Catalogue Panel Meter

Embed Size (px)

Citation preview

  • 8/17/2019 Catalogue Panel Meter

    1/28116

    ANALOGUE PROFILE INSTRUMENTS

    DIMENSIONS in mm

    96x24Weight: 0,15 Kg

    24x96Weight: 0,15 Kg

    CUT OUT

    CUT OUT

  • 8/17/2019 Catalogue Panel Meter

    2/28117

    MOVING COIL INSTRUMENTS FOR DIRECT CURRENT

    ERPC24/O (Horizontal version)

    BURDEN 1mA

    ACCURACY CLASS 1,5

    MICROAMMETER CAPACITIES25-50-100-150-200-250-500 µA

    MILLIAMMETER CAPACITIES1-5-10-50-100-150-200-250-500-600mA4/20mA

    AMMETER CAPACITIES1-1,5-2-2,5-3-4-5A direct input

    .../60mV input by means a shunt with secondary 60 mV

    MILLIVOLTMETER CAPACITIES60÷300mV

    VOLTMETER CAPACITIES1-1,5-2,5-4-6-10-15-30-40-50-60-80-100-150-200-250-300-400-500-600V

    Different capacities can be carried out on request

    EXAMPLES WHEN ORDERINGERPC24/O 200V voltmeter direct input, 200V end scale valueERPC24/O 300A/60mV ammeter input by means of shunt 300A/60mV

    For connection diagram see page 139

    MOVING COIL INSTRUMENTS FOR DIRECT CURRENT

    ERPC 24/V (Vertical version)

    BURDEN 1mA

    ACCURACY CLASS 1,5

    MICROAMMETER CAPACITIES25-50-100-150-200-250-500 µA

    MILLIAMMETER CAPACITIES1-5-10-50-100-150-200-250-500-600mA4/20mA

    AMMETER CAPACITIES1-1,5-2-2,5-3-4-5A direct input

    .../60mV input by means a shunt with secondary 60 mV

    MILLIVOLTMETER CAPACITIES

    60÷300mVVOLTMETER CAPACITIES1-1,5-2,5-4-6-10-15-30-40-50-60-80-100-150-200-250-300-400-500-600V

    Different capacities can be carried out on request

    EXAMPLES WHEN ORDERINGERPC24/V 200V voltmeter direct input, 200V end scale valueERPC24/V 300A/60mV ammeter input by means of shunt 300A/60mV

    For connection diagram see page 139

    MOVING COIL INSTRUMENTS FOR ALTERNATING CURRENT

    MOVING COIL INSTRUMENTS FOR ALTERNATING CURRENT

    ERPI24/O (Horizontal version with internal rectifier)

    BURDEN 1mA

    OPERATING FREQUENCY 40 ÷ 60 Hz

    ACCURACY CLASS 1,5

    AMMETER CAPACITIES0,5-1-1,5-2-2,5-5A direct input

    .../1A, .../5A input by means of C.T. with secondary 1A or 5A

    VOLTMETER CAPACITIES6-10-15-25-40-60-100-150-250-300-400-500-600V

    Different capacities can be carried out on request

    EXAMPLES WHEN ORDERINGERPI24/0 10A ammeter direct input, 10A end scale valueERPI24/0 500V voltmeter direct input, 500V end scale valueERPI24/0 100/5A ammeter input by means of C.T., secondary 5A

    For connection diagram see page 139

    ERPI24/V (Vertical version with internal rectifier)

    BURDEN 1mA

    OPERATING FREQUENCY 40 ÷ 60 Hz

    ACCURACY CLASS 1,5

    AMMETER CAPACITIES0,5-1-1,5-2-2,5-5A direct input

    .../1A, .../5A input by means of C.T. with secondary 1A or 5A

    VOLTMETER CAPACITIES

    6-10-15-25-40-60-100-150-250-300-400-500-600VDifferent capacities can be carried out on request

    EXAMPLES WHEN ORDERINGERPI24/V 10A ammeter direct input, 10A end scale valueERPI24/V 500V voltmeter direct input, 500V end scale valueERPI24/V 100/5A ammeter input by means of C.T., secondary 5A

    For connection diagram see page 139

  • 8/17/2019 Catalogue Panel Meter

    3/28118

    74+0,2

    4  1   + 0    ,2  

    94+0,2

     5   9   +

     0    ,2  

    Ø   5   4    , 4   

    53

            4        5

    Ø   6   9    , 5   

    65

            6        0

    Ø 3

    Ø 4

    46

    12 25 9

    52,5

    12 34,5 6

    ANALOGUE PANEL INSTRUMENTS

    DIMENSIONS in mm

    Length of the scale graduation: 58 mm CUT OUT

    Cut out with use of

    A55R mask

    CUT OUT

    Cut out with use ofA70R mask

    Depth

    Depth

    EMI55M / EMC55M

    A55R mask

    A55N mask

    Length of the scale graduation: 78 mm

    EMI70M / EMC70M

    A70R mask

    A70N mask

  • 8/17/2019 Catalogue Panel Meter

    4/28119

    MOVING COIL INSTRUMENTS FOR DIRECT CURRENT

    EMC55M - EMC70MEMC55M+A55R - EMC70M+A70R

    EMC55M+A55N - EMC70M+A70NBURDEN Ammeter 60mV - Voltmeter 1000Ω /VACCURACY CLASS 1,5

    Housing in thermoplastic resin

    Front in plastic, transparent acrylic with antistatic as standard

    MICROAMMETER CAPACITIES50-60-100-150-250-400-500-600-800-900µA direct input

    MILLIAMMETER CAPACITIES1-1,5-2,5-4-5-6-10-15-20-25-30-40-60-100-150-250-400-600-800-900mA4/20mA

    AMMETER CAPACITIES1-1,5-2,5-4-5-6-10-15-20-25-30-40-50-60A direct input.../60mV input by means a Shunt, secondary 60 mV

    MILLIVOLTMETER CAPACITIES60-100-150-250-400-600mV

    VOLTMETER CAPACITIES

    1-1,5-2,5-4-6-10-15-25-40-60-100-150-250-300-400-500-600VDifferent capacities can be carried out on request

    EXAMPLES WHEN ORDERING

    EMC55M 150µA microammeter, end scale value 150µAdiameter 55mm

    EMC70M 200A/60mV input by means a Shunt 200/60mVdiameter 70mm

    EMC55M 60A ammeter, direct input, end scale value 60Adiameter 55mm

    EMC70M 150V voltmeter direct input, end scale value 150Vdiameter 70mm

    A55R mask for EMC55M rectangular cut out

    A55N mask for EMC55M

    A70R mask for EMC70M rectangular cut out

    A70N mask for EMC70M

    Medium weight Kg 0,18For connection diagram see page 139

    MOVING IRON INSTRUMENTS FOR ALTERNATING CURRENT

    EMI55M - EMI70MEMI55M+A55R - EMI70M+A70REMI55M+A55N - EMI70M+A70N

    BURDEN Ammeter 0,3VA - Voltmeter 1,5VA

    ACCURACY CLASS 1,5

    OPERATING FREQUENCY 40 ÷ 60 Hz

    Housing in thermoplastic resin

    Front in plastic, transparent acrylic with antistatic as standard

    MILLIAMMETER CAPACITIES250, 400, 600, 800, 900 mA

    AMMETER CAPACITIES1-1,5-2,5-4-5-6-10-15-25-30- 40-50-60A direct input.../1A, .../5A input by means a C.T., secondary 1A or 5A

    VOLTMETER CAPACITIES6-10-15-25-40-60-100-150-250-300-400-500-600V direct input.../100V, .../110V input by means a V.T., secondary 100V or 110V

    Different capacities can be carried out on request

    EXAMPLES WHEN ORDERINGEMI55M 40A ammeter direct input

    diameter 55mm, end scale value 40A, 1 In (no overload)

    EMI70M 100/5A ammeter input by means a C.T., secondary 5Adiameter 70mm, end scale value 100/5A, 1 In (no overload)

    EMI70M 50/250/5A ammeter input by means a C.T., secondary 5Adiameter 70mm, end scale value 50A, 5 In (50/250/5A)

    EMI55M 300V voltmeter direct input, end scale value 300Vdiameter 55mm

    A55R mask for EMI55M rectangular cut outA55N mask for EMI55M

    A70R mask for EMI70M rectangular cut out

    A70N mask for EMI70M

    Medium weight Kg 0,15

    For connection diagram see page 139

  • 8/17/2019 Catalogue Panel Meter

    5/28120

    ANALOGUE SWITCHBOARD INSTRUMENTS

    DIMENSIONS in mm

    48x48 72x72 96x96

    144x144

    ERFA / ERW / ERV / ERIC / ERFC / ERCC96

    1COR

  • 8/17/2019 Catalogue Panel Meter

    6/28121

    MOVING IRON INSTRUMENTS FOR ALTERNATING CURRENT

    ERI48 - ERI72 - ERI96 - ERI144 (90°interchangeable scale plate)

    BURDEN Ammeter 48 = 0,3÷0,8VA 72/96/144 = 0,3÷1,2VA

    Voltmeter 48 = 1,2÷2VA 72/96/144 = 1,5÷4VA

    OPERATING FREQUENCY 40 ÷ 60 Hz

    ACCURACY CLASS 1,5

    MILLIAMMETER CAPACITIES 250, 400, 600, 800, 900 mA

    AMMETER CAPACITIES1-1,5-2,5-4-5-6-10-15-20-25-30-40-50-60A direct input.../1A, .../5A input by means a C.T., secondary 1A or 5A

