4 - 35 CITY MULTI DATA G8 SYSTEM DESIGN Y SERIES SYSTEM DESIGN Y SERIES 1. Electrical work.................................................................................................................................................. 4 - 36 1-1.General cautions ....................................................................................................................................... 4 - 36 1-2.Power supply for Indoor unit and Outdoor unit .......................................................................................... 4 - 37 1-3.Power cable specifications ........................................................................................................................ 4 - 43 1-4.Power supply examples............................................................................................................................. 4 - 44 2. M-NET control.................................................................................................................................................. 4 - 47 2-1.Transmission cable length limitation.......................................................................................................... 4 - 47 2-2.Transmission cable specifications ............................................................................................................. 4 - 48 2-3.System configuration restrictions............................................................................................................... 4 - 49 2-4.Address setting .......................................................................................................................................... 4 - 52 3. Piping Design................................................................................................................................................... 4 - 65 3-1.R410A Piping material ............................................................................................................................... 4 - 65 3-2.Piping Design ............................................................................................................................................ 4 - 66 3-3.Refrigerant charging calculation ................................................................................................................ 4 - 69 4. Outdoor Installation.......................................................................................................................................... 4 - 70 4-1.Requirement on installation site ................................................................................................................ 4 - 70 4-2.Spacing...................................................................................................................................................... 4 - 71 4-3.Piping direction .......................................................................................................................................... 4 - 73 4-4.Weather countermeasure .......................................................................................................................... 4 - 78 4-5.Caution on selecting outdoor units ............................................................................................................ 4 - 80 5. Caution for refrigerant leakage ........................................................................................................................ 4 - 81 5-1.Refrigerant property................................................................................................................................... 4 - 81 5-2.Confirm the Critical concentration and take countermeasure.................................................................... 4 - 81

CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 35

CITY MULTI

DATA G8

SYSTEM DESIGN Y SERIES

SYSTEM DESIGN Y SERIES

1. Electrical work.................................................................................................................................................. 4 - 361-1.General cautions ....................................................................................................................................... 4 - 361-2.Power supply for Indoor unit and Outdoor unit .......................................................................................... 4 - 371-3.Power cable specifications ........................................................................................................................ 4 - 431-4.Power supply examples............................................................................................................................. 4 - 44

2. M-NET control.................................................................................................................................................. 4 - 472-1.Transmission cable length limitation.......................................................................................................... 4 - 472-2.Transmission cable specifications ............................................................................................................. 4 - 482-3.System configuration restrictions............................................................................................................... 4 - 492-4.Address setting.......................................................................................................................................... 4 - 52

3. Piping Design................................................................................................................................................... 4 - 653-1.R410A Piping material ............................................................................................................................... 4 - 653-2.Piping Design ............................................................................................................................................ 4 - 663-3.Refrigerant charging calculation ................................................................................................................ 4 - 69

4. Outdoor Installation.......................................................................................................................................... 4 - 704-1.Requirement on installation site ................................................................................................................ 4 - 704-2.Spacing...................................................................................................................................................... 4 - 714-3.Piping direction .......................................................................................................................................... 4 - 734-4.Weather countermeasure .......................................................................................................................... 4 - 784-5.Caution on selecting outdoor units ............................................................................................................ 4 - 80

5. Caution for refrigerant leakage ........................................................................................................................ 4 - 815-1.Refrigerant property................................................................................................................................... 4 - 815-2.Confirm the Critical concentration and take countermeasure.................................................................... 4 - 81

Page 2: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

1. Electrical work DATA G8

SYSTEM DESIGN 4 - 36

Syst

em Y

I.1. Electrical work1-1. General cautions

OK NO

Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiringregulations, and guidance of each electric power company.Wiring for control (hereinafter referred to as transmission cable) shall be (50mm[1-5/8in.] or more) apart from power sourcewiring so that it is not influenced by electric noise from power source wiring. (Do not insert transmission cable and power source wire in the same conduit.)Be sure to provide designated grounding work to outdoor unit.Give some allowance to wiring for electrical part box of indoor and outdoor units, because the box is sometimes removedat the time of service work.Never connect 380~415V(220~240V) power source to terminal block of transmission cable. If connected,electrical partswill be burnt out.Use 2-core shield cable for transmission cable. If transmission cables of different systems are wired with the samemultiple-core cable, the resultant poor transmitting and receiving will cause erroneous operations.

Outdoorunit

Indoor unit

Remote

BC controllercontroller

2-core shield cable

2-core shield cable

Outdoorunit

Remotecontroller

Indoor unit

Multiple-core cable

BC controller

Page 3: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 37

1. Electrical work DATA G8

SYSTEM DESIGN

System Y

1-2. Power supply for Indoor unit and Outdoor unit1-2-1. Electrical characteristics of Indoor unit

Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Motor Output : Fan motor rated output

PMFY-P-VBM-EPower supply IFM

Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PMFY-P20VBM-E

220-240V / 50Hz220V / 60Hz

Max.: 264VMin.: 198V

0.25 0.028 0.20PMFY-P25VBM-E 0.26 0.028 0.21PMFY-P32VBM-E 0.26 0.028 0.21PMFY-P40VBM-E 0.33 0.028 0.26

PLFY-P-VCM-EPower supply IFM

Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PLFY-P20VCM-E

220-240V / 50Hz Max.: 264VMin.: 198V

0.29 0.011 0.23PLFY-P25VCM-E 0.29 0.015 0.23PLFY-P32VCM-E 0.35 0.020 0.28PLFY-P40VCM-E 0.35 0.020 0.28

PLFY-P-VBM-EPower supply IFM

Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PLFY-P32VBM-E

220-240V / 50Hz220V / 60Hz

Max.: 264VMin.: 198V

0.28 0.050 0.22PLFY-P40VBM-E 0.36 0.050 0.29PLFY-P50VBM-E 0.36 0.050 0.29PLFY-P63VBM-E 0.45 0.050 0.36PLFY-P80VBM-E 0.64 0.050 0.51PLFY-P100VBM-E 1.25 0.120 1.00PLFY-P125VBM-E 1.34 0.120 1.07

PLFY-P-VLMD-EPower supply IFM

Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PLFY-P20VLMD-E

220-240V / 50Hz220-230V / 60Hz

Max.: 264VMin.: 198V

0.45 / 0.46 0.015 0.36 / 0.37PLFY-P25VLMD-E 0.45 / 0.46 0.015 0.36 / 0.37PLFY-P32VLMD-E 0.45 / 0.46 0.015 0.36 / 0.37PLFY-P40VLMD-E 0.50 / 0.53 0.015 0.40 / 0.42PLFY-P50VLMD-E 0.51 / 0.54 0.020 0.41 / 0.43PLFY-P63VLMD-E 0.61 / 0.64 0.020 0.49 / 0.51PLFY-P80VLMD-E 0.90 / 0.93 0.020 0.72 / 0.74PLFY-P100VLMD-E 0.94 / 1.10 0.030 0.75 / 0.88PLFY-P125VLMD-E 1.69 / 1.69 0.078x2 1.35 / 1.35

PEFY-P-VMR-E-L/RPower supply IFM

Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PEFY-P20VMR-E-L/R

220-240V / 50Hz220-230V / 60Hz

Max.: 264VMin.: 198V

0.37 / 0.37 0.018 0.29 / 0.29PEFY-P25VMR-E-L/R 0.37 / 0.37 0.018 0.29 / 0.29PEFY-P32VMR-E-L/R 0.43 / 0.48 0.023 0.34 / 0.38

PEFY-P-VMS1-EPower supply IFM

Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PEFY-P15VMS1-E

220-240V / 50Hz220-240V / 60Hz

Max.: 264VMin.: 198V

0.63 / 0.63 0.096 0.50 / 0.50PEFY-P20VMS1-E 0.70 / 0.70 0.096 0.56 / 0.56PEFY-P25VMS1-E 0.75 / 0.75 0.096 0.60 / 0.60PEFY-P32VMS1-E 0.75 / 0.75 0.096 0.60 / 0.60PEFY-P40VMS1-E 0.83 / 0.82 0.096 0.66 / 0.65PEFY-P50VMS1-E 1.02 / 1.00 0.096 0.81 / 0.80PEFY-P63VMS1-E 1.08 / 1.07 0.096 0.86 / 0.85

Page 4: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

1. Electrical work DATA G8

SYSTEM DESIGN 4 - 38

Syst

em Y

Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Motor Output : Fan motor rated output

PEFY-P-VMS1L-EPower supply IFM

Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PEFY-P15VMS1L-E

220-240V / 50Hz220-240V / 60Hz

Max.: 264VMin.: 198V

0.46 / 0.46 0.096 0.37 / 0.37PEFY-P20VMS1L-E 0.54 / 0.54 0.096 0.43 / 0.43PEFY-P25VMS1L-E 0.59 / 0.59 0.096 0.47 / 0.47PEFY-P32VMS1L-E 0.59 / 0.59 0.096 0.47 / 0.47PEFY-P40VMS1L-E 0.68 / 0.68 0.096 0.54 / 0.54PEFY-P50VMS1L-E 0.84 / 0.84 0.096 0.67 / 0.67PEFY-P63VMS1L-E 0.91 / 0.91 0.096 0.73 / 0.73

PEFY-P-VMH-EPower supply IFM

Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PEFY-P40VMH-E

220-240V / 50Hz220-240V / 60Hz

Max.: 264VMin.: 198V

1.21 / 1.61 0.08 0.97 / 1.29PEFY-P50VMH-E 1.21 / 1.61 0.08 0.97 / 1.29PEFY-P63VMH-E 1.49 / 1.95 0.12 1.19 / 1.56PEFY-P71VMH-E 1.58 / 2.18 0.14 1.26 / 1.74PEFY-P80VMH-E 1.85 / 2.40 0.18 1.48 / 1.92PEFY-P100VMH-E 3.03 / 3.93 0.26 2.42 / 3.14PEFY-P125VMH-E 3.03 / 3.93 0.26 2.42 / 3.14PEFY-P140VMH-E 3.10 / 3.98 0.26 2.48 / 3.18PEFY-P200VMH-E 380-415V / 50Hz

380-415V / 60HzMax.: 456VMin.: 342V

2.03 / 2.33 0.76 1.62 / 1.86PEFY-P250VMH-E 2.50 / 2.88 1.08 2.00 / 2.30

PEFY-P-VMA-EPower supply IFM

Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PEFY-P20VMA-E

220-240V / 50Hz220-240V / 60Hz

Max.: 264VMin.: 198V

1.03 0.085 0.82PEFY-P25VMA-E 1.03 0.085 0.82PEFY-P32VMA-E 1.18 0.085 0.95PEFY-P40VMA-E 1.43 0.085 1.14PEFY-P50VMA-E 1.54 0.085 1.23PEFY-P63VMA-E 2.22 0.121 1.78PEFY-P71VMA-E 2.46 0.121 1.97PEFY-P80VMA-E 2.47 0.121 1.98PEFY-P100VMA-E 3.30 0.244 2.64PEFY-P125VMA-E 3.39 0.244 2.71PEFY-P140VMA-E 3.29 0.244 2.63

PEFY-P-VMAL-EPower supply IFM

Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PEFY-P20VMAL-E

220-240V / 50Hz220-240V / 60Hz

Max.: 264VMin.: 198V

0.92 0.085 0.74PEFY-P25VMAL-E 0.92 0.085 0.74PEFY-P32VMAL-E 1.07 0.085 0.86PEFY-P40VMAL-E 1.32 0.085 1.06PEFY-P50VMAL-E 1.40 0.085 1.12PEFY-P63VMAL-E 2.08 0.121 1.67PEFY-P71VMAL-E 2.32 0.121 1.86PEFY-P80VMAL-E 2.36 0.121 1.89PEFY-P100VMAL-E 3.19 0.244 2.55PEFY-P125VMAL-E 3.27 0.244 2.62PEFY-P140VMAL-E 3.17 0.244 2.53

PEFY-P-VMH-E-FPower supply IFM

Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PEFY-P80VMH-E-F 220-240V / 50Hz

208-230V / 60HzMax.: 264VMin.: 187V

0.92 / 1.15 0.09 0.73 / 0.92PEFY-P140VMH-E-F 1.58 / 1.84 0.14 1.26 / 1.47PEFY-P200VMH-E-F 380-415V / 50Hz

380-415V / 60HzMax.: 456VMin.: 342V

0.73 / 0.93 0.20 0.58 / 0.74PEFY-P250VMH-E-F 0.85 / 1.08 0.23 0.68 / 0.86

Page 5: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 39

1. Electrical work DATA G8

SYSTEM DESIGN

System Y

Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Motor Output : Fan motor rated output

PKFY-P-VBM-EPower supply IFM

Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PKFY-P15VBM-E

220-240V / 50Hz220V / 60Hz

Max.: 264VMin.: 198V

0.25 0.017 0.20PKFY-P20VBM-E 0.25 0.017 0.20PKFY-P25VBM-E 0.25 0.017 0.20

PKFY-P-VHM-EPower supply IFM

Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PKFY-P32VHM-E

220-240V / 50Hz220V / 60Hz

Max.: 264VMin.: 198V

0.38 0.030 0.30PKFY-P40VHM-E 0.38 0.030 0.30PKFY-P50VHM-E 0.38 0.030 0.30

PKFY-P-VKM-EPower supply IFM

Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PKFY-P63VKM-E 220-240V / 50Hz

220V / 60HzMax.: 264VMin.: 198V

0.36 0.056 0.29PKFY-P100VKM-E 0.63 0.056 0.50

PCFY-P-VKM-EPower supply IFM

Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PCFY-P40VKM-E

220-240V / 50Hz220V / 60Hz

Max.: 264VMin.: 198V

0.35 0.090 0.28PCFY-P63VKM-E 0.41 0.095 0.33PCFY-P100VKM-E 0.81 0.160 0.65PCFY-P125VKM-E 0.95 0.160 0.76

PFFY-P-VKM-EPower supply IFM

Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)PFFY-P20VKM-E

220-240V / 50Hz Max.: 264VMin.: 198V

0.25 0.03x2 0.20PFFY-P25VKM-E 0.25 0.03x2 0.20PFFY-P32VKM-E 0.25 0.03x2 0.20PFFY-P40VKM-E 0.30 0.03x2 0.24

PFFY-P-VLEM-EPower supply IFM

Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PFFY-P20VLEM-E

220-240V / 50Hz208-230V / 60Hz

Max.: 264VMin.: 187V

0.24 / 0.31 0.015 0.19 / 0.25PFFY-P25VLEM-E 0.24 / 0.31 0.015 0.19 / 0.25PFFY-P32VLEM-E 0.36 / 0.38 0.018 0.29 / 0.30PFFY-P40VLEM-E 0.40 / 0.41 0.030 0.32 / 0.33PFFY-P50VLEM-E 0.50 / 0.51 0.035 0.40 / 0.41PFFY-P63VLEM-E 0.58 / 0.59 0.050 0.46 / 0.47

Page 6: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

1. Electrical work DATA G8

SYSTEM DESIGN 4 - 40

Syst

em Y

Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Motor Output : Fan motor rated output

PFFY-P-VLRM-EPower supply IFM

Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PFFY-P20VLRM-E

220-240V / 50Hz208-230V / 60Hz

Max.: 264VMin.: 187V

0.24 / 0.31 0.015 0.19 / 0.25PFFY-P25VLRM-E 0.24 / 0.31 0.015 0.19 / 0.25PFFY-P32VLRM-E 0.36 / 0.38 0.018 0.29 / 0.30PFFY-P40VLRM-E 0.40 / 0.41 0.030 0.32 / 0.33PFFY-P50VLRM-E 0.50 / 0.51 0.035 0.40 / 0.41PFFY-P63VLRM-E 0.58 / 0.59 0.050 0.46 / 0.47

PFFY-P-VLRMM-EPower supply IFM

Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)PFFY-P20VLRMM-E

220-240V / 50Hz Max.: 264VMin.: 198V

0.59 / 0.58 0.096 0.47 / 0.46PFFY-P25VLRMM-E 0.59 / 0.58 0.096 0.47 / 0.46PFFY-P32VLRMM-E 0.69 / 0.69 0.096 0.55 / 0.55PFFY-P40VLRMM-E 0.78 / 0.76 0.096 0.62 / 0.61PFFY-P50VLRMM-E 0.80 / 0.79 0.096 0.64 / 0.63PFFY-P63VLRMM-E 0.93 / 0.93 0.096 0.74 / 0.74

GUF-RDH3Power supply IFM

Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)GUF-50RD(H)3 220-240V / 50Hz

220V / 60HzMax.: 264VMin.: 198V

1.85 / 1.85 0.081x2 1.48 / 1.48GUF-100RD(H)3 3.49 / 3.49 0.16x2 2.79 / 2.79

Page 7: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 41

1. Electrical work DATA G8

SYSTEM DESIGN

System Y

1-2-2. Electrical characteristics of Outdoor unit

PUHY-P-YJM Unit CombinationUnits Power supply Compressor FAN RLA(A)(50/60Hz)

Hz Volts Voltage range MCA(A) Output(kW) SC(A) Output

(kW) Cooling Heating

PUHY-P200YJM-A(-BS) -

50/60380 400 415

Max:456V Min:342V

16.01 5.4

8

0.46 9.4 / 9.0 / 8.6 9.8 / 9.3 / 9.0

PUHY-P250YJM-A(-BS) - 18.17 6.8 0.46 12.4 / 11.8 / 11.4 12.3 / 11.7 / 11.3

PUHY-P300YJM-A(-BS) - 21.88 7.7 0.46 15.1 / 14.4 / 13.9 15.6 / 14.8 / 14.2 PUHY-P350YJM-A(-BS) - 26.75 9.9 0.46 18.5 / 17.6 / 17.0 18.8 / 17.9 / 17.2

