  • Manual

    Central CO

    CO Control Panel

    Centrale CO

    REF.

    CCO122 / CCO222 / CCO322 / CCO422

    CCO110 / CCO115

  • CCO122 / CCO222 / CCO322 / CCO422 CCO110 / CCO115

    FABRICANTE DE PRODUCTOS CONTRA INCENDIOS FIRE PROTECTION MANUFACTURER - FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 1 -

    CONTENIDO / CONTENTS

    CASTELLANO ......................................................................................... Pag. 2

    CENTRALES CCO122, CCO222, CCO322 Y CCO422 ................................................................................ Pag. 2

    CENTRALES CCO110 Y CCO115 ... ........................... Pag. 7

    ENGLISH .................................................................................................... Pag. 10

    CONTROL PANELS CCO122, CCO222, CCO322 & CCO422 ............................................................................... Pag. 10

    CONTROL PANELS CCO110 & CCO115 .............................. Pag. 15

    PORTUGUS... Pag. 18

    CENTRALE CCO 122, CCO 222, CCO 322 & CCO442... Pag 18

    CENTRALE CCO 122, CCO 222, CCO 322 & CCO442 Dupla ventilao e (OPCIONAL) baterias. Pag 22

    CENTRALE CCO110 &CCO115........Pag 23

    MAR11

  • CCO122 / CCO222 / CCO322 / CCO422 CASTELLANO

    FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 2 -

    CENTRALES CCO122, CCO222, CCO322 Y CCO422

    Indicadores luminosos

    A Led verde: Indica que el sistema est operativo. B Led rojo: Indica la activacin del Rel de Alarma. C Led verde: Indica que se ha activado el Rel de Ventilacin. D Led mbar: Indica que se ha superado el Nivel de Ventilacin. E Led mbar: Indica una avera o una irregularidad en la lnea de deteccin.

    Pulsadores de mando

    1 y 2. : Permiten el desplazamiento vertical por las diferentes opciones y lneas del men. Tambin permite incrementar ( ) o decrementar ( ) los parmetros numricos.

    3. ESC/MENU: Permite retroceder una pgina de pantalla. 4. ENTER: Permite avanzar hacia la siguiente pgina de pantalla o

    confirmar una seleccin. Manejo de la central

    En condiciones normales de operacin la central muestra la pantalla principal, visualizando la concentracin de CO en cada zona y el estado de la lnea de deteccin y los rels de ventilacin y alarma.

    ZONA 1 AnuladaZONA 2 Sin SensoresZONA 3 AnuladaZONA 4 Anulada

    Z1: 100 Vent. Man. HZ2: 250 Vent. Man. FZ3: 065 Niv. V. :050Z4: 300 Vent. Autom.

    Nmero de zona

    Concentracin de CO (ppm)

    Estado de la zona

  • CCO122 / CCO222 / CCO322 / CCO422 CASTELLANO

    FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 3 -

    Pulsando la tecla men se accede a las pantallas de men. Existen 5 pantallas de men a las que se puede acceder a travs de las teclas o :

    Ventilacin (Activacin Manual/Modo Ventilacin, ver figura 1). Servicio (Zonas On/Off, ver figura 2). Programacin de Ventilacin (Nivel y Retardo, ver figura 3). Programacin de Retardo de Alarmas

    (figura 4). Recuperar Datos de Origen (figura 5).

    Los datos de origen son los siguientes:

    Parmetro Valor Margen

    Nivel de Ventilacin: 50 ppm Programable (20 150 ppm) Retardo Ventilacin: 4 min Programable (1 9 min) Retardo Postventilacin: 4 min Fijo Nivel de Alarma: 300 ppm Fijo Retardo Alarma: 15 min Programable (10 30 min)

    Las flechas y que aparecen en algunas pantallas de men, indican la existencia de pantallas anteriores y posteriores, respectivamente, a la pantalla actual.

    Instalacin

    La figura muestra el esquema general de conexionado de los diferentes elementos con la central. Se pueden conectar un mximo de 22 detectores por zona. Se recomienda el uso de cable con una seccin mnima de 1.5 mm2 y la longitud mxima del mismo por zona no debe exceder los 400m, en una distribucin lineal de detectores.

    Importante. Los detectores de Monxido de Carbono DCO tienen polaridad.

    +-ZONAVENT.

    +-ALAR.

    +

    -

    +

    -

    +

    -

    +

    -

    +

    -

    +

    -

    Ventilacin

    Alarma

    Detectores CO (mx. 22)

    Estructura por Zona

    +-

    Alarma Parada [CO]

    Nivel de Ventilacin

    Nivel de Alarma

    Retardo Ventilacin

    Ventilacin Activada

    Ventilacin Activada

    Retardo Postventilacin

    Ventilacin Parada

    Alarma Activada

    Retardo Alarma

    Tiempo

  • CCO122 / CCO222 / CCO322 / CCO422 CASTELLANO

    FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 4 -

    M : A / VENTILACIONActivar Manual

    A / VENT. zona 2zona 1

    zona 3zona 4

    MANUAL A / ZONA 1MODO VENT

    fija1 hora

    ENTER Seleccin de zona + ENTER

    fija + ENTER

    ENTER1 hora +

    A / ZONA 1VENT. MAN. F

    start stop

    A / ZONA 1VENT. MAN. H

    start stop

    ZONA 1Conectada fija

    Ventilacion

    ZONA 1Manual Parada

    Ventilacion

    ZONA 1Conectada 1 hora

    Ventilacion

    ZONA 1Manual Parada

    Ventilacion

    start + ENTER

    stop + ENTER

    start + ENTER

    stop + ENTER

    Figura 1. Pantalla Ventilacin Manual.

