Head Office/Factory :Jl. Gatot Subroto Km 7,8 Kel Pasir Jaya, Kec. Jati Uwung, Tangerang 15135-IndonesiaPhone : (62-21) 5922404, 5928066 (Hunting) Fax. : (62-21) 59301979, 5922576, 5901469
c Copyright Sumi Indo Kabel 2007
All rights reserved. This catalogue is the copyright work of PT. Sumi Indo Kabel Tbk. No part of this publication may be reproduced, stored in a retrieval system, or transmitted,in any form or by means, electronic, mechanical, photocopying, recording or otherwise, without prior permission of PT. Sumi Indo Kabel.
All information contained in this catalogue is believed to be accurate at the time issue. PT. Sumi Indo Kabel reserve the right to change information or specification at any timein the light of technical developments or revisions.
Issue : Second Date: September '07
Section 1 - Contents & Information
Low Voltage Catalogue Index Page Number
SECTION 1 - Contents & InformationIndex Page 1
Company Profile of PT. SUMI INDO KABEL Tbk 2
Cable Specification 3
SECTION 2 - PVC Insulated CablesUnarmoured Cables
450/750 Volts PVC Insulated Cables (Cu/PVC, NYA) 5
450/750 Volts PVC Insulated Cables (Flexible Cu/PVC, NYAF) 6
300/500 Volts PVC Insulated and PVC Sheathed Cables (PVC/PVC, NYM) 8
300/500 Volts PVC Insulated and PVC Sheathed Cables (Flexible PVC/PVC, NYMHY) 10
450/750 Volts PVC Insulated and PVC Sheathed Cables (Flexible PVC/PVC, NYYHY) 11
600/1000 Volts PVC Insulated and PVC Sheathed Cables (PVC/PVC, NYY) 18
600/1000 Volts PVC Insulated, Copper Tape Shielded and PVC Sheathed Cables (PVC/PVC-S, NYSY) 30
Armoured Cables
600/1000 Volts PVC Insulated, Steel Wire Armoured and PVC Sheathed Cables (PVC/SWA/PVC, NYRY) 35
600/1000 Volts PVC Insulated, Flat Steel Wire Armoured and PVC Sheathed Cables (PVC/FSWA/PVC, NYFGbY) 41
600/1000 Volts PVC Insulated, Double Steel Tape Armoured and PVC Sheathed Cables (PVC/DSTA/PVC, NYBY) 46
SECTION 3 - XLPE Insulated CablesUnarmoured Cables
600/1000 Volts XLPE Insulated and PVC Sheathed Cables (XLPE/PVC, N2XY) 52
600/1000 Volts XLPE Insulated, Copper Tape Shielded and PVC Sheathed Cables (XLPE/PVC-S, N2XSY) 62
Armoured Cables
600/1000 Volts XLPE Insulated, Steel Wire Armoured and PVC Sheathed Cables (XLPE/SWA/PVC, N2XRY) 67
600/1000 Volts XLPE Insulated, Flat Steel Wire Armoured and PVC Sheathed Cables (XLPE/FSWA/PVC, N2XFGbY) 73
600/1000 Volts XLPE Insulated, Double Steel Tape Armoured and PVC Sheathed Cables (XLPE/DSTA/PVC, N2XBY) 78
SECTION 4 - General InformationCurrent Carrying Capacity for XLPE Insulated cable (single core) 83
Current Carrying Capacity for XLPE Insulated cable (multicore) 84
Current Carrying Capacity for PVC Insulated cable (single core) 85
Current Carrying Capacity for PVC Insulated cable (multicore) 86
Correction factor of Curent carrying capacity 87Cable arrangement for Installation purpose 88Explanation of Flame Retardant / Fire Resistant Characteristic 91
Page - 1
Section 1 - Contents & Information
Page - 2
1
Company Profile of PT. Sumi Indo Kabel Tbk
The Company was established on July 23, 1981 with its Head Officeand Factory located in Tangerang, Banten. The Company is engaged in the manufacturing of Power Cable, Telecommunication Cable &Fiber Optic, and Copper Wire.
The Company was listed in the Jakarta and Surabaya Stock Exchangesin 1990. The Company became Foreign Capital Investment (PMA)in 1994, with the participation of Sumitomo Electric Industries, Ltd.,Japan, one of the biggest in cable and wire industries in the world. Thename of Company became PT Sumi Indo Kabel Tbk. since 1999.
The Company received official recognition of its quality managementsystem standard from SGS, certification ISO 9001 : 2000 for its PowerCable & Control Cable, Telephone Cable & Fiber Optic Cable, andCopper Wire Rod in 2002. This was the first recognition in Indonesiafor Electric Cable and Wire industries.
Section 1 - Contents & Information
1 Scope
2 Conductor
The conductor shall be solid, circular stranded or compacted stranded.
3 Insulation
4 Identification of cores
Number of core Identification of coresSingle core Black (Natural for XLPE insulated)Two cores Red, BlackThree cores Red, Yellow, BlueFour cores Red, Yellow, Blue, BlackFive core or more Black insulation with white numbered code.
5 Cabling and filling
6 Metallic Shielding (if required)The metallic shielding shall consist of either one or more Copper tapes or a concentric layer of copper wires.
7 Inner sheath (armour cable only).
8 Metallic armour
9 Outer sheathThe outer sheath shall consist of a thermoplastic compound such as polyvinyl chloride (PVC),polyethylene (PE), halogen free (LSOH), etc in accordance with IEC 60502-1.
Page - 3
The cores of all cables shall be identified by color or numbered printed on the surface of insulationin accordance with the following sequence or other sequence.
The multi cores shall be laid up together with suitable filler to give the completed cable asubstantially circular cross section and bound with suitable binder tape.
The inner sheath shall consist of extruded thermoplastic compound such as :polyvinyl chloride(PVC), polyethylene (PE),halogen free (LSOH), etc in accordance to IEC 60502-1.
The metallic armour shall consist of single layer of round galvanized steel wire or flat galvanizedsteel wire and steel tape or double layer of galvanized steel tapes in accordance to IEC 60502-1.The armour of single core cables shall consist of single layer of aluminium wire or double layers ofaluminium tape as non magnetic material.
Cable Specification
These specification apply to material and constructions of cross-linked thermosetting polyethylene(XLPE) or Polivinyl chloride (PVC) insulated wire and cables for rated voltages 0.3/0.5 kV up to0.6/1(1.2) kV accordance to IEC 60502-1, Indonesia Electric Power Company (SPLN)
The conductor shall be formed from plain annealed copper or aluminium complying with IEC60228, ASTM B3 and B8.
The insulation shall be cross-linked polyethylene (XLPE) or Polivinyl chloride (PVC) in accordanceto IEC 60502-1.
Section 2 - PVC Insulated Cables Unarmoured Cables
450/750 V PVC INSULATED WIRE (Cu/PVC)acc. to IEC 60227
Copper Conductor (Solid) PVC Insulation
Copper Conductor (Stranded) PVC Insulation
Colour of Insulation : Red, White, Black, Green, Brown, Blue, Yellow, Green-yellow
450/750 V PVC INSULATED WIRE (Cu/PVC Flexible)acc. to IEC 60227
Copper Conductor (Flexible) PVC Insulation
Colour of Insulation : Red, White, Black, Green, Brown, Blue, Yellow, Green-yellow
Page - 4
Note : Special application upon request* Available product in accordance to : SPLN or other requirement.* Tin coated Copper conductor.
Section 2 - PVC Insulated CablesUnarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 450/750 V
Insulation : PVC Compound type C Operating Temperature
Colour Ident. : Red, White, Black, Green, Maximum 70°C
Blue, Yellow, Green-yellow
1.5 1 / 1.38 1.38 0.7 3.0 22 12.1 0.011 2500
1.5 7 / 0.52 1.56 0.7 3.5 23 12.1 0.010 2500
2.5 1 / 1.78 1.78 0.8 4.0 33 7.41 0.010 2500
2.5 7 / 0.67 2.01 0.8 4.0 35 7.41 0.009 2500
4 1 / 2.26 2.26 0.8 4.5 49 4.61 0.0085 2500
4 7 / 0.85 2.55 0.8 4.5 52 4.61 0.0077 2500
6 1 / 2.77 2.77 0.8 5.0 69 3.08 0.0070 2500
6 7 / 1.04 3.12 0.8 5.0 72 3.08 0.0065 2500
10 1 / 3.57 3.57 1.0 6.0 113 1.83 0.0070 2500
10 7 / 1.35 4.05 1.0 6.5 119 1.83 0.0065 2500
16 7 / 1.70 5.10 1.0 7.5 179 1.15 0.0050 2500
25 7 / 2.13 6.39 1.2 9.0 277 0.727 0.0050 2500
35 7 / 2.52 7.56 1.2 10.5 377 0.524 0.0040 2500
50 19 / 1.83 9.15 1.4 12.5 530 0.387 0.0045 2500
70 19 / 2.17 10.85 1.4 14.0 727 0.268 0.0035 2500
95 19 / 2.52 12.60 1.6 16.5 985 0.193 0.0035 2500
120 37 / 2.03 14.21 1.6 18.0 1218 0.153 0.0032 2500
150 37 / 2.27 15.89 1.8 20.0 1522 0.124 0.0032 2500
185 37 / 2.52 17.64 2.0 22.0 1873 0.0991 0.0032 2500
240 61 / 2.26 20.34 2.2 25.5 2465 0.0754 0.0032 2500
300 61 / 2.52 22.68 2.4 28.0 3055 0.0601 0.0030 2500
400 61 / 2.86 25.74 2.6 31.5 3927 0.0470 0.0028 2500
Page - 5
V/5 min
Maximum AC
Test
Voltage
Minimum
Insulation
MΩ.km
Thickness
Nominal
Resistance Resistance
wire
Conductor
of
Nominal No./
Diameter
area (approx.)
Cross-
Diameter
of wire
(approx.)
Conductorsection
mm²
(Approx.)
Insulation
Weight
Nominal
Overall
(Approx.)
No./mm Ω/kmkg/kmmmmm mm
450/750 V PVC INSULATED WIRECU/PVC (IEC 60227)
Conductor
at 70°Cat 20°C
of Diameter of
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type C Operating Temperature
Colour Ident. : Red, White, Black, Green, Maximum 70°C
Blue, Yellow, Green-yellow
1.5 1.58 0.7 3.5 22 13.30 0.010 2500
2.5 0.26 2.04 0.8 4.0 34 7.98 0.009 2500
4 0.31 2.59 0.8 4.5 50 4.95 0.007 2500
6 0.31 3.46 0.8 5.5 75 3.30 0.006 2500
10 0.41 4.62 1.0 7.0 130 1.91 0.0056 2500
16 0.41 5.66 1.0 8.0 186 1.21 0.0046 2500
25 0.41 7.06 1.2 10.0 286 0.78 0.0044 2500
35 0.41 8.43 1.2 11.0 395 0.554 0.0038 2500
50 0.41 10.07 1.4 13.5 550 0.386 0.0037 2500
70 0.51 11.97 1.4 15.0 760 0.272 0.0032 2500
95 0.51 13.73 1.6 17.5 1008 0.206 0.0032 2500
120 0.51 15.53 1.6 19.5 1270 0.161 0.0029 2500
150 0.51 17.56 1.8 22.0 1605 0.129 0.0029 2500
185 0.51 19.16 2.0 24.0 1914 0.106 0.0029 2500
240 0.51 22.0 2.2 27.0 2491 0.0801 0.0028 2500
Page - 6
Maximum MinimumNominal Nominal
Thickness Overall
section Conductor
Nominal Diameter Insulation
Cross- of of Diameter of Resistance Resistance
Weight Conductor
mm² mm
0.26
at 70°C
area (Approx.) (Approx.)(approx.)
mm mm kg/km Ω/km
(approx.)
Insulation wire at 20°C
mm V/5 minMΩ.km
Conductor AC
Maximum Test
Diameter Voltage
of wire
450/750 V PVC INSULATED WIRECU/PVC-Flexible (IEC 60227)
Section 2 - PVC Insulated Cables Unarmoured Cables
300/500 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC (NYM) - IEC 60227 , SPLN 42-2
Conductor PVC Inner coveringPVC Insulation PVC Sheath
300/500 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC Flexible (NYMHY) - IEC 60227 , SPLN 42-2
ConductorPVC Insulation PVC Sheath
450/750 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC Flexible (IEC 60227, SPLN 42-6-3)
Tape (manufacturer's option)Conductor PVC Sheath
PVC InsulationFiller (Polyprophylene yarn,or extruded filler up to request)
Page - 7
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 and 2) Uo/U - 300/500 V
Insulation : PVC Compound Operating Temperature
Inner covering : PVC Compound Maximum 70°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation : Two cores - Red,Black
Three cores - Red,Yellow, Blue
Sheath - White
TWO AND THREE CORES
No.
of
Core
-
1.5 1 / 1.38 1.38 0.7 0.4 1.2 9.5 129 12.1
7 / 0.52 1.56 0.7 0.4 1.2 10.0 138 12.1
2.5 1 / 1.78 1.78 0.8 0.4 1.2 11.0 173 7.41
7 / 0.67 2.01 0.8 0.4 1.2 11.0 184 7.41
4 1 / 2.26 2.26 0.8 0.4 1.2 12.0 222 4.61
2 7 / 0.85 2.55 0.8 0.4 1.2 12.5 239 4.61
6 1 / 2.77 2.77 0.8 0.4 1.2 13.0 294 3.08
7 / 1.04 3.12 0.8 0.4 1.2 14.0 313 3.08
10 1 / 3.57 3.57 1.0 0.6 1.4 16.0 453 1.83
7 / 1.35 4.05 1.0 0.6 1.4 17.0 492 1.83
16 7 / 1.70 5.10 1.0 0.6 1.4 19.0 668 1.15
25 7 / 2.13 6.39 1.2 0.8 1.4 23.0 998 0.727
35 7 / 2.52 7.56 1.2 1.0 1.6 26.0 1336 0.524
1.5 1 / 1.38 1.38 0.7 0.4 1.2 10.0 150 12.1
7 / 0.52 1.56 0.7 0.4 1.2 10.5 159 12.1
2.5 1 / 1.78 1.78 0.8 0.4 1.2 11.5 205 7.41
7 / 0.67 2.01 0.8 0.4 1.2 12.0 216 7.41
4 1 / 2.26 2.26 0.8 0.4 1.2 12.5 266 4.61
3 7 / 0.85 2.55 0.8 0.4 1.2 13.0 286 4.61
6 1 / 2.77 2.77 0.8 0.4 1.4 14.0 357 3.08
7 / 1.04 3.12 0.8 0.4 1.4 14.5 381 3.08
10 1 / 3.57 3.57 1.0 0.6 1.4 17.0 557 1.83
7 / 1.35 4.05 1.0 0.6 1.4 18.0 600 1.83
16 7 / 1.70 5.10 1.0 0.8 1.4 20.5 849 1.15
25 7 / 2.13 6.39 1.2 0.8 1.6 24.5 1270 0.727
35 7 / 2.52 7.56 1.2 1.0 1.6 27.5 1679 0.524
Conductor Nominal Nominal
Ω/km
Resistance
Thickness
Sheath
Weightdiameter
cable cable
of of
section
Overall Maximum
Nominal No./ Diameter Thickness
at 20°C
Conductor
Cross- Diameter of of
(approx.) (approx.)
mm kg/kmmm
300/500 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC (NYM) - IEC 60227 , SPLN 42-2
of wire Conductor Insulation
(approx.)
of
mm² No./mm
Thickness
of Inner
covering
(approx.)
mm mm
(approx.)
mm
area
Page - 8
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 and 2) Uo/U - 300/500 V
Insulation : PVC Compound Operating Temperature
Inner covering : PVC Compound Maximum 70°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation : Four core - Red,Yellow, Blue, Black
Five core - Black with numbering code
Sheath - White
FOUR AND FIVE CORES
No.
of
Core
-
1.5 1 / 1.38 1.38 0.7 0.4 1.2 11.0 177 12.1
7 / 0.52 1.56 0.7 0.4 1.2 11.5 189 12.1
2.5 1 / 1.78 1.78 0.8 0.4 1.2 12.5 247 7.41
7 / 0.67 2.01 0.8 0.4 1.2 13.0 262 7.41
4 1 / 2.26 2.26 0.8 0.4 1.4 14.0 340 4.61
4 7 / 0.85 2.55 0.8 0.4 1.4 14.5 361 4.61
6 1 / 2.77 2.77 0.8 0.4 1.4 15.5 456 3.08
7 / 1.04 3.12 0.8 0.4 1.4 16.0 482 3.08
10 1 / 3.57 3.57 1.0 0.6 1.4 18.5 690 1.83
7 / 1.35 4.05 1.0 0.6 1.4 19.5 742 1.83
16 7 / 1.70 5.10 1.0 0.8 1.4 22.5 1059 1.15
25 7 / 2.13 6.39 1.2 1.0 1.6 27.5 1616 0.727
35 7 / 2.52 7.56 1.2 1.0 1.6 30.0 2107 0.524
1.5 1 / 1.38 1.38 0.7 0.4 1.2 11.5 210 12.1
7 / 0.52 1.56 0.7 0.4 1.2 12.0 223 12.1
2.5 1 / 1.78 1.78 0.8 0.4 1.2 13.5 293 7.41
7 / 0.67 2.01 0.8 0.4 1.2 14.0 313 7.41
4 1 / 2.26 2.26 0.8 0.6 1.4 15.5 424 4.61
5 7 / 0.85 2.55 0.8 0.6 1.4 16.5 452 4.61
6 1 / 2.77 2.77 0.8 0.6 1.4 17.0 548 3.08
7 / 1.04 3.12 0.8 0.6 1.4 17.5 579 3.08
10 1 / 3.57 3.57 1.0 0.6 1.4 20.0 839 1.83
7 / 1.35 4.05 1.0 0.6 1.4 21.5 898 1.83
16 7 / 1.70 5.10 1.0 0.8 1.6 25.0 1310 1.15
25 7 / 2.13 6.39 1.2 1.0 1.6 30.0 1969 0.727
35 7 / 2.52 7.56 1.2 1.2 1.6 33.5 2617 0.524
300/500 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC (NYM) - IEC 60227 , SPLN 42-2
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of of of Resistance
Sheath cable cablesection of wire Conductor Insulation
mm mm
at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
covering
Page - 9
Ω/kmmm mm mm kg/kmmm² No./mm
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 300/500 V
Insulation : PVC Compound type D Operating Temperature
Sheath : PVC Compound type ST5 Maximum 70°C
Colour Ident. : Insulation: Two core - Red,Black
Three core - Red,Yellow, Blue
Four core - Red,Yellow, Blue, Black
Five core - Black with numbering code
Sheath - White
Number
of
Core
-
0.75 1.13 7.0 64 26.0
2 1 0.21 1.31 7.5 74 19.5
1.5 1.58 8.5 98 13.3
2.5 0.26 2.04 10.0 145 7.98
0.75 1.13 7.5 75 26.0
3 1 0.21 1.31 7.5 87 19.5
1.5 1.58 9.0 121 13.3
2.5 0.26 2.04 10.5 180 7.98
0.75 1.13 8.0 90 26.0
4 1 0.21 1.31 8.5 108 19.5
1.5 1.58 10.0 150 13.3
2.5 0.26 2.04 11.5 219 7.98
0.75 1.13 9.0 111 26.0
5 1 0.21 1.31 9.5 129 19.5
1.5 1.58 11.0 182 13.3
2.5 0.26 2.04 13.0 266 7.98
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
cable at 20°Csection of wire Conductor Insulation
(approx.) (approx.) (approx.)
Sheath cable
Ω/km
(approx.)
mm² mm mm mm mm mm kg/km
area
0.6 0.8
0.26 0.7 0.8
0.8 1.0
0.21 0.6 0.8
0.6 0.8
0.26 0.7 0.9
0.8 1.1
0.21 0.6 0.8
0.6 0.9
0.26 0.7 1.0
0.26 0.7 1.1
0.8 1.1
0.21 0.6 0.9
0.21
300/500 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC Flexible (IEC 60227, SPLN 42-6-2)
Page - 10
0.8 1.2
0.80.6
0.6 0.9
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Red,Black
Sheath - Black
TWO CORES
1.5 1.58 1.8 10.5 126 13.3
2.5 0.26 2.04 1.8 12.0 166 7.98
4 0.31 2.59 1.8 14.0 230 4.95
6 0.31 3.46 1.8 15.5 297 3.30
10 0.41 4.62 1.8 18.0 422 1.91
16 0.41 5.66 1.8 20.0 562 1.21
25 0.41 7.06 1.8 23.5 809 0.780
35 0.41 8.43 1.8 26.0 1061 0.554
50 0.41 10.07 1.8 30.5 1451 0.386
70 0.51 11.97 1.9 34.5 1949 0.272
95 0.51 13.73 2.0 39.0 2546 0.206
120 0.51 15.53 2.1 43.0 3160 0.161
Conductor
Maximum
Diameter
kg/km
1.6
450/750 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC Flexible (IEC 60227, SPLN 42-6-3)
0.26
mm mm mm
(approx.) (approx.)(approx.)(approx.)
of
Weight
mm² mmmm
of
Insulation Sheath
Thickness
area
Nominal Nominal
Conductor
Ω/km
1.4
1.4
1.6
Thickness
MaximumOverall
at 20°C
diameter
Resistance
cable
of
section Conductor
Nominal Diameter
Cross- of
of wire
of
cable
0.7
0.8
1.0
1.0
1.0
1.0
1.2
1.2
Page - 11
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Red,Yellow , Blue
Sheath - Black
THREE CORES
1.5 1.58 1.8 11.0 153 13.3
2.5 0.26 2.04 1.8 12.5 204 7.98
4 0.31 2.59 1.8 14.5 287 4.95
6 0.31 3.46 1.8 16.5 380 3.30
10 0.41 4.62 1.8 19.0 552 1.91
16 0.41 5.66 1.8 21.0 744 1.21
25 0.41 7.06 1.8 25.0 1085 0.780
35 0.41 8.43 1.8 28.0 1443 0.554
50 0.41 10.07 1.8 32.5 1986 0.386
70 0.51 11.97 2.0 37.0 2702 0.272
95 0.51 13.73 2.1 42.0 3542 0.206
120 0.51 15.53 2.2 46.0 4408 0.161
(approx.)area (approx.) (approx.) (approx.)
at 20°Csection of wire Conductor Insulation Sheath cable cable
of ResistanceofofCross- Diameter of of
Thickness diameter Weight
450/750 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC Flexible (IEC 60227, SPLN 42-6-3)
Conductor Nominal Nominal
ConductorNominal Maximum Diameter Thickness
Overall Maximum
mm² mm mm mm mm mm kg/km Ω/km
0.26
0.8
1.0
1.0
1.0
1.0
1.2
0.7
1.2
1.4
1.4
1.6
1.6
Page - 12
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Red,Yellow , Blue , Black
Sheath - Black
FOUR CORES
1.5 1.58 1.8 12.0 181 13.3
2.5 0.26 2.04 1.8 13.5 247 7.98
4 0.31 2.59 1.8 16.0 353 4.95
6 0.31 3.46 1.8 18.0 471 3.30
10 0.41 4.62 1.8 20.5 696 1.91
16 0.41 5.66 1.8 23.5 942 1.21
25 0.41 7.06 1.8 27.5 1390 0.780
35 0.41 8.43 1.8 31.0 1856 0.554
50 0.41 10.07 1.9 36.0 2579 0.386
70 0.51 11.97 2.1 41.0 3517 0.272
95 0.51 13.73 2.2 47.0 4610 0.206
120 0.51 15.53 2.4 51.5 5769 0.161
450/750 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC Flexible (IEC 60227, SPLN 42-6-3)
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
cable at 20°Csection of wire Conductor Insulation
(approx.) (approx.)