PUHY-P400YJM-A(-BS) - 31.89 10.1 0.46 22.1 / 21.0 / 20.2 21.6 / 20.5 / 19.8

PUHY-P450YJM-A(-BS) - 37.61 11.6 0.46 26.1 / 24.8 / 23.9 24.6 / 23.4 / 22.5

PUHY-P500YSJM-A(-BS)PUHY-P250YJM-A(-BS)

37.046.8 0.46

25.9 / 24.6 / 23.7 25.3 / 24.1 / 23.2 PUHY-P250YJM-A(-BS) 6.8 0.46

PUHY-P500YSJM-A1(-BS)PUHY-P200YJM-A(-BS)

36.335.4 0.46

25.4 / 24.1 / 23.2 26.1 / 24.8 / 23.9 PUHY-P300YJM-A(-BS) 7.7 0.46

PUHY-P550YSJM-A(-BS)PUHY-P250YJM-A(-BS)

41.336.8 0.46

28.9 / 27.5 / 26.5 28.4 / 27.0 / 26.0 PUHY-P300YJM-A(-BS) 7.7 0.46

PUHY-P600YSJM-A(-BS)PUHY-P250YJM-A(-BS)

45.196.8 0.46

31.6 / 30.0 / 28.9 31.8 / 30.2 / 29.1 PUHY-P350YJM-A(-BS) 9.9 0.46

PUHY-P600YSJM-A1(-BS)PUHY-P300YJM-A(-BS)

45.767.7 0.46

32.0 / 30.4 / 29.3 32.5 / 30.8 / 29.7 PUHY-P300YJM-A(-BS) 7.7 0.46

PUHY-P650YSJM-A(-BS)PUHY-P300YJM-A(-BS)

49.27.7 0.46

34.4 / 32.7 / 31.5 34.5 / 32.8 / 31.6 PUHY-P350YJM-A(-BS) 9.9 0.46

PUHY-P700YSJM-A(-BS)PUHY-P350YJM-A(-BS)

54.29.9 0.46

37.9 / 36.0 / 34.7 37.5 / 35.7 / 34.4 PUHY-P350YJM-A(-BS) 9.9 0.46

PUHY-P700YSJM-A1(-BS)PUHY-P300YJM-A(-BS)

55.637.7 0.46

38.9 / 36.9 / 35.6 38.9 / 37.0 / 35.6 PUHY-P400YJM-A(-BS) 10.1 0.46

PUHY-P750YSJM-A(-BS)PUHY-P350YJM-A(-BS)

59.499.9 0.46

41.6 / 39.6 / 38.1 41.6 / 39.5 / 38.1 PUHY-P400YJM-A(-BS) 10.1 0.46

PUHY-P800YSJM-A(-BS)PUHY-P350YJM-A(-BS)

65.369.9 0.46

45.7 / 43.4 / 41.8 43.3 / 41.2 / 39.7 PUHY-P450YJM-A(-BS) 11.6 0.46

PUHY-P800YSJM-A1(-BS)PUHY-P400YJM-A(-BS)

64.7810.1 0.46

45.3 / 43.0 / 41.5 45.6 / 43.3 / 41.7 PUHY-P400YJM-A(-BS) 10.1 0.46

PUHY-P850YSJM-A(-BS)PUHY-P400YJM-A(-BS)

71.510.1 0.46

50.0 / 47.5 / 45.7 47.9 / 45.5 / 43.9 PUHY-P450YJM-A(-BS) 11.6 0.46

PUHY-P900YSJM-A(-BS)PUHY-P450YJM-A(-BS)

77.3711.6 0.46

54.1 / 51.4 / 49.5 50.7 / 48.1 / 46.4 PUHY-P450YJM-A(-BS) 11.6 0.46

PUHY-P950YSJM-A(-BS)

PUHY-P250YJM-A(-BS)

73.51

6.8 0.46

51.4 / 48.9 / 47.1 50.6 / 48.1 / 46.4 PUHY-P300YJM-A(-BS) 7.7 0.46PUHY-P400YJM-A(-BS) 10.1 0.46

PUHY-P1000YSJM-A(-BS)

PUHY-P300YJM-A(-BS)

77.37

7.7 0.46

54.1 / 51.4 / 49.6 55.9 / 53.1 / 51.2 PUHY-P300YJM-A(-BS) 7.7 0.46PUHY-P400YJM-A(-BS) 10.1 0.46

PUHY-P1050YSJM-A(-BS)

PUHY-P300YJM-A(-BS)

81.51

7.7 0.46

57.0 / 54.2 / 52.2 57.5 / 54.6 / 52.7 PUHY-P350YJM-A(-BS) 9.9 0.46PUHY-P400YJM-A(-BS) 10.1 0.46

PUHY-P1100YSJM-A(-BS)

PUHY-P350YJM-A(-BS)

86.23

9.9 0.46

60.3 / 57.3 / 55.2 60.9 / 57.8 / 55.7 PUHY-P350YJM-A(-BS) 9.9 0.46PUHY-P400YJM-A(-BS) 10.1 0.46

PUHY-P1150YSJM-A(-BS)

PUHY-P350YJM-A(-BS)

92.53

9.9 0.46

64.7 / 61.4 / 59.2 62.9 / 59.7 / 57.6 PUHY-P350YJM-A(-BS) 9.9 0.46PUHY-P450YJM-A(-BS) 11.6 0.46

PUHY-P1200YSJM-A(-BS)

PUHY-P350YJM-A(-BS)

98.53

9.9 0.46

68.9 / 65.4 / 63.1 66.2 / 62.9 / 60.6 PUHY-P400YJM-A(-BS) 10.1 0.46PUHY-P450YJM-A(-BS) 11.6 0.46

PUHY-P1250YSJM-A(-BS)

PUHY-P350YJM-A(-BS)

103.54

9.9 0.46

72.4 / 68.8 / 66.3 68.9 / 65.5 / 63.1 PUHY-P450YJM-A(-BS) 11.6 0.46PUHY-P450YJM-A(-BS) 11.6 0.46

Page 8: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

1. Electrical work DATA G8

SYSTEM DESIGN 4 - 42

Syst

em Y

PUHY-EP-YJM Unit CombinationUnits Power supply Compressor FAN RLA(A)(50/60Hz)

Hz Volts Voltage range MCA(A) Output(kW) SC(A) Output

(kW) Cooling Heating

PUHY-EP200YJM-A(-BS) -

50/60380 400 415

Max:456V Min:342V

16.01 5.4

8

0.46 8.5 / 8.1 / 7.8 9.3 / 8.8 / 8.5 PUHY-EP250YJM-A(-BS) - 18.17 6.8 0.46 11.3 / 10.7 / 10.4 12.0 / 11.4 / 11.0

PUHY-EP300YJM-A(-BS) - 21.88 7.7 0.46 13.5 / 12.8 / 12.4 14.1 / 13.4 / 12.9

PUHY-EP400YSJM-A(-BS)PUHY-EP200YJM-A(-BS)

24.895.4 0.46

17.4 / 16.5 / 15.9 19.2 / 18.2 / 17.6 PUHY-EP200YJM-A(-BS) 5.4 0.46

PUHY-EP450YSJM-A(-BS)PUHY-EP200YJM-A(-BS)

28.65.4 0.46

20.0 / 19.0 / 18.3 21.7 / 20.6 / 19.9 PUHY-EP250YJM-A(-BS) 6.8 0.46

PUHY-EP500YSJM-A(-BS)PUHY-EP200YJM-A(-BS)

32.045.4 0.46

22.4 / 21.3 / 20.5 24.1 / 22.9 / 22.0 PUHY-EP300YJM-A(-BS) 7.7 0.46

PUHY-EP500YSJM-A1(-BS)PUHY-EP250YJM-A(-BS)

32.896.8 0.46

23.0 / 21.8 / 21.0 24.5 / 23.3 / 22.4 PUHY-EP250YJM-A(-BS) 6.8 0.46

PUHY-EP550YSJM-A(-BS)PUHY-EP250YJM-A(-BS)

37.046.8 0.46

25.9 / 24.6 / 23.7 26.6 / 25.3 / 24.3 PUHY-EP300YJM-A(-BS) 7.7 0.46

PUHY-EP600YSJM-A(-BS)PUHY-EP300YJM-A(-BS)

40.477.7 0.46

28.3 / 26.9 / 26.0 29.2 / 27.7 / 26.7 PUHY-EP300YJM-A(-BS) 7.7 0.46

PUHY-EP650YSJM-A(-BS)

PUHY-EP200YJM-A(-BS)

42.05

5.4 0.46

29.4 / 28.0 / 26.9 31.3 / 29.7 / 28.6 PUHY-EP200YJM-A(-BS) 5.4 0.46PUHY-EP250YJM-A(-BS) 6.8 0.46

PUHY-EP700YSJM-A(-BS)

PUHY-EP200YJM-A(-BS)

46.05

5.4 0.46

32.2 / 30.6 / 29.5 33.7 / 32.0 / 30.9 PUHY-EP200YJM-A(-BS) 5.4 0.46PUHY-EP300YJM-A(-BS) 7.7 0.46

PUHY-EP700YSJM-A1(-BS)

PUHY-EP200YJM-A(-BS)

46.77

5.4 0.46

32.7 / 31.1 / 30.0 34.3 / 32.5 / 31.4 PUHY-EP250YJM-A(-BS) 6.8 0.46PUHY-EP250YJM-A(-BS) 6.8 0.46

PUHY-EP750YSJM-A(-BS)

PUHY-EP200YJM-A(-BS)

49.2

5.4 0.46

34.4 / 32.7 / 31.5 37.0 / 35.1 / 33.8 PUHY-EP250YJM-A(-BS) 6.8 0.46PUHY-EP300YJM-A(-BS) 7.7 0.46

PUHY-EP750YSJM-A1(-BS)

PUHY-EP250YJM-A(-BS)

50.48

6.8 0.46

35.3 / 33.5 / 32.3 36.7 / 34.9 / 33.6 PUHY-EP250YJM-A(-BS) 6.8 0.46PUHY-EP250YJM-A(-BS) 6.8 0.46

PUHY-EP800YSJM-A(-BS)

PUHY-EP200YJM-A(-BS)

52.2

5.4 0.46

36.5 / 34.6 / 33.4 38.4 / 36.5 / 35.1 PUHY-EP300YJM-A(-BS) 7.7 0.46PUHY-EP300YJM-A(-BS) 7.7 0.46

PUHY-EP800YSJM-A1(-BS)

PUHY-EP250YJM-A(-BS)

53.49

6.8 0.46

37.4 / 35.5 / 34.2 38.7 / 36.8 / 35.5 PUHY-EP250YJM-A(-BS) 6.8 0.46PUHY-EP300YJM-A(-BS) 7.7 0.46

PUHY-EP850YSJM-A(-BS)

PUHY-EP250YJM-A(-BS)

56.92

6.8 0.46

39.8 / 37.8 / 36.4 41.6 / 39.5 / 38.1 PUHY-EP300YJM-A(-BS) 7.7 0.46PUHY-EP300YJM-A(-BS) 7.7 0.46

PUHY-EP900YSJM-A(-BS)

PUHY-EP300YJM-A(-BS)

59.78

7.7 0.46

41.8 / 39.7 / 38.3 43.0 / 40.8 / 39.4 PUHY-EP300YJM-A(-BS) 7.7 0.46PUHY-EP300YJM-A(-BS) 7.7 0.46

Page 9: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 43

1. Electrical work DATA G8

SYSTEM DESIGN

System Y

1-3. Power cable specifications

Thickness of wire for main power supply, capacities of the switch and system impedance

ModelMinimum wire thickness (mm2)

Breaker for current leakageLocal swtich (A) Breaker for wiring

(NFB) (A)Max..Permissive

System ImpedanceMain cable Branch Ground Capacity Fuse

Outdoor unit

PUHY-(E)P200YJM 4.0 - 4.0 30A 100mA 0.1sec. or less 25 25 30 *1PUHY-(E)P250YJM 4.0 - 4.0 30A 100mA 0.1sec. or less 32 32 30 *1

PUHY-(E)P300YJM 4.0 - 4.0 30A 100mA 0.1sec. or less 32 32 30 *1

PUHY-P350YJM 6.0 - 6.0 40A 100mA 0.1sec. or less 40 40 40 0.27�PUHY-P400YJM 10.0 - 10.0 60A 100mA 0.1sec. or less 63 63 60 0.22�

PUHY-P450YJM 10.0 - 10.0 60A 100mA 0.1sec. or less 63 63 60 0.19�

Total operatingcurrent of

the indoor unit

F0 = 20 or less *2 1.5 1.5 1.5 20A current sensitivity *3 20 20 20 (apply to IEC61000-3-3)F0 = 30 or less *2 2.5 2.5 2.5 30A current sensitivity *3 30 30 30 (apply to IEC61000-3-3)

F0 = 40 or less *2 4.0 4.0 4.0 40A current sensitivity *3 40 40 40 (apply to IEC61000-3-3)

*1: Meet technical requirements of IEC61000-3-3

*2: Please take the larger of F1 or F2 as the value for F0.F1 = Total operating maximum current of the indoor units × 1.2 Indoor unit V1

F2 = (V1 × Quantity of Type A) + (V1 × Quantity of Type B) + (V1 × Quantity of Others) Type A PLFY-VBM, PMFY-VBM, PEFY-VMS1(L), PCFY-VKM, PKFY-VHM, PKFY-VKM, PFFY-VKM, PFFY-VLRMM

1.6

Type B PEFY-VMA(L) 3.2

Others Other indoor unit 0

*3: Current sensitivity is calculated using the following formula.G1 = (V2 × Quantity of Type 1) + (V2 × Quantity of Type 2) + (V2 × Quantity of Others) + (V3 × Wire length [km])

G1 Current sensitivity Indoor unit V2 Wire thickness (mm2) V3

30mA or less 30mA 0.1sec. or less Type 1 PLFY-VBM, PMFY-VBM, PEFY-VMS1(L), PCFY-VKM, PKFY-VHM, PKFY-VKM, PFFY-VKM, PFFY-VLRMM

2.4 1.5 48

100mA or less 100mA 0.1sec. or less Type 2 PEFY-VMA(L) 1.6 2.5 56

Others Other indoor unit 0 4.0 66

1. Use dedicated power supplies for the outdoor unit and indoor unit. Ensure OC and OS are wired individually.

2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.3. The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one rank thicker in diameter. Make sure the power-supply voltage does not drop more

than 10%.

4. Specific wiring requirements should adhere to the wiring regulations of the region.5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For example, use wiring such as YZW.

6. A switch with at least 3 mm contact separation in each pole shall be provided by the Air Conditioner installer.

� Be sure to use specified wires for connections and ensure no external force is imparted to terminal connections. If connections are not fixed firmly, heating or fire may result.

� Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.

� Some installation sites may require attachment of an earth leakage breaker for the inverter. If no earth leakage breaker is installed, there is a danger of electric shock.

� Do not use anything other than a breaker and fuse with the correct capacity. Using a fuse or wire of too large capacity may cause malfunction or fire.

� This device is intended for the connection to a power supply system with a maximum permissible system impedance shown in the above table at the interface point (power service box) of the user's supply.

� The user must ensure that this device is connected only to a power supply system which fulfils the requirement above.If necessary, the user can ask the public power supply company for the system impedance at the interface point.

� This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc(*2) at the interface point between the user's supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc(*2).

Ssc(*2)Model Ssc(MVA)

PUHY-(E)P200YJM 1.24

PUHY-P250YJM 1.41PUHY-EP250YJM 1.27

PUHY-P300YJM 1.70

PUHY-EP300YJM 1.51PUHY-P350YJM 2.08

PUHY-P400YJM 2.48

PUHY-P450YJM 2.92

Page 10: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

1. Electrical work DATA G8

SYSTEM DESIGN 4 - 44

Syst

em Y

1-4. Power supply examples

The local standards and/or regulations is applicable at a higher priority.1-4-1. PUHY-P200-450YJM-A, PUHY-EP200-300YJM-A

Note4

Note3

To *1 or *2

*1

*2

Note7

Connector CN41 CN40

Power supply3-phase 4-wire380-400-415V 50/60HzNote10,13

Power supply1-phase220-240V 50/60HzNote10 Power supply

1-phase 220-240V 50/60Hz

Centralized control transmission cable>=1.25mm2

Shield cable(CVVS, CPEVS MVVS)

Indoor-outdoor transmission cable>=1.25mm2

Shield cable

Indoor-outdoor transmission cable>=1.25mm2

Shield cable

>=dia.1.6mm

(Using MA remote controller)Connecting TB5 terminal.

(Using ME remote controller)Connecting TB5 terminal.

