5
AECOM Technical Services of North Carolina, Inc. 5925 Carnegie Blvd Suite 370 Charlotte, NC 28209 www.aecom.com (704) 553-6150 tel (704) 553-6151 fax Charlotte-Mecklenburg Schools Drinking Water Program Phase II – <1990 Administrative, Middle School and High School Facilities Laboratory Analytical Results Summary: Myers Park HS 2400 Colony Road Charlotte, NC 28209 Sampling Date: 11/10/2018 Number of Consumption Points Sampled: 95 Consumption Points with Values Exceeding NCDEQ DWS: 2 (Pb) & 2 (Cu) Low Value (µg/L): <0.40 (Pb - lead); <0.28 (Cu - copper) High Value (µg/L): 140 (Pb - lead); 2,860 (Cu - copper) Consumption Point(s) in Exceedance of NCDEQ DWS Sample Collection Point ID Sample Collection Date Fixture Type Location Initial Result (µg/L) Flush Result (µg/L) CMS Notification Date Corrective Action 466-KS-8 11/10/18 Kitchen Sink Football Field Visitors Concession Stand 22.6 (Pb) 1.89 (Pb) 12/5/18 Fixture taken out of service 12/5/18 466-WC-1 11/10/18 Water Cooler Cafeteria 2,860 (Cu) Pending 12/5/18 Fixture taken out of service 12/5/18 466-WC-19 11/10/18 Water Cooler Auditorium Back Stage 140 (Pb) Pending 12/5/18 Fixture taken out of service 12/5/18 466-WC-50 11/10/18 Water Cooler Hallway Outside Room #SET-311 2,450 (Cu) Pending 12/5/18 Fixture taken out of service 12/5/18 Notes: Pb = Lead Cu = Copper NCDEQ = North Carolina Department of Environmental Quality DWS = Drinking Water Standard (Pb = 15 µg/L, Cu = 1,300 µg/L) µg/L = micrograms per liter or parts per billion (ppb) Bolded, highlighted values indicate concentrations in excess of the respective NCDEQ DWS * A detailed report summarizing all assessment and remediation activities will be provided upon completion of the Drinking Water Program Phase II

Charlotte-Mecklenburg Schools Drinking Water Program …...Drinking Water Program Phase II –

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Charlotte-Mecklenburg Schools Drinking Water Program …...Drinking Water Program Phase II –

AECOM Technical Services of North Carolina, Inc.

5925 Carnegie Blvd

Suite 370

Charlotte, NC 28209

www.aecom.com

(704) 553-6150 tel

(704) 553-6151 fax

Charlotte-Mecklenburg Schools

Drinking Water Program Phase II – <1990 Administrative, Middle School

and High School Facilities

Laboratory Analytical Results Summary: Myers Park HS

2400 Colony Road

Charlotte, NC 28209

Sampling Date: 11/10/2018

Number of Consumption Points

Sampled: 95

Consumption Points with Values

Exceeding NCDEQ DWS: 2 (Pb) & 2 (Cu)

Low Value (µg/L): <0.40 (Pb - lead); <0.28 (Cu - copper)

High Value (µg/L): 140 (Pb - lead); 2,860 (Cu - copper)

Consumption Point(s) in Exceedance of NCDEQ DWS

Sample

Collection

Point ID

Sample

Collection

Date

Fixture

Type Location

Initial

Result

(µg/L)

Flush

Result

(µg/L)

CMS

Notification

Date

Corrective Action

466-KS-8 11/10/18 Kitchen

Sink

Football Field

Visitors

Concession Stand

22.6 (Pb) 1.89 (Pb) 12/5/18 Fixture taken out

of service 12/5/18

466-WC-1 11/10/18 Water

Cooler Cafeteria 2,860 (Cu) Pending 12/5/18

Fixture taken out

of service 12/5/18

466-WC-19 11/10/18 Water

Cooler

Auditorium –

Back Stage 140 (Pb) Pending 12/5/18

Fixture taken out

of service 12/5/18

466-WC-50 11/10/18 Water

Cooler

Hallway Outside

Room #SET-311 2,450 (Cu) Pending 12/5/18

Fixture taken out

of service 12/5/18

Notes:

Pb = Lead

Cu = Copper

NCDEQ = North Carolina Department of Environmental Quality

DWS = Drinking Water Standard (Pb = 15 µg/L, Cu = 1,300 µg/L)

µg/L = micrograms per liter or parts per billion (ppb)

Bolded, highlighted values indicate concentrations in excess of the respective NCDEQ DWS

* A detailed report summarizing all assessment and remediation activities will be provided upon completion of the Drinking Water Program Phase II

Page 2: Charlotte-Mecklenburg Schools Drinking Water Program …...Drinking Water Program Phase II –

466-KS-8Myers Park HSKitchen SinkFootball Stadium Visitor's Side Concession Stand Sink

Sample Collection Point IDSchoolFixture TypeNotes

Sample Collection Date 11/10/2018

robert.brookshire
Stamp
Page 3: Charlotte-Mecklenburg Schools Drinking Water Program …...Drinking Water Program Phase II –

466-WC-1Myers Park HSWater CoolerCafeteria

Sample Collection Point IDSchoolFixture TypeNotes

Sample Collection Date 11/10/2018

robert.brookshire
Stamp
Page 4: Charlotte-Mecklenburg Schools Drinking Water Program …...Drinking Water Program Phase II –

466-WC-19Myers Park HSWater CoolerAuditorium - Back Stage

Sample Collection Point IDSchoolFixture TypeNotes

Sample Collection Date 11/10/2018

robert.brookshire
Stamp
Page 5: Charlotte-Mecklenburg Schools Drinking Water Program …...Drinking Water Program Phase II –

466-WC-50Myers Park HSWater CoolerHallway Outside of Room #SET-311 (left water cooler in pair)

Sample Collection Point IDSchoolFixture TypeNotes

Sample Collection Date 11/10/2018

robert.brookshire
Stamp