2 HOUR FIRE RESISTANCE RATING FROM FLOOR SLAB TIGHT TOROOF DECK ABOVE WITH 90 MINUTE OPENING PROTECTIVES
CONSTRUCTION:8" CONCRETE MASONRY UNITS, 2" RIGID INSULATION & 4" FACEBRICK (14" TOTAL THICKNESS) U.L. DESIGN No. U902
ONE HOUR FIRE RESISTANCE RATING FROM FLOOR SLAB TIGHTTO ROOF DECK ABOVE WITH 45 MINUTE OPENING PROTECTIVES
CONSTRUCTION:8" CONCRETE MASONRY UNITS U.L. DESIGN No. U905
OR, ONLY WHERE SHOWN ON DRAWINGSONE LAYER 5/8" FIRECODE GYPSUM BOARD EACH SIDE OF3.5/8" x 20 GA. METAL STUDS @ 16"oc U.L. DESIGN No. U465
OR 8" CONCRETE MASONRY UNITS U.L. DESIGN No. U905
46
DENOTES FIRE RESISTANCE RATING OF OPENING PROTECTIVE (IN MINUTES)
OCCUPANT LOAD
FIRE EXTINGUISHER
CONSTRUCTION:8" & 12" CONCRETE MASONRY UNITS
SMOKE TIGHT (NO FIRE RESISTANCE RATING) FROMFLOOR SLAB TIGHT TO ROOF DECK OR SOLID CEILINGABOVE WITH 1.3/4" SOLID-CORE OR 1/4" GLASS OPENINGPROTECTIVES
P DENOTES PANIC HARDWARE DEVICE ON EACH DOOR LEAF
"ACCESSIBLE" ROUTE/ENTRANCE/EGRESS
BUILDING EXIT WITH EGRESS WIDTH
ONE HOUR FIRE RESISTANCE RATING (FOR SMOKE BARRIER WALLS)WITH 20-MINUTE SELF-CLOSING OR SMOKE ACTIVATED LABEL DOORS.INSTALL FROM FLOOR SLAB TO UNDERSIDE OF ROOF DECK ABOVE.GLAZED OPENINGS ARE PERMITTED IF 3/4 HOUR RATED, PER NFPA 257(U.L. 9) . OPENING SHALL BE LESS THAN 25% OF THE SMOKE BARRIERWALL. NOTE THAT WHERE THE SMOKE BARRIER WALL IS ALSO A 2 HOURAREA SEPARATION WALL, THE MORE STRINGENT REQUIREMENTSSHALL APPLY.
2-HR
1-HR
LEGEND - CODE COMPLIANCE PLAN
SMOKE
20
SMOKE TIGHT
64" w.
FE
GMB
ARCHITECT + ENGINEERARCHITECURE + ENGINEERING
85 East Eighth Street, Suite 200, Holland, MI 49423P. 616.796.0200 F. 616.796.0201 www.gmb.com
OWNER
GMB Project #
Printed On Recycled Paper
GRCC Project # 1213-11034
OWEN AMES KIMBALL
CONSTRUCTION MANAGER
300 Ionia Ave, NW, Grand Rapids, MI 49503-2507P. 616.456.1521 F. 616.4580770 www.owen-ames-kimball.com
VICINITY MAP
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
COLLEGE PARK PLAZA
GRAND RAPIDS COMMUNITY COLLEGE
GRAND RAPIDS, MICHIGAN5-242011/5/12
BIDDING AND CONSTRUCTION
GRAND RAPIDS COMMUNITY COLLEGE143 BOSTWICK AVE N.E. GRAND RAPIDS MI 49503
616.234.4000 www.cms.grcc.edu
180 N. DIVISION
INFRASTRUCTURE RENOVATION
ARCHITECTURALA2.0 PHASE 2 - RAMP FLOOR PLANA2.1 PHASE 2 - PLAZA FLOOR PLANA2.1M PHASE 2 - MEZZANINE FLOOR PLANA2.2 PHASE 2 - SECOND FLOOR PLANA2.3 PHASE 2 - THIRD FLOOR PLANA2.4 PHASE 2 - FOURTH FLOOR PLANA2.5 PHASE 2 - FIFTH FLOOR PLANA2.6 PHASE 2 - SIXTH FLOOR PLANA2.7 PHASE 2 - PENTHOUSEA3.0 RAMP REFLECTED CEILING PLAN NEW AND DEMOLITIONA3.1 PLAZA REFLECTED CEILING PLAN NEW AND DEMOLITIONA3.1M MEZZANINE REFLECTED CEILING PLAN NEW AND DEMOLITIONA3.2 SECOND FLOOR REFLECTED CEILING PLAN NEW AND DEMOLITIONA3.3 THIRD FLOOR REFLECTED CEILING PLAN NEW AND DEMOLITIONA3.4 FOURTH FLOOR REFLECTED CEILING PLAN NEW AND DEMOLITIONA3.5 FIFTH FLOOR REFLECTED CEILING PLAN NEW AND DEMOLITIONA3.6 SIXTH FLOOR REFLECTED CEILING PLAN NEW AND DEMOLITIONA5.1 DOOR FRAME SCHEDULE DETAILSFIRE PROTECTIONFP0.0 RAMP AND PLAZA FIRE PROTECTION DEMOLITION PLANSFP2.0 RAMP AND PLAZA FIRE PROTECTION PLANSFP2.1 MEZZANINE AND SECOND FLOOR FIRE PROTECTION PLANSFP2.2 THIRD AND FOURTH FLOOR FIRE PROTECTION PLANSFP2.3 FIFTH AND SIXTH FLOOR FIRE PROTECTION PLANSFP2.4 PENTHOUSE FIRE PROTECTION PLAN AND DETAILSMECHANICALM0.0 PHASE 2 - RAMP MECHANICAL DEMOLITION PLANM0.1 PHASE 2 - PLAZA & MEZZANINE MECHANICAL DEMOLITION PLANM0.2 PHASE 2 - SECOND & THIRD FLOOR MECHANICAL DEMOLITION PLANM0.3 PHASE 2 - FOURTH & FIFTH FLOOR MECHANICAL DEMOLITION PLANM0.4 PHASE 2 - SIXTH FLOOR & PENTHOUSE MECHANICAL DEMOLITION PLANM2.0 PHASE 2 - ENLARGED RAMP HVAC PLANM2.1 PHASE 2 - PLAZA & MEZZANINE HVAC PLANM2.2 PHASE 2 - SECOND & THIRD FLOOR HVAC PLANM2.3 PHASE 2 - FOURTH & FIFTH FLOOR HVAC PLANM2.4 PHASE 2 - SIXTH FLOOR HVAC PLANM2.5 PHASE 2 - ENLARGED PENTHOUSE HVAC PLANM3.0 PHASE 2 - ENLARGED RAMP HYDRONIC PIPING PLANM3.1 PHASE 2 - PLAZA & MEZZANINE HYDRONIC PIPING PLANM3.2 PHASE 2 - SECOND & THIRD FLOOR HYDRONIC PIPING PLANM3.3 PHASE 2 - FOURTH & FIFTH FLOOR HYDRONIC PIPING PLANM3.4 PHASE 2 - SIXTH FLOOR HYDRONIC PIPING PLANM3.5 PHASE 2 - ENLARGED PENTHOUSE HYDRONIC PIPING PLAN - ADDENDUMM4.0 PHASE 2 - HOT WATER & CHILLED WATER HYDRONIC PIPING SCHEMATICSM7.0 PHASE 2 - MECHANICAL DETAILSM8.0 PHASE 2 - MECHANICAL EQUIPMENT SCHEDULEELECTRICALE0.0 PHASE 2 - RAMP ELECTRICAL DEMOLITION PLANE0.1 PHASE 2 - PLAZA & MEZZANINE ELECTRICAL DEMOLITION PLANE0.2 PHASE 2 - SECOND & THIRD FLOOR ELECTRICAL DEMOLITION PLANE0.3 PHASE 2 - FOURTH & FIFTH FLOOR ELECTRICAL DEMOLITION PLANE0.4 PHASE 2 - SIXTH FLOOR & PENTHOUSE ELECTRICAL DEMOLITION PLANE2.0 PHASE 2 - RAMP ELECTRICAL PLANE2.1 PHASE 2 - PLAZA & MEZZANINE ELECTRICAL PLANE2.2 PHASE 2 - SECOND & THIRD FLOOR ELECTRICAL PLANE2.3 PHASE 2 - FOURTH & FIFTH FLOOR ELECTRICAL PLANE2.4 PHASE 2 - SIXTH FLOOR & PENTHOUSE ELECTRICAL PLANE3.0 PHASE 2 - RAMP LIGHTING PLANE3.1 PHASE 2 - PLAZA & MEZZANINE LIGHTING PLANE3.2 PHASE 2 - SECOND & THIRD FLOOR LIGHTING PLANE3.3 PHASE 2 - FOURTH & FIFTH FLOOR LIGHTING PLANE3.4 PHASE 2 - SIXTH FLOOR & PENTHOUSE LIGHTING PLANE4.0 PHASE 2 – ONE-LINE DIAGRAME5.0 PHASE 2 - SCHEDULESE5.1 PHASE 2 - SCHEDULESE7.0 PHASE 2 – SYMBOL LEGEND & NOTES
CODE BASED ON : 2009 MICHIGAN REHABILITATION CODE FOR EXISTING BUILDINGSFIRE PROTECTION: 2007 NFPA 13 + 14MECHANICAL: 2009 MICHIGAN MECHANICAL CODEELECTRICAL: 2008 MICHIGAN ELECTRICAL CODE (NEC)
FLOOR AREA SQUARE FOOTAGE / OCCUPANT LOAD
Name Gross AreaSQ. FT. PerOccupant
OccupantLoad
PENTHOUSE LEVEL 3096 SF 100 31SIXTH FLOOR 6776 SF 100 68FIFTH FLOOR 6776 SF 100 68FOURTH FLOOR 6512 SF 100 65THIRD FLOOR 6512 SF 100 65SECOND FLOOR 6248 SF 100 62MEZZANINE 3787 SF 100 38PLAZA 2609 SF 100 26PLAZA ANNEX 1133 SF 100 11RAMP LEVEL 2575 SF 100 26
UP
UP
UP
UP
11
4
6
7
9
1
13
A B C D F G H K L
14
15
16
M
12
NEW 4" MECHANICALMAINT. PADS
3
2 HR. RATED ROOM FORFIRE PROTECTION RISERTHIS AREA PER:NFPA 20 2010 ADDITION4.12.1.1
VESTIBULE001
LOBBY002
MECHANICAL003
FIRE PUMP004
004A
003A
27' - 4"
8' - 5
"
10' -
6"
30' - 0"
COORD. EXISTING PADSW/ NEW PADS
COORD. EXISTING PADSW/ NEW PADS
7' - 4
"
1A2.0
NEW 6" CONC. FLOORW/ REINF. DOWEL INTOEXISTING SLAB @ 24" O.C.
1A5.1
Sim
STORAGE0057'
- 4"
2A2.0
005A
NEW 2HR
NEW 2HR NEW 1HR
EXISTING 1HR
EXISTING 1HRNEW 1HR
21' - 4"
ALL NEW WALLS TO BEPAINTED BOTH SIDES
PATCH REPAIR OLD LOUVEROPENINGS THIS WALL MATCHADJACENT FINISHES
COORDINATE NEW MECH.OPENING (52"x34") THISAREA U12 SEE LINTELSCHEDULE A2.7
COORDINATE FLOOR CUTTING &PATCHING FOR NEW MECH/PLUMBING/CONDUITS
U8 FOR NEW LOUVERTHIS LOCATION SEELINTEL SCHEDULE
NEW LOUVER (7'-10"X6'-6")REWORK GUARDRAILAND SILL AS REQUIREDCOORDINATE W/ MECH.
U8 ABOVE DOORSEE LINTEL SCHEDULE
U8 ABOVE DOORSEE LINTEL SCHEDULE
CONT. U12 ABOVE DOORAND LOUVER SEE LINTELSCHEDULE
WALL INFILL THIS AREAWITH LIKE MATERIALSCOORDINATE THISLOCATION WITH MECH.
11
4
6
7
9
1
13
A B C D F G H K L
14
15
16
M
12
3
CUT AND REMOVECONC. FLOOR THISAREA
REMOVE DOORS AND LOUVERPREP FOR NEW DOOR AND LOUVER
8" CMU WALL W/ #5 BARS @ 48" O.C.PAINTED W/ FOAM FILLED CORES
2HR. RATED WALL SEALTIGHT TO CONC. DECKABOVE
2" GAP FIRE SEAL TYPICAL
VAPOR BARRIER
NEW 6" CONC. FLOORW/ REINF. DOWEL INTOEXISTING SLAB @ 24" O.C.
7
8" CMU WALL W/ #5 BARS @ 48" O.C.PAINTED W/ FOAM FILLED CORES
1HR. RATED WALL SEALTIGHT TO CONC. DECKABOVE
2" GAP FIRE SEAL TYPICAL
2' - 0
"
12" #4 DOWEL INTOEXISTING SLAB @24" O.C.
2" RIGIDINSULATION
CONT. # 5 BARTOP AND BOTT.
VAPOR BARRIERTURN UP ATSLAB EDGE
NEW 6" CONC.FLOOR W/REINF. DOWELINTO EXISTINGSLAB @ 24" O.C.
10' -
0"
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A2.0
5-2420
PHASE 2 - RAMP FLOOR PLAN
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"RAMPNORTH
1/8" = 1'-0"RAMP - DEMO
A2.0 3/4" = 1'-0"
1 PUMP ROOM WALL
A2.0 3/4" = 1'-0"
2 STORAGE WALL
DN
UP
UP
UP
DN
UP
DN
UP
UP
UP
DN
11
4
6
7
9
1
13
A B C D F G H K L
14
15
16
M
12
3
NEW 6" CONC. THISAREA COORDINATEW/ MECH. & ELEC.
NEW FIRE RISER STANDPIPEIN STAIR WELL, SEEFIRE PROTECTION WRITE-UPSECURE TO STAIR PAINTPIPE AND SUPPORTS
NEW FIRE RISER STANDPIPE IN STAIR WELL, SEEFIRE PROTECTION WRITE-UP SECURE TO STAIR PAINTPIPE AND SUPPORTS
VESTP101
MECHP102
LOBBYP103
CONFP104
WORK ROOMP105RECEPT
P106
VAULTP107
CORRP108
OFFICEP109
MECHP110
OFFICEP111
T.P112
CORRP113
JANP114
OFFICEP115
OFFICEP116
OFFICEP117
1A2.1
Sim
1A2.1
Sim
1A2.1
Sim
1A2.1
Sim
1A2.1
Sim
NEW ENTRY SIGNAGEAND OVERHEAD"CRASH" BAR SEEDETAIL 3/A2.1
A2.1 2
NEW FRAMING AND GYP.BOARD INFILL AT LOCATIONOF REMOVED FIRE HOSECABINET PAINT AND FINISHTO MATCH EXISTING WALL
EXISTING 2HR
EXISTING 2HR
8' - 0" 8' - 0" 8' - 0" 7' - 0"
9' - 6
"4'
- 2"
6" BUMP POST TYPICALOF (5) SEE DETAIL 4/A2.1
EXISTING 2HR EXISTING 2HR
PATCH REPAIR EXISTINGWALL FOR NEW PANELS THISLOCATION COORDINATE W/ELEC. AND FIRE PROTECTION
1' - 4"
1' - 0
"
4 1/2"
8"ONE PIECE 24 GA. ALUM.BENT METAL CAP W/KYNAR PAINT FINISH
CONT. 2x TREATEDBLOCKING
CONT. KEEPER BOTHSIDES TYP.
45 MIL EPDM MEMBRANE
11
4
6
7
9
1
13
A B C D F G H K L
14
15
16
M
12
3A2.1 2
EXISTING CONC. ANDEQUIPMENT PAD THISAREA TO BE REMOVED
DEMO EXISTING ENTRY SIGNAGETHIS AREA. CLEAN BRICK ANDPREP FOR NEW SIGNAGE
REMOVE FIREHOSE CABINETTHIS LOCATION
PLAZA651' - 6"
Mezzanine660' - 10"
4 61 3
ENTER 7'-0" CLR. NO ENTRY
11' - 11"
1' - 0
"
3' - 11" 3' - 11"3' - 11" 3' - 11"
1' - 0
"
11' - 11"
7' - 0
"
3A2.1
Sim1
A2.1
Sim A2.15
Sim
1 1/2"
1 1/2"
4"
7"1'
- 3"
9"
1' - 0
"2"
8"
EXISTING WALL
(3) 6" x 1/2" DIA. ANCHORBOLTS USE HILTI HY120
1/4" PLATE
2"x3" TUBE
PAINTED FIBERGLASSHEIGHT RESTRICTIONSIGNAGE SEE SPEC.
1/4" PLATE
CONNECTION BYSIGNAGEMANUFACTURE
NOTE:SIGNAGE SUPPORT BRACKET PAINTING INFORMATION:
A. FIRST COAT: KEM KROMIK UNIVERSAL METAL PRIMER, B50Z SERIESB. FINISH COAT: (2) COATS INDUSTRIAL ENAMEL, B54 SERIES, B54Z-100, B54Z-400 SERIES
(PAINT COLOR TO BE BLACK)
3"
FULL END CAP
2"x3" TUBE
7 1/2"
7 1/2"
1' - 3
"
5"
1 1/2" 1 1/2"
1 1/2"
4' - 0
"3'
- 0"
9" 6" 9"
2' - 0"
ROUND TOP WITH CONCRETEPAINT AS SPECIFIED (2)COAT MINIMUM
6" DIA. SCH. 40 STEEL PIPEFILL WITH CONCRETE SEEPLANS FOR LOCATIONSLOCATE POST 12" FROM WALL
SEAL JOINT AROUND POST
2'-0" x 3'-6" DEEP CONCRETEFOUNDATION FOR POST
CONCRETE PAVINGENTER 7'-0" CLR.
NO ENTRY
11' - 11"
1' - 0
"
11' - 11"
1' - 0
"
2"5"
1"
1"7" LETTERING(SCOTCHCALWHITE VINYL)
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A2.1
5-2420
PHASE 2 - PLAZA FLOOR PLAN
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"PLAZA FLOOR
A2.1 1 1/2" = 1'-0"
1 WALL CAP DETAIL
NORTH
1/8" = 1'-0"PLAZA FLOOR - DEMO
A2.1 1/8" = 1'-0"
2 PLAZA LEVEL ENTRY SIGNAGE ELEVATION
A2.1 1 1/2" = 1'-0"
3 SIGNAGE SUPPORT BRACKETA2.1 1/2" = 1'-0"
4 BUMP POST DETAILA2.1 1/4" = 1'-0"
5 SIGNAGE LAYOUT
DN
DNUPDN
UP
DN
DNUPDN
UP
11
4
6
7
9
A B C D F G H K L
12
3
OFFICEM101
CORRM102
MECHM103
JANM104
LOBBYM105
OFFICEM106 OFFICE
M107
OPEN OFFICEM108
STORM109
OFFICEM110
OFFICEM111
OFFICEM112
WORK ROOMM113
ELECM114
MENSM115
LOUNGEM118
WOMENSM117
MECHM116
NEW FRAMING AND GYP.BOARD INFILL AT LOCATIONOF REMOVED FIRE HOSECABINET PAINT AND FINISHTO MATCH EXISTING WALL
EXISTING 2HR
EXISTING 2HR
NEW FIRE RISER STANDPIPEIN STAIR WELL, SEEFIRE PROTECTION WRITE-UPSECURE TO STAIR PAINTPIPE AND SUPPORTS
NEW FIRE RISER STANDPIPE IN STAIR WELL, SEEFIRE PROTECTION WRITE-UP SECURE TO STAIR PAINTPIPE AND SUPPORTS
NEW 5/8" TYPE'X' GYP. PAINTED
EXISTING 2HR EXISTING 2HR
NOTE:REFER TO CARPET REPLACEMENTSCHEDULE THIS SHEET FOR AREAS OFCARPET AND VINYL BASE INSTALLATION
11
4
6
7
9
A B C D F G H K L
12
3
REMOVE FIREHOSE CABINETTHIS LOCATION
REMOVE WOODPANELINGTHESE WALLSPREP FOR NEWGYP.
NOTE:REFER TO CARPET REPLACEMENTSCHEDULE THIS SHEET FOR AREAS OFCARPET AND VINYL BASE REMOVAL
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A2.1M
5-2420
PHASE 2 - MEZZANINE FLOORPLAN
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"MEZZANINE FLOORNORTH
1/8" = 1'-0"MEZZANINE FLOOR - DEMO
CARPET REPLACEMENT SCHEDULE MEZZANINELevel Name Number Area Floor Finish
MezzanineMezzanine OFFICE M101 418 SF EXISTING TO REMAINMezzanine CORR M102 84 SF EXISTING TO REMAINMezzanine MECH M103 115 SF EXISTING TO REMAINMezzanine JAN M104 37 SF EXISTING TO REMAINMezzanine LOBBY M105 133 SF CARPET 1 W/ 4" VINYL BASEMezzanine OFFICE M106 152 SF CARPET 1 W/ 4" VINYL BASEMezzanine OFFICE M107 106 SF CARPET 1 W/ 4" VINYL BASEMezzanine OPEN OFFICE M108 670 SF CARPET 1 W/ 4" VINYL BASEMezzanine STOR M109 36 SF CARPET 1 W/ 4" VINYL BASEMezzanine OFFICE M110 106 SF CARPET 1 W/ 4" VINYL BASEMezzanine OFFICE M111 104 SF CARPET 1 W/ 4" VINYL BASEMezzanine OFFICE M112 152 SF CARPET 1 W/ 4" VINYL BASEMezzanine WORK ROOM M113 290 SF EXISTING TO REMAINMezzanine ELEC M114 36 SF EXISTING TO REMAINMezzanine MENS M115 123 SF EXISTING TO REMAINMezzanine MECH M116 47 SF EXISTING TO REMAINMezzanine WOMENS M117 192 SF EXISTING TO REMAINMezzanine LOUNGE M118 196 SF EXISTING TO REMAIN
NOTE:REMOVE EXISTING CARPET AND VINYL BASE PREP FOR NEWCARPET AND BASE INSTALLATION EXCEPT WHERE NOTED ONDEMOLITION PLAN
DNUPDN
UPDN
UPDNUP
11
4
6
7
9
1
A B C D F G H K L
12
3
RATED FRAME NEW 90MIN. DOOR REQUIREDTHIS LOCATION
CORR.201
MENS202
OFFICE203
OFFICE204
OFFICE205
OFFICE206
OFFICE207
OFFICE208
CORR209
MECH210
OFFICE211
OFFICE212
LOBBY213
ENTRY214
WORK RM215
CONF216
OFFICE217
LIBRARY218
MECH219
WOMENS220
ELEC221
JAN222
CORR223
CONF224
CORR225
OFFICE226
OFFICE227
OFFICE228
OFFICE229
OFFICE230
OFFICE231
CORR200
NEW FRAMING AND GYP.BOARD INFILL AT LOCATIONOF REMOVED FIRE HOSECABINET PAINT AND FINISHTO MATCH EXISTING WALL
EXISTING 2HR
EXISTING 2HR201A
NEW FIRE RISER STANDPIPEIN STAIR WELL, SEEFIRE PROTECTION WRITE-UPSECURE TO STAIR PAINTPIPE AND SUPPORTS
NEW FIRE RISER STANDPIPE IN STAIR WELL, SEEFIRE PROTECTION WRITE-UP SECURE TO STAIR PAINTPIPE AND SUPPORTS
EXISTING 2HR EXISTING 2HR
SAND REFINISH WOODFLOOR THIS ROOM
NOTE:REFER TO CARPET REPLACEMENTSCHEDULE THIS SHEET FOR AREAS OFCARPET AND VINYL BASE INSTALLATION
213A
NEW DOORSREWORKEDFRAME
11
4
6
7
9
1
A B C D F G H K L
12
3
WOOD FLOORINGTHIS AREA TO BE REFINISHEDSEE FLOOR PLAN REMOVE FIRE
HOSE CABINETTHIS LOCATION
NOTE:REFER TO CARPET REPLACEMENTSCHEDULE THIS SHEET FOR AREAS OFCARPET AND VINYL BASE REMOVAL
REMOVE DOORSREWORK WOODFRAME FORALTERNATESWING
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A2.2
5-2420
PHASE 2 - SECOND FLOORPLAN
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"SECOND FLOORNORTH
1/8" = 1'-0"SECOND FLOOR - DEMO
CARPET REPLACEMENT SCHEDULE 2ND FLOORLevel Name Number Area Floor Finish
2F2F CORR 200 86 SF EXISTING TO REMAIN2F CORR. 201 299 SF EXISTING TO REMAIN2F MENS 202 146 SF EXISTING TO REMAIN2F OFFICE 203 144 SF CARPET 1 W/ 4" VINYL BASE2F OFFICE 204 148 SF CARPET 1 W/ 4" VINYL BASE2F OFFICE 205 148 SF CARPET 1 W/ 4" VINYL BASE2F OFFICE 206 148 SF CARPET 1 W/ 4" VINYL BASE2F OFFICE 207 148 SF CARPET 1 W/ 4" VINYL BASE2F OFFICE 208 188 SF CARPET 1 W/ 4" VINYL BASE2F CORR 209 187 SF CARPET 1 W/ 4" VINYL BASE2F MECH 210 100 SF EXISTING TO REMAIN2F OFFICE 211 99 SF CARPET 1 W/ 4" VINYL BASE2F OFFICE 212 82 SF CARPET 1 W/ 4" VINYL BASE2F LOBBY 213 133 SF EXISTING TO REMAIN2F ENTRY 214 289 SF SAND AND REFINISH WOOD FLOOR2F WORK RM 215 277 SF CARPET 1 W/ 4" VINYL BASE2F CONF 216 188 SF CARPET 1 W/ 4" VINYL BASE2F OFFICE 217 249 SF CARPET 1 W/ 4" VINYL BASE2F LIBRARY 218 120 SF CARPET 1 W/ 4" VINYL BASE2F MECH 219 59 SF EXISTING TO REMAIN2F WOMENS 220 138 SF EXISTING TO REMAIN2F ELEC 221 37 SF EXISTING TO REMAIN2F JAN 222 55 SF EXISTING TO REMAIN2F CORR 223 238 SF CARPET 1 W/ 4" VINYL BASE2F CONF 224 170 SF CARPET 1 W/ 4" VINYL BASE2F CORR 225 240 SF CARPET 1 W/ 4" VINYL BASE2F OFFICE 226 213 SF CARPET 1 W/ 4" VINYL BASE2F OFFICE 227 175 SF CARPET 1 W/ 4" VINYL BASE2F OFFICE 228 115 SF CARPET 1 W/ 4" VINYL BASE2F OFFICE 229 115 SF CARPET 1 W/ 4" VINYL BASE2F OFFICE 230 174 SF CARPET 1 W/ 4" VINYL BASE2F OFFICE 231 232 SF CARPET 1 W/ 4" VINYL BASE
NOTE:REMOVE EXISTING CARPET AND VINYL BASE PREP FOR NEWCARPET AND BASE INSTALLATION EXCEPT WHERE NOTED ONDEMOLITION PLAN
DNUPDNUP
DNUPDNUP
11
4
6
7
9
A B C D F G H K L M
12
3
OFFICE301
OFFICE302
OFFICE303
OFFICE304
OFFICE305
OFFICE306
OFFICE307
OFFICE308
CORR309
MENS310
MECH311
CONF312
STOR313
OFFICE314
MECH315
WOMENS316
ELEC317
JAN.318
LOBBY319
CORR320
STOR321
FILES322
CORR323
STOR324
CONF325
OFFICE326
OFFICE327
CONF328
OFFICE329
OFFICE330
OFFICE331
OFFICE332
OFFICE333
NEW FRAMING AND GYP.BOARD INFILL AT LOCATIONOF REMOVED FIRE HOSECABINET PAINT AND FINISHTO MATCH EXISTING WALL
EXISTING 2HR
EXISTING 2HR
NEW FIRE RISER STANDPIPEIN STAIR WELL, SEEFIRE PROTECTION WRITE-UPSECURE TO STAIR PAINTPIPE AND SUPPORTS
NEW FIRE RISER STANDPIPE IN STAIR WELL, SEEFIRE PROTECTION WRITE-UP SECURE TO STAIR PAINTPIPE AND SUPPORTS
EXISTING 2HR EXISTING 2HR
NOTE:REFER TO CARPET REPLACEMENTSCHEDULE THIS SHEET FOR AREAS OFCARPET AND VINYL BASE INSTALLATION
11
4
6
7
9
A B C D F G H K L M
12
3
REMOVE FIREHOSE CABINETTHIS LOCATION
NOTE:REFER TO CARPET REPLACEMENTSCHEDULE THIS SHEET FOR AREAS OFCARPET AND VINYL BASE REMOVAL
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A2.3
5-2420
PHASE 2 - THIRD FLOOR PLAN
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"THIRD FLOORNORTH
1/8" = 1'-0"THIRD FLOOR - DEMO
CARPET REPLACEMENT SCHEDULE 3RD FLOORLevel Name Number Area Floor Finish
3F3F OFFICE 301 203 SF EXISTING TO REMAIN3F OFFICE 302 135 SF EXISTING TO REMAIN3F OFFICE 303 146 SF EXISTING TO REMAIN3F OFFICE 304 146 SF EXISTING TO REMAIN3F OFFICE 305 146 SF EXISTING TO REMAIN3F OFFICE 306 146 SF EXISTING TO REMAIN3F OFFICE 307 152 SF EXISTING TO REMAIN3F OFFICE 308 188 SF EXISTING TO REMAIN3F CORR 309 381 SF EXISTING TO REMAIN3F MENS 310 166 SF EXISTING TO REMAIN3F MECH 311 102 SF EXISTING TO REMAIN3F CONF 312 163 SF EXISTING TO REMAIN3F STOR 313 96 SF CARPET 1 W/ 4" VINYL BASE3F OFFICE 314 254 SF CARPET 1 W/ 4" VINYL BASE3F MECH 315 60 SF EXISTING TO REMAIN3F WOMENS 316 138 SF EXISTING TO REMAIN3F ELEC 317 37 SF EXISTING TO REMAIN3F JAN. 318 54 SF EXISTING TO REMAIN3F LOBBY 319 315 SF EXISTING TO REMAIN3F CORR 320 89 SF EXISTING TO REMAIN3F STOR 321 40 SF EXISTING TO REMAIN3F FILES 322 100 SF EXISTING TO REMAIN3F CORR 323 283 SF EXISTING TO REMAIN3F STOR 324 21 SF EXISTING TO REMAIN3F CONF 325 136 SF EXISTING TO REMAIN3F OFFICE 326 261 SF EXISTING TO REMAIN3F OFFICE 327 213 SF EXISTING TO REMAIN3F CONF 328 390 SF EXISTING TO REMAIN3F OFFICE 329 150 SF EXISTING TO REMAIN3F OFFICE 330 150 SF EXISTING TO REMAIN3F OFFICE 331 150 SF EXISTING TO REMAIN3F OFFICE 332 226 SF EXISTING TO REMAIN3F OFFICE 333 298 SF EXISTING TO REMAIN
NOTE:REMOVE EXISTING CARPET AND VINYL BASE PREP FOR NEWCARPET AND BASE INSTALLATION EXCEPT WHERE NOTED ONDEMOLITION PLAN
DNUP
DNUP
DNUP
DNUP
11
4
6
7
9
A B C D F G H K L
12
3
OFFICE401
OFFICE402
OFFICE403
OFFICE404
OFFICE405 OFFICE
406
MENS407
MECH408
CORR409
OFFICE410
OFFICE411
STOR412
ELEC413B
WOMENS414
LOBBY415
ENTRY416
KITCHETTE417
CORR418
JAN419
OFFICE420
WORK RM421
CONF422
CORR423
CONF424
OFFICE425
OFFICE426
OFFICE427
OFFICE428
OFFICE429
TOILET430
NEW FRAMING AND GYP.BOARD INFILL AT LOCATIONOF REMOVED FIRE HOSECABINET PAINT AND FINISHTO MATCH EXISTING WALL
EXISTING 2HR
EXISTING 2HR
NEW FIRE RISER STANDPIPEIN STAIR WELL, SEEFIRE PROTECTION WRITE-UPSECURE TO STAIR PAINTPIPE AND SUPPORTS
NEW FIRE RISER STANDPIPE IN STAIR WELL, SEEFIRE PROTECTION WRITE-UP SECURE TO STAIR PAINTPIPE AND SUPPORTS
MECH413A
EXISTING 2HR EXISTING 2HR
NOTE:REFER TO CARPET REPLACEMENTSCHEDULE THIS SHEET FOR AREAS OFCARPET AND VINYL BASE INSTALLATION
11
4
6
7
9
A B C D F G H K L
12
3
REMOVE FIREHOSE CABINETTHIS LOCATION
NOTE:REFER TO CARPET REPLACEMENTSCHEDULE THIS SHEET FOR AREAS OFCARPET AND VINYL BASE REMOVAL
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A2.4
5-2420
PHASE 2 - FOURTH FLOORPLAN
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"FOURTH FLOORNORTH
1/8" = 1'-0"FOURTH FLOOR - DEMO
CARPET REPLACEMENT SCHEDULE 4TH FLOORLevel Name Number Area Floor Finish
4F4F OFFICE 401 302 SF CARPET 1 W/ 4" VINYL BASE4F OFFICE 402 227 SF CARPET 1 W/ 4" VINYL BASE4F OFFICE 403 146 SF EXISTING TO REMAIN4F OFFICE 404 146 SF CARPET 1 W/ 4" VINYL BASE4F OFFICE 405 221 SF CARPET 1 W/ 4" VINYL BASE4F OFFICE 406 316 SF CARPET 1 W/ 4" VINYL BASE4F MENS 407 165 SF EXISTING TO REMAIN4F MECH 408 102 SF EXISTING TO REMAIN4F CORR 409 247 SF EXISTING TO REMAIN4F OFFICE 410 140 SF CARPET 1 W/ 4" VINYL BASE4F OFFICE 411 216 SF EXISTING TO REMAIN4F STOR 412 61 SF CARPET 1 W/ 4" VINYL BASE4F MECH 413A 60 SF EXISTING TO REMAIN4F ELEC 413B 38 SF EXISTING TO REMAIN4F WOMENS 414 138 SF EXISTING TO REMAIN4F LOBBY 415 150 SF EXISTING TO REMAIN4F ENTRY 416 371 SF EXISTING TO REMAIN4F KITCHETTE 417 215 SF EXISTING TO REMAIN4F CORR 418 324 SF EXISTING TO REMAIN4F JAN 419 54 SF EXISTING TO REMAIN4F OFFICE 420 80 SF EXISTING TO REMAIN4F WORK RM 421 108 SF EXISTING TO REMAIN4F CONF 422 171 SF CARPET 1 W/ 4" VINYL BASE4F CORR 423 204 SF EXISTING TO REMAIN4F CONF 424 394 SF EXISTING TO REMAIN4F OFFICE 425 148 SF CARPET 1 W/ 4" VINYL BASE4F OFFICE 426 147 SF CARPET 1 W/ 4" VINYL BASE4F OFFICE 427 147 SF CARPET 1 W/ 4" VINYL BASE4F OFFICE 428 147 SF CARPET 1 W/ 4" VINYL BASE4F OFFICE 429 344 SF CARPET 1 W/ 4" VINYL BASE4F TOILET 430 39 SF EXISTING TO REMAIN
NOTE:REMOVE EXISTING CARPET AND VINYL BASE PREP FOR NEWCARPET AND BASE INSTALLATION EXCEPT WHERE NOTED ONDEMOLITION PLAN
DNUPDN UPDNUPDN UP
11
4
6
7
9
A B C D F G H K L
12
3
OFFICE501
OFFICE502
OFFICE503
OFFICE504
OFFICE505
OFFICE506
STOR507
BREAK509OFFICE
510 CORR511
MENS512
MECH513
FILES514
CONF515
OPEN OFFICE516
MECH517
ELEC518
WOMENS519
JAN520
CORR521
OFFICE522
CONF523
OPEN OFFICE524
OPEN OFFICE525
OFFICE526
OFFICE527
OFFICE528
OFFICE529
OFFICE530
STOR508
NEW FRAMING AND GYP.BOARD INFILL AT LOCATIONOF REMOVED FIRE HOSECABINET PAINT AND FINISHTO MATCH EXISTING WALL
EXISTING 2HR
EXISTING 2HR
REPLACE SPANDREL GLASSPANEL BETWEEN 5TH AND SIXTHFLOOR THIS LOCATION
REPLACE SPANDREL GLASSPANEL BETWEEN 5TH AND SIXTHFLOOR THIS LOCATION
NEW FIRE RISER STANDPIPEIN STAIR WELL, SEEFIRE PROTECTION WRITE-UPSECURE TO STAIR PAINTPIPE AND SUPPORTS
NEW FIRE RISER STANDPIPE IN STAIR WELL, SEEFIRE PROTECTION WRITE-UP SECURE TO STAIR PAINTPIPE AND SUPPORTS
NEW 5/8" TYPE'X' GYP. PAINTED
EXISTING 2HR EXISTING 2HR
NOTE:REFER TO CARPET REPLACEMENTSCHEDULE THIS SHEET FOR AREAS OFCARPET AND VINYL BASE INSTALLATION
11
4
6
7
9
A B C D F G H K L
12
3
REMOVE FIREHOSE CABINETTHIS LOCATIONREMOVE WOOD
PANELINGTHESE WALLSPREP FOR NEWGYP.