>=dia.1.6mm

<In the case a system controller is connected.>

TB7(S)

TB1(L1,L2,L3,N)

TB3(M1,M2)

TB5(M1,M2)

TB2(L,N)S

TB15(1,2)

TB5(M1,M2)

TB2(L,N)S

TB15(1,2)

TB5(M1,M2)

TB2(L,N)S

S S

E

TB15(1,2)

TB5(M1,M2)

TB2(L,N)TB1

(R,S)TB2 TB3

S

TB15(1,2)

TB7 (M1,M2)GFI

LWWB

GFI

GFI

Power supply1-phase 220-240V 50/60Hz

LWWB

SC

TransmissionboosterNote8Note9

MA R/C MA R/C MA R/C

ME R/C ME R/C ME R/C

MA R/C cable0.3-1.25mm2

(0.75~1.25mm2)<=200mNote5, Note11

ME R/C cable0.3~1.25mm2

(0.75~1.25mm2)<=10mNote5, Note11

OU

IU (Shield)

(Shield) (Shield)

(Shield)(Shield) (Shield)

Note4

To other OU

Note6Note7

Note6Note7

* Power supply GFI, LW, WB specifications vary with the model of connected indoor units

Note7Power supply1-phase220-240V 50/60HzNote10

>=dia.1.6mm>=dia.1.6mm

TB5(M1,M2)

TB2(L,N)S

TB15(1,2)

TB5(M1,M2)

TB2(L,N)S

TB15(1,2)

TB5(M1,M2)

TB2(L,N)S

S S

E

TB15(1,2)

TB5(M1,M2)

TB2(L,N)TB1

(R,S)TB2 TB3

S

TB15(1,2)

GFILWWB

LWWB

GFILWWB

TransmissionboosterNote8Note9

IU (Shield)

(Shield) (Shield)

(Shield)(Shield) (Shield)* Power supply, GFI, LW, WB specifications vary with the model of connected indoor units

Note: 1 The transmission cable is not-polarity double-wire. 2 Symbol means a screw terminal for wiring. 3 The shield wire of transmission cable should be connected to the grounding terminal at

Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be connected to the S terminal at Indoor unit or all shield wire should be connected together. The broken line at the scheme means shield wire.

4 When the Outdoor unit connected with system controller, power-supply to TB7 of the outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the outdoor units will enable the outdoor unit to supply power to TB7, or an extra power supplying unit PAC-SC51KUA should be used. The transmission cable (above 1.25mm2, shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is called centralized control transmission cable. The shield wire of the centralized control transmission cable must be grounded at the Outdoor unit whose CN41 is changed to CN40.

5 MA R/C transmission cable (0.3-1.25mm2) must be less than 200m in length, while ME R/C transmission cable (0.3-1.25mm2) must be less than 10m in length. But transmission cable to the ME R/C can be extend using a M-NET cable (>=1.25mm2) when the length is counted in the M-Net length. Both Compact MA and ME R/C transmission cables size 0.75~1.25mm2 in thickness.

6 MA remote controller and ME remote controller should not be grouped together.7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA

transmission cable to connect all the TB15 terminals of the Indoor units. It is called "Grouping". If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address Setting".

8 Indoor board consumes power from TB3. The power balance should be considered according to System Design 2-3 "System configuration restrictions".

9 If Transmission booster is needed, be sure to connect the shield wires to the both sides to the booster.

10 The critical current for choosing power source equipment is approximate 1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).

11 Numbers shown with ( ) indicates a diameter of the compact remote controller.12 When System controller (SC) is connected to the system, turn the SW2-1 on.13 The phases of electricity power must be confirmed to be right used. Phase-reverse, or phase-missing could break the controllers.

Note12

Pull box

Pull box

*1 The Ground-fault interrupter should support Inverter circuit. (e.g. Mitsubishi Electric's NV-C series or equivalent).*2 Ground-fault interrupter should combine using of local switch or wiring breaker.*3 It shows data for B-type fuse of the breaker for current leakage.

Local switch Minimum Wire thickness

Earth wire<mm2>

Power wire<mm2>

Wiring breaker(NFB)<A>

OCP*3<A>

BC<A>

Ground-fault interrupter*1, *2

Model Symbol

GFILWBCOCPWBNFBOUIUSCMA R/CME R/C

Ground-fault interrupterLocal switchBreaker capacityOver-current protectorWiring breakerNon-fuse breakerOutdoor unitIndoor unitSystem controllerMA remote controllerME remote controller

PUHY- E P200YJM 30A 100mA 0.1sec. or less 25 25 30 4 4PUHY- E P250YJM 30A 100mA 0.1sec. or less 32 32 30 4 4PUHY- E P300YJM 30A 100mA 0.1sec. or less 32 32 30 4 4PUHY-P350YJM 40A 100mA 0.1sec. or less 40 40 40 6 6PUHY-P400YJM 60A 100mA 0.1sec. or less 63 63 60 10 10PUHY-P450YJM 60A 100mA 0.1sec. or less 63 63 60 10 10

Page 11: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 45

1. Electrical work DATA G8

SYSTEM DESIGN

System Y

The local standards and/or regulations is applicable at a higher priority.1-4-2. PUHY-P500-900YSJM-A(1), PUHY-EP400-600YSJM-A(1)

Power supply3-phase 4-wire380-400-415V 50/60HzNote10,13

GFILWWB

Power supply3-phase 4-wire380-400-415V 50/60HzNote10,13

GFILWWB

Note4

Note3Note3

To *1 or *2

*1

Connector CN41 CN40

Power supply1-phase220-240V 50/60HzNote10

Centralized control transmission cable>=1.25mm2

Shield cable(CVVS, CPEVS MVVS)

Indoor-outdoortransmission cable>=1.25mm2

Shield cable

(Using MA remote controller)Connecting TB5 terminal.

>=dia.1.6mm

TB7(S)

TB7(S)

TB1(L1,L2,L3,N)TB3

(M1,M2)TB7

(M1,M2)TB3

(M1,M2)TB7

(M1,M2)

GFI

SCNote12

OU OUNote4

To other OU

* Power supply, GFI·LW·WB specifications vary with the model of connected indoor units

LWWB

<In the case a system controller is connected.>

TB1(L1,L2,L3,N)

Note: 1 The transmission cable is not-polarity double-wire. 2 Symbol means a screw terminal for wiring. 3 The shield wire of transmission cable should be connected to the grounding terminal at

Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be connected to the S terminal at Indoor unit or all shield wire should be connected together. The broken line at the scheme means shield wire.

4 When the Outdoor unit connected with system controller, power-supply to TB7 of the outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the outdoor units will enable the outdoor unit to supply power to TB7, or an extra power supplying unit PAC-SC51KUA should be used. The transmission cable (above 1.25mm2, shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is called centralized control transmission cable. The shield wire of the centralized control transmission cable must be grounded at the Outdoor unit whose CN41 is changed to CN40.

5 MA R/C transmission cable (0.3-1.25mm2) must be less than 200m in length, while ME R/C transmission cable (0.3-1.25mm2) must be less than 10m in length. But transmission cable to the ME R/C can be extend using a M-NET cable (>=1.25mm2) when the length is counted in the M-Net length. Both Compact MA and ME R/C transmission cables size 0.75~1.25mm2 in thickness.

6 MA remote controller and ME remote controller should not be grouped together.7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA

transmission cable to connect all the TB15 terminals of the Indoor units. It is called "Grouping". If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address Setting".

8 Indoor board consumes power from TB3. The power balance should be considered according to System Design 2-3 "System configuration restrictions".

9 If Transmission booster is needed, be sure to connect the shield wires to the both sides to the booster.

10 The critical current for choosing power source equipment is approximate 1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).

11 Numbers shown with ( ) indicates a diameter of the compact remote controller.12 When System controller (SC) is connected to the system, turn the SW2-1 on.13. The phases of electricity power must be confirmed to be right used. Phase-reverse, or phase-missing could break the controllers.

Note7

Power supply1-phase 220-240V 50/60Hz

>=dia.1.6mm

TB5(M1,M2)

TB2(L,N)S

TB15(1,2)

TB5(M1,M2)

TB2(L,N)S

TB15(1,2)

TB5(M1,M2)

TB2(L,N)S

S S

E

TB15(1,2)

TB5(M1,M2)

TB2(L,N)TB1

(R,S)TB2 TB3

S

TB15(1,2)

GFILWWB

TransmissionboosterNote8Note9

MA R/C MA R/C MA R/C

MA R/C cable0.3-1.25mm2

(0.75~1.25mm2)<=200mNote5, Note11

IU (Shield)

(Shield) (Shield)

(Shield)(Shield) (Shield)

Note6Note7

Pull box

*1 The Ground-fault interrupter should support Inverter circuit. (e.g. Mitsubishi Electric's NV-C series or equivalent).*2 Ground-fault interrupter should combine using of local switch or wiring breaker.*3 It shows data for B-type fuse of the breaker for current leakage.

Local switch Minimum Wire thickness

Earth wire<mm2>

Power wire<mm2>

Wiring breaker(NFB)<A>

OCP*3<A>

BC<A>

Ground-fault interrupter*1, *2

Model Symbol

GFILWBCOCPWBNFBOUIUSCMA R/CME R/C

Ground-fault interrupterLocal switchBreaker capacityOver-current protectorWiring breakerNon-fuse breakerOutdoor unitIndoor unitSystem controllerMA remote controllerME remote controller

PUHY-(E)P200YJM 30A 100mA 0.1sec. or less 25 25 30 4 4PUHY-(E)P250YJM 30A 100mA 0.1sec. or less 32 32 30 4 4PUHY-(E)P300YJM 30A 100mA 0.1sec. or less 32 32 30 4 4PUHY-P350YJM 40A 100mA 0.1sec. or less 40 40 40 6 6PUHY-P400YJM 60A 100mA 0.1sec. or less 63 63 60 10 10PUHY-P450YJM 60A 100mA 0.1sec. or less 63 63 60 10 10

*2

Indoor-outdoor transmission cable>=1.25mm2

Shield cable

(Using ME remote controller)Connecting TB5 terminal.

Power supply1-phase 220-240V 50/60Hz

ME R/C ME R/C ME R/C

ME R/C cable0.3~1.25mm2

(0.75~1.25mm2)<=10mNote5, Note11

Note6Note7

Note7Power supply1-phase220-240V 50/60HzNote10

>=dia.1.6mm>=dia.1.6mm

TB5(M1,M2)

TB2(L,N)S

TB15(1,2)

TB5(M1,M2)

TB2(L,N)S

TB15(1,2)

TB5(M1,M2)

TB2(L,N)S

S S

E

TB15(1,2)

TB5(M1,M2)

TB2(L,N)TB1

(R,S)TB2 TB3

S

TB15(1,2)

GFILWWB

GFILWWB

TransmissionboosterNote8Note9

IU (Shield)

(Shield) (Shield)

(Shield)(Shield) (Shield)* Power supply, GFI·LW·WB specifications vary with the model of connected indoor units

Pull box

Page 12: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

1. Electrical work DATA G8

SYSTEM DESIGN 4 - 46

Syst

em Y

The local standards and/or regulations is applicable at a higher priority.1-4-3. PUHY-P950-1250YSJM-A, PUHY-EP650-900YSJM-A(1)

Note4

Note3Note3

Connector CN41 CN40

Centralized control transmission cable>=1.25mm2

Shield cable(CVVS, CPEVS MVVS)

TB7(S)

TB7(S)

TB1(L1,L2,L3,N)TB3

(M1,M2)TB7

(M1,M2)TB3

(M1,M2)TB7

(M1,M2)

SC

OU OU

Note3

TB7(S)

TB1(L1,L2,L3,N) TB3

(M1,M2)TB7

(M1,M2)

OUNote4

To other OU

<In the case a system controller is connected.>

To *1 or *2

*1

Power supply1-phase220-240V 50/60HzNote10

Indoor-outdoortransmission cable>=1.25mm2

Shield cable

(Using MA remote controller)Connecting TB5 terminal.

>=dia.1.6mmGFI

* Power supply, GFI·LW·WB specifications vary with the model of connected indoor units

LWWB

Note12

TB1(L1,L2,L3,N)

Note: 1 The transmission cable is not-polarity double-wire. 2 Symbol means a screw terminal for wiring. 3 The shield wire of transmission cable should be connected to the grounding terminal at

Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be connected to the S terminal at Indoor unit or all shield wire should be connected together. The broken line at the scheme means shield wire.

4 When the Outdoor unit connected with system controller, power-supply to TB7 of the outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the outdoor units will enable the outdoor unit to supply power to TB7, or an extra power supplying unit PAC-SC51KUA should be used. The transmission cable (above 1.25mm2, shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is called centralized control transmission cable. The shield wire of the centralized control transmission cable must be grounded at the Outdoor unit whose CN41 is changed to CN40.

5 MA R/C transmission cable (0.3-1.25mm2) must be less than 200m in length, while ME R/C transmission cable (0.3-1.25mm2) must be less than 10m in length. But transmission cable to the ME R/C can be extend using a M-NET cable (>=1.25mm2) when the length is counted in the M-Net length. Both Compact MA and ME R/C transmission cables size 0.75~1.25mm2 in thickness.

6 MA remote controller and ME remote controller should not be grouped together.7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA

transmission cable to connect all the TB15 terminals of the Indoor units. It is called "Grouping". If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address Setting".

8 Indoor board consumes power from TB3. The power balance should be considered according to System Design 2-3 "System configuration restrictions".

9 If Transmission booster is needed, be sure to connect the shield wires to the both sides to the booster.

10 The critical current for choosing power source equipment is approximate 1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).

11 Numbers shown with ( ) indicates a diameter of the compact remote controller.12 When System controller (SC) is connected to the system, turn the SW2-1 on.13. The phases of electricity power must be confirmed to be right used. Phase-reverse, or phase-missing could break the controllers.

Note7

Power supply1-phase 220-240V 50/60Hz

>=dia.1.6mm

TB5(M1,M2)

TB2(L,N)S

TB15(1,2)

TB5(M1,M2)

TB2(L,N)S

TB15(1,2)

TB5(M1,M2)

TB2(L,N)S

S S

E

TB15(1,2)

TB5(M1,M2)

TB2(L,N)TB1

(R,S)TB2 TB3

S

TB15(1,2)

GFILWWB

TransmissionboosterNote8Note9

MA R/C MA R/C MA R/C

MA R/C cable0.3-1.25mm2

(0.75~1.25mm2)<=200mNote5, Note11

IU (Shield)

(Shield) (Shield)

(Shield)(Shield) (Shield)

Note6Note7

Pull box

Power supply3-phase 4-wire380-400-415V 50/60HzNote10,13

GFILWWB

Power supply3-phase 4-wire380-400-415V 50/60HzNote10,13

GFILWWB

Power supply3-phase 4-wire380-400-415V 50/60HzNote10,13

GFILWWB

*1 The Ground-fault interrupter should support Inverter circuit. (e.g. Mitsubishi Electric's NV-C series or equivalent).*2 Ground-fault interrupter should combine using of local switch or wiring breaker.*3 It shows data for B-type fuse of the breaker for current leakage.

Local switch Minimum Wire thickness

Earth wire<mm2>

Power wire<mm2>

Wiring breaker(NFB)<A>

OCP*3<A>

BC<A>

Ground-fault interrupter*1, *2

Model Symbol

GFILWBCOCPWBNFBOUIUSCMA R/CME R/C

Ground-fault interrupterLocal switchBreaker capacityOver-current protectorWiring breakerNon-fuse breakerOutdoor unitIndoor unitSystem controllerMA remote controllerME remote controller

PUHY-(E)P200YJM 30A 100mA 0.1sec. or less 25 25 30 4 4PUHY-(E)P250YJM 30A 100mA 0.1sec. or less 32 32 30 4 4PUHY-(E)P300YJM 30A 100mA 0.1sec. or less 32 32 30 4 4PUHY-P350YJM 40A 100mA 0.1sec. or less 40 40 40 6 6PUHY-P400YJM 60A 100mA 0.1sec. or less 63 63 60 10 10PUHY-P450YJM 60A 100mA 0.1sec. or less 63 63 60 10 10

*2

Indoor-outdoor transmission cable>=1.25mm2

Shield cable

(Using ME remote controller)Connecting TB5 terminal.

Power supply1-phase 220-240V 50/60Hz

ME R/C ME R/C ME R/C

ME R/C cable0.3~1.25mm2

(0.75~1.25mm2)<=10mNote5, Note11

Note6Note7

Note7Power supply1-phase220-240V 50/60HzNote10

>=dia.1.6mm>=dia.1.6mm

TB5(M1,M2)

TB2(L,N)S

TB15(1,2)

TB5(M1,M2)

TB2(L,N)S

TB15(1,2)

TB5(M1,M2)

TB2(L,N)S

S S

E

TB15(1,2)

TB5(M1,M2)

TB2(L,N)TB1

(R,S)TB2 TB3

S

TB15(1,2)

GFILWWB

GFILWWB

TransmissionboosterNote8Note9

IU (Shield)

(Shield) (Shield)

(Shield)(Shield) (Shield)* Power supply, GFI·LW·WB specifications vary with the model of connected indoor units

Pull box

Page 13: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 47

2. M-NET control DATA G8

SYSTEM DESIGN

System Y

2. M-NET control2-1. Transmission cable length limitation2-1-1. Using MA Remote controller

2-1-2. Using ME Remote controller

Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm2 [AWG16] or thickerMax. length to Outdoor (M-NET cable) L1+L8, L3+L4, L6, L2+L6+L8, L7 <=200m[656ft.] 1.25mm2 [AWG16] or thickerMax. length from MA to Indoor a1+a2, a1+a2+a3+a4 <=200m[656ft.] 0.3-1.25 mm2 [AWG22-16]24VDC to AG-150A n <=50m[164ft.] 0.75-2.0 mm2 [AWG18-14]

Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7,L1+L2+L3+L5, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm2 [AWG16] or thickerMax. length to Outdoor (M-NET cable) L1+L8, L3+L4, L6, L2+L6+L8, L7, L3+L5 <=200m[656ft.] 1.25mm2 [AWG16] or thickerMax. length from ME to Indoor e1, e2+e3, e4 <=10m[32ft.]*1 0.3-1.25 mm2 [AWG22-16] *124VDC to AG-150A n <=50m[164ft.] 0.75-2.0 mm2 [AWG18-14] *1. If the length from ME to Indoor exceed 10m, use 1.25 mm2 [AWG16] shielded cable, but the total length should be counted into Max. length via Outdoor.

