Terna Rete Italia – Head of Research Center -Florence Chairman Comitato Nazionale CIGRE-Italia M. Rebolini CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO EXPERIENCE

CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

  • Upload
    lamngoc

  • View
    219

  • Download
    3

Embed Size (px)

Citation preview

Page 1: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

Terna Rete Italia – Head of Research Center -Florence

Chairman Comitato Nazionale CIGRE-Italia

M. Rebolini

CIGRE ATLASOFHVDCSYSTEMSWITHITALIANTSO EXPERIENCE

Page 2: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

2

1987 40 HVDC System 11 mercury-arc valves29 thyristor valves

ATLAS OF HVDC SYSTEM

Page 3: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

3

2009 103 HVDC System in operation 8 HVDC System retired3 HVDC System BtB( Austria-

Hungary & Germany-Cech Republic & Austria) and after retired17 HVDC System in construction5 VSC in operation

2015 166 HVDC System in operation ( 3 UHVDC +/- 800 kV)61 HVDC System in construction/planned10 VSC in operation1 Hybrid System ( LCC-VSC)

2015-2020 28 UHVDC(±800 kV, ±1100 kV) planned for

implementation

ATLAS OF HVDC SYSTEM

Page 4: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

4

Number of HVDC installations by Year

7 10

23

4650

29

165

0

20

40

60

80

100

120

140

160

180

50-70 70-80 80-90 90-2000 2000-2010 2010-Today Total

40

136

165

ATLAS OF HVDC SYSTEM

Page 5: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

5

HVDC From Global Interconnection to ……. ATLAS OF HVDC SYSTEM

Page 6: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

HVDC & FACTS for SubTransmission & Industrial

Distribution Systems

ATLAS OF HVDC SYSTEM

Page 7: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

7

HVDC From Interconnection to …..Connection

ATLAS OF HVDC SYSTEM

Page 8: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

More HVDC investments in the nextyears

Global Investment in HVDC Transmission Systems 2012-2020 120 Billion $ (1)

(1) Source Pyke Research

ATLAS OF HVDC SYSTEM

Page 9: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

(1) Source Technavio Analyst Report

Converter Stations account for about 12 Billion $ per year ( 5% of total network investments) other are related to HVDC OHL and sea cables CAGR from 2014 to 2019 20% New Market analysis (1) gives grow of HVDC Converter at a CAGR of 24,1% 2016-2020Market share 2015 : EMEA (Europe, MiddleEast,Africa ) 36,12%, APAC (Asia Pacific) 32,65%, Americas 31,32%.

ATLAS OF HVDC SYSTEM

Page 10: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

One third ( 33% of totalinvestment ) 50 billion € (56 billion $) are submarine HVDC interconnections

Also Europe strong increasinginvestments on HVDC Systems

ATLAS OF HVDC SYSTEM

Page 11: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

HVDC is integral part of «smart grid solutions»Power flow & frequency control

WHY HVDC?

HVDC used in the connection of offshore Wind Farms

HVDC used in the integration of Networks ( mainly with long sea link )

HVDC used as BtB Systems for interconnection of asynchronous Networks

HVDC used for Very Long Distance Huge Power Transfer

HVDC become more acceptable ( both with OHLs and cables ) in Authorization/Environment Assessment vs. AC OHL technology

Now

Classical

ATLAS OF HVDC SYSTEM

Page 12: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

System description LCC-HVCD VSC-HVDC

System ratings in operation ±800 kV, 7000 MW ±320 kV, 600 MW

System ratings available ±1100 kV, 13000 MW ±500 kV, 2000 MW

Operational experience 50 years 15 years

Lifetime 30 years 30 years

Converter Losses(at full load ,per converter ) 0.75 % 1,1 %

Availability (per system) >98% >98%

System Capabilities

Transmission Capacity ••• ••

Power Flow Control ••• •••

Transient Stability •• •••

Voltage stability • •••Power Oscillation damping •• •••

Reactive Power demand ••• •

System perturbation ••• •

Reactive Injection possible no yes

Easy meshing no yes

Black starting no Yes

SCR AC grid > 2,5 No problem

Investment costs per MW •• •••

Legenda: •small; • •medium; • • • strong

WHICH KIND HVDC-Technology ?

