Upload
cyong7788
View
223
Download
0
Embed Size (px)
Citation preview
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 1/46
7-1
Chapter 7Cable Testing Fundamentals
Contents
• Testing Twisted Pair Cables
•
Wire Map Test
• Wire Length Test
• DC Resistance Test
• NEXT, ELFEXT, and Power Sum Test
• Attenuation Test
• Return Loss Test
• Impedance Test
• Delay and Skew Test
• Capacitance Test
• ACR and Power Sum ACR Test
• Headroom Test
• Testing and Troubleshooting 10Base-T Cabling
• Testing and Troubleshooting Nexans Cabling System
• Testing and Troubleshooting with a Block Connector System
• Testing and Troubleshooting Coax Cabling
• Testing and Troubleshooting Fiber Optics
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 2/46
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 3/46
Chapter 7Cable Testing Fundamentals
7-3
Table 7-1: Twisted Pair Cable Types and Associated Networks
Cable Type Network ExamplesTIA Cat 3, 5e, 6 UTP or STP and 7 STP Ethernet, Fast Ethernet, ATM, and Gigabit
Ethernet
ISO Class C, D, E and F UTP or STP Ethernet, Fast Ethernet, ATM
TP-PMD / TP-DDI FDDI or ATM on Copper
10Base-T Ethernet
Single Pair Telephone, Apple Local Talk, ISDN
Shielded Two-Pair (1,2,7,8) ATM, Fiber Channel on Copper
Shielded Twisted Pair (STP)
Testing the continuity of the shield is important and requires shielded test leads at
both the Display Handset and Remote Handset. When testing STP, be sure to
select Shielded Cable Type (STP) in the Cable Type menu.
Twists are maintained to within ½”as required per TIA Category 5e insulation guidelines
Screened Category 5e Cable(ScTP)
Metallic shield provides EMIprotection
Figure 7-2: Shield Continuity Test Connections Twisted Pair
USOC Wiring
If a USOC (Universal Service Ordering Code) or other wiring scheme is used, a
special adapter may be required for connection. Refer to Appendix D, Model
Accessories for a full list of available cable adapters.Note: If your testing requirements include connection to something other than an RJ-45
or Tera style jack, refer to Testing with Block Adapters later in this chapter.
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 4/46
Chapter 7Cable Testing Fundamentals
7-4
Permanent Link Test Setup
ANSI, EIA, TIA, and ISO all provide two network communication circuit
specifications: permanent link and channel link. A permanent link consists of up
to 90 meters of horizontal network cabling. The permanent link (shown below) is
used to certify the horizontal network cable installation before network
connection and user hookup. It excludes adapters, patchcords, and jumpers.
Display
Handset
RemoteHandset
Channel Link Adapter and2 Meter Patchcord
NetworkPatch Panel
RJ-45Wall Outlet
Horizontal Network Cable(Maximum of 90 Meters)
AUTOTEST
NETMONITOR
WIREMAP
TDR
LENGTH
SHIFT
750 MHz Certifier
F1 F2 F3 F4F5 F6 F7 F8
ENTER
Escape
TALK
ANALYZE
SETUP
HELP
1 2 3
4 5 6
7 8 9
0
ABC D EF G HI
J KL M NO P QR
ST U VWX YZ
SPACE
AUTOTEST
ESCAPE
TONE MODE
TONE
PAGE
TALK
SHIFT
Remote
HAZARD PAS S FAIL ON
750 MHz Certifier
Channel Link Adapter and2 Meter Patchcord
Figure 7-3: Permanent Link Test Connections
Connection Cable Length Limits
Horizontal Network Cable Maximum of 90 meters
Note: Ensure that the Cable Type is set to Twisted Pair Permanent Link.If you exceed the tester length test limits, the tester will fail the link.
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 5/46
Chapter 7Cable Testing Fundamentals
7-5
Channel Link Test Setup
A channel link includes all aspects of the cabling system. It consists of up to 90
meters of horizontal network cabling, user patchcords, jumpers, and channel
adapters at each end. The channel link (shown below) is used to certify the
network installation, including the horizontal link and user patchcords.
