Continuity of supply
Discrimination guarantees co-ordination between the operating characteristics of serial-connected circuit-breakers. Should a fault occurs downstream, only the circuit-breakerplaced immediately upstream from the fault will trip.
SM6Medium voltage switchboardsystem from 1 to 36 kV
SepamProtection relays
MasterpactProtection switchgear from 100 to 6300 A
The guide Design offi ce, consultant, contractor, panelbuilder, teacher, trainer, The Guide, according to IEC 60364, is the essential tool to “guide” you at any time to comprehensive and concrete information on the new technical solutions, the components of an installation,the IEC standards modifi cations, the fundamental electrotechnical knowledge, the design stages, from medium to low voltage.
The technical guides The electrical installation guide, the switchboard implementation guide, the technical publications or “Cahiers Techniques” and coordination tables all form genuine reference tools for the design of high-performance electrical installations.These guides help you to comply to installation rules and standards.
A consistent design of offers from Medium Voltage to Low Voltage
Guiding tools for more effi cient design and implementation of your installations
Type tested switchboardsby simple assembly
Knowledge at all times of installation status
Direct connection of the Canalis KT busbartrunking on theMasterpact 3200 Acircuit-breaker
Thanks to the use of standard Web technologies,you can offer your customers intelligent Merlin Gerin switchboards allowing easy access to information: follow-up of currents, voltages, powers, consumption history, etc.
CompactProtection switchgear system from 100 to 630 A
Multi 9Modular protection switchgear system up to 125 A
Prisma plusFunctional system for electrical distribution switchboards up to 3200 A
CAD software and tools The CAD software and tools enhanceproductivity and safety.They help you create your installationsby simplifying product choice while alsocomplying with standards and proper procedures.
TrainingTraining allows you to acquire theMerlin Gerin expertise (installation design,work with power on, etc.) for increasedeffi ciency and a guarantee of improvedcustomer service.
These technical guides help you comply with installation standardsand rules i.e.:the electrical installation guide, the protection guide, the switchboard implementation guide,the technical booklets and the co-ordination tables all form genuine reference tools for the design of high performance electrical installations.For example, the LV protection co-ordination guide - discrimination and cascading - optimises choice of protection and connection devices while also increasing markedly continuity of supply in the installations.
This international site allows you to access all the Merlin Gerin products in just 2 clicks via comprehensive range data-sheets, with direct links to:
complete library: technical documents, catalogs, FAQs, brochures…
selection guides from the e-catalog.
product discovery sites and their Flash animations.
You will also fi nd illustrated overviews, news to which you can subscribe, the list of country contacts…
b
b
b
1
LBSkitup to 36 kV
Contents
The experience of a world leader 2The product’s advantages 3Technical characteristics 4Dimensions and weights 5Safety of people 6By switchgear 6By operating mechanism safety 7
Operating mechanisms 8Auxiliaries 9Interlocks 10Installation Guides 11Selection Guides for 24 kV 12Order form for 24 kV 15Selection Guides for 36 kV 20Order form for 36 kV 23
2
LBSkitup to 36 kV
The experience of a world leader
The Schneider Electric group’s experience extends over 30 years in SF6 technology for Medium Voltage products.
This gives you the advantage of unique experience, that of a world leader, with over 1,600,000 SF6 Medium Voltage units installed throughout the world.
Putting this experience at your service and remaining attentive to your requirements is the spirit of active partnership that we want to develop in offering you the LBSkit.
LBSkit is a product to let you develop harmonized functions equipped with SF6 breaking technology switchgear. These functions allow you to produce all your Medium Voltage substation requirements up to 36 kV.The result of in-depth analysis of your requirements, both now and in the future, LBSkit means that you can take advantage of all the features of both a modern and proven technology.
PE
5635
0
3
LBSkitup to 36 kV
The product’s advantages
UpgradabilityLBSkit, a comprehensive product
A comprehensive product covering your present and future requirementsA design adapted to the extension of your unitsA catalogue of components for all your applicationsA product designed to be in compliance with standards constraintsOptions to anticipate the telecontrol of your units.
CompactnessLBSkit, an optimised product
Compact components, for reduced increment unitsRationalised space requirement for switchboard installation.
MaintenanceLBSkit, a product with reduced maintenance
The active parts (breaking and earthing) are integrated in an SF6-fi lled, “sealed for life” unit
The control mechanisms, are intented to function with reduced maintenance under normal operating conditions
Enhanced electrical endurance when breaking.
Ease of installationLBSkit, a simple product to incorporate
Reduced dimensions and weightsA solution adapted to cable connectionSimplifi ed switchboard busbar connection.
Easy and safe to operateLBSkit, a well-proven product
A three position switch to prevent incorrect operatingThe earthing disconnector has full closing capacityPositive breaking of position indicatorsClear and animated display mimicsSwitching lever with an “anti-refl ex” function.
