 66.6 79.3 120.7 90A2F PVC31

    All Dimensions in Millimetres

    A

    B

    C

    D

    A2F Flameproof EEx d & Increased Safety EEx e Cable Gland A2F GLAND

    ADDITIONAL APPROVALS

    MARINE APPROVALS LLOYDS, DNV,ABS

    CSA APPROVAL 1211841

    CEPEL/INMENRD APPROVAL EX-023

    SAQAS APPROVAL AUS EX764

    GOST APPROVAL 2002 . C256

    * Integral Entry Thread Seal Option Available(for this option pre-fix gland type with ‘R’, e.g. 25RA2F)Also available in Brass with Nickel Plated finish, Stainless Steel & Aluminium

      U  N  A  R  M  O  U  R  E  D

      C  A  B  L  E

  • 8/17/2019 Cat-CMP Cable Gland

    27/64

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    25

       U   N   A   R   M   O   U   R   E   D

       C   A   B   L   E

    Sureseal 2000 (SS2K) EEx ‘d’ & EEx ‘e’ Cable Gland SS2K GLAND

    Flameproof (Type ‘d’) and Increased Safety (Type ‘e’) Brass Cable Gland for all

    types of Unarmored Cables.This Cable Gland provides an explosion proof seal on

    the cable inner or outer sheath and a secondary environmental seal on the cable

    outer sheath. Suitable for use in Zone 1 and 2 Hazardous Areas, this Cable Gland

    design affords extra stability and superior resistance to cable pull out.Type SS2KPBavailable for unarmoured cables with lead sheath.

    TECHNICAL DATA

    A

    B

    C

    D

    E

    TYPE SS2K (SS2KPB FOR LEAD SHEATHED CABLES)

    CERTIFICATION DETAIL SIRA 02ATEX1057X

    CODE OF PROTECTION CATEGORY ATEX II 2 GD EEx d IIC & EEx e II,

    Equipment Zone 1, Zone 2, Zone 21,

    & Zone 22 - Gas Groups IIA, IIB, IIC

    COMPLIANCE CODE EN50014:1997, EN50018:2000,

    EN50019:2000, EN50281-1-1:1998

    TEMPERATURE RATING

    (CONT. OPERATION) -60°C TO +130°C

    INGRESS PROTECTION IP66, IP67 & IP68 (DEPTH OF 10M)

    DELUGE PROTECTION TO DTS 01:91

    GLAND MATERIAL BRASS

    SEAL MATERIAL LSF THERMOPLASTIC ELASTOMER

    CABLE TYPE UNARMOURED

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA(S) OUTER SHEATH (DOUBLE SEAL)

    OPTIONAL ACCESSORIES LOCKNUT,EARTH TAG, SERRATED

    WASHER, ENTRY THREAD SEAL,

    ADAPTOR/REDUCER

    Integral Entry Thread Seal Option Available (for this option pre-fix glandtype with ‘R’ e.g. 25RSS2K).

    Standard Entry Minimum Cable Dia ‘A’ / ‘B’ Across OrderingGland Threads ‘C’ Thread Millimetres Corners ReferenceSize

    Metric NPT PG Length ‘D’ Min Max Dia ‘E’ Max (Metric)

    16 16 1/2” PG11 15 3.1 8.6 24.4 16SS2K20/16 20 1/2” PG11 15 3.1 8.6 24.4 20/16SS2K

    20S 20 1/2” PG13.5 15 6.1 11.6 26.5 20SSS2K

    20 20 1/2” PG16 15 6.5 13.9 30.0 20SS2K

    25 25 3/4” PG21 15 11.1 19.9 39.9 25SS2K

    32 32 1” PG29 15 17.0 26.2 45.5 32SS2K

    40 40 1-1/4” PG36 15 22.0 32.1 55.4 40SS2K

    50S 50 1-1/2” PG36 15 29.5 38.1 61.0 50SSS2K

    50 50 2” PG42 15 35.6 44.0 66.5 50SS2K

    63S 63 2” PG48 15 40.1 49.9 77.6 63SSS2K

    63 63 2-1/2” - 15 47.2 55.9 83.2 63SS2K

    75S 75 2-1/2” - 15 52.8 61.9 88.7 75SSS2K

    75 75 3” - 15 59.1 67.9 94.2 75SS2K90 90 3” - 15 66.6 79.3 120.7 90SS2K

    All Dimensions in Millimetres

  • 8/17/2019 Cat-CMP Cable Gland

    28/64

    w w w . c m p –  p r o d u c t s . c o m

      U  N  A  R  M  O  U  R  E  D  C  A  B  L  E

      (  C  O  N  D  U  I  T  )

