CATALOGUE SURGE PROTECTION LOW VOLTAGE

CATALOGUE - Surgetek · 2014-08-12 · SALTEK, s.r.o. (limited liability company), is a Czech company specialising in the develop-ment and manufacture of surge protection devices

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

CATALOGUE

SURGE PROTECTIONLOW VOLTAGE

SALTEK, s.r.o. (limited liability company), is a Czech company specialising in the develop-ment and manufacture of surge protection devices (SPD). SALTEK offer a wide range of li-ghtning current arresters and surge arresters type 1 to 3, pursuant to EN 61643-11, as well as surge arresters for information technolo-gy, measurement and control, telecommuni-cations, also for the protection of photovol-taic applications.SALTEK has been in the business since 1995. Currently, the company has 2 centres in the Czech Republic.. Its headquarters, manage-ment, R+D, manufacturing premises, test lab and logistics are based in Ústí nad Labem. The Export subsidiary SALTEK TRADE and techni-cal support is situated in Prague.Our in-house product development is crucial for the dynamic growth and advancement of the company. The design office and laboratories are equipped with unique instruments and technologies. State-of-the-art materials, design procedures, technologies and measure-

ment methods are used for this development.Exceptional attention is paid to product quality. From the in-coming material and component testing, through multiple checks during manufacturing, up to robotised output control. Shortly after it was established, SALTEK introduced and then certified its management system in compliance with internati-onal standards. In 2005 the company introduced an integrated IMS management system, which consists of a quali-ty management system under ISO 9001, an envi-ronmental protection ma-nagement system under ISO 14001 and a health and safety management

system under OHSAS 18001. The IMS system is perio-dically reviewed by an external auditing company TÜV NORD Czech. In 2010, to handle the rapid growth of the company SALTEK adopted an information system SAP enabling smart control over all its processes.

SPD type 1 and 2 FLP-B+C MAXI VSPowerful combined lightning and surge arrestermodern technology – no follow current, no leakage current

T1 T2

SPD type 1 and 2 FLP-12,5 VEconomical lightning and surge arresters FLP-275 Vbased on MOV technology

T1 T2

SPD type 2 SLP-275 VVersatile standard product with excelent reliabilityVariety of voltages

T2

SPD type 2 SLP-275 VBEnhanced MOV-GDT combination reducing leakage currentwith prolonged MOV lifetime, T3 tested

T2

SPD type 3 DA-275 VTerminal protection for DIN rail DA-275 DJ

T3

SPD type 3 CZ-275 ATerminal protection

T3

SPD type 1 FLP-SG50 V SLightning current arresters based on spark-gap technology FLP-A50N VS FLP-A100N VS

T1

The complete range of devices for low voltage power supply, signal, measurement, data and telecom lines also for photovoltaic applications is available on

www.saltek.eu

CATALOGUE

SURGE PROTECTIONLOW VOLTAGE

1. Introduction – Legislative

The use of modern sophisticated equipment, consumer electronics and control systems places high demands on their electromagnetic compatibility. Modern electronic control systems provided with circuits with a very high integration level are becoming more and more sensitive to electromagnetic disturbance and overvoltage. The installation of surge protections according to effective legal standards will reduce the danger of their being damaged to a minimum. Technical designs are defined by standards harmonised with EU standards:

a) Protective bonding to the same potential including the conductor cross section for the main and additional bonding is defined by standards EN 50310 ed. 2. , IEC 60364-5-54, IEC 60364-4-41

b) Lightning protection is specified in the EN 62305 collection of new standards, harmonised with European standards. EN 62305 – Part 1 deals with general principles.

Lightning protection level

Maximum lightning

parameter according to LPL

LPL First short discharge

LPL I 200 kA

LPL II 150 kALPL III 100 kALPL IV 100 kA

EN 62305 – Part 2 – deals with the risk assessment for buildings or engineering networks struck by lightning.

EN 62305 – Part 3 – deals with the proposal for external lightning protection (lightning conductor).

EN 62305 – Part 4 – deals with protective measures resulting in the reduction of failures of electrical and electronic systems inside the building (zone protection)

c) Classification of protections is set forth in standard EN 61643-11.Devices are classified into three basic categories:SPD type 1 – lightning current arrestersSPD type 2 – surge arrestersSPD type 3 – surge arresters

d) Classification of low-voltage distribution into impulse resistance categories, including specification of the maximum allowed overvoltage is determined in standard EN 60664-1

Lightning and surge protection

Rated impulse for equipment (acc. to EN 60664-1) or Impulse-withstand voltage.

Lightning protection zones

The standard EN 62305-4 defines lightning protection zones LPZ in view of the direct and indirect (electromagnetic pulse – LEMP) lightning effect:

LPZ 0A – free area (possibility of a direct lightning strike, non-attenuated LEMP)

LPZ 0B – lightning conductor receiver protection area (direct lightning strike protection, non-attenuated LEMP)

LPZ 1 – inside a building (direct lightning strike is eliminated, attenuated LEMP – depending upon shielding)

LPZ 2 – inside a room – e.g. a server room with a conductive floor, FeAl floors and wall lining (further attenuation of LEMP in connection with a higher shielding level)

LPZ 3 – inside a metal box (e.g. 19“ RACK)

Lightning and surge protection

Example of main and additional bonding

telephone cable

gas pipeline

water pipeline

base ground

main protective bonding bar

2

Insulation coordination

liftflats appliance

appliances

Lightning and surge protection

2. Connection of protections in TN, TT and IT systems

SPD connection in TN-C system SPD connection in TN-S system SPD connection in TT system SPD connection in IT system

Principle of connection of surge protections in TN systemsSPD type 1 SPD type 2 SPD type 3

3. Principles of positioning and wiring of surge arresters and lightning current arresters

Surge arresters and lightning current arresters cannot be installed in the distribution system at random. You must be aware of the fact that protection should be placed at the closest proximity to the input feed cable in order to minimize the inductive loop area, see fig. 1.

Fig. 1 – Examples of device positioning in the distribution system.

overhead, PEN (PE) down overhead, PEN (PE) up underground, PEN (PE) down underground, PEN (PE) up

Another important condition for the wiring of arresters is to minimize the impedance of interconnecting conductors. Furthermore, the length of theinterconnecting conductors must be as short as possible (the total length of interconnecting conductors must not exceed 1 m). The cross section of theinterconnecting conductors should be as large as possible – up to the maximum cross section available for the terminal type.The cross section of interconnecting conductors is recommended to be larger by at least one cable size than the PEN (PE) conductor diameter (e.g.if the PEN conductor diameter is 10 mm2, the cross section of the interconnecting conductor should be 16 mm2).If arresters are placed in a circuit fitted with residual current devices (RCD), the arrester must be installed before the RCD (not in the RCD circuit) to avoidspontaneous RCD tripping due to surge arresters or lightning current arresters.If the RCD is placed before the protection, it is necessary to use the delayed RCD type, e.g. S-type or G-type.

