1
CERTIFICATE OF SEISMIC COMPLIANCE This is to signify that Stored Energy Systems (SENS) 1840 Industrial Circle Longmont, CO 80501 has tested the following product per the referenced test standard, and passed functionality requirements: Microgenius S2 & S4 Scope of Certification: Product Type: Battery Chargers Mfg Series/Make: Microgenius Mfg Model: S2, S4 Mounting: Rigid/Isolated wall Mounted Public Report No: P22987-Trans-01 Codes and Standards: IBC 2009, 2012, 2015, 2018 ASCE 7-05, 7-10, 7-16 ICCES AC-156-2015 Maximum Design Loads: S DS (g)= 2.5 Ip= 1.5 Fp/Wp= 1.88 z/h= 1.0 Weight(lbs)= 32 A FLXH = 3.2 Dimensions: 14.25x16.5x10.44 A FLXV = 1.68 Notes: Certification valid for testing compliance of units in scope. Equipment must be installed, mounted, seismically braced and anchored per mfg instructions. Equipment must only be used as intended. Certification verifies that representative product line units have been shake tested per referenced codes and standards and confirmed to function after the test. Certificate does not guarantee the equipment will remain compliant to other standards (i.e. ETL,UL, etc.) after a seismic event. See Public Report for complete explanation of qualification, limits, and requirements. Certificate No.: SN01-COC-1801 Certificate date: May 25, 2018 Expires: May 25, 2019 ____________________________________ Robert E Simmons, PE, CEO Seismic Source International, LLC / 14525 FM 529, Suite 205, Houston TX 77095 / 281.656.1439 / www.seismic-source.com Test Lab: ETL, Dallas, TX Qualification Agency: Petra Seismic Design

CERTIFICATE OF SEISMIC COMPLIANCE Stored Energy Systems …… · Certificate does not guarantee the equipment will remain compliant to other standards (i.e. ETL,UL, etc.) after a

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: CERTIFICATE OF SEISMIC COMPLIANCE Stored Energy Systems …… · Certificate does not guarantee the equipment will remain compliant to other standards (i.e. ETL,UL, etc.) after a

CERTIFICATE OF SEISMIC COMPLIANCE

This is to signify that

Stored Energy Systems (SENS)1840 Industrial CircleLongmont, CO 80501

has tested the following product per the referenced test standard, and passed functionality requirements:Microgenius S2 & S4

Scope of Certification:Product Type: Battery Chargers Mfg Series/Make: MicrogeniusMfg Model: S2, S4Mounting: Rigid/Isolated wall MountedPublic Report No: P22987-Trans-01

Codes and Standards:IBC 2009, 2012, 2015, 2018ASCE 7-05, 7-10, 7-16 ICCES AC-156-2015

Maximum Design Loads:SDS(g)= 2.5 Ip= 1.5Fp/Wp= 1.88 z/h= 1.0 Weight(lbs)= 32 AFLXH= 3.2Dimensions: 14.25x16.5x10.44 AFLXV= 1.68

Notes:Certification valid for testing compliance of units in scope. Equipment must be installed, mounted, seismically braced and anchored per mfg instructions. Equipment must only be usedas intended. Certification verifies that representative product line units have been shake tested per referenced codes and standards and confirmed to function after the test. Certificatedoes not guarantee the equipment will remain compliant to other standards (i.e. ETL,UL, etc.) after a seismic event. See Public Report for complete explanation of qualification, limits,and requirements.

Certificate No.: SN01-COC-1801Certificate date: May 25, 2018 Expires: May 25, 2019

____________________________________Robert E Simmons, PE, CEO

Seismic Source International, LLC / 14525 FM 529, Suite 205, Houston TX 77095 / 281.656.1439 / www.seismic-source.com

Test Lab: ETL, Dallas, TX Qualification Agency: Petra Seismic Design