Ch -10 Air Condition Systemxxx

Embed Size (px)

Citation preview

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    1/48

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    2/48

    Definition

    AirConditioner

    Types

    Central UnitUnitary Systems

    Remote Split

    Operation

    IEE regulations

    Installation &Wiring

    Maintenance &Troubleshooting

    http://opt/scribd/conversion/tmp/scratch2313/slide3.xmlhttp://opt/scribd/conversion/tmp/scratch2313/slide4.xmlhttp://opt/scribd/conversion/tmp/scratch2313/slide6.xmlhttp://opt/scribd/conversion/tmp/scratch2313/slide7.xmlhttp://opt/scribd/conversion/tmp/scratch2313/slide20.xmlhttp://opt/scribd/conversion/tmp/scratch2313/slide46.xmlhttp://opt/scribd/conversion/tmp/scratch2313/slide46.xmlhttp://opt/scribd/conversion/tmp/scratch2313/slide20.xmlhttp://opt/scribd/conversion/tmp/scratch2313/slide7.xmlhttp://opt/scribd/conversion/tmp/scratch2313/slide6.xmlhttp://opt/scribd/conversion/tmp/scratch2313/slide4.xmlhttp://opt/scribd/conversion/tmp/scratch2313/slide3.xml
  • 8/14/2019 Ch -10 Air Condition Systemxxx

    3/48

    Definition : simultaneous mechanical control oftemperature, humidity, air purity & air motion. It

    include the process of extracting the warm &dirty atmosphere from enclosed area thatcombine the use of air filter & refrigeration plant.

    Why do we need Air Cond?- To improve the control of industrial process.

    - To maintain human comfort

    - Hospital operating Suites - reduceinfection risk and humidity controll.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    4/48

    Types of domestic air conditioning

    1.Central Unit Systems

    - Compressor, condenser,evaporators and expansion valve isplaced in one close location & the

    cooling tower is located outside of it .- Cool air is piped out from

    evaporators in air monitoring room tothe space to be air conditioned. Thissystem is used at hotels, shoppingcomplex and big building

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    5/48

    Click to edit Master text stylesSecond level

    Third level

    Fourth level Fifth level

    Central Unit Systems

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    6/48

    2.Unitary Systems

    - In this system, factory assembled airconditioners are installed in oradjacent to the space to beconditioned. The unitary airconditioning systems are either self-contained system such as window

    units and packed units, or remotesplit systems.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    7/48

    3.Remote Split System

    These systems are in more common use in theresidential and small commercial installations.

    They have the evaporator, blower and furnacelocated in a closet in an equipment room withcondensing unit.

    The refrigerant is piped from the condensing unit

    to the indoor coil through copper tubing. The airis ducted from the air conditioning equipmentto the space to be conditioned.

    Most residential units have the indoor section

    centrally located within the space, whicheliminates the need for a return air ductsystem.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    8/48

    Unitary Systems

    SelfContainedSystem

    Air-

    cooledsystems

    Water-

    cooledsystems

    Window Units

    Packed

    Units

    WaterCooled

    AirCooled

    Remote Split System

    http://opt/scribd/conversion/tmp/scratch2313/slide9.xmlhttp://opt/scribd/conversion/tmp/scratch2313/slide9.xmlhttp://opt/scribd/conversion/tmp/scratch2313/slide11.xmlhttp://opt/scribd/conversion/tmp/scratch2313/slide11.xmlhttp://opt/scribd/conversion/tmp/scratch2313/slide11.xmlhttp://opt/scribd/conversion/tmp/scratch2313/slide9.xml
  • 8/14/2019 Ch -10 Air Condition Systemxxx

    9/48

    Window unit Advantages

    1. Separate temperature control foreach unit in an enclosed area.

    2. No need of Air tubing. Reduce cost.

    3. Piping work is no need.

    4. Easy installation but unremovable.

    Window unit Disadvantages

    1.

    Need special area at the window.2. Air quantity decide by the factory.