Sheath cable
(approx.)
mm² mm mm mm mm mm kg/km
area (approx.)
Ω/km
0.26
0.8
1.0
1.0
1.0
1.0
1.2
0.7
1.2
1.4
1.4
1.6
1.6
Page - 13
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
FIVE CORES
1.5 1.58 1.8 13.0 215 13.3
2.5 0.26 2.04 1.8 14.5 290 7.98
4 0.31 2.59 1.8 17.0 425 4.95
6 0.31 3.46 1.8 19.5 567 3.30
10 0.41 4.62 1.8 22.5 847 1.91
16 0.41 5.66 1.8 25.5 1154 1.21
25 0.41 7.06 1.8 30.5 1703 0.780
35 0.41 8.43 1.9 34.0 2297 0.554
50 0.41 10.07 2.0 40.0 3200 0.386
450/750 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC Flexible (IEC 60227, SPLN 42-6-3)
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
cable at 20°Csection of wire Conductor Insulation
(approx.) (approx.)
Sheath cable
(approx.)
mm² mm mm mm mm mm kg/km
area (approx.)
Ω/km
0.26
1.0
1.0
1.2
0.7
Page - 14
0.8
1.0
1.2
1.4
1.0
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 1.5 mm²
6 1.58 1.8 14.0 240 13.3
7 0.26 1.58 1.8 14.0 258 13.3
8 0.26 1.58 1.8 15.0 295 13.3
9 0.26 1.58 1.8 16.0 326 13.3
10 0.26 1.58 1.8 17.0 360 13.3
12 0.26 1.58 1.8 17.5 408 13.3
14 0.26 1.58 1.8 18.5 458 13.3
15 0.26 1.58 1.8 19.0 489 13.3
16 0.26 1.58 1.8 19.0 514 13.3
18 0.26 1.58 1.8 20.0 562 13.3
19 0.26 1.58 1.8 20.0 580 13.3
20 0.26 1.58 1.8 21.0 614 13.3
24 0.26 1.58 1.8 23.5 725 13.3
30 0.26 1.58 1.8 24.5 868 13.3
32 0.26 1.58 1.8 25.0 921 13.3
37 0.26 1.58 1.8 26.5 1034 13.3
40 0.26 1.58 1.8 27.5 1110 13.3
50 0.26 1.58 1.9 30.5 1374 13.3
52 0.26 1.58 1.9 31.5 1424 13.3
60 0.26 1.58 1.9 33.0 1617 13.3
61 0.26 1.58 1.9 33.0 1635 13.3
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
Conductor
0.7
0.7
0.7
0.7
Maximum Diameter
Ω/km
0.26 0.7
0.7
(approx.)
mm mm mm mm mm kg/km
core (approx.) (approx.) (approx.)
Sheath cable cable at 20°Cof of wire Conductor Insulation
Weight Conductor
No Diameter of of of of of Resistance
Thickness
450/750 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC Flexible (IEC 60227, SPLN 42-6-3)
Nominal Nominal Overall Maximum
Thickness diameter
Page - 15
0.7
0.7
0.7
0.7
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 2.5 mm²
6 2.04 1.8 15.5 331 7.98
7 0.26 2.04 1.8 15.5 358 7.98
8 0.26 2.04 1.8 17.0 406 7.98
9 0.26 2.04 1.8 18.0 455 7.98
10 0.26 2.04 1.8 19.5 505 7.98
12 0.26 2.04 1.8 20.0 577 7.98
14 0.26 2.04 1.8 21.0 654 7.98
15 0.26 2.04 1.8 21.5 697 7.98
16 0.26 2.04 1.8 22.0 732 7.98
18 0.26 2.04 1.8 23.0 806 7.98
19 0.26 2.04 1.8 23.0 834 7.98
20 0.26 2.04 1.8 24.0 887 7.98
24 0.26 2.04 1.8 27.0 1049 7.98
30 0.26 2.04 1.8 28.5 1266 7.98
32 0.26 2.04 1.8 29.0 1342 7.98
37 0.26 2.04 1.9 31.0 1527 7.98
40 0.26 2.04 1.9 32.0 1644 7.98
50 0.26 2.04 2.0 35.5 2037 7.98
52 0.26 2.04 2.0 36.5 2115 7.98
60 0.26 2.04 2.1 39.0 2423 7.98
61 0.26 2.04 2.1 39.0 2450 7.98
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
Ω/km
0.26 0.8
0.8
(approx.)
mm mm mm mm mm kg/km
core (approx.) (approx.) (approx.)
Resistance
of of wire Conductor Insulation Sheath cable cable at 20°C
diameter Weight Conductor
No Diameter of of of of of
Maximum Diameter Thickness Thickness
450/750 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC Flexible (IEC 60227, SPLN 42-6-3)
Conductor Nominal Nominal Overall Maximum
Page - 16
0.8
0.8
0.8
0.8
Section 2 - PVC Insulated CablesUnarmoured Cables
Constructions :Conductor (Annealed Copper)
Insulation (PVC Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Outer sheath (PVC Compound)
600/1000 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC (acc. to IEC 60502-1)
Page - 17
1 1
22
3
4
5 5
1
2
3
4
5
Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Anti termite performance.* Tin coated Copper conductor.* Polyethylene / Low smoke Halogen Free sheathed
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Sheath : PVC Compound type ST1 Maximum 70°C
Colour Ident. : Insulation - Black
Sheath - Black
SINGLE CORE
1.5 1 / 1.38 1.38 0.8 1.4 6.5 55 12.1
1.5 7 / 0.52 1.56 0.8 1.4 6.5 58 12.1
2.5 1 / 1.78 1.78 0.8 1.4 7.0 68 7.41
2.5 7 / 0.67 2.01 0.8 1.4 7.0 71 7.41
4 1 / 2.26 2.26 1.0 1.4 7.5 94 4.61
4 7 / 0.85 2.55 1.0 1.4 8.0 98 4.61
6 7 / 1.04 3.12 1.0 1.4 8.5 123 3.08
10 7 / 1.35 4.05 1.0 1.4 9.5 172 1.83
16 7 / 1.70 5.10 1.0 1.4 10.5 239 1.15
25 7 / 2.13 6.39 1.2 1.4 12.0 349 0.727
35 7 / 2.52 7.56 1.2 1.4 13.5 457 0.524
50 19 / 1.83 9.15 1.4 1.4 15.5 623 0.387
70 19 / 2.17 10.85 1.4 1.4 17.0 832 0.268
95 19 / 2.52 12.60 1.6 1.5 19.5 1114 0.193
120 37 / 2.03 14.21 1.6 1.5 21.0 1359 0.153
150 37 / 2.27 15.89 1.8 1.6 23.5 1689 0.124
185 37 / 2.52 17.64 2.0 1.7 25.5 2068 0.0991
240 61 / 2.26 20.34 2.2 1.8 29.0 2698 0.0754
300 61 / 2.52 22.68 2.4 1.9 32.0 3327 0.0601
400 61 / 2.86 25.74 2.6 2.0 36.0 4249 0.0470
500 61 / 3.20 28.80 2.8 2.1 39.5 5266 0.0366
630 91 / 2.96 32.56 2.8 2.2 43.5 6580 0.0283
800 127 / 2.85 37.05 2.8 2.3 48.0 8345 0.0221
1000 127 / 3.20 41.60 3.0 2.5 53.5 10455 0.0176
Weight
Page - 18
mm mm
Sheath cable
mm²(approx.)
of
(approx.)No./mm
areamm
ofsection
Thickness
at 20°C
kg/km(approx.) (approx.)
diameterof
cable
Ω/kmmm
No./Diameter
of wire Conductor
Overall
Insulation
MaximumConductor
ConductorNominal Cross- Resistance
NominalThickness
of
Nominal
of Diameter
PVC/PVC (IEC 60502-1)600/1000 V PVC INSULATED AND PVC SHEATHED CABLES
Section 2 - PVC Insulated CablesUnarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Black
Sheath - Black
TWO CORES
1.5 1 / 1.38 1.38 0.8 1.8 10.5 128 12.1
1.5 7 / 0.52 1.56 0.8 1.8 11.0 136 12.1
2.5 1 / 1.78 1.78 0.8 1.8 11.5 159 7.41
2.5 7 / 0.67 2.01 0.8 1.8 12.0 168 7.41
4 1 / 2.26 2.26 1.0 1.8 13.0 220 4.61
4 7 / 0.85 2.55 1.0 1.8 14.0 231 4.61
6 7 / 1.04 3.12 1.0 1.8 15.0 287 3.08
10 7 / 1.35 4.05 1.0 1.8 17.0 398 1.83
16 7 / 1.70 5.10 1.0 1.8 19.0 545 1.15
25 7 / 2.13 6.39 1.2 1.8 22.0 794 0.727
35 7 / 2.52 7.56 1.2 1.8 24.5 1032 0.524
50 19 / 1.83 9.15 1.4 1.8 28.5 1411 0.387
70 19 / 2.17 10.85 1.4 1.9 32.0 1880 0.268
95 19 / 2.52 12.60 1.6 2.0 37.0 2507 0.193
120 37 / 2.03 14.21 1.6 2.1 40.5 3065 0.153
150 37 / 2.27 15.89 1.8 2.2 45.0 3796 0.124
185 37 / 2.52 17.64 2.0 2.4 49.5 4654 0.0991
240 61 / 2.26 20.34 2.2 2.6 56.0 6067 0.0754
300 61 / 2.52 22.68 2.4 2.7 62.0 7463 0.0601
Page - 19
(approx.) (approx.)cable
mm mm
Sheath
mm
Insulation
Ω/kmkg/km
Weightof
MaximumConductorResistance
at 20°Ccable
mm
Conductor
mm² No./mm
Conductorsection area of wire(approx.) (approx.)
600/1000 V PVC INSULATED AND PVC SHEATHED CABLES
Diameterof
NominalThickness
of
NominalNo./
Diameter
PVC/PVC (IEC 60502-1)
Nominal Cross- of
ThicknessOverall
diameterof
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow , Blue
Sheath - Black
THREE CORES
1.5 1 / 1.38 1.38 0.8 1.8 11.0 155 12.1
1.5 7 / 0.52 1.56 0.8 1.8 11.5 163 12.1
2.5 1 / 1.78 1.78 0.8 1.8 12.0 195 7.41
2.5 7 / 0.67 2.01 0.8 1.8 12.5 207 7.41
4 1 / 2.26 2.26 1.0 1.8 14.0 277 4.61
4 7 / 0.85 2.55 1.0 1.8 14.5 290 4.61
6 7 / 1.04 3.12 1.0 1.8 15.5 367 3.08
10 7 / 1.35 4.05 1.0 1.8 18.0 521 1.83
16 7 / 1.70 5.10 1.0 1.8 20.0 728 1.15
25 7 / 2.13 6.39 1.2 1.8 23.5 1078 0.727
35 7 / 2.52 7.56 1.2 1.8 26.0 1410 0.524
50 6.8 1.4 1.8 25.0 1741 0.387
70 8.2 1.4 2.0 28.0 2415 0.268
95 9.7 1.6 2.1 33.0 3319 0.193
120 10.9 1.6 2.2 35.5 3963 0.153
150 11.9 1.8 2.3 38.5 4851 0.124
185 13.6 2.0 2.5 43.5 6056 0.0991
240 15.8 2.2 2.7 49.0 8072 0.0754
300 17.5 2.4 2.9 54.0 10034 0.0601
Page - 20
(approx.) (approx.) (approx.)(approx.)Sheath cable cable
600/1000 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC (IEC 60502-1)
Ω/km
Three-
Segmental
Stranded
kg/kmmm mmmm² No./mm mm mm
at 20°Csection area of wire Conductor Insulationof of ResistanceCross- Diameter of of of
Thickness diameter Weight ConductorNominal No./ Diameter ThicknessConductor Nominal Nominal Overall Maximum
Section 2 - PVC Insulated CablesUnarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow , Blue , Black
Sheath - Black
FOUR CORES
1.5 1 / 1.38 1.38 0.8 1.8 12.0 184 12.1
1.5 7 / 0.52 1.56 0.8 1.8 12.5 193 12.1
2.5 1 / 1.78 1.78 0.8 1.8 13.0 239 7.41
2.5 7 / 0.67 2.01 0.8 1.8 13.5 251 7.41
4 1 / 2.26 2.26 1.0 1.8 15.0 342 4.61
4 7 / 0.85 2.55 1.0 1.8 16.0 360 4.61
6 7 / 1.04 3.12 1.0 1.8 17.0 461 3.08
10 7 / 1.35 4.05 1.0 1.8 19.5 658 1.83
16 7 / 1.70 5.10 1.0 1.8 22.0 930 1.15
25 7 / 2.13 6.39 1.2 1.8 26.0 1378 0.727
35 7 / 2.52 7.56 1.2 1.8 29.0 1818 0.524
50 8.1 1.4 1.9 28.5 2264 0.387
70 9.7 1.4 2.1 32.0 3148 0.268
95 11.4 1.6 2.2 37.5 4326 0.193
120 12.9 1.6 2.4 41.0 5198 0.153
150 14.2 1.8 2.5 45.0 6373 0.124
185 16.0 2.0 2.7 50.0 7938 0.0991
240 18.2 2.2 2.9 56.0 10564 0.0754
300 20.6 2.4 3.1 62.5 13201 0.0601
Page - 21
(approx.) (approx.)(approx.) (approx.)mm mm kg/km Ω/kmmm² No./mm mm mm
Sheath cable cable at 20°Csection area of wire Conductor Insulationof of of ResistanceCross- Diameter of of
Thickness diameter Weight ConductorNominal No./ Diameter ThicknessConductor Nominal Nominal Overall Maximum
Stranded
Segmental
Four-
600/1000 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC (IEC 60502-1)
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
FIVE CORES
1.5 1 / 1.38 1.38 0.8 1.8 13.0 218 12.1
1.5 7 / 0.52 1.56 0.8 1.8 13.5 230 12.1
2.5 1 / 1.78 1.78 0.8 1.8 14.0 280 7.41
2.5 7 / 0.67 2.01 0.8 1.8 14.5 296 7.41
4 1 / 2.26 2.26 1.0 1.8 16.5 408 4.61
4 7 / 0.85 2.55 1.0 1.8 17.5 430 4.61
6 7 / 1.04 3.12 1.0 1.8 18.5 556 3.08
10 7 / 1.35 4.05 1.0 1.8 21.5 800 1.83
16 7 / 1.70 5.10 1.0 1.8 24.0 1135 1.15
25 7 / 2.13 6.39 1.2 1.8 28.5 1692 0.727
35 7 / 2.52 7.56 1.2 1.9 32.0 2257 0.524
50 19 / 1.83 9.15 1.4 2.1 38.0 3152 0.387
Page - 22
(approx.) (approx.)
Maximum
(approx.) (approx.)
600/1000 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC (IEC 60502-1)
Sheath cable cable at 20°C
Ω/kmmm² No./mm mm mm mm mm kg/km
section area of wire Conductor InsulationResistanceCross- Diameter of of of of of ConductorNominal No./ Diameter Thickness Thickness diameter Weight
Conductor Nominal Nominal Overall
Section 2 - PVC Insulated CablesUnarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 1.5 mm² (Solid conductor)
No Nominal of Cross-section
core area
mm²
6 1.5 1 / 1.38 1.38 0.8 1.8 14.0 245 12.1
7 1.5 1 / 1.38 1.38 0.8 1.8 14.0 263 12.1
8 1.5 1 / 1.38 1.38 0.8 1.8 15.0 297 12.1
9 1.5 1 / 1.38 1.38 0.8 1.8 16.0 332 12.1
10 1.5 1 / 1.38 1.38 0.8 1.8 17.0 367 12.1
12 1.5 1 / 1.38 1.38 0.8 1.8 17.5 416 12.1
14 1.5 1 / 1.38 1.38 0.8 1.8 18.5 468 12.1
15 1.5 1 / 1.38 1.38 0.8 1.8 19.0 500 12.1
16 1.5 1 / 1.38 1.38 0.8 1.8 19.5 525 12.1
18 1.5 1 / 1.38 1.38 0.8 1.8 20.0 575 12.1
19 1.5 1 / 1.38 1.38 0.8 1.8 20.0 593 12.1
20 1.5 1 / 1.38 1.38 0.8 1.8 21.0 628 12.1
21 1.5 1 / 1.38 1.38 0.8 1.8 21.0 650 12.1
24 1.5 1 / 1.38 1.38 0.8 1.8 23.5 742 12.1
30 1.5 1 / 1.38 1.38 0.8 1.8 24.5 889 12.1
32 1.5 1 / 1.38 1.38 0.8 1.8 25.0 943 12.1
37 1.5 1 / 1.38 1.38 0.8 1.8 26.5 1059 12.1
40 1.5 1 / 1.38 1.38 0.8 1.8 27.5 1139 12.1
50 1.5 1 / 1.38 1.38 0.8 1.9 30.5 1408 12.1
52 1.5 1 / 1.38 1.38 0.8 1.9 31.5 1460 12.1
60 1.5 1 / 1.38 1.38 0.8 2.0 33.5 1674 12.1
61 1.5 1 / 1.38 1.38 0.8 2.0 33.5 1692 12.1
Page - 23
cable cableInsulation Sheath(approx.) (approx.)(approx.) (approx.)
at 20°C
No./mm mm mm mm mm kg/km Ω/km
of wire Conductor
diameter Weight ConductorDiameter of of of of of Resistance
No./ Diameter Thickness Thickness
600/1000 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall Maximum
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 1.5 mm² (Stranded conductor)
No Nominal of Cross-section
core area
mm²
6 1.5 7 / 0.52 1.56 0.8 1.8 14.5 259 12.1
7 1.5 7 / 0.52 1.56 0.8 1.8 14.5 278 12.1
8 1.5 7 / 0.52 1.56 0.8 1.8 15.5 314 12.1
9 1.5 7 / 0.52 1.56 0.8 1.8 16.5 351 12.1
10 1.5 7 / 0.52 1.56 0.8 1.8 18.0 389 12.1
12 1.5 7 / 0.52 1.56 0.8 1.8 18.5 439 12.1
14 1.5 7 / 0.52 1.56 0.8 1.8 19.0 494 12.1
15 1.5 7 / 0.52 1.56 0.8 1.8 19.5 527 12.1
16 1.5 7 / 0.52 1.56 0.8 1.8 20.0 554 12.1
18 1.5 7 / 0.52 1.56 0.8 1.8 21.0 608 12.1
19 1.5 7 / 0.52 1.56 0.8 1.8 21.0 626 12.1
20 1.5 7 / 0.52 1.56 0.8 1.8 22.0 663 12.1
21 1.5 7 / 0.52 1.56 0.8 1.8 22.0 687 12.1
24 1.5 7 / 0.52 1.56 0.8 1.8 24.5 786 12.1
30 1.5 7 / 0.52 1.56 0.8 1.8 26.0 939 12.1
32 1.5 7 / 0.52 1.56 0.8 1.8 26.5 996 12.1
37 1.5 7 / 0.52 1.56 0.8 1.8 28.0 1119 12.1
40 1.5 7 / 0.52 1.56 0.8 1.8 29.0 1204 12.1
50 1.5 7 / 0.52 1.56 0.8 1.9 32.0 1488 12.1
52 1.5 7 / 0.52 1.56 0.8 1.9 33.0 1543 12.1
60 1.5 7 / 0.52 1.56 0.8 2.0 35.0 1770 12.1
61 1.5 7 / 0.52 1.56 0.8 2.0 35.0 1788 12.1
Page - 24
600/1000 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall MaximumNo./ Diameter Thickness Thickness
at 20°CDiameter of of of
of wire Conductor Insulation Sheath cable
Conductorof of Resistance
diameter Weight
cable(approx.) (approx.) (approx.) (approx.)
