CITY MULTI
DATA G8
SYSTEM DESIGN Y SERIES
SYSTEM DESIGN Y SERIES
1. Electrical work.................................................................................................................................................. 4 - 361-1.General cautions ....................................................................................................................................... 4 - 361-2.Power supply for Indoor unit and Outdoor unit .......................................................................................... 4 - 371-3.Power cable specifications ........................................................................................................................ 4 - 431-4.Power supply examples............................................................................................................................. 4 - 44
2. M-NET control.................................................................................................................................................. 4 - 472-1.Transmission cable length limitation.......................................................................................................... 4 - 472-2.Transmission cable specifications ............................................................................................................. 4 - 482-3.System configuration restrictions............................................................................................................... 4 - 492-4.Address setting.......................................................................................................................................... 4 - 52
3. Piping Design................................................................................................................................................... 4 - 653-1.R410A Piping material ............................................................................................................................... 4 - 653-2.Piping Design ............................................................................................................................................ 4 - 663-3.Refrigerant charging calculation ................................................................................................................ 4 - 69
4. Outdoor Installation.......................................................................................................................................... 4 - 704-1.Requirement on installation site ................................................................................................................ 4 - 704-2.Spacing...................................................................................................................................................... 4 - 714-3.Piping direction .......................................................................................................................................... 4 - 734-4.Weather countermeasure .......................................................................................................................... 4 - 784-5.Caution on selecting outdoor units ............................................................................................................ 4 - 80
5. Caution for refrigerant leakage ........................................................................................................................ 4 - 815-1.Refrigerant property................................................................................................................................... 4 - 815-2.Confirm the Critical concentration and take countermeasure.................................................................... 4 - 81
1. Electrical work DATA G8
SYSTEM DESIGN 4 - 36
Syst
em Y
I.1. Electrical work1-1. General cautions
OK NO
Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiringregulations, and guidance of each electric power company.Wiring for control (hereinafter referred to as transmission cable) shall be (50mm[1-5/8in.] or more) apart from power sourcewiring so that it is not influenced by electric noise from power source wiring. (Do not insert transmission cable and power source wire in the same conduit.)Be sure to provide designated grounding work to outdoor unit.Give some allowance to wiring for electrical part box of indoor and outdoor units, because the box is sometimes removedat the time of service work.Never connect 380~415V(220~240V) power source to terminal block of transmission cable. If connected,electrical partswill be burnt out.Use 2-core shield cable for transmission cable. If transmission cables of different systems are wired with the samemultiple-core cable, the resultant poor transmitting and receiving will cause erroneous operations.
Outdoorunit
Indoor unit
Remote
BC controllercontroller
2-core shield cable
2-core shield cable
Outdoorunit
Remotecontroller
Indoor unit
Multiple-core cable
BC controller
4 - 37
1. Electrical work DATA G8
SYSTEM DESIGN
System Y
1-2. Power supply for Indoor unit and Outdoor unit1-2-1. Electrical characteristics of Indoor unit
Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Motor Output : Fan motor rated output
PMFY-P-VBM-EPower supply IFM
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PMFY-P20VBM-E
220-240V / 50Hz220V / 60Hz
Max.: 264VMin.: 198V
0.25 0.028 0.20PMFY-P25VBM-E 0.26 0.028 0.21PMFY-P32VBM-E 0.26 0.028 0.21PMFY-P40VBM-E 0.33 0.028 0.26
PLFY-P-VCM-EPower supply IFM
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PLFY-P20VCM-E
220-240V / 50Hz Max.: 264VMin.: 198V
0.29 0.011 0.23PLFY-P25VCM-E 0.29 0.015 0.23PLFY-P32VCM-E 0.35 0.020 0.28PLFY-P40VCM-E 0.35 0.020 0.28
PLFY-P-VBM-EPower supply IFM
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PLFY-P32VBM-E
220-240V / 50Hz220V / 60Hz
Max.: 264VMin.: 198V
0.28 0.050 0.22PLFY-P40VBM-E 0.36 0.050 0.29PLFY-P50VBM-E 0.36 0.050 0.29PLFY-P63VBM-E 0.45 0.050 0.36PLFY-P80VBM-E 0.64 0.050 0.51PLFY-P100VBM-E 1.25 0.120 1.00PLFY-P125VBM-E 1.34 0.120 1.07
PLFY-P-VLMD-EPower supply IFM
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PLFY-P20VLMD-E
220-240V / 50Hz220-230V / 60Hz
Max.: 264VMin.: 198V
0.45 / 0.46 0.015 0.36 / 0.37PLFY-P25VLMD-E 0.45 / 0.46 0.015 0.36 / 0.37PLFY-P32VLMD-E 0.45 / 0.46 0.015 0.36 / 0.37PLFY-P40VLMD-E 0.50 / 0.53 0.015 0.40 / 0.42PLFY-P50VLMD-E 0.51 / 0.54 0.020 0.41 / 0.43PLFY-P63VLMD-E 0.61 / 0.64 0.020 0.49 / 0.51PLFY-P80VLMD-E 0.90 / 0.93 0.020 0.72 / 0.74PLFY-P100VLMD-E 0.94 / 1.10 0.030 0.75 / 0.88PLFY-P125VLMD-E 1.69 / 1.69 0.078x2 1.35 / 1.35
PEFY-P-VMR-E-L/RPower supply IFM
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PEFY-P20VMR-E-L/R
220-240V / 50Hz220-230V / 60Hz
Max.: 264VMin.: 198V
0.37 / 0.37 0.018 0.29 / 0.29PEFY-P25VMR-E-L/R 0.37 / 0.37 0.018 0.29 / 0.29PEFY-P32VMR-E-L/R 0.43 / 0.48 0.023 0.34 / 0.38
PEFY-P-VMS1-EPower supply IFM
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PEFY-P15VMS1-E
220-240V / 50Hz220-240V / 60Hz
Max.: 264VMin.: 198V
0.63 / 0.63 0.096 0.50 / 0.50PEFY-P20VMS1-E 0.70 / 0.70 0.096 0.56 / 0.56PEFY-P25VMS1-E 0.75 / 0.75 0.096 0.60 / 0.60PEFY-P32VMS1-E 0.75 / 0.75 0.096 0.60 / 0.60PEFY-P40VMS1-E 0.83 / 0.82 0.096 0.66 / 0.65PEFY-P50VMS1-E 1.02 / 1.00 0.096 0.81 / 0.80PEFY-P63VMS1-E 1.08 / 1.07 0.096 0.86 / 0.85
1. Electrical work DATA G8
SYSTEM DESIGN 4 - 38
Syst
em Y
Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Motor Output : Fan motor rated output
PEFY-P-VMS1L-EPower supply IFM
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PEFY-P15VMS1L-E
220-240V / 50Hz220-240V / 60Hz
Max.: 264VMin.: 198V
0.46 / 0.46 0.096 0.37 / 0.37PEFY-P20VMS1L-E 0.54 / 0.54 0.096 0.43 / 0.43PEFY-P25VMS1L-E 0.59 / 0.59 0.096 0.47 / 0.47PEFY-P32VMS1L-E 0.59 / 0.59 0.096 0.47 / 0.47PEFY-P40VMS1L-E 0.68 / 0.68 0.096 0.54 / 0.54PEFY-P50VMS1L-E 0.84 / 0.84 0.096 0.67 / 0.67PEFY-P63VMS1L-E 0.91 / 0.91 0.096 0.73 / 0.73
PEFY-P-VMH-EPower supply IFM
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PEFY-P40VMH-E
220-240V / 50Hz220-240V / 60Hz
Max.: 264VMin.: 198V
1.21 / 1.61 0.08 0.97 / 1.29PEFY-P50VMH-E 1.21 / 1.61 0.08 0.97 / 1.29PEFY-P63VMH-E 1.49 / 1.95 0.12 1.19 / 1.56PEFY-P71VMH-E 1.58 / 2.18 0.14 1.26 / 1.74PEFY-P80VMH-E 1.85 / 2.40 0.18 1.48 / 1.92PEFY-P100VMH-E 3.03 / 3.93 0.26 2.42 / 3.14PEFY-P125VMH-E 3.03 / 3.93 0.26 2.42 / 3.14PEFY-P140VMH-E 3.10 / 3.98 0.26 2.48 / 3.18PEFY-P200VMH-E 380-415V / 50Hz
380-415V / 60HzMax.: 456VMin.: 342V
2.03 / 2.33 0.76 1.62 / 1.86PEFY-P250VMH-E 2.50 / 2.88 1.08 2.00 / 2.30
PEFY-P-VMA-EPower supply IFM
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PEFY-P20VMA-E
220-240V / 50Hz220-240V / 60Hz
Max.: 264VMin.: 198V
1.03 0.085 0.82PEFY-P25VMA-E 1.03 0.085 0.82PEFY-P32VMA-E 1.18 0.085 0.95PEFY-P40VMA-E 1.43 0.085 1.14PEFY-P50VMA-E 1.54 0.085 1.23PEFY-P63VMA-E 2.22 0.121 1.78PEFY-P71VMA-E 2.46 0.121 1.97PEFY-P80VMA-E 2.47 0.121 1.98PEFY-P100VMA-E 3.30 0.244 2.64PEFY-P125VMA-E 3.39 0.244 2.71PEFY-P140VMA-E 3.29 0.244 2.63
PEFY-P-VMAL-EPower supply IFM
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PEFY-P20VMAL-E
220-240V / 50Hz220-240V / 60Hz
Max.: 264VMin.: 198V
0.92 0.085 0.74PEFY-P25VMAL-E 0.92 0.085 0.74PEFY-P32VMAL-E 1.07 0.085 0.86PEFY-P40VMAL-E 1.32 0.085 1.06PEFY-P50VMAL-E 1.40 0.085 1.12PEFY-P63VMAL-E 2.08 0.121 1.67PEFY-P71VMAL-E 2.32 0.121 1.86PEFY-P80VMAL-E 2.36 0.121 1.89PEFY-P100VMAL-E 3.19 0.244 2.55PEFY-P125VMAL-E 3.27 0.244 2.62PEFY-P140VMAL-E 3.17 0.244 2.53
PEFY-P-VMH-E-FPower supply IFM
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PEFY-P80VMH-E-F 220-240V / 50Hz
208-230V / 60HzMax.: 264VMin.: 187V
0.92 / 1.15 0.09 0.73 / 0.92PEFY-P140VMH-E-F 1.58 / 1.84 0.14 1.26 / 1.47PEFY-P200VMH-E-F 380-415V / 50Hz
380-415V / 60HzMax.: 456VMin.: 342V
0.73 / 0.93 0.20 0.58 / 0.74PEFY-P250VMH-E-F 0.85 / 1.08 0.23 0.68 / 0.86
4 - 39
1. Electrical work DATA G8
SYSTEM DESIGN
System Y
Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Motor Output : Fan motor rated output
PKFY-P-VBM-EPower supply IFM
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PKFY-P15VBM-E
220-240V / 50Hz220V / 60Hz
Max.: 264VMin.: 198V
0.25 0.017 0.20PKFY-P20VBM-E 0.25 0.017 0.20PKFY-P25VBM-E 0.25 0.017 0.20
PKFY-P-VHM-EPower supply IFM
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PKFY-P32VHM-E
220-240V / 50Hz220V / 60Hz
Max.: 264VMin.: 198V
0.38 0.030 0.30PKFY-P40VHM-E 0.38 0.030 0.30PKFY-P50VHM-E 0.38 0.030 0.30
PKFY-P-VKM-EPower supply IFM
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PKFY-P63VKM-E 220-240V / 50Hz
220V / 60HzMax.: 264VMin.: 198V
0.36 0.056 0.29PKFY-P100VKM-E 0.63 0.056 0.50
PCFY-P-VKM-EPower supply IFM
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PCFY-P40VKM-E
220-240V / 50Hz220V / 60Hz
Max.: 264VMin.: 198V
0.35 0.090 0.28PCFY-P63VKM-E 0.41 0.095 0.33PCFY-P100VKM-E 0.81 0.160 0.65PCFY-P125VKM-E 0.95 0.160 0.76
PFFY-P-VKM-EPower supply IFM
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PFFY-P20VKM-E
220-240V / 50Hz Max.: 264VMin.: 198V
0.25 0.03x2 0.20PFFY-P25VKM-E 0.25 0.03x2 0.20PFFY-P32VKM-E 0.25 0.03x2 0.20PFFY-P40VKM-E 0.30 0.03x2 0.24
PFFY-P-VLEM-EPower supply IFM
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PFFY-P20VLEM-E
220-240V / 50Hz208-230V / 60Hz
Max.: 264VMin.: 187V
0.24 / 0.31 0.015 0.19 / 0.25PFFY-P25VLEM-E 0.24 / 0.31 0.015 0.19 / 0.25PFFY-P32VLEM-E 0.36 / 0.38 0.018 0.29 / 0.30PFFY-P40VLEM-E 0.40 / 0.41 0.030 0.32 / 0.33PFFY-P50VLEM-E 0.50 / 0.51 0.035 0.40 / 0.41PFFY-P63VLEM-E 0.58 / 0.59 0.050 0.46 / 0.47
1. Electrical work DATA G8
SYSTEM DESIGN 4 - 40
Syst
em Y
Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Motor Output : Fan motor rated output
PFFY-P-VLRM-EPower supply IFM
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PFFY-P20VLRM-E
220-240V / 50Hz208-230V / 60Hz
Max.: 264VMin.: 187V
0.24 / 0.31 0.015 0.19 / 0.25PFFY-P25VLRM-E 0.24 / 0.31 0.015 0.19 / 0.25PFFY-P32VLRM-E 0.36 / 0.38 0.018 0.29 / 0.30PFFY-P40VLRM-E 0.40 / 0.41 0.030 0.32 / 0.33PFFY-P50VLRM-E 0.50 / 0.51 0.035 0.40 / 0.41PFFY-P63VLRM-E 0.58 / 0.59 0.050 0.46 / 0.47
PFFY-P-VLRMM-EPower supply IFM
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PFFY-P20VLRMM-E
220-240V / 50Hz Max.: 264VMin.: 198V
0.59 / 0.58 0.096 0.47 / 0.46PFFY-P25VLRMM-E 0.59 / 0.58 0.096 0.47 / 0.46PFFY-P32VLRMM-E 0.69 / 0.69 0.096 0.55 / 0.55PFFY-P40VLRMM-E 0.78 / 0.76 0.096 0.62 / 0.61PFFY-P50VLRMM-E 0.80 / 0.79 0.096 0.64 / 0.63PFFY-P63VLRMM-E 0.93 / 0.93 0.096 0.74 / 0.74
