STEAM (STM)
CONDENSATE (COND)
PROCESS CHILLED WATER (CHILL)
CONDITIONING (TREAT)
PROCESS COOLING WATER (COOL)CRITICAL CONTROL POINTI.D. #CB-COOL
`
CENTRAL UTILITY PROCESSING BUILDING
Reduced PressureBackflow Preventer
Double CheckDetector Backflow
Preventer
Fire Protection Supply
Reduced PressureBackflow Preventer
LakosSeparator
CoolingTower #2
CoolingTower #1
CoolingTower #3
CoolingTower #4
Cooling WaterTreatment
HeatExchanger
HV-1
HeatExchanger
HV-2
Chiller #4Chiller #3Chiller #2Chiller #1
Pump Pump Pump
Chilled Water SupplyFrom Hospital
Chilled WaterChemical Treatment
SecondaryPump
SecondaryPump
SecondaryPump
SecondaryPump
PrimaryPump
PrimaryPump
PrimaryPump
BoilerBoilerBoiler
Steam ToHospital
CondensateTreatment
CondensateTreatment
AlkalinityBuilder
Treatment
Condensate ReturnFrom Hospital
Deaerator
AlkalinityBuilder
TreatmentSurge Tank #2Surge Tank #1
AlkalinityBuilder
Treatment
Softener
Softener
Pump Pump PumpPump Pump Pump
Pump Pump PumpPumpPump
CONDENSATE RETURN
DOMESTIC COLD WATER SUPPLY
COOLING WATER RETURN
COOLING WATER SUPPLY
CHILLED WATER SUPPLY
CHILLED WATER RETURN
NON-POTABLE COLD WATER SUPPLY
PROCESS STEPS
RECEIVING (REC)1
FIRE PROTECTION SYSTEM (FP)2
DOMESTIC COLD WATERPOINT OF ENTRY (POE)CRITICAL CONTROL POINTI.D. #CB-POE
DOMESTIC COLD WATERPOINTS OF USE (POU)CRITICAL CONTROL POINTI.D. #CB-POU
3
4
LAWN IRRIGATION (IRR)CRITICAL CONTROL POINTI.D. #CB-IRR
5
C.U.P BuildingCity Water Main
City Water SupplyTo Tower Building
And C.U.P. Building
Lawn Irrigation
6
7
8
Reduced PressureBackflow Preventer
WASTE
11 Sanitary Sewer
9
10
CHILLED WATER SUPPLY PIPING
DOMESTIC COLD WATERSUPPLY PIPING
LEGEND
NON-POTABLE COLDWATER SUPPLY PIPING
CHILLED WATER RETURN PIPING
COOLING WATER SUPPLY PIPING
COOLING WATER RETURN PIPING
COOLING TOWERBASIN WATER
CONDENSATE RETURN PIPING
To Cooling Water/Cooling Towers
Chilled Water ReturnFrom Hospital
NON-POTABLE COLD WATER SUPPLY
© 2017 | HydroCorp | hydrocorpinc.com
SAMPLE W
ATER FLOW D
IAGRAM
`
`
DOMESTIC HOT WATERDISTRIBUTION SYSTEM (DHWS)CRITICAL CONTROL POINTI.D. #LC-DHWS
DOMESTIC COLD WATERPOINT OF ENTRY (POE)CRITICAL CONTROL POINTI.D. #LC-POE
LAUNDRY / CANCER
Lower Level
1ST FLOORCancer Center
FishTank
ReturnPump Water
Heater
North LaundryCity Water Riser
DetectorCheck Valve
Fire Protection Supply
PROCESS STEPS
1
2
FIRE PROTECTION SYSTEM (FP)
RECEIVING (REC)
City Water Supply
3
DOMESTIC COLD WATER SUPPLY
DOMESTIC COLD WATERPOINTS OF USE (POU)CRITICAL CONTROL POINTI.D. #LC-POU4
5
FISH TANK (FISH)CRITICAL CONTROL POINTI.D. #LC-FISH
6
DOMESTIC HOT WATERMAKE-UP (DHW) CRITICAL CONTROL POINTI.D. #LC-DHW7
WASTE
8 Sanitary Sewer
DOMESTIC HOT WATERRETURN PIPING
DOMESTIC COLD WATERSUPPLY PIPING
LEGEND
DOMESTIC HOT WATERSUPPLY PIPING
DOMESTIC HOT WATER SUPPLY
- Cancer patient rooms may contain sinks and toilets. Minimal showers (none in Cancer area per personnel) - associated with Laundry area only. Areas may contain ice machines (filtered), drinking fountains, janitor sinks with soap dispenser connections, and public restrooms.- One- (1) central 82 gallon electric domestic hot water heater located on ground floor,north end break room area. Recirculating system. - Fish tank located on 1st floor.- Floor highlighted RED may be considered to be high risk patient population area. Control measures may need to be modified accordingly.