DisplayHandset
RemoteHandset
User Patch Cord
Channel Adapter
Channel Adapter User Patch Cord
NetworkPatch Panel
RJ-45Wall Outlet
Horizontal Network Cable(Maximum of 90 Meters)
AUTOTEST
NETMONITOR
WIREMAP
TDR
LENGTH
SHIFT
750 MHz Certifier
F1 F2 F3 F4
F5 F6 F7 F8
ENTER
Escape
TALK
ANALYZE
SETUP
HELP
1 2 3
4 5 6
7 8 9
0
A BC D EF GHI
J KL M NO P QR
S TU V WX YZ
SPACE
AUTOTEST
ESCAPE
TONE MODE
TONE
PAGE
TALK
SHIFT
Remote
HAZARD PAS S FAIL ON
750 MHz Certifier
Figure 7-4: Channel Link Test Connections
Connection Cable Length Limits
Horizontal Network Cable Maximum of 90 meters
User Patchcords Combined Maximum length of 10 meters
Note: Ensure that the Cable Type is set to Twisted Pair Channel Link when testing with
channel adapters. If you exceed the tester length test limits, the tester will fail thelink.
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 6/46
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 7/46
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 8/46
Chapter 7Cable Testing Fundamentals
7-8
Troubleshooting Wiremap Problems
Problem: One or more open pins
Probable Causes Connector-to-wire punch down not mated
Defective jack or plug.
Broken wire(s).
Other Tests Affected Test Possible ResultDC Resistance Fail.
Attenuation Fail.
NEXT Some false measurements.
Mutual Capacitance 0 reading possible.
Length May be low if the open is near the
Display Handset.
Problem: Shorted pins
Probable Causes Conductors making contact at a connector.
Jack or plug has pin or circuit defect.
Cable damaged.
Other Tests Affected Test Possible ResultDC Resistance Low or zero.
Attenuation Fail.
NEXT Some false measurements.
Capacitance Over limit.
Length Reduced or shorted pairs.
Problem: Miswired pinsProbable Causes Conductors reversed at a connector.
Other Tests Affected Test Possible Result
Usually none Infrequently, one or more tests
may fail.
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 9/46
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 10/46
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 11/46
Chapter 7Cable Testing Fundamentals
7-11
DC Resistance Test
This test measures the loop resistance of each pair of wires. The instrument tests
to make sure total loop resistance does not exceed recommended limits. Results
are displayed with resistance in ohms for each pair, and a comparison limit for the
cable type.
Note: The RH is required to perform this test.
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 12/46
Chapter 7Cable Testing Fundamentals
7-12
DC Resistance Errors
All four pairs of a network link should have approximately the same resistance.
Pair resistance that exceeds the limit is indicated as a failure. The maximum limits
in the default tables are based on the maximum length limit of the link or cable
segment.
Troubleshooting DC Resistance Problems
Problem: Excessive Resistance
Probable Causes Mismatched cable types.
Poor punch block connection.
Poor RJ-45 termination connections.
Wire pair has a tap (never done).Cable damage.
Shorted cable.
Other Tests Affected Test Possible Result
Wire Map May fail.
Attenuation May fail.
NEXT May have false readings.
Capacitance May fail.
Problem: One wire pair has a very high DC loop resistance, othersare normal.
Probable Causes Poor connection points.
Cable damage.
Connector blades not fully piercing wire insulation.
Worn Connector
Other Tests Affected Test Possible Result
Wire Map May fail.
Attenuation May fail.
NEXT May have false readings.
Capacitance May fail.
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 13/46
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 14/46
Ch
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 15/46
Chapter 7Cable Testing Fundamentals
7-15
The FEXT test is similar to the NEXT test except that the traffic is generated at
the RH and crosstalk is measured at the DH.
• NEXT measurements are made at each end of the cable for all pair
combinations (pair 1-2 vs. 3-6, etc.), yielding a total of twelve measurements.
• ELFEXT measurements are made with the DH and RH for all possible pair
combinations (1-2 vs. 3-6, 3-6 vs. 1-2, 1-2 etc.) at both ends yielding a total
of twenty-four measurements.
Power Sum NEXT and Power Sum ELFEXT
Power Sum tests measure the crosstalk effects of three transmitting pairs on the
fourth pair in the same cable sheath.
1
2
3
6
4
5
7
8
2
1
3
6
4
5
7
8
Effects of 3 Pairs on 1 Pair
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 16/46
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 17/46
Chapter 7
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 18/46
Chapter 7Cable Testing Fundamentals
7-18
NEXT and ELFEXT Errors
Crosstalk is usually caused by poor connector termination on the ends of the
cable. The smaller the number, the greater the crosstalk.
