LV product characteristics
2005
Circuit protectionand control devices
0.5 to 6300 A
cover.fm Page 1 Mercredi, 16. mars 2005 2:59 14
The Guiding System, the new way to create your electrical installations
A comprehensive offer of products with consistent design
The Guiding System is first and foremost a Merlin Gerin product offer covering all electrical distribution needs. However, what makes all the difference is that these products have been designed to operate together: mechanical and electrical compatibility, interoperability, modularity, communication.Thus the electrical installation is both optimised and more efficient: better continuity of supply, enhanced safety for people and equipment, guaranteed upgradeability, effective monitoring and control.
Tools to simplify design and implementation
With the Guiding System, you have a comprehensive range of tools - the Guiding Tools - that will help you increase your product knowledge and product utilisation. Of course this is in compliance with current standards and procedures.These tools include technical booklets and guides, design aid software, training courses, etc. and are regularly updated.
For a genuine partnership with you
Because each electrical installation is unique, there is no standard solution. With the Guiding System, the variety of combinations allows for genuine customisation solutions. You can create and implement electrical installations to meet your creative requirements and design knowledge. You and Merlin Gerin’s Guiding System form a genuine partnership.
For more details on the Guiding System,consult www.merlin-gerin.com
cover.fm Page 2 Mercredi, 16. mars 2005 2:59 14
1
0
A consistent design of offers from Medium Voltage to Ultra terminal
All Merlin Gerin offers are designed according to electrical, mechanical and communication consistency rules.The products express this consistency by their overall design and shared ergonomics.
Electrical consistency:
Each product complies with or enhances system performance at co-ordination level: breaking capacity, Isc, temperature rise, etc. for more safety, continuity of supply (discrimination) or economic optimisation (cascading).The leading edge technologies employed in Merlin Gerin’s Guiding System ensure high performance levels in discrimination and cascading of protection devices, electrodynamic withstand of switches and current distributors, heat loss of devices, distribution blocks and enclosures.Likewise, inter-product ElectroMagnetic Compatibilty (EMC) is guaranteed.
Discrimination guarantees co-ordination between the operating characteristics of serial-connected circuit-breakers. Should a fault occurs downstream, only the circuit-breaker placed immediately upstream from the fault will trip.
Mechanical consistency:
Each product adopts dimensional standards simplifying and optimising its use within the system.It shares the same accessories and auxiliaries and complies with global ergonomic choices (utilisation mode, operating mode, setting and configuration devices, tools, etc.) making its installation and operation within the system a simpler process.
Prefabricated and tested solutions, upstream and downstream from the device complying with the IEC 60439-1 switchboard standard.
Communication consistency:
Each product complies with global choices in terms of communication protocols (Modbus, Ethernet, etc.) for simplified integration in the management, supervision and monitoring systems.
Thanks to the use of standard Web technologies, you can offer your customers intelligent Merlin Gerin switchboards allowing easy access to information: follow-up of currents, voltages, powers, consumption history, etc.
Guiding Tools for more efficient design and implementation of your installations.
p01-04.fm Page 1 Lundi, 14. mars 2005 5:17 17
2
0
SM6
Medium voltage switchboard system from 1 to 36 kV
Sepam
Protection relays
Masterpact
Protection switchgear from 100 to 6300 A
TrihalMV/LV dry cast resin transformer from 160 to 5000 kVA
EvolisMV vacuum switchgear and components from 1 to 24 kV.
The Technical guide
These technical guides help you comply with installation standards and rules i.e.:The electrical installation guide, the protection guide, the switchboard implementation guide, the technical booklets and the co-ordination tables all form genuine reference tools for the design of high-performance electrical installations.For example, the LV protection co-ordination guide - discrimination and cascading - optimises choice of protection and connection devices while also increasing markedly continuity of supply in the installations.
CAD software and tools
The CAD software and tools enhance productivity and safety.They help you create your installations by simplifying product choice through easy browsing in the Guiding System offers.Last but not least, they optimise use of our products while also complying with standards and proper procedures.
p01-04.fm Page 2 Lundi, 14. mars 2005 5:17 17
3
0
Compact
Protection switchgear system from 100 to 630 A
Multi 9
Modular protection switchgear system up to 125 A
Prisma Plus
Functional system for electrical distribution switchboards up to 3200 A
Pragma CanalisEnclosures for distribution switchboards up to 160 A
Prefabricated Busbar Trunking from 25 to 4000 A
PowerLogicPowermanagement
Training
Training allows you to acquire the Merlin Gerin expertise (installation design, work with power on, etc.) for increased efficiency and a guarantee of improved customer service.The training catalogue includes beginner’s courses in electrical distribution, knowledge of MV and LV switchgear, operation and maintenance of installations, design of LV installations to give but a few examples.
p01-04.fm Page 3 Lundi, 14. mars 2005 5:17 17
4
p01-04.fm Page 4 Lundi, 14. mars 2005 5:17 17
5
Circuit protection and control devices
Contents
Multi 9Multi 9 circuit breakers from 0.5 to 125 A 6
EasyPactEasyPact circuit breakers from 15 to 250 A 8
Compact NSCompact NS AC circuit breakers up to 630 A 10Compact NS AC circuit breakers from 630 to 3200 A 12Compact NS DC circuit breakers from 100 to 630 A 14
Masterpact NT and NWMasterpact NT06 to NT16AC circuit breakers and switch-disconnectors from 630 to 1600 A 16Masterpact NW08 to NW63AC circuit breakers and switch-disconnectors from 800 to 6300 A 18Masterpact NW10 to NW40 DC circuit breakers from 800 to 6300 A 20
Micrologic control unitsOverview of functions 22
Interpact INSInterpact INS40 to 160 switch-disconnectors 24Interpact INS250-100 to 630 switch-disconnectors 28Interpact INS630b to 2500 switch-disconnectors 32
Interpact INVInterpact INV100 to 630 switch-disconnectors 36Interpact INV630b to 2500 switch-disconnectors 40
Fupact Fupact INFp32 to INFp800 switch-disconnector fuses 44Fupact ISFT100 to ISFT630 fuse-switch disconnectors 48Fupact ISFL160 to ISFL630 fuse-switch disconnectors 52
VigirexProtection and monitoring relays 56
p05.fm Page 5 Lundi, 14. mars 2005 5:17 17
6
Multi 9
C60.
DPN Vigi.
C120.
Multi 9 circuit breakersfrom 0.5 to 125 A
NG125.
0569
84N
R_2
1P
B10
0270
_16
0567
38R
_29
0569
08N
R-3
3
Multi 9 circuit breakers 6 to 1 to 4 to 6 to 6 to32 A 40 A 40 A 45 A 40 ADPNa DPN N DPN N Vigi C60H RCBO C60a
Number of poles 1 + N 1 + N 1 + N 1 + N 1 2-
Electrical characteristicsRated current (A) In 30 °C 6-32 1-40 4-40 6-45 6-40
40 °C - - - - -Rated insulation voltage (V) Ui 300 300 300 440 500Impulse withstand voltage (kV) Uimp 4 4 4 4 6Rated operational voltage (V) Ue AC 50/60 Hz 230 230 230 50-250 440Fast closing b b b b bDisconnection with positive contact indication - b b - bAC breaking capacity (kA rms) - - - - -IEC 60947-2 (EN 60947-2) Icu 130 V - - - - 10 -
240 V - - - 10 5 10400 V - - - - 3 5415 V - - - - 3 5440 V - - - - - 3500 V - - - - - -
Ics (% of Icu) - - - - 75 %IEC 60898 Icn 230/400 V 4.5 6 6 - 4.5
Ics 230/400 V 4.5 6 6 - 4.5
DC breaking capacity (kA)
IEC 60947-2 (EN 60947-2) Icu 24/48 V - - - - -60 V - 15 - - 10 (1P)125 V - - - - 10 (2P)125 V - - - - 20 (3P)250 V - - - - 25 (4P)500 V - - - - -
Ics (% of Icu) 100 % 100 % - - 100 %
Trip units (non adjustable)Curve type B (lm = 3.2 to 4.8 ln) b b b - b
C (lm = 7 to 10 ln) b b b b bD (lm = 10 to 14 ln) - - - - -K (lm = 10 to 14 In) - - - - -Z (lm = 2.4 to 3.2) - - - - -MA (lm = 12 ln) - - - - -
Personal protection
Add-on rcd's (Vigi module) - - integrated integrated b30-300 mA 10-100 mA
Electrical auxiliaries
Auxiliary and alarm switches (OF-SD) - b b - bShunt trip (MX); undervoltage release (MN) - b b - b
InstallationPlug in base - - - - bTerminal shieds - - - - bPadlocking device - b b b bRotary handle - - - - bDimensions (mm) W 18 18 36 18 18/P
H 81 81 81 111 81D 70 70 70 73 73
p06-07.p65 14/03/2005, 17:066
7
Multi 9
1 to 4 to 6 to 6 to 0.5 to 63 A 0.5 to 32 to 50 to 63 to 10 to 125 A 10 to 80 A 4 to40 A 40 A 45 A 40 A 25 A 40 A 63 A 125 A 80 ADPN N DPN N Vigi C60H RCBO C60a C60N C60H C60L C120N C120H NG125N NG125H NG125L NG125LMA1 + N 1 + N 1 + N 1 2-3-4 1 2-3-4 1 2-3-4 1 2-3-4 1 2-3-4 1 2-3-4 1 2-3-4 1 2-3-4 1 2-3-4 1 2-3-4 1 2-3-4 - 2-3
1-40 4-40 6-45 6-40 63 63 - - - - - - - - -- - - - - - y 25 32-40 50-63 63-125 10-125 10-125 10-80 10-80 4-80300 300 440 500 500 500 500 500 500 500 500 690 690 690 6904 4 4 6 6 6 6 6 6 6 6 8 8 8 8230 230 50-250 440 440 440 440 440 440 440 440 500 500 500 500b b b b b b b b b b b b b b bb b - b b b b b b b b b b b b- - - - - - - - - - - - - - -- - - 10 - 20 - 30 - 50 - 50 - 50 - 20 - 30 - 50 - 70 - 100 - -- - 10 5 10 10 20 15 30 25 50 20 40 15 30 10 20 15 30 25 50 36 70 50 100 100- - - 3 5 3 10 4 15 6 25 5 20 4 15 3 10 4.5 15 6 25 9 36 12.5 50 50- - - 3 5 3 10 4 15 6 25 5 20 4 15 3 10 4.5 15 6 25 9 36 12.5 50 50- - - - 3 - 6 - 10 - 20 - 15 - 10 - 6 - 10 - 20 - 30 - 40 40- - - - - - - - - - - - - - - - - - - 6 8 6 10 6 12 12- - - 75 % 75 % 50 % 50 % 50 % 50 % 75 % 50 % 75 % 75 % 75 % 75 %6 6 - 4.5 6 10 - - - 10 15 - - - -6 6 - 4.5 6 7.5 - - - 7.5 7.5 - - - -
- - - - - - - - - 10 (1P) 15 (1P) - - - -15 - - 10 (1P) 15 (1P) 20 (1P) 25 (1P) 25 (1P) 25 (1P) - - 25 (1P) 36 (1P) 50 (1P) -- - - 10 (2P) 20 (2P) 25 (2P) 30 (2P) 30 (2P) 30 (2P) 10 (1P) 15 (1P) 25 (1P) 36 (1P) 50 (1P) -- - - 20 (3P) 30 (3P) 40 (3P) 50 (3P) 50 (3P) 50 (3P) - - - - - -- - - 25 (4P) 40 (4P) 50 (4P) 60 (4P) 60 (4P) 60 (4P) 10 (2P) 15 (2P) 25 (2P) 36 (2P) 50 (2P) -- - - - - - - - - - - 25 (4P) 36 (4P) 50 (4P) -100 % - - 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % -
b b - b b b b b b b b b - b -b b b b b b b b b b b b b b -- - - - b b b b b b b b - b -- - - - - - b b b - - - - - -- - - - - - b b b - - - - - -- - - - - - b y 40 A - - - - - b
- integrated integrated b b b b b b b b b b30-300 mA 10-100 mA
b b - b b b b b b b b b bb b - b b b b b b b b b b
- - - b b y 63 A -- - - b b bb b b b b b- - - b b b18 36 18 18/P 27/P 27/P81 81 111 81 81 10370 70 73 73 73 81
p06-07.p65 14/03/2005, 17:067
8
EasyPact EasyPact circuit breakersfrom 15 to 250 A 0
DB
1068
91-2
5
EZC100.
EasyPact circuit breakersNumber of polesRated current (A) In at 40 °C
Rated insulation voltage (V) UiRated impulse withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DC
Electrical characteristics as per IEC 60947-2 and EN 60947-2Ultimate breaking capacity (kA rms) Icu AC 50/60 Hz 110/130 V
220/230/240 V380 V400/415 V440 V
PB
1012
10a-
27
EZC250.
