Answers for infrastructure and cities.
www.siemens.com/medium-voltage-switchgear
Fixed-Mounted Circuit-Breaker SwitchgearType NXPLUS up to 40.5 kV, Gas-InsulatedMedium-Voltage Switchgear Catalog HA 35.51 2012
http://www.siemens.com/mittelspannungsschaltanlagenhttp://www.siemens.com/mittelspannungsschaltanlagen7/24/2019 Catalogue Nxplus En
2/56
2 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
R-HA35-090
eps
R-HA35-092
eps
R-HA35-156 eps
ApplicationPublic power supplysystem
ApplicationSteel works
ApplicationOffshore wind park
7/24/2019 Catalogue Nxplus En
3/56
3Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Application Page
Types, typical uses, ratings 4 and 5
Requirements
Features, safety, technology 6 and 7
Technical Data
Electrical data 8 and 9Room planning 10Shipping data, classification 11
Dimensions
Front views, sections,floor openings, fixing points 12 to 21
Product Range
Single-busbar panels 22 and 23Double-busbar panels 24 to 27
Design
Single-busbar panel design 28Double-busbar panel design 29
Components
Vacuum circuit-breaker 30 and 31Three-position disconnector 32 and 33Busbar, module coupling 34Current transformers 35Voltage transformers 36 to 38Panel connection with outside cone 39 and 41Installation possibilities with outside cone 42 and 43Panel connection with inside cone 44 and 45Installation possibilities with inside cone 46 and 47Indicating and measuring equipment 48 to 51Protection, control, measuring
and monitoring equipment 52
Standards
Standards, specifications, guidelines 53 and 54
Fixed-MountedCircuit-Breaker
SwitchgearType NXPLUS up to40.5 kV, Gas-InsulatedMedium-Voltage Switchgear
Catalog HA 35.51 2012
Invalid: Catalog HA 35.51 2011
www.siemens.com/medium-voltage-switchgear
Contents
The products and systems described in this catalog are man-ufactured and sold according to a certified managementsystem (acc. to ISO 9001, ISO 14001 and BS OHSAS 18001).
http://www.siemens.com/mittelspannungsschaltanlagenhttp://www.siemens.com/mittelspannungsschaltanlagen7/24/2019 Catalogue Nxplus En
4/56
4 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Types
Application
Panel for
double busbar
Panel for
single busbar
R-HA35.51-76
tif
R-HA35.51-77
tif
7/24/2019 Catalogue Nxplus En
5/56
5Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Fixed-mounted circuit-breaker switchgear NXPLUS is afactory-assembled, type-tested, metal-enclosed,metal-clad, SF6-insulated switchgear for single-busbar anddouble-busbar applications for indoor installation.
It is used in transformer and switching substations,e. g., in:
Power supply companies Power stations Cement industry Automobile industry
Iron and steel works Rolling mills Mining industry Textile, paper and food industries Chemical industry Petroleum industry Pipeline installations Offshore installations
Electrochemical plants Petrochemical plants
Shipbuilding industry Diesel power plants Emergency power supply installations Lignite open-cast mines Traction power supply systems.
Typical uses, ratings
Application
1) 2500 A on request
Double-busbar panels
Rated voltage max. kV 12 24 36
Rated frequency Hz 50 / 60
Rated short-duration kVpower-frequency withstand voltage
28 50 70
Rated lightning kVimpulse withstand voltage
75 125 170
Rated short-circuit max. kAbreaking current
31.5
Rated short-time max. kAwithstand current, 3 s
31.5
Rated short-circuit max. kAmaking current
80
Rated peak max. kAwithstand current
80
Rated normal current max. Aof the busbar 2500 2500 2500
Rated normal current max. Aof the feeders
2500 2500 2500
Electrical data (maximum values) and dimensions
Single-busbar panels
Rated voltage max. kV 12 24 36 40.5
Rated frequency Hz 50 / 60
Rated short-duration kVpower-frequency withstand voltage
28 50 70 85
Rated lightning kVimpulse withstand voltage
75 125 170 185
Rated short-circuit max. kAbreaking current
31.5
Rated short-time max. kAwithstand current, 3 s
31.5
Rated short-circuit max. kAmaking current
80
Rated peak max. kAwithstand current
80
Rated normal current max. Aof the busbar
2000 1) 2000 1) 2000 1) 2000
Rated normal current max. Aof the feeders
2000 1) 2000 1) 2000 1) 2000
7/24/2019 Catalogue Nxplus En
6/56
6 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Requirements
Environmental independence
Hermetically tight, welded switchgear vessels made ofstainless steel as well as single-pole solid insulation makethe parts of the primary circuit under high voltage ofNXPLUS switchgear Insensitive to certain aggressive ambient conditions,
such as: Air humidity Dust
Condensation Tight to ingress of foreign objects, such as:
Dust Pollution Small animals Humidity
Independent of the site altitude.
Compact design
Thanks to the use of SF6insulation, compact dimensions arepossible up to 40.5 kV.Thus:
Existing switchgear rooms can be used effectively New constructions cost little Costly city-area space is saved.
Maintenance-free design
Switchgear vessels designed as sealed pressure systems,maintenance-free switching devices and enclosed cableplugs ensure: Maximum supply reliability Personnel safety
Sealed-for-life design according to IEC 62271-200(sealed pressure system)
Installation, operation, extension and replacementwithout SF6gas work
Reduced operating costs Cost-efficient investment No maintenance cycles.
Innovation
The use of digital secondary systems and combinedprotection and control devices ensures: Clear integration in process control systems
Flexible and highly simplified adaptation to new systemconditions and thus to cost-efficient operation.
Service life
Under normal operating conditions, the expected servicelife of gas-insulated switchgear NXPLUS is at least 35 years,probably 40 to 50 years, taking the tightness of the
hermetically welded switchgear vessel into account. Theservice life is limited by the maximum number of operatingcycles of the switchgear devices installed: For circuit-breakers, according to the endurance class
defined in IEC 62271-100 For three-position disconnectors and earthing switches,
according to the endurance class defined in IEC 62271-102.
Personal safety
Safe-to-touch and hermetically sealed primary enclosure Cable terminations, busbars and voltage transformers are
surrounded by earthed layers All high-voltage parts including the cable terminations,
busbars and voltage transformers are metal-enclosed or
metal-coated. Capacitive voltage detecting system to verify safe isolation
from supply
Operating mechanisms and auxiliary switches safelyaccessible outside the primary enclosure (switchgearvessel)
Due to the system design, operation is only possible withclosed switchgear enclosure
Standard degree of protection IP 65 for all high-voltageparts of the primary circuit, IP 3XD for the switchgearenclosure according to IEC 60529 and VDE 0470-1
High resistance to internal arcs by logical mechanicalinterlocks and tested switchgear enclosure
Panels tested for resistance to internal faults up to 31.5 kA Logical mechanical interlocks prevent maloperation Make-proof earthing by means of the vacuum
circuit-breaker.
Security of operation
Hermetically sealed primary enclosure independent ofenvironmental effects (pollution, humidity and smallanimals)
Maintenance-free in an indoor environment (IEC 62271-1and VDE 0671-1)
Operating mechanisms of switching devices accessible
outside the primary enclosure (modules) Metal-coated or metal-enclosed, plug-in inductive voltagetransformers mounted outside the SF6switchgear vessel
Current transformers as ring-core current transformersmounted outside the SF6switchgear vessel
Complete switchgear interlocking system with logicalmechanical interlocks
Welded switchgear vessels, sealed for life Minimum fire load Type and routine-tested
Standardized and manufactured using numericallycontrolled machines
Quality assurance in accordance with DIN EN ISO 9001
More than 500,000 switchgear panels of Siemens inoperation worldwide for many years
Option: Resistance against earthquakes (single busbaronly).
Reliability
Type and routine-tested Standardized and manufactured using numerically
controlled machines Quality assurance in accordance with DIN EN ISO 9001
More than 500,000 switchgear panels of Siemens inoperation worldwide for many years.
Features Safety
7/24/2019 Catalogue Nxplus En
7/56
7Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Technology
Requirements
General
3-pole enclosure of the primary part via modules made ofstainless steel
Insulating gas SF6 Three-position switch as busbar disconnector and feeder
earthing switch
Make-proof earthing by means of the vacuumcircuit-breaker
Panel spacing of incoming and outgoing feeder panels:600 mm (1200 mm as of 2300 A feeder current)
Hermetically tight, welded switchgear vessel made ofstainless steel
1-pole solid-insulated, screened module coupling in boltedtechnology
Cable connection with inside-cone or outside-cone plug-insystem, or for connection of solid-insulated bars
Wall-standing or free-standing arrangement Cable connection access from front or rear
Low-voltage door hinges on the left or on the right Installation and extension of existing switchgear at bothends without gas work and without modification ofexisting panels
Panel-internal control cables in metallic wiring ducts.
Interlocks
According to IEC 62271-200 and VDE 0671-200 Logical mechanical interlocks prevent maloperation Three-position disconnector can only be operated with
circuit-breaker in OPEN position Circuit-breaker can only be operated with three-position
switch in end position and operating lever removed
Three-position disconnector interlocked against thecircuit-breaker in circuit-breaker panels and in bussectionalizers with one panel spacing
Feeder earthed locking device Locking device for three-position switch
The following interlocks can be fulfilled by placing thepadlock accordingly: Padlock on the left:Three-position switch DISCONNECTING function cannotbe operated,three-position switch READY-TO-EARTH function can beoperated Padlock in the center:
Control gate blocked, no switching operations possible Padlock on the right:Three-position switch DISCONNECTING function can beoperated,three-position switch READY-TO-EARTH function cannotbe operated
Option: Cable compartment cover interlocked against thethree-position switch (circuit-breaker panel, disconnectorpanel)
Option: Electromagnetic interlocks Option: Actuating openings of the circuit-breaker can be
padlocked Option: Feeder locking device.
Modular design
Replacement of the circuit-breaker module without gaswork
Low-voltage compartment removable, plug-in bus wires.
Instrument transformers
Can be removed without altering the position of thebusbar and circuit-breaker modules (outside the gascompartments)
Current transformers not subjected to dielectric stress Easy replacement of ring-core current transformers Metal-coated or metal-enclosed, plug-in and disconnect-
able voltage transformers.