    Doc Ref : TPC 164 issue 04 2005

    Minimum ✝ Standard AcrossOrderingGland Standard Entry Threads ‘B’

    Thread FemaleCable Dia ‘A’

    CornersReferenceSize

    Metric NPT PG Length ‘C’ NPT Threads Min Max Dia ‘D’ Max

    20/16 20 1/2” PG11 15 1/2” 3.1 8.6 30.0 20/16A2FRC20S 20 1/2” PG13.5 15 1/2” 6.1 11.6 30.0 20SA2FRC

    20 20 1/2” PG16 15 1/2” 6.5 13.9 30.0 20A2FRC

    25 25 3/4” PG21 15 3/4” 11.1 19.9 39.9 25A2FRC

    32 32 1” PG29 15 1” 17.0 26.2 45.5 32A2FRC

    40 40 1-1/4” PG36 15 1-1/4” 22.0 32.1 55.4 40A2FRC

    50S 50 1-1/2” PG36 15 1-1/2” 29.5 38.1 61.0 50SA2FRC

    50 50 2” PG42 15 2” 35.6 44.0 72.1 50A2FRC

    63S 63 2” PG48 15 2” 40.1 49.9 77.6 63SA2FRC

    63 63 2-1/2” - 15 2-1/2” 47.2 55.9 88.7 63A2FRC

    75S 75 2-1/2” - 15 2-1/2” 52.8 61.9 88.7 75SA2FRC

    75 75 3” - 15 3” 59.1 67.9 105.3 75A2FRC

    90 90 3” - 15 3” 66.6 79.3 120.7 90A2FRC

    All Dimensions in Millimetres

    ✝ Female connection threads in NPT, other thread forms manufactured to order. When ordering please confirm Male & Female Threads required.

    A

    B

    C

    D

     A2FRC GLAND

    3426

    A2FRC Flameproof EEx d & Increased Safety EEx e Cable Gland

    Also available in Brass with Nickel Plated finish

    Dual Certified Flameproof (Type 'd') and Increased Safety (Type 'e') indoor and

    outdoor cable gland for use in Zone 1,Zone 2, Zone 21 and Zone 22 Hazardous

    Areas with all types unarmoured cable housed in rigid or flexible conduit system.

    The cable gland provides a Flameproof Seal on the cable outer sheath and is

    equipped with a rotating female connection for ease of conduit installation.

    TECHNICAL DATA

    TYPE A2FRC

    DETAIL SIRA02ATEX1057X

    CODE OF PROTECTION CATEGORY ATEX II 2 GD EEx d IIC & EEx e II,

    EQUIPMENT ZONE 1,ZONE 2, ZONE 21,

    & ZONE 22 - GAS GROUPS IIA, IIB, IIC

    COMPLIANCE S TANDARDS EN50014, EN50018, EN50019, EN50281-1-1

    CONTINUOUS OPERATING TEMP RANGE -60ºC TO +130ºC

    INGRESS PROTECTION IP66, IP67 & IP68 (10M DEPTH)

    GLAND MATERIAL BRASS

    SEAL MATERIAL CMP SOLO LSF

    CABLE TYPE UNARMOURED

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA(S) OUTER SHEATH

    OPTIONAL ACCESSORIES LOCKNUT, EARTH TAG, SERRATED WASHER

    ENTRY THREAD SEAL,ADAPTOR/REDUCER

    ADDITIONAL APPROVALS

    MARINE APPROVALS LLOYDS,ABS

    GOST APPROVAL 2002 . C256

  • 8/17/2019 Cat-CMP Cable Gland

    29/64

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    V-Tec (A2Pe) For Hazazrdous Locations

    CMP V-TEC EX M Cable Glands (A2Pe) - Code of protection EEx e II

    *Sealing range based upon strain relief & twist protection to VDE 0619 - Available colours: Black, Light Grey (RAL 7001) & Silver Grey (RAL 7035).For colour options please add the folowing suffix to the ordering codes above:B= Black. G= Light Grey. S= Silver GreyOther colours and other non-metallic products in the V-TEC range are also available, please consult CMP Products for further information.

