CleanAgent 2001

Embed Size (px)

Citation preview

  • 8/10/2019 CleanAgent 2001

    1/7

    Printed on: 2014/01/11 19:41 Page 1

    PASS/FAIL Enclosure Integrity ReportCleanAgent 2001 retention time prediction program revision 2.5.4. Complies with NFPA 2001 Appendix C, year 2000 edition.By Retrotec, Inc, 2200 Queen Street, Bellingham, WA USA 98229 360-738-9835 www.retrotec.comSoftware Licensed to: CRF Tech Engineering Solutions air leaks in

    agent leaks out

    Building, Location Example Building 1, Exampletown, WA, USACompany, Contact General Electric, John Client Dude

    Room nameChange range experiment

    Test number1Calibration Certificate # 2 Certificate created 2002/02/03

    Test date/time 2002/03/31 00:00 Net Protected Volume, V 15 m^3Tester Sample Tech Maximum Protected Height, HO 3.66 m.

    Certified to Level: 4 - ISO multi-point & vent test Minimum Protected Height, H 3.00 m.Signature ....................................................... Static during retention, PSH 0.0 Pa

    Elevation above sea level 229 m. Operating temperature 21 CCorrection method NFPA 2001 (2000) Formula A-3-5.3.3 CInitial concentration, 7.26%

    Correction factor 0.97 Mixing during retention NoAgent FM200 (HFC227ea) Agent quantity 1 m^3

    Total room leakage, ELA 0.2676 m^2 Minimum concentration, CF 7.26%

    Lower Leakage, BCLA 0.1338 m^2 Minimum retention time 10.0 minutes

    Below ceiling leakage defaulting to worst case -- 50% of total leakage.

    This enclosure was tested in compliance with NFPA 2001 and 12A.Assuming no continual mixing during the retention period,enclosure leakage could allow sufficient agent to be lost tocause an air/agent interface to descend from a MaximumProtected Height of 3.66 m. to the Minimum ProtectedHeight specified of 3.00 m.The retention time would then be 0.2 minutes which is

    less than the minimum retention time of 10 minutes. Theenclosure therefore FAILS this acceptance procedure.Notes here are a bunch of notes here are a bunch ofnotes here are a bunch of notes here are a bunch ofnotes here are a bunch of notes here are a bunch ofnotes here are a bunch of notes here

    Witnesses

  • 8/10/2019 CleanAgent 2001

    2/7

    DOOR FAN TEST -- Total Room Leakage DataCleanAgent 2001 retention time prediction program revision 2.5.4. Complies with NFPA 2001 Appendix C, year 2000 edition.By Retrotec, Inc, 2200 Queen Street, Bellingham, WA USA 98229 360-738-9835 www.retrotec.comSoftware Licensed to: CRF Tech Engineering Solutions air leaks in

    agent leaks out

    Building, Location Example Building 1, Exampletown, WA, USACompany, Contact General Electric, John Client Dude

    Room nameChange range experiment

    Test number1Calibration Certificate # 2 Certificate created 2002/02/03

    Total Room LeakageOperator In the room Smoke doesn't move Temperature during test (C)

    Static pressure 0 Pa 21 inside 21 outside

    Depressurization Range for room pressures: -15.8 to -18.8Blower range Room pressure -10*

    Auto corrected RP -9.5Range 9 Flow Pressure 100

    Auto corrected FP 102.6

    Corrected flow (m^3/sec.) -0.6610

    * Room pressure is too low. Retention time may be 9% shorter than predicted.

    Pressurization Range for room pressures: 15.8 to 18.8Blower range Room pressure 11*

    Auto corrected RP 10.5Range 9 Flow Pressure 123

    Auto corrected FP 126.8Corrected flow (m^3/sec.) 0.7030

    * Room pressure is too low. Retention time may be 7% shorter than predicted.

    F

    0.5010.0

    ELA m^2

    0.2679

    Standard ErrorNANA

    CorrelationNANA

    Intercept k10.20900.21200.2105

    Slope n0.50000.50000.5000

    FA

    0.50

    @Pa9.5

    10.510.0

    ELA m^20.26570.26940.2676

    DepressurizationPressurization

    Average

    Lower Leakage

    Below ceiling leakage of 0.1338 m^2 @ 10.0 Pais the worst case assumption of 50%

    Technician: Sample Tech Certified to Level: 4 - ISO multi-point & vent testYes Level 1 - Fire enclosure design basics for improving agent retention and passive protection

    Yes Level 2 - adds single door fan operation and NFPA clean agent retention time calculationsYes Level 3 - adds double door fan operation for Lower Leak measurementYes Level 4 - adds multi-point ISO door fan operation and discharge pressure relief vent