LBSkit: a product designed with telecontrol in mindLBSkit is perfectly adapted to telecontrol applications. Motorised, option available, LBSkit combines with remote control interface. You, therefore, benefi t from a ready-to connect unit that is easy to incorporate providing guaranteed operation.
LBSkit: a product with adapted fuse-switch protectionWith the LBSkit, Schneider Electric proposes components for MV protections with fuses. Fusarc CF fuse range is an excellent solution to protect various types devices such as MV transformers, motors, capacitors, public and industrial distribution networks.
bbbbb
bb
b
b
b
bbb
bbbbb
6100
3N
4
LBSkitup to 36 kV
Technical characteristics
General characteristicsRated voltage (kV) 7.2 12 17.5 24 36Insulation level *
50 Hz - 1 min(kV r ms)
Insulation 20 28 38 50 70Isolation 23 32 45 60 80
1.2/50 µs(kV peak)
Insulation 60 75 95 125 170Isolation 70 85 110 145 195
Short-time withstand current Switch (kA/1 s) 25 630 A
20 630 A16 630 A12.5 630 A
Disconnector (kA/1 s) 25 630 - 1250 A 1250 A20 630 - 1250 A16 630 - 1250 A12.5 630 - 1250 A
Maximum breaking capacityTransformer off load (A) 16Cables off load (A) 31.5 50 Switch (A) 630 Fuse-switch ** (kA) 25 20
The making capacity is equal to 2.5 times the short-time withstand current.(*) Equipped referring to installation guide, and setting up at an altitude below 1000 m. (**) Depending on fuse characteristics, and on using of Merlin Gerin Fusarc CF fuses.
EnduranceUnits Mechanical
enduranceElectrical endurance
SwitchFuse-switch
IEC 602651000 operationsClass M1
IEC 60265100 breaks at In, p.f. = 0.7Class E3
Disconnector IEC 62271-1021000 operations
TemperaturesThe products must be stored in a dry area free from dust and with limited temperature variations
b for stocking: from –40°C to +70°Cb for working: from –5°C to +40°Cb other temperatures, consult us
StandardsLBSkit units meet all the following recommendations:
Switch: IEC 60265: High voltage switches for rated voltages of 52 kV and above.
Disconnector: IEC 62271-102: High-voltage alternating current disconnectors and earthing switches.
Switch /disconnector: IEC 62271-200: A.C. metal-enclosed switchgear and controlgear for rated voltage above 1 kV and up to including 52 kV.
b
b
b
In addition to its technical characteristics, LBSkit is designed for indoor applications, and meets requirements concerning human safety as well as ease of installation, operation and protection of the environment.
PE
5635
4
Switch and earthing switch 24 kV
PE
5635
6
Switch and earthing switch 36 kV
5
LBSkitup to 36 kV
Dimensions and weights
LBSkit 24 kV630 A switch - 630 A disconnector Weight: 50 kg
Below view Side view Front view
DE
5715
1
72D
E57
151
202
940
840
365
350220 200 200
417,
5
213
190
1250 A disconnector Weight: 51 kg
Below view Side view Front view
DE
5715
1
72
DE
5715
1
191
940 365
350220 200 200
417,
5
213
190
840
LBSkit 36 kV630 A switch - 630 A disconnector Weight: 75 kg
Below view Side view Front view
DE
5715
5
DE
5715
6
1340 720
700
290
307.6
136
207 395.5
350.895 350 350
1250 A disconnector Weight: 76 kg
Below view Side view Front view
DE
5715
7
DE
5715
8 1340 720700
279
307.
6
136
207 39
5.5
350.895 350 350
6
LBSkitup to 36 kV
Safety of peopleBy switchgear
Switch or disconnector and earthing switchb Gas tightnessThe three rotating contacts are placed in an enclosure fi lled with gas to a relative pressure of 0.4 bar (400 hPa) for LBSkit 24 kV and 1.5 bar (1500 hPa) for LBSkit 36 kV. It satisfi es “sealed pressure system” requirements and seal tightness is always factory checked.
b Operating safetythe switch may be in one of three positions: “closed”, “open”, or “earthed”,
representing a natural interlocking system that prevents incorrect operation.Moving-contact rotation is driven by a fast-acting mechanism that is independent of the action of the operator.
the device combines the breaking and disconnection functions.the earthing switch placed in the SF6 has a short-circuit making capacity,
in compliance with standards.any accidental over-pressures are eliminated by the opening of the safety
membrane, in which case the gas is directed toward the back of the unit, away from the operator.
v
vv
v
MT2
0184
Closed position Open position Earth position
6102
9N
LBSkit 24 kV
PE
5635
7
LBSkit 36 kV
7
LBSkitup to 36 kV
Safety of peopleBy operating mechanism safety
Reliable operating mechanismb Switchgear status indicator: Fitted directly to the drive shaft, these give a defi nite indication of the contact’s position. (appendix A of standard IEC 62271-102).b Operating lever: This is designed with an anti-refl ex device that stops any attempt to re-open the device immediately after closing the switch or the earthing disconnector.b Locking device: Between one and three padlocks enable the following to be locked:v access to the switching shaft of the switch or the circuit breakerv access to the switching shaft of the earthing disconnectorv operating of the opening release push-button.