    VOLTMETER CAPACITIES6-10-15-25-40-60-100-150-250-300-400-500-600V direct input.../100V, .../110V input by means a V.T., secondary 100V or 110VDifferent capacities can be carried out on request

    EXAMPLES WHEN ORDERINGERI48 5A5+ESI48 50A5 ammeter input by means a C.T., secondary 5A, 50/250/5A end scale value, 90°5InERI48 500/100V voltmeter input by means a V.T., secondary 100V, 500V end scale value

    for use with VT 500/100V, 90°ERI72 5A1+ESI72 100A1 ammeter input by means a C.T., secondary 5A, 100/5A end scale value, 90°1InERI96 5A2+ESI96 600A2 ammeter input by means a C.T., secondary 5A, 600/1200/5A end scale value, 90°2InERI144 600V voltmeter direct input, 90°

    MEDIUM WEIGHT (Kg) ERI48 (0,10) ERI72 (0,20) ERI96 (0,30) ERI144 (0,35)

    For connection diagram see page 139

    MOVING IRON INSTRUMENTS FOR ALTERNATING CURRENT, WITH INCORPORATED SWITCH

    ERI72C - ERI96CBURDEN Ammeter 0,3÷1,2VA

    Voltmeter 1,5÷4VA

    OPERATING FREQUENCY 40 ÷ 60 Hz

    ACCURACY CLASS 1,5

    AMMETER CAPACITIES (with interchangeable scale plate).../5A2 input by means a C.T, secondary 5A, 2Inammeters provided with one pole switch, low voltage, for three current transformers L1-L2-L3

    VOLTMETER CAPACITIES6-10-15-25-40-60-100-150-250-300-400-500-600V direct input.../100V, .../110V input by means a V.T., secondary 100V or 110Vvoltmeters provided with switch, low voltage, for three phase-phase and three phase-neutral voltageL1N-L2N-L3N / L1L2-L2L3-L3L1

    Different capacities can be carried out on request

    PROTECTION ON FRONT IP00

    EXAMPLES WHEN ORDERING

    ERIC72C 500V voltmeter direct input, 500V end scale valueERI96C 5A2+ESI96C 100A2 ammeter without scale plate, secondary 5A, input by means a C.T., 2In+ interchangeable scale plate 100/200/5A

    MEDIUM WEIGHT (kg): 0,25

    For connection diagram see page 139

    1) Turn to Off with suitablescrewdriver the screw situatedon the center of the knob(making at least 3 completeturns)

    2) Insert the scale plate as shownon the figure

    3) Push the scale plate deeplyuntil the two holes are in line

    4) Replace the knob being sure topush deeply the internal screwwith the screwdriver and turn

    AMMETERS INTERCHANGEABILITY SCALE PLATE

    Pay attention to positioning thewhite mark on the knob to thecorrect phase.

    On request we supply the ammeterswith the scale plates built-in.

  • 8/17/2019 Catalogue Panel Meter

    7/28122

    TACHOMETER INDICATORS

    ERCT48D - ERCT72D - ERCT96D - ERCT144D (for VDC tacho generator, 90°)ERCT48A - ERCT72A - ERCT96A - ERCT144A (for VAC tacho alternator, 90°)

    ERCTL48D - ERCTL72D - ERCTL96D - ERCTL144D (for VDC tacho generator, 240°)ERCTL48A - ERCTL72A - ERCTL96A - ERCTL144A (for VAC tacho alternator, 240°)

    These instruments are moving coil and have an incorporated potentiometer, they are suitable for measuringthe number of revolutions on a tacho generator (VDC) or tacho alternator (VAC)

    BURDEN 600µA

    ACCURACY CLASS 1,5

    When ordering, indicate the scale, unit of measurement, input voltage and number of revolutions.

    EXAMPLES WHEN ORDERINGERCT72D 10VDC 1500G/min indicator for tacho generator where 1500 revs per minute correspond to

    10 VDC, 90°scale plateERCTL96A 10VCA 100l/h indicator for tacho alternator where 100 litres per hour correspond to

    10 VAC, 240°scale plate

    MEDIUM WEIGHT(kg): ERCT48 (0,10) ERCT72 (0,20) ERCT96 (0,25) ERCT144 (0,35)ERCTL48 (0,21) ERCTL72 (0,30) ERCTL96 (0,40) ERCTL144 (0,45)

    For connection diagram see page 139

    MOVING COIL INSTRUMENTS FOR DIRECT CURRENT

    ERC48 - ERC72 - ERC96 - ERC144 (90° interchangeable scale plate)

    ERCL48 - ERCL72 - ERCL96 - ERCL144 (240° interchangeable scale plate)

    The main characteristic of these instruments is their low current consumption, in circuits where high internalconsumption and drop in voltage can bring about measuring errors. The low consumption means that theseinstruments can also be used with converters, tacho generators or thermocouples. Up to 60A they can beprovided with an incorporated shunt for direct connection, above 60A use a separate shunt.

    BURDEN Ammeter 60mV - Voltmeter 1000Ω /VACCURACY CLASS 1,5

    MICROAMMETER CAPACITIES 50-60-100-150-250-400-600-800-900µA

    MILLIAMMETER CAPACITIES 1-1,5-2,5-4-5-6-10-15-20-25-40-60-100-150-250-400-600-800-900mA4/20mA

    AMMETER CAPACITIES1-1,5-2,5-4-6-10-15-25-40-60A direct input

    .../60mV, .../150mV input by means a Shunt, secondary 60mV or 150mVMILLIVOLTMETER CAPACITIES 60-100-150-250-400-600mV

    VOLTMETER CAPACITIES 1-1,5-2,5-4-6-10-15-25-40-60-100-150-250-300-400-500-600V

    Different capacities can be carried out on request

    EXAMPLES WHEN ORDERINGERC48 15A ammeter direct input, 15A end scale value, 90°ERCL72 250V voltmeter direct input, 250V end scale value, 240°ERCL96 60mV+ESCL96 100A input by means a Shunt, secondary 60mV

    100/60mV end scale value, 240°ERC144 100V voltmeter direct input, 100V end scale value, 90°

    MEDIUM WEIGHT (kg) ERC48 (0,10) ERC72 (0,20) ERC96 (0,25) ERC144 (0,35)

    ERCL48 (0,21) ERCL72 (0,30) ERCL96 (0,40) ERCL144 (0,45)

    For connection diagram see page 139

    MOVING COIL INSTRUMENTS FOR ALTERNATING CURRENT

    ERR48 - ERR72 - ERR96 - ERR144 (internal rectifier, 90°interchangeable scale plate)

    ERIL48 - ERIL72 - ERIL96 - ERIL144 (internal rectifier, 240°interchangeable scale plate)

    BURDEN Ammeter less than capacity of 600mA: 1÷1,5Vgreater capacity of 600mA: 0,25VA

    Voltmeter 1mA approx.

    ACCURACY CLASS 1,5

    For capacities of more than 5A, use current transformers.These instruments are constructed for the measurement of alternating current, from 25 to 10,000Hz, and aregauged for reading the effective value of the sinusoidal current. For other wave forms please consult us.

    MICROAMMETER CAPACITIES 100-150-250-400-600µA

    MILLIAMMETER CAPACITIES 1-1,5-2,5-4-5-6-10-15-20-25-40-60-100-150-250-400-600mAAMMETER CAPACITIES1-1,5-2,5-4-5 direct input.../1A, .../5A input by means a C.T, secondary 1A or 5A

    VOLTMETER CAPACITIES6-10-15-25-40-60-100-150-250-300-400-500-600V direct input.../100V, .../110V input by means a V.T., secondary 100V or 110V

    Different capacities can be carried out on request

    EXAMPLES WHEN ORDERINGERR48 15A ammeter direct input, 15A end scale value, 90°ERR72 300V voltmeter direct input, 300V end scale value, 90°ERIL72 500V voltmeter direct input, 500V end scale value, 240°ERIL96 10A5 ammeter direct input, 10/50A end scale value, 240°5In

    MEDIUM WEIGHT (kg): ERR48 (0,10) ERR72 (0,20) ERR96 (0,25) ERR144 (0,35)

    ERIL48 (0,21) ERIL72 (0,30) ERIL96 (0,40) ERIL144 (0,45)

    For connection diagram see page 139

  • 8/17/2019 Catalogue Panel Meter

    8/28123

    POINTER FREQUENCY METERS

    ERF48 - ERF72 - ERF96 - ERF144 (90°scale plate)

    ERFL72 - ERFL96 - ERFL144 (240°scale plate)

    BURDEN 1,5 VA

    ACCURACY CLASS 0,5

    THERMIC DRIFT 0,12% / °C

    CAPACITIES 45/65Hz 110V, 230V or 400V

    Different capacities can be carried out on request

    EXAMPLES WHEN ORDERINGERF48 230V 45/65Hz frequency meter 230VAC aux supply, 90°scale plate, 45/65HzERFL72 400V 45/65Hz frequency meter 400VAC aux supply, 240°scale plate, 45/65Hz

    MEDIUM WEIGHT(kg): ERF48 (0,20) ERF72 (0,22) ERF96 (0,30) ERF144 (0,35)

    ERFL72 (0,27) ERFL96 (0,35) ERFL144 (0,40)

    For connection diagram see page 139

    MULTISCALE TACHOMETER INDICATORS

    ERCT48D /1/2/3 - ERCT72D /1/2/3 - ERCT96D /1/2/3 - ERCT144D /1/2/3 (90°)