550 VDC 125 V (1P)
250 V (2P in series)
Rated service breaking capacity Ics % Icu 110-400 V415-550 V
Suitability for isolation
Utilisation categoryPollution degreeEndurance (C-O cycles) Mechanical
Electrical In/415 V
Electrical characteristics as per JIS C8370Breaking capacity (kA) Icn AC 50/60 Hz 130 V
220 V
460 V
Electrical characteristics as per NEMA-AB1Breaking capacity (kA) HIC AC 50/60 Hz 240 V
277/480Y VProtection
Overload protection BimetalInstantaneous protection MagneticAuxiliaries
Indication contacts Auxiliary switch AXAlarm switch ALCombined AX + AL AXAL
Voltage releases Shunt trip release SHTUndervoltage release UVR
InstallationConnection Crimp lugs/barsAccessories Box lugs for bare cables
Rotary handles directextended
Terminal extensions
SpreadersPhase barriersTerminal shields
Padlocking systemDIN rail plate
Dimension and weightDimensions (mm) W
HD
Weight (kg)(1) Only 3 poles.(2) 50 in 2 poles.
p08-09.fm Page 8 Lundi, 14. mars 2005 5:20 17
9
EasyPact0
EZC100B EZC100F EZC100N EZC100H EZC250F EZC250N EZC250H3 3 1 3 1 2-3 3 3 2-315, 20, 25, 30, 40, 50, 60
15, 20, 25, 30, 40, 50, 60, 75, 80, 100
15, 20, 25, 30, 40, 50, 60, 75, 80, 100
15, 20, 25, 30, 40, 50, 60, 75, 80, 100
15, 20, 25, 30, 40, 50, 60, 75, 80, 100
15, 20, 25, 30, 40, 50, 60, 75, 80, 100
100, 125, 150, 160, 175, 200, 225, 250
100, 125, 150, 160, 175, 200, 225, 250
100, 125, 150, 160, 175, 200, 225, 250
690 690 690 690 690 690 690 690 6906 6 6 6 6 6 6 6 6
550-
550250
550250
550250
550250
550250
550250
550250
550250
10 25 25 25 50 100 25 50 85
10 25 18 25 25 100 (1) 25 50 857.5 10 2.5 18 5 30 18 25 367.5 10 2.5 15 5 30 18 25 365 7.5 - 10 - 20 15 20 252.5 5 - 5 - 10 5 8 10- 5
55-
55
10-
1010
55
2020
3030-
25 % 50 % 50 % 50 % 50 % 50 % 50 % 50 % 50 %25 % 50 % 50 % 50 % 50 % 25 % 50 % 50 % 50 %b b b b b b b b bA A A A A A A A A3 3 3 3 3 3 3 3 38500 8500 8500 8500 8500 8500 10000 10000 10000
4000 4000 4000 4000 4000 4000 5000 5000 5000
10 25 15 25 30 100 30 50 8510 25 - 25 - 100 30 50 85
5 7.5 - 10 - 25 15 25 35
- - 10 25 18 100 25 50 85- - 10 10 18 18 (2) 15 18 25 (1)
fixed fixed fixed fixed fixed fixed fixed fixed fixedfixed fixed fixed fixed fixed fixed fixed fixed fixed
b b b b b b b b bb b b b b b b b bb b b b b b b b bb b b b b b b b bb b b b b b b b b
b b b b b b b b bb b b b b b b b bb b b b b b b b bb b b b b b b b b- - - - - - b b bb b b b b b b b bb b b b b b b b bb b b b b b b b bb b b b b b b b bb b b b b b - - -
75 75 25 75 25 60 105 105 50 (2), 75 (1)
130 130 130 130 130 130 165 165 16560 60 60 60 60 60 60 60 60
0.78 0.78 0.28 0.78 0.28 0.78 1.3 1.3 1.1
p08-09.fm Page 9 Lundi, 14. mars 2005 5:20 17
Compact NS
10
Compact NS AC circuit breakersup to 630 A
Compact NS250H.
Compact NS630N.
PB
1010
44_4
2
(1) 2P in 3P case for type N only.(2) Specific trip units are available for operationalvoltages > 525 V.(3) NS100N et U u 500 V: Ics = 50 % Icu.(4) Operational voltage y 500 V.
PB
1010
50_3
3
Compact circuit breakers NS125ENumber of poles 3-4Control manual toggle b
direct or extended rotary handle -electric -
Connections fixed front connection brear connection b
plug-in (on base) front connection -rear connection -
withdrawable (on chassis) front connection -rear connection -
Electrical characteristics as per IEC 60947-2 and EN 60947-2Rated current (A) In 40 °C 125
65 °C -Rated insulation voltage (V) Ui 750Rated impulse withstand voltage (kV) Uimp 8Rated operational voltage (V) Ue AC 50/60 Hz 500
DC -
Type of circuit breaker E
Ultimate breaking capacity (kA rms) lcu AC 220/240 V 2550/60 Hz 380/415 V 16/10
440 V 10500 V 6525 V -660/690 V -
Service breaking capacity (kA rms) lcs % Icu 50 %Suitability for isolation bUtilisation category ADurability (C-O cycles) mechanical 10000
electrical 440 V In/2 6000In 6000
Electrical characteristics as per NEMA AB1 (H.I.C.) EBreaking capacity (kA) 240 V 5
480 V 5600 V -
Electrical characteristics as per UL508 EBreaking capacity (kA) 240 V -
480 V -600 V -
Protection
Trip units non interchangeableOverload protection long time Ir (In x …) 12.5… 125 (A)Short-circuit protection short time lsd (Ir x …) -
instantaneous Ii (In x …) -Earth-fault protection lg (In x …) -Zone selective interlocking ZSI -Add-on earth-leakage protection add-on Vigi module b
combination with Vigirex relay bCurrent measurements -
Additional measurement, indication and control auxiliaries
Indication contacts bMX shunt and MN undervoltage releases bVoltage-presence indicator -Current-transformer module and ammeter module -Insulation-monitoring module -
Remote communication by bus
Device-status indication -Device remote operation -Transmission of settings -Indication and identification of protection devices and alarms -Transmission of measured current values -
InstallationAccessories terminal extensions and spreaders b
terminal shields and interphase barriers bescutcheons b
Dimensions (mm) W x H x D fixed, front connections 2-3P / 4P 105 x 161 x 86Weight (kg) fixed, front connections 3P / 4P 1.8 / 2.3
Source changeover system
Manual, remote-operated and automatic source changeover systems -
p10-13.p65 14/03/2005, 17:1410
11
Compact NS
NS125E NS100 NS160 NS250 NS400 NS6303-4 2 (1)-3-4 2 (1)-3-4 2 (1)-3-4 3-4 3-4b b b b b b
or extended rotary handle - b b b b b- b b b b b
front connection b b b b b brear connection b b b b b bfront connection - b b b b brear connection - b b b b bfront connection - b b b b brear connection - b b b b b
7-2125 100 160 250 400 630- 100 150 220 320 500750 750 750 750 750 7508 8 8 8 8 8
/60 Hz 500 690 690 690 690 690- 500 500 500 500 500
E N SX H L N SX H L N SX H L N H L N H L
220/240 V 25 85 90 100 150 85 90 100 150 85 90 100 150 85 100 150 85 100 150Hz 380/415 V 16/10 36 50 70 150 36 50 70 150 36 50 70 150 50 70 150 50 70 150
440 V 10 35 50 65 130 35 50 65 130 35 50 65 130 42 65 130 42 65 130500 V 6 25 36 50 100 30 36 50 70 30 36 50 70 30 50 100 30 50 70525 V - 22 35 35 100 22 35 35 50 22 35 35 50 22 35 100 22 35 50660/690 V - 8 10 10 75 8 10 10 20 8 10 10 20 10 (2) 20 (2) 75 (2) 10 (2) 20 (2) 35 (2)
50 % 100 % (3) 100 % 100 % 100 % 100 % (4)
b b b b b bA A A A A A10000 50000 40000 20000 15000 15000
In/2 6000 50000 40000 20000 12000 8000In 6000 30000 20000 10000 6000 4000
E N SX H L N SX H L N SX H L N H L N H L5 85 90 100 200 85 90 100 200 85 90 100 200 85 100 200 85 100 2005 35 50 65 130 35 50 65 130 35 50 65 130 42 65 130 42 65 130- 8 20 35 50 20 20 35 50 20 20 35 50 20 35 50 20 35 50
E N SX H L N SX H L N SX H L N H L N H L- 85 85 85 - 85 85 85 - 85 85 85 - - - - - - -- 25 50 65 - 35 50 65 - 35 50 65 - - - - - - -- 10 10 10 - 10 10 10 - 18 18 18 - - - - - - -
non interchangeable TM (thermal-magnetic) STR22 (electronic) STR23 (electronic) STR53 (electronic)…) 12.5… 125 (A) b b b bx …) - - b b b…) - b b b b
x …) - - - - b- - - - b
n Vigi module b b b b bnation with Vigirex relay b b b b b
- - - - b
b b bb b b- b b- b b- b b
- b b b b- b b b b- - - - b- - - - b- - - - b
nd spreaders b b bnterphase barriers b b b
b b bns 2-3P / 4P 105 x 161 x 86 105 x 161 x 86 / 140 x 161 x 86 140 x 255 x 110 / 185 x 255 x 110ns 3P / 4P 1.8 / 2.3 2.0 to 2.2 / 2.6 to 2.8 6.2 to 8.1
- b b
p10-13.p65 14/03/2005, 17:1411
Compact NS
12
E45
178R
_68
(1) 65 °C with vertical connections. See the temperaturederating tables for other types of connections.(2) Ics: 100 % Icu for breaking capacity 440V/500V/660V
Ics: 75 % Icu for breaking capacity 220V/380V.
Compact NS1600H.
Compact NS2000H.
PB
1012
06_3
9 Compact circuit breakers NS630b NS80Number of poles 3-4Control manual toggle b
direct or extended rotary handle belectric b
Type of circuit breaker N H LConnections fixed front connection b b b
rear connection b b bfront connection with bare cables b b -
withdrawable (on chassis) front connection b b brear connection b b b
Electrical characteristics as per IEC 60947-2 and EN 60947-2Rated current (A) In 50 °C 630 800
65 °C (1) 630 800Rated insulation voltage (V) Ui 750Rated impulse withstand voltage (kV) Uimp 8Rated operational voltage (V) Ue AC 50/60 Hz 690
DC 500
Type of circuit breaker N H LUltimate breaking capacity (kA rms) lcu AC 220/240 V 50 70 150
50/60 Hz 380/415 V 50 70 150440 V 50 65 130500/525 V 40 50 100660/690 V 30 42 25
DC 250 V - - -500 V - - -
Service breaking capacity (kA rms) lcs Value or % Icu manual operation 100 % 75 % 100 %electrical operation 75 % 50 % 100 %
Short-time withstand current (kA rms) lcw 0.5 s 25 25 10V AC 50/60 Hz 1 s 17 17 7V AC 50/60 Hz 3 s - - -Integrated instantaneous protection kA peak ±10 % 55Suitability for isolation bUtilisation category B B ADurability (C-O cycles) mechanical 10000
electrical 440 V In/2 6000 6000 4000In 5000 5000 3000
690 V In/2 4000 4000 3000In 2000 2000 2000
Pollution degree III
Electrical characteristics as per Nema AB1 N H LBreaking capacity at 60 Hz (kA) 240 V 50 65 125
480 V 35 50 100600 V 25 50 -
Protection and measurementsInterchangeable control units Micrologic 2.0Overload protection long time Ir (In x …) bShort-circuit protection short time Isd (Ir x …) -
instantaneous Ii (In x …) bEarth-fault protection lg (In x …) -Residual earth-leakage protection I∆∆∆∆∆n -Zone selective interlocking ZSI -Protection of the fourth pole bCurrent measurements -
Remote communication by busDevice-status indication bDevice remote operation bTransmission of settings -Indication and identification of protection devices and alarms -Transmission of measured current values -
Additional indication and control auxiliariesIndication contacts bVoltage releases MX shunt release b
MN undervoltage release b
InstallationAccessories terminal extensions and spreaders b
terminal shields and interphase barriers bescutcheons b
Dimensions fixed devices, front connections (mm) 3P 327 x 210 x 147H x W x D 4P 327 x 280 x 147Weight fixed devices, front connections (kg) 3P 14
4P 18
Source changeover systemManual, remote-operated and automatic source changeover systems b
Compact NS AC circuit breakersfrom 630 to 3200 A
p10-13.p65 14/03/2005, 17:1412
13
Compact NS
NS630b NS800 NS1000 NS1250 NS1600 NS1600b NS2000 NS2500 NS32003-4 3-4 3-4 3-4b b b b
xtended rotary handle b b b -b b b -
N H L N H N H N Hection b b b b b b b b bection b b b b b b b - -ection with bare cables b b - b b - - - -ection b b b b b b b - -ection b b b b b b b - -
7-2630 800 1000 1250 1600 1600 2000 2500 3200630 800 1000 1250 1510 1550 1900 2500 2970750 750 750 7508 8 8 8
Hz 690 690 690 690500 500 500 500
N H L N H N H N H220/240 V 50 70 150 50 70 50 70 85 125380/415 V 50 70 150 50 70 50 70 70 85440 V 50 65 130 50 65 50 65 65 85500/525 V 40 50 100 40 50 40 50 65 -660/690 V 30 42 25 30 42 30 42 65 -250 V - - - - - - - - -500 V - - - - - - - - -
% Icu manual operation 100 % 75 % 100 % 100 % 75 % 75 % 50 % 100 % (2) 75 %electrical operation 75 % 50 % 100 % 75 % 50 % 75 % 50 % 100 % (2) 75 %
25 25 10 25 25 25 25 - -17 17 7 17 17 17 17 - -- - - - - - - 32 32
10 % 55 55 55 130 130b b b bB B A B B B B B B10000 10000 10000 5000
In/2 6000 6000 4000 5000 5000 3000In 5000 5000 3000 4000 2000 2000In/2 4000 4000 3000 3000 2000 2000In 2000 2000 2000 2000 1000 1000
III III III III
N H L N H N H N H240 V 50 65 125 50 65 50 65 85 125480 V 35 50 100 35 50 35 50 65 85600 V 25 50 - 25 50 25 50 50 -
Micrologic 2.0 Micrologic 5.0 Micrologic 2.0 A Micrologic 5.0 A Micrologic 6.0 A Micrologic 7.0 Ab b b b b b
…) - b - b b bb b b b b b
) - - - - b -- - - - - b- - b b b bb b b b b b- - b b b b
b b b b b bb b b b - -- - b b b b- - b b b b- - b b b b
b bb b
e b b
spreaders b -rphase barriers b b
b b327 x 210 x 147 350 x 420 x 160327 x 280 x 147 350 x 535 x 16014 2418 36
b -
p10-13.p65 14/03/2005, 17:1513
14
Compact NS Compact NS DC circuit breakers from 100 to 630 A
PB
1010
47a-
14
Compact circuit breakersNumber of poles
Electrical characteristics as per IEC 60947-1/ 60947-2 and EN 60947-1 / 60947-2Rated current at 40 °C In (A)Rated insulation voltage Ui (V)
Rated impulse withstand voltage Uimp (kV peak)Rated operational voltage Ue (V DC)Type of circuit breaker
Ultimate breaking capacity(L/R = 5 ms and L/R = 15 ms)
Icu (kA rms) V DC 48-125 V (1P) (1)
250 V (1P) (1)
500 V (2P) (1)
750 V (3P) (1)
PB
1010
48a-
20
Service breaking capacity Ics % IcuRated making capacity Icm % Icu
Utilisation categoryBreaking time (ms)Suitability for isolation
Pollution degree (as per IEC 60664-1)Protection against overcurrents (see "LV circuit breakers and switch-disconnectors direct current 16 to 4000 A" - ABTED205160EN)
Trip units Built-in
InterchangeableProtection Overloads
Short-circuits
Durability
PB
1010
55a-
27
(O/F cycles) MechanicalElectrical 250 V In
250 V In/2500 V In
500 V In/2750 V In750 V In/2
Indication and control auxiliariesAuxiliary contactsVoltage release MX shunt release
MN undervoltage release
Installation and connectionsFixed Front connection
PB
1009
05a-
36
Rear connectionPlug-in (base) Front connection
Rear connectionWithdrawable (chassis) Front connection
Rear connection
Dimensions and weightDimensionsH x W x D (mm) connected in series
Fixed 1P2P
3P4P
Weight (kg)connected in series
Fixed 1P
2P3P4P
(1) Number of poles taking part in current interruption.Example. The NS100N circuit breaker exists in the following versions:- 1 pole with an Icu of 50 kA, for systems y 250 V- 2 poles with an Icu of 85 kA, for systems y 500 V; 1 pole can be used in a 250 V system.