Vacuum circuit-breaker
Maintenance-free under normal ambient conditionsaccording to IEC 62271-1 and VDE 0671-1
No relubrication or readjustment Up to 10,000 operating cycles Vacuum-tight for life.
Secondary systems
Customary protection, measuring and control equipment
Option: Numerical multifunction protection relay withintegrated protection, control, communication, operatingand monitoring functions
Can be integrated in process control systems.
7/24/2019 Catalogue Nxplus En
8/56
8 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Electrical data, filling pressure, temperature for single-busbar switchgear
Technical Data
Commonelectricaldata,fillingpressureandtemperature
Rated insulation level Rated voltage Ur kV 12 24 36 40.5Rated short-duration power-frequency withstand voltageUd: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV
2832
5060
7080
8590
Rated lightning impulse withstand voltage Up: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV
7585
125145
170195
185218
Rated frequency fr Hz 50 / 60Rated normal current Ir2) for the busbar up to A 2000 1) 2000 1) 2000 1) 2000Rated filling level pre3) Minimum functional level pme3)
Ambient air temperature
Data of the switchgear panels
Circuit-breaker panelOutside cone1250 A
Rated normal current Ir2) A 1250 1250 1250 Rated short-timewithstand current Ik
for switchgear with tk= 3 s up to kA 31.5 31.5 31.5
Rated peak withstand current Ip up to kA 80 80 80
Rated short-circuit making current Ima up to kA 80 80 80 Rated short-circuit breaking current Isc up to kA 31.5 31.5 31.5
Electrical endurance ofvacuum circuit-breakers
at rated normal currentat rated short-circuit breaking current
Circuit-breaker paneland bussectionalizerInside cone1250 A1600 A2000 A
Rated normal current Ir2) A A A
125016002000
125016002000
125016002000
125016002000
Rated short-timewithstand current Ik
for switchgear with tk= 3 s up to kA 31.5 31.5 31.5 31.5
Rated peak withstand current Ip up to kA 80 80 80 80Rated short-circuit making current Ima up to kA 80 80 80 80Rated short-circuit breaking current Isc up to kA 31.5 31.5 31.5 31.5
Electrical endurance ofvacuum circuit-breakers
at rated normal currentat rated short-circuit breaking current
Circuit-breaker panelSeparateinside cone1250 A1600 A
2000 A
Rated normal current Ir2) A A A
125016002000
125016002000
125016002000
125016002000
Rated short-timewithstand current Ik
for switchgear with tk= 3 s up to kA 31.5 31.5 31.5 31.5
Rated peak withstand current Ip up to kA 80 80 80 80
Rated short-circuit making current Ima up to kA 80 80 80 80Rated short-circuit breaking current Isc up to kA 31.5 31.5 31.5 31.5
Electrical endurance ofvacuum circuit-breakers
at rated normal currentat rated short-circuit breaking current
DisconnectorpanelOutside cone1250 A
Rated normal current Ir2) A 1250 1250 1250 1250Rated short-timewithstand current Ik
for switchgear with tk= 3 s up to kA 31.5 31.5 31.5 31.5
Rated peak withstand current Ip up to kA 80 80 80 80
DisconnectorpanelInside cone1250 A1600 A2000 A
Rated normal current Ir2) A A A
125016002000
125016002000
125016002000
125016002000
Rated short-timewithstand current Ik
for switchgear with tk= 3 s up to kA 31.5 31.5 31.5 31.5
Rated peak withstand current Ip up to kA 80 80 80 80
150 kPa (absolute) at 20 C130 kPa (absolute) at 20 C
10000 operating cycles
10000 operating cycles
10000 operating cycles
5 C to + 55 C
50 breaking operations
50 breaking operations
50 breaking operations
1) 2500 A on request
2) The rated normal currents apply to ambient air temperatures of max. 40 C.
The 24- hour mean value is max. 35 C (according to IEC 62271-1 / VDE 0671-1)3) Pressure values for gas-insulated switchgear vessels
7/24/2019 Catalogue Nxplus En
9/56
9Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Commonelectricaldata,fillingpressureandtemperature
Rated insulation level Rated voltage Ur kV 12 24 36Rated short-duration power-frequency withstand voltage Ud: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV
2832
5060
7080
Rated lightning impulse withstand voltage Up: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV
7585
125145
170195
Rated frequency fr Hz 50 / 60Rated normal current Ir1) for the busbar up to A 2500 2500 2500Rated filling level pre2) Minimum functional level pme2)
Ambient air temperature
Data of the switchgear panels
Circuit-breakerpanelOutside cone1250 A
Rated normal current Ir1) A 1250 1250 1250Rated short-timewithstand current Ik
for switchgear with tk= 3 s up to kA 31.5 31.5 31.5
Rated peak withstand current Ip up to kA 80 80 80
Rated short-circuit making current Ima up to kA 80 80 80Rated short-circuit breaking current Isc up to kA 31.5 31.5 31.5
Electrical endurance ofvacuum circuit-breakers
at rated normal currentat rated short-circuit breaking current
Circuit-breakerpanel, buscoupler, bussectionalizerInside cone1250 A1600 A2000 A2300 A2500 A
Rated normal current Ir2)
A A A A A
12501600200023002500
12501600200023002500
12501600200023002500
Rated short-timewithstand current Ik
for switchgear with tk= 3 s up to kA 31.5 31.5 31.5
Rated peak withstand current Ip up to kA 80 80 80Rated short-circuit making current Ima up to kA 80 80 80Rated short-circuit breaking current Isc up to kA 31.5 31.5 31.5
Electrical endurance ofvacuum circuit-breakers
at rated normal currentat rated short-circuit breaking current
Circuit-breakerpanelSeparateinside cone
1250 A1600 A2000 A2300 A2500 A
Rated normal current Ir2) A A A A A
12501600200023002500
12501600200023002500
12501600200023002500
Rated short-timewithstand current Ik
for switchgear with tk= 3 s up to kA 31.5 31.5 31.5
Rated peak withstand current Ip up to kA 80 80 80
Rated short-circuit making current Ima up to kA 80 80 80Rated short-circuit breaking current Isc up to kA 31.5 31.5 31.5
Electrical endurance ofvacuum circuit-breakers
at rated normal current
at rated short-circuit breaking current
150 kPa (absolute) at 20 C130 kPa (absolute) at 20 C
10000 operating cycles
10000 operating cycles
10000 operating cycles
5 C to +55 C
50 breaking operations
50 breaking operations
50 breaking operations
Electrical data, filling pressure, temperature for double-busbar switchgear
Technical Data
1) The rated normal currents apply to ambient air temperatures of max. 40 C .
The 24- hour mean value is max. 35 C (according to IEC 62271-1 / VDE 0671-1)2) Pressure values for gas-insulated switchgear vessels
7/24/2019 Catalogue Nxplus En
10/56
10 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Room planning
Technical Data
Room planning for single-busbar switchgear
Room planning for double-busbar switchgear
Switchgear installation
For single-busbar or double-busbar applications:
Wall-standing arrangement or
Free-standing arrangement Face-to-face arrangement
accordingly.
Room dimensions
See opposite dimensiondrawings.
Room height
SBB 2950 mm DBB 3100 mm.
Door dimensions
The door dimensions depend onthe dimensions of the individualpanels(see pages 12 to 21).
Switchgear fixing
Floor openings and fixingpoints of the switchgear(see pages 12 to 21)
Foundations: Steel girder construction Steel-reinforced concrete with
foundation rails, welded orbolted on.
Panel dimensions
See pages 12 to 21.
WeightsSingle-busbar panels 1200 kg.Double-busbar panels 1800 kg.
Wall-standing arrangement (top view)
Free-standing arrangement (top view)
Wall-standing arrangement / free-standing arrangement
(top view)
* Aisle width
** Free space next to the last panel installed,either on the left or on the right of the switchgear row
*** Recommendation 500 mm
1) 1200 mm at 230 0 / 2500 A
2) 900 mm or 1200 mm at2300 / 2500 A
Panel width B1(spacing)
Circuit-breaker panel 600 mmDisconnector panel 600 mm
Bus sectionalizer panel 900 mm
Panel width B2(spacing)
Circuit-breaker panel 1) 600 mm
Bus coupler panel 1) 600 mm
Bus sectionalizer panel,system 1 or system 2 2)
600 mm
Metering panel 300 mmor600 mm
7/24/2019 Catalogue Nxplus En
11/56
11Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Shipping data, classification
Technical Data
Transport
NXPLUS switchgear is deliveredin form of individual panels.Please observe the following: Transport facilities on site Transport dimensions and
transport weights Size of door openings in
building.
Packing
Means of transport:Rail and truck Panels on pallets Open packing with
PE protective foil.
Means of transport:Ship
Panels on pallets In closed crates with sealedupper and lower PE protectivefoil
With desiccant bags With sealed wooden base Max. storage time: 6 months.