    A2XPI / A2XLP1 PG 7 8.0 15.0 3.5 6.5 18.0 23.0 15.0 16.5 0.41 50

    A2XP2 / A2XLP2 PG 9 8.0 15.0 5.0 8.0 21.0 27.0 19.0 21.0 0.67 50

    A2XP3 / A2XLP3 PG 11 8.0 15.0 4.5 10.0 22.0 29.0 22.0 25.0 0.93 50

    A2XP4 / A2XLP4 PG 13.5 9.0 15.0 6.5 12.0 22.0 30.0 24.0 27.0 1.09 50

    A2XP5 / A2XLP5 PG 16 10.0 15.0 7.0 14.0 25.0 33.0 27.0 30.0 1.49 25

    A2XP6 / A2XLP6 PG 21 11.0 15.0 12.0 18.0 28.0 38.0 33.0 37.5 2.33 25

    A2XP7 / A2XLP7 PG 29 11.0 15.0 17.0 25.0 32.0 43.0 42.0 47.5 3.86 20

    A2XP9 / A2XLP9 PG 42 13.0 18.0 24.0 38.0 42.0 57.0 60.0 68.5 10.07 5

    A2XP10 / A2XLP10 PG 48 14.0 18.0 30.0 44.0 42.0 58.0 65.0 74.0 10.73 5

    CMP V-TEC EX & EX L Cable Glands (A2Pe) - Code of protection EEx e II

    Size Ref.ThreadSize ‘A’

    Thread Length ‘B’

    EX EX L

    Cable AcceptanceRange ‘C’

    Min Max

    Overall Length ‘D’

    Min Max

    AcrossFlats

    AcrossCorners

    Weight(KG/100)

    Pack QTY.

    A2XMP1 M12 8.0 3.5 6.5 18.0 23.0 15.0 16.5 0.36 50

    A2XMP2 M16 8.0 5.0 8.0 21.0 27.0 19.0 21.0 0.63 50

    A2XMP3 M20 9.0 7.0 12.0 23.0 30.0 24.0 27.0 1.00 50

    A2XMP4 M25 11.0 12.0 18.0 28.0 38.0 33.0 37.5 2.35 25

    A2XMP5 M32 11.0 17.0 25.0 32.0 43.0 42.0 47.5 3.90 20

    Size Ref.ThreadSize ‘A’

    Cable AcceptanceRange ‘C’

    Min Max

    Overall Length ‘D’AcrossFlats

    AcrossCorners

    Weight(KG/100)

    Pack QTY.

    ThreadLength ‘B’

    Min Max

    TYPE DESIGNATION V-TEC, EX L & EX M (A2PE)

    CLASSIFICATION,HAZARDOUS AREA II 2G EEX E II

    COMPLIANCE CODE EN50014 & EN50019

    CENELEC CERTIFICATION PTB 99 ATEX 3112X & ATEX 3113X

    UL LISTING EI70293

    CABLE GLAND MATERIAL PA POLYAMIDE, (COLOUR BLACK)

    SEAL MATERIAL CMP SOLO LSF

    FLAME RETARDANCY SPECIFICATION VDE 0471/IEC 695 PART 2-1

    WITHSTAND TEMPERATURE TESTED +750˚C

    CONTINUOUS OPERATING -20˚C TO +70˚CTEMPERATURE RANGE

    INGRESS PROTECTION IP68(AT 5 BAR) TO VDE 0619 / IEC529

    CABLE TYPE UNARMOURED

    SEALING AREA OUTER SHEATH

    SEALING TECHNIQUE CONTROLLED SEAL WITH STRAIN RELIEF

    OPTIONAL ACCESSORIES LOCKNUT, ADAPTOR / REDUCER

    TECHNICAL DATA

    Plastic gland for use with unarmoured cables.