NOTE:REFER TO CARPET REPLACEMENTSCHEDULE THIS SHEET FOR AREAS OFCARPET AND VINYL BASE REMOVAL
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A2.5
5-2420
PHASE 2 - FIFTH FLOOR PLAN
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"FIFTH FLOORNORTH
1/8" = 1'-0"FIFTH FLOOR - DEMO
CARPET REPLACEMENT SCHEDULE 5TH FLOORLevel Name Number Area Floor Finish
5F5F OFFICE 501 226 SF CARPET 1 W/ 4" VINYL BASE5F OFFICE 502 181 SF CARPET 1 W/ 4" VINYL BASE5F OFFICE 503 181 SF CARPET 1 W/ 4" VINYL BASE5F OFFICE 504 181 SF CARPET 1 W/ 4" VINYL BASE5F OFFICE 505 181 SF EXISTING TO REMAIN5F OFFICE 506 141 SF CARPET 1 W/ 4" VINYL BASE5F STOR 507 97 SF CARPET 1 W/ 4" VINYL BASE5F STOR 508 34 SF EXISTING TO REMAIN5F BREAK 509 69 SF CARPET 1 W/ 4" VINYL BASE5F OFFICE 510 116 SF CARPET 1 W/ 4" VINYL BASE5F CORR 511 365 SF CARPET 1 W/ 4" VINYL BASE5F MENS 512 169 SF EXISTING TO REMAIN5F MECH 513 102 SF EXISTING TO REMAIN5F FILES 514 170 SF CARPET 1 W/ 4" VINYL BASE5F CONF 515 190 SF CARPET 1 W/ 4" VINYL BASE5F OPEN OFFICE 516 381 SF CARPET 1 W/ 4" VINYL BASE5F MECH 517 57 SF EXISTING TO REMAIN5F ELEC 518 40 SF EXISTING TO REMAIN5F WOMENS 519 144 SF EXISTING TO REMAIN5F JAN 520 60 SF EXISTING TO REMAIN5F CORR 521 397 SF CARPET 1 W/ 4" VINYL BASE5F OFFICE 522 85 SF CARPET 1 W/ 4" VINYL BASE5F CONF 523 266 SF CARPET 1 W/ 4" VINYL BASE5F OPEN OFFICE 524 651 SF CARPET 1 W/ 4" VINYL BASE5F OPEN OFFICE 525 495 SF CARPET 1 W/ 4" VINYL BASE5F OFFICE 526 220 SF CARPET 1 W/ 4" VINYL BASE5F OFFICE 527 175 SF CARPET 1 W/ 4" VINYL BASE5F OFFICE 528 102 SF EXISTING TO REMAIN5F OFFICE 529 159 SF CARPET 1 W/ 4" VINYL BASE5F OFFICE 530 176 SF CARPET 1 W/ 4" VINYL BASE
NOTE:REMOVE EXISTING CARPET AND VINYL BASE PREP FOR NEWCARPET AND BASE INSTALLATION EXCEPT WHERE NOTED ONDEMOLITION PLAN
DNUPDNUP
DNUPDNUP
11
4
6
7
9
A B C D F G H K L
12
3
6A2.7
OFFICE600
OFFICE602
OFFICE603
OFFICE604
OFFICE605
OFFICE606 OFFICE
607A
MENS608
MECH609
CORR610
OFFICE611
OFFICE612
OFFICE613
ELEC614B
WOMENS615
LOBBY616
OFFICE617B
CORR618
OFFICE620
OFFICE621
OFFICE622
OFFICE623
CORR624
WORK ROOM625
OFFICE626
OFFICE627
OFFICE628
OFFICE629
OFFICE630
CONF.631
OFFICE601
OFFICE607B
CLOSET619
OFFICE617A NEW FRAMING AND GYP.
BOARD INFILL AT LOCATIONOF REMOVED FIRE HOSECABINET PAINT AND FINISHTO MATCH EXISTING WALL
EXISTING 2HR
EXISTING 2HR
NEW FIRE RISER STANDPIPEIN STAIR WELL, SEEFIRE PROTECTION WRITE-UPSECURE TO STAIR PAINTPIPE AND SUPPORTS
NEW FIRE RISER STANDPIPE IN STAIR WELL, SEEFIRE PROTECTION WRITE-UP SECURE TO STAIR PAINTPIPE AND SUPPORTS
MECH614A
EXISTING 2HR EXISTING 2HR
NOTE:REFER TO CARPET REPLACEMENTSCHEDULE THIS SHEET FOR AREAS OFCARPET AND VINYL BASE INSTALLATION
11
4
6
7
9
A B C D F G H K L
12
3
REMOVE FIREHOSE CABINETTHIS LOCATION
NOTE:REFER TO CARPET REPLACEMENTSCHEDULE THIS SHEET FOR AREAS OFCARPET AND VINYL BASE REMOVAL
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A2.6
5-2420
PHASE 2 - SIXTH FLOOR PLAN
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"SIXTH FLOORNORTH
1/8" = 1'-0"SIXTH FLOOR - DEMO
CARPET REPLACEMENT SCHEDULE 6TH FLOORLevel Name Number Area Floor Finish
6F6F OFFICE 600 201 SF CARPET 1 W/ 4" VINYL BASE6F OFFICE 601 132 SF CARPET 1 W/ 4" VINYL BASE6F OFFICE 602 167 SF CARPET 1 W/ 4" VINYL BASE6F OFFICE 603 167 SF CARPET 1 W/ 4" VINYL BASE6F OFFICE 604 167 SF CARPET 1 W/ 4" VINYL BASE6F OFFICE 605 167 SF CARPET 1 W/ 4" VINYL BASE6F OFFICE 606 167 SF CARPET 1 W/ 4" VINYL BASE6F OFFICE 607A 201 SF CARPET 1 W/ 4" VINYL BASE6F OFFICE 607B 131 SF CARPET 1 W/ 4" VINYL BASE6F MENS 608 208 SF EXISTING TO REMAIN6F MECH 609 49 SF EXISTING TO REMAIN6F CORR 610 375 SF EXISTING TO REMAIN6F OFFICE 611 131 SF EXISTING TO REMAIN6F OFFICE 612 126 SF EXISTING TO REMAIN6F OFFICE 613 134 SF EXISTING TO REMAIN6F MECH 614A 62 SF EXISTING TO REMAIN6F ELEC 614B 39 SF EXISTING TO REMAIN6F WOMENS 615 194 SF EXISTING TO REMAIN6F LOBBY 616 262 SF EXISTING TO REMAIN6F OFFICE 617A 134 SF CARPET 1 W/ 4" VINYL BASE6F OFFICE 617B 201 SF EXISTING TO REMAIN6F CORR 618 272 SF EXISTING TO REMAIN6F CLOSET 619 37 SF EXISTING TO REMAIN6F OFFICE 620 129 SF EXISTING TO REMAIN6F OFFICE 621 125 SF EXISTING TO REMAIN6F OFFICE 622 132 SF EXISTING TO REMAIN6F OFFICE 623 92 SF EXISTING TO REMAIN6F CORR 624 322 SF EXISTING TO REMAIN6F WORK ROOM 625 290 SF EXISTING TO REMAIN6F OFFICE 626 142 SF EXISTING TO REMAIN6F OFFICE 627 142 SF EXISTING TO REMAIN6F OFFICE 628 142 SF EXISTING TO REMAIN6F OFFICE 629 142 SF EXISTING TO REMAIN6F OFFICE 630 142 SF EXISTING TO REMAIN6F CONF. 631 294 SF EXISTING TO REMAIN
NOTE:REMOVE EXISTING CARPET AND VINYL BASE PREP FOR NEWCARPET AND BASE INSTALLATION EXCEPT WHERE NOTED ONDEMOLITION PLAN
DNDN
UP
DNDN
11
4
6
7
9
A B C D F G H K L
12
NEW FIRE RISER STAND PIPEIN STAIR WELL, SEE FIREPROTECTION WRITE-UPSECURE TO STAIR
NEW LOUVER THIS LOCATIONCOORDINATE W/ MECH
3
NEW FIRE RISER STAND PIPEIN STAIR WELL, SEE FIREPROTECTION WRITE-UPSECURE TO STAIR
6A2.7
MECH701
PENTHOUSE702
EQUIPMENT703
12' -
10"
34' - 4"
16' - 6" 15' - 4"
15' -
6"
NEW 4" MECHANICALMAINT. PADS
COORD. EXISTING PADSW/ NEW PADS
NEW 2HR. GYP. BOARDWALL SYSTEM. TIGHTTO DECK (2) LAYERS5/8" GYP. ON EACHSIDE OF 3 5/8" MTL.STUD AT 16" O.C.
ELEV. RM704
ELEV. RM705
705A
EXISTING 2HR
EXISTING 2HR
704A
2HR
2A5.1
Sim
4A2.7
7' - 6
"
11' - 0" 11' - 0" 11' - 0"
7' - 8
"
EDGE OF 4" CONC.ISOLATION PAD
40' - 4 7/32" 7' - 0"
15' -
6"4'
- 0 9/
16"
702A
8' - 11"
10' -
0"4'
- 9 1/
2"
16' - 4"
ALIGN WALL TOSIDE OF SHAFT
RUN WALL TIGHT TOEDGE OF SHAFT
COORDINATE WALL INFILLAND LOUVER THIS LOCATION
W10X15
W10
X15
W10
X15
W10X15 W10X15
W10
X15
W10X15
W10
X15
HSS6X6X
5/16
HSS6X6X
5/16
HSS6X6X
5/16
HSS6X6X
5/16
HSS6X6X
5/16
HSS6X6X
5/16
HSS6X6X
5/16
HSS6X6X
5/16
3A2.7
Sim 3A2.7
Sim
2A2.7
Sim2
A2.7
Sim
COORDINATE FLOOR CUTTING &PATCHING FOR NEW MECH/PLUMBING/CONDUITS
COORDINATE LOUVERINFILL THIS WALL WITHMECHANICAL
NEW DUCT PENETRATION INWALL AND ROOF THISLOCATION COORDINATEWITH MECH
10A2.7
Sim
ACOUSTIC BARRIERWALL SEE SPEC.
ACOUSTIC BARRIERWALL SEE SPEC.
11
4
6
7
9
A B C D F G H K L
12
3
DEMO EXISTINGFENCING AROUNDELEV. EQUIP. TYP.
NEW DOOR LOCATIONCOORDINATE RELOCATIONOF EXISTING DOOR PREPFOR REUSE
PLAN VIEW
SECTION
1 1/2"
1 1/2"
1 1/2"1 1/2"
5"4"
BASE PL 3/4"X8"X1'-0"
EXISTING W10 BEAM
1/2"1/2"
BASE PL 3/4"X8"X1'-0"
6"x6"x5/16" HSSREMOVE SLAB ANDDECK AS NESSECARYTO INSTALL COLUMNREPAIR CONCRETEAFTER COLUMN ISINSTALLED
6"x6"x5/16" HSS
0' - 6"
1' -
0"
2' - 0"
W10X15 BEAMGALVANIZED
L4X4X1/4" BRACEGALVANIZED
A2.71
Sim
L6X6X5/16GALVANIZED
6"x6"x5/16" HSSCOLUMN GALVANIZED
1' -
0"
2' - 0"
W10X15 BEAMGALVANIZED
L4X4X1/4" BRACEGALVANIZED
A2.71
Sim
W10X12 BEAMGALVANIZED
L6X6X5/16GALVANIZED
3/4" CAP PL
6F718' - 2"
Penthouse729' - 6"
4 63
3' - 0
"2'
- 4"
9' - 0
"
6' - 4" 7' - 6" 7' - 8"
4" ISOLATION PAD SEEDETAILS THIS SHEET
A2.77
Sim 4' - 4 1/2"
ACOUSTIC BARRIERWALL SEE SPEC.
Penthouse729' - 6"
6
(2) 3/4" DIA. SOLIDBARS CONT.LENGHT OF BEAM
4-12
1/2"x10" PLATE CONT.LENGTH OF BEAM
4
6
D F G H K L M
3W12X16 W12X16 W12X16 W12X16 W12X16 W12X16
W16
X26
W16
X40
W21X62 W21X62 W24X76
W10
X30
W10
X30
W10
X30
W10
X30
W10
X30
W10
X30
W10
X45
W10
X30
W10
X30
W10
X30
W10
X22
W10
X22
W10
X22
W10
X22
W10
X22
W10
X22
W10
X22
W10
X22
W10
X39
W10
X22
W10
X22
W8X10
W8X
10
W10X17
W8X
10
W10X17
W8X10 W8X10
W8X
10
W8X10
C8X11.5
C6X8.2C5X
6.7
C5X
6.7
C5X
6.7
C5X
6.7
C5X6.7
C5X6.7
EXIST.
TO BEREINFORCED
EXIST.
TO BEREINFORCED
EXIST.
TO BEREINFORCED
EXIST.
TO BEREINFORCED
EXIST.
TO BEREINFORCED
EXIS
T.
TO B
ERE
INFO
RCED
EXIS
T.
TO B
ERE
INFO
RCED
EXIS
T.
TO B
ERE
INFO
RCED
EXIS
T.
TO B
ERE
INFO
RCED
EXIS
T.
TO B
ERE
INFO
RCED
EXIS
T.
TO B
ERE
INFO
RCED
EXIS
T.
TO B
ERE
INFO
RCED
EXIS
T.
TO B
ERE
INFO
RCED
4A2.7
Sim
4A2.7
Sim
4"
8"
EXISTING ROOF INSULATIONPOURED DECK AND STRUCTURE
NEW 4" CONC. ISOLATION PADPOURED ON SCARED CONCSURFACE
6"x6" HSS FRAME SUPPORT COLUMNSEE STRUCTURAL DETAILS
PRE-MOLDED FLASHING COLLAR
ROOF LAPSEALANT
RUN MEMBRANE OVERWOOD BLOCKING
PROVIDE (2) 12" SCUPPERSALONG LOW SIDE OF PAD
SEE PLAN
5" INSULATIONW/ TAPERSLOPE TOSCUPPER
RELOCATEEXISTING BALLASTFROM THIS AREABACK ONTO NEWROOF AREA
1' - 0
"
TAPER INSULATIONTO SCUPPER
PROVIDE (2) 12"SCUPPERS ALONGLOW SIDE OF PAD
SECTION PLAN
3/4" CHAMFER -ALL EDGES (TYP.)
EXISTING CONCRETESLAB
DRILL & EPOXY SET #4 DOWELAT ALL CORNERS OF NEW PAD -EMBED 2.1/2" INTO BOTH EXISTINGSLAB & NEW PAD
SCARIFY EXISTING SLABSURFACE UNDER NEW PAD& COAT WITH BONDING AGENT
CONCRETE PAD WITH6x6-W1.4xW1.4 WWM(FLAT SHEETS)
MIN.4"
4"
NOTE: INSTALL REINFORCEMENTANGLES PRIOR TO CUTTING HOLE
CUT NEW 20" x 9" OPENINGTHRU WEB OF EXISTING BEAMAND REINFORCE BOTH FACESOF WEB WITH L3x3x3/8" ANGLESALONG ALL 4 SIDES OF OPENING
NEW DUCT OPENING
5/16 6" L.
TYPICAL ATENDS TOP& BOTTOM
RADIUS INSIDECORNER CUTS
EXISTING W21 BEAM
5/16 3"@9"
TYPICAL ATREMAINDERBOTH SIDES
EQ.
9"EQ
.
8" 10" 10" 8"
3'-2" TO COLUMN LINE
NOTE:SEE MECHANICAL PLANSFOR LOCATIONS OF BEAMPENETRATIONS
GENERAL STRUCTURAL NOTES:1.
2.
FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TOFABRICATION AND INSTALLATION, AND WITH THE ARCHITECT'S APPROVALMAKE ANY AND ALL NECESSARY MODIFICATIONS TO INSURE A PROPER FIT.
3. THE EXISTING STRUCTURAL PLANS ARE DIAGRAMATIC AND ARE BASED ONEXISTING OWNER DOCUMENTS AND LIMITED FIELD INVESTIGATION. VARYING &HIDDEN CONDITIONS MAY EXIST. IF DISCREPACIES ARE FOUND, NOTIFY THEARCHITECT & ENGINEER FOR DIRECTION/RESOLUTION BEFORE CONTINUINGWORK IN THOSE AREAS.
COORDINATE ALL WORK INCLUDING DEMOLITION WITH ALL OTHER TRADESAND WITH THE REQUIREMENTS FOUND IN THE CONSTRUCTION DOCUMENTS.
GENERAL STRUCTURAL NOTES
U8
U10
LINTEL SCHEDULE
MARK MATERIAL SHAPE
W8x10-107
BEAM SIZE PLATE WIDTH:07 = 7.1/2"09 = 9.1/2"11 = 11.1/2"13 = 13.1/2"15 = 15.1/2"17 = 17.1/2"
PLATE THICKNESS:1 = 1/4"3 = 3/8"
ALL BEARING PLATES SHALL BE "BP2A" FOR ALL LINTELS UNLESSNOTED OTHERWISE ON PLANS. (NOT SHOWN FOR CLARITY)
ALL STEEL LINTELS IN EXTERIOR WALLS SHALL BE GALVANIZED.
SEE DETAIL BELOW FOR ADDITIONAL REQUIREMENTS.
8" MASONRY U-BLOCK W/(2) #5 BARS AND CONCRETE FILL.
10" MASONRY U-BLOCK W/(2) #5 BARS AND CONCRETE FILL.
U6 6" MASONRY U-BLOCK W/(2) #5 BARS AND CONCRETE FILL.
U12 12" MASONRY U-BLOCK W/(3) #5 BARS AND CONCRETE FILL.
L3
L5
L3.1/2" x 3.1/2" x 1/4"
L5" x 3.1/2" x 1/4" LLV
3/16"
ELEVATION
SECTION
2" @ 12"o.c.
THREADED STUD WELDEDTO BEARING PLATE ANDOVERSIZED HOLE IN BEAMFLANGE FOR BOLTING DOWN(OPP. END FROM WELD)
STEEL LINTEL PLATEWITH SAME LENGTHAS OPENING WIDTHSTEEL LINTEL BEAM-FIELD WELD ONE ENDTO BEARING PLATE
STEEL BEARING PLATEAT EACH END
GROUT CORES FULL FORMIN. (3) COURSES BELOWBEARING-UNLESS NOTEDOTHERWISE
AT W16 OR LARGER-PROVIDE WELD ONVENEER ANCHORS &ADJUSTABLE TIES AT16"o.c. (BOTH FACES)
1/2" DIA. x 4" LONGHEADED STUDS AT32"o.c. (TYP.)
CENTER BEAM & BRG.PLATES ON STRUCT.WYTH OF MASONRY
CENTER LINTEL PLATEON TOTAL WALL WIDTH
3/16" 2" @ 12"o.c.
MASONRY OPENING
BEARING PLATE IF LONGER
MINIMUM 8" OR LENGTH OF
(6" AT END WALL)
EXISTING ROOF SYSTEM
EXTEND ROOF BASEFLASHING UP & OVERCURB.
PRE-FABRICATEDINSULATED ROOFCURB.
EQUIPMENT HOUSINGOR FLASHING - SEEMECHANICAL DWGS.
CRICKET BEYOND (TYP.)HIGH SIDE OF ROOF CURB
PROVIDE NEW FLASHINGALL SIDES NEW ROOF CURBSEAL TO EXISTING ROOFSYSTEM
2'-0"
MIN
.
7
9
F G H K L
EXISTING ROOFSTRUCT.
L5X3X1/4
L5X3X1/4
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A2.7
5-2420
PHASE 2 - PENTHOUSE
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"PENTHOUSENORTH
1/8" = 1'-0"PENTHOUSE - DEMO
A2.7 1 1/2" = 1'-0"
1 CHILLER FRAME COLUMN DETAIL
A2.7 3/4" = 1'-0"
2 CHILLER FRAME SECTION
A2.7 3/4" = 1'-0"
3 CHILLER FRAME SECTION 2A2.7 1/4" = 1'-0"
6 PARTIAL ENLARGED SECTION
A2.7 3/4" = 1'-0"
4 LONG BEAM REINFORCEMENT
A2.7 1/8" = 1'-0"
8 EXISTING STEEL REINFORCING PLAN
A2.7 1" = 1'-0"
7 CONC. ROOF PAD DETAIL
A2.7 1 1/2" = 1'-0"
5 EQUIPMENT PAD DETAIL
A2.7 1" = 1'-0"
9 BEAM PENETRATION DETAIL
A2.7 1 1/2" = 1'-0"
10 SLOPED ROOF CURB DETAIL
A2.7 1/8" = 1'-0"
11 EXISTING STEEL REINFORCING PLAN
S
S
S M
11
4
6
7
9
1
13
A B C D F G H K L
14
15
16
M
12
3
PHASE II CEILING NOTE:
LAY-IN CEILINGS SHOWN ARE PART OF PHASE I
SOME CEILING LAYOUTS AND HEIGHTS MAY HAVE CHANGED AS A PARTOF COORDINATION WITH MECHANICAL AND ELECTRICAL LAYOUTS
SEE PLANS FOR NEW GYP. BOARD BULKHEADS, LAYOUTS AND HEIGHTS
SEE PLANS FOR AREAS OF PATCH AND REPAIR OF EXISTING BULKHEADSAS A PART OF MECHANICAL, PLUMBING AND ELECTRICAL WORK
11
4
6
7
9
1
13
A B C D F G H K L
14
15
16
M
12
3
NEW PARKING AREACEILING SYSTEM
NEW PARKING AREACEILING SYSTEM
NEW PARKING AREACEILING SYSTEM
NEW PARKING AREACEILING SYSTEM
A.F.F.7' - 4"
A.F.F.7' - 4"
RE-LAY BATT INSULATION ON NEW CEILING.
RE-LAY BATT INSULATION ON NEW CEILING.
RE-LAY BATT INSULATION ON NEW CEILING. RE-LAY BATT INSULATION ON NEW CEILING. RE-LAY BATT INSULATION ON NEW CEILING.
RE-LAY BATT INSULATION ON NEW CEILING. RE-LAY BATT INSULATION ON NEW CEILING.RE-LAY BATT INSULATION ON NEW CEILING.
RE-LAY BATT INSUL.ON NEW CEILING.
RE-LAY BATT INSUL.ON NEW CEILING.
RE-LAY BATT INSUL.ON NEW CEILING.
RE-LAY BATT INSUL.ON NEW CEILING.
RE-LAY BATT INSUL.ON NEW CEILING.
1A2.0
2A2.0
A.F.F.10' - 0"
A.F.F.10' - 0"
A.F.F.10' - 0"
A.F.F.10' - 0"
A.F.F.10' - 0"
NEW 'GREEN BOARD'BULKHEAD WITHRELOCATED HEIGHTSIGNAGE. PAINTED
A.F.F.7' - 2"
A.F.F.7' - 4"
A.F.F.6' - 6"
A.F.F.10' - 0"
A.F.F.10' - 0"
A.F.F.10' - 0"
A.F.F.10' - 0"
A.F.F.10' - 0"
A.F.F.10' - 0"
NOTE:LAY-IN CEILING DEMOLITON PART OF PHASE I WORK.COORDINATE DEMOLITION OF BULKHEADS ASREQUIRED WITH MECH/ELEC/PLUMBING. PREP FORREPAIR AND REFINISHING TO MATCH ADJACENTSURFACES
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A3.0
5-2420
RAMP REFLECTED CEILINGPLAN NEW AND DEMOLITION
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"RAMP REFLECTED CEILING PLAN - DEMO NORTH
1/8" = 1'-0"RAMP REFLECTED CEILING PLAN - PHASE II
M
MM
M
11
4
6
7
9
A B C D F G H K L
12
3A2.1 2
PHASE II CEILING NOTE:
LAY-IN CEILINGS SHOWN ARE PART OF PHASE I
SOME CEILING LAYOUTS AND HEIGHTS MAY HAVE CHANGED AS A PARTOF COORDINATION WITH MECHANICAL AND ELECTRICAL LAYOUTS
SEE PLANS FOR NEW GYP. BOARD BULKHEADS, LAYOUTS AND HEIGHTS
SEE PLANS FOR AREAS OF PATCH AND REPAIR OF EXISTING BULKHEADSAS A PART OF MECHANICAL, PLUMBING AND ELECTRICAL WORK
11
4
6
7
9
1
A B C D F G H K L
12
3NEW PARKING AREACEILING SYSTEM
NEW PARKING AREACEILING SYSTEM
NEW PARKING AREACEILING SYSTEM
OPEN TO ABOVE OPEN TO ABOVE
OPEN TO ABOVE
OPEN TO ABOVE
OPEN TO ABOVE
OPEN TO ABOVE
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.8' - 0"
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.7' - 5"
A.F.F.7' - 4"
RE-LAY BATT INSULATION ON NEW CEILING.
RE-LAY BATT INSUL.ON NEW CEILING.
PATCH REPAIR SOFFITTHIS LOCATION
NOTE:LAY-IN CEILING DEMOLITON PART OF PHASE I WORK.COORDINATE DEMOLITION OF BULKHEADS ASREQUIRED WITH MECH/ELEC/PLUMBING. PREP FORREPAIR AND REFINISHING TO MATCH ADJACENTSURFACES
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A3.1
5-2420
PLAZA REFLECTED CEILINGPLAN NEW AND DEMOLITION
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"PLAZA REFLECTED CEILING PLAN - DEMO NORTH
1/8" = 1'-0"PLAZA REFLECTED CEILING PLAN - PHASE II
M
M
M
MM
M
M
M
M
M
M M M
MM
M
11
4
6
7
9
A B C D F G H K L
12
3
EXISTING GYP.BD.BULKHEADS TO REMAIN.
EXISTING GYP.BD.BULKHEADS TO REMAIN.
EXISTING GYP.BD.BULKHEADS TO REMAIN.
EXISTING GYP.BD.BULKHEADS TO REMAIN.
PHASE II CEILING NOTE:
LAY-IN CEILINGS SHOWN ARE PART OF PHASE I
SOME CEILING LAYOUTS AND HEIGHTS MAY HAVE CHANGED AS A PARTOF COORDINATION WITH MECHANICAL AND ELECTRICAL LAYOUTS
SEE PLANS FOR NEW GYP. BOARD BULKHEADS, LAYOUTS AND HEIGHTS
SEE PLANS FOR AREAS OF PATCH AND REPAIR OF EXISTING BULKHEADSAS A PART OF MECHANICAL, PLUMBING AND ELECTRICAL WORK
11
4
6
7
9
1
A B C D F G H K L
12
3NEW PARKING AREACEILING SYSTEM
NEW PARKING AREACEILING SYSTEM
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"A.F.F.
7' - 9"
A.F.F.8' - 9"
A.F.F.7' - 4"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 9"
A.F.F.8' - 0"
A.F.F.7' - 4"
A.F.F.7' - 4"A.F.F.
8' - 8"
A.F.F.16' - 8"
A.F.F.8' - 0"
EXISTINGGYP.BD.BULKHEADSTO REMAIN.
EXISTINGGYP.BD.BULKHEADSTO REMAIN.
EXISTINGGYP.BD.BULKHEADSTO REMAIN.
EXISTING GYP.BD.BULKHEADS TO REMAIN.