1) Average values depending onthe degree to which panels areequipped
2) Panels with 1100 mm highlow-voltage compartment
3) Corresponds to metal-clad
according to former standardIEC 60298
Transport dimensions, transport weights 1)
Panel widths Transport dimensionsWidth x Height x Depth
Transport weightwith packing without packing
mm mm mm mm approx. kg approx. kg
Single-busbar switchgear transport by rail or truck
1 600 1100 2680 (2850)2)
2100 1300 12001 900 1870 2680 (2850) 2) 2100 1350 1200
Single-busbar switchgear transport by ship
1 600 1150 3000 2100 1300 1200
1 900 1920 3000 2100 1350 1200
Double-busbar switchgear transport by rail or truck
1 600 1100 2630 (2850) 2) 2100 1900 1800
1 900 1870 2630 (2850) 2) 2100 2000 1800
1 1200 1870 2630 (2850) 2) 2100 2000 1800
Double-busbar switchgear transport by ship
1 600 1150 3000 2100 1900 1800
1 900 1920 3000 2100 2000 1800
1 1200 1920 3000 2100 2000 1800
Classification of NXPLUS switchgear according to IEC 62271-200
Design and construction
Partition class PM (partition of metal) 3)
Loss of service continuity category LSC 2
Accessibility to compartments(enclosure)Busbar compartmentSwitching-device compartmentLow-voltage compartmentCable compartment
Tool-basedTool-basedTool-basedTool-based
Internal arc classification
Designation of the internalarc classification IACIAC class for:Wall-standing arrangementFree-standing arrangement
IAC A FL 31.5 kA, 1 sIAC A FLR 31.5 kA, 1 s
Type of accessibility A
F L R
Switchgear in closed electrical service location, accessfor authorized personnel only(according to IEC 62271-200))FrontLateralRear (for free-standing arrangement)
Arc test current 31.5 kA
Test duration 1 s
7/24/2019 Catalogue Nxplus En
12/56
12 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Circuit-breaker panelsOutside cone
Separate inside cone
Front views, sections, floor openings, fixing points for single-busbar switchgear
Dimensions
Inside cone
1 Fixing point
2 Floor opening for high-voltage cables
3 Floor opening for control cables
1250 A
1250 A1600 A2000 A
1250 A1600 A2000 A
7/24/2019 Catalogue Nxplus En
13/56
13Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Disconnector panelsOutside cone
Bus sectionalizer
Front views, sections, floor openings, fixing points for single-busbar switchgear
Dimensions
Inside cone
1 Fixing point
2 Floor opening for high-voltage cables
3 Floor opening for control cables
1250 A 1250 A1600 A2000 A
1250 A1600 A2000 A
7/24/2019 Catalogue Nxplus En
14/56
7/24/2019 Catalogue Nxplus En
15/56
15Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Front views, sections, floor openings, fixing points for double-busbar switchgear
Dimensions
2300 A2500 A
1250 A1600 A2000 A
Separate inside cone
1Fixing point
2 Floor opening for high-voltage cables
3 Floor opening for control cables
Circuit-breaker panelsSeparate inside cone
7/24/2019 Catalogue Nxplus En
16/56
16 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Front views, sections, floor openings, fixing points for double-busbar switchgear
Dimensions
Bus sectionalizersBusbar system 1
1Fixing point
3 Floor opening for control cables
1250 A
1600 A2000 A
2300 A2500 A
7/24/2019 Catalogue Nxplus En
17/56
17Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Front views, sections, floor openings, fixing points for double-busbar switchgear
Dimensions
Bus sectionalizersBusbar system 2
1250 A
1600 A2000 A
2300 A2500 A
1Fixing point
3 Floor opening for control cables
7/24/2019 Catalogue Nxplus En
18/56
7/24/2019 Catalogue Nxplus En
19/56
19Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Front views, sections, floor openings, fixing points for double-busbar switchgear
Dimensions
Bus sectionalizer consiting of circuit-breaker panel + disconnector panel:
1250 A1600 A2000 A
2300 A2500 A
7/24/2019 Catalogue Nxplus En
20/56
20 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
DimensionsFront views, sections, floor openings, fixing points for double-busbar switchgear
Bus couplers
1Fixing point
3 Floor opening for control cables
1250 A
1600 A2000 A
2300 A2500 A
7/24/2019 Catalogue Nxplus En
21/56
21Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
DimensionsFront views, sections, floor openings, fixing points for double-busbar switchgear
1 Fixing point
3 Floor opening for control cables
Metering panels
7/24/2019 Catalogue Nxplus En
22/56
22 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Product RangeSingle-busbar panels
Busbar current
transformer
Solid-insulated
bar
Voltage transformer,
plug-in type
Capacitive voltage
detecting system
Plug-in cable,
1-to 4-fold,
inside-cone inter-
face type 2 or 3
(not included in the
scope of supply)
Surge arrester,
plug-in type
Current transformer
Circuit-breaker panel(cable connection as inside cone)
and 1) or
or or
or or
or
or
Circuit-breaker panel(cable connection as outside cone)
and 1)
or or
or
or
or
1) Not possible with busbar voltage
transformer
2) Requires cable connection with vessel
for separate inside cone
HA35-2541b
eps
Voltage transformer,
disconnectable
Cable connection
with outside-cone
plug (not included
in the scope of
supply)
Capacitive voltage
detecting system
7/24/2019 Catalogue Nxplus En
23/56
23Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Single-busbar panels
Product Range
Disconnector panel(cable connection as outside cone) Busbar current
transformer
Solid-insulatedbar
Voltage transformer,plug-in type
Capacitive voltagedetecting system
Plug-in cable,1-to 4-fold,inside-cone inter-face type 2 or 3(not included in thescope of supply)
Surge arrester,
plug-in type
Cable connectionwith outside-coneplug (not includedin the scope ofsupply)
Current transformer
Disconnector panel(cable connection as inside cone)
and 1) or
or or
or or
or
or
and 1)
or or
or
or
or
1) Not possible with busbar voltage
transformer
Bus sectionalizer
HA35-2541b
eps
Voltage transformer,disconnectable
Capacitive voltagedetecting system
7/24/2019 Catalogue Nxplus En
24/56
24 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Double-busbar panels
Product Range
1) Requires cable connection with vesselfor separate inside cone
2) Ring-core current transformer, ovaldesign, suitable for use as of 1000 A
Abbreviations
SS1 = Busbar 1
SS2 = Busbar 2
HA35-2541b
eps
Voltage transformer,disconnectable
Busbar currenttransformer
Solid-insulatedbar
Voltage transformer,plug-in type
Capacitive voltagedetecting system
Plug-in cable,1-to 4-fold,inside-cone inter-face type 2 or 3(not included in thescope of supply)
Surge arrester,
plug-in type
Current transformer
Cable connectionwith outside-coneplug (not includedin the scope ofsupply)
Capacitive voltagedetecting system
Circuit-breaker panel(cable connection as inside cone)
or
or
or
or
Circuit-breaker panel(cable connection as outside cone)
or
or
2)
7/24/2019 Catalogue Nxplus En
25/56
25Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Double-busbar panels
Product Range
Abbreviations
SS1 = Busbar 1
SS2 = Busbar 2
HA35-2541b
eps
Voltage transformer,disconnectable
Busbar currenttransformer
Solid-insulatedbar
Voltage transformer,plug-in type
Capacitive voltagedetecting system
Plug-in cable,1-to 4-fold,inside-cone inter-face type 2 or 3(not included in thescope of supply)
Surge arrester,
plug-in type
Current transformer
Cable connectionwith outside-coneplug (not includedin the scope ofsupply)
Capacitive voltagedetecting system
Bus sectionalizer
Bus sectionalizer circuit-breaker panel(cable connection as inside cone)
or or
or or
or or
or or
Bus sectionalizer disconnector panel(cable connection as inside cone)
7/24/2019 Catalogue Nxplus En
26/56
26 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Double-busbar panels
Product range
HA35-2541b
eps
Capacitive voltagedetecting system
Current transformer
Voltage transformer,plug-in type
Capacitive voltagedetecting system
Abbreviations
SS1 = Busbar 1
SS2 = Busbar 2
Bus coupler
Metering panel
7/24/2019 Catalogue Nxplus En
27/56
27Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Single-busbar panels, double-busbar panels
Product Range
Single-busbar panelsCircuit-breaker panel
With cable connection as outside cone for Rated voltage up to 36 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars up to 2000 A
(2500 A on request), and of feeders up to 1250 A With cable connection as inside cone for
Rated voltage up to 40.5 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars and feeders up to2000 A (2500 A on request)
With cable connection as separate inside cone for Rated voltage up to 40.5 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars and feeders up to2000 A (2500 A on request).
Disconnector panel
With cable connection as outside cone for Rated voltage up to 36 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars up to 2000 A(2500 A on request), and of feeders up to 1250 A
With cable connection as inside cone for Rated voltage up to 40.5 kV Rated short-time withstand current up to 31.5 kA Rated normal currents of busbars and feeders up to2000 A (2500 A on request).
Bus sectionalizer
for Rated voltage up to 40.5 kV
Rated short-circuit breaking current up to 31.5 kA Rated normal current of busbars up to 2000 A(2500 A on request).
Double-busbar panelsCircuit-breaker panel
With cable connection as outside cone for Rated voltage up to 36 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars up to 2500 A, and of
feeders up to 1250 A With cable connection as inside cone for
Rated voltage up to 36 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars and feeders up to2500 A
With cable connection as separate inside cone for Rated voltage up to 36 kV Rated short-circuit breaking current up to 31.5 kA Rated normal currents of busbars and feeders up to2500 A.
Bus sectionalizer
for Rated voltage up to 36 kV Rated short-circuit breaking current up to 31.5 kA Rated normal current of busbars up to 2500 A.
Bus sectionalizer
(circuit-breaker panel and disconnector panel) With cable connection as inside cone for
Rated voltage up to 36 kV Rated short-circuit breaking current up to 31.5 kA Rated normal current of busbars and feeders up to2500 A.
Bus coupler
for Rated voltage up to 36 kV Rated short-circuit breaking current up to 31.5 kA Rated normal current of busbars up to 2500 A.
Metering panel with a panel spacing of 300 mm or600 mm
for Rated voltage up to 36 kV Rated normal current of busbars up to 2500 A.
7/24/2019 Catalogue Nxplus En
28/56
7/24/2019 Catalogue Nxplus En
29/56
29Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Double-busbar panel design
Design
Modular design (example)
Front view
Detail Z:
Panel with integrated inside cone
Panel with integrated inside cone
1 Low-voltage compartment
2 Multifunction protection relay SIPROTEC 4(example)
3 Actuating opening for charging the circuit-breaker springs
4 Position indicator for circuit-breaker
5 Spring charged indicator
6 Operations counter for circuit-breaker
7 Capacitive voltage detecting system
8 Interrogation lever
9 Control gate and locking device fordisconnecting / earthing functions ofthree-position switch
10 Actuating opening for disconnectingfunction of three-position switch
11 Actuating opening for ready-to-earthfunction of three-position switch
12 Position indicator for disconnecting functionof three-position switch
13 Position indicator for ready-to-earth
function of three-position switch14 Busbar cover
15 Busbar module, welded,SF6-insulated
16 Pressure relief (bursting disc)
17 Three-phase busbar system
18 Three-position disconnector
19 Module coupling between busbar moduleand circuit-breaker module
20 Circuit-breaker module, welded,SF6-insulated
21 Selector gate for selectingthe three-position disconnectorin double-busbar switchgear
22 ON pushbutton for circuit-breaker23 OFF pushbutton for circuit-breaker
24 Vacuum interrupter of circuit-breaker
25 Feeder locking device (suitable forpadlocking)
26 Pressure relief duct
27 Integrated cable connection as inside cone
28 Cover of cable compartment
29 Cable connection with inside-cone plugs
30 Feeder current transformer
31 Operating mechanism for three-positionswitch
32 Mechanical control board
33 Operating mechanism for circuit-breaker
34 Voltage transformer connection socket asoutside cone
35 Cable compartment
36 Feeder voltage transformer
37 Earthing busbar
38 Disconnecting facility for feeder voltagetransformer
39 Bushing for feeder voltage transformer
40 Cable connection with outside-cone T-plugs
41 Module coupling between circuit-breakermodule and separate inside-cone module
42 Separate inside-cone module
43 Integrated cable connection as inside cone
44 Voltage transformer connection socket asoutside cone
7/24/2019 Catalogue Nxplus En
30/56
30 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Vacuum circuit-breaker
Components
Features
According to IEC 62271-100 and VDE 0671-100(for standards, see page 53)
Application in hermetically welded switchgear vessel inconformity with the system
Climate-independent vacuum interrupter poles in the
SF6-filled switchgear vessel Maintenance-free for indoor installation according to
IEC 62271-1 and VDE 0671-1
Individual secondary equipment A metal bellows is used for gasketless separation of the
SF6insulation and the operating mechanism (already usedwith success for over 2 million vacuum interrupters).