    ERCTL48D /1/2/3 - ERCTL72D /1/2/3 - ERCTL96D /1/2/3 - ERCTL144D /1/2/3 (240°)

    This version is suitable where there are a number of input voltages, a simple scale change is all that isnecessary, with only three instruments it is possible to cover the complete voltage range from 2V to 280V.Model ERCTD/1 (ERCTLD/1) covers the range from 2V to 12V and from 12V to 22VModel ERCTD/2 (ERCTLD/2) covers the range from 20V to 67V and from 67V to 144VModel ERCTD/3 (ERCTLD/3) covers the range from 80V to 180V and from 180V to 280V

    BURDEN 600µA

    ACCURACY CLASS 1,5

    EXAMPLES WHEN ORDERING

    ERCTL72D/3 200VCC 2000 RPM tachometer indicator where 2000 RPM correspond to 200Vdc (connectthe 180-280V terminals), 240°scale plateERCT96D/1 10VCC 300m/min tachometer indicator where 300 meters per minute correspond to

    10VDC of input (connect the 2-12V terminals), 90°scale plate

    MEDIUM WEIGHT (kg): ERCT48 (0,10) ERCT72 (0,20) ERCT96 (0,30) ERCT144 (0,35)

    ERCTL48 (0,21) ERCTL72 (0,30) ERCTL96 (0,40) ERCTL144 (0,45)

    For connection diagram see page 139

    TEMPERATURE INDICATORS

    ERT72 - ERT96 (90°scale plate)

    ERTL72 - ERTL96 (240°scale plate)

    Instruments with moving coil system of high sensitivity provided with internal potentiometer for linecompensation. They are used for measuring the temperature by means of a 500°C thermocouple.

    BURDEN 600µA

    ACCURACY CLASS 1,5

    Measurement of the ∆TCAPACITIES

    Fe/CuNi (Fe-Const). Ra max0-600 °C 20 Ohm0-900 °C 20 Ohm

    NiCr/Ni Ra max0-600 °C 20 Ohm0-900 °C 20 Ohm Ra=Line resistance + thermocouple

    0-1200°C 20 OhmPtRh/Pt Ra max0-1200°C 20 Ohm0-1600°C 20 Ohm

    EXAMPLES WHEN ORDERINGERT72 600°C Fe/CuNi Scale temperature reading: 600°C for Ferro-Constantana probe

    90°Scale plateERTL96 900°C NiCr/Ni Scale temperature reading: 900°for NickelChrome-Nickel probe

    240°Scale plate

    MEDIUM WEIGHT (kg): ERT72 (0,20) ERT96 (0,25)

    ERTL72 (0,30) ERTL96 (0,40)

    For connection diagram see page 139

  • 8/17/2019 Catalogue Panel Meter

    9/28

    ERB72 - ERB96 (90°interchangeable scale plate)

    BURDEN 2,5VA

    ACCURACY CLASS 3This type of instrument is used to check long over loading in transformers, cable and substations.They also make it possible to check, economically, distribution networks in the place of very costly recorders.A special sealable knob makes it possible to zero the general indicator. The capacity is 6A for use with .../5AC.T. and maximum over loading of 20%.On request instruments can be provided with a capacity of 1,2A for use with C.T. .../1A.

    STANDARD CAPACITIES

    EXAMPLES WHEN ORDERINGERB72 5A 15 min+ESB72 50/5A ammeter input by means of C.T. 50/5, 15 min. delay, 50/60/5Ascale plateERB96 1A 8 min+ESB96 800/1A ammeter input by means of C.T. 800/1, 8 min. delay, 800/960/1A scale plate

    MEDIUM WEIGHT(kg): ERB72 (0,20) ERB96 (0,22)

    For connection diagram see page 139124

    MAXIMUM DEMAND AMMETERS

    100%10152025

    30405060

    120%12182430

    36486072

    100%80

    120125150

    200250300400

    120%96

    120150180

    240300360480

    100%500600750800

    1000120015002000

    120%600720900960

    1200140018002400

    100%2500300040005000

    120%3000360048006000

    Primary CT(A)

    Scalecapacity

    Primary CT(A)

    Scalecapacity

    Primary CT(A)

    Scalecapacity

    Primary CT(A)

    Scalecapacity

    DOUBLE VIBRATING REED FREQUENCY METERS

    ERFVD96 - ERFVD144

    BURDEN for each system 100V = 1,5VA230V = 3 VA400V = 4 VA

    ACCURACY CLASS 0,5These instruments are formed of two rows of reeds to permit one instrument alone to measure the frequencyof two different lines; it is therefore particulary suitable for paralleling two generators or a generator with themains.

    CAPACITIES

    2x47/53Hz 2x100V/2x230V/2x400V 2x13 reeds (for types ERFVD96/144)2x57/63Hz 2x100V/2x230V/2x400V 2x13 reeds (for types ERFVD96/144)2x45/55Hz 2x100V/2x230V/2x400V 2x21 reeds (for types ERFVD96/144)2x55/65Hz 2x100V/2x230V/2x400V 2x21 reeds (for types ERFVD96/144)

    Different capacities can be carried out on requestEXAMPLES WHEN ORDERINGERFVD96 230V 47-53 double frequency meter 96x96, 230V aux supply with 2x13 vibrating

    reeds and a 47/53Hz capacityERFVD14 100V 55-65 double frequency meter 144x144, 100V aux supply with 2x21 vibrating

    reeds and a 55/65Hz capacity

    MEDIUM WEIGHT (kg): ERFVD96 (0,60) ERFVD144 (0,70)

    For connection diagram see page 139

    VIBRATING REED FREQUENCY METERS

    ERFV72 - ERFV96 - ERFV144

    BURDEN 100V = 1,5VA230V = 3 VA400V = 4 VA

    ACCURACY CLASS 0,5The difference between the periods of vibration of two adjoining reeds is 0,5 or 1 Hz. In the case of twoadjoining reeds vibrating with the same amplitude, the measuring of the frequency will be averaged betweenthe vibration periods of both reeds. If the 50 and 50,5Hz reeds vibrate with the same amplitude, for example,the frequency measured will be 50.25Hz.Reading example:

    CAPACITIES

    47/53Hz 100V / 230V / 400V 13 reeds (for types ERFV 72/96/144)57/63Hz 100V / 230V / 400V 13 reeds (for types ERFV 72/96/144)45/55Hz 100V / 230V / 400V 21 reeds (for types ERFV 96/144)55/65Hz 100V / 230V / 400V 21 reeds (for types ERFV 96/144)

    Different capacities can be carried out on request

    EXAMPLES WHEN ORDERINGERFV72 230V 47-53 frequency meter 72x72, 230V aux supply with 13 vibrating reeds and a

    47/53Hz capacityERFV96 400V 45-55 frequency meter 96x96, 400V aux supply with 21 vibrating reeds and a

    45/55Hz capacity

    MEDIUM WEIGHT (kg): ERFV72 (0,25) ERFV96 (0,30) ERFV144 (0,35)

    For connection diagram see page 139

  • 8/17/2019 Catalogue Panel Meter

    10/28125

    ERBC72 - ERBC96 (90°interchangeable scale plate)BURDEN of the moving iron system: 0,3÷1,2 VA

    of the bimetal system: 2,5 VAACCURACY CLASS of the moving iron system: 1,5

    of the bimetal system: 3These instruments exploit the combining of thermal equipment with moving iron equipment, permittingdeferred reading (typical of bimetallic systems) combined with instantaneous reading of the current values.The capacity is 6A for moving iron connection .../5A C.T. On request instruments can be provided with acapacity of 1,2A for connection to a 1A C.T. while the normal over loading in the moving iron system is of100% and 20% in the bimetallic system.

    STANDARD CAPACITIES

    EXAMPLES WHEN ORDERINGERBC72 5A 15 min+ESBC72 100/5A ammeter input by means of C.T. 100/5, 15 min. delay,

    100-120-200/5A scale plateERBC96 1A 8 min+ESBC96 600/1A ammeter input by means of C.T. 600/1, 8 min. delay,

    600-720-1200/1A scale plate

    MEDIUM WEIGHT (kg) ERBC72 (0,22) ERBC96 (0,27)

    For connection diagram see page 139

    ELECTRONIC SYNCHRONOSCOPES

    ERSI96These instruments are intended for measuring phase difference ∆ϕ between a bus-bar and a generator.Theyare provided with a synchronising check relay which enables switch-on of synchronisation when the setparameters are reached. These instruments are equipped with a circular display of phase angle whichconsists of 18 led’s.Momentary phase difference is displayed by led. Within synchronisation range (∆ϕ=0°between -15°el and +15°el) resolution is increased to 5°el. If difference of frequency between input voltagesexceeds 3Hz, three leds above FAST (fgen > frete) or SLOW (fgen < frete) inscription are alternately illuminated.A green SYNC. LED is illuminated when synchronisation conditions are made.A red ∆U led is illuminated when difference between voltages is above the set value or when the bus-barvoltage is lower then 80% of nominal value Un. In these instruments comparison of the input voltage ofgenerator Ugen and net Unet method is used ,through and A/D converter of the microprocessor.The inputvoltages are galvanically insulated by a transformer and a microprocessor controls all the operations of thesynchronoscope verifying the values of the input voltages coming from the A/D converter, determining thedifference of phase (∆ϕ) between generator and net. The synchronoscopes are provided with threepotentiometers for settting conditions of a synchronisation relay switch-on at the instrument rear side: forsetting permitted phase difference ∆ϕ, for setting permitted voltage difference ∆U, for a delay ofsynchronisation relay switch-on (DELAY). When phase difference and voltage difference between a generatorand bus-bar for time of delay of synchronisation check relay are within the set limits, the synchronisationcheck relay is switched on for approx 150ms. In that time the SYNC. Led is illuminated as well.INPUT VOLTAGE TECHNICAL DATA- Nominal voltage Un: 57, 100, 230, 400 V (to be specified when ordering)- Voltage range: Un +/-20%- Frequency range: 45/65 Hz- Burden (bus-bar):

  • 8/17/2019 Catalogue Panel Meter

    11/28126

    ELECTRONIC SEQUENCE METERS

    ERS72 - ERS96BURDEN 1,5 VA

    ACCURACY CLASS 0,5

    These instruments, for alternating three-phase current, and are used when it is necessary to know whetherthe sequence of the phases of a three-phase line are correct or not.If the sequence is exact (L1-L2-L3), the green pilot light comes in; if not, the red pilot light will come on.Should one of the phases be missing, the two pilot lights will come on at the same time with a luminousintensity which will be half the original intensity.