kg/km Ω/kmNo./mm mm mm mm mm
Section 2 - PVC Insulated CablesUnarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 2.5 mm² (Solid conductor)
No Nominal of Cross-section
core area
mm²
6 2.5 1 / 1.78 1.78 0.8 1.8 15.0 320 7.41
7 2.5 1 / 1.78 1.78 0.8 1.8 15.0 348 7.41
8 2.5 1 / 1.78 1.78 0.8 1.8 16.0 394 7.41
9 2.5 1 / 1.78 1.78 0.8 1.8 17.0 442 7.41
10 2.5 1 / 1.78 1.78 0.8 1.8 18.5 488 7.41
12 2.5 1 / 1.78 1.78 0.8 1.8 19.0 558 7.41
14 2.5 1 / 1.78 1.78 0.8 1.8 20.0 636 7.41
15 2.5 1 / 1.78 1.78 0.8 1.8 20.5 673 7.41
16 2.5 1 / 1.78 1.78 0.8 1.8 21.0 710 7.41
18 2.5 1 / 1.78 1.78 0.8 1.8 22.0 783 7.41
19 2.5 1 / 1.78 1.78 0.8 1.8 22.0 811 7.41
20 2.5 1 / 1.78 1.78 0.8 1.8 23.0 863 7.41
21 2.5 1 / 1.78 1.78 0.8 1.8 23.5 890 7.41
24 2.5 1 / 1.78 1.78 0.8 1.8 26.0 1018 7.41
30 2.5 1 / 1.78 1.78 0.8 1.8 27.5 1232 7.41
32 2.5 1 / 1.78 1.78 0.8 1.8 28.0 1303 7.41
37 2.5 1 / 1.78 1.78 0.8 1.9 29.5 1487 7.41
40 2.5 1 / 1.78 1.78 0.8 1.9 30.5 1600 7.41
50 2.5 1 / 1.78 1.78 0.8 2.0 34.0 1981 7.41
52 2.5 1 / 1.78 1.78 0.8 2.0 35.0 2060 7.41
60 2.5 1 / 1.78 1.78 0.8 2.1 37.0 2359 7.41
61 2.5 1 / 1.78 1.78 0.8 2.1 37.0 2387 7.41
600/1000 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC (IEC 60502-1)
MaximumConductor
Page - 25
Overalldiameter Weight ConductorThickness
Nominal NominalNo./ Diameter
of of Diameter of of ofThickness
Resistanceof wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.)No./mm mm mm mm
(approx.)mm kg/km Ω/km
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 2.5 mm² (Stranded conductor)
No Nominal of Cross-section
core area
mm²
6 2.5 7 / 0.67 2.01 0.8 1.8 15.5 338 7.41
7 2.5 7 / 0.67 2.01 0.8 1.8 15.5 365 7.41
8 2.5 7 / 0.67 2.01 0.8 1.8 17.0 415 7.41
9 2.5 7 / 0.67 2.01 0.8 1.8 18.0 465 7.41
10 2.5 7 / 0.67 2.01 0.8 1.8 19.5 515 7.41
12 2.5 7 / 0.67 2.01 0.8 1.8 20.0 590 7.41
14 2.5 7 / 0.67 2.01 0.8 1.8 21.0 669 7.41
15 2.5 7 / 0.67 2.01 0.8 1.8 21.5 713 7.41
16 2.5 7 / 0.67 2.01 0.8 1.8 22.0 749 7.41
18 2.5 7 / 0.67 2.01 0.8 1.8 23.0 826 7.41
19 2.5 7 / 0.67 2.01 0.8 1.8 23.0 854 7.41
20 2.5 7 / 0.67 2.01 0.8 1.8 24.0 908 7.41
21 2.5 7 / 0.67 2.01 0.8 1.8 24.5 938 7.41
24 2.5 7 / 0.67 2.01 0.8 1.8 27.0 1074 7.41
30 2.5 7 / 0.67 2.01 0.8 1.8 28.5 1298 7.41
32 2.5 7 / 0.67 2.01 0.8 1.8 29.0 1377 7.41
37 2.5 7 / 0.67 2.01 0.8 1.9 31.0 1567 7.41
40 2.5 7 / 0.67 2.01 0.8 1.9 32.5 1687 7.41
50 2.5 7 / 0.67 2.01 0.8 2.0 35.5 2088 7.41
52 2.5 7 / 0.67 2.01 0.8 2.0 36.5 2168 7.41
60 2.5 7 / 0.67 2.01 0.8 2.1 39.0 2488 7.41
61 2.5 7 / 0.67 2.01 0.8 2.1 39.0 2515 7.41
Page - 26
600/1000 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall MaximumNo./ Diameter Thickness Thickness
at 20°CDiameter of of of
of wire Conductor Insulation Sheath cable
Conductorof of Resistance
diameter Weight
cable(approx.) (approx.) (approx.) (approx.)
kg/km Ω/kmNo./mm mm mm mm mm
Section 2 - PVC Insulated CablesUnarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 clas 1) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 4 mm² (Solid conductor)
No Nominal of Cross-section
core area
mm²
6 4 1 / 2.26 2.26 1.0 1.8 17.5 465 4.61
7 4 1 / 2.26 2.26 1.0 1.8 17.5 508 4.61
8 4 1 / 2.26 2.26 1.0 1.8 19.0 579 4.61
9 4 1 / 2.26 2.26 1.0 1.8 20.5 650 4.61
10 4 1 / 2.26 2.26 1.0 1.8 22.0 722 4.61
12 4 1 / 2.26 2.26 1.0 1.8 23.5 831 4.61
14 4 1 / 2.26 2.26 1.0 1.8 24.0 950 4.61
15 4 1 / 2.26 2.26 1.0 1.8 24.5 1012 4.61
16 4 1 / 2.26 2.26 1.0 1.8 25.5 1068 4.61
18 4 1 / 2.26 2.26 1.0 1.8 26.5 1178 4.61
19 4 1 / 2.26 2.26 1.0 1.8 26.5 1221 4.61
20 4 1 / 2.26 2.26 1.0 1.8 27.5 1294 4.61
21 4 1 / 2.26 2.26 1.0 1.8 28.0 1344 4.61
24 4 1 / 2.26 2.26 1.0 1.9 31.5 1555 4.61
30 4 1 / 2.26 2.26 1.0 2.0 33.5 1904 4.61
32 4 1 / 2.26 2.26 1.0 2.0 34.0 2020 4.61
37 4 1 / 2.26 2.26 1.0 2.1 26.5 2300 4.61
40 4 1 / 2.26 2.26 1.0 2.1 37.5 2478 4.61
50 4 1 / 2.26 2.26 1.0 2.3 42.0 3090 4.61
52 4 1 / 2.26 2.26 1.0 2.3 43.0 3212 4.61
60 4 1 / 2.26 2.26 1.0 2.4 46.0 3678 4.61
61 4 1 / 2.26 2.26 1.0 2.4 46.0 3721 4.61
Page - 27
kg/km Ω/kmNo./mm mm mm mm mm
cable(approx.) (approx.) (approx.) (approx.)
Conductorof of Resistance
diameter Weight
at 20°CDiameter of of of
of wire Conductor Insulation Sheath cable
No./ Diameter Thickness Thickness
600/1000 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall Maximum
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 clas 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70°C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 4 mm² (Stranded conductor)
No Nominal of Cross-section
core area
mm²
6 4 7 / 0.85 2.55 1.0 1.8 18.5 491 4.61
7 4 7 / 0.85 2.55 1.0 1.8 18.5 535 4.61
8 4 7 / 0.85 2.55 1.0 1.8 20.0 610 4.61
9 4 7 / 0.85 2.55 1.0 1.8 21.5 686 4.61
10 4 7 / 0.85 2.55 1.0 1.8 23.5 760 4.61
12 4 7 / 0.85 2.55 1.0 1.8 24.0 875 4.61
14 4 7 / 0.85 2.55 1.0 1.8 25.5 1000 4.61
15 4 7 / 0.85 2.55 1.0 1.8 26.0 1066 4.61
16 4 7 / 0.85 2.55 1.0 1.8 27.0 1126 4.61
18 4 7 / 0.85 2.55 1.0 1.8 28.0 1243 4.61
19 4 7 / 0.85 2.55 1.0 1.8 28.0 1287 4.61
20 4 7 / 0.85 2.55 1.0 1.8 29.0 1364 4.61
21 4 7 / 0.85 2.55 1.0 1.8 29.5 1417 4.61
24 4 7 / 0.85 2.55 1.0 1.9 33.0 1638 4.61
30 4 7 / 0.85 2.55 1.0 2.0 35.5 2006 4.61
32 4 7 / 0.85 2.55 1.0 2.0 36.0 2128 4.61
37 4 7 / 0.85 2.55 1.0 2.1 38.5 2424 4.61
40 4 7 / 0.85 2.55 1.0 2.1 40.0 2612 4.61
50 4 7 / 0.85 2.55 1.0 2.3 44.5 3254 4.61
52 4 7 / 0.85 2.55 1.0 2.3 45.5 3380 4.61
60 4 7 / 0.85 2.55 1.0 2.4 48.5 3877 4.61
61 4 7 / 0.85 2.55 1.0 2.4 48.5 3922 4.61
Page - 28
600/1000 V PVC INSULATED AND PVC SHEATHED CABLESPVC/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall MaximumNo./ Diameter Thickness Thickness
at 20°CDiameter of of of
of wire Conductor Insulation Sheath cable
Conductorof of Resistance
diameter Weight
cable(approx.) (approx.) (approx.) (approx.)
kg/km Ω/kmNo./mm mm mm mm mm
Section 2 - PVC Insulated CablesUnarmoured Cables
Constructions : Conductor (Annealed Copper)
Insulation (PVC Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Copper Tape screen
Binding tape (Manufacturer's option)
Outer sheath (PVC Compound)
600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLESPVC/PVC-S (IEC 60502-1)
Page - 29
1
23
4
5
6
7
1
2
3
4
5
7
6
Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Anti termite performance.* Tin coated Copper conductor.* Copper wire screen.* Polyethylene / Low smoke Halogen Free sheathed
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Black
Sheath - Black
TWO CORES
1.5 1 / 1.38 1.38 0.8 0.1 1.8 10.5 145 12.1
1.5 7 / 0.52 1.56 0.8 0.1 1.8 11.0 147 12.1
2.5 1 / 1.78 1.78 0.8 0.1 1.8 11.5 176 7.41
2.5 7 / 0.67 2.01 0.8 0.1 1.8 11.5 179 7.41
4 1 / 2.26 2.26 1.0 0.1 1.8 13.0 240 4.61
4 7 / 0.85 2.55 1.0 0.1 1.8 13.5 246 4.61
6 7 / 1.04 3.12 1.0 0.1 1.8 14.5 304 3.08
10 7 / 1.35 4.05 1.0 0.1 1.8 16.5 418 1.83
16 7 / 1.70 5.10 1.0 0.1 1.8 18.5 568 1.15
25 7 / 2.13 6.39 1.2 0.1 1.8 22.0 822 0.727
35 7 / 2.52 7.56 1.2 0.1 1.8 24.5 1064 0.524
50 19 / 1.83 9.15 1.4 0.1 1.8 28.5 1450 0.387
70 19 / 2.17 10.85 1.4 0.1 1.9 32.0 1910 0.268
95 19 / 2.52 12.60 1.6 0.1 2.0 36.5 2542 0.193
120 37 / 2.03 14.21 1.6 0.1 2.1 40.0 3103 0.153
150 37 / 2.27 15.89 1.8 0.1 2.2 44.5 3840 0.124
185 37 / 2.52 17.64 2.0 0.1 2.4 49.0 4679 0.0991
240 61 / 2.26 20.34 2.2 0.1 2.6 55.5 6096 0.0754
300 61 / 2.52 22.68 2.4 0.1 2.7 61.5 7523 0.0601
Nominal
Cross- of
Thickness
Overall
diameter
of
Nominal
Thickness
600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES
Diameter
of
Nominal
Thickness
of
Nominal
No./
Diameter
PVC/PVC-S (IEC 60502-1)
mm
Conductor
mm² No./mm
Conductorsection area of wire
(approx.) (approx.)
Ω/kmkg/km
Weight
of
Maximum
Conductor
Resistance
at 20°Ccablecable
mm mm
Sheath
mm
Insulation
(approx.) (approx.) (approx.)
of
Copper tape
mm
Page - 30
Section 2 - PVC Insulated CablesUnarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow , Blue
Sheath - Black
THREE CORES
1.5 1 / 1.38 1.38 0.8 0.1 1.8 11.0 173 12.1
1.5 7 / 0.52 1.56 0.8 0.1 1.8 11.5 174 12.1
2.5 1 / 1.78 1.78 0.8 0.1 1.8 12.0 214 7.41
2.5 7 / 0.67 2.01 0.8 0.1 1.8 12.5 220 7.41
4 1 / 2.26 2.26 1.0 0.1 1.8 14.0 298 4.61
4 7 / 0.85 2.55 1.0 0.1 1.8 14.5 306 4.61
6 7 / 1.04 3.12 1.0 0.1 1.8 15.0 385 3.08
10 7 / 1.35 4.05 1.0 0.1 1.8 17.5 542 1.83
16 7 / 1.70 5.10 1.0 0.1 1.8 20.0 753 1.15
25 7 / 2.13 6.39 1.2 0.1 1.8 23.5 1108 0.727
35 7 / 2.52 7.56 1.2 0.1 1.8 26.0 1445 0.524
50 6.8 1.4 0.1 1.9 25.0 1774 0.387
70 8.2 1.4 0.1 2.0 28.0 2439 0.268
95 9.7 1.6 0.1 2.1 32.5 3348 0.193
120 10.9 1.6 0.1 2.2 35.0 3994 0.153
150 11.9 1.8 0.1 2.4 38.5 4885 0.124
185 13.6 2.0 0.1 2.5 43.0 6076 0.0991
240 15.8 2.2 0.1 2.7 48.5 8095 0.0754
300 17.5 2.4 0.1 2.9 53.5 10060 0.0601
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
of of ResistanceCross- Diameter of of
at 20°Csection area of wire Conductor Insulation
mm² No./mm mm mm
Stranded
kg/kmmm mm
600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLESPVC/PVC-S (IEC 60502-1)
Ω/km
Three-
Segmental
(approx.) (approx.) (approx.)(approx.)
Sheath cable cable
of
Nominal
Thickness
of
Copper tape
mm
(approx.)
Page - 31
Section 2 - PVC Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow , Blue , Black
Sheath - Black
FOUR CORES
1.5 1 / 1.38 1.38 0.8 0.1 1.8 12.0 202 12.1
1.5 7 / 0.52 1.56 0.8 0.1 1.8 12.5 206 12.1
2.5 1 / 1.78 1.78 0.8 0.1 1.8 13.0 260 7.41
2.5 7 / 0.67 2.01 0.8 0.1 1.8 13.5 265 7.41
4 1 / 2.26 2.26 1.0 0.1 1.8 15.0 366 4.61
4 7 / 0.85 2.55 1.0 0.1 1.8 15.5 378 4.61
6 7 / 1.04 3.12 1.0 0.1 1.8 17.0 482 3.08
10 7 / 1.35 4.05 1.0 0.1 1.8 19.5 682 1.83
16 7 / 1.70 5.10 1.0 0.1 1.8 21.5 957 1.15
25 7 / 2.13 6.39 1.2 0.1 1.8 26.0 1412 0.727
35 7 / 2.52 7.56 1.2 0.1 1.8 28.5 1856 0.524
50 8.1 1.4 0.1 2.0 28.5 2302 0.387
70 9.7 1.4 0.1 2.1 32.0 3177 0.268
95 11.4 1.6 0.1 2.2 37.0 4360 0.193
120 12.9 1.6 0.1 2.4 40.5 5217 0.153
150 14.2 1.8 0.1 2.5 44.5 6394 0.124
185 16.0 2.0 0.1 2.7 49.5 7962 0.0991
240 18.2 2.2 0.1 2.9 55.5 10591 0.0754
300 20.6 2.4 0.1 3.1 61.5 13179 0.0601
Stranded
Segmental
Four-
600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLESPVC/PVC-S (IEC 60502-1)
Conductor Nominal Nominal Overall MaximumNominal
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section area of wire Conductor Insulation Sheath cable cable at 20°C
mm² No./mm mm mm mm mm kg/km Ω/km
(approx.) (approx.) (approx.) (approx.)
Thickness
of
Copper tape
mm
(approx.)
Page - 32
Section 2 - PVC Insulated CablesUnarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
FIVE CORES
1.5 1 / 1.38 1.38 0.8 0.1 1.8 12.5 238 12.1
1.5 7 / 0.52 1.56 0.8 0.1 1.8 13.5 244 12.1
2.5 1 / 1.78 1.78 0.8 0.1 1.8 14.0 302 7.41
2.5 7 / 0.67 2.01 0.8 0.1 1.8 14.5 312 7.41
4 1 / 2.26 2.26 1.0 0.1 1.8 16.5 434 4.61
4 7 / 0.85 2.55 1.0 0.1 1.8 17.0 450 4.61
6 7 / 1.04 3.12 1.0 0.1 1.8 18.5 578 3.08
10 7 / 1.35 4.05 1.0 0.1 1.8 21.0 827 1.83
16 7 / 1.70 5.10 1.0 0.1 1.8 24.0 1166 1.15
25 7 / 2.13 6.39 1.2 0.1 1.8 28.5 1730 0.727
35 7 / 2.52 7.56 1.2 0.1 1.9 31.5 2286 0.524
50 19 / 1.83 9.15 1.4 0.1 2.1 37.5 3057 0.387
Conductor Nominal Nominal OverallNominal
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section area of wire Conductor Insulation
mm² No./mm mm mm mm mm kg/km Ω/km
(approx.) (approx.)
600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLESPVC/PVC-S (IEC 60502-1)
Sheath cable cable at 20°C
(approx.) (approx.)
Maximum
mm
(approx.)
Page - 33
Thickness
of
Copper tape
Section 2 - PVC Insulated Cables Armoured Cables
Constructions :Conductor (Annealed Copper)
Insulation (PVC Compound)
Inner Covering (PVC Compound)
Round Aluminium Wire armour
Binding tape (Manufacturer's option)
Outer sheath (PVC Compound)
Constructions :Conductor (Annealed Copper)
Insulation (PVC Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Inner Covering (PVC Compound)
Galvanized Round Steel Wire armour
Binding tape (Manufacturer's option)
Outer sheath (PVC Compound)
Page - 34
600/1000 V PVC INSULATED, ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLESPVC/AWA/PVC (acc. to IEC 60502-1)
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLESPVC/SWA/PVC (acc. to IEC 60502-1)
11
2
3
5
4
6
7
8
2
3
4
5
6
7
8
1
2
3
4
5
6
1
2
3
4
5
6
Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Anti termite performance.* Tin coated Copper conductor.* Polyethylene / Low smoke Halogen Free sheathed
Section 2 - PVC Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Inner covering : PVC Compound ST1 Maximum 70°C
Armour : Aluminium Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black
Sheath - Black
SINGLE CORE
16 7 / 1.70 5.10 1.0 1.0 0.8 1.8 14.5 370 1.15
25 7 / 2.13 6.39 1.2 1.0 0.8 1.8 16.5 495 0.727
35 7 / 2.52 7.56 1.2 1.0 0.8 1.8 17.5 620 0.524
50 19 / 1.83 9.15 1.4 1.0 1.25 1.8 20.5 845 0.387
70 19 / 2.17 10.85 1.4 1.0 1.25 1.8 22.0 1075 0.268
95 19 / 2.52 12.60 1.6 1.0 1.25 1.8 24.5 1380 0.193
120 37 / 2.03 14.21 1.6 1.0 1.6 1.8 27.0 1705 0.153
150 37 / 2.27 15.89 1.8 1.0 1.6 1.8 29.0 2054 0.124
185 37 / 2.52 17.64 2.0 1.0 1.6 1.8 31.0 2450 0.0991
240 61 / 2.26 20.34 2.2 1.0 1.6 1.9 34.0 3110 0.0754
300 61 / 2.52 22.68 2.4 1.0 2.0 2.0 38.0 3865 0.0601
400 61 / 2.86 25.74 2.6 1.2 2.0 2.1 42.0 4885 0.0470
500 61 / 3.20 28.80 2.8 1.2 2.0 2.2 46.0 5965 0.0366
630 91 / 2.96 32.56 2.8 1.2 2.0 2.4 50.0 7335 0.0283
800 127 / 2.85 37.05 2.8 1.4 2.5 2.5 56.0 9410 0.0221
1000 127 / 3.20 41.60 3.0 1.4 2.5 2.7 61.0 11635 0.0176
Nominal
mm
Nominal
Thickness
of inner
covering
(approx.)
mm
(approx.)
PVC/AWA/PVC (IEC 60502-1)600/1000 V PVC INSULATED,ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLES
Nominal
Cross- Resistance
Nominal
Thickness
of
Nominal
No./
Diameter
of wire Conductor
Overall
Insulation
Maximum
Conductor
Conductor
Ω/kmmm
of
Thickness
at 20°C
kg/km
(approx.) (approx.)
diameter
of
mm²
(approx.)(approx.)
No./mm
area
mm
section
Weight
of
cable
Aluminium
wire
diameter ofDiameter
of
Page - 35
mm mm
Sheath cable
Section 2 - PVC Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Black
Sheath - Black
TWO CORES
1.5 1 / 1.38 1.38 0.8 1.0 0.8 1.8 14.0 332 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 1.8 14.5 347 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 1.8 15.0 380 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 1.8 15.5 395 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 1.8 16.5 473 4.61
4 7 / 0.85 2.55 1.0 1.0 0.8 1.8 17.5 494 4.61
6 7 / 1.04 3.12 1.0 1.0 1.25 1.8 19.0 667 3.08
10 7 / 1.35 4.05 1.0 1.0 1.25 1.8 21.0 837 1.83
16 7 / 1.70 5.10 1.0 1.0 1.25 1.8 23.0 1019 1.15
25 7 / 2.13 6.39 1.2 1.0 1.6 1.8 27.5 1507 0.727
35 7 / 2.52 7.56 1.2 1.0 1.6 1.8 30.0 1810 0.524
50 19 / 1.83 9.15 1.4 1.0 1.6 1.9 34.0 2318 0.387
70 19 / 2.17 10.85 1.4 1.0 2.0 2.0 38.0 3122 0.268
95 19 / 2.52 12.60 1.6 1.2 2.0 2.2 43.5 3987 0.193
120 37 / 2.03 14.21 1.6 1.2 2.0 2.3 47.0 4695 0.153
150 37 / 2.27 15.89 1.8 1.2 2.5 2.4 52.0 5994 0.124
185 37 / 2.52 17.64 2.0 1.4 2.5 2.6 57.0 7109 0.0991
240 61 / 2.26 20.34 2.2 1.4 2.5 2.8 63.5 8827 0.0754
300 61 / 2.52 22.68 2.4 1.6 2.5 2.9 70.0 10574 0.0601
(approx.)
mm mm mm kg/kmmmmm
section of wire Conductor
mm² No./mm mm
area (approx.) (approx.)