Trip-free mechanism
The vacuum circuit-breaker is fitted with a trip-freemechanism according to IEC 62271 and VDE 0671.
Switching duties and operating mechanisms
The switching duties of the vacuum circuit-breaker are
dependent, among other factors, on its type of operatingmechanism.Motor operating mechanism Motor operating stored-energy mechanism
For auto-reclosing (K) For synchronization and rapid load transfer (U).
Further operating mechanism features Located outside the switchgear vessel in the operating
mechanism box and behind the control board Stored-energy spring mechanism for 10,000 operating cycles.
Operating mechanism functions
Motor operating mechanism 1)(M1 *)
In the case of motor operating mechanism, the closingspring is charged by means of a motor and latched in thecharged position (spring charged indication is visible).Closing is effected either by means of an ON pushbuttonor a closing solenoid. The closing spring is rechargedautomatically (for auto-reclosing).
Endurance class of circuit-breaker
Function Class Standard Property of NXPLUS
BREAKING M2 IEC 62271-100 10,000 times mechanically withoutmaintenance
E2 IEC 62271-100 10,000 times rated normal currentwithout maintenance50 times short-circuit breaking currentwithout maintenance
C2 IEC 62271-100 Very low probability of restrikesOperating times
Closing time Closing solenoid < 75 ms
Opening time 1strelease2ndrelease
< 65 ms< 50 ms
Arcing time at 50 Hz < 15 ms
Break time 1strelease2ndrelease
< 80 ms< 65 ms
Dead time 300 ms
Total charging time < 15 s
1 Gear with motor (M1 *) 2 Position switch (S4 *)
3Closing spring
4 Closing spring charged indication
5 Closing solenoid (Y9 *)
6Operations counter
7 Auxiliary switch 6 NO + 6 NC (S1 *), option: 12 NO + 12 NC
8 CLOSED/OPEN position indicator for circuit-breaker
9Option: 2nd release (Y2 *), 3rdrelease (Y7 *)
10 1strelease (Y1 *)
11 Feeder locking device
12Fixed terminal
13 Pole support
14 Vacuum interrupter
15 Moving terminal
16Metal bellows
17 Switchgear vessel, SF6-insulated, with vacuum interrupter
18 Operating mechanism box (see figure above)
19Operating kinematics
Section through the vacuum circuit-breaker
R-HA35-126ae
ps
Abbreviations for switching duties:U = Synchronization and rapid load transfer (closing time 90 ms)K = Auto-reclosing1) Motor rating at 60 V to 220 V DC: 700 W 110 V and 230 V DC: 1100 VA* Item designation
Inside view of the vacuum circuit-breaker
7
11
10
1
5
98
4
2
3
6
7/24/2019 Catalogue Nxplus En
31/56
31Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Vacuum circuit-breaker
Components
Secondary equipment
The scope of the secondary equipment of the vacuum circuit-breaker depends on the type of application and offers a widerange of possible variations, allowing almost every require-ment to be satisfied:
Closing solenoid
Type 3AY15 10 (Y9 *) For electrical closing.
Shunt release
Types: Standard: 3AY15 10 (Y1 *) Option: 3AX11 01 (Y2 *), with energy store
Tripping by protection relay or electrical actuation.
Undervoltage release
Type 3AX11 03 (Y7 *)
Consisting of: Energy store and unlatching mechanism Electromagnetic system, which is permanently connected
to voltage while the vacuum circuit-breaker is closed;
tripping is initiated when this voltage drops Connection to voltage transformers possible.
Anti-pumping(mechanical and electrical)
Function: If constant CLOSE and OPEN commands arepresent at the vacuum circuit-breaker at the same time,the vacuum circuit-breaker will return to the open positionafter closing. It remains in this position until a new CLOSEcommand is given. In this manner, continuous closing andopening (= pumping) is avoided.
Circuit-breaker tripping signal
For electrical signaling (as pulse > 10 ms), e. g. to remote con-trol systems, in the case of automatic tripping (e. g. protection)
Via limit switch (S6 *) and cutout switch (S7 *).
Varistor module
To limit overvoltages to approx. 500 V for protectiondevices (when inductive components are mounted in thevacuum circuit-breaker)
For auxiliary voltages 60 V DC.
Auxiliary switch
Type 3SV9 (S1 *)
Standard: 6 NO + 6 NC, free contacts thereof 1)2 NO + 2 NC
Option: 12 NO + 12 NC, free contacts thereof 1)8 NO + 8 NC.
Position switch
Type 3AX4 (S41, S42, S16 *)
For signaling closing spring charged
For circuit-breaker blocked indication.Mechanical interlocking
Mechanical interlocking to the three-position disconnector During operation of the three-position switch, the vacuum
circuit-breaker cannot be operated.
Switching rate of the vacuum interrupter
Electrical data
Curve Curve Curve Curve
Rated voltage 12 kV 24 kV 24 kV 36 / 40.5 kV
Rated short-circuit-breaking current 31.5 kA 25 kA 25 kA 31.5 kA
Rated normal current 1250 A 1250 A 2000 A 2500 A
Rated operating sequences
Rapid transfer (U): O-t-CO-t-CO (t0.3 s, t 3 min)
Auto-reclosing (K): O-t-CO-t-CO (t0.3 s, t 3 min)
Multiple-shotauto-reclosing: O-t-CO-t-CO-t-CO-t-CO (t0.3 s, t 15 s)
O = OPEN operation
C = CLOSE operation
CO = CLOSE operation with subsequent OPEN operation at the shortest
internal close-open time of the vacuum circuit-breaker
Possible release combinations
Release
1 2 3 4
1st shunt release type 3AY1510
2nd shunt release type 3AX1101
Undervoltage release type 3AX1103
Release combination
1) For utilization
by the customer* Item designation
Abbreviations:NO = normally open contactNC = normally closed contact
7/24/2019 Catalogue Nxplus En
32/56
32 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Three-position disconnector
Components
Features of the three-position disconnector
According to IEC 62271-102 and VDE 0671-102(for standards, see page 43)
Application in hermetically welded switchgear vessel inconformity with the system
Climate-independent contacts in the SF6-filled switchgear
vessel Maintenance-free for indoor installation according to
IEC 62271-1 and VDE 0671-1 A metal bellows is used for gasketless separation of the
SF6insulation and the operating mechanism as alreadyused with success in millions of vacuum interrupters
Compact design due to short contact gaps in SF6gas Operating shaft and contact blades with common center
of rotation and reliable switch position up to the operatingfront of the panel
2000 mechanical operating cycles for CLOSED / OPEN 1000 mechanical operating cycles for
OPEN / READY-TO-EARTH
Position indication via mechanical coupled indicators Separate operating shafts for the disconnecting and
ready-to-earth functions Maintenance-free.
Switch positions of thethree-position disconnector
Switch positions of the three-position disconnector
CLOSED
OPEN
FeederEARTHED
Switch positions
Endurance class of three-position disconnector
Function Class Standard Property of NXPLUS
DISCONNECTING M1 IEC 62271-102 2000 times mechanicallywithout maintenance
READY-TO-EARTH
1000 times mechanicallywithout maintenance
EARTHING E2 1) IEC 62271-200IEC 62271-102
50 times rated short-circuitmaking current Imawithoutmaintenance
CLOSED
Closed current path
between busbar and
vacuum circuit-breaker
Contact blades
connected with fixed
contacts at the busbar
bushings
OPEN
Open current path
between busbar and
vacuum circuit-breaker
Isolating distances
withstand prescribed
test voltages
READY-TO-EARTH
Contact blades
connected with earth
contact of switchgear
vessel
Earthing and short-
circuiting the cable
connection possible
by closing the
vacuum circuit-
breaker
Three-position disconnector(in OPEN position)(view into the laterallyopen switchgear vessel)
1 Fixed contact at the busbar2Swivel-mounted contact blade3 Fixed contact for feeder EARTHED4 Push rod
21
4
3
R-HA35-073b eps
7/24/2019 Catalogue Nxplus En
33/56
33Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
ComponentsThree-position disconnector
Interlocks
Selection of permissible switching operations by meansof a control gate with mechanically interlocked vacuumcircuit-breaker
Corresponding operating shafts are not released at theoperating front until they have been pre-selected with the
control gate Operating lever cannot be removed until switching
operation has been completed Circuit-breaker cannot be closed until control gate is in
neutral position again Switchgear interlocking system also possible with electro-
mechanical interlocks if switchgear is equipped withmotor operating mechanisms (mechanical interlocking formanual operation remains).
Switch positions
CLOSED, OPEN, EARTHED or READY-TO-EARTH In circuit-breaker panels, earthing and short-circuiting
the cable connection is completed by closing the vacuumcircuit-breaker.