GUF-RDH3Power supply IFM
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)GUF-50RD(H)3 220-240V / 50Hz
220V / 60HzMax.: 264VMin.: 198V
1.85 / 1.85 0.081x2 1.48 / 1.48GUF-100RD(H)3 3.49 / 3.49 0.16x2 2.79 / 2.79
4 - 41
1. Electrical work DATA G8
SYSTEM DESIGN
System Y
1-2-2. Electrical characteristics of Outdoor unit
PUHY-P-YJM Unit CombinationUnits Power supply Compressor FAN RLA(A)(50/60Hz)
Hz Volts Voltage range MCA(A) Output(kW) SC(A) Output
(kW) Cooling Heating
PUHY-P200YJM-A(-BS) -
50/60380 400 415
Max:456V Min:342V
16.01 5.4
8
0.46 9.4 / 9.0 / 8.6 9.8 / 9.3 / 9.0
PUHY-P250YJM-A(-BS) - 18.17 6.8 0.46 12.4 / 11.8 / 11.4 12.3 / 11.7 / 11.3
PUHY-P300YJM-A(-BS) - 21.88 7.7 0.46 15.1 / 14.4 / 13.9 15.6 / 14.8 / 14.2 PUHY-P350YJM-A(-BS) - 26.75 9.9 0.46 18.5 / 17.6 / 17.0 18.8 / 17.9 / 17.2
PUHY-P400YJM-A(-BS) - 31.89 10.1 0.46 22.1 / 21.0 / 20.2 21.6 / 20.5 / 19.8
PUHY-P450YJM-A(-BS) - 37.61 11.6 0.46 26.1 / 24.8 / 23.9 24.6 / 23.4 / 22.5
PUHY-P500YSJM-A(-BS)PUHY-P250YJM-A(-BS)
37.046.8 0.46
25.9 / 24.6 / 23.7 25.3 / 24.1 / 23.2 PUHY-P250YJM-A(-BS) 6.8 0.46
PUHY-P500YSJM-A1(-BS)PUHY-P200YJM-A(-BS)
36.335.4 0.46
25.4 / 24.1 / 23.2 26.1 / 24.8 / 23.9 PUHY-P300YJM-A(-BS) 7.7 0.46
PUHY-P550YSJM-A(-BS)PUHY-P250YJM-A(-BS)
41.336.8 0.46
28.9 / 27.5 / 26.5 28.4 / 27.0 / 26.0 PUHY-P300YJM-A(-BS) 7.7 0.46
PUHY-P600YSJM-A(-BS)PUHY-P250YJM-A(-BS)
45.196.8 0.46
31.6 / 30.0 / 28.9 31.8 / 30.2 / 29.1 PUHY-P350YJM-A(-BS) 9.9 0.46
PUHY-P600YSJM-A1(-BS)PUHY-P300YJM-A(-BS)
45.767.7 0.46
32.0 / 30.4 / 29.3 32.5 / 30.8 / 29.7 PUHY-P300YJM-A(-BS) 7.7 0.46
PUHY-P650YSJM-A(-BS)PUHY-P300YJM-A(-BS)
49.27.7 0.46
34.4 / 32.7 / 31.5 34.5 / 32.8 / 31.6 PUHY-P350YJM-A(-BS) 9.9 0.46
PUHY-P700YSJM-A(-BS)PUHY-P350YJM-A(-BS)
54.29.9 0.46
37.9 / 36.0 / 34.7 37.5 / 35.7 / 34.4 PUHY-P350YJM-A(-BS) 9.9 0.46
PUHY-P700YSJM-A1(-BS)PUHY-P300YJM-A(-BS)
55.637.7 0.46
38.9 / 36.9 / 35.6 38.9 / 37.0 / 35.6 PUHY-P400YJM-A(-BS) 10.1 0.46
PUHY-P750YSJM-A(-BS)PUHY-P350YJM-A(-BS)
59.499.9 0.46
41.6 / 39.6 / 38.1 41.6 / 39.5 / 38.1 PUHY-P400YJM-A(-BS) 10.1 0.46
PUHY-P800YSJM-A(-BS)PUHY-P350YJM-A(-BS)
65.369.9 0.46
45.7 / 43.4 / 41.8 43.3 / 41.2 / 39.7 PUHY-P450YJM-A(-BS) 11.6 0.46
PUHY-P800YSJM-A1(-BS)PUHY-P400YJM-A(-BS)
64.7810.1 0.46
45.3 / 43.0 / 41.5 45.6 / 43.3 / 41.7 PUHY-P400YJM-A(-BS) 10.1 0.46
PUHY-P850YSJM-A(-BS)PUHY-P400YJM-A(-BS)
71.510.1 0.46
50.0 / 47.5 / 45.7 47.9 / 45.5 / 43.9 PUHY-P450YJM-A(-BS) 11.6 0.46
PUHY-P900YSJM-A(-BS)PUHY-P450YJM-A(-BS)
77.3711.6 0.46
54.1 / 51.4 / 49.5 50.7 / 48.1 / 46.4 PUHY-P450YJM-A(-BS) 11.6 0.46
PUHY-P950YSJM-A(-BS)
PUHY-P250YJM-A(-BS)
73.51
6.8 0.46
51.4 / 48.9 / 47.1 50.6 / 48.1 / 46.4 PUHY-P300YJM-A(-BS) 7.7 0.46PUHY-P400YJM-A(-BS) 10.1 0.46
PUHY-P1000YSJM-A(-BS)
PUHY-P300YJM-A(-BS)
77.37
7.7 0.46
54.1 / 51.4 / 49.6 55.9 / 53.1 / 51.2 PUHY-P300YJM-A(-BS) 7.7 0.46PUHY-P400YJM-A(-BS) 10.1 0.46
PUHY-P1050YSJM-A(-BS)
PUHY-P300YJM-A(-BS)
81.51
7.7 0.46
57.0 / 54.2 / 52.2 57.5 / 54.6 / 52.7 PUHY-P350YJM-A(-BS) 9.9 0.46PUHY-P400YJM-A(-BS) 10.1 0.46
PUHY-P1100YSJM-A(-BS)
PUHY-P350YJM-A(-BS)
86.23
9.9 0.46
60.3 / 57.3 / 55.2 60.9 / 57.8 / 55.7 PUHY-P350YJM-A(-BS) 9.9 0.46PUHY-P400YJM-A(-BS) 10.1 0.46
PUHY-P1150YSJM-A(-BS)
PUHY-P350YJM-A(-BS)
92.53
9.9 0.46
64.7 / 61.4 / 59.2 62.9 / 59.7 / 57.6 PUHY-P350YJM-A(-BS) 9.9 0.46PUHY-P450YJM-A(-BS) 11.6 0.46
PUHY-P1200YSJM-A(-BS)
PUHY-P350YJM-A(-BS)
98.53
9.9 0.46
68.9 / 65.4 / 63.1 66.2 / 62.9 / 60.6 PUHY-P400YJM-A(-BS) 10.1 0.46PUHY-P450YJM-A(-BS) 11.6 0.46
PUHY-P1250YSJM-A(-BS)
PUHY-P350YJM-A(-BS)
103.54
9.9 0.46
72.4 / 68.8 / 66.3 68.9 / 65.5 / 63.1 PUHY-P450YJM-A(-BS) 11.6 0.46PUHY-P450YJM-A(-BS) 11.6 0.46
1. Electrical work DATA G8
SYSTEM DESIGN 4 - 42
Syst
em Y
PUHY-EP-YJM Unit CombinationUnits Power supply Compressor FAN RLA(A)(50/60Hz)
Hz Volts Voltage range MCA(A) Output(kW) SC(A) Output
(kW) Cooling Heating
PUHY-EP200YJM-A(-BS) -
50/60380 400 415
Max:456V Min:342V
16.01 5.4
8
0.46 8.5 / 8.1 / 7.8 9.3 / 8.8 / 8.5 PUHY-EP250YJM-A(-BS) - 18.17 6.8 0.46 11.3 / 10.7 / 10.4 12.0 / 11.4 / 11.0
PUHY-EP300YJM-A(-BS) - 21.88 7.7 0.46 13.5 / 12.8 / 12.4 14.1 / 13.4 / 12.9
PUHY-EP400YSJM-A(-BS)PUHY-EP200YJM-A(-BS)
24.895.4 0.46
17.4 / 16.5 / 15.9 19.2 / 18.2 / 17.6 PUHY-EP200YJM-A(-BS) 5.4 0.46
PUHY-EP450YSJM-A(-BS)PUHY-EP200YJM-A(-BS)
28.65.4 0.46
20.0 / 19.0 / 18.3 21.7 / 20.6 / 19.9 PUHY-EP250YJM-A(-BS) 6.8 0.46
PUHY-EP500YSJM-A(-BS)PUHY-EP200YJM-A(-BS)
32.045.4 0.46
22.4 / 21.3 / 20.5 24.1 / 22.9 / 22.0 PUHY-EP300YJM-A(-BS) 7.7 0.46
PUHY-EP500YSJM-A1(-BS)PUHY-EP250YJM-A(-BS)
32.896.8 0.46
23.0 / 21.8 / 21.0 24.5 / 23.3 / 22.4 PUHY-EP250YJM-A(-BS) 6.8 0.46
PUHY-EP550YSJM-A(-BS)PUHY-EP250YJM-A(-BS)
37.046.8 0.46
25.9 / 24.6 / 23.7 26.6 / 25.3 / 24.3 PUHY-EP300YJM-A(-BS) 7.7 0.46
PUHY-EP600YSJM-A(-BS)PUHY-EP300YJM-A(-BS)
40.477.7 0.46
28.3 / 26.9 / 26.0 29.2 / 27.7 / 26.7 PUHY-EP300YJM-A(-BS) 7.7 0.46
PUHY-EP650YSJM-A(-BS)
PUHY-EP200YJM-A(-BS)
42.05
5.4 0.46
29.4 / 28.0 / 26.9 31.3 / 29.7 / 28.6 PUHY-EP200YJM-A(-BS) 5.4 0.46PUHY-EP250YJM-A(-BS) 6.8 0.46
PUHY-EP700YSJM-A(-BS)
PUHY-EP200YJM-A(-BS)
46.05
5.4 0.46
32.2 / 30.6 / 29.5 33.7 / 32.0 / 30.9 PUHY-EP200YJM-A(-BS) 5.4 0.46PUHY-EP300YJM-A(-BS) 7.7 0.46
PUHY-EP700YSJM-A1(-BS)
PUHY-EP200YJM-A(-BS)
46.77
5.4 0.46
32.7 / 31.1 / 30.0 34.3 / 32.5 / 31.4 PUHY-EP250YJM-A(-BS) 6.8 0.46PUHY-EP250YJM-A(-BS) 6.8 0.46
PUHY-EP750YSJM-A(-BS)
PUHY-EP200YJM-A(-BS)
49.2
5.4 0.46
34.4 / 32.7 / 31.5 37.0 / 35.1 / 33.8 PUHY-EP250YJM-A(-BS) 6.8 0.46PUHY-EP300YJM-A(-BS) 7.7 0.46
PUHY-EP750YSJM-A1(-BS)
PUHY-EP250YJM-A(-BS)
50.48
6.8 0.46
35.3 / 33.5 / 32.3 36.7 / 34.9 / 33.6 PUHY-EP250YJM-A(-BS) 6.8 0.46PUHY-EP250YJM-A(-BS) 6.8 0.46
PUHY-EP800YSJM-A(-BS)
PUHY-EP200YJM-A(-BS)
52.2
5.4 0.46
36.5 / 34.6 / 33.4 38.4 / 36.5 / 35.1 PUHY-EP300YJM-A(-BS) 7.7 0.46PUHY-EP300YJM-A(-BS) 7.7 0.46
PUHY-EP800YSJM-A1(-BS)
PUHY-EP250YJM-A(-BS)
53.49
6.8 0.46
37.4 / 35.5 / 34.2 38.7 / 36.8 / 35.5 PUHY-EP250YJM-A(-BS) 6.8 0.46PUHY-EP300YJM-A(-BS) 7.7 0.46
PUHY-EP850YSJM-A(-BS)
PUHY-EP250YJM-A(-BS)
56.92
6.8 0.46
39.8 / 37.8 / 36.4 41.6 / 39.5 / 38.1 PUHY-EP300YJM-A(-BS) 7.7 0.46PUHY-EP300YJM-A(-BS) 7.7 0.46
PUHY-EP900YSJM-A(-BS)
PUHY-EP300YJM-A(-BS)
59.78
7.7 0.46
41.8 / 39.7 / 38.3 43.0 / 40.8 / 39.4 PUHY-EP300YJM-A(-BS) 7.7 0.46PUHY-EP300YJM-A(-BS) 7.7 0.46
4 - 43
1. Electrical work DATA G8
SYSTEM DESIGN
System Y
1-3. Power cable specifications
Thickness of wire for main power supply, capacities of the switch and system impedance
ModelMinimum wire thickness (mm2)
Breaker for current leakageLocal swtich (A) Breaker for wiring
(NFB) (A)Max..Permissive
System ImpedanceMain cable Branch Ground Capacity Fuse
Outdoor unit
PUHY-(E)P200YJM 4.0 - 4.0 30A 100mA 0.1sec. or less 25 25 30 *1PUHY-(E)P250YJM 4.0 - 4.0 30A 100mA 0.1sec. or less 32 32 30 *1
PUHY-(E)P300YJM 4.0 - 4.0 30A 100mA 0.1sec. or less 32 32 30 *1
PUHY-P350YJM 6.0 - 6.0 40A 100mA 0.1sec. or less 40 40 40 0.27�PUHY-P400YJM 10.0 - 10.0 60A 100mA 0.1sec. or less 63 63 60 0.22�
PUHY-P450YJM 10.0 - 10.0 60A 100mA 0.1sec. or less 63 63 60 0.19�
Total operatingcurrent of
the indoor unit
F0 = 20 or less *2 1.5 1.5 1.5 20A current sensitivity *3 20 20 20 (apply to IEC61000-3-3)F0 = 30 or less *2 2.5 2.5 2.5 30A current sensitivity *3 30 30 30 (apply to IEC61000-3-3)
F0 = 40 or less *2 4.0 4.0 4.0 40A current sensitivity *3 40 40 40 (apply to IEC61000-3-3)
*1: Meet technical requirements of IEC61000-3-3
*2: Please take the larger of F1 or F2 as the value for F0.F1 = Total operating maximum current of the indoor units × 1.2 Indoor unit V1
F2 = (V1 × Quantity of Type A) + (V1 × Quantity of Type B) + (V1 × Quantity of Others) Type A PLFY-VBM, PMFY-VBM, PEFY-VMS1(L), PCFY-VKM, PKFY-VHM, PKFY-VKM, PFFY-VKM, PFFY-VLRMM
1.6
Type B PEFY-VMA(L) 3.2
Others Other indoor unit 0
*3: Current sensitivity is calculated using the following formula.G1 = (V2 × Quantity of Type 1) + (V2 × Quantity of Type 2) + (V2 × Quantity of Others) + (V3 × Wire length [km])
G1 Current sensitivity Indoor unit V2 Wire thickness (mm2) V3
30mA or less 30mA 0.1sec. or less Type 1 PLFY-VBM, PMFY-VBM, PEFY-VMS1(L), PCFY-VKM, PKFY-VHM, PKFY-VKM, PFFY-VKM, PFFY-VLRMM
2.4 1.5 48
100mA or less 100mA 0.1sec. or less Type 2 PEFY-VMA(L) 1.6 2.5 56
Others Other indoor unit 0 4.0 66
1. Use dedicated power supplies for the outdoor unit and indoor unit. Ensure OC and OS are wired individually.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.3. The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one rank thicker in diameter. Make sure the power-supply voltage does not drop more
than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For example, use wiring such as YZW.
6. A switch with at least 3 mm contact separation in each pole shall be provided by the Air Conditioner installer.
� Be sure to use specified wires for connections and ensure no external force is imparted to terminal connections. If connections are not fixed firmly, heating or fire may result.
� Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
� Some installation sites may require attachment of an earth leakage breaker for the inverter. If no earth leakage breaker is installed, there is a danger of electric shock.
� Do not use anything other than a breaker and fuse with the correct capacity. Using a fuse or wire of too large capacity may cause malfunction or fire.
� This device is intended for the connection to a power supply system with a maximum permissible system impedance shown in the above table at the interface point (power service box) of the user's supply.
� The user must ensure that this device is connected only to a power supply system which fulfils the requirement above.If necessary, the user can ask the public power supply company for the system impedance at the interface point.
� This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc(*2) at the interface point between the user's supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc(*2).
Ssc(*2)Model Ssc(MVA)
PUHY-(E)P200YJM 1.24
PUHY-P250YJM 1.41PUHY-EP250YJM 1.27
PUHY-P300YJM 1.70
PUHY-EP300YJM 1.51PUHY-P350YJM 2.08
PUHY-P400YJM 2.48
PUHY-P450YJM 2.92
1. Electrical work DATA G8
SYSTEM DESIGN 4 - 44
Syst
em Y
1-4. Power supply examples
The local standards and/or regulations is applicable at a higher priority.1-4-1. PUHY-P200-450YJM-A, PUHY-EP200-300YJM-A
Note4
Note3
To *1 or *2
*1
*2
Note7
Connector CN41 CN40
Power supply3-phase 4-wire380-400-415V 50/60HzNote10,13
Power supply1-phase220-240V 50/60HzNote10 Power supply
1-phase 220-240V 50/60Hz
Centralized control transmission cable>=1.25mm2
Shield cable(CVVS, CPEVS MVVS)
Indoor-outdoor transmission cable>=1.25mm2
Shield cable
Indoor-outdoor transmission cable>=1.25mm2
Shield cable
>=dia.1.6mm
(Using MA remote controller)Connecting TB5 terminal.
(Using ME remote controller)Connecting TB5 terminal.
>=dia.1.6mm
<In the case a system controller is connected.>
TB7(S)
TB1(L1,L2,L3,N)
TB3(M1,M2)
TB5(M1,M2)
TB2(L,N)S
TB15(1,2)
TB5(M1,M2)
TB2(L,N)S
TB15(1,2)
TB5(M1,M2)
TB2(L,N)S
S S
E
TB15(1,2)
TB5(M1,M2)
TB2(L,N)TB1
(R,S)TB2 TB3
S
TB15(1,2)
TB7 (M1,M2)GFI
LWWB
GFI
GFI
Power supply1-phase 220-240V 50/60Hz
LWWB
SC
TransmissionboosterNote8Note9
MA R/C MA R/C MA R/C
ME R/C ME R/C ME R/C
MA R/C cable0.3-1.25mm2
(0.75~1.25mm2)<=200mNote5, Note11
ME R/C cable0.3~1.25mm2
(0.75~1.25mm2)<=10mNote5, Note11
OU
IU (Shield)
(Shield) (Shield)
(Shield)(Shield) (Shield)
Note4
To other OU
Note6Note7
Note6Note7
* Power supply GFI, LW, WB specifications vary with the model of connected indoor units
Note7Power supply1-phase220-240V 50/60HzNote10
>=dia.1.6mm>=dia.1.6mm
TB5(M1,M2)
TB2(L,N)S
TB15(1,2)
TB5(M1,M2)
TB2(L,N)S
TB15(1,2)
TB5(M1,M2)
TB2(L,N)S
S S
E
TB15(1,2)
TB5(M1,M2)
TB2(L,N)TB1
(R,S)TB2 TB3
S
TB15(1,2)
GFILWWB
LWWB
GFILWWB
TransmissionboosterNote8Note9
IU (Shield)
(Shield) (Shield)
(Shield)(Shield) (Shield)* Power supply, GFI, LW, WB specifications vary with the model of connected indoor units
Note: 1 The transmission cable is not-polarity double-wire. 2 Symbol means a screw terminal for wiring. 3 The shield wire of transmission cable should be connected to the grounding terminal at
Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be connected to the S terminal at Indoor unit or all shield wire should be connected together. The broken line at the scheme means shield wire.
