Chilled Water Piping Systems (VPF Focus)
8/10/2019 CHILLED WATER SYSTEM.ppt
2/48
AgendaChilled Water Distribution Systems
Chilled Water Distribution Systems
Primary (Constant) / Secondary (Variable2W Valves)
Low Delta T
Primary Only (Variable Flow - 2W Valves)
VPF Design/Control Considerations
8/10/2019 CHILLED WATER SYSTEM.ppt
3/48
Primary (Constant Flow) / Secondary (Variable Flow)
8/10/2019 CHILLED WATER SYSTEM.ppt
4/48
Primary/Secondary System
Primary Pumps
Secondary Pumps
Common Pipe
Typical
load
with
two
way
valve
8/10/2019 CHILLED WATER SYSTEM.ppt
5/48
Primary (Constant Flow) / Secondary (Variable Flow)
2 Way Valves
Higher Capital Cost Installed (vs Constant Flow 3W Valve system)
Lower CHW Pumping Energy (vs Constant Flow 3W Valve system)
Well Understood & Easy to Control
8/10/2019 CHILLED WATER SYSTEM.ppt
6/48
Primary/Secondary System at Design
56.0 F
56.0 F
56.0 F
44.0 F
44.0 F
44.0 F
Primary Pumps
1000 GPM Each
3000 GPM @ 56.0 F
Secondary Pumps
3000 GPM @ 44.0 F
Typical
Coil
No flow
44.0 F
56.0 F
500 ton chillers
1000 GPM Each
56.0-44.0F
8/10/2019 CHILLED WATER SYSTEM.ppt
7/48
Primary/Secondary System at Part Load
53.0 F
53.0 F
53.0 F
44.0 F
44.0 F
44.0 F
Primary Pumps
1000 GPM Each
3000 GPM @ 53.0 F
Secondary Pumps
2250 GPM @ 44.0 F
Typical
Coil
44.0 F
56.0 F
750 GPM @ 44.0 F
2250 GPM @ 56.0 F
75% System Load
8/10/2019 CHILLED WATER SYSTEM.ppt
8/48
Primary/Secondary System
53.0 F
53.0 F
44.0 F
44.0 F
Primary Pumps
1000 GPM Each
2000 GPM @ 53.0 F
Secondary Pumps
1500 GPM @ 44.0 F
Typical
Coil
44.0 F
56.0 F
500 GPM @ 44.0 F
1500 GPM @ 56.0 F
OFF 50% System Load
8/10/2019 CHILLED WATER SYSTEM.ppt
9/48
Low Delta T Syndrome
8/10/2019 CHILLED WATER SYSTEM.ppt
10/48
10
Dirty Coils
Major Causes of Low Delta T
8/10/2019 CHILLED WATER SYSTEM.ppt
11/48
Chilled Water Coil
8/10/2019 CHILLED WATER SYSTEM.ppt
12/48
12
Dirty Coils
Controls Calibration
Leaky 2 Way Valves
3 Way Valves at end of Index circuit
Major Causes of Low Delta T
8/10/2019 CHILLED WATER SYSTEM.ppt
13/48
Primary/Secondary System
Primary Pumps
Secondary Pumps
Common Pipe
8/10/2019 CHILLED WATER SYSTEM.ppt
14/48
8/10/2019 CHILLED WATER SYSTEM.ppt
15/48
15
Dirty Coils
Controls Calibration
Leaky 2 Way Valves
3 Way Valves at end of Index circuit
Coils piped up backwards
Major Causes of Low Delta T
8/10/2019 CHILLED WATER SYSTEM.ppt
16/48
Chilled Water Coil
8/10/2019 CHILLED WATER SYSTEM.ppt
17/48
17
P Load= Flow X Delta T S Load= FlowX Delta T
Primary (Constant) / Secondary (Variable)
SecondaryPumps
PrimaryPumps
Typical load with 2 way valve
Decoupler/Bypass
8/10/2019 CHILLED WATER SYSTEM.ppt
18/48
18
100% Load = 100% Sec Flow
Primary (Constant) / Secondary (Variable)
Ideal Operation
SecondaryPumps
PrimaryPumpsDecoupler
/Bypass
100% Flow = 3000 gpm
100% Flow = 3000 gpm
0 gpm
1
2
8/10/2019 CHILLED WATER SYSTEM.ppt
19/48
SecondaryPumps
PrimaryPumpsDecoupler
/Bypass
67% Flow = 2000 gpm
67% Flow = 2000 gpm
0 gpm
19
67% Load = 67% Sec Flow
Primary (Constant) / Secondary (Variable)
Ideal Operation
1
2
8/10/2019 CHILLED WATER SYSTEM.ppt
20/48
20
Primary / Secondary Rule of Flow
Primary flow must always be equal
to or greater than Secondary flow.