PATCH REPAIRSOFFIT THISLOCATION
A.F.F.7' - 4"
NOTE:LAY-IN CEILING DEMOLITON PART OF PHASE I WORK.COORDINATE DEMOLITION OF BULKHEADS ASREQUIRED WITH MECH/ELEC/PLUMBING. PREP FORREPAIR AND REFINISHING TO MATCH ADJACENTSURFACES
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A3.1M
5-2420
MEZZANINE REFLECTEDCEILING PLAN NEW AND
DEMOLITION
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"MEZZANINE REFLECTED CEILING PLAN - DEMO NORTH
1/8" = 1'-0"MEZZANINE REFLECTED CEILING PLAN - PHASE II
M
M
M
M
M
M
M
M
M M
M
M
M
M
M
M
M
11
4
6
7
9
A B C D F G H K L
12
3
EXISTING BULKHEADS TO REMAIN
5/8" GYP BOARD OVER6" MTL. FRAMING
NEW LAY-INCELING SYSTEM
1' - 0"
SEE
PLAN
S
1' - 6
" +/-
5/8" GYP BOARD OVER 3 5/8"MTL. FRAMING AT 16" O.C.
5/8" GYP. BOARD OVER 3 5/8"MTL. FRAMING AT 16" O.C.
LOCATION OFLIGHT FIXTURESEE ELECTRICAL
METAL CORNERBEADS TYP.
SECURE METAL FRAMINGTO EXISTING STRUCTURE
PHASE II CEILING NOTE:
LAY-IN CEILINGS SHOWN ARE PART OF PHASE I
SOME CEILING LAYOUTS AND HEIGHTS MAY HAVE CHANGED AS A PARTOF COORDINATION WITH MECHANICAL AND ELECTRICAL LAYOUTS
SEE PLANS FOR NEW GYP. BOARD BULKHEADS, LAYOUTS AND HEIGHTS
SEE PLANS FOR AREAS OF PATCH AND REPAIR OF EXISTING BULKHEADSAS A PART OF MECHANICAL, PLUMBING AND ELECTRICAL WORK
11
4
6
7
9
A B C D F G H K L
12
3
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 0"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 4"
A.F.F.8' - 8"
A.F.F.8' - 4"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.9' - 6"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.7' - 4"
A.F.F.7' - 4"
LINE OF LAY-INCEILING ABOVE
A.F.F.8' - 0"
NEW GYP.BD.BULKHEAD
1A3.2
Sim
6' - 7
"
5' - 0"
NOTE:LAY-IN CEILING DEMOLITON PART OF PHASE I WORK.COORDINATE DEMOLITION OF BULKHEADS ASREQUIRED WITH MECH/ELEC/PLUMBING. PREP FORREPAIR AND REFINISHING TO MATCH ADJACENTSURFACES
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A3.2
5-2420
SECOND FLOOR REFLECTEDCEILING PLAN NEW AND
DEMOLITION
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
11/2/2012 BIDDING & CONST.
NORTH
1/8" = 1'-0"SECOND FLOOR REFLECTED CEILING PLAN - DEMO
A3.2 1 1/2" = 1'-0"
1 ELEVATOR LOBBY LIGHT COVE DETAIL
NORTH
1/8" = 1'-0"SECOND FLOOR REFLECTED CEILING PLAN - PHASE II
M
M
M
M
M
M
M
M
M M
MM
M
M
M
M
M
11
4
6
7
9
A B C D F G H K L
12
3
EXISTING GYP.BD.BULKHEADS TO REMAIN.
EXISTING GYP.BD.BULKHEADS TO REMAIN.
PHASE II CEILING NOTE:
LAY-IN CEILINGS SHOWN ARE PART OF PHASE I
SOME CEILING LAYOUTS AND HEIGHTS MAY HAVE CHANGED AS A PARTOF COORDINATION WITH MECHANICAL AND ELECTRICAL LAYOUTS
SEE PLANS FOR NEW GYP. BOARD BULKHEADS, LAYOUTS AND HEIGHTS
SEE PLANS FOR AREAS OF PATCH AND REPAIR OF EXISTING BULKHEADSAS A PART OF MECHANICAL, PLUMBING AND ELECTRICAL WORK
11
4
6
7
9
A B C D F G H K L
12
3
A.F.F.8' - 8"
A.F.F.8' - 8"
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.8' - 10"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.8' - 7"
A.F.F.7' - 7"
A.F.F.7' - 7"
A.F.F.8' - 10"
A.F.F.7' - 7"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"A.F.F.
8' - 0"
A.F.F.7' - 4"
A.F.F.7' - 4"
LINE OF LAY-INCEILING ABOVE
EXISTING GYP.BD.BULKHEADS TO REMAIN.
EXISTING GYP.BD.BULKHEADS TOREMAIN.
EXISTING GYP.BD.BULKHEADS TO REMAIN.
NOTE:LAY-IN CEILING DEMOLITON PART OF PHASE I WORK.COORDINATE DEMOLITION OF BULKHEADS ASREQUIRED WITH MECH/ELEC/PLUMBING. PREP FORREPAIR AND REFINISHING TO MATCH ADJACENTSURFACES
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A3.3
5-2420
THIRD FLOOR REFLECTEDCEILING PLAN NEW AND
DEMOLITION
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"THIRD FLOOR REFLECTED CEILING PLAN - DEMO NORTH
1/8" = 1'-0"THIRD FLOOR REFLECTED CEILING PLAN - PHASE II
M
M M
M
M
M
M
M
M
MM
M M
M
M
M
M
M
11
4
6
7
9
A B C D F G H K L
12
3
EXISTING GYP.BD.BULKHEADS TO REMAIN.
EXISTING GYP.BD.BULKHEADS TO REMAIN.
PHASE II CEILING NOTE:
LAY-IN CEILINGS SHOWN ARE PART OF PHASE I
SOME CEILING LAYOUTS AND HEIGHTS MAY HAVE CHANGED AS A PARTOF COORDINATION WITH MECHANICAL AND ELECTRICAL LAYOUTS
SEE PLANS FOR NEW GYP. BOARD BULKHEADS, LAYOUTS AND HEIGHTS
SEE PLANS FOR AREAS OF PATCH AND REPAIR OF EXISTING BULKHEADSAS A PART OF MECHANICAL, PLUMBING AND ELECTRICAL WORK
11
4
6
7
9
A B C D F G H K L
12
3
A.F.F.8' - 1"
A.F.F.8' - 7 1/2"
A.F.F.8' - 7 1/2"
A.F.F.8' - 7 1/2"
A.F.F.8' - 7 1/2"
A.F.F.8' - 7 1/2"
A.F.F.8' - 7 1/2"
A.F.F.8' - 7 1/2"
A.F.F.8' - 7 1/2"
A.F.F.8' - 7 1/2"
A.F.F.8' - 7 1/2"
A.F.F.8' - 7 1/2"
A.F.F.7' - 10" A.F.F.
8' - 7 1/2"
A.F.F.8' - 7 1/2"
A.F.F.8' - 8"
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.8' - 7"
A.F.F.8' - 0"
A.F.F.7' - 4"
A.F.F.8' - 7"
A.F.F.8' - 7"
A.F.F.7' - 4"
A.F.F.8' - 7"
A.F.F.8' - 8"
A.F.F.8' - 7"
A.F.F.8' - 6"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.8' - 0"
LINE OF LAY-INCEILING ABOVE
EXISTING GYP.BD.BULKHEADS TO REMAIN.
EXISTINGGYP.BD.BULKHEADS TOREMAIN.
EXISTINGGYP.BD.BULKHEADSTO REMAIN.
EXISTING GYP.BD.BULKHEADS TO REMAIN.
NOTE:LAY-IN CEILING DEMOLITON PART OF PHASE I WORK.COORDINATE DEMOLITION OF BULKHEADS ASREQUIRED WITH MECH/ELEC/PLUMBING. PREP FORREPAIR AND REFINISHING TO MATCH ADJACENTSURFACES
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A3.4
5-2420
FOURTH FLOOR REFLECTEDCEILING PLAN NEW AND
DEMOLITION
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"FOURTH FLOOR REFLECTED CEILING PLAN - DEMO NORTH
1/8" = 1'-0"FOURTH FLOOR REFLECTED CEILING PLAN - PHASE II
M
M
M
M
M
M M
M
M
M
M
M
M
M
11
4
6
7
9
A B C D F G H K L
12
3
EXISTING GYP.BD.BULKHEADS TOREMAIN.
PHASE II CEILING NOTE:
LAY-IN CEILINGS SHOWN ARE PART OF PHASE I
SOME CEILING LAYOUTS AND HEIGHTS MAY HAVE CHANGED AS A PARTOF COORDINATION WITH MECHANICAL AND ELECTRICAL LAYOUTS
SEE PLANS FOR NEW GYP. BOARD BULKHEADS, LAYOUTS AND HEIGHTS
SEE PLANS FOR AREAS OF PATCH AND REPAIR OF EXISTING BULKHEADSAS A PART OF MECHANICAL, PLUMBING AND ELECTRICAL WORK
11
4
6
7
9
A B C D F G H K L
12
3
A.F.F.9' - 0"
A.F.F.7' - 4"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0" A.F.F.
9' - 0"
A.F.F.9' - 0"
A.F.F.7' - 4"
A.F.F.9' - 0"
A.F.F.7' - 8"
A.F.F.7' - 4"
A.F.F.8' - 0"
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.8' - 0"
A.F.F.7' - 4"
A.F.F.9' - 6"A.F.F.
8' - 0"A.F.F.8' - 0"
A.F.F.9' - 0"
A.F.F.8' - 10"
A.F.F.7' - 4"
A.F.F.8' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.7' - 4"
A.F.F.7' - 10"
A.F.F.8' - 0"
LINE OF LAY-INCEILING ABOVE
A.F.F.8' - 0"
1A3.2
Sim
EXISTING GYP.BD.BULKHEADS TO REMAIN.
EXISTINGGYP.BD.BULKHEADS TOREMAIN.
EXISTING GYP.BD.BULKHEADS TOREMAIN.
EXISTING GYP.BD.BULKHEADS TOREMAIN.
GYP.BD. BULKHEADNOT IN SCOPE OFPHASE 1.
6A2.7
6' - 7
"
5' - 0"
NOTE:LAY-IN CEILING DEMOLITON PART OF PHASE I WORK.COORDINATE DEMOLITION OF BULKHEADS ASREQUIRED WITH MECH/ELEC/PLUMBING. PREP FORREPAIR AND REFINISHING TO MATCH ADJACENTSURFACES
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A3.5
5-2420
FIFTH FLOOR REFLECTEDCEILING PLAN NEW AND
DEMOLITION
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"FIFTH FLOOR REFLECTED CEILING PLAN - DEMO NORTH
1/8" = 1'-0"FIFTH FLOOR REFLECTED CEILING PLAN - PHASE II
M M M M M
M
M
M
M
M
MMMMMMM
M M
M
M
M
M M
M
M
M M
M
MMM
M
M3
3
T
T
11
4
6
7
9
A B C D F G H K L
12
3
EXISTINGGYP.BD.BULKHEADSTO REMAIN.
EXISTINGGYP.BD.BULKHEADSTO REMAIN.
PHASE II CEILING NOTE:
LAY-IN CEILINGS SHOWN ARE PART OF PHASE I
SOME CEILING LAYOUTS AND HEIGHTS MAY HAVE CHANGED AS A PARTOF COORDINATION WITH MECHANICAL AND ELECTRICAL LAYOUTS
SEE PLANS FOR NEW GYP. BOARD BULKHEADS, LAYOUTS AND HEIGHTS
SEE PLANS FOR AREAS OF PATCH AND REPAIR OF EXISTING BULKHEADSAS A PART OF MECHANICAL, PLUMBING AND ELECTRICAL WORK
11
4
6
7
9
A B C D F G H K L
12
3
A.F.F.7' - 11"
A.F.F.7' - 11"
A.F.F.7' - 11"
A.F.F.7' - 11"
A.F.F.7' - 11"
A.F.F.7' - 11"
A.F.F.7' - 11"
A.F.F.7' - 11"
A.F.F.7' - 11"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0" A.F.F.
9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.9' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.7' - 10"
A.F.F.8' - 0"A.F.F.
9' - 0" A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"
A.F.F.8' - 0"
EXISTING GYP.BD.BULKHEADS TOREMAIN.
EXISTING GYP.BD.BULKHEADS TOREMAIN.
NOTE:LAY-IN CEILING DEMOLITON PART OF PHASE I WORK.COORDINATE DEMOLITION OF BULKHEADS ASREQUIRED WITH MECH/ELEC/PLUMBING. PREP FORREPAIR AND REFINISHING TO MATCH ADJACENTSURFACES
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A3.6
5-2420
SIXTH FLOOR REFLECTEDCEILING PLAN NEW AND
DEMOLITION
DA RD
PBAB TMND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"SIXTH FLOOR REFLECTED CEILING PLAN - DEMO NORTH
1/8" = 1'-0"SIXTH FLOOR REFLECTED CEILING PLAN - PHASE II
SEE FLOOR PLANS FORVERTICAL WALLREINFORCING REQUIRED.(TYPICAL)
LOUVER SILL
BLOCK JAMBBEYOND. ALUMINUM LOUVER SECTION.
SEALANT OVER BACKER RODAT PERIMETER OF LOUVERBOTH SIDES. (TYPICAL)
COORD. W/ MECH.INVERTED8" OR 12"BLOCK -SEE PLANSFOR SIZE.(TYPICAL)
LOUVER HEAD
STEEL LINTEL- SEEFLOOR PLANS
PAINT EXPOSEDSTEEL PLATE.(TYPICAL)
BLOCK JAMBBEYOND.
ALUMINUM LOUVER - SEESPECIFICATIONS.
SEALANT OVER BACKER RODAT PERIMETER OF LOUVERBOTH SIDES. (TYPICAL)
COORD W/ MECH
SEALANT OVER BACKER RODAT PERIMETER OF LOUVERBOTH SIDES. (TYPICAL)
ALUMINUM LOUVER - SEESPECIFICATIONS.
BLOCK WALL MATCH EXISTING WIDTHW/ HORIZ. REINF. AT 16" o/c.
GROUT FILL JAMB BLOCK
METAL SILL BELOW
MASONRY WALLMATCH EXISTING WIDTH
MASONRY WALLMATCH EXISTING WIDTH
11 5/
8"
7 5/8"
11 5/8"
7 5/8"
11 5/8" 7 5/8"
SILL
EXISTINGINSULATION.
SEALANT AROUND PERIMETERBOTH SIDES.
HEAD
SEALANT AROUND PERIMETERBOTH SIDES.
JAMB
(2) 6"x 18GA. METALCHANNEL HEADER.
(2) 18GA. METAL STUDS AT JAMB- FLOOR TO STUCTURE ABOVE(TYP.) MATCH EXISTINGFRAMING
LOUVER HEADCOORD W/ MECH
EXISTING PENTHOUSE WALL SYSTEM
EXISTING PENTHOUSE WALL SYSTEM
EXISTING PENTHOUSE WALL SYSTEM
METAL SILL BELOW
LOUVER SILLCOORD W/ MECH
SEALANT AROUND PERIMETERBOTH SIDES.
NEW ALUM. FLASHING
NEW SILL FLASHING
NEW 'J' CHANNEL
JAMB
NOTE:
(2) 3.5/8"x 20 GA. METALSTUDS AT JAMB - CONTINUETO STRUCTURE ABOVE ATBOTH SIDES OF OPENING (TYP.)
SEE DOOR HEAD FOR TYP.NOTES AT JAMB CONDITION
HEAD
(2) 3.5/8"x 20 GA. METALCHANNEL HEADER.
SEALANT AROUND PERIMETERBOTH SIDES.
HOLLOW METAL DRYWALLFRAME - SEE DOOR ANDFRAME SCHEDULE.
SEE DOOR SCHEDULEFOR DOOR TYPE.
SOUND BATT INSULATION.
(2) LAYERS 5/8" FIRE CODE GYP.BD.OVER BOTH SIDES OF 3.5/8"x20 GA. METAL STUDS AT 16"o/c.(EXTEND TO DECK ABOVE)
NOTE:
SEE PLANS FOR EXACTWALL CONFIGURATION.
NOTE:
SEE DRAWINGSFOR EXACT LINTELCONFIGURATION.
JAMBPROVIDE (3) ANCHORSPER JAMB MINIMUMW/ GROUT INFILL.
3/8"
SEE DOOR SCHEDULEFOR DOOR TYPE.
BLOCK WALL - SEE PLANSFOR THICKNESS.
U-BLOCK LINTEL -SEE STRUCTURAL DWGS.
SEE DOOR SCHEDULEFOR DOOR TYPE.
STEEL LINTEL ANDPLATE - SEE STRUCTURALDRAWINGS. (PAINT ALLEXPOSED STEEL)
BLOCK WALL - SEE PLANSFOR THICKNESS.
HEADSTEEL LINTEL
HEADU-BLOCK LINTEL
3/8"
3/8"
BULLNOSE BLOCK - EXCEPTAT LOCATIONS WITH TILE ON WALL (SEE R.F. SCHEDULE)
HOLLOW METAL DOOR FRAMEW/ GROUT FILL
HOLLOW METAL DOOR FRAMEW/ GROUT FILL
CONT. BACKER ROD & SEALANTAROUND FRAME PERIMETERBOTH SIDES.
CONT. BACKER ROD & SEALANTAROUND FRAME PERIMETERBOTH SIDES.
01H H01HOLLOW METAL FRAME PAINTED TYP.
GALV. AT RAMP LEVELHOLLOW METAL DOOR PAINTED TYP.
GALV. AT RAMP LEVEL
1/4" = 1'-0"
DOOR TYPE AND FRAME TYPE
W05WOOD DOOR STAINED TYP.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
OC
AL
PR
OJE
CTS
\5-2
420A
_CE
NTR
AL_
reed
d.rv
t
A5.1
5-2420
DOOR FRAME SCHEDULEDETAILS
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
Door Schedule
Mark Type
GMBDOORTYPE FRAME Fire Rating
HARDWARESET HEAD JAMB SILL REMARKS
003A 4' 0 x 7' 2" x 1 3/4" H01 01H 90 1 4/A5.1 4/A5.1 -- U8 LINTEL W/ (2) #5 BARS & CONC. FILL004A 3' 0 x 7' 2" x 1 3/4" H01 01H 90 2 4/A5.1 4/A5.1 -- U8 LINTEL W/ (2) #5 BARS & CONC. FILL005A 3' 0 x 7' 2" x 1 3/4" 1HR H01 01H 45 3 4/A5.1 4/A5.1 -- U8 LINTEL W/ (2) #5 BARS & CONC. FILL201A 3' 0 x 7' 2" x 1 3/4" EXISTING FRAME H01 01H 90 4 EXISTING EXISTING -- EXISTING FRAME NEW DOOR213A (2) 3' 0" x 7' 2" x 1 3/4" W05 02H 5 EXISTING EXISTING REWORK EXISTING FRAME NEW WOOD DOOR702A 4' 0 x 7' 2" x 1 3/4" RELOCATED H01 01H -- SIM 2/A5.1 SIM 2/A5.1 RELOCATED DOOR AND FRAME704A 3' 0 x 4'-0" x 1 3/4" H01 01H 90 6 3/A5.1 3/A5.1 --705A 3' 0 x 7' 2" x 1 3/4" H01 01H 90 6 3/A5.1 3/A5.1
A5.1 1 1/2" = 1'-0"
1 LOUVER SILL DETAIL
A5.1 1 1/2" = 1'-0"
2 ROOF LOUVER DETAIL
NOT TO SCALEA5.13 RATED DOOR & WALL DETAIL
A5.1 1 1/2" = 1'-0"
4 BLOCK WALL H.M. DOOR DETAIL
GENERAL DEMOLITION NOTES:
INVESTIGATION OF EXISTING FIRE PROTECTION SYSTEMS WILL BE REQUIRED BY THE CONTRACTORAS PART OF HIS BID PRICE, SO THAT THE EXACT EXTENT OF DEMOLITION CAN BE ACCURATELYDETERMINED. THE CONTRACTOR'S BID PRICE SHALL ALSO COVER REMOVAL OF SOME PORTIONSOF FIRE PROTECTION SYSTEMS NOT EXPLICITLY SHOWN ON THE DEMOLITION DRAWINGS, BUTDISCOVERED DURING THE INVESTIGATION PROCESS.
2.
CONTRACTOR SHALL PROTECT ALL WALLS, CEILINGS, FLOORS, LIGHTS AND OTHER FINISHEDSURFACES WHICH ARE NOT SCHEDULED FOR IMMEDIATE REMOVAL. IF SURFACES OR LIGHTSARE DAMAGED, CONTRACTOR SHALL REPAIR OR REPLACE TO MATCH ORIGINAL CONDITIONS.
3.
FIRE PROTECTION DEMOLITION NOTES:1
REMOVE EXISTING WET PIPE SPRINKLER SYSTEM AND APPURTENANCES IN ITS ENTIRETY AND ALL ASSOCIATEDPIPING, VALVES, FITTINGS, FLOW SWTCHES, AND HANGERS BACK TO SERVICE ENTRANCE AND CAP.
2REMOVE ENTIRE EXSITING DRY PIPE SPRINKLER SYSTEM AND APPURTENANCES IN ITS ENTIRETY AND ALLASSOCIATED PIPING, VALVES, FITTINGS, FLOW SWITCHES, AND HANGERS BACK TO SERVICE ENTRANCE ANDCAP.
3REMOVE EXISTING 2-1/2" HOSE OUTLET VALVE, 1-1/2" HOSE VALVE AND HOSE RACK, CABINET, AND ASSOCIATEDSTANDPIPE PIPING. FIELD VERIFY ACTUAL LOCATION(S).
EXISTING PIPING, AND EQUIPMENT SHOWN (IF ANY) AS DASHED SHALL BE REMOVED.1.
4REMOVE EXISTING FIRE DEPARTMENT CONNECTION AND ASSOCIATED PIPING.
EXIST 6" FPSERVICE TOREMAIN
1
2
2
1
3
11
4
6
7
9
1
13
A B C D F G H K L
14
15
16
M
12
3
3
4
3TYPICAL ALL FLOORSPLAZA TO PENTHOUSE(8 TOTAL)
11
4
6
7
9
1
13
A B C D F G H K L
14
15
16
M
12
3
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
\5-2
420F
P_C
EN
TRA
L_ch
risv_
chris
v.rv
t
FP0.0
5-2420
RAMP AND PLAZA FIREPROTECTION DEMOLITION
PLANS
CAV
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
M
ICH
IGA
N
NORTH
1/8" = 1'-0"RAMP FIRE PROTECTION DEMOLITION PLANNORTH
1/8" = 1'-0"PLAZA FIRE PROTECTION DEMOLITION PLAN
SB SBATSATS
MECHANICAL003
LOBBY002
VESTIBULE001
ANTI-FREEZE SYSTEM TOTAL AREA PROTECTED:APPROX 8,210 SQ FT THIS FLOOR
WET SYSTEM TOTAL AREA PROTECTED:APPROX 2,295 SQ FT THIS FLOOR
EXIST 6" FPSERVICE
FURNISH AND INSTALLSPRINKLER HEAD GUARDSON SPRINKLER HEADS INMECHANICAL 003
FURNISH AND INSTALLSPRINKLER HEADS BELOWDUCTWORK 48" ANDLARGER, TYP. COORDWITH OTHER TRADES
11
4
6
7
9
1
13
A B C D F G H K L
14
15
16
M
12
3
REFER TO ENLARGED PARTIAL RAMPFIRE PROTECTION PLAN - FIRE PUMP004 ON DWG FP2.4 FOR WORK THISAREA
FIRE PUMP004
FURNISH AND INSTALL PENDENTSPRINKLER HEADS IN AREAS OFPARKING RAMP WITHOUT CEILINGS.MOUNT DEFLECTOR AT 9'-6" ABOVERAMP FF (+\-)
FURNISH AND INSTALL EXTENDEDCOVERAGE DRY RECESSED PENDENTSPRINKLERS IN PARKING RAMP TECTUMCEILING SYSTEM
FURNISH AND INSTALLSPRINKLER HEAD GUARDSON SPRINKLER HEADS INPARKING RAMP
FURNISH AND INSTALL EXTENDEDCOVERAGE RECESSED PENDENTSPRINKLERS IN PARKING RAMP AREASWITH TECTUM CEILING SYSTEM
FP2.41
4" UPTO FDC
6" UP TOPUMP TEST
FPFDC
PUMP TEST
SPRINKLERSTANDPIPE
SPRINKLERSTANDPIPE
FP UP & DN
6" STANDPIPE DN
SPRI
NKLE
R (A
NTIF
REEZ
E)SP
RINK
LER
(ANT
IFRE
EZE)
SPRI
NKLE
R (A
NTIF
REEZ
E)
ROUTE BRANCH PIPING TOSPRINKLERS IN EXIST HIGHCORES PARKING DECKSTRUCTURE. FIELD VERIFYSIZES AND LOCATIONS
SPRINKLER (ANTIFREEZE)
ROUTE BRANCH PIPING TOSPRINKLERS IN EXIST HIGHCORES PARKING DECKSTRUCTURE. FIELD VERIFYSIZES AND LOCATIONS
COORD PIPE ROUTINGWITH DUCTWORK ANDEXIST STRUCTURE
COORD PIPE ROUTINGWITH DUCTWORK ANDEXIST STRUCTURE
ROUTE SPRINKLER MAINBELOW STRUCTURE AT9'-0" ABOVE RAMP FF (+\-).
FP UP & DN
6" STANDPIPE DN
STORAGE005
FURNISH AND INSTALLSPRINKLER HEAD GUARDSON SPRINKLER HEADS INSTORAGE 005
FIRE PROTECTION NOTES:FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FORTHE COORDINATION OF HIS WORK WITH ALL OTHER TRADES.ALL WORK SHALL BE EXECUTED IN A WORKMANLIKE MANNER.
1.
THESE DRAWINGS ARE DIAGRAMATIC IN NATURE. THE FIREPROTECTION CONTRACTOR IS REMINDED THAT HE IS RESPONSIBLEFOR THE FINAL DESIGN OF THE SYSTEM, INCLUDING PIPE SIZINGAND LOCATION. THE CONTRACTOR IS FURTHER EXPECTEDTO VISIT THE SITE AND VERIFY THE CONDITIONS UNDER WHICHTHE WORK SHALL BE PERFORMED.
2.
3.
MAXIMUM HANGER SPACING FOR PIPING 3" AND LARGER SHALLBE 12'-0" ON CENTER.
4.
FLOW TEST PERFORMED BY THE CITY OF GRAND RAPIDS, MI FROM 16"MEDIUM PRESSURE MAIN IN LYON ST (HYDRANT GAUGED AT INTERSECTIONOF LAFAYETTE AVE NE & LYON ST - ELEVATION 746.00' USGS, AND HYDRANTFLOWED AT LAFAYETTE AVE NE, 1ST HYDRANT NORTH OF LYON ST) INDICATESTHE FOLLOWING: 50 PSI STATIC, 47 PSI RESIDUAL AT 1,087 GPM. DATE OFTEST 08/21/12. BUILDING ELEVATION AT PLAZA LEVE IS 651.50' USGS - APPROX94.50' LOWER THAN GAUGED HYDRANT. CONTRACTOR SHALL PERFORMFLOW TEST (IN ACCORDANCE WITH NFPA 291) AT THE SITE TO VERIFYACCURACY OF THE INFORMATION. COPY OF FLOW TEST SHALL BE SUBMITTEDTO ARCHITECT.
5.
CONTRACTOR SHALL BE PERMITTED TO UITILIZE EXTENDEDCOVERAGE SPRINKLER HEADS WHERE APPROVED BY THEAUTHORITY HAVING JURISDICTION AND INSTALLED IN ACORDANCEWITH NFPA 13. CONTRACTOR SHALL BE RESPONSIBLE FORTHE COORDINATION OF SPRINKLER HEAD SPACING WITH ALLOTHER TRADES.
TOTAL AREA PROTECTED:APPROX 2,415 SQ FT THIS FLOOR
OFFICEP111
MECHP110
T.P112
OFFICEP116
JANP114
CORRP113
OFFICEP115
OFFICEP117
STAIRS-2
OFFICEP109
VESTIBULE001
VAULTP107
CORRP108
LOBBYP103
RECEPTP106
CONFP104
ELEVXXX
11
4
6
7
9
1
13
A B C D F G H K L
14
15
16
M
12
3
6" STANDPIPE
2-1/2" HOSE CONN
6" STANDPIPE
2-1/2" HOSE CONN
FDC
SECURE STANDPIPE TO STAIRSTRINGER AT EACH LEVEL.COORD WITH OTHER TRADES
PUMP TESTCONNECTION
FURNISH AND INSTALL SPRINKLERHEAD WITH GUARD BELOW FIRSTSTAIR LANDING AT BOTTOM OFSTAIRWELL, TYP 2 PLACES
FURNISH AND INSTALLSPRINKLER HEAD GUARDSON SPRINKLER HEADS INMECH P110
FURNISH AND INSTALLSPRINKLER HEAD GUARDON SPRINKLER HEAD INJAN P114
6" STANDPIPEUP & DN
FP DN
SPRI
NKLE
RSP
RINK
LER
SPRINKLER
FP UP & DN
6" STANDPIPEUP & DN
COORDINATE LOCATIONS OFSTANDPIPE AND SPRINKLERRISERS WITH EXIST HVAC ANDPLUMB, TYP ALL FLOORS
SPRI
NKLE
R
ROUTE SPRINKLER MAIN TIGHTTO BOTTOM OF STRUCTURE ANDROUTE AROUND EXIST GIRDERSRUNNING NORTH AND SOUTH ORTHROUGH EXIST HOLES IN GIRDERSIF NOT USED BY OTHER TRADES, TYP
COORDINATE LOCATIONS OFSTANDPIPE AND SPRINKLERRISERS WITH EXIST HVAC ANDPLUMB, TYP ALL FLOORS
SPRI
NKLE
R
SPRI
NKLE
R
HORN ANDSTROBE
VESTP101
REMOTEALARM PANEL
FURNISH AND INSTALLSPRINKLER HEAD GUARDON SPRINKLER HEAD INVAULT P107
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
\5-2
420F
P_C
EN
TRA
L_ch
risv_
chris
v.rv
t
FP2.0
5-2420
RAMP AND PLAZA FIREPROTECTION PLANS
CAV
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
M
ICH
IGA
N
NORTH
1/8" = 1'-0"RAMP FIRE PROTECTION PLANNORTH
1/8" = 1'-0"PLAZA FIRE PROTECTION PLAN
TOTAL AREA PROTECTED:APPROX 3,010 SQ FT THIS FLOOR
LOUNGEM118
OFFICEM112
LOBBYM105
STAIRS-2
OFFICEM106
OFFICEM101
OFFICEM111
OFFICEM110
OFFICEM107
STAIRS-1
CORRM102 MENS
M115
WOMENSM117
WORK ROOMM113
ELECM114
MECHM116
STORM109
OPEN OFFICEM108
JANM104
11
4
6
7
9
1
13
A B C D F G H K L
14
15
16
M
12
3
6" STANDPIPE
2-1/2" HOSE CONN
6" STANDPIPE
2-1/2" HOSE CONN
SECURE STANDPIPE TO STAIRSTRINGER AT EACH LEVEL.COORD WITH OTHER TRADES
FURNISH AND INSTALLSPRINKLER HEAD GUARDON SPRINKLER HEADS INMECH M103 AND JAN M104
MECHM103
FURNISH AND INSTALLSPRINKLER HEAD GUARDSON SPRINKLER HEADS INMECH M116 AND ELEC M114
FP UP & DN
6" STANDPIPEUP & DN
COORDINATE LOCATIONS OFSTANDPIPE AND SPRINKLERRISERS WITH EXIST HVAC ANDPLUMB, TYP ALL FLOORS
SPRINKLER SPRINKLER
SPRI
NKLE
R
SPRINKLER
SPRI
NKLE
R
ROUTE SPRINKLER MAIN TIGHTTO BOTTOM OF STRUCTURE ANDROUTE AROUND EXIST GIRDERSRUNNING NORTH AND SOUTH ORTHROUGH EXIST HOLES IN GIRDERSIF NOT USED BY OTHER TRADES, TYP
ROUTE SPRINKLER MAIN TIGHTTO BOTTOM OF STRUCTURE ANDROUTE AROUND EXIST GIRDERSRUNNING NORTH AND SOUTH ORTHROUGH EXIST HOLES IN GIRDERSIF NOT USED BY OTHER TRADES, TYP
6" STANDPIPE UP & DN
COORDINATE LOCATION OFSTANDPIPE RISER WITH EXISTHVAC AND PLUMB, TYP ALLFLOORS
TOTAL AREA PROTECTED:APPROX 5,195 SQ FT THIS FLOOR
OFFICE203
OFFICE204
OFFICE205
OFFICE206
OFFICE207
CONF216
LIBRARY218
OFFICE211
WORK RM215
OFFICE212
OFFICE217
CORR200
MENS202
OFFICE208
MECH219
ELEC221
WOMENS220
JAN222
MECH210
STAIRS-1
LOBBY213
CORR.201
STAIRS-2
CONF224
OFFICE231
OFFICE230
OFFICE229
OFFICE228
OFFICE226
OFFICE227
ENTRY214
CORR225
CORR223
CORR209
11
4
6
7
9
1
13
A B C D F G H K L
14
15
16
M
12
3
6" STANDPIPE
2-1/2" HOSE CONN
6" STANDPIPE
2-1/2" HOSE CONN
SECURE STANDPIPE TO STAIRSTRINGER AT EACH LEVEL.COORD WITH OTHER TRADES
FP UP & DN
FURNISH AND INSTALLSPRINKLER HEAD GUARDSON SPRINKLER HEADS INMECH 219 AND ELEC 221
FURNISH AND INSTALLSPRINKLER HEAD GUARDON SPRINKLER HEAD INMECH 210
6" STANDPIPE DN
6" STANDPIPE DN
STAN
DPIP
EST
ANDP
IPE
STAN
DPIP
E
COORDINATE LOCATIONS OFSTANDPIPE AND SPRINKLERRISERS WITH EXIST HVAC ANDPLUMB, TYP ALL FLOORS
COORDINATE LOCATION OFSTANDPIPE RISER WITH EXISTHVAC AND PLUMB, TYP ALLFLOORS
ROUTE SPRINKLER MAIN TIGHTTO BOTTOM OF STRUCTURE ANDROUTE AROUND EXIST GIRDERSRUNNING NORTH AND SOUTH ORTHROUGH EXIST HOLES IN GIRDERSIF NOT USED BY OTHER TRADES, TYP
SPRINKLER SPRINKLER
SPRI
NKLE
R
SPRINKLER
SPRI
NKLE
R
STAN
DPIP
E
FIRE PROTECTION NOTES:FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FORTHE COORDINATION OF HIS WORK WITH ALL OTHER TRADES.ALL WORK SHALL BE EXECUTED IN A WORKMANLIKE MANNER.