4 When the Outdoor unit connected with system controller, power-supply to TB7 of the outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the outdoor units will enable the outdoor unit to supply power to TB7, or an extra power supplying unit PAC-SC51KUA should be used. The transmission cable (above 1.25mm2, shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is called centralized control transmission cable. The shield wire of the centralized control transmission cable must be grounded at the Outdoor unit whose CN41 is changed to CN40.
5 MA R/C transmission cable (0.3-1.25mm2) must be less than 200m in length, while ME R/C transmission cable (0.3-1.25mm2) must be less than 10m in length. But transmission cable to the ME R/C can be extend using a M-NET cable (>=1.25mm2) when the length is counted in the M-Net length. Both Compact MA and ME R/C transmission cables size 0.75~1.25mm2 in thickness.
6 MA remote controller and ME remote controller should not be grouped together.7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
transmission cable to connect all the TB15 terminals of the Indoor units. It is called "Grouping". If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address Setting".
8 Indoor board consumes power from TB3. The power balance should be considered according to System Design 2-3 "System configuration restrictions".
9 If Transmission booster is needed, be sure to connect the shield wires to the both sides to the booster.
10 The critical current for choosing power source equipment is approximate 1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
11 Numbers shown with ( ) indicates a diameter of the compact remote controller.12 When System controller (SC) is connected to the system, turn the SW2-1 on.13 The phases of electricity power must be confirmed to be right used. Phase-reverse, or phase-missing could break the controllers.
Note12
Pull box
Pull box
*1 The Ground-fault interrupter should support Inverter circuit. (e.g. Mitsubishi Electric's NV-C series or equivalent).*2 Ground-fault interrupter should combine using of local switch or wiring breaker.*3 It shows data for B-type fuse of the breaker for current leakage.
Local switch Minimum Wire thickness
Earth wire<mm2>
Power wire<mm2>
Wiring breaker(NFB)<A>
OCP*3<A>
BC<A>
Ground-fault interrupter*1, *2
Model Symbol
GFILWBCOCPWBNFBOUIUSCMA R/CME R/C
Ground-fault interrupterLocal switchBreaker capacityOver-current protectorWiring breakerNon-fuse breakerOutdoor unitIndoor unitSystem controllerMA remote controllerME remote controller
PUHY- E P200YJM 30A 100mA 0.1sec. or less 25 25 30 4 4PUHY- E P250YJM 30A 100mA 0.1sec. or less 32 32 30 4 4PUHY- E P300YJM 30A 100mA 0.1sec. or less 32 32 30 4 4PUHY-P350YJM 40A 100mA 0.1sec. or less 40 40 40 6 6PUHY-P400YJM 60A 100mA 0.1sec. or less 63 63 60 10 10PUHY-P450YJM 60A 100mA 0.1sec. or less 63 63 60 10 10
4 - 45
1. Electrical work DATA G8
SYSTEM DESIGN
System Y
The local standards and/or regulations is applicable at a higher priority.1-4-2. PUHY-P500-900YSJM-A(1), PUHY-EP400-600YSJM-A(1)
Power supply3-phase 4-wire380-400-415V 50/60HzNote10,13
GFILWWB
Power supply3-phase 4-wire380-400-415V 50/60HzNote10,13
GFILWWB
Note4
Note3Note3
To *1 or *2
*1
Connector CN41 CN40
Power supply1-phase220-240V 50/60HzNote10
Centralized control transmission cable>=1.25mm2
Shield cable(CVVS, CPEVS MVVS)
Indoor-outdoortransmission cable>=1.25mm2
Shield cable
(Using MA remote controller)Connecting TB5 terminal.
>=dia.1.6mm
TB7(S)
TB7(S)
TB1(L1,L2,L3,N)TB3
(M1,M2)TB7
(M1,M2)TB3
(M1,M2)TB7
(M1,M2)
GFI
SCNote12
OU OUNote4
To other OU
* Power supply, GFI·LW·WB specifications vary with the model of connected indoor units
LWWB
<In the case a system controller is connected.>
TB1(L1,L2,L3,N)
Note: 1 The transmission cable is not-polarity double-wire. 2 Symbol means a screw terminal for wiring. 3 The shield wire of transmission cable should be connected to the grounding terminal at
Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be connected to the S terminal at Indoor unit or all shield wire should be connected together. The broken line at the scheme means shield wire.
4 When the Outdoor unit connected with system controller, power-supply to TB7 of the outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the outdoor units will enable the outdoor unit to supply power to TB7, or an extra power supplying unit PAC-SC51KUA should be used. The transmission cable (above 1.25mm2, shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is called centralized control transmission cable. The shield wire of the centralized control transmission cable must be grounded at the Outdoor unit whose CN41 is changed to CN40.
5 MA R/C transmission cable (0.3-1.25mm2) must be less than 200m in length, while ME R/C transmission cable (0.3-1.25mm2) must be less than 10m in length. But transmission cable to the ME R/C can be extend using a M-NET cable (>=1.25mm2) when the length is counted in the M-Net length. Both Compact MA and ME R/C transmission cables size 0.75~1.25mm2 in thickness.
6 MA remote controller and ME remote controller should not be grouped together.7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
transmission cable to connect all the TB15 terminals of the Indoor units. It is called "Grouping". If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address Setting".
8 Indoor board consumes power from TB3. The power balance should be considered according to System Design 2-3 "System configuration restrictions".
9 If Transmission booster is needed, be sure to connect the shield wires to the both sides to the booster.
10 The critical current for choosing power source equipment is approximate 1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
11 Numbers shown with ( ) indicates a diameter of the compact remote controller.12 When System controller (SC) is connected to the system, turn the SW2-1 on.13. The phases of electricity power must be confirmed to be right used. Phase-reverse, or phase-missing could break the controllers.
Note7
Power supply1-phase 220-240V 50/60Hz
>=dia.1.6mm
TB5(M1,M2)
TB2(L,N)S
TB15(1,2)
TB5(M1,M2)
TB2(L,N)S
TB15(1,2)
TB5(M1,M2)
TB2(L,N)S
S S
E
TB15(1,2)
TB5(M1,M2)
TB2(L,N)TB1
(R,S)TB2 TB3
S
TB15(1,2)
GFILWWB
TransmissionboosterNote8Note9
MA R/C MA R/C MA R/C
MA R/C cable0.3-1.25mm2
(0.75~1.25mm2)<=200mNote5, Note11
IU (Shield)
(Shield) (Shield)
(Shield)(Shield) (Shield)
Note6Note7
Pull box
*1 The Ground-fault interrupter should support Inverter circuit. (e.g. Mitsubishi Electric's NV-C series or equivalent).*2 Ground-fault interrupter should combine using of local switch or wiring breaker.*3 It shows data for B-type fuse of the breaker for current leakage.
Local switch Minimum Wire thickness
Earth wire<mm2>
Power wire<mm2>
Wiring breaker(NFB)<A>
OCP*3<A>
BC<A>
Ground-fault interrupter*1, *2
Model Symbol
GFILWBCOCPWBNFBOUIUSCMA R/CME R/C
Ground-fault interrupterLocal switchBreaker capacityOver-current protectorWiring breakerNon-fuse breakerOutdoor unitIndoor unitSystem controllerMA remote controllerME remote controller
PUHY-(E)P200YJM 30A 100mA 0.1sec. or less 25 25 30 4 4PUHY-(E)P250YJM 30A 100mA 0.1sec. or less 32 32 30 4 4PUHY-(E)P300YJM 30A 100mA 0.1sec. or less 32 32 30 4 4PUHY-P350YJM 40A 100mA 0.1sec. or less 40 40 40 6 6PUHY-P400YJM 60A 100mA 0.1sec. or less 63 63 60 10 10PUHY-P450YJM 60A 100mA 0.1sec. or less 63 63 60 10 10
*2
Indoor-outdoor transmission cable>=1.25mm2
Shield cable
(Using ME remote controller)Connecting TB5 terminal.
Power supply1-phase 220-240V 50/60Hz
ME R/C ME R/C ME R/C
ME R/C cable0.3~1.25mm2
(0.75~1.25mm2)<=10mNote5, Note11
Note6Note7
Note7Power supply1-phase220-240V 50/60HzNote10
>=dia.1.6mm>=dia.1.6mm
TB5(M1,M2)
TB2(L,N)S
TB15(1,2)
TB5(M1,M2)
TB2(L,N)S
TB15(1,2)
TB5(M1,M2)
TB2(L,N)S
S S
E
TB15(1,2)
TB5(M1,M2)
TB2(L,N)TB1
(R,S)TB2 TB3
S
TB15(1,2)
GFILWWB
GFILWWB
TransmissionboosterNote8Note9
IU (Shield)
(Shield) (Shield)
(Shield)(Shield) (Shield)* Power supply, GFI·LW·WB specifications vary with the model of connected indoor units
Pull box
1. Electrical work DATA G8
SYSTEM DESIGN 4 - 46
Syst
em Y
The local standards and/or regulations is applicable at a higher priority.1-4-3. PUHY-P950-1250YSJM-A, PUHY-EP650-900YSJM-A(1)
Note4
Note3Note3
Connector CN41 CN40
Centralized control transmission cable>=1.25mm2
Shield cable(CVVS, CPEVS MVVS)
TB7(S)
TB7(S)
TB1(L1,L2,L3,N)TB3
(M1,M2)TB7
(M1,M2)TB3
(M1,M2)TB7
(M1,M2)
SC
OU OU
Note3
TB7(S)
TB1(L1,L2,L3,N) TB3
(M1,M2)TB7
(M1,M2)
OUNote4
To other OU
<In the case a system controller is connected.>
To *1 or *2
*1
Power supply1-phase220-240V 50/60HzNote10
Indoor-outdoortransmission cable>=1.25mm2
Shield cable
(Using MA remote controller)Connecting TB5 terminal.
>=dia.1.6mmGFI
* Power supply, GFI·LW·WB specifications vary with the model of connected indoor units
LWWB
Note12
TB1(L1,L2,L3,N)
Note: 1 The transmission cable is not-polarity double-wire. 2 Symbol means a screw terminal for wiring. 3 The shield wire of transmission cable should be connected to the grounding terminal at
Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be connected to the S terminal at Indoor unit or all shield wire should be connected together. The broken line at the scheme means shield wire.
4 When the Outdoor unit connected with system controller, power-supply to TB7 of the outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the outdoor units will enable the outdoor unit to supply power to TB7, or an extra power supplying unit PAC-SC51KUA should be used. The transmission cable (above 1.25mm2, shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is called centralized control transmission cable. The shield wire of the centralized control transmission cable must be grounded at the Outdoor unit whose CN41 is changed to CN40.
5 MA R/C transmission cable (0.3-1.25mm2) must be less than 200m in length, while ME R/C transmission cable (0.3-1.25mm2) must be less than 10m in length. But transmission cable to the ME R/C can be extend using a M-NET cable (>=1.25mm2) when the length is counted in the M-Net length. Both Compact MA and ME R/C transmission cables size 0.75~1.25mm2 in thickness.
6 MA remote controller and ME remote controller should not be grouped together.7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
transmission cable to connect all the TB15 terminals of the Indoor units. It is called "Grouping". If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address Setting".
8 Indoor board consumes power from TB3. The power balance should be considered according to System Design 2-3 "System configuration restrictions".
9 If Transmission booster is needed, be sure to connect the shield wires to the both sides to the booster.
10 The critical current for choosing power source equipment is approximate 1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
11 Numbers shown with ( ) indicates a diameter of the compact remote controller.12 When System controller (SC) is connected to the system, turn the SW2-1 on.13. The phases of electricity power must be confirmed to be right used. Phase-reverse, or phase-missing could break the controllers.
Note7
Power supply1-phase 220-240V 50/60Hz
>=dia.1.6mm
TB5(M1,M2)
TB2(L,N)S
TB15(1,2)
TB5(M1,M2)
TB2(L,N)S
TB15(1,2)
TB5(M1,M2)
TB2(L,N)S
S S
E
TB15(1,2)
TB5(M1,M2)
TB2(L,N)TB1
(R,S)TB2 TB3
S
TB15(1,2)
GFILWWB
TransmissionboosterNote8Note9
MA R/C MA R/C MA R/C
MA R/C cable0.3-1.25mm2
(0.75~1.25mm2)<=200mNote5, Note11
IU (Shield)
(Shield) (Shield)
(Shield)(Shield) (Shield)
Note6Note7
Pull box
Power supply3-phase 4-wire380-400-415V 50/60HzNote10,13
GFILWWB
Power supply3-phase 4-wire380-400-415V 50/60HzNote10,13
GFILWWB
Power supply3-phase 4-wire380-400-415V 50/60HzNote10,13
GFILWWB
*1 The Ground-fault interrupter should support Inverter circuit. (e.g. Mitsubishi Electric's NV-C series or equivalent).*2 Ground-fault interrupter should combine using of local switch or wiring breaker.*3 It shows data for B-type fuse of the breaker for current leakage.
Local switch Minimum Wire thickness
Earth wire<mm2>
Power wire<mm2>
Wiring breaker(NFB)<A>
OCP*3<A>
BC<A>
Ground-fault interrupter*1, *2
Model Symbol
GFILWBCOCPWBNFBOUIUSCMA R/CME R/C
Ground-fault interrupterLocal switchBreaker capacityOver-current protectorWiring breakerNon-fuse breakerOutdoor unitIndoor unitSystem controllerMA remote controllerME remote controller
PUHY-(E)P200YJM 30A 100mA 0.1sec. or less 25 25 30 4 4PUHY-(E)P250YJM 30A 100mA 0.1sec. or less 32 32 30 4 4PUHY-(E)P300YJM 30A 100mA 0.1sec. or less 32 32 30 4 4PUHY-P350YJM 40A 100mA 0.1sec. or less 40 40 40 6 6PUHY-P400YJM 60A 100mA 0.1sec. or less 63 63 60 10 10PUHY-P450YJM 60A 100mA 0.1sec. or less 63 63 60 10 10
*2
Indoor-outdoor transmission cable>=1.25mm2
Shield cable
(Using ME remote controller)Connecting TB5 terminal.
Power supply1-phase 220-240V 50/60Hz
ME R/C ME R/C ME R/C
ME R/C cable0.3~1.25mm2
(0.75~1.25mm2)<=10mNote5, Note11
Note6Note7
Note7Power supply1-phase220-240V 50/60HzNote10
>=dia.1.6mm>=dia.1.6mm
TB5(M1,M2)
TB2(L,N)S
TB15(1,2)
TB5(M1,M2)
TB2(L,N)S
TB15(1,2)
TB5(M1,M2)
TB2(L,N)S
S S
E
TB15(1,2)
TB5(M1,M2)
TB2(L,N)TB1
(R,S)TB2 TB3
S
TB15(1,2)
GFILWWB
GFILWWB
TransmissionboosterNote8Note9
IU (Shield)
(Shield) (Shield)
(Shield)(Shield) (Shield)* Power supply, GFI·LW·WB specifications vary with the model of connected indoor units
Pull box
4 - 47
2. M-NET control DATA G8
SYSTEM DESIGN
System Y
2. M-NET control2-1. Transmission cable length limitation2-1-1. Using MA Remote controller
2-1-2. Using ME Remote controller
Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm2 [AWG16] or thickerMax. length to Outdoor (M-NET cable) L1+L8, L3+L4, L6, L2+L6+L8, L7 <=200m[656ft.] 1.25mm2 [AWG16] or thickerMax. length from MA to Indoor a1+a2, a1+a2+a3+a4 <=200m[656ft.] 0.3-1.25 mm2 [AWG22-16]24VDC to AG-150A n <=50m[164ft.] 0.75-2.0 mm2 [AWG18-14]
Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7,L1+L2+L3+L5, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm2 [AWG16] or thickerMax. length to Outdoor (M-NET cable) L1+L8, L3+L4, L6, L2+L6+L8, L7, L3+L5 <=200m[656ft.] 1.25mm2 [AWG16] or thickerMax. length from ME to Indoor e1, e2+e3, e4 <=10m[32ft.]*1 0.3-1.25 mm2 [AWG22-16] *124VDC to AG-150A n <=50m[164ft.] 0.75-2.0 mm2 [AWG18-14] *1. If the length from ME to Indoor exceed 10m, use 1.25 mm2 [AWG16] shielded cable, but the total length should be counted into Max. length via Outdoor.