    M : B / SERVICIOOn / Off Zonas

    B / SERV.zona 2zona 1

    zona 3zona 4

    ON_OFF

    ENTER Seleccin de zona + ENTER

    ZONA 1 QuedaAnulada

    ZONA 1 Queda en Servicio

    on + ENTER

    ENTERoff +

    B / ZONA 1SERVICIO

    on off

    Figura 2. Pantalla Servicio.

  • CCO122 / CCO222 / CCO322 / CCO422 CASTELLANO

    FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 5 -

    M : C / PROGRAMACIONVENT: NIvel / Ret

    C / PROG. zona 2zona 1

    zona 3zona 4

    NIVELRETARDO

    C / PROG.Nivel: 050 ppm

    ZONA 1 C / GRABAR NIVELNO: esc SI: enter

    C / PROG. ZONA 1Retardo: 4 min

    C / GRABAR RETARDONO: esc SI: enter

    ENTER Seleccin de zona + ENTER

    nivel + ENTER

    ENTERretardo +

    C / PROG.ZONA 1

    nivel retardo

    Seleccin de nivel + ENTER

    Seleccin de retardo + ENTER

    ENTER

    ENTER

    ESC

    ESC

    Zona 1 GrabandoseNivel de ventilacion ... OK

    Zona 1 Grabandoseretardo de ventilacion ... OK

    C / PROG.ZONA 1

    nivel retardo

    C / PROG.ZONA 1

    nivel retardo

    Figura 3. Pantalla Programacin de Ventilacin.

    D / GRABA RETARDONO: esc SI: enter

    M : D/ PROG. ALARMASRetardo: 10 min

    Seleccin de retardo + ENTERENTER

    ESC

    Zona 1 RetardoAlarma grabandose ... OK

    M : D/ PROG. ALARMASRetardo: 10 min

    Figura 4. Pantalla Programacin Retardo de Alarmas.

    M : E/ RECUPERARDATOS DE ORIGEN

    < E / GRABAR DATOS ?NO: esc SI: enter

    ENTER

    ESC

    Zona 1 Datos deorigen grabandose ... OK

    M : E/ RECUPERARDATOS DE ORIGEN

    Figura 5. Pantalla Recuperar Datos de Origen.

  • CCO122 / CCO222 / CCO322 / CCO422 CASTELLANO

    FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 6 -

    Doble ventilacin y (OPCIONAL) bateras

    Doble ventilacin:

    En el caso de que la central disponga de doble ventilacin, el conexionado se debe realizar tal y como se muestra en la figura.

    Los datos de origen son los siguientes:

    Bateras:

    Se deben conectar a la entrada del circuito situado en la parte derecha de la fuente de alimentacin, esta salida est identificada.

    Conexin de las dos bateras de 12 V en serie:

    Parmetro Valor Margen

    Nivel de Ventilacin 1: 50 ppm Programable (20 150 ppm)

    Retardo Ventilacin 1: 4 min Programable (1 9 min)

    Retardo Postventilacin 1: 4 min Fijo Nivel de Ventilacin 2: 200 ppm Programable

    (20 300 ppm) y Nivel ventilacin 1

    Retardo Ventilacin 2: 10 min Programable (1 30 min) y Retardo ventilacin 1

    Retardo Postventilacin: 4 min Fijo Nivel de Alarma: 300 ppm Fijo Retardo Alarma: 15 min Programable

    (10 30 min)

    12V12V

    -

    +

    -

    +-

    Alar VentAlar Vent Zona2 Zona1

    + - + -+ +--Alar VentAlar Vent Zona2 Zona1

    + - + -+ +--

    Vent1 Z1

    Vent1 Z2

    Vent1 Z3( *Z1)

    Vent1 Z4( *Z2)

    61

    R2

    K1

    Q4

    D2D1D3

    R3

    K2

    Q3Q1

    R1

    K3

    R5

    K5

    R4

    1

    U5

    K4

    J4

    1

    U1

    Q5

    U3

    1

    U4

    1

    U2

    D4 D5

    Q2

    - +ALZ4Z3Z2Z1

    Vent2Z4

    - +

    J1

    GND CPU

    Vent2 Z2

    Vent2 Z3

    Vent2 Z1

    Vent2 Z4

    En caso de que la central sea de 1 o 2 zonas seguir las indicaciones con *

    Bateras

    +-

    BAT

    Vent2Z2 Vent2Z3Vent2Z1

    Alarma Z4(*Z2)