p14-15.fm Page 14 Lundi, 14. mars 2005 5:22 17
15
Compact NS
NS100 NS160 NS250 NS400 NS6301 2 3-4 1 2 3-4 3-4 3-4 3-4
100 160 250 400 550800 800 800 800 800
8 8 8 8 8250 500 750 250 500 750 750 750 750N H N H DC N H N H DC DC DC DC50 85 85 100 100 50 85 85 100 100 100 100 10050 85 85 100 100 50 85 85 100 100 100 100 100- - 85 100 100 - - 85 100 100 100 100 100
- - - - 100 - - - - 100 100 100 100100 %100 %
A< 10 msbIII
b b b b - b b b b - - - -
- - - - b - - - - b b b bb b b b b b b b b b - - -b b b b b b b b b b b b b
10000 50005000 1000
10000 20005000 1000
10000 20005000 100010000 2000
bbb
bb - - - - b - - - - b b b b - - - - b - - - - b b b b - - - - b - - - - b b b b - - - - b - - - - b b b b
161 x 35 x 86 - - 161 x 35 x 86 - - - - 161 x 70 x 86 - - 161 x 70 x 86 - -
- - 161 x 105 x 86 - - 161 x 105 x 86 255 x 140 x 110 - - 161 x 140 x 86 - - 161 x 140 x 86 225 x 185 x 1100.7 - - 0.7 - - -
- 1.2 - - 1.2 - - - - 1.6 to 1.9 - - 1.6 to 1.9 6.0 - - 2.1 to 2.3 - - 2.1 to 2.3 7.8
p14-15.fm Page 15 Lundi, 14. mars 2005 5:22 17
16
Masterpact NT and NW Masterpact NT06 to NT16AC circuit breakers and switch-disconnectorsfrom 630 to 1600 A 0
PB
1007
67a-
48
Common characteristicsNumber of poles 3-4Rated insulation voltage (V) Ui 1000
Impulse withstand voltage (kV) Uimp 12Rated operational voltage (V AC 50/60 Hz) Ue 690/1000Suitability for isolation IEC 60947-2
Degree of pollution IEC 60664-1 3
Circuit-breaker characteristics as per IEC 60947-2Rated current (A) In at 40 °C/50 °C (1)
Rating of 4th pole (A)
Sensor ratings (A)Type of circuit breaker
Ultimate breaking capacity (kA rms) Icu 220/415 V
V AC 50/60 Hz 440 V525 V690 V
1000 VRated service breaking capacity (kA rms) Ics % IcuUtilisation category
Rated short-time withstand current (kA rms)V AC 50/60 Hz
Icw 0.5 s1 s3 s
Integrated instantaneous protection (kA peak ±10 %) Rated making capacity (kA peak) Icm 220/415 VV AC 50/60 Hz 440 V
525 V690 V
1000 VBreak time (ms) between tripping order and arc extinctionClosing time (ms)
Circuit-breaker characteristics as per NEMA AB1Breaking capacity (kA)V AC 50/60 Hz
240 V
480 V600 V
(1) 50 °C: rear vertical connected. Refer to temperature derating tables for other connection types.(2) See the current-limiting curves in the "additional characteristics" section.(3) SELLIM system.(4) Available for 480 V NEMA.(5) Suitable for motor control (direct-on-line starting).
Switch-disconnector characteristics as per IEC 60947-3 and Annex AType of switch-disconnector
Rated making capacity (kA peak) Icm 220 VAC23A/AC3 category V AC 50/60 Hz 440 V
525/690 V
1000 VRated short-time withstand current (kA rms) Icw 0.5 sAC23A/AC3 category V AC 50/60 Hz 1 s
3 sUltimate breaking capacity Icu (kA rms) with an external protection relayMaximum time delay: 350 ms
690 V
Mechanical and electrical durability as per IEC 60947-2/3 at In/IeService life Mechanical with maintenance
C/O cycles x 1000 without maintenanceType of circuit breakerRated current In (A)
C/O cycles x 1000 Electrical without maintenance 440 V (4)
IEC 60947-2 690 V 1000 V
Type of circuit breaker or switch-disconnectorRated operationnal current Ie (A) AC23A
C/O cycles x 1000 Electrical without maintenance 440 V (4)
IEC 60947-3 690VType of circuit breaker or switch-disconnectorRated operationnal current Ie (A) AC3 (5)
Motor power 380/415 V (kW)440 V (kW)
C/O cycles x 1000 Electrical without maintenance 440 V (4)
IEC 60947-3 Annex M/IEC 60947-4-1 690 V
p16-19.fm Page 16 Lundi, 14. mars 2005 5:24 17
17
Masterpact NT and NW
Sensor selectionSensor rating (A) 250 (1) 400 630 800 1000 1250 1600Ir threshold setting(A) 100 to 250 160 to 400 250 to 630 320 to 800 400 to 1000 500 to 1250 640 to 1600
(1) For NT02 rating, please consult us.
NT06 NT08 NT10 NT12 NT16630 800 1000 1250 1600630 800 1000 1250 1600
400 to 630 400 to 800 400 to 1000 630 to 1250 800 to 1600H1 H2 L1 (2) H10 H1 H2 H1042 50 150 - 42 50 -
42 50 130 - 42 50 -42 42 100 - 42 42 -42 42 25 - 42 42 -
- - - 20 - - 20100 % 100 %B B A B B B B
42 36 10 20 42 36 2042 36 - 20 - 36 2024 20 - - 24 20 -
- 90 10 x In (3) - - 90 -88 105 330 - 88 105 -88 105 286 - 88 105 -
88 88 220 - 88 88 -88 88 52 - 88 88 -
- - - 42 - - 4225 25 9 - 25 25 -< 50 < 50
42 50 150 - 42 50 -
42 50 100 - 42 50 -42 42 25 - 42 42 -
HA HA10 HA HA1075 - 75 -75 - 75 -75 - 75 -
- 42 - 4236 20 36 2036 20 36 20
20 20 20 2036 36
25
12.5H1 H2 L1 H10 H1 H2 L1 H10 H1 H2 L1 H10 H1 H2 H10 H10 H1 H2630 800 1000 1250 16006 6 3 - 6 6 3 - 6 6 3 - 6 6 - - 6 63 3 2 - 3 3 2 - 3 3 2 - 3 3 - - 3 3- - - 0.5 - - - 0.5 - - - 0.5 - - 0.5 0.5 - -
H1/H2/HA630 800 1000 1250 16006 6 6 6 6
3 3 3 3 3H1/H2/HA500 630 800 1000 1000y 250 250 to 335 335 to 450 450 to 560 450 to 560y 300 300 to 400 400 to 500 500 to 630 500 to 6306
-
p16-19.fm Page 17 Lundi, 14. mars 2005 5:24 17
18
Masterpact NT and NW Masterpact NW08 to NW63AC circuit breakers and switch-disconnectorsfrom 800 to 6300 A
PB
1007
68a-
38
Common characteristicsNumber of poles 3-4Rated insulation voltage (V) Ui 1000/1250
Impulse withstand voltage (kV) Uimp 12Rated operational voltage (V AC 50/60 Hz) Ue 690/1150 Suitability for isolation IEC 60947-2
Degree of pollution IEC 60664-1 4 (1000 V) / 3 (1250 V)
Circuit-breaker characteristics as per IEC 60947-2Rated current (A) at 40 °C / 50 °C (1)
Rating of 4th pole (A)
Sensor ratings (A)
PB
1007
69a-
70
Type of circuit breakerUltimate breaking capacity (kA rms)V AC 50/60 Hz
Icu 220/415/440 V525 V
690 V1150 V
Rated service breaking capacity (kA rms) Ics % Icu
Utilisation categoryRated short-time withstand current (kA rms)V AC 50/60 Hz
Icw 1 s3 s
Integrated instantaneous protection (kA peak ±10 %)Rated making capacity (kA peak)V AC 50/60 Hz
Icm 220/415/440 V525 V
690 V1150 V
Break time (ms) between tripping order and arc extinctionClosing time (ms)
Circuit-breaker characteristics as per NEMA AB1Breaking capacity (kA)V AC 50/60 Hz
240/480 V600 V
Unprotected circuit-breaker characteristics: tripping by shunt trip as per IEC 60947-2Type of circuit breaker
Ultimate breaking capacity (kA rms) V AC 50/60 Hz Icu 220...690 VRated service breaking capacity (kA rms) Ics % IcuRated short-time withstand current (kA rms) Icw 1 s
3 sOverload and short-circuit protection with external protection relay:short-circuit protection, maximum delay: 350 ms (4)
Rated making capacity (kA peak) V AC 50/60 Hz Icm 220...690 V
(1) 50 °C: rear vertical connected. Refer to temperature derating tables for other connection types.(2) See the current-limiting curves in the "additional characteristics" section.(3) Equipped with a trip unit with a making current of 90 kA peak.(4) External protection must comply with permissible thermal constraints of the circuit breaker (please consult us).No fault-trip indication by the SDE or the reset button.(5) Available for 480 V NEMA.(6) Suitable for motor control (direct-on-line starting).
Switch-disconnector characteristics as per IEC 60947-3 and Annex AType of switch-disconnector
Rated making capacity (kA peak)AC23A/AC3 category V AC 50/60 Hz
Icm 220...690 V
1150 VRated short-time withstand current (kA rms)AC23A/AC3 category V AC 50/60 Hz
Icw 0.5 s1 s
3 s
Mechanical and electrical durability as per IEC 60947-2/3 at In/IeService life Mechanical with maintenanceC/O cycles x 1000 without maintenanceType of circuit breakerRated current In (A)
C/O cycles x 1000 Electrical without maintenance 440 V (5)
IEC 60947-2 690 V
1150 VType of circuit breaker or switch-disconnectorRated operational current Ie (A) AC23A
C/O cycles x 1000 Electrical without maintenance 440 V (5)
IEC 60947-3 690 VType of circuit breaker or switch-disconnectorRated operational current Ie (A) AC3 (6)
Motor power 380/415 V (kW)440 V (5) (kW)
690 V (kW)C/O cycles x 1000 Electrical without maintenance 440/690 V (5)
IEC 60947-3 Annex M/IEC 60947-4-1
p16-19.fm Page 18 Lundi, 14. mars 2005 5:24 17
19
Masterpact NT and NW
Sensor selectionSensor rating (A) 250 (1) 400 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300Ir threshold setting(A) 100 160 250 320 400 500 630 800 1000 1250 1600 2000 2500
to 250 to 400 to 630 to 800 to 1000 to 1250 to 1600 to 2000 to 2500 to 3200 to 4000 to 5000 to 6300(1) For NW02 rating, please consult us.
NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW40b NW50 NW63800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300
400to 800
400to 1000
630to 1250
800 to 1600 1000 to 2000 1250to 2500
1600to 3200
2000 to 4000 2000to 4000
2500to 5000
3200to 6300
N1 H1 H2 L1 (2) H10 H1 H2 H3 L1 (2) H10 H1 H2 H3 H10 H1 H242 65 100 150 - 65 100 150 150 - 65 100 150 - 100 15042 65 85 130 - 65 85 130 130 - 65 85 130 - 100 130
42 65 85 100 - 65 85 100 100 - 65 85 100 - 100 100- - - - 50 - - - - 50 - - - 50 - -100 % 100 % 100 % 100 %
B B B B42 65 85 30 50 65 85 65 30 50 65 85 65 50 100 10022 36 50 30 50 36 75 65 30 50 65 75 65 50 100 100
Without Without 190 80 Without Without 190 150 80 Without Without 190 150 Without Without 27088 143 220 330 - 143 220 330 330 - 143 220 330 - 220 33088 143 187 286 - 143 187 286 286 - 143 187 286 - 220 286
88 143 187 220 - 143 187 220 220 - 143 187 220 - 220 220- - - - 105 - - - - 105 - - - 105 - -
25 25 25 10 25 25 25 25 10 25 25 25 25 25 25 25< 70 < 70 < 70 < 80
42 65 100 150 - 65 100 150 150 - 65 100 150 - 100 15042 65 85 100 - 65 85 100 100 - 65 85 100 - 100 100
HA HF (3) HA HF (3) HA HF (3) HA50 85 50 85 55 85 85
100 % 100 % 100 % 100 %50 85 50 85 55 85 85
36 50 36 75 55 75 85Without Without Without Without Without Without Without
105 187 105 187 121 187 187
NW08 / NW10 / NW12 NW16 NW20 NW25 / NW32 / NW40 NW40b / NW50 / NW63NA HA HF HA10 HA HF HA10 HA HF HA10 HA HF HA10 HA88 105 187 - 105 187 - 105 187 - 121 187 - 187
- - - 105 - - 105 - - 105 - - 105 -- - - - - - - - - - - - - -42 50 85 50 50 85 50 50 85 50 55 85 50 85
- 36 50 50 50 50 50 50 50 50 55 75 50 85
25 20 1012.5 10 5N1/H1/H2 L1 H10 H1/H2 L1 H10 H1/H2 H3 H10 H1 H2800/1000/1250/1600 2000 2500/3200/4000 4000b/5000/630010 3 - 8 3 - 5 1.25 - 1.5 1.510 3 - 6 3 - 2.5 1.25 - 1.5 1.5
- - 0.5 - - 0.5 - - 0.5 - -H1/H2/NA/HA/HF H1/H2/H3/HA/HF H1/H2/HA800/1000/1250/1600 2000 2500/3200/4000 4000b/5000/630010 8 5 1.510 6 2.5 1.5H1/H2/HA/HF H1/H2/H3/HA/HF800 1000 1250 1600 2000335 to 450 450 to 560 560 to 670 670 to 900 900 to 1150400 to 500 500 to 630 500 to 800 800 to 1000 1000 to 1300
y 800 800 to 1000 1000 to 1250 1250 to 1600 1600 to 20006
p16-19.fm Page 19 Lundi, 14. mars 2005 5:24 17
20
Masterpact NT and NW Masterpact NW10 to NW40 DC circuit breakersfrom 800 to 6300 A
E88
193a
-31
Masterpact circuit breakersNumber of poles Version C or D
Version E
Electrical characteristics as per IEC 60947-1/ 60947-2 and EN 60947-1 / 60947-2Rated current at 40 °C / 50 °C (1) In (A)
Rated insulation voltage Ui (V)Rated impulse withstand voltage Uimp (kV peak)Rated operational voltage Ue (V DC)
Type of circuit breakerUltimate breaking capacity L/R = 5 ms Icu (kA) V DC 500
750
PB
1011
29a-
34
900L/R = 15 ms Icu 500
750
900L/R = 30 ms Icu 500
750
900Service breaking capacity Ics % IcuRated making capacity Icm % Icu
NW10DC 4P. Short-time withstand current Icw 1 sUtilisation categoryBreaking time (ms)
Making time (ms)Suitability for isolationPollution degree (as per IEC 60664-1)
Protection against overcurrents (see "LV circuit breakers and switch-disconnectors direct current 16 to 4000 A" - ABTED205160EN)Trip units Built-in
Protection OverloadsShort-circuits
Durability(O/F cycles) Mechanical With maintenance
Without maintenanceElectrical Without maintenance 500 V CC
900 V CCIndication and control auxiliaries
Auxiliary contacts
Voltage release MX shunt releaseMN undervoltage release
Characteristics of switch-disconnectors as per IEC 60947-3 and EN 60947-3Type of switch-disconnector
Rated making capacity Icm % Icu
Rated short-time withstand current Icw 1 s
Installation and connectionsConnection Drawout 3P RC Horizontal
4P VerticalFixed 3P RC Horizontal
4P VerticalDimensions and weight
DimensionsH x W x D (mm) connected in series
Drawout 3P
4PFixed 3P
4P
Weight (kg)connected in series (approximate values)
Drawout 3P4P
Fixed 3P
4P(1) 50 °C - see the derating table for the NW40.
p20-21.fm Page 20 Lundi, 14. mars 2005 5:25 17
21
Masterpact NT and NW
NW10 NW20 NW403 3 34 4 4
1000 2000 4000
1000 2000 400012 12 12500/900 500/900 500/900
N H N H N H85 100 85 100 85 100- 85 - 85 - 85
- 85 - 85 - 8535 85 35 85 35 85- 50 - 50 - 50
- 35 - 35 - 3525 50 25 50 25 50- 50 - 50 - 50
- 25 - 25 - 25100 %100 %
50 85 50 85 50 85B30 to 75
< 70b b b b b b4
b b b b b b- - - - - -b b b b b b
20000100008500 5000 2000
- 2000 - 2000 - 1000
b b b b b bb b b b b bb b b b b b
HA HA HA- 85 - 85 - 85
- 85 - 85 - 85
b b b b - -b b b b b bb b b b - -
b b b b b b
439 x 441 x 494 439 x 441 x 594
439 x 556 x 494 439 x 556 x 594352 x 422 x 427 352 x 422 x 527352 x 537 x 427 352 x 537 x 527
90 to 116125 to 14660 to 86
85 to 106
p20-21.fm Page 21 Lundi, 14. mars 2005 5:25 17
22
Micrologic control units Overview of functions 0
All Masterpact and Compact NS630b up to 3200 A are equipped with a Micrologic control unit that can be changed on site.Control units are designed to protect Power circuits and loads. Alarms may be programmed for remote indications.Measurements of current, voltage, frequency, power and power quality optimise continuity of service and energy management.
DependabilityIntegration of protection functions in an ASIC electronic component used in all Micrologic control units guarantees a high degree of reliability and immunity to conducted or radiated disturbances.On Micrologic A, P and H control units, advanced functions are managed by an independent microprocessor.
Note: in the event of Masterpact circuit breaker DC, there is a version Micrologic 1.0 DC.For more information, consult the "LV circuit breakers and switch-disconnectors direct current 16 to 4000 A" catalogue - ABTED205160EN.
Micrologic name codes Current protection
X: type of protectionb 2 for basic protectionb 5 for selective protectionb 6 for selective + earth-fault protectionb 7 for selective + earth-leakage protection.
Y: control-unit generationIdentification of the control-unit generation."0" signifies the first generation.
Z: type of measurementb A for "ammeter"b P for "power meter"b H for "harmonic meter".
Micrologic 2: basic protection
DB
1011
16
Protection:long time+ instantaneous
Micrologic 5: basic protection
DB
1011
17
Protection: long time+ short time+ instantaneous
PB
1007
72a-
32 Micrologic 6: selective + earth-fault protection
DB
1011
17
DB
1011
18
Protection: long time + short time + instantaneous + earth fault
Micrologic 7: selective + earth-leakage protection
DB
1011
17
DB
1011
19
Protection: long time + short time + instantaneous + earth leakage
2.0 AX Y Z
p22-23.fm Page 22 Lundi, 14. mars 2005 5:26 17
23
Micrologic control units0
Measurements and programmable protectionA: ammeterb I1, I2, I3, IN, Iearth-fault, Iearth-leakage and maximeter for these measurementsb fault indicationsb settings in amperes and in seconds.
P: A + power meter + programmable protectionb measurements of V, A, W, VAR, VA, Wh, VARh, VAh, Hz, Vpeak, Apeak, power factor and maximeters and minimetersb IDMTL long-time protection, minimum and maximum voltage and frequency, voltage and current imbalance, phase sequence, reverse powerb load shedding and reconnection depending on power or currentb measurements of interrupted currents, differentiated fault indications, maintenance indications, event histories and time-stamping, etc.
H: P + harmonicsb power quality: fundamentals, distortion, amplitude and phase of harmonics up to the 31st orderb waveform capture after fault, alarm or on requestb enhanced alarm programming: thresholds and actions.
2.0 A
DB
1011
20
5.0 A
DB
1011
21
5.0 P
DB
1011
22
5.0 H
DB
1011
22
6.0 A
DB
1011
23
6.0 P
DB
1011
24
6.0 H
DB
1011
24
7.0 A
DB
1011
23
7.0 P
DB
1011
24
7.0 H
DB
1011
24
p22-23.fm Page 23 Lundi, 14. mars 2005 5:26 17
24
Interpact INS Interpact INS40 to 160switch-disconnectors 0
0521
64a-
38
Interpact INS80 switch-disconnector.
Interpact INS switch-disconnectorsNumber of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3Conventional thermal current (A) Ith at 60 °CConventional thermal current in enclosure Ithe at 60 °C
Rated insulation level (V) Ui AC 50/60 HzImpulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DCRated operational voltage AC20 and DC20 (V) AC 50/60 HzRated operational current (A) Ie Electrical AC 50/60 Hz
220-240 V
0521
68a-
50
Interpact INS160 switch-disconnector.
380-415 V440-480 V (1)
500 V660-690 V
Electrical DC125 V (2P in series)250 V (4P in series)
Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V230 V (NEMA)380-415 V
440 V480 V (NEMA)500-525 V
660-690 V
0592
02a-
50
Interpact INS160 emergency-off switch-disconnector.
Rated duties Uninterrupted duty
Intermittent dutyShort-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone)
Max. (with upstream protectioncircuit breaker)
Short-time withstand current (A rms) Icw 1 s
3 s20 s30 s
Suitability for isolationDurability (category A) (O - C-O cycles) Mechanical
Electrical AC 50/60 Hz220-240 V380-415 V440 V
500 V690 V
Electrical DC250 V
Positive contact indicationVisible break
Emergency-off switch disconnectorDegree of pollution
Upstream protectionSee the “LV switch-disconnectors - Interpact INS/INV 40 to 2500 A" catalogue(1) Suitable for 480 V NEMA.
p24-27.fm Page 24 Lundi, 14. mars 2005 5:26 17
25
Interpact INS0
INS40 INS63 INS80 INS100 INS125 INS1603-4 3-4 3-4 3-4 3-4 3-4
40 63 80 100 125 16040 63 80 100 125 160
690 690 690 750 750 7508 8 8 8 8 8500 500 500 690 690 690
250 250 250 250 250 250690 690 690 750 750 750AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A40 40 63 63 80 80 100 100 125 125 160 16040 40 63 63 80 72 100 100 125 125 160 16040 40 63 63 80 63 100 100 125 125 160 160
40 32 63 40 80 40 100 100 125 125 160 160- - - - - - 100 63 125 80 160 100DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A40 40 63 63 80 80 100 100 125 125 160 16040 40 63 63 80 80 100 100 125 125 160 160
11 15 22 22 37 457,5 15 15 22 37 4520 30 37 45 55 75
22 30 37 55 55 9022 30 30 55 75 9018,5 22 22 55 75 110
- - - 55 75 90b b b b b bclass 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 %15 15 15 20 20 2075 75 75 154 154 154
3000 3000 3000 5500 5500 5500
1730 1730 1730 3175 3175 3175670 670 670 1230 1230 1230550 550 550 1000 1000 1000
b b b b b b20000 20000 20000 15000 15000 15000AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15001500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15001500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500
1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500- - - - - - 1500 1500 1500 1500 1500 1500DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500b b b b b b- - - - - -
b b b b b bIII III III III III III
- - - - - -
p24-27.fm Page 25 Lundi, 14. mars 2005 5:26 17
26
Interpact INS Interpact INS40 to 160switch-disconnectors 0
Interpact INS switch-disconnectorsInstallation
Fixed, front connectionFixed, rear connectionOn symmetrical rails
On a backplate
ConnectionBy cables To bare cable connectorsBy cables with lugs Directly to terminals
To spreaders
To vertical-connection adapters via cable-lug adaptersFlat-facing bars Directly to terminals
To spreaders
Edgewise bars To vertical-connection adapters
Indication and measurement auxiliariesAuxiliary contactsVoltage-presence indicatorCurrent-transformer module
Ammeter module
Control, locking and interlockingControl Direct front rotary handle
Extended front rotary handleDirect lateral rotary handle
Extended lateral rotary handleLocking By keylock
By padlocks
Interlocking By keylockMechanical
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3-4 poles with front handle)
Installation and connection accessoriesBare cable connectorsRear connectors
Terminal extensionsSpreadersOne-piece spreader
Terminal shroudsTerminal shieldsInterphase-barrier
Front panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm)
Dimensions and weightsOverall dimensions H x W x D (mm) 3 poles
4 polesApproximate weight (kg) 3 poles
4 poles
Enclosure dimensions for Ithe
DB
1054
13
H x W x D (mm)
p24-27.fm Page 26 Lundi, 14. mars 2005 5:26 17
27
Interpact INS0
INS40 INS63 INS80 INS100 INS125 INS160
b b b b b b- - - b b bb b b - - -
b b b b b b
b b b b b b- - - b b b- - - - - -
- - - - - -- - - b b b- - - - - -
- - - - - -
b b b b b b- - - - - -- - - - - -
- - - - - -
b b b b b bb b b b b bb b b b b bb b b b b b- - - - - -b b b b b b- - - - - -b b b b b b- - - b b b0.7 < Nm < 1.3 0.7 < Nm < 1.3 0.7 < Nm < 1.3 1.4 < Nm < 2 1.4 < Nm < 2 1.4 < Nm < 2
b b b b b b- - - - - -
- - - - - -- - - - - -- - - - - -
b b b b b bb b b b b bb b b b b b- - - - - -- - - - - -8 8 8 8 8 8
85 x 90 x 62.5 85 x 90 x 62.5 85 x 90 x 62.5 100 x 135 x 62.5 100 x 135 x 62.5 100 x 135 x 62.5
85 x 90 x 62.5 85 x 90 x 62.5 85 x 90 x 62.5 100 x 135 x 62.5 100 x 135 x 62.5 100 x 135 x 62.50.5 0.5 0.5 0.8 0.8 0.80.6 0.6 0.6 0.9 0.9 0.9
190 x 115 x 55 190 x 115 x 55 190 x 115 x 55 260 x 160 x 55 260 x 160 x 55 260 x 160 x 55
p24-27.fm Page 27 Lundi, 14. mars 2005 5:26 17
28
Interpact INS Interpact INS250-100 to 630switch-disconnectors 0
0566
48a-
41
Interpact INS250 switch-disconnector.