Troubleshooting NEXT and ELFEXT Problems
Problem: Low dB test readingsProbable Causes Installed cable or patch cable not correctly rated.
Defective, poor quality cable or too many connectors.
Poor quality installation at the connection points.
Too much insulation has been stripped from the wires at
termination.
A pair of wires has been untwisted too much at termination.
Split-pairs.Poor quality connectors or connectors not rated to desired
category.
Delay skew (ELFEXT).
Other Tests Affected Test Possible Result
Return Loss May be over limit.
NEXT May show same symptoms.
Chapter 7
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 19/46
Chapter 7Cable Testing Fundamentals
7-19
Attenuation Test
This test measures the overall signal strength loss in the cable and verifies that it
is within acceptable limits. Low attenuation is essential for error-free
transmission. Attenuation is measured by injecting a signal of known amplitude at
the Remote Handset and reading the amplitude at the Display Handset.
Note: The RH is required to perform this test.
Chapter 7
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 20/46
C apteCable Testing Fundamentals
7-20
Attenuation Errors
Attenuation causes a loss of signal strength over a cable. The loss increases with
cable length, signal frequency, and temperature. Attenuation testing can be used
to find problems in the cable, connectors, or connecting hardware. The larger the
number, the greater the attenuation.
Troubleshooting Attenuation Problems
Problem: High Attenuation Reading
Probable Causes Poor connector termination points.
Excessive cable length.
Incorrect or poor quality adapter cable.
Incorrect cable.
Other Tests Affected Test Possible Result
DC Loop Resistance May be high.
Capacitance May be high.
Length May be over limit.
NEXT May be low on pair combinations.
Average Impedance May be low.
Return Loss May be over limit.
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 21/46
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 22/46
Chapter 7
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 23/46
Cable Testing Fundamentals
7-23
Impedance Test
Average impedance is derived from electrical delay and capacitance
measurements. The results of this test are expressed in ohms. Average impedance
testing can help identify physical damage to the cable, connector defects, or cable
segments with incorrect characteristic impedance.
This test uses capacitive measurements; therefore, it is necessary to specify the
correct cable type in order to accurately perform the test.
Note: If a CAT 3 cable is selected (specified as the cable type where PVC is used in the
cable insulation) but a CAT 5 cable (where Teflon is used as the cable insulation)is actually used, the average impedance will be calculated incorrectly. To avoid this problem, be sure to specify the correct cable type.
Note: The RH is not required to perform this test.
Chapter 7C bl T ti F d t l
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 24/46
Cable Testing Fundamentals
7-24
Impedance Errors
Impedance errors cause signal reflection and strength reduction. Averageimpedance of each pair should be equal to the LAN system impedance of 100,
120, or 150 Ω, plus or minus 15 Ω.
Troubleshooting Impedance Problems
Problem: High Impedance Readings
Probable Causes Compression, stretching, or excessive bending damage to
the cable.
Defective connectors.
Insulation damage at a connector.
Ground loops created between cable shielding (if used) and
equipment grounding (via RS-232 cable to computer, or auxiliary power).
Improperly chosen cables or patch cords.
Moisture in the cable.
Other Tests Affected Test Possible Result
Length Affected pairs will appear longer.
Average Impedance Change in average impedance isinversely proportional to change in
capacitance.
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 25/46
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 26/46
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 27/46
Chapter 7Cable Testing Fundamentals
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 28/46
Cable Testing Fundamentals
7-28
Capacitance Errors
The larger the capacitance, the higher the error rate. Small changes in the
capacitance measurements are normal due to the handling of the cable during
shipping and installation. The addition of connectors and patch cables will also
affect capacitance values.
Troubleshooting Capacitance Problems
Problem: Capacitance Exceeds the Maximum Limit
Probable Causes Compression, stretching, or excessive bending damage to
the cable.
Defective connectors.
Insulation damage at a connector.
Ground loops created between cable shielding (if used) andequipment grounding (via RS-232 cable to computer, or
auxiliary power).
Improperly chosen cables or patch cords.
Moisture in the cable.
Poor connections at punch downs and wall plates
Other Tests Affected Test Possible Result
Length Affected pairs will appear longer.Average Impedance Change in average impedance is
inversely proportional to change in
capacitance.