Operating mechanism
Slow motion mechanism, used in: Circuit-breaker panel Disconnector panel Bus sectionalizer
Bus coupler Slow motion mechanism actuated via operating lever at the
operating front of the panel Separate operating shafts for the DISCONNECTING and
EARTHING or READY-TO-EARTH functions
Option: Motor operating mechanism for theDISCONNECTING and EARTHING or READY-TO-EARTHfunctions
Maintenance-free due to non-rusting design of partssubjected to mechanical stress
Bearings which require no lubrication.
Transmission principle for operating mechanisms(see illustration) Transmission of operating power from outside into the
gas-filled switchgear vessel by means of a metal bellows
Gas-tight Maintenance-free.
Transmission principle for operating mechanisms
1 Gas-filledswitchgear vessel
2 Gas-tightwelded-inmetal bellows
Three-position disconnector
7/24/2019 Catalogue Nxplus En
34/56
34 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Busbar, module coupling
Components
Busbar
Designed as module coupling Solid-insulated Interconnects the panels as well
as the vessels within a panel.
Module coupling Single-pole, bolted type
Consisting of round-bar copper,cast-resin insulated
Bolted busbar joint, silicone-rubber insulated
Field control by means ofelectrically conductive layers onthe insulation (inside and outside)
Screened by earthing the externallayers with the switchgear vessel
Switchgear installation, extensionor panel replacement without SF6
gas work.
Panel interconnectionsin circuit-breaker panel(example)
Module couplingsfor single-busbar panels
Module couplingsfor double-busbar panels
1 Module coupling
2 Busbar module3 Circuit-breaker module
4 End wall
5 Bushing in adjacent panel
6 Busbar conductor
7 Silicone sleeve
8 Earthing clamps
9 High-quality joint
10 Cast-resin bushing
11 Vessel wall
12 Cast-resin insulation
13 Conductive layer
14 Bolted busbar joint
15 Pressure ring
Busbar moduleSF6-insulated
Busbar moduleSF6-insulated
Module coupling
(solid-insulated)
R-HA35-115
eps
Module coupling
7/24/2019 Catalogue Nxplus En
35/56
35Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Current transformers
Components
Features
According to IEC 60044-1and VDE 0414-1
Designed as ring-core currenttransformers, single-pole
Flexibility for selecting the
mounting location Free of dielectrically stressed
cast-resin parts (due todesign)
Insulation class E Inductive type Certifiable Climate-independent Secondary connection by
means of a terminal strip inthe low-voltage compartmentof the panel.
Installation Arranged outside the primaryenclosure (switchgear vessel)
Mounting locations At the busbar (1) Between busbar module and
circuit-breaker module (2) At the panel connection (3) Between circuit-breaker
module and cable connectionmodule (4)
Zero-sequence currenttransformer.
Current transformer types Busbar current transformer (1):
Inside diameter oftransformer 120 mm
Max. usable height 170 mm Current transformer between
busbar module and circuit-breaker module (2): Inside diameter oftransformer 120 mm
Max. usable height 170 mm Current transformer at the
panel connection (3):
Inside diameter oftransformer 120 mm
Max. usable height 205 mm Current transformer between
circuit-breaker module andcable connection module (4): Inside diameter oftransformer 120 mm
Max. usable height 170 mm Zero-sequence current
transformer underneaththe panels (included in thescope of supply); on-site
installation.
Electrical data
Designation Type 4MC
Operating voltage max. 0.8 kVRated short-durationpower-frequencywithstand voltage(winding test)
3 kV
Rated frequency 50 / 60 Hz
Rated continuousthermal current
max. 1.2 xrated current(primary)
Rated short-timethermal current,max. 3 s
max. 31.5 kA
Rated dynamiccurrent primary
secondary
unlimited,40 A to2500 A1 A and 5 A
Designation Type 4MC
Multi ratio (secondary) 200 A 100 Ato2500 A 1250 A
Core data depending on therated primary current:Measuring Ratingcore Class Overcurrent
factorProtection Ratingcore Class Overcurrent
factor
max. 3 cores
2.5 VA to 30 VA0.2 to 1
FS 5, FS 102.5 VA to 30 VA5 P or 10 P10 to 30
Permissible ambient airtemperature
max. 60 C
Insulation class E
Current transformer installation(basic scheme)
1 Current transformer at the busbar2 Current transformer between busbar module and circuit-breaker module3 Current transformer at the panel connection4 Current transformer between circuit-breaker module and cable connection module
7/24/2019 Catalogue Nxplus En
36/56
36 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Voltage transformer installation (basic scheme)
Voltage transformers
Components
Features
According to IEC 60044-2and VDE 0414-2
Single-pole, plug-in design Connection system with
plug-in contact
Inductive type Safe-to-touch due to
metal enclosure Certifiable Climate-independent Secondary connection by
means of plugs inside thepanel
Cast-resin insulated Arranged outside the
primary enclosure(switchgear vessel)
Mounting locations: At the busbar on the busbarmodule (1) (single busbar),or in a separate meteringpanel (8) (double busbar)
At the panel connection(2)(3)(5).
Voltage transformer types
Busbar voltage transformer4MT6 (1) on the busbarmodule (single busbar) Pluggable into aninside-cone socket size 2
No separate meteringpanel required
Suitable for 80% of therated short-durationpower-frequency withstandvoltage at rated frequency
Busbar voltage transformer4MT9 (8) in a separate,300 mm or 600 mm widemetering panel (doublebusbar) Connected with the busbarthrough a flexible cable
with inside-cone plug,for connection to thebusbar and to the voltagetransformer
Suitable for 80 % of therated short-durationpower-frequency withstandvoltage at rated frequency.
Voltage transformers
Feeder voltage transformer
(metal-coated) 4MT3
R-HA35.51-82
eps
R-HA35-120
eps
Busbar voltage transformer
(metal-enclosed) 4MT6
Disconnecting facility for feeder
voltage transformer (detail Z)
OPEN and EARTHED
CLOSED
1 Voltage transformer at the busbar
2 Voltage transformer at the panel connection(inside-cone connection)
3 Voltage transformer at the panel connection(outside-cone connection)
4 Operating lever for disconnecting facility
5 Voltage transformer at the panel connection(separate inside-cone connection)
6 Panel connection
7Switchgear vessel wall (earthed)
7/24/2019 Catalogue Nxplus En
37/56
37Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
2 Voltage transformer at the panel connection(inside-cone connection)
3 Voltage transformer at the panel connection(outside-cone connection)
4 Operating lever for disconnecting facility
5 Voltage transformer at the panel connection(separate inside-cone connection)
8 Voltage transformer at the busbar(double-busbar metering panel)
Voltage transformer installation (basic scheme)
Voltage transformers
Components
Voltage transformers 4MU1or 4MT3 (3) at the panelconnection of the panels withoutside-cone connection Pluggable into an outside-cone bushing at the panel
connection Application of type 4MU1 at36 kV or 24 kV and 31.5 kA
Application of type 4MT3up to 24 kV
Disconnectable via adisconnecting facility at thecable connection
Switchable through anSF6-insulated disconnectingfacility in the switchgearvessel
Positions: CLOSED and
Transformer bushingEARTHED
Operation of thedisconnecting facilityfrom outside through ametal bellows weldedin the switchgear vessel
Voltage transformers4MU2 or 4MT5 at the panelconnection of the panels withinside-cone connection Connection via an outside-cone bushing at the panel
connection for type 4MU2 (2) Connection via a flexiblecable between aninside-cone socket at thepanel connection and aninside-cone socket at thevoltage transformer type4MU2 (5)
Application of type 4MU2up to 36 kV
Application of type 4MT5up to 40.5 kV.
7/24/2019 Catalogue Nxplus En
38/56
38 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Voltage transformers
Components
Rated voltage
kV
Rated short-durationpower-frequencywithstand voltage
kV
Rated lightningimpulse withstandvoltage
kV
Standard Operating voltage
kV
7.2 20 60 IEC 6.0 / 3; 6.24 / 3; 6.3 / 3;6.6 / 3; 6.9 / 3
12 28 75 IEC 7.2 / 3; 7.6 / 3; 8.0 / 3;8.3 / 3; 8.4 / 3; 8.9 / 3;10 / 3; 10.5 / 3; 11 / 3;11.4 / 3; 11.5 / 3; 11.6 / 3
17.5 38 95 IEC 12 / 3; 12.4 / 3; 12.47 / 3;12.5 / 3; 12.8 / 3; 13.2 / 3;13.4 / 3; 13.8 / 3; 14.4 / 3;15 / 3; 15.8 / 3; 16/ 3;17/ 3;
24 50 125 IEC 17.5 / 3; 18 / 3; 19 / 3;20 / 3; 22 / 3; 23 / 3;
36 70 170 IEC 24 / 3; 25.0 / 3; 25.8 / 3;27.6 / 3; 30.0 / 3; 33.0 / 3;34.5 / 3; 35.0 / 3;
40.5 85 185 IEC 38 / 3;
Electrical data
Primary data
For types 4MT3, 4MT5, 4MT6, 4MT9, 4MU1 and 4MU2For operating voltages from 6.0 kV to 38 kV, rated voltage factor Un/ 8h = 1.9; Un/ continuous = 1.2
Fortype
Operatingvoltage
V
Auxiliarywinding
V
Thermallimit current(measuringwinding)
A
Rated long-time current8 h
A
Rating at accuracy class
0.2
VA
0.5
VA
1
VA
3
VA4MT3 100 / 3
110 / 3120 / 3
100 / 3110 / 3120 / 3
6 4 IEC
10, 15, 20,25, 30
10, 15, 20,25, 30, 45,50, 60, 75,90
10, 15, 20,25, 30, 45,50, 60, 75,90, 100, 120,150, 180
10, 15, 20,25, 30, 45,50, 60, 75,90, 100, 120,150, 180
4MT5 100 / 3110 / 3120 / 3
100 / 3110 / 3120 / 3
6 6 IEC
5, 10, 15,20, 25
10, 15, 20,25, 30, 45,50, 60, 75
10, 15, 20,25, 30, 45,50, 60, 75,90, 100,120, 150
10, 15, 20,25, 30, 45,50, 60, 75,90, 100,120, 150
4MT64MT9
100 / 3110 / 3120 / 3
100 / 3110 / 3120 / 3
6 6 IEC
5, 10, 15,20, 25
10, 15, 20,25, 30, 45,
50, 60, 75
10, 15, 20,25, 30, 45,
50, 60, 75,90, 100,120, 150
10, 15, 20,25, 30, 45,
50, 60, 75,90, 100,120, 150
4MU14MU2
100 / 3;110 / 3;120 / 3
100 / 3;110 / 3;120 / 3
6 6 IEC
5, 10.15, 20,25
10, 15, 20,25, 30, 45
10, 15, 20,25, 30, 45,50, 60, 75
10, 15, 20,25, 30, 45,50, 60, 75
Secondary data
7/24/2019 Catalogue Nxplus En
39/56
39Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
ComponentsPanel connection with outside cone
Features
For circuit-breaker panel1250 A,for disconnector panel1250 A
Bushings with outside cone
With bolted contact (M16) asinterface type C accordingto EN 50180 / EN 50181
Cable connection height591 mm
Max. connection depth:960 mm with standard cablecompartment cover
With cable bracket,type C40 according toDIN EN 50024
Option: Acess to cablecompartment only if the
feeder is isolated and earthed For thermoplastic-insulated
cables For shielded cable T-plugs or
cable elbow plugs with boltedcontact
For connection cross-sectionsup to 800 mm2
Larger cross-sections onrequest
Cable routing downwards,cable connection from thefront
For rated normal currentsup to 1250 A
Cable T-plugs are notincluded in the scope ofsupply.