OC, OS1, OS2 : Outdoor unit controller; IC: Indoor unit controller; MA: MA remote controller

OC, OS1, OS2: Outdoor unit controller; IC: Indoor unit controller; ME: ME remote controller

M2

TB7

TB3

IC

(52)

M1 M2 1 2STB5 TB15

1 2TB15

1 2TB15

1 2TB15

1 2TB15

1 2TB 15

1 2TB15

MA

(01)

IC

M1 M2 STB5

(02)

IC

M1 M2 STB5

(04)

IC

M1 M2 STB5

(03)

IC

M1 M2 STB5

(05)

IC

M1 M2 STB5

(07)

IC

M1 M2 STB5

(06)

L2

L1L8

MA

MA

MA

OS1

TB7

(51)

OC

M1 M2 S

TB7

TB3

(54 )

OC

a1 a4

a3

L8

L3 L4

a2

A BA B A B

A B

a2

a1

a1

a2

Group1 Group3 Group5

Shielded wire

Shielded wire

S

Power Supply Unit

AG-150A

PAC-SC51KUA

L6L2

L7

A B

SA B

M2M1 M1

M2M1

M2 S M2M1 M1 S

TB3

IC

Group1 Group3 Group5

M1 M2 STB5

ME

(01)

IC

M1 M2 STB5

(02)

IC

M1 M2 STB5

(04)

IC

M1 M2 STB5

(03)

IC

M1 M2 STB5

(05)

IC

M1 M2 STB5

(07)

IC

M1 M2 STB5

(06)

L1

(101)

ME

(105)

ME

(103)

ME

(155)

e3

L4

L5

e2

e4

e1

A B A B A B

A B

M2

TB7

TB3

(53)

OS2

M1

M2 SM1

SA B

SA B

M2

TB7

TB3

(52)

OS1

TB7

(51)

OC

M1 M2 S

TB7

TB3

(54 )

OC L3

Power Supply Unit

AG-150A

PAC-SC51KUA

L6L7

M2M1 M1

M2M1

M2 S M2M1

M2

TB7

TB3

(53)

OS2

M1

M2 SM1 M1 S

TB3

V+V-FG

n

V+V-FG

V+V-FG

n

V+V-FG

Page 14: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

2. M-NET control DATA G8

SYSTEM DESIGN 4 - 48

Syst

em Y

2-2. Transmission cable specifications

Type of cable

Cable size

Remarks

Sheathed 2-core cable (unshielded)CVV

2

Shielding wire (2-core)CVVS, CPEVS or MVVS

Transmission cables ME Remote controller cables

CVVS, MVVS : PVC insulated PVC jacketed shielded control cableCPEVS :

Connected with simple remote controller. PE insulated PVC jacketed shielded communication cable

CVV : PV insulated PVC sheathed control cable

— Max length : 200m [656ft]

(Li) MA Remote controller cables

When 10m [32ft] is exceeded, use cables withthe same specification as transmission cables.

More than 1.25 [AWG16]2 0.3 1.25 [AWG22 16]

(0.75 1.25 [AWG18 16]) 2

2 0.3 1.25 [AWG22 16](0.75 1.25 [AWG18 16])

Page 15: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 49

2. M-NET control DATA G8

SYSTEM DESIGN

System Y

2-3. System configuration restrictions2-3-1. Common restrictions for the CITYMULTI system

Table 2-3-1 The equivalent power consumption

Table 2-3-2 The equivalent power supply

With the equivalent power consumption values in Table 2-3-1 and Table 2-3-2, PAC-SF46EPA can be designed into theair-conditioner system to ensure proper system communication according to 2-3-2-A, B, C.2-3-2-A) Firstly, count from TB3 at TB3 side the total quantity of Indoor units, OA process units and ME remote controller, Timers

and System controllers. If the total quantity reaches 40, a PAC-SF46EPA should be set. In this case, Indoor unit sizedP200, 250 is counted as 7 Indoor units, but MA remote controller(s), LOSSNAY, PZ-60DR-E is NOT counted.

2-3-2-B) Secondly, count from TB7 side to TB3 side the total transmission power consumption. If the total power consumptionreaches 32, a PAC-SF46EPA should be set. Yet, if a PAC-SC51KUA is used to supply power at TB7 side, count fromTB3 side only.

2-3-2-C) Thirdly, count from TB7 at TB7 side the total transmission power consumption, If the total power consumption reaches6, a PAC-SF46EPA should be set.

For each Outdoor unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table. A) 1 Group of Indoor units can have 1-16 Indoor units; *OA processing unit GUF-RD(H) is considered as Indoor unit. B) Maximum 2 remote controllers for 1 Group; (MA/ME remote controllers cannot be present together in 1group.) C) 1 LOSSNAY unit can interlock maximum 16 Indoor units; 1 Indoor unit can interlock only 1 LOSSNAY unit. D) Maximum 3 System controllers are connectable when connecting to TB3 of the Outdoor unit. E) Maximum 3 System controllers are connectable when connecting to TB7 of the Outdoor unit, if the transmission power is supplied by the Outdoor unit. F) 4 System controllers or more are connectable when connecting to TB7 of the Outdoor unit, if the transmission power is supplied by the power supply unit PAC-SC51KUA. Details refer to 2-3-3-C. *System controller connected as described in D) and E) would have a risk that the failure of connected Outdoor unit would stop power supply to the System controller.

In order to ensure proper communication among Outdoor unit, Indoor unit, LOSSNAY, and OA processing unit GUF-RD(H), and Controllers, the transmission power situation for the M-NET should be observed. In some cases, Transmission booster should be used. Taking the power consumption of Indoor unit sized P20-P140 as 1, the equivalent power consumption or supply of others are listed at Table 2-3-1 and Table 2-3-2.

Indoor, OA unit Indoor unit MA RC. LOSSNAY ME Remote Contr. Timers, System Contr.

System Controller

ON/OFF Contr.

1 7 0 1/4 1/2 1 1/2 2

Sized P15-P140GUF-50, 100

Sized P200,P250

BC controller

2

CMB PAR-21MAAPAC-YT51CRA(B)PAR-FA32MALGH-RX-EPZ-60DR-E

PAR-F27MEAPAC-SE51CRAPZ-52SF-E

PAC-SC30GRAPAC-SF44SRAPAC-YT34STAAG-150A

PAC-YT40ANRA CMS-MNF-B

CMS-MNG-E

*RC : Remote Controller

Transmission Booster

25PAC-SF46EPA

Power supply unit

5PAC-SC51KUA

Expansion controller

6PAC-YG50ECA

Outdoor unit

32Connector TB3 and TB7 total *

Outdoor unit

6Connector TB7 only

*If PAC-SC51KUA is used to supply power at TB7 side, no power supply need from Outdoor unit at TB7, Connector TB3 itself will therefore have 32. Not applicable to the PUMY model.

2-3-2. Ensuring proper communication power for M-NET

MN Converter

BM ADAPTER

6BAC-HD150

6GB-50ADA

System example

Power supply unitPAC-SC51KUA

ME remote controller

ME remote controller

PZ-52SF-E

LOSSNAYunit

PZ-52SF-E

LOSSNAYunit

Outdoor unit

24VDC

M-NET

0201

if the total quantity of Indoor units, OA process units and ME remote controllers reaches 40, (Indoor unit sized P200, 250 is counted as 7); or if the total equivalent transmission power consumption reaches 32.

N1

N3

N2Transmission booster (No.1) should be used,

1.The total quantity of Indoor units, OA process units and ME remote controller should not exceed 40. *Indoor unit sized P200, 250 is counted as 7 units.2.The total equivalent transmission power consumption should not exceed 25.

Within N2, conditions 1,2 should be followed.

N4Within N4, the total equivalent transmission power consumption should not exceed 25.

TB7 TB3

TB7 TB3

if the total equivalent transmission power consumption reaches 5. Transmission booster (No.2) should be used,

PAC-SF46EPA

TRANSMISSION BOOSTER

3.4kg

220-240V:0.7A ~/N

WEIGHT

POWER RATING

MODEL

MADE IN JAPAN

50

UP

PAC-SF46EPA

TRANSMISSION BOOSTER

3.4kg

220-240V:0.7A ~/N

WEIGHT

POWER RATING

MODEL

MADE IN JAPAN

50

UP

Transmissionbooster(No.1)

TransmissionboosterPAC-SF46EPA(No.2)Centralized controller

(AG-150A)

CENTRALIZED CONTROLLER AG-150A

Page 16: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

2. M-NET control DATA G8

SYSTEM DESIGN 4 - 50

Syst

em Y

PAC-SC51KUA

Outdoor unit

MA remote controller

Group Group

Indoor unit

M-NET transmission lines(transmission lines for centralized controller)

M-NET transmission lines(transmission lines for centralized controller)

Outdoor unit

ME remote controller

MA remote controller

ME remote controller

Group Group

Group Group

Group Group

Indoor unit

Indoor unit

Indoor unit

Replacement of CN41 with CN40

Use CN41 as it is.

TB7TB3

TB3

Outdoor unit

Outdoor unit

Replacement of CN41 with CN40

Use CN41 as it is.

System controller (excluding LMAP02-E)

System controller

M-NET transmission lines (Indoor-Outdoor transmission lines)

TB7TB3

System controller

TB7

TB7TB3

Maximum 3 System controllers can be connected to TB3.

Maximum 3 System controllers can be connected to TB7.

M-NET transmission lines(transmission lines for centralized controller) MA remote controller

ME remote controller

Group Group

Group Group

Indoor unit

Indoor unit

TB3

Outdoor unit

Outdoor unit

Use CN41 as it is.

Use CN41 as it is.

System controller

TB7

TB7TB3

CAUTION

M-NET transmission lines (Indoor-Outdoor transmission lines)

M-NET transmission lines (Indoor-Outdoor transmission lines)

The power to System controller (excluding LMAP02-E) is supplied via M-NET transmission line. M-NET transmission line at TB7 side is called Centralized control transmission line while one at TB3 side is called Indoor-Outdoor transmission line. There are 3 ways to supply power to the System controller .A) Connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.B) Connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit. C) Connecting to TB7 of the Outdoor unit but receiving power from power supply unit PAC-SC51KUA.

Maximum 3 System controllers can be connected to TB3. If there is more than 1 Outdoor unit, it is necessary to replace power supply switch connector CN41 with CN40 on one Outdoor unit.

Maximum 3 System controllers can be connected to TB7 and receiving power from the Outdoor unit. It is necessary to replace power supply switch connector CN41 with CN40 on one Outdoor unit.

Fig. 2-3-3-A

Fig. 2-3-3-B

Fig. 2-3-3-C

2-3-3-A. When connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.

2-3-3-B. When connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit.

2-3-3-C. When connecting to TB7 of the Outdoor unit but receiving power from PAC-SC51KUA.

2-3-3. Ensuring proper power supply to System controller

When using PAC-SC51KUA to supply transmission power, the power supply connector CN41 on the Outdoor units should be kept as it is. It is also a factory setting. 1 PAC-SC51KUA supports maximum 1 AG-150A unitdue to the limited power 24VDC at its TB3. However, 1 PAC-SC51KUA supplies transmission power at its TB2 equal to 5 Indoor units, which is referable at Table 2-3-2.If PZ-52SF-E, Timers, System controller, ON/OFF controller connected to TB7 consume transmission power more than 5 (Indoor units), Transmission booster PAC-SF46EPA is needed. PAC-SF46EPA supplies transmission power equal to 25 Indoor units.

AG-150A*1 is recommended to connect to TB7 because it performs back-up to a number of data. In an air conditioner system has more than 1 Outdoor units, AG-150A receiving transmission power through TB7 on one of the Outdoor units would have a risk that the connected Outdoor unit failure would stop power supply to AG-150A, and disrupt the whole system. When applying apportioned electric power function, AG-150A is necessary to connected to TB7 and has its own power supply unit PAC-SC51KUA.*2

*1: AG-150A is an example model of system controllers.*2: Power supply unit PAC-SC51KUA is for AG-150A.

Page 17: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 51

2. M-NET control DATA G8

SYSTEM DESIGN

System Y

1-phase 220-240V AC power supply is needed.The power supply unit PAC-SC51KUA is not necessary when connecting only the LMAP02-E. Yet, make sure to change the power supply changeover connector CN41 to CN40 on the LM adapter.

2-3-4. Power supply to LM adapter LMAP02-E

1-phase 100-240VAC power supply is needed.The power supply unit PAC-SC51KUA is not necessary.The expansion controller supplies power through TB3, which equals 6 indoor units. (refer to Table 2-3-2)

2-3-5. Power supply to expansion controller

1-phase 100-240VAC power supply is needed.The power supply unit PAC-SC51KUA is not necessary when only BM ADAPTER is connected.Yet, make sure to move the power jumper from CN41 to CN40 on the BM ADAPTER.

2-3-6. Power supply to BM ADAPTER

1-phase 100-240VAC power supply is needed.The power supply unit PAC-SC51KUA is not necessary.GB-50ADA supplies power through TB3, which equals 6 indoor units. (refer to Table 2-3-2)

2-3-7. Power supply to GB-50ADA

Page 18: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

2. M-NET control DATA G8

SYSTEM DESIGN 4 - 52

Syst

em Y

2-4. Address setting

BranchNo. setting Unit address No. setting

Rotary switchIn order to constitute CITY MULTI in a complete system, switch operation for setting the unit address No. and connection No. is required.

À Address No. of outdoor unit, indoor unit and remote controller.The address No. is set at the address setting board. In the case of R2 system, it is necessary to set the same No. at the branch No. switch of indoor unit as that of the BC controller connected. (When connecting two or more branches, use the lowest branch No.)

Á Caution for switch operations

 MA remote controller

¥ Be sure to shut off power source before switch setting. If operated with power source on, switch can not operate properly.

¥ When connecting only one remote controller to one group, it is always the main remote controller. When connecting two remote controllers to one group, set one remote controller as the main remote controller

and the other as the sub remote controller.

¥ No units with identical unit address shall exist in one whole air conditioner system. If set erroneously, the system can not operate.

¥ The factory setting is Main .

2-4-1. Switch operation

0 1 2 3 4 5 6 7 8 9 A B C D

E F 0 1 2 3 4 5 6 7

8

9 0 1 2 3 4 5 6 7

8

9

PAR-21MAAThe MA remote controller does not have the switches listed above.Refer to the installation manual for the function setting.

Setting the dip switchesThere are switches on the front of the remote controller. Remote controller Main/Sub and other function settings are performed using these switches. Ordinarily, only change the Main/Sub setting of SW1. (The factory settings are all “ON”.)

SW No

1

2

3

SW contents MainRemote controllerMain/Sub settingTemperature displayunits settingCooling/heating dis-play in AUTO mode

ON

Main

Celsius

Yes

OFF

Sub

Fahrenheit

No

Comment

Set one of the two remote controllers at one group to “Main”

When the temperature is displayed in [Fahrenheit], set to “No”.

When you do not want to display “Cooling” and “Heating” in theAuto mode, set to “No”.

PAC-YT51CRB

Page 19: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 53

2. M-NET control DATA G8

SYSTEM DESIGN

System Y

2-4-2. Rule of setting address

Unit

Indoor unit

ME, LOSSNAYRemote controller(Main)

ME, LOSSNAYRemote controller(Sub)

Address setting

01 ~ 50

52 ~ 99, 100

101 ~ 150

151 ~ 199, 200

NoteExample

The address of outdoor unit + 1 Please reset one of them to an address between 51

and 99 when two addresses overlap. The address automatically becomes "100" if it is set

as "01~ 50"

The smallest address of indoor unit in the group + 100

The place of "100" is fixed to "1"

System remotecontroller

ON/OFF remote controller

AG-150AGB-50ADA

000, 201 ~ 250

000, 201 ~ 250

000, 201 ~ 250

Loca

l remo

te co

ntroll

erSy

stem

con

trolle

r

The address of main remote controller + 50

The address automatically becomes "200" if it is set as "00"

10 1

10 1

0 1 2 3 4 5 6 7

8

9 0 1 2 3 4 5 6 7

8

9

10 1

10 1

0 1 2 3 4 5 6 7

8

9 0 1 2 3 4 5 6 7

8

9

0 1 2 3 4 5 6 7

8

9 0 1 2 3 4 5 6 7

8

9

0 1 2 3 4 5 6 7

8

9 0 1 2 3 4 5 6 7

8

9

0 1 2 3 4 5 6 7

8

90 1 2 3 4 5 6 7

8

9 0 1 2 3 4 5 6 7

8

9

10 1

10 1100

0 1 2 3 4 5 6 7

8

90 1 2 3 4 5 6 7

8

9 0 1 2 3 4 5 6 7

8

9

10 1100

10 1100

LMAP02-E 201 ~ 250

1

1

Fixed

Fixed

Group remote controller 201 ~ 250

The smallest group No. to be managed + 200

10 1

2Fixed

2Fixed

Outdoor unit

BC controller(Main)

52 ~ 99, 100Lowest address within the indoor units connected to the BC controller (Sub) plus 50.

