STANDARDS AND APPROVALS

Page 3: Catalog Darka FRC 2015

Fire Performance Cables 9

IEC 60332 Part 3 - Flame Propagation Test

D C B A yrogetaC

No. of litres of combustible material in a 1 metre sample. 7 3.5 1.5 0.5

Exposure (mins) 40 40 20 20

The cable samples are placed vertically next to one another on a

for the pre-arranged times.

After burning, the samples are wiped clean to examine for char (the crumbling) of the cable surface. The charring should not have reached a height exceeding 2.5m above the bottom edge of the burner.

MAX-FOH cables meet the requirement of IEC 60332 part 3

IEC 60754 – Acid Gas Emission Test

IEC 60331 – Fire Test

Due to the concern regarding the amount of acid gas which could be produced when cables are burnt, this international test was developed to determine the amount of gas evolved by burning cables.

The recommended values of the test state that the weighted pH value should not be less than 4.3, when related to 1 litre of water. The weighted valued of conductivity should not exceed 10us/mm.

MAX-FOH cables meet the above requirements.

The international fire test is designed to establish whether a cable can maintain circuit integrity during and after exposure to fire.

A sample of cable is exposed to fire for 90 minutes at a temperature of between 750°C and 800°C, after 90 minutes the fire is extinguished and the current is turned off. After a further 12 hours, the sample of cable is re-energized and must maintain its circuit integrity.

MAX-FOH cables meet the requirements of IEC 60331

Additional Considerations

As well as requirements written into international and British cable standards, there are other essentialcriteria which designers and consultants need to consider – is the cable able to withstand voltage spikes, transmit date and prevent flame propagation?

All MAX-FOH cables do comply with these additional benefits, including the added advantage thatMAX-FOH requires fewer joints in a cable run compare to mineral, reducing the risk of weak links in thechain. MAX-FOH does not require complicated terminations and is therefore quicker and easier to install.

This test defines the ability of bunched cables to restrict vertical flame propagation when laid in trunking, cable trays or conduit. The test comprises of 3 categories each determined by the amount of combustible material in a 1 metre sample, as shown in the table below.

Page 4: Catalog Darka FRC 2015

Fire Performance Cables10

Identification of coresNo. of cores

1

2

3

4

5

6 and above

2 noitpO1 noitpO

tseuqer no ruoloc rehtOlarutaN

Red, BlackBrown, Blue

Red, Yellow BlueBrown, Black, Grey

Red, Yellow, Blue, Black Brown, Black, Grey, Blue

Red, Yellow, Blue, Black, Green/Yellow Brown, Black, Grey, Blue, Green/Yellow

Black with white numbering

Note: Special construction and design to customers’ specification can be upon request.

CONSTRUCTION OF CABLE

Construction MAX-FOH500 Multi-Cores

MAX-FOH-OSCR500V Twisted pair

MAX-FOH0.6/1KV

MAX-FOH-I0.6/1KV

MAX-FOH-1250.6/1KV

1 - Conductor Strandedanealed copper

Strandedannealed copper

Stranded annealedcopper

Strandedanneald copper

Strandedannealed copper

2 - Fire Barrier Mica tape Mica tape Mica tape Mica tape Mica tape

3 - Insulation Cross-linkedpolyethylene(XLPE)

Cross-linkedpolyethylene(XLPE)

Cross-linkedpolyethylene(XLPE)

Cross-linkedEVA**(XLEVA)‹Orange›

Cross-linkedEVA **(XLEVA)

4 - Shield* Optional* Aluminium foilwith tinned copperdrain wire

Aluminium foilwith tinned copper drain wire

- Aluminium foilwith tinned copperdrain wire

5 - Filler* /6+)�¿OOHU�RUpolypropylene split yam

/6+)�¿OOHU�RUpolypropylene split yam

/6+)�¿OOHU�RUpolypropylene splityam

- /6+)�¿OOHU�RUpolypropylene split yam

6 - Binder Tape* Polyester tape Polyester tape Polyester tape - Polyester tape

7 - Bedding* Low smokehalogen free(LSHF) compound(Black)

Low smokehalogen free(LSHF) compound(Black)

Low smokehalogen free(LSHF) compound(Black)

- Low smokehalogen free(LSHF) compound(Black)