    3. Unit installed at the wall. So needto break the wall structure.

    4. If failure occur, it is not easy tobring the unit down individually.

    Click to edit Master text styles

    Second level Third level

    Fourth level Fifth level

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    10/48

    Window unit Advantages

    1. Sebuah bilik menggunakan sebuahunit penyamanan udara yangmengawal suhu secara berasingan.

    2.

    Salur udara tidak diperlukan.Menjimatkan kos.

    3. Kerja pempaipan tidak perlu.

    4. Pemasangan adalah mudah tetapipemasangan kekal (tidak boleh ubah)

    Window unit Disadvantages

    1. Memerlukan ruang tertentu padasesebuah tingkap.

    2. Kuantiti udara biasanya ditentukanoleh pengeluar.

    3. Unit dipasang didinding, jadi dindingterpaksa dipecahkan.

    4. Sekiranya berlaku kerosakan, sukarmenurunkan unit secaraberseorangan.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    11/48

    Remote Split System Advantages

    1. No need of air feeder.

    2. No need of water piping work.

    3. Easy installation.4. Suitable for user that desire to

    install heater & conditioner athome.

    Remote Split System

    Disadvantages

    1. Difficult to do maintenance iffailure occurred.

    2. Have indoor and outdoor unit.

    3. Need speacial space.4. Installation cost is expensive.

    Click to edit Master text styles

    Second level Third level

    Fourth level Fifth level

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    12/48

    Split unit air conditioner system that separate theevaporator and condensor unit.

    This unit divided to TWO are :-Indoor and Outdoor unit.

    Indoor unit installed in the room while the outdoorunit installed

    There are 3 types of Split Unit air conditioner :-

    Wall type (Lekapan dinding) Cassette type (Lekapan lantai) Ceiling type (Gantungan siling)

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    13/48

    Air Conditioning System Basics andTheories

    Most central air conditioning unitsoperate by means of a split system.

    1.Hot sideconsist of condensing coil,

    compressor & fan located o/sideroom.

    2.Cold sideconsist of expansion

    valve & cold air (part of furnace/ airhandler) located inside the room.Furnace blow air through evaporatorcoil which cooled the air.DIAGRAM

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    14/48

    The refrigeration cycle:1) condensing coil,2) expansion valve,3) evaporator coil,4) compressor

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    15/48

    Air cond have 5 mechanical components :

    i. Compressor

    ii. Expansion valve / metering device

    iii. Evaporator coil / Condensor

    iv. Blower

    v. Refrigerant

    DIAGRAM

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    16/48

    Click to edit Master text stylesSecond level

    Third level Fourth level

    Fifth level

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    17/48

    Compressor (heart)

    Refrigeration cycle uses an electric motor

    to drive a compressor.Act as a pump causing the refrigerant to flowthrough the system.

    Contain 2 type of feeder : 1. Suction line

    2. Discharge line

    Its job is to draw in a low pressure, low temprefrigerant in a gaseous state & by compressingthis gas, raise the pressure & temp of therefrigerant.

    The high pressure, high temp gas then flows to

    the condensor coil.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    18/48

    Condensor

    The condensor coil is a series of piping with a

    fan that draws o/side air across the coil.As the refrigerant passes through thecondensor coil & the cooler o/side air passesacross the coil, the air absorbs heat from the

    refrigerant which causes the refrigerant tocondense from a gas to a liquid state.

    The high pressure, high temp liquid then

    reaches the expansion valve.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    19/48

    Expansion valve (brain) By sensing the temp of the evaporator/

    cooling coil,

    it allows liquid to pass through a verysmall orifice which causes the refrigerantto expand to a low pressure & low tempgas.

    This cold refrigerant flows to the

    evaporator.

    Evaporator Coil A series of piping connected to a furnace

    @ air handler that blows indoor air acrossit causing the coil to absorb heat from theair.

    Absorb heat & change refrigerant in liquidstate (low temp/ pressure) to a gas (low

    temp/ pressure).

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    20/48

    Operation

    A compressor is a pump that compressrefrigerant vapor & pumps the refrigerantthrough the refrigeration system.

    The compressed refrigerant moves to thecondensor through the discharge linewhere heat is rejected & the vapor iscondensed into a liquid.