Simple and effortless switchingMechanical and electrical controls are side by side on the front fascia, on a panel including the schematic diagram indicating the device’s status (closed, open, earthed):b Closed: the drive shaft is operated via a quick acting mechanism, independent of the operator. No energy is stored in the switch, apart from when switching operations are taking place.For combined switch fuses, the opening mechanism is armed at the same time as the contacts are closed.b Opening: the switch is opened using the same quick acting mechanism, operated in the opposite direction.For a combined switch fuses unit, opening is controlled by: v a push-buttonv a fault.b Earthing: a specifi c control shaft enables the opening or closing of the earthing contacts. Access to this shaft is blocked by a cover that can be slid back if the switch is open but which remains locked in place if it is closed.
Voltage presence indicatorThis device has integrated VPIS (Voltage Presence Indicating System) type lights, in conformity with IEC standard 61958, enabling the presence (or absence) of voltage to be checked on the cables.
Insensitivity to the environmentb An internal sealed enclosure, contains the active parts of the LBSkit (switch, earthing disconnector). It is fi lled with SF6 in accordance with the defi nitions in IEC recommendation 62271-200 for “sealed pressure systems”. Sealing is systematically checked in the factory. b Parts are designed in order to obtain optimum electrical fi eld distribution.
PE
5635
1
Cover for LBSkit 24 kV
DE
5691
1
8
LBSkitup to 36 kV
Operating mechanisms
Double-function operating mechanism CITb Switch function Independent-operation opening or closing by lever or motor.b Earthing-switch function Independent-operation opening or closing by lever.Operating energy is provided by a compressed spring which, when released, causes the contacts to open or close.b Auxiliary contactsv switch (2 O + 2 C) *v switch (2 O + 3 C) and earthing switch (1 O + 1 C).b Motor option
Double-function operating mechanism CI1b Switch function v independent-operation closing by lever.Operating energy is provided by a compressed spring which, when released, causes the contacts to close.v independent-operation opening by push-button (O) or trip units.b Earthing-switch function Independent-operation closing and opening by lever.Operating energy is provided by a compressed spring which, when released, causes the contacts to open or close.b Auxiliary contactsv switch (2 O + 2 C) v switch (2 O + 3 C) and earthing switch (1 O + 1 C).b Opening releasesv shunt trip.
Double-function operating mechanism CI2b Switch function v independent-operation closing in two steps:1 - operating mechanism recharging by lever or motor2 - stored energy released by push-button (I) or trip unit.v independent-operation opening by push-button (O) or trip unit.b Earthing-switch functionIndependent-operation closing and opening by lever.Operating energy is provided by a compressed spring which, when released, causes the contacts to open or close.b Auxiliary contactsv switch (2 O + 2 C) * v switch (2 O + 3 C) and earthing switch (1 O + 1 C).b Opening release shunt tripb Closing release shunt tripb Motor option
Double-function operating mechanism CS1b Switch and earth switch functionsDependent-operation opening and closing by lever.b Auxiliary contactsv disconnector (2 O + 2 C).
Example of functions Type of operating mechanism assembled with the switch
Load break switch CIT CI2Disconnector CS1Fuse switch combination CI2
(*) Included with the motor option.
6102
9N61
030N
6103
1N61
032N
9
LBSkitup to 36 kV
Auxiliaries
Motor option and releases for switch-unitsThe operating mechanisms CIT and CI2 may be motorised.
Un DC AC (50/60 Hz)Power supply (V) 24 48 110 220Motor option
(W) 200(VA) 200
Operating time for CIT (s) 1 to 2 1 to 2and charging time for CI2 (s) 4 to 7 4 to 7Opening releases
Shunt trip (W) 200 250 300(VA) 750
Response time (ms) 35 35Closing release
Shunt trip (W) 200 250 300(VA) 750
Response time (ms) 55 55
Example of applications for main line switching
Types of operating mechanismWithout motor With motor
Manual operation With lever CITWith push button CI2Remote control
For network management without need of quick opening and closing
CIT
For network management for quick switching (generator, loop) or transformer protection
CI2
6103
6N
10
LBSkitup to 36 kV
Interlocks
Functional interlocksThese comply with IEC recommendation 62271-200.In addition to the functional interlocks, each disconnector and switch include built-in padlocking capacities (padlocks not supplied).
Switch/disconnector built-in interlocksb The switch can be closed only if the earthing switch is open and the access panel is in closed position.b The earthing switch can be closed only if the switch is open.b The access panel for connections can be opened only if the earthing switch is closed.b The switch is locked in the open position when the access panel is removed. The earthing switch may be operated for tests.