1.
THESE DRAWINGS ARE DIAGRAMATIC IN NATURE. THE FIREPROTECTION CONTRACTOR IS REMINDED THAT HE IS RESPONSIBLEFOR THE FINAL DESIGN OF THE SYSTEM, INCLUDING PIPE SIZINGAND LOCATION. THE CONTRACTOR IS FURTHER EXPECTEDTO VISIT THE SITE AND VERIFY THE CONDITIONS UNDER WHICHTHE WORK SHALL BE PERFORMED.
2.
CONTRACTOR SHALL BE PERMITTED TO UITILIZE EXTENDEDCOVERAGE SPRINKLER HEADS WHERE APPROVED BY THEAUTHORITY HAVING JURISDICTION AND INSTALLED IN ACORDANCEWITH NFPA 13. CONTRACTOR SHALL BE RESPONSIBLE FORTHE COORDINATION OF SPRINKLER HEAD SPACING WITH ALLOTHER TRADES.
3.
MAXIMUM HANGER SPACING FOR PIPING 3" AND LARGER SHALLBE 12'-0" ON CENTER.
4.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
\5-2
420F
P_C
EN
TRA
L_ch
risv_
chris
v.rv
t
FP2.1
5-2420
MEZZANINE AND SECONDFLOOR FIRE PROTECTION
PLANS
CAV
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
M
ICH
IGA
N
NORTH
1/8" = 1'-0"MEZZANINE FIRE PROTECTION PLANNORTH
1/8" = 1'-0"SECOND FLOOR FIRE PROTECTION PLAN
TOTAL AREA PROTECTED:APPROX 5,520 SQ FT THIS FLOOR
FILES322
STOR321
STOR313
CONF312
OFFICE301
OFFICE308
MECH315
ELEC317
WOMENS316
MECH311
LOBBY319STAIR
S-1STAIR
S-2STOR324
CONF325
OFFICE333
OFFICE332
OFFICE331
OFFICE330
OFFICE329
CONF328
OFFICE302
OFFICE303
OFFICE304
OFFICE305
OFFICE306
OFFICE307
MENS310
CORR309
OFFICE327
OFFICE326
CORR323
CORR320
11
4
6
7
9
1
13
A B C D F G H K L
14
15
16
M
12
3
6" STANDPIPE
2-1/2" HOSE CONN
6" STANDPIPE
2-1/2" HOSE CONN
SECURE STANDPIPE TO STAIRSTRINGER AT EACH LEVEL.COORD WITH OTHER TRADES
FURNISH AND INSTALLSPRINKLER HEAD GUARDSON SPRINKLER HEADS INMECH 315 AND ELEC 317
FURNISH AND INSTALLSPRINKLER HEAD GUARDON SPRINKLER HEAD INMECH 311
FP UP & DN
COORDINATE LOCATION OFSPRINKLER RISER WITH EXISTHVAC AND PLUMB, TYP ALLFLOORS
ROUTE SPRINKLER MAIN TIGHTTO BOTTOM OF STRUCTURE ANDROUTE AROUND EXIST GIRDERSRUNNING NORTH AND SOUTH ORTHROUGH EXIST HOLES IN GIRDERSIF NOT USED BY OTHER TRADES, TYP
SPRINKLER SPRINKLER
SPRI
NKLE
R
SPRINKLER
SPRI
NKLE
R
ROUTE SPRINKLER MAIN TIGHTTO BOTTOM OF STRUCTURE ANDROUTE AROUND EXIST GIRDERSRUNNING NORTH AND SOUTH ORTHROUGH EXIST HOLES IN GIRDERSIF NOT USED BY OTHER TRADES, TYP
JAN318
TOTAL AREA PROTECTED:APPROX 5,575 SQ FT THIS FLOOR
STOR412
OFFICE411
OFFICE410
WORK RM421
KITCHENETTE417
ELEC413
WOMENS414
JAN419
TOILET430
ENTRY416
STAIRS-1
LOBBY415
MECH408
STAIRS-2
OFFICE429
OFFICE428
OFFICE427OFFICE
426OFFICE
425
CONF424
OFFICE401
OFFICE402
OFFICE403
OFFICE404
OFFICE405
OFFICE406
MENS407
CORR409
CORR418
OFFICE420
CORR423
11
4
6
7
9
1
13
A B C D F G H K L
14
15
16
M
12
3
6" STANDPIPE
2-1/2" HOSE CONN
6" STANDPIPE
2-1/2" HOSE CONN
FURNISH AND INSTALLSPRINKLER HEAD GUARDSON SPRINKLER HEADS INELEC 413
SECURE STANDPIPE TO STAIRSTRINGER AT EACH LEVEL.COORD WITH OTHER TRADES
FURNISH AND INSTALLSPRINKLER HEAD GUARDON SPRINKLER HEAD INMECH 408
FP UP & DN
COORDINATE LOCATION OFSPRINKLER RISER WITH EXISTHVAC AND PLUMB, TYP ALLFLOORS
ROUTE SPRINKLER MAIN TIGHTTO BOTTOM OF STRUCTURE ANDROUTE AROUND EXIST GIRDERSRUNNING NORTH AND SOUTH ORTHROUGH EXIST HOLES IN GIRDERSIF NOT USED BY OTHER TRADES, TYP
SPRINKLER SPRINKLER
SPRI
NKLE
R
SPRINKLER
SPRI
NKLE
R
FIRE PROTECTION NOTES:FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FORTHE COORDINATION OF HIS WORK WITH ALL OTHER TRADES.ALL WORK SHALL BE EXECUTED IN A WORKMANLIKE MANNER.
1.
THESE DRAWINGS ARE DIAGRAMATIC IN NATURE. THE FIREPROTECTION CONTRACTOR IS REMINDED THAT HE IS RESPONSIBLEFOR THE FINAL DESIGN OF THE SYSTEM, INCLUDING PIPE SIZINGAND LOCATION. THE CONTRACTOR IS FURTHER EXPECTEDTO VISIT THE SITE AND VERIFY THE CONDITIONS UNDER WHICHTHE WORK SHALL BE PERFORMED.
2.
CONTRACTOR SHALL BE PERMITTED TO UITILIZE EXTENDEDCOVERAGE SPRINKLER HEADS WHERE APPROVED BY THEAUTHORITY HAVING JURISDICTION AND INSTALLED IN ACORDANCEWITH NFPA 13. CONTRACTOR SHALL BE RESPONSIBLE FORTHE COORDINATION OF SPRINKLER HEAD SPACING WITH ALLOTHER TRADES.
3.
MAXIMUM HANGER SPACING FOR PIPING 3" AND LARGER SHALLBE 12'-0" ON CENTER.
4.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
\5-2
420F
P_C
EN
TRA
L_ch
risv_
chris
v.rv
t
FP2.2
5-2420
THIRD AND FOURTH FLOORFIRE PROTECTION PLANS
CAV
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
M
ICH
IGA
N
NORTH
1/8" = 1'-0"THIRD FLOOR FIRE PROTECTION PLANNORTH
1/8" = 1'-0"FOURTH FLOOR FIRE PROTECTION PLAN
TOTAL AREA PROTECTED:APPROX 5,815 SQ FT THIS FLOOR
OFFICE522
OFFICE530
JAN520
ELEC518
MECH517
WOMENS519
CONF515
BREAK509OFFICE
510
STOR507
STAIRS-1
STAIRS-2
OPEN OFFICE524
OFFICE529
OFFICE528
OFFICE527
OFFICE526
OPEN OFFICE525
OFFICE501
OFFICE502
OFFICE503
OFFICE504
OFFICE505
MECH513
MENS512
FILES514
CORR511
OPEN OFFICE516
CONF523
STOR508
OFFICE506
CORR521
11
4
6
7
9
1
A B C D F G H K L M
12
3
6" STANDPIPE
2-1/2" HOSE CONN
6" STANDPIPE
2-1/2" HOSE CONN
SECURE STANDPIPE TO STAIRSTRINGER AT EACH LEVEL.COORD WITH OTHER TRADES
FURNISH AND INSTALLSPRINKLER HEAD GUARDSON SPRINKLER HEADS INMECH 517 AND ELEC 518
FURNISH AND INSTALLSPRINKLER HEAD GUARDSON SPRINKLER HEAD INMECH 513
FP UP & DN
SPRINKLER SPRINKLER
SPRI
NKLE
R
SPRINKLER
SPRI
NKLE
R
TOTAL AREA PROTECTED:APPROX 5,300 SQ FT THIS FLOOR
STAIRS-1
STAIRS-2
MECH609
ELEC614
WOMENS615
OFFICE630
OFFICE629
OFFICE628
OFFICE627
OFFICE626
WORK ROOM625
OFFICE602
OFFICE603
OFFICE604
OFFICE606
OFFICE605
OFFICE617B
OFFICE613
OFFICE622
OFFICE612
OFFICE611
OFFICE621
OFFICE620
MENS608
CORR610
CORR618
CORR624
CONF.631
OFFICE601
OFFICE600
OFFICE617A
CLOSET619
OFFICE623
OFFICE607B
OFFICE607A
LOBBY616
11
4
6
7
9
1
A B C D F G H K L M
12
3
6" STANDPIPE
2-1/2" HOSE CONN
6" STANDPIPE
2-1/2" HOSE CONN
SECURE STANDPIPE TO STAIRSTRINGER AT EACH LEVEL.COORD WITH OTHER TRADES
FURNISH AND INSTALLSPRINKLER HEAD GUARDSON SPRINKLER HEADS INMECH 6?? AND ELEC 614
MECH6??
FURNISH AND INSTALLSPRINKLER HEAD GUARDSON SPRINKLER HEAD INMECH 609
FP UP & DN
COORDINATE LOCATION OFSPRINKLER RISER WITH EXISTHVAC AND PLUMB, TYP ALLFLOORS
ROUTE SPRINKLER MAIN TIGHTTO BOTTOM OF STRUCTURE ANDROUTE AROUND EXIST GIRDERSRUNNING NORTH AND SOUTH ORTHROUGH EXIST HOLES IN GIRDERSIF NOT USED BY OTHER TRADES, TYP
SPRINKLERSPRINKLER
SPRI
NKLE
R
SPRINKLER
ROUTE SPRINKLER MAIN TIGHTTO BOTTOM OF STRUCTURE ANDROUTE AROUND EXIST GIRDERSRUNNING NORTH AND SOUTH ORTHROUGH EXIST HOLES IN GIRDERSIF NOT USED BY OTHER TRADES, TYP
SPRI
NKLE
R
FIRE PROTECTION NOTES:FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FORTHE COORDINATION OF HIS WORK WITH ALL OTHER TRADES.ALL WORK SHALL BE EXECUTED IN A WORKMANLIKE MANNER.
1.
THESE DRAWINGS ARE DIAGRAMATIC IN NATURE. THE FIREPROTECTION CONTRACTOR IS REMINDED THAT HE IS RESPONSIBLEFOR THE FINAL DESIGN OF THE SYSTEM, INCLUDING PIPE SIZINGAND LOCATION. THE CONTRACTOR IS FURTHER EXPECTEDTO VISIT THE SITE AND VERIFY THE CONDITIONS UNDER WHICHTHE WORK SHALL BE PERFORMED.
2.
CONTRACTOR SHALL BE PERMITTED TO UITILIZE EXTENDEDCOVERAGE SPRINKLER HEADS WHERE APPROVED BY THEAUTHORITY HAVING JURISDICTION AND INSTALLED IN ACORDANCEWITH NFPA 13. CONTRACTOR SHALL BE RESPONSIBLE FORTHE COORDINATION OF SPRINKLER HEAD SPACING WITH ALLOTHER TRADES.
3.
MAXIMUM HANGER SPACING FOR PIPING 3" AND LARGER SHALLBE 12'-0" ON CENTER.
4.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
\5-2
420F
P_C
EN
TRA
L_ch
risv_
chris
v.rv
t
FP2.3
5-2420
FIFTH AND SIXTH FLOOR FIREPROTECTION PLANS
CAV
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
M
ICH
IGA
N
NORTH
1/8" = 1'-0"FIFTH FLOOR FIRE PROTECTION PLANNORTH
1/8" = 1'-0"SIXTH FLOOR FIRE PROTECTION PLAN
TOTAL AREA PROTECTED:APPROX 2,695 SQ FT THIS FLOOR
STAIRS-1
STAIRS-2
MECH701
EQUIPMENT703
11
4
6
7
9
1
A B C D F G H K L M
12
3
FURNISH AND INSTALLSPRINKLER HEAD GUARDSON SPRINKLER HEADS INMECHANICAL 003
FURNISH AND INSTALLSPRINKLER HEADS BELOWDUCTWORK 48" ANDLARGER, TYP. COORDWITH OTHER TRADES
FURNISH AND INSTALL SPRINKLER HEADSWITH DEFLECTORS SLOPED TO MATCHSTEEL SLOPE (10 DEGREES +\-) AND ATTHE SAME ELEVATION AS THE BOTTOM OFSTEEL IN PENTHOUSE (VARIES), STAIRS,MECH, AND EQUIPMENT ROOMS
SLOPE FP PIPING TO MATCHSTEEL SLOPE (10 DEGREES +\-)
FP DN
SPRINKLER
SPRINKLER SPRINKLER
FURNISH AND INSTALLSPRINKLER HEAD GUARDSON SPRINKLER HEADS INEQUIPMENT 703 AND STAIRS-2
FURNISH AND INSTALLSPRINKLER HEAD GUARDSON SPRINKLER HEADS INMECH 701, ELEV ROOM 705,AND STAIR S-1
FIRE PROTECTION NOTES:FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FORTHE COORDINATION OF HIS WORK WITH ALL OTHER TRADES.ALL WORK SHALL BE EXECUTED IN A WORKMANLIKE MANNER.
1.
THESE DRAWINGS ARE DIAGRAMATIC IN NATURE. THE FIREPROTECTION CONTRACTOR IS REMINDED THAT HE IS RESPONSIBLEFOR THE FINAL DESIGN OF THE SYSTEM, INCLUDING PIPE SIZINGAND LOCATION. THE CONTRACTOR IS FURTHER EXPECTEDTO VISIT THE SITE AND VERIFY THE CONDITIONS UNDER WHICHTHE WORK SHALL BE PERFORMED.
2.
CONTRACTOR SHALL BE PERMITTED TO UITILIZE EXTENDEDCOVERAGE SPRINKLER HEADS WHERE APPROVED BY THEAUTHORITY HAVING JURISDICTION AND INSTALLED IN ACORDANCEWITH NFPA 13. CONTRACTOR SHALL BE RESPONSIBLE FORTHE COORDINATION OF SPRINKLER HEAD SPACING WITH ALLOTHER TRADES.
3.
MAXIMUM HANGER SPACING FOR PIPING 3" AND LARGER SHALLBE 12'-0" ON CENTER.
4.
FIRE PROTECTION ABBREVIATIONS
AFF ABOVE FINISH FLOORAPPROX APPROXIMATELY
CLG CEILINGCONN CONNECTIONCONT CONTINUATIONCONTR CONTRACTORDN DOWNDWG DRAWINGEA EACH
FF FINISH FLOORFLR FLOORFP FIRE PROTECTIONHSS HOLLOW STRUCTURAL SECTIONLOC LOCATION0 S & Y OUTSIDE STEM AND YOLKSQ FT DOWNTYP TYPICAL
FDC FIRE DEPARTMENT CONNECTION
ATS AUTOMATIC TRANSFER SWITCH
1. THE FIRE PROTECTION CONTRACTOR SHALL USE THE SYMBOLS IN THIS LEGEND TO INDICATE THE TYPE AND LOCATION OF SPRINKLERS ON HIS "WORKING PLANS".
NOTES:
OR
OR
OR
STANDARD PENDENT SPRINKLER
200
175 200
175 200
286
286
286
175 200
200175
286
FIRE PROTECTION SPRINKLER HEAD LEGEND
RECESSED PENDENT SPRINKLER WIITHMATCHING 2-PIECE ESCUTCHEON
CONCEALED PENDENT SPRINKLER
STANDARD UPRIGHT SPRINKLER
HORIZONTAL SIDEWALL SPRINKLER
EXTENDED COVERAGE PENDENT SPRINKLER
EXTENDED COVERAGE RECESSEDPENDENT SPRINKLER WITH MATCHING2-PIECE ESCUTCHEONEXTENDED COVERAGE CONCEALEDSPRINKLER
DRY PENDENT SPRINKLER
INTERMEDIATE TEMPERATURESTANDARD PENDENT SPRINKLER
EXTENDED COVERAGE UPRIGHTSPRINKLER
DRY HORIZONTAL SIDEWALL SPRINKLER
EXTENDED COVERAGE HORIZONTALSIDEWALL SPRINKLER
INTERMEDIATE TEMPERATURERECESSED PENDENT SPRINKLERWITH MATCHING 2-PIECE ESCUTCHEON
INTERMEDIATE TEMPERATURECONCEALED PENDENT SPRINKLER
INTERMEDIATE TEMPERATUREUPRIGHT SPRINKLER
INTERMEDIATE TEMPERATUREHORIZONTAL SIDEWALL SPRINKLER
HIGH TEMPERATUREPENDENT SPRINKLER
HIGH TEMPERATURE RECESSEDPENDENT SPRINKLER WITH MATCHIN2-PIECE ESCUTCHEON
HIGH TEMPERATUREUPRIGHT SPRINKLER
HIGH TEMPERATURE HORIZONTALSIDEWALL SPRINKLER
NOTES:1. TYPICAL FOR ALL PENDENT SPRINKLER HEADS.2. WHERE FLEXIBLE SPRINKLER DROPS ARE USED, TAKE OFF FROM BRANCH LINE SHALL BE HORIZONTAL WITH A MINIMUM OF A 3" RADIUS ON BENDS (3 BENDS MAXIMUM) WITH A 40" MAXIMUM LENGTH, AND INSTALLED PER MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS.
BRANCH LINE
1" x 2" PIPE NIPPLE
1" 90 DEGREE ELBOW
1" ARMOVER
1" ARMOVER
1" DROP
REDUCER
PENDENTSPRINKLERHEAD
2'-0" x 4'-0" TILE 2'-0" x 2'-0" TILE(OR 2'-0" x 4'-0"TILE WITH 2'-0"x 2'-0" PATTERN)
NOTES:1. SPRINKLER HEAD SHALL BE CENTERED IN ALL DIRECTIONS ON CEILING TILES THAT ARE LESS THAN FULL.
TYPICALCENTER
TYPICALCENTER
SPRINKLER HEAD PERMITTEDON HALF TILE ONLY WHERE2'-0" x 2'-0" LIGHT OR DIFFUSERSHARES CEILING TILE
EQUAL EQUAL
EQUALEQUAL
EQUA
LEQ
UAL
EQUA
LEQ
UAL
EQUAL EQUAL
SPRINKLER
FINISH FLOOR
WATTS SERIES 994RPDA-OSY-GXGREDUCED PRESSURE DETECTORASSEMBLY. ROUTE DRAIN FROMAIR GAP TO EXTERIOR/RAMP SPRINKLER (ANTIFREEZE)
FILL CUPOR FILLINGCONNECTION
AMTROL FIRE-X-TROL EXPANSIONCHAMBER. SIZE PER MANUFACTURER'SWRITTEN SIZING LITERATURE ANDIN ACCORDANCE WITH NFPA 13
BALL VALVE
BALL VALVE(SYSTEM DRAIN)
PIPE STAND, TYP(HSS 2"x2"x 1/4" POSTWITH 4"x4"x 3/8" TOPAND BASE PLATES)
NOTES:1. FIRE PROTECTION SPRINKLER SYSTEMS SHALL BE HYDRAULICALLY CALCULATED PER SPECIFICATION SECTION 211300.
RISING STEM O S & Y VALVEWITH TAMPER SWITCH (WIREDBY FIRE ALARM CONTR), TYP
6
C D F
STAN
DPIP
E
SPRI
NKLE
R (A
NTIF
REEZ
E)
SPRINKLER
FDC
PUMP
TES
T
SPRI
NKLE
R
JOCKEY PUMPCONTROLLERFIRE PUMPCONTROLLERWITH ATS
FP-1FIRE PUMP, 750GPM, 40 HP, 50PSI BOOST (MIN)
JP-1JOCKEY PUMP, 5GPM, 1 HP, 60 PSI
ANTIFREEZE SYSTEMPIPING, REFER TO DETAILTHIS DWG (5/FP2.4)
FURNISH AND INSTALLSPRINKLER HEAD GUARDSON SPRINKLER HEADSIN FIRE PUMP 004
FIRE PUMP004
STANDPIPE
2FP2.4
FP
6" S
TAND
PIPE
4" F
DC
6" P
UMP
TEST
SYSTEM SENSOR WFD SERIESFLOW SWITCH (WIRED BY FIREALARM CONTR)
4" DIAMETER , 0-200 PSIPRESSURE GAUGE, TYP
2" ANGLE VALVE FORSYSTEM MAIN DRAIN, TYP
RISING STEM O S & Y VALVEWITH TAMPER SWITCH (WIREDBY FIRE ALARM CONTR), TYP
CAP
PIPE STAND, TYP(HSS 2"x2"x 1/4" POSTWITH 4"x4"x 3/8" TOPAND BASE PLATES)
NOTES:1. FIRE PROTECTION STANDPIPE AND SPRINKLER SYSTEMS SHALL BE HYDRAULICALLY CALCULATED PER SPECIFICATION SECTION 211300.
HYDRAULIC NAMEPLATE, TYP(PROVIDE INFORMATION INACCORDANCE WITH NFPA 13)
6" WATTS SERIES SS07FSTAINLESS STEEL SINGLEDECTECTOR CHECK VALVE
FIRE PUMP
CHECK VALVE
6" WATTS SERIES 774DCDAOSYDOUBLE CHECK DETECTORASSEMBLY
4" DIAMETER , 0-200 PSIPRESSURE GAUGE, TYP
6" FP, REFER TODWG FP2.0 FORCONT
PIPE STAND, TYP(HSS 2"x2"x 1/4" POSTWITH 4"x4"x 3/8" TOPAND BASE PLATES)
ROUTE SYSTEM MAINDRAINS TO EXTERIOR/RAMP
SPRI
NKLE
R
RISING STEM O S & Y VALVE WITHTAMPER SWITCH (WIRED BY FIREALARM CONTR). SUPERVISED"CLOSED" ON BYPASS
6" BYPASSRISING STEM O S & Y VALVEWITH TAMPER SWITCH (WIREDBY FIRE ALARM CONTR), TYP
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
\5-2
420F
P_C
EN
TRA
L_ch
risv_
chris
v.rv
t
FP2.4
5-2420
PENTHOUSE FIREPROTECTION PLAN AND
DETAILS
CAV
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
M
ICH
IGA
N
NORTH
1/8" = 1'-0"PENTHOUSE FIRE PROTECTION PLAN
Not to ScaleFP2.43 RETURN BEND DETAIL
Not to ScaleFP2.44 CEILING TILE DETAIL
NOT TO SCALEFP2.45 ANTIFREEZE SYSTEM PIPING DETAIL
FP2.4 1/4" = 1'-0"
1 ENLARGED PARTIAL RAMP FIRE PROTECTION PLAN - FIRE PUMP 004
NOT TO SCALEFP2.42 FIRE PROTECTION PUMP AND RISER DETAIL
UP
MM
GRAND RAPIDS COMMUNITY COLLEGE RESERVES THE RIGHT OF FIRST REFUSAL IN OWNERSHIPOF ANY EQUIPMENT ITEMS AND MATERIAL TO BE REMOVED FROM THE BUILDING AND SITE.
INVESTIGATION OF EXISTING HEATING, PLUMBING AND VENTILATION SYSTEMS WILL BE REQUIREDBY THE CONTRACTOR AS PART OF HIS BID PRICE, SO THAT THE EXACT EXTENT OF DEMOLITIONCAN BE ACCURATELY DETERMINED. THE CONTRACTOR'S BID PRICE SHALL ALSO COVERREMOVAL OF SOME PORTIONS OF HEATING, PLUMBING AND VENTILATION SYSTEMS NOTEXPLICITLY SHOWN ON THIS DRAWING, BUT DISCOVERED DURING THE INVESTIGATION PROCESS.THE CONTRACTOR SHALL WORK WITH THE A/E AND THE OWNER TO DETERMINE WHICHPORTIONS OF EXISTING SYSTEMS MUST REMAIN ACTIVE AND WHICH PORTIONS MUST BEDEMOLISHED. REMOVE ALL INACTIVE DUCTWORK AND PIPING TO THE NEAREST ACTIVE MAINS.DUCTWORK SHALL BE CAPPED AND SEALED AIRTIGHT AT TERMINATION POINTS. PIPING SHALL BECAPPED AT TERMINATION POINTS.
ALL PIPING AND EQUIPMENT SHOWN DASHED SHALL BE REMOVED OR RELOCATED UNLESSOTHERWISE NOTED. PROTECT EXISTING WORK WHICH IS TO REMAIN IN PLACE FOR REUSE WITHTEMPORARY COVERS, SHORING, BRACING, AND SUPPORTS. VERIFY LOCATIONS OF AND PROTECTEXISTING INTERIOR ELECTRICAL AND MECHANICAL UTILITIES AND SERVICES, EXCEPT WHEREINDICATED OTHERWISE. ALL MATERIALS AND EQUIPMENT REMOVED, AND NOT REUSED SHALLBECOME PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE OWNERSPROPERTY. THE OWNER RESERVES THE RIGHT TO SALVAGE PARTS FROM ALL MECHANICALEQUIPMENT BEFORE REMOVAL FROM THE SITE. ALL MATERIALS AND EQUIPMENT REQUIRINGREMOVAL AND RELOCATION FOR REUSE SHALL BE CAREFULLY REMOVED AND STORED TOPREVENT DAMAGE AND REINSTALLED AS THE WORK PROGRESSES.
CONTRACTOR TO FIELD VERIFY ACTUAL LOCATION AND SIZES OF EXISTING PIPING, DUCTWORK,EQUIPMENT AND SUPPORTS.
PATCH AND REPAIR ALL WALL, FLOOR AND CEILING OPENINGS DUE TO DEMOLITION WHICH ARENOT BE REUSED TO MATCH EXISTING CONSTRUCTION.
CONTRACTOR SHALL DRAIN EXISTING SYSTEMS AS REQUIRED FOR DEMOLITION, AND SHALL BERESPONSIBLE FOR FILLING, TESTING AND STARTUP OF SYSTEMS UPON COMPLETION.CONTRACTOR SHALL MAINTAIN OWNER'S CHEMICAL TREATMENT PROGRAM.
IF ASBESTOS MATERIAL IS ENCOUNTERED IT WILL BE REMOVED BY OWNER.
MODIFICATIONS TO ROOFING SYSTEM FOR DEMOLITION OR INSTALLATION OF EQUIPMENT SHALLBE DONE BY THIS CONTRACTOR. WORK SHALL MAINTAIN OWNER'S ROOFING WARRANTY.
REFER TO SPECIFICATION SECTION 02 41 19 SELECTIVE DEMOLITION FOR A LIST OF ITEMS TO BEREMOVED AND RETURNED TO THE OWNER
ALL PLUMBING PIPING AS SHOWN SHALL REMAIN. GAS PIPING SHALL BE REMOVED AS NOTED ANDSHOWN.
GENERAL MECHANICAL DEMOLITION NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
M
11
4
6
7
9
1
A B C D F G H L
12
3
EXISTING FINNEDTUBE TO REMAIN,TYP.
EXISTING FINNEDTUBE TO REMAIN,TYP.
15
15
EXISTING FINNEDTUBE TO REMAIN,TYP.
EXISTINGCONVECTOR
EXISTINGCONVECTOR
05
05
05 05 05
05
05
05
05
05
05
05
01
0109
03
4" CHGS&R
02
02
01
04
04
04
04
04
04
08
12
12
07
04 04
10
10
01
01
0101
01
REMOVE EXISTING CONTROL AIRCOMPRESSOR AND RELATEDACCESSORIES. RETURN TO OWNER.
56"x26"
50"x18"
1" HW
1" HW
1" HW
1" HW
1" HW
1" HW1" HW
1" HW
1" HW
1" HW
1" HW
1" HW
3/4" HWS&R, TYP. OFALL CONVECTORS
3/4" HWS&R,TYP. OF ALL FT
SHOWN FROMLEFT TO RIGHT2.1/2" CW TO REMAIN3" GAS TO BE REMOVED3" CGS TO BE REMOVED3" CGR TO BE REMOVED1.1/4" HW TO REMAIN
SHOWN FROMTOP TO BOTTOM4" VENT TO REMAIN4" SAN TO REMAIN4" STORM TO REMAIN1.1/4" HW TO REMAIN2.1/2" CW TO REMAIN1.1/4" HW TO REMAIN2.1/2" HWS TO BE REMOVED2.1/2" HWR TO BE REMOVED
0808
EXISTING FINNEDTUBE TO REMAIN,TYP.
F.D.
REMOVE.EXISTING F.D.
F.D.
F.D.
01REMOVE DUCTWORK, HANGERS, INSULATION, GRILLES, DIFFUSERS, DAMPERS, AND ALL RELATEDACCESSORIES AS SHOWN. NOTE: ALL SIDEWALL RA GRILLES TO REMAIN.
MECHANICAL DEMOLITION KEYNOTES:
02REMOVE AIR HANDLING UNIT, DAMPERS, CONTROLS, ASSOCIATED PIPING, VALVES, & ALL RELATEDACCESSORIES FOR A COMPLETE REMOVAL OF EXISTING AIR HANDLING SYSTEM.
03REMOVE AS MUCH EXISTING UNDERGROUND CHILLED WATER PIPING UNDERGROUND AS POSSIBLE. CAP ANDABANDON REMAINING. REFER TO ARCHITECTURAL PLANS FOR LOCATION OF CONCRETE REMOVAL NEAREXISTING CHILLER.
04REMOVE EXISTING HYDRONIC PIPING, SUPPORTS, HANGERS, INSULATION, VALVES, AND ALL RELATEDACCESSORIES.
05EXISTING FINNED TUBE TO REMAIN. CONTRACTOR SHALL REMOVE EXISTING MONOFLO FITTINGS. REMOVE ASMUCH PIPING EXISTING PIPING AS POSSIBLE. PREP PIPE TO RECONNECT WITH NEW. REFER TO NEW HYDRONICPIPING PLANS AND DETAILS FOR MORE INFORMATION.
06REMOVE EXISTING CHILLER, CONTROLS, ASSOCIATED PIPING, AND ALL RELATED ACCESSORIES FOR ACOMPLETE REMOVAL.
07REMOVE EXISTING SHEET METAL ASSOCIATED WITH OUTDOOR INTAKE AREAWAY AND ASSOCIATED OADAMPERS. SEE HVAC PLANS FOR MORE INFORMATION.