8/10/2019 CHILLED WATER SYSTEM.ppt
21/48
SecondaryPumps
PrimaryPumpsDecoupler
/Bypass
100% Flow = 3000 gpm
80% Flow = 2400 gpm (400 gpm over-pumped)
600 gpm
21
67% Load = 80% Sec Flow
Primary (Constant) / Secondary (Variable)
Low Delta T Operation
1
0
8/10/2019 CHILLED WATER SYSTEM.ppt
22/48
Higher Secondary Pump Energy
Higher CHW Plant Chiller/Auxiliary Energy
Major Effects of Low Delta T
8/10/2019 CHILLED WATER SYSTEM.ppt
23/48
23
Solution to (or reduce effects of) Low Delta T
Address the causes
Clean Coils
Calibrate controls occasionally
Select proper 2W valves (dynamic/close-off ratings) and maintain them
no 3W valves in design
find and correct piping installation errors
Over pump chillers at ratio of Design Delta T / Actual Delta T
Increase Delta T across chillers with CHW Re-set (down).
Use Variable Speed Chillers & sequence to operate from 30 to 70% Load
Use VPF Systems (mitigates energy waste in plant)
Header pumps & operate more pumps than chillers
If dedicated pumping, over-size (design at 80% speed).
8/10/2019 CHILLED WATER SYSTEM.ppt
24/48
Primary/Secondary System
Primary Pumps
Secondary Pumps
Common Pipe
P
8/10/2019 CHILLED WATER SYSTEM.ppt
25/48
Primary Only (Variable Flow)
8/10/2019 CHILLED WATER SYSTEM.ppt
26/48
Primary/Secondary System
Variable Primary System
SecondaryPumps
PrimaryPumps
Primary Pumps
Flow Meter
BypassValve
Automatic Isolation Valve
Typical load with 2 way valve
Typical load with 2 way valve
8/10/2019 CHILLED WATER SYSTEM.ppt
27/48
Primary Only (Variable Flow)
2 Way Valves
Lower Capital Cost Installed (vs Primary/Secondary)
No secondary pumps/piping/valves/electrical to buy and install
No large Common pipe, but smaller Bypass pipe/valve/flow meter/controls
Lower CHW Pumping Energy
Smaller Footprint (vs Primary/Secondary)
Relatively New & More Complex Controls
Reduces Negative Impacts from Low Delta T
Chillers are not staged on by flow requirements
Chillers can load up and are staged on load
8/10/2019 CHILLED WATER SYSTEM.ppt
28/48
Primary Only (Variable Flow)
Disadvantages
Higher (potentially) PSID rated 2-Way valves in system
Requires more robust (complex and calibrated) control system
Requires coordinated control of chillers, isolation valves, and pumps in sequencing
Longer (potentially) Commissioning time
Requires greater operator sophistication
8/10/2019 CHILLED WATER SYSTEM.ppt
29/48
Variable-Primary-Flow System
Primary Pumps
Flow Meter
Typical
load
with
twoway
valve
AutomaticIsolation Valve
Bypass
8/10/2019 CHILLED WATER SYSTEM.ppt
30/48
Variable Primary System at Design
56.0 F
56.0 F
56.0 F
44.0 F
44.0 F
44.0 F
Primary Pumps
1000 GPM Each
3000 GPM @ 56.0 F
3000 GPM @ 44.0 F
AutomaticIsolation Valve
Bypass
Closed
500 ton chillers
1000 GPM Each56.0-44.0F
Typical
load
with
two
wayvalve
8/10/2019 CHILLED WATER SYSTEM.ppt
31/48
Variable Primary SystemPart Load
56.0 F
56.0 F
56.0 F
44.0 F
44.0 F
44.0 F
Primary Pumps
750 GPM Each
2250 GPM @ 56.0 F
2250 GPM @ 44.0 F
AutomaticIsolation Valve
Bypass
Closed
Typical
load
with
twoway
valve
75% System Load
8/10/2019 CHILLED WATER SYSTEM.ppt
32/48
Variable Primary SystemPart Load