    From the condenser the refrigerant ispumped to the metering device where the

    amount of the refrigerant moving into theevaporator is controlled.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    21/48

    The metering device causes part of therefrigerant to vaporize as it moves into the

    evaporator & the pressure & temperatureare greatly reduced.

    This reduction in pressure causes a severelowering in temp. inside the evaporator.

    The evaporator absorbs heat from thesurrounding air which cools the air.

    The vapor proceeds through the suction lineto the compressor where it is compressed &the cycle starts over.

    S ifi ti

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    22/48

    SpecificationPlaces

    RatingDrugstore Beauty Saloon Doctors office

    Voltage 208V, 3 , 3 wire,

    60Hz

    208V, 3 , 3 wire,

    60Hz

    208V, 3 , 2 wire,

    60Hz

    Refrigerantcompressor-

    motor

    Rated load current20.2A, 208V 3

    Rated loadcurrent 14.1A,

    208V3

    Rated loadcurrent 16.8A,

    208V3

    Evaporator motorFull load current3.2A, 208V 1

    Full load current3.3A, 208V

    1

    Full load current3.7A, 208V

    1

    Condensermotor

    Full load current3.2A, 208V 1

    Full load current3.3A, 208V

    1

    Full load current3.7A, 208V

    1

    Minimum cctcapacity

    31.65A 20.92A 24.7A

    Over protection

    current

    50A, time delay

    fuse

    35A, time delay

    fuse

    40A, time delay

    fuse

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    23/48

    3-Selit hos akhir untukpenyambung (tertutup) Paip

    BahanPaipOksigen

    1- Buka penutup yang melindungisambungan oksigen

    2-Selit hos akhir untuk penyambung (luar)

    Installation & Wiring

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    24/48

    Air Conditioning System Basics and Theories

    The refrigeration cycle:

    1) condensing coil,2) expansion valve,3) evaporator coil,4) compressor

    Heat pump transfers heat from a lower temperature heatsource into a higher temperature heat sink. Heat would

    naturally flow in the opposite direction. A refrigerator pumps the heat out of the interior into theroom in which it stands.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    25/48

    Refrigeration cycle uses an electric motor to drive acompressor.

    Since evaporation occurs when heat is absorbed, and

    condensation occurs when heat is released, airconditioners are designed to use a compressor tocause pressure changes between two compartments,and actively pump a refrigerant around.

    A refrigerant is pumped into the cooled compartment

    (the evaporator coil), where the low pressure and loadtemperature cause the refrigerant to evaporate into avapor, taking heat with it.

    In the other compartment (the condenser), the

    refrigerant vapour is compressed and forced throughanother heat exchange coil, condensing into a liquid,rejecting the heat previously absorbed from the cooledspace.

    Refrigerant cycle 1

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    26/48

    Refrigerant cycle 1

    Pemampat akan memampatkan wap bahan dingin ygbertekanan/ suhu rendah menjadi wap bahan dingin ygbertekanan/ suhu tinggi & dialirkan ke pemeluwapan melalui

    discharge line.

    Pemeluwap haba yg disingkirkan lalu wap bahan dingin ygbertekanan/ bersuhu tinggi menjadi cecair bahan dingin ygbertekanan/ bersuhu tinggi & dialirkan ke peranti pemeteranmelalui liquid line.

    Peranti pemeteran Cecair bahan pendingin yg bertekanan/bersuhu tinggi akan dikawal pengalirannya lalu menjadi cecairbahan dingin yg bertekanan/ bersuhu rendah & dialirkan kepenyejat melalui evaporator line.

    Penyejat Haba diserap lalu cecair bahan dingin ygbertekanan bersuhu rendah menjadi wap bahan dingin ygbertekanan/ suhu rendah & masuk ke pemampat melaluisuction line.

    Seterusnya proses ini berulang semula.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    27/48

    Refrigerant cycle 2

    Satu proses mengalihkan haba dari satu

    tempat ke tempat yg lain.Haba dialih melalui unit penyejat dandisingkirkan ke udara luar pd unitpemeluwap bg setiap jenis alat pendinginudara.