3

FLP-SG50 VFLP-SG50 VS

SPD type 1 – lightning current arresterEncapsulated high-performance spark gap with replaceable module, visual fault signalling

To be installed in low-voltage distributions at the boundary of LPZ 0A and LPZ 1 zones to prevent overvoltage effects induced during direct or indirect lightning strikes in the most demanding applications in the heavy and chemicals industry, power stations, etc.Remote status signalling (S).

Dimension drawing Basic circuit diagram

connection of signalization

terminal3666

4590

9

15

Lightning Current Arresters

4

Technical data FLP-SG50 VS

Nominal voltage Un 230 V ACMaximum operating voltage Uc 255 V ACNominal discharge current (8/20 μs) In 50 kALightning impulse current (10/350 μs) Iimp 50 kAVoltage protection level Up <2,5 kV

Response time ta 100 nsAbility to independently switch off the following current Ifi 50 kANominal short circuit current ISCCR 50 kArms

Maximum overcurrent protection 315 A gL/gGMaximum overcurrent protection for serial connection 125 A gL/gGTOV voltage UT 335 V/5 sec.Degree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 2,5/50 mm2 ; AWG: 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2Visual fault indication red indication fieldRemote indication – S design potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard EN 61643-11:2012 Ordering number 8595090540533Ordering number

FLP-SG50 V 8595090540533FLP-SG50 VS 8595090540540

Lightning Current Arresters

SPD type 1 – lightning current arresterN-PE module, replaceable module

To be installed in low-voltage distributions at the boundary of LPZ 0A–LPZ 1 zones and higher to prevent overvoltage effects induced during direct or indirect lightning strikes for the connection of SPD type 1 in the mode 1+1.

Dimension drawing Basic circuit diagram

FLP-A50N VS

Technical data FLP-A50N VS

Nominal voltage Un —Maximum operating voltage Uc 255 V ACNominal discharge current (8/20 μs) In 50 kAMaximum discharge current (8/20 μs) Imax 100 kALightning impulse current (10/350 μs) Iimp 50 kAVoltage protection level Up 1,5 kVResponse time ta 100 nsAbility to independently switch off the following current Ifi 100 AShort-circuit proof at maximum overcurrent protection —Maximum overcurrent protection —Degree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 2,5/50 mm2 ; AWG: 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2Visual fault indication noRemote indication * potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number 8595090535737Replacement module FLP-A50N V/0 8595090535379

* Remote signalling of N-PE module shows the presence of the replaceable module

90 45

66 36

9

15

N( )

N( )

(N)

(N)

5

Lightning Current Arresters

SPD type 1 – lightning current arresterN-PE module, replaceable module

To be installed in low-voltage distributions at the boundary of LPZ 0A and LPZ 1 zones to prevent overvoltage effects induced during direct or indirect lightning strikes for the connection of SPD type 1 in the mode 3+1.

Dimension drawing Basic circuit diagram

FLP-A100N VS

Technical data FLP-A100N VS

Nominal voltage Un —Maximum operating voltage Uc 255 V ACNominal discharge current (8/20 μs)/pole In 100 kAMaximum discharge current (8/20 μs) Imax 100 kALighting impulse current (10/350 μs)/pole Iimp 100 kAVoltage protection level Up 1,5 kVResponse time ta 100 nsAbility to independently switch off the following current Ifi 100 AShort-circuit proof at maximum overcurrent protection —Maximum overcurrent protection —Degree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected condutors Solid min/max ISO: 2,5/50 mm2 ; AWG: 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2Visual fault indication noRemote indication * potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number 8595090535744Replacement module FLP-A100N V/0 8595090535362

* Remote signalling of N-PE module shows the presence of the replaceable module

90 45

66 36

9

15

N( )

N( )

(N)

(N)

6

Lightning Current Arresters

FLP-B+C MAXI VFLP-B+C MAXI VS

Dimension drawing Basic circuit diagram

SPD type 1 and type 2versatile single-pole arrester Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage(230/400 V AC) networks and connected appliances against surge voltages due to direct or indirectlightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1(or higher) zones.Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA(10/350 μsec pulse) with high energy varistors block. This proven technology guarantee no followcurrent, no leakage current and low residual voltage.Remote status signalling contact – version „S“.

Technical data FLP-B+C MAXI VS

Nominal voltage Un 230 V ACMaximum operating voltage Uc 260 V ACNominal discharge current (8/20 μs) In 30 kAMaximum discharge current (8/20 μs) Imax 60 kALightning impulse current (10/350 μs) Iimp 25 kAVoltage protection level Up 1,5 kV

Response time ta 100 nsAbility to independently switch off the following current Ifi no following currentShort-circuit proof at maximum overcurrent protection 50 kArms

Maximum overcurrent protection 250 A gL/gGMaximum overcurrent protection for serial connection 125 A gL/gGDegree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 2,5/50 mm2 ; AWG : 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2Visual fault indication red indication fieldRemote indication potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberFLP-B+C MAXI V 8595090550914FLP-B+C MAXI VS 8595090535331

Replacement module FLP-B+C MAXI V/0 8595090535355

connection of signalization

terminal3666

4590

9

15

(L/N)

L/N ( )

L/N( )

(L/N)

7

SPD type 1 and type 22-pole (1+NPE) arrester for single phase TT (TNS) networksTotal Iimp = 50kA (10/350) Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage (230/400 V AC) networks and connected appliances against surge voltages due to direct or indirect lightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones.Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven technology guarantee no follow current, no leakage current and low residual voltage.Remote status signalling contact – version „S“.

Dimension drawing Basic circuit diagram

Technical data L-N N-PE

Nominal voltage Un 230 V AC —Maximum operating voltage Uc 260 V AC 255 V ACNominal discharge current (8/20 μs) In 30 kA 50 kAMaximum discharge current Imax 60 kA 100 kALighting impulse current Iimp 25 kA 50 kAVoltage protection level Up 1,5 kV 1,5 kVResponse time ta 100 ns 100 nsAbility to independently switch off the following current Ifi no following current 100 AShort-circuit proof at maximum overcurrent protection 50 kArms —Maximum overcurrent protection 250 A gL/gG —Maximum overcurrent protection for serial connection 125 A gL/gG —Degree of protection IP 20 IP 20Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °CMounting on DIN rail 35 mm DIN rail 35 mmCross-section of connected condutors Solid min/max ISO: 2,5/50 mm2 ; AWG: 13/1 ISO: 2,5/50 mm2 ; AWG: 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2 ISO: 2,5/35 mm2 ; AWG: 13/2Visual fault indication red indication field noRemote indication* potential-free change-over contact potential-free change-over contact*Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2 max. 1,5 mm2