08REMOVE EXISTING LOUVER AND ALL ASSOCIATED ACCESSORIES. REFER TO ARCH. PLANS FOR MOREINFORMATION/.
09REMOVE EXISTING PUMPS, MOTORS, CONTROLS, & ALL RELATED ACCESSORIES. RETURN PUMPS & MOTORS TOOWNER.
10REMOVE AIR SEPARATOR, EXPANSION TANK, AND ALL OTHER EQUIPMENT ASSOCIATED WITH THE CHWSYSTEM.
11REMOVE EXISTING DUAL DUCT BOX, CONTROLS, HANGERS, VALVES, AND ALL RELATED ACCESSORIES. IFPNEUMATIC TUBING IS PRESENT, REMOVE ALL PNEUMATIC TUBING. REMOVE EXISTING SENSOR/THERMOSTATASSOCIATED WITH DUAL DUCT BOX. REUSE EXISTING LOCATION FOR NEW SENSOR. IF LOCATION CANNOT BEREUSED, PATCH TO MATCH EXISTING.
12EXISTING CONVECTOR TO REMAIN. RECONNECT WITH NEW HYDRONIC PIPING. REFER TO HYDRONIC PIPINGPLANS AND DETAILS FOR MORE INFORMATION.
13REMOVE EXISTING CONDENSING UNIT, REFRIGERANT PIPING, CURB, AND ALL RELATED ACCESSORIES. RETURNUNIT TO OWNER.
14REMOVE EXISTING NATURAL GAS METER SET AND APPURTENANCES. COORDINATE DEMOLITION AND NEWMETER SET ROUGH IN REQUIREMENTS WITH UTILITY PURVEYOR (DTE ENERGY CONTACT: BRAD LEITER [email protected]).
15REMOVE EXISTING NATURAL GAS PIPING AND ASSOCIATED VALVES, FITTINGS, AND HANGERS FROM METERSET TO PENTHOUSE. FIELD VERIFY SIZE AND ACTUAL LOCATION.
16REMOVE EXISTING BOILER, CONTROLS, PIPING, PUMPS, TANKS, VALVES, VENTING /INTAKE, AND ALL RELATEDACCESSORIES FOR A COMPLETE REMOVAL OF THE SYSTEM.
17REMOVE EXISTING EXHAUST FAN, HANGERS, DUCTWORK, DAMPERS, AND ALL ASSOCIATED ACCESSORIES.RETURN FAN TO OWNER.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M0.0
5-2420
PHASE 2 - RAMP MECHANICALDEMOLITION PLAN
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"PHASE 2 - RAMP MECHANICAL DEMOLITION PLAN
DN
UP
UP
UP
DN
DNUPDN
UP
GRAND RAPIDS COMMUNITY COLLEGE RESERVES THE RIGHT OF FIRST REFUSAL IN OWNERSHIPOF ANY EQUIPMENT ITEMS AND MATERIAL TO BE REMOVED FROM THE BUILDING AND SITE.
INVESTIGATION OF EXISTING HEATING, PLUMBING AND VENTILATION SYSTEMS WILL BE REQUIREDBY THE CONTRACTOR AS PART OF HIS BID PRICE, SO THAT THE EXACT EXTENT OF DEMOLITIONCAN BE ACCURATELY DETERMINED. THE CONTRACTOR'S BID PRICE SHALL ALSO COVERREMOVAL OF SOME PORTIONS OF HEATING, PLUMBING AND VENTILATION SYSTEMS NOTEXPLICITLY SHOWN ON THIS DRAWING, BUT DISCOVERED DURING THE INVESTIGATION PROCESS.THE CONTRACTOR SHALL WORK WITH THE A/E AND THE OWNER TO DETERMINE WHICHPORTIONS OF EXISTING SYSTEMS MUST REMAIN ACTIVE AND WHICH PORTIONS MUST BEDEMOLISHED. REMOVE ALL INACTIVE DUCTWORK AND PIPING TO THE NEAREST ACTIVE MAINS.DUCTWORK SHALL BE CAPPED AND SEALED AIRTIGHT AT TERMINATION POINTS. PIPING SHALL BECAPPED AT TERMINATION POINTS.
ALL PIPING AND EQUIPMENT SHOWN DASHED SHALL BE REMOVED OR RELOCATED UNLESSOTHERWISE NOTED. PROTECT EXISTING WORK WHICH IS TO REMAIN IN PLACE FOR REUSE WITHTEMPORARY COVERS, SHORING, BRACING, AND SUPPORTS. VERIFY LOCATIONS OF AND PROTECTEXISTING INTERIOR ELECTRICAL AND MECHANICAL UTILITIES AND SERVICES, EXCEPT WHEREINDICATED OTHERWISE. ALL MATERIALS AND EQUIPMENT REMOVED, AND NOT REUSED SHALLBECOME PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE OWNERSPROPERTY. THE OWNER RESERVES THE RIGHT TO SALVAGE PARTS FROM ALL MECHANICALEQUIPMENT BEFORE REMOVAL FROM THE SITE. ALL MATERIALS AND EQUIPMENT REQUIRINGREMOVAL AND RELOCATION FOR REUSE SHALL BE CAREFULLY REMOVED AND STORED TOPREVENT DAMAGE AND REINSTALLED AS THE WORK PROGRESSES.
CONTRACTOR TO FIELD VERIFY ACTUAL LOCATION AND SIZES OF EXISTING PIPING, DUCTWORK,EQUIPMENT AND SUPPORTS.
PATCH AND REPAIR ALL WALL, FLOOR AND CEILING OPENINGS DUE TO DEMOLITION WHICH ARENOT BE REUSED TO MATCH EXISTING CONSTRUCTION.
CONTRACTOR SHALL DRAIN EXISTING SYSTEMS AS REQUIRED FOR DEMOLITION, AND SHALL BERESPONSIBLE FOR FILLING, TESTING AND STARTUP OF SYSTEMS UPON COMPLETION.CONTRACTOR SHALL MAINTAIN OWNER'S CHEMICAL TREATMENT PROGRAM.
IF ASBESTOS MATERIAL IS ENCOUNTERED IT WILL BE REMOVED BY OWNER.
MODIFICATIONS TO ROOFING SYSTEM FOR DEMOLITION OR INSTALLATION OF EQUIPMENT SHALLBE DONE BY THIS CONTRACTOR. WORK SHALL MAINTAIN OWNER'S ROOFING WARRANTY.
REFER TO SPECIFICATION SECTION 02 41 19 SELECTIVE DEMOLITION FOR A LIST OF ITEMS TO BEREMOVED AND RETURNED TO THE OWNER
ALL PLUMBING PIPING AS SHOWN SHALL REMAIN. GAS PIPING SHALL BE REMOVED AS NOTED ANDSHOWN.
GENERAL MECHANICAL DEMOLITION NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
13
11
4
6
7
9
1
A B C D F G H L
12
3
9"x5"
9"x8"
16"x6"
10"x6"
16"x5"
14"x3"
14"x6" 18"x8"
15
EXIST GASSERVICETO REMAIN
14
04
05
0505 0505 05
05
05
05
05
0505
05
0505
0404
04
04
04
04
04
12
12
12
12
04
11
01
01
1" HW
1" HW
1" HW
1" HW
1" HW
1" HW1" HW
1" HW
1" HW
1" HW
3/4" HWS&R, TYP. OFALL CONVECTORS
3/4" HWS&R, TYP.OF ALL FT
3/4" HWS&R, TYP.OF ALL FT
3/4" HWS&R, TYP. OFALL CONVECTORS
SHOWN FROMLEFT TO RIGHT2.1/2" CW TO REMAIN3" GAS TO BE REMOVED3" CGS TO BE REMOVED3" CGR TO BE REMOVED1.1/4" HW TO REMAIN
SHOWN FROMTOP TO BOTTOM4" VENT TO REMAIN4" SAN TO REMAIN4" STORM TO REMAIN1.1/4" HW TO REMAIN2.1/2" CW TO REMAIN1.1/4" HW TO REMAIN2.1/2" HWS TO BE REMOVED2.1/2" HWR TO BE REMOVED
01
06
051" HW
13
M
11
4
6
7
9
1
A B C D F G H L
12
3
6"ø
12"x9"
12"x6"12"x6"
30"x16"
30"x10"
24"x10"
18"x12"
46"x16"
14"x8"20"x10" 16"x10" 15"x8"
15"x8"16"x10"
16"x10"
9"x5"
05 05 05 05 05 05
05
05
0505
05
04 04
04
04
04
04
04
04
04
0404
0101
01
01 01
01
0101
01
01 05
01
01
01
11
1" HW
1" HW
1" HW
1" HW
1" HW
1" HW 1" HW
1" HW
1" HW
3/4" HWS&R, TYP. OFALL CONVECTORS
3/4" HWS&R, TYP.OF ALL FT
3/4" HWS&R, TYP.OF ALL FT
3/4" HWS&R, TYP. OFALL CONVECTORS
SHOWN FROMLEFT TO RIGHT2.1/2" CW TO REMAIN3" GAS TO BE REMOVED3" CGS TO BE REMAINED3" CGR TO BE REMOVED1.1/4" HW TO REMAIN
SHOWN FROMTOP TO BOTTOM4" VENT TO REMAIN4" SAN TO REMAIN4" STORM TO REMAIN1.1/4" HW TO REMAIN2.1/2" CW TO REMAIN1.1/4" HW TO REMAIN2" HWS TO BE REMOVED2" HWR TO BE REMOVED
TO REMAIN, TYP
01 TO REMAIN, TYP.
12
12
12
12
01REMOVE DUCTWORK, HANGERS, INSULATION, GRILLES, DIFFUSERS, DAMPERS, AND ALL RELATEDACCESSORIES AS SHOWN. NOTE: ALL SIDEWALL RA GRILLES TO REMAIN.
MECHANICAL DEMOLITION KEYNOTES:
02REMOVE AIR HANDLING UNIT, DAMPERS, CONTROLS, ASSOCIATED PIPING, VALVES, & ALL RELATEDACCESSORIES FOR A COMPLETE REMOVAL OF EXISTING AIR HANDLING SYSTEM.
03REMOVE AS MUCH EXISTING UNDERGROUND CHILLED WATER PIPING UNDERGROUND AS POSSIBLE. CAP ANDABANDON REMAINING. REFER TO ARCHITECTURAL PLANS FOR LOCATION OF CONCRETE REMOVAL NEAREXISTING CHILLER.
04REMOVE EXISTING HYDRONIC PIPING, SUPPORTS, HANGERS, INSULATION, VALVES, AND ALL RELATEDACCESSORIES.
05EXISTING FINNED TUBE TO REMAIN. CONTRACTOR SHALL REMOVE EXISTING MONOFLO FITTINGS. REMOVE ASMUCH PIPING EXISTING PIPING AS POSSIBLE. PREP PIPE TO RECONNECT WITH NEW. REFER TO NEW HYDRONICPIPING PLANS AND DETAILS FOR MORE INFORMATION.
06REMOVE EXISTING CHILLER, CONTROLS, ASSOCIATED PIPING, AND ALL RELATED ACCESSORIES FOR ACOMPLETE REMOVAL.
07REMOVE EXISTING SHEET METAL ASSOCIATED WITH OUTDOOR INTAKE AREAWAY AND ASSOCIATED OADAMPERS. SEE HVAC PLANS FOR MORE INFORMATION.
08REMOVE EXISTING LOUVER AND ALL ASSOCIATED ACCESSORIES. REFER TO ARCH. PLANS FOR MOREINFORMATION/.
09REMOVE EXISTING PUMPS, MOTORS, CONTROLS, & ALL RELATED ACCESSORIES. RETURN PUMPS & MOTORS TOOWNER.
10REMOVE AIR SEPARATOR, EXPANSION TANK, AND ALL OTHER EQUIPMENT ASSOCIATED WITH THE CHWSYSTEM.
11REMOVE EXISTING DUAL DUCT BOX, CONTROLS, HANGERS, VALVES, AND ALL RELATED ACCESSORIES. IFPNEUMATIC TUBING IS PRESENT, REMOVE ALL PNEUMATIC TUBING. REMOVE EXISTING SENSOR/THERMOSTATASSOCIATED WITH DUAL DUCT BOX. REUSE EXISTING LOCATION FOR NEW SENSOR. IF LOCATION CANNOT BEREUSED, PATCH TO MATCH EXISTING.
12EXISTING CONVECTOR TO REMAIN. RECONNECT WITH NEW HYDRONIC PIPING. REFER TO HYDRONIC PIPINGPLANS AND DETAILS FOR MORE INFORMATION.
13REMOVE EXISTING CONDENSING UNIT, REFRIGERANT PIPING, CURB, AND ALL RELATED ACCESSORIES. RETURNUNIT TO OWNER.
14REMOVE EXISTING NATURAL GAS METER SET AND APPURTENANCES. COORDINATE DEMOLITION AND NEWMETER SET ROUGH IN REQUIREMENTS WITH UTILITY PURVEYOR (DTE ENERGY CONTACT: BRAD LEITER [email protected]).
15REMOVE EXISTING NATURAL GAS PIPING AND ASSOCIATED VALVES, FITTINGS, AND HANGERS FROM METERSET TO PENTHOUSE. FIELD VERIFY SIZE AND ACTUAL LOCATION.
16REMOVE EXISTING BOILER, CONTROLS, PIPING, PUMPS, TANKS, VALVES, VENTING /INTAKE, AND ALL RELATEDACCESSORIES FOR A COMPLETE REMOVAL OF THE SYSTEM.
17REMOVE EXISTING EXHAUST FAN, HANGERS, DUCTWORK, DAMPERS, AND ALL ASSOCIATED ACCESSORIES.RETURN FAN TO OWNER.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M0.1
5-2420
PHASE 2 - PLAZA & MEZZANINEMECHANICAL DEMOLITION
PLAN
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"PHASE 2 - PLAZA MECHANICAL DEMOLITION PLAN
NORTH
1/8" = 1'-0"PHASE 2 - MEZZANINE MECHANICAL DEMOLITION PLAN
DNUPDNUP
T
DNUPDN
UP
T T T
T
T
T
T
T
T
GRAND RAPIDS COMMUNITY COLLEGE RESERVES THE RIGHT OF FIRST REFUSAL IN OWNERSHIPOF ANY EQUIPMENT ITEMS AND MATERIAL TO BE REMOVED FROM THE BUILDING AND SITE.
INVESTIGATION OF EXISTING HEATING, PLUMBING AND VENTILATION SYSTEMS WILL BE REQUIREDBY THE CONTRACTOR AS PART OF HIS BID PRICE, SO THAT THE EXACT EXTENT OF DEMOLITIONCAN BE ACCURATELY DETERMINED. THE CONTRACTOR'S BID PRICE SHALL ALSO COVERREMOVAL OF SOME PORTIONS OF HEATING, PLUMBING AND VENTILATION SYSTEMS NOTEXPLICITLY SHOWN ON THIS DRAWING, BUT DISCOVERED DURING THE INVESTIGATION PROCESS.THE CONTRACTOR SHALL WORK WITH THE A/E AND THE OWNER TO DETERMINE WHICHPORTIONS OF EXISTING SYSTEMS MUST REMAIN ACTIVE AND WHICH PORTIONS MUST BEDEMOLISHED. REMOVE ALL INACTIVE DUCTWORK AND PIPING TO THE NEAREST ACTIVE MAINS.DUCTWORK SHALL BE CAPPED AND SEALED AIRTIGHT AT TERMINATION POINTS. PIPING SHALL BECAPPED AT TERMINATION POINTS.
ALL PIPING AND EQUIPMENT SHOWN DASHED SHALL BE REMOVED OR RELOCATED UNLESSOTHERWISE NOTED. PROTECT EXISTING WORK WHICH IS TO REMAIN IN PLACE FOR REUSE WITHTEMPORARY COVERS, SHORING, BRACING, AND SUPPORTS. VERIFY LOCATIONS OF AND PROTECTEXISTING INTERIOR ELECTRICAL AND MECHANICAL UTILITIES AND SERVICES, EXCEPT WHEREINDICATED OTHERWISE. ALL MATERIALS AND EQUIPMENT REMOVED, AND NOT REUSED SHALLBECOME PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE OWNERSPROPERTY. THE OWNER RESERVES THE RIGHT TO SALVAGE PARTS FROM ALL MECHANICALEQUIPMENT BEFORE REMOVAL FROM THE SITE. ALL MATERIALS AND EQUIPMENT REQUIRINGREMOVAL AND RELOCATION FOR REUSE SHALL BE CAREFULLY REMOVED AND STORED TOPREVENT DAMAGE AND REINSTALLED AS THE WORK PROGRESSES.
CONTRACTOR TO FIELD VERIFY ACTUAL LOCATION AND SIZES OF EXISTING PIPING, DUCTWORK,EQUIPMENT AND SUPPORTS.
PATCH AND REPAIR ALL WALL, FLOOR AND CEILING OPENINGS DUE TO DEMOLITION WHICH ARENOT BE REUSED TO MATCH EXISTING CONSTRUCTION.
CONTRACTOR SHALL DRAIN EXISTING SYSTEMS AS REQUIRED FOR DEMOLITION, AND SHALL BERESPONSIBLE FOR FILLING, TESTING AND STARTUP OF SYSTEMS UPON COMPLETION.CONTRACTOR SHALL MAINTAIN OWNER'S CHEMICAL TREATMENT PROGRAM.
IF ASBESTOS MATERIAL IS ENCOUNTERED IT WILL BE REMOVED BY OWNER.
MODIFICATIONS TO ROOFING SYSTEM FOR DEMOLITION OR INSTALLATION OF EQUIPMENT SHALLBE DONE BY THIS CONTRACTOR. WORK SHALL MAINTAIN OWNER'S ROOFING WARRANTY.
REFER TO SPECIFICATION SECTION 02 41 19 SELECTIVE DEMOLITION FOR A LIST OF ITEMS TO BEREMOVED AND RETURNED TO THE OWNER
ALL PLUMBING PIPING AS SHOWN SHALL REMAIN. GAS PIPING SHALL BE REMOVED AS NOTED ANDSHOWN.
GENERAL MECHANICAL DEMOLITION NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
M
11
4
6
7
9
A B C D F G H L
12
3
10"x10"
12"x8"
10"x6"
12"x8"
12"x6"
20"x10"
15"x8"
60"x15"
38"x14"
18"x8"30"x12" 22"x8"
12"x10" SA
12"x10" SA
20"x16" SA20"x16" SA
20"x10" SA
20"x10" SA
16"x12" SA
16"x12" SA
20"x10" SA
20"x10" SA
12"x10" SA
12"x10" SA8"ø
8"ø
8"ø
8"ø
05 05050505050505
05
05 05 05 05 05 05
05
12
12
1212
12
04 04
04
04
04
04
04 04
04
04
11
1111
11
1111
11
11
11
11
01
01
01
01
01
01
01
01
01
0101
01 01 01
01
0101
01
01
01
01 01
01 0101
01
01
01
01
3/4" HWS&R, TYP. OFALL CONVECTORS
3/4" HWS&R, TYP. OFALL CONVECTORS
3/4" HWS&R, TYP.OF ALL FT
3/4" HWS&R, TYP.OF ALL FT
1" HW
1" HW
1" HW
1" HW
1" HW
1" HW
1" HW
SHOWN FROMLEFT TO RIGHT2" CW TO REMAIN3" GAS TO BE REMOVED3" CGS TO BE REMOVED3" CGR TO BE REMOVED1.1/2" HW TO REMAIN
SHOWN FROMTOP TO BOTTOM4" VENT TO REMAIN4" SAN TO REMAIN4" STORM TO REMAIN1.1/4" HW TO REMAIN2" CW TO REMAIN1.1/4" HW RECIRC TO REMAIN1.1/4" HWS TO BE REMOVED1.1/4" HWR TO BE REMOVED
RA DUCT TOBE REMOVED
HWS(3) 4" C.I.F.D.
TO REMAIN, TYP.
TO REMAIN, TYP.
01REMOVE DUCTWORK, HANGERS, INSULATION, GRILLES, DIFFUSERS, DAMPERS, AND ALL RELATEDACCESSORIES AS SHOWN. NOTE: ALL SIDEWALL RA GRILLES TO REMAIN.
MECHANICAL DEMOLITION KEYNOTES:
02REMOVE AIR HANDLING UNIT, DAMPERS, CONTROLS, ASSOCIATED PIPING, VALVES, & ALL RELATEDACCESSORIES FOR A COMPLETE REMOVAL OF EXISTING AIR HANDLING SYSTEM.
03REMOVE AS MUCH EXISTING UNDERGROUND CHILLED WATER PIPING UNDERGROUND AS POSSIBLE. CAP ANDABANDON REMAINING. REFER TO ARCHITECTURAL PLANS FOR LOCATION OF CONCRETE REMOVAL NEAREXISTING CHILLER.
04REMOVE EXISTING HYDRONIC PIPING, SUPPORTS, HANGERS, INSULATION, VALVES, AND ALL RELATEDACCESSORIES.
05EXISTING FINNED TUBE TO REMAIN. CONTRACTOR SHALL REMOVE EXISTING MONOFLO FITTINGS. REMOVE ASMUCH PIPING EXISTING PIPING AS POSSIBLE. PREP PIPE TO RECONNECT WITH NEW. REFER TO NEW HYDRONICPIPING PLANS AND DETAILS FOR MORE INFORMATION.
06REMOVE EXISTING CHILLER, CONTROLS, ASSOCIATED PIPING, AND ALL RELATED ACCESSORIES FOR ACOMPLETE REMOVAL.
07REMOVE EXISTING SHEET METAL ASSOCIATED WITH OUTDOOR INTAKE AREAWAY AND ASSOCIATED OADAMPERS. SEE HVAC PLANS FOR MORE INFORMATION.
08REMOVE EXISTING LOUVER AND ALL ASSOCIATED ACCESSORIES. REFER TO ARCH. PLANS FOR MOREINFORMATION/.
09REMOVE EXISTING PUMPS, MOTORS, CONTROLS, & ALL RELATED ACCESSORIES. RETURN PUMPS & MOTORS TOOWNER.
10REMOVE AIR SEPARATOR, EXPANSION TANK, AND ALL OTHER EQUIPMENT ASSOCIATED WITH THE CHWSYSTEM.
11REMOVE EXISTING DUAL DUCT BOX, CONTROLS, HANGERS, VALVES, AND ALL RELATED ACCESSORIES. IFPNEUMATIC TUBING IS PRESENT, REMOVE ALL PNEUMATIC TUBING. REMOVE EXISTING SENSOR/THERMOSTATASSOCIATED WITH DUAL DUCT BOX. REUSE EXISTING LOCATION FOR NEW SENSOR. IF LOCATION CANNOT BEREUSED, PATCH TO MATCH EXISTING.
12EXISTING CONVECTOR TO REMAIN. RECONNECT WITH NEW HYDRONIC PIPING. REFER TO HYDRONIC PIPINGPLANS AND DETAILS FOR MORE INFORMATION.
13REMOVE EXISTING CONDENSING UNIT, REFRIGERANT PIPING, CURB, AND ALL RELATED ACCESSORIES. RETURNUNIT TO OWNER.
14REMOVE EXISTING NATURAL GAS METER SET AND APPURTENANCES. COORDINATE DEMOLITION AND NEWMETER SET ROUGH IN REQUIREMENTS WITH UTILITY PURVEYOR (DTE ENERGY CONTACT: BRAD LEITER [email protected]).
15REMOVE EXISTING NATURAL GAS PIPING AND ASSOCIATED VALVES, FITTINGS, AND HANGERS FROM METERSET TO PENTHOUSE. FIELD VERIFY SIZE AND ACTUAL LOCATION.
16REMOVE EXISTING BOILER, CONTROLS, PIPING, PUMPS, TANKS, VALVES, VENTING /INTAKE, AND ALL RELATEDACCESSORIES FOR A COMPLETE REMOVAL OF THE SYSTEM.
17REMOVE EXISTING EXHAUST FAN, HANGERS, DUCTWORK, DAMPERS, AND ALL ASSOCIATED ACCESSORIES.RETURN FAN TO OWNER.
M
11
4
6
7
9
1
A B C D F G H L
12
3
FD FD
6" ST
30"x14"
30"x14"
34"x14"
32"x14"
28"x12" 28"x10"
24"x8"
14"x6"
24"x14" 24"x12" 20"x8"
18"x12"
8"ø
12"x8"
8"ø
24"x12"
18"x10"
18"x10"
10"x10"10"x10"
12"ø
24"x12"
7"ø
7"ø
15"x6"
10"x9"
12
12
12
12
12
05
05 05 05 05 05 05
05
05
0505050505
05
1111 11
11
11
11
11 1111
040404
04
04
04
04 04
04
04
01
01
01
01
01
01
01
0101
01
01
01
01
01
01
01
01
01
01
01
01
01
01 01
3/4" HWS&R, TYP.OF ALL FT
3/4" HWS&R, TYP.OF ALL FT
3/4" HWS&R, TYP. OFALL CONVECTORS
3/4" HWS&R, TYP. OFALL CONVECTORS
1" HW
1" HW
1" HW
1" HW
1" HW1" HW
1" HW
1" HW
SHOWN FROMLEFT TO RIGHT2" CW TO REMAIN3" GAS TO BE REMOVED3" CGS TO BE REMOVED3" CGR TO BE REMOVED1.1/2" HW TO REMAIN
SHOWN FROMTOP TO BOTTOM4" VENTTO REMAIN4" SAN TO REMAIN4" STORM TO REMAIN1.1/4" HW TO REMAIN2" CW TO REMAIN1.1/4" HW TO REMAIN1.1/2" HWS TO BE REMOVED1.1/2" HWR TO BE REMOVED
RA DUCT TOBE REMOVED
SA DUCT TO BEREMOVED
TO REMAIN, TYP
TO REMAIN, TYP
HWS(3) 4" C.I.F.D.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M0.2
5-2420
PHASE 2 - SECOND & THIRDFLOOR MECHANICAL
DEMOLITION PLAN
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"PHASE 2 - THIRD FLOOR MECHANICAL DEMOLITION PLAN
NORTH
1/8" = 1'-0"PHASE 2 - SECOND FLOOR MECHANICAL DEMOLITION PLAN
DNUP
DNUP
T
T T
T
T
T
T
DNUPDN UP
GRAND RAPIDS COMMUNITY COLLEGE RESERVES THE RIGHT OF FIRST REFUSAL IN OWNERSHIPOF ANY EQUIPMENT ITEMS AND MATERIAL TO BE REMOVED FROM THE BUILDING AND SITE.
INVESTIGATION OF EXISTING HEATING, PLUMBING AND VENTILATION SYSTEMS WILL BE REQUIREDBY THE CONTRACTOR AS PART OF HIS BID PRICE, SO THAT THE EXACT EXTENT OF DEMOLITIONCAN BE ACCURATELY DETERMINED. THE CONTRACTOR'S BID PRICE SHALL ALSO COVERREMOVAL OF SOME PORTIONS OF HEATING, PLUMBING AND VENTILATION SYSTEMS NOTEXPLICITLY SHOWN ON THIS DRAWING, BUT DISCOVERED DURING THE INVESTIGATION PROCESS.THE CONTRACTOR SHALL WORK WITH THE A/E AND THE OWNER TO DETERMINE WHICHPORTIONS OF EXISTING SYSTEMS MUST REMAIN ACTIVE AND WHICH PORTIONS MUST BEDEMOLISHED. REMOVE ALL INACTIVE DUCTWORK AND PIPING TO THE NEAREST ACTIVE MAINS.DUCTWORK SHALL BE CAPPED AND SEALED AIRTIGHT AT TERMINATION POINTS. PIPING SHALL BECAPPED AT TERMINATION POINTS.
ALL PIPING AND EQUIPMENT SHOWN DASHED SHALL BE REMOVED OR RELOCATED UNLESSOTHERWISE NOTED. PROTECT EXISTING WORK WHICH IS TO REMAIN IN PLACE FOR REUSE WITHTEMPORARY COVERS, SHORING, BRACING, AND SUPPORTS. VERIFY LOCATIONS OF AND PROTECTEXISTING INTERIOR ELECTRICAL AND MECHANICAL UTILITIES AND SERVICES, EXCEPT WHEREINDICATED OTHERWISE. ALL MATERIALS AND EQUIPMENT REMOVED, AND NOT REUSED SHALLBECOME PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE OWNERSPROPERTY. THE OWNER RESERVES THE RIGHT TO SALVAGE PARTS FROM ALL MECHANICALEQUIPMENT BEFORE REMOVAL FROM THE SITE. ALL MATERIALS AND EQUIPMENT REQUIRINGREMOVAL AND RELOCATION FOR REUSE SHALL BE CAREFULLY REMOVED AND STORED TOPREVENT DAMAGE AND REINSTALLED AS THE WORK PROGRESSES.
CONTRACTOR TO FIELD VERIFY ACTUAL LOCATION AND SIZES OF EXISTING PIPING, DUCTWORK,EQUIPMENT AND SUPPORTS.
PATCH AND REPAIR ALL WALL, FLOOR AND CEILING OPENINGS DUE TO DEMOLITION WHICH ARENOT BE REUSED TO MATCH EXISTING CONSTRUCTION.
CONTRACTOR SHALL DRAIN EXISTING SYSTEMS AS REQUIRED FOR DEMOLITION, AND SHALL BERESPONSIBLE FOR FILLING, TESTING AND STARTUP OF SYSTEMS UPON COMPLETION.CONTRACTOR SHALL MAINTAIN OWNER'S CHEMICAL TREATMENT PROGRAM.
IF ASBESTOS MATERIAL IS ENCOUNTERED IT WILL BE REMOVED BY OWNER.
MODIFICATIONS TO ROOFING SYSTEM FOR DEMOLITION OR INSTALLATION OF EQUIPMENT SHALLBE DONE BY THIS CONTRACTOR. WORK SHALL MAINTAIN OWNER'S ROOFING WARRANTY.
REFER TO SPECIFICATION SECTION 02 41 19 SELECTIVE DEMOLITION FOR A LIST OF ITEMS TO BEREMOVED AND RETURNED TO THE OWNER
ALL PLUMBING PIPING AS SHOWN SHALL REMAIN. GAS PIPING SHALL BE REMOVED AS NOTED ANDSHOWN.
GENERAL MECHANICAL DEMOLITION NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
M
11
4
6
7
9
A B C D F G H L
12
3
FD
HWS
(3) 4" C.I.
12"x10"
20"x10"
14"x8"
24"x8"
16"x8"
12"x6"
12"x10"
24"x12"
12"x10"
18"x10"
22"x18"
22"x18"
22"x18"
9"ø9"ø
16"x14"
16"x14"
16"x14"
16"x14"
7"ø
60"x14"
38"x14"
32"x14"
30"x12" 24"x12"
32"x14"
30"x12"
12"x8" EA
05 05 05 05 05 05 0505
05
05050505050505
05
05
12
12
12
12
12
0404
04
04
04
04 04
04
04
04
11
11
11
11
11
111101
01 01
0101
01
01
01
01
01
01
01
0101
01
01
01
01
01
01
01
01
01
01
01
01
01
3/4" HWS&R, TYP.OF ALL FT
3/4" HWS&R, TYP.OF ALL FT
3/4" HWS&R, TYP. OFALL CONVECTORS
3/4" HWS&R, TYP. OFALL CONVECTORS
1" HW1" HW
1" HW
1" HW
1" HW1" HW
1" HW
1" HW
SHOWN FROMLEFT TO RIGHT2" CW TO REMAIN3" GAS TO BE REMOVED3" CGS TO BE REMOVED3" CGR TO BE REMOVED1.1/2" HW TO REMAIN
SHOWN FROMTOP TO BOTTOM4" VENT TO REMAIN4" VENT TO REMAIN4" STORM TO REMAIN1" HW TO REMAIN2" CW TO REMAIN1" HW TO REMAIN1" HWS TO BE REMOVED1" HWR TO BE REMOVED
TO REMAIN, TYP.
TO REMAIN, TYP.
TO REMAIN, TYP.
M
11
4
6
7
9
A B C D F G H L
12
3
FD
HWS
(3) 4" C.I.