Cross- Diameter of of
Maximum
(approx.)
Insulation
Conductor
of of of
Thickness
of Inner
covering
Diameter Thickness
OverallNominal Nominal
Diameter Weightdiameter
Nominal
cable cable at 20°C
(approx.)
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLESPVC/SWA/PVC (IEC 60502-1)
Thickness
Sheath
Conductor
Ω/km
Resistance
Nominal No./
of Galv.
Steel wire
Page - 36
Section 2 - PVC Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow, Blue
Sheath - Black
THREE CORES
1.5 1 / 1.38 1.38 0.8 1.0 0.8 1.8 14.5 371 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 1.8 15.0 385 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 1.8 15.5 429 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 1.8 16.0 446 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 1.8 18.0 637 4.61
4 7 / 0.85 2.55 1.0 1.0 1.25 1.8 18.5 660 4.61
6 7 / 1.04 3.12 1.0 1.0 1.25 1.8 20.0 768 3.08
10 7 / 1.35 4.05 1.0 1.0 1.25 1.8 22.0 973 1.83
16 7 / 1.70 5.10 1.0 1.0 1.25 1.8 24.0 1229 1.15
25 7 / 2.13 6.39 1.2 1.0 1.6 1.8 29.0 1819 0.727
35 7 / 2.52 7.56 1.2 1.0 1.6 1.8 31.5 2230 0.524
50 6.8 1.4 1.0 1.6 2.0 30.5 2558 0.387
70 8.2 1.4 1.2 2.0 2.1 34.5 3577 0.268
95 9.7 1.6 1.2 2.0 2.2 39.0 4653 0.193
120 10.9 1.6 1.2 2.0 2.3 42.0 5410 0.153
150 11.9 1.8 1.4 2.5 2.5 46.0 6830 0.124
185 13.6 2.0 1.4 2.5 2.7 51.0 8260 0.0991
240 15.8 2.2 1.6 2.5 2.9 57.0 10632 0.0754
300 17.5 2.4 1.6 2.5 3.1 62.0 12795 0.0601
area (approx.)
Sector Shape
mm mm
(approx.)
mm² No./mm Ω/km
(approx.) (approx.)
mm mm kg/km
(approx.)
mm mm
Maximum
Sheath cable
Thickness
Resistance
cable at 20°C
Conductor Nominal Nominal OverallNominal
ConductorNominal No./ Diameter Thickness Thickness Diameter
of of of Galv. ofof Inner
diameter Weight
Conductor Insulation
Cross- Diameter of of
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLESPVC/SWA/PVC (IEC 60502-1)
Page - 37
covering Steel wiresection of wire
stranded
Section 2 - PVC Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow, Blue, Black
Sheath - Black
FOUR CORES
1.5 1 / 1.38 1.38 0.8 1.0 0.8 1.8 15.5 412 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 1.8 16.0 434 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 1.8 16.5 486 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 1.8 17.0 508 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 1.8 19.5 736 4.61
4 7 / 0.85 2.55 1.0 1.0 1.25 1.8 20.0 762 4.61
6 7 / 1.04 3.12 1.0 1.0 1.25 1.8 21.0 894 3.08
10 7 / 1.35 4.05 1.0 1.0 1.25 1.8 23.5 1142 1.83
16 7 / 1.70 5.10 1.0 1.0 1.6 1.8 27.0 1621 1.15
25 7 / 2.13 6.39 1.2 1.0 1.6 1.8 31.0 2183 0.727
35 7 / 2.52 7.56 1.2 1.0 1.6 1.9 34.0 2698 0.524
50 8.1 1.4 1.2 2.0 2.1 35.0 3467 0.387
70 9.7 1.4 1.2 2.0 2.2 38.5 4455 0.268
95 11.4 1.6 1.2 2.5 2.4 44.5 6222 0.193
120 12.9 1.6 1.4 2.5 2.5 48.5 7248 0.153
150 14.2 1.8 1.4 2.5 2.7 52.5 8663 0.124
185 16.0 2.0 1.6 2.5 2.9 58.0 10503 0.0991
240 18.2 2.2 1.6 2.5 3.1 63.5 13414 0.0754
300 20.6 2.4 1.6 2.5 3.3 70.0 16298 0.0601
Conductor Nominal MaximumNominal
PVC/SWA/PVC (IEC 60502-1)
Weight ConductorNominal No./ Diameter Thickness Thickness Diameter
of ResistanceCross- Diameter of of of Inner of Galv. of
at 20°Csection of wire Conductor Insulation covering Steel wire Sheath cable
mm² No./mm mm
cable
area (approx.) (approx.) (approx.) (approx.)
mm
(approx.)
kg/km
stranded
Ω/km
Sector Shape
mm mm
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
Page - 38
mm
of
mm
Thickness
Nominal
diameter
Overall
Section 2 - PVC Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
FIVE CORES
1.5 1 / 1.38 1.38 0.8 1.0 0.8 1.8 16.5 465 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 1.8 17.0 488 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 1.8 17.5 551 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 1.8 18.0 572 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 1.8 20.5 835 4.61
4 7 / 0.85 2.55 1.0 1.0 1.25 1.8 21.5 865 4.61
6 7 / 1.04 3.12 1.0 1.0 1.25 1.8 22.5 1021 3.08
10 7 / 1.35 4.05 1.0 1.0 1.6 1.8 26.5 1479 1.83
16 7 / 1.70 5.10 1.0 1.0 1.60 1.8 29.0 1893 1.15
25 7 / 2.13 6.39 1.2 1.0 1.6 1.9 33.5 2577 0.727
35 7 / 2.52 7.56 1.2 1.0 2.0 2.0 38.0 3468 0.524
50 19 / 1.83 9.15 1.4 1.2 2.0 2.2 44.0 4503 0.387
kg/km Ω/kmmm mm mm mmmm² No./mm mm mm
cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
of Resistance
section of wire Conductor Insulation covering Steel wire Sheath cable
Weight Conductor
Cross- Diameter of of of Inner of Galv. of of
Thickness Diameter Thickness diameterNominal No./ Diameter Thickness
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLESPVC/SWA/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall MaximumNominal
Page - 39
Section 2 - PVC Insulated Cables Armoured Cables
C Constructions :Conductor (Annealed Copper)
Insulation (PVC Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Inner Covering (PVC Compound)
Galvanized Flat Steel Wire armour
Galvanized Steel Tape binding
Outer sheath (PVC Compound)
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLESPVC/FSWA/PVC (acc. to IEC 60502-1)
Page - 40
1
2
34
5
6
7
8
1
2
3
4
5
6
7
Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Anti termite performance.* Tin coated Copper conductor.* Polyethylene / Low smoke Halogen Free sheathed
Section 2 - PVC Insulated CablesArmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Black
Sheath - Black
TWO CORES
1.5 1 / 1.38 1.38 0.8 1.0 0.8 0.3 1.8 14.0 406 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 0.3 1.8 14.5 417 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 0.3 1.8 15.0 442 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 0.3 1.8 15.5 480 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 0.3 1.8 17.0 569 4.61
4 7 / 0.85 2.55 1.0 1.0 0.8 0.3 1.8 17.5 584 4.61
6 7 / 1.04 3.12 1.0 1.0 0.8 0.3 1.8 18.5 674 3.08
10 7 / 1.35 4.05 1.0 1.0 0.8 0.3 1.8 20.5 826 1.83
16 7 / 1.70 5.10 1.0 1.0 0.8 0.3 1.8 22.5 1040 1.15
25 7 / 2.13 6.39 1.2 1.0 0.8 0.3 1.8 26.0 1365 0.727
35 7 / 2.52 7.56 1.2 1.0 0.8 0.3 1.8 28.0 1672 0.524
50 19 / 1.83 9.15 1.4 1.0 0.8 0.3 1.8 32.0 2134 0.387
70 19 / 2.17 10.85 1.4 1.0 0.8 0.3 1.9 35.5 2691 0.268
95 19 / 2.52 12.60 1.6 1.2 0.8 0.3 2.1 41.0 3484 0.193
120 37 / 2.03 14.21 1.6 1.2 0.8 0.3 2.2 44.5 4149 0.153
150 37 / 2.27 15.89 1.8 1.2 0.8 0.3 2.3 49.0 4995 0.124
185 37 / 2.52 17.64 2.0 1.4 0.8 0.3 2.4 53.5 5968 0.0991
240 61 / 2.26 20.34 2.2 1.4 0.8 0.3 2.6 60.0 7540 0.0754
300 61 / 2.52 22.68 2.4 1.6 0.8 0.3 2.8 66.5 9178 0.0601
Minimumthicknessof Galv.
Steel tapemm
thicknessof Galv.
FlatSteel wire
Thicknessof Innercovering(approx.)
mm mm mm kg/kmmmmm
of wire Conductor
mm² No./mm mmarea (approx.) (approx.)
Insulation
ConductorCross- Diameter of of of of of section
Overall Maximum
(approx.)
Nominal No./ Diameter Thickness Weightdiameter
cable cable at 20°C(approx.)
Ω/km
Resistance
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLESPVC/FSWA/PVC (IEC 60502-1)
Thickness
Sheath
Conductor Nominal NominalNominal
Page - 41
Section 2 - PVC Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow, Blue
Sheath - Black
THREE CORES
1.5 1 / 1.38 1.38 0.8 1.0 0.8 0.3 1.8 14.5 437 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 0.3 1.8 15.0 447 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 0.3 1.8 15.5 509 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 0.3 1.8 16.0 524 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 0.3 1.8 17.5 631 4.61
4 7 / 0.85 2.55 1.0 1.0 0.8 0.3 1.8 18.0 649 4.61
6 7 / 1.04 3.12 1.0 1.0 0.8 0.3 1.8 19.0 760 3.08
10 7 / 1.35 4.05 1.0 1.0 0.8 0.3 1.8 21.5 982 1.83
16 7 / 1.70 5.10 1.0 1.0 0.8 0.3 1.8 23.5 1230 1.15
25 7 / 2.13 6.39 1.2 1.0 0.8 0.3 1.8 27.0 1685 0.727
35 7 / 2.52 7.56 1.2 1.0 0.8 0.3 1.8 30.0 2089 0.524
50 6.8 1.4 1.0 0.8 0.3 1.9 28.5 2385 0.387
70 8.2 1.4 1.2 0.8 0.3 2.0 32.0 3149 0.268
95 9.7 1.6 1.2 0.8 0.3 2.2 37.0 4184 0.193
120 10.9 1.6 1.2 0.8 0.3 2.3 39.5 4902 0.153
150 11.9 1.8 1.4 0.8 0.3 2.4 43.0 5887 0.124
185 13.6 2.0 1.4 0.8 0.3 2.6 47.5 7212 0.0991
240 15.8 2.2 1.6 0.8 0.3 2.8 54.0 9457 0.0754
300 17.5 2.4 1.6 0.8 0.3 2.9 58.5 11517 0.0601
Minimumthicknessof Galv.
of Galv.
Ω/km
Sector Shape
mm mm mm(approx.)
mm² No./mm mm mm mm mm kg/kmarea (approx.) (approx.) (approx.)
Sheath cablecovering Flat(approx.) Steel wire Steel tape
cable at 20°C
Conductor Nominal Nominal OverallThickness thickness
of Inner
MaximumNominal No./ Diameter Thickness Thickness diameter Weight ConductorCross- Diameter of of of of of Resistancesection of wire Conductor Insulation
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLESPVC/FSWA/PVC (IEC 60502-1)
Nominal
Page - 42
stranded
Section 2 - PVC Insulated CablesArmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow, Blue, Black
Sheath - Black
FOUR CORES
1.5 1 / 1.38 1.38 0.8 1.0 0.8 0.3 1.8 15.5 497 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 0.3 1.8 16.0 510 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 0.3 1.8 16.5 560 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 0.3 1.8 17.0 602 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 0.3 1.8 18.5 731 4.61
4 7 / 0.85 2.55 1.0 1.0 0.8 0.3 1.8 19.5 754 4.61
6 7 / 1.04 3.12 1.0 1.0 0.8 0.3 1.8 20.5 890 3.08
10 7 / 1.35 4.05 1.0 1.0 0.8 0.3 1.8 23.0 1157 1.83
16 7 / 1.70 5.10 1.0 1.0 0.8 0.3 1.8 25.5 1498 1.15
25 7 / 2.13 6.39 1.2 1.0 0.8 0.3 1.8 29.5 2055 0.727
35 7 / 2.52 7.56 1.2 1.0 0.8 0.3 1.9 32.5 2567 0.524
50 8.1 1.4 1.2 0.8 0.3 2.0 32.5 3041 0.387
70 9.7 1.4 1.2 0.8 0.3 2.1 36.0 3991 0.268
95 11.4 1.6 1.2 0.8 0.3 2.3 41.5 5307 0.193
120 12.9 1.6 1.4 0.8 0.3 2.4 45.0 6286 0.153
150 14.2 1.8 1.4 0.8 0.3 2.6 49.0 7567 0.124
185 16.0 2.0 1.6 0.8 0.3 2.7 54.5 9306 0.0991
240 18.2 2.2 1.6 0.8 0.3 3.0 60.5 12117 0.0754
300 20.6 2.4 1.6 0.8 0.3 3.2 66.5 14861 0.0601
Minimumthicknessof Galv.
Steel tape
Thickness thicknessof Inner of Galv.
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLESPVC/FSWA/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall MaximumNominal No./ Diameter Thickness Thickness diameter Weight ConductorCross- Diameter of of of of of Resistance
mm mmmm² No./mm
section of wire Conductor Insulationarea (approx.) (approx.) (approx.)
Sector Shape
mm mm
cable(approx.)
cableFlat Sheath
mm
covering
mm Ω/kmkg/km
Nominal
mm
at 20°C
Page - 43
stranded
(approx.) Steel wire
Section 2 - PVC Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
FIVE CORES
1.5 1 / 1.38 1.38 0.8 1.0 0.8 0.3 1.8 16.5 538 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 0.3 1.8 17.0 580 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 0.3 1.8 17.5 635 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 0.3 1.8 18.0 654 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 0.3 1.8 20.0 832 4.61
4 7 / 0.85 2.55 1.0 1.0 0.8 0.3 1.8 21.0 860 4.61
6 7 / 1.04 3.12 1.0 1.0 0.8 0.3 1.8 22.0 1022 3.08
10 7 / 1.35 4.05 1.0 1.0 0.8 0.3 1.8 25.0 1338 1.83
16 7 / 1.70 5.10 1.0 1.0 0.8 0.3 1.8 27.5 1745 1.15
25 7 / 2.13 6.39 1.2 1.0 0.8 0.3 1.8 32.0 2413 0.727
35 7 / 2.52 7.56 1.2 1.0 0.8 0.3 1.9 35.5 3066 0.524
50 19 / 1.83 9.15 1.4 1.2 0.8 0.3 2.1 41.5 4013 0.387
thicknessof Galv.
Steel tapemm kg/km Ω/kmmm mm mm mmmm² No./mm mm mm
cable at 20°Carea (approx.) (approx.) (approx.) Steel wire (approx.) (approx.)
of Resistancesection of wire Conductor Insulation covering Flat Sheath cable
Weight ConductorCross- Diameter of of of Inner of Galv. of of
Thickness thickness Thickness diameterMinimumNominal No./ Diameter Thickness
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLESPVC/FSWA/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall MaximumNominal
Page - 44
Section 2 - PVC Insulated Cables Armoured Cables
Constructions :Conductor (Annealed Copper)
Insulation (PVC Compound)
Inner Covering (PVC Compound)
Double Aluminium Tape armour
Outer sheath (PVC Compound)
Constructions :Conductor (Annealed Copper)
Insulation (PVC Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Inner Covering (PVC Compound)
Double Galvanized Steel Tape armour
Outer sheath (PVC Compound)
600/1000 V PVC INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLESPVC/DATA/PVC (acc. to IEC 60502-1)
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLESPVC/DSTA/PVC (acc. to IEC 60502-1)
Page - 45
11
2
3
54
6
7
2
3
4
5
6
7
1
2
3
4
5
1
2
34
5
Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Anti termite performance.* Tin coated Copper conductor.* Polyethylene / Low smoke Halogen Free sheathed
Section 2 - PVC Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Inner covering : PVC Compound Maximum 70°C
Armour : Double Aluminium tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black
Sheath - Black
SINGLE CORE
50 19 / 1.83 9.15 1.4 1.0 0.5 1.8 19.5 817 0.387
70 19 / 2.17 10.85 1.4 1.0 0.5 1.8 21.0 1045 0.268
95 19 / 2.52 12.60 1.6 1.0 0.5 1.8 23.5 1344 0.193
120 37 / 2.03 14.21 1.6 1.0 0.5 1.8 25.0 1607 0.153
150 37 / 2.27 15.89 1.8 1.0 0.5 1.8 27.0 1949 0.124
185 37 / 2.52 17.64 2.0 1.0 0.5 1.8 29.5 2339 0.0991
240 61 / 2.26 20.34 2.2 1.0 0.5 1.9 32.5 2987 0.0754
300 61 / 2.52 22.68 2.4 1.0 0.5 1.9 35.0 3628 0.0601
400 61 / 2.86 25.74 2.6 1.2 0.5 2.1 39.5 4638 0.0470
500 61 / 3.20 28.80 2.8 1.2 0.5 2.2 43.5 5694 0.0366
Thickness
Sheath
Conductor Nominal NominalWeightdiameter
Overall
600/1000 V PVC INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLESPVC/DATA/PVC (IEC 60502-1)
ofat 20°Ccable
Nominal No./ Diameter ThicknessMaximum
Ω/km
Resistance
kg/km
cable(approx.)
Insulation
Conductorof of of
Thicknessof Innercovering
(approx.)(approx.)
Cross- Diameter of
mmmm
section of wire Conductor
mm² No./mm mmarea (approx.)
Page - 46
(approx.)
Nominalthickness ofAluminium
tapemm mm mm
Section 2 - PVC Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Black
Sheath - Black
TWO CORES
1 / 1.38 1.38 0.8 1.0 0.2 1.8 13.0 237 12.1
7 / 0.52 1.56 0.8 1.0 0.2 1.8 13.0 250 12.1
1 / 1.78 1.78 0.8 1.0 0.2 1.8 13.5 276 7.41
7 / 0.67 2.01 0.8 1.0 0.2 1.8 14.0 290 7.41
1 / 2.26 2.26 1.0 1.0 0.2 1.8 15.5 357 4.61
7 / 0.85 2.55 1.0 1.0 0.2 1.8 16.0 374 4.61
7 / 1.04 3.12 1.0 1.0 0.2 1.8 17.0 440 3.08
10 7 / 1.35 4.05 1.0 1.0 0.2 1.8 19.0 574 1.83
16 7 / 1.70 5.10 1.0 1.0 0.2 1.8 21.0 742 1.15
25 7 / 2.13 6.39 1.2 1.0 0.2 1.8 24.5 1026 0.727
35 7 / 2.52 7.56 1.2 1.0 0.2 1.8 27.0 1290 0.524
50 19 / 1.83 9.15 1.4 1.0 0.2 1.8 31.0 1712 0.387
70 19 / 2.17 10.85 1.4 1.0 0.2 1.9 34.0 2262 0.268
95 19 / 2.52 12.60 1.6 1.2 0.2 2.1 39.0 2896 0.193
120 37 / 2.03 14.21 1.6 1.2 0.5 2.2 43.5 3921 0.153
150 37 / 2.27 15.89 1.8 1.2 0.5 2.3 48.0 4722 0.124
185 37 / 2.52 17.64 2.0 1.4 0.5 2.4 52.5 5675 0.0991
240 61 / 2.26 20.34 2.2 1.4 0.5 2.6 58.5 7166 0.0754
300 61 / 2.52 22.68 2.4 1.6 0.5 2.8 64.5 8710 0.0601
1.5
2.5
4
1.5
2.5
4
6
Thicknessof Galv.
Steel tape
Thicknessof Innercovering(approx.)
mm mm mm kg/kmmmmmmm² No./mm mmarea (approx.) (approx.)
of of of section of wire ConductorCross- Diameter of of
Maximum
(approx.)
Weightdiameter
cable cable at 20°C(approx.)