Meets the requirements of standard EN 61643-11 + A11 EN 61643-11:2012

Ordering numberFLP-B+C MAXI V/1+1 8595090550952FLP-B+C MAXI VS/1+1 8595090537830

Replacement moduleFLP-B+C MAXI V/0 (for L-N) 8595090535355FLP-A50N V/0 (for N-PE) 8595090535379

* Remote signalling of N-PE module shows the presence of the replaceable module

FLP-B+C MAXI V/1+1FLP-B+C MAXI VS/1+1

connection ofsignalization terminal

15

PE PE

7266

4590

9

15

N

LL

N NN

Lightning Current Arresters

8

SPD type 1 and type 22-pole arrester for single phase TNS networksTotal Iimp= 50kA (10/350) Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage (230/400 V AC) networks and connected appliances against surge voltages due to direct or indirect lightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones.Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven technology guarantee no follow current, no leakage current and low residual voltage.Remote status signalling contact – version „S“.

Dimension drawing Basic circuit diagram

Technical data FLP-B+C MAXI VS/2

Nominal voltage Un 230 V ACMaximum operating voltage Uc 260 V ACNominal discharge current (8/20 μs)/pole In 30 kAMaximum discharge current (8/20 μs)/pole Imax 60 kALightning impulse current (10/350 μs)/pole Iimp 25 kAVoltage protection level Up 1,5 kVResponse time ta 100 nsAbility to independently switch off the following current Ifi no following currentShort-circuit proof at maximum overcurrent protection 50 kArms

Maximum overcurrent protection 250 A gL/gGMaximum overcurrent protection for serial connection 125 A gL/gGDegree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 2,5/50 mm2 ; AWG: 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2Visual fault indication red indication fieldRemote indication potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberFLP-B+C MAXI V/2 8595090550921FLP-B+C MAXI VS/2 8595090537847

Replacement module FLP-B+C MAXI V/0 8595090535355

FLP-B+C MAXI V/2FLP-B+C MAXI VS/2

connection of signalization terminal

15

7266

4590

9

15

PE

L/N

L/N

L/N

L/N

PE PE PE

Lightning Current Arresters

9

SPD type 1 and type 23-pole arrester for 3-phase TNC networks Total Iimp= 75kA (10/350) Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage (230/400 V AC) networks and connected appliances against surge voltages due to direct or indirect lightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones.Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven technology guarantee no follow current, no leakage current and low residual voltage.Remote status signalling contact – version „S“.

Technical data FLP-B+C MAXI VS/3

Nominal voltage Un 230 V ACMaximum operating voltage Uc 260 V ACNominal discharge current (8/20 μs)/pole In 30 kAMaximum discharge current (8/20 μs)/pole Imax 60 kALightning impulse current (10/350 μs)/pole Iimp 25 kAVoltage protection level Up 1,5 kVResponse time ta 100 nsAbility to independently switch off the following current Ifi no following currentShort-circuit proof at maximum overcurrent protection 50 kArms

Maximum overcurrent protection 250 A gL/gGMaximum overcurrent protection for serial connection 125 A gL/gGDegree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 2,5/50 mm2 ; AWG: 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2Visual fault indication red indication fieldRemote indication potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberFLP-B+C MAXI V/3 8595090550938FLP-B+C MAXI VS/3 8595090535706

Replacement module FLP-B+C MAXI V/0 8595090535355

FLP-B+C MAXI V/3FLP-B+C MAXI VS/3

connection of signalization terminal

Dimension drawing Basic circuit diagram

90 45

66 108

9

15

Lightning Current Arresters

10

Lightning Current Arresters

SPD type 1 and type 24-pole arrester for 3-phase TNS networksTotal Iimp= 100kA (10/350) Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage (230/400 V AC) networks and connected appliances against surge voltages due to direct or indirect lightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones.Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven technology guarantee no follow current, no leakage current and low residual voltage.Remote status signalling contact – version „S“.

Dimension drawing Basic circuit diagram

FLP-B+C MAXI V/4FLP-B+C MAXI VS/4

connection of signalization terminal

Technical dataFLP-B+C MAXI VS/4

Nominal voltage Un 230 V ACMaximum operating voltage Uc 260 V ACNominal discharge current (8/20 μs)/pole In 30 kAMaximum discharge current (8/20 μs)/pole Imax 60 kALighting impulse current (10/350 μs)/pole Iimp 25 kAVoltage protection level Up 1,5 kVResponse time ta 100 nsAbility to independently switch off the following current Ifi no following currentShort-circuit proof at maximum overcurrent protection 50 kArms

Maximum overcurrent protection 250 A gL/gGMaximum overcurrent protection for serial connection 125 A gL/gGDegree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected condutors Solid min/max ISO: 2,5/50 mm2 ; AWG: 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2Visual fault indication red indication fieldRemote indication potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberFLP-B+C MAXI V/4 8595090550945FLP-B+C MAXI VS/4 8595090535713

Replacement module FLP-B+C MAXI V/0 8595090535355

66

4590

144

9

15

66

4590

144

9

15

11

SPD type 1 and type 24-pole (3+NPE) arrester for 3-phase TT(TNS) networksTotal Iimp= 100kA (10/350) Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage (230/400 V AC) networks and connected appliances against surge voltages due to direct or indirect lightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones.Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven technology guarantee no follow current, no leakage current and low residual voltage.Remote status signalling contact – version „S“.

Dimension drawing Basic circuit diagram

Technical dataL-N N-PE

Nominal voltage Un 230 V AC —Maximum operating voltage Uc 260 V AC 255 V ACNominal discharge current (8/20 μs)/pole In 30 kA 100 kAMaximum discharge current (8/20 μs) Imax 60 kA 100 kALighting impulse current (10/350 μs)/pole Iimp 25 kA 100 kAVoltage protection level Up 1,5 kVVoltage protection level (L - PE) Up 2,2 kVResponse time ta 100 ns 100 nsAbility to independently switch off the following current Ifi no following current 100 AShort-circuit proof at maximum overcurrent protection 50 kArms —Maximum overcurrent protection 250 A gL/gG —Maximum overcurrent protection for serial connection 125 A gL/gG —Degree of protection IP 20 IP 20Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °CMounting on DIN rail 35 mm DIN rail 35 mmCross-section of connected condutors Solid min/max ISO: 2,5/50 mm2 ; AWG: 13/1 ISO: 2,5/50 mm2 ; AWG: 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2 ISO: 2,5/35 mm2 ; AWG: 13/2Visual fault indication red indication field noRemote indication* potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberFLP-B+C MAXI V/3+1 8595090550969FLP-B+C MAXI VS/3+1 8595090535720