60"x16"
14"x8"
12"x6"
20"x14"
12"x8"
12"x8"
21"x16"
14"x6"
10"x4"
10"x4"
10"x5" 10"x6"
16"x8"
12"x6"
16"x8"
10"x5"
44"x12"24"x10"
44"x10"24"x10"
12"ø12"ø
12"x6"
16"x8"22"x8"
16"x8"
12"x6"
16"x8"
12"x4"
24"x8"24"x8"
12"x8" EA
05 05050505050505
0505 0505 05 05 05 05
12
12
1212
12
11
11 11
1111
11
11
11
11
11
04
04
04
04
04
04
04 04
04
04
04
0404
01
01
11
01
01
0101
01
01
010101
01
01
01
01
0101
01
0101
01
01
01
01
0101 01
01
3/4" HWS&R, TYP.OF ALL FT
3/4" HWS&R, TYP. OFALL CONVECTORS
3/4" HWS&R, TYP.OF ALL FT
3/4" HWS&R, TYP.OF ALL FT
1" HW
1" HW
1" HW
1" HW
1" HW
1" HW
1" HW
1" HW
1" HW 1" HW
1" HW
SHOWN FROMLEFT TO RIGHT1.1/2" CW TO REMAIN3" GAS TO BE REMOVED3" CGS TO BE REMOVED3" CGR TO BE REMOVED1.1/2" HW TO REMAIN
SHOWN FROMTOP TO BOTTOM4" C.I. TO REMAIN4" C.I. TO REMAIN1" HW TO REMAIN1.1/2" CW TO REMAIN1" HW TO REMAIN1" HWS TO BE REMOVED1" HWR TO BE REMOVED
01REMOVE DUCTWORK, HANGERS, INSULATION, GRILLES, DIFFUSERS, DAMPERS, AND ALL RELATEDACCESSORIES AS SHOWN. NOTE: ALL SIDEWALL RA GRILLES TO REMAIN.
MECHANICAL DEMOLITION KEYNOTES:
02REMOVE AIR HANDLING UNIT, DAMPERS, CONTROLS, ASSOCIATED PIPING, VALVES, & ALL RELATEDACCESSORIES FOR A COMPLETE REMOVAL OF EXISTING AIR HANDLING SYSTEM.
03REMOVE AS MUCH EXISTING UNDERGROUND CHILLED WATER PIPING UNDERGROUND AS POSSIBLE. CAP ANDABANDON REMAINING. REFER TO ARCHITECTURAL PLANS FOR LOCATION OF CONCRETE REMOVAL NEAREXISTING CHILLER.
04REMOVE EXISTING HYDRONIC PIPING, SUPPORTS, HANGERS, INSULATION, VALVES, AND ALL RELATEDACCESSORIES.
05EXISTING FINNED TUBE TO REMAIN. CONTRACTOR SHALL REMOVE EXISTING MONOFLO FITTINGS. REMOVE ASMUCH PIPING EXISTING PIPING AS POSSIBLE. PREP PIPE TO RECONNECT WITH NEW. REFER TO NEW HYDRONICPIPING PLANS AND DETAILS FOR MORE INFORMATION.
06REMOVE EXISTING CHILLER, CONTROLS, ASSOCIATED PIPING, AND ALL RELATED ACCESSORIES FOR ACOMPLETE REMOVAL.
07REMOVE EXISTING SHEET METAL ASSOCIATED WITH OUTDOOR INTAKE AREAWAY AND ASSOCIATED OADAMPERS. SEE HVAC PLANS FOR MORE INFORMATION.
08REMOVE EXISTING LOUVER AND ALL ASSOCIATED ACCESSORIES. REFER TO ARCH. PLANS FOR MOREINFORMATION/.
09REMOVE EXISTING PUMPS, MOTORS, CONTROLS, & ALL RELATED ACCESSORIES. RETURN PUMPS & MOTORS TOOWNER.
10REMOVE AIR SEPARATOR, EXPANSION TANK, AND ALL OTHER EQUIPMENT ASSOCIATED WITH THE CHWSYSTEM.
11REMOVE EXISTING DUAL DUCT BOX, CONTROLS, HANGERS, VALVES, AND ALL RELATED ACCESSORIES. IFPNEUMATIC TUBING IS PRESENT, REMOVE ALL PNEUMATIC TUBING. REMOVE EXISTING SENSOR/THERMOSTATASSOCIATED WITH DUAL DUCT BOX. REUSE EXISTING LOCATION FOR NEW SENSOR. IF LOCATION CANNOT BEREUSED, PATCH TO MATCH EXISTING.
12EXISTING CONVECTOR TO REMAIN. RECONNECT WITH NEW HYDRONIC PIPING. REFER TO HYDRONIC PIPINGPLANS AND DETAILS FOR MORE INFORMATION.
13REMOVE EXISTING CONDENSING UNIT, REFRIGERANT PIPING, CURB, AND ALL RELATED ACCESSORIES. RETURNUNIT TO OWNER.
14REMOVE EXISTING NATURAL GAS METER SET AND APPURTENANCES. COORDINATE DEMOLITION AND NEWMETER SET ROUGH IN REQUIREMENTS WITH UTILITY PURVEYOR (DTE ENERGY CONTACT: BRAD LEITER [email protected]).
15REMOVE EXISTING NATURAL GAS PIPING AND ASSOCIATED VALVES, FITTINGS, AND HANGERS FROM METERSET TO PENTHOUSE. FIELD VERIFY SIZE AND ACTUAL LOCATION.
16REMOVE EXISTING BOILER, CONTROLS, PIPING, PUMPS, TANKS, VALVES, VENTING /INTAKE, AND ALL RELATEDACCESSORIES FOR A COMPLETE REMOVAL OF THE SYSTEM.
17REMOVE EXISTING EXHAUST FAN, HANGERS, DUCTWORK, DAMPERS, AND ALL ASSOCIATED ACCESSORIES.RETURN FAN TO OWNER.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M0.3
5-2420
PHASE 2 - FOURTH & FIFTHFLOOR MECHANICAL
DEMOLITION PLAN
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"PHASE 2 - FOURTH FLOOR MECHANICAL DEMOLITION PLAN
NORTH
1/8" = 1'-0"PHASE 2 - FIFTH FLOOR MECHANICAL DEMOLITION PLAN
DNUPDNUP
DNDN
GRAND RAPIDS COMMUNITY COLLEGE RESERVES THE RIGHT OF FIRST REFUSAL IN OWNERSHIPOF ANY EQUIPMENT ITEMS AND MATERIAL TO BE REMOVED FROM THE BUILDING AND SITE.
INVESTIGATION OF EXISTING HEATING, PLUMBING AND VENTILATION SYSTEMS WILL BE REQUIREDBY THE CONTRACTOR AS PART OF HIS BID PRICE, SO THAT THE EXACT EXTENT OF DEMOLITIONCAN BE ACCURATELY DETERMINED. THE CONTRACTOR'S BID PRICE SHALL ALSO COVERREMOVAL OF SOME PORTIONS OF HEATING, PLUMBING AND VENTILATION SYSTEMS NOTEXPLICITLY SHOWN ON THIS DRAWING, BUT DISCOVERED DURING THE INVESTIGATION PROCESS.THE CONTRACTOR SHALL WORK WITH THE A/E AND THE OWNER TO DETERMINE WHICHPORTIONS OF EXISTING SYSTEMS MUST REMAIN ACTIVE AND WHICH PORTIONS MUST BEDEMOLISHED. REMOVE ALL INACTIVE DUCTWORK AND PIPING TO THE NEAREST ACTIVE MAINS.DUCTWORK SHALL BE CAPPED AND SEALED AIRTIGHT AT TERMINATION POINTS. PIPING SHALL BECAPPED AT TERMINATION POINTS.
ALL PIPING AND EQUIPMENT SHOWN DASHED SHALL BE REMOVED OR RELOCATED UNLESSOTHERWISE NOTED. PROTECT EXISTING WORK WHICH IS TO REMAIN IN PLACE FOR REUSE WITHTEMPORARY COVERS, SHORING, BRACING, AND SUPPORTS. VERIFY LOCATIONS OF AND PROTECTEXISTING INTERIOR ELECTRICAL AND MECHANICAL UTILITIES AND SERVICES, EXCEPT WHEREINDICATED OTHERWISE. ALL MATERIALS AND EQUIPMENT REMOVED, AND NOT REUSED SHALLBECOME PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE OWNERSPROPERTY. THE OWNER RESERVES THE RIGHT TO SALVAGE PARTS FROM ALL MECHANICALEQUIPMENT BEFORE REMOVAL FROM THE SITE. ALL MATERIALS AND EQUIPMENT REQUIRINGREMOVAL AND RELOCATION FOR REUSE SHALL BE CAREFULLY REMOVED AND STORED TOPREVENT DAMAGE AND REINSTALLED AS THE WORK PROGRESSES.
CONTRACTOR TO FIELD VERIFY ACTUAL LOCATION AND SIZES OF EXISTING PIPING, DUCTWORK,EQUIPMENT AND SUPPORTS.
PATCH AND REPAIR ALL WALL, FLOOR AND CEILING OPENINGS DUE TO DEMOLITION WHICH ARENOT BE REUSED TO MATCH EXISTING CONSTRUCTION.
CONTRACTOR SHALL DRAIN EXISTING SYSTEMS AS REQUIRED FOR DEMOLITION, AND SHALL BERESPONSIBLE FOR FILLING, TESTING AND STARTUP OF SYSTEMS UPON COMPLETION.CONTRACTOR SHALL MAINTAIN OWNER'S CHEMICAL TREATMENT PROGRAM.
IF ASBESTOS MATERIAL IS ENCOUNTERED IT WILL BE REMOVED BY OWNER.
MODIFICATIONS TO ROOFING SYSTEM FOR DEMOLITION OR INSTALLATION OF EQUIPMENT SHALLBE DONE BY THIS CONTRACTOR. WORK SHALL MAINTAIN OWNER'S ROOFING WARRANTY.
REFER TO SPECIFICATION SECTION 02 41 19 SELECTIVE DEMOLITION FOR A LIST OF ITEMS TO BEREMOVED AND RETURNED TO THE OWNER
ALL PLUMBING PIPING AS SHOWN SHALL REMAIN. GAS PIPING SHALL BE REMOVED AS NOTED ANDSHOWN.
GENERAL MECHANICAL DEMOLITION NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
M
11
4
6
7
9
A B C D F G H L
12
3
ACCESSDOOR
DOORLOCATION
ACCESSDOOR
12"ø SA
12"ø SA
20"x12" SA
20"x12" SA
16"x12"10"ø SA
16"x12" SA10"ø SA
20"x12"
20"x12"
20"x12"
20"x12" SA
10"ø SA
20"x12"
20"x12"
20"x12"
12"x12" SA
12"x12" SA
10"ø
10"ø SA
12"x10"12"x10" 10"x10"
10"x10"
10"x10"
12"x12"
12"x12"
12"x12"12"x12"
10"x10" SA
10"ø SA
20"x12" SA
10"ø10"ø SA
10"x10"
10"x10"
10"x10"
10"x8"
10"x8"
14"x12"
14"x12"
14"x12"10"x10"
12"x8" EA
36"x14"
40"x16"
11
11 11 11
11
11
11
11
11
11 11
11
05 05 05 05 05 05 0505
05050505050505
05
12
12
12
12
12
01
01
01
01
01 01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01 01
01
01
01
01
01
01
0101
01 01
0101
01
01
0101
01
3/4" HWS&R, TYP.OF ALL FT
3/4" HWS&R, TYP. OFALL CONVECTORS
3/4" HWS&R, TYP. OFALL CONVECTORS
3/4" HWS&R, TYP.OF ALL FT
SHOWN FROMTOP TO BOTTOM4" VENT TO REMAIN4" SAN TO REMAIN4" STORM TO REMAIN1" HW TO REMAIN1.1/2" CW TO REMAIN1" HW RECIRC TO REMAIN1" HWS TO BE REMOVED1" HWR TO BE REMOVED
SHOWN FROMTOP TO BOTTOM1.1/2" CW TO REMAIN3" GAS TO BE REMOVED3" CGS TO BE REMOVED3" CGR TO BE REMOVED1.1/2" HW TO REMAIN
11
4
6
7
9
A B C D F G H L
12
3
48"x30" SA
88"x28"
48"x12"
60"x26"
1702
02
02
17
13CONTRACTOR SHALL PATCHROOF PENETRATIONS TOMATCH EXISTING.
17
48"x30" SA64"x22"
EXISTINGBOILER
09
16
EXISTING DHWHEATER TO REMAIN
01
01
01
01
01
REMOVE EXISTING HUMIDIFIER ANDRELATED ACCESSORIES
3" CHWS&R2 1/2" HWS&R
2 1/2" HWS&R
3" CHWS&R
04
04
04 04
08
16"x20"
16"x20"
08
08
EXISTING 18"W x 36"H LOUVER TO REMAIN.CONTRACTOR SHALL REMOVE EXISTINGMOTORIZED DAMPER AND INSTALL NEW.SEE NEW PLANS FOR MORE INFO. 08
F.D.
01REMOVE DUCTWORK, HANGERS, INSULATION, GRILLES, DIFFUSERS, DAMPERS, AND ALL RELATEDACCESSORIES AS SHOWN. NOTE: ALL SIDEWALL RA GRILLES TO REMAIN.
MECHANICAL DEMOLITION KEYNOTES:
02REMOVE AIR HANDLING UNIT, DAMPERS, CONTROLS, ASSOCIATED PIPING, VALVES, & ALL RELATEDACCESSORIES FOR A COMPLETE REMOVAL OF EXISTING AIR HANDLING SYSTEM.
03REMOVE AS MUCH EXISTING UNDERGROUND CHILLED WATER PIPING UNDERGROUND AS POSSIBLE. CAP ANDABANDON REMAINING. REFER TO ARCHITECTURAL PLANS FOR LOCATION OF CONCRETE REMOVAL NEAREXISTING CHILLER.
04REMOVE EXISTING HYDRONIC PIPING, SUPPORTS, HANGERS, INSULATION, VALVES, AND ALL RELATEDACCESSORIES.
05EXISTING FINNED TUBE TO REMAIN. CONTRACTOR SHALL REMOVE EXISTING MONOFLO FITTINGS. REMOVE ASMUCH PIPING EXISTING PIPING AS POSSIBLE. PREP PIPE TO RECONNECT WITH NEW. REFER TO NEW HYDRONICPIPING PLANS AND DETAILS FOR MORE INFORMATION.
06REMOVE EXISTING CHILLER, CONTROLS, ASSOCIATED PIPING, AND ALL RELATED ACCESSORIES FOR ACOMPLETE REMOVAL.
07REMOVE EXISTING SHEET METAL ASSOCIATED WITH OUTDOOR INTAKE AREAWAY AND ASSOCIATED OADAMPERS. SEE HVAC PLANS FOR MORE INFORMATION.
08REMOVE EXISTING LOUVER AND ALL ASSOCIATED ACCESSORIES. REFER TO ARCH. PLANS FOR MOREINFORMATION/.
09REMOVE EXISTING PUMPS, MOTORS, CONTROLS, & ALL RELATED ACCESSORIES. RETURN PUMPS & MOTORS TOOWNER.
10REMOVE AIR SEPARATOR, EXPANSION TANK, AND ALL OTHER EQUIPMENT ASSOCIATED WITH THE CHWSYSTEM.
11REMOVE EXISTING DUAL DUCT BOX, CONTROLS, HANGERS, VALVES, AND ALL RELATED ACCESSORIES. IFPNEUMATIC TUBING IS PRESENT, REMOVE ALL PNEUMATIC TUBING. REMOVE EXISTING SENSOR/THERMOSTATASSOCIATED WITH DUAL DUCT BOX. REUSE EXISTING LOCATION FOR NEW SENSOR. IF LOCATION CANNOT BEREUSED, PATCH TO MATCH EXISTING.
12EXISTING CONVECTOR TO REMAIN. RECONNECT WITH NEW HYDRONIC PIPING. REFER TO HYDRONIC PIPINGPLANS AND DETAILS FOR MORE INFORMATION.
13REMOVE EXISTING CONDENSING UNIT, REFRIGERANT PIPING, CURB, AND ALL RELATED ACCESSORIES. RETURNUNIT TO OWNER.
14REMOVE EXISTING NATURAL GAS METER SET AND APPURTENANCES. COORDINATE DEMOLITION AND NEWMETER SET ROUGH IN REQUIREMENTS WITH UTILITY PURVEYOR (DTE ENERGY CONTACT: BRAD LEITER [email protected]).
15REMOVE EXISTING NATURAL GAS PIPING AND ASSOCIATED VALVES, FITTINGS, AND HANGERS FROM METERSET TO PENTHOUSE. FIELD VERIFY SIZE AND ACTUAL LOCATION.
16REMOVE EXISTING BOILER, CONTROLS, PIPING, PUMPS, TANKS, VALVES, VENTING /INTAKE, AND ALL RELATEDACCESSORIES FOR A COMPLETE REMOVAL OF THE SYSTEM.
17REMOVE EXISTING EXHAUST FAN, HANGERS, DUCTWORK, DAMPERS, AND ALL ASSOCIATED ACCESSORIES.RETURN FAN TO OWNER.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M0.4
5-2420
PHASE 2 - SIXTH FLOOR &PENTHOUSE MECHANICAL
DEMOLITION PLAN
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"PHASE 2 - SIXTH FLOOR MECHANICAL DEMOLITION FLOOR PLAN
NORTH
1/8" = 1'-0"PHASE 2 - PENTHOUSE MECHANICAL DEMOLITION PLAN
UP
D DD
D
M
66"x36" OA
48"x24" EA
11
4
6
7
9
1
A B C D F G H L
12
3
LOBBY002
VESTIBULE001
MECHANICAL003
FIRE PUMP004
66"x36" OA
48"x24" SA
48"x24" LINED SA
66"x24" RA
48"x30" SA WITH 1" DW UPSEE DWG. M2.1 FORCONTINUATION UP
48"x36" RA WITH X" DW UPSEE DWG. M2.1 FORCONTINUATION UP
L-18'-6" W x 7'-6" HREFER TO ARCH.DWG.'S FOR ELEV.
8'-2" W x 6'-0"H X 9'-0" DRELIEF AIR DISCHARGEPLENUM. CONTRACTORSHALL VERIFY SIZEPRIOR TO FABRICATION.
3' - 1"
CONTRACTORSHALL INSTALLSOLID BAFFLEWITHIN PLENUMTO SEPARATE ASSHOWN. SEALAIRTIGHT, TYP.
AHU-2
48"x36" OA
24"x48" RA
36"x20" LINED SA
36"x20" LINED SA 48"x24" RA WITH X" DW UPSEE DWG. M2.1 FORCONTINUATION UP
36"x20" SA WITH 1" DW UPSEE DWG. M2.1 FORCONTINUATION UP
AHU-1
EF-3
EF-2
L-22'-8" W x 1'-4" HREFER TO ARCHITECTURALDRAWINGS FOR ELEVATION.
TRANSITION FROMLOUVER TO PLENUM
WITH ECCENTRICFITTING FLAT ON
BOTTOM.
STORAGE005
INSTALL BIRDSCREENOVER INLET OF DUCT
INSTALL BIRDSCREENOVER END OF DUCT
INTERLOCKMOTORIZED
DAMPER W/ EF-2
INTERLOCKMOTORIZEDDAMPER W/ EF-3
INSTALL BIRDSCREENOVER INLET OF DUCT
FD
FD
FD
12"x12" OA
10"x10" OA
12"x12" EA
12"x12" EA
10"x10" OA
INSTALL BIRDSCREENOVER INLET OF FAN
EF-1
8"x8" SAS-2
200 CFM
R-6
200 CFM
10"x6" RA
8"ø SA
12"x12" SA
8"x12" SA
8"x12" SA
12"x12" RA
8"x12" RA
16"x6" SA
16"x6" SA
16"x6" RA
16"x6" RA
12"x12" RA
4"ø SA
VAV-1-19800 CFM
VAV-1-20200 CFM
1" D.W.
1" D.W.
1" D.W.
02
01
01
03
1" D.W.
1" D.W.
CONNECT NEW OA DUCTSTO EXISTING INTAKE AREAWAY.BLOCK OFF EXISTING OPENINGWITH SHEET METAL. REFER TOSPECIFICATION FOR INSULATEREQUIREMENTS. SEALAIRTIGHT, TYP.
DUCT FITTINGS AT SAPLENUM SHALL CONNECT TOPERFORATED INNER LINER.
MECHANICAL CONTRACTOR SHALLCONSTRUCT 4'-8"L x 8'-4"W x 4'-0"HWITH 4" DW INTERNALLY LINEDPERFORATED DOUBLE WALLDISCHARGE PLENUM.FIELD VERIFY SIZE PRIOR TOFABRICATION & INSTALLATION.
DUCT FITTINGS AT SAPLENUM SHALL CONNECT TOPERFORATED INNER LINER.
MECHANICAL CONTRACTOR SHALLCONSTRUCT 4'-2"L x 6'-8"W x 5'-0"HWITH 4" DW INTERNALLY LINEDPERFORATED DOUBLE WALLDISCHARGE PLENUM.FIELD VERIFY SIZE PRIOR TOFABRICATION & INSTALLATION.
ø8"
S
OA DUCT DROP TO AHUSHALL MATCH INLET SIZE,FIELD VERIFY.
RA DUCT DROP TO AHUSHALL MATCH INLET SIZE,FIELD VERIFY.
24"x4
8" R
A
RA DUCT DROP TO AHUSHALL MATCH INLET SIZE,
FIELD VERIFY.
OA DUCT DROP TO AHUSHALL MATCH INLET SIZE,FIELD VERIFY.
EA DISCHARGEDUCT CONNECTTO EXIST. LOUVER.
MECHANICAL CONTRACTOR SHALLCONSTRUCT 4'-8"L x 8'-4"W x 3'-10"HWITH 4" DW INTERNALLY LINEDPERFORATED DOUBLE WALLDISCHARGE PLENUM.FIELD VERIFY SIZE PRIOR TOFABRICATION & INSTALLATION.
COORDINATELOCATION OF
AHU-1 WITHEXISTING SUMP
INSTALL BIRDSCREENOVER END OF DUCT
INTERLOCKMOTORIZED
DAMPER W/ EF-1
T
T
T
REVERSE ACTINGAVERAGING THERMOSTATTO ENERGIZE EF-3 & OPEN
MOTORIZED DAMPER WHENTHE SPACE TEMPERATURE
EXCEEDS SETPOINT
REVERSE ACTINGAVERAGING T-STAT
TO ENERGIZE EF-2 &OPEN MOTORIZED
DAMPER WHEN THESPACE
TEMP.EXCEEDSSETPOINT
REVERSE ACTINGAVERAGING T-STAT
TO ENERGIZE EF-2 &OPEN MOTORIZED
DAMPER WHEN THESPACE
TEMP.EXCEEDSSETPOINT
SEAL TO EXISTINGAREAWAY AIRTIGHT,TYP.
INSTALL 1" DRAIN INBOTTOM OF LOUVER.CONNECT TO NEARESTFLOOR DRAIN.
SLOPE PLENUMTOWARDS LOUVER FORDRAINAGE, TYP.
2'-8" W x 1'-4"H X 2'-0" DRELIEF AIR DISCHARGEPLENUM. CONTRACTOR
SHALL VERIFY SIZEPRIOR TO
FABRICATION.
DUCT SMOKEDETECTOR, TYP.INSTALL IN SAPLENUM.
DUCT SMOKEDETECTOR, TYP.INSTALL IN RA DUCTDROP TO AHU.
DUCT SMOKEDETECTOR, TYP.INSTALL IN SAPLENUM.
DUCT SMOKEDETECTOR, TYP.INSTALL IN RA DUCTDROP TO AHU.
14"x14" OA
F/SD
F/SD
FIRE/SMOKEDAMPER, TYP.
FIRE/SMOKEDAMPER, TYP.
F/SD
F/SD
ALL SUPPLY, RELIEF, AND RETURN AIR DUCTWORK SHOWN WITH DASHES SHALL BE INTERNALLY LINED DOUBLEWALL DUCTWORK WITH 1" THICK DUCT LINER FOR ROUND AND OVAL SUPPLY DUCT AND 1" THICK DUCT LINERFOR RECTANGULAT SUPPLY AND RETURN DUCT. ALL EXHAUST DUCTWORK SHOWN WITH DASHES SHALL BEACOUSTICALLY LINED SINGLE WALL DUCTWORK UNLESS NOTED OTHERWISE.
ACTUAL LOCATION OF GRILLES AND DIFFUSERS SHALL BE COORDINATED WITH REFLECTED CEILING PLAN. IFTHERE ARE ANY DISCREPANCIES, VERIFY FINAL LOCATION WITH A/E.
INSTALL THERMOSTAT/SENSORS AT 48" A.F.F. TO TOP OF THERMOSTATS/SENSORS UNLESS NOTEDOTHERWISE. ALL THERMOSTATS/SENSORS INSTALLED ON OUTSIDE WALLS SHALL HAVE INSULATEDBACKPLATES.
CONTRACTOR SHALL FIELD VERIFY ALL MECHANICAL EQUIPMENT CONDITIONS PRIOR TO FABRICATION ANDCONNECTION OF HYDRONIC AND DUCTWORK COMPONENTS. REFER TO HYDRONIC SHEETS AND DETAILSHEETS FOR ADDITIONAL INFORMATION.
IN AREAS OF ACOUSTICAL LINED OR DOUBLE WALL DUCTWORK, THE DIMENSIONS LISTED ARE THE FREE AREAWITHIN THE DUCTWORK.
IN AREAS WHERE DUCTWORK IS EXPOSED, ROUTE DUCTWORK AS HIGH AS POSSIBLE UNLESS SPECIFICALLYNOTED ON THE DRAWINGS.
CONTRACTOR SHALL REFER TO CODE COMPLIANCE DRAWING FOR INFORMATION ON RATINGS OF FIRE/SMOKEDAMPERS.
ALL EXHAUST FAN (I.E. NOT ERU EXHAUST) DUCTWORK SHOWN WITH DASHED LINES SHALL BE ACOUSTICALLYLINED DUCTWORK UNLESS NOTED OTHERWISE.
PAINT INTERIOR OF ALL DUCT AT LINEAR SIDEWALL SUPPLY, RETURN, AND EXHAUST DIFFUSERS/GRILLES FLATBLACK.
FLEXIBLE DUCTWORK CORE SHALL BE CLAMPED AND TAPED AT ALL CONNECTIONS AND JOINTS (i.e. ATCONNECTION TO BRANCH DUCTWORK, DIFFUSERS, ETC.). TAPE SHALL MEET REQUIREMENTS OF UL1818-FX. INADDITION, FLEXIBLE DUCTWORK JACKET SHALL BE TAPED AT ALL CONNECTIONS AND JOINTS WITH TAPEMEETING THE ABOVE STATED REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
VERIFY AND MAINTAIN ALL MANUFACTURER'S RECOMMENDED MECHANICAL EQUIPMENT SERVICE CLEARANCES.
ALL MITERED 90 DEGREE ELBOWS SHALL INCLUDE TURNING VANES.
AHU-1, AHU-2, AND AHU-3 SHALL HAVE NEOPRENE ISOLATION PADS EQUAL TO KINETICS MODEL RSP UNDERUNITS IN MECHANICAL ROOM AND PENTHOUSE.
GENERAL HVAC NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
DUCT FITTING LEGEND
TAG
01
02
03
04
05
06
07
08
09
10
11
12
13
14
SR0TR
KS0PTL
SR0PTLR
SROT
SR0PTC
KR0T
SR0PT
SR0TLR
SR0TXLR
SROYR
SR0TCR
SROPTL
SR0TL
FITTING TYPE
SINGLE WALL/ROUND/REDUCING TEE
DOUBLE WALL/SQUARE/90 DEG. INCREASED TAP (FLARED TAP)
SINGLE WALL/ROUND/CONICAL DUCT TAP
SINGLE WALL/ROUND/STRAIGHT TEE
FITTING DESCRIPTION
SINGLE WALL/ROUND/LO-LOSS DUCT TAP W/ REDUCER
DOUBLE WALL/ROUND/STRAIGHT TAP
SINGLE WALL/ROUND/STRAIGHT DUCT TAP
SINGLE WALL/ROUND/REDUCING LO-LOSS TEE
SINGLE WALL/ROUND/REDUCING LO-LOSS 90 DEG. CROSS
SINGLE WALL/ROUND/Y-BRANCH 90 DEG. REDUCING
SINGLE WALL/ROUND/REDUCING CONICAL TEE
SINGLE WALL/ROUND/LO-LOSS DUCT TAP
SINGLE WALL/ROUND/LO-LOSS TEE
SS0PTL SINGLE WALL/SQUARE/90 DEG. INCREASED TAP (FLARED TAP)
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M2.0
5-2420
PHASE 2 - ENLARGED RAMPHVAC PLAN
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/4" = 1'-0"HVAC PLAN RAMP - NEW
DN
DNUPDN
UP
DN
UP
UP
UP
M
S-3
250 CFM
S-4300 CFM
S-7125 CFM
S-12
75 CFMS-4
300 CFM
S-4
300 CFM
S-4
400 CFM
E-4225 CFM
E-5
350 CFM
S-4
350 CFM
11
4
6
7
9
1
A B C D F G H L
12
3
OFFICEM101
CORRM102
MECHM103
JANM104
LOBBYM105
OFFICEM106
OFFICEM107
OPEN OFFICEM108
STORM109 OFFICE
M110OFFICE
M111
OFFICEM112
WORK ROOMM113
ELECM114
MECHM116
MENSM115
LOUNGEM118
WOMENSM117
S-3
275 CFM
S-3
275 CFM
R-10
550 CFMVAV-1-8900 CFM
R-3100 CFM
S-13100 CFM
S-3
200 CFM
R-7
200 CFM
VAV-1-11000 CFM
VAV-1-21000 CFM
S-7
125 CFM
S-7
125 CFM
VAV-1-9250 CFM
VAV-1-10300 CFM
VAV-1-111600 CFM
S-4
400 CFM
S-4
400 CFM
R-13
800 CFM
VAV-1-13300 CFM
VAV-1-12375 CFM R-12
300 CFM
R-12300 CFM
VAV-1-14400 CFM
VAV-1-15875 CFM
S-9
450 CFM
R-9
450 CFM
R-8
400 CFM
VAV-1-16200 CFM
S-15
275 CFM
R-9350 CFM
S-14150 CFM
10"ø SA10"ø SA
13"x10" SA
12"x10" SA12"x6" SA
6"ø SA14"x4" SA
7"ø SA16"ø SA
12"ø SA
9"ø SA 7"ø SA
6"ø SA 10"x8" SA
8"ø SA10"ø SA8"ø SA8"ø SA
10"ø SA
8"ø SA 10"ø SA
10"ø SA
8"ø SA
24"x16" SA
16"ø SA
8"ø SA 10"ø SA10"ø SA8"ø SA
8"ø SA
8"ø SA10"ø SA
8"x8" SA18"x10" SA
10"ø SA
8"ø SA
8"ø SA
16"ø SA
11"x6" SA
11"x6" RA
12"x6" RA
14"x8" RA
10"x8" SA
5"ø SA
6"ø SA
8"ø SA
12"ø SA
13"x13" SA
20"x6" SA16"x16" SA
20"x8" SA
16"x6" SA 16"x6" SA
6"ø SA
10"x10" SA
10"x10" SA
12"x6" SA
6"ø SA
12"x6" SA
6"ø SA16"x6" SA
8"ø SA
12"ø SA
14"x12" SA18"x8" SA
16"x6" SA
10"x10" SA
8"ø SA
8"x10" SA
18"x4" SA
8"x10" SA
12"x12" RA
20"x6" RA
6"x6" RA20"x6" RA
54"x10" RA
38"x14" RA
10"x10" RA 10"x6" RA
10"x6" RA
14"x8" RA
24"x6" RA
12"x6" RA
17"x6" RA24"x6" RA
24"x6" RA
12"x8" RA20"x8" RA
12"x8" RA
24"x6" RA
11"x8" RA16"x6" RA
14"x6" RA
24"x6" RA
12"x6" RA6"x6" EA
10"x10" EA
18"x4" EA
12"x10" EA
8"x10" EA
10"x10" EA
6"x6" EA8"x6" EA
VAV-1-17350 CFM
02 02
02
04
05
06
07
08
09
36"x20"SA DN.
48"x36"RA UP & DN.
48"x24"SA UP & DN.
07
05
05
16"x8" DN.
14"ø SA16"ø SA
7"ø SA
S
S S
S
SS S
S
S
S
18"x10" SA10" DIA. SA
16"ø SA
12"ø SA
E-2
75 CFM
X28S-10
400 CFM
S-10400 CFM
10"x8" RA
FIRE/SMOKEDAMPER, TYP.
F/SD
F/SD
F/SD
F/SD
F/SD
F/SD
ALL SUPPLY, RELIEF, AND RETURN AIR DUCTWORK SHOWN WITH DASHES SHALL BE INTERNALLY LINED DOUBLEWALL DUCTWORK WITH 1" THICK DUCT LINER FOR ROUND AND OVAL SUPPLY DUCT AND 1" THICK DUCT LINERFOR RECTANGULAT SUPPLY AND RETURN DUCT. ALL EXHAUST DUCTWORK SHOWN WITH DASHES SHALL BEACOUSTICALLY LINED SINGLE WALL DUCTWORK UNLESS NOTED OTHERWISE.