       U   N   A   R   M   O   U   R   E   D   C   A   B   L   E   S

    27

  • 8/17/2019 Cat-CMP Cable Gland

    30/64

    A4e Increased Safety EEx e Cable Gland

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

      A  R  M  O  U  R  E  D  C  A  B

      L  E  S  T  A

    28

    TYPE A4e

    CERTIFICATION DETAIL SIRA02ATEX1057X

    CODE OF PROTECTION CATEGORY ATEX II 2 GD EEx e II, Equipment

    Zone 1, Zone 2, Zone 21,& Zone 22 - Gas

    Groups IIA, IIB, IIC

    COMPLIANCE CODE EN50014:1997, EN50019:2000,

    EN50281-1-1:1998

    CONTINUOUS OPERATING

    TEMPERATURE RANGE -60°C TO +130°C

    INGRESS PROTECTION IP66

    GLAND MATERIAL BRASS

    SEAL MATERIAL LSF THERMOPLASTIC ELASTOMER

    CABLE TYPE STEEL TAPE ARMOUR

    ARMOUR TERMINATION LEAD CONTINUITY SEAL

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA (S) OUTER SHEATH

    OPTIONAL ACCESSORIES SHROUD, LOCKNUT, EARTH TAG,

    ENTRY THREAD SEAL, SERRATED WASHER

    ADAPTOR/REDUCER

    * SOLO Option with LSF Shrouds also Available.

    A

    B

    C

    D

    E

     A4e GLAND

    Brass indoor and outdoor cable gland for use in Zone 1 and Zone 2 Hazardous Areas

    with all types of steel tape armour cable, providing a seal on the cable outer sheath,

    and an electrical earth continuity seal on the Tape Armour.

    TECHNICAL DATA

    Minimum Across Ordering PVC

    Gland SizeStandard Entry Threads ‘C’

    ThreadCable Dia ‘A’ Cable Dia ‘B’

    Corners Reference Shroud

    Metric NPT PG Length ‘D’ Min Max Min Max Dia ‘E’ Max (Metric) Ref.

    20S 20 1/2” PG13.5 15 6.5 11.6 6.1 11.6 26.5 20SA4e PVC0420 20 1/2” PG16 15 10.0 13.9 6.5 13.9 30.0 20A4e PVC05

    25 25 3/4” PG21 15 11.6 19.9 11.1 19.9 39.9 25A4e PVC09

    32 32 1” PG29 15 19.0 26.2 17.0 26.2 45.5 32A4e PVC10

    40 40 1-1/4” PG36 15 25.0 32.1 22.0 32.1 55.4 40A4e PVC13

    50S 50 1-1/2” PG36 15 27.5 38.1 29.5 38.1 61.0 50SA4e PVC15

    50 50 2” PG42 15 33.1 44.0 35.6 44.0 66.5 50A4e PVC18

    63S 63 2” PG48 15 40.1 50.0 40.1 49.9 77.6 63SA4e PVC21

    63 63 2-1/2” - 15 47.2 55.9 47.2 55.9 83.2 63A4e PVC23

    75S 75 2-1/2” - 15 43.5 61.9 52.8 61.9 88.7 75SA4e PVC24

    75 75 3” - 15 49.8 67.9 59.1 67.9 94.2 75A4e PVC26

    90 90 3” - 15 64.0 79.3 66.6 79.3 120.7 90A4e PVC31

    All Dimensions are in Millimetres

  • 8/17/2019 Cat-CMP Cable Gland

    31/64

    w w w . c m p –  p r o d u c t s . c o m

    3429

       M   U   L   T   I   P   L   E   A   R   M   O   U

       R   C   A   B   L   E   S

    Doc Ref : TPC 164 issue 04 2005

    Increased Safety (Type 'e') Deluge Proof cable gland for all types of armoured cables

    including Single Wire Armour (SWA), Steel Tape Armour (STA) and Braided cables.This

    cable gland provides an environmental seal on the cable outer sheath and incorporates

    an enclosed 'O' ring seal for deluge protection which has been independently tested to

    DTS 01:1991.The gland also provides mechanical cable retention and earth continuity

    via armour termination. Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22

    Hazardous Areas in Increased Safety (type 'e') apparatus or EEx de equipment which

    has an increased safety terminal chamber.

    TECHNICAL DATA

    TYPE C2K

    DETAIL SIRA01ATEX3283X

    COMPLIANCE STANDARDS EN50014,EN50019, EN50281-1-1

    COMPLIANCE STANDARDS ATEX II 2 GD EEx e II, EQUIPMENT ZONE 1,ZONE 2,

    ZONE 21, & ZONE 22 - GAS GROUPS IIA, IIB, IIC

    CONTINUOUS OPERATING

    TEMPERATURE RATING -60°C TO +130°CINGRESS PROTECTION IP66, I P67, I P68 (10M DEPTH)

    DELUGE PROTECTION TO DTS 01: 1991

    GLAND MATERIAL BRASS

    SEAL MATERIAL CMP SOLO LSF

    CABLE TYPE STEEL WIRE, STEEL TAPE OR WIRE BRAID ARMOUR

    ARMOUR CLAMPING REVERSIBLE ARMOUR CONE

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA (S) OUTER SHEATH

    OPTIONAL ACCESSORIES LOCKNUT, EARTH TAG, ENTRY THREAD SEAL

    SERRATED WASHER, ADAPTOR/REDUCER

    ✝ For IP67 & IP68 requirements the cable diameter ‘B’ (minimum value) shown above should be increased by 1.0mm to ensure compliance.