56.0 F
56.0 F
44.0 F
44.0 F
Primary Pumps
750 GPM Each
1500 GPM @ 56.0 F
1500 GPM @ 44.0 F
AutomaticIsolation Valve
Bypass
Closed
Typical
load
with
twoway
valve
50% System LoadChiller off
Pump off
8/10/2019 CHILLED WATER SYSTEM.ppt
33/48
Variable Primary SystemPart Load
52.0 F
52.0 F
44.0 F
44.0 F
Primary Pumps
750 GPM Each
2250 GPM @ 52.0 F
2250 GPM @ 44.0 F
AutomaticIsolation Valve
Bypass
Closed
Typical
load
with
twoway
valve
50% System Load
Low T
Chiller off
Pump on
8/10/2019 CHILLED WATER SYSTEM.ppt
34/48
Variable Primary SystemMin Flow (400 gpm each)
50.0 F
44.0 F
Primary Pumps
400 GPM (oneoperating)
400 GPM @ 50.0 F
200 GPM @ 44.0 F
AutomaticIsolation Valve
Bypass
Open
Typical
load
with
twoway
valve
System flow below chiller
minimum flow
Chiller off
Chiller off
Closed
Closed
200 GPM @ 44.0
200 GPM @ 56.0 FFlowmeter
Pumps
off
8/10/2019 CHILLED WATER SYSTEM.ppt
35/48
Chiller Design Considerations
Flow rate changesStaging on additional chillers
8/10/2019 CHILLED WATER SYSTEM.ppt
36/48
Variable Primary System (1 chiller running)
56.0 F
44.0 F
Primary Pumps
333 GPM Each
1000 GPM @ 56.0 F
1000 GPM @ 44.0 F
AutomaticIsolation Valve
Bypass
Closed
Typical
load
with
two
wayvalve1000 GPM
8/10/2019 CHILLED WATER SYSTEM.ppt
37/48
Variable Primary System (Staging on second chiller)
57.0 F
45.0 F
Primary Pumps
333 GPM Each
1100 GPM @ 57.0 F
1100 GPM @ 45.0 F
AutomaticIsolation Valve
Bypass
Closed
Typical
load
with
two
wayvalve1100 GPM
Need to add chiller
8/10/2019 CHILLED WATER SYSTEM.ppt
38/48
Variable Primary System (Open isolation valve)
57.0 F
45.0 F
Primary Pumps
333 GPM Each
1100 GPM @ 57.0 F
1100 GPM @ 45.0 F
AutomaticIsolation Valve
Bypass
Closed
Typical
load
with
two
wayvalve550 GPM
550 GPM
Load = F X DT DT = 12 = 57- 45
24Load = 1/2F X 2DT DT = 24
24 LCHWT = 35!
8/10/2019 CHILLED WATER SYSTEM.ppt
39/48
Variable Primary System (Open isolation valve)
57.0 F
45.0 F
Primary Pumps
333 GPM Each
1100 GPM @ 57.0 F
1100 GPM @ 45.0 F
AutomaticIsolation Valve
Bypass
Closed
Typical
load
with
two
wayvalve550 GPM
550 GPM
LCHWT approaches 35
LWT Cutout at 4 deg below
44 set-point or 40
Off goes chiller 1
8/10/2019 CHILLED WATER SYSTEM.ppt
40/48
Variable Primary System (Open isolation valve slowly)
57.0 F
45.0 F
Primary Pumps
333 GPM Each
1100 GPM @ 57.0 F
1100 GPM @ 45.0 F
AutomaticIsolation Valve
Bypass
Closed
Typical
load
with
two
wayvalve1100 GPM
Open over 1.5 to 2 min
8/10/2019 CHILLED WATER SYSTEM.ppt
41/48
42
VPF Systems Design/Control Considerations Summary
Chillers
Equal Sized Chillers preferred, but not required
Maintain Min flow rates with Bypass control (1.5 fps)
Maintain Max flow rates (11.0 to 12.0 fps)
Isolation Valves (Modulating or Stroke-able to 1.5 to 2 min)
Dont vary flow too quickly through chillers (VSD Ramp function typical setting of 10%/min)
Chiller Type
System Water Volume
Chiller Load
Active Loads
Sequence
If Constant Speedrun chiller to max load (Supply Temp rise). Do not run more chillers than
needed (water-cooled) If Variable Speedrun chillers between 30% and 70% load (depending on ECWT). Run more
chillers than load requires.
