Click here to load reader

CO1224T and CO1224TR Carbon Monoxide Detectors Sensor/SystemSensor...RealTest® Feature: The System Sensor CO1224T and CO1224TR Carbon Monoxide Detectors with RealTest enable evaluation

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

  • Agency Listings

    CO1224T and CO1224TRCarbon MonoxideDetectorswith RealTest® Technology

    The System Sensor CO1224T and CO1224TR (round)

    Carbon Monoxide (CO) Detectors use a highly accurate

    and reliable electrochemical sensing cell to provide early

    warning of dangerous CO levels.

    Features

    • RealTest®enablesafunctionaltestusingcannedCO

    • FullcompliancewithUL2075

    • Acode-requiredtroublerelay

    • WiringsupervisionwithSEMSterminals

    • Asix-yearend-of-lifetimer

    • 12/24VDC

    • Alowcurrentdrawof20mAinstandbyand40mAinalarm

    • Versatilemountingforwallandceiling

    • Accurateandreliableelectrochemicalsensingtechnology

    • OptionalCO-PLATECODetectorReplacementPlatetoupgradepreviouslyinstalledcompetitordetectorstotheCO1224T

    With RealTest® technology, theCOgassensingcellusedintheCO1224TandCO1224TRCOdetectorscanbetestedusingaCOgasagent,fullymeetingtherequirementsofNFPA720:2009.SimplyputthedetectorintoRealTestmode,sprayasmallamountofCOintothedetectorpertheinstallationinstructions,andwithinsecondsthedetectorwillalarm,indicatingsuccessfulgasentry.(Seethereversepageortheusermanualforcompleteinstructions.)

    WhendangerousamountsofCOaredetected,theCO1224TandCO1224TRdetectorsalertresidentsbysoundingandflashingatemp4signalalarm.With24/7centralstationmonitoring,residentsareguaranteedprotectionwhethertheyareawayfromhome,sleeping,oralreadysufferingfromtheeffectsofCO.

    TheCO1224TandCO1224TRaredesignedforsystemoperation.ThesedetectorsarefullylistedtoUL2075andofferacode-requiredtroublerelaytosendasensorfailureorend-of-lifesignaltothecontrolpanelandthecentralstation.TheCO1224TandCO1224TRalsouseSEMS-typeterminalPhilipsheadscrewsforquickerandmorepositivewiringconnectionsandcode-requiredwiringsupervision.Withalowcurrentdraw,thesedetectorsenablemoredevicestobeconnectedtothepanel,limitingtheneedtopurchaseextrapowersuppliesormoreexpensivepanels.As12/24VDCdetectors,theCO1224TandCO1224TRwilloperateonmostindustrysecurityandfirealarmcontrolpanels.

    E307195 E304075 5276-1653:0194

  • 3825OhioAvenue•St.Charles,IL60174Phone:800-SENSOR2•Fax:630-377-6495

    www.systemsensor.com

    ©2012SystemSensor.Productspecificationssubjecttochangewithoutnotice.Visitsystemsensor.comforcurrentproductinformation,includingthelatestversionofthisdatasheet.

    SCDS00100•4/12

    Ordering InformationPart No. DescriptionCO1224T 12/24volt,4-wiresystem-monitoredcarbonmonoxidedetectorwithRealTest®TechnologyCO1224TR 12/24volt,4-wiresystem-monitoredroundcarbonmonoxidedetectorwithRealTest®TechnologyCO-PLATE COdetectorreplacementplatetocoverthefootprintofpreviouslyinstalledcompetitivedetectorsasnecessary

    CO1224T and CO1224TR Carbon Monoxide Detector SpecificationsArchitectural/Engineering Specifications

    Carbonmonoxide(CO)detectorshallbeasystem-connectedSystemSensormodelnumberCO1224TorCO1224TRlistedtoUnderwritersLaboratoriesUL2075forGasandVaporDetectorsandSensors.Thedetectorshallbeequippedwithasounderandatroublerelay.Thedetector’sbaseshallbeabletomounttoasingle-gangelectricalboxordirect(surface)mounttothewallorceiling.WiringconnectionsshallbemadebymeansofSEMSscrews.Thedetectorshallprovidedual-colorLEDindicationthatblinkstoindicatenormalstandby,alarm,orend-of-life.Whenthesensorsupervisionisinatroublecondition,thedetectorshallsendatroublesignaltothepanel.Whenthedetectorgivesatroubleorend-of-lifesignal,thedetectorshallbereplaced.ThedetectorshallprovideameanstotestCOgasentryintotheCOsensingcell.ThedetectorshallprovidethiswithatestmodethatacceptsCOgasfromatestagentandalarmsimmediatelyuponsensingCOentry.ThedetectorshallperforminthedetectionofCOupto12,000feetabovesealevelandalarmwithinthetimespecifiedbyANSI/UL2034forCOconcentrationsof70,150and400partspermillion(ppm),asverifiedbyaNationallyRecognizedTestLaboratory.Electrical Specifications

    Operating Voltage 12/24VDCAudible Signal 85dBinalarmStandby Current 20mAAlarm Current 40mA(75mAtest)Alarm Contact Ratings 0.5A@30VDCTrouble Contact Ratings 0.5A@30VDCPhysical Specifications

    Size: CO1224T Length:5.1in,Width:3.3in,Height:1.3in CO1224TR Diameter:6in,Height:1.3inApproximate Weight CO1224T:7oz;CO1224TR:11ozOperating Temperature Range 32°Fto104°F(0°Cto40°C)Operating Humidity Range 22to90%RHInput Terminals 14to22AWGMounting Single-gangbackbox;surfacemounttowallorceiling

    Operation ModesOperation Mode Green LED Red LED Sounder

    Normal(standby) Blink1perminute — —

    Alarm — Blinkintemp4pattern Soundintemp4pattern

    RealTest®Feature: TheSystemSensorCO1224TandCO1224TRCarbonMonoxideDetectorswithRealTestenableevaluationofthefunctionalityoftheCOsensingcellusingacannedCOtestagent.

    HushFeature: PushingtheTest/Hushbuttonwillsilencethesounderfor5minutes(exceptinRealTestmode).TroubleFeature: Whenthedetectorisinatroublecondition,itwillsendatroublesignaltothepanel.End-of-LifeTimer: Afterthedetector’sinternalsensorhasreachedtheendofitslife,atroublesignalwillbesentto

    thepaneltoindicateitistimetoreplacethedetector.AnelectrochemicalCOdetectorlifespanisaboutsixyears.Thedetectormustbereplacedbythedatemarkedontheinsideoftheproduct.

    CO-PLATE: SystemSensoralsoofferstheCO-PLATECODetectorReplacementPlatetocoverthefootprint(whennecessary)ofpreviouslyinstalledcompetitivecarbonmonoxidedetectorsthatrequirereplacement.

    3.

    PushandholdtheTest/HushbuttonfortwosecondstoenterRealTestmode.ThegreenLEDwillflashonceeverysecondtoindicateRealTestmodehasstarted.

    SpraycannedCOagentintothedetector.

    CO-PLATE

    VerifyCOsensingatthecontrolpanel.ThedetectorwillautomaticallyexitRealTestalarmmodeafterabout20-60seconds.

    NOTE:CheckwithlocalcodesandtheAHJtodetermineifafunctionalgastestisdesiredforaninstallation.