    Alarma Z3(*Z1)

    Alarma Z2

    Alarma Z1

    Alarma Parada [CO]

    Nivel de Ventilacin 2

    Retardo Ventilacin 1

    Ventilacin 1

    Ventilacin 1

    Retardo Postventilacin 1

    Ventilacin 1 Parada

    Alarma Activada

    Retardo Alarma

    Tiempo

    Nivel de Alarma

    Retardo Ventilacin 2

    Ventilacin 2

    Ventilacin 2

    Retardo Postventilacin

    Ventilacin 2

    Nivel de Ventilacin 1

  • CCO110 / CCO115

    CASTELLANO

    FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 7 -

    CENTRALES CCO110 Y CCO115

    Indicadores luminosos

    A Led verde: Indica que el sistema est operativo. B Led rojo: Indica la activacin del Rel de Alarma. C Led verde: Indica que se ha activado el Rel de Ventilacin. D Led mbar: Indica que se ha superado el Nivel de Ventilacin. E Led mbar: Indica una avera o una irregularidad en la lnea de deteccin. F Led verde: Indica que el display muestra concentracin de CO (ppm). G Led verde: Indica que el display muestra el Nivel de Ventilacin. H Led verde: Indica que el display muestra el Retardo de Ventilacin

    Pulsadores de mando

    1. Seleccin Display: Permite seleccionar el dato mostrado por el display: Concentracin de CO, Nivel de Ventilacin o Retardo de Ventilacin.

    2 y 3. : Permiten incrementar ( ) o decrementar ( ) los parmetros numricos

    4. ON/OFF Ventilacin Permite activar o desactivar manualmente la ventilacin en cualquier momento

  • CCO110 / CCO115

    CASTELLANO

    FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 8 -

    +-ZONA VENT.

    +-ALAR.

    +

    -

    +

    -

    +

    -

    +

    -

    +

    -

    +

    -

    Ventilacin

    Alarma

    Estructura por Zona

    +

    (max. 15 en CCO115)

    Detectores CO

    Manejo de la central

    La central permite la programacin del Nivel de Ventilacin y del Retardo de Ventilacin mediante las teclas y SELECCION DISPLAY. La tecla ON/OFF VENTILACION MANUAL permite activar/desactivar manualmente la ventilacin en cualquier momento.

    Los datos de origen son los siguientes:

    Parmetro Valor Margen

    Nivel de Ventilacin: 50 ppm Programable (20 150 ppm, en incrementos de 10 ppm)

    Retardo Ventilacin: 4 min Programable (1 9 min, en incrementos de 1 min)

    Retardo Postventilacin: 4 min Fijo Nivel de Alarma: 300 ppm Fijo Retardo Alarma: 0 min Fijo

    Instalacin

    La figura muestra el esquema general de conexionado de los diferentes elementos con la central. Se pueden conectar un mximo de 10 detectores por zona en la central CCO110 y 15 en la central CCO115. Se recomienda el uso de cable con una seccin mnima de 1,5mm2 y la longitud mxima del mismo por zona no debe exceder los 400m, en una distribucin lineal de detectores.

    Importante. Los detectores de Monxido de Carbono DCO tienen polaridad

    Alarma Parada [CO]

    Nivel de Ventilacin

    Nivel de Alarma

    Retardo Ventilacin

    Ventilacin Activada

    Ventilacin Activada

    Retardo Postventilacin

    Ventilacin Parada

    Alarma Activada

    Retardo Alarma

    Tiempo

  • CCO110 / CCO115

    CASTELLANO

    FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 9 -

    Doble ventilacin y (OPCIONAL) bateras

    Doble ventilacin:

    En el caso de que la central disponga de doble ventilacin, dispondremos de dos salidas de ventilacin.

    La primera salida de ventilacin est identificada como VENT1, y la segunda ventilacin como VENT2.

    El nivel de alarma tambin queda modificado en estas centrales a 200 ppm.

    Los datos de origen son los siguientes:

    Parmetro Valor Margen

    Nivel de Ventilacin 1: 50 ppm Fijo Retardo Ventilacin 1: 1 min Programable

    (1 9 min) Retardo Postventilacin 1: 4 min Fijo Nivel de Ventilacin 2: 100 ppm Fijo Retardo Ventilacin 2: 0 min Fijo Retardo Postventilacin: 0 min Fijo Nivel de Alarma: 200 ppm Fijo Retardo Alarma: 0 min Fijo

    Bateras:

    Las bateras se deben conectar a la entrada de bateras del circuito situada en la parte derecha del circuito fuente de alimentacin, esta salida est identificada.