Add Chiller - CHW Supply Temp or Load (Adjusted* Flow X Delta T) or amps (if CSD)
Subtract Chiller - Load (Adjusted* Flow X Delta T) or Amps (if CSD)
8/10/2019 CHILLED WATER SYSTEM.ppt
42/48
43
VPF Systems Design/Control Considerations Summary
Pumps
Variable Speed Driven
Headered arrangement preferred
Sequence
with chillers (run more pumps than chillers for over-pumping capability)
on flow (add pump when existing inadequate, subtract when can)
optimized algorithm (total kW of more pumps, lower than less pumps)
Stay within pump/motor limits (25% to 100% speed)
Subtract a Pump at 25 to 30% speed
Add a pump back when speed of operating pumps high enough
Speed controlled by pressure sensors at endof index circuit
8/10/2019 CHILLED WATER SYSTEM.ppt
43/48
44
VPF Systems Design/Control Considerations Summary
Bypass Valve
Maintain a minimum chilled water flow rate through the chillers
Differential pressure measurement across each chiller evaporator
Flow meter preferred
Modulates open to maintain the minimum flow through operating chiller(s).
Bypass valve is normally open, but closed unless Min flow breeched
Pipe and valve sized for Min flow of operating chillers
High Rangeability (100:1 preferred)
PSID Ratings for Static, Dynamic, And Close Off = Shut Off Head of Pumps
Linear Proportion (Flow to Valve Position) Characteristic preferred
Fast Acting Actuator
Locate in Plant around chillers/pumps (preferrred)
Energy
Avoid Network traffic
8/10/2019 CHILLED WATER SYSTEM.ppt
44/48
8/10/2019 CHILLED WATER SYSTEM.ppt
45/48
46
Summary on VPF Design
Chillers
Size equally with same WPDs (best)
Respect Min/Max Flows through chillers
Set Pump VSD Ramp function to about 10%/min (600 sec 0 to Max Speed)
Use Modulating or Strokeable Valves (preferred) on chiller evaps, headered pumping
Use 2 Position Valves (1 min stroke) on chiller evaps, dedicated pumping
Pumps
VSD Controllers
Headered Pumping Arrangement (preferred)
Dedicated Pumping OK (over-size pumps)
2 Way Valves
Select for Static, Dynamic, Close-off ratings (PSID) equal to pump SOH (plus fill pressure)
Range-ability 100 to 200:1
If Bypassfast acting, linear proportion
If Coilsslow acting, equal percentage, On-Off stagger air units (10-15 min intervals)
Controls
Set-point far out in index circuit (lower the value, the better the pump energy)
Set Ramp function in VSD Controller (10%/min average)
Run 1 more pump than chillers (when headered)
Chillers On by common Supply Temp, Load, Amps, Adj Flow (Adj for Low Delta T)
Chillers Off by Amps, Load, Adj Flow (Adj for Low Delta T)
Over-pump Chillers to combat Low Delta T and get Max Cap out of chillers
Bypass controlled by Min flow (preferred) or Min WPD of largest chiller (locate in plant for best energy, but can go anywhere in system)
8/10/2019 CHILLED WATER SYSTEM.ppt
46/48
Chilled Water Piping Systems (VPF Focus)
Questions?
8/10/2019 CHILLED WATER SYSTEM.ppt
47/48
Supply
Terminal
Balance
and
Service
Valve
2-Way
Control
Valve
Return
Service Valve
Air
2 Way Valve/Coil Detail
8/10/2019 CHILLED WATER SYSTEM.ppt
48/48
Electric Energy Cost Equations
Chiller
Energy Cost
Lbs Refrig/hr X Head
33,015 X Comp Eff
X Hours X Cost/Unit Energy=
Pump
Energy Cost
GPM X Head
3960 X Pump Eff
X Hours X Cost/Unit Energy=
Fan
Energy Cost
CFM X TSP
6356 X Fan Eff
X Hours X Cost/Unit Energy=
0.7459
Mot Eff
0.7459
Mot Eff
0.7459
Mot Eff
X
X
X
Energy Cost
Mass Flow/t X Lift
33,015 X EfficiencyX Hours X Cost/Unit Energy=
0.7459
Mot EffX