Replacement moduleFLP-B+C MAXI VS/0 (for L-N) 8595090535355FLP-A100N V/0 (for N-PE) 8595090535362

* Remote signalling of N-PE module shows the presence of the replaceable module

FLP-B+C MAXI V/3+1FLP-B+C MAXI VS/3+1

connection ofsignalization terminal

Lightning Current Arresters

90 45

66 144

9

15

90 45

66 144

9

15

12

Technical data

Lightning Current Arresters

SPD type 1 and type 2versatile single-pole arrester

Varistor lightning and surge current arrester to be installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

Dimension drawing Basic circuit diagram

Technical data FLP-12,5 VS

Nominal voltage Un 230 V ACMaximum operating voltage Uc 275 V AC / 350 V DCNominal discharge current (8/20 μs) In 30 kAMaximal discharge current Imax 60 kALightning impulse current (10/350 μs) Iimp 12,5 kAVoltage protection level Up 1,2 kVVoltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kVResponse time ta 25 nsShort-circuit proof at maximum overcurrent protection 50 kArms

Maximum overcurrent protection 160 A gL/gGDegree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4Fault indication red indication fieldRemote indication – S design potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering number FLP-12,5 V 8595090534211 FLP-12,5 VS 8595090534228

Replacement module FLP-12,5 V/0 8595090534310

FLP-12,5 VFLP-12,5 VS

connection ofsignalization terminal

13

FLP-12,5 V/3

Nominal voltage Un 230 V ACMaximum operating voltage Uc 275 V AC / 350 V DCNominal discharge current (8/20 μs)/pole In 30 kAMaximal discharge current/pole Imax 60 kALightning impulse current (10/350 μs)/pole Iimp 12,5 kAVoltage protection level Up 1,2 kVVoltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kVResponse time ta 25 nsShort-circuit proof at maximum overcurrent protection 50 kArms

Maximum overcurrent protection 160 A gL/gGDegree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4Fault indication red indication fieldRemote indication – S design potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberFLP-12,5 V/3 8595090534259FLP-12,5 V/3S 8595090534266

Replacement module FLP-12,5 V/0 8595090534310

Lightning Current Arresters

SPD type 1 and type 23-pole arrester for 3-phase TNC networksTotal Iimp= 37,5kA (10/350)

Varistor lightning and surge current arresters to be installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

Technical data

FLP-12,5 V/3 FLP-12,5 V/3 S

Dimension drawing Basic circuit diagram

connection ofsignalization terminal

14

Lightning Current Arresters

SPD type 1 and type 24-pole arrester for 3-phase TNS networksTotal Iimp= 50kA (10/350)

Varistor lightning and surge current arresters to be installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

Dimension drawing Basic circuit diagram

Technical data FLP-12,5 V/4

Nominal voltage Un 230 V ACMaximum operating voltage Uc 275 V AC / 350 V DCNominal discharge current (8/20 μs)/pole In 30 kAMaximal discharge current/pole Imax 60 kALightning impulse current (10/350 μs)/pole Iimp 12,5 kAVoltage protection level Up 1,2 kVVoltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kVResponse time ta 25 nsShort-circuit proof at maximum overcurrent protection 50 kArms

Maximum overcurrent protection 160 A gL/gGDegree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4Fault indication red indication fieldRemote indication – S design potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberFLP-12,5 V/4 8595090534297FLP-12,5 V/4S 8595090534303

Replacement module FLP-12,5 V/0 8595090534310

FLP-12,5 V/4 FLP-12,5 V/4 S

connection ofsignalization terminal

15

L-N N-PE

Nominal voltage Un 230 V AC —Maximum operating voltage Uc 275 V AC 255 V ACNominal discharge current (8/20 μs) In 30 kA 30 kAMaximal discharge current (8/20 μs) Imax 60 kA 60 kALightning impulse current (10/350 μs) Iimp 12,5 kA 25 kAVoltage protection level Up 1,2 kV 1,5 kVVoltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV —Voltage protection level (L - PE) Up 1,5 kVResponse time ta 25 ns 100 nsAbility independently switch off the following current Ifi no following current 100 AShort-circuit proof at maximum overcurrent protection 50 kArms —Maximum overcurrent protection 160 A gL/gG —Degree of protection IP 20 IP 20Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °CMounting on DIN rail 35 mm DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4Fault indication red indication field noRemote indication – S design potential-free change-over contact —Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —Cross-section of remote indication conductors max. 1,5 mm2 —

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberFLP-12,5 V/1+1 8595090534235FLP-12,5 V/1S+1 8595090534242

Replacement moduleFLP-12,5 V/0 (for L-N) 8595090534310FLP-NPE 25 V/0 (for N-PE) 8595090534327

Lightning Current Arresters

SPD type 1 and type 22-pole (1+NPE) arrester for single phase TT(TNS) networksTotal Iimp= 25kA (10/350)

Varistor lightning and surge current arrester and heavy duty encapsulated spark gap to be installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

FLP-12,5 V/1+1FLP-12,5 V/1S+1

Dimension drawing Basic circuit diagram

connection ofsignalization terminal

Technical data

16

L-N N-PE

Nominal voltage Un 230 V AC —Maximum operating voltage Uc 275 V AC 255 V ACNominal discharge current (8/20 μs) In 30 kA 50 kAMaximal discharge current (8/20 μs) Imax 60 kA 100 kALightning impulse current (10/350 μs) Iimp 12,5 kA 50 kAVoltage protection level Up 1,2 kV 1,5 kVVoltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV —Voltage protection level (L - PE) Up 1,5 kVResponse time ta 25 ns 100 nsAbility independently switch off the following current Ifi no following current 100 AShort-circuit proof at maximum overcurrent protection 50 kArms —Maximum overcurrent protection 160 A gL/gG —Degree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4Fault indication red indication field noRemote indication – S design potential-free change-over contact —Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —Cross-section of remote indication conductors max. 1,5 mm2 —

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberFLP-12,5 V/3+1 8595090534273FLP-12,5 V/3S+1 8595090534280

Replacement module FLP-12,5 V/0 8595090534310

Lightning Current Arresters

SPD type 1 and type 24-pole (3+NPE) arrester for 3-phase TT(TNS) networksTotal Iimp= 50kA (10/350)

Varistor lightning and surge current arresters and fixed N-PE modul with heavy duty encapsulated spark gap. To be installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

FLP-12,5 V/3+1FLP-12,5 V/3S+1

Dimension drawing Basic circuit diagram

connection ofsignalization terminal

Technical data

17

Lightning Current Arresters

SPD type 1 and type 2versatile single-pole arrester

Varistor lightning and surge current arrester to be installed in low-voltage distributions at the boundary of LPZ 0B–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