Surge arresters
Pluggable on cable T-plug Surge arresters
recommended if, at the sametime,
the cable system is directlyconnected to the overhead
line, the protection zone of the
surge arrester at the endtower of the overheadline does not cover theswitchgear.
Surge limiters
Pluggable on cable T-plug Surge limiters recommended
when motors with startingcurrents < 600 A areconnected.
Connectable cablesCable T-plug with coupling insert
Cable T-plug with coupling T-plug
Cable compartment
Connection with1 cable per phase
Connection with2 cables per phase
Connection with2 cables per phase
Connection with3 cables per phase
Connection with 3 cables per phase
Panel width 600 mm
1 Cable T-plug2 Coupling T-plug3 Screw-type coupling insert
4 End adapter
Solid-insulated bar
7/24/2019 Catalogue Nxplus En
40/56
40 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Components
Cable type Cable sealing end Comment
Make Type Cross-sectionmm2
Thermoplastic-insulated cables 12 kV according to IEC 60502-2 and VDE 0276-620
1-core cable,PE and XLPE-insulatedN2YSY (Cu) and
N2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)
Euromold 400TB / G430TB-630A440TB / G
35 to 30035 to 300400 to 630
EPDM with semi-conductive layerEPDM with semi-conductive layerEPDM with semi-conductive layer
nkt cables CB 12-630CB 17.5-630CB 36-630(1250)
25 to 30025 to 500400 to 630
Silicone with semi-conductive layer (optionally with metal housing)Silicone with semi-conductive layerSilicone with semi-conductive layer
Sdkabel SET 12SEHDT 13
50 to 300400 to 500
Silicone with semi-conductive layer (optionally with metal housing)Silicone with semi-conductive layer (optionally with metal housing)
Tyco ElectronicsRaychem
RSTI-L56xxRSTI-58xxRSTI-395xRSTI-36Lxx
25 to 30025 to 300400 to 800400 to 630
Silicone with semi-conductive layer, with capacitive measuring pointSilicone with semi-conductive layer, with capacitive measuring pointSilicone with semi-conductive layer, with capacitive measuring pointSilicone with semi-conductive layer, with capacitive measuring point
3M 93-EE 705-693-EE 715-6
50 to 240300 to 400
Silicone with semi-conductive layer (optionally with metal housing)Silicone with semi-conductive layer (optionally with metal housing)
GCA CJB10-630 35 to 500 Silicone with semi-conductive layer
ABB Kabeldon CSE-A 12630-xx 25 to 630 EPDM with semi-conductive layer
3-core cable,PE and XLPE-insulated,N2YSY (Cu) andN2XSY (Cu)
orNA2YSY (Al) andNA2XSY (Al)
Euromold 400TB / G430TB-630A
35 to 30035 to 300
EPDM with semi-conductive layer, in combination with distribution kitEPDM with semi-conductive layer, in combination with distribution kit
nkt cables CB 12-630
CB 17.5-630
25 to 300
25 to 500
Silicone with semi-conductive layer (optionally with metal housing),in combination with distribution kitSilicone with semi-conductive layer, in combination with distribution kit
Sdkabel SET 12
SEHDT 13
50 to 300
400 to 500
Silicone with semi-conductive layer (optionally with metal housing),in combination with distribution kitSilicone with semi-conductive layer (optionally with metal housing),in combination with distribution kit
Tyco ElectronicsRaychem
RSTI-L56xx
RSTI-58xx
25 to 300
25 to 300
Silicone with semi-conductive layer, with capacitive measuring point,in combination with distribution kit RSTI-TRF0xSilicone with semi-conductive layer, with capacitive measuring point,in combination with distribution kit RSTI-TRF0x
3M 93-EE 705-6
93-EE 715-6
50 to 240
300 to 400
Silicone with semi-conductive layer (optionally with metal housing),in combination with distribution kitSilicone with semi-conductive layer (optionally with metal housing),in combination with distribution kit
GCA CJB10-630 25 to 500 Sil icone with semi-conductive layer, in combination with distr ibution kit
ABB Kabeldon CSE-A 12630-xx 25 to 630 EPDM with semi-conductive layer, in combination with distribution kit
Thermoplastic-insulated cables 15 / 17.5 / 24 kV according to IEC 60502-2 and VDE 0276-620
1-core cable,PE and XLPE-insulated,N2YSY (Cu) andN2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)
Euromold K400TB / GK430TB-630AK440TB / G
35 to 30035 to 300400 to 630
EPDM with semi-conductive layerEPDM with semi-conductive layerEPDM with semi-conductive layer
nkt cables CB 24-630CB 36-630(1250)
25 to 300400 to 630
Silicone with semi-conductive layer (optionally with metal housing)Silicone with semi-conductive layer
Sdkabel SET 24SEHDT 23
50 to 300400 to 500
Silicone with semi-conductive layer (optionally with metal housing)Silicone with semi-conductive layer (optionally with metal housing)
Tyco ElectronicsRaychem
RSTI-L56xxRSTI-58xxRSTI-595xRSTI-56Lxx
25 to 30025 to 300400 to 800400 to 630
Silicone with semi-conductive layer, with capacitive measuring pointSilicone with semi-conductive layer, with capacitive measuring pointSilicone with semi-conductive layer, with capacitive measuring pointSilicone with semi-conductive layer, with capacitive measuring point
3M 93-EE 705-693-EE 715-6
25 to 240300 to 400
Silicone with semi-conductive layer (optionally with metal housing)Silicone with semi-conductive layer (optionally with metal housing)
GCA CJB20-630 35 to 500 Silicone with semi-conductive layer
ABB Kabeldon CSE-A 24630-xx 25 to 630 EPDM with semi-conductive layer
3-core cable,PE and XLPE-insulated,
N2YSY (Cu) andN2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)
Euromold K400TB / GK430TB-630A
35 to 30035 to 300
EPDM with semi-conductive layer, in combination with distribution kitEPDM with semi-conductive layer, in combination with distribution kit
nkt cables CB 24-630 25 to 300 Silicone with semi-conductive layer (optionally with metal housing),in combination with distribution kit
Sdkabel SET 24
SEHDT 23
50 to 300
400 to 500
Silicone with semi-conductive layer (optionally with metal housing),in combination with distribution kitSilicone with semi-conductive layer (optionally with metal housing),in combination with distribution kit
Tyco ElectronicsRaychem
RSTI-L56xx
RSTI-58xx
25 to 300
25 to 300
Silicone with semi-conductive layer, with capacitive measuring point,in combination with distribution kit RSTI-TRF0xSilicone with semi-conductive layer, with capacitive measuring point,in combination with distribution kit RSTI-TRF0x
3M 93-EE 705-6
93-EE 715-6
25 to 240
300 to 400
Silicone with semi-conductive layer (optionally with metal housing),in combination with distribution kitSilicone with semi-conductive layer (optionally with metal housing),in combination with distribution kit
GCA CJB20-630 25 to 500 Sil icone with semi-conductive layer, in combination with distr ibution kit
ABB Kabeldon CSE-A 24630-xx 25 to 630 EPDM with semi-conductive layer, in combination with distribution kit
Panel connection with outside cone (commercially available cable plugs and bar connections)
7/24/2019 Catalogue Nxplus En
41/56
41Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
ComponentsPanel connection with outside cone(commercially available cable plugs and bar connections)
Cable type Cable sealing end Comment
Make Type Cross-sectionmm2
Paper-insulated belted cables (non-draining cables) 12 kV according to IEC 60055 and VDE 0255
3-core cable,paper insulatedNKBA (Cu), NKBY (Cu),
NKRA (Cu) and NKFA (Cu)orNAKBA (Al), NAKBY (Al),NAKRA (Al) und NAKFA (Al)
Euromold 400TB / G
430TB-630A
35 to 300
35 to 300
EPDM with semi-conductive layerin combination with distribution kit MINDEPDM with semi-conductive layer
in combination with distribution kit MINDnkt cables CB 24-630 25 to 240 Sil icone with semi-conductive layer (optionally with metal housing),
in combination with transition sealing end type SEV 10
Paper-insulated belted cables (non-draining cables) 12 kV according to GOST 18410-73
3-core cable,paper insulatedASB and ASBL
Euromold 400TB / G
430TB-630A
35 to 300
35 to 300