    Single supply voltage from 150V to 600V.

    EXAMPLES WHEN ORDERINGERS72 150-600V sequence meter dimensions 72x72ERS96 150-600V sequence meter dimensions 96x96

    WEIGHT (kg) ERS72 (0,20) ERS96 (0,30)

    For connection diagram see page 139

    DOUBLE VOLTMETERS

    DOUBLE FREQUENCY METERSERF96DThese instruments consist of two equipments mounted on a common axis permitting the two pointersindicating on one graduation. In this way there is the immediate comparison of the parallel adjustment. Themoving coil system reduces drastically the burden and permits linear graduations.

    BURDEN 1,5VA

    OPERATING FREQUENCY 45/65 Hz

    ACCURACY CLASS 1,5

    STANDARD CAPACITY 2 x 45/65 Hz

    Different capacities can be carried out on request

    EXAMPLES WHEN ORDERINGERF96D 45/65 Hz double frequency meter, 2x45/65 Hz end scale value

    WEIGHT (kg): 0,45

    For connection diagram see page 145

    ERI96DThese instruments consist of two equipments mounted on a common axis permitting the two pointersindicating on one graduation. In this way there is the immediate comparison of the parallel adjustment. Themoving coil system reduces drastically the burden and permits linear graduations.

    BURDEN 1,5VA

    OPERATING FREQUENCY 45/65 Hz

    ACCURACY CLASS 1,5

    STANDARD CAPACITY 2x500V

    Different capacities can be carried out on request

    EXAMPLES WHEN ORDERINGERI96D 500V double voltmeter, 2x500V end scale value

    WEIGHT (kg): 0,42For connection diagram see page 145

  • 8/17/2019 Catalogue Panel Meter

    12/28127

    VOLTMETERS WITH SUPPRESSED ZEROERZS48 - ERZS72 - ERZS96 - ERZS144 (90°scale plate)

    ERZSL48 - ERZSL72 - ERZSL96 - ERZSL144 (240°scale plate)

    BURDEN 1 VA

    These instruments consist of moving coil movements and internal rectifier which are used to determine veryprecisely the normal value of the sinusoidal alternating voltage

    Measuring ranges between 90 to 110% approximately of the voltage.

    CAPACITIES

    0-90/110V0-100/120V0-200/240V0-340/420V

    EXAMPLES WHEN ORDERING

    ERZS72 0-100/120V voltmeter with suppressed zero and supply voltage at 100V,90°scale plateERZSL96 0-200/240V voltmeter with suppressed zero and supply voltage at 200V,

    240°scale plate

    WEIGHT (kg) ERZS48 (0,10) ERZS72 (0,20) ERZS96 (0,22) ERZS144 (0,30)

    ERZSL48 (0,22) ERZSL72 (0,30) ERZSL96 (0,35) ERZSL144 (0,40)

    For connection diagram see page 139

    SINGLE PHASE POWER FACTOR METERS

    ERFA 96/1 (90°scale plate)

    ERFAL 96/1 (240°scale plate)

    These instruments are produced in a single housing with an incorporated electronic circuit

    BURDEN voltage circuit: 1,5 VAcurrent circuit: 0,1 VA

    ACCURACY CLASS 1,5

    STANDARD CAPACITIES 0,5-1-0,5 cos ϕ

    AUX POWER SUPPLY 100V, 230V, 400V to be specified when ordering

    INPUT CURRENT 5A

    EXAMPLES WHEN ORDERINGERFA96/12 5A 230V 0,5-1-0,5 cos ϕ single phase meter with 230V aux supplyERFA96/14 5A 400V 0,5-1-0,5 cos ϕ single phase meter with 400V aux supplyWhen testing it is necessary to applya minimum load of 10% if not

    the instrument will not indicateany value

    WEIGHT (kg) ERFA 96/1 (0,45) ERFAL 96/1 (0,50)

    For connection diagram see page 140

    ZEROVOLTMETER

    ERZ48 - ERZ72 - ERZ96 - ERZ144 (90°scale plate)

    ERZL48 - ERZL72 - ERZL96 - ERZL144 (240°scale plate)

    BURDEN 1 mA

    These instruments consist of moving coil movements with internal rectifier which can be used to replace theSinchronoscope in the synchronizing of two generators or one generator in the network. When the twovoltages to be synchronized are the same, the instrument indicates “zero”.

    STANDARD CAPACITIES from 0 to 50V, extended as far as 800V

    (The instrument can therefore be used with all the voltages

    as the equipment withstands up to 800V continuously)

    EXAMPLES WHEN ORDERINGERZ48 50V-800V zerovoltmeter 48x48, 90°end scale valueERZL96 50V-800V zerovoltmeter 96x96, 240°end scale value

    WEIGHT (kg) ERZ48 (0,10) ERZ72 (0,20) ERZ96 (0,22) ERZ144 (0,30)

    ERZL48 (0,22) ERZL72 (0,30) ERZL96 (0,35) ERZL144 (0,40)

    For connection diagram see page 139

  • 8/17/2019 Catalogue Panel Meter

    13/28128

    THREE PHASE, BALANCED LOAD POWER FACTOR METERS

    +

    ERC48 (72-96-144, 90°scale plate) + 1CORFP20ERCL48 (72-96-144, 240°scale plate) + 1CORFP20

    These measure consist of a 1mA direct current instrument (ERC-ERCL) for use with an external multi-voltageaccessory (1CORFP20). They have been produced separately to permit the reading of the cosϕ withinstruments of various designs other than 96x96 mm

    STANDARD CAPACITY 0,5-1-0,5 cos ϕTECHNICAL DATAERC-ERCL 1CORFP20see page 122 - Auxiliary power supply (separate): 230V /400V AC

    - Nominal input values: voltage: 400V ACcurrent: 5A (1A on types 1CORFP20...B)

    - Output nominal values: (selectable):1 - 5 - 10 - VDC and 1 - 5 - 10 - 20 - 4/20 mA DC1 mA DC degrees value for connection with analogue instruments

    - Conversion type:proportional to the phase angle

    - Resistive load: 700Ω- Measuring range: 0,5 (cap) - 1 - 0,5 (ind) standard- Accuracy class: 0,5- Overload: Permanent 2 In / 1,2 Un

    Instantaneous 10 In / 2 Un for 1 sec- Operating frequency: 50 / 60 Hz- Response time: ≤ 300 ms- Alternated residual: ≤ 1%- Burden: voltage ≤ 1VA current ≤ 0,8VA aux supply ≤ 4VA- Galvanic separation between inputs and outputs:

    insulation between inputs and outputs, aux supply 2kV for 1min at 50Hzinsulation between all circuits and earth: 4kV for 1min at 50Hz

    - Operating temperature: 0 °C ÷ +55 °C

    EXAMPLES WHEN ORDERINGERC48+1CORFP20 400V three phase meter, aux supply 400V;

    5A input current and 0,5-1-0,5 scale plateAn ERC48 instrument 1mAwill be provided with a 0,5-1-0,5 cosϕ scale plate and a 1CORFP20 accessory onwhich should be connected the terminals corresponding to 400V

    When testing it is necessary to applya minimum load of 10% if not theinstrument will not indicateany value

    For connection diagram see page 141

    SINGLE PHASE POWER FACTOR METERS

    ERC48 (72-96-144 90°scale plate) + 1CORFP10

    ERCL48 (72-96-144 240°scale plate) + 1CORFP10

    These measure consist of a 1mA direct current instrument (ERC-ERCL) for use with an external multi-voltageaccessory (1CORFP10). They have been produced separately to permit the reading of the cosϕ withinstruments of various designs other than 96x96 mm

    STANDARD CAPACITY 0,5-1-0,5 cos ϕTECHNICAL DATAERC-ERCL 1CORFP10see page 122 - Auxiliary power supply (separate): 230V AC

    - Nominal input values: voltage: 230V AC

    current: 5A (1A on types 1CORFP10...B)- Output nominal values: (selectable):1 - 5 - 10 - VDC and 1 - 5 - 10 - 20 - 4/20 mA DC1 mA DC degrees value for connection with analogue instruments

    - Conversion type:proportional to the phase angle

    - Resistive load: 700Ω- Measuring range: 0,5 (cap) - 1 - 0,5 (ind) standard- Accuracy class: 0,5- Overload: Permanent 2 In / 1,2 Un

    Instantaneous 10 In / 2 Un for 1 sec- Operating frequency: 50 / 60 Hz- Response time: ≤ 300 ms- Alternated residual: ≤ 1%- Burden: voltage ≤ 1VA current ≤ 0,8VA aux supply ≤ 4VA- Galvanic separation between inputs and outputs:

    insulation between inputs and outputs, aux supply 2kV for 1min at 50Hzinsulation between all circuits and earth: 4kV for 1min at 50Hz

    - Operating temperature: 0 °C ÷ +55 °C

    EXAMPLES WHEN ORDERINGERC72+1CORFP10 230V single phase meter, aux supply 230V;

    5A input current and 0,5-1-0,5 scale plateAn ERC72 instrument 1mAwill be provided with a 0,5-1-0,5 cosϕ scale plate and a 1CORFP10 accessory onwhich should be connected the terminals corresponding to 230V

    When testing it is necessary to applya minimum load of 10% if not theinstrument will not indicateany value

    For connection diagram see page 140

    +

  • 8/17/2019 Catalogue Panel Meter

    14/28

  • 8/17/2019 Catalogue Panel Meter

    15/28

  • 8/17/2019 Catalogue Panel Meter

    16/28131

    By adopting a single instrument with an interchangeable scale and multi-voltage converter it is possible to obtain all the capacities shown on thetable below. It is sufficient to select the input voltage on the accessory and to insert the scale corresponding to the current transformer used.