    Conexin de las dos bateras de 12 V en serie:

    12V12V

    -

    +

    -

    +-

    Alarma Parada [CO]

    Nivel de Ventilacin 2

    Retardo Ventilacin 1

    Ventilacin 1

    Ventilacin 1

    Retardo Postventilacin 1

    Ventilacin 1 Parada

    Alarma Activada

    Retardo Alarma

    Tiempo

    Nivel de Alarma

    Retardo Ventilacin 2

    Ventilacin 2

    Ventilacin 2

    Retardo Postventilacin

    Ventilacin 2

    Nivel de Ventilacin 1

    Alarm OFF

  • CCO122 / CCO222 / CCO322 / CCO422 ENGLISH

    FIRE PROTECTION MANUFACTURER Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 10 -

    CCO122, CCO222, CCO322 & CCO422 CONTROL PANELS

    Light Indicators

    A Green LED: system operating normal. B Red LED: Indicates activation of Alarm Relay. C Green LED: Indicates activation of Ventilation Relay. D Amber LED: Indicates Ventilation Level has been exceed. E Amber LED: Indicates Fault or trouble on detection zone.

    External Controls

    1 & 2. : To move up and down trough different options and lines of menu. Also, allows to increase ( ) or decrease ( ) numerical parameters.

    3. ESC/MENU: To go back a display. 4. ENTER: To move forward next display or confirm a selection

    Operation of Control Panel

    Under normal condition, display of control panel shows main screen, visualizing CO concentration on each zone, situation of detection zone, and situation of ventilation and alarm relays.

    CO Concentration (ppm)

    ZONE 1 Disabled

    ZONE 3 DisabledZONE 4 Disabled

    ZONE 2 No Sensors

    Zone information

    Z1: 100 Man.Vent.HZ2: 250 Man.Vent.FZ3: 065 V.Lev.:050Z4: 300 Autom.Vent.

    N of zone

  • CCO122 / CCO222 / CCO322 / CCO422 ENGLISH

    FIRE PROTECTION MANUFACTURER Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 11 -

    To accede into menu displays, press MENU pushbutton. There are 5 different menu displays.

    Using cursors or to move forward different menus:

    Ventilation (Activate Manual/Ventilation Mode, see picture 1).

    Operation (Zones On/Off, see picture 2).

    Programming of Ventilation (Level and Delay, see picture 3).

    Programming of Alarm delays (see picture 4).

    Restore Factory Settings (see picture 5).

    Factory settings are as follows:

    Parameter Value Margins

    Ventilation Levels: 50 ppm Programmable (20 150

    ppm, on a 10 ppm increase rate)

    Ventilation Delay: 4 min Programmable (1 9 min)

    Post-ventilation delay: 4 min Fixed Alarm Level: 300 ppm Fixed

    Alarm Delay: 15 min Programmable (10 30 min)

    Cursors and which appears in some displays of menu, indicates that there are previous and next displays, respectively, than the current one.

    Installation

    Below picture shows the general connection outline of different components. It is possible to connect up to 22 sensors per zone. Wiring: it is recommended to use cable with 1.5 mm2 of minimum section. Maximum length of cable per zone must not exceed 400m, in a lineal distribution of sensors.

    Note. Attention to polarity requirements of CO sensors.

    [CO]

    Ventilation level

    Alarm level

    Ventilation Delay

    Ventilation ON

    Ventilation ON

    Post-ventilation Delay

    Postventilacin Ventilation OFF

    Alarm ON

    Alarm Delay

    Time

  • CCO122 / CCO222 / CCO322 / CCO422 ENGLISH

    FIRE PROTECTION MANUFACTURER Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 12 -

    ENTERstart stop

    start + ENTER

    stop + ENTER

    start + ENTER

    stop + ENTER

    1 hour + A / ZONE 1 MAN.VENT

    A / VENT. MANUAL

    ENTER ENTER

    ENTER start stop

    fixed + A / ZONE 1 MAN.VENT

    M: A / VENTILATIONActivate Manual

    zone 1zone 2zone 3zone 4

    A / ZONE 1 fixedVENT. MODE 1 hour

    Zone selection +

    ZONE 1 VentilationConnected fixed

    ZONE 1 VentilationManual Stopped

    ZONE 1

    ZONE 1

    Manual Stopped

    Ventilation

    Ventilation

    Connected 1 hour

    Picture 1. Manual Ventilation display.

    ON_OFF

    ENTER ENTER

    on + ENTER

    ENTERoff +

    on

    offOn / Off Zones

    B / OPER. zone 1zone 2zone 3zone 4

    B / ZONE 1OPERATION

    zone selection +

    ZONE 1 isoperating

    ZONE 1 isdisabled

    M : B / OPERATION

    Picture 2. Operation display.

  • CCO122 / CCO222 / CCO322 / CCO422 ENGLISH

    FIRE PROTECTION MANUFACTURER Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 13 -

    ENTERretardo +

    C / PROG.

    ENTER

    ENTER

    ESC

    C / PROG.

    leveldelay

    leveldelay

    C / PROG. ZONE 1Delay: 4 min

    C / PROG.

    C / PROG.