Dimension drawing Basic circuit diagram

FLP-275 VFLP-275 VS

Technical data FLP-275 V

Nominal voltage Un 230 V AC

Maximum operating voltage Uc 275 V AC / 350 V DC

Nominal discharge current (8/20 μs) In 30 kA

Maximum discharge current Imax 60 kA

Lightning impulse current (10/350 μs) Iimp 8 kA

Voltage protection level Up 1,2 kV

Response time ta 25 ns

Short-circuit proof at maximum overcurrent protection 50 kArms

Maximum overcurrent protection 160 A gL/gG

Degree of protection IP 20

Range of operating temperatures – 40 °C … + 80 °C

Mounting on DIN rail 35 mm

Cross-section of connected conductors

Solid min/max ISO: 1/35 mm2 ; AWG: 17/2

Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4

Fault indication red indication field

Remote indication – S design potential-free change-over contact

Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC

Cross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering number FLP-275 V 8595090516200

FLP-275 VS 8595090516217Replacement module FLP-275 V/0 8595090532972

connection ofsignalization terminal

18

Lightning Current Arresters

SPD type 1 and type 23-pole arrester for 3-phase TNC networksTotal Iimp= 24kA (10/350)

Varistor lightning and surge current arresters to be installed in low-voltage distributions at the boundary of LPZ 0B–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

Dimension drawing Basic circuit diagram

Technical data FLP-275 V/3

Nominal voltage Un 230 V AC

Maximum operating voltage Uc 275 V AC / 350 V DCNominal discharge current (8/20 μs)/pole In 30 kAMaximum discharge current (8/20 μs)/pole Imax 60 kALightning impulse current (10/350 μs)/pole Iimp 8 kAVoltage protection level Up 1,2 kVResponse time ta 25 nsShort-circuit proof at maximum overcurrent protection 50 kArms

Maximum overcurrent protection 160 A gL/gGDegree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4Fault indication red indication fieldRemote indication – S design potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberFLP-275 V/3 8595090517757FLP-275 V/3 S 8595090517771

Replacement module FLP-275 V/0 8595090535972

FLP-275 V/3FLP-275 V/3 S

connection of signalization terminal

19

Lightning Current Arresters

SPD type 1 and type 24-pole arrester for 3-phase TNS networksTotal Iimp= 32kA (10/350)

Varistor lightning and surge current arresters to be installed in low-voltage distributions at the boundary of LPZ 0B–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

Dimension drawing Basic circuit diagram

Technical data FLP-275 V/4

Nominal voltage Un 230 V AC

Maximum operating voltage Uc 275 V AC / 350 V DCNominal discharge current (8/20 μs)/pole In 30 kAMaximum discharge current (8/20 μs)/pole Imax 60 kALighting impulse current (10/350 μs)/pole Iimp 8 kAVoltage protection level Up 1,2 kVResponse time ta 25 nsShort-circuit proof at maximum overcurrent protection 50 kArms

Maximum overcurrent protection 160 A gL/gGDegree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected condutors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4Fault indication red indication fieldRemote indication – S design potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberFLP-275 V/4 8595090517788FLP-275 V/4 S 8595090517795

Replacement module FLP-275 V/0 8595090532972

FLP-275 V/4FLP-275 V/4 S

connection of signalization terminal

20

Lightning Current Arresters

SPD type 1 and type 22-pole (1+NPE) arrester for single phase TT(TNS) networks

Varistor lightning and surge current arrester and heavy duty encapsulated spark gap in the mode 1+1. To be installed in low-voltage distributions at the boundary of LPZ 0B and LPZ 1 zones to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

FLP-275 V/1+1FLP-275 V/1S+1

Dimension drawing Basic circuit diagram

connection of signalization terminal

Technical data L-N N-PE

Nominal voltage Un 230 V AC —Maximum operating voltage Uc 275 V AC 255 V ACNominal discharge current (8/20 μs) In 30 kA 20 kAMaximum discharge current (8/20 μs) Imax 60 kA 40 kALighting impulse current (10/350 μs) Iimp 8 kA 25 kAVoltage protection level Up 1,2 kV 1,5 kVVoltage protection level (L - PE) Up 1,5 kVResponse time ta 25 ns 25 nsAbility to independently switch off the following current Ifi no following current 100 AShort-circuit proof at maximum overcurrent protection 50 kArms —Maximum overcurrent protection 160 A gL/gG —Degree of protection IP 20 IP 20Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °CMounting on DIN rail 35 mm DIN rail 35 mmCross-section of connected condutors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4Fault indication red indication field neRemote indication – S design potential-free change-over contact —Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —Cross-section of remote indication conductors max. 1,5 mm2 —

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberFLP-275 V/1+1 8595090533085FLP-275 V/1S+1 8595090533092

Replacement moduleFLP-275 V/0 (for L-N) 8595090532972FLP-NPE 25 V/0 (for N-PE) 8595090534327

21

Lightning Current Arresters

SPD type 1 and type 24-pole (3+NPE) arrester for 3-phase TT(TNS) networksTotal Iimp= 25kA (10/350)

Varistor lightning and surge current arresters and heavy duty encapsulated spark gap connected in the mode 3+1. To be installed in low-voltage distributions at the boundary of LPZ 0B and LPZ 1 zones to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

FLP-275 V/3+1FLP-275 V/3S+1

Technical data L-N N-PE

Nominal voltage Un 230 V AC —Maximum operating voltage Uc 275 V AC 255 V ACNominal discharge current (8/20 μs)/pole In 30 kA 20 kAMaximum discharge current (8/20 μs)/pole Imax 60 kA 40 kALighting impulse current (10/350 μs)/pole Iimp 8 kA 25 kAVoltage protection level Up 1,2 kV 1,5 kVVoltage protection level (L - PE) Up 1,5 kVResponse time ta 25 ns 100 nsAbility to independently switch off the following current Ifi no following current 100 AShort-circuit proof at maximum overcurrent protection 50 kArms —Maximum overcurrent protection 160 A gL/gG —Degree of protection IP 20 IP 20Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °CMounting on DIN rail 35 mm DIN rail 35 mmCross-section of connected condutors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4Fault indication red indication field noRemote indication – S design potential-free change-over contact —Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —Cross-section of remote indication conductors max. 1,5 mm2 —

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberFLP-275 V/3+1 8595090531128FLP-275 V/3S+1 8595090531135

Replacement moduleFLP-275 V/0 (for L-N) 8595090532972FLP-NPE 25 V/0 (for N-PE) 8595090534327

Dimension drawing Basic circuit diagram

connection of signalization terminal

22

Surge Arresters

Dimension drawing Basic circuit diagram

Technical data SLP-275 V

Nominal voltage Un 230 V AC

Maximum operating voltage Uc 275 V AC / 350 V DCMaximum operating voltage of varistor —Nominal discharge current (8/20 μs) In 20 kAMaximum discharge current (8/20 μs) Imax 40 kAVoltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kVVoltage protection level Up 1,2 kVResponse time ta 25 nsShort-circuit proof at maximum overcurrent protection 50 kArms

Maximum overcurrent protection 160 A gL/gGDegree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4Fault indication red indication fieldRemote indication – S version potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberSLP-xxx V 8595090516170

SLP-xxx VS 8595090516187

Replacement module SLP-xxx V/0 8595090523680

SLP-275 VSLP-275 VS

connection ofsignalization terminal

23

SPD type 2versatile single-pole arrester

Varistor surge protection to be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones to protect the distributions and equipment against overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Remote status signalling (S).