    Printed on: 2014/01/11 19:41 Page 2

  • 8/10/2019 CleanAgent 2001

    3/7

    Printed on: 2014/01/11 19:41 Page 3

    DOOR FAN TEST -- GraphCleanAgent 2001 retention time prediction program revision 2.5.4. Complies with NFPA 2001 Appendix C, year 2000 edition.By Retrotec, Inc, 2200 Queen Street, Bellingham, WA USA 98229 360-738-9835 www.retrotec.comSoftware Licensed to: CRF Tech Engineering Solutions air leaks in

    agent leaks out

    Building, Location Example Building 1, Exampletown, WA, USACompany, Contact General Electric, John Client Dude

    Room nameChange range experiment

    Test number1Calibration Certificate # 2 Certificate created 2002/02/03

  • 8/10/2019 CleanAgent 2001

    4/7

    One Year Calibration Certificate Certificate # 2 System Model # Retrotec - 970hp

    System Owned By Demo Certificate Console # 145898

    For CA2001 ver 2.0 license # 125-555 Equipment Calibrated by Colin Genge

    Good for one year date: 2002/02/03 expires: 2003/02/03

    This certificate complies with calibration requirements of NFPA 2001 Appendix C, year 2000 edition andISO 14520. Completed by Retrotec Inc, 2200 Queen Street, Bellingham, WA, USA 98226-4766

    Analog 60 This gauge used for Room Pressure

    serial # 93333

    to correct mult by & add gauge CR MRC error Pa

    0.00 - 10.50 0.95 0.00 8.0 7.6 8.0 -0.4

    10.50 - 14.75 0.98 -0.25 12.0 11.5 12.0 -0.5

    14.75 - 17.50 1.04 -1.14 15.0 14.4 15.0 -0.6

    17.50 - 26.00 0.94 0.53 20.0 19.4 20.0 -0.6

    26.00 - 36.50 0.95 0.24 31.0 29.8 30.0 -0.2

    36.50 - 51.00 1.03 -2.76 41.5 40.2 40.0 0.2

    51.00 - 999.00 1.00 -1.00 55.5 54.5 55.0 -0.5

    Analog 250 This gauge used for Flow Pressure, Blower #1

    serial # 93334

    to correct mult by & add gauge CR MRC error Pa

    0.00 - 31.00 0.97 0.00 25.0 24.2 25.0 -0.8

    31.00 - 40.50 1.05 -2.63 35.0 34.2 35.0 -0.8

    40.50 - 60.00 1.03 -1.54 49.0 48.7 50.0 -1.3

    60.00 - 88.00 1.07 -4.29 73.5 74.5 75.0 -0.5

    88.00 - 126.00 1.05 -2.63 96.0 98.4 100.0 -1.6

    126.00 - 174.00 1.04 -1.25 145.0 149.8 150.0 -0.2

    174.00 - 999.00 1.00 6.00 194.0 200.0 200.0 0.0

    Analog 250 This gauge used for Flow Pressure, Blower #2

    serial # 93335

    to correct mult by & add gauge CR MRC error Pa

    0.00 - 31.00 0.97 0.00 25.0 24.2 25.0 -0.8

    31.00 - 40.50 1.05 -2.63 35.0 34.2 35.0 -0.8

    40.50 - 60.00 1.03 -1.54 49.0 48.7 50.0 -1.3

    60.00 - 88.00 1.07 -4.29 73.5 74.5 75.0 -0.588.00 - 126.00 1.05 -2.63 96.0 98.4 100.0 -1.6

    126.00 - 174.00 1.04 -1.25 145.0 149.8 150.0 -0.2

    174.00 - 999.00 1.00 6.00 194.0 200.0 200.0 0.0

  • 8/10/2019 CleanAgent 2001

    5/7

    Five Year Calibration Certificate Certificate # 2 System Model # Retrotec - 970hp

    System Owned By Demo Certificate Console # 145898

    For CA2001 ver 2.0 license # 125-555 Equipment Calibrated by Colin Genge

    Good for five years date: 2002/02/03 expires: 2007/02/03

    This certificate complies with calibration requirements of NFPA 2001 Appendix C, year 2000 edition andISO 14520. Completed by Retrotec Inc, 2200 Queen Street, Bellingham, WA, USA 98226-4766

    CR is the Corrected Room pressure.CR = "gauge" reading X "mult by" factor + "& add" factor.

    CF is the Corrected Flow pressure derived the same way.The corrected readings are compared to the TRUE reading from our Master Reference Calibration (MRC)gauge and the resulting error shown in Pascals. Maximum allowable error is +/- 1 Pa from 0 to 50 Pa and+/- 5 Pa over 50 Pa.