    If for example there is a need for a mono-phase 380V Wattmeter (Varmeter) with a C.T. ratio of 300/5A; the corresponding scale to insert into theinstrument has a 120KW (KVar) scale.

    This function only applies if the input voltage is direct and not by means of a V.T. in which case calibration in the factory is preferable. If insteadit is necessary to take advantage of the multi-scale function, even if the entry voltage derives from a V.T., eg: 1500/100V, always bearing in mind amono-phase wattmeter, it is necessary to seek the voltage constant and therefore 1500:100=15.

    In order to obtain the scale value to introduce into the indicating instrument, it is necessary to multiply the number found (15) by the value of the scaleon the table corresponding to C.T. 300/5A, which is 30KW (KVar)

    Therefore 15 x 30KW (KVar) = 450KW (KVar)

    In order to achieve the above, the various converters have been calibrated as follows:

    For the Active Power:100V, 5A=500W 230V, 5A=1000W 400V, 5A=2000W in the single phase system

    100V, 5A=1000W 230V, 5A=2000W 400V, 5A=4000W in the system: Balanced three phase without neutral, 3 wiresUnbalanced threephase without neutral, 3 wires (ARON)Balanced threephase with neutral, 4 wiresUnbalanced threephase with neutral, 4 wires

    For the Reactive Power100V, 5A=500VAR 230V, 5A=1000W 400V, 5A=2000VAR in the single phase system

    100V, 5A=1000VAR 230V, 5A=2000W 400V, 5A=4000VAR in the system: Balanced three phase without neutral, 3 wiresUnbalanced threephase without neutral, 3 wires (ARON)

    Balanced threephase with neutral, 4 wiresUnbalanced threephase with neutral, 4 wires

    Different capacities can be carried out on request

    SINGLE-PHASE WATTMETERS AND VARMETERS

    100V 230V 400V

    500 W (VAR) 1000 W (VAR) 2000 W (VAR)1000 W (VAR) 2000 W (VAR) 4000 W (VAR)1500 W (VAR) 3000 W (VAR) 6000 W (VAR)2000 W (VAR) 4000 W (VAR) 8000 W (VAR)2500 W (VAR) 5000 W (VAR) 10 KW (KVAR)3000 W (VAR) 6000 W (VAR) 12 KW (KVAR)4000 W (VAR) 8000 W (VAR) 16 KW (KVAR)5000 W (VAR) 10 KW (KVAR) 20 KW (KVAR)

    6000 W (VAR) 12 KW (KVAR) 24 KW (KVAR)8000 W (VAR) 16 KW (KVAR) 32 KW (KVAR)10 KW (KVAR) 20 KW (KVAR) 40 KW (KVAR)15 KW (KVAR) 30 KW (KVAR) 60 KW (KVAR)20 KW (KVAR) 40 KW (KVAR) 80 KW (KVAR)25 KW (KVAR) 50 KW (KVAR) 100 KW (KVAR)30 KW (KVAR) 60 KW (KVAR) 120 KW (KVAR)40 KW (KVAR) 80 KW (KVAR) 160 KW (KVAR)50 KW (KVAR) 100 KW (KVAR) 200 KW (KVAR)60 KW (KVAR) 120 KW (KVAR) 240 KW (KVAR)80 KW (KVAR) 160 KW (KVAR) 320 KW (KVAR)

    100 KW (KVAR) 200 KW (KVAR) 400 KW (KVAR)150 KW (KVAR) 300 KW (KVAR) 600 KW (KVAR)200 KW (KVAR) 400 KW (KVAR) 800 KW (KVAR)250 KW (KVAR) 500 KW (KVAR) 1000 KW (KVAR)

    THREE-PHASE WATTMETERS AND VARMETERS

    100V 230V 400V

    1000 W (VAR) 2000 W (VAR) 4000 W (VAR)2000 W (VAR) 4000 W (VAR) 8000 W (VAR)3000 W (VAR) 6000 W (VAR) 12 KW (KVAR)4000 W (VAR) 8000 W (VAR) 16 KW (KVAR)5000 W (VAR) 10 KW (KVAR) 20 KW (KVAR)6000 W (VAR) 12 KW (KVAR) 24 KW (KVAR)8000 W (VAR) 16 KW (KVAR) 32 KW (KVAR)10 KW (KVAR) 20 KW (KVAR) 40 KW (KVAR)

    12 KW (KVAR) 24 KW (KVAR) 48 KW (KVAR)16 KW (KVAR) 32 KW (KVAR) 64 KW (KVAR)20 KW (KVAR) 40 KW (KVAR) 80 KW (KVAR)30 KW (KVAR) 60 KW (KVAR) 120 KW (KVAR)40 KW (KVAR) 80 KW (KVAR) 160 KW (KVAR)50 KW (KVAR) 100 KW (KVAR) 200 KW (KVAR)60 KW (KVAR) 120 KW (KVAR) 240 KW (KVAR)80 KW (KVAR) 160 KW (KVAR) 320 KW (KVAR)

    100 KW (KVAR) 200 KW (KVAR) 400 KW (KVAR)120 KW (KVAR) 240 KW (KVAR) 480 KW (KVAR)160 KW (KVAR) 320 KW (KVAR) 640 KW (KVAR)200 KW (KVAR) 400 KW (KVAR) 800 KW (KVAR)300 KW (KVAR) 600 KW (KVAR) 1200 KW (KVAR)400 KW (KVAR) 800 KW (KVAR) 1600 KW (KVAR)500 KW (KVAR) 1000 KW (KVAR) 2000 KW (KVAR)

    CURRENTTRANSFORMER

    5/5 A10/5 A15/5 A20/5 A25/5 A30/5 A40/5 A50/5 A

    60/5 A80/5 A

    100/5 A150/5 A200/5 A250/5 A300/5 A400/5 A500/5 A600/5 A800/5 A

    1000/5 A1500/5 A2000/5 A2500/5 A

    INTERCHANGEABLE SCALE TABLE

    MULTISCALE FUNCTION IN WATTMETERS AND VARMETERS FOR ALTERNATING CURRENT

  • 8/17/2019 Catalogue Panel Meter

    17/28132

    ELECTRONIC INDICATORS WITH

    CONTACTS AND TIME DELAYS

    DIMENSIONS in mm

    1COR

    Weight: 0,65 Kg

  • 8/17/2019 Catalogue Panel Meter

    18/28133

    There is, pratically an unlimited variety of applications regarding electronic regulators.They are used for regulating and checking all those parameters which can be measured by an electrical instrument, both directly and by meansof a converter.These instruments offer a wide range of uses when there is a need for analogue signals, controls, automatic adjustments, protection, automaticprocess checks, etc.They have two adjustment channels which can be used one at a time or together and each channel has a potentiometer and a graduation in %of the scale (the scale value on the instrument corresponds to 100% on the graduated disc) and this adjustment can be carried out along theentire length of the scale.The diodes on the scale indicate whether the reading has been carried out inside or outside the limits of the scale limits.These instruments also have two timing circuits, one per channel, which make it possible to delay the exit signal when the user does not want

    the pick-up currents to be indicated.The timer immediately returns to zero and, should the indicator oscillate, these various times are not totalled together.When the timing of the signal is not necessary it is sufficient to place the potentiometer on point 0 for the instrument to immediately operate.

    GENERAL NOTES

    GENERAL NOTES

    SUPPLY VOLTAGE 220V +/-10% at 45/65Hz

    INFLUENCE OF THE SUPPLY VOLTAGE < 0,2% for +/-10%Vn

    BURDEN 3VA

    RELAYS

    MAXIMUM INTERRUPTION POWER WITH RESISTIVE LOAD   ≤ 600VA (≤ 3A, ≤ 250V)CHANNEL I EXIT adjustment of the minimum value

    CHANNEL II EXIT adjustment of the maximum value

    SIGNALING APPARATUS

    Adjustments by means of knob on the back of the instruments

    CLASS +/- 5% between 25% and 75% of the scale bottom value+/- 15% between 0 and 25% of the minimum valueand between 75% and 100% of the maximum value

    HYSTERESIS < 1% of the end scale value

    RANGE OF ADJUSTMENT OF THE SIGNAL INVERTION TIME from 0,5 to 30 seconds with precision +/- 20%, +/- 2 sec.