    C2K Increased Safety EEx e Cable Gland

    ADDITIONAL APPROVALS

    MARINE APPROVALS LLOYDS, DNV,ABS

    GOST APPROVAL 2002 . C256

    C2K GLAND

    Standard Entry Minimum Cable Dia ‘A’ ✝ Cable Dia ‘B’ Armour Range Across OrderingGland Threads ‘C’ Thread (mm) (mm) Grooved Cone Plain Cone Corners ReferenceSize

    Metric NPT Length ‘D’ Max Min Max Min Max Min Max ‘E’ Max (Metric)

    20/16 20 1/2” 15 8.6 6.0 13.4 0 1.0 0.9 1.0 24.4 20/16C2K20S 20 1/2” 15 11.6 9.5 15.9 0 1.0 0.9 1.25 26.6 20SC2K

    20 20 1/2” 15 13.9 12.5 20.9 0 1.0 0.9 1.25 33.3 20C2K

    25 25 3/4” 15 19.9 17.0 26.2 0 1.0 1.25 1.6 40.5 25C2K

    32 32 1” 15 26.2 22.9 33.9 0 1.0 1.6 2.0 51.0 32C2K

    40 40 1-1/4” 15 32.1 26.0 40.4 0 1.0 1.6 2.0 61.0 40C2K

    50S 50 1-1/2” 15 38.1 35.0 46.7 0 1.0 2.0 2.5 66.5 50SC2K

    50 50 2” 15 44.0 38.0 53.1 0 1.0 2.0 2.5 77.7 50C2K

    63S 63 2” 15 50.0 45.6 59.4 0 1.0 2.5 2.5 83.2 63SC2K

    63 63 2-1/2” 15 55.9 54.6 65.9 0 1.0 2.5 2.5 88.7 63C2K

    75S 75 2-1/2” 15 61.9 57.0 72.1 0 1.0 2.5 2.5 101.6 75SC2K

    75 75 3” 15 67.9 60.4 78.5 0 1.0 2.5 2.5 111.1 75C2K

    90 90 3-1/2” 15 79.3 69.2 90.4 0 1.6 2.5 2.5 128.6 90C2K

    All Dimensions are in Millimetres

    D

    A

    B

    C

    E

  • 8/17/2019 Cat-CMP Cable Gland

    32/64

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    Increased Safety (Type 'e') indoor and outdoor cable gland for use in Zone 1, Zone 2,

    Zone 21 and Zone 22 Hazardous Areas with all types of SWA cable providing an

    environmental seal on the cable outer sheath.The cable gland also provides mechanical

    cable retention and earth continuity via armour wire termination. Suitable for use in

    conjunction with Increased Safety (type 'e') apparatus or EEx de equipment which has

    an increased safety terminal chamber.

    TECHNICAL DATA

    TYPE CWe

    DETAIL SIRA01ATEX3287X

    CODE OF PROTECTION CATEGORY ATEX II 2 GD EEx e II, EQUIPMENTZONE 1, ZONE 2, ZONE 21,& ZONE 22 -GAS GROUPS IIA, IIB, IIC

    COMPLIANCE STANDARDS EN50014, EN50019, EN50281-1-1

    CONTINUOUS OPERATINGTEMPERATURE RANGE -60°C TO +130°C

    INGRESS PROTECTION IP66

    GLAND MATERIAL BRASS

    SEAL MATERIAL CMP SOLO LSF

    CABLE TYPE STEEL WIRE ARMOUR

    ARMOUR CLAMPING TWO PART ARMOUR LOCK(THREE PART OPTION AVAILABLE).

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA (S) OUTER SHEATH

    OPTIONAL ACCESSORIES SHROUD, LOCKNUT, EARTH TAG,ENTRY THREAD SEAL, SERRATED WASHERADAPTOR/REDUCER

    * CMP SOLO Option with LSF Shrouds also Available.