Interpact INS switch-disconnectorsNumber of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3Conventional thermal current (A) Ith at 60 °CConventional thermal current in enclosure Ithe at 60 °C
Rated insulation level (V) Ui AC 50/60 HzImpulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DCRated operational voltage AC20 and DC20 (V) AC 50/60 HzRated operational current (A) Ie Electrical AC 50/60 Hz
220-240 V380-415 V440-480 V (1)
500-525 V
0566
52a-
41
Interpact INS250 emergency-off switch-disconnector.
660-690 VElectrical DC
125 V (2P in series)250 V (4P in series)
Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V230 V (NEMA)380-415 V
440 V480 V (NEMA)500-525 V
660-690 VRated duties Uninterrupted duty
Intermittent duty
0594
87a-
49
Interpact INS400 switch-disconnector.
Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone)Max. (with upstream protectioncircuit breaker)
Short-time withstand current (A rms) Icw 1 s
3 s20 s30 s
Suitability for isolationDurability (category A) (O - C-O cycles) Mechanical
Electrical AC 50/60 Hz440 V500 V690 V
Electrical DC250 V
Positive contact indication
Visible breakEmergency-off switch disconnectorDegree of pollution
0594
88a-
49
Interpact INS400 emergency-off switch-disconnector.
Upstream protectionSee the “LV switch-disconnectors - Interpact INS/INV 40 to 2500 A" catalogue
(1) Suitable for 480 V NEMA.(2) 550 A (DC).
p28-31.fm Page 28 Lundi, 14. mars 2005 5:26 17
29
Interpact INS0
INS250-100 INS250-160 INS250-200 INS250 INS320 INS400 INS500 INS6303-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4
100 160 200 250 320 400 500 630100 160 200 250 320 400 500 630 (2)
750 750 750 750 750 750 750 7508 8 8 8 8 8 8 8690 690 690 690 690 690 690 690
250 250 250 250 250 250 250 250750 750 750 750 750 750 750 750AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A100 100 160 160 200 200 250 250 320 320 400 400 500 500 630 630100 100 160 160 200 200 250 250 320 320 400 400 500 500 630 630100 100 160 160 200 200 250 250 320 320 400 400 500 500 630 630
100 100 160 160 200 200 250 250 320 320 400 400 500 500 630 630100 100 160 160 200 200 250 250 320 320 400 400 500 500 630 630DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC23B100 100 160 160 200 200 250 250 320 320 400 400 500 500 550 550 630100 100 160 160 200 200 250 250 320 320 400 400 500 500 550 550 630
22 45 55 75 90 110 132 20022 45 55 75 90 110 150 20045 75 90 132 160 200 250 315
55 90 110 150 185 220 250 40055 90 110 150 185 220 250 37555 110 132 160 220 250 355 400
55 90 160 210 250 400 500 560b b b b b b b bclass 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 %30 30 30 30 50 50 50 50330 330 330 330 330 330 330 330
8500 8500 8500 8500 20000 20000 20000 20000
4900 4900 4900 4900 11500 11500 11500 115002200 2200 2200 2200 4900 4900 4900 49001800 1800 1800 1800 4000 4000 4000 4000
b b b b b b b b15000 15000 15000 15000 10000 10000 10000 10000AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15001500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15001500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500
DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC23A DC23B DC23A DC23B DC23A DC23B DC23A DC23B1500 1500 1500 1500 1500 1500 1500 1500 1000 - 1000 - 1000 - 1000 200b b b b b b b b- - - - - - - -b b b b b b b bIII III III III III III III III
- - - - - - - -
p28-31.fm Page 29 Lundi, 14. mars 2005 5:26 17
30
Interpact INS Interpact INS250-100 to 630switch-disconnectors 0
Interpact INS switch-disconnectorsInstallation
Fixed, front connectionFixed, rear connectionOn symmetrical rails
On a backplate
ConnectionBy cables To bare cable connectorsBy cables with lugs Directly to terminals
To spreaders
To vertical-connection adapters via cable-lug adaptersFlat-facing bars Directly to terminals
To spreaders
Edgewise bars To vertical-connection adapters
Indication and measurement auxiliariesAuxiliary contactsVoltage-presence indicatorCurrent-transformer module
Ammeter module
Control, locking and interlockingControl Direct front rotary handle
Extended front rotary handleDirect lateral rotary handle
Extended lateral rotary handleLocking By keylock
By padlocks
Interlocking By keylockMechanical
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3-4 poles with front handle)
Installation and connection accessoriesBare cable connectorsRear connectors
Terminal extensionsSpreadersOne-piece spreader
Terminal shroudsTerminal shieldsInterphase-barrier
Front panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm)
Dimensions and weightsOverall dimensions H x W x D (mm) 3 poles
4 polesApproximate weight (kg) 3 poles
4 poles
Enclosure dimensions for Ithe
DB
1054
13
H x W x D (mm)
p28-31.fm Page 30 Lundi, 14. mars 2005 5:26 17
31
Interpact INS0
INS250-100 INS250-160 INS250-200 INS250 INS320 INS400 INS500 INS630
b b b b b b b bb b b b b b b b- - - - - - - -
b b b b b b b b
b b b b b b b bb b b b b b b bb b b b b b b b- - - - - - - -b b b b b b b bb b b b b b b b- - - - b b b b
b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b b
b b b b b b b bb b b b b b b bb b b b - - - -
b b b b - - - -b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b b5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 13.5 < Nm < 16.5 13.5 < Nm < 16.5 13.5 < Nm < 16.5 13.5 < Nm < 16.5
b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b bb b b b - - - -
- - - - - - - -b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b b15 15 15 15 50 50 50 50
136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130
136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130 205 x 185 x 1302 2 2 2 4.6 4.6 4.6 4.62.2 2.2 2.2 2.2 4.9 4.9 4.9 4.9
400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200
p28-31.fm Page 31 Lundi, 14. mars 2005 5:26 17
32
Interpact INS Interpact INS630b to 2500switch-disconnectors 0
PB
1000
16a-
55
Interpact INS1600 switch-disconnector.
Interpact INS switch-disconnectorsNumber of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3Conventional thermal current (A) Ith at 60 °CConventional thermal current in enclosure Ithe at 60 °C
Rated insulation level (V) Ui AC 50/60 HzImpulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DCRated operational voltage AC20 and DC20 (V) AC 50/60 HzRated operational current (A) Ie Electrical AC 50/60 Hz
220-240 V
380-415 V
PB
1000
18a-
55
Interpact INS1600 emergency-off switch-disconnector.
440-480 V (1)
500-525 V
660-690 V
Electrical DC125 V (2P in series)250 V (4P in series)
Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V380-400 V
415 V500-525 V660-690 V
Rated duties Uninterrupted dutyIntermittent duty
PB
1000
20a-
65
Interpact INS2500 switch-disconnector.
Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone)
Max. (with upstream protectioncircuit breaker)
Short-time withstand current (A rms) Icw 0.5 s0.8 s1 s
3 s20 s30 s
Suitability for isolationDurability (category B) (O - C-O cycles) Mechanical
Electrical AC 50/60 Hz
220-240 V
380-415 V
440-480 V (1)
500-525 V
660-690 V
Electrical DC125 V (2P)250 V (4P)
Positive contact indication
Visible breakEmergency-off switch disconnectorDegree of pollution
Upstream protectionSee the “LV switch-disconnectors - Interpact INS/INV 40 to 2500 A" catalogue
(1) Suitable for 480 V NEMA.(2) For vertical connection busbars only. For horizontal connection busbars, see derating charts in the “LV switch-disconnectors - Interpact INS/INV 40 to 2500 A" catalogue.
p32-35.fm Page 32 Lundi, 14. mars 2005 5:29 17
33
Interpact INS 0
INS630b INS800 INS1000 INS1250 INS1600 INS2000 INS25003-4 3-4 3-4 3-4 3-4 3-4 3-4
630 800 1000 1250 1600 (2) 2000 2500630 800 1000 1250 1600 (2) 2000 2500
1000 1000 1000 1000 1000 1000 100012 12 12 12 12 12 12690 690 690 690 690 690 690
750 750 750 750 750 750 750800 800 800 800 800 800 800AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B
AC21AAC22BAC22A
AC23A AC21B AC22B AC23B AC21B AC22B AC23B
630 630 630 800 800 800 1000 1000 1000 1250 1250 1250 16001450
16001450
1250 2000 2000 - 2500 2500 -
630 630 630 800 800 800 1000 1000 1000 1250 1250 1250 16001450
16001450
1250 2000 2000 - 2500 2500 -
630 630 630 800 800 800 1000 1000 1000 1250 1250 1250 16001250
16001250
1250 2000 2000 - 2500 2500 -
630 630 630 800 800 800 1000 1000 1000 1250 1250 1250 16001250
16001250
1250 2000 2000 - 2500 2500 -
630 630 630 800 800 800 1000 1000 1000 1250 1250 1250 16001250
16001250
1250 2000 2000 - 2500 2500 -
DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21B DC22B DC23B DC21B DC22B DC23B630/2 630/2 630/2 800/2 800/2 800/2 1000/2 1000/2 1000/2 1250/2 1250/2 1250/2 1600/2 1600/2 1600/2 2000/2 2000/2 - 2500/2 2500/2 -630/4 630/4 630/4 800/4 800/4 800/4 1000/4 1000/4 1000/4 1250/4 1250/4 1250/4 1600/4 1600/4 1600/4 2000/4 2000/4 - 2500/4 2500/4 -
250 250 315 400 400 - -400 400 560 710 710 - -
500 500 630 800 800 - -560 560 710 900 900 - -710 710 900 - - - -
b b b b b b bclass 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 %75 75 75 75 75 105 105
330 330 330 75 75 105 105
50 50 50 50 50 50 5042 42 42 42 42 50 5035 35 35 35 35 50 50
20 20 20 20 20 30 3010 10 10 10 10 13 138 8 8 8 8 11 11
b b b b b b b5000 3000 3000 3000 3000 500 500AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B
AC21AAC22BAC22A
AC23B AC21B AC22B AC23B AC21B AC22B AC23B
1000 1000 1000 500 500 500 500 500 500 500 500 500 100500
100500
500 100 100 - 100 100 -
1000 1000 1000 500 500 500 500 500 500 500 500 500 100500
100500
500 100 100 - 100 100 -
1000 1000 1000 500 500 500 500 500 500 500 500 500 100500
100500
500 100 100 - 100 100 -
1000 1000 1000 500 500 500 500 500 500 500 500 500 100500
100500
500 100 100 - 100 100 -
1000 1000 1000 500 500 500 500 500 500 500 500 500 100500
100500
500 100 100 - 100 100 -
DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23B DC21B DC22B DC23B DC21B DC22B DC23B1000 1000 1000 500 500 500 500 500 500 500 500 500 500 500 500 100 100 - 100 100 -1000 1000 1000 500 500 500 500 500 500 500 500 500 500 500 500 100 100 - 100 100 -b b b b b b b- - - - - - -b b b b b - -III III III III III III III
- - - - - - -
p32-35.fm Page 33 Lundi, 14. mars 2005 5:29 17
34
Interpact INS Interpact INS630b to 2500switch-disconnectors 0
Interpact INS switch-disconnectorsInstallation
Fixed, front connectionFixed, rear connectionOn symmetrical rails
On a backplate
ConnectionBy cables To bare cable connectorsBy cables with lugs Directly to terminals
To spreaders
To vertical-connection adapters via cable-lug adaptersFlat-facing bars Directly to terminals
To spreaders
Edgewise bars To vertical-connection adapters
Indication and measurement auxiliariesAuxiliary contactsVoltage-presence indicatorCurrent-transformer module
Ammeter module
Control, locking and interlockingControl Direct front rotary handle
Extended front rotary handleDirect lateral rotary handle
Extended lateral rotary handleLocking By keylock
By padlocks
Interlocking By keylockMechanical
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3-4 poles with front handle)
Installation and connection accessoriesBare cable connectorsRear connectors
Terminal extensionsSpreadersOne-piece spreader
Terminal shroudsTerminal shieldsInterphase-barrier
Front panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm)
Dimensions and weightsOverall dimensions H x W x D (mm) 3 poles
4 polesApproximate weight (kg) 3 poles
4 poles
Enclosure dimensions for Ithe
DB
1054
13
H x W x D (mm)
p32-35.fm Page 34 Lundi, 14. mars 2005 5:29 17
35
Interpact INS0
INS630b INS800 INS1000 INS1250 INS1600 INS2000 INS2500
b b b b b b bb b b b b b b- - - - - - -
b b b b b b b
- - - - - - -- - - - - b b- - - - - - -
b b b b b - -b b b b b b bb b b b b - -
b b b b b - -
b b b b b b b- - - - - - -- - - - - - -
- - - - - - -
b b b b b b bb b b b b b b- - - - - - -
- - - - - - -b b b b b b bb b b b b b bb b b b b b b- - - - - - -
- - - - - - -30 30 30 30 30 60 60
- - - - - - -- - - - - - -
b b b b b b bb b b b b b b- - - - - - -
- - - - - - -b b b b b b bb b b b b b bb b b b b b b- - - - - - -50 50 50 50 50 50 50
300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 440 x 347.5 x 227.5 440 x 347.5 x 227.5
300 x 410 x 146.5 300 x 410 x 146.5 300 x 410 x 146.5 300 x 410 x 146.5 300 x 410 x 146.5 440 x 462.5 x 227.5 440 x 462.5 x 227.514 14 14 14 14 35 3518 18 18 18 18 45 45
- - - - - - -
p32-35.fm Page 35 Lundi, 14. mars 2005 5:29 17
36
Interpact INV Interpact INV100 to 630 switch-disconnectors 0
0566
50a-
48
Interpact INV250 switch-disconnector.