© 2017 | HydroCorp | hydrocorpinc.com
SAMPLE W
ATER FLOW D
IAGRAM
`
DOMESTIC COLD WATERPOINTS OF USE (POU)CRITICAL CONTROL POINTI.D. #SB-POU
DOMESTIC HOT WATERDISTRIBUTION SYSTEM (DHWS)CRITICAL CONTROL POINTI.D. #SB-DHWS
PROCESS CHILLED WATER (CHILL)
PROCESS HOT WATERHEATING (PHW)
DOMESTIC HOT WATERMAKE-UP (DHW) CRITICAL CONTROL POINTI.D. #SB-DHW
DOMESTIC COLD WATERPOINT OF ENTRY (POE)CRITICAL CONTROL POINTI.D. #SB-POE
PROCESS STEPS
RECEIVING (REC)
FIRE PROTECTION SYSTEM (FP)
SOUTH BUILDING
1st FLOORCafé, Gift Shop, Radiology,
Patient Registration
2nd FLOORDialysis, Clinical Decision Unit,
Employee Health
3rd FLOOROB Special Care, Mother/
Baby Center
Automated EndoscopeReprocessors
4th FLOORCardiac Stepdown/Recovery Unit
5th FLOORPediatric Intensive Care
Children s Center
6th FLOORInpatient Rehabilitation
7th FLOORMed-Surg Pavilion, Medical
Intermediate Care Unit
8th FLOORMedical Short Stay Unit
(Unoccupied)
Penthouse
Lawn Irrigation
Process HotWater
Chilled Water
City Water SupplyTo/From Sample 1 & 2
BoosterPump
BoosterPump
LOWER LEVELChapel, Surgical Lounge, Surgical
Post OP
Reduced PressureBackflow Preventer
South Mechanical RoomCity Water Main
Fire Protection System
City Water Supply
Reduced Pressure DetectorBackflow Preventer
ReturnPump
ReturnPump
HeatExchanger #1
(Not in Se rvice)
HeatExchanger #2
Domestic HotWater Booster
Pump
Domestic HotWater Booster
Pump
Domestic Cold Water Supply
Do
me
stic
Ho
t W
ate
r R
etu
rn
Dom
estic
Ho
t Wat
er S
upp
ly
Domestic Cold Water Supply
Domestic Hot Water ReturnD
omes
tic C
old
Wat
er S
uppl
y
Domestic Hot Water Supply
1
2
DOMESTIC HOT WATERRETURN PIPING
DOMESTIC COLD WATERSUPPLY PIPING
LEGEND
DOMESTIC HOT WATERSUPPLY PIPING
3
4
LAWN IRRIGATION (IRR)CRITICAL CONTROL POINTI.D. #SB-IRR
5
6
7
8
9
AUTOMATED ENDOSCOPEREPROCESSORS (AER)CRITICAL CONTROL POINTI.D. #SB-AER
10
WASTE
11 Sanitary Sewer
- South patient rooms contain sinks, toilets and showers (many with hose and wand). Most floors contain nurse stations with ice machines (filtered). Floors may generally contain eyewashes, drinking fountains, janitor sinks with soap dispenser connections, bed pan washers and public restrooms.- Two- (2) central heat exchangers located in Lower Level Mechanical Room supply domestic hot water to various areas of South Building; one- (1) unit is out of service/backup. Dead leg piping associated with backup unit. - Note not all domestic hot water booster pumps anddomestic hot water return pumps are active - some units are backup.- 8th floor currently not occupied. Control measures may need to be modified accordingly.- Floors highlighted RED may be considered to be high risk patient population areas. Control measures may need to be modified accordingly.