Key-type interlocks
Type C4: transformer protection
DE
5590
4
S
SO
O
Aimb To prevent the closing of the earthing switch on a transformer protection unit unless the LV circuit breaker is locked in “open” or “disconnected” position.b To prevent the access to the transformer if the earthing switch for transformerprotection has not fi rst been closed.
Type P1: ring units
DE
5590
9
X
O
O
X
Aimb To prevent the closing of an earthing switch if the switch of the other unit has not been locked in the “open” position.
Type A3: ring units
DE
5590
5
O
O
Aimb To prevent the closing of the earthing switch of a load-side cubicle unless the line-side switch is locked “open”.
Legend for key-type interlocks:no key free key captive key panel or door
11
LBSkitup to 36 kV
Installation Guides
The Installation Guides have been written for “Panel Builders” who have to design, realize, inspect and maintain own functions with LBSkit in compliance with international standards of the International Electrotechnical Commission (IEC).
The Installation Guides are single documents covering the assembly of LBSkit and related components and recommendations. They are intended for Panel Builders who want to develop their own functions, then a range using LBSkit.
An international standard such as the IEC 62271-200 “A.C. metal-enclosed switchgear and controlgear for rated voltage above 1 kV and up to including 52 kV” specifi es extensively the rules to comply with to ensure safety and predicted operational characteristics for all types of electrical applications. As the standard must be extensive and has to be applicable to all types of products and technical solutions in use worldwide, the text of the IEC rules is complex, and not presented in a ready-to-use order. The standard can not therefore be considered as a working handbook, but only as a reference document.
Electrical equipment should be designed, realized and used only by qualifi ed persons, and “Installation Guides” should not be viewed as suffi cient instructions for those who are not qualifi ed to design, realize, use or maintain the components discussed. Although reasonable care has been taken to provide accurate and authoritative information in these documents, no reponsibility is assumed by Schneider Electric for any consequences arising from the use of that material.
PE
5635
2 - P
E56
353
Operating mechanism
Assembled switch and operating mechanismwithout motor (basic offer)Assembled switch and operating mechanismwith motor (basic offer)Auxiliary voltage: 24 VDC
48 VDC
110 VDC
220 VAC
Coil kitsCoil type:
Auxiliary voltage: 24 VDC
48 VDC
110 VDC-220 VAC
Operating mechanism cover
Auxiliary contacts: 4 AC : 2O-2C switch
7 AC : 2O-3C switch+ 1O-1C earthing switch
Operating mechanism handle
Upper fi eld distributors (3 pieces per unit)
Connection for one cable (3 pieces per unit)
Capacitive divider (3 pieces per unit)
Voltage presence indicator Service voltage: 3 to 7.2 kV
10 to 24 kVVoltage presence indicator wiring
Busbar fi eld distributor (3 pieces per unit)
Interlocking and lock kitsLock type: Interlocking type: A3
P1
(*) See drawing in Installation Guide
12
CIT CI1 CI2
3730109AU
3730109AV
3730109AW
3730109AX
3730109AC
Without Openingrelease
3730304B+ 3730333A
3730304B+ 3730335A
3730304B+ 3730332A
51238920FA(4 pieces)
3730109AB
3730109AY
3730109AZ
3730109BA
3730109BB
3730109AD
Without
3730300B
3730300B+ 3730301B
51238920FA(4 pieces)
Included in motorized
switch
51238920FB(4 pieces)
3730300B
3730300B+ 3730301B
51238920FB(4 pieces)
3730307B
3730307B+ 3730308B
51238920FE(4 pieces)
3730300B
3730300B+ 3730301B
51238920FE(4 pieces)
Metal cover manufactured by customer *
3730307B
3730307B+ 3730308B
51238920FE(4 pieces)
3728693
LBSkit 24 kV Selection GuideSwitch unit 1 to 24 kV, 630 A
Opening/closingrelease
(included in motorized
switch)
Opening/closingrelease
3730305B+ 3730338A
3730305B+ 3730340A
3730305B+ 3730337A
Without
3736435
51238497FA (24 pieces)