ACTUAL LOCATION OF GRILLES AND DIFFUSERS SHALL BE COORDINATED WITH REFLECTED CEILING PLAN. IFTHERE ARE ANY DISCREPANCIES, VERIFY FINAL LOCATION WITH A/E.
INSTALL THERMOSTAT/SENSORS AT 48" A.F.F. TO TOP OF THERMOSTATS/SENSORS UNLESS NOTEDOTHERWISE. ALL THERMOSTATS/SENSORS INSTALLED ON OUTSIDE WALLS SHALL HAVE INSULATEDBACKPLATES.
CONTRACTOR SHALL FIELD VERIFY ALL MECHANICAL EQUIPMENT CONDITIONS PRIOR TO FABRICATION ANDCONNECTION OF HYDRONIC AND DUCTWORK COMPONENTS. REFER TO HYDRONIC SHEETS AND DETAILSHEETS FOR ADDITIONAL INFORMATION.
IN AREAS OF ACOUSTICAL LINED OR DOUBLE WALL DUCTWORK, THE DIMENSIONS LISTED ARE THE FREE AREAWITHIN THE DUCTWORK.
IN AREAS WHERE DUCTWORK IS EXPOSED, ROUTE DUCTWORK AS HIGH AS POSSIBLE UNLESS SPECIFICALLYNOTED ON THE DRAWINGS.
CONTRACTOR SHALL REFER TO CODE COMPLIANCE DRAWING FOR INFORMATION ON RATINGS OF FIRE/SMOKEDAMPERS.
ALL EXHAUST FAN (I.E. NOT ERU EXHAUST) DUCTWORK SHOWN WITH DASHED LINES SHALL BE ACOUSTICALLYLINED DUCTWORK UNLESS NOTED OTHERWISE.
PAINT INTERIOR OF ALL DUCT AT LINEAR SIDEWALL SUPPLY, RETURN, AND EXHAUST DIFFUSERS/GRILLES FLATBLACK.
FLEXIBLE DUCTWORK CORE SHALL BE CLAMPED AND TAPED AT ALL CONNECTIONS AND JOINTS (i.e. ATCONNECTION TO BRANCH DUCTWORK, DIFFUSERS, ETC.). TAPE SHALL MEET REQUIREMENTS OF UL1818-FX. INADDITION, FLEXIBLE DUCTWORK JACKET SHALL BE TAPED AT ALL CONNECTIONS AND JOINTS WITH TAPEMEETING THE ABOVE STATED REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
VERIFY AND MAINTAIN ALL MANUFACTURER'S RECOMMENDED MECHANICAL EQUIPMENT SERVICE CLEARANCES.
ALL MITERED 90 DEGREE ELBOWS SHALL INCLUDE TURNING VANES.
AHU-1, AHU-2, AND AHU-3 SHALL HAVE NEOPRENE ISOLATION PADS EQUAL TO KINETICS MODEL RSP UNDERUNITS IN MECHANICAL ROOM AND PENTHOUSE.
GENERAL HVAC NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
11
4
6
7
9
1
A B C D F G H L
12
3
OFFICEP111
MECHP110
T.P112
OFFICEP116
JANP114
CORRP113
OFFICEP115
OFFICEP117
CONFP104
OFFICEP109
VESTP101
MECHP102
VAULTP107
CORRP108
LOBBYP103
RECEPTP106
MECHANICAL003
VAV-1-4400 CFM
VAV-1-7350 CFM
VAV-1-6200 CFM
VAV-1-3800 CFM
VAV-1-18250 CFM
S-14200 CFM
S-3200 CFM
S-3
200 CFM
S-3200 CFM
S-3200 CFM S-3
350 CFM
S-3
200 CFM
R-3
200 CFM
R-5250 CFM
R-4200 CFM
VAV-1-5200 CFM
R-1
75 CFM
S-12100 CFM
S-3
200 CFM
S-150 CFM
S-8
50 CFM
R-16
400 CFM
R-16400 CFM
S-11400 CFM
S-11400 CFM
R-4200 CFM
R-11200 CFM
R-8400 CFM
R-3150 CFM
S-2150 CFM
S-1
100 CFM
R-3
100 CFM
8"ø SA
10"x8" SA7"ø SA
5"ø SA
6"x6" RA
10"x6" RA
10"x6" RA
12"x4" RA
8"x6" RA
24"x6" RA
16"x8" SA
8"x8" SA
16"x8" SA12"x8" SA8"x8" SA
8"ø SA8"ø SA
12"x10" SA10"x8" SA
10"x8" SA
6"ø SA 7"ø SA
8"x8" SA
6"ø SA
8"ø SA
6"ø SA
12"x6" RA
8"x6" RA
12"x8" RA
6"x6" RA
16"x8" RA
6"x6" RA
16"x8" RA
10"ø SA6"ø SA
12"x8" SA
6"x6" SA
8"ø SA
10"x8" SA
6"x8" SA
16"x8" SA UP
04
36"x20" SAUP & DN.
48"x30" SA WITH1" DW UP & DN.
14
05
11
08S
TOVAV-1-19
48"x24" RAUP & DN.
S
S
S
S
S S
48"x36" RA WITH1" DW UP & DN.
E-1
75 CFM
S
TOVAV-1-1
STOVAV-1-2
FIRE/SMOKEDAMPER, TYP.
F/SD
F/SD
FIRE/SMOKEDAMPER, TYP.
F/SD
F/SD
F/SD
F/SD
DUCT FITTING LEGEND
TAG
01
02
03
04
05
06
07
08
09
10
11
12
13
14
SR0TR
KS0PTL
SR0PTLR
SROT
SR0PTC
KR0T
SR0PT
SR0TLR
SR0TXLR
SROYR
SR0TCR
SROPTL
SR0TL
FITTING TYPE
SINGLE WALL/ROUND/REDUCING TEE
DOUBLE WALL/SQUARE/90 DEG. INCREASED TAP (FLARED TAP)
SINGLE WALL/ROUND/CONICAL DUCT TAP
SINGLE WALL/ROUND/STRAIGHT TEE
FITTING DESCRIPTION
SINGLE WALL/ROUND/LO-LOSS DUCT TAP W/ REDUCER
DOUBLE WALL/ROUND/STRAIGHT TAP
SINGLE WALL/ROUND/STRAIGHT DUCT TAP
SINGLE WALL/ROUND/REDUCING LO-LOSS TEE
SINGLE WALL/ROUND/REDUCING LO-LOSS 90 DEG. CROSS
SINGLE WALL/ROUND/Y-BRANCH 90 DEG. REDUCING
SINGLE WALL/ROUND/REDUCING CONICAL TEE
SINGLE WALL/ROUND/LO-LOSS DUCT TAP
SINGLE WALL/ROUND/LO-LOSS TEE
SS0PTL SINGLE WALL/SQUARE/90 DEG. INCREASED TAP (FLARED TAP)
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M2.1
5-2420
PHASE 2 - PLAZA & MEZZANINEHVAC PLAN
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"HVAC PLAN MEZZANINENORTH
1/8" = 1'-0"HVAC PLAN PLAZA
DNUPDN
UPDNUPDN
UP
M
11
4
6
7
9
1
A B C D F G H L
12
3
CORR.201
MENS202
CORR200
OFFICE203
OFFICE204
OFFICE205
ENTRY214
CORR209
OFFICE211
OFFICE212
WORK RM215
OFFICE217
OFFICE206
OFFICE207 OFFICE
208
WOMENS220
MECH219
CORR223
JAN222ELEC
221
LOBBY213
OFFICE226 OFFICE
227
CORR225
CONF216
OFFICE228
OFFICE230
OFFICE231
CONF224
LIBRARY218
OFFICE229
VAV-2-1775 CFM
VAV-2-3400 CFM
VAV-2-4400 CFM
VAV-2-5400 CFM
VAV-2-6400 CFM VAV-2-7
400 CFM
VAV-2-8450 CFM
VAV-2-12200 CFM
VAV-2-9700 CFM
VAV-2-14400 CFM
VAV-2-15400 CFM
VAV-2-16400 CFM
VAV-2-11250 CFM
VAV-2-17400 CFM
VAV-2-18425 CFM
VAV-2-19425 CFM
VAV-2-13225 CFM
VAV-2-2350 CFM
10"ø SA
8"x8" SA
12"x8" SA
12"x8" SA 6"ø SA
8"x8" SA
12"x8" SA
12"x8" SA
12"x8" SA
6"ø SA
28"x16" SA
8"ø SA
8"ø SA
14"x10" SA 8"ø SA 6"ø SA
6"ø SA
10"x10" SA
8"ø SA
6"ø SA
10"ø SA
8"ø SA
6"ø SA
10"ø SA
8"ø SA
8"ø SA
6"ø SA
14"ø SA
8"ø SA
6"ø SA
7"ø SA
7"ø SA
10"ø SA
10"x10" SA
12"x8" SA
12"x8" SA 12"x8" SA 12"x8" SA
10"ø SA
12"x8" SA
8"x8" SA
12"x12" SA
6"ø SA
6"ø SA
6"ø SA
8"ø SA
6"ø SA6"ø SA6"ø SA10"ø SA
12"ø SA
12"x10" SA
14"x12" SA
S-4
400 CFM
16"x12" SA
S-4
400 CFM
S-4
400 CFMS-4
400 CFMS-4400 CFM
S-4425 CFM
S-4425 CFM
S-14
175 CFM
S-14
200 CFM
S-14
250 CFM
S-4
400 CFM
S-4400 CFM
S-4400 CFM S-4
400 CFM S-4450 CFM
S-2125 CFM
S-2125 CFM
S-3150 CFM
S-3
200 CFM
S-3250 CFM
S-3200 CFM
S-3150 CFM
S-3225 CFM
S-14150 CFM
S-1100 CFM
S-1
75 CFM
S-2
175 CFM
S-2
175 CFM
S-1
100 CFM
S-14
175 CFM
E-1
150 CFM
36"x10" RA
18"x10" RA
20"x12" RA
36"x12" RA10"x8" RA
36"x18" RA
36"x16" RA
36"x20" RA
22"x8" RA
36"x14" RA
30"x14" RA16"x8" RA 30"x14" RA
24"x14" RA
24"x12" RA
24"x12" RA
16"x8" RA
10"x8" RA 12"x10" EA
10"x8" EA
12"x6" EA
8"x6" EA8"x6" EA
8"x6" EA
6"x8" EA
6"x8" EA
12"x6" EA
EXIST. RA GRILLE425 CFMEXIST. RA GRILLE
425 CFM
EXIST. RA GRILLE400 CFM
EXIST. RA GRILLE400 CFM
EXIST. RA GRILLE400 CFM
EXIST. RA GRILLE400 CFM
EXIST. RA GRILLE250 CFM
EXIST. RA GRILLE550 CFM
EXIST. RA GRILLE525 CFM
EXIST. RA GRILLE400 CFM
EXIST. RA GRILLE400 CFM
EXIST. RA GRILLE400 CFM
EXIST. RA GRILLE200 CFM
EXIST. RA GRILLE400 CFM
S-3
200 CFM
EXIST. RA GRILLE400 CFM
VAV-2-10900 CFM E-2
125 CFM
E-6
250 CFM
E-2150 CFM
E-6
250 CFM
05
8"ø SA
5"ø SA
48"x24" SA DN.32"x24" SA UP
09 12 02 04
07
14
10
13100410
1005
13
09
09
09
6"ø SA
S
S
S
SSSS
S
S
S
S
SS
S
S
S
S
S S
18"x12" SA
16"x10" SA
ø8"
8"ø SA
ø8"
4"ø SA
6"ø SA
8"ø SA
ø8"
8"ø SA
12"x8" SA
8"ø SA
8"ø SA
6"ø SA
8"ø SA
S-13100 CFM
28"x12" SA10"ø SA
12"ø SA
10"x10" EA
FIRE/SMOKEDAMPER, TYP.
F/SD
F/SD
F/SD
F/SD
F/SD
M
11
4
6
7
9
1
A B C D F G H L
12
3
OFFICE301
OFFICE302
OFFICE303
OFFICE304
OFFICE305
OFFICE306
OFFICE307
MECH311MENS
310
LOBBY319
CORR309
CONF312
STOR313
OFFICE314
CORR320 CORR
323
ELEC317
MECH315
OFFICE308
WOMENS316
Room318
CONF325
OFFICE333
OFFICE332
OFFICE331
OFFICE327
FILES322
STOR321
OFFICE330
OFFICE329
CONF328
OFFICE326
VAV-2-22400 CFM
VAV-2-25400 CFM
VAV-2-27450 CFM
VAV-2-34600 CFM
VAV-2-35400 CFM
VAV-2-37400 CFM
VAV-2-38600 CFM
VAV-2-39600 CFM
VAV-2-32600 CFM
VAV-2-31550 CFM
VAV-2-29200 CFM
VAV-2-28600 CFM
VAV-2-30200 CFM
VAV-2-33325 CFM
VAV-2-20450 CFM
VAV-2-23400 CFM
VAV-2-24400 CFM
VAV-2-26400 CFM
VAV-2-36400 CFM
S-4450 CFM
S-4
400 CFMS-4400 CFM
S-4400 CFM
S-4400 CFM
S-4
400 CFM S-4400 CFM
S-4
450 CFM
S-14225 CFM
E-6300 CFM
S-3200 CFM
S-4325 CFM
S-14175 CFM
S-1
75 CFM
E-2
125 CFM
S-4375 CFM
S-1375 CFM
E-2
75 CFM S-2
100 CFM
S-3
200 CFM
S-3150 CFM
S-3150 CFM
S-4300 CFM
S-4300 CFM
S-4400 CFM
S-4
400 CFM S-4
400 CFM S-4
300 CFM
S-4
300 CFM
S-4300 CFM
S-4
300 CFM
S-13
100 CFM
S-2
75 CFM
S-1275 CFM
10"x10" SA
7"ø SA
8"ø SA
12"x8" SA
10"x10" SA
10"ø SA
12"x8" SA
8"ø SA
12"x8" SA
8"ø SA
6"ø SA
12"x8" SA
10"ø SA16"x12" SA16"x10" SA 18"x12" SA
10"ø SA
11"ø SA
8"ø SA8"ø SA
12"x8" SA
8"ø SA
8"ø SA
38"x14" SA
12"x8" SA
12"x10" SA10"x8" SA
8"x10" SA
8"ø SA
8"ø SA
4"ø SA
12"x8" SA
12"x8" SA
6"ø SA
8"x8" SA8"ø SA
14"x10" SA
10"ø SA10"ø SA
14"x10" SA10"ø SA
12"x10" SA
10"ø SA
10"ø SA
12"ø SA10"ø SA
11"ø SA
8"x8" SA
6"ø SA
12"ø SA
9"ø SA
9"ø SA
8"ø SA
6"ø SA6"ø SA
12"ø SA
12"x10" SA
8"ø SA
8"ø SA
6"ø SA
14"x12" SA8"ø SA
8"ø SA
12"x8" SA
8"ø SA6"ø SA
12"x8" SA
9"ø SA
6"ø SA
5"ø SA
10"ø SA
12"x8" SA
8"ø SA
6"ø SA
8"x10" SA
6"ø SA
VAV-2-21400 CFM 11"ø SA
R-2375 CFM
R-2
475 CFMR-2
200 CFM
E-2
150 CFM
E-1150 CFM
E-6250 CFM
E-2
125 CFM
VAV-2-40200 CFM
24"x14" SA20"x14" SA
12"ø SA
09 05 04 10 10
04
05
14
10
0913
09
09
10
09
09
09
EXIST. RA GRILLE600 CFM
EXIST. RA GRILLE400 CFM
EXIST. RA GRILLE400 CFM
EXIST. RA GRILLE400 CFM EXIST. RA GRILLE
600 CFM
EXIST. RA GRILLE600 CFM
EXIST. RA GRILLE450 CFM
EXIST. RA GRILLE400 CFM
EXIST. RAGRILLE400 CFM
EXIST. RA GRILLE325 CFM
EXIST. RA GRILLE400 CFM
EXIST. RA GRILLE400 CFM
EXIST. RA GRILLE450 CFM
EXIST. RA GRILLE200 CFM
36"x16" RA
36"x32" RA
18"x10" RA
16"x8" RA
18"x8" RA
36"x14" RA
14"x6" RA
16"x8" RA
26"x14" RA14"x6" RA
14"x6" RA
24"x12" RA
14"x6" RA16"x8" RA12"x8" RA
12"x8" RA
36"x16" RA
12"x8" RA
36"x16" RA
16"x8" RA16"x8" RA
16"x8" RA
12"x8" RA
24"x12" RA
8"x6" EA
6"x6" EA
6"x6" EA
12"x8" EA12"x10" EA
6"x6" EA6"x6" EA
10"x8" EA
12"x12" EA14"x12" EA 6"x6" EA12"x6" EA
SS S SSSSS
S
S
S
12"ø SA
S
S S
S
S
S
S
S
SS
12"ø SA
6"ø SA
8"ø SA
10"ø SA
8"ø SA
11"ø SA
F/SD
F/SD
F/SD
F/SD
F/SD
FIRE/SMOKEDAMPER, TYP.
ALL SUPPLY, RELIEF, AND RETURN AIR DUCTWORK SHOWN WITH DASHES SHALL BE INTERNALLY LINED DOUBLEWALL DUCTWORK WITH 1" THICK DUCT LINER FOR ROUND AND OVAL SUPPLY DUCT AND 1" THICK DUCT LINERFOR RECTANGULAT SUPPLY AND RETURN DUCT. ALL EXHAUST DUCTWORK SHOWN WITH DASHES SHALL BEACOUSTICALLY LINED SINGLE WALL DUCTWORK UNLESS NOTED OTHERWISE.
ACTUAL LOCATION OF GRILLES AND DIFFUSERS SHALL BE COORDINATED WITH REFLECTED CEILING PLAN. IFTHERE ARE ANY DISCREPANCIES, VERIFY FINAL LOCATION WITH A/E.
INSTALL THERMOSTAT/SENSORS AT 48" A.F.F. TO TOP OF THERMOSTATS/SENSORS UNLESS NOTEDOTHERWISE. ALL THERMOSTATS/SENSORS INSTALLED ON OUTSIDE WALLS SHALL HAVE INSULATEDBACKPLATES.
CONTRACTOR SHALL FIELD VERIFY ALL MECHANICAL EQUIPMENT CONDITIONS PRIOR TO FABRICATION ANDCONNECTION OF HYDRONIC AND DUCTWORK COMPONENTS. REFER TO HYDRONIC SHEETS AND DETAILSHEETS FOR ADDITIONAL INFORMATION.
IN AREAS OF ACOUSTICAL LINED OR DOUBLE WALL DUCTWORK, THE DIMENSIONS LISTED ARE THE FREE AREAWITHIN THE DUCTWORK.
IN AREAS WHERE DUCTWORK IS EXPOSED, ROUTE DUCTWORK AS HIGH AS POSSIBLE UNLESS SPECIFICALLYNOTED ON THE DRAWINGS.
CONTRACTOR SHALL REFER TO CODE COMPLIANCE DRAWING FOR INFORMATION ON RATINGS OF FIRE/SMOKEDAMPERS.
ALL EXHAUST FAN (I.E. NOT ERU EXHAUST) DUCTWORK SHOWN WITH DASHED LINES SHALL BE ACOUSTICALLYLINED DUCTWORK UNLESS NOTED OTHERWISE.
PAINT INTERIOR OF ALL DUCT AT LINEAR SIDEWALL SUPPLY, RETURN, AND EXHAUST DIFFUSERS/GRILLES FLATBLACK.
FLEXIBLE DUCTWORK CORE SHALL BE CLAMPED AND TAPED AT ALL CONNECTIONS AND JOINTS (i.e. ATCONNECTION TO BRANCH DUCTWORK, DIFFUSERS, ETC.). TAPE SHALL MEET REQUIREMENTS OF UL1818-FX. INADDITION, FLEXIBLE DUCTWORK JACKET SHALL BE TAPED AT ALL CONNECTIONS AND JOINTS WITH TAPEMEETING THE ABOVE STATED REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
VERIFY AND MAINTAIN ALL MANUFACTURER'S RECOMMENDED MECHANICAL EQUIPMENT SERVICE CLEARANCES.
ALL MITERED 90 DEGREE ELBOWS SHALL INCLUDE TURNING VANES.
AHU-1, AHU-2, AND AHU-3 SHALL HAVE NEOPRENE ISOLATION PADS EQUAL TO KINETICS MODEL RSP UNDERUNITS IN MECHANICAL ROOM AND PENTHOUSE.
GENERAL HVAC NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
DUCT FITTING LEGEND
TAG
01
02
03
04
05
06
07
08
09
10
11
12
13
14
SR0TR
KS0PTL
SR0PTLR
SROT
SR0PTC
KR0T
SR0PT
SR0TLR
SR0TXLR
SROYR
SR0TCR
SROPTL
SR0TL
FITTING TYPE
SINGLE WALL/ROUND/REDUCING TEE
DOUBLE WALL/SQUARE/90 DEG. INCREASED TAP (FLARED TAP)
SINGLE WALL/ROUND/CONICAL DUCT TAP
SINGLE WALL/ROUND/STRAIGHT TEE
FITTING DESCRIPTION
SINGLE WALL/ROUND/LO-LOSS DUCT TAP W/ REDUCER
DOUBLE WALL/ROUND/STRAIGHT TAP
SINGLE WALL/ROUND/STRAIGHT DUCT TAP
SINGLE WALL/ROUND/REDUCING LO-LOSS TEE
SINGLE WALL/ROUND/REDUCING LO-LOSS 90 DEG. CROSS
SINGLE WALL/ROUND/Y-BRANCH 90 DEG. REDUCING
SINGLE WALL/ROUND/REDUCING CONICAL TEE
SINGLE WALL/ROUND/LO-LOSS DUCT TAP
SINGLE WALL/ROUND/LO-LOSS TEE
SS0PTL SINGLE WALL/SQUARE/90 DEG. INCREASED TAP (FLARED TAP)
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M2.2
5-2420
PHASE 2 - SECOND & THIRDFLOOR HVAC PLAN
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"HVAC SECOND FLOORNORTH
1/8" = 1'-0"HVAC THIRD FLOOR
DNUP
DNUP
DNUPDN UP
M
S-5
225 CFM
S-3225 CFM
11
4
6
7
9
1
A B C D F G H L
12
3
S-4400 CFM
S-4400 CFM
S-4
400 CFM
S-4400 CFM S-3
300 CFM
S-3300 CFM
S-3300 CFM
S-3300 CFM
S-4
400 CFMS-4400 CFM
S-4
400 CFM
S-4
400 CFM
S-3
200 CFMS-3
200 CFM
S-3
200 CFM
S-175 CFM
S-3
200 CFM
S-2
125 CFM
S-3
175 CFM
S-3300 CFM
S-1
75 CFM
S-14
175 CFM
S-3275 CFM
S-13
100 CFM
S-2
100 CFM
S-4350 CFM
S-3175 CFM
S-3200 CFM
S-2
125 CFM
S-14225 CFM
OFFICE401
OFFICE402
OFFICE403
OFFICE404
Room409
OFFICE405
OFFICE406
WOMENS414
JAN419
ELEC413B
CONF422
STOR412
OFFICE411
OFFICE410
MENS407
LOBBY415
ENTRY416
KITCHETTE417
CORR418
CONF424 OFFICE
425OFFICE
426
CORR423
OFFICE427
OFFICE428
OFFICE420
WORK RM421
OFFICE429
TOILET430
MECH408
VAV-3-1450 CFM
VAV-3-2400 CFM
VAV-3-3400 CFM
VAV-3-4400 CFM
VAV-3-5400 CFM
VAV-3-9650 CFM
VAV-3-7750 CFM
VAV-3-11400 CFM
VAV-3-8200 CFM
VAV-3-10250 CFM
VAV-3-12300 CFM
VAV-3-18675 CFM
VAV-3-17400 CFM
VAV-3-15400 CFM
VAV-3-14400 CFMVAV-3-13
600 CFM
VAV-3-6600 CFM
E-6
300 CFM
E-6250 CFM
E-2
150 CFM
E-2
125 CFM
E-2
100 CFM
E-6
125 CFM
E-6200 CFM
E-1
0 CFM
VAV-3-16400 CFM
VAV-3-61350 CFM
44"x14" 1" D.W. DN.FROM PENTHOUSE
09 05 1004
0210
14
14
0202
04
02
10
040410
10
10
09
EXIST. RA GRILLE600 CFM
EXIST. RA GRILLE400 CFM
EXIST. RA GRILLE400 CFM
EXIST. RA GRILLE125 CFM
EXIST. RA GRILLE400 CFM
EXIST. RA GRILLE650 CFM
EXIST. RA GRILLE300 CFM
EXIST. RA GRILLE600 CFM
EXIST. RA GRILLE400 CFMEXIST. RA GRILLE
400 CFM
EXIST. RA GRILLE400 CFM
EXIST. RA GRILLE350 CFM
EXIST. RA GRILLE175 CFM
EXIST. RA GRILLE450 CFM
12"x10" SA
8"ø SA
8"x10" SA
8"ø SA
16"x8" SA10"x8" SA
12"x8" SA
10"x10" SA
14"x10" SA
8"x10" SA
8"ø SA
8"ø SA
8"ø SA
6"ø SA
14"x10" SA
8"x8" SA
8"ø SA
8"ø SA
8"ø SA
8"ø SA
44"x14" SA
8"x10" SA
8"ø SA
8"x10" SA
10"ø SA
14"x10" SA
6"ø SA
8"ø SA 8"ø SA
40"x12" SA
24"x12" SA
8"ø SA
18"x12" SA
9"ø SA
6"ø SA
8"ø SA
6"ø SA8"ø SA
24"x12" SA
6"ø SA12"ø SA
12"x8" SA
6"ø SA
10"x8" SA
12"x8" SA10"x6" SA
10"x6" SA
12"x8" SA12"x8" SA
12"x8" SA
12"x8" SA
6"ø SA
6"ø SA
12"x8" SA
6"ø SA
6"ø SA
10"ø SA
8"ø SA
6"ø SA
12"x8" SA
8"ø SA
8"x8" SA8"ø SA
12"x8" SA
4"ø SA
6"ø SA
10"x8" SA
6"ø SA
6"ø SA
6"ø SA
32"x12" SA
32"x12" SA
60"x16" RA
40"x14" RA
16"x8" RA10"x12" RA
34"x12" RA
16"x8" RA 16"x8" RA16"x8" RA
16"x8" RA
12"x6" RA
14"x8" RA16"x8" RA16"x8" RA
40"x14" RA
12"x10" RA
16"x10" RA
24"x10" RA
30"x12" RA
36"x12" RA14"x8" RA
12"x8" RA
12"x8" RA
6"x6" EA
6"x6" EA
10"x6" EA
8"x6" EA
12"x10" EA
12"x10" EA
12"x10" EA
16"x12" EA10"x8" EA
12"x12" EA
SSSSS
S
S
S
S
S
S
S
S
S
SS S SS
S-2
100 CFM
34"x12" SA
6"ø SA
60"x16" RA UPTO 5TH FL.
FIRE/SMOKEDAMPER, TYP.
F/SD
F/SD
F/SD F/SD
ALL SUPPLY, RELIEF, AND RETURN AIR DUCTWORK SHOWN WITH DASHES SHALL BE INTERNALLY LINED DOUBLEWALL DUCTWORK WITH 1" THICK DUCT LINER FOR ROUND AND OVAL SUPPLY DUCT AND 1" THICK DUCT LINERFOR RECTANGULAT SUPPLY AND RETURN DUCT. ALL EXHAUST DUCTWORK SHOWN WITH DASHES SHALL BEACOUSTICALLY LINED SINGLE WALL DUCTWORK UNLESS NOTED OTHERWISE.
ACTUAL LOCATION OF GRILLES AND DIFFUSERS SHALL BE COORDINATED WITH REFLECTED CEILING PLAN. IFTHERE ARE ANY DISCREPANCIES, VERIFY FINAL LOCATION WITH A/E.
INSTALL THERMOSTAT/SENSORS AT 48" A.F.F. TO TOP OF THERMOSTATS/SENSORS UNLESS NOTEDOTHERWISE. ALL THERMOSTATS/SENSORS INSTALLED ON OUTSIDE WALLS SHALL HAVE INSULATEDBACKPLATES.
CONTRACTOR SHALL FIELD VERIFY ALL MECHANICAL EQUIPMENT CONDITIONS PRIOR TO FABRICATION ANDCONNECTION OF HYDRONIC AND DUCTWORK COMPONENTS. REFER TO HYDRONIC SHEETS AND DETAILSHEETS FOR ADDITIONAL INFORMATION.
IN AREAS OF ACOUSTICAL LINED OR DOUBLE WALL DUCTWORK, THE DIMENSIONS LISTED ARE THE FREE AREAWITHIN THE DUCTWORK.
IN AREAS WHERE DUCTWORK IS EXPOSED, ROUTE DUCTWORK AS HIGH AS POSSIBLE UNLESS SPECIFICALLYNOTED ON THE DRAWINGS.
CONTRACTOR SHALL REFER TO CODE COMPLIANCE DRAWING FOR INFORMATION ON RATINGS OF FIRE/SMOKEDAMPERS.
ALL EXHAUST FAN (I.E. NOT ERU EXHAUST) DUCTWORK SHOWN WITH DASHED LINES SHALL BE ACOUSTICALLYLINED DUCTWORK UNLESS NOTED OTHERWISE.
PAINT INTERIOR OF ALL DUCT AT LINEAR SIDEWALL SUPPLY, RETURN, AND EXHAUST DIFFUSERS/GRILLES FLATBLACK.
FLEXIBLE DUCTWORK CORE SHALL BE CLAMPED AND TAPED AT ALL CONNECTIONS AND JOINTS (i.e. ATCONNECTION TO BRANCH DUCTWORK, DIFFUSERS, ETC.). TAPE SHALL MEET REQUIREMENTS OF UL1818-FX. INADDITION, FLEXIBLE DUCTWORK JACKET SHALL BE TAPED AT ALL CONNECTIONS AND JOINTS WITH TAPEMEETING THE ABOVE STATED REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
VERIFY AND MAINTAIN ALL MANUFACTURER'S RECOMMENDED MECHANICAL EQUIPMENT SERVICE CLEARANCES.
ALL MITERED 90 DEGREE ELBOWS SHALL INCLUDE TURNING VANES.
AHU-1, AHU-2, AND AHU-3 SHALL HAVE NEOPRENE ISOLATION PADS EQUAL TO KINETICS MODEL RSP UNDERUNITS IN MECHANICAL ROOM AND PENTHOUSE.