    Also available in Brass with Nickel Plated finish and Aluminium

    CWe Increased Safety EEx e Cable GlandCWe GLAND

    ADDITIONAL APPROVALS

    MARINE APPROVALS LLOYDS,ABS

    GOST APPROVAL 2002 . C256

    ANZEX APPROVAL ANZEX 03. 3000-0

    Gland SizeMetric Minimum Cable Cable Armour Across

    OrderingPVC

    Entry Thread Dia ‘A’ Dia ‘B’ Wire CornersReference

    Shroud

    Thread ‘C’ Length ‘D’ Max Min Max Dia Dia ‘E’ Max Ref.

    20/16 20 15 8.6 6.0 13.4 0.9 24.4 20/16CWe PVC02

    20S 20 15 11.6 9.5 15.9 0.9/1.25 26.6 20SCWe PVC04

    20 20 15 13.9 12.5 20.9 0.9/1.25 33.3 20CWe PVC06

    25 25 15 19.9 17.0 26.2 1.25/1.6 40.5 25CWe PVC09

    32 32 15 26.2 22.9 33.9 1.6/2.0 51.0 32CWe PVC11

    40 40 15 32.1 26.0 40.4 1.6/2.0 61.0 40CWe PVC15

    50S 50 15 38.1 35.0 46.7 2.0/2.5 66.5 50SCWe PVC18

    50 50 15 44.0 38.0 53.1 2.0/2.5 78.6 50CWe PVC21

    63S 63 15 50.0 45.6 59.4 2.5 83.2 63SCWe PVC23

    63 63 15 55.9 54.6 65.9 2.5 89.0 63CWe PVC25

    75S 75 15 61.9 57.0 72.1 2.5 101.6 75SCWe PVC28

    75 75 15 67.9 60.4 78.5 2.5/3.15 111.1 75CWe PVC30

    All Dimensions in Millimetres

      A  R  M  O  U  R  E  D  C  A  B  L  E  S  S  W  A

    30

    D

    A

    B

    C

    E

  • 8/17/2019 Cat-CMP Cable Gland

    33/64

    w w w . c m p –  p r o d u c t s . c o m

    3431

    Doc Ref : TPC 164 issue 04 2005

       B   R   A   I   D   E   D

       O   R   S   T   A

       C   A   B   L   E

    CXe GLAND

    Increased Safety (Type 'e') indoor and outdoor cable gland for use in Zone 1, Zone 2,

    Zone 21 and Zone 22 Hazardous Areas with all types of braided cable or STA cables

    providing an environmental seal on the cable outer sheath.The gland also provides

    mechanical cable retention and electrical continuity via armour termination. Suitable

    for use in conjunction with Increased Safety (type 'e') apparatus or EEx de equipment

    which has an increased safety terminal chamber.

    TECHNICAL DATA

    TYPE CXe

    DETAIL SIRA01ATEX3287X

    CODE OF PROTECTION CATEGORY ATEX II 2 GD EEx e II, EQUIPMENTZONE 1, ZONE 2, ZONE 21, & ZONE 22-GAS GROUPS IIA, IIB, IIC

    COMPLIANCE STANDARDS EN50014, EN50019, EN50281-1-1

    CONTINUOUS OPERATINGTEMPERATURE RANGE -60°C TO +130°C

    INGRESS PROTECTION IP66

    GLAND MATERIAL BRASS

    SEAL MATERIAL CMP SOLO LSF

    CABLE TYPE WIRE BRAID OR STA ARMOUR

    ARMOUR CLAMPING THREE PART ARMOUR LOCK

    SEALING TECHNIQUE CMP DISPLACEMENT SEAL CONCEPT

    SEALING AREA OUTER SHEATH

    OPTIONAL ACCESSORIES SHROUD, LOCKNUT, EARTH TAG,ENTRY THREAD SEAL, SERRATED WASHERADAPTOR/REDUCER

    * CMP SOLO Option with LSF Shrouds also Available.

    Also available in Brass with Nickel Plated finish

    CXe Increased Safety EEx e Cable Gland

    ADDITIONAL APPROVALS

    MARINE APPROVALS LLOYDS,ABS

    GOST APPROVAL 2002 . C256

    ANZEX APPROVAL ANZEX 03. 3000-0

    Gland SizeMetric Minimum Cable Cable Braid Across

    OrderingPVC

    Entry Thread Dia ‘A’ Dia ‘B’ Thickness CornersReference

    Shroud

    Thread ‘C’ Length ‘D’ Max Min Max Max Dia ‘E’ Max Ref.