    ENTER ENTER

    ENTER

    Seleccin de nivel + ENTERENTER

    ESC

    C / PROG.M : C / PROGRAMMINGVENT: Level / Del

    LEVELDELAY

    zone 1zone 2zone 3zone 4

    zone selection +

    ZONE 1

    level + ZONE 1Level: 050 ppmC / SAVE LEVEL

    NO: esc YES: enter

    NO: esc YES: enterC / SAVE DELAY

    leveldelayZONE 1

    ZONE 1

    Zone 1 SavingVentilation level ..... OK

    Zone 1 Savingventilation delay ..... OKDelay selection +

    Picture 3. Programming of ventilation display.

    ENTERENTER

    ESC

    Delay selection +

    M : D/ PROG. ALARMSDelay: 10 min

    D / SAVE DELAYNO: esc YES: enter

    M : D/ PROG. ALARMSDelay: 10 min

    Zone 1 savingAlarm delay ..... OK

    Picture 4. Programming of Alarms delays display.

    M : E/ RESTOREFACTORY SETTINGS

    ENTER

    ESC

    M : E/ RESTOREFACTORY SETTINGS

    < E/ SAVE SETTINGS?NO: esc YES: enter

    Zone 1 savingfactory settings ..... OK

    Picture 5. Restore Factory settings screen.

  • CCO122 / CCO222 / CCO322 / CCO422 ENGLISH

    FIRE PROTECTION MANUFACTURER Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 14 -

    12V12V

    -

    +

    -

    +-

    Double ventilation and (OPTIONAL) batteries

    Double ventilation:

    If the control panel has double ventilation, then it should be connected according to the following schematic.

    Factory settings are as follows:

    Parameter Value Margins

    Ventilation 1 Level: 50 ppm Programmable

    (20 150 ppm)

    Ventilation 1 Delay: 4 min Programmable

    (1 9 min)

    Post-ventilation 1 delay: 4 min Fixed Ventilation 2 Level: 200 ppm Programable

    (20 300 ppm) and Ventilation 1 level

    Ventilation 2 Delay: 10 min Programable (1 30 min) and Ventilation 1 delay

    Post-ventilation 2 delay: 4 min Fixed Alarm Level: 300 ppm Fixed

    Alarm Delay: 15 min Programmable

    (10 30 min)

    Batteries:

    Batteries must be wired to the to the battery output on the board on the right side of the panel, this output is labelled.

    Two 12V-batteries series-connected:

    Alarm OFF [CO]

    Ventilation 2 level

    Ventilation 1 Delay

    Ventilation 1 ON

    Ventilation 1 ON

    Post-ventilation 1 Delay

    Ventilation 1 OFF

    Alarm ON

    Alarm Delay

    Tiempo

    Alarm level

    Ventilation 2 Delay

    Ventilation 2 ON

    Ventilation 2 ON

    Post-ventilation 2 Delay

    Ventilation 2 OFF

    Ventilation 1 level

    Alar VentAlar Vent Zona2 Zona1

    + - + -+ +--Alar VentAlar Vent Zona2 Zona1

    + - + -+ +--

    Vent1 Z1

    Vent1 Z2

    Vent1 Z3( *Z1)

    Vent1 Z4( *Z2)

    61

    R2

    K1

    Q4

    D2D1D3

    R3

    K2

    Q3Q1

    R1

    K3

    R5

    K5

    R4

    1

    U5

    K4

    J4

    1

    U1

    Q5

    U3

    1

    U4

    1

    U2

    D4 D5

    Q2

    - +ALZ4Z3Z2Z1

    Vent2Z4

    - +

    J1

    GND CPU

    Vent2 Z2

    Vent2 Z3

    Vent2 Z1

    Vent2 Z4

    Bateras

    +-

    BAT

    Vent2Z2 Vent2Z3Vent2Z1

    Alarma Z4(*Z2)

    Alarma Z3(*Z1)

    Alarma Z2

    Alarma Z1

    In case of 1 or 2 zones Control Panel, you have to follow indications with *

  • CCO110 / CCO115 ENGLISH

    FIRE PROTECTION MANUFACTURER Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 15 -

    CCO110 & CCO115 CONTROL PANELS

    Light Indicators

    A Green LED: System operating normal. B Red LED: Indicates Alarm Relay activation. C Green LED: Indicates Ventilation Relay activated. D Amber LED: Indicates that Ventilation Level has been exceed. E Amber LED: Indicates fault or trouble on detection zone. F Green LED: Indicates that display is showing a CO concentration (ppm). G Green LED: Indicates that display is showing the Ventilation Level. H Green LED: Indicates that display is showing the Ventilation Delay (temporization).

    External Controls

    1. Seleccin Display: To select the information shown in the display: CO Concentration, Ventilation Level or Ventilation Delay.

    2 & 3. : To increase ( ) or decrease ( ) the numerical parameters. 4. ON/OFF Ventilation To activate/deactivate on manual mode the ventilation at any

    moment.

  • CCO110 / CCO115 ENGLISH

    FIRE PROTECTION MANUFACTURER Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 16 -

    +-ZONE VENT.

    +-ALAR.