10 1

BC controller(Sub)

51 ~ 99, 100

The smallest address of indoor unit in same refrigerant system + 50Assign sequential address numbers to the outdoor units in one refrigerant circuit system. OC, OS1 and OS2 are automatically detected. (Note 2) Please reset one of them to an address between 51

and 99 when two addresses overlap. The address automatically becomes "100" if it is set

as "01~ 50"

Use the most recent address within the same group of indoor units. Make the indoor units address connected to the BC controller (Sub) larger than the indoor units address connected to the BC controller (Main).If applicable, set the sub BC controllers in an PURY system in the following order: (1) Indoor unit to be connected to the BC controller (Main) (2) Indoor unit to be connected to the BC controller (No.1 Sub) (3) Indoor unit to be connected to the BC controller (No.2 Sub)Set the address so that (1)<(2)<(3)

0 1 2 3 4 5 6 7

8

9 0 1 2 3 4 5 6 7

8

9

0 1 2 3 4 5 6 7

8

9 0 1 2 3 4 5 6 7

8 9

0 1 2 3 4 5 6 7

8

9 0 1 2 3 4 5 6 7

8

9

0 1 2 3 4 5 6 7

8

9 0 1 2 3 4 5 6 7

8

9

10 1(Note1)

0,2 0~5 0~9

PAC-YG50ECA 000, 201 ~ 250

10 1100

0,2 0~5 0~9

BAC-HD150 000, 201 ~ 250

10 1100

0,2 0~5 0~9

The smallest group No. to be managed is changeable.

Settings are made on the initial screen of AG-150A.

Settings are made with setting tool of BM ADAPTER.

The smallest group No. to be managed + 200

Note1: To set the address to "100", set it to "50"Note2: Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.

Page 20: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

2. M-NET control DATA G8

SYSTEM DESIGN 4 - 54

Syst

em Y

2-4-3. System examples

Factory setting

Setting at the site

Original switch setting of the outdoors, indoors, controllers, LMAP and BM ADAPTER at shipment is as follows. Outdoor unit : Address: 00, CN41: U (Jumper), DipSW2-1: OFF Indoor unit : Address: 00 ME remote controller : Address: 101 LMAP : Address: 247, CN41: U (Jumper), DipSW1-2: OFF BM ADAPTER : Address: 00

DipSW2-1(Outdoor) : When the System Controller is used, all the Dip SW2-1 at the outdoor units should be set to "ON". * Dip SW2-1 remains OFF when only LMAP02-E is used. DipSW1-2(LMAP) : When the LMAP is used together with System Controller, DipSW1-2 at the LMAP should be set to "ON". CN40/CN41 : Change jumper from CN41 to CN 40 at outdoor control board will activate central transmission power supply to TB7; (Change jumper at only one outdoor unit when activating the transmission power supply without using a power supply unit.) Change jumper from CN41 to CN 40 at LMAP will activate transmission power supply to LMAP itself; Power supply unit is recommended to use for a system having more than 1 outdoor unit, because the central transmission power supply from TB7 of one of outdoor units is risking that the outdoor unit failure may let down the whole system controller system.

2-4-3-1. MA remote controller, Single-refrigerant-system, No System Controller

1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.2. No address setting is needed.3. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at 2-3 "System configuration restrictions".

NOTE:

Indoor unit

MA R/C MA R/C MA R/C(Main) (Sub)

MA R/CSRU

Wireless R/C

1*

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

1*

00 00 00 00 00TB15TB5 TB5TB5 TB5 TB5TB15 TB15 TB15 TB15

Group 2Group 1 Group 3 Group 4

<Three outdoor units> <Two outdoor units> <One outdoor unit>

TB3 TB3TB3

000000OC OS1 OS2

PUHY

TB3TB3

0000OC OS1

PUHY

TB3

00OC

CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

PUHY

Page 21: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 55

2. M-NET control DATA G8

SYSTEM DESIGN

System Y

2-4-3. System examples

2-4-3-2. MA remote controller, Single-refrigerant-system, System Controller

2. Address should be set to Indoor units and centralized controller.3. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at 2-3 "System configuration restrictions".

NOTE:1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.

Indoor unit

MA R/C MA R/C MA R/C(Main) (Sub)

MA R/CSRU

Wireless R/C

1*

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.*SC can be connected to TB3 side or TB7 side; Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.

1*

01 02 03 04 05TB15TB5 TB5TB5 TB5 TB5TB15 TB15 TB15 TB15

Group 2Group 1 Group 3 Group 4

TB3 TB3TB3

201

535251OC OS1 OS2

PUHY

SC

TB3TB3

5251OC OS1

PUHY

TB3

51OC

CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

PUHY<Three outdoor units> <Two outdoor units> <One outdoor unit>

Page 22: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

2. M-NET control DATA G8

SYSTEM DESIGN 4 - 56

Syst

em Y

2-4-3. System examples

2-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7/TB3 side, Booster for long M-NET wiring

2. Address should be set to Indoor units, LOSSNAY and system controller.3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".

NOTE:1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.

Indoor unit

MA R/C MA R/C(Main) (Sub)

MA R/CSRU

Wireless R/C

*1

*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System. For AG-150A, 24V DC should be used with the PAC-SC51KUA.

*1202

01 02 03 30TB15TB5 TB5TB5 TB2

Transmission BoosterPAC-SF46EPA

TB5TB15 TB15 TB3 TB15

MA R/C(Main) (Sub)

MA R/C

TB15

Indoor unit

ME R/C MA R/CPZ-52SF-ESRU

Wireless R/C

*1

*1 142 143

*2

41 42 43 45 46TB15TB5 TB5

LOSSNAY

TB5 TB5 TB5TB15

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

Group 2Group 1 Group 21

Group 33Group 32Group 31 Group 34 Group 36Group 35

TB3 TB3

TB7TB7 TB7 TB7 TB7 TB7

TB3

TB2

000 or 201

Power supply unit(PAC-SC51KUA)

535251

OC OS1 OS2PUHY

SC*3

TB3TB3

9291

OC OS1PUHY

TB3

98

OC

CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

PUHY

SC*3

203SC *3

*3 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main" controller and others as "sub". Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".

PZ-60DR-E

47TB5 TM4

LOSSNAY

Page 23: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 57

2. M-NET control DATA G8

SYSTEM DESIGN

System Y

2-4-3. System examples

2-4-3-4. ME remote controller, Single-refrigerant-system, No system controller

2. Address should be set to Indoor units, system controller and ME remote controllers.3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME RC consume the M-NET power for transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".

NOTE:1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.

Indoor unit

ME R/C ME R/C ME R/C

01 02 03 04 05TB5 TB5TB5

102

ME R/C

104 105 155

TB5 TB5

ME R/C

101

Group 2Group 1 Group 3 Group 4

TB3 TB3TB3

535251OC OS1 OS2

PUHY

TB3TB3

5251OC OS1

PUHY

TB3

51OC

CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

PUHY<Three outdoor units> <Two outdoor units> <One outdoor unit>

2-4-3-5. ME remote controller, Single-refrigerant-system, System controller, LOSSNAY

2. Address should be set to Indoor units, LOSSNAY centralized controller, ME remote controllers.3. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at 2-3 "System configuration restrictions".

NOTE:

ME R/C ME R/C

Indoor unit

ME R/C ME R/CPZ-52SF-E102 103 104 105 155

01 02 03 04 05TB5 TB5

LOSSNAY

TB5 TB5 TB5 TM4

ME R/C101

Group 2 Group 3Group 1 Group 4 Group 5

201

SC

*SC can be connected to TB3 side or TB7 side; Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.

1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.

<Three outdoor units> <Two outdoor units> <One outdoor unit>

TB3 TB3TB3

535251OC OS1 OS2

PUHY

TB3TB3

5251OC OS1

PUHY

TB3

51OC

CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

PUHY

Group 6

PZ-60DR-E

06TB5

LOSSNAY

Page 24: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

2. M-NET control DATA G8

SYSTEM DESIGN 4 - 58

Syst

em Y

2-4-3. System examples

2-4-3-6. ME remote controller, Multi-refrigerant-system, System Controller at TB 7side, LOSSNAY, Booster for long M-NET wiring

2. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".

NOTE:1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.

Indoor unit

ME R/C ME R/C

*1 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System. For AG-150A, 24V DC should be used with the PAC-SC51KUA.

01 02 03 30TB5 TB5TB5 TB2

Transmission BoosterPAC-SF46EPA

TB5TB3

ME R/C ME R/C

Indoor unit

ME R/C ME R/CPZ-52SF-E142 144 145 195

130 180

143

*1

41 42 43 44 45TB5 TB5

LOSSNAY

TB5 TB5 TB5 TM4

ME R/C141203

ME R/C101

SC *2

SC *2

202ME R/C

102

Group 2Group 1 Group 21

Group 32 Group 33

PZ-60DR-E

46LOSSNAY

Group 36Group 31 Group 34 Group 35

TB3 TB3

TB7TB7 TB7 TB7 TB7 TB7

TB3

TB2

000 or 201

Power supply unit(PAC-SC51KUA)

535251

OC OS1 OS2PUHY

SC*2

TB3TB3

9291

OC OS1PUHY

TB3

97

OC

CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

PUHY

*2 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main" controller and others as "sub". Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".

TB5

Page 25: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 59

2. M-NET control DATA G8

SYSTEM DESIGN

System Y

2-4-3-7. ME remote controller, Multi-refrigerant-system, No Power supply unit

NOTE It is necessary to change the connecter to CN40 on the outdoor unit control board (only one outdoor unit) when the group is set between other refrigerant systems. It is necessary to set on the remote controller by manual when group sets on the different refrigerant system. Please refer to remote controller installation manual.

NOTE It is necessary to change the connecter to CN40 on the outdoor unit control board (only one outdoor unit) when the group is set between other refrigerant systems. It is necessary to set on the remote controller by manual when group sets on the different refrigerant system. Please refer to remote controller installation manual.

SC201

Group 1

Group 3Group 4

Group 2

ME R/C

01 02 03 04 05

101 105

0910 08 07 06

110 107ME R/C

ME R/C

ME R/C

TB7

TB3

56CN41CN40

OFFDipSW2-1

TB3

TB7TB7

TB3

5251CN41CN40CN41CN40

OFFDipSW2-1

OFFDipSW2-1

OC OCOSPUHY PUHY

2-4-3-8. ME remote controller, Multi-refrigerant-system, System Controller at TB7 side, No Power sypply unit

Group 1

Group 3Group 4

Group 2

ME R/C

01 02 03 04 05

101 105

0910 08 07 06

110 107ME R/C

ME R/C

ME R/C

TB7

TB3

56CN41CN40

ONDipSW2-1

TB3

TB7TB7

TB3

5251CN41CN40CN41CN40

ONDipSW2-1

ONDipSW2-1

OC OCOSPUHY PUHY

Page 26: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

2. M-NET control DATA G8

SYSTEM DESIGN 4 - 60

Syst

em Y

2-4-3-9. TG-2000A(*1)+AG-150A*2AG-150A can control max. 50 indoor units;TG-2000A can control max. 40 AG-150A;*3TG-2000A can control max. 2000 indoor units.

HUB

PC withTG-2000A

LAN AG-150A

24VDC

AG-150A

000

000

24VDC

Power supply unit(PAC-SC51KUA)

Indoor unit

MA R/C MA R/C(Main) (Sub)

MA R/CSRU

Wireless R/C

*4

*4

01 02 03 42TB15TB5 TB5TB5 TB2

Transmission BoosterPAC-SF46EPA

TB5TB15 TB15 TB3 TB15

Group 2Group 1 Group 40

TB7

TB3

TB3 TB2

TB2

TB3

51

OC

CN41CN40

ONDipSW2-1

Indoor unit

ME R/C ME R/C ME R/C

01 02 03 30TB5 TB5TB5 TB2

Transmission BoosterPAC-SF46EPA

TB5

ME R/C

101 102 130 180

TB3

Group 2Group 1 Group 21

TB7 TB7 TB7

TB3TB3

5251

OC OS

TB3

91

OC

CN41CN40CN41CN40 CN41CN40

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ME R/C ME R/C

Indoor unit

ME R/C ME R/C142 144 145 195

41 42 43 44 45TB5 TB5

InterlockedLOSSNAY

TB5 TB5 TB5

Group 32

46TB5 TM4

LOSSNAY

Group 35Group 31 Group 33 Group 34

ME R/C

141

PUHY

PUHY PUHY

*1 TG-2000A (Ver.5.5 or later) supports AG-150A (Ver.1 series). TG-2000A (Ver. 6.1 or later) supports AG-150A (Ver. 2.1 or later) connected with the expansion controller (EC).*2 AG-150A (Ver.1 series) does not support the expansion controller (EC).*3 When AG-150A connected with the expansion controller (EC) is connected, the number of EC will be the maximum controllable number. TG-2000A can control up to 40 EC or AG-150A without EC connection.*4 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

It is planned that GB-50ADA will be supported on TG-2000A Ver. 6.3* or later.

PZ-60DR-E

Power supply unit(PAC-SC51KUA)

Page 27: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 61

2. M-NET control DATA G8

SYSTEM DESIGN

System Y

2-4-3. System examples

2-4-3-10. AG-150A + PAC-YG50ECA (Expansion controller)AG-150A can control max. 150 indoor units/ via expansion controllers.

HUB

PC withBrowser

LAN

PAC-YG50ECA

AG-150A

PAC-YG50ECA

PAC-YG50ECA

Indoor unit

MA R/C MA R/C(Main) (Sub)

MA R/CSRU

Wireless R/C

*1

*1

01 02 03 42TB15TB5 TB5TB5 TB2

Transmission BoosterPAC-SF46EPA

TB5TB15 TB15 TB3 TB15

Group 2Group 1 Group 40

TB3 TB3

TB7TB7 TB7 TB7 TB7 TB7

TB3

24VDCTB3

535251

OC OS1 OS2

TB3TB3

5251

OC OS1

TB3

51

OC

CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

Indoor unit

ME R/C ME R/C ME R/C

01 02 03 30TB5 TB5TB5 TB2

Transmission BoosterPAC-SF46EPA

TB5

ME R/C

101 102 130 180

TB3

Group 2Group 1 Group 21

TB3 TB3

TB7TB7 TB7 TB7 TB7 TB7

TB3

535251

OC OS1 OS2

TB3TB3

9291

OC OS1

TB3

96

OC

CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ME R/C ME R/C

Indoor unit

ME R/C ME R/CPZ-52SF-E142 143 144 145 195

41 42 43 44 45TB5 TB5

LOSSNAY

TB5 TB5 TB5

Group 32 Group 33Group 31 Group 34 Group 35

ME R/C

141

PUHY PUHY PUHY

PUHY PUHY PUHY

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

<Three outdoor units> <Two outdoor units> <One outdoor unit>

Power supply unit(PAC-SC51KUA)

When connecting AG-150A to PAC-YG50ECA, TB2 for power supply unit does not need to be connected to AG-150A.NOTE

000

CN40 CN41

000

CN40 CN41

000

CN40 CN41

Page 28: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

2. M-NET control DATA G8

SYSTEM DESIGN 4 - 62

Syst

em Y

2-4-3. System examples

2-4-3-11. LMAP

LMAP(01)

24VDC

(LONWORKs adapter)

PC

LONWORKS card

LONWORKS card

LONWORKS card For other equipments (Lighting, security, elevator etc.)

LMAP can transmission for max. 50 indoor units in single-refrigerant-system or multi-refrigerant-system.

DipSW1-2OFF

247

LONW

OR

KS

000

AG-150A

Power supply unit(PAC-SC51KUA)

identified by Neuron ID

LMAP(02)

DipSW1-2ON

247identified by Neuron ID

<Three outdoor units> <Two outdoor units> <One outdoor unit>

CN41CN40

CN41CN40

LMAP can transmission for max. 50 indoor units;If system controller (SC) is used, DipSW1-2 at LMAP and DipSW2-1 at Outdoor unit should set to "ON".Change Jumper from CN41 to CN40 to activate power supply to LMAP itself for those LMAP connected without system controller (SC).

Indoor unit

MA R/C MA R/C(Main) (Sub)

MA R/CSRU

Wireless R/C

*1

*1

01 02 03 42TB15TB5 TB5TB5 TB2

Transmission BoosterPAC-SF46EPA

TB5TB15 TB15 TB3 TB15

Group 2Group 1 Group 40

TB3 TB3

TB7TB7

TB3

TB2

TB7 TB7 TB7 TB7

TB3

535251

OC OS1 OS2

TB3TB3

5251

OC OS1

TB3

51

OC

CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

Indoor unit

ME R/C ME R/C ME R/C

01 02 03 30TB5 TB5TB5 TB2

Transmission BoosterPAC-SF46EPA

TB5

ME R/C

101 102 130 180

TB3

Group 2Group 1 Group 21

TB3 TB3

TB7TB7 TB7 TB7 TB7 TB7

TB3

535251

OC OS1 OS2

TB3TB3

9291

OC OS1

TB3

97

OC

CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ME R/C ME R/C

Indoor unit

ME R/C ME R/CPZ-52SF-E142 143 144 145 195

41 42 43 44 45TB5 TB5

LOSSNAY

TB5 TB5 TB5

Group 32 Group 33Group 31 Group 34 Group 35

ME R/C

141

PUHY PUHY PUHY

PUHY PUHY PUHY

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

PZ-60DR-E

46TB5 TM4

LOSSNAY

Group 36

Page 29: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 63

2. M-NET control DATA G8

SYSTEM DESIGN

System Y

2-4-3. System examples

2-4-3-12. BM ADAPTER

BM ADAPTER(01)

HUB

For other equipments (Lighting, security, elevator etc.)

BM ADAPTER can transmission for max. 50 indoor units in single-refrigerant-system or multi-refrigerant-system.