    20/16 20 15 8.6 6.0 13.4 0.85 24.4 20/16CXe PVC02

    20S 20 15 11.6 9.5 15.9 0.85 26.6 20SCXe PVC04

    20 20 15 13.9 12.5 20.9 0.9 33.3 20CXe PVC06

    25 25 15 19.9 17.0 26.2 1.25 40.5 25CXe PVC09

    32 32 15 26.2 22.9 33.9 1.4 51.0 32CXe PVC11

    40 40 15 32.1 26.0 40.4 1.4 61.0 40CXe PVC15

    50S 50 15 38.1 35.0 46.7 1.4 66.5 50SCXe PVC18

    50 50 15 44.0 38.0 53.1 1.4 78.6 50CXe PVC21

    63S 63 15 50.0 45.6 59.4 1.5 83.2 63SCXe PVC23

    63 63 15 55.9 54.6 65.9 1.5 89.0 63CXe PVC25

    75S 75 15 61.9 57.0 72.1 1.5 101.6 75SCXe PVC28

    75 75 15 67.9 60.4 78.5 1.5 111.1 75CXe PVC30

    All Dimensions in Millimetres

    A

    B

    C

    D

    E

  • 8/17/2019 Cat-CMP Cable Gland

    34/64

    w w w . c m p –  p r o d u c t s . c o m

    Doc Ref : TPC 164 issue 04 2005

    T3CDS Cable Gland

    * For IP67 & IP68 requirements the Cable Diameter ‘B’ (minimum value) shown should be increased by 1.0mm to ensure complete compliance

    TRITON CDS (Compensating Displacement seal) T3CDS Flameproof EEx d andIncreased Safety EEx e brass cable gland for all types of armoured & braided cableincluding lead sheathed versions, providing a Flameproof seal on the cable inner sheathand an environmental seal on the cable outer sheath.Equipped with a unique ReversibleArmour Cone and Bi-Directional Armour Clamping Ring which can accommodate SWA,braided and STA cables. The Cable Gland provides mechanical cable retention, and

    electrical continuity via armour termination. Suitable for use in Zone 1, Zone 2,Zone 21and Zone 22 Hazardous Areas.

    20/16 M20 1/2” PG 11 15 3.1 8.6 6 13.4 0 1 0.9 1.25 24.4 22 74 20/16T3CDS POSPVC02

    20S M20 1/2” PG13.5 15 6.1 11.6 9.5 15.9 0 1 0.9 1.25 26.6 24 70 20ST3CDS POSPVC04

    20 M20 1/2” PG16 15 6.5 13.9 12.5 20.9 0 1 0.9 1.25 33.3 30.5 74 20T3CDS POSPVC06

    25 M25 3/4” PG21 15 11.1 19.9 18 26.2 0 1 1.25 1.6 40.5 37.5 82 25T3CDS POSPVC09

    25S M25 3/4” PG21 15 11.1 19.9 14 22 0 1 1.25 1.6 40.5 37.5 82 25ST3CDS POSPVC09

    32 M32 1” PG29 15 17 26.2 22.9 33.9 0 1 1.6 2 51 46 82 32ST3CDS POSPVC11

    40 M40 1-1/4” PG36 15 22 32.1 26 40.4 0 1 1.6 2 61 55 85 40T3CDS POSPVC15

    50S M50 1-1/2” PG36 15 29.5 38.1 35 46.7 0 1 2 2.5 66.5 60 93 50ST3CDS POSPVC18

    50 M50 2” PG42 15 35.6 44 38 53.1 0 1 2 2.5 78.6 70.1 98 50T3CDS POSPVC21

    63S M63 2” PG48 15 40.1 49.9 45.6 59.4 0 1 2.5 2.5 83.2 75 100 63ST3CDS POSPVC23

    63 M63 2-1/2” - 15 47.2 55.9 54.6 65.9 0 1 2.5 2.5 89 80 100 63T3CDS POSPVC25

    75S M75 2-1/2” - 15 52.8 60.5 57 72.1 0 1 2.5 2.5 101.6 90 100 75ST3CDS POSPVC28

    75 M75 3” - 15 59.1 67.9 60.4 78.5 0 1 2.5 2.5 111.1 100 110 75T3CDS POSPVC30

    90 M90 3-1/2” - 15 66.6 79.3 69.2 90.4 0 1 2.5 2.5 127.5 115 135 90T3CDS POSPVC32

    GlandSize

    Min.ThreadLength

    ‘D’