    +

    -

    +

    -

    +

    -

    +

    -

    +

    -

    +

    -

    Ventilation

    Alarm

    Estructure per Zone

    +

    (CCO115 up to 15)

    CO Detectors

    Operation of control panel

    The control panel allows to program the Ventilation Level and the Ventilation Delay using cursors , and DISPLAY SELECTION. The MANUAL VENTILATION ON/OFF pushbutton allows to activate/deactivate on manual mode the ventilation at any moment. The factory settings are as follows:

    Installation

    Below picture shows the general connection outline of different components. It is possible to connect up to 10 sensors per zone in CCO110 panel and up to 15 sensors in CCO115 panel. Wiring: it is recommended to use cable with 1.5 mm2 of minimum section. Maximum length of cable per zone must not exceed 400m, in a lineal distribution of sensors.

    NOTE: Attention to polarity requirements of CO sensors.

    Parameter Value Margin Ventilation Level: 50 ppm Programmable (20 150 ppm,

    on a 10 ppm increase rate) Ventilation Delay: 4 min Programmable (1 9 min, on a

    1 min increase) Post-ventilation Delay: 4 min Fixed Alarm Level: 300 ppm Fixed Alarm Delay: 0 min Fixed

    Alarm OFF [CO]

    Ventilation level

    Alarm level

    Ventilation Delay

    Ventilation ON

    Ventilation ON

    Post-ventilation Delay

    Postventilacin Ventilation OFF

    Alarm ON

    Alarm Delay

    Time

  • CCO110 / CCO115 ENGLISH

    FIRE PROTECTION MANUFACTURER Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 17 -

    Double ventilation and (OPTIONAL) batteries

    Double ventilation:

    If the control panel has double ventilation, we have two ventilation outputs.

    The first ventilation output is VENT1 labeled, and second ventilation level is VENT2 labeled.

    The alarm level in this control panels is 200 ppm.

    Factory settings are as follows:

    Parameter Value Margins

    Ventilation 1 Level: 50 ppm Fixed

    Ventilation 1 Delay: 1 min Programmable

    (1 9 min)

    Post-ventilation 1 delay: 4 min Fixed Ventilation 2 Level: 100 ppm Fixed Ventilation 2 Delay: 0 min Fixed Post-ventilation 2 delay: 0 min Fixed Alarm Level: 200 ppm Fixed

    Alarm Delay: 0 min Fixed

    Batteries:

    Batteries must be wired to the to the battery output on the board on the right side of the panel, this output is labelled.

    Two 12V-batteries series-connected

    12V12V

    -

    +

    -

    +-

    Alarm OFF [CO]

    Ventilation 2 level

    Ventilation 1 Delay

    Ventilation 1 ON

    Ventilation 1 ON

    Post-ventilation 1 Delay

    Ventilation 1 OFF

    Alarm ON

    Alarm Delay

    Tiempo

    Alarm level

    Ventilation 2 Delay

    Ventilation 2 ON

    Ventilation 2 ON

    Post-ventilation 2 Delay

    Ventilation 2 OFF

    Ventilation 1 level

  • CCO122 / CCO222 / CCO322 / CCO422 PORTUGUS

    FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 18 -

    CENTRALE CCO122, CCO222, CCO322 Y CCO422

    Indicadores luminosos

    A Led verde: Indica que o sistema est operativo. B Led vermelho: Indica a activao do Rel de Alarme. C Led verde: Indica que se activou o Rel de Ventilao. D Led mbar: Indica que se superou o Nvel de Ventilao. E Led mbar: Indica uma avaria ou uma irregularidade na linha de deteco.

    Botes de comando

    1 e 2. : Permitem o deslocamento vertical pelas diferentes opes e linhas do menu. Tambm permite aumentar ( ) ou diminuir ( ) os parmetros

    numricos.

    3. ESC/MENU: Permite retroceder uma pgina de ecr. 4. ENTER: Permite avanar para a pgina seguinte de ecr ou confirmar uma

    seleco.

    Manuseio da central

    Em condies normais de funcionamento a central mostra o ecr principal, visualizando a concentrao

    de CO em cada zona e o estado da linha de deteco e os rels de ventilao e alarme.

  • CCO122 / CCO222 / CCO322 / CCO422 PORTUGUS

    FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 19 -

    +-ZONAVENT.

    +-ALAR.

    +

    -

    +

    -

    +

    -

    +

    -

    +

    -

    +

    -

    Ventilacin

    Alarma

    Detectores CO (mx. 22)

    Estructura por Zona

    +-Ventilao

    Alarme

    Estructura por zona

    Premindo a tecla menu acede-se aos ecrs de menu. Existem 5 ecrs de menu aos quais se pode aceder atravs das teclas ou :

    * Ventilao (Activao Manual/Modo Ventilao, ver figura 1). * Servio (Zonas On/Off, ver figura 2). * Programao de Ventilao (Nvel e Atraso, ver figura 3). * Programao de Atraso de Alarmes (figura 4). * Recuperar Dados de Origem (figura 5).