Conductor
Ω/km
Resistance
Conductor Nominal NominalNominal No./ Diameter Thickness
Overall
Insulation
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLESPVC/DSTA/PVC (IEC 60502-1)
Thickness
Sheath
Nominal
Page - 47
Section 2 - PVC Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow, Blue
Sheath - Black
THREE CORES
1 / 1.38 1.38 0.8 1.0 0.2 1.8 13.5 270 12.1
7 / 0.52 1.56 0.8 1.0 0.2 1.8 13.5 281 12.1
1 / 1.78 1.78 0.8 1.0 0.2 1.8 14.0 318 7.41
7 / 0.67 2.01 0.8 1.0 0.2 1.8 14.5 335 7.41
1 / 2.26 2.26 1.0 1.0 0.2 1.8 16.0 420 4.61
7 / 0.85 2.55 1.0 1.0 0.2 1.8 16.5 441 4.61
7 / 1.04 3.12 1.0 1.0 0.2 1.8 18.0 530 3.08
10 7 / 1.35 4.05 1.0 1.0 0.2 1.8 20.0 707 1.83
16 7 / 1.70 5.10 1.0 1.0 0.2 1.8 22.0 935 1.15
25 7 / 2.13 6.39 1.2 1.0 0.2 1.8 26.0 1328 0.727
35 7 / 2.52 7.56 1.2 1.0 0.2 1.8 28.5 1685 0.524
50 6.8 1.4 1.0 0.2 1.9 27.0 2002 0.387
70 8.2 1.4 1.2 0.2 2.0 30.5 2724 0.268
95 9.7 1.6 1.2 0.5 2.2 36.5 4062 0.193
120 10.9 1.6 1.2 0.5 2.3 39.5 4765 0.153
150 11.9 1.8 1.4 0.5 2.4 42.5 5745 0.124
185 13.6 2.0 1.4 0.5 2.6 47.5 7055 0.0991
240 15.8 2.2 1.6 0.5 2.8 53.5 9254 0.0754
300 17.5 2.4 1.6 0.5 2.9 58.0 11299 0.0601
1.5
2.5
mm² No./mm
Three-
Segmental
Stranded
1.5
2.5
4
6
4
Thickness Thicknessof Inner of Galv.
Ω/kmmm mm(approx.)
mm mm kg/km(approx.)(approx.)
mm mmarea (approx.) (approx.)
Sheath cablecovering Steel tape cable at 20°C
Conductor Nominal Nominal Overall Maximum
Cross-Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
of Resistancesection of wire Conductor Insulation
Diameter of of of of
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLESPVC/DSTA/PVC (IEC 60502-1)
Nominal
Page - 48
Section 2 - PVC Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Red,Yellow, Blue, Black
Sheath - Black
FOUR CORES
1 / 1.38 1.38 0.8 1.0 0.2 1.8 14.0 307 12.1
7 / 0.52 1.56 0.8 1.0 0.2 1.8 14.5 322 12.1
1 / 1.78 1.78 0.8 1.0 0.2 1.8 15.0 372 7.41
7 / 0.67 2.01 0.8 1.0 0.2 1.8 15.5 390 7.41
1 / 2.26 2.26 1.0 1.0 0.2 1.8 17.5 499 4.61
7 / 0.85 2.55 1.0 1.0 0.2 1.8 18.0 524 4.61
7 / 1.04 3.12 1.0 1.0 0.2 1.8 19.0 638 3.08
10 7 / 1.35 4.05 1.0 1.0 0.2 1.8 21.5 860 1.83
16 7 / 1.70 5.10 1.0 1.0 0.2 1.8 24.0 1158 1.15
25 7 / 2.13 6.39 1.2 1.0 0.2 1.8 28.0 1650 0.727
35 7 / 2.52 7.56 1.2 1.0 0.2 1.8 31.0 2120 0.524
50 8.1 1.4 1.2 0.2 2.0 31.0 2592 0.387
70 9.7 1.4 1.2 0.5 2.1 36.0 3862 0.268
95 11.4 1.6 1.2 0.5 2.3 41.0 5171 0.193
120 12.9 1.6 1.4 0.5 2.4 44.5 6122 0.153
150 14.2 1.8 1.4 0.5 2.6 49.0 7405 0.124
185 16.0 2.0 1.6 0.5 2.7 54.0 9113 0.0991
240 18.2 2.2 1.6 0.5 3.0 60.0 11899 0.0754
300 20.6 2.4 1.6 0.5 3.2 66.5 14624 0.0601
1.5
4
2.5
Segmental
Stranded
Four-
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLESPVC/DSTA/PVC (IEC 60502-1)
ConductorThickness
Cross-section
Thicknessof Inner of Galv.
Nominal Overall MaximumNominal No./ Diameter Thickness Thickness diameter Weight Conductor
Nominal
Diameter of of of of of Resistancecable at 20°Cof wire Conductor Insulation covering Steel tape
(approx.) (approx.)Sheath cable
(approx.) (approx.)mm² No./mm mm mm mm mm kg/kmarea (approx.)
Ω/kmmm mm
1.5
2.5
4
6
Nominal
Page - 49
Section 2 - PVC Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
FIVE CORES
1 / 1.38 1.38 0.8 1.0 0.2 1.8 15.0 350 12.1
7 / 0.52 1.56 0.8 1.0 0.2 1.8 15.5 368 12.1
1 / 1.78 1.78 0.8 1.0 0.2 1.8 16.0 424 7.41
7 / 0.67 2.01 0.8 1.0 0.2 1.8 16.5 446 7.41
1 / 2.26 2.26 1.0 1.0 0.2 1.8 18.5 578 4.61
7 / 0.85 2.55 1.0 1.0 0.2 1.8 19.5 609 4.61
7 / 1.04 3.12 1.0 1.0 0.2 1.8 20.5 748 3.08
10 7 / 1.35 4.05 1.0 1.0 0.2 1.8 23.5 1022 1.83
16 7 / 1.70 5.10 1.0 1.0 0.2 1.8 26.0 1386 1.15
25 7 / 2.13 6.39 1.2 1.0 0.2 1.8 30.5 1991 0.727
35 7 / 2.52 7.56 1.2 1.0 0.2 1.9 34.0 2577 0.524
50 19 / 1.83 9.15 1.4 1.2 0.2 2.1 40.0 3400 0.387
1.5
4
2.5
1.5
2.5
mm²area
4
6
Nominal Maximum
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
No./ Diameter Thickness Thickness Thickness Thickness diameter Weight ConductorCross- Diameter of of of Inner of Galv. of of of Resistancesection of wire Conductor Insulation covering Steel tape Sheath cable cable
(approx.) (approx.) (approx.)mm mm kg/km
at 20°C(approx.) (approx.)
Nominal
PVC/DSTA/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall
Page - 50
Ω/kmmm mm mm mmNo./mm
Section 3 - XLPE Insulated Cables Unarmoured Cables
Constructions :Conductor (Annealed Copper)
Insulation (XLPE Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Outer sheath (PVC Compound)
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLESXLPE/PVC (IEC 60502-1)
Page - 51
1
2
3
4
5
1
23
4
5
2
Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Anti termite performance.* Tin coated Copper conductor.* Polyethylene / Low smoke Halogen Free sheathed
Section 3 - XLPE Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Sheath : PVC Compound type ST2 Maximum 90°C
Colour Ident. : Insulation - Black
Sheath - Black
SINGLE CORE
1.5 1 / 1.38 1.38 0.7 1.4 6.0 49 12.1
1.5 7 / 0.52 1.56 0.7 1.4 6.5 51 12.1
2.5 1 / 1.78 1.78 0.7 1.4 6.5 62 7.41
2.5 7 / 0.67 2.01 0.7 1.4 7.0 64 7.41
4 1 / 2.26 2.26 0.7 1.4 7.0 80 4.61
4 7 / 0.85 2.55 0.7 1.4 7.5 83 4.61
6 7 / 1.04 3.12 0.7 1.4 8.0 106 3.08
10 7 / 1.35 4.05 0.7 1.4 9.0 152 1.83
16 4.7 0.7 1.4 9.5 206 1.15
25 5.9 0.9 1.4 11.0 302 0.727
35 7.1 0.9 1.4 12.0 399 0.524
50 8.1 1.0 1.4 13.5 518 0.387
70 9.7 1.1 1.4 15.0 721 0.268
95 11.6 1.1 1.5 17.5 979 0.193
120 12.9 1.2 1.5 19.0 1212 0.153
150 14.3 1.4 1.6 21.0 1502 0.124
185 16.0 1.6 1.6 23.0 1854 0.0991
240 18.3 1.7 1.7 26.0 2406 0.0754
300 20.7 1.8 1.8 28.5 2996 0.0601
400 23.4 2.0 1.9 32.0 3799 0.0470
500 26.5 2.2 2.0 35.5 4842 0.0366
630 30.3 2.4 2.2 40.0 6233 0.0283
800 34.3 2.6 2.3 45.0 7933 0.0221
1000 127 / 3.2 41.6 2.8 2.4 53.0 10109 0.0176
round
stranded
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLESXLPE/PVC (IEC 60502-1)
cable at 20°C
(approx.)
mmmm
Thickness diameter
Sheath cable
Maximum
Weight Conductor
of of
Conductor Nominal Nominal Overall
Nominal No./ Diameter Thickness
Cross- Diameter of of
Insulation
of Resistance
(approx.) (approx.)
mm² No./mm mm
section of wire Conductor
Page - 52
area (approx.)
kg/km Ω/kmmm
Compact
Section 3 - XLPE Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Black
Sheath - Black
TWO CORES
1.5 1 / 1.38 1.38 0.7 1.8 10.0 116 12.1
1.5 7 / 0.52 1.56 0.7 1.8 10.5 121 12.1
2.5 1 / 1.78 1.78 0.7 1.8 11.0 145 7.41
2.5 7 / 0.67 2.01 0.7 1.8 11.5 150 7.41
4 1 / 2.26 2.26 0.7 1.8 12.0 188 4.61
4 7 / 0.85 2.55 0.7 1.8 12.5 196 4.61
6 7 / 1.04 3.12 0.7 1.8 13.5 246 3.08
10 7 / 1.35 4.05 0.7 1.8 15.5 352 1.83
16 4.7 0.7 1.8 17.0 468 1.15
25 5.9 0.9 1.8 20.0 684 0.727
35 7.1 0.9 1.8 22.5 899 0.524
50 8.1 1.0 1.8 25.0 1162 0.387
70 9.7 1.1 1.8 28.5 1607 0.268
95 11.6 1.1 2.0 32.5 2185 0.193
120 12.9 1.2 2.1 36.0 2709 0.153
150 14.3 1.4 2.2 39.5 3350 0.124
185 16.0 1.6 2.3 44.5 4152 0.0991
240 18.3 1.7 2.5 50.0 5382 0.0754
300 20.7 1.8 2.7 55.5 6711 0.0601
400 23.4 2.0 2.9 62.0 8494 0.0470
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLESXLPE/PVC (IEC 60502-1)
Thickness
Sheath
Conductor Nominal Nominal
Weightdiameter
cable cable at 20°C
(approx.)
Ω/km
Resistance
Nominal No./ Diameter Thickness
Overall Maximum
(approx.)
Insulation
Conductor
Cross- Diameter of of of of of
section of wire Conductor
mm² No./mm mm
area (approx.) (approx.)
mm mm mm kg/km
Compact
round
stranded
Page - 53
Section 3 - XLPE Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue
Sheath - Black
THREE CORES
1.5 1 / 1.38 1.38 0.7 1.8 10.5 139 12.1
1.5 7 / 0.52 1.56 0.7 1.8 11.0 145 12.1
2.5 1 / 1.78 1.78 0.7 1.8 11.5 175 7.41
2.5 7 / 0.67 2.01 0.7 1.8 12.0 183 7.41
4 1 / 2.26 2.26 0.7 1.8 12.5 234 4.61
4 7 / 0.85 2.55 0.7 1.8 13.5 243 4.61
6 7 / 1.04 3.12 0.7 1.8 14.5 314 3.08
10 7 / 1.35 4.05 0.7 1.8 16.5 458 1.83
16 4.7 0.7 1.8 18.0 626 1.15
25 5.9 0.9 1.8 21.0 928 0.727
35 7.1 0.9 1.8 24.0 1232 0.524
50 8.1 1.0 1.8 26.5 1605 0.387
70 9.7 1.1 1.9 30.5 2251 0.268
95 11.6 1.1 2.0 35.0 3051 0.193
120 12.9 1.2 2.1 38.0 3799 0.153
150 14.3 1.4 2.3 42.5 4720 0.124
185 16.0 1.6 2.4 47.5 5862 0.0991
240 18.3 1.7 2.6 53.5 7618 0.0754
300 20.7 1.8 2.8 59.5 9494 0.0601
400 23.4 2.0 3.1 67.0 12111 0.0470
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLESXLPE/PVC (IEC 60502-1)
section of wire Conductor Insulation
of of of ResistanceCross- Diameter of of
Thickness diameter Weight ConductorNominal No./ Diameter Thickness
MaximumConductor Nominal Nominal Overall
Sheath cable cable at 20°C
Ω/km
Compact
round
stranded
mm kg/kmNo./mm mm mm
(approx.)
mm²
Page - 54
area (approx.) (approx.) (approx.)
mm
Section 3 - XLPE Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue, Black
Sheath - Black
FOUR CORES
1.5 1 / 1.38 1.38 0.7 1.8 11.5 162 12.1
1.5 7 / 0.52 1.56 0.7 1.8 12.0 170 12.1
2.5 1 / 1.78 1.78 0.7 1.8 12.5 215 7.41
2.5 7 / 0.67 2.01 0.7 1.8 13.0 224 7.41
4 1 / 2.26 2.26 0.7 1.8 13.5 286 4.61
4 7 / 0.85 2.55 0.7 1.8 14.5 298 4.61
6 7 / 1.04 3.12 0.7 1.8 15.5 391 3.08
10 7 / 1.35 4.05 0.7 1.8 18.0 576 1.83
16 4.7 0.7 1.8 19.5 796 1.15
25 5.9 0.9 1.8 23.5 1190 0.727
35 7.1 0.9 1.8 26.0 1584 0.524
50 8.1 1.0 1.9 29.5 2091 0.387
70 9.7 1.1 2.0 34.0 2940 0.268
95 11.6 1.1 2.1 38.5 3997 0.193
120 12.9 1.2 2.3 42.5 4995 0.153
150 14.3 1.4 2.4 47.0 6184 0.124
185 16.0 1.6 2.6 53.0 7700 0.0991
240 18.3 1.7 2.8 59.5 9999 0.0754
300 20.7 1.8 3.0 66.5 12495 0.0601
Ω/km
Compact
round
stranded
(approx.)
mm² No./mm mm mm mm mm kg/km
area (approx.) (approx.) (approx.)
Sheath cable cable at 20°Csection of wire Conductor Insulation
of of of ResistanceCross- Diameter of of
Thickness diameter Weight ConductorNominal No./ Diameter Thickness
XLPE/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall Maximum
Page - 55
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES
Section 3 - XLPE Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
FIVE CORES
1.5 1 / 1.38 1.38 0.7 1.8 12.5 192 12.1
1.5 7 / 0.52 1.56 0.7 1.8 13.0 200 12.1
2.5 1 / 1.78 1.78 0.7 1.8 13.5 251 7.41
2.5 7 / 0.67 2.01 0.7 1.8 14.0 261 7.41
4 1 / 2.26 2.26 0.7 1.8 15.0 344 4.61
4 7 / 0.85 2.55 0.7 1.8 15.5 358 4.61
6 7 / 1.04 3.12 0.7 1.8 17.0 469 3.08
10 7 / 1.35 4.05 0.7 1.8 19.5 696 1.83
16 4.7 0.7 1.8 21.0 974 1.15
25 5.9 0.9 1.8 25.5 1234 0.727
35 7.1 0.9 1.8 29.0 1950 0.524
50 8.1 1.0 2.0 32.5 2590 0.387
Ω/km
stranded
round
Compact
(approx.)
mm² No./mm mm mm mm mm kg/km
area (approx.) (approx.) (approx.)
Sheath cable cable at 20°Csection of wire Conductor Insulation
of of of ResistanceCross- Diameter of of
Thickness diameter Weight ConductorNominal No./ Diameter Thickness
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLESXLPE/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall Maximum
Page - 56
Section 3 - XLPE Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 clas 1) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler (if necessary) : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 1.5 mm² (Solid conductor)
No Nominal of Cross-section
core area
mm²
6 1.5 1 / 1.38 1.38 0.7 1.8 13.0 214 12.1
7 1.5 1 / 1.38 1.38 0.7 1.8 13.0 229 12.1
8 1.5 1 / 1.38 1.38 0.7 1.8 14.0 256 12.1
9 1.5 1 / 1.38 1.38 0.7 1.8 15.0 286 12.1
10 1.5 1 / 1.38 1.38 0.7 1.8 16.0 316 12.1
12 1.5 1 / 1.38 1.38 0.7 1.8 16.5 358 12.1
14 1.5 1 / 1.38 1.38 0.7 1.8 17.5 400 12.1
15 1.5 1 / 1.38 1.38 0.7 1.8 18.0 426 12.1
16 1.5 1 / 1.38 1.38 0.7 1.8 18.5 448 12.1
18 1.5 1 / 1.38 1.38 0.7 1.8 19.0 488 12.1
19 1.5 1 / 1.38 1.38 0.7 1.8 19.0 502 12.1
20 1.5 1 / 1.38 1.38 0.7 1.8 19.5 532 12.1
24 1.5 1 / 1.38 1.38 0.7 1.8 22.0 628 12.1
30 1.5 1 / 1.38 1.38 0.7 1.8 23.5 748 12.1
32 1.5 1 / 1.38 1.38 0.7 1.8 24.0 793 12.1
37 1.5 1 / 1.38 1.38 0.7 1.8 25.0 888 12.1
40 1.5 1 / 1.38 1.38 0.7 1.8 26.0 953 12.1
50 1.5 1 / 1.38 1.38 0.7 1.9 29.0 1178 12.1
52 1.5 1 / 1.38 1.38 0.7 1.9 29.5 1221 12.1
60 1.5 1 / 1.38 1.38 0.7 1.9 31.5 1384 12.1
61 1.5 1 / 1.38 1.38 0.7 1.9 31.5 1398 12.1
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLESXLPE/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall MaximumNo./ Diameter Thickness Thickness
at 20°CDiameter of of of
of wire Conductor Insulation Sheath cable
Conductorof of Resistance
diameter Weight
cable(approx.) (approx.) (approx.) (approx.)
Page - 57
kg/km Ω/kmNo./mm mm mm mm mm
Section 3 - XLPE Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 clas 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler (if necessary) : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 1.5 mm² (Stranded conductor)
No Nominal of Cross-section
core area
mm²
6 1.5 7 / 0.52 1.56 0.7 1.8 14.0 224 12.1
7 1.5 7 / 0.52 1.56 0.7 1.8 14.0 239 12.1
8 1.5 7 / 0.52 1.56 0.7 1.8 15.0 269 12.1
9 1.5 7 / 0.52 1.56 0.7 1.8 16.0 300 12.1
10 1.5 7 / 0.52 1.56 0.7 1.8 17.0 331 12.1
12 1.5 7 / 0.52 1.56 0.7 1.8 17.5 374 12.1
14 1.5 7 / 0.52 1.56 0.7 1.8 18.5 418 12.1
15 1.5 7 / 0.52 1.56 0.7 1.8 19.0 447 12.1
16 1.5 7 / 0.52 1.56 0.7 1.8 19.0 468 12.1
18 1.5 7 / 0.52 1.56 0.7 1.8 20.0 511 12.1
19 1.5 7 / 0.52 1.56 0.7 1.8 20.0 526 12.1
20 1.5 7 / 0.52 1.56 0.7 1.8 21.0 557 12.1
24 1.5 7 / 0.52 1.56 0.7 1.8 23.5 657 12.1
30 1.5 7 / 0.52 1.56 0.7 1.8 24.5 786 12.1
32 1.5 7 / 0.52 1.56 0.7 1.8 25.0 830 12.1
37 1.5 7 / 0.52 1.56 0.7 1.8 26.5 928 12.1
40 1.5 7 / 0.52 1.56 0.7 1.8 27.5 997 12.1
50 1.5 7 / 0.52 1.56 0.7 1.9 30.5 1232 12.1
52 1.5 7 / 0.52 1.56 0.7 1.9 31.5 1276 12.1
60 1.5 7 / 0.52 1.56 0.7 1.9 33.0 1447 12.1
61 1.5 7 / 0.52 1.56 0.7 1.9 33.0 1462 12.1
kg/km Ω/kmNo./mm mm mm mm mm
cable(approx.) (approx.) (approx.) (approx.)