    AcrossCorners

    ‘E’

    AcrossFlats‘F’

    OrderingReference

    PVCShround

    Reference

    InstalledLength

    Protrusion‘G’

    Entry Threads ‘C’

    Standard Optional

    Cable Dia‘A’

    Cable Dia‘B’ Armour Range

    Metric NPT PG Min Max Max Max MaxGrooved Cone Plain ConeMin Max

    TRITON CDS (T3CDS)

    Triton CDS delivers a unique concept in cable sealing techniques incorporatingthe patented Compensating Displacement Seal system, CDS

    INNER FLAMEPROOF SEAL• Unique new Compensating Displacement Seal (CDS) system, compatible with all

    types of cable (eliminates cable damage and cold flow)• At the critical cable sealing point the CDS system protects the cable inner sheath

    from any excess force, which is transferred to and absorbed by the internalcompensator incorporated in the CDS system

    • Allows the Cable Gland to be tightened face to face every time regardlessof cable diameter.

    TECHNICAL DATA

    TYPE DESIGNATION T3CDS (T3CDS PB FOR LEAD SHEATHED CABLES)

    CODE OF PROTECTION CATEGORY ATEX II 2 GD EEx d IIC & EEx e II,

    COMPLIANCE STANDARDS EN50014,EN50018, EN50019 & EN50281-1-1:1998

    CONTINUOUS OPERATINGTEMPERATURE RANGE -60°C TO +130°C

    INGRESS PROTECTION IP66, I P67, I P68 & DTS 01:1991

    DELUGE PROTECTION TO DTS 01:1991

    STANDARD CABLE GLAND BRASS

    SEAL MATERIAL CMP SOLO LSF

    CABLE TYPE S.W.A., S.T.A. & WIRE BRAID

    ARMOUR CLAMPING REVERSIBLE ARMOUR CLAMPINGCONE & BI-DIRECTIONAL CLAMPING RING

    SEALING TECHNIQUE CMP UNIQUE COMPENSATINGDISPLACEMENT SEAL (CDS) SYSTEM

    SEALING AREA(S) INNER & OUTER SHEATH

    ACCESSORIES SHROUD, LOCKNUT, EARTH TAG, SERRATEDWASHER,ADAPTOR / REDUCER,ENTRY THREAD SEAL

    * Integral Entry Thread option Available (for this option pre-fixing / and type with ‘R’, e.g. RT3CDS or RT3CDSPB)

      M  U  L  T  I  P  L  E  A  R  M  O  U

      R  C  A  B  L  E  S

    32

    All Dimensions in Millimetres

  • 8/17/2019 Cat-CMP Cable Gland

    35/64

    w w w . c m p –  p r o d u c t s . c o m

    34

    Doc Ref : TPC 164 issue 04 2005

       A   R   M   O   U   R   E   D   C   A   B

       L   E   S   W   A

    33

    A

    B

    C

    D

    E

    Dual Certified Flameproof (Type 'd') and Increased Safety (Type 'e') indoor and outdoor

    cable gland for use in Zone 1, Zone 2, Zone 21 and Zone 22 Hazardous Areas with all

    types of SWA cable providing a Flameproof seal on the cable inner sheath and an

    environmental seal on the cable outer sheath.The gland also provides mechanical cable

    retention and electrical continuity via armour wire termination.

    TECHNICAL DATA

    TYPE E1FW

    CENELEC (ATEX) CERTIFICATION DETAIL SIRA01ATEX1286X, SIRA01ATEX3287X

    CODE OF PROTECTION CATEGORY ATEX II 2 GD EEx d IIC & EEx e II,EQUIPMENT ZONE 1, ZONE 2, ZONE 21, &ZONE 22 - GAS GROUPS IIA, IIB, IIC

    COMPLIANCE STANDARDS EN50014, EN50018, EN50019, EN50281-1-1

    CONTINUOUS OPERATING TEMP. RANGE -60°C TO +130°C

    INGRESS PROTECTION IP66

    GLAND MATERIAL BRASS

    SEAL MATERIAL CMP SOLO LSF

    CABLE TYPE STEE