    Os dados de origem so os seguintes:

    Parmetro Valor Margem

    Nvel de Ventilao: 50 ppm Programvel (20 150 ppm) Atraso Ventilao: 4 min Programvel (1 9 min) Atraso Ps-ventilao: 4 min Fixo Nivel de Alarme: 300 ppm Fixo Atraso Alarme: 15 min Programvel (10 30 min)

    As flechas e que aparecem em alguns ecrs de menu, indicam a existncia de ecrs anteriores e posteriores, respectivamente, ao ecr actual.

    Instalao

    A figura mostra o esquema geral de ligao dos diferentes elementos com a central.

    Pode ligar-se um mximo de 22 detectores por zona. Recomenda-se o uso de cabo com uma seco mnima de 1.5 mm

    2 e a longitude mxima do mesmo por

    zona no deve exceder os 400m, numa distribuio linear de detectores.

    Importante. Os detectores de Monxido de Carbono DCO tm polaridade.

    Alarme OFF [CO]

    Nivel Ventilaco

    Nivel Alarme

    Atraso Ventilaco

    Ventilaco ON

    Ventilaco ON

    Atraso Ps-ventilaco

    Ventilaco OFF

    Alarme ON

    Atraso Alarme

    Tempo

  • CCO122 / CCO222 / CCO322 / CCO422 PORTUGUS

    FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 20 -

    Figura 1. Ecr Ventilao Manual.

    Figura 2. Ecr Servio.

  • CCO122 / CCO222 / CCO322 / CCO422 PORTUGUS

    FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 21 -

    Figura 3. Ecr Programao de Ventilao.

    Figura 4. Ecr Programao Atraso de Alarmes.

    Figura 5. Ecr Recuperar Dados de Origem.

  • CCO122 / CCO222 / CCO322 / CCO422 PORTUGUS

    FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 22 -

    12V12V

    -

    +

    -

    +-

    Dupla ventilao e (OPCIONAL) baterias

    Dupla ventilao:

    No caso em que a central tm dupla ventilao a ligao deve ser feita como mostrado na figura.

    Os dados de origem so os seguintes:

    Parmetro Valor Margem

    Nvel de Ventilao 1: 50 ppm Programvel (20 150 ppm)

    Atraso Ventilao 1: 4 min Programvel (0 9 min)

    Atraso Ps-ventilao 1: 4 min Fixo Nvel de Ventilao 2: 120 ppm Programvel

    (20 200 ppm) e

    Nivel ventilaco 1 Atraso Ventilao 2: 10 min Programvel

    (0 30 min) e

    Atraso ventilaco 1 Atraso Ps-ventilao 2: 4 min Fixo Nivel de Alarme: 200 ppm Fixo Atraso Alarme: 0 min Programvel

    (0 30 min)

    Baterias: As baterias devem ligar-se entrada de

    baterias do circuito situado na parte direita do cofre, esta sada est identificada

    Ligao das duas baterias de 12 V em srie:

    Alar VentAlar Vent Zona2 Zona1

    + - + -+ +--Alar VentAlar Vent Zona2 Zona1

    + - + -+ +--

    Vent1 Z1

    Vent1 Z2

    Vent1 Z3( *Z1)

    Vent1 Z4( *Z2)

    61

    R2

    K1

    Q4

    D2D1D3

    R3

    K2

    Q3Q1

    R1

    K3

    R5

    K5

    R4

    1

    U5

    K4

    J4

    1

    U1

    Q5

    U3

    1

    U4

    1

    U2

    D4 D5

    Q2

    - +ALZ4Z3Z2Z1

    Vent2Z4

    - +

    J1

    GND CPU

    Vent2 Z2

    Vent2 Z3

    Vent2 Z1

    Vent2 Z4

    Bateras

    +-

    BAT

    Vent2Z2 Vent2Z3Vent2Z1

    Alarma Z4(*Z2)

    Alarma Z3(*Z1)

    Alarma Z2

    Alarma Z1

    No caso em que a central de 1 ou 2 zonas, siga com *

    Alarme OFF [CO]

    Nivel Ventilaco 2

    Atraso Ventilaco 1

    Ventilaco 1 ON

    Ventilaco1 ON

    Atraso Post-ventilaco 1

    Ventilaco1 OFF

    Alarme ON

    Atraso Alarme

    Tempo

    Nivel Alarme

    Atraso Ventilaco 2

    Ventilaco 2 ON

    Ventilaco 2 ON

    Atraso Post-ventilaco 2

    Ventilaco 2 OFF

    Nivel Ventilaco 1

  • CCO110 / CCO115 PORTUGUS

    FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 23 -

    CENTRALE CCO110 Y CCO115

    A Led verde: Indica que o sistema est operativo. B Led vermelho: Indica a activao do Rel de Alarme. C Led verde: Indica que se activou o Rel de Ventilao. D Led mbar: Indica que se superou o Nvel de Ventilao. E Led mbar: Indica uma avaria ou uma irregularidade na linha de deteco. F Led verde: Indica que o display mostra concentrao de CO (ppm). G Led verde: Indica que o display mostra o Nvel de Ventilao. H Led verde: Indica que o display mostra o Atraso de Ventilao.