ATLAS OF HVDC SYSTEM

Page 13: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

Malta Sicily

SAPEI

Sorgente - Rizziconi

Italy- France

0

100

200

300

400

500

600

0 100 200 300 400 500 600 700

Rat

ed

Vo

ltag

e (

kV)

cable length (km)

Uneconomical Voltage Levels

AC

3 p

has

eHVDC - LCC

HVDC- VSC1st generation

HVDC-VSC2nd generation

HVDC-VSC3nd generation

ATLAS OF HVDC SYSTEM

Page 14: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

MAIN CHALLENGES &ITALIAN VIEW from TSO EXPERIENCE SOME CASES

Page 15: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

15

SACOI 1 1967-1992

SACOI 21992-today

• Voltage: ±200 kV LCC

(Line Commutate Converter• Air cooled Thyristors Valves

• Rated power: 300 MW

• Nominal Current 1500 A

• Total Length 385 km :121 km

sea cables, 264 km DC OHL

The world first triterminal HVDC( 1987)

• Voltage: ±200 kV LCC

(Line Commutate ConverterMercury Valves )

• Rated power: 200 MW

• Nominal Current 1500 A

• Max Depth 500 m

• Total lengh 413 km :292 km

DC OHL and 121 km sea

cables

• 1987 Lucciana Tap (250 A;

50 MW)

Was connected

To 380 kV grid

TERNA HVDC Plants

Page 16: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

HVDC Italy-Greece Link

The world first deepest submarine HVDC cable

(1.000 m)

In operation 2001

Voltage: ±400 kV LCC

Monopolar with marine electrodes

Rated power: 500 MW

Nominal Current : 1250 A

Length 316 km ( dc UG -OFcable 43 km

Italy side , 160 km sea cable and 113 km

dcOHL Greek side )

TERNA HVDC Plants

Page 17: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

HVDC link that increases security

of supply and improves market

competitiveness in Sardinia

• Voltage: ±500 kV LCC

(Line Commutate ConverterThyristor water cooling)

• Rated power: 1.000 MW

HVDC LINK SARDINIA-MAINLAND

«SAPEI» In Operation 2011The longest HVDC cable at time of construction

(435 km)

The world deepest submarine HVDC cable

(1.640 m)

TERNA HVDC Plants

Page 18: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

Under construction

New HVDC interconnection

• Voltage: ±500 kV LCC(Bipolar )

• Rated power: 1.200 MW

Length 400 km.

Depth: 1200 m

NEW INTERCONNECTION ITALY-MONTENEGROFirst electricity HVDC link

between Europe and the

Balkans

TERNA HVDC Plants

Page 19: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

SACOI GRITA SAPEI MONITAManufacturer Converter / Thyristor

GE-Ansaldo ABB ABB TOSHIBA / Infineon

Valve Number 12 12 12 12Modules for Valve 7 10 8 3+3Thyristors for Module 8 6 9 12+13Number Thyristors for valve…

56 60 72 75

…redundancy 3 2 3 3Number Thyristors for a pole

672 720 864 900

AccensioneETT=elettrically triggered thyristorLTT=light triggered thyristor

ETT ETT ETT LTT

Thyristor Current [A] 1500 1250 1000 1200Tensione tiristore VBO [kV]

4,5 8,5 7,5

Cooling air water water water

TERNA HVDC Plants

Page 20: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

Under construction

New HVDC interconnection

• Voltage: ±320 kV VSC

(Voltage Source Converter)• Rated power: 2x600 MW

• Total length 190 km

NEW INTERCONNECTION FRANCE-ITALY

• The first synergy between HVDC link and highway

infrastructure crossing Alps in Service Tunnel of

Frejus

TERNA HVDC Plants

Page 21: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

21

What are main challenges for HVDC

Economics

Long Duration of Design ( all phases)

Obsolescence Risks-Life exstension

Authorization/ Environmental Phases Risks

Technological Risks ( some cases)

Page 22: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

22

Economics

Page 23: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

23

Substation cost

Trasmission Line costs

Reactive Power Compensation costs

Operation & Maintenance costs

Loss evaluation costs

Right of way costs

Economics

Page 24: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

24

Other economics evaluationto consider

Economics

Page 25: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

25

Long Duration of Design ( all phases)

Page 26: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

26

2003 -Feasibility Study

2010 New evaluation !!

Due to economical crisis and phase out of some Thermal PP in Sardinia the ESCR falls down in the range 1,4-1,7 p.u. !

Long Duration of Design ( all phases)

Page 27: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

27

Long Duration of Design ( all phases)

Page 28: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

28

AGEING Lifetime

Spare parts criteria

Digital Control System:Life time critical point

Obsolescence Risks

Page 29: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

Fast development of new power electronics devices while beneficial in terms of technology improvement may be an issue for recently proposed projects, in terms of technology obsolescence.Obsolescent topologies:• 2 and 3 level large HVDC VSC links started

commercial operation in the 2000s (Cross Sound,Murraylink ). Nowadays this topology is alreadyobsolete.

• DC neutral is ungrounded in most recent modularmultilevel converter up to 320 kV. DC groundingwill most probably be adopted in the future forhigher voltage level.