    STABILITY OF THE ADJUSTMENT POINT +/- 0,5%

    TECHNICAL CHARACTERISTICS

    As the two potentiometers are independent, either of them can be used for any value of the scale.

    ADJUSTMENT EXAMPLES

    M A X I I

    M I N I

    M A X I I

    M I N I

    M A X I IM I N I

    CON TACT

    INSTRUMENTLIMIT SIGNA L

    MONI T OR

    MA X I I

    M I N I

    CONTACT

    INSTRUMENTLIMIT SIGNA L

    MONI T OR

    MA X I I

    M I N I

    CONTACT

    INSTRUMENTLIMIT SIGNA L

    MONI T OR

    MA X I I

    M I N I

    M I N I

    M A X I I M A X I I

    M I N I

    M A X I IM I N I

    CON TACT

    INSTRUMENTLIMIT SIGNA L

    MONI T OR

    MA X I I

    M I N I

    CONTACT

    INSTRUMENTLIMIT SIGNA L

    MONI T OR

    MA X I I

    M I N I

    CONTACT

    INSTRUMENTLIMIT SIGNA L

    MONI T OR

    MA X I I

    M I N I

    min/max min/min max/max

    Note: Channel I corresponds to the minimum contact,the potentiometer of which, if not used, should be set on the 0% pointChannel II corresponds to the maximum contact,the potentiometer of which, if not used, should be set on the 100% point

  • 8/17/2019 Catalogue Panel Meter

    19/28134

    SINGLE PHASE POWER FACTOR METERS

    ERCC96 + 1CORFP10These instruments are made up of a 1mA direct current instrument (ERCC) and by an external multi-voltageaccessory (1CORFP10).

    STANDARD CAPACITY 0,5-1-0,5 cos ϕTECHNICAL DATAERCC 1CORFP10see above - Auxiliary power supply (separate): 230V AC

    - Nominal input values: voltage: 230V ACcurrent: 5A (1A on types 1CORFP10...B)

    - Output nominal values: (selectable):1 - 5 - 10 - VDC and 1 - 5 - 10 - 20 - 4/20 mA DC1 mA DC degrees value for connection with analogue instruments

    - Conversion type:proportional to the phase angle

    - Resistive load: 700Ω- Measuring range: 0,5 (cap) - 1 - 0,5 (ind) standard- Accuracy class: 0,5- Overload: Permanent 2 In / 1,2 Un

    Instantaneous 10 In / 2 Un for 1 sec- Operating frequency: 50 / 60 Hz- Response time: ≤ 300 ms- Alternated residual: ≤ 1%- Burden: voltage ≤ 1VA current ≤ 0,8VA aux supply ≤ 4VA- Galvanic separation between inputs and outputs:

    insulation between inputs and outputs, aux supply 2kV for 1min at 50Hzinsulation between all circuits and earth: 4kV for 1min at 50Hz

    - Operating temperature: 0 °C ÷ +55 °C

    EXAMPLES WHEN ORDERING

    ERCC96+1CORFP10 230V single phase meter, aux supply 230V; 5A input current and 0,5-1-0,5 scale plateAn ERCC96 instrument 1mAwill be provided with a 0,5-1-0,5 cosϕ scale plateand a 1CORFP10 accessory on which should be connected the terminalscorresponding to 230V

    When testing it is necessary to applya minimum load of 10% if not theinstrument will not indicateany value

    For connection diagram see page 140

    MOVING IRON INSTRUMENT FOR ALTERNATING CURRENT

    FREQUENCY METERS

    ERIC96BURDEN 3VAPOWER SUPPLY 220V +/-10% at 45/65HzINFLUENCE OF POWER SUPPLY < 0,2% for +/-10%VnAMMETER CAPACITIES . .. /5A input by means of C.T. with 5A secondaryVOLTMETER CAPACITIES 600V direct inputDifferent capacities can be carried out on requestEXAMPLES WHEN ORDERINGERIC96 5A1 + ESIC 250A1 220V ammeter input by means of C.T. with 5A secondary, 1In

    with 250/5A end scale value, 90°ERIC96 600V 220V voltmeter direct input with 600V end scale value, 90°

    For the connection diagram please see page 145

    ERFC96BURDEN 3VAPOWER SUPPLY 220V +/-10% at 45/65HzINFLUENCE OF POWER SUPPLY < 0,2% for +/-10%VnSTANDARD CAPACITY 45/65HzDifferent capacities can be carried out on requestEXAMPLES WHEN ORDERINGERFC96 45/65Hz 220V Frequency with end scale value 45/65HzFor the connection diagram please see page 145

    MOVING COIL INSTRUMENTS FOR DIRECT CURRENT

    ERCC96BURDEN 3VAPOWER SUPPLY 220V +/-10% at 45/65HzINFLUENCE OF POWER SUPPLY < 0,2% for +/-10%VnMILLIAMMETER CAPACITIES 1mA - 4/20 mAAMMETER CAPACITIES . .. /60mV input by means of Shunt, secondary 60mVVOLTMETER CAPACITIES 600V direct inputDifferent capacities can be carried out on requestEXAMPLES WHEN ORDERINGERCC96 60mV + ESCC96 400A 220V ammeter input by means of Shunt

    secondary 60mV, end scale value 400AERCC96 1mA + ESCC96 40A 220V ammeter 1mA, end scale value 40AFor the connection diagram please see page 145

    +

  • 8/17/2019 Catalogue Panel Meter

    20/28135

    THREE PHASE, BALANCED LOAD POWER FACTOR METERS

    ERCC96 + 1CORFP20These instruments are made up of a 1mA direct current instrument ( ERCC) and by an external multi-voltageaccessory (1CORFP20).

    STANDARD CAPACITY 0,5-1-0,5 cos ϕTECHNICAL DATAERCC 1CORFP20see page 136 - A uxiliary power supply (separate): 230V /400V AC

    - Nominal input values: voltage: 400V ACcurrent: 5A (1A on types 1CORFP20...B)

    - Output nominal values: (selectable):1 - 5 - 10 - VDC and 1 - 5 - 10 - 20 - 4/20 mA DC1 mA DC degrees value for connection with analogue instruments

    - Conversion type:proportional to the phase angle- Resistive load: 700Ω- Measuring range: 0,5 (cap) - 1 - 0,5 (ind) standard- Accuracy class: 0,5- Overload: Permanent 2In / 1,2Un - Instantaneous 10In / 2Un for 1 sec- Operating frequency: 50 / 60 Hz- Response time: ≤ 300 ms- Alternated residual: ≤ 1%- Burden: voltage ≤ 1VA current ≤ 0,8VA aux supply ≤ 4VA- Galvanic separation between inputs and outputs:

    insulation between inputs and outputs, aux supply 2kV for 1min at 50Hzinsulation between all circuits and earth: 4kV for 1min at 50Hz

    - Operating temperature: 0 °C ÷ +55 °C

    EXAMPLES WHEN ORDERINGERCC96+1CORFP20 400V three phase meter, aux supply 400V; 5A input current and 0,5-1-0,5 scale plate

    An ERCC96 instrument 1mAwill be provided with a 0,5-1-0,5 cosϕ scale plateand a 1CORFP20 accessory on which should be connected the terminalscorresponding to 400V

    When testing it is necessary to applya minimum load of 10% if not theinstrument will not indicateany value

    For connection diagram see page 141

    +

    MULTISCALE WATTMETERS AND VARMETERS FOR ALTERNATING CURRENT

    ERCC96 + 1CORPA1/2/3/4/5 (1CORPR1/2/3/4/5)These instruments are made up of a 1mA direct current instrument ( ERCC) and by an external multi-voltageaccessory (1CORPA/1CORPR) multivoltage. This accessory permits the interchangeability of the scale platesas shown on page 131.

    The possible systems are as follows:ERCC+ 1CORPA1 (1CORPR1) - Single phase, Wattmeter (Varmeter)ERCC+ 1CORPA2 (1CORPR2) - Three phase, Wattmeter (Varmeter), balanced load, without neutral, 3 wireERCC+1CORPA3 (1CORPR3) - Three phase, Wattmeter (Varmeter), unbalanced load, without neutral, 3 wire (ARON)

    ERCC+1CORPA4 (1CORPR4) - Three phase, Wattmeter (Varmeter), balanced load, with neutral, 4 wireERCC+1CORPA5 (1CORPR5) - Three phase, Wattmeter (Varmeter), unbalanced load, with neutral, 4 wire

    The scale plates are linear with values expressed in: Watt (W), Kilowatt (KW), Megawatt (MW)

    Var (Var), Kilovar (KVar) Megavar (MVar)TECHNICAL DATAERCC 1CORPA1, 1CORPA2, 1CORPA3, 1CORPA4, 1CORPA5see page 136 1CORPR1, 1CORPR2, 1CORPR3, 1CORPR4, 1CORPR5

    - Auxiliary power supply (separate): 230V / 400V AC- Nominal input values: voltage: 230V AC

    current: 5A (1A)- Output nominal values: (selectable):

    1 - 5 - 10 - VDC e 1 - 5 - 10 - 20 - 4/20 mA DC- Resistive load: 700Ω- Measuring range: 0 ÷ Pn (0 ÷ Qn)- Standard calibration: 100V,5A=500W (Var)

    230V,5A=1000W (Var)400V,5A=2000W (Var)

    - Accuracy class: 0,5- Overload: Permanent 2 In / 1,2 Un

    Instantaneous 10 In / 2 Un for 1 sec.- Operating frequency: 50 / 60 Hz- Response time: ≤ 300 ms- Alternated residual: ≤ 1%- Burden: voltage ≤ 1VA current ≤ 0,8VA aux supply ≤ 4VA- Galvanic separation between inputs and outputs:

    insulation between inputs and outputs, aux supply 2kV for 1min at 50Hzinsulation between all circuits and earth: 4kV for 1min at 50Hz

    - Operating temperature: 0 °C ÷ +55 °C

    INFORMATIONS NECESSARY WHEN ORDERING1) System type: single phase or three phase, with or without neutral, balanced or unbalanced load; 3 or 4 wire2) Voltage: between phases; between phase and neutral.