51238495FA (12 pieces)
51193386F051193388F0
3736842
3729742 (3 pieces)
3730352B + 37314403730351B + 3731440
Profalux Ronis
3730352B + 37316403730351B + 3731640
Included in motorized
switch
Metal cover manufactured by customer *
Metal cover manufactured by customer *
Metal cover manufactured by customer *
Metal cover manufactured by customer *
Metal cover manufactured by customer *
Metal cover manufactured by customer *
Without
Operating mechanism
Assembled switch and operating mechanismwithout motor (basic offer)Assembled switch and operating mechanismwith motor (basic offer)Auxiliary voltage: 24 VDC
48 VDC
110 VDC
220 VAC
Coil kitsCoil type:
Auxiliary voltage: 24 VDC
48 VDC
110 VDC-220 VAC
Operating mechanism cover
Auxiliary contacts: 4 AC : 2O-2C switch
7 AC : 2O-3C switch+ 1O-1C earthing switch
Operating mechanism handle
Earthing switch 2 kA
DIN fuse holder and fi eld distributor (3 pieces per unit)
Capacitive divider (3 pieces per unit)
Fuse trip system
Voltage presence indicator Service voltage: 3 to 7.2 kV
10 to 24 kVVoltage presence indicator wiring
Busbar fi eld distributor (3 pieces per unit)
Interlocking and lock kitsLock type:
Interlocking type: A3
P1
C4
(*) See drawing in Installation Guide
13
LBSkit 24 kV Selection GuideFuse-switch unit 1 to 24 kV, 630 A
CI1 CI2
3730109AC
Without Opening release
3730304B+ 3730333A
3730304B+ 3730335A
3730304B+ 3730332A
3730109AY
3730109AZ
3730109BA
3730109BB
3730109AD
51238920FC(4 pieces)
3730300B
3730300B+ 3730301B
51238920FC(4 pieces)
3730306B
3730306B+ 3730308B
51238920FF(4 pieces)
3730300B
3730300B+ 3730301B
51238920FF(4 pieces)
Metal cover manufactured by customer *
3730306B
3730306B+ 3730308B
51238920FF(4 pieces)
3728693
Opening/closing release(included in motorized
switch)
Opening/closing release
3730305B+ 3730338A
3730305B+ 3730340A
3730305B+ 3730337A
Without
Included in earthing switch kit (3 pieces)
51238922FA
51238495FA (12 pieces)
51193386F051193388F0
3736842
3729742 (3 pieces)
3730352B + 3731440
3730351B+ 3731440
Profalux Ronis
3730352B + 3731640
3730351B + 3731640
Included in motorized
switch
Metal cover manufactured by customer *
Metal cover manufactured by customer *
Metal cover manufactured by customer *
Metal cover manufactured by customer *
51238498FA (18 pieces)
Included in earthing switch kit (3 pieces)
51238921FA51238921FA
3730350B + 3731438+ 3731439
3730350B + 3731638+ 3731639
(*) See drawing in Installation Guide
Operating mechanism
Assembled switch and operating mechanism (basic offer)Rated normal current: 630 A
1250 A
Operating mechanism cover
Auxiliary contacts: 4 AC : 2O-2C switch
Operating mechanism handle
Upper fi eld distributors (3 pieces per unit)
Connection for one cable (3 pieces per unit)
Capacitive divider (3 pieces per unit)
Voltage presence indicator Service voltage: 3 to 7.2 kV
10 to 24 kVVoltage presence indicator wiring
Busbar fi eld distributor (3 pieces per unit)
14
LBSkit 24 kV Selection GuideDisconnector unit 1 to 24 kV
CS1
3730109AE
51238920FD (4 pieces)
3730300B
Metal cover manufactured by
customer *
3730109AF
3728693
3736435
51238497FA (24 pieces)
51238495FA (12 pieces)
51193386F051193388F0
3736842
3729742 (3 pieces)
15
LBSkit 24 kV Order formComponents
Number of pieces by reference
Reference Quantity minimum to order
Quantity (1)
Switches (basic offer)
DE
5656
1 Load-break switch 630 A With CIT mechanism 1 3730109AB 1With CI1 mechanism 1 3730109AC 1With CI2 mechanism 1 3730109AD 1
Motorized switches (basic offer)
DE
5656
3 Motorized switch CIT 24 VDC+4AC 1 3730109AU 148 VDC+4AC 1 3730109AV 1110 VDC+4AC 1 3730109AW 1220 V 50 Hz+4AC 1 3730109AX 1
Motorized switch CI2 24 VDC+4AC+O/C coils 1 3730109AY 148 VDC+4AC+O/C coils 1 3730109AZ 1110 VDC+4AC+O/C coils 1 3730109BA 1220 V 50 Hz+4AC+O/C coils 1 3730109BB 1
Disconnectors (basic offer)
DE
5656
2 Disconnector 630 A With CS1 mechanism 1 3730109AE 1Disconnector 1250 A With CS1 mechanism 1 3730109AF 1
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.