GENERAL HVAC NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
13
14
15
16
M
11
4
6
7
9
1
A B C D F G H L
12
3
OFFICE501
OFFICE502
OFFICE503
OFFICE504
OFFICE505
OFFICE506
STOR507
BREAK509
WOMENS519
JAN520
ELEC518
MECH517
STOR508
CONF515
OPEN OFFICE516
FILES514
MECH513
OFFICE510
MENS512
CORR521
OFFICE522
OPEN OFFICE525
OFFICE526 OFFICE
527
OFFICE528
OFFICE529
OFFICE530
OPEN OFFICE524CONF
523
VAV-3-22400 CFM
VAV-3-23400 CFM
VAV-3-24400 CFM
VAV-3-57800 CFM
VAV-3-27200 CFM
VAV-3-28275 CFM
VAV-3-56350 CFM
VAV-3-55500 CFM
VAV-3-20400 CFM
VAV-3-19500 CFM
VAV-3-291260 CFM
VAV-3-30810 CFM
VAV-3-31600 CFM
VAV-3-32400 CFM
VAV-3-33300 CFM
VAV-3-34400 CFM
VAV-3-35400 CFM
VAV-3-21400 CFM
S-3250 CFM
S-3250 CFM
S-4
400 CFM S-4
400 CFM
S-4400 CFM
S-4
400 CFM
S-4
400 CFM
S-13125 CFM
S-14225 CFM
E-6300 CFM
S-2
100 CFM
S-3
250 CFMS-4
300 CFM
S-3175 CFM
E-6250 CFM
S-3
200 CFM
S-2
125 CFMS-4
325 CFMS-3270 CFM
S-3270 CFM
S-3270 CFM
S-3
270 CFM
S-3
270 CFMS-3270 CFM
S-6
600 CFM
S-4
400 CFM S-4
300 CFM
S-4
400 CFM
S-4400 CFM
S-3200 CFM
S-4300 CFM
S-14
200 CFM
S-1275 CFM
S-2
100 CFM
R-2
800 CFM
R-2600 CFM
R-2
400 CFM
R-2300 CFM
R-2
400 CFM
R-2
400 CFM
R-2810 CFMR-2
325 CFM
R-2
125 CFM
R-2
350 CFM
R-2300 CFM
R-2175 CFM
R-2
500 CFM
R-2400 CFM
R-2
400 CFMR-2
400 CFM
R-2400 CFM
E-2
150 CFM
S-2150 CFM
R-2
400 CFM
S-3175 CFM
R-2
900 CFM
10"x10" SA
E-275 CFM
E-2
125 CFM
E-6
150 CFM
E-1150 CFM
E-3150 CFM
VAV-3-26400 CFM
VAV-3-25350 CFM
44"x16" 1" D.W. DN.FROM PENTHOUSE
44"x14" 1" D.W. DN.FROM PENTHOUSE
09
02
02 02
04
04
02
02
02
14
14
10
05
040404
04
0505
05
40"x12" SA
26"x12" SA
12"x8" SA
12"ø SA
22"x10" SA
12"ø SA
8"ø SA
12"x8" SA
22"x12" SA
10"x10" SA
7"ø SA
8"ø SA 8"ø SA
6"ø SA
8"ø SA
12"x8" SA
6"ø SA
6"ø SA
6"ø SA
10"x10" SA
8"ø SA18"x10" SA
10"ø SA8"ø SA
10"x8" SA
10"ø SA
8"ø SA
10"ø SA6"ø SA
10"ø SA16"x10" SA
8"ø SA8"ø SA8"ø SA
10"ø SA
12"x8" SA
6"ø SA
6"ø SA
5"ø SA
6"ø SA
6"x8" SA
6"ø SA
10"x8" SA
8"ø SA
12"x8" SA
12"x8" SA12"x8" SA
12"x8" SA 12"x8" SA
8"ø SA
10"ø SA
6"ø SA
8"ø SA
8"ø SA8"ø SA
8"x10" SA
12"x8" SA
10"x10" SA
6"ø SA
8"ø SA
6"ø SA
28"x12" SA
18"x12" SA
8"ø SA
6"ø SA
6"ø SA6"ø SA6"ø SA
8"ø SA
11"ø SA6"ø SA
12"x8" SA
4"ø SA
60"x16" RA
46"x12" RA
38"x14" RA
14"x12" RA
20"x12" RA
18"x12" RA
12"x12" RA
12"x8" RA
16"x10" RA
12"x8" RA
24"x10" RA
12"x6" RA
12"x8" RA
20"x10" RA
30"x14" RA
10"x8" RA14"x12" RA20"x12" RA
50"x12" RA
14"x12" RA
12"x10" RA
12"x6" RA
42"x12" RA
12"x8" RA
24"x12" RA
12"x8" RA 12"x8" RA
42"x12" RA
16"x12" RA
12"x8" RA
12"x8" RA
6"x6" EA
10"x8" EA
6"x6" EA
8"x6" EA
12"x6" EA
12"x6" EA18"x8" EA
16"x12" EA
6"x6" EA
14"x12" EA
8"x6" EA
8"x6" EA
12"x6" EA 6"x6" EA
S
S
SSSS
S
S
S
S
S
S
S
S
SSS
SS
S
42"x42" RA TRANSITIONTO 60"x25" IN VERTICAL.AFTER 60"x16" TO 5TH FL.TRANSITION TO 60"x16"DN. TO 4TH FL.
42"x42" RA UPTO 6TH FL.
FIRE/SMOKEDAMPER, TYP.
F/SD
F/SDF/SD
F/SD
F/SD
DUCT FITTING LEGEND
TAG
01
02
03
04
05
06
07
08
09
10
11
12
13
14
SR0TR
KS0PTL
SR0PTLR
SROT
SR0PTC
KR0T
SR0PT
SR0TLR
SR0TXLR
SROYR
SR0TCR
SROPTL
SR0TL
FITTING TYPE
SINGLE WALL/ROUND/REDUCING TEE
DOUBLE WALL/SQUARE/90 DEG. INCREASED TAP (FLARED TAP)
SINGLE WALL/ROUND/CONICAL DUCT TAP
SINGLE WALL/ROUND/STRAIGHT TEE
FITTING DESCRIPTION
SINGLE WALL/ROUND/LO-LOSS DUCT TAP W/ REDUCER
DOUBLE WALL/ROUND/STRAIGHT TAP
SINGLE WALL/ROUND/STRAIGHT DUCT TAP
SINGLE WALL/ROUND/REDUCING LO-LOSS TEE
SINGLE WALL/ROUND/REDUCING LO-LOSS 90 DEG. CROSS
SINGLE WALL/ROUND/Y-BRANCH 90 DEG. REDUCING
SINGLE WALL/ROUND/REDUCING CONICAL TEE
SINGLE WALL/ROUND/LO-LOSS DUCT TAP
SINGLE WALL/ROUND/LO-LOSS TEE
SS0PTL SINGLE WALL/SQUARE/90 DEG. INCREASED TAP (FLARED TAP)
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M2.3
5-2420
PHASE 2 - FOURTH & FIFTHFLOOR HVAC PLAN
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"HVAC FOURTH FLOOR
NORTH
1/8" = 1'-0"HVAC FIFTH FLOOR
DNUPDNUP
D D
D
13
14
15
16
M
11
4
6
7
9
1
A B C D F G H L
12
3
OFFICE600
OFFICE602
OFFICE603
OFFICE601
CORR610
OFFICE604
OFFICE605
OFFICE606
OFFICE607A
OFFICE607B
CORR618
ELEC614B
OFFICE613
OFFICE612
OFFICE611
MENS608
LOBBY616
OFFICE617A
OFFICE617B
OFFICE622
OFFICE621
OFFICE620
WORK ROOM625
OFFICE626
OFFICE627
OFFICE628
OFFICE629
OFFICE630
CORR624
OFFICE623
CLOSET619
CONF.631
VAV-3-36400 CFM
VAV-3-37400 CFM VAV-3-38
400 CFMVAV-3-39400 CFM
VAV-3-40400 CFM VAV-3-41
400 CFM
VAV-3-49400 CFM
VAV-3-50400 CFM
VAV-3-51400 CFM
VAV-3-52400 CFM
VAV-3-53400 CFM
VAV-3-54600 CFM
VAV-3-47700 CFM
VAV-3-46500 CFM
VAV-3-59300 CFM
VAV-3-42500 CFM
VAV-3-58500 CFM
VAV-3-44600 CFM
VAV-3-43925 CFM
VAV-3-60200 CFM
VAV-3-45500 CFM
VAV-3-48600 CFM
09 09 040404
04
04
0202
02
S-6
500 CFM
14
14
0210
05
02040404
04
0509
S-4300 CFM
8"ø SA 10"ø SA 11"ø SA
6"ø SA6"ø SA
6"ø SA
16"x12" SA
20"x12" SA
20"x12" SA
24"x12" SA
8"ø SA
8"ø SA6"ø SA
40"x12" SA
6"ø SA
4"ø SA
44"x14" SA1" DW DN. FROMPENTHOUSE TO4TH FLOOR.
44"x16" SA1" DW DN. FROMPENTHOUSE TO5TH FLOOR.
46"x16" SA1" DW DN. FROMPENTHOUSE.
46"x16"SA1" DW
30"x1
2" S
A
8"ø SA5"ø SA
6"ø SA
26"x12" SA
6"ø SA 6"ø SA
22"x12" SA
6"ø SA6"ø SA
18"x12" SA
6"ø SA 10"ø SA 11"ø SA
6"ø SA7"ø SA
9"ø SA
12"x8" SA
12"x8" SA 12"x8" SA 12"x8" SA
12"x8" SA
18"x10" SA8"ø SA
16"x8" SA
12"x8" SA8"x8" SA
8"ø SA8"ø SA8"ø SA
12"x10" SA16"x8" SA
8"ø SA
16"x8" SA
12"x8" SA
6"ø SA
10"x10" SA
12"x10" SA
8"ø SA
10"ø SA
8"x8" SA
8"ø SA
8"x8" SA
8"ø SA
10"ø SA
8"ø SA
12"x6" SA
12"x8" SA12"x8" SA
12"x8" SA
12"x8" SA
8"ø SA
8"ø SA
6"ø SA
12"x8" SA
12"x8" SA
12"x8" SA12"x8" SA
12"x6" SA
12"x8" SA
8"x8" SA
6"ø SA
12"x8" SA
16"x8" SA
40"x12" RA
44"x14" RA20"x10" RA
12"x8" RA
14"x8" RA
36"x14" RA
12"x8" RA 12"x8" RA
36"x12" RA
12"x8" RA 12"x8" RA
12"x8" RA
14"x8" RA
22"x10" RA
12"x8" RA
40"x14" RA
30"x12" RA20"x10" RA14"x10" RA
12"x8" RA
12"x6" RA
12"x8" RA
12"x6" RA
30"x14" RA
12"x8" RA 12"x8" RA
12"x6" RA
12"x8" RA
24"x8" RA
14"x6" RA
12"x6" RA 12"x6" RA
12"x8" RA
8"x6" RA12"x6" RA
60"x16" RA8"ø SA
12"x8" RA
12"x8" EA
12"x8" EA
14"x8" EA
8"x6" EA
S
SSS
S
SSS
S
S
S
S
S
S
S
SS SSSS
S
S-4
400 CFM
S-4400 CFM
S-4400 CFM
S-4
400 CFM
S-4400 CFM
12"x8" SA
12"x8" SA
S-6500 CFM
S-4400 CFM
S-3
200 CFM
S-3200 CFM
S-3
200 CFM
S-14200 CFM
R-2
875 CFM
S-15
300 CFM
S-4
425 CFM
R-2200 CFM
S-4300 CFMS-3
200 CFM
S-14200 CFM
S-3
150 CFM
S-13150 CFM
S-3
200 CFM
S-3
200 CFM
S-3
200 CFM
S-4
300 CFM
S-4300 CFM
S-4
400 CFM
S-4
400 CFM
S-4
400 CFM
S-4400 CFM
S-6400 CFM
S-4300 CFM
S-4300 CFM
42"x42" RA UPFROM 5TH FL.TO PENTHOUSE.
R-2
500 CFM
R-2400 CFM
R-2400 CFM
R-2
400 CFM
R-2
400 CFM
R-2400 CFM
R-2
400 CFM
R-2400 CFM
R-2
500 CFM
R-2300 CFM
R-2350 CFM
R-2
200 CFM
R-2
200 CFMR-2
200 CFM
R-2600 CFM
R-2400 CFM
R-2400 CFM
R-2
400 CFM
R-2
400 CFM
R-2
200 CFMR-2200 CFM
S-13100 CFM
R-2
200 CFM
R-2
150 CFM
R-2400 CFM
R-2600 CFM
E-6
275 CFM
E-6275 CFM
E-1
150 CFME-6375 CFM
60"x16" RA UPTO PENTHOUSE.
8" DIA.
FIRE/SMOKEDAMPER, TYP.
F/SD
F/SD
F/SD
ALL SUPPLY, RELIEF, AND RETURN AIR DUCTWORK SHOWN WITH DASHES SHALL BE INTERNALLY LINED DOUBLEWALL DUCTWORK WITH 1" THICK DUCT LINER FOR ROUND AND OVAL SUPPLY DUCT AND 1" THICK DUCT LINERFOR RECTANGULAT SUPPLY AND RETURN DUCT. ALL EXHAUST DUCTWORK SHOWN WITH DASHES SHALL BEACOUSTICALLY LINED SINGLE WALL DUCTWORK UNLESS NOTED OTHERWISE.
ACTUAL LOCATION OF GRILLES AND DIFFUSERS SHALL BE COORDINATED WITH REFLECTED CEILING PLAN. IFTHERE ARE ANY DISCREPANCIES, VERIFY FINAL LOCATION WITH A/E.
INSTALL THERMOSTAT/SENSORS AT 48" A.F.F. TO TOP OF THERMOSTATS/SENSORS UNLESS NOTEDOTHERWISE. ALL THERMOSTATS/SENSORS INSTALLED ON OUTSIDE WALLS SHALL HAVE INSULATEDBACKPLATES.
CONTRACTOR SHALL FIELD VERIFY ALL MECHANICAL EQUIPMENT CONDITIONS PRIOR TO FABRICATION ANDCONNECTION OF HYDRONIC AND DUCTWORK COMPONENTS. REFER TO HYDRONIC SHEETS AND DETAILSHEETS FOR ADDITIONAL INFORMATION.
IN AREAS OF ACOUSTICAL LINED OR DOUBLE WALL DUCTWORK, THE DIMENSIONS LISTED ARE THE FREE AREAWITHIN THE DUCTWORK.
IN AREAS WHERE DUCTWORK IS EXPOSED, ROUTE DUCTWORK AS HIGH AS POSSIBLE UNLESS SPECIFICALLYNOTED ON THE DRAWINGS.
CONTRACTOR SHALL REFER TO CODE COMPLIANCE DRAWING FOR INFORMATION ON RATINGS OF FIRE/SMOKEDAMPERS.
ALL EXHAUST FAN (I.E. NOT ERU EXHAUST) DUCTWORK SHOWN WITH DASHED LINES SHALL BE ACOUSTICALLYLINED DUCTWORK UNLESS NOTED OTHERWISE.
PAINT INTERIOR OF ALL DUCT AT LINEAR SIDEWALL SUPPLY, RETURN, AND EXHAUST DIFFUSERS/GRILLES FLATBLACK.
FLEXIBLE DUCTWORK CORE SHALL BE CLAMPED AND TAPED AT ALL CONNECTIONS AND JOINTS (i.e. ATCONNECTION TO BRANCH DUCTWORK, DIFFUSERS, ETC.). TAPE SHALL MEET REQUIREMENTS OF UL1818-FX. INADDITION, FLEXIBLE DUCTWORK JACKET SHALL BE TAPED AT ALL CONNECTIONS AND JOINTS WITH TAPEMEETING THE ABOVE STATED REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
VERIFY AND MAINTAIN ALL MANUFACTURER'S RECOMMENDED MECHANICAL EQUIPMENT SERVICE CLEARANCES.
ALL MITERED 90 DEGREE ELBOWS SHALL INCLUDE TURNING VANES.
AHU-1, AHU-2, AND AHU-3 SHALL HAVE NEOPRENE ISOLATION PADS EQUAL TO KINETICS MODEL RSP UNDERUNITS IN MECHANICAL ROOM AND PENTHOUSE.
GENERAL HVAC NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
DUCT FITTING LEGEND
TAG
01
02
03
04
05
06
07
08
09
10
11
12
13
14
SR0TR
KS0PTL
SR0PTLR
SROT
SR0PTC
KR0T
SR0PT
SR0TLR
SR0TXLR
SROYR
SR0TCR
SROPTL
SR0TL
FITTING TYPE
SINGLE WALL/ROUND/REDUCING TEE
DOUBLE WALL/SQUARE/90 DEG. INCREASED TAP (FLARED TAP)
SINGLE WALL/ROUND/CONICAL DUCT TAP
SINGLE WALL/ROUND/STRAIGHT TEE
FITTING DESCRIPTION
SINGLE WALL/ROUND/LO-LOSS DUCT TAP W/ REDUCER
DOUBLE WALL/ROUND/STRAIGHT TAP
SINGLE WALL/ROUND/STRAIGHT DUCT TAP
SINGLE WALL/ROUND/REDUCING LO-LOSS TEE
SINGLE WALL/ROUND/REDUCING LO-LOSS 90 DEG. CROSS
SINGLE WALL/ROUND/Y-BRANCH 90 DEG. REDUCING
SINGLE WALL/ROUND/REDUCING CONICAL TEE
SINGLE WALL/ROUND/LO-LOSS DUCT TAP
SINGLE WALL/ROUND/LO-LOSS TEE
SS0PTL SINGLE WALL/SQUARE/90 DEG. INCREASED TAP (FLARED TAP)
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M2.4
5-2420
PHASE 2 - SIXTH FLOOR HVACPLAN
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
1/8" = 1'-0"1 HVAC SIXTH FLOOR
DNDN
DD
D
ALL SUPPLY, RELIEF, AND RETURN AIR DUCTWORK SHOWN WITH DASHES SHALL BE INTERNALLY LINED DOUBLEWALL DUCTWORK WITH 1" THICK DUCT LINER FOR ROUND AND OVAL SUPPLY DUCT AND 1" THICK DUCT LINERFOR RECTANGULAT SUPPLY AND RETURN DUCT. ALL EXHAUST DUCTWORK SHOWN WITH DASHES SHALL BEACOUSTICALLY LINED SINGLE WALL DUCTWORK UNLESS NOTED OTHERWISE.
ACTUAL LOCATION OF GRILLES AND DIFFUSERS SHALL BE COORDINATED WITH REFLECTED CEILING PLAN. IFTHERE ARE ANY DISCREPANCIES, VERIFY FINAL LOCATION WITH A/E.
INSTALL THERMOSTAT/SENSORS AT 48" A.F.F. TO TOP OF THERMOSTATS/SENSORS UNLESS NOTEDOTHERWISE. ALL THERMOSTATS/SENSORS INSTALLED ON OUTSIDE WALLS SHALL HAVE INSULATEDBACKPLATES.
CONTRACTOR SHALL FIELD VERIFY ALL MECHANICAL EQUIPMENT CONDITIONS PRIOR TO FABRICATION ANDCONNECTION OF HYDRONIC AND DUCTWORK COMPONENTS. REFER TO HYDRONIC SHEETS AND DETAILSHEETS FOR ADDITIONAL INFORMATION.
IN AREAS OF ACOUSTICAL LINED OR DOUBLE WALL DUCTWORK, THE DIMENSIONS LISTED ARE THE FREE AREAWITHIN THE DUCTWORK.
IN AREAS WHERE DUCTWORK IS EXPOSED, ROUTE DUCTWORK AS HIGH AS POSSIBLE UNLESS SPECIFICALLYNOTED ON THE DRAWINGS.
CONTRACTOR SHALL REFER TO CODE COMPLIANCE DRAWING FOR INFORMATION ON RATINGS OF FIRE/SMOKEDAMPERS.
ALL EXHAUST FAN (I.E. NOT ERU EXHAUST) DUCTWORK SHOWN WITH DASHED LINES SHALL BE ACOUSTICALLYLINED DUCTWORK UNLESS NOTED OTHERWISE.
PAINT INTERIOR OF ALL DUCT AT LINEAR SIDEWALL SUPPLY, RETURN, AND EXHAUST DIFFUSERS/GRILLES FLATBLACK.
FLEXIBLE DUCTWORK CORE SHALL BE CLAMPED AND TAPED AT ALL CONNECTIONS AND JOINTS (i.e. ATCONNECTION TO BRANCH DUCTWORK, DIFFUSERS, ETC.). TAPE SHALL MEET REQUIREMENTS OF UL1818-FX. INADDITION, FLEXIBLE DUCTWORK JACKET SHALL BE TAPED AT ALL CONNECTIONS AND JOINTS WITH TAPEMEETING THE ABOVE STATED REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
VERIFY AND MAINTAIN ALL MANUFACTURER'S RECOMMENDED MECHANICAL EQUIPMENT SERVICE CLEARANCES.
ALL MITERED 90 DEGREE ELBOWS SHALL INCLUDE TURNING VANES.
AHU-1, AHU-2, AND AHU-3 SHALL HAVE NEOPRENE ISOLATION PADS EQUAL TO KINETICS MODEL RSP UNDERUNITS IN MECHANICAL ROOM AND PENTHOUSE.
GENERAL HVAC NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
M
DUCT FITTINGS AT SA PLENUMSHALL CONNECT TO PERFORATEDINNER LINER.
4
6
7
9
1
A B C D F G H L
3
46"x16" SA1" DW DN. TO6TH FL.
44"x16" SA1" DW DN. TO5TH FL.
44"x14" SA1" DW DN. TO4TH FL.
PENTHOUSE702
MECH701
EQUIPMENT703
MECHANICAL CONTRACTOR SHALLCONSTRUCT 5'-5"L x 10'-5"W x 2'-10"HWITH 4" DW INTERNALLY LINEDPERFORATED DOUBLE WALLDISCHARGE PLENUM.FIELD VERIFY SIZE PRIOR TOFABRICATION & INSTALLATION.
IN-FILLUNUSEDFLOOROPENING
01
01
60"x24" SA1" DW
60"x24" SA1" DW
01
01
46"x16" SA1" DW
6'-10" W x 6'-0"H X 11'-0" DRELIEF AIR DISCHARGEPLENUM. CONTRACTORSHALL VERIFY SIZEPRIOR TO FABRICATION.
L-36'-8" W x 9'-0" HREFER TO ARCHITECTURALDRAWINGS FOR ELEVATION.
TRANSITION FROMLOUVER TO PLENUM
WITH ECCENTRICFITTING FLAT ON
BOTTOM.
INSTALL 1" DRAIN INBOTTOM OF LOUVER.
CONNECT TO NEARESTFLOOR DRAIN.
EXISTING OUTDOOR AIR LOUVER.INSTALL NEW MOTORIZED DAMPER.INTERLOCK W/ EF-6. CONTRACTOR SHALLFIELD VERIFY SIZE.
66"x36" RA
66"x36" RA
106"x24" RA
T
REVERSE ACTINGAVERAGING THERMOSTAT TO
ENERGIZE EF-6 & OPENMOTORIZED DAMPER WHENTHE SPACE TEMPERATURE
EXCEEDS SETPOINT
IV-1
TRANSITION OUTDOOR AIRDUCT FROM INTAKEVENTILATOR IV-1 TO AHU-3INTAKE.
AHU-3OA DUCT DROP TO AHUSHALL MATCH INLET SIZE,FIELD VERIFY.
RA DUCT DROP TO AHUSHALL MATCH INLET SIZE,FIELD VERIFY.
60"x16" RA UP FROM6TH FL. CONNECT TOBOTTOM OF 66"x36" RATO AHU-3.
42"x42" RA UP FROM6TH FL (RA FROM 4TH &5TH FLOORS) TRANSITIONTO 66"x36" IN VERTICAL,ROUTE TO AHU-3.
SLOPE RA DUCT WITHROOF STRUCTURE.ROUTE DUCTWORK ASHIGH AS POSSIBLE.
SLOPE SA DUCT WITHROOF STRUCTURE.ROUTE DUCTWORK ASHIGH AS POSSIBLE.
DUCT SMOKEDETECTOR, TYP.
DUCT SMOKEDETECTOR, TYP.
DUCT SMOKEDETECTOR, TYP.
FIRE/SMOKEDAMPER, TYP.AT FLOOR INPENTHOUSE.
F/SD F/SD
FIRE/SMOKEDAMPER, TYP.AT FLOOR INPENTHOUSE.
F/SD
F/SD
F/SD
DUCT FITTING LEGEND
TAG
01
02
03
04
05
06
07
08
09
10
11
12
13
14
SR0TR
KS0PTL
SR0PTLR
SROT
SR0PTC
KR0T
SR0PT
SR0TLR
SR0TXLR
SROYR
SR0TCR
SROPTL
SR0TL
FITTING TYPE
SINGLE WALL/ROUND/REDUCING TEE
DOUBLE WALL/SQUARE/90 DEG. INCREASED TAP (FLARED TAP)
SINGLE WALL/ROUND/CONICAL DUCT TAP
SINGLE WALL/ROUND/STRAIGHT TEE
FITTING DESCRIPTION
SINGLE WALL/ROUND/LO-LOSS DUCT TAP W/ REDUCER
DOUBLE WALL/ROUND/STRAIGHT TAP
SINGLE WALL/ROUND/STRAIGHT DUCT TAP
SINGLE WALL/ROUND/REDUCING LO-LOSS TEE
SINGLE WALL/ROUND/REDUCING LO-LOSS 90 DEG. CROSS
SINGLE WALL/ROUND/Y-BRANCH 90 DEG. REDUCING
SINGLE WALL/ROUND/REDUCING CONICAL TEE
SINGLE WALL/ROUND/LO-LOSS DUCT TAP
SINGLE WALL/ROUND/LO-LOSS TEE
SS0PTL SINGLE WALL/SQUARE/90 DEG. INCREASED TAP (FLARED TAP)
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M2.5
5-2420
PHASE 2 - ENLARGEDPENTHOUSE HVAC PLAN
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/4" = 1'-0"HVAC PENTHOUSE
UP
UP
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING PIPE ROUTING WITH DUCTWORKAND ELECTRICAL TRADES.
INSTALL THERMOSTATS/SENSORS AT 48" A.F.F. TO TOP OF THERMOSTATS/ SENSORS, UNLESSNOTED OTHERWISE. ALL THERMOSTATS/SENSORS INSTALLED ON OUTSIDE WALLS SHALL HAVEINSULATED BACKPLATES.
CONTRACTOR SHALL FIELD VERIFY MECHANICAL EQUIPMENT CONDITIONS PRIOR TOFABRICATION AND CONNECTION OF HYDRONIC AND DUCTWORK COMPONENTS. CONTRACTORSHALL BE RESPONSIBLE FOR THE COORDINATION OF PIPE ROUTING WITH DUCTWORK ANDELECTRICAL TRADES. REFER TO DETAIL SHEETS M7.01 AND M7.02 FOR TYPICAL COIL,EQUIPMENT, VALVE AND PIPING INFORMATION.
CORE HOLES IN WALLS AND FLOORS FOR PIPES, PROVIDE SLEEVES, AND FIRE STOP TOMAINTAIN WALL/FLOOR RATING. SEE CODE COMPLIANCE PLANS FOR RATINGS.
ALL PIPING BRANCHES SHALL HAVE ISOLATION VALVES LOCATED ABOVE THE CEILING(INCORRIDORS) OR MECHANICAL ROOMS AND/0R CLOSETS AT AN ACCESSIBLE LOCATION ANDHEIGHT. INTENT OF DESIGN IS FOR ALL DUCTWORK TO BE LOCATED HIGH AS POSSIBLE WHEREPIPING AND DUCTWORK CROSS OR INHABIT SAME LOCATIONS, ALL HYDRONIC PIPING SHALL BELOCATED UNDER DUCTWORK. COORDINATE INSTALLATION WITH MECHANICAL/HVACCONTRACTOR.
PATCH AND REPAIR ALL EXISTING PIPE INSULATION WHERE NEW HOT WATER HEATING SUPPLYAND RETURN PIPING CONNECTS TO EXISTING PIPING, TYPICAL.
COORDINATE PIPING AND THERMOSTATS WITH APPROPRIATE TRADES TO AVOIDINTERFERENCES.
GENERAL HYDRONIC PIPING NOTES:
1.
2.
3.
4.
5.
6.
7.
13
14
15
16
M
11
4
6
7
9
1
A B C D F G H L
12
3
4" G (1/4 PSI) UP
4" G (1/2 PSI) UP
4" G UP
G (1/2 PSI)
G(1/2
PSI
)G(
1/4 P
SI)
EXIST 2" GSERVICE UP
EXIST 2" GSERVICE
G
ROUTE 4" G (1/2 PSI) AND 4" G (1/4 PSI) AT18" BELOW PLAZA FF (MIN). COORD LOCATIONSWITH EXIST CATCH BASIN AND STORM DRAINPIPING. FIELD VERIFY ACTUAL LOCATIONS
G (1/2 PSI)
4" G UP
LOBBY002
VESTIBULE001
MECHANICAL003
FIRE PUMP004
AHU-2AHU-1
COORDINATE WITHDUCTWORK & FIRE
PROTECTION PIPINGIN THIS AREA.
26.1 GPM HTG.78.3 GPM CLG.
43.8 GPM HTG.131.3 GPM CLG.
4"ø CHGS4"ø CHGR
2 1/2"ø HWS2 1/2"ø HWR
3"ø HWR3"ø HWS
4"ø CHGR
4"ø CHGS
UH-16.1 GPM
UP THRU CHASESEE DWG. M2.1 FORCONTINUATION UP
1 1/4"ø HWR 1 1/4"ø HWS
UH-22.7 GPM3/4"ø HWS
3/4"ø HWR
UH-32.7 GPM
1 1/4"ø HWS
1 1/4"ø HWR
3" CHGS&R TO AHU-1 2" HWS&R TO AHU-1
CLG.
COI
L
HTG.
COI
L
HTG.
COI
L
CLG.
COI
L
3" CHGS&R TO AHU-12" HWS&R TO AHU-1
4" CHGS&R3" CHGS&R
3/4"ø HWS
3/4"ø HWR
RACK 3/4" HWS&RTIGHT ALONG WALLSTORAGE
005
3/4"ø HWS (FT)3/4"ø HWR (FT)
EXISTING FINNED TUBE;0.5 GPM EACH, TYP.
EXISTING FINNED TUBE;0.5 GPM EACH, TYP.
EXISTING FINNED TUBE;0.5 GPM EACH, TYP.
1" HW (FT), TYP.
1" HW
1" HW (FT),TYP.
1" HW (FT),TYP.
VAV-1-200.8 GPM
VAV-1-195.2 GPM
INSTALL NEW F.D.CONNECT TO EXISTINGSANITARYINSTALL NEW F.D.
CONNECT TO EXISTINGSANITARY
1.1/2" COND. DRAINW/ TRAP
1.1/2" COND. DRAINW/ TRAP
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M3.0
5-2420
PHASE 2 - ENLARGED RAMPHYDRONIC PIPING PLAN
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"HYDRONIC PIPING PLAN RAMP
DN
DNUPDN
UP
DN
UP
UP
UP
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING PIPE ROUTING WITH DUCTWORKAND ELECTRICAL TRADES.
INSTALL THERMOSTATS/SENSORS AT 48" A.F.F. TO TOP OF THERMOSTATS/ SENSORS, UNLESSNOTED OTHERWISE. ALL THERMOSTATS/SENSORS INSTALLED ON OUTSIDE WALLS SHALL HAVEINSULATED BACKPLATES.
CONTRACTOR SHALL FIELD VERIFY MECHANICAL EQUIPMENT CONDITIONS PRIOR TOFABRICATION AND CONNECTION OF HYDRONIC AND DUCTWORK COMPONENTS. CONTRACTORSHALL BE RESPONSIBLE FOR THE COORDINATION OF PIPE ROUTING WITH DUCTWORK ANDELECTRICAL TRADES. REFER TO DETAIL SHEETS M7.01 AND M7.02 FOR TYPICAL COIL,EQUIPMENT, VALVE AND PIPING INFORMATION.
CORE HOLES IN WALLS AND FLOORS FOR PIPES, PROVIDE SLEEVES, AND FIRE STOP TOMAINTAIN WALL/FLOOR RATING. SEE CODE COMPLIANCE PLANS FOR RATINGS.
ALL PIPING BRANCHES SHALL HAVE ISOLATION VALVES LOCATED ABOVE THE CEILING(INCORRIDORS) OR MECHANICAL ROOMS AND/0R CLOSETS AT AN ACCESSIBLE LOCATION ANDHEIGHT. INTENT OF DESIGN IS FOR ALL DUCTWORK TO BE LOCATED HIGH AS POSSIBLE WHEREPIPING AND DUCTWORK CROSS OR INHABIT SAME LOCATIONS, ALL HYDRONIC PIPING SHALL BELOCATED UNDER DUCTWORK. COORDINATE INSTALLATION WITH MECHANICAL/HVACCONTRACTOR.
PATCH AND REPAIR ALL EXISTING PIPE INSULATION WHERE NEW HOT WATER HEATING SUPPLYAND RETURN PIPING CONNECTS TO EXISTING PIPING, TYPICAL.
COORDINATE PIPING AND THERMOSTATS WITH APPROPRIATE TRADES TO AVOIDINTERFERENCES.
GENERAL HYDRONIC PIPING NOTES:
1.
2.
3.
4.
5.
6.
7.
11
4
6
7
9
A B C D F G H L
3
OFFICEM101
CONFP104
MECHM103
JANM104
CORRM102
LOBBYM105
LOUNGEM118
WOMENSM117
MENSM115
MECHM116
ELECM114
WORK ROOMM113
OFFICEM112OFFICE
M111OFFICEM110
OPEN OFFICEM108OFFICE
M107
OFFICEM106
RECEPTP106
VAV-1-83.6 GPM
VAV-1-13.1 GPM
VAV-1-171.1 GPM
VAV-1-160.0 GPM
VAV-1-155.2 GPM
VAV-1-133.3 GPM
VAV-1-147.3 GPM
VAV-1-120.8 GPM
VAV-1-117.3 GPM
VAV-1-103.3 GPM
VAV-1-90.8 GPM
VAV-1-23.1 GPM
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.EXISTING FINNED
TUBE, 0.5 GPM,TYP.
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.EXISTING FINNED
TUBE, 0.5 