    If the voltage transformer is used please indicate the primary and secondary value.3) Current: max 5A for direct connection.

    If a current transformer is used please indicate the primary and secondary value.(the C.T. should however be in class 0,5)

    4) Desired scale value (if different from standard)EXAMPLES WHEN ORDERINGERCC96+ 1CORPA3 400V 100/5A 80KW

    Three phase Wattmeter, unbalanced load, without neutral, 3 wire (ARON)voltmetric direct input 400V, ammetric input by means a C.T. 100A/5Aand 80kW end scale value

    For connection diagram see from page 143 to 145

    +

  • 8/17/2019 Catalogue Panel Meter

    21/28136

    SINGLE PHASE INSULATION INDICATORS

    ERCC96MIThese instruments are used to measure continuously, with power applied, the insulation value respect to theearth of single phase lines with insulated neutral; or the insulation respect to the mass of the positive andnegative of direct current lines. The indicators ERCC96MI are provided with a separate accessory transducer(1RAMI) on which the power circuit is included.TECHNICAL DATAERCC96MI 1RAMIsee page 134 - Power supply: 100V AC ±10%

    - Measurement input voltage: max 500VAC/DC- Operating frequency: 45 ÷ 65 Hz- Burden: 1,5 - 2 VA- Operating temperature: -10°C ÷ +55 °C

    - Storage temperature: -40°C ÷ +70 °C- Overload: 1,2 Vn

    +

    L1

    1 4

    L2

    L3

    Fuse

    Fuse

    Fuse

    2A

    5 86 7

      I  n  s  u  l  a  t  i  o  n

       r  e  s  i  s  t  a  n  c  e

       m

      e  a  s  u  r  e  m

      e  n  t

       0      ÷

      5  0  0  V

       m

      a  x

    TVR .../100 V AC

    Pow er supply100VAC ±10% , 50/60 H z

    +-

    1RAMI ERCC96 end scale 5MΩ

    L1

    1 4

    L2

    L3

    Fuse

    Fuse

    Fuse

    2A

    5 86 7

      I  n  s  u  l  a  t  i  o  n

       r  e  s  i  s  t  a  n  c  e

       m

      e  a  s  u  r  e  m

      e  n  t

       0      ÷

      5  0  0  V

       m

      a  x

    TVR .../100 V AC

    Pow er supply100VAC ±10% , 50/60 H z

    +-

    1RAMI ERCC96 end scale 5MΩ

    0L1

    L2

    L3  S  w

      i  t  c  h

    CONNECTION DIAGRAMS

    WITHOU switch

    WITH switch

  • 8/17/2019 Catalogue Panel Meter

    22/28139

    CONNECTION DIAGRAMS FOR ANALOGUEINSTRUMENTS

    L1N

    L1N

    S1 S2

    P1 P2

    L1

    L2

    L3

    S1 S2

    P1 P2S1 S2

    P1 P2S1 S2

    P1 P2

    +-

    +-

    LL (N)

    L

    L1L2L3

    GL (N)

    L1L2L3N

    +-

    GL1L2L3

    L1

    SYNC

    L2 L1L2 L1

    GEN BUS BAR

    GL2

    L3

    ERPI - EMI - ERI - ERR

    ERIL - ERB - ERBC

    ERI...C

    AC / DC ammeters DC ammeters

    Maximum demand ammeters

    Ammeters with incorporated

    switch

    ERPC - EMC - ERC - ERCL

    DC ammeters

    ERPI - EMI - ERI - ERR

    ERIL - ERRL

    ERZ - ERZL

    AC / DC voltmeters,

    Suppressed zero voltmeters

    Frequencymeters

    Hourmeters

    Voltmeters with incorporated

    switch AC Voltmeters

    Zerovoltmeters

    ERS

    Sequence meters

    ERT - ERTL

    Temperature indicators

    ERCT - ERCTL

    Tachometers indicators

    ERSI96

    Syncronoscopes

    Direct input Input by means of V.T. Generator

    Direct input Input by means of C.T. Input by means of Shunt

    TachoGenerator

    Probe

    ERPI - EMI - ERI - ERR - ERIL

    ERPC - EMC - ERC - ERCL

    ERPI - EMI - ERI - ERIVH

    ERR - ERIL - ERRL - ERPC

    EMC - ERC - ERCL - ERZS

    ERZSL - ERFV - ERFVd

    ERF - ERFL - 4RK - 4RH

    ERI...C

    Generator

  • 8/17/2019 Catalogue Panel Meter

    23/28140

    L1

    N

    8 2 191

    S1 S2

    P1 P2L1

    N

    S1 S2

    P1 P2L1

    N

    S1

    P1

    S2

    P2

    8 2 191

    8 2 191

    +1

    311

    2

    L1

    N

    ERFA96/1 - ERFAL96/1

    Single phase Power Factor meters

    Note: Any operation necessary for installing theseinstruments must take place in the absolute absenceof voltage, as there is no insulation between line andinstrument direct input

    input by means ofC.T. (.../5A)

    input by means of C.T.(.../5A) and V.T. (.../100V)

    Terminals

    Terminals

    Terminals

    L1

    N

    2 3 111

    S1 S2

    P1 P2L1

    N

    S1 S2

    P1 P2L1

    N

    S1

    P1

    S2

    P2

    2 3 111

    2 3 111

    S1 S2

    P1 P2L1

    L2

    L3

    S1 S2

    P1 P2L1

    L2

    L3

    L1

    L2

    L3

    S1 S2

    P 1 P 2

    3 5 81

    3 5 81

    3 5 81

    +1

    3

    5 8

    L1

    L2

    L3

    ERFA96/2 - ERFAL96/2Three phase, balanced load without neutral,

    Power Factor meters

    Note: Any operation necessary for installing theseinstruments must take place in the absolute absenceof voltage, as there is no insulation between line andinstrument

    direct input

    input by means ofC.T. (.../5A)

    input by means of C.T.(.../5A) and V.T. (.../100V)

    Terminals

    Terminals

    Terminals

    1CORFP10 + ERC48 / ERC72 / ERC96 / ERC144 / ERCC96 1CORFP10 + ERCL48 / ERCL72 / ERCL96 / ERCL144

    Single phase Power Factor meters

    direct input

    input by means ofC.T. (.../5A)

    input by means ofC.T. (.../5A) and

    V.T. (.../100V)

    Terminals

    Terminals

    Terminals

    Signal conversion’s Dip

    proportional to the phase angle(output in degrees, for use with an analogic instrument)

    OFF

    1 2 3 4 5 6

    ON

    1 2 3 4

    220 V

    45-65 Hz

    1mADC-+

    V

    1 2 8

    P1 P2

    S1 S2

    5A

    N

    L1

    13 14 23 24

    + -

    20

    N

    230V

    C

        1   m    A    D    C

    22

    400V

  • 8/17/2019 Catalogue Panel Meter

    24/28

  • 8/17/2019 Catalogue Panel Meter

    25/28142

    31 2 11

    31 2 11

    P1 P2L1

    L2

    S1 S2

    U V

    u v

    L3

    N

    P1 P2L1

    L2

    S1 S2

    L3

    N

    L1

    L2

    L3

    N

    31 2 11

    S1 S2

    P1 P2L1

    L2

    L3

    S1 S2

    P1 P2L1

    L2

    L3

    L1

    L2

    L3

    S1 S2

    P 1 P 2

    3 5 81

    31

    3 5 81

    2 7 9

    5 82 7 9

    2 7 9

    S1 S2

    P1 P2L1

    L2

    L3

    S1 S2

    P1 P2L1

    L2

    L3

    L1

    L2

    L3

    S1 S2

    P 1 P 2

    3 5 81

    3 5 81

    3 5 81

    L1

    L2

    L3

    +1

    32 5 8

    7

    9

    ERV96/2 - ERVL96/2

    ERW96/3 - ERWL96/3 ERV96/3 - ERVL96/3

    ERW96/4 - ERWL96/4

    Three phase, balanced load, 3 wires without neutral,

    Varmeters

    Note: Any operation necessary for installing theseinstruments must take place in the absoluteabsence of voltage, as there is no insulationbetween line and instrument

    Three phase, unbalanced load, 3 wires without

    neutral (ARON), Wattmeters and Varmeters

    Note: Any operation necessary for installing theseinstruments must take place in the absoluteabsence of voltage, as there is no insulationbetween line and instrument

    Three phase, balanced load, 4 wires with neutral,

    Wattmeters

    Note: Any operation necessary for installing these

    instruments must take place in the absolute absence ofvoltage, as there is no insulation between line andinstrument

    direct input

    input by means ofC.T. (.../5A)

    input by means of C.T.(.../5A) and V.T. (.../100V)

    Terminals

    Terminals

    Terminals

    direct input

    input by means ofC.T. (.../5A)

    input by means of C.T.(.../5A) and V.T. (.../100V)