Obsolescent power electronics:• IGCT ( Integrated-Gate Commutated Thyristor )

IGBT ( Insulated-Gate Bipolar Transistor)• Press Pack (direct / indirect pressure)• Silicon Carbide ( SiC ) power device in the future.

Obsolescence Risks

Page 30: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

- 30 -

Technological Risks :operating experience important factor

In order to verify the quality of the operatingdata, TERNA has adopted the requirements ofthe protocol established by the B4 Committee ofC.I.G.R.E.

In the follwing slides are summarized the resultsof operation of SACOI2 link from 1993 to 2013

Page 31: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

SA.CO.I.2 Report of performances 1993-2013 (1/3)

The figure 3 shows that the availability ofthe Link is almost a constant value from 1993to 2013 (above 90% ).

The utilization of the link has been growingfrom 2002 (average 58.44%) compared to arather low average (33.72%) in previousyears.

Fig.2 Direction of power flow between Sardinia and Tuscany

Fig.3 Energy utilization (U) and Energy Availability (EA)

Direzione Ingegneria

Fig.1 Total Energy transmitted

Page 32: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

SA.CO.I Report of performances 1993-2013 (2/3)

Failures on cable have a big impact on the total forcedoutage period (91%), but slightly affect the values ofreliability because the presence of the second cableallows to operate the link even if with reducedperformance 50%

Figure 6 FEU in equivalent outage hours

CAUSE OF FAILURE OF CABLES FROM 1967 TO 2013

Page 33: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

SA.CO.I Report of performances 1993-2013 (3/3)

Fig.6 Main substation forced outageFigures 7 and 8 show in terms of equivalent hours and percentage,forced outages attributable to the main converter stations.

• The control and protection system and the AC yardequipments (especially the filters) are the two leading causes.

• No problem with thyristors;the total number of failures is not increasing

Fig.8 Breakdown of substation forced outage by equipment categories

Fig. 7

Fig. 9

Page 34: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

34

Technological Risks: Fire

GRITA DESIGN Improve requirements vs Fire Events

Fire Risk in these years become very important because of several disastrous fire incidents in HVDC Plants ,the last occurred in autumn 1993 in Sylmar East Station full destroying one quadruple valve.

Page 35: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

35

Model scenario of fire in valve hall was used for computer simulation.Oil spill fire was based on insulation oil spread out on the floor while the fire in the thyristor module was upper 4 meters below ceiling ( impact on average T gas layer).Smoke ventilation in operation.

Page 36: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

36

-Mimize amount of combustible material – Material selection and mechanical features-Sectionize equipment and segregation barriers to prevent spread of fire or leak water-valves designed exclude corona in operation voltage to avoid degradation of plastic materials( checked type and routine test)-Detect a fire in incipient stage using Fast Acting ( <10’) Fire Detection devices ( like VESDA or IFD )-Exstinguish a possible fire-Minimize secondary damages caused by increased T and combustion product

VALVE HALL CRITERIA adopted vs. RISK of FIRE

Page 37: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

37

Technological Risks: Fire

To keep oil filled equipment out of valve hallwas decided to avoid oil smoothing reactorand using air cooled type smoothing reactor

Page 38: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

38

Technological Risks: Earthquake

GRITA DESIGN Improve requirements bothConverter Station vs Earthquake , do to Arachtossite

Suspended Valves

The seismic design of the CS equiment was based onTwo level severity:OBE and MDE ( Maximum Design Eartquake).Qualification methods followsTest procedure and seismicverification was developed with a linear elastic modal analysisprocedure.

Page 39: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

Technological Risks:Transport

Page 40: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

Technological Risks: Permitting Phase Risks

SAPEI Architecture Design To Improve public acceptance and speedup Permitting phase

SAPEI Marine Impact Assessment on mammals life ( dolphins, whales etc)

Page 41: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

Technological Risks: Converter Transformer failure risk

SAPEI PROJECT : After design review was performed a special test : short circuit on unit of Converter Transformer at KEMA Platform test.

Page 42: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

Technological Risks: Pollution and Insulation

GRITA design taking in to consideration 500 kV wall bushingsflash over( mainly in rainy weather )

in Ghenzuoba -ShangaiHVDC System experience .Was installed a silicone bushing rather thanporcelain

SAPEI adopted indoor type Solution for all equipment in Sardinia side for salt and coal pollution

Page 43: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

Technological Risks: Pollution and Insulation

Page 44: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR

Technological Risks: Organization Task

More than 70 people TSO involved in SAPEI Project Management and Test

Page 45: CIGRE ATLAS OF HVDC SYSTEMS WITH ITALIAN TSO …convegni.aeit.it/HVDC2017/wkspvnc/02_00_Rebolini.pdf ·  · 2017-03-31New Market analysis (1) gives grow of HVDC Converter at a CAGR