16
LBSkit 24 kV Order formComponents (continued)
Number of pieces by reference
Reference Quantity minimum to order
Quantity (1)
Auxiliary contactFor switch without motor
DE
5656
4 For CIT, CI1, CI2 4:2O-2C/Switch 1 3730300B 17:2O-3C/Switch + 1O-1C/Earth. sw. 1 + 1 3730300B + 3730301B 1 + 1
For CI1, CI2 with coil
4:2O-2C/Switch 1 3730307B 17:2O-3C/Switch + 1O-1C/Earth. sw. 1 + 1 3730307B + 3730308B 1 + 1
For fuse-switch without motor
DE
5656
4 For CI1, CI2 4:2O-2C/Switch 1 3730300B 17:2O-3C/Switch + 1O-1C/Earth. sw. 1 + 1 3730300B + 3730301B 1 + 1
For CI1, CI2 with coil
4:2O-2C/Switch 1 3730306B 17:2O-3C/Switch + 1O-1C/Earth. sw. 1 + 1 3730306B + 3730308B 1 + 1
For disconnector
DE
5656
4 For CS1 4:2O-2C/Switch 1 3730300B 1
CoilFor switch or fuse-switch without motor
DE
5656
5 Coil for CI1 24 VDC 1 + 1 3730304B + 3730332A 1 + 148 VDC 1 + 1 3730304B + 3730333A 1 + 1110 VDC 1 + 1 3730304B + 3730335A 1 + 1220 V 50 Hz 1 + 1 3730304B + 3730335A 1 + 1
Coils for CI2 24 VDC 1 + 1 3730305B + 3730337A 1 + 148 VDC 1 + 1 3730305B + 3730338A 1 + 1110 VDC 1 + 1 3730305B + 3730340A 1 + 1220 V 50 Hz 1 + 1 3730305B + 3730340A 1 + 1
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.
17
LBSkit 24 kV Order formComponents (continued)
Number of pieces by reference
Reference Quantity minimum to order
Quantity (1)
Accessories
DE
5656
6 Handle Operating handle 1 3728693 20 *
DE
5656
7 Earthing switch Earthing switch (25 kA) 1 3932567 1
DE
5656
8
DE
5657
0
Fig. 1
Fig. 2
Fig. 3
Field distributor Busbar fi eld distributor (fi g. 1) 3 3729742 10Upper fi eld distributor (fi g. 2) 24 51238497FA 1
Field distributor/fuse holder For DIN fuses (fi g. 3) 18 51238498FA 1
DE
5656
9
DE
5657
7 Cable connection for fi eld repartitor
Connection for one cable 1 3736435 50 *
DE
5657
1 Voltage presence indicator VPIS 10-24 kV 1 51193388F0 20 *VPIS 3-7.2 kV 1 51193386F0 20 *
DE
5657
2 Voltage presence wiring VPIS wiring 1 3736842 60 *
DE
5657
3 Capacitive divider/Insulator 12 51238495FA 1Post insulator 12 51238496FA 1
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.(*) Piece!
18
LBSkit 24 kV Order formComponents (continued)
Number of pieces by reference
Reference Quantity minimum to order
Quantity (1)
Accessories
DE
5657
5 Earthing switch 2 kA for fuse-switch CI1 and CI2(no need to order 51238498FA)
1 51238922FA 1
DE
5657
4 Fuse trip system for fuse-switch 1 51238921FA 1
DE
5657
6 Mechanism cover (complete with mimic diagram and shutters)
Switch unit with CIT 4 51238920FA 1Switch unit with CI1 4 51238920FB 1Fuse-switch unit with CI1 4 51238920FC 1Disconnector unit with CS1 4 51238920FD 1Switch unit with CI2 4 51238920FE 1Fuse-switch unit with CI2 4 51238920FF 1
DE
5657
8
Profalux
Ronis
Interlockings A3 Profalux 1 + 1 3730351B + 3731440 1 + 1A3 Ronis 1 + 1 3730351B + 3731640 1 + 10 *P1 Profalux 1 + 1 3730352B + 3731440 1 + 1P1 Ronis 1 + 1 3730352B + 3731640 1 + 10 *C4 Profalux 1 + 1 + 1 3730350B + 3731438
+ 37314391 + 5 * + 5 *
C4 Ronis 1 + 1 + 1 3730350B + 3731638 + 3731639
1 + 3 * + 3 *
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.(*) Piece!