Surge Arresters

SPD type 2 – surge arrester 3-pole arrester for 3-phase TNC networks

3-pole varistor surge protection to be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones to protect the distributions and equipment against overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

SLP-275 V/3SLP-275 V/3S

Dimension drawing Basic circuit diagram

connection of signalization terminal

Technical data SLP-275 V/3

Nominal voltage Un 230 V AC

Maximum operating voltage Uc 275 V AC / 350 V DCNominal discharge current (8/20 μs)/pole In 20 kAMaximum discharge current (8/20 μs)/pole Imax 40 kAVoltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kVVoltage protection level Up 1,2 kVResponse time ta 25 nsShort-circuit proof at maximum overcurrent protection 50 kArms

Maximum overcurrent protection 160 A gL/gGDegree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4Fault indication red indication fieldRemote indication – S design potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberSLP-275 V/3 8595090517603SLP-275 V/3S 8595090517610

Replacement module SLP-275 V/0 8595090523680

24

Surge Arresters

SPD type 2 – surge arrester 4-pole arrester for 3-phase TNS networks

4-pole varistor surge protection to be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones to protect the distributions and equipment against overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

SLP-275 V/4SLP-275 V/4S

Dimension drawing Basic circuit diagram

connection of signalization

terminal

Technical data SLP-275 V/4

Nominal voltage Un 230 V AC

Maximum operating voltage Uc 275 V AC / 350 V DCNominal discharge current (8/20 μs)/pole In 20 kAMaximum discharge current (8/20 μs)/pole Imax 40 kAVoltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kVVoltage protection level Up 1,2 kVResponse time ta 25 nsShort-circuit proof at maximum overcurrent protection 50 kArms

Maximum overcurrent protection 160 A gL/gGDegree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4Fault indication red indication fieldRemote indication – S design potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberSLP-275 V/4 8595090517221SLP-275 V/4S 8595090517634

Replacement module SLP-275 V/0 8595090523680

25

Surge Arresters

SPD type 2 – surge arrester 2-pole (1+NPE) arrester for single phase TT(TNS) networks

Combination of varistor surge protection and an encapsulated spark gap connected in the mode 1+1. To be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

Dimension drawing Basic circuit diagram

Technical data L-N N-PE

Nominal voltage Un 230 V AC —

Maximum operating voltage Uc 275 V AC 255 V AC Nominal discharge current (8/20 μs) In 20 kA 20 kAMaximum discharge current (8/20 μs) Imax 40 kA 40 kALighting impulse current (10/350 μs) Iimp — 15 kAVoltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV —Voltage protection level Up 1,2 kV 1,5 kVVoltage protection level (L - PE) Up 1,5 kVResponse time ta 25 ns 100 nsAbility to independently switch off the following current Ifi no following current 100 AShort-circuit proof at maximum overcurrent protection 50 kArms —Maximum overcurrent protection 160 A gL/gG —Degree of protection IP 20 IP 20Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °CMounting on DIN rail 35 mm DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4Fault indication red indication field noRemote indication – S design potential-free change-over contact —Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —Cross-section of remote indication conductors max. 1,5 mm2 —

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberSLP-275 V/1+1 8595090519485SLP-275 V/1S+1 8595090524915

Replacement moduleSLP-275 V/0 (for L-N) 8595090523680SLP-NPE V/0 (for N-PE) 8595090537229

SLP-275 V/1+1SLP-275 V/1S+1

connection of signalization terminal

26

Surge Arresters

SPD type 2 – surge arrester 4-pole (3+NPE) arrester for 3-phase TT(TNS) networks

Combination of 3-pole varistor surge protection and an encapsulated spark gap connected in the mode 3+1. To be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

Dimension drawing Basic circuit diagram

Technical data L-N N-PE

Nominal voltage Un 230 V AC —

Maximum operating voltage Uc 275 V AC 255 V AC Nominal discharge current (8/20 μs)/pole In 20 kA 20 kAMaximum discharge current (8/20 μs)/pole Imax 40 kA 40 kALighting impulse current (10/350 μs) Iimp — 15 kAVoltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV —Voltage protection level Up 1,2 kV 1,5 kVVoltage protection level (L - PE) Up 1,5 kVResponse time ta 25 ns 100 nsAbility to independently switch off the following current Ifi no following current 100 AShort-circuit proof at maximum overcurrent protection 50 kArms —Maximum overcurrent protection 160 A gL/gG —Degree of protection IP 20 IP 20Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °CMounting on DIN rail 35 mm DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4Fault indication red indication field noRemote indication – S design potential-free change-over contact —Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —Cross-section of remote indication conductors max. 1,5 mm2 —

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberSLP-275 V/3+1 8595090519461SLP-275 V/3S+1 8595090520023

Replacement moduleSLP-275 V/0 (for L-N) 8595090523680SLP-NPE V/0 (for N-PE) 8595090537229

SLP-275 V/3+1SLP-275 V/3S+1

connection of signalization

terminal

27

Surge Arresters

Dimension drawing Basic circuit diagram

Technical data SLP-075 V SLP-150 V SLP-385 V SLP-440 V SLP-600 V

Nominal voltage Un — 120 V AC — 400 V AC —

Maximum operating voltage Uc 75 V AC / 100 V DC 150 V AC / 200 V DC 385 V AC / 500 V DC 440 V AC / 585 V DC 600 V ACMaximum operating voltage of varistor — — — — 880 V ACNominal discharge current (8/20 μs) In 15 kA 15 kA 20 kA 20 kA 15 kAMaximum discharge current (8/20 μs) Imax 40 kA 40 kA 40 kA 40 kA 40 kAVoltage protection level @ I = 5 kA (8/20 μs) Up 0,3 kV 0,45 kV 1,3 kV 1,5 kV 2,7 kVVoltage protection level Up 0,4 kV 0,6 kV 1,8 kV 1,9 kV 3,2 kVResponse time ta 25 ns 25 ns 25 ns 25 ns 25 nsShort-circuit proof at maximum overcurrent protection 50 kArms 50 kArms 50 kArms 50 kArms 50 kArms