8 - Amour*/# Galvanised steelwire (aluminiumor copper wire forsingle core)

Galvanised steelwire (aluminiumor copper wire forsingle core)

Galvanised steelwire (aluminium)or copper wire forsingle core)

- Galvanised steelwire (aluminiumor copper wire forsingle core)

9 - Sheath Low Smokehalogen free(LSHF) compound(Orange)

Low Smokehalogen free(LSHF) compound(Orange)

Low smokehalogen free(LSHF) compound(Orange)

- Low Smokehalogen free(LSHF) compound(Orange)

* Optional: Depending on requirement# Braided armour alaso available on request** XLEVA (Cross-linked Ethylene Vinyl Acetate) material used are suitable for operating temperature of 110ŃC up to 125ŃC- XLPE (Cross-linked Polyethylene) material used for operating temperature of 90ŃC

1

2

3

9

1235679

123

456789

FOUR PAIR

FOUR CORE

SINGLE CORE

Page 5: Catalog Darka FRC 2015

Fire Performance Cables 11

Applicable Standards

* Standards applied will vary depending on cable construction.

Comparision between test standards IEC 60331 Part 21 & SS 299 Part 1

Ref Description of tests IEC 60331Part 21

0.6/1kVcables

Datacables

Opticalfibre

cables

SS 299 Part 1 0.6/1kV cables

Datacables

Opticalfibre

cables

1 Resistance to FIRE alone

Flame temperature / Duration 750oC/90 min

Cat A- 650 OC/3hrCat B- 750 OC/3hrCat C- 950 OC/3hrCat S - 650OC/20min

2 Resistance to FIRE with mechanical shock

Flame temperature / Duration

Mechanical shock

830oC/120 min

Every 5 min

Cat X- 650 OC/3hrCat Y - 750OC/3hrCat Z- 950 OC/3hr

Every 30 sec

3 Res istance to FIRE with water spray

056 -W taCelbaliava toNnoitaruD / erutarepmet emalF OC/15min

4 Other tests

Electrical requirements for completed cablesBending characteristicsRe sistance of cable to impact

Not availableNot availableNot available

AvailableAvailableAvailable

IEC 60502-1AS/NZS 3198

IEC 60228BS 6360AS/NZS 1125

IEC 60754-1BS 6425-2AS/NZS 1160.5

IEC 60754-2BS 6426-2AS/NZS 1160.5.4

IEC 60331AS/NZS 1160.5.5

IEC 60332 Part 1BS 4066 Part 1

IEC 60332 Part 3BS 4066 Part 3 Category A,B,C/AS/NZS 1660.5.1

IEC 61034BS 7622AS/NZS 1660.5.2

BS 6387SS 299 Part 1

BS 6724

BS 7211

BS 7846

AS/NZS 3013

Extruded solid dielectric insulated power cable for rated voltage of 1 kV up to 30kV

Conductors of insulated cables

Test on gases evolved during combustion of electric cables –Detemination of the amount of halogen acid gases

Test on gases evolved during combustion of electric cables –Detemination of degree of acidity of gases evolved by measuring pH and conductivity

Fire resistant characteristics of electric cable (750°C for 90 minutes)

Test on electric cables under fire conditions – Test on a single vertical insulated wire or cable

Test on electric cables under fire conditions – Test on bunched wires or cables

Measurement of smoke density of electric cables burning under defined conditions

Performance requirements for cables required to maintain circuit integrity under fire condition –Category C : tested at 950°C for 3 hoursCategory W: fire with waterCategory Z : fire with mechanical shock

Armoured cables for electricity supply having thermosetting insulation with low emission of smokeand corrosive gases when affected by fire

Thermosetting insulated cables (non-armoured) for electric power and lighting with low emission ofsmoke and corrosive gases when affected by fire

600/1000V armoured fire-resistant electric cables having low emission of smoke and corrosivegases when affected by fire

Electrical installations – Classification of the fire and mechanical performance of wiring systems

Page 6: Catalog Darka FRC 2015

Fire Performance Cables12

MAX-FOHInsulated and sheathed500Vac. Unarmoured andArmoured

MAX-FOH (OSCR)Insulated and sheathed500Vac. Unarmoured andArmoured with Shield