Interpact INV switch-disconnectorsNumber of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3Conventional thermal current (A) Ith at 60 °CConventional thermal current in enclosure Ithe at 60 °C
Rated insulation level (V) Ui AC 50/60 HzImpulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DCRated operational voltage AC20 and DC20 (V) AC 50/60 HzRated operational current (A) Ie Electrical AC 50/60 Hz
220-240 V380-415 V440-480 V (1)
500-525 V660-690 V
Electrical DC
0566
54a-
48
Interpact INV250 emergency-off switch-disconnector.
125 V (2P in series)250 V (4P in series)
Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V230 V (NEMA)380-415 V
440 V480 V (NEMA)500-525 V
660-690 VRated duties Uninterrupted duty
Intermittent dutyShort-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone)
Max. (with upstream protectioncircuit breaker)
Short-time withstand current (A rms) Icw 1 s
3 s20 s30 s
Suitability for isolationDurability (category A) (O - C-O cycles) Mechanical
Electrical AC 50/60 Hz440 V500 V690 V
Electrical DC250 V
Positive contact indication
Visible breakEmergency-off switch disconnectorDegree of pollution
Upstream protectionSee the “LV switch-disconnectors - Interpact INS/INV 40 to 2500 A" catalogue
(1) Suitable for 480 V NEMA.(2) 550 A (DC).
p36-39.fm Page 36 Lundi, 14. mars 2005 5:29 17
37
Interpact INV 0
INV100 INV160 INV200 INV250 INV320 INV400 INV500 INV6303-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4
100 160 200 250 320 400 500 630100 160 200 250 320 400 500 630 (2)
750 750 750 750 750 750 750 7508 8 8 8 8 8 8 8690 690 690 690 690 690 690 690
250 250 250 250 250 250 250 250750 750 750 750 750 750 750 750AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A/B
100 100 100 160 160 160 200 200 200 250 250 250 320 320 320 400 400 400 500 500 500 630 630 630/630100 100 100 160 160 160 200 200 200 250 250 250 320 320 320 400 400 400 500 500 500 630 630 630/630100 100 100 160 160 160 200 200 200 250 250 250 320 320 320 400 400 400 500 500 500 630 630 630/630
100 100 100 160 160 160 200 200 200 250 250 200 320 320 320 400 400 400 500 500 500 630 630 500/630100 100 100 160 160 160 200 200 200 250 250 200 320 320 320 400 400 400 500 500 500 630 550 500/630DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A/B
100 100 100 160 160 160 200 200 200 250 250 200 320 320 320 400 400 400 500 500 500 550 550 550/630100 100 100 160 160 160 200 200 200 250 250 200 320 320 320 400 400 400 500 500 500 550 550 550/630
22 45 55 75 90 110 132 20022 45 55 75 90 110 150 20045 75 90 132 160 200 250 315
55 90 110 150 185 220 250 40055 50 110 150 185 220 250 37555 110 132 132 220 250 355 400
55 90 160 160 250 400 500 560b b b b b b b bclass 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 %30 30 30 30 50 50 50 50330 330 330 330 330 330 330 330
8500 8500 8500 8500 20000 20000 20000 20000
4900 4900 4900 4900 11500 11500 11500 115002200 2200 2200 2200 4900 4900 4900 49001800 1800 1800 1800 4000 4000 4000 4000
b b b b b b b b15000 15000 15000 15000 10000 10000 10000 10000AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A/B
1500 1500 1500 1500 1500 1500 1500 1500 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000/-1500 1500 1500 1500 1500 1500 1500 1500 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000/-1500 1500 1500 1500 1500 1500 1500 1500 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000/200DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A/B
1500 1500 1500 1500 1500 1500 1500 1500 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000/200b b b b b b b bb b b b b b b bb b b b b b b bIII III III III III III III III
- - - - - - - -
p36-39.fm Page 37 Lundi, 14. mars 2005 5:29 17
38
Interpact INV Interpact INV100 to 630switch-disconnectors 0
Interpact INV switch-disconnectorsInstallation
Fixed, front connectionFixed, rear connectionOn symmetrical rails
On a backplate
ConnectionBy cables To bare cable connectorsBy cables with lugs Directly to terminals
To spreaders
To vertical-connection adapters via cable-lug adaptersFlat-facing bars Directly to terminals
To spreaders
Edgewise bars To vertical-connection adapters
Indication and measurement auxiliariesAuxiliary contactsVoltage-presence indicatorCurrent-transformer module
Ammeter module
Control, locking and interlockingControl Direct front rotary handle
Extended front rotary handleDirect lateral rotary handle
Extended lateral rotary handleLocking By keylock
By padlocks
Interlocking By keylockMechanical
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3-4 poles with front handle)
Installation and connection accessoriesBare cable connectorsRear connectors
Terminal extensionsSpreadersOne-piece spreader
Terminal shroudsTerminal shieldsInterphase-barrier
Front panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm)
Dimensions and weightsOverall dimensions H x W x D (mm) 3 poles
4 polesApproximate weight (kg) 3 poles
4 poles
Enclosure dimensions for Ithe
DB
1054
13
H x W x D (mm)
p36-39.fm Page 38 Lundi, 14. mars 2005 5:29 17
39
Interpact INV 0
INV100 INV160 INV200 INV250 INV320 INV400 INV500 INV630
b b b b b b b bb b b b b b b b- - - - - - - -
b b b b b b b b
b b b b b b b bb b b b b b b bb b b b b b b b- - - - - - - -b b b b b b b bb b b b b b b b- - - - b b b b
b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b b
b b b b b b b bb b b b b b b bb b b b - - - -
b b b b - - - -b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b b- - - - - - - -5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 13,5 < Nm < 16.5 13,5 < Nm < 16.5 13,5 < Nm < 16.5 13,5 < Nm < 16.5
b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b b- - - - - - - -b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b b15 15 15 15 50 50 50 50
136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130
136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130 205 x 185 x 1302 2 2 2 4.6 4.6 4.6 4.62.2 2.2 2.2 2.2 4.9 4.9 4.9 4.9
400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200
p36-39.fm Page 39 Lundi, 14. mars 2005 5:29 17
40
Interpact INV Interpact INV630b to 2500switch-disconnectors 0
PB
1000
17a-
55
Interpact INV1600 switch-disconnector.
Interpact INV switch-disconnectorsNumber of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3Conventional thermal current (A) Ith at 60 °CConventional thermal current in enclosure Ithe at 60 °C
Rated insulation level (V) Ui AC 50/60 HzImpulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DCRated operational voltage AC20 and DC20 (V) AC 50/60 HzRated operational current (A) Ie Electrical AC 50/60 Hz
220-240 V
380-415 V
PB
1000
19a-
55
Interpact INV1600 emergency-off switch-disconnector.
440-480 V (1)
500-525 V
660-690 V
Electrical DC125 V (2P in series)250 V (4P in series)
Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V380-400 V
415 V500-525 V660-690 V
Rated duties Uninterrupted dutyIntermittent duty
PB
1000
21a-
65
Interpact INV2500 switch-disconnector.
Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone)
Max. (with upstream protectioncircuit breaker)
Short-time withstand current (A rms) Icw 0.5 s0.8 s1 s
3 s20 s30 s
Suitability for isolationDurability (category B) (O - C-O cycles) Mechanical
Electrical AC 50/60 Hz
220-240 V
380-415 V
440-480 V (1)
500-525 V
660-690 V
Electrical DC125 V (2P)250 V (4P)
Positive contact indication
Visible breakEmergency-off switch disconnectorDegree of pollution
Upstream protectionSee the “LV switch-disconnectors - Interpact INS/INV 40 to 2500 A" catalogue
(1) Suitable for 480 V NEMA.(2) For vertical connection busbars only. For horizontal connection busbars, see derating charts in the “LV switch-disconnectors - Interpact INS/INV 40 to 2500 A" catalogue.
p40-43.fm Page 40 Lundi, 14. mars 2005 5:30 17
41
Interpact INV0
INV630b INV800 INV1000 INV1250 INV1600 INV2000 INV25003-4 3-4 3-4 3-4 3-4 3-4 3-4
630 800 1000 1250 1600 (2) 2000 2500630 800 1000 1250 1600 (2) 2000 2500
1000 1000 1000 1000 1000 1000 100012 12 12 12 12 12 12690 690 690 690 690 690 690
750 750 750 750 750 750 750800 800 800 800 800 800 800AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B
AC21AAC22BAC22A
AC23A AC21B AC22B AC23B AC21B AC22B AC23B
630 630 630 800 800 800 1000 1000 1000 1250 1250 1250 16001450
16001450
1250 2000 2000 - 2500 2500 -
630 630 630 800 800 800 1000 1000 1000 1250 1250 1250 16001450
16001450
1250 2000 2000 - 2500 2500 -
630 630 630 800 800 800 1000 1000 1000 1250 1250 1250 16001250
16001250
1250 2000 2000 - 2500 2500 -
630 630 630 800 800 800 1000 1000 1000 1250 1250 1250 16001250
16001250
1250 2000 2000 - 2500 2500 -
630 630 630 800 800 800 1000 1000 1000 1250 1250 1250 16001250
16001250
1250 2000 2000 - 2500 2500 -
DC21A DC22A DC23A DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23A DC21B DC22B DC23B DC21B DC22B DC23B630/2 630/2 630/2 800/2 800/2 800/2 1000/2 1000/2 1000/2 1250/2 1250/2 1250/2 1600/2 1600/2 1600/2 2000/2 2000/2 - 2500/2 2500/2 -630/4 630/4 630/4 800/4 800/4 800/4 1000/4 1000/4 1000/4 1250/4 1250/4 1250/4 1600/4 1600/4 1600/4 2000/4 2000/4 - 2500/4 2500/4 -
250 250 315 400 400 - -400 400 560 710 710 - -
500 500 630 800 800 - -560 560 710 900 900 - -710 710 900 - - - -
b b b b b b bclass 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 %75 75 75 75 75 105 105
330 330 330 75 75 105 105
50 50 50 50 50 50 5042 42 42 42 42 50 5035 35 35 35 35 50 50
20 20 20 20 20 30 3010 10 10 10 10 13 138 8 8 8 8 11 11
b b b b b b b5000 3000 3000 3000 3000 500 500AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B
AC21AAC22BAC22A
AC23B AC21B AC22B AC23B AC21B AC22B AC23B
1000 1000 1000 500 500 500 500 500 500 500 500 500 100500
100500
500 100 100 - 100 100 -
1000 1000 1000 500 500 500 500 500 500 500 500 500 100500
100500
500 100 100 - 100 100 -
1000 1000 1000 500 500 500 500 500 500 500 500 500 100500
100500
500 100 100 - 100 100 -
1000 1000 1000 500 500 500 500 500 500 500 500 500 100500
100500
500 100 100 - 100 100 -
1000 1000 1000 500 500 500 500 500 500 500 500 500 100500
100500
500 100 100 - 100 100 -
DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21B DC22B DC23B DC21B DC22B DC23B1000 1000 1000 500 500 500 500 500 500 500 500 500 500 500 500 100 100 - 100 100 -1000 1000 1000 500 500 500 500 500 500 500 500 500 500 500 500 100 100 - 100 100 -b b b b b b b- - - - - - -b b b b b - -III III III III III III III
- - - - - - -
p40-43.fm Page 41 Lundi, 14. mars 2005 5:30 17
42
Interpact INV Interpact INV630b to 2500switch-disconnectors 0
Interpact INS switch-disconnectorsInstallation
Fixed, front connectionFixed, rear connectionOn symmetrical rails
On a backplate
ConnectionBy cables To bare cable connectorsBy cables with lugs Directly to terminals
To spreaders
To vertical-connection adapters via cable-lug adaptersFlat-facing bars Directly to terminals
To spreaders
Edgewise bars To vertical-connection adapters
Indication and measurement auxiliariesAuxiliary contactsVoltage-presence indicatorCurrent-transformer module
Ammeter module
Control, locking and interlockingControl Direct front rotary handle
Extended front rotary handleDirect lateral rotary handle
Extended lateral rotary handleLocking By keylock
By padlocks
Interlocking By keylockMechanical
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3-4 poles with front handle)
Installation and connection accessoriesBare cable connectorsRear connectors
Terminal extensionsSpreadersOne-piece spreader
Terminal shroudsTerminal shieldsInterphase-barrier
Front panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm)
Dimensions and weightsOverall dimensions H x W x D (mm) 3 poles
4 polesApproximate weight (kg) 3 poles
4 poles
Enclosure dimensions for Ithe
DB
1054
13
H x W x D (mm)
p40-43.fm Page 42 Lundi, 14. mars 2005 5:30 17
43
Interpact INV0
INV630b INV800 INV1000 INV1250 INV1600 INV2000 INV2500
b b b b b b bb b b b b b b- - - - - - -
b b b b b b b
- - - - - - -- - - - - b b- - - - - - -
b b b b b - -b b b b b b bb b b b b - -
b b b b b - -
b b b b b b b- - - - - - -- - - - - - -
- - - - - - -
b b b b b b bb b b b b b b- - - - - - -
- - - - - - -b b b b b b bb b b b b b bb b b b b b b- - - - - - -
- - - - - - -30 30 30 30 30 60 60
- - - - - - -- - - - - - -
b b b b b b bb b b b b b b- - - - - - -
- - - - - - -b b b b b b bb b b b b b bb b b b b b b- - - - - - -50 50 50 50 50 50 50
300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 440 x 347.5 x 227.5 440 x 347.5 x 227.5
300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 440 x 462.5 x 227.5 440 x 462.5 x 227.514 14 14 14 14 35 3518 18 18 18 18 45 45
- - - - - - -
p40-43.fm Page 43 Lundi, 14. mars 2005 5:30 17
44
Fupact Fupact INFp32 to INFp800switch-disconnector fuses
0590
00a-
2,4x
2,12 Fupact INFp switch-disconnector fuses
Number of poles / type of fuse-link 3 poles / 3 fuse-links4 poles / switched neutral4 poles / 4 fuse-links
Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / EN 60947-3Conventional thermal current (A) In free air Ith at 40 °C
Maximum fuse power dissipation (W)In enclosure Ithe at 40 °CMaximum fuse power dissipation (W)
Rated insulation voltage (V) Ui AC 50/60 Hz / DC
0565
02a-
5,8x
3,75
Rated impulse-withstand voltage (kV) UimpRated operational voltage (AC20 and DC20) (V) UeRated operational voltage (V) Ue AC 50/60 Hz
DCRated operational current (A) Ie AC 50/60 Hz
220/240 V380/415 V440/480 V (1)
500/525 V660/690 V
DC125 V/nbr of poles in series250 V/nbr of poles in series440 V/nbr of poles in series500 V/nbr of poles in series
0565
03a-
6x4,
21
750 V/nbr of poles in seriesRated operational power (kW) (3)
(motor power given for direct on-line starting)AC 220/240 V
380/400 V415 V500/525 V660/690 V
Rated duties Uninterrupted dutyIntermittent duty
Rated short-circuit making capacity (kA peak)Switch-disconnector without fuse (refer to single- phase fuse limitation curves)
Icm 415 V500 V690 V
Rated short-circuit breaking capacity (kA rms) / Rated short-circuit making capacity (kA peak) (4)
Icn / Icm 415 V (BS fuse-link)500 V (DIN fuse-link)690 V (BS/DIN fuse-link)
Rated short-time withstand current (A rms) Icw 1 s
0565
04a-
6,8x
4,19
3 s20 s30 s
Endurance (category A) (CO cycles) MechanicalElectrical AC AC22A 500 V
AC22A 690 VAC23A 500 VAC23A 690 V
Suitability for isolationPositive contact indicationPollution degreeControl
Direct front rotary handleExtended front rotary handleExtended lateral rotary handleLocking by padlocksOperating torque (typical for 3 poles switch-disconnector fuses) (Nm)Indication auxiliaries
Auxiliary contactsBlown-fuse indicatorFuse monitorAuxiliary contact test position(1) Suitable for 480 V NEMA.(2) AC23B.(3) Some fuse-links limit these values. Motor starting current must be considered separately.(4) Switch-disconnector combined with fuses.(5) Only for NFC fuse-links.(6) Only for DIN fuse-links.