Maximum overcurrent protection 160 A gL/gG 160 A gL/gG 160 A gL/gG 160 A gL/gG 160 A gL/gGDegree of protection IP 20Range of operating temperatures – 40 °C … + 80 °CMounting on DIN rail 35 mmCross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4Fault indication red indication fieldRemote indication – S version potential-free change-over contactRemote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DCCross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering numberSLP-xxx V 8595090518150 8595090551850 8595090519553 8595090518174 8595090533016

SLP-xxx VS 8595090518235 8595090551867 8595090527718 8595090518259 8595090533023

Replacement module SLP-xxx V/0 8595090518112 8595090551935 8595090519508 8595090518136 8595090533030

SLP-075 V(S)SLP-150 V(S)SLP-385 V(S)SLP-440 V(S)SLP-600 V(S)

SPD type 2versatile single-pole arrester

Varistor surge protection to be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones to protect the distributions and equipment against overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Remote status signalling (S). Multi-pole versions and other (special) voltages on request.

connection ofsignalization terminal

28

Surge Arresters

Dimension drawing Basic circuit diagram

Technical data SLP-075 VB SLP-130 VB SLP-275 VB

Nominal voltage Un — 120 V AC 230 V AC

Maximum operating voltage Uc 75 V AC / 100 V DC 135 V AC / 175 V DC 275 V AC / 350 V DC

Nominal discharge current (8/20 μs) In 15 kA 20 kA 20 kA

Maximum discharge current (8/20 μs) Imax 25 kA 25 kA 25 kA

Voltage protection level @ I = 5 kA (8/20 μs) Up 0,3 kV 0,5 kV 0,9 kV

Voltage protection level Up 0,6 kV 0,7 kV 1,2 kV

Response time ta 100 ns 100 ns 100 ns

Short-circuit proof at maximum overcurrent protection 35 kArms 35 kArms 35 kArms

Maximum overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG

Degree of protection IP 20 IP 20 IP 20

Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C – 40 °C … + 80 °C

Mounting on DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm

Cross-section of connected conductors

Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2

Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4

Fault indication red indication field red indication field red indication field

Remote indication – S design potential-free change-over contact

Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC

Cross-section of remote indication conductors max. 1,5 mm2

Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012

IEC 61643-11 ed. 1.0 EN 61643-11:2012

IEC 61643-11 ed. 1.0 EN 61643-11:2012

Ordering number SLP-xxx VB 8595090521556 8595090552147 8595090519447

SLP-xxx VBS 8595090521563 8595090552154 8595090519454

Replacement module SLP-xxx VB/0 8595090521549 8595090552161 8595090519430

SLP-075 VB(S)SLP-130 VB(S)SLP-275 VB(S)SPD type 2 – surge arrester Replaceable module, visual fault signalling

Efficient varistor connected in series with an encapsulated spark gap. To be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones. Designed to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage in areas with higher storm activity or to protect measuring circuits as a 1st protection level. In idle state it has very little leakage current, which remains stable for the duration of the service life; protective elements are not subject to ageing.Optional remote status signalling (S).

connection of signalization

terminal

29

Surge Arresters

SPD type 3 – surge arresterReplaceable module, visual fault signalling

Combination of varistor surge protection and an encapsulated spark gap connected in the mode 1+1. To be installed in low-voltage distributions at the boundary of LPZ 2 and LPZ 3 zones to protect distributions and equipment against overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

Dimension drawing Basic circuit diagram

Technical data L-N N-PE

Nominal voltage Un 230 V AC —

Maximum operating voltage Uc 275 V AC 255 V AC

Nominal discharge current (8/20 μs) In 5 kA 10 kA

Test voltage Uoc 10 kV 20 kV

Voltage protection level Up 1 kV 1,5 kV

Voltage protection level (L - PE) Up 1,5 kV

Response time ta 25 ns 100 ns

Maximum overcurrent protection 63 A gL/gG —

Degree of protection IP 20 IP 20

Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C

Mounting on DIN rail 35 mm DIN rail 35 mm

Cross-section of connected conductors

Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2

Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4

Fault indication red indication field no

Remote indication – S design potential-free change-over contact —

Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —

Cross-section of remote indication conductors max. 1,5 mm2 —

Meets the requirements of standard EN 61643-11 + A11 EN 61643-11 + A11

Ordering numberDA-275 V/1+1 8595090518723

DA-275 V/1S+1 8595090519751

Replacement moduleDA-275 V/0 (for L-N) 8595090518518

DA-NPE V/0 (for N-PE) 8595090530046

DA-275 V/1+1DA-275 V/1S+1

connection of signalization terminal

30

Surge Arresters

SPD type 3 – surge arresterReplaceable module, visual fault signalling

Combination of 3-pole varistor surge protection and an encapsulated spark gap connected in the mode 3+1. To be installed in low-voltage distributions at the boundary of LPZ 2 and LPZ 3 zones to protect distributions and equipment against overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

Dimension drawing Basic circuit diagram

Technické parametry L-N N-PE

Nominal voltage Un 230 V AC —

Maximum operating voltage Uc 275 V AC 255 V AC

Nominal discharge current (8/20 μs)/pole In 5 kA 10 kA

Test voltage Uoc 10 kV 20 kV

Voltage protection level Up 1 kV 1,5 kV

Voltage protection level (L - PE) Up 1,5 kV

Response time ta 25 ns 100 ns

Maximum overcurrent protection 63 A gL/gG —

Degree of protection IP 20 IP 20

Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C

Mounting on DIN rail 35 mm DIN rail 35 mm

Cross-section of connected conductors

Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2

Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4

Fault indication red indication field no

Remote indication – S design potential-free change-over contact —

Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —

Cross-section of remote indication conductors max. 1,5 mm2 —

Meets the requirements of standard EN 61643-11 + A11 EN 61643-11 + A11

Ordering numberDA-275 V/3+1 8595090518488

DA-275 V/3S+1 8595090518495

Replacement moduleDA-275 V/0 (for L-N) 8595090518518

DA-NPE V/0 (for N-PE) 8595090530046

DA-275 V/3+1DA-275 V/3S+1

connection of signalization

terminal

31

Surge Arresters

AccessoriesSALTEK SPD type 1–3 with a “V“ in the part number are made with replaceable modules. This enables simple withdrawal of the module from its base to test the systems insulation, without the need to disconnect the device from the circuit. Furthermore the new modules enable simple up-down orientation of the SPD, according to the incoming cables and also it serve for fast and easy replacement in case of failure.The replacement modules (marked “xxx V/0”) are identical to the ones used in original product.The voltages used cannot be mixed because of the identical voltage key on the module and the corresponding base part.