Chapter 7Cable Testing Fundamentals
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 29/46
g
7-29
ACR and Power Sum ACR Test
The ACR (Attenuation-to-Crosstalk Ratio) test performs a mathematical
comparison (difference calculation) between the results of the Attenuation and
NEXT tests. The difference reading between each pair gives an indication of how
problem-free the cable pair will be for transmissions.
The ACR measurements are calculated pair-to-pair.
Note: The RH is required to perform these tests.
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 30/46
Chapter 7Cable Testing Fundamentals
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 31/46
7-31
Headroom Test
The Headroom measurement is a mathematical analysis of the data already
existing from previous tests. The calculated value is the sum of the Power Sum
ACR test (Power Sum ACR of the worst pair after the attenuation for that pair has
been normalized to 100 meters or 328 feet) and the additional margin between the
worst case PS NEXT and the limit for PS NEXT.
Headroom provides a simplified means of reporting the margin available in asingle cable run which will support an application with error-free performance. It
also gives an indication of additional margin which may be achieved through the
utilization of “enhanced” cable and connectors and careful installation practices.
Note: The RH is required to perform this test.
Chapter 7Cable Testing Fundamentals
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 32/46
7-32
Headroom Errors
The Headroom number, reported in dB, characterizes the worst-case margin
found in a single cable run. A large number is desirable, since it indicates a
strong signal and little noise interference. The pass/fail limit for Headroom is the
same as Power Sum ACR.
Testing and Troubleshooting 10BASE-T Cabling
10BASE-T Ethernet systems use twisted pair cabling for transmission of network
data frames. Both the cable and connecting hardware must meet minimum
standards as specified in the IEEE 802.3 standard. The default settings for
10BASE-T network links in the LANTEK tester reflect these standards.
10BASE-T systems use the 1 and 2 pins for transmit and the 3 and 6 pins for receive, as shown in Figure 7-5. The instrument passes or fails the Wire Map
based on this pin configuration. If your system does not use the IEEE 802.3
wiring standard, a custom adapter is required to align nonstandard transmit and
receive pairs.
Figure 7-5: 10BASE-T Connector
Note: Other pairs may be wired, but 10BASE-T uses only the pairs shown.
Chapter 7Cable Testing Fundamentals
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 33/46
7-33
Testing and Troubleshooting Nexans Cabling System
A field calibration should be performed prior to implementing a test of the
Nexans cabling system. This process will ensure (1) synchronizing of the units,
(2) qualifying (testing) of the patchcords and (3) gathering of loss data regarding
the patchcords and mated connections.
The field calibration is a 4-step process. Process 1 and 2 are performed with the
Nexans Calibration Adapters connected to the Handsets. Process 3 and 4 are performed with the Nexans Permanent Link Adapters open-ended patchcords and
then the Nexans Calibration Load Terminator attached.
The Nexans testing kit comprises a Category 7 connector product which is
backward compatible with Category 6 – RJ45s.
The equipment required for a Nexans calibration procedure are:
• Display Handset
• Remote Handset
• Nexans Calibration Adapters
(Two adapters joined by a short segment of Category 7 cable)
• Nexans Calibration Load Terminator
(100Ω Jack)
• Nexans Permanent Link Adapters
(A set of two adapters, each with a patchcord (approximately 2 meters)soldered to the adapter at one end and a Nexans Category 7 plug at the
opposite end)
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 34/46
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 35/46
Chapter 7Cable Testing Fundamentals
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 36/46
7-36
Testing a Nexans Cabling System
Figure 7-6: Typical Configuration for Nexans Cable Testing
Typical configuration for testing has the DH unit and RH unit connected to the
Nexans Permanent Link Adapters. Each Nexans Permanent Link Adapter has a
patchcord (approximately 2 meters) soldered to the adapter at one end and a
Nexans Category 7 plug at the opposite end. The cable under test is connected at
the Category 7 plug end of both the DH and RH ends.
Chapter 7Cable Testing Fundamentals
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 37/46
7-37
Testing and Troubleshooting with a Block Connector
SystemAt times, it is necessary to test directly from a connecting block to either a patch
panel or office outlet.
A field calibration should be performed prior to implementing a test of the block
system. This process will ensure (1) synchronizing of the units, (2) qualifying
(testing) of the patchcords and (3) gathering of loss data regarding the patchcordsand mated connections.