INFB32.
INFC63.
INFD160.
INFD400.
p44-47.fm Page 44 Vendredi, 25. mars 2005 10:17 10
45
Fupact
INFp32 INFD40 INFp63 INFB100 INFC125 INFp160 INFp250 INFp400 INFp630 INFp800NFC-BS DIN NFC-DIN-BS BS NFC DIN-BS DIN-BS DIN-BS DIN-BS DIN-BSNFC-BS DIN NFC-DIN-BS BS NFC DIN-BS DIN-BS DIN-BS DIN-BS DIN-BSNFC - NFC-DIN - NFC DIN DIN DIN DIN DIN
32 40 63 100 125 160 250 400 630 8003.5 4.5 7.5 12 12 12 32 45 60 6532 40 63 100 125 160 135 250 230 400 360 600 570 7203.5 4.5 7.5 12 12 10 12 23 27 34 37 45 50 55800 800 800 800 800 800 800 800 800 8008 8 8 8 8 8 8 8 8 8800 800 800 800 800 800 800 800 800 800750 750 750 750 750 750 750 750 750 750750 750 750 750 750 750 750 750 750 750AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A32 32 40 40 63 63 100 100 125 125 160 160 250 250 400 400 630 630 800 72032 32 40 40 63 63 100 100 125 125 160 160 250 250 400 400 630 630 800 72032 32 40 40 63 63 100 100 125 125 160 160 250 250 400 400 630 630 800 72032 32 40 40 63 63 100 100 125 125 160 160 250 250 400 400 630 630 800 72032 32 40 40 63 63 (2) 100 100 (2) 125 125 (2) 160 160 (2) 250 250 400 400 630 630 800 720DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A32/2 32/2 40/2 40/2 63/3 63/3 100/2 100/2 125/2 125/2 160/2 160/2 250/2 250/2 400/2 400/2 630/2 630/2 800/2 800/232/4 32/4 40/4 40/4 63/3 63/3 100/2 100/2 125/2 125/2 160/2 160/2 250/2 250/2 400/2 400/2 630/2 630/2 800/2 800/232/4 32/4 40/4 40/4 63/3 63/3 100/2 100/2 125/2 125/2 160/2 160/2 250/2 250/2 400/2 400/2 630/2 630/2 800/2 800/2- - - - - - 100/4 100/4 100/4 100/4 100/4 100/4 250/3 250/3 400/3 400/3 630/3 630/3 800/3 800/3- - - - - - - - - - - - 250/3 250/3 400/3 400/3 630/3 630/3 800/3 800/38 11 18.5 30 37 45 70 110 180 20014 18.5 30 45 60 80 132 210 315 35015 18.5 30 55 60 90 140 230 340 38018 22 37 60 80 110 170 280 400 47025 30 60 90 110 132 230 330 540 600b b b b b b b b b bclass 120-60 % class 120-60 % class 120-60 % class 120-60 % class 120-60 % class 120-60 % class 120-60 % class 120-60 % class 120-60 % class 120-60 %9 9 17 22 22 22 40 40 75 757.5 7.5 17 22 22 22 40 40 75 756 6 13 15 15 15 35 35 60 6080/176 80/176 80/176 80/176 80/176 80/176 80/176 80/176 80/176 80/176100/220 100/220 100/220 100/220 100/220 100/220 100/220 100/220 100/220 100/22050/105 50/105 50/105 50/105 50/105 50/105 50/105 50/105 50/105 50/1051000 1000 2500 5000 5000 5000 8000 10000 16000 16000570 570 1440 2900 2900 2900 4650 5800 9250 9250220 220 560 1150 1150 1150 1800 2250 3600 3600180 180 460 950 950 950 1500 1850 2950 295010000 10000 10000 10000 10000 10000 8000 8000 5000 50001500 1500 1500 1500 1500 1500 1000 1000 1000 10001500 1500 1500 1500 1500 1500 1000 1000 1000 10001500 1500 1500 1500 1500 1500 1000 1000 1000 10001500 1500 1500 1500 1500 1500 1000 1000 1000 1000b b b b b b b b b byes yes yes yes yes yes yes yes yes yesIII III III III III III III III III III
b b b b b b b b b bb b b b b b b b b bb b b b b b b - - -b b b b b b b b b b3 3 4 8 8 8 22 22 28 28
b b b b b b b b b bb (5) - b (5) - b - b (6) b (6) b (6) b (6)
b b b b b b b b b bb (standard) b (standard) b (standard) b (standard) b (standard) b (standard) b (optional) b (optional) b (optional) b (optional)
p44-47.fm Page 45 Vendredi, 25. mars 2005 10:17 10
46
Fupact Fupact INFp32 to INFp800switch-disconnector fuses
Fupact INFp switch-disconnector fusesType of fuse-link
NFC 10 x 3814 x 5122 x 58
DIN (NH) NH000NH00NH0,1
NH0,1,2NH3
BS (fixing centres in mm) (3) A1 (44,5)
F1A2 (73,0)A3 (73,0)
A4 (93,7)B1 (111)B2 (111)
B3 (111)B4 (111)C1 (133)
C2 (133)C3 (133)
Installation and connectionFixed front connectionTerminal tightening torque (Nm)
Fuse-link bolts tightening torque (Nm)Installation and connection accessories
Bare-cable connectorsTerminalsNeutral link
Terminal shieldsDimensions and weight
Overall dimensions H x W x D (mm) 3P
4PApproximate weight without fuses (kg) 3P
4P
Enclosure dimensions for ItheH x W x D (mm)
Temperature derating (4) (5)
"Vertical mounting" fuse-links in vertical position
Ith (A) 404550
556065
70"Horizontal mounting" fuse-links in horizontal position
Ith (A) 3540
455055
606570
(1) Maximum fuse body diameter: Ø32 mm.(2) Maximum fuse body diameter: Ø55 mm.(3) A: fuse-link with centre bolted tags. B: fuse-link with offset bolted tags.(4) Derating data is based on:- the maximum rating for fuse-links intended for the device,- maximum heat loss.(5) For installation on a ceiling, derate an additional 10 %.
p44-47.fm Page 46 Vendredi, 25. mars 2005 10:17 10
47
Fupact
INFp32 INFD40 INFp63 INFB100 INFC125 INFp160 INFp250 INFp400 INFp630 INFp800
b - - - - - - - - -b - b - - - - - - -- - b - b b - - - -
- b b - - b - - - -- - b - - b - - - -- - - - - - b - - -
- - - - - - - b - -- - - - - - - - b bb - - - - - - - - -
b - - - - - - - - -b - b b - b - - - -- - b b - b - - - -
- - - b (1) - b (1) - - - -- - - - - - b b - -- - - - - - b b - -
- - - - - - b (2) b - -- - - - - - - b - -- - - - - - - - b b- - - - - - - - b b- - - - - - - - - b
b b b b b b b b b b2 2 3.5 15-22 15-22 15-22 30-44 30-44 50-75 50-75
2 2 2 M5: 3.5 M8: 5 - M5: 3.5 M8: 5 15 15 40 40
b (standard) b (standard) b (standard) b (optional) b (optional) b (optional) b (optional) b (optional) b (optional) b (optional)- - - b b b b b b bb b b b b b b b b b- b b b b b b b b b
97 x 106 x 105 97 x 106 x 133 100 x 143 x 128 140 x 180 x 130 140 x 180 x 130 140 x 180 x 130 162 x 278 x 199 180 x 302 x 206 232 x 378 x 234 232 x 408 x 234
97 x 142 x 105 97 x 142 x 133 100 x 188 x 128 140 x 215 x 130 140 x 215 x 130 140 x 215 x 130 162 x 340 x 199 180 x 372 x 206 232 x 458 x 234 232 x 498 x 2340.7 0.7 1.3 1.5 1.5 1.5 6.9 7.8 15.5 170.9 0.9 1.6 1.8 1.8 1.8 7.9 8.8 19 21
300x350x200 600 x 350 x 300 / 500 x 400 x 250 600 x 700 x 300 / 800 x 600 x 270NFC-BS DIN NFC-DIN-BS BS NFC DIN-BS DIN-BS DIN-BS DIN-BS DIN-BS32 40 63 100 125 160 250 400 630 80030.4 38 60 95 119 152 237 380 600 76028.8 36 56.7 90 113 144 225 360 567 720
27.2 34 53.6 85 106 136 212 340 536 68025.6 32 50.4 80 100 128 200 320 504 64025 30 47.2 75 94 120 187 300 474 600
24.4 28 44 70 88 112 175 280 441 56031 38 61 96 121 156 242 386 610 77229.5 36 58 92 115 148 230 368 580 736
28 34 55 87 109 140 218 350 550 70026.5 32 52.2 83 103 133 207 331 522 66225 30 49.3 78 97 126 195 313 493 625
23.5 28 46.4 74 92 118 184 295 464 58822 26 43 69 86 111 172 277 434 55220.5 24 40 65 81 103 161 268 406 514
p44-47.fm Page 47 Vendredi, 25. mars 2005 10:17 10
48
Fupact Fupact ISFT100 to ISFT630fuse-switch disconnectors
ISFT100.
ISFT160.
ISFT630.
Fupact ISFT fuse-switch disconnectorsNumber of poles / type of fuse-link IEC60 269-2-1 Section 1
Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / EN 60947-3Conventional thermal current (A) In free air Ith at 40 °C
Maximum fuse power dissipation (W)
In enclosure Ithe at 40 °CMaximum fuse power dissipation (W)
Rated insulation voltage (V) Ui AC 50/60 Hz / DC
Rated impulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DC
Rated operational voltage (AC20 and DC20) (V) UeRated operational current (A) Ie AC 50/60 Hz
220/240 V
380/415 V440/480 V (2)
500 V
660/690 VDC/poles in series
125 V /Nbr of poles
220 V /Nbr of poles440 V /Nbr of poles
Rated duties Uninterrupted duty
Rated short-circuit breaking capacity (kA rms) / Rated short-circuit making capacity (kA peak)/ In fuse-link (A) (3)
Icn/Icm/In fuse-link 415 V500 V690 V
Endurance (category B) (CO cycles) MechanicalElectrical AC AC22B 415 V
AC21B 690 VSuitability for isolationVisible break
Pollution degreeControl
Direct front rotary handle (operator-dependent opening and closing)
Locking PadlocksLead seal
Indication auxiliaryAuxiliary contactsBlown-fuse indicator
Installation and connection accessoriesMounting position Horizontal
Vertical
Bare-cable connectorsOther connectors For bare Cu/Al cables
For flexible bars
Distribution connectorLugs for copper cablesComb busbars
Insulated comb coversIncoming connector for comb busbarsTerminal shields
Dimensions and weightOverall dimensions H x W x D (mm) 3PApproximate weight without fuse-links (kg) 3P
(1) With 95 mm2 connector.(2) Suitable for 480 V NEMA.(3) Fuse-switch disconnector with fuse-links.