Dimension drawing

Replaceable modules

type ordering number

FLP-12,5 V/0 8595090534310

FLP-NPE 25 V/0 8595090534327

SLP-075 V/0 8595090518112

FLP-275 V/0 8595090532972

SLP-150 V/0 8595090551935

SLP-275 V/0 8595090523680

SLP-385 V/0 8595090519508

SLP-440 V/0 8595090518136

SLP-600 V/0 8595090533030

SLP-075 VB/0 8595090521549

SLP-150 VB/0 8595090552161

SLP-275 VB/0 8595090519430

SLP-NPE V/0 8595090537229

DA-275 V/0 8595090518518

DA-NPE V/0 8595090530046

type ordering code

FLP-B+C MAXI V/0 8595090535355

FLP-A50N V/0 8595090535379

FLP-A100N V/0 8595090535362

36 mm (2TE) 18 mm (1TE)

Illustration photo Illustration photo

32

3652,5

Surge Arresters

SPD type 3 – surge arresterVisual fault signalling

Surge protection designed to protect all types of electric and electronic equipment connected to a low-voltage distribution against pulse overvoltage.

Dimension drawing Basic circuit diagram

Technical data DA-075 DJ DA-130 DJ DA-275 DJ

Nominal voltage Un — 110 V AC 230 V AC

Maximum operating voltage Uc 75 V AC 130 V AC 275 V AC

Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 2 kA, 2 kA, 4 kA 2,5 kA, 2,5 kA, 5 kA 3 kA, 3 kA, 5 kA

Test voltage L-N, L(N)-PE, L+N-PE Uoc 4 kV, 4 kV, 8 kV 5 kV, 5 kV, 10 kV 6 kV, 6 kV, 10 kV

Voltage protection level L-N, L(N)-PE Up 0,4 kV, 1,2 kV 0,6 kV, 1,5 kV 1,2 kV, 1,6 kV

Response time L-N, L(N)-PE ta 25 ns, 100 ns 25 ns, 100 ns 25 ns, 100 ns

Short-circuit proof at maximum overcurrent protection 6 kA rms 6 kA rms 6 kA rms

Maximum overcurrent protection 16 A gL/gG; C 16 A 16 A gL/gG; C 16 A 16 A gL/gG; C 16 A

Degree of protection IP 20 IP 20 IP 20

Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C – 40 °C … + 80 °C

Mounting on DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm

Cross-section of connected conductors

Solid max ISO: 6 mm2 ; AWG: 10 ISO: 6 mm2 ; AWG: 10 ISO: 6 mm2 ; AWG: 10

Stranded max ISO: 4 mm2 ; AWG: 11 ISO: 4 mm2 ; AWG: 11 ISO: 4 mm2 ; AWG: 11

Fault indication red indicator red indicator red indicator

Meets the requirements of standard EN 61643-11 + A11 EN 61643-11 + A11 EN 61643-11 + A11

Ordering number 8595090533191 8595090521891 8595090506362

DA-075 DJDA-130 DJDA-275 DJ

33

Surge Arresters

SPD type 3 – surge arrester

Surge protection designed to protect all types of electric and electronic equipment connected to a low-voltage distribution against pulse overvoltage.

Dimension drawing Basic circuit diagram

Technical data DA-275 A

Nominal voltage Un 230 V AC

Maximum operating voltage Uc 275 V AC

Nominal discharge current (8/20 μs) L-N, L(N)-PE In 2,0 kA, 2,0 kA

Test voltage L-N, L(N)-PE Uoc 4,0 kV, 4,0 kV

Voltage protection level L-N, L(N)-PE Up 1,5 kV, 1,5 kV

Response time L-N, L(N)-PE ta 25 ns, 100 ns

Maximum overcurrent protection 16 A gL/gG or B16 A

TOV 5 s L-N 335 V

Degree of protection IP 20

Range of operating temperatures – 25 °C … + 40 °C

Mounting on in wiring boxes

Fault indication acoustic signalling

Remote indication no

Meets the requirements of standard EN 61643-11:2012

Ordering number 8595090540472

DA-275 A

L/N

PE

N/L

TEST

34

Surge Arresters

SPD type 3 – surge arresterRemote fault signalling

Surge protection for additional installation in devices, equipment, etc. designed to protect all types of low-voltage electric and electronic equipment against pulse overvoltage.

Dimension drawing Basic circuit diagram

DA-275 CZS

C 16 A

remoteindication contact

group of protectedoutlets

Technical data DA-275 CZS

Nominal voltage Un 230 V AC

Maximum operating voltage Uc 275 V AC

Nominal discharge current (8/20 μs) L-N, L(N)-PE In 3,0 kA, 3,0 kA

Test voltage L-N, L(N)-PE Uoc 6 kV, 6 kV

Voltage protection level L-N, L(N)-PE Up 1,0 kV, 1,5 kV

Response time L-N, L(N)-PE ta 25 ns, 100 ns

Maximum overcurrent protection 16 A gL/gG or C16 A

TOV 5 s L-N 335 V

TOV 5 s L-PE 400 V

TOV 200 ms L-PE 1 430 V

Degree of protection IP 20

Range of operating temperatures –25 °C … + 40 °C

Mounting in wiring boxes

Fault indication open contact

Remote indication potential-free open contact

Remote indication contacts 230 V AC/0,5 A, 24 V DC/0,5 A

Meets the requirements of standard EN 61643-11 + A11

Ordering number 8595090519164

35

25

10 20 300

15,8

Notes

PRODUCT RANGE

For more details please contact us or visit www.saltek.eu

Low voltageSPD type 1, type 2 and type 3 for lightning and surge protectionof LV distribution systems

Renewable energySPD for photovoltaic applications (AC side, DC side, communication lines),electric vehicle charging stations, wind turbines and biogas plants

Surger protection with RFI filterSPD type 3 to protect against surges and high frequency interferencevoltages caused by inverters

Control linesSurge protection devices for AI, AO, DI, DO and bus forcontrol, security or fire protection systems

Telecom linesSurge protection devices for analog, ISDN and ADSL lines and other DSLlines for installation on DIN rail or LSA-PLUS

Video/securitySurge protection devices for coaxial lines for N/F/BNC connectors for useon frequencies 0-5,8 GHz.

EthernetSurge protection devices for Ethernet category 5 and 6 and for Power overEthernet (POE, POE PLUS)

Manufactureand headquarter

SALTEK s.r.o.Drážďanská 85400 07 Ústí nad LabemCzech Republic

tel.: +420 475 655 511fax: +420 475 622 213GSM: +420 602 413 437e-mail: [email protected]

Sales officeand technical support

SALTEK TRADE, s.r.o.Vodňanská 1419/229198 00 Praha 9Czech Republic

tel.: +420 272 942 470fax: +420 267 913 411GSM: +420 602 472 633 e-mail: [email protected]

www.saltek.eu EN 2014/04