Transmission lines
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
• Transmission lines constitute more than 60%
transmission.
• They traverse an incredible range of kilomet
environments, climates and terrains.
• In India man
y of the Transmission lines curr
were built in the 1960s and 70s and are sub
problems including ageing.
• With growing demands, there is huge expec
transmission companies to keep the transmnear to 100%.
• Hence accurate fault location, health check
same is very much essential.
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
3/30
Type of
commonfaults inoverheadTransmissionlines
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
All T
ypes of Open & Short Categ
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
4/30
Overhead
Transmissionline faultlocator &
Analyzer
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
• Pre-Commissioning Check of EHV Li
Phase Sequence, line length verifica
• Ascert
aining line healthiness befor
• For Preventive & Predictive Mainte
existing EHV Lines.
• Restore the EHV lines ASAP to main
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
5/30
FaultLocator andtypes offault locator
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
OVER HEADTRANSMISSIONLIN
LOCATOR (OHFL)
• Online
• Offline
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
6/30
OHFLBasicPrincipals ofworking
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
• ONLINE-Systems works on the prin
system Parameters & Data is taken
breakdown condition and this dataaccuracy depending on the residua
the line.
• OFFLINE-Systems works on the prin
pulse Eco Co-relation technique &any input parameters for accurate fa
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
7/30
Onlinemethodsome of it’s
limitations
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
• Each Line require one dedica
equipment.
• It is not helpful for spur lines
• Open Circuit faults can’t loc
online systems.
• Fault locating accuracy may v
percentage. (+/_ 10% or mor
• Pre-Commissioning tests are
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
8/30
Offlinemethod
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
• Advanced high frequency multip
co-relation technique
• How it works:
- High frequency Coded pulse sethe powerline
- picks up different types of distu
and location
- Information Decoded
- Generates User Friendly Report
complete vision of the line end
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
9/30
Offlinemethodsand it’sadvantages
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
• It’ is accurate up to +/- 100Mtr.
• One equipment is enough for whole
• It can be used for Spur line fault locat
• Pre –Commissioning tests are possible
• Offline system can identify the second
before re charging the line.
• It can find out Open Circuit faults.
• Does not require any complimentary
end of the sub station.
• It can Locate faults up to 2500KM.
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
10/30
OfflineOHFLDiagnosticoutputs
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
•
Fault Locator(Breakdown): For findingaccurate distance.
• Line Signature Analysis: for understan
healthiness of the line.
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
11/30
Overhead
transmissionline faultlocator
benefits
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
• Apart from finding dead faults , use
predictive and preventive mainteni) It can detect developing faults .
ii) It can detect nature of the fault(O
iii) It can indicate severity of the fault
Faults).
• Less time to find faults and its loca
• Healthiness check up for the entire
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
12/30
CaseStudies
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
• Short circuit Fault
• De-capping• All jumpers not through in Quad
• Leaky Insulators
• Clearance related problems
•
High frequency effects on transm
CASE STUDIES SHORT CIRCUIT FAULT t 112 KM
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
13/30
CASE STUDIES
Short circuit FaultDe-capping
All jumpers not through inQuad lineLeaky Insulators
Clearance related problemsHigh frequency effects ontransmission lines
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
SHORT CIRCUIT FAULT at 112 KM
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
14/30
STUDIES
Short circuit FaultDe-capping All jumpers not through inQuad lineLeaky InsulatorsClearance relatedproblemsHigh frequency effects ontransmission linesPrashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
Decapping Fault at 69 Km in B
Decapping
Fault
STUDIES ALL JUMPERS NOT THROUGH AT
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
15/30
STUDIES
Short circuit FaultDe-cappingAll jumpers not throughin Quad lineLeaky InsulatorsClearance relatedproblemsHigh frequency effects ontransmission linesPrashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
ALL JUMPERS NOT THROUGH AT
STUDIES Corona due to loose jumper
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
16/30
STUDIES
Short circuit FaultDe-capping All jumpers not through inQuad lineLeaky InsulatorsClearance relatedproblemsHigh frequency effects ontransmission linesPrashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
Corona due to loose jumper
STUDIESSIGNATURE AFTER THROUGH JUMPER
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
17/30
STUDIES
Short circuit FaultDe-capping All jumpers not through inQuad lineLeaky InsulatorsClearance relatedproblemsHigh frequency effects ontransmission linesPrashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
SIGNATURE AFTER THROUGH JUMPER
STUDIES Flashover insulator at 5 8 and 5 3 KM
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
18/30
STUDIES
Short circuit FaultDe-capping All jumpers not through inQuad lineLeaky InsulatorsClearance relatedproblemsHigh frequency effects ontransmission linesPrashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
Flashover insulator at 5.8 and 5.3 KM
STUDIES
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
19/30
STUDIES
Short circuit FaultDe-capping All jumpers not through inQuad lineLeaky InsulatorsClearance relatedproblemsHigh frequency effects ontransmission linesPrashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
STUDIES Trees very close to Transmission Line in
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
20/30
STUDIES
Short circuit FaultDe-capping All jumpers not through inQuad lineLeaky InsulatorsClearance relatedproblemsHigh frequency effects ontransmission linesPrashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
Trees very close to Transmission Line in
STUDIES After Removal of trees
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
21/30
STUDIES
Short circuit FaultDe-capping All jumpers not through inQuad lineLeaky InsulatorsClearance relatedproblemsHigh frequency effects ontransmission linesPrashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
After Removal of trees
STUDIES
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
22/30
STUDIES
Short circuit FaultDe-capping All jumpers not through inQuad lineLeaky InsulatorsClearance relatedproblemsHigh frequency effects ontransmission linesPrashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
• Line Signature Analyser could identify the
caused by high frequency noise flowing o
insulators and flashover.