© 2017 | HydroCorp | hydrocorpinc.com
SAMPLE W
ATER FLOW D
IAGRAM
`
`
TOWER
City Water Supply
Fish Tank
Fish Tank
Booster Pump
Booster Pump
Expansion Tank
South CityWater Main
Reduced PressureBackflow Preventer
Fire Protection Supply
Double CheckDetector Backflow
Preventer
City Water SupplyFrom Tower North
(CUP Building)
Heat Exchanger
#3
Heat Exchanger
#2
Return
Pump
#1
Return
Pump
#2
Lawn Irrigation
Chilled Water
Process Hot Water
LOWER LEVELPre-Operative Surgery
1st FLOORMain Lobby, Parking Ramp
2nd FLOORMechanical Room
3rd FLOORCardiac Intensive Care
4th FLOORHeart and Vascular Center
5th FLOORMedical Oncology
6th FLOOROrthopedics
7th FLOORSurgical Med. Unit, Critical Care
8th FLOORPFT Lab, Respiratory Therapy
9th FLOORNeurophysiology
10th FLOOR Neuro ICU, Neuro Stepdown
Heat Exchanger #1
(Back-up Only)
PROCESS STEPS
DOMESTIC HOT WATERRETURN PIPING
DOMESTIC COLD WATERSUPPLY PIPING
LEGEND
DOMESTIC HOT WATERSUPPLY PIPINGRECEIVING (REC)
1
FIRE PROTECTION SYSTEM (FP)
2
3
DOMESTIC COLD WATERPOINT OF ENTRY (POE)CRITICAL CONTROL POINTI.D. #TOW-POE
LAWN IRRIGATION (IRR)CRITICAL CONTROL POINTI.D. #TOW-IRR4
PROCESS CHILLED WATER (CHILL)5
PROCESS HOT WATERHEATING (PHW)
6
Heat Exchanger
#4
Return
Pump
#3
DOMESTIC HOT WATERMAKE-UP (DHW) CRITICAL CONTROL POINTI.D. #TOW-DHW7
DOMESTIC HOT WATERDISTRIBUTION SYSTEM (DHWS)CRITICAL CONTROL POINTI.D. #TOW-DHWS
8
DOMESTIC COLD WATERPOINTS OF USE (POU)CRITICAL CONTROL POINTI.D. #TOW-POU
9
FISH TANK (FISH)CRITICAL CONTROL POINTI.D. #TOW-FISH
10
FISH TANK (FISH)CRITICAL CONTROL POINTI.D. #TOW-FISH
WASTE
11 Sanitary Sewer
Dom
estic
Ho
t Wat
er R
etur
n
Dom
estic
Ho
t Wat
er R
etur
n
Dom
estic
Col
d W
ater
Sup
ply
Dom
estic
Col
d W
ater
Sup
ply
Domestic Cold Water Supply
Domestic Hot Water Supply
- Tower patient rooms contain sinks, toilets and showers(many with hose and wand). Most floors contain nursestations with ice machines (filtered). Floors may generallycontain eyewashes, drinking fountains, janitor sinks with soapdispenser connections, bed pan washers and publicrestrooms.- Four- (4) central heat exchangers located in 2nd floorMechanical Room supply domestic hot water to various areasof Tower Building; one- (1) unit is out of service/backup. Deadleg piping associated with backup unit.- Fish tanks located on 3rd and 10th floors.- Floors highlighted RED may be considered to be high risk patient population areas. Control measures may need to bemodified accordingly.
© 2017 | HydroCorp | hydrocorpinc.com
SAMPLE W
ATER FLOW D
IAGRAM
`
DOMESTIC HOT WATERMAKE-UP (DHW)CRITICAL CONTROL POINTI.D. #N-DHW(SAMPLE 1, 5-7 FLOORS)
`
FIRE PROTECTION SYSTEM (FP)
SAMPLE 2 POSTSAMPLE 1
4th FLOORPediatric Outpatient Services
3rd FLOOREmergency Med. Residency
Program
Dialysis Make-up
1ST FLOORMicrobiology/Pathology
LOWER LEVELCafeteria Operations/Offices
Fire Protection Supply
Double CheckDetector Backflow
Preventer
City Water Supply
North Meter RoomCity Water Main
Reduced PressureBackflow Preventer
Pump PumpPump
ReturnPumps
#3 and #4
ReturnPumps
#1 and #2
HeatExchanger
#1
LOWER LEVELChapel, Sur. Lounge, Surg. Post-OP
1st FLOORRadiology, Pharmacy, Café
2nd FLOORInpatient Dialysis, Clin. Decision
Unit
3rd FLOOROB Special Care, Endoscopy
4th FLOORCardiac Stepdown/Recovery Unit
5th FLOORPediatric Intensive Care,