    Dlm proses pemindahan haba, 4 pekara inidiperlukan dlm kitaran tsbt iaitupemeluwap, pemampat, pemejalwapandan injap pengembagan dan menjadibahan pendingin.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    28/48

    Condensation

    (pemeluwap)

    Compressor

    Evaporation

    (penyejat)

    Txv ( meter equipment)

    Low pressure /

    Low Side

    High pressure /

    High Side

    Dust

    Refrigerant (Freon 11 Freon 12 Freon 22)

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    29/48

    Refrigerant (Freon-11, Freon-12, Freon-22)

    Refrigerant are designated with an R & a number.

    The refrigerant must be safe, detectable, have low boiling

    point & have good pumping characteristics.Freon - These refrigerants used due to the superiorstability and safety properties. Unfortunately, evidencehas accumulated that these chlorine bearing refrigerantsreach the upper atmosphere when they escape.

    CFC refrigerants in common but receeding usage includeR-11 and R-12.

    Environmentally-safe refrigerants include HCFCs (R-22,used in homes) & HFCs (R-134a, used in cars) have

    replaced CFC use.HCFCs in turn are being phased out under the MontrealProtocol and replaced by hydrofluorocarbons (HFCs),such as R-410A, which lack chlorine.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    30/48

    D O L

    OUTDOOR UNITINDOOR UNIT

    L

    E

    N

    C(A)

    SR(P)

    AC

    S

    CM

    CFM

    L

    RC

    SPEEDCONTROL

    RECEIVER POWER SUPPLY

    TIMER

    TEMPERATURECONTROL

    TRANSMITTER

    L

    LC

    E

    N

    RELAY

    MOTORA/C

    Indoor Unit

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    31/48

    Indoor UnitPower Supply - Convert AC -> DC

    - Step down voltage

    - Distribute voltage

    Receiver Cct - Receive instruction from user via remote control

    Timer - Every line must pass through the timer.

    - Timer is for delay

    - Setting time for ON/OFF

    Speed Control - Instruction in voltage signalRelay - Voltage from speed control send to the relay

    - Relay On, voltage supply enter & start themotor.

    Negative Thermistor (NTC)

    positioned at the evaporator inlet side. - NTC Temp. low , resistance increase (cold)

    - PTC Temp. high, resistance increase (hot)

    - suitable temp. in Malaysia 21C humidity 55%

    Outdoor Unit

    Overload Relay - When overload occurred, relay will open.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    32/48

    Direct On Line (D.O.L.)Function For overload protection.

    Load below 7.46W / 1Hp no need to use DOLFuse to open when O/L occur

    Thermal O/L Relay (TOR) Trip when thermal notnormal condition

    PB start To start the cct.

    PB Stop To stop the cct.

    When push PB start button, Motor Contactor (MC) will beNormally Close, motor coil will get the power supply andthe Motor will operate.

    Click to edit Master text styles

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    33/48

    Click to edit Master text stylesSecond level

    Third level Fourth level

    Fifth level

    Direct On Line (D.O.L.)

    Click to edit Master text styles

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    34/48

    Click to edit Master text stylesSecond level

    Third level Fourth level

    Fifth level

    Control circuit for Star - Delta

    Click to edit Master text styles

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    35/48

    Click to edit Master text stylesSecond level

    Third level Fourth level

    Fifth level

    Star - Delta Power Circuit

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    36/48

    Star - Delta Connection

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    37/48

    Star Delta Cct operation

    Power cct for motor operation need Star - Delta cctto get a smooth start.

    To start the motor, the torque power need to be high.

    So, for starting time, its use Star cct because whenthe magnet flux is high, the power torque high.

    The connection to Star cct is in 3 ~ 5 sec.

    Then after 5 sec @ the motor operate, the Delta cctwill operate for motor running time.

    This type of connection is used to operates loadbelow 5 Hp ~ 20 Hp.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    38/48

    Notes : Operate load between 20 Hp ~ 100 Hp

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    39/48

    Maintenance & TroubleshootingThe system has an effect on the amount of energy

    that is used & the amount of money that is spent eachmonth.

    Air cond also have influence to an individual throughthe air quality.