    Botes de comando

    1. Seleco Display: Permite seleccionar o dado mostrado pelo diplay: Concentrao de Co, Nvel de Ventilao ou Atraso de Ventilao.

    2 e 3. Permitem aumentar ( ) ou diminuir ( ) os parmetros numricos. 4. ON/OFF Ventilao: Permite activar ou desactivar manualmente a ventilao a qualquer

    momento.

  • CCO110 / CCO115 PORTUGUS

    FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 24 -

    +-ZONA VENT.

    +-ALAR.

    +

    -

    +

    -

    +

    -

    +

    -

    +

    -

    +

    -

    ventilao

    Alarme

    Estructura por Zona

    +

    (CCO115 max 15)

    Detectores CO

    Manobra da central

    A central permite a programao do Nvel de Ventilao e do Atraso de Ventilao a travs das teclas

    , e SELECO DISPLAY.

    A tecla ON/OFF VENTILAO MANUAL permite activar/desactivar manualmente a ventilao a

    qualquer momento.

    Os dados de origen so os seguintes:

    Parmetro Valor Margem

    Nvel de Ventilao: 50 ppm Programvel (20 150 ppm) Atraso Ventilao: 4 min Programvel (1 9 min) Atraso Ps-ventilao: 4 min Fixo Nivel de Alarme: 300 ppm Fixo Atraso Alarme: 0 min Fixo

    Instalao

    A figura mostra o esquema geral de ligao dos diferentes elementos com a central.

    Pode ligar-se um mximo de 10 detectores por zona.

    Recomenda-se o uso de cabo com uma seco mnima de 1.5 mm2 e a longitude mxima do mesmo por

    zona no debe exceder os 400m, numa distribuio linear de detectores.

    Importante. Os detectores de Monxido de Carbono DCO tm polaridade.

    Alarme OFF [CO]

    Nivel Ventilaco

    Nivel Alarme

    Atraso Ventilaco

    Ventilaco ON

    Ventilaco ON

    Atraso Ps-ventilaco

    Ventilaco OFF

    Alarme ON

    Atraso Alarme

    Tempo

  • CCO110 / CCO115 PORTUGUS

    FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 25 -

    Dupla ventilao e baterias

    Dupla ventilao:

    No caso da central dispor de dupla ventilao, disporemos de duas sadas de ventilao.

    A primeira sada de ventilao est identificada como VENT1. A segunda ventilao est identificada como VENT2.

    O nvel de alarme tambm fica modificado nestas centrais a 200 ppm.

    Os dados de origen so os seguintes:

    Parmetro Valor Margem

    Nvel de Ventilao 1: 50 ppm Fixo Atraso Ventilao 1: 1 min Programvel

    (1 9 min)

    Atraso Ps-ventilao 1: 4 min Fixo Nvel de Ventilao 2: 100 ppm Fixo Atraso Ventilao 2: 0 min Fixo Atraso Ps-ventilao 2: 0 min Fixo Nivel de Alarme: 200 ppm Fixo Atraso Alarme: 0 min Fixo

    Baterias:

    As baterias devem ligar-se entrada de baterias do circuito situada na parte direita do circuito fonte de alimentao, esta sada est identificada.

    Ligao das duas baterias de 12 V em srie:

    12V12V

    -

    +

    -

    +-

    Alarme OFF [CO]

    Nivel Ventilaco 2

    Atraso Ventilaco 1

    Ventilaco 1 ON

    Ventilaco1 ON

    Atraso Post-ventilaco 1

    Ventilaco1 OFF

    Alarme ON

    Atraso Alarme

    Tempo

    Nivel Alarme

    Atraso Ventilaco 2

    Ventilaco 2 ON

    Ventilaco 2 ON

    Atraso Post-ventilaco 2

    Ventilaco 2 OFF

    Nivel Ventilaco 1

  • CCO122 / CCO222 / CCO322 / CCO422 CCO110 / CCO115

    FABRICANTE DE PRODUCTOS CONTRA INCENDIOS FIRE PROTECTION MANUFACTURER - FABRICANTE DE PRODUCTOS DE INCNDIO Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.

    Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com - 26 -

    NOTAS/NOTES/NOTAS

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

    .............................................................................................................

  • 18

    FABRICANTE DE PRODUCTOS CONTRA INCENDIOS - FIRE PROTECTION MANUFACTURE FABRICANTS DE PRODUITS CONTRE INCENDIES

    Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) SPAIN.

    Atencin Tcnico Comercial +34 902 448 811 [email protected] Technical & Commercial Service Ventas +34 935 862 690 [email protected] Sales Marketing +34 935 862 690 [email protected] Marketing S.A.T. +34 935 862 692 [email protected] T.A.S. Compras +34 935 862 693 [email protected] Purchase Export +34 935 862 694 [email protected] Export Fax pedidos +34 902 338 811 Orders Fax Fax general +34 936 999 261 Fax

    ABCDEF [Escriba una cita del documento o