000

BA

C n

et

BM ADAPTER(02)

201

<Three outdoor units> <Two outdoor units> <One outdoor unit>

CN41CN40

BM ADAPTER can transmission for max. 50 indoor units;Change Jumper from CN41 to CN40 to activate power supply to BM ADAPTER itself for those BM ADAPTER connected without the power supply unit.

Indoor unit

MA R/C MA R/C(Main) (Sub)

MA R/CSRU

Wireless R/C

*1

*1

01 02 03 42TB15TB5 TB5TB5 TB2

Transmission BoosterPAC-SF46EPA

TB5TB15 TB15 TB3 TB15

Group 2Group 1 Group 40

TB3 TB3

TB7TB7 TB7 TB7 TB7 TB7

TB3

535251

OC OS1 OS2

TB3TB3

5251

OC OS1

TB3

51

OC

CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

Indoor unit

ME R/C ME R/C ME R/C

01 02 03 30TB5 TB5TB5 TB2

Transmission BoosterPAC-SF46EPA

TB5

ME R/C

101 102 130 180

TB3

Group 2Group 1 Group 21

TB3 TB3

TB7TB7 TB7 TB7 TB7 TB7

TB3

535251

OC OS1 OS2

TB3TB3

9291

OC OS1

TB3

96

OC

CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ME R/C ME R/C

Indoor unit

ME R/C ME R/CPZ-52SF-E142 143 144 145 195

41 42 43 44 45TB5 TB5

LOSSNAY

TB5 TB5 TB5

Group 32 Group 33Group 31 Group 34 Group 35

ME R/C

141

PUHY PUHY PUHY

PUHY PUHY PUHY

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

HUB

CN41CN40

Page 30: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

2. M-NET control DATA G8

SYSTEM DESIGN 4 - 64

Syst

em Y

2-4-3. System examples

2-4-3-13. BM ADAPTER+PAC-YG50ECA (Expansion controller)

000

000

<Three outdoor units> <Two outdoor units> <One outdoor unit>

CN41CN40

BM ADAPTER(*1) can transmission for max. 150 indoor units/via expansion controllers (PAC-YG50ECA).

Indoor unit

MA R/C MA R/C(Main) (Sub)

MA R/CSRU

Wireless R/C

*2

*2

01 02 03 42TB15TB5 TB5TB5 TB2

Transmission BoosterPAC-SF46EPA

TB5TB15 TB15 TB3 TB15

Group 2Group 1 Group 40

TB3 TB3

TB7TB7 TB7 TB7 TB7 TB7

TB3

535251

OC OS1 OS2

TB3TB3

5251

OC OS1

TB3

51

OC

CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

OFFDipSW2-1

Indoor unit

ME R/C ME R/C ME R/C

01 02 03 30TB5 TB5TB5 TB2

Transmission BoosterPAC-SF46EPA

TB5

ME R/C

101 102 130 180

TB3

Group 2Group 1 Group 21

TB3 TB3

TB7TB7 TB7 TB7 TB7 TB7

TB3

535251

OC OS1 OS2

TB3TB3

9291

OC OS1

TB3

96

OC

CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ONDipSW2-1

ME R/C ME R/C

Indoor unit

ME R/C ME R/CPZ-52SF-E142 143 144 145 195

41 42 43 44 45TB5 TB5

LOSSNAY

TB5 TB5 TB5

Group 32 Group 33Group 31 Group 34 Group 35

ME R/C

141

PUHY PUHY PUHY

PUHY PUHY PUHYCN41CN40

NOTE•It is not necessary to connect the M-NET transmission line to the TB3 on BM ADAPTER. Leave the power jumper of BM ADAPTER connected to CN41.

*1 BM ADAPTER (Ver.2.00 or later) supports the expansion controller.*2 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.*3 AG-150A (Ver.2.30 or later) supports the BM ADAPTER.*4 PAC-YG50ECA (Ver.1.30 or later) supports the BM ADAPTER.

PAC-YG50ECA*4

PAC-YG50ECA*4

BACnet

LAN

LAN2

LAN1

PAC-YG50ECA *4

AG-150A *3

Power supply unit(PAC-SC51KUA)

TB324VDC

000CN41CN40

HUB

BM ADAPTER

CN41CN40

Page 31: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 65

3. Piping Design DATA G8

SYSTEM DESIGN

System Y

3. Piping Design3-1. R410A Piping material

Refrigerant pipe for CITY MULTI shall be made of phosphorus deoxidized copper, and has two types. A. Type-O : Soft copper pipe (annealed copper pipe), can be easily bent with human's hand. B. Type-1/2H pipe : Hard copper pipe (Straight pipe), being stronger than Type-O pipe of the same radical thickness. The maximum operation pressure of R410A air conditioner is 4.30 MPa [623psi] . The refrigerant piping should ensure the safety under the maximum operation pressure. MITSUBISHI ELECTRIC recommends pipe size as Table 3-1, or You shall follow the local industrial standard. Pipes of radical thickness 0.7mm or less shall not be used.

* F * The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes that meet the local standards.

or pipe sized ø19.05 (3/4") for R410A air conditioner, choice of pipe type is up to you.

Size (mm) Size (inch) Radial thickness (mm) Pipe typeø6.35 ø1/4" 0.8 Type-Oø9.52 ø3/8" 0.8 Type-Oø12.7 ø1/2" 0.8 Type-O

ø15.88 ø5/8" 1.0 Type-Oø19.05 ø3/4" 1.2 Type-Oø19.05 ø3/4" 1.0 Type-1/2H or Hø22.2 ø7/8" 1.0 Type-1/2H or Hø25.4 ø1" 1.0 Type-1/2H or H

ø28.58 ø1-1/8" 1.0 Type-1/2H or Hø31.75 ø1-1/4" 1.1 Type-1/2H or Hø34.93 ø1-3/8" 1.2 Type-1/2H or Hø41.28 ø1-5/8" 1.4

Radial thickness (mil)[32][32][32][40][48][40][40][40][40][44][48][56] Type-1/2H or H

Table 3-1. Copper pipe size and radial thickness for R410A CITY MULTI.

Flare

Due to the relative higher operation pressure of R410A compared to R22, the flare connection should follow dimensions mentioned below so as to achieve enough the air-tightness.

Flare pipe Pipe size A (For R410A) Flare nut Pipe size (mm[in.]) (mm[in.]) B (For R410A)

ø6.35 [1/4"]ø9.52 [3/8"]

ø12.70 [1/2"]ø15.88 [5/8"]ø19.05 [3/4"] 24.0

16.619.7

9.113.2

ø6.35 [1/4"]ø9.52 [3/8"]

ø12.70 [1/2"]ø15.88 [5/8"]ø19.05 [3/4"] 36.0

17.022.026.029.0

A

B

Page 32: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

3. Piping Design DATA G8

SYSTEM DESIGN 4 - 66

Syst

em Y

3-2. Piping Design

Joint selection rule Total down-stream Indoor capacity Joint ~ P200 CMY-Y102S-G2 P201 ~ P400 CMY-Y102L-G2 P401 ~ P650 CMY-Y202-G2 P651 ~ CMY-Y302-G2*PUHY-P450YJM's first Joint is always CMY-Y202-G2;*Concerning detailed usage of Joint parts, refer to its Installation Manual.

Header selection rule 4-branch Header 8-branch Header 10-branch Header CMY-Y104-G CMY-Y108-G CMY-Y1010-G Total down-stream Indoor capacity <=P200 <=P400 <=P650* CMY-Y104-G can directly connect PUHY-(E)P200YJM, but can NOT directly connect PUHY-(E)P250YJM or above; * CMY-Y108-G can directly connect PUHY-(E)P200-450YJM, but can NOT directly connect PUHY-(E)P500YSJM or above; * CMY-Y1010-G can directly connect PUHY-P200-650Y(S)JM,PUHY-EP200-600Y(S)JM; * CMY-Y104-G can NOT connect P200,P250 Indoor, but CMY-Y108, Y1010-G can do; * Concerning detailed usage of Header parts, refer to its Installation Manual.

Note3. Indoor capacity is described as its model size; For example, PEFY-P32VMA-E, its capacity is P32;Note4. Total down-stream Indoor capacity is the summary of the model size of Indoors downstream. For example, PEFY-P25VMA-E+PEFY-P32VMA-E: Total Indoor capacity=P25+P32=P57Note5. Piping sized determined by the Total down-stream indoor capacity is NOT necessary to be bigger than the up-stream one. i.e. A>=B; A>=C>=D

Note1. No Joint after Header; Piping direct to Indoor Unit from Header;Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;

Piping length needs to consider the actual length and equivalent length which bents are counted.Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.

IU : Indoor unit , OU : Outdoor unitFig. 3-2-1A Piping scheme

L1

L2C

b

h1

c

d ge

A

B

D a

OU

Joint

H (O

U a

bove

IU)

H' (

OU

und

er IU

)

IU IU

f

E

IU IU

IU IU IU

Header

1st JointCapped

*1*2

3-2-1. PUHY-P200-450YJM-A,PUHY-EP200-300YJM-A Piping

Piping length (m [ft.]) Item Piping in the figure Max. length Max. equivalent length Total piping length A+B+C+D+E+a+b+c+d+e+f+g 1000 [3280'] - Fartherest IU from OU (L1) A+C+D+E+g / A+B+c 165 [541'] 190 [623'] Fartherest IU from first Joint (L2) C+D+E+g / B+c 40 [131'] 40 [131'] Height between OU and IU (OU above IU) H 50 [164'] - Height between OU and IU (OU under IU) H' 40 [131'] - Height between IU and IU h1 15 [49'] -OU: Outdoor Unit, IU: Indoor Unit

Piping "A" size selection rule (mm [in.]) Outdoor and the first Joint Pipe(Liquid) Pipe(Gas) PUHY-(E)P200YJM=CMY-Y102L-G2,Y102S-G2 ø9.52 [3/8"] ø19.05 [3/4"] PUHY-(E)P250YJM=CMY-Y102L-G2 ø9.52 [3/8"] *1 ø22.20 [7/8"] PUHY-(E)P300YJM=CMY-Y102-G2 ø9.52 [3/8"] *2 ø22.20 [7/8"] PUHY-P350YJM=CMY-Y102-G2 ø12.70 [1/2"] ø28.58 [1-1/8"] PUHY-P400YJM=CMY-Y202-G2 ø12.70 [1/2"] ø28.58 [1-1/8"] PUHY-P450YJM=CMY-Y202-G2 ø15.88 [5/8"] ø28.58 [1-1/8"]*1. A>=90m [295ft.], ø12.70mm [1/2in.] ; A<90m [295ft.], ø9.52mm [3/8in.]*2. A>=40m [131ft.], ø12.70mm [1/2in.] ; A<40m [131ft.], ø9.52mm [3/8in.]

Piping"B","C","D","E"size selection rule (mm [in.]) Total down-stream Indoor capacity Pipe(Liquid) Pipe(Gas) ~ P140 ø9.52 [3/8"] ø15.88 [5/8"] P141 ~ P200 ø9.52 [3/8"] ø19.05 [3/4"] P201 ~ P300 ø9.52 [3/8"] ø22.20 [7/8"] P301 ~ P400 ø12.70 [1/2"] ø28.58 [1-1/8"] P401 ~ P650 ø15.88 [5/8"] ø28.58 [1-1/8"] P651 ~ P800 ø19.05 [3/4"] ø34.93 [1-3/8"] P801 ~ ø19.05 [3/4"] ø41.28 [1-5/8"]

Piping "a","b","c","d","e","f","g" size selection rule (mm [in.]) Indoor Unit size Pipe(Liquid) Pipe(Gas) P20,P25,P32,P40,P50,GUF-50RD(H) ø6.35 [1/4"] ø12.70 [1/2"] P63,P71,P80,P100,P125,GUF-100RD(H) ø9.52 [3/8"] ø15.88 [5/8"] P200 ø9.52 [3/8"] ø19.05 [3/4"] P250 ø9.52 [3/8"] ø22.20 [7/8"]

Bent equivalent length "M" Outdoor unit model M (m/bent [ft./bent]) PUHY-(E)P200YJM-A 0.35 [1.15] PUHY-(E)P250YJM-A 0.42 [1.38] PUHY-(E)P300YJM-A 0.42 [1.38] PUHY-P350YJM-A 0.47 [1.54] PUHY-P400YJM-A 0.50 [1.64] PUHY-P450YJM-A 0.50 [1.64]

*1 90m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.*2 60m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.

Page 33: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 67

3. Piping Design DATA G8

SYSTEM DESIGN

System Y

Joint selection rule Total down-stream Indoor capacity Joint ~ P200 CMY-Y102S-G2 P201 ~ P400 CMY-Y102L-G2 P401 ~ P650 CMY-Y202-G2 P651 ~ CMY-Y302-G2*PUHY-P500-650YSJM's first Joint is always CMY-Y202-G2;*PUHY-P700-900YSJM's first Joint is always CMY-Y302-G2;*PUHY-EP450-600YSJM's first Joint is always CMY-Y202-G2;*Concerning detailed usage of Joint parts, refer to its Installation Manual.*The total capacity of the units in the downstream of the branch joint on at least one of the piping lines that are connected to the branch joint should be 650 or below. If the total capacity of the units in the downstream of the branch joints on both lines is 650 or above use two branch joints (CMY-Y302-G2).

Header selection rule 4-branch Header 8-branch Header 10-branch Header CMY-Y104-G CMY-Y108-G CMY-Y1010-G Total down-stream Indoor capacity <=P200 <=P400 <=P650* CMY-Y104-G can directly connect PUHY-(E)P200YJM, but can NOT directly connect PUHY-(E)P250YJM or above; * CMY-Y108-G can directly connect PUHY-(E)P200-450YJM, but can NOT directly connect PUHY-(E)P500YSJM or above; * CMY-Y1010-G can directly connect PUHY-P200-650Y(S)JM, PUHY-EP200-600Y(S)JM; * CMY-Y104-G can NOT connect P200,P250 Indoor, but CMY-Y108, Y1010-G can do; * Concerning detailed usage of Header parts, refer to its Installation Manual.

Outdoor Twinning KitCMY-Y100,200VBK2

Note1. No Joint after Header; Piping direct to Indoor Unit from Header;Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;

Piping length needs to consider the actual length and equivalent length which bents are counted.Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.

H (O

U a

bove

IU)

h1

H' (

OU

und

er IU

)

h2

1st Joint

Joint

ba

L2L1

IU

IU IUIU

g

IU

e

IU

d

C

D

IU

f

E

TS

A BHeader

Capped

IU : Indoor unit , OU : Outdoor unitFig. 3-2-1B Piping scheme

c

2m To indoor unitTo indoor unitTo indoor unit To indoor unit 2 m max

Trap (gas pipe only)

Upward incline

Downward incline

Install the pipes from the outdoor unit to the branch joint with a downward incline.

If the length of pipe between the branch joint and outdoor unit exceeds 2 m, provide at rap at a distance 2 m or less from the branch joint.

OK NG

3-2-2. PUHY-P500-900YSJM-A(1),PUHY-EP400-600YSJM-A(1) Piping

Piping length (m [ft.]) Item Piping in the figure Max. length Max. equivalent length Total piping length S+T+A+B+C+D+E+a+b+c+d+e+f+g 1000 [3280'] - Distance between OU and OU S+T 10[32'] - Height between OU and OU h2 0.1[0.3'] - Fartherest IU from OU (L1) S(T)+A+C+D+E+g / S(T)+A+B+c 165 [541'] 190 [623'] Fartherest IU from the first Joint (L2) C+D+E+g / B+c 40 [131'] 40 [131'] Height between OU and IU (OU above IU) H 50 [164'] - Height between OU and IU (OU under IU) H' 40 [131'] - Height between IU and IU h1 15 [49'] -OU: Outdoor Unit, IU: Indoor Unit

Piping "A" size selection rule (mm [in.]) Outdoor and the first Joint Pipe(Liquid) Pipe(Gas) CMY-Y100VBK2=CMY-Y202-G2 ø12.70[1/2"] ø28.58[1-1/8"]*1 ø15.88[5/8"] ø28.58[1-1/8"]*2 CMY-Y200VBK2=CMY-Y302-G2 ø19.05[3/4"] ø34.93[1-3/8"]*3 ø19.05[3/4"] ø41.28[1-5/8"]*4CMY-Y100VBK2; *1 PUHY-EP400YSJM, *2 PUHY-P500-650YSJM, EP450-600YSJMCMY-Y200VBK2; *3 PUHY-P700-800YSJM, *4 PUHY-P850-900YSJMFor Piping size "S","T", please refer to specification of the Twining kit CMY-Y100,200VBK2 at the Outdoor unit's external drawing.