6219
3a-3
,2x4
,562
194a
-3,6
x4,8
562
195a
-5x5
,35
p48-51.fm Page 48 Mercredi, 16. mars 2005 1:58 13
49
Fupact
ISFT100 ISFT160 ISFT250 ISFT400 ISFT6303P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH)
160 (1) 160 250 400 6309 12 23 34 48
160 (1) 160 250 400 6309 12 23 34 48690 800 800 800 800
6 8 8 8 8690 690 690 690 690440 440 440 440 440
690 800 800 800 800AC21B AC22B AC21B AC22B AC21B AC22B AC21B AC22B AC21B AC22B160 160 160 160 250 250 400 400 630 630
160 160 160 160 250 250 400 400 630 630100 - 160 - 250 - 400 - 630 -100 - 160 - 250 - 400 - 630 -
100 - 100 - 250 - 400 - 630 -DC21B DC22B DC21B DC22B DC21B DC22B DC21B DC22B DC21B DC22B100/1 - 160/1 - 250/1 - 400/1 - 630/1 -
100/1 - 160/1 - 250/1 - 400/1 - 630/1 -100/1 - 160/2 - 250/2 - 400/2 - 630/2 -b b b b b80 / 176 / 100 50 / 105 / 160 50 / 105 / 250 50 / 105 / 400 50 / 105 / 63050 / 105 / 100 50 / 105 / 160 50 / 105 / 250 50 / 105 / 400 50 / 105 / 63050 / 105 / 100 50 / 105 / 100 50 / 105 / 200 50 / 105 / 315 50 / 105 / 500
2000 1600 1600 1000 1000300 200 200 200 200
300 200 200 200 200b b b b bb b b b bIII III III III III
b b b b b- - - - -b b b b b
b b b b b- b - - -
b b b b bb b b b bb b - - -- b b b b- b b b bb b - - -
b b b bb - - - -
b - - - -b - - - -- b b b b
141 x 89 x 71 163 x 107 x 80 246 x 186 x 110 271 x 210 x 127 271 x 250 x 1320.46 0.64 2.06 2.96 4.00
p48-51.fm Page 49 Mercredi, 16. mars 2005 1:58 13
50
Fupact Fupact ISFT100 to ISFT630fuse-switch disconnectors
Fupact ISFT fuse-switch disconnectorsType of fuse-link
DIN NH000DIN NH00DIN NH1
DIN NH2DIN NH3
Installation and connectionSymmetrical railDirect connection on backplate
Push-on connection to 60 mm busbarsHook-on connection to 60 mm busbarsHook-on connection to 100 mm busbars
Tightening torque (Nm)
Temperature derating (with gG fuse-link) (1) (2)
"Vertical mounting" fuse-links in vertical position
Ith (A) 40 °C45 °C
50 °C55 °C60 °C
65 °C70 °C
"Horizontal mounting"fuse-links in horizontal position
Ith (A) 40 °C
45 °C50 °C55 °C
60 °C65 °C
70 °C(1) Derating data is based on:- the maximum rating for fuse-links intended for the device,- maximum heat loss.(2) For installation on a ceiling, derate an additional 10 %.(3) With 100/160 A fuse-link.
p48-51.fm Page 50 Mercredi, 16. mars 2005 1:58 13
51
Fupact
ISFT100 ISFT160 ISFT250 ISFT400 ISFT630
b b - - -- b - - -- - b - -
- - - b -- - - - b
b - - - -b b b b b- b b - -- b b b b- - b b bsee "New fusepact range from 32 to 800 A - Fupact" catalogue
100/160 (3) 160 250 400 630100/160 160 250 400 63095/152 152 238 380 599
90/144 144 225 360 56785/136 136 213 340 53680/128 128 200 320 504
75/120 120 188 300 47370/112 112 175 280 441100/160 160 250 400 630
95/152 152 238 380 59990/144 144 225 360 56785/136 136 213 340 536
80/128 128 200 320 50475/120 120 188 300 473
70/112 112 175 280 441
p48-51.fm Page 51 Mercredi, 16. mars 2005 1:58 13
52
Fupact Fupact ISFL160 to ISFL630fuse-switch disconnectors
ISFL160.
Fupact ISFL fuse-switch disconnectorsNumber of poles / type of fuse-link IEC60 269-2-1 Section 1
Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / EN 60947-3Conventional thermal current (A) In free air Ith at 40 °C
Maximum fuse power dissipation (W)
In enclosure Ithe at 40 °CMaximum fuse power dissipation (W)
Rated insulation voltage (V) Ui AC 50/60 Hz / DC
Rated impulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DC
Rated operational voltage (AC20 and DC20) (V) UeRated operational current (A) Ie AC 50/60 Hz
220/240 V
380/415 V440/480 V (1)
500 V
660/690 VDC/poles in series
125 V /Nbr of poles
220 V /Nbr of poles440 V /Nbr of poles
Rated duties Uninterrupted duty
Rated short-circuit breaking capacity (kA rms) / Rated short-circuit making capacity (kA peak)/ In fuse-link (A) (2)
Icn/Icm/In fuse-link 415 V500 V690 V
Endurance (category B) (CO cycles) MechanicalElectrical AC AC22B 415 V
AC21B 690 VSuitability for isolationVisible break
Pollution degreeControl
Direct front rotary handle (operator-dependent opening and closing)
Locking PadlocksLead seal
Indication auxiliaryAuxiliary contactsBlown-fuse indicatorCurrent transformer
Installation and connection accessoriesMounting position Horizontal
VerticalConnector For bare Cu/Al cables
For flexible bars
Lugs for Cu/Al cablesTerminal shieldsDimensions and weight
Overall dimensions H x W x D (mm) 3PApproximate weight without fuse-links (kg) 3P
ISFL250. (1) Suitable for 480 V NEMA.(2) Fuse-switch disconnector with fuse-links.
6219
6a-2
,5x6
,49
6219
7a-2
,08x
9,65
p52-55.fm Page 52 Mardi, 15. mars 2005 8:56 08
53
Fupact
ISFL160 ISFL250 ISFL400 ISFL6303P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH)
160 250 400 63012 23 34 48
160 250 400 63012 23 34 48800 800 800 800
8 8 8 8690 690 690 690440 440 440 440
800 800 800 800AC21B AC22B AC21B AC22B AC21B AC22B AC21B AC22B160 160 250 250 400 400 630 630
160 160 250 250 400 400 630 630160 - 250 - 400 - 630 -160 - 250 - 400 - 630 -
100 - 250 - 400 - 630 -DC21B DC22B DC21B DC22B DC22B DC21B DC22B DC21B- - - - - - - -
- - - - - - - -- - - - - - - -b b b b50 / 105 / 160 100 / 220 / 250 100 / 220 / 400 100 / 220 / 63050 / 105 / 160 50 / 105 / 250 50 / 105 / 400 50 / 105 / 63050 / 105 / 100 50 / 105 / 200 50 / 105 / 315 50 / 105 / 500
1600 1600 1000 1000200 200 200 200
200 200 200 200b b b bb b b bIII III III III
b b b bb b b b- - - -
b b b b- - - -b b b b
b - - -
b b b bb b b bb - - -
b - - -b b b b
456 x 50 x 159 755 x 100 x 192 755 x 100 x 192 755 x 100 x 1921.35 6.35 6.35 6.35
p52-55.fm Page 53 Mardi, 15. mars 2005 8:56 08
54
Fupact Fupact ISFL160 to ISFL630fuse-switch disconnectors
Fupact ISFL fuse-switch disconnectorsType of fuse-link
DIN NH000DIN NH00DIN NH1
DIN NH2DIN NH3
Installation and connectionHook-on connection to 60 mm busbarsDirect connection to 100 mm busbars
Direct connection to 185 mm busbarsTo 60 mm busbars using single-device conversion kitTo 185 mm busbars using single or double device conversion kit
Tightening torque (Nm)
Temperature derating (with gG fuse-link) (1)
"Vertical mounting" fuse-links in vertical position
Ith (A) 40 °C45 °C
50 °C55 °C60 °C
65 °C70 °C
"Horizontal mounting"fuse-links in horizontal position
Ith (A) 40 °C
45 °C50 °C55 °C
60 °C65 °C
70 °C(1) Derating data is based on:- the maximum rating for fuse-links intended for the device- maximum heat loss.
p52-55.fm Page 54 Mardi, 15. mars 2005 8:56 08
55
Fupact
ISFL160 ISFL250 ISFL400 ISFL630
b - - -b - - -- b - -
- - b -- - - b
b - - -b - - -
- b b bb - - -b - - -
see "New fusepact range from 32 to 800 A - Fupact" catalogue
- - -
160 250 400 630152 238 380 599
144 225 360 567136 213 340 536128 200 320 504
120 188 300 473112 175 280 441160 - - -
152 - - -144 - - -136 - - -
128 - - -120 - - -
112 - - -
p52-55.fm Page 55 Mardi, 15. mars 2005 8:56 08
56
Vigirex Protection and monitoring relays 0
Protection relays (2)
RH10 RH21All Vigirex products are type A devices (1), also covering the requirements of type AC devices.
PB
1004
35a_
18
PB
1004
30a_
19
PB
1004
33a_
18
PB
1004
31a_
19
FunctionsProtection b bLocal indications b bRemote indications (hard-wired) - -
Remote indications (via communication) - -Display of measurements - -
WiringOptimum continuity of service b bOptimum safety (failsafe) b b
MountingDIN rail b bFront-panel mount b b
Rated operational voltage1 DC voltage range from 12 to 48 V b b1 DC voltage range from 24 to 130 V and AC 48 V - -6 AC voltage ranges from 12 to 525 V b b4 AC voltage ranges from 48 to 415 V - -
ThresholdsFault (I∆n) 1 fixed instantaneous threshold
choose from 0.03 A to 1 A2 user-selectable thresholds 0.03 A or 0.3 A
Alarm - -
Pre-alarm - -
Time delaysFault Instantaneous Instantaneous for I∆n = 0.03 A
1 user-selectable time delayinstantaneous or 0.06 s for I∆n = 0.3 A
Alarm - -
Pre-alarm - -
Display and indicationsVoltage presence (LED and/or relay) (6) b bThreshold overrun fault (LED) b b
alarm (LED and relay) - -pre-alarm (LED and relay) - -
Leakage current (digital) - -Settings (digital) - -
Test with or without actuation of output contactsLocal b bRemote (hard-wired) b bRemote (hard-wired for several relays) b bRemote (via communication) - -
CommunicationSuitable for supervision (internal bus) - -
Characteristicssee "Low-voltage residual-current protection relays - Vigirex" catalogue
see "Low-voltage residual-current protection relays - Vigirex" catalogue
SensorsMerlin Gerin A, OA, E toroids (7) up to 630 A b bMerlin Gerin rectangular sensors up to 3200 A b b(1) Type A relays up to I∆N = 5 A.(2) Relay with output contact requiring local, manual reset after fault clearance.(3) Relay with output contact that automatically resets after fault clearance.
(4) Mandatory with an RMH (multiplexing for the 12 toroids).(5) Mandatory with an RM12T (multiplexing for the 12 toroids).
p56-cover.fm Page 56 Lundi, 14. mars 2005 5:41 17
Vigirex0
Monitoring relays (3)
RH99 RH197P RHUs or RHU RH99 RMH
PB
1004
34a_
18
PB
1004
32a_
19
PB
1007
15a_
20
0594
83a_
21
PB
1004
29R
a_18
PB
1004
32R
a_20
(4)
0594
85R
a_27
b b b - -b b b b b- b b b b- - b except RHUs - b- b (8) b - b 12 measurement channels (5)
b b b - -b b b - -
b - - b -
b b b b b
b - - b -- b - - -b - - b -
- b b - 220 to 240 V AC
9 user-selectable thresholds from 0.03 A to 30 A
19 user-selectable thresholds from 0.03 A to 30 A
1 adjustable threshold from 0.03 A to 30 A
- -
- Fixed: 50 % I∆n 1 adjustable thresholdfrom 0.015 A to 30 A
9 user-selectable thresholds from 0.03 A to 30 A
1 adjustable threshold/channelfrom 0.03 A to 30 A
- - - - 1 adjustable threshold/channelfrom 0.015 A to 30 A
9 user-selectable time delays instantaneous to 4.5 s
7 user-selectable time delaysinstantaneous to 4.5 s
1 adjustable threshold instantaneous to 4.5 s
- -
- instantaneous 1 adjustable threshold instantaneous to 4.5 s
9 user-selectable time delays instantaneous to 4.5 s
1 adjustable threshold/channelinstantaneous to 5 s
- - - - 1 adjustable threshold/channelinstantaneous to 5 s
b b (9) b b bb b b - -- b b b b- - - - b- on bargraph b - b- - b - b
(10)
b b b b bb b b b -
b b b b -- - b except RHUs - b
- - b except RHUs - b
see "Low-voltage residual-current protection relays - Vigirex" catalogue
see "Low-voltage residual-current protection relays - Vigirex" catalogue
see "Low-voltage residual-current protection relays - Vigirex" catalogue
see "Low-voltage residual-current protection relays - Vigirex" catalogue
see "Low-voltage residual-current protection relays - Vigirex" catalogue
b b b b bb b b b b
(6) Depending on the type of wiring (optimum continuity of service or optimum safety).(7) see "Low-voltage residual-current protection relays - Vigirex" catalogue.
(8) On a bargraph.(9) No voltage presence relay.(10) With actuation of contacts only.
+0
0594
84R
a_21
p56-cover.fm Page 57 Lundi, 14. mars 2005 5:41 17
Schneider Electric Industries SAS89, boulevard Franklin RooseveltF - 92500 Rueil-Malmaison (France)Tel : +33 (0)1 41 29 85 00
http://www.schneider-electric.comhttp://www.merlin-gerin.comhttp://www.schneider-electric.co
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.
This document has been printed on ecological paper.