  • 8/10/2019 CleanAgent 2001

    6/7

    Five Year Calibration Certificate Certificate # 2 System Model # Retrotec - 970hp

    System Owned By Demo Certificate Console # 145898

    For CA2001 ver 2.0 license # 125-555 Equipment Calibrated by Colin Genge

    Good for five years date: 2002/02/03 expires: 2007/02/03

    This certificate complies with calibration requirements of NFPA 2001 Appendix C, year 2000 edition andISO 14520. Completed by Retrotec Inc, 2200 Queen Street, Bellingham, WA, USA 98226-4766

    CALIBRATION EQUATIONS WITH CALCULATION EXAMPLES:

    blower #1 serial # >> 93335 blower #2 serial # >> 93336

    blower range N K K1 K2 K3 K4 MF CR FF cfm m3/ sec

    #1 18F 0.4690 311.5000 0.000 1.000 0.000 1.027 10.0 21.5 75 2,423 1.1437

    #1 18R 0.4800 366.8000 0.000 1.000 0.000 0.793 10.0 21.3 88.6 2,503 1.1813

    #1 9 0.4920 144.5000 0.000 1.000 0.000 0.993 10.0 17.6 78.5 1,228 0.5794

    #1 5 0.4510 97.4100 0.000 1.000 0.000 0.997 10.0 19.3 69.6 658 0.3106

    #1 3 0.4700 51.4800 0.000 1.000 0.000 1.055 10.0 13.2 74.5 412 0.1944

    #1 1.4 0.4670 30.4200 0.000 1.000 0.000 1.026 10.0 11.4 75 234 0.1106

    #1 1.3 0.4420 27.7100 0.000 1.000 0.000 1.179 10.0 24.1 74.5 220 0.1036

    #1 1.2 0.4830 17.2600 0.000 1.000 0.000 1.169 10.0 15.5 23.2 92 0.0435

    #1 1.1 0.4740 12.7100 0.000 1.000 0.000 1.111 10.0 34.7 81.4 114 0.0536

    #1 0.1 0.5100 5.7700 0.000 1.000 0.000 1.049 10.0 20.3 64.8 51 0.0240

    #2 18F 0.4690 311.5000 0.000 1.000 0.000 1.095 10.0 23.1 72.9 2,550 1.2033

    #2 18R 0.4800 366.8000 0.000 1.000 0.000 0.793 10.0 23.1 88.9 2,507 1.1832

    This calibration certificate comparesthe calibration holes in the Retrotectest chamber with the testedblower's measurement of those

    holes. The left hand column showsthe area of holes open in theRetrotec flow chamber. To the rightis the comparable Retrotec DoorFan result using the abovereferenced CA2001 softwarelicense. Maximum allowable error is+/- 5%.

    BLOWER TEST RESULTS: error

    Holes

    open

    in

    flow

    chamber

    cm2 blower range cm2 % cm2

    3,148 1 18F 3,135 -0.4 -13

    3,148 1 18R 3,254 3.3 106

    1,834 1 9 1,755 -4.3 -79

    925 1 5 899 -2.8 -26

    678 1 3 680 0.3 2

    419 1 1.4 417 -0.6 -2

    274 1 1.3 268 -2.1 -6

    143 1 1.2 141 -1.8 -2

    115 1 1.1 115 0.6 0

    67 1 0.1 68 1.0 1

    3,152 2 18F 3,183 1.0 31

    3,152 2 18R 3,129 -0.7 -23

    This calibration includes both gauge and blower error combined. CR and CF come from the One YearCertificate. For Flow Towards the operator, CF must be reduced by CR before calculating flow to yield FF,the symbol for the Final Flow pressure. For Flow Away from the operator CF=FF.FF must be >=MF and (CR * K2) otherwise flow pressure is too low for accurate resultsFlow in cfm = (FF-CR*K1)^N*(K+K3*FF)*K4 For m3/sec, divide by 2118.882.

  • 8/10/2019 CleanAgent 2001

    7/7

    Five Year Calibration Certificate Certificate # 2 System Model # Retrotec - 970hp

    System Owned By Demo Certificate Console # 145898

    For CA2001 ver 2.0 license # 125-555 Equipment Calibrated by Colin Genge

    Good for five years date: 2002/02/03 expires: 2007/02/03

    This certificate complies with calibration requirements of NFPA 2001 Appendix C, year 2000 edition andISO 14520. Completed by Retrotec Inc, 2200 Queen Street, Bellingham, WA, USA 98226-4766

    Technician: Sample Tech Certified to Level: 4 - ISO multi-point & vent testYes Level 1 - Fire enclosure design basics for improving agent retention and passive protectionYes Level 2 - adds single door fan operation and NFPA clean agent retention time calculationsYes Level 3 - adds double door fan operation for Lower Leak measurementYes Level 4 - adds multi-point ISO door fan operation and discharge pressure relief vent