The field calibration is a 4-step process. Process 1 and 2 are performed with the
patchcords connected to the Handsets. Process 3 and 4 are performed with open-
ended patchcords (Only one end connected to the Handsets).
Note: The following process describes the calibration and testing procedures for theblock connector system. These procedures can be used for either the 110, 210,BIX, or 66 Block systems.
The equipment required for a block calibration procedure are:
• Display Handset
• Remote Handset
• RJ45 to RJ45 Patchcord
• RJ45 to Block Plug Patchcord
• A Block Calibration Adapter (T568A or T568B) depending on the
connection system that will be scheduled for testing.
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 38/46
Chapter 7Cable Testing Fundamentals
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 39/46
7-39
Field Calibration using Block Adapters
Note: A Block Adapter Kit can be ordered from IDEAL INDUSTRIES. The kit containsadapters for the following block systems: 110, 210, BIX and 66.
Step 1
Connect the channel adapters to the Display Handset (DH) and Remote Handset
(RH).
Power both units on.
Connect the RJ45 to RJ45 Patchcord that you plan to use as the RH Patchcord to
the adapters of the DH and RH units.
From the DH Ready screen, select Field Calibration .
The Calibration screen appears.
Chapter 7Cable Testing Fundamentals
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 40/46
7-40
From the DH Field Calibration
screen, select to begin the
calibration process on the first (RH)Patchcord. This first process takes
about 30 seconds to complete.
At the completion of the first calibration process, tag the RH end of the first
patchcord. Disconnect the first patchcord from the DH and RH unit adapters. This
tag will remind you which end to reinsert into the RH for Step 4.
Step 2
Insert the block calibration adapter either T568A or T568B into the RH unitadapter. Insert the second (DH) RJ45 to Block Plug patchcord into both the DH
and RH adapters. The RJ45 end into the DH unit adapter, the block plug into the
block calibration adapter connected to the RH.
Note: If field testing a TIA-568A connection system, use a T568A calibration adapter. If field testing a TIA-568B connection system, use a T568B calibration adapter.
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 41/46
Chapter 7Cable Testing Fundamentals
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 42/46
7-42
Step 4
From on the RH, press to begin the fourth calibration process.
If calibration is successful, the DH will briefly Display “Calibration Complete”
and the RH will briefly display the PASS light. The handsets and the patchcords
are ready for testing procedures.
If calibration is unsuccessful, the DH will briefly display either a Warning screen
displaying “No Remote Handset” or a Calibration Failure screen.
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 43/46
Chapter 7Cable Testing Fundamentals
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 44/46
7-44
Testing and Troubleshooting Coax Cabling
Field Calibration using Coax Adapters
Field Calibration using Coax adapters uses a modification of the LANTEK 4-step
process. Since Coax testing is done for low frequencies, the additional data
obtained during calibration processes is essentially ignored therefore the
LANTEK will request one calibration process step to be performed.
To calibrate the tester, perform the following:
Connect the Coax adapters to the
Display Handset (DH) and Remote
Handset (RH).
Power both units on.
Insert the short calibration cable into
both the DH and RH adapters.
From the DH Ready screen, select
Field Calibration. The Calibration
screen appears.
From the DH Field Calibration screen,
select to begin the calibration
process.
When calibration process is completed, the LANTEK is ready for testing.
Chapter 7Cable Testing Fundamentals
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 45/46
7-45
Testing and Troubleshooting Fiber Optics
FIBERTEK TM allows you to perform optical power loss measurements for both
Singlemode and Multimode fiber optic cables on either the LANTEK ®
6 or 7
Cable Certifiers.
The fiber testing performed makes use of laser sources for all wavelengths,
permitting certification of Gigabit Ethernet applications on the fiber optic cable.
TRACETEK TM is an advanced troubleshooting tool designed to quickly identify
and provide assistance in diagnosing common cabling problems.
Fiber Optics testing and troubleshooting kit(s) are available and contain the
FIBERTEK TM
and/or TRACETEK TM
products as well as detailed information
within a manual structure regarding their function.
For further details and/or procurements of these products call your local IDEAL
INDUSTRIES representative.
Chapter 7Cable Testing Fundamentals
7/27/2019 @Chapter 7, Cable Testing Fundamental
http://slidepdf.com/reader/full/chapter-7-cable-testing-fundamental 46/46
7-46