Conductorof of Resistance
diameter Weight
at 20°CDiameter of of of
of wire Conductor Insulation Sheath cable
No./ Diameter Thickness Thickness
XLPE/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall Maximum
Page - 58
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES
Section 3 - XLPE Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler (if necessary) : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 2.5 mm² (Solid conductor)
No Nominal of Cross-section
core area
mm²
6 2.5 1 / 1.78 1.78 0.7 1.8 14.5 284 7.41
7 2.5 1 / 1.78 1.78 0.7 1.8 14.5 307 7.41
8 2.5 1 / 1.78 1.78 0.7 1.8 15.5 348 7.41
9 2.5 1 / 1.78 1.78 0.7 1.8 16.5 389 7.41
10 2.5 1 / 1.78 1.78 0.7 1.8 18.0 431 7.41
12 2.5 1 / 1.78 1.78 0.7 1.8 18.5 490 7.41
14 2.5 1 / 1.78 1.78 0.7 1.8 19.0 558 7.41
15 2.5 1 / 1.78 1.78 0.7 1.8 19.5 590 7.41
16 2.5 1 / 1.78 1.78 0.7 1.8 20.0 622 7.41
18 2.5 1 / 1.78 1.78 0.7 1.8 21.0 684 7.41
19 2.5 1 / 1.78 1.78 0.7 1.8 21.0 707 7.41
20 2.5 1 / 1.78 1.78 0.7 1.8 22.0 754 7.41
24 2.5 1 / 1.78 1.78 0.7 1.8 24.5 887 7.41
30 2.5 1 / 1.78 1.78 0.7 1.8 26.0 1070 7.41
32 2.5 1 / 1.78 1.78 0.7 1.8 26.5 1131 7.41
37 2.5 1 / 1.78 1.78 0.7 1.8 28.0 1276 7.41
40 2.5 1 / 1.78 1.78 0.7 1.9 29.0 1386 7.41
50 2.5 1 / 1.78 1.78 0.7 2.0 32.5 1714 7.41
52 2.5 1 / 1.78 1.78 0.7 2.0 33.0 1782 7.41
60 2.5 1 / 1.78 1.78 0.7 2.0 35.0 2024 7.41
61 2.5 1 / 1.78 1.78 0.7 2.0 35.0 2046 7.41
(approx.)mm kg/km Ω/km
(approx.) (approx.) (approx.)No./mm mm mm mm
Resistanceof wire Conductor Insulation Sheath cable cable at 20°C
Diameterof of Diameter of of of
Thickness
Page - 59
Overalldiameter Weight ConductorThickness
Nominal NominalNo./
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLESXLPE/PVC (IEC 60502-1)
MaximumConductor
Section 3 - XLPE Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler (if necessary) : Suitable material Maximum 90°C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 2.5 mm² (Stranded conductor)
No Nominal of Cross-section
core area
mm²
6 2.5 7 / 0.67 2.01 0.7 1.8 15.0 296 7.41
7 2.5 7 / 0.67 2.01 0.7 1.8 15.0 320 7.41
8 2.5 7 / 0.67 2.01 0.7 1.8 16.0 362 7.41
9 2.5 7 / 0.67 2.01 0.7 1.8 17.0 405 7.41
10 2.5 7 / 0.67 2.01 0.7 1.8 18.5 449 7.41
12 2.5 7 / 0.67 2.01 0.7 1.8 19.0 510 7.41
14 2.5 7 / 0.67 2.01 0.7 1.8 20.0 580 7.41
15 2.5 7 / 0.67 2.01 0.7 1.8 20.5 614 7.41
16 2.5 7 / 0.67 2.01 0.7 1.8 21.0 647 7.41
18 2.5 7 / 0.67 2.01 0.7 1.8 22.0 712 7.41
19 2.5 7 / 0.67 2.01 0.7 1.8 22.0 736 7.41
20 2.5 7 / 0.67 2.01 0.7 1.8 23.0 784 7.41
24 2.5 7 / 0.67 2.01 0.7 1.8 26.0 923 7.41
30 2.5 7 / 0.67 2.01 0.7 1.8 27.5 1114 7.41
32 2.5 7 / 0.67 2.01 0.7 1.8 28.0 1177 7.41
37 2.5 7 / 0.67 2.01 0.7 1.8 29.5 1328 7.41
40 2.5 7 / 0.67 2.01 0.7 1.9 30.5 1443 7.41
50 2.5 7 / 0.67 2.01 0.7 2.0 34.0 1784 7.41
52 2.5 7 / 0.67 2.01 0.7 2.0 35.0 1854 7.41
60 2.5 7 / 0.67 2.01 0.7 2.0 37.0 2105 7.41
61 2.5 7 / 0.67 2.01 0.7 2.0 37.0 2129 7.41
kg/km Ω/kmNo./mm mm mm mm mm
cable(approx.) (approx.) (approx.) (approx.)
Conductorof of Resistance
diameter Weight
at 20°CDiameter of of of
of wire Conductor Insulation Sheath cable
No./ Diameter Thickness Thickness
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLESXLPE/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall Maximum
Page - 60
Section 3 - XLPE Insulated Cables Unarmoured Cables
Constructions :Conductor (Annealed Copper)
Insulation (XLPE Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Copper Tape screen
Binding tape (Manufacturer's option)
Outer sheath (PVC Compound)
600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLESXLPE/PVC-S (IEC 60502-1)
Page - 61
1
2
3
6
7
4
12
3
4
5
6
7
5
Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Anti termite performance.* Tin coated Copper conductor.* Copper wire screen.* Polyethylene / Low smoke Halogen Free sheathed
Section 3 - XLPE Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Black
Sheath - Black
TWO CORES
1.5 1 / 1.38 1.38 0.7 0.1 1.8 10.0 125 12.1
1.5 7 / 0.52 1.56 0.7 0.1 1.8 10.5 131 12.1
2.5 1 / 1.78 1.78 0.7 0.1 1.8 11.0 155 7.41
2.5 7 / 0.67 2.01 0.7 0.1 1.8 11.5 162 7.41
4 1 / 2.26 2.26 0.7 0.1 1.8 12.0 200 4.61
4 7 / 0.85 2.55 0.7 0.1 1.8 12.5 209 4.61
6 1 / 2.77 2.77 0.7 0.1 1.8 13.0 250 3.08
6 7 / 1.04 3.12 0.7 0.1 1.8 13.5 261 3.08
10 7 / 1.35 4.05 0.7 0.1 1.8 15.5 369 1.83
16 4.7 0.7 0.1 1.8 16.5 489 1.15
25 5.9 0.9 0.1 1.8 20.0 712 0.727
35 7.1 0.9 0.1 1.8 22.5 934 0.524
50 8.1 1.0 0.1 1.8 24.5 1196 0.387
70 9.7 1.1 0.1 1.9 28.5 1648 0.268
95 11.6 1.1 0.1 2.0 32.5 2226 0.193
120 12.9 1.2 0.1 2.1 35.5 2753 0.153
150 14.3 1.4 0.1 2.2 39.5 3394 0.124
185 16.0 1.6 0.1 2.3 44.0 4205 0.0991
240 18.3 1.7 0.1 2.5 49.5 5425 0.0754
300 20.7 1.8 0.1 2.7 55.0 6752 0.0601
400 23.4 2.0 0.1 2.9 61.5 8543 0.0470
round
kg/kmmm mm
Sheath
mm
Insulation
(approx.)
Copper tape
mm
cable
Page - 62
Resistance
(approx.)
at 20°Ccable
of
Ω/km
Conductorsection area of wire
(approx.) (approx.)
mm² No./mm
Compact
600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES
Diameter
Nominal
Thickness
Overall
diameter
Conductor Maximum
Conductor
Nominal
No./
Diameter
Thickness
Nominal
Thickness
of ofof
mm
stranded
XLPE/PVC-S (IEC 60502-1)
Nominal Weight
ofofCross-
(approx.)
Section 3 - XLPE Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow , Blue
Sheath - Black
THREE CORES
1.5 1 / 1.38 1.38 0.7 0.1 1.8 10.5 149 12.1
1.5 7 / 0.52 1.56 0.7 0.1 1.8 11.0 155 12.1
2.5 1 / 1.78 1.78 0.7 0.1 1.8 11.5 186 7.41
2.5 7 / 0.67 2.01 0.7 0.1 1.8 12.0 195 7.41
4 1 / 2.26 2.26 0.7 0.1 1.8 12.5 246 4.61
4 7 / 0.85 2.55 0.7 0.1 1.8 13.0 257 4.61
6 1 / 2.77 2.77 0.7 0.1 1.8 13.5 318 3.08
6 7 / 1.04 3.12 0.7 0.1 1.8 14.0 330 3.08
10 7 / 1.35 4.05 0.7 0.1 1.8 16.5 478 1.83
16 4.7 0.7 0.1 1.8 17.5 650 1.15
25 5.9 0.9 0.1 1.8 21.0 959 0.727
35 7.1 0.9 0.1 1.8 23.5 1273 0.524
50 8.1 1.0 0.1 1.8 26.5 1642 0.387
70 9.7 1.1 0.1 1.9 30.0 2282 0.268
95 11.6 1.1 0.1 2.0 34.5 3106 0.193
120 12.9 1.2 0.1 2.2 38.0 3868 0.153
150 14.3 1.4 0.1 2.3 42.0 4775 0.124
185 16.0 1.6 0.1 2.4 47.0 5907 0.0991
240 18.3 1.7 0.1 2.6 53.0 7673 0.0754
300 20.7 1.8 0.1 2.8 59.0 9561 0.0601
400 23.4 2.0 0.1 3.1 66.0 12110 0.0470
Compact
(approx.) (approx.)
mm
round
No./mm
stranded
(approx.)
cable
Thickness
of
Copper tape
(approx.)
cable at 20°Csection area of wire Conductor Insulation Sheath
600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES
Cross- Diameter of of of Resistanceof
NominalNominal MaximumOverall
diameterNo./ Diameter Thickness
mm²
(approx.)
Thickness
Conductor Nominal
Nominal
XLPE/PVC-S (IEC 60502-1)
mm Ω/kmkg/kmmm mm
Weight Conductor
of
mm
Page - 63
Section 3 - XLPE Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow , Blue , Black
Sheath - Black
FOUR CORES
1.5 1 / 1.38 1.38 0.7 0.1 1.8 11.5 173 12.1
1.5 7 / 0.52 1.56 0.7 0.1 1.8 12.0 182 12.1
2.5 1 / 1.78 1.78 0.7 0.1 1.8 12.5 228 7.41
2.5 7 / 0.67 2.01 0.7 0.1 1.8 13.0 237 7.41
4 1 / 2.26 2.26 0.7 0.1 1.8 13.5 300 4.61
4 7 / 0.85 2.55 0.7 0.1 1.8 14.0 318 4.61
6 1 / 2.77 2.77 0.7 0.1 1.8 14.5 394 3.08
6 7 / 1.04 3.12 0.7 0.1 1.8 15.5 409 3.08
10 7 / 1.35 4.05 0.7 0.1 1.8 18.0 598 1.83
16 4.7 0.7 0.1 1.8 19.5 823 1.15
25 5.9 0.9 0.1 1.8 23.0 1227 0.727
35 7.1 0.9 0.1 1.8 26.0 1632 0.524
50 8.1 1.0 0.1 1.9 29.0 2120 0.387
70 9.7 1.1 0.1 2.0 33.5 2976 0.268
95 11.6 1.1 0.1 2.2 38.5 4073 0.193
120 12.9 1.2 0.1 2.3 42.5 5052 0.153
150 14.3 1.4 0.1 2.5 47.0 6243 0.124
185 16.0 1.6 0.1 2.6 52.5 7751 0.0991
240 18.3 1.7 0.1 2.8 59.0 10066 0.0754
300 20.7 1.8 0.1 3.0 65.5 12547 0.0601
400 23.4 2.0 0.1 3.3 73.5 15898 0.0470
(approx.)(approx.) (approx.) (approx.)
Compact
round
stranded
Thickness
Conductor Nominal Nominal
of
Thickness Weight
cable
mmmm kg/km Ω/kmmmmm² No./mm mm mm
at 20°Csection area of wire Conductor Insulation Sheath cableCopper tape
of of
Thickness
Resistance
diameter
Diameter of of of
600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLESXLPE/PVC-S (IEC 60502-1)
Page - 64
No./ DiameterNominal
(approx.)
Overall MaximumNominal
Conductor
Cross-
Section 3 - XLPE Insulated Cables Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
FIVE CORES
1.5 1 / 1.38 1.38 0.7 0.1 1.8 12.0 204 12.1
1.5 7 / 0.52 1.56 0.7 0.1 1.8 12.5 214 12.1
2.5 1 / 1.78 1.78 0.7 0.1 1.8 13.5 265 7.41
2.5 7 / 0.67 2.01 0.7 0.1 1.8 14.0 276 7.41
4 1 / 2.26 2.26 0.7 0.1 1.8 14.5 360 4.61
4 7 / 0.85 2.55 0.7 0.1 1.8 15.5 376 4.61
6 1 / 2.77 2.77 0.7 0.1 1.8 16.0 471 3.08
6 7 / 1.04 3.12 0.7 0.1 1.8 17.0 488 3.08
10 7 / 1.35 4.05 0.7 0.1 1.8 19.5 720 1.83
16 4.7 0.7 0.1 1.8 21.0 1005 1.15
25 5.9 0.9 0.1 1.8 25.5 1491 0.727
35 7.1 0.9 0.1 1.9 28.5 2005 0.524
50 8.1 1.0 0.1 2.0 32.0 2620 0.387
(approx.)
600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLESXLPE/PVC-S (IEC 60502-1)
Nominal
(approx.)
round
No./
Compact
Copper tape
mm
stranded
Conductor
mm² No./mm mm
Cross- Diameter of
Nominal
Maximum
Conductor
cable at 20°C
of Resistance
Weight
(approx.)
of of
Thickness
Overall
Sheath cable
Thickness diameter
mm
section area of wire Conductor Insulation
(approx.)
mm mm kg/km Ω/km
of
Diameter Thickness
Nominal Nominal
of
Page - 65
(approx.)
Section 3 - XLPE Insulated Cables Armoured Cables
Constructions :Conductor (Annealed Copper)
Insulation (XLPE Compound)
Inner Covering (PVC Compound)
Round Aluminium Wire armour
Binding tape (Manufacturer's option)
Outer sheath (PVC Compound)
Constructions :Conductor (Annealed Copper)
Insulation (XLPE Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Inner Covering (PVC Compound)
Galvanized Round Steel Wire armour
Binding tape (Manufacturer's option)
Outer sheath (PVC Compound)
600/1000 V XLPE INSULATED, ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLESXLPE/AWA/PVC (acc. to IEC 60502-1)
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLESXLPE/SWA/PVC (acc. to IEC 60502-1)
Page - 66
1
2
3
4
5
6
7
1
2
3
4
5
1
2
3
4
6
1
2
3
5
4
6
7
88
6
5
Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Anti termite performance.* Tin coated Copper conductor.* Polyethylene / Low smoke Halogen Free sheathed
Section 3 - XLPE Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Inner covering : PVC Compound Maximum 90°C
Armour : Aluminium Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black
Sheath - Black
SINGLE CORE
16 4.7 0.7 1.0 0.8 1.8 13.5 325 1.15
25 5.9 0.9 1.0 0.8 1.8 15.5 435 0.727
35 7.1 0.9 1.0 0.8 1.8 16.5 545 0.524
50 8.1 1.0 1.0 1.25 1.8 18.5 715 0.387
70 9.7 1.1 1.0 1.25 1.8 20.0 940 0.268
95 11.6 1.1 1.0 1.25 1.8 22.0 1215 0.193
120 12.9 1.2 1.0 1.6 1.8 24.5 1565 0.153
150 14.3 1.4 1.0 1.6 1.8 26.5 1865 0.124
185 16.0 1.6 1.0 1.6 1.8 28.5 2270 0.0991
240 18.3 1.7 1.0 1.6 1.9 31.0 2860 0.0754
300 20.7 1.8 1.0 1.6 1.9 34.0 3490 0.0601
400 23.4 2.0 1.2 2.0 2.1 38.5 4385 0.0470
500 26.5 2.2 1.2 2.0 2.2 42.0 5485 0.0366
630 30.3 2.4 1.2 2.0 2.3 46.5 6930 0.0283
800 34.3 2.6 1.4 2.5 2.5 52.5 8915 0.0221
1000 Round stranded 41.6 2.8 1.4 2.5 2.5 60.5 11315 0.0176
Compact
round
stranded
600/1000 V XLPE INSULATED, ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLESXLPE/AWA/PVC (IEC 60502-1)
Thickness
Sheath
Conductor Nominal Nominal
Weightdiameter
cable cable
Overall
mmmm mm mm
(approx.)
Ω/km
Resistance
kg/km
of
of wire Conductor at 20°C
Nominal No./ Diameter Thickness
Maximum
(approx.)
Insulation
Conductor
of of of
Thickness
of Inner
covering
No./mm mm
area (approx.) (approx.)
Cross- Diameter of
section
Page - 67
(approx.)
Nominal
diameter of
Aluminium
wire
mmmm²
Section 3 - XLPE Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Black
Sheath - Black
TWO CORES
1.5 1 / 1.38 1.38 0.7 1.0 0.8 1.8 13.5 314 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 1.8 14.0 325 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 1.8 14.5 355 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 1.8 15.0 372 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 1.8 15.5 422 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 1.8 16.0 437 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 1.8 16.5 485 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 1.8 17.0 511 3.08
10 7 / 1.35 4.05 0.7 1.0 1.25 1.8 20.0 757 1.83
16 4.7 0.7 1.0 1.25 1.8 21.0 907 1.15
25 5.9 0.9 1.0 1.6 1.8 25.0 1342 0.727
35 7.1 0.9 1.0 1.6 1.8 27.5 1630 0.524
50 8.1 1.0 1.0 1.6 1.8 30.0 1965 0.387
70 9.7 1.1 1.0 1.6 2.0 34.0 2549 0.268
95 11.6 1.1 1.2 2.0 2.1 39.0 3517 0.193
120 12.9 1.2 1.2 2.0 2.2 42.0 4159 0.153
150 14.3 1.4 1.2 2.0 2.3 46.0 4966 0.124
185 16.0 1.6 1.4 2.5 2.5 52.0 6435 0.0991
240 18.3 1.7 1.4 2.5 2.7 57.5 7894 0.0754
300 20.7 1.8 1.6 2.5 2.8 63.0 9543 0.0601
Nominal
diameter
of
Steel wire
Thickness
of Inner
covering
(approx.)
Compact
round
stranded
mm mm mm kg/kmmmmm
of wire Conductor
mm² No./mm mm
area (approx.) (approx.)
Insulation
Conductor
Cross- Diameter of of of of of
section
Overall Maximum
(approx.)
Nominal No./ Diameter Thickness Weightdiameter
cable cable at 20°C
(approx.)
Ω/km
Resistance
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLESXLPE/SWA/PVC (IEC 60502-1)
Thickness
Sheath
Conductor Nominal Nominal
Page - 68
Section 3 - XLPE Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue
Sheath - Black
THREE CORES
1.5 1 / 1.38 1.38 0.7 1.0 0.8 1.8 14.0 343 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 1.8 14.5 360 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 1.8 15.0 398 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 1.8 15.5 417 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 1.8 16.0 474 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 1.8 17.0 502 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 1.8 17.0 570 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 1.8 18.0 591 3.08
10 7 / 1.35 4.05 0.7 1.0 1.25 1.8 20.5 887 1.83
16 4.7 0.7 1.0 1.25 1.8 22.0 1087 1.15
25 5.9 0.9 1.0 1.6 1.8 26.5 1622 0.727
35 7.1 0.9 1.0 1.6 1.8 29.0 2015 0.524
50 8.1 1.0 1.0 1.6 1.9 31.5 2461 0.387
70 9.7 1.1 1.2 2.0 2.0 37.0 3522 0.268
95 11.6 1.1 1.2 2.0 2.2 41.5 4491 0.193
120 12.9 1.2 1.2 2.0 2.3 45.0 5381 0.153
150 14.3 1.4 1.4 2.5 2.5 50.0 6919 0.124
185 16.0 1.6 1.4 2.5 2.6 55.0 8285 0.0991
240 18.3 1.7 1.6 2.5 2.8 61.5 10398 0.0754
300 20.7 1.8 1.6 2.5 3.0 67.5 12550 0.0601
Thickness Nominal
of Inner diameter
Ω/km
Compact
round
stranded
mm mm
(approx.)
mm² No./mm mm mm mm mm kg/km
area (approx.) (approx.) (approx.)
Sheath cablecovering of
(approx.) Steel wire
cable at 20°C
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLESXLPE/SWA/PVC (IEC 60502-1)
Page - 69
Section 3 - XLPE Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue, Black
Sheath - Black
FOUR CORES
1.5 1 / 1.38 1.38 0.7 1.0 0.8 1.8 15.0 384 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 1.8 15.5 398 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 1.8 16.0 455 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 1.8 16.5 471 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 1.8 17.0 550 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 1.8 18.0 575 4.61
6 7 / 2.77 2.77 0.7 1.0 1.25 1.8 19.0 755 3.08
6 7 / 1.04 3.12 0.7 1.0 1.25 1.8 19.5 792 3.08
10 7 / 1.35 4.05 0.7 1.0 1.25 1.8 22.0 1039 1.83
16 4.7 0.7 1.0 1.25 1.8 23.5 1292 1.15
25 5.9 0.9 1.0 1.6 1.8 28.5 1955 0.727
35 7.1 0.9 1.0 1.6 1.9 31.5 2440 0.524
50 8.1 1.0 1.0 1.6 2.0 34.5 3039 0.387
70 9.7 1.1 1.2 2.0 2.2 40.5 4345 0.268
95 11.6 1.1 1.2 2.0 2.3 45.0 5577 0.193
120 12.9 1.2 1.4 2.5 2.5 50.0 7191 0.153
150 14.3 1.4 1.4 2.5 2.6 55.0 8600 0.124
185 16.0 1.6 1.4 2.5 2.8 60.5 10388 0.0991
240 18.3 1.7 1.6 2.5 3.0 67.5 13059 0.0754
300 20.7 1.8 1.6 2.5 3.2 74.0 15807 0.0601
Thickness Nominal
of Inner diameter
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLESXLPE/SWA/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
cable at 20°Csection of wire Conductor Insulation covering of
(approx.) (approx.)