Operating mechanism
Assembled switch and operating mechanismwithout motor (basic offer)Assembled switch and operating mechanismwith motor (basic offer)Auxiliary voltage: 24 VDC
48 VDC
110 VDC
220 VAC
Coil kitsCoil type:
Auxiliary voltage: 24 VDC
48 VDC
110 VDC-220 VAC
Operating mechanism cover
Auxiliary contacts: 4 AC : 2O-2C switch
7 AC : 2O-3C switch+ 1O-1C earthing switch
Operating mechanism handle
Upper fi eld distributors (3 pieces per unit)
Connection for one cable (3 pieces per unit)
Capacitive divider (3 pieces per unit)
Voltage presence indicator Service voltage: 10 to 36 kV
Voltage presence indicator wiring
Busbar fi eld distributor (3 pieces per unit)
Interlocking and lock kitsLock type: Interlocking type: A3
P1
(*) See drawing in Installation Guide
3730300B+ 3730301B
20
CIT CI1 CI2
51000162S
51000162T
51000162U
51000162V
51000162M
Without Openingrelease
3730304B+ 3730333A
3730304B+ 3730335A
3730304B+ 3730332A
51000162A
51000162W
51000162X
51000162Y
51000162Z
51000162C
Without
3730300B
3730300B+ 3730301B
Included in motorized
switch3730300B 3730307B
3730307B+ 3730308B
3730300B
3730300B+ 3730301B
Metal cover manufactured by customer *
3730307B
3730307B+ 3730308B
51000861
Opening/closingrelease
(included in motorized
switch)
Opening/closingrelease
3730305B+ 3730338A
3730305B+ 3730340A
3730305B+ 3730337A
Without
3736435
51238497FA (24 pieces)
51257952
59904
51257931
3727841
3730352B + 37314403730351B + 3731440
Profalux Ronis
3730352B + 37316403730351B + 3731640
Included in motorized
switch
Metal cover manufactured by customer *
Metal cover manufactured by customer *
Metal cover manufactured by customer *
Metal cover manufactured by customer *
Metal cover manufactured by customer *
Metal cover manufactured by customer *
Without
LBSkit 36 kV Selection GuideSwitch unit 36 kV, 630 A
Operating mechanism
Assembled switch and operating mechanismwithout motor (basic offer)Assembled switch and operating mechanismwith motor (basic offer)Auxiliary voltage: 24 VDC
48 VDC
110 VDC
220 VAC
Coil kitsCoil type:
Auxiliary voltage: 24 VDC
48 VDC
110 VDC-220 VAC
Operating mechanism cover
Auxiliary contacts: 4 AC : 2O-2C switch
7 AC : 2O-3C switch+ 1O-1C earthing switch
Operating mechanism handle
Earthing switch 2 kA
DIN fuse holder and fi eld distributor (3 pieces per unit)
Capacitive divider (3 pieces per unit)
Fuse trip system
Voltage presence indicator Service voltage: 10 to 36 kV
Voltage presence indicator wiring
Busbar fi eld distributor (3 pieces per unit)
Interlocking and lock kitsLock type:
Interlocking type: A3
P1
C4
(*) See drawing in Installation Guide
21
CI1 CI2
51000162M
Without Opening release
3730304B+ 3730333A
3730304B+ 3730335A
3730304B+ 3730332A
51000162W
51000162X
51000162Y
51000162Z
51000162C
3730300B
3730300B+ 3730301B
3730306B
3730306B+ 3730308B
3730300B
3730300B+ 3730301B
Metal cover manufactured by customer *
3730306B
3730306B+ 3730308B
51000861
Opening/closing release(included in motorized
switch)
Opening/closing release
3730305B+ 3730338A
3730305B+ 3730340A
3730305B+ 3730337A
Without
Included in earthing switch kit (3 pieces)
51257700B
51257952
51257931
3727841
3730352B + 3731440
3730351B+ 3731440
Profalux Ronis
3730352B + 3731640
3730351B + 3731640
Included in motorized
switch
Metal cover manufactured by customer *
Metal cover manufactured by customer *
Metal cover manufactured by customer *
Metal cover manufactured by customer *
51238498FA (18 pieces)
Included in earthing switch kit (3 pieces)
51254461A51254461A
3730350B + 3731438+ 3731439
3730350B + 3731638+ 3731639
59904
LBSkit 36 kV Selection GuideFuse-switch unit 36 kV, 630 A
Operating mechanism
Assembled switch and operating mechanism (basic offer)Rated normal current: 630 A
1250 A
Operating mechanism cover
Auxiliary contacts: 4 AC : 2O-2C switch
Operating mechanism handle
Upper fi eld distributors (3 pieces per unit)
Connection for one cable (3 pieces per unit)
Capacitive divider (3 pieces per unit)
Voltage presence indicator Service voltage: 10 to 36 kV
Voltage presence indicator wiring
Busbar fi eld distributor (3 pieces per unit)
(*) See drawing in Installation Guide
22
LBSkit 36 kV Selection GuideDisconnector unit 36 kV, 630-1250 A
CS1
51000162H
3730300B
Metal cover manufactured by
customer *
51000162AF
51000861
3736435
51238497FA (24 pieces)
51257952
51257931
3727841
59904
23
LBSkit 36 kV Order formComponents
Number of pieces by reference
Reference Quantity minimum to order
Quantity (1)
Switches (basic offer)
DE
5714
0 Load-break switch 630 A With CIT mechanism 1 51000162A 2 *With CI1 mechanism 1 51000162M 2 *With CI2 mechanism 1 51000162C 2 *
Motorized switches (basic offer)
DE
5714
1 Motorized switch CIT 24 VDC+4AC 1 51000162S 148 VDC+4AC 1 51000162T 1110 VDC+4AC 1 51000162U 1220 V 50 Hz+4AC 1 51000162V 1
Motorized switch CI2 24 VDC+4AC+O/C coils 1 51000162W 148 VDC+4AC+O/C coils 1 51000162X 1110 VDC+4AC+O/C coils 1 51000162Y 1220 V 50 Hz+4AC+O/C coils 1 51000162Z 1
Disconnectors (basic offer)
DE
5714
0 Disconnector 630 A With CS1 mechanism 1 51000162H 2 *Disconnector 1250 A With CS1 mechanism 1 51000162AF 2 *
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.(*) Piece!