OC, OS1, OS2 : Outdoor unit controller; IC: Indoor unit controller; MA: MA remote controller
OC, OS1, OS2: Outdoor unit controller; IC: Indoor unit controller; ME: ME remote controller
M2
TB7
TB3
IC
(52)
M1 M2 1 2STB5 TB15
1 2TB15
1 2TB15
1 2TB15
1 2TB15
1 2TB 15
1 2TB15
MA
(01)
IC
M1 M2 STB5
(02)
IC
M1 M2 STB5
(04)
IC
M1 M2 STB5
(03)
IC
M1 M2 STB5
(05)
IC
M1 M2 STB5
(07)
IC
M1 M2 STB5
(06)
L2
L1L8
MA
MA
MA
OS1
TB7
(51)
OC
M1 M2 S
TB7
TB3
(54 )
OC
a1 a4
a3
L8
L3 L4
a2
A BA B A B
A B
a2
a1
a1
a2
Group1 Group3 Group5
Shielded wire
Shielded wire
S
Power Supply Unit
AG-150A
PAC-SC51KUA
L6L2
L7
A B
SA B
M2M1 M1
M2M1
M2 S M2M1 M1 S
TB3
IC
Group1 Group3 Group5
M1 M2 STB5
ME
(01)
IC
M1 M2 STB5
(02)
IC
M1 M2 STB5
(04)
IC
M1 M2 STB5
(03)
IC
M1 M2 STB5
(05)
IC
M1 M2 STB5
(07)
IC
M1 M2 STB5
(06)
L1
(101)
ME
(105)
ME
(103)
ME
(155)
e3
L4
L5
e2
e4
e1
A B A B A B
A B
M2
TB7
TB3
(53)
OS2
M1
M2 SM1
SA B
SA B
M2
TB7
TB3
(52)
OS1
TB7
(51)
OC
M1 M2 S
TB7
TB3
(54 )
OC L3
Power Supply Unit
AG-150A
PAC-SC51KUA
L6L7
M2M1 M1
M2M1
M2 S M2M1
M2
TB7
TB3
(53)
OS2
M1
M2 SM1 M1 S
TB3
V+V-FG
n
V+V-FG
V+V-FG
n
V+V-FG
2. M-NET control DATA G8
SYSTEM DESIGN 4 - 48
Syst
em Y
2-2. Transmission cable specifications
Type of cable
Cable size
Remarks
Sheathed 2-core cable (unshielded)CVV
2
Shielding wire (2-core)CVVS, CPEVS or MVVS
Transmission cables ME Remote controller cables
CVVS, MVVS : PVC insulated PVC jacketed shielded control cableCPEVS :
Connected with simple remote controller. PE insulated PVC jacketed shielded communication cable
CVV : PV insulated PVC sheathed control cable
— Max length : 200m [656ft]
(Li) MA Remote controller cables
When 10m [32ft] is exceeded, use cables withthe same specification as transmission cables.
More than 1.25 [AWG16]2 0.3 1.25 [AWG22 16]
(0.75 1.25 [AWG18 16]) 2
2 0.3 1.25 [AWG22 16](0.75 1.25 [AWG18 16])
4 - 49
2. M-NET control DATA G8
SYSTEM DESIGN
System Y
2-3. System configuration restrictions2-3-1. Common restrictions for the CITYMULTI system
Table 2-3-1 The equivalent power consumption
Table 2-3-2 The equivalent power supply
With the equivalent power consumption values in Table 2-3-1 and Table 2-3-2, PAC-SF46EPA can be designed into theair-conditioner system to ensure proper system communication according to 2-3-2-A, B, C.2-3-2-A) Firstly, count from TB3 at TB3 side the total quantity of Indoor units, OA process units and ME remote controller, Timers
and System controllers. If the total quantity reaches 40, a PAC-SF46EPA should be set. In this case, Indoor unit sizedP200, 250 is counted as 7 Indoor units, but MA remote controller(s), LOSSNAY, PZ-60DR-E is NOT counted.
2-3-2-B) Secondly, count from TB7 side to TB3 side the total transmission power consumption. If the total power consumptionreaches 32, a PAC-SF46EPA should be set. Yet, if a PAC-SC51KUA is used to supply power at TB7 side, count fromTB3 side only.
2-3-2-C) Thirdly, count from TB7 at TB7 side the total transmission power consumption, If the total power consumption reaches6, a PAC-SF46EPA should be set.
For each Outdoor unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table. A) 1 Group of Indoor units can have 1-16 Indoor units; *OA processing unit GUF-RD(H) is considered as Indoor unit. B) Maximum 2 remote controllers for 1 Group; (MA/ME remote controllers cannot be present together in 1group.) C) 1 LOSSNAY unit can interlock maximum 16 Indoor units; 1 Indoor unit can interlock only 1 LOSSNAY unit. D) Maximum 3 System controllers are connectable when connecting to TB3 of the Outdoor unit. E) Maximum 3 System controllers are connectable when connecting to TB7 of the Outdoor unit, if the transmission power is supplied by the Outdoor unit. F) 4 System controllers or more are connectable when connecting to TB7 of the Outdoor unit, if the transmission power is supplied by the power supply unit PAC-SC51KUA. Details refer to 2-3-3-C. *System controller connected as described in D) and E) would have a risk that the failure of connected Outdoor unit would stop power supply to the System controller.
In order to ensure proper communication among Outdoor unit, Indoor unit, LOSSNAY, and OA processing unit GUF-RD(H), and Controllers, the transmission power situation for the M-NET should be observed. In some cases, Transmission booster should be used. Taking the power consumption of Indoor unit sized P20-P140 as 1, the equivalent power consumption or supply of others are listed at Table 2-3-1 and Table 2-3-2.
Indoor, OA unit Indoor unit MA RC. LOSSNAY ME Remote Contr. Timers, System Contr.
System Controller
ON/OFF Contr.
1 7 0 1/4 1/2 1 1/2 2
Sized P15-P140GUF-50, 100
Sized P200,P250
BC controller
2
CMB PAR-21MAAPAC-YT51CRA(B)PAR-FA32MALGH-RX-EPZ-60DR-E
PAR-F27MEAPAC-SE51CRAPZ-52SF-E
PAC-SC30GRAPAC-SF44SRAPAC-YT34STAAG-150A
PAC-YT40ANRA CMS-MNF-B
CMS-MNG-E
*RC : Remote Controller
Transmission Booster
25PAC-SF46EPA
Power supply unit
5PAC-SC51KUA
Expansion controller
6PAC-YG50ECA
Outdoor unit
32Connector TB3 and TB7 total *
Outdoor unit
6Connector TB7 only
*If PAC-SC51KUA is used to supply power at TB7 side, no power supply need from Outdoor unit at TB7, Connector TB3 itself will therefore have 32. Not applicable to the PUMY model.
2-3-2. Ensuring proper communication power for M-NET
MN Converter
BM ADAPTER
6BAC-HD150
6GB-50ADA
System example
Power supply unitPAC-SC51KUA
ME remote controller
ME remote controller
PZ-52SF-E
LOSSNAYunit
PZ-52SF-E
LOSSNAYunit
Outdoor unit
24VDC
M-NET
0201
if the total quantity of Indoor units, OA process units and ME remote controllers reaches 40, (Indoor unit sized P200, 250 is counted as 7); or if the total equivalent transmission power consumption reaches 32.
N1
N3
N2Transmission booster (No.1) should be used,
1.The total quantity of Indoor units, OA process units and ME remote controller should not exceed 40. *Indoor unit sized P200, 250 is counted as 7 units.2.The total equivalent transmission power consumption should not exceed 25.
Within N2, conditions 1,2 should be followed.
N4Within N4, the total equivalent transmission power consumption should not exceed 25.
TB7 TB3
TB7 TB3
if the total equivalent transmission power consumption reaches 5. Transmission booster (No.2) should be used,
PAC-SF46EPA
TRANSMISSION BOOSTER
3.4kg
220-240V:0.7A ~/N
WEIGHT
POWER RATING
MODEL
MADE IN JAPAN
50
UP
PAC-SF46EPA
TRANSMISSION BOOSTER
3.4kg
220-240V:0.7A ~/N
WEIGHT
POWER RATING
MODEL
MADE IN JAPAN
50
UP
Transmissionbooster(No.1)
TransmissionboosterPAC-SF46EPA(No.2)Centralized controller
(AG-150A)
CENTRALIZED CONTROLLER AG-150A
2. M-NET control DATA G8
SYSTEM DESIGN 4 - 50
Syst
em Y
PAC-SC51KUA
Outdoor unit
MA remote controller
Group Group
Indoor unit
M-NET transmission lines(transmission lines for centralized controller)
M-NET transmission lines(transmission lines for centralized controller)
Outdoor unit
ME remote controller
MA remote controller
ME remote controller
Group Group
Group Group
Group Group
Indoor unit
Indoor unit
Indoor unit
Replacement of CN41 with CN40
Use CN41 as it is.
TB7TB3
TB3
Outdoor unit
Outdoor unit
Replacement of CN41 with CN40
Use CN41 as it is.
System controller (excluding LMAP02-E)
System controller
M-NET transmission lines (Indoor-Outdoor transmission lines)
TB7TB3
System controller
TB7
TB7TB3
Maximum 3 System controllers can be connected to TB3.
Maximum 3 System controllers can be connected to TB7.
M-NET transmission lines(transmission lines for centralized controller) MA remote controller
ME remote controller
Group Group
Group Group
Indoor unit
Indoor unit
TB3
Outdoor unit
Outdoor unit
Use CN41 as it is.
Use CN41 as it is.
System controller
TB7
TB7TB3
CAUTION
M-NET transmission lines (Indoor-Outdoor transmission lines)
M-NET transmission lines (Indoor-Outdoor transmission lines)
The power to System controller (excluding LMAP02-E) is supplied via M-NET transmission line. M-NET transmission line at TB7 side is called Centralized control transmission line while one at TB3 side is called Indoor-Outdoor transmission line. There are 3 ways to supply power to the System controller .A) Connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.B) Connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit. C) Connecting to TB7 of the Outdoor unit but receiving power from power supply unit PAC-SC51KUA.
Maximum 3 System controllers can be connected to TB3. If there is more than 1 Outdoor unit, it is necessary to replace power supply switch connector CN41 with CN40 on one Outdoor unit.
Maximum 3 System controllers can be connected to TB7 and receiving power from the Outdoor unit. It is necessary to replace power supply switch connector CN41 with CN40 on one Outdoor unit.
Fig. 2-3-3-A
Fig. 2-3-3-B
Fig. 2-3-3-C
2-3-3-A. When connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.
2-3-3-B. When connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit.
2-3-3-C. When connecting to TB7 of the Outdoor unit but receiving power from PAC-SC51KUA.
2-3-3. Ensuring proper power supply to System controller
When using PAC-SC51KUA to supply transmission power, the power supply connector CN41 on the Outdoor units should be kept as it is. It is also a factory setting. 1 PAC-SC51KUA supports maximum 1 AG-150A unitdue to the limited power 24VDC at its TB3. However, 1 PAC-SC51KUA supplies transmission power at its TB2 equal to 5 Indoor units, which is referable at Table 2-3-2.If PZ-52SF-E, Timers, System controller, ON/OFF controller connected to TB7 consume transmission power more than 5 (Indoor units), Transmission booster PAC-SF46EPA is needed. PAC-SF46EPA supplies transmission power equal to 25 Indoor units.
AG-150A*1 is recommended to connect to TB7 because it performs back-up to a number of data. In an air conditioner system has more than 1 Outdoor units, AG-150A receiving transmission power through TB7 on one of the Outdoor units would have a risk that the connected Outdoor unit failure would stop power supply to AG-150A, and disrupt the whole system. When applying apportioned electric power function, AG-150A is necessary to connected to TB7 and has its own power supply unit PAC-SC51KUA.*2
*1: AG-150A is an example model of system controllers.*2: Power supply unit PAC-SC51KUA is for AG-150A.
4 - 51
2. M-NET control DATA G8
SYSTEM DESIGN
System Y
1-phase 220-240V AC power supply is needed.The power supply unit PAC-SC51KUA is not necessary when connecting only the LMAP02-E. Yet, make sure to change the power supply changeover connector CN41 to CN40 on the LM adapter.
2-3-4. Power supply to LM adapter LMAP02-E
1-phase 100-240VAC power supply is needed.The power supply unit PAC-SC51KUA is not necessary.The expansion controller supplies power through TB3, which equals 6 indoor units. (refer to Table 2-3-2)
2-3-5. Power supply to expansion controller
1-phase 100-240VAC power supply is needed.The power supply unit PAC-SC51KUA is not necessary when only BM ADAPTER is connected.Yet, make sure to move the power jumper from CN41 to CN40 on the BM ADAPTER.
2-3-6. Power supply to BM ADAPTER
1-phase 100-240VAC power supply is needed.The power supply unit PAC-SC51KUA is not necessary.GB-50ADA supplies power through TB3, which equals 6 indoor units. (refer to Table 2-3-2)
2-3-7. Power supply to GB-50ADA
2. M-NET control DATA G8
SYSTEM DESIGN 4 - 52
Syst
em Y
2-4. Address setting
BranchNo. setting Unit address No. setting
Rotary switchIn order to constitute CITY MULTI in a complete system, switch operation for setting the unit address No. and connection No. is required.
À Address No. of outdoor unit, indoor unit and remote controller.The address No. is set at the address setting board. In the case of R2 system, it is necessary to set the same No. at the branch No. switch of indoor unit as that of the BC controller connected. (When connecting two or more branches, use the lowest branch No.)
Á Caution for switch operations
 MA remote controller
¥ Be sure to shut off power source before switch setting. If operated with power source on, switch can not operate properly.
¥ When connecting only one remote controller to one group, it is always the main remote controller. When connecting two remote controllers to one group, set one remote controller as the main remote controller
and the other as the sub remote controller.
¥ No units with identical unit address shall exist in one whole air conditioner system. If set erroneously, the system can not operate.
¥ The factory setting is Main .
2-4-1. Switch operation
0 1 2 3 4 5 6 7 8 9 A B C D
E F 0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
PAR-21MAAThe MA remote controller does not have the switches listed above.Refer to the installation manual for the function setting.
Setting the dip switchesThere are switches on the front of the remote controller. Remote controller Main/Sub and other function settings are performed using these switches. Ordinarily, only change the Main/Sub setting of SW1. (The factory settings are all “ON”.)
SW No
1
2
3
SW contents MainRemote controllerMain/Sub settingTemperature displayunits settingCooling/heating dis-play in AUTO mode
ON
Main
Celsius
Yes
OFF
Sub
Fahrenheit
No
Comment
Set one of the two remote controllers at one group to “Main”
When the temperature is displayed in [Fahrenheit], set to “No”.
When you do not want to display “Cooling” and “Heating” in theAuto mode, set to “No”.
PAC-YT51CRB
4 - 53
2. M-NET control DATA G8
SYSTEM DESIGN
System Y
2-4-2. Rule of setting address
Unit
Indoor unit
ME, LOSSNAYRemote controller(Main)
ME, LOSSNAYRemote controller(Sub)
Address setting
01 ~ 50
52 ~ 99, 100
101 ~ 150
151 ~ 199, 200
NoteExample
The address of outdoor unit + 1 Please reset one of them to an address between 51
and 99 when two addresses overlap. The address automatically becomes "100" if it is set
as "01~ 50"
The smallest address of indoor unit in the group + 100
The place of "100" is fixed to "1"
System remotecontroller
ON/OFF remote controller
AG-150AGB-50ADA
000, 201 ~ 250
000, 201 ~ 250
000, 201 ~ 250
Loca
l remo
te co
ntroll
erSy
stem
con
trolle
r
The address of main remote controller + 50
The address automatically becomes "200" if it is set as "00"
10 1
10 1
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
10 1
10 1
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
0 1 2 3 4 5 6 7
8
90 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
10 1
10 1100
0 1 2 3 4 5 6 7
8
90 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
10 1100
10 1100
LMAP02-E 201 ~ 250
1
1
Fixed
Fixed
Group remote controller 201 ~ 250
The smallest group No. to be managed + 200
10 1
2Fixed
2Fixed
Outdoor unit
BC controller(Main)
52 ~ 99, 100Lowest address within the indoor units connected to the BC controller (Sub) plus 50.