EPDM with semi-conductive layerin combination with distribution kit MINDEPDM with semi-conductive layerin combination with distribution kit MIND
nkt cables CB 24-630 25 to 240 Sil icone with semi-conductive layer (optionally with metal housing),in combination with transition sealing end type SEV 10
Paper-insulated belted cables (mass-impregnated cables) 12 kV according to IEC 60055 and VDE 0255
3-core cable,paper insulatedNKBA (Cu), NKBY (Cu),NKRA (Cu) and NKFA (Cu)orNAKBA (Al), NAKBY (Al),NAKRA (Al) und NAKFA (Al)
nkt cables CB 24-630 25 to 240 Sil icone with semi-conductive layer (optionally with metal housing),in combination with transition sealing end type SEV 10
Paper-insulated belted cables (mass-impregnated cables) 12 kV according to GOST 18410-73
3-core cable,paper insulatedASB and ASBL
nkt cables CB 24-630 25 to 240 Sil icone with semi-conductive layer (optionally with metal housing),in combination with transition sealing end type SEV 10
Commercially available bar systems
Bar type Bar connection Comment
Make Type Conductor material Max. rated current
Solid-insulated bar MGCMoser Glaser
Duresca DE Aluminum 1250 A Outer sheath made of polyamide(polyamide tube)Duresca DE Copper 1250 A
Duresca DG Aluminum 1250 A Outer sheath made of CrNi steel or aluminum(metal sheath)Duresca DG Copper 1250 A
Preissinger ISOBUS MR Aluminum 1250 A Outer sheath made of heat shrinkable tube;
insulated with cast-resin impregnated paper bandageISOBUS MR Copper 1250 A
Surge-proof caps
Make Type Size Rated voltage Comment
Outside-cone plug-insystem according toEN 50181
3M SP 33SP 33SP 33
Outside cone type COutside cone type COutside cone type C
12 kV24 kV36 kV
Silicone with semi-conductive layer
NexansEuromold
400DR-BK400DR-BM400DR-B
Outside cone type COutside cone type COutside cone type C
12 kV24 kV36 kV
EPDM with semi-conductive layer
nkt cables CBC 40,5-630CBC 40,5-630CBC 40,5-630
Outside cone type COutside cone type COutside cone type C
12 kV24 kV36 kV
Silicone with semi-conductive layer
Sdkabel SP 33SP 33SP 33
Outside cone type COutside cone type COutside cone type C
12 kV24 kV36 kV
Silicone with semi-conductive layer
7/24/2019 Catalogue Nxplus En
42/56
42 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Installation possibilities with outside cone for cable connections and surge arresters
Components
Numberof cablesper paneland phase
Make Ratedvolt-age
Conductorcross-section1)
Insula-tion
Cable T-plugs Coupling inserts /coupling plugs
Surge arresterswith coupling inserts
According tostandard
ArrestersCouplinginserts
kV mm2 bolted bolted additionally
GOST forRussia & CISGB / DL for China
Circuit-breaker panel 1250 A Disconnector panel 1250 A1 Nexans
Euromold122436
25 to 30035 to 30050 to 240
EPDM 1x 400TB / G1x K400TB / G1x M400TB / G
400PB-5(10)-SA-xxx400PB-5(10)-SA-xxx400PB-5(10)-SA-xxx
IEC
122436
25 to 30035 to 30050 to 240
EPDM 1x 430TB / G1x K430TB / G1x M430TB / G
300SA-5(10)SA300SA-5(10)SA300SA-5(10)SA
IEC
122436
400 to 630400 to 630300 to 630
EPDM 1x 440TB / G1x K440TB / G1x M440TB / G
400PB-5(10)-SA-xxx400PB-5(10)-SA-xxx400PB-5(10)-SA-xxx
IEC
122436
50 to 63035 to 63035 to 630
EPDM 1x 484TB / G1x K484TB / G1x M484TB / G
800SA-10-xxx800SA-10-xxx800SA-10-xxx
IEC
Sdkabel 122436
50 to 30025 to 24070 to 300
Silicone 1x SET 121x SET 241x SET 36
MUT 23MUT 23MUT 33
KU 33
IEC
1224
36
300 to 500300 to 630
300 to 500
Silicone 1x SEHDT 131x SEHDT 23
1x SEHDT 33
MUT 23MUT 23
MUT 33
KU 33
IEC
nkt cables 122436
25 to 30025 to 30025 to 300
Silicone 1x CB 12-6301x CB 24-6301x CB 36-630
CSA 12-xCSA 24-xCSA 36-x
IEC
122436
400 to 630400 to 630400 to 630
Silicone 1x CB 36-630(1250)1x CB 36-630(1250)1x CB 36-630(1250)
CSA 12-xCSA 24-xCSA 36-x
IEC
TycoElectronicsRaychem
122436
25 to 30025 to 30050 to 300
Silicone 1x RSTI-L56xx1x RSTI-L56xx1x RSTI-66xx
RSTI-CC-L56SAxxxxorRSTI-CC-66SAxxxx
IEC
122436
25 to 30025 to 30035 to 300
Silicone 1x RSTI-58xx1x RSTI-58xx1x RSTI-68xx
RSTI-CC-58SAxxxxRSTI-CC-58SAxxxx
IEC
122436
400 to 800400 to 800400 to 800
Silicone 1x RSTI-395x1x RSTI-595x1x RSTI-695x
RSTI-CC-58SAxxxxorRSTI-CC-68SAxxxx
IEC
1224
36
400 to 630400 to 630
400 to 630
Silicone 1x RSTI-36Lxx1x RSTI-56Lxx
1x RSTI-66Lxx
RSTI-L56SAxxxxor
RSTI-66SAxxxx
RSTI-66CP-M16RSTI-66CP-M16
RSTI-66CP-M16
IEC
ABBKabeldon
122436
25 to 63025 to 63050 to 630
EPDM 1x CSE-A 12630-xx1x CSE-A 24630-xx1x CSE-A 36630-xx
IEC
2 NexansEuromold
122436
25 to 30035 to 30050 to 240
EPDM 2x 400TB / G2x K400TB / G2x M400TB / G
1x 400CP1x K400CP1x M400CP
400PB-5(10)-SA-xxx400PB-5(10)-SA-xxx400PB-5(10)-SA-xxx
IEC
122436
25 to 30035 to 30050 to 240
EPDM 1x 430TB / G1x K430TB / G1x M430TB / G
1x 300PB / G1x K300PB / G1x K300PB / G
300SA-5(10)SA300SA-5(10)SA300SA-5(10)SA
IEC
122436
400 to 630400 to 630300 to 630
EPDM 2x 440TB / G2x K440TB / G2x M440TB / G
1x 400CP1x K400CP1x M400CP
400PB-5(10)-SA-xxx400PB-5(10)-SA-xxx400PB-5(10)-SA-xxx
IEC
122436
50 to 63035 to 63035 to 630
EPDM 1x 484TB / G1x K484TB / G1x M484TB / G
1x 804TB / G1x K804TB / G1x M804TB / G
800SA-10-xxx800SA-10-xxx800SA-10-xxx
IEC
Sdkabel 12
24
50 to 300
25 to 240
Silicone 1x SET 12
1x SET 24
1x SEHDK 13.1
1x SEHDK 23.1
MUT 23
MUT 23
IEC
1224
50 to 30025 to 240
Silicone 2x SET 122x SET 24
1x KU 23.21x KU 23.2
MUT 23MUT 23
IEC
122436
300 to 500300 to 630300 to 500
Silicone 2x SEHDT 132x SEHDT 232x SEHDT 33
1x KU 331x KU 331x KU 33
MUT 23MUT 23MUT 33
KU 33
IEC
1) Observe the actual short-circuit and current carrying capacity of the cables and sealing ends
7/24/2019 Catalogue Nxplus En
43/56
43Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Installation possibilities with outside cone for cable connections and surge arresters
Components
Numberof cablesper paneland phase
Make Ratedvolt-age
Conductorcross-section1)
Insula-tion
Cable T-plugs Coupling inserts /coupling plugs
Surge arresterswith coupling inserts
According tostandard
ArrestersCouplinginserts
kV mm2 bolted bolted additionally
GOST forRussia & CISGB / DL for China
Circuit-breaker panel 1250 A Disconnector panel 1250 A2 nkt cables 12
2436
25 to 30025 to 30025 to 300
Silicone 1x CB 12-6301x CB 24-6301x CB 36-630
1x CC 12-6301x CC 24-6301x CC 36-630
CSA 12-xCSA 24-xCSA 36-x
IEC
122436
25 to 30025 to 30025 to 300
Silicone 2x CB 12-6302x CB 24-6302x CB 36-630
1x CP 630-C1x CP 630-C1x CP 630-C
CSA 12-xCSA 24-xCSA 36-x
IEC
122436
400 to 630400 to 630400 to 630
Silicone 1x CB 36-630(1250)1x CB 36-630(1250)1x CB 36-630(1250)
1x CC 36-630(1250)1x CC 36-630(1250)1x CC 36-630(1250)
CSA 12-xCSA 24-xCSA 36-x
IEC
122436
400 to 630400 to 630400 to 630
Silicone 2x CB 36-630(1250)2x CB 36-630(1250)2x CB 36-630(1250)
1x CP 630-M161x CP 630-M161x CP 630-M16
CSA 12-xCSA 24-xCSA 36-x
IEC
TycoElectronicsRaychem
122436
25 to 30025 to 30050 to 300
Silicone 1x RSTI-L56xx1x RSTI-L56xx1x RSTI-66xx
1x RSTI-CC-L56xx1x RSTI-CC-L56xx1x RSTI-CC-66xx
RSTI-CC-L56SAxxxxorRSTI-CC-66SAxxxx
IEC
1224
36
25 to 30025 to 300
35 to 300
Silicone 1x RSTI-58xx1x RSTI-58xx
1x RSTI-68xx
1x RSTI-CC-58xx1x RSTI-CC-58xx
1x RSTI-CC-68xx
RSTI-CC-58SAxxxxRSTI-CC-58SAxxxx
IEC
122436
400 to 800400 to 800400 to 800
Silicone 1x RSTI-395x1x RSTI-595x1x RSTI-695x
1x RSTI-CC-395x1x RSTI-CC-595x1x RSTI-CC-695x
RSTI-CC-58SAxxxxorRSTI-CC-68SAxxxx
IEC
122436
400 to 630400 to 630400 to 630
Silicone 2x RSTI-36Lxx2x RSTI-56Lxx2x RSTI-66Lxx
1x RSTI-66CP-M161x RSTI-66CP-M161x RSTI-66CP-M16
RSTI-L56SAxxxxorRSTI-66SAxxxx
RSTI-66CP-M16RSTI-66CP-M16RSTI-66CP-M16
IEC
ABB Kabel-don
122436
25 to 63025 to 63050 to 630
EPDM 2x CSE-A 12630-xx2x CSE-A 24630-xx2x CSE-A-36630-xx
PC 630-3PC 630-3PC 630-3 L
IEC
3 NexansEuromold
122436
25 to 30035 to 30050 to 240
EPDM 3x 400TB / G3x K400TB / G3x M400TB / G
2x400CP2xK400CP2xM400CP
IEC
122436
25 to 30035 to 30050 to 240
EPDM 1x 430TB / G1x K430TB / G1x M430TB / G
x 300PB / G2x K300PB / G2x K300PB / G
IEC
1224
36
400 to 630400 to 630
300 to 630
EPDM 3x 440TB / G3x K440TB / G
3x M440TB / G
2x400CP2xK400CP