24
LBSkit 36 kV Order formComponents (continued)
Number of pieces by reference
Reference Quantity minimum to order
Quantity (1)
Auxiliary contactFor switch without motor
DE
5656
4 For CIT, CI1, CI2 4:2O-2C/Switch 1 3730300B 17:2O-3C/Switch + 1O-1C/Earth. sw. 1 + 1 3730300B + 3730301B 1 + 1
For CI1, CI2 with coil
4:2O-2C/Switch 1 3730307B 17:2O-3C/Switch + 1O-1C/Earth. sw. 1 + 1 3730307B + 3730308B 1 + 1
For fuse-switch without motor
DE
5656
4 For CI1, CI2 4:2O-2C/Switch 1 3730300B 17:2O-3C/Switch + 1O-1C/Earth. sw. 1 + 1 3730300B + 3730301B 1 + 1
For CI1, CI2 with coil
4:2O-2C/Switch 1 3730306B 17:2O-3C/Switch + 1O-1C/Earth. sw. 1 + 1 3730306B + 3730308B 1 + 1
For disconnector
DE
5656
4 For CS1 4:2O-2C/Switch 1 3730300B 1
CoilFor switch or fuse-switch without motor
DE
5656
5 Coil for CI1 24 VDC 1 + 1 3730304B + 3730332A 1 + 148 VDC 1 + 1 3730304B + 3730333A 1 + 1110 VDC 1 + 1 3730304B + 3730335A 1 + 1220 V 50 Hz 1 + 1 3730304B + 3730335A 1 + 1
Coils for CI2 24 VDC 1 + 1 3730305B + 3730337A 1 + 148 VDC 1 + 1 3730305B + 3730338A 1 + 1110 VDC 1 + 1 3730305B + 3730340A 1 + 1220 V 50 Hz 1 + 1 3730305B + 3730340A 1 + 1
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.
25
LBSkit 36 kV Order formComponents (continued)
Number of pieces by reference
Reference Quantity minimum to order
Quantity (1)
Accessories
DE
5656
6 Handle Operating handle 1 51000861 5 *
DE
5714
4 Earthing switch Earthing switch (20 kA) 1 51254700A 1
DE
5714
5
DE
5657
0
Fig. 1
Fig. 2
Fig. 3
Field distributor Busbar fi eld distributor (fi g. 1) 1 3727841 60 *Upper fi eld distributor (fi g. 2) 24 51238497FA 1
Field distributor/fuse holder For DIN fuses (fi g. 3) 18 51238498FA 1
DE
5656
9
DE
5657
7 Cable connection for fi eld repartitor
Connection for one cable 1 3736435 50 *
DE
5657
1 Voltage presence indicator VPIS 10-40.5 kV 1 59904 1
DE
5657
2 Voltage presence wiring VPIS wiring 1 51257931 10 *
DE
5714
2 Capacitive divider/Insulator 1 51257952 30 *Post insulator 1 1946501 30 *
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.(*) Piece!
26
LBSkit 36 kV Order formComponents (continued)
Number of pieces by reference
Reference Quantity minimum to order
Quantity (1)
Accessories
DE
5714
3 Earthing switch 2 kA for fuse-switch CI1 and CI2(no need to order 51238498FA)
1 51254700B 1
DE
5657
4 Fuse trip system for fuse-switch (for 6 units) 1 51254461A 1
DE
5657
8
Profalux
Ronis
Interlockings A3 Profalux 1 + 1 3730351B + 3731440 1 + 1A3 Ronis 1 + 1 3730351B + 3731640 1 + 10 *P1 Profalux 1 + 1 3730352B + 3731440 1 + 1P1 Ronis 1 + 1 3730352B + 3731640 1 + 10 *C4 Profalux 1 + 1 + 1 3730350B + 3731438
+ 37314391 + 5 * + 5 *
C4 Ronis 1 + 1 + 1 3730350B + 3731638 + 3731639
1 + 3 * + 3 *
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.(*) Piece!
As standards, specifi cations and designs change from time to time, please ask for confi rmation of the information given in this publication.
Publishing: Schneider Electric Industries SASDesign: Schneider Electric Industries SASPrinting: Imprimerie du Pont de Claix/JPF - Made in France
This document has been printed on ecological paper
Schneider Electric Industries SAS89, boulevard Franklin RooseveltF-92506 Rueil-Malmaison CedexTel: +33 (0)1 41 29 85 00www.schneider-electric.comwww.merlin-gerin.com
AMTED306003EN 04-2007
AR
T.81
9791
© S
chne
ider
Ele
ctric
Indu
strie
s S
AS
- A
ll rig
hts
rese