Sheath cable
(approx.) Steel wire (approx.)
mm² No./mm mm mm mm mm kg/km
area (approx.)
round
stranded
mm mm
Page - 70
Ω/km
Compact
Section 3 - XLPE Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
FIVE CORES
1.5 1 / 1.38 1.38 0.7 1.0 0.8 1.8 16.0 427 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 1.8 16.5 447 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 1.8 17.0 510 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 1.8 17.5 531 7.41
4 1 / 2.26 2.26 0.7 1.0 1.25 1.8 19.0 727 4.61
4 7 / 0.85 2.55 0.7 1.0 1.25 1.8 19.5 763 4.61
6 1 / 2.77 2.77 0.7 1.0 1.25 1.8 20.5 905 3.08
6 7 / 1.04 3.12 0.7 1.0 1.25 1.8 21.0 908 3.08
10 7 / 1.35 4.05 0.7 1.0 1.25 1.8 24.0 1203 1.83
16 4.7 0.7 1.0 1.6 1.8 26.5 1666 1.15
25 5.9 0.9 1.0 1.6 1.8 30.5 2290 0.727
35 7.1 0.9 1.0 1.6 1.9 34.0 2878 0.524
50 8.1 1.0 1.2 2.0 2.1 39.0 3920 0.387
round
kg/km Ω/km
stranded
mm mm mm mm
Compact
mm² No./mm mm mm
cable at 20°C
area (approx.) (approx.) (approx.) Steel wire (approx.) (approx.)
of Resistance
section of wire Conductor Insulation covering of Sheath cable
Weight Conductor
Cross- Diameter of of of Inner diameter of of
Thickness Nominal Thickness diameterNominal No./ Diameter Thickness
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLESXLPE/SWA/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall Maximum
Page - 71
Section 3 - XLPE Insulated Cables Armoured Cables
Conductor (Annealed Copper)
Insulation (XLPE Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Inner Covering (PVC Compound)
Galvanized Flat Steel Wire armour
Galvanized Steel Tape binding
Outer sheath (PVC Compound)
Page - 72
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLESXLPE/FSWA/PVC (acc. to IEC 60502-1)
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Anti termite performance.* Tin coated Copper conductor.* Polyethylene / Low smoke Halogen Free sheathed
Section 3 - XLPE Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Black
Sheath - Black
TWO CORES
1.5 1 / 1.38 1.38 0.7 1.0 0.8 0.3 1.8 14.0 365 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 0.3 1.8 14.0 398 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 0.3 1.8 14.5 426 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 0.3 1.8 15.0 434 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 0.3 1.8 15.5 502 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 0.3 1.8 16.0 514 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 0.3 1.8 16.5 575 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 0.3 1.8 17.0 598 3.08
10 7 / 1.35 4.05 0.7 1.0 0.8 0.3 1.8 19.0 744 1.83
16 4.7 0.7 1.0 0.8 0.3 1.8 20.5 896 1.15
25 5.9 0.9 1.0 0.8 0.3 1.8 23.5 1187 0.727
35 7.1 0.9 1.0 0.8 0.3 1.8 26.0 1472 0.524
50 8.1 1.0 1.0 0.8 0.3 1.8 28.5 1804 0.387
70 9.7 1.1 1.0 0.8 0.3 1.9 32.0 2328 0.268
95 11.6 1.1 1.2 0.8 0.3 2.0 36.5 3031 0.193
120 12.9 1.2 1.2 0.8 0.3 2.1 39.5 3635 0.153
150 14.3 1.4 1.2 0.8 0.3 2.2 43.5 4381 0.124
185 16.0 1.6 1.4 0.8 0.3 2.4 48.5 5342 0.0991
240 18.3 1.7 1.4 0.8 0.3 2.6 54.0 6724 0.0754
300 20.7 1.8 1.6 0.8 0.3 2.7 60.0 8222 0.0601
400 23.4 2.0 1.6 0.8 0.3 3.0 66.5 10210 0.0470
Page - 73
Compact
round
stranded
Minimum
thickness
of Galv.
Steel tape
mm
Steel wire
Thickness
of Inner
covering
(approx.)
mm mm mm kg/kmmmmmmm² No./mm mm
area (approx.) (approx.)
section of wire Conductor
ofCross- Diameter of
Overall Maximum
(approx.)
Conductor
at 20°C
(approx.)
of of
Ω/km
Resistance
Weightdiameter
cable cable
Nominal
Nominal No./ Thickness
Sheath
Thickness
Insulation
of
thickness
of Galv.
Flat
Diameter
Nominal
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLESXLPE/FSWA/PVC (IEC 60502-1)
Conductor Nominal
Section 3 - XLPE Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue
Sheath - Black
THREE CORES
1.5 1 / 1.38 1.38 0.7 1.0 0.8 0.3 1.8 14.5 418 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 0.3 1.8 14.5 426 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 0.3 1.8 15.0 460 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 0.3 1.8 15.5 497 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 0.3 1.8 16.0 551 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 0.3 1.8 17.0 593 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 0.3 1.8 17.5 665 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 0.3 1.8 18.0 671 3.08
10 7 / 1.35 4.05 0.7 1.0 0.8 0.3 1.8 20.0 884 1.83
16 4.7 0.7 1.0 0.8 0.3 1.8 21.5 1087 1.15
25 5.9 0.9 1.0 0.8 0.3 1.8 25.0 1466 0.727
35 7.1 0.9 1.0 0.8 0.3 1.8 27.5 1841 0.524
50 8.1 1.0 1.0 0.8 0.3 1.8 30.0 2285 0.387
70 9.7 1.1 1.2 0.8 0.3 2.0 34.5 3070 0.268
95 11.6 1.1 1.2 0.8 0.3 2.1 39.0 3989 0.193
120 12.9 1.2 1.2 0.8 0.3 2.2 42.0 4816 0.153
150 14.3 1.4 1.4 0.8 0.3 2.3 46.5 5871 0.124
185 16.0 1.6 1.4 0.8 0.3 2.4 52.0 7162 0.0991
240 18.3 1.7 1.6 0.8 0.3 2.7 58.0 9123 0.0754
300 20.7 1.8 1.6 0.8 0.3 2.8 64.0 11130 0.0601
Page - 74
Compact
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLESXLPE/FSWA/PVC (IEC 60502-1)
Ω/kmmm
(approx.)
mm²
Minimum
thickness
of Galv.
round
stranded
mm mmNo./mm mm mm mm mm kg/km
area (approx.) (approx.) (approx.)(approx.) Steel wire Steel tape
Sheath cablecovering Flat cable at 20°C
Conductor Nominal Nominal Overall
Thickness thickness
of Inner
Nominal No./ Diameter Thickness
Cross- Diameter of of
diameter Weight Conductor
Maximum
of of Resistanceof Galv.
section of wire Conductor Insulation
of
Thickness
Nominal
Section 3 - XLPE Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue, Black
Sheath - Black
FOUR CORES
1.5 1 / 1.38 1.38 0.7 1.0 0.8 0.3 1.8 15.0 446 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 0.3 1.8 15.5 483 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 0.3 1.8 16.0 532 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 0.3 1.8 16.5 544 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 0.3 1.8 17.0 637 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 0.3 1.8 18.0 659 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 0.3 1.8 18.5 645 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 0.3 1.8 19.0 783 3.08
10 7 / 1.35 4.05 0.7 1.0 0.8 0.3 1.8 21.5 1039 1.83
16 4.7 0.7 1.0 0.8 0.3 1.8 23.0 1295 1.15
25 5.9 0.9 1.0 0.8 0.3 1.8 27.0 1795 0.727
35 7.1 0.9 1.0 0.8 0.3 1.8 30.0 2263 0.524
50 8.1 1.0 1.0 0.8 0.3 1.9 32.5 2830 0.387
70 9.7 1.1 1.2 0.8 0.3 2.1 38.0 3838 0.268
95 11.6 1.1 1.2 0.8 0.3 2.2 42.5 5013 0.193
120 12.9 1.2 1.4 0.8 0.3 2.3 47.0 6144 0.153
150 14.3 1.4 1.4 0.8 0.3 2.5 51.5 7450 0.124
185 16.0 1.6 1.4 0.8 0.3 2.7 57.5 9123 0.0991
240 18.3 1.7 1.6 0.8 0.3 2.9 64.0 11666 0.0754
300 20.7 1.8 1.6 0.8 0.3 3.1 70.5 14268 0.0601
Page - 75
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLESXLPE/FSWA/PVC (IEC 60502-1)
Minimum
thickness
of Galv.
Steel tape
Conductor Nominal
Thickness thickness
Nominal Overall Maximum
Nominal Weight Conductor
Cross- Diameter of of
No./ Diameter Thickness Thickness
of wire Conductor Insulation covering
of Inner of Galv.
mm² No./mm
cable
area (approx.) (approx.) (approx.) (approx.)
mm
section
stranded
mm mmmm mm
Compact
Nominal
mm
at 20°CFlat Sheath cable
of of of
diameter
mm Ω/kmkg/km
Resistance
(approx.) Steel wire
round
Section 3 - XLPE Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : XLPE Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
FIVE CORES
1.5 1 / 1.38 1.38 0.7 1.0 0.8 0.3 1.8 16.0 508 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 0.3 1.8 16.5 520 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 0.3 1.8 17.0 601 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 0.3 1.8 17.5 615 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 0.3 1.8 18.5 730 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 0.3 1.8 19.0 750 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 0.3 1.8 20.0 875 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 0.3 1.8 20.5 897 3.08
10 7 / 1.35 4.05 0.7 1.0 0.8 0.3 1.8 23.0 1196 1.83
16 4.7 0.7 1.0 0.8 0.3 1.8 25.0 1512 1.15
25 5.9 0.9 1.0 0.8 0.3 1.8 29.0 2100 0.727
35 7.1 0.9 1.0 0.8 0.3 1.9 32.5 2700 0.524
50 8.1 1.0 1.2 0.8 0.3 2.0 36.0 3432 0.387
Page - 76
round
stranded
Compact
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLESXLPE/FSWA/PVC (IEC 60502-1)
NominalConductor Nominal Nominal Overall Maximum
Steel tape
mm
thickness
kg/km Ω/kmmm mm mm mmmm² No./mm mm mm
cable at 20°C
area (approx.) (approx.) (approx.) Steel wire (approx.) (approx.)
of Galv.
of Resistance
section of wire Conductor Insulation covering Flat Sheath cable
Weight Conductor
Cross- Diameter of of of Inner of Galv. of of
Thickness diameterMinimumNominal No./ Diameter Thickness Thickness thickness
Section 3 - XLPE Insulated Cables Armoured Cables
Constructions :Conductor (Annealed Copper)
Insulation (XLPE Compound)
Inner Covering (PVC Compound)
Double Aluminium Tape armour
Outer sheath (PVC Compound)
Constructions :Conductor (Annealed Copper)
Insulation (XLPE Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Inner Covering (PVC Compound)
Double Galvanized Steel Tape armour
Outer sheath (PVC Compound)
Page - 77
600/1000 V XLPE INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLESXLPE/DATA/PVC (acc. to IEC 60502-1)
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLESXLPE/DSTA/PVC (acc. to IEC 60502-1)
11
2
3
54
6
7
2
3
4
5
6
7
1
2
3
4
5
1
2
34
5
Note : Special application upon request* Available product in accordance to : SPLN, ICEA/NEMA, AS standard or other requirement.* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.* Anti termite performance.* Tin coated Copper conductor.* Polyethylene / Low smoke Halogen Free sheathed
Section 3 - XLPE Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Inner covering : PVC Compound Maximum 90°C
Armour : Double Aluminium tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black
Sheath - Black
SINGLE CORE
16 4.7 0.7 1.0 0.5 1.8 13.5 335 1.15
25 5.9 0.9 1.0 0.5 1.8 15.0 455 0.727
35 7.1 0.9 1.0 0.5 1.8 16.5 570 0.524
50 8.1 1.0 1.0 0.5 1.8 17.5 705 0.387
70 9.7 1.1 1.0 0.5 1.8 19.5 930 0.268
95 11.6 1.1 1.0 0.5 1.8 21.5 1210 0.193
120 12.9 1.2 1.0 0.5 1.8 23.0 1470 0.153
150 14.3 1.4 1.0 0.5 1.8 24.5 1760 0.124
185 16.0 1.6 1.0 0.5 1.8 27.0 2155 0.0991
240 18.3 1.7 1.0 0.5 1.8 29.5 2735 0.0754
300 20.7 1.8 1.0 0.5 1.9 32.0 3365 0.0601
400 23.4 2.0 1.2 0.5 2.0 35.5 4240 0.0470
500 26.5 2.2 1.2 0.5 2.1 39.5 5350 0.0366
630 30.3 2.4 1.2 0.5 2.3 44.0 6670 0.0283
Nominal
(approx.)
Thickness
of
Aluminium
tape
mm mm mm kg/kmmmmmmm² No./mm mm
area (approx.) (approx.)
covering
Cross- Diameter of of
section of wire Conductor
of of of
Thickness
of Inner
(approx.)
Ω/km
Resistance
Nominal No./ Diameter Thickness
(approx.)
Insulation
Conductor
cable
Overall
at 20°C
Maximum
XLPE/DATA/PVC (IEC 60502-1)
Thickness
Sheath
Conductor Nominal Nominal
Weightdiameter
cable
Page - 78
Compact
round
stranded
600/1000 V XLPE INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
Section 3 - XLPE Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Black
Sheath - Black
TWO CORES
1.5 1 / 1.38 1.38 0.7 1.0 0.2 1.8 12.5 220 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.2 1.8 13.0 230 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.2 1.8 13.0 258 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.2 1.8 13.5 268 7.41
4 1 / 2.26 2.26 0.7 1.0 0.2 1.8 14.0 312 4.61
4 7 / 0.85 2.55 0.7 1.0 0.2 1.8 15.0 326 4.61
6 1 / 2.77 2.77 0.7 1.0 0.2 1.8 15.0 372 3.08
6 7 / 1.04 3.12 0.7 1.0 0.2 1.8 16.0 387 3.08
10 7 / 1.35 4.05 0.7 1.0 0.2 1.8 18.0 514 1.83
16 4.7 0.7 1.0 0.2 1.8 19.0 643 1.15
25 5.9 0.9 1.0 0.2 1.8 23.0 893 0.727
35 7.1 0.9 1.0 0.2 1.8 24.5 1134 0.524
50 8.1 1.0 1.0 0.2 1.8 27.0 1422 0.387
70 9.7 1.1 1.0 0.2 1.9 30.5 1905 0.268
95 11.6 1.1 1.2 0.2 2.0 35.0 2544 0.193
120 12.9 1.2 1.2 0.5 2.1 39.5 3505 0.153
150 14.3 1.4 1.4 0.5 2.3 43.5 4245 0.124
185 15.9 1.6 1.4 0.5 2.4 48.5 5180 0.0991
240 18.3 1.7 1.6 0.5 2.6 54.0 6530 0.0754
300 20.7 1.8 1.6 0.5 2.7 59.5 8004 0.0601
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLESXLPE/DSTA/PVC (IEC 60502-1)
Thickness
Sheath
Conductor Nominal Nominal
Weightdiameter
cable cable at 20°C
(approx.)
Ω/km
Resistance
Nominal No./ Diameter Thickness
Overall Maximum
(approx.)
Insulation
Conductor
Cross- Diameter of of of of of
section of wire Conductor
mm² No./mm mm
area (approx.) (approx.)
mm mm mm kg/kmmmmm
Compact
round
stranded
Nominal
thickness
of
Steel tape
Thickness
of Inner
covering
(approx.)
Page - 79
Section 3 - XLPE Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue
Sheath - Black
THREE CORES
1.5 1 / 1.58 1.58 0.7 1.0 0.2 1.8 13.0 249 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.2 1.8 13.5 259 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.2 1.8 13.5 294 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.2 1.8 14.0 307 7.41
4 1 / 2.26 2.26 0.7 1.0 0.2 1.8 15.0 263 4.61
4 7 / 0.85 2.55 0.7 1.0 0.2 1.8 15.5 381 4.61
6 1 / 2.77 2.77 0.7 1.0 0.2 1.8 16.0 445 3.08
6 7 / 1.04 3.12 0.7 1.0 0.2 1.8 16.5 463 3.08
10 7 / 1.35 4.05 0.7 1.0 0.2 1.8 18.5 630 1.83
16 4.7 0.7 1.0 0.2 1.8 20.0 812 1.15
25 5.9 0.9 1.0 0.2 1.8 23.5 1150 0.727
35 7.1 0.9 1.0 0.2 1.8 26.0 1481 0.524
50 8.1 1.0 1.0 0.2 1.8 28.5 1882 0.387
70 9.7 1.1 1.2 0.2 1.9 33.0 2588 0.268
95 11.6 1.1 1.2 0.2 2.1 37.5 3456 0.193
120 12.9 1.2 1.2 0.5 2.2 42.0 4669 0.153
150 14.3 1.4 1.4 0.5 2.4 46.5 5708 0.124
185 15.9 1.6 1.4 0.5 2.5 51.5 6965 0.0991
240 18.3 1.7 1.6 0.5 2.7 58.0 8905 0.0754
300 20.7 1.8 1.6 0.5 2.9 64.0 10919 0.0601
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLESXLPE/DSTA/PVC (IEC 60502-1)
section of wire Conductor Insulation
of of of ResistanceCross- Diameter of of
Thickness diameter Weight ConductorNominal No./ Diameter Thickness
Maximum
cable at 20°C
Conductor Nominal Nominal Overall
(approx.) (approx.)
Sheath cablecovering of
(approx.) Steel tape (approx.)
mm² No./mm mm mm mm mm kg/km
area (approx.)
Ω/km
Compact
round
stranded
mm mm
of Inner thickness
Page - 80
Thickness Nominal
Section 3 - XLPE Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue, Black
Sheath - Black
FOUR CORES
1.5 1 / 1.38 1.38 0.7 1.0 0.2 1.8 13.5 280 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.2 1.8 14.0 293 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.2 1.8 14.5 343 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.2 1.8 15.0 357 7.41
4 1 / 2.26 2.26 0.7 1.0 0.2 1.8 16.0 426 4.61
4 7 / 0.85 2.55 0.7 1.0 0.2 1.8 16.5 446 4.61
6 1 / 2.77 2.77 0.7 1.0 0.2 1.8 17.0 531 3.08
6 7 / 1.04 3.12 0.7 1.0 0.2 1.8 17.5 552 3.08
10 7 / 1.35 4.05 0.7 1.0 0.2 1.8 20.0 764 1.83
16 4.7 0.7 1.0 0.2 1.8 21.5 999 1.15
25 5.9 0.9 1.0 0.2 1.8 25.5 1434 0.727
35 7.1 0.9 1.0 0.2 1.8 28.5 1859 0.524
50 8.1 1.0 1.0 0.2 1.9 31.5 2383 0.387
70 9.7 1.1 1.2 0.2 2.0 36.0 3311 0.268
95 11.6 1.1 1.2 0.5 2.2 42.5 4872 0.193
120 12.9 1.2 1.4 0.5 2.4 46.5 5983 0.153
150 14.3 1.4 1.4 0.5 2.5 51.0 7274 0.124
185 15.9 1.6 1.4 0.5 2.7 57.0 8922 0.0991
240 18.3 1.7 1.6 0.5 2.9 64.0 11427 0.0754
300 20.7 1.8 1.6 0.5 3.1 70.5 14015 0.0601
Ω/km
Compact
round
stranded
mm mm
(approx.)
mm² No./mm mm mm mm mm kg/km
area (approx.) (approx.) (approx.)
Sheath cable
(approx.) Steel tape
cable at 20°Csection of wire Conductor Insulation covering of
of of of ResistanceCross- Diameter of of
Thickness diameter Weight ConductorNominal No./ Diameter Thickness
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLESXLPE/DSTA/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall Maximum
Page - 81
Thickness Nominal
of Inner thickness
Section 3 - XLPE Insulated Cables Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90°C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
FIVE CORES
1.5 1 / 1.38 1.38 0.7 1.0 0.2 1.8 14.5 319 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.2 1.8 15.0 333 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.2 1.8 15.5 390 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.2 1.8 16.0 405 7.41
4 1 / 2.26 2.26 0.7 1.0 0.2 1.8 17.0 496 4.61
4 7 / 0.85 2.55 0.7 1.0 0.2 1.8 17.5 520 4.61
6 1 / 2.77 2.77 0.7 1.0 0.2 1.8 18.5 620 3.08
6 7 / 1.04 3.12 0.7 1.0 0.2 1.8 19.0 645 3.08
10 7 / 1.35 4.05 0.7 1.0 0.2 1.8 22.0 900 1.83
16 4.7 0.7 1.0 0.2 1.8 23.5 1196 1.15
25 5.9 0.9 1.0 0.2 1.8 27.5 1720 0.727
35 7.1 0.9 1.0 0.2 1.9 31.0 2252 0.524
50 8.1 1.0 1.2 0.2 2.0 35.0 2946 0.387
stranded
kg/km Ω/km
round
mm mm mm mm
Compact
mm² No./mm mm mm
cable at 20°C
area (approx.) (approx.) (approx.) Steel tape (approx.) (approx.)
of Resistance
section of wire Conductor Insulation covering of Sheath cable
Weight Conductor
Cross- Diameter of of of Inner thickness of of
Thickness Nominal Thickness diameterNominal No./ Diameter Thickness
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLESXLPE/DSTA/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall Maximum
Page - 82
DC Alternating Minimum ConductorConductor Current Insulation Short
Flat Trefoil Trefoil Resistance resistance Nominal Resistance circuit
at 20°C at 90°C / Trefoil Flat Trefoil Flat Capacitance at 20°C current /
50 Hzcore to core core to core 1 sec
A A A Ω / km Ω / km Ω / km Ω / km mH / km mH / km µF / km M Ω. km A
1.5 re/rm 22 21 22 12.1 15.43 0.1459 0.1603 0.4646 0.5108 0.0520 3000 212
2.5 re/rm 30 29 29 7.41 9.45 0.1339 0.1484 0.4264 0.4726 0.0571 2500 353
4 re/rm 42 40 37 4.61 5.88 0.1244 0.1391 0.3962 0.4424 0.0621 2000 564
6 re/rm 55 53 46 3.08 3.93 0.1160 0.1305 0.3693 0.4155 0.0665 2000 846
10 re/rm 77 74 61 1.83 2.34 0.1072 0.1217 0.3416 0.3878 0.0721 1500 1410
16 cm 105 101 79 1.15 1.47 0.1028 0.1172 0.3264 0.3726 0.0751 1500 2256
25 cm 141 135 101 0.727 0.927 0.0984 0.1130 0.3124 0.3586 0.0752 1500 3525
35 cm 176 169 122 0.524 0.669 0.0932 0.1077 0.2967 0.3429 0.0789 1000 4935
50 cm 216 207 144 0.387 0.494 0.0911 0.1056 0.2890 0.3353 0.0796 1000 7050
70 cm 279 268 178 0.268 0.343 0.0875 0.1023 0.2778 0.3240 0.0815 900 9870
95 cm 342 328 211 0.193 0.247 0.0845 0.0991 0.2674 0.3136 0.0848 800 13395
120 cm 400 383 240 0.153 0.196 0.0827 0.0974 0.2629 0.3091 0.0853 800 16920
150 cm 464 444 271 0.124 0.159 0.0829 0.0975 0.2626 0.3088 0.0846 800 21150
185 cm 533 510 304 0.0991 0.1272 0.0830 0.0976 0.2612 0.3074 0.0833 900 26085
240 cm 634 607 351 0.0754 0.0972 0.0814 0.0960 0.2565 0.3028 0.0848 800 33840
300 cm 736 703 396 0.0601 0.0779 0.0799 0.0944 0.2526 0.2988 0.0860 800 42300
400 cm 868 823 464 0.0470 0.0614 0.0728 0.0874 0.2500 0.2962 0.0865 700 56400
500 cm 998 946 525 0.0366 0.0482 0.0777 0.0923 0.2471 0.2933 0.0871 700 70500
630 cm 1151 1088 596 0.0283 0.0376 0.0770 0.0916 0.2447 0.2909 0.0880 700 88830
800 cm 1328 1252 679 0.0221 0.0310 0.0763 0.0908 0.2425 0.2887 0.0883 700 112800
1000 rm 1511 1420 767 0.0176 0.0258 0.0743 0.0889 0.2363 0.2825 0.0902 600 141000
Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W Note : 1) Reference methode of installation to be used to obtain current carryingrm : Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cm capacity for : in cable ducting, in cables conduit, cables direct in the -cm : Circular stranded compacted conductor IEC 60228 class 2 Base temperature : 20°C ground with / without added protection against mechanical damage
2) The Inductance calculated for non armour cable.