Piping"B","C","D","E" size selection rule (mm [in.]) Total down-stream Indoor capacity Pipe(Liquid) Pipe(Gas) ~ P140 ø9.52 [3/8"] ø15.88 [5/8"] P141 ~ P200 ø9.52 [3/8"] ø19.05 [3/4"] P201 ~ P300 ø9.52 [3/8"] ø22.20 [7/8"] P301 ~ P400 ø12.70 [1/2"] ø28.58 [1-1/8"] P401 ~ P650 ø15.88 [5/8"] ø28.58 [1-1/8"] P651 ~ P800 ø19.05 [3/4"] ø34.93 [1-3/8"] P801 ~ ø19.05 [3/4"] ø41.28 [1-5/8"]

Piping"a","b","c","d","e","f","g" size selection rule (mm [in.]) Indoor Unit size Pipe(Liquid) Pipe(Gas) P20,P25,P32,P40,P50,GUF-50RD(H) ø6.35 [1/4"] ø12.70 [1/2"] P63,P71,P80,P100,P125,GUF-100RD(H) ø9.52 [3/8"] ø15.88 [5/8"] P200 ø9.52 [3/8"] ø19.05 [3/4"] P250 ø9.52 [3/8"] ø22.20 [7/8"]

Bent equivalent length "M" Outdoor unit model M (m/bent [ft./bent]) PUHY-EP400YSJM-A 0.50 [1.64] PUHY-EP450YSJM-A 0.50 [1.64] PUHY-(E)P500YSJM-A(1) 0.50 [1.64] PUHY-(E)P550YSJM-A 0.50 [1.64] PUHY-(E)P600YSJM-A(1) 0.50 [1.64] PUHY-P650YSJM-A 0.50 [1.64] PUHY-P700YSJM-A(1) 0.70 [2.29] PUHY-P750YSJM-A 0.70 [2.29] PUHY-P800YSJM-A(1) 0.70 [2.29] PUHY-P850YSJM-A 0.80 [2.62] PUHY-P900YSJM-A 0.80 [2.62]

*1*2

OUOU

Note3. Indoor capacity is described as its model size; For example, PEFY-P32VMA-E, its capacity is P32;Note4. Total down-stream Indoor capacity is the summary of the model size of Indoors downstream. For example, PEFY-P25VMA-E+PEFY-P32VMA-E: Total Indoor capacity=P25+P32=P57Note5. Piping sized determined by the Total down-stream indoor capacity is NOT necessary to be bigger than the up-stream one. i.e. A>=B; A>=C>=D

*1 90m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.*2 60m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.

Page 34: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

3. Piping Design DATA G8

SYSTEM DESIGN 4 - 68

Syst

em Y

Joint selection rule Total down-stream Indoor capacity Joint ~ P200 CMY-Y102S-G2 P201 ~ P400 CMY-Y102L-G2 P401 ~ P650 CMY-Y202-G2 P651 ~ CMY-Y302-G2*PUHY-P950-1250YSJM's first Joint is always CMY-Y302-G2;*PUHY-EP650YSJM's first Joint is always CMY-Y202-G2;*PUHY-EP700-900YSJM's first Joint is always CMY-Y302-G2;*The total capacity of the units in the downstream of the branch joint on at least one of the piping lines that are connected to the branch joint should be 650 or below. If the total capacity of the units in the downstream of the branch joints on both lines is 650 or above use two branch joints (CMY-Y302-G2). *Concerning detailed usage of Joint parts, refer to its Installation Manual.

Header selection rule 4-branch Header 8-branch Header 10-branch Header CMY-Y104-G CMY-Y108-G CMY-Y1010-G Total down-stream Indoor capacity <=P200 <=P400 <=P650* CMY-Y104-G can directly connect PUHY-(E)P200YJM, but can NOT directly connect PUHY-(E)P250YJM or above; * CMY-Y108-G can directly connect PUHY-(E)P200-450YJM, but can NOT directly connect PUHY-(E)P500YSJM or above; * CMY-Y1010-G can directly connect PUHY-P200-650Y(S)JM, PUHY-EP200-600Y(S)JM; * CMY-Y104-G can NOT connect P200,P250 Indoor, but CMY-Y108, Y1010-G can do; * Concerning detailed usage of Header parts, refer to its Installation Manual.

2nd Outdoor Twinning Kit

1st Outdoor Twinning Kit

Note1. No Joint after Header; Piping direct to Indoor Unit from Header;Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;

Piping length needs to consider the actual length and equivalent length which bents are counted.Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.

H (O

U a

bove

IU)

H' (

OU

und

er IU

)

h2

1st Joint

Joint

L2L1

IU

g

IU

e

IU

d

C

D

IU

f

E

T

S

M N

A BHeader

IU : Indoor unit , OU : Outdoor unitFig. 3-2-1C Piping scheme

2m To indoor unitTo indoor unitTo indoor unit To indoor unit 2 m max

Trap (gas pipe only)

Upward incline

Downward incline

Install the pipes from the outdoor unit to the branch joint with a downward incline.

If the length of pipe between the branch joint and outdoor unit exceeds 2 m, provide at rap at a distance 2 m or less from the branch joint.

OK NG

h1

ba

IU IUIU

c

Capped

3-2-3. PUHY-P950-1250YSJM-A,PUHY-EP650-900YSJM-A(1) Piping

Piping length (m [ft.]) Item Piping in the figure Max. length Max. equivalent length Total piping length S+T+M+N+A+B+C+D+E+a+b+c+d+e+f+g 1000[3280'] - Distance between OU and OU M+N+S+T 10[32'] - Height between OU and OU h2 0.1[0.3'] - Fartherest IU from OU (L1) M(N)+S+A+C+D+E+g / M(N)+S+A+B+c 165[541'] 190[623'] Fartherest IU from the first Joint (L2) C+D+E+g / B+c 40[131'] 40[131'] Height between OU and IU (OU above IU) H 50[164'] - Height between OU and IU (OU under IU) H' 40[131'] - Height between IU and IU h1 15[49'] -OU: Outdoor Unit, IU: Indoor Unit

Piping "A" size selection rule (mm [in.]) Outdoor and the first Joint Pipe(Liquid) Pipe(Gas) CMY-Y300VBK2=CMY-Y202-G2 ø15.88[5/8"] ø28.58[1-1/8"]*1 CMY-Y300VBK2=CMY-Y302-G2 ø19.05[3/4"] ø34.93[1-3/8"]*2 ø19.05[3/4"] ø41.28[1-5/8"]*3For Piping size"M","N","S","T", please refer to specification of the Twining kit CMY-Y300VBK2 at the Outdoor unit's external drawing.

*1 PUHY-EP650YSJM*2 PUHY-EP700-800YSJM*3 PUHY-P950-1250YSJM, PUHY-EP850, 900YSJM

Piping"B","C","D","E" size selection rule (mm [in.]) Total down-stream Indoor capacity Pipe(Liquid) Pipe(Gas) ~ P140 ø9.52 [3/8"] ø15.88 [5/8"] P141 ~ P200 ø9.52 [3/8"] ø19.05 [3/4"] P201 ~ P300 ø9.52 [3/8"] ø22.20 [7/8"] P301 ~ P400 ø12.70 [1/2"] ø28.58 [1-1/8"] P401 ~ P650 ø15.88 [5/8"] ø28.58 [1-1/8"] P651 ~ P800 ø19.05 [3/4"] ø34.93 [1-3/8"] P801 ~ ø19.05 [3/4"] ø41.28 [1-5/8"]

Piping"a","b","c","d","e","f","g" size selection rule (mm [in.]) Indoor Unit size Pipe(Liquid) Pipe(Gas) P20,P25,P32,P40,P50,GUF-50RD(H) ø6.35 [1/4"] ø12.70 [1/2"] P63,P71,P80,P100,P125,GUF-100RD(H) ø9.52 [3/8"] ø15.88 [5/8"] P200 ø9.52 [3/8"] ø19.05 [3/4"] P250 ø9.52 [3/8"] ø22.20 [7/8"]

Bent equivalent length "M" Outdoor unit model M (m/bent [ft./bent]) PUHY-EP650YSJM-A 0.50 [1.64] PUHY-EP700YSJM-A(1) 0.70 [2.29] PUHY-EP750YSJM-A(1) 0.70 [2.29] PUHY-EP800YSJM-A(1) 0.70 [2.29] PUHY-EP850YSJM-A 0.80 [2.62] PUHY-EP900YSJM-A 0.80 [2.62] PUHY-P950YSJM-A 0.80 [2.62] PUHY-P1000YSJM-A 0.80 [2.62] PUHY-P1050YSJM-A 0.80 [2.62] PUHY-P1100YSJM-A 0.80 [2.62] PUHY-P1150YSJM-A 0.80 [2.62] PUHY-P1200YSJM-A 0.80 [2.62] PUHY-P1250YSJM-A 0.80 [2.62]

*1*2

*1 90m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.*2 60m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.

OU OU

OU

Note3. Indoor capacity is described as its model size; For example, PEFY-P32VMA-E, its capacity is P32;Note4. Total down-stream Indoor capacity is the summary of the model size of Indoors downstream. For example, PEFY-P25VMA-E+PEFY-P32VMA-E: Total Indoor capacity=P25+P32=P57Note5. Piping sized determined by the Total down-stream indoor capacity is NOT necessary to be bigger than the up-stream one. i.e. A>=B; A>=C>=D

Page 35: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 69

3. Piping Design DATA G8

SYSTEM DESIGN

System Y

3-3. Refrigerant charging calculation

Sample connection(with 8 indoor units)

Amount of refrigerant to be chargedRefrigerant for extended pipes (field piping) is not factory-charged to the outdoor unit. Add an appropriate amount of refrigerant for each pipe on site.

Record the size of each liquid pipe and the amount of refrigerant that was charged on the outdoor unit for future reference.

Calculating the amount of refrigerant to be chargedThe amount of refrigerant to be charged is calculated with the size of the on-site-installed liquid pipes and their length.Calculate the amount of refrigerant to be charged according to the formula below.Round up the calculation result to the nearest 0.1kg. (i.e., 16.08 kg = 16.1 kg)

<Amount of refrigerant to be charged>Calculating the amount of refrigerant to be charged

Amount of factory-charged refrigerant

Sample calculation

Total length of ø19.05 liquid pipe x 0.29

(m)x0.29(kg/m)

+Total length of ø15.88 liquid pipe x 0.2

(m)x0.2(kg/m)

ø19.05ø15.88ø12.70ø9.52ø6.35

C+E=42D+F=1+10=11mB+G=2+5=7mA+I+J+K+M+a+b+c+d+e+f+g=3+5+30+5+5+15+15+5+5+5+5+5=103mi=5m=40x0.29+11x0.2+7x0.12+103x0.06+5x0.024+10=31.52kg=31.5kg

Indoor1:P2502:P2003:P804:P715:P1406:P1257:P638:P25

A : ø9.52B : ø12.70C : ø19.05D : ø15.88E : ø19.05F : ø15.88G : ø12.70 I : ø9.52J : ø9.52K : ø9.52M : ø9.52

a : ø9.52b : ø9.52c : ø9.52d : ø9.52e : ø9.52 f : ø9.52g : ø9.52 i : ø6.35

3m 2m 2m 1m40m10m 5m 5m30m 5m 5m

15m15m 5m 5m 5m 5m 5m 5m

2.0kg2.5kg3.0kg3.5kg4.5kg5.0kg6.0kg8.0kg9.0kg

10.0kg12.0kg14.0kg

+Total length of ø12.7 liquid pipe x 0.12

(m)x0.12(kg/m)

Total length for each pipe size :

This yields the following result :

+Total length of ø9.52 liquid pipe x 0.06

(m)x0.06(kg/m)

+Total length of ø6.35 liquid pipe x 0.024

(m)x0.024(kg/m)

+ ~8081~160

161~330331~390391~480481~630631~710711~800801~890

891~10701071~1250

1251~

Total capacity of connected indoor units

Charged amount

OU OUOU Note1. No Joint after Header; Piping direct to Indoor Unit from Header;

Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;Piping length needs to consider the actual length and equivalent length which bents are counted.Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.

2m To indoor unitTo indoor unitTo indoor unit To indoor unit 2 m max

Trap (gas pipe only)

Upward incline

Downward incline

Install the pipes from the outdoor unit to the branch joint with a downward incline.

If the length of pipe between the branch joint and outdoor unit exceeds 2 m, provide at rap at a distance 2 m or less from the branch joint.

OK NG

Outdoor Twinning KitCMY-Y300VBK2

1st Joint

1 : P250 2 : P200 3 : P80 4 : P71

5 : P140 6 : P125 7 : P63 8 : P25

IU IU IU IU

IU IU IU IU

A B

C

D

E

J K M

F

a b c d

e f g i

G I

8.0kg

6.5kg

11.5kg

11.8kg

P200 modelP250 modelEP200 modelP300 modelP350 modelP400 modelEP250 modelP450 modelEP300 model

Outdoor unit model Charged amount

Page 36: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4. Outdoor Installation DATA G8

SYSTEM DESIGN 4 - 70

Syst

em Y

4. Outdoor Installation4-1. Requirement on installation site

1. No direct thermal radiation to the unit.2. No possibility of annoying the neighbors by the sound of the unit. Valves and refrigerant flow on the outdoor unit may generate noise. 3. Avoid the sites where strong winds blow.4. With strength to bear the weight of the unit.5. Drain flow from the unit is cared at heating mode.6. Enough space for installation and service as shown at 4-2.7. Avoid the sites where acidic solutions or chemical sprays (sulfur series) are used frequently.8. The unit should be secure from combustible gas, oil, steam, chemical gas like acidic solution, sulfur gas and so on.

Page 37: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 71

4. Outdoor Installation DATA G8

SYSTEM DESIGN

System Y

4-2. Spacing

1000[39-3/8]

240 [9-15/32]

45°

50 [1-31/32]<C>

(Unit : mm [in.])

<B>

500

[19-11

/16]

H

h

h

H

100*[3-15/16]

450*[17-23/32]

50* [1-31/32] 50* [1-31/32]

<A>

(1) If the distance is 300 mm [11-13/16 in.] or more between the rear side and the wall

15* [19/32] 15* [19/32]

450*[17-23/32]

300*[11-13/16]

<A>(2) If the distance is 100 mm [3-15/16 in.] or more between the rear side and the wall

• Secure enough space around the unit as shown in the figure.In case of single installation

(3) If the wall height (H) of the front, rear or side exceeds the wall height restriction

(4) If there are obstacles at the upper part of the unit

<A> : Top view<B> : Side view<C> : When there is little space up to an obstruction

::

• When the height of the walls on the front, back or on the sides <H> exceeds the wall height limit as defined below, add the height that exceeds the height limit <h> to the figures that are marked with an asterisk.

<Wall height limit> Front: Up to the unit height Back: Up to 500mm [19-11/16 in.] from the unit bottom Side: Up to the unit height

A

BCD : Air outlet guide (Procured at the site)

: FrontUnit height

Back

A

A

AB

CA

D

If the unit cannot be kept clear of the wall, please change the direction of the air outlet of the unit to blow against the wall to avoid air short cycle.

Page 38: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4. Outdoor Installation DATA G8

SYSTEM DESIGN 4 - 72

Syst

em Y

In case of collective installation and continuous installation

:: Wall height (H)

(Unit : mm [in.])

A

BC

30

450*

300*

100 450*

100*

450* 100*450 450

15*

450 450

900

300*

300*

1000*

900

300*

• When multiple units are installed adjacent to each other, secure enough space to allow for air circulation and passageways between groups of units as shown in the figures.

• At least two sides must be left open.• As with the single installation, add the height that exceeds the height limit <h> to the figures that are marked with

• If there is a wall at both the front and the rear of the unit, install up to six units (three units : P450, EP300) consecutively in the side direction and provide a space of 1000mm or more as inlet space/passage space for each six units (three units : P450, EP300).

an asterisk.

: FrontMust be open

[17-23/32] [17-23/32]

[17-23/32] [17-23/32] [17-23/32] [3-15/16]

[39-3/8]

[17-2

3/32]

[17

-23/3

2]

[11-1

3/16]

[11-1

3/16]

[11

-13/1

6]

[11-1

3/16]

[35

-7/16

] [35

-7/16

]

[3-1

5/16

]

[3-15/16]

[1-3/16]

AA

A

AAA

AAA

AB B

B B

B

B

B B

B

B

C

C

C

C

CC

C

C

C

C

Page 39: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 73

4. Outdoor Installation DATA G8

SYSTEM DESIGN

System Y

4-3. Piping direction

4-3-1. Lifting method

· When lifting the unit with ropes, run the ropes under the unit and use the lifting hole.· Support the unit at four points with two ropes, and avoid giving mechanical shock.· Suspension rope angle must be 40˚ or less, so as to avoid compressing fan guard.· Use two ropes, each at least 8m [26 ft.] in length· Use ropes strong enough to support the weight of the unit.· Always suspend the unit from four corners. (It is dangerous to suspend a unit from two corners and must not be attempt-

ed.)· Use protective pads to keep the ropes from scratching the panels on the unit.

· Products weighing more than 20 kg [45 LBS] should not be carried alone.· Do not carry the product by the PP bands.· To avoid the risk of injury, do not touch the heat exchanger fins. · Plastic bags may pose a risk of choking hazard to children. Tear plastic bags into pieces before disposing of them.· When lifting and transporting outdoor units with ropes, run the ropes through lifting hole at the unit base. Securely

fix the unit so that the ropes will not slide off, and always lift the unit at four points to prevent the unit from falling.

Exercise caution when transporting products.CAUTION

8 [26]

8 [26]

P200-P300EP200

P350-P400EP250

P450EP300

40°

(Unit : m [ft.])

1 2 3

8 [26]40°

8 [26]

8 [26] 40

8 [26]

Page 40: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4. Outdoor Installation DATA G8

SYSTEM DESIGN 4 - 74

Syst

em Y

4-3-2. Installation

30m

m[1

-3/1

6 in

.]30

mm

[1-3

/16

in.]

Install the unit in such a way that the corner of the angle bracket at the base of the unit shown in the figure is securely supported. The brackets may bend if they are not securely supported.

: M10 anchor bolt procured at the site.

: Corner is not seated.

: Fixing bracket for hole-in anchor bolt (3 locations to fix with screws).