Children s Center
6th FLOORInpatient Rehab
7th FLOORMed-Surg Pavilion, Med. Intensive
Care Unit
Central SterileProcessing
LOWER LEVELChapel, Sur. Lounge, Surg. Post-OP
1st FLOORRadiology, Pharmacy, Café
2nd FLOORInpatient Dialysis, Clin. Decision
Unit
6th FLOORInpatient Rehab
7th FLOORMed-Surg Pavilion, Med. Intensive
Care Unit
Mixing Valve(Cold Supply
Off)
Tempered DomesticHot Water SupplyTo 5th, 6th and 7th
Floors
DOMESTIC HOT WATER SUPPLY
DOMESTIC HOT WATER SUPPLY
DOMESTIC HOT WATER RETURN
DOMESTIC COLD WATER SUPPLY
DOMESTIC HOT WATER RETURN
DO
MES
TIC
HO
T W
ATE
R R
ETU
RN
DO
MES
TIC
HO
T W
ATE
R R
ETU
RN
DO
MES
TIC
HO
T W
ATE
R S
UPP
LY
DOMESTIC HOT WATERRETURN PIPING
DOMESTIC COLD WATERSUPPLY PIPING
LEGEND
DOMESTIC HOT WATERSUPPLY PIPING
City Water SupplyTo/From South Building
PROCESS STEPS SAMPLE 1, SAMPLE 2 & POST
RECEIVING (REC)
1
2
DOMESTIC COLD WATERPOINT OF ENTRY (POE)CRITICAL CONTROL POINTI.D. #NFP-POE
3
DOMESTIC COLD WATERPOINTS OF USE (POU)CRITICAL CONTROL POINTI.D. #NFP-POU
4
DOMESTIC HOT WATERMAKE-UP (DHW) CRITICAL CONTROL POINTI.D. #NFP-DHW(BUILDING)
6
PROCESS HOT WATERHEATING (PHW)7
DIALYSIS MAKE-UP (DIAL)8
PROCESS CHILLED WATER (CHILL)9
DOMESTIC HOT WATERDISTRIBUTION SYSTEM (DHWS)CRITICAL CONTROL POINTI.D. #NFP-DHWS(BUILDING)
10
DOMESTIC HOT WATER SUPPLY
DOMESTIC HOT WATERDISTRIBUTION SYSTEM (DHWS)CRITICAL CONTROL POINTI.D. #N-DHWS(SAMPLE 1, 5-7 FLOORS)11
DO
MES
TIC
COLD
WA
TER
SUPP
LY
DOMESTIC HOT WATER RETURN
3rd FLOOROB Special Care, Endoscopy
4th FLOORCardiac Stepdown/Recovery Unit
5th FLOORPediatric Intensive Care,
Children s Center
HeatExchanger #2
HeatExchanger #1(Not in use)12
PROCESS HOT WATERHEATING (PHW)
13
Process Hot Water
WASTE
14 Sanitary Sewer
CENTRAL STERILE PROCESSING (CSP)
5
City Water SupplyTo/From Tower Building
Domestic Hot WaterSupply and Return to
Connector Restrooms Floors 5-8
ReturnPump
2nd FLOORRadiology Administration/Offices
HeatExchanger
#2
Process Hot Water
Chilled Water
- Sample 1 and Sample 2 patient rooms contain sinks, toilets and showers (many with hose and wand). Mostfloors contain nurse stations with ice machines (filtered). Floors may generally contain eyewashes, drinkingfountains, janitor sinks with soap dispenser connections, bed pan washers and public restrooms.- Two- (2) central heat exchangers located in 2nd floor Mechanical Room/Sample 1 both supply domestic hotwater to Sample 1, 2 and Post. Note that on the 6th floor of Sample 1 (Mechanical Room), there are two- (2) heatexchangers supplying domestic hot water to floors 5 through 7 (Sample1), one- (1) of which is out of service/backup. The one- (1) active heat exchanger supplies domestic hot water directly to floors 5 through 7, and alsosupplies domestic hot water to a master mixing valve. The potable cold water supply to the mixing valve isclosed, suggesting domestic hot water downstream is not being tempered Some sinks downstream of this 6th
floor heat exchanger system may be electronic hands free with cold supplies not connected (suggesting dead legsin potable cold system).
- Floors highlighted RED may be considered to be high risk patient population areas. Control measures may needto be modified accordingly.
© 2017 | HydroCorp | hydrocorpinc.com
SAMPLE W
ATER FLOW D
IAGRAM