Conductor Nominal
Area
In Air ( 30°C ) In Ground 1)
mm²
CURRENT CARRYING CAPACITY FOR SINGLE CORE XLPE INSULATED CABLE
Reactance2) (50 Hz) Inductance2) (50 Hz)Current Carrying Capacity
Section 4 - General Information
Page - 83
DC Alternating Minimum ConductorConductor Current Insulation Short
Resistance resistance Nominal Resistance circuit 2 3 / 4 * 2 3 / 4 * at 20°C at 90°C / 2 / 3 4 2 / 3 4 Capacitance at 20°C current /
Core Core Core Core 50 Hz Core Core Core Core core to core core to core 1 sec
A A A A Ω / km Ω / km Ω / km Ω / km mH / km mH / km µF / km M Ω. km A
1.5 re/rm 26 23 26 22 12.1 15.43 0.0999 0.1125 0.3181 0.2498 0.0520 3000 2122.5 re/rm 36 32 34 29 7.41 9.45 0.0961 0.1086 0.3057 0.2325 0.0571 2500 3534 re/rm 49 42 44 37 4.61 5.88 0.0899 0.1025 0.2860 0.2128 0.0621 2000 5646 re/rm 63 54 56 46 3.08 3.93 0.0853 0.0980 0.2714 0.1982 0.0665 2000 846
10 re/rm 86 75 73 61 1.83 2.34 0.0802 0.0930 0.2552 0.1819 0.0721 1500 141016 cm 115 100 95 79 1.15 1.47 0.0781 0.0910 0.2485 0.1752 0.0751 1500 225625 cm 149 127 121 101 0.727 0.927 0.0779 0.0908 0.2480 0.1748 0.0752 1500 352535 cm 185 158 146 122 0.524 0.669 0.0753 0.0883 0.2397 0.1664 0.0789 1000 4935
50 cm 225 192 173 144 0.387 0.494 0.0748 0.0877 0.2379 0.1646 0.0796 1000 705070 cm 289 246 213 178 0.268 0.343 0.0734 0.0864 0.2335 0.1602 0.0815 900 987095 cm 352 298 252 211 0.193 0.247 0.0711 0.0842 0.2262 0.1530 0.0848 800 13395120 cm 410 346 287 240 0.153 0.197 0.0708 0.0839 0.2254 0.1521 0.0853 800 16920
150 cm 473 399 324 271 0.124 0.160 0.0712 0.0843 0.2267 0.1534 0.0846 800 21150185 cm 542 456 363 304 0.0991 0.1281 0.0720 0.0851 0.2292 0.1559 0.0833 900 26085240 cm 641 538 419 351 0.0754 0.0984 0.0711 0.0842 0.2264 0.1531 0.0848 800 33840300 cm 741 621 474 396 0.0601 0.0799 0.0704 0.0835 0.2240 0.1507 0.0860 800 42300400 cm 892 745 555 464 0.0470 0.0633 0.0701 0.0832 0.2231 0.1498 0.0865 700 56400
Note : re : Round solid conductor IEC 60228 class 1 Thermal resistivity of soil : 2.5 K.m / W 4* : 3 Phasa + Netral / Groundrm : Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cmcm : Circular stranded compacted conductor IEC 60228 class 2 Base temperature : 20°C
In Air ( 30°C ) Underground, Direct burial
CURRENT CARRYING CAPACITY FOR MULTICORE XLPE INSULATED CABLE
Current Carrying Capacity Reactance (50 Hz) Inductance (50 Hz)Conductor
mm²
Underground :
NominalArea
Section 4 - General Information
Page - 84
DC Alternating Minimum ConductorConductor Current Insulation Short
Flat Trefoil Trefoil Resistance resistance Nominal Resistance circuit
at 20°C at 70°C / Trefoil Flat Trefoil Flat Capacitance at 20°C current /
50 Hzcore to core core to core 1 sec
A A A Ω / km Ω / km Ω / km Ω / km mH / km mH / km µF / km M Ω. km A
1.5 re/rm 18 17 18 12.1 14.4777 0.1476 0.1735 0.4697 0.5159 0.1391 50 1742.5 re/rm 25 24 24 7.41 8.8661 0.1359 0.1621 0.4327 0.4789 0.1531 50 2904 re/rm 34 33 31 4.61 5.5159 0.1291 0.1555 0.4110 0.4572 0.1553 50 4646 re/rm 45 43 39 3.08 3.6853 0.1209 0.1475 0.3848 0.4310 0.1671 50 69610 re/rm 63 60 52 1.83 2.1897 0.1112 0.1381 0.3538 0.4000 0.1827 50 1160
16 rm 85 82 67 1.15 1.3761 0.1034 0.1307 0.3292 0.3754 0.1966 40 185625 rm 114 110 86 0.727 0.87 0.0988 0.1263 0.3145 0.3607 0.2001 40 290035 rm 143 137 103 0.524 0.6272 0.0941 0.1218 0.2995 0.3457 0.2100 40 406050 rm 174 167 122 0.387 0.4634 0.0909 0.1188 0.2895 0.3357 0.2127 30 580070 rm 225 216 151 0.268 0.3212 0.0869 0.1150 0.2767 0.3229 0.2223 30 8120
95 rm 275 264 179 0.193 0.2317 0.0864 0.1145 0.2749 0.3212 0.2205 30 11020120 rm 321 308 203 0.153 0.1841 0.0838 0.1121 0.2669 0.3131 0.2270 30 13920150 rm 372 356 230 0.124 0.1497 0.0833 0.1116 0.2651 0.3113 0.2274 20 17400185 rm 427 409 258 0.0991 0.1202 0.0828 0.1111 0.2634 0.3096 0.2279 20 21460240 rm 507 485 297 0.0754 0.0924 0.0814 0.1098 0.2592 0.3054 0.2308 20 27840
300 rm 587 561 336 0.0601 0.0746 0.0807 0.1091 0.2567 0.3029 0.2323 20 34800400 rm 689 656 394 0.0470 0.0597 0.0799 0.1084 0.2543 0.3005 0.2387 20 46400500 rm 789 749 445 0.0366 0.0482 0.0790 0.1075 0.2513 0.2975 0.2355 20 58000630 rm 905 855 506 0.0283 0.0395 0.0773 0.1059 0.2459 0.2921 0.2416 20 73080800 rm 1037 971 577 0.0221 0.0334 0.0756 0.1044 0.2406 0.2868 0.2476 20 928001000 rm 1167 1079 652 0.0176 0.0290 0.0750 0.1038 0.2386 0.2848 0.2500 20 116000
Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W Note : 1) Reference methode of installation to be used to obtain current carryingrm : Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cm capacity for : in cable ducting, in cables conduit, cables direct in the -
Base temperature : 20°C ground with / without added protection against mechanical damage2) The Inductance calculated for non armour cable.
Nominal
mm²
Area
Reactance2) (50 Hz) Inductance 2) (50 Hz)Conductor
Current Carrying Capacity In Air ( 30°C ) In Ground 1)
CURRENT CARRYING CAPACITY FOR SINGLE CORE PVC INSULATED CABLE
Section 4 - General Information
Page - 85
DC Alternating Minimum ConductorConductor Current Insulation Short
Resistance resistance Nominal Resistance circuit 2 3 / 4 * 2 3 / 4 * at 20°C at 70°C / 2 / 3 4 2 / 3 4 Capacitance at 20°C current /
Core Core Core Core 50 Hz Core Core Core Core core to core core to core 1 sec
A A A A Ω / km Ω / km Ω / km Ω / km mH / km mH / km µF / km M Ω. km A
1.5 re/rm 22 18.5 22 18 12.1 14.4777 0.1075 0.1199 0.3421 0.2688 0.1391 50 1742.5 re/rm 30 25 29 24 7.41 8.8661 0.0994 0.1120 0.3165 0.2433 0.1531 50 2904 re/rm 40 34 38 31 4.61 5.5159 0.0983 0.1109 0.3130 0.2398 0.1553 50 4646 re/rm 51 43 47 39 3.08 3.6853 0.0928 0.1054 0.2954 0.2221 0.1671 50 696
10 re/rm 70 60 63 52 1.83 2.1897 0.0865 0.0993 0.2754 0.2021 0.1827 50 116016 rm 94 80 81 67 1.15 1.3761 0.0818 0.0946 0.2604 0.1871 0.1966 40 185625 rm 119 101 104 86 0.727 0.8701 0.0807 0.0936 0.2569 0.1836 0.2001 40 290035 rm 148 126 125 103 0.524 0.6273 0.0778 0.0907 0.2478 0.1745 0.2100 40 4060
50 rm/sm 180 153 148 122 0.387 0.4635 0.0822 0.0950 0.2617 0.1884 0.2127 30 580070 rm/sm 232 196 183 151 0.268 0.3213 0.0789 0.0917 0.2510 0.1777 0.2223 30 812095 rm/sm 282 238 216 179 0.193 0.2318 0.0791 0.0920 0.2518 0.1785 0.2205 30 11020120 rm/sm 328 276 246 203 0.153 0.1842 0.0772 0.0901 0.2457 0.1724 0.2270 30 13920
150 rm/sm 379 319 278 230 0.124 0.150 0.0775 0.0904 0.2466 0.1733 0.2274 20 17400185 rm/sm 434 364 312 258 0.0991 0.1204 0.0769 0.0898 0.2447 0.1714 0.2279 20 21460240 rm/sm 514 430 361 297 0.0754 0.0926 0.0759 0.0889 0.2417 0.1684 0.2308 20 27840300 rm/sm 593 497 408 336 0.0601 0.0749 0.0756 0.0886 0.2407 0.1674 0.2323 20 34800
Note : re : Round solid conductor IEC 60228 class 1 Thermal resistivity of soil : 2.5 K.m / W 4* : 3 Phasa + Netral / Groundrm : Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cmsm : Sector shape stranded conductor IEC 60228 class 2 Base temperature : 20°C
In Air ( 30°C ) Underground, Direct burial
Underground :
mm²
Reactance (50 Hz) Inductance (50 Hz)Conductor
CURRENT CARRYING CAPACITY FOR MULTICORE PVC INSULATED CABLE
NominalArea
Current Carrying Capacity
Section 4 - General Information
Page - 86
Rating factor relating to open air temperature
Air temperature°C 10 15 20 25 30 35 40 45 50 55 60 65 70 80
PVC Insulation 1.22 1.17 1.12 1.06 1.00 0.94 0.87 0.79 0.71 0.61 0.50 - - -
XLPE Insulation 1.15 1.12 1.08 1.04 1.00 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.41
Rating factor relating to Ground temperature
Ground temp °C 10 15 20 25 30 35 40 45 50 55 60 65 70 80
PVC Insulation 1.10 1.05 1.00 0.95 0.89 0.84 0.77 0.71 0.63 0.55 0.45 - - -
XLPE Insulation 1.07 1.04 1.00 0.96 0.93 0.89 0.85 0.80 0.76 0.71 0.65 0.60 0.53 0.38
Rating factor relating to themal ground resistivity
1 1.5 2 2.5 3
1.18 1.1 1.05 1.00 0.96
Thermal Resistivity of soil K.m / W
Rating factors
In Air
Rating factor based on 3 core cable for size 1.5 ~ 10 mm²
5 0.70 0.75
Number of coreUnder ground
7 0.60 0.65
10 0.50 0.55
0.40 0.45
24 0.35 0.40
14 0.45 0.50
61 0.25 0.30
40 0.30 0.35
19 Section 4 - General Information
Page - 87
Section 4 - General Information
to be applied to reference ratings for multi-core cables in free air
Number Number of cables
of trays 1 2 3 4 6 9
1 1.00 0.88 0.82 0.79 0.76 0.73
2 1.00 0.87 0.80 0.77 0.73 0.68
3 1.00 0.86 0.79 0.76 0.71 0.66
1 1.00 1.00 0.98 0.95 0.91 -
2 1.00 0.99 0.96 0.92 0.87 -
3 1.00 0.98 0.95 0.91 0.85 -
1 1.00 0.88 0.82 0.78 0.73 0.72
2 1.00 0.88 0.81 0.76 0.71 0.70
1 1.00 0.91 0.89 0.88 0.87 -
2 1.00 0.91 0.88 0.87 0.85 -
1 1.00 0.87 0.82 0.80 0.79 0.78
2 1.00 0.86 0.80 0.78 0.76 0.73
3 1.00 0.85 0.79 0.76 0.73 0.70
1 1.00 1.00 1.00 1.00 1.00 -
2 1.00 0.99 0.98 0.97 0.96 -
3 1.00 0.98 0.97 0.96 0.93 -
Factors apply to single layer groups of cables as shown above and do not apply when cables are installed in more than one layer touching each other.
Values for such installations may be significantly lower and shall be determined by an appropriate method.
NOTE 1 Values given are averages for the cable types and range of conductor sizes considered. The spread of values is generally less than ± 5 %.
NOTE 2 Values are given for vertical a spacing between trays of 300 mm and at least 20 mm between trays and wall. For closer spacing the factors
should be reduced.
NOTE 3 Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back. For closer spacing the factors should be
reduced.
Reduction factors for group of more than one multi-core cable (note 1)
Page - 88
Method of installation
Perforated trays
(note 2)
Perforated
Vertical
trays
supports,
cleats, etc.
(note 2)
(note 3)
Ladder
Touching
Spaced
≥ 20 mm
≥ 20 mm
D
Touching
Spaced
Touching
Spaced
≥ 20 mm
≥ 20 mm
D
≥225 mm
≥225 mm
D
Section 4 - General Information
to be applied to reference rating for one circuit of single-core cables in free air
Number of
trays 1 2 3
1 0.98 0.91 0.87
2 0.96 0.87 0.81
3 0.95 0.85 0.78
1 0.96 0.86 -
2 0.95 0.84 -
1 1.00 0.97 0.96
2 0.98 0.93 0.89
3 0.97 0.90 0.86
1 1.00 0.98 0.96
2 0.97 0.93 0.89
3 0.96 0.92 0.86
1 1.00 0.91 0.89
2 1.00 0.90 0.86
1 1.00 1.00 1.00
2 0.97 0.95 0.93
3 0.96 0.94 0.90
NOTE 1 Value given are averages for the cable types and range of conductor sizes considered. The spread of values is generally less than ± 5 %.
NOTE 2 For circuits having more than one cable in parallel per phase, each three phase set of conductors should be considered as a circuit for the
purpose of this table
NOTE 3 Values are given for vertical spacings between trays of 300 mm.For closer spacing the factors should be reduced.
NOTE 4 Values are given for horizontal spacings between trays of 225 mm with trays mounted back to back and at least 20 mm between the tray
and any wall. For closer spacing the factors should be reduced.
Reduction factors for groups of more than one circuit of single-core cables (Note 1)
Perforated
trays
Page - 89
(note 4)
formation
(Note 3)
supports,cleats etc.
(Note 3)
Vertical
perforated trays
(Note 3)
Ladder
supports,cleats etc.
(Note 3)
Perforated
trays
Vertically
(Note 4)
Ladder
Use as a multiplier to
rating for
Perforated
trays
Three cables in
horizontal
Method of installation
Three cables in
trefoil
formation
Three cables in
horizontal
formation
Three cables
in vertcal
formation
Touching
≥ 20 mm
Spaced
≥
Touching
≥ 20 mm
≥ 20 mm
≥ 2 D D
225 mm
D
≥ 2 D
≥ 20 mm
≥ 2 D D
Touching
≥225 mm
Section 4 - General Information
PERMISSIBLE PULLING TENSION
Pulling equipment Permissible pulling tension (kg)
PULLING EYE 7 x (Number of core) x (Cross section area of conductor)
CABLE NET About 500 kg, but the maximum tension shall not be more than one of
conductor (same calculation as using PULLING EYE)
Reference data on Aluminium conductor
Pulling equipment Permissible pulling tension (kg)
PULLING EYE 4 x (Number of core) x (Cross section area of conductor)
CABLE NET About 500 kg, but the maximum tension shall not be more than one of
conductor (same calculation as using PULLING EYE)
Note) Cable net shall be covered more than 500 mm in length
MINIMUM BENDING RADIUS D : Diameter of cable
Reference data on other types of POWER cables
Reference data on other types of INSTRUMENT cables
Note) Sheild tape shall be
AL mylar tape
PERMISSIBLE SIDE WALL PRESSURE
300kg/m is suggested as permissible side wall pressure to the cable during installation.
Side wall pressure (T1) can be calculated with below formula.
T1 = Pulling tension (T) / Bending radius (r)
CALCULATION OF CABLE PULLING TENSION DURING INSTALLATION
The cable pulling tension (T2) during installation can be calculated with below formula.
1) Horizontal straight part : W : Weight of cable (kg/m)
2) Horizontal curve part : L : Length of cable with straight part (m)
θ : Angle of curve part (rad)
µ : Friction factor T2 : Pulling tension (kg)
on pulley T3 : Pulling tension before curve part (kg)
underground T4 : Pulling tension after curve part (kg)
in pipe
Page - 90
6D
Type of cable
Non shield cable ( XLPE/PVC etc )
Sheild cable (XLPE/PVC-S etc)
6D
0.2
0.2 - 0.3
0.5 - 0.7
Friction factor
Triplex type cable ( CVT etc )
Wire armored cable ( XLPE/SWA/PVC etc)
Tape armored cable (XLPE/DSTA/PVC etc)
Flat tape armored (XLPE/FSWA/PVC etc)
Type of cable
Sheild cable ( XLPE/PVC-S etc )
Non Sheild cable ( XLPE/PVC etc )
Multi Core Cable
8D
Sector conductorRound / Compacted Conductor
10D 12DMedium Voltage Cable
10D
10D
Minimum bending radius
Single core cable
Multi core cableSector conductor
Round/Compacted
conductor
8D
6D
8D
10D
10D
8D 12D
-
12D
12D10D
Minimum bending radius
Multi core cable
Minimum bending radius
Single core cableType of cable
12D
12D
10D
10D
-
T kg
LWT **2
µ=( )θµ
eTT *43
=
r
Section 4 - Contents & Information
Fire Performance TestsFlame Propagation Tests IEC 60332-1Part 1 - Test on a single vertical insulated wire or cable This is a relatively simple method for providing adequate indication of the flame-retardant characteristics of a single cable.
A 600 mm long cable sample is verticatlly suspended, placed in the middle of a three-sided metal screen.
This is subjected to the regulated flame of one (up to a cable diameter of 50 mm) or two (above 50 mm diameter) gas burners at an
angle of 45° to the cable. The flame is applied for a continuous time calculated according to an increasing with the cable weight
(from around 1-minute for a small control cable to about 7 minutes for a 4 core 300 mm² power cable). The test is passed if the cable
has self-extinguished and the charred or flame affected portion of the cable has not reached the top of the sample.
IEC 60332-3Part 3 - Test on bunched wire or cablesThis test was developed to obtain a method to determine the flame propagation characteristics of bunched cables.
It can not be assumed that because a single vertical cable complies with the requirements of IEC 60332 part 1 it will also behave in
a similar manner when bunched with others cables.
The propagation of a flame along a bunch of cables depends on a number of features, such as :
The volume of combustible material exposed to the fire
The geometrical configuration of the cables
The temperature at which it is possible to ignite any gases emitted from the cables
The quantity of combustible gas released from the cables
The volume of air passing through the cable installation
The test consists of a vertical chamber, 1 x 2 x 4 m. Openings air inlet and outlet are provided in the base and the top of the test
chamber for a controlled air flow rate during the test. The cable samples to be tested are 3.5 m long and fixed to a steel ladder mounted
150 mm from the rear wall vertically with the test chamber. The number of lengths of cables in the test depends on the test categoty
based on the volume of combustible material.
Test Category Volume of combustible material Time of flame application
A 7 litres / m 40 Minutes
B 3.5 litres / m 40 Minutes
C 1.5 litres / m 20 Minutes
A ribbon gas burner of a set size and heat flow rate, operating at 800°C is mounted horizontally in front of the cable samples at a set
distance and height. The test is passed if the charred or affected portion of the samples have not reached a height exceeding 2.5 m
above the bottom edge of the burner.
IEC 60331 - 21 (1999)
Fire resisting characteristics of electric cables Circuit Integrity TestThis test determines the circuit integrity of a cable during and after a prolonged fire :
A horizontally suspended sample 1200 mm long is placed 75 mm above a 610 mm long ribbon type gas burner, the flame temperature
of which is regulated to 750°C. The conductors of the sample are connected to an AC voltage source, at the operating voltage, via fuses.
The flame and test voltage shall be applied continuously for a period of 90 min. 12 hours after the flame has been extinguished the cable
is energised again.
The test is passed if no failure of any of the fuses occurs.