    Nowadays, split unit system is the most popular type that are

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    40/48

    Nowadays, split unit system is the most popular type that arechoose by the customer.

    Besaide it is operating quietly, it is also built in with an optionalfunction like the ironnizer. There is 4 maintenance task that need

    to be implement to makesure the airconditioner operates followthe specification.

    1. Filter cleaning Filter is take out from the cover and clean byusing water. Dry the filter before assemble it again.

    2. Evaporater cleaning Clean the evaporator (cooling coil)from dust by using vacuum.

    3. Water duct cleaning Clean the water duct that feed waterout from evaporator to avoid water jelly by using air blower.

    4.

    Condensor checking Makesure the aluminium fin is notblock with the area that is near to each other.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    41/48

    An air conditioning system should be checked twiceeach year by a qualified person. An inspection typicallyincludes :

    1. Checking system functions & safety controls &adjusting the operating sequence where appropriate.

    2. Make an inspection to an electrical components &connections & repairing/ replacing @ tightening asrequired. i.e checking the contactor, check capacitor.

    3. Ensuring proper airflow & changing dirty air filters.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    42/48

    4. Inspecting pumps & checking flow rates whereappropriate.

    5. Cleaning & lubricating motors are required.

    6. Examining belts, and adjusting & aligning asrequired.

    7. Inspecting, cleaning & balancing blowers asrequired.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    43/48

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    44/48

    Maintenance Record (Maintenance schedule for 25 to 50hours or months)

    This schedule consist of checking method that need to

    be done in every 25 to 50 hours or per month to any air

    conditioner. The process that will be implement and

    record in the monthly schedule is :-

    Refill the gaseous and check the gas pressure.

    Check the blower ( Fan )

    Check the cool water and makesure it is a pure water

    B l h d l h th l f i t h d l f 25

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    45/48

    Subject Date Type of failure Action taken

    1 Gas/

    Refrigerant

    30.1.2007 Air not cool Check refrigerant pressure

    Add refrigerant gas if itsbelow requirement level

    2 Cooling tower 30.1.2007 Water coolen lessTower dirty

    Check water coolant( added when lesser water

    coolant). Clean reservoir3m/6m. Replace with watermixed with chlorine.

    3 Blower (Fan) 30.1.2007 Fan dirtyRotation of the fan istoo rigorousThe filter is dirty

    Clean the fan from dust. Grisshould be done.Clean filter.

    4 Cooled Water 30.1.2007 Water mixed a lotwith impurety

    Need the water pure.

    Below schedule show the example of maintenance schedule for 25to 50 hours or permonth.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    46/48

    Institute of Electrical Engineering (IEE)Laws

    Always wear googles when working with refrigerant in these

    systems. Always wear googles around ductwork to prevent cutting the

    hands and fingers. Provide protective shields around operating motor & fans.

    Be sure that the electric power is off before servicing

    electrical components. Keep hand, feet & clothing clears of belts, fans & ratating

    parts. Use only safe ladders when working on the roofs of building.

    Never carry equipment , tools @ supplies up @ down aladder. Transport these items with a rope of buildings.

    Avoid contact with electric circuits when the area around theequipment is wet.

    Unit should firmly fixed at a place that have a set that

    endurable to carry heavy thing.

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    47/48

    3-Selit hos akhir untukpenyambung

    (tertutup) Paip

    BahanPaipOksigen

    1- Buka penutup yangmelindungi sambungan

    oksigen2-Selit hos akhir

    untuk penyambung(luar)

  • 8/14/2019 Ch -10 Air Condition Systemxxx

    48/48

    Assignment 2

    1. Explain the method of operation for each type of

    below unitary system & give 3 advantages and

    disadvantages for each unit type :

    a. Window unit

    b. Remote Split System Lekapan dinding

    c. Remote Split System Lekapan lantai

    d. Remote Split System Lekapan ceiling

    e. Self Contained System - Water-cooled systems

    f. Self Contained System - Air-cooled systems

    g. Packed Units - Water Cooled

    h. Packed Units - Air Cooled

    2. Give 3 IEE Regulation that relates to air cond system.