2xM400CP
IEC
122436
50 to 63035 to 63035 to 630
EPDM 1x 484TB / G1x K484TB / G1x M484TB / G
2x 804TB / G2x K804TB / G2x M804TB / G
IEC
nkt cables 122436
25 to 30025 to 30025 to 300
Silicone 1x CB 12-6301x CB 24-6301x CB 36-630
2x CC 12-6302x CC 24-6302x CC 36-630
IEC
122436
25 to 30025 to 30025 to 300
Silicone 3x CB 12-6303x CB 24-6303x CB 36-630
2x CP 630-C2x CP 630-C2x CP 630-C
IEC
122436
400 to 630400 to 630400 to 630
Silicone 1x CB 36-630(1250)1x CB 36-630(1250)1x CB 36-630(1250)
2x CC 36-630(1250)2x CC 36-630(1250)2x CC 36-630(1250)
IEC
122436
400 to 630400 to 630400 to 630
Silicone 3x CB 36-630(1250)3x CB 36-630(1250)3x CB 36-630(1250)
2x CP 630-M162x CP 630-M162x CP 630-M16
IEC
Tyco
ElectronicsRaychem
12
2436
25 to 300
25 to 30050 to 300
Silicone 1x RSTI-L56xx
1x RSTI-L56xx1x RSTI-66xx
2x RSTI-CC-L56xx
2x RSTI-CC-L56xx2x RSTI-CC-66xx
IEC
122436
25 to 30025 to 30035 to 300
Silicone 1x RSTI-58xx1x RSTI-58xx1x RSTI-68xx
2x RSTI-CC-58xx2x RSTI-CC-58xx2x RSTI-CC-68xx
IEC
122436
400 to 800400 to 800400 to 800
Silicone 1x RSTI-395x1x RSTI-595x1x RSTI-695x
2x RSTI-CC-395x2x RSTI-CC-595x2x RSTI-CC-695x
IEC
122436
400 to 630400 to 630400 to 630
Silicone 3x RSTI-36Lxx3x RSTI-56Lxx3x RSTI-66Lxx
2x RSTI-66CP-M162x RSTI-66CP-M162x RSTI-66CP-M16
IEC
1) Observe the actual short-circuit and current carrying capacity of the cables and sealing ends
7/24/2019 Catalogue Nxplus En
44/56
44 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
ComponentsPanel connection with inside cone
Panel connection withinside-cone plug-in system orsolid-insulated bar
Features
For circuit-breaker and
disconnector panels Inside-cone plug-in systemaccording to DIN EN 50181
For connection cross-sectionsup to 630 mm2
Up to 4 cables with inside-coneplug size 2
Up to 3 cables with inside-coneplug size 3
With cable bracket, type C40according to DIN EN 50024
Option: Access to the cablecompartment only if the feeder has
been isolated and earthed For thermoplastic-insulated cables Cable routing downwards,
cable connection from the front Inside-cone plugs are not
part of the scope of supply Additionally one outside-cone
termination (up to 36 kV) or oneinside-cone socket (40.5 kV) forconnection of a voltage transformer
Instead of an inside-cone plug,the cable connection can also bedesigned for a solid-insulated bar.
Surge arresters
Inside-cone sockets can beequipped with a surge arresterinstead of an inside-cone cable plug
Surge arresters are available forplug-in sockets size 2 or 3
Surge arresters are available withdischarge currents of 5 kA and10 kA.
Connection options
4 cables per phase (option: surge arrester)Interface type 2
3 cables per phase (option: surge arrester)Interface type 2 or 3
2 cables per phase (option: surge arrester)Interface type 2 or 3
1 cable per phase (option: surge arrester)
Interface type 2 or 3
1 solid-insulated
bar per phase
1 Cable plug-in sockets
2 Voltage transformer connection socket
3 Cable plug, interface type 2
4 Cable plug, interface type 2 or 3
5 Silicone sleeve
6 Solid-insulated bar
7/24/2019 Catalogue Nxplus En
45/56
45Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
ComponentsPanel connection with inside cone(commercially available cable plugs and bar connections)
Panel connection(commercially available plugs)
Cable type Cable sealing end Comment
Make Type Size Cross-sectionmm2
Thermoplastic-insulated cables 12 kV according to IEC 60502-2 and VDE 0276-620
1-core cable or3-core cable,PE and XPLE-insulatedN2YSY (Cu) andN2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)
nkt cables CPI 2 2 25 to 300 Insulation material silicone rubber, with or withoutmetal housing, installation without special tool
CPI 3 3 185 to 630Pfisterer CONNEX 2 50 to 300 Insulation material silicone rubber,
with metal housingCONNEX 3 240 to 630
Sdkabel SEIK 14 2 25 to 300 Insulation material silicone rubber,with metal housingSEIK 15 3 120 to 630
Thermoplastic-insulated cables 24 kV according to IEC 60502-2 and VDE 0276-620
1-core cable or3-core cable,PE and XPLE-insulatedN2YSY (Cu) andN2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)
nkt cables CPI 2 2 25 to 300 Insulation material silicone rubber, with or withoutmetal housing, installation without special toolCPI 3 3 95 to 630
Pfisterer CONNEX 2 50 to 300 Insulation material silicone rubber,with metal housingCONNEX 3 150 to 630
Sdkabel SEIK 24 2 25 to 300 Insulation material silicone rubber,with metal housingSEIK 25 3 50 to 630
Thermoplastic-insulated cables 36 kVaccording to IEC 60502-2 and VDE 0276-620
1-core cable or
3-core cable,PE and XPLE-insulatedN2YSY (Cu) andN2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)
nkt cables CPI 2 2 25 to 300 Insulation material silicone rubber, with or without
metal housing, installation without special toolCPI 3 3 50 to 630Pfisterer CONNEX 2 25 to 300 Insulation material silicone rubber,
with metal housingCONNEX 3 95 to 630
Sdkabel SEIK 34 2 35 to 300 Insulation material silicone rubber,with metal housingSEIK 35 3 50 to 630
Commercially available bar systems
Bar type Bar connection Comment
Make Type Conductor material Max. rated current
Solid-insulated bar MGCMoser Glaser
Duresca DE Aluminum 2500 A Outer sheath made of polyamide(polyamide tube)Duresca DE Copper 2500 A
Duresca DG Aluminum 2500 A Outer sheath made of CrNi steel or aluminum (metalsheath)Duresca DG Copper 2500 A
Preissinger ISOBUS MR Aluminum 2500 A Outer sheath made of heat shrinkable tube;insulated with cast-resin impregnated paper bandageISOBUS MR Copper 2500 A
Surge-proof caps
Make Type Size Rated voltage Comment
Inside-cone plug-insystem according toEN 50181
nkt cables FPI 2 Inside cone size 2 40.5 kV Silicone with metal cover
FPI 3 Inside cone size 3 40.5 kV Silicone with metal cover
Pfisterer CONNEX Inside cone size 2 40.5 kV Silicone with metal cover
CONNEX Inside cone size 3 40.5 kV Silicone with metal cover
Sdkabel ISIK 14ISIK 24ISIK 34
Inside cone size 2Inside cone size 2Inside cone size 2
12 kV24 kV40.5 kV
Silicone with metal cover
ISIK 15ISIK 25ISIK 35
Inside cone size 3Inside cone size 3Inside cone size 3
12 kV24 kV40.5 kV
Silicone with metal cover
7/24/2019 Catalogue Nxplus En
46/56
46 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kV, Gas-Insulated Siemens HA 35.51 2012
Installation possibilities with inside cone for cable connections and surge arresters
Components
Numberof cablesper paneland phase
Size ofinside-coneplug-insystem
Make Ratedvoltage
Conductorcross-section1)
Insulation Cable plugs Surge arresters According tostandard
kV mm2
bolted
additionalinside-cone plug-in
connection required
GOST forRussia & CIS
GB / DL for China Circuit-breaker panel 1250 A Circuit-breaker panel 1600 A Circuit-breaker panel 2000 A Circuit-breaker panel 2300 A Circuit-breaker panel 2500 A Disconnector panel 1250 A Disconnector panel 1600 A Disconnector panel 2000 A
1 Size 2 nkt cables 12243640.5
25 to 30025 to 30025 to 30025 to 300
Silicone 1x CPI 21x CPI 21x CPI 21x CPI 2
SPI 2 IEC
Pfisterer 12243640.5
50 to 30050 to 30035 to 30035 to 300
Silicone 1x MV-CONNEX1x MV-CONNEX1x MV-CONNEX1x MV-CONNEX
MV-CONNEX IEC
Sdkabel 12243640.5
25 to 30025 to 30035 to 300
Silicone 1x SEIK 141x SEIK 241x SEIK 34
IEC
Size 3 nkt cables 122436
40.5
185 to 63095 to 63050 to 630
50 to 630
Silicone 1x CPI 31x CPI 31x CPI 3
1x CPI 3
SPI 3 IEC
Pfisterer 12243640.5
240 to 630150 to 30095 to 30095 to 300
Silicone 1x MV-CONNEX1x MV-CONNEX1x MV-CONNEX1x MV-CONNEX
MV-CONNEX IEC
Sdkabel 12243640.5
120 to 63050 to 63050 to 63095 to 400
Silicone 1x SEIK 151x SEIK 251x SEIK 351x SEIK 55
IEC
2 Size 2 nkt cables 12243640.5
25 to 30025 to 30025 to 30025 to 300
Silicone 2x CPI 22x CPI 22x CPI 22x CPI 2
SPI 2 IEC
Pfisterer 12243640.5
50 to 30050 to 30035 to 30035 to 300
Silicone 2x MV-CONNEX2x MV-CONNEX2x MV-CONNEX2x MV-CONNEX
MV-CONNEX IEC
Sdkabel 12
243640.5
25 to 300
25