• Line Signature Analyser printout with an
reveal the presence of several kV’s of high
and really a cause for flash over of insulators
• The noise was later found due to paralle
thyristor switching action
STUDIESAnnexure
–A without filter
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
23/30
STUDIES
Short circuit FaultDe-capping All jumpers not through in
Quad lineLeaky InsulatorsClearance relatedproblemsHigh frequency effects ontransmission linesPrashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
Padghe – BBLR – gain 1 without filter-Lots of n
STUDIESAnnexure
–B with HVDC filter
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
24/30
STUDIES
Short circuit FaultDe-capping All jumpers not through in
Quad lineLeaky InsulatorsClearance relatedproblemsHigh frequency effects ontransmission linesPrashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
Padghe – BBLR – Gain1 No noise observed
CASE
Case Studies of 25 lines taken in a Transmission ZONE during 2011-2012 . Statistics arrecord maintained for 365 days
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
25/30
CASESTUDIES
OFFLINEOVERHEADLINE FAULTLOCATOR
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
record maintained for 365 days
Line
Lengths in
KMs
Without
OHFL time
taken to
rectify the
fault in a
line (Hrs)
With
OHFL
time
taken to
rectify
fault in a
line
(Hrs)
No. Of
Lines in
the Zone
(Total
Sample 25
lines)
Average
No. of
Tripping
in a
Year/Line
Total
Trippi
ngs in
a Year
Ideally
with
OHFL
time
would
have
taken
OHFL
used
at
Time
taken to
find
fault
with
OHFL in
( Hrs)
O
u
0 to 150
KMs15 3 19 3 57
171
hrs
30
places
90
hrs p
150 to
250 Kms19 4 4 2 8
32
hrs
5
Places
20
hrs P
250 to
350 Kms23 4 2 2 4
16
hrs
1
places
4
hrs p
Case
C St di f 73 li i Utilit T i i
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
26/30
CaseStudies
OFFLINE OHFL
Line
Signature
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
Case Studies of 73 new lines in a Utility Transmission
KV of the line No.of Lines
No of Tripping
Without Line
Signature test
No.of Lines signatu
test was done
132KV 5 3 3
220KV 20 11 9
400KV 40 16 14
765KV 8 3 3
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
27/30
Importantparameters-
whilechoosing anoverheadtransmis
sion line faultlocator
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
• Equipment should be Portable & Ba
•Induction Voltage Suppression capa
• Auto Impedance matching facility f
used in any EHV Lines.
• Instrument should be EMI/EMC Co
PAPER
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
28/30
PAPER
Presented by
POWERGRID IN CBIP– INTERNATIONALCONFERENCE
Using Offline FaultLocator
TO DIAGNOSE THETRANSMISSION LINE
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
mailto:[email protected]://www.tauruspowertronics.com/http://www.tauruspowertronics.com/mailto:[email protected]
8/17/2019 CIGRE-Over Head Line Fault Locator
29/30
8/17/2019 CIGRE-Over Head Line Fault Locator
30/30
Thank
you foryour
attendan
ce
Prashant Das Tauruspowertronics Pvt. Ltd
[email protected] www.tauruspowertronics.com
For more information Write to :
PRASHANT DAS
prashant.das@tauruspowertronic
+91 9766355355
mailto:[email protected]://www.tauruspowertronics.com/mailto:[email protected]:[email protected]://www.tauruspowertronics.com/mailto:[email protected]