    Terminals

    Terminals

    Terminals

    direct input

    input by means ofC.T. (.../5A)

    input by means of C.T.(.../5A) and V.T. (.../100V)

    Terminals

    Terminals

    Terminals

    +1

    3

    5 8

    L1

    L2

    L3

    +1

    3

    5 8

    L1

    L2

    L3

    N

  • 8/17/2019 Catalogue Panel Meter

    26/28

    1 2 3 4 5 6 7 8 9 11

    1 2 3 4 5 6 7 8 9 11

    P1 P2L1

    L2

    S1 S2

    L3

    N

    P1 P2

    S1 S2

    P1 P2

    S1 S2

    1 2 3 4 5 6 7 8 9 11

    P1 P2L1

    L2

    S1 S2

    L3

    N

    P1 P2

    S1 S2

    P1 P2

    S1 S2

    L1

    L2

    L3

    N

    U

    V

    u

    v

    U

    V

    u

    v

    U

    V

    u

    v

    L1

    N

    8 2 191

    S1 S2

    P1 P2L1

    N

    S1 S2

    P1 P2L1

    N

    S1

    P1

    S2

    P2

    8 2 191

    8 2 191

    51 3 8

    P1 P2L1

    L2

    S1 S2

    U   V

    u v

    L3

    N

    P1 P2L1

    L2

    S1 S2

    L3

    N

    L1

    L2

    L3

    N

    51 3 8

    51 3 8

    +1

    3

    5 8

    L1

    L2

    L3

    N

    L1

    L2

    L3

    N

    14

    7

    36 9 11

    2 5 8

    1 2 8

    N

    L1

    16 17 21 23 24

    1 mA DC

    + -

    19

    N

    400V 230V

    C

    V

       1  m   A

       D   C

       2   3   0   V

    220 V

    45-65 Hz

    1mADC-+

    143

    ERV96/4 - ERVL96/4

    ERW96/5 - ERWL96/5 ERV96/5 - ERVL96/5

    1CORPA1 (1CORPR1) + ERC48 (72, 96, 144) / 2RCD36 (48, 72, 96) / ERCC96

    Three phase, balanced load, 4 wires with neutral,

    Varmeters

    Note: Any operation necessary for installing theseinstruments must take place in the absoluteabsence of voltage, as there is no insulationbetween line and instrument

    Three phase, unbalanced load, 4 wires with

    neutral, Wattmeters

    Three phase, unbalanced load, 4 wires with

    neutral, Varmeters

    Note: Any operation necessary for installingthese instruments must take place in theabsolute absence of voltage, as there is noinsulation between line and instrument

    Single phase Wattmeters (1CORPA1 + ERC48 (72, 96, 144) / 2RCD36 (48, 72, 96) / ERCC96

    Single phase Varmeters (1CORPR1 + ERC48 (72, 96, 144) / 2RCD36 (48, 72, 96) / ERCC96

    direct input

    input by means ofC.T. (.../5A)

    input by means of C.T.(.../5A) and V.T. (.../100V)

    Terminals

    Terminals

    Terminals

    direct input

    input by means ofC.T. (.../5A)

    input by means of C.T.(.../5A) and V.T. (.../100V)

    Terminals

    Terminals

    Terminals

    direct input

    input by means ofC.T. (.../5A)

    input by means of C.T.(.../5A) and V.T. (.../100V)

    Terminals

    Terminals

    Terminals

  • 8/17/2019 Catalogue Panel Meter

    27/28144

    L1

    S1 S2

    P1 P2

    S1 S2

    P1 P2L1

    S1

    P1

    S2

    P2

    21 198

    L2

    L3

    L1

    L2

    L3

    NN

    N

    L2

    L3

    N

    21 198

    21 198

    S1 S2

    P1 P2L1

    L2

    L3

    L1

    L2

    L3

    S1 S2

    P1 P2

    S1 S2

    P1 P2L1

    L2

    L3

    S1 S2

    P1   P2

    S2

    P2

    S1

    P1

    S2

    P2

    S1

    P1

    2 10 1281 5 6 19

    2 10 1281 5 6 19

    2 10 1281 5 6 19

    S1 S2

    P1 P2L1

    L2

    L3

    S1 S2

    P1 P2L1

    L2

    L3

    L1

    L2

    L3

    S1 S2

    P1 P2

    S1 S2

    P 1 P 2

    2 10 1281

    2 10 1281

    2 10 1281

    1CORPA2 (1CORPR2) + ERC48 (72, 96, 144) / 2RCD36 (48, 72, 96) / ERCC96

    1CORPA3 (1CORPR3) + ERC48 (72, 96, 144) / 2RCD36 (48, 72, 96) / ERCC96

    1CORPA4 (1CORPR4) + ERC48 (72, 96, 144) / 2RCD36 (48, 72, 96) / ERCC96

    Three phase, balanced load, 3 wires without neutral, Wattmeters (1CORPA2 + ERC48 (72, 96, 144) / 2RCD36 (48, 72, 96) / ERCC96

    Three phase, balanced load, 3 wires without neutral, Varmeters (1CORPR2 + ERC48 (72, 96, 144) / 2RCD36 (48, 72, 96) / ERCC96

    Three phase, unbalanced load (ARON), 3 wires without neutral, Wattmeters

    (1CORPA3 + ERC48 (72, 96, 144) / 2RCD36 (48, 72, 96) / ERCC96

    Three phase, unbalanced load (ARON), 3 wires without neutral, Varmeters

    (1CORPR3 + ERC48 (72, 96, 144) / 2RCD36 (48, 72, 96) / ERCC96

    Three phase, balanced load, 4 wires with neutral, Wattmeters (1CORPA4 + ERC48 (72, 96, 144) / 2RCD36 (48, 72, 96) / ERCC96

    Three phase, balanced load, 4 wires with neutral, Varmeters (1CORPR4 + ERC48 (72, 96, 144) / 2RCD36 (48, 72, 96) / ERCC96

    direct input

    input by means ofC.T. (.../5A)

    input by means of C.T.(.../5A) and V.T. (.../100V)

    Terminals

    Terminals

    Terminals

    direct input

    input by means ofC.T. (.../5A)

    input by means of C.T.(.../5A) and V.T. (.../100V)

    Terminals

    Terminals

    Terminals

    direct input

    input by means ofC.T. (.../5A)

    input by means of C.T.(.../5A) and V.T. (.../100V)

    Terminals

    Terminals

    Terminals

    1 2 8

    L2

    L1

    16 17 21 23 24

    1 mA DC

    + -

    400V 230V

    C

    10 12

    V

    L3

       1  m   A   D   C

       2   3   0   V

    1 2 8

    L2

    L1

    16 17 21 23 24

    1 mA DC

    + -

    400V 230V

    C

    10 12

    V

    L3

    19

    5 6

       1  m   A   D   C

       2   3   0   V

    1 2

    L2

    L1

    16 17 21 23 24

    1 mA DC

    + -

    400V 230V

    C

    V

    L3

    8

    19

    N

    N

       1  m   A   D   C

       2   3   0   V

    220 V

    45-65 Hz

    1mADC-+

    220 V

    45-65 Hz

    1mADC-+

    220 V

    45-65 Hz

    1mADC-+

  • 8/17/2019 Catalogue Panel Meter

    28/28

    L1

    L2

    L3

    N

    S1 S2

    P1 P2

    S1 S2

    P1 P2

    S1 S2

    P1 P2

    S1 S2

    P1 P2 P1

    S1 S2

    P1 P2

    S1 S2

    P2

    S1 S2

    P1 P2 P1

    S1 S2

    P1 P2

    S1 S2

    P2

    S1 S2

    P 1 P 2

    S1 S2

    P 1 P 2

    S1 S2

    P 1 P 2

    L1

    L2

    L3

    N

    1 8 2 3 10 4 5 12 6 19

    L1

    L2

    L3

    N

    1 8 2 3 10 4 5 12 6 19

    1 8 2 3 10 4 5 12 6 19

    L2

    L1

    16 17 21 23 24

    1 mA DC

    + -

    400V 230V

    C

    L3

    19

    N

    N

    1 2 3 4 5 6 8 10 12

    V

       1  m   A   D   C

       2   3   0   V

    ERIC96 - ERCC96 ERFC

    AC ammeters (ERIC96)

    DC ammeters (ERCC96)

    AC voltmeters (ERIC96)

    DC voltmeters (ERCC96)

    Frequencymeter

    ERIC96 - ERCC96

    _+

    220 V

    45-65 Hz   +

    _220 V

    45-65 Hz

    60-500V ~220 V

    45-65 Hz

    ERI96D - ERF96D

    Double voltmeter

    Double frequencymeter

    1CORPA5 (1CORPR5) + ERC48 (72, 96, 144) / 2RCD36 (48, 72, 96) / ERCC96

    Three phase, unbalanced load, 4 wires with neutral, Wattmeters (1CORPA5 + ERC48 (72, 96, 144) / 2RCD36 (48, 72, 96) / ERCC96

    Three phase, unbalanced load, 4 wires with neutral, Varmeters (1CORPR5 + ERC48 (72, 96, 144) / 2RCD36 (48, 72, 96) / ERCC96

    direct input

    input by means ofC.T. (.../5A)

    input by means of C.T.(.../5A) and V.T. (.../100V)

    Terminals

    Terminals

    Terminals

    220 V

    45-65 Hz

    1mADC-+

    L1

    GL2

    L3

    L1

    L2

    L3