10 1
BC controller(Sub)
51 ~ 99, 100
The smallest address of indoor unit in same refrigerant system + 50Assign sequential address numbers to the outdoor units in one refrigerant circuit system. OC, OS1 and OS2 are automatically detected. (Note 2) Please reset one of them to an address between 51
and 99 when two addresses overlap. The address automatically becomes "100" if it is set
as "01~ 50"
Use the most recent address within the same group of indoor units. Make the indoor units address connected to the BC controller (Sub) larger than the indoor units address connected to the BC controller (Main).If applicable, set the sub BC controllers in an PURY system in the following order: (1) Indoor unit to be connected to the BC controller (Main) (2) Indoor unit to be connected to the BC controller (No.1 Sub) (3) Indoor unit to be connected to the BC controller (No.2 Sub)Set the address so that (1)<(2)<(3)
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8 9
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
10 1(Note1)
0,2 0~5 0~9
PAC-YG50ECA 000, 201 ~ 250
10 1100
0,2 0~5 0~9
BAC-HD150 000, 201 ~ 250
10 1100
0,2 0~5 0~9
The smallest group No. to be managed is changeable.
Settings are made on the initial screen of AG-150A.
Settings are made with setting tool of BM ADAPTER.
The smallest group No. to be managed + 200
Note1: To set the address to "100", set it to "50"Note2: Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
2. M-NET control DATA G8
SYSTEM DESIGN 4 - 54
Syst
em Y
2-4-3. System examples
Factory setting
Setting at the site
Original switch setting of the outdoors, indoors, controllers, LMAP and BM ADAPTER at shipment is as follows. Outdoor unit : Address: 00, CN41: U (Jumper), DipSW2-1: OFF Indoor unit : Address: 00 ME remote controller : Address: 101 LMAP : Address: 247, CN41: U (Jumper), DipSW1-2: OFF BM ADAPTER : Address: 00
DipSW2-1(Outdoor) : When the System Controller is used, all the Dip SW2-1 at the outdoor units should be set to "ON". * Dip SW2-1 remains OFF when only LMAP02-E is used. DipSW1-2(LMAP) : When the LMAP is used together with System Controller, DipSW1-2 at the LMAP should be set to "ON". CN40/CN41 : Change jumper from CN41 to CN 40 at outdoor control board will activate central transmission power supply to TB7; (Change jumper at only one outdoor unit when activating the transmission power supply without using a power supply unit.) Change jumper from CN41 to CN 40 at LMAP will activate transmission power supply to LMAP itself; Power supply unit is recommended to use for a system having more than 1 outdoor unit, because the central transmission power supply from TB7 of one of outdoor units is risking that the outdoor unit failure may let down the whole system controller system.
2-4-3-1. MA remote controller, Single-refrigerant-system, No System Controller
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.2. No address setting is needed.3. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at 2-3 "System configuration restrictions".
NOTE:
Indoor unit
MA R/C MA R/C MA R/C(Main) (Sub)
MA R/CSRU
Wireless R/C
1*
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
1*
00 00 00 00 00TB15TB5 TB5TB5 TB5 TB5TB15 TB15 TB15 TB15
Group 2Group 1 Group 3 Group 4
<Three outdoor units> <Two outdoor units> <One outdoor unit>
TB3 TB3TB3
000000OC OS1 OS2
PUHY
TB3TB3
0000OC OS1
PUHY
TB3
00OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
PUHY
4 - 55
2. M-NET control DATA G8
SYSTEM DESIGN
System Y
2-4-3. System examples
2-4-3-2. MA remote controller, Single-refrigerant-system, System Controller
2. Address should be set to Indoor units and centralized controller.3. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at 2-3 "System configuration restrictions".
NOTE:1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
Indoor unit
MA R/C MA R/C MA R/C(Main) (Sub)
MA R/CSRU
Wireless R/C
1*
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.*SC can be connected to TB3 side or TB7 side; Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
1*
01 02 03 04 05TB15TB5 TB5TB5 TB5 TB5TB15 TB15 TB15 TB15
Group 2Group 1 Group 3 Group 4
TB3 TB3TB3
201
535251OC OS1 OS2
PUHY
SC
TB3TB3
5251OC OS1
PUHY
TB3
51OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
PUHY<Three outdoor units> <Two outdoor units> <One outdoor unit>
2. M-NET control DATA G8
SYSTEM DESIGN 4 - 56
Syst
em Y
2-4-3. System examples
2-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7/TB3 side, Booster for long M-NET wiring
2. Address should be set to Indoor units, LOSSNAY and system controller.3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".
NOTE:1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
Indoor unit
MA R/C MA R/C(Main) (Sub)
MA R/CSRU
Wireless R/C
*1
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System. For AG-150A, 24V DC should be used with the PAC-SC51KUA.
*1202
01 02 03 30TB15TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5TB15 TB15 TB3 TB15
MA R/C(Main) (Sub)
MA R/C
TB15
Indoor unit
ME R/C MA R/CPZ-52SF-ESRU
Wireless R/C
*1
*1 142 143
*2
41 42 43 45 46TB15TB5 TB5
LOSSNAY
TB5 TB5 TB5TB15
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
Group 2Group 1 Group 21
Group 33Group 32Group 31 Group 34 Group 36Group 35
TB3 TB3
TB7TB7 TB7 TB7 TB7 TB7
TB3
TB2
000 or 201
Power supply unit(PAC-SC51KUA)
535251
OC OS1 OS2PUHY
SC*3
TB3TB3
9291
OC OS1PUHY
TB3
98
OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
PUHY
SC*3
203SC *3
*3 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main" controller and others as "sub". Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".
PZ-60DR-E
47TB5 TM4
LOSSNAY
4 - 57
2. M-NET control DATA G8
SYSTEM DESIGN
System Y
2-4-3. System examples
2-4-3-4. ME remote controller, Single-refrigerant-system, No system controller
2. Address should be set to Indoor units, system controller and ME remote controllers.3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME RC consume the M-NET power for transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".
NOTE:1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
Indoor unit
ME R/C ME R/C ME R/C
01 02 03 04 05TB5 TB5TB5
102
ME R/C
104 105 155
TB5 TB5
ME R/C
101
Group 2Group 1 Group 3 Group 4
TB3 TB3TB3
535251OC OS1 OS2
PUHY
TB3TB3
5251OC OS1
PUHY
TB3
51OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
PUHY<Three outdoor units> <Two outdoor units> <One outdoor unit>
2-4-3-5. ME remote controller, Single-refrigerant-system, System controller, LOSSNAY
2. Address should be set to Indoor units, LOSSNAY centralized controller, ME remote controllers.3. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at 2-3 "System configuration restrictions".
NOTE:
ME R/C ME R/C
Indoor unit
ME R/C ME R/CPZ-52SF-E102 103 104 105 155
01 02 03 04 05TB5 TB5
LOSSNAY
TB5 TB5 TB5 TM4
ME R/C101
Group 2 Group 3Group 1 Group 4 Group 5
201
SC
*SC can be connected to TB3 side or TB7 side; Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
<Three outdoor units> <Two outdoor units> <One outdoor unit>
TB3 TB3TB3
535251OC OS1 OS2
PUHY
TB3TB3
5251OC OS1
PUHY
TB3
51OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
PUHY
Group 6
PZ-60DR-E
06TB5
LOSSNAY
2. M-NET control DATA G8
SYSTEM DESIGN 4 - 58
Syst
em Y
2-4-3. System examples
2-4-3-6. ME remote controller, Multi-refrigerant-system, System Controller at TB 7side, LOSSNAY, Booster for long M-NET wiring
2. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".
NOTE:1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
Indoor unit
ME R/C ME R/C
*1 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System. For AG-150A, 24V DC should be used with the PAC-SC51KUA.
01 02 03 30TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5TB3
ME R/C ME R/C
Indoor unit
ME R/C ME R/CPZ-52SF-E142 144 145 195
130 180
143
*1
41 42 43 44 45TB5 TB5
LOSSNAY
TB5 TB5 TB5 TM4
ME R/C141203
ME R/C101
SC *2
SC *2
202ME R/C
102
Group 2Group 1 Group 21
Group 32 Group 33
PZ-60DR-E
46LOSSNAY
Group 36Group 31 Group 34 Group 35
TB3 TB3
TB7TB7 TB7 TB7 TB7 TB7
TB3
TB2
000 or 201
Power supply unit(PAC-SC51KUA)
535251
OC OS1 OS2PUHY
SC*2
TB3TB3
9291
OC OS1PUHY
TB3
97
OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
PUHY
*2 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main" controller and others as "sub". Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".
TB5
4 - 59
2. M-NET control DATA G8
SYSTEM DESIGN
System Y
2-4-3-7. ME remote controller, Multi-refrigerant-system, No Power supply unit
NOTE It is necessary to change the connecter to CN40 on the outdoor unit control board (only one outdoor unit) when the group is set between other refrigerant systems. It is necessary to set on the remote controller by manual when group sets on the different refrigerant system. Please refer to remote controller installation manual.
NOTE It is necessary to change the connecter to CN40 on the outdoor unit control board (only one outdoor unit) when the group is set between other refrigerant systems. It is necessary to set on the remote controller by manual when group sets on the different refrigerant system. Please refer to remote controller installation manual.
SC201
Group 1
Group 3Group 4
Group 2
ME R/C
01 02 03 04 05
101 105
0910 08 07 06
110 107ME R/C
ME R/C
ME R/C
TB7
TB3
56CN41CN40
OFFDipSW2-1
TB3
TB7TB7
TB3
5251CN41CN40CN41CN40
OFFDipSW2-1
OFFDipSW2-1
OC OCOSPUHY PUHY
2-4-3-8. ME remote controller, Multi-refrigerant-system, System Controller at TB7 side, No Power sypply unit
Group 1
Group 3Group 4
Group 2
ME R/C
01 02 03 04 05
101 105
0910 08 07 06
110 107ME R/C
ME R/C
ME R/C
TB7
TB3
56CN41CN40
ONDipSW2-1
TB3
TB7TB7
TB3
5251CN41CN40CN41CN40
ONDipSW2-1
ONDipSW2-1
OC OCOSPUHY PUHY
2. M-NET control DATA G8
SYSTEM DESIGN 4 - 60
Syst
em Y
2-4-3-9. TG-2000A(*1)+AG-150A*2AG-150A can control max. 50 indoor units;TG-2000A can control max. 40 AG-150A;*3TG-2000A can control max. 2000 indoor units.
HUB
PC withTG-2000A
LAN AG-150A
24VDC
AG-150A
000
000
24VDC
Power supply unit(PAC-SC51KUA)
Indoor unit
MA R/C MA R/C(Main) (Sub)
MA R/CSRU
Wireless R/C
*4
*4
01 02 03 42TB15TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5TB15 TB15 TB3 TB15
Group 2Group 1 Group 40
TB7
TB3
TB3 TB2
TB2
TB3
51
OC
CN41CN40
ONDipSW2-1
Indoor unit
ME R/C ME R/C ME R/C
01 02 03 30TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5
ME R/C
101 102 130 180
TB3
Group 2Group 1 Group 21
TB7 TB7 TB7
TB3TB3
5251
OC OS
TB3
91
OC
CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ME R/C ME R/C
Indoor unit
ME R/C ME R/C142 144 145 195
41 42 43 44 45TB5 TB5
InterlockedLOSSNAY
TB5 TB5 TB5
Group 32
46TB5 TM4
LOSSNAY
Group 35Group 31 Group 33 Group 34
ME R/C
141
PUHY
PUHY PUHY
*1 TG-2000A (Ver.5.5 or later) supports AG-150A (Ver.1 series). TG-2000A (Ver. 6.1 or later) supports AG-150A (Ver. 2.1 or later) connected with the expansion controller (EC).*2 AG-150A (Ver.1 series) does not support the expansion controller (EC).*3 When AG-150A connected with the expansion controller (EC) is connected, the number of EC will be the maximum controllable number. TG-2000A can control up to 40 EC or AG-150A without EC connection.*4 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
It is planned that GB-50ADA will be supported on TG-2000A Ver. 6.3* or later.
PZ-60DR-E
Power supply unit(PAC-SC51KUA)
4 - 61
2. M-NET control DATA G8
SYSTEM DESIGN
System Y
2-4-3. System examples
2-4-3-10. AG-150A + PAC-YG50ECA (Expansion controller)AG-150A can control max. 150 indoor units/ via expansion controllers.
HUB
PC withBrowser
LAN
PAC-YG50ECA
AG-150A
PAC-YG50ECA
PAC-YG50ECA
Indoor unit
MA R/C MA R/C(Main) (Sub)
MA R/CSRU
Wireless R/C
*1
*1
01 02 03 42TB15TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5TB15 TB15 TB3 TB15
Group 2Group 1 Group 40
TB3 TB3
TB7TB7 TB7 TB7 TB7 TB7
TB3
24VDCTB3
535251
OC OS1 OS2
TB3TB3
5251
OC OS1
TB3
51
OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
Indoor unit
ME R/C ME R/C ME R/C
01 02 03 30TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5
ME R/C
101 102 130 180
TB3
Group 2Group 1 Group 21
TB3 TB3
TB7TB7 TB7 TB7 TB7 TB7
TB3
535251
OC OS1 OS2
TB3TB3
9291
OC OS1
TB3
96
OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ME R/C ME R/C
Indoor unit
ME R/C ME R/CPZ-52SF-E142 143 144 145 195
41 42 43 44 45TB5 TB5
LOSSNAY
TB5 TB5 TB5
Group 32 Group 33Group 31 Group 34 Group 35
ME R/C
141
PUHY PUHY PUHY
PUHY PUHY PUHY
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
<Three outdoor units> <Two outdoor units> <One outdoor unit>
Power supply unit(PAC-SC51KUA)
When connecting AG-150A to PAC-YG50ECA, TB2 for power supply unit does not need to be connected to AG-150A.NOTE
000
CN40 CN41
000
CN40 CN41
000
CN40 CN41
2. M-NET control DATA G8
SYSTEM DESIGN 4 - 62
Syst
em Y
2-4-3. System examples
2-4-3-11. LMAP
LMAP(01)
24VDC
(LONWORKs adapter)
PC
LONWORKS card
LONWORKS card
LONWORKS card For other equipments (Lighting, security, elevator etc.)
LMAP can transmission for max. 50 indoor units in single-refrigerant-system or multi-refrigerant-system.
DipSW1-2OFF
247
LONW
OR
KS
000
AG-150A
Power supply unit(PAC-SC51KUA)
identified by Neuron ID
LMAP(02)
DipSW1-2ON
247identified by Neuron ID
<Three outdoor units> <Two outdoor units> <One outdoor unit>
CN41CN40
CN41CN40
LMAP can transmission for max. 50 indoor units;If system controller (SC) is used, DipSW1-2 at LMAP and DipSW2-1 at Outdoor unit should set to "ON".Change Jumper from CN41 to CN40 to activate power supply to LMAP itself for those LMAP connected without system controller (SC).
Indoor unit
MA R/C MA R/C(Main) (Sub)
MA R/CSRU
Wireless R/C
*1
*1
01 02 03 42TB15TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5TB15 TB15 TB3 TB15
Group 2Group 1 Group 40
TB3 TB3
TB7TB7
TB3
TB2
TB7 TB7 TB7 TB7
TB3
535251
OC OS1 OS2
TB3TB3
5251
OC OS1
TB3
51
OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
Indoor unit
ME R/C ME R/C ME R/C
01 02 03 30TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5
ME R/C
101 102 130 180
TB3
Group 2Group 1 Group 21
TB3 TB3
TB7TB7 TB7 TB7 TB7 TB7
TB3
535251
OC OS1 OS2
TB3TB3
9291
OC OS1
TB3
97
OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ME R/C ME R/C
Indoor unit
ME R/C ME R/CPZ-52SF-E142 143 144 145 195
41 42 43 44 45TB5 TB5
LOSSNAY
TB5 TB5 TB5
Group 32 Group 33Group 31 Group 34 Group 35
ME R/C
141
PUHY PUHY PUHY
PUHY PUHY PUHY
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
PZ-60DR-E
46TB5 TM4
LOSSNAY
Group 36
4 - 63
2. M-NET control DATA G8
SYSTEM DESIGN
System Y
2-4-3. System examples
2-4-3-12. BM ADAPTER
BM ADAPTER(01)
HUB
For other equipments (Lighting, security, elevator etc.)
BM ADAPTER can transmission for max. 50 indoor units in single-refrigerant-system or multi-refrigerant-system.
000
BA
C n
et
BM ADAPTER(02)
201
<Three outdoor units> <Two outdoor units> <One outdoor unit>
CN41CN40
BM ADAPTER can transmission for max. 50 indoor units;Change Jumper from CN41 to CN40 to activate power supply to BM ADAPTER itself for those BM ADAPTER connected without the power supply unit.