: Detachable leg

A

<Without detachable leg>

A

B

B

C

C

D

A A A A

724±

3 [(2

8-13

/32~

28-5

/8)]

724±

3 [(2

8-13

/32~

28-5

/8)]

(For maintenance)

30 [1-3/16]190 [7-1/2]

30 [1-3/16]190 [7-1/2]

4-3-3. Anchor bolt positions

· Secure the unit with anchor bolts as shown in the figure below so that the unit will not topple over with strong wind orduring an earthquake.

· Install the unit on a durable base made of such materials as concrete or angle steel.· Take appropriate anti-vibration measures (e.g., vibration damper pad, vibration isolation base) to keep vibrations and

noise from being transmitted from the unit through walls and floors.· When using a rubber cushion, install it so that the cushion covers the entire width of the unit leg.· Install the unit in such a way that the corner of the angle bracket at the base of the unit shown in the figure below is

securely supported.· Install the anchor bolt in such a way that the top end of the anchor bolt do not stick out more than 30 mm [1-3/16 in.].· This unit is not designed to be anchored with post-installation-type anchor bolts, although by adding fixing brackets

anchoring with such type of anchor bolts becomes possible.

• Individual <P200-P400, EP200, EP250>

installation • Collective installation

Take into consideration the durability of the base, water drainage route (Drain water is discharged from outdoor unitsduring operation.), piping route, and wiring route when performing foundation work.

Properly install the unit on a surface that can withstand the weight ofthe unit. Unit installed on an unstable surface may fall and cause injury.

WARNING

Take appropriate safety measures against strong winds and earth-quakes to prevent the unit from falling.

WARNING

(Unit : mm [in.])

Leave a minimum of 30 mm [1-3/16 in.] between units.

760±2 [29-15/16(29-27/32~30)]

1060±2 [41-3/4(41-21/32~41-13/16)]

P350, P400, EP250

Install the unit in such a way that the corner of the angle bracket at the base of the unit shown in the figure is securely supported. The brackets may bend if they are not securely supported.

<With detachable leg>

A

B

CC

D

D

D

<P450, EP300>

A 795±2 [31-5/16(31-1/4~31-13/32)]

P450, EP300PUHY

A

PUHY

A

P200-P300, EP200PUHY

A A A A

724±

3 [(2

8-13

/32~2

8-5/8

)]

724±

3 [(2

8-13

/32~2

8-5/8

)]

(For maintenance)A

(For maintenance)A

30 [1-3/16]190 [7-1/2]

30 [1-3/16]190 [7-1/2]A A

Leave a minimum of 30 mm [1-3/16 in.] between units.

Page 41: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 75

4. Outdoor Installation DATA G8

SYSTEM DESIGN

System Y

4-3-5. Refrigerant pipe routing

4-3-4. Installation

· P200-P300EP200

· P350-P400EP250

Installation base perpendicular to the unit’s front panelInstallation base parallel to the unit’s front panel

When the pipes and/or cables are routed at the bottom of the unit, make sure that the through hole at the base ofthe unit does not get blocked with the installation base. When the pipes are routed at the bottom of the unit, the base should be at least 100 mm [3-15/16 in.] in height.

(Unit : mm [in.])

(Unit : mm [in.])

(Unit : mm [in.])221 150

86 [3

-13/32

]92

[3-5

/8]

145 [

5-23/3

2]

145

(Mou

ntin

g pi

tch)

(Mounting pitch)

2X2-14X20 Oval hole

Refrigerant service valve <gas>

Refrigerant service valve <liquid>

(760

[29-

15/1

6])

80 760 [29-15/16] 80

1818

131

83251

186

Bottom view

724(

721

72

7)

150

84 [3

-5/16

]

[5-3

/16]

[5-2

3/32

]

[5-3

/16]

[5-2

3/32

]

94 [3

-23/32

]

(Mounting pitch)

Refrigerant servicevalve <liquid>

(Mou

ntin

g pi

tch)

2X2-14X20 Oval hole

Refrigerant servicevalve <gas>

271

216

18

8080 1060 [41-3/4]

18[2

3/32

][2

3/32

]

[23/

32]

[23/

32]

[28-

13/3

2~28

-5/8

]

[28-

13/3

2~28

-5/8

]

301 83

131

(760

[29-

15/1

6])14

5

145 [

5-23/3

2]

Bottom view

724(

721

727

)

[3-5/32][3-5/32][3-5/32] [3-5/32]

[7-11/32] [8-17/32]

[11-7/8] [3-9/32]

[10-11/16] [5-29/32]

[9-29/32] [3-9/32]

[8-23/32] [5-29/32]

The gaps around the edges of through holes for pipes and wires on theunit allow water or mice to enter the unit and damage its parts. Closethese gaps with filler plates.

This unit allows two types of pipe routing:• Bottom piping• Front piping

To prevent small animals, water, and snow fromentering the unit and damage its parts, close thegap around the edges of through holes for pipesand wires with filler plates.

CAUTION

Fill the gap at the siteFiller plate(not supplied)

· P450, EP300

Bottom view[3-5/32]

80795 [31-5/16]

(Mounting pitch) (Mounting pitch)[31-5/16]795

[3-5/32]80 18

[23/

32]

724(

721~

727)

[28-

13/3

2~28

-5/8

]

(Mou

ntin

g pi

tch)

(760

[29-

15/1

6])

18 [23/

32]

[3-2

3/32

]94

84[5

-23/

32]

145 [3

-5/1

6]

[3-9/32]83[21-31/32]558

590[23-1/4][20-1/8]511[5

-3/1

6][5

-23/

32]

145

131

Refrigerant servicevalve <liquid>

Refrigerant service valve <gas>

2X3-14[9/16]X20[13/16] Oval hole[5-29/32]150

Page 42: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4. Outdoor Installation DATA G8

SYSTEM DESIGN 4 - 76

Syst

em Y

4-3-6. Twinning on the outdoor unit side

Reducer

±15°

The tilt angle of the reducer should be within ±15°with the horizontal plane.

Note: See the following drawing for the fitting position of the twinning pipe.

The tilt angle of the twinning pipeThe tilt angle of the twinning pipe must be within ±15° with the horizontal plane. Tilting the twinning pipe more than specified will cause damage to the unit.

The length of the straight part of the pipe before the branchingFor the twinning kit, always use the accessory piping parts. The length of the straight part of pipe connected in front of the twinning pipe must be 500 mm [19 in.] or longer. (Connect the field piping so that the length of the straight part of pipe connected in front of the twinning pipe can be 500 mm [19 in.] or longer.) If the length is less than 500 mm [19 in.], it will cause damage to the unit.

To Indoor unit

Less than 2 m [6 ft.]

To Indoor unit2m

To Indoor unit200 mm [7 in.] or over

Trap (gas pipe only)

The piping connectionWhen connecting the twinning kit to the outdoor unit, note the following:If the length of piping from the twinning kit to the outdoor unit is more than 2 m [6 ft.], install a trap within 2 m [6 ft.] from the outdoor unit. The height of the trap must be 200 mm [7 in.] or higher.

When installing the twinning kit in a higher position than the outdoor unit base, make sure that the twinning kit is installed in a position lower than 200 mm [7 in.] from the outdoor unit base.

<2 m [6 ft.] or less>

<PUHY-P500YSJM-A>

<PUHY-P950YSJM-A>

<More than 2 m [6 ft.]>

Outdoor unit 1 Outdoor unit 2

200 mm [7 in.] or less

Twinning pipe1

To Indoor unit

Outdoor unit 1 Outdoor unit 2 Outdoor unit 3

200 mm [7 in.] or less

Twinning pipe 1 Twinning pipe 2

To Indoor unit

Make sure the pipes from the twinning pipe to the outdoor unit are sloped downwards (towards the twinning pipes).

Do not install traps other than the ones between outdoor units described on a separate sheet to prevent oil backflow and compressor start-up failure.

Caution•

Do not install solenoid valves to prevent oil backflow and compressor start-up failure. • Do not install a sight glass because it may show improper refrigerant flow.If a sight glass is installed, inexperienced technicians that use the glass may overcharge the refrigerant.

Page 43: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 77

4. Outdoor Installation DATA G8

SYSTEM DESIGN

System Y

Field piping

Field piping

Twinning kit

The length of the straight pipe

must be 500 mm [19 in.] or longer

Field piping

Field piping

Field piping

Twinning kit

Twinning kitThe length of the straight pipe

must be 500 mm [19 in.] or longer The length of the straight pipe

must be 500 mm [19 in.] or longer

See the following drawing for connecting the pipes between the outdoor units.

<PUHY-P500YSJM-A>

<PUHY-P950YSJM-A>

4-3-7. Twinning on the outdoor unit side

The length of the straight pipe must be 500mm[19 in.] or longer.If not, it may cause improper operation.

CAUTION

Page 44: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4. Outdoor Installation DATA G8

SYSTEM DESIGN 4 - 78

Syst

em Y

4-4. Weather countermeasure

Prevention the Outdoor unit from wind and snow damages in cold or snowy areas, snow hood shown below is recommended and helpful.• Snow hood

Countermeasure to snow and wind

Outlet Inlet

<Side view><Front view> <Front view

<Front view>

>

750 [29-17/32]

453[17-27/32]760 [29-15/16]

(760)[29-15/16]

1210 [47-21/32]

H13

24 [5

2-5/

32]

1324

[52-

5/32

]

(1220)[48-1/16]

1206 [47-1/2]906 [35-11/16]

453[17-27/32]

453[17-27/32]

453[17-27/32]

453[17-27/32]910 [35-27/32]

H86

[3-1

3/32

]

86[3

-13/

32]

800

[31-

1/2]

800

[31-

1/2]

(920)[36-1/4]

In cold and/or snowy areas, sufficient countermeasures to wind and snow damages should be taken for operating unit in normal and good condition in winter time. Surround the units with snow nets or fences to protect them from snow. Even in the other areas, full consideration is required for installation of unit in order to prevent abnormal operations caused by wind or snow. When rain and snow directly fall on unit in the case of air-conditioning operations in 10 or less degrees centigrade outdoor air (50 or less degrees fahrenheit outdoor air) , mount inlet and outlet ducts on unit for assuring stable operations.

A

A

B

B

B

<Side view>

750 [29-17/32]

453[17-27/32]760 [29-15/16]

(760)[29-15/16]

A

B

B

B

B

B

B

453 [17-27/32]

453 [17-27/32] 1750 [68-29/32]

1324

[52-

5/32

]86

[3-1

3/32

]H

800

[31-

1/2]

1740 [68-17/32]

1750 [68-29/32]

Page 45: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 79

4. Outdoor Installation DATA G8

SYSTEM DESIGN

System Y

Countermeasure to windReferring to the figure shown below, take appropriate measures which will suit the actual situation of the place for installation.A unit installed alone is vulnerable to strong winds. Select the installation site carefully to minimize the effect of winds.To install a unit in a place where the wind always blows from the same direction, install the unit so that the outlet faces away from the direction of the wind.

Note:1. Height of frame base for snow damage prevention (H) shall be twice as high as expected snowfall. Width of frame base

shall not exceed that of the unit. The frame base shall be made of angle steel, etc., and designed so that snow and wind slip through the structure. (If frame base is too wide, snow will be accumulated on it.)

2. Install unit so that wind will not directly lash against openings of inlet and outlet ducts.3. Build frame base at customer referring to this figure.

Material : Galvanized steel plate 1.2T [1/16 in. T]Painting : Overall painting with polyester powderColor : Munsell 5Y8/1 (same as that of unit)

4. To install units side by side, install a filler plate between the fan guard and the outlet-side snow food as shown in Figure A. (The filler plate provided accommodates the installation pitch of between 30-80 mm [1-3/16~3-5/32 in.].) 5. When the unit is used in a cold region and the heating operation is continuously performed for a long time when the outside air temperature is below freezing, install a heater to the unit base or take other appropriate measures to prevent water from freezing on the base.

Filler plateFigure A

Wind

Install the outdoor unit where seasonal winds do not blow directly against the unit, such as behind a building.

Install the outdoor unit to avoid having seasonal winds against the front of air outlet/inlet on the unit.

A

A

A

A

Page 46: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4. Outdoor Installation DATA G8

SYSTEM DESIGN 4 - 80

Syst

em Y

4-5. Caution on selecting outdoor units

Consult your dealer when the following issues on Y system are the key concern.· Warm air may flow out from the indoor unit during heating Thermo-OFF.· Refrigerant flow sound may occur in the rooms with low background noise such as hotel rooms, hospital rooms, bedrooms, or conference rooms.To avoid the above issues on Y system, changing board settings on the indoor and outdoor units is required.Ask AC&R Works for details.

Page 47: CITY MULTI SYSTEM DESIGN Y SERIES - Mitsubishi Electric...1. Electrical work DATA G8 SYSTEM DESIGN 4 - 36 System Y I.1. Electrical work 1-1. General cautions OK NO Follow ordinance

4 - 81

5. Caution for refrigerant leakage DATA G8

SYSTEM DESIGN

System Y

5. Caution for refrigerant leakageThe installer and/or air conditioning system specialist shall secure safety against refrigerant leakage according to local regulations or standards.The following standard may be applicable if no local regulation or standard is available.

5-1. Refrigerant property

5-2. Confirm the Critical concentration and take countermeasure

R410A refrigerant is harmless and incombustible. The R410A is heavier than the indoor air in density. Leakage of the refrigerant in a room has possibility to lead to a hypoxia situation. Therefore, the Critial concentration specified below shall not be exceeded even if the leakagehappens.

Critical concentrationCritical concentration hereby is the refrigerant concentration in which no human body would be hurt if immediate measures can be takenwhen refrigerant leakage happens.

Critical concentration of R410A: 0.30kg/m3

(The weight of refrigeration gas per 1 m3 air conditioning space.);The Critical concentration is subject to ISO5149, EN378-1.

For the CITY MULTI system, the concentration of refrigerant leaked should not have a chance to exceed the Critical concentration in any situntion.

The maximum refrigerant leakage concentration (Rmax) is defined as the result of the possible maximum refrigerant weight (Wmax)leaked into a room divided by its room capacity (V).It is referable to Fig.5-1.The refrigerant of Outdoor unit here includes its originalcharge and additional charge at the site.The additional charge is calculated according to “3-3 .Refrigerant charging calculation” and shall not be over charged at the site.Procedure 5-2-1~3 tells how to confirm maximum refrigerant leakage concentration (Rmax) and how to take countermeasures againsta possible leakage.

Refrigerant pipe

to Outdoor unit

Indoor unit

Opening

Fresh air supply fan (always ON)

Indoor space

(Floor)

Fig.5-2.Fresh air supply always ON

Refrigerant pipe

to Outdoor unit

Indoor unit

Opening

Sensor for refrigerant leakage (Oxygen sensor or refrigerant sensor).[At 0.3m height from the floor]

Fresh air supply fan

Indoor space

(Floor)

Fig.5-3.Fresh air supply upon sensor action

Refrigerant pipe (high pressure pipe)

Refrigerant stop valve

to Outdoor unit

Indoor unit

Opening

Sensor for refrigerant leakage (Oxygen sensor or refrigerant sensor).[At 0.3m height from the floor]

Fresh air supply fan

Indoor space

(Floor)

Fig.5-4.Fresh air supply and refrigerantshut-off upon sensor action

Note 1.Countermeasure 3 should be done in a proper way in which the fresh air supply shall be on whenever the leakage happens.Note 2.In principle, MITSUBISHI ELECTRIC requires proper piping design, installation and air-tight testing after installation to avoid leakage happening.

In the area should earthquake happen, anti-vibration measures should be fully considered.The piping should consider the extension due to the temperature variation.

Outdoor unit (No.1)

Flow of refrigerant

Indoor unit

Maximum refrigerant leakage concentration (Rmax)

Outdoor unit (No.1) Outdoor unit (No.2)

Indoor unit

Flow of refrigerant Flow of refrigerant

Rmax=Wmax / V (kg/m3)Maximum refrigerant leakage concentration (Rmax) Rmax=Wmax / V (kg/m3)where, Wmax=W1+W2

W1: Refrigerant weight of Outdoor unit No.1W2: Refrigerant weight of Outdoor unit No.2

Fig. 5-1 The maximum refrigerant leakage concentration5-2-1.Find the room capacity (V),

If a room having total opening area more than 0.15% of the floor area at a low position with another room/space, the two rooms/space areconsidered as one.The total space shall be added up.

5-2-2.Find the possible maximum leakage (Wmax) in the room.If a room has Indoor unit(s) from more than 1 Outdoor unit, add up the refriger-ant of the Outdoor units.

5-2-3.Divide (Wmax) by (V) to get the maximum refrigerant leakage concentration (Rmax).5-2-4.Find if there is any room in which the maximum refrigerant leakage concentration (Rmax) is over 0.30kg/m3.

If no, then the CITY MULTI is safe against refrigerant leakage.If yes, following countermeasure is recommended to do at site.Countermeasure 1:Let-out (making V bigger)

Design an opening of more than 0.15% of the floor area at a low position of the wall to let out the refrigerant whenever leaked.e.g.make the upper and lower seams of door big enough.

Countermeasure 2:Smaller total charge (making Wmax smaller) e.g.Avoid connecting more than 1 Outdoor unit to one room.e.g.Using smaller model size but more Outdoor units.e.g.Shorten the refrigerant piping as much as possible.

Countermeasure 3:Fresh air in from the ceiling (Ventilation) As the density of the refrigerant is bigger than that of the air.Fresh air supply from the ceiling is better than air exhausting from the ceiling.Fresh air supply solution refers to Fig.5-2~4.