Indoor unit
MA R/C MA R/C(Main) (Sub)
MA R/CSRU
Wireless R/C
*1
*1
01 02 03 42TB15TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5TB15 TB15 TB3 TB15
Group 2Group 1 Group 40
TB3 TB3
TB7TB7 TB7 TB7 TB7 TB7
TB3
535251
OC OS1 OS2
TB3TB3
5251
OC OS1
TB3
51
OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
Indoor unit
ME R/C ME R/C ME R/C
01 02 03 30TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5
ME R/C
101 102 130 180
TB3
Group 2Group 1 Group 21
TB3 TB3
TB7TB7 TB7 TB7 TB7 TB7
TB3
535251
OC OS1 OS2
TB3TB3
9291
OC OS1
TB3
96
OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ME R/C ME R/C
Indoor unit
ME R/C ME R/CPZ-52SF-E142 143 144 145 195
41 42 43 44 45TB5 TB5
LOSSNAY
TB5 TB5 TB5
Group 32 Group 33Group 31 Group 34 Group 35
ME R/C
141
PUHY PUHY PUHY
PUHY PUHY PUHY
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
HUB
CN41CN40
2. M-NET control DATA G8
SYSTEM DESIGN 4 - 64
Syst
em Y
2-4-3. System examples
2-4-3-13. BM ADAPTER+PAC-YG50ECA (Expansion controller)
000
000
<Three outdoor units> <Two outdoor units> <One outdoor unit>
CN41CN40
BM ADAPTER(*1) can transmission for max. 150 indoor units/via expansion controllers (PAC-YG50ECA).
Indoor unit
MA R/C MA R/C(Main) (Sub)
MA R/CSRU
Wireless R/C
*2
*2
01 02 03 42TB15TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5TB15 TB15 TB3 TB15
Group 2Group 1 Group 40
TB3 TB3
TB7TB7 TB7 TB7 TB7 TB7
TB3
535251
OC OS1 OS2
TB3TB3
5251
OC OS1
TB3
51
OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
Indoor unit
ME R/C ME R/C ME R/C
01 02 03 30TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5
ME R/C
101 102 130 180
TB3
Group 2Group 1 Group 21
TB3 TB3
TB7TB7 TB7 TB7 TB7 TB7
TB3
535251
OC OS1 OS2
TB3TB3
9291
OC OS1
TB3
96
OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ME R/C ME R/C
Indoor unit
ME R/C ME R/CPZ-52SF-E142 143 144 145 195
41 42 43 44 45TB5 TB5
LOSSNAY
TB5 TB5 TB5
Group 32 Group 33Group 31 Group 34 Group 35
ME R/C
141
PUHY PUHY PUHY
PUHY PUHY PUHYCN41CN40
NOTE•It is not necessary to connect the M-NET transmission line to the TB3 on BM ADAPTER. Leave the power jumper of BM ADAPTER connected to CN41.
*1 BM ADAPTER (Ver.2.00 or later) supports the expansion controller.*2 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.*3 AG-150A (Ver.2.30 or later) supports the BM ADAPTER.*4 PAC-YG50ECA (Ver.1.30 or later) supports the BM ADAPTER.
PAC-YG50ECA*4
PAC-YG50ECA*4
BACnet
LAN
LAN2
LAN1
PAC-YG50ECA *4
AG-150A *3
Power supply unit(PAC-SC51KUA)
TB324VDC
000CN41CN40
HUB
BM ADAPTER
CN41CN40
4 - 65
3. Piping Design DATA G8
SYSTEM DESIGN
System Y
3. Piping Design3-1. R410A Piping material
Refrigerant pipe for CITY MULTI shall be made of phosphorus deoxidized copper, and has two types. A. Type-O : Soft copper pipe (annealed copper pipe), can be easily bent with human's hand. B. Type-1/2H pipe : Hard copper pipe (Straight pipe), being stronger than Type-O pipe of the same radical thickness. The maximum operation pressure of R410A air conditioner is 4.30 MPa [623psi] . The refrigerant piping should ensure the safety under the maximum operation pressure. MITSUBISHI ELECTRIC recommends pipe size as Table 3-1, or You shall follow the local industrial standard. Pipes of radical thickness 0.7mm or less shall not be used.
* F * The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes that meet the local standards.
or pipe sized ø19.05 (3/4") for R410A air conditioner, choice of pipe type is up to you.
Size (mm) Size (inch) Radial thickness (mm) Pipe typeø6.35 ø1/4" 0.8 Type-Oø9.52 ø3/8" 0.8 Type-Oø12.7 ø1/2" 0.8 Type-O
ø15.88 ø5/8" 1.0 Type-Oø19.05 ø3/4" 1.2 Type-Oø19.05 ø3/4" 1.0 Type-1/2H or Hø22.2 ø7/8" 1.0 Type-1/2H or Hø25.4 ø1" 1.0 Type-1/2H or H
ø28.58 ø1-1/8" 1.0 Type-1/2H or Hø31.75 ø1-1/4" 1.1 Type-1/2H or Hø34.93 ø1-3/8" 1.2 Type-1/2H or Hø41.28 ø1-5/8" 1.4
Radial thickness (mil)[32][32][32][40][48][40][40][40][40][44][48][56] Type-1/2H or H
Table 3-1. Copper pipe size and radial thickness for R410A CITY MULTI.
Flare
Due to the relative higher operation pressure of R410A compared to R22, the flare connection should follow dimensions mentioned below so as to achieve enough the air-tightness.
Flare pipe Pipe size A (For R410A) Flare nut Pipe size (mm[in.]) (mm[in.]) B (For R410A)
ø6.35 [1/4"]ø9.52 [3/8"]
ø12.70 [1/2"]ø15.88 [5/8"]ø19.05 [3/4"] 24.0
16.619.7
9.113.2
ø6.35 [1/4"]ø9.52 [3/8"]
ø12.70 [1/2"]ø15.88 [5/8"]ø19.05 [3/4"] 36.0
17.022.026.029.0
A
B
3. Piping Design DATA G8
SYSTEM DESIGN 4 - 66
Syst
em Y
3-2. Piping Design
Joint selection rule Total down-stream Indoor capacity Joint ~ P200 CMY-Y102S-G2 P201 ~ P400 CMY-Y102L-G2 P401 ~ P650 CMY-Y202-G2 P651 ~ CMY-Y302-G2*PUHY-P450YJM's first Joint is always CMY-Y202-G2;*Concerning detailed usage of Joint parts, refer to its Installation Manual.
Header selection rule 4-branch Header 8-branch Header 10-branch Header CMY-Y104-G CMY-Y108-G CMY-Y1010-G Total down-stream Indoor capacity <=P200 <=P400 <=P650* CMY-Y104-G can directly connect PUHY-(E)P200YJM, but can NOT directly connect PUHY-(E)P250YJM or above; * CMY-Y108-G can directly connect PUHY-(E)P200-450YJM, but can NOT directly connect PUHY-(E)P500YSJM or above; * CMY-Y1010-G can directly connect PUHY-P200-650Y(S)JM,PUHY-EP200-600Y(S)JM; * CMY-Y104-G can NOT connect P200,P250 Indoor, but CMY-Y108, Y1010-G can do; * Concerning detailed usage of Header parts, refer to its Installation Manual.
Note3. Indoor capacity is described as its model size; For example, PEFY-P32VMA-E, its capacity is P32;Note4. Total down-stream Indoor capacity is the summary of the model size of Indoors downstream. For example, PEFY-P25VMA-E+PEFY-P32VMA-E: Total Indoor capacity=P25+P32=P57Note5. Piping sized determined by the Total down-stream indoor capacity is NOT necessary to be bigger than the up-stream one. i.e. A>=B; A>=C>=D
Note1. No Joint after Header; Piping direct to Indoor Unit from Header;Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;
Piping length needs to consider the actual length and equivalent length which bents are counted.Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.
IU : Indoor unit , OU : Outdoor unitFig. 3-2-1A Piping scheme
L1
L2C
b
h1
c
d ge
A
B
D a
OU
Joint
H (O
U a
bove
IU)
H' (
OU
und
er IU
)
IU IU
f
E
IU IU
IU IU IU
Header
1st JointCapped
*1*2
3-2-1. PUHY-P200-450YJM-A,PUHY-EP200-300YJM-A Piping
Piping length (m [ft.]) Item Piping in the figure Max. length Max. equivalent length Total piping length A+B+C+D+E+a+b+c+d+e+f+g 1000 [3280'] - Fartherest IU from OU (L1) A+C+D+E+g / A+B+c 165 [541'] 190 [623'] Fartherest IU from first Joint (L2) C+D+E+g / B+c 40 [131'] 40 [131'] Height between OU and IU (OU above IU) H 50 [164'] - Height between OU and IU (OU under IU) H' 40 [131'] - Height between IU and IU h1 15 [49'] -OU: Outdoor Unit, IU: Indoor Unit
Piping "A" size selection rule (mm [in.]) Outdoor and the first Joint Pipe(Liquid) Pipe(Gas) PUHY-(E)P200YJM=CMY-Y102L-G2,Y102S-G2 ø9.52 [3/8"] ø19.05 [3/4"] PUHY-(E)P250YJM=CMY-Y102L-G2 ø9.52 [3/8"] *1 ø22.20 [7/8"] PUHY-(E)P300YJM=CMY-Y102-G2 ø9.52 [3/8"] *2 ø22.20 [7/8"] PUHY-P350YJM=CMY-Y102-G2 ø12.70 [1/2"] ø28.58 [1-1/8"] PUHY-P400YJM=CMY-Y202-G2 ø12.70 [1/2"] ø28.58 [1-1/8"] PUHY-P450YJM=CMY-Y202-G2 ø15.88 [5/8"] ø28.58 [1-1/8"]*1. A>=90m [295ft.], ø12.70mm [1/2in.] ; A<90m [295ft.], ø9.52mm [3/8in.]*2. A>=40m [131ft.], ø12.70mm [1/2in.] ; A<40m [131ft.], ø9.52mm [3/8in.]
Piping"B","C","D","E"size selection rule (mm [in.]) Total down-stream Indoor capacity Pipe(Liquid) Pipe(Gas) ~ P140 ø9.52 [3/8"] ø15.88 [5/8"] P141 ~ P200 ø9.52 [3/8"] ø19.05 [3/4"] P201 ~ P300 ø9.52 [3/8"] ø22.20 [7/8"] P301 ~ P400 ø12.70 [1/2"] ø28.58 [1-1/8"] P401 ~ P650 ø15.88 [5/8"] ø28.58 [1-1/8"] P651 ~ P800 ø19.05 [3/4"] ø34.93 [1-3/8"] P801 ~ ø19.05 [3/4"] ø41.28 [1-5/8"]
Piping "a","b","c","d","e","f","g" size selection rule (mm [in.]) Indoor Unit size Pipe(Liquid) Pipe(Gas) P20,P25,P32,P40,P50,GUF-50RD(H) ø6.35 [1/4"] ø12.70 [1/2"] P63,P71,P80,P100,P125,GUF-100RD(H) ø9.52 [3/8"] ø15.88 [5/8"] P200 ø9.52 [3/8"] ø19.05 [3/4"] P250 ø9.52 [3/8"] ø22.20 [7/8"]
Bent equivalent length "M" Outdoor unit model M (m/bent [ft./bent]) PUHY-(E)P200YJM-A 0.35 [1.15] PUHY-(E)P250YJM-A 0.42 [1.38] PUHY-(E)P300YJM-A 0.42 [1.38] PUHY-P350YJM-A 0.47 [1.54] PUHY-P400YJM-A 0.50 [1.64] PUHY-P450YJM-A 0.50 [1.64]
*1 90m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.*2 60m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.
4 - 67
3. Piping Design DATA G8
SYSTEM DESIGN
System Y
Joint selection rule Total down-stream Indoor capacity Joint ~ P200 CMY-Y102S-G2 P201 ~ P400 CMY-Y102L-G2 P401 ~ P650 CMY-Y202-G2 P651 ~ CMY-Y302-G2*PUHY-P500-650YSJM's first Joint is always CMY-Y202-G2;*PUHY-P700-900YSJM's first Joint is always CMY-Y302-G2;*PUHY-EP450-600YSJM's first Joint is always CMY-Y202-G2;*Concerning detailed usage of Joint parts, refer to its Installation Manual.*The total capacity of the units in the downstream of the branch joint on at least one of the piping lines that are connected to the branch joint should be 650 or below. If the total capacity of the units in the downstream of the branch joints on both lines is 650 or above use two branch joints (CMY-Y302-G2).
Header selection rule 4-branch Header 8-branch Header 10-branch Header CMY-Y104-G CMY-Y108-G CMY-Y1010-G Total down-stream Indoor capacity <=P200 <=P400 <=P650* CMY-Y104-G can directly connect PUHY-(E)P200YJM, but can NOT directly connect PUHY-(E)P250YJM or above; * CMY-Y108-G can directly connect PUHY-(E)P200-450YJM, but can NOT directly connect PUHY-(E)P500YSJM or above; * CMY-Y1010-G can directly connect PUHY-P200-650Y(S)JM, PUHY-EP200-600Y(S)JM; * CMY-Y104-G can NOT connect P200,P250 Indoor, but CMY-Y108, Y1010-G can do; * Concerning detailed usage of Header parts, refer to its Installation Manual.
Outdoor Twinning KitCMY-Y100,200VBK2
Note1. No Joint after Header; Piping direct to Indoor Unit from Header;Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;
Piping length needs to consider the actual length and equivalent length which bents are counted.Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.
H (O
U a
bove
IU)
h1
H' (
OU
und
er IU
)
h2
1st Joint
Joint
ba
L2L1
IU
IU IUIU
g
IU
e
IU
d
C
D
IU
f
E
TS
A BHeader
Capped
IU : Indoor unit , OU : Outdoor unitFig. 3-2-1B Piping scheme
c
2m To indoor unitTo indoor unitTo indoor unit To indoor unit 2 m max
Trap (gas pipe only)
Upward incline
Downward incline
Install the pipes from the outdoor unit to the branch joint with a downward incline.
If the length of pipe between the branch joint and outdoor unit exceeds 2 m, provide at rap at a distance 2 m or less from the branch joint.
OK NG
3-2-2. PUHY-P500-900YSJM-A(1),PUHY-EP400-600YSJM-A(1) Piping
Piping length (m [ft.]) Item Piping in the figure Max. length Max. equivalent length Total piping length S+T+A+B+C+D+E+a+b+c+d+e+f+g 1000 [3280'] - Distance between OU and OU S+T 10[32'] - Height between OU and OU h2 0.1[0.3'] - Fartherest IU from OU (L1) S(T)+A+C+D+E+g / S(T)+A+B+c 165 [541'] 190 [623'] Fartherest IU from the first Joint (L2) C+D+E+g / B+c 40 [131'] 40 [131'] Height between OU and IU (OU above IU) H 50 [164'] - Height between OU and IU (OU under IU) H' 40 [131'] - Height between IU and IU h1 15 [49'] -OU: Outdoor Unit, IU: Indoor Unit
Piping "A" size selection rule (mm [in.]) Outdoor and the first Joint Pipe(Liquid) Pipe(Gas) CMY-Y100VBK2=CMY-Y202-G2 ø12.70[1/2"] ø28.58[1-1/8"]*1 ø15.88[5/8"] ø28.58[1-1/8"]*2 CMY-Y200VBK2=CMY-Y302-G2 ø19.05[3/4"] ø34.93[1-3/8"]*3 ø19.05[3/4"] ø41.28[1-5/8"]*4CMY-Y100VBK2; *1 PUHY-EP400YSJM, *2 PUHY-P500-650YSJM, EP450-600YSJMCMY-Y200VBK2; *3 PUHY-P700-800YSJM, *4 PUHY-P850-900YSJMFor Piping size "S","T", please refer to specification of the Twining kit CMY-Y100,200VBK2 at the Outdoor unit's external drawing.
Piping"B","C","D","E" size selection rule (mm [in.]) Total down-stream Indoor capacity Pipe(Liquid) Pipe(Gas) ~ P140 ø9.52 [3/8"] ø15.88 [5/8"] P141 ~ P200 ø9.52 [3/8"] ø19.05 [3/4"] P201 ~ P300 ø9.52 [3/8"] ø22.20 [7/8"] P301 ~ P400 ø12.70 [1/2"] ø28.58 [1-1/8"] P401 ~ P650 ø15.88 [5/8"] ø28.58 [1-1/8"] P651 ~ P800 ø19.05 [3/4"] ø34.93 [1-3/8"] P801 ~ ø19.05 [3/4"] ø41.28 [1-5/8"]
Piping"a","b","c","d","e","f","g" size selection rule (mm [in.]) Indoor Unit size Pipe(Liquid) Pipe(Gas) P20,P25,P32,P40,P50,GUF-50RD(H) ø6.35 [1/4"] ø12.70 [1/2"] P63,P71,P80,P100,P125,GUF-100RD(H) ø9.52 [3/8"] ø15.88 [5/8"] P200 ø9.52 [3/8"] ø19.05 [3/4"] P250 ø9.52 [3/8"] ø22.20 [7/8"]
Bent equivalent length "M" Outdoor unit model M (m/bent [ft./bent]) PUHY-EP400YSJM-A 0.50 [1.64] PUHY-EP450YSJM-A 0.50 [1.64] PUHY-(E)P500YSJM-A(1) 0.50 [1.64] PUHY-(E)P550YSJM-A 0.50 [1.64] PUHY-(E)P600YSJM-A(1) 0.50 [1.64] PUHY-P650YSJM-A 0.50 [1.64] PUHY-P700YSJM-A(1) 0.70 [2.29] PUHY-P750YSJM-A 0.70 [2.29] PUHY-P800YSJM-A(1) 0.70 [2.29] PUHY-P850YSJM-A 0.80 [2.62] PUHY-P900YSJM-A 0.80 [2.62]
*1*2
OUOU
Note3. Indoor capacity is described as its model size; For example, PEFY-P32VMA-E, its capacity is P32;Note4. Total down-stream Indoor capacity is the summary of the model size of Indoors downstream. For example, PEFY-P25VMA-E+PEFY-P32VMA-E: Total Indoor capacity=P25+P32=P57Note5. Piping sized determined by the Total down-stream indoor capacity is NOT necessary to be bigger than the up-stream one. i.e. A>=B; A>=C>=D
*1 90m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.*2 60m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.
3. Piping Design DATA G8
SYSTEM DESIGN 4 - 68
Syst
em Y
Joint selection rule Total down-stream Indoor capacity Joint ~ P200 CMY-Y102S-G2 P201 ~ P400 CMY-Y102L-G2 P401 ~ P650 CMY-Y202-G2 P651 ~ CMY-Y302-G2*PUHY-P950-1250YSJM's first Joint is always CMY-Y302-G2;*PUHY-EP650YSJM's first Joint is always CMY-Y202-G2;*PUHY-EP700-900YSJM's first Joint is always CMY-Y302-G2;*The total capacity of the units in the downstream of the branch joint on at least one of the piping lines that are connected to the branch joint should be 650 or below. If the total capacity of the units in the downstream of the branch joints on both lines is 650 or above use two branch joints (CMY-Y302-G2). *Concerning detailed usage of Joint parts, refer to its Installation Manual.
Header selection rule 4-branch Header 8-branch Header 10-branch Header CMY-Y104-G CMY-Y108-G CMY-Y1010-G Total down-stream Indoor capacity <=P200 <=P400 <=P650* CMY-Y104-G can directly connect PUHY-(E)P200YJM, but can NOT directly connect PUHY-(E)P250YJM or above; * CMY-Y108-G can directly connect PUHY-(E)P200-450YJM, but can NOT directly connect PUHY-(E)P500YSJM or above; * CMY-Y1010-G can directly connect PUHY-P200-650Y(S)JM, PUHY-EP200-600Y(S)JM; * CMY-Y104-G can NOT connect P200,P250 Indoor, but CMY-Y108, Y1010-G can do; * Concerning detailed usage of Header parts, refer to its Installation Manual.
2nd Outdoor Twinning Kit
1st Outdoor Twinning Kit
Note1. No Joint after Header; Piping direct to Indoor Unit from Header;Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;
Piping length needs to consider the actual length and equivalent length which bents are counted.Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.
H (O
U a
bove
IU)
H' (
OU
und
er IU
)
h2
1st Joint
Joint
L2L1
IU
g
IU
e
IU
d
C
D
IU
f
E
T
S
M N
A BHeader
IU : Indoor unit , OU : Outdoor unitFig. 3-2-1C Piping scheme
2m To indoor unitTo indoor unitTo indoor unit To indoor unit 2 m max
Trap (gas pipe only)
Upward incline
Downward incline
Install the pipes from the outdoor unit to the branch joint with a downward incline.
If the length of pipe between the branch joint and outdoor unit exceeds 2 m, provide at rap at a distance 2 m or less from the branch joint.
OK NG
h1
ba
IU IUIU
c
Capped
3-2-3. PUHY-P950-1250YSJM-A,PUHY-EP650-900YSJM-A(1) Piping
Piping length (m [ft.]) Item Piping in the figure Max. length Max. equivalent length Total piping length S+T+M+N+A+B+C+D+E+a+b+c+d+e+f+g 1000[3280'] - Distance between OU and OU M+N+S+T 10[32'] - Height between OU and OU h2 0.1[0.3'] - Fartherest IU from OU (L1) M(N)+S+A+C+D+E+g / M(N)+S+A+B+c 165[541'] 190[623'] Fartherest IU from the first Joint (L2) C+D+E+g / B+c 40[131'] 40[131'] Height between OU and IU (OU above IU) H 50[164'] - Height between OU and IU (OU under IU) H' 40[131'] - Height between IU and IU h1 15[49'] -OU: Outdoor Unit, IU: Indoor Unit
Piping "A" size selection rule (mm [in.]) Outdoor and the first Joint Pipe(Liquid) Pipe(Gas) CMY-Y300VBK2=CMY-Y202-G2 ø15.88[5/8"] ø28.58[1-1/8"]*1 CMY-Y300VBK2=CMY-Y302-G2 ø19.05[3/4"] ø34.93[1-3/8"]*2 ø19.05[3/4"] ø41.28[1-5/8"]*3For Piping size"M","N","S","T", please refer to specification of the Twining kit CMY-Y300VBK2 at the Outdoor unit's external drawing.
*1 PUHY-EP650YSJM*2 PUHY-EP700-800YSJM*3 PUHY-P950-1250YSJM, PUHY-EP850, 900YSJM
Piping"B","C","D","E" size selection rule (mm [in.]) Total down-stream Indoor capacity Pipe(Liquid) Pipe(Gas) ~ P140 ø9.52 [3/8"] ø15.88 [5/8"] P141 ~ P200 ø9.52 [3/8"] ø19.05 [3/4"] P201 ~ P300 ø9.52 [3/8"] ø22.20 [7/8"] P301 ~ P400 ø12.70 [1/2"] ø28.58 [1-1/8"] P401 ~ P650 ø15.88 [5/8"] ø28.58 [1-1/8"] P651 ~ P800 ø19.05 [3/4"] ø34.93 [1-3/8"] P801 ~ ø19.05 [3/4"] ø41.28 [1-5/8"]
Piping"a","b","c","d","e","f","g" size selection rule (mm [in.]) Indoor Unit size Pipe(Liquid) Pipe(Gas) P20,P25,P32,P40,P50,GUF-50RD(H) ø6.35 [1/4"] ø12.70 [1/2"] P63,P71,P80,P100,P125,GUF-100RD(H) ø9.52 [3/8"] ø15.88 [5/8"] P200 ø9.52 [3/8"] ø19.05 [3/4"] P250 ø9.52 [3/8"] ø22.20 [7/8"]
Bent equivalent length "M" Outdoor unit model M (m/bent [ft./bent]) PUHY-EP650YSJM-A 0.50 [1.64] PUHY-EP700YSJM-A(1) 0.70 [2.29] PUHY-EP750YSJM-A(1) 0.70 [2.29] PUHY-EP800YSJM-A(1) 0.70 [2.29] PUHY-EP850YSJM-A 0.80 [2.62] PUHY-EP900YSJM-A 0.80 [2.62] PUHY-P950YSJM-A 0.80 [2.62] PUHY-P1000YSJM-A 0.80 [2.62] PUHY-P1050YSJM-A 0.80 [2.62] PUHY-P1100YSJM-A 0.80 [2.62] PUHY-P1150YSJM-A 0.80 [2.62] PUHY-P1200YSJM-A 0.80 [2.62] PUHY-P1250YSJM-A 0.80 [2.62]
*1*2
*1 90m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.*2 60m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.
OU OU
OU
Note3. Indoor capacity is described as its model size; For example, PEFY-P32VMA-E, its capacity is P32;Note4. Total down-stream Indoor capacity is the summary of the model size of Indoors downstream. For example, PEFY-P25VMA-E+PEFY-P32VMA-E: Total Indoor capacity=P25+P32=P57Note5. Piping sized determined by the Total down-stream indoor capacity is NOT necessary to be bigger than the up-stream one. i.e. A>=B; A>=C>=D
4 - 69
3. Piping Design DATA G8
SYSTEM DESIGN
System Y
3-3. Refrigerant charging calculation
Sample connection(with 8 indoor units)
Amount of refrigerant to be chargedRefrigerant for extended pipes (field piping) is not factory-charged to the outdoor unit. Add an appropriate amount of refrigerant for each pipe on site.
Record the size of each liquid pipe and the amount of refrigerant that was charged on the outdoor unit for future reference.
Calculating the amount of refrigerant to be chargedThe amount of refrigerant to be charged is calculated with the size of the on-site-installed liquid pipes and their length.Calculate the amount of refrigerant to be charged according to the formula below.Round up the calculation result to the nearest 0.1kg. (i.e., 16.08 kg = 16.1 kg)
<Amount of refrigerant to be charged>Calculating the amount of refrigerant to be charged
Amount of factory-charged refrigerant
Sample calculation
Total length of ø19.05 liquid pipe x 0.29
(m)x0.29(kg/m)
+Total length of ø15.88 liquid pipe x 0.2
(m)x0.2(kg/m)
ø19.05ø15.88ø12.70ø9.52ø6.35
C+E=42D+F=1+10=11mB+G=2+5=7mA+I+J+K+M+a+b+c+d+e+f+g=3+5+30+5+5+15+15+5+5+5+5+5=103mi=5m=40x0.29+11x0.2+7x0.12+103x0.06+5x0.024+10=31.52kg=31.5kg
Indoor1:P2502:P2003:P804:P715:P1406:P1257:P638:P25
A : ø9.52B : ø12.70C : ø19.05D : ø15.88E : ø19.05F : ø15.88G : ø12.70 I : ø9.52J : ø9.52K : ø9.52M : ø9.52
a : ø9.52b : ø9.52c : ø9.52d : ø9.52e : ø9.52 f : ø9.52g : ø9.52 i : ø6.35
3m 2m 2m 1m40m10m 5m 5m30m 5m 5m
15m15m 5m 5m 5m 5m 5m 5m
2.0kg2.5kg3.0kg3.5kg4.5kg5.0kg6.0kg8.0kg9.0kg
10.0kg12.0kg14.0kg
+Total length of ø12.7 liquid pipe x 0.12
(m)x0.12(kg/m)
Total length for each pipe size :
This yields the following result :
+Total length of ø9.52 liquid pipe x 0.06
(m)x0.06(kg/m)
+Total length of ø6.35 liquid pipe x 0.024
(m)x0.024(kg/m)
+ ~8081~160
161~330331~390391~480481~630631~710711~800801~890
891~10701071~1250
1251~
Total capacity of connected indoor units
Charged amount
OU OUOU Note1. No Joint after Header; Piping direct to Indoor Unit from Header;
Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;Piping length needs to consider the actual length and equivalent length which bents are counted.Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.
2m To indoor unitTo indoor unitTo indoor unit To indoor unit 2 m max
Trap (gas pipe only)
Upward incline
Downward incline
Install the pipes from the outdoor unit to the branch joint with a downward incline.
If the length of pipe between the branch joint and outdoor unit exceeds 2 m, provide at rap at a distance 2 m or less from the branch joint.
OK NG
Outdoor Twinning KitCMY-Y300VBK2
1st Joint
1 : P250 2 : P200 3 : P80 4 : P71
5 : P140 6 : P125 7 : P63 8 : P25
IU IU IU IU
IU IU IU IU
A B
C
D
E
J K M
F
a b c d
e f g i
G I
8.0kg
6.5kg
11.5kg
11.8kg
P200 modelP250 modelEP200 modelP300 modelP350 modelP400 modelEP250 modelP450 modelEP300 model
Outdoor unit model Charged amount
4. Outdoor Installation DATA G8
SYSTEM DESIGN 4 - 70
Syst
em Y
4. Outdoor Installation4-1. Requirement on installation site
1. No direct thermal radiation to the unit.2. No possibility of annoying the neighbors by the sound of the unit. Valves and refrigerant flow on the outdoor unit may generate noise. 3. Avoid the sites where strong winds blow.4. With strength to bear the weight of the unit.5. Drain flow from the unit is cared at heating mode.6. Enough space for installation and service as shown at 4-2.7. Avoid the sites where acidic solutions or chemical sprays (sulfur series) are used frequently.8. The unit should be secure from combustible gas, oil, steam, chemical gas like acidic solution, sulfur gas and so on.
4 - 71
4. Outdoor Installation DATA G8
SYSTEM DESIGN
System Y
4-2. Spacing
1000[39-3/8]
240 [9-15/32]
45°
50 [1-31/32]<C>
(Unit : mm [in.])
<B>
500
[19-11
/16]
H
h
h
H
100*[3-15/16]
450*[17-23/32]
50* [1-31/32] 50* [1-31/32]
<A>
(1) If the distance is 300 mm [11-13/16 in.] or more between the rear side and the wall
15* [19/32] 15* [19/32]
450*[17-23/32]
300*[11-13/16]
<A>(2) If the distance is 100 mm [3-15/16 in.] or more between the rear side and the wall
• Secure enough space around the unit as shown in the figure.In case of single installation
(3) If the wall height (H) of the front, rear or side exceeds the wall height restriction
(4) If there are obstacles at the upper part of the unit
<A> : Top view<B> : Side view<C> : When there is little space up to an obstruction
::
• When the height of the walls on the front, back or on the sides <H> exceeds the wall height limit as defined below, add the height that exceeds the height limit <h> to the figures that are marked with an asterisk.
<Wall height limit> Front: Up to the unit height Back: Up to 500mm [19-11/16 in.] from the unit bottom Side: Up to the unit height
A
BCD : Air outlet guide (Procured at the site)
: FrontUnit height
Back
A
A
AB
CA
D
If the unit cannot be kept clear of the wall, please change the direction of the air outlet of the unit to blow against the wall to avoid air short cycle.
4. Outdoor Installation DATA G8
SYSTEM DESIGN 4 - 72
Syst
em Y
In case of collective installation and continuous installation
:: Wall height (H)
(Unit : mm [in.])
A
BC
30
450*
300*
100 450*
100*
450* 100*450 450
15*
450 450
900
300*
300*
1000*
900
300*
• When multiple units are installed adjacent to each other, secure enough space to allow for air circulation and passageways between groups of units as shown in the figures.
• At least two sides must be left open.• As with the single installation, add the height that exceeds the height limit <h> to the figures that are marked with
• If there is a wall at both the front and the rear of the unit, install up to six units (three units : P450, EP300) consecutively in the side direction and provide a space of 1000mm or more as inlet space/passage space for each six units (three units : P450, EP300).
an asterisk.
: FrontMust be open
[17-23/32] [17-23/32]
[17-23/32] [17-23/32] [17-23/32] [3-15/16]
[39-3/8]
[17-2
3/32]
[17
-23/3
2]
[11-1
3/16]
[11-1
3/16]
[11
-13/1
6]
[11-1
3/16]
[35
-7/16
] [35
-7/16
]
[3-1
5/16
]
[3-15/16]
[1-3/16]
AA
A
AAA
AAA
AB B
B B
B
B
B B
B
B
C
C
C
C
CC
C
C
C
C
4 - 73
4. Outdoor Installation DATA G8
SYSTEM DESIGN
System Y
4-3. Piping direction
4-3-1. Lifting method
· When lifting the unit with ropes, run the ropes under the unit and use the lifting hole.· Support the unit at four points with two ropes, and avoid giving mechanical shock.· Suspension rope angle must be 40˚ or less, so as to avoid compressing fan guard.· Use two ropes, each at least 8m [26 ft.] in length· Use ropes strong enough to support the weight of the unit.· Always suspend the unit from four corners. (It is dangerous to suspend a unit from two corners and must not be attempt-
ed.)· Use protective pads to keep the ropes from scratching the panels on the unit.
· Products weighing more than 20 kg [45 LBS] should not be carried alone.· Do not carry the product by the PP bands.· To avoid the risk of injury, do not touch the heat exchanger fins. · Plastic bags may pose a risk of choking hazard to children. Tear plastic bags into pieces before disposing of them.· When lifting and transporting outdoor units with ropes, run the ropes through lifting hole at the unit base. Securely
fix the unit so that the ropes will not slide off, and always lift the unit at four points to prevent the unit from falling.
Exercise caution when transporting products.CAUTION
8 [26]
8 [26]
P200-P300EP200
P350-P400EP250
P450EP300
40°
(Unit : m [ft.])
1 2 3
8 [26]40°
8 [26]
8 [26] 40
8 [26]
4. Outdoor Installation DATA G8
SYSTEM DESIGN 4 - 74
Syst
em Y
4-3-2. Installation
30m
m[1
-3/1
6 in
.]30
mm
[1-3
/16
in.]
Install the unit in such a way that the corner of the angle bracket at the base of the unit shown in the figure is securely supported. The brackets may bend if they are not securely supported.
: M10 anchor bolt procured at the site.
: Corner is not seated.
: Fixing bracket for hole-in anchor bolt (3 locations to fix with screws).
: Detachable leg
A
<Without detachable leg>
A
B
B
C
C
D
A A A A
724±
3 [(2
8-13
/32~
28-5
/8)]
724±
3 [(2
8-13
/32~
28-5
/8)]
(For maintenance)
30 [1-3/16]190 [7-1/2]
30 [1-3/16]190 [7-1/2]
4-3-3. Anchor bolt positions
· Secure the unit with anchor bolts as shown in the figure below so that the unit will not topple over with strong wind orduring an earthquake.
· Install the unit on a durable base made of such materials as concrete or angle steel.· Take appropriate anti-vibration measures (e.g., vibration damper pad, vibration isolation base) to keep vibrations and
noise from being transmitted from the unit through walls and floors.· When using a rubber cushion, install it so that the cushion covers the entire width of the unit leg.· Install the unit in such a way that the corner of the angle bracket at the base of the unit shown in the figure below is
securely supported.· Install the anchor bolt in such a way that the top end of the anchor bolt do not stick out more than 30 mm [1-3/16 in.].· This unit is not designed to be anchored with post-installation-type anchor bolts, although by adding fixing brackets
anchoring with such type of anchor bolts becomes possible.
• Individual <P200-P400, EP200, EP250>
installation • Collective installation
Take into consideration the durability of the base, water drainage route (Drain water is discharged from outdoor unitsduring operation.), piping route, and wiring route when performing foundation work.
Properly install the unit on a surface that can withstand the weight ofthe unit. Unit installed on an unstable surface may fall and cause injury.
WARNING
Take appropriate safety measures against strong winds and earth-quakes to prevent the unit from falling.
WARNING
(Unit : mm [in.])
Leave a minimum of 30 mm [1-3/16 in.] between units.
760±2 [29-15/16(29-27/32~30)]
1060±2 [41-3/4(41-21/32~41-13/16)]
P350, P400, EP250
Install the unit in such a way that the corner of the angle bracket at the base of the unit shown in the figure is securely supported. The brackets may bend if they are not securely supported.
<With detachable leg>
A
B
CC
D
D
D
<P450, EP300>
A 795±2 [31-5/16(31-1/4~31-13/32)]
P450, EP300PUHY
A
PUHY
A
P200-P300, EP200PUHY
A A A A
724±
3 [(2
8-13
/32~2
8-5/8
)]
724±
3 [(2
8-13
/32~2
8-5/8
)]
(For maintenance)A
(For maintenance)A
30 [1-3/16]190 [7-1/2]
30 [1-3/16]190 [7-1/2]A A
Leave a minimum of 30 mm [1-3/16 in.] between units.
4 - 75
4. Outdoor Installation DATA G8
SYSTEM DESIGN
System Y
4-3-5. Refrigerant pipe routing
4-3-4. Installation
· P200-P300EP200
· P350-P400EP250
Installation base perpendicular to the unit’s front panelInstallation base parallel to the unit’s front panel
When the pipes and/or cables are routed at the bottom of the unit, make sure that the through hole at the base ofthe unit does not get blocked with the installation base. When the pipes are routed at the bottom of the unit, the base should be at least 100 mm [3-15/16 in.] in height.
(Unit : mm [in.])
(Unit : mm [in.])
(Unit : mm [in.])221 150
86 [3
-13/32
]92
[3-5
/8]
145 [
5-23/3
2]
145
(Mou
ntin
g pi
tch)
(Mounting pitch)
2X2-14X20 Oval hole
Refrigerant service valve <gas>
Refrigerant service valve <liquid>
(760
[29-
15/1
6])
80 760 [29-15/16] 80
1818
131
83251
186
Bottom view
724(
721
72
7)
150
84 [3
-5/16
]
[5-3
/16]
[5-2
3/32
]
[5-3
/16]
[5-2
3/32
]
94 [3
-23/32
]
(Mounting pitch)
Refrigerant servicevalve <liquid>
(Mou
ntin
g pi
tch)
2X2-14X20 Oval hole
Refrigerant servicevalve <gas>
271
216
18
8080 1060 [41-3/4]
18[2
3/32
][2
3/32
]
[23/
32]
[23/
32]
[28-
13/3
2~28
-5/8
]
[28-
13/3
2~28
-5/8
]
301 83
131
(760
[29-
15/1
6])14
5
145 [
5-23/3
2]
Bottom view
724(
721
727
)
[3-5/32][3-5/32][3-5/32] [3-5/32]
[7-11/32] [8-17/32]
[11-7/8] [3-9/32]
[10-11/16] [5-29/32]
[9-29/32] [3-9/32]
[8-23/32] [5-29/32]
The gaps around the edges of through holes for pipes and wires on theunit allow water or mice to enter the unit and damage its parts. Closethese gaps with filler plates.
This unit allows two types of pipe routing:• Bottom piping• Front piping
To prevent small animals, water, and snow fromentering the unit and damage its parts, close thegap around the edges of through holes for pipesand wires with filler plates.
CAUTION
Fill the gap at the siteFiller plate(not supplied)
· P450, EP300
Bottom view[3-5/32]
80795 [31-5/16]
(Mounting pitch) (Mounting pitch)[31-5/16]795
[3-5/32]80 18
[23/
32]
724(
721~
727)
[28-
13/3
2~28
-5/8
]
(Mou
ntin
g pi
tch)
(760
[29-
15/1
6])
18 [23/
32]
[3-2
3/32
]94
84[5
-23/
32]
145 [3
-5/1
6]
[3-9/32]83[21-31/32]558
590[23-1/4][20-1/8]511[5
-3/1
6][5
-23/
32]
145
131
Refrigerant servicevalve <liquid>
Refrigerant service valve <gas>
2X3-14[9/16]X20[13/16] Oval hole[5-29/32]150
4. Outdoor Installation DATA G8
SYSTEM DESIGN 4 - 76
Syst
em Y
4-3-6. Twinning on the outdoor unit side
Reducer
±15°
The tilt angle of the reducer should be within ±15°with the horizontal plane.
Note: See the following drawing for the fitting position of the twinning pipe.
The tilt angle of the twinning pipeThe tilt angle of the twinning pipe must be within ±15° with the horizontal plane. Tilting the twinning pipe more than specified will cause damage to the unit.
The length of the straight part of the pipe before the branchingFor the twinning kit, always use the accessory piping parts. The length of the straight part of pipe connected in front of the twinning pipe must be 500 mm [19 in.] or longer. (Connect the field piping so that the length of the straight part of pipe connected in front of the twinning pipe can be 500 mm [19 in.] or longer.) If the length is less than 500 mm [19 in.], it will cause damage to the unit.
To Indoor unit
Less than 2 m [6 ft.]
To Indoor unit2m
To Indoor unit200 mm [7 in.] or over
Trap (gas pipe only)
The piping connectionWhen connecting the twinning kit to the outdoor unit, note the following:If the length of piping from the twinning kit to the outdoor unit is more than 2 m [6 ft.], install a trap within 2 m [6 ft.] from the outdoor unit. The height of the trap must be 200 mm [7 in.] or higher.
When installing the twinning kit in a higher position than the outdoor unit base, make sure that the twinning kit is installed in a position lower than 200 mm [7 in.] from the outdoor unit base.
<2 m [6 ft.] or less>
<PUHY-P500YSJM-A>
<PUHY-P950YSJM-A>
<More than 2 m [6 ft.]>
Outdoor unit 1 Outdoor unit 2
200 mm [7 in.] or less
Twinning pipe1
To Indoor unit
Outdoor unit 1 Outdoor unit 2 Outdoor unit 3
200 mm [7 in.] or less
Twinning pipe 1 Twinning pipe 2
To Indoor unit
Make sure the pipes from the twinning pipe to the outdoor unit are sloped downwards (towards the twinning pipes).
Do not install traps other than the ones between outdoor units described on a separate sheet to prevent oil backflow and compressor start-up failure.
Caution•
Do not install solenoid valves to prevent oil backflow and compressor start-up failure. • Do not install a sight glass because it may show improper refrigerant flow.If a sight glass is installed, inexperienced technicians that use the glass may overcharge the refrigerant.
•
4 - 77
4. Outdoor Installation DATA G8
SYSTEM DESIGN
System Y
Field piping
Field piping
Twinning kit
The length of the straight pipe
must be 500 mm [19 in.] or longer
Field piping
Field piping
Field piping
Twinning kit
Twinning kitThe length of the straight pipe
must be 500 mm [19 in.] or longer The length of the straight pipe
must be 500 mm [19 in.] or longer
See the following drawing for connecting the pipes between the outdoor units.
<PUHY-P500YSJM-A>
<PUHY-P950YSJM-A>
4-3-7. Twinning on the outdoor unit side
The length of the straight pipe must be 500mm[19 in.] or longer.If not, it may cause improper operation.
CAUTION
4. Outdoor Installation DATA G8
SYSTEM DESIGN 4 - 78
Syst
em Y
4-4. Weather countermeasure
Prevention the Outdoor unit from wind and snow damages in cold or snowy areas, snow hood shown below is recommended and helpful.• Snow hood
Countermeasure to snow and wind
Outlet Inlet
<Side view><Front view> <Front view
<Front view>
>
750 [29-17/32]
453[17-27/32]760 [29-15/16]
(760)[29-15/16]
1210 [47-21/32]
H13
24 [5
2-5/
32]
1324
[52-
5/32
]
(1220)[48-1/16]
1206 [47-1/2]906 [35-11/16]
453[17-27/32]
453[17-27/32]
453[17-27/32]
453[17-27/32]910 [35-27/32]
H86
[3-1
3/32
]
86[3
-13/
32]
800
[31-
1/2]
800
[31-
1/2]
(920)[36-1/4]
In cold and/or snowy areas, sufficient countermeasures to wind and snow damages should be taken for operating unit in normal and good condition in winter time. Surround the units with snow nets or fences to protect them from snow. Even in the other areas, full consideration is required for installation of unit in order to prevent abnormal operations caused by wind or snow. When rain and snow directly fall on unit in the case of air-conditioning operations in 10 or less degrees centigrade outdoor air (50 or less degrees fahrenheit outdoor air) , mount inlet and outlet ducts on unit for assuring stable operations.
A
A
B
B
B
<Side view>
750 [29-17/32]
453[17-27/32]760 [29-15/16]
(760)[29-15/16]
A
B
B
B
B
B
B
453 [17-27/32]
453 [17-27/32] 1750 [68-29/32]
1324
[52-
5/32
]86
[3-1
3/32
]H
800
[31-
1/2]
1740 [68-17/32]
1750 [68-29/32]
4 - 79
4. Outdoor Installation DATA G8
SYSTEM DESIGN
System Y
Countermeasure to windReferring to the figure shown below, take appropriate measures which will suit the actual situation of the place for installation.A unit installed alone is vulnerable to strong winds. Select the installation site carefully to minimize the effect of winds.To install a unit in a place where the wind always blows from the same direction, install the unit so that the outlet faces away from the direction of the wind.
Note:1. Height of frame base for snow damage prevention (H) shall be twice as high as expected snowfall. Width of frame base
shall not exceed that of the unit. The frame base shall be made of angle steel, etc., and designed so that snow and wind slip through the structure. (If frame base is too wide, snow will be accumulated on it.)
2. Install unit so that wind will not directly lash against openings of inlet and outlet ducts.3. Build frame base at customer referring to this figure.
Material : Galvanized steel plate 1.2T [1/16 in. T]Painting : Overall painting with polyester powderColor : Munsell 5Y8/1 (same as that of unit)
4. To install units side by side, install a filler plate between the fan guard and the outlet-side snow food as shown in Figure A. (The filler plate provided accommodates the installation pitch of between 30-80 mm [1-3/16~3-5/32 in.].) 5. When the unit is used in a cold region and the heating operation is continuously performed for a long time when the outside air temperature is below freezing, install a heater to the unit base or take other appropriate measures to prevent water from freezing on the base.
Filler plateFigure A
Wind
Install the outdoor unit where seasonal winds do not blow directly against the unit, such as behind a building.
Install the outdoor unit to avoid having seasonal winds against the front of air outlet/inlet on the unit.
A
A
A
A
4. Outdoor Installation DATA G8
SYSTEM DESIGN 4 - 80
Syst
em Y
4-5. Caution on selecting outdoor units
Consult your dealer when the following issues on Y system are the key concern.· Warm air may flow out from the indoor unit during heating Thermo-OFF.· Refrigerant flow sound may occur in the rooms with low background noise such as hotel rooms, hospital rooms, bedrooms, or conference rooms.To avoid the above issues on Y system, changing board settings on the indoor and outdoor units is required.Ask AC&R Works for details.
4 - 81
5. Caution for refrigerant leakage DATA G8
SYSTEM DESIGN
System Y
5. Caution for refrigerant leakageThe installer and/or air conditioning system specialist shall secure safety against refrigerant leakage according to local regulations or standards.The following standard may be applicable if no local regulation or standard is available.
5-1. Refrigerant property
5-2. Confirm the Critical concentration and take countermeasure
R410A refrigerant is harmless and incombustible. The R410A is heavier than the indoor air in density. Leakage of the refrigerant in a room has possibility to lead to a hypoxia situation. Therefore, the Critial concentration specified below shall not be exceeded even if the leakagehappens.
Critical concentrationCritical concentration hereby is the refrigerant concentration in which no human body would be hurt if immediate measures can be takenwhen refrigerant leakage happens.
Critical concentration of R410A: 0.30kg/m3
(The weight of refrigeration gas per 1 m3 air conditioning space.);The Critical concentration is subject to ISO5149, EN378-1.
For the CITY MULTI system, the concentration of refrigerant leaked should not have a chance to exceed the Critical concentration in any situntion.
The maximum refrigerant leakage concentration (Rmax) is defined as the result of the possible maximum refrigerant weight (Wmax)leaked into a room divided by its room capacity (V).It is referable to Fig.5-1.The refrigerant of Outdoor unit here includes its originalcharge and additional charge at the site.The additional charge is calculated according to “3-3 .Refrigerant charging calculation” and shall not be over charged at the site.Procedure 5-2-1~3 tells how to confirm maximum refrigerant leakage concentration (Rmax) and how to take countermeasures againsta possible leakage.
Refrigerant pipe
to Outdoor unit
Indoor unit
Opening
Fresh air supply fan (always ON)
Indoor space
(Floor)
Fig.5-2.Fresh air supply always ON
Refrigerant pipe
to Outdoor unit
Indoor unit
Opening
Sensor for refrigerant leakage (Oxygen sensor or refrigerant sensor).[At 0.3m height from the floor]
Fresh air supply fan
Indoor space
(Floor)
Fig.5-3.Fresh air supply upon sensor action
Refrigerant pipe (high pressure pipe)
Refrigerant stop valve
to Outdoor unit
Indoor unit
Opening
Sensor for refrigerant leakage (Oxygen sensor or refrigerant sensor).[At 0.3m height from the floor]
Fresh air supply fan
Indoor space
(Floor)
Fig.5-4.Fresh air supply and refrigerantshut-off upon sensor action
Note 1.Countermeasure 3 should be done in a proper way in which the fresh air supply shall be on whenever the leakage happens.Note 2.In principle, MITSUBISHI ELECTRIC requires proper piping design, installation and air-tight testing after installation to avoid leakage happening.
In the area should earthquake happen, anti-vibration measures should be fully considered.The piping should consider the extension due to the temperature variation.
Outdoor unit (No.1)
Flow of refrigerant
Indoor unit
Maximum refrigerant leakage concentration (Rmax)
Outdoor unit (No.1) Outdoor unit (No.2)
Indoor unit
Flow of refrigerant Flow of refrigerant
Rmax=Wmax / V (kg/m3)Maximum refrigerant leakage concentration (Rmax) Rmax=Wmax / V (kg/m3)where, Wmax=W1+W2
W1: Refrigerant weight of Outdoor unit No.1W2: Refrigerant weight of Outdoor unit No.2
Fig. 5-1 The maximum refrigerant leakage concentration5-2-1.Find the room capacity (V),
If a room having total opening area more than 0.15% of the floor area at a low position with another room/space, the two rooms/space areconsidered as one.The total space shall be added up.
5-2-2.Find the possible maximum leakage (Wmax) in the room.If a room has Indoor unit(s) from more than 1 Outdoor unit, add up the refriger-ant of the Outdoor units.
5-2-3.Divide (Wmax) by (V) to get the maximum refrigerant leakage concentration (Rmax).5-2-4.Find if there is any room in which the maximum refrigerant leakage concentration (Rmax) is over 0.30kg/m3.
If no, then the CITY MULTI is safe against refrigerant leakage.If yes, following countermeasure is recommended to do at site.Countermeasure 1:Let-out (making V bigger)
Design an opening of more than 0.15% of the floor area at a low position of the wall to let out the refrigerant whenever leaked.e.g.make the upper and lower seams of door big enough.
Countermeasure 2:Smaller total charge (making Wmax smaller) e.g.Avoid connecting more than 1 Outdoor unit to one room.e.g.Using smaller model size but more Outdoor units.e.g.Shorten the refrigerant piping as much as possible.
Countermeasure 3:Fresh air in from the ceiling (Ventilation) As the density of the refrigerant is bigger than that of the air.Fresh air supply from the ceiling is better than air exhausting from the ceiling.Fresh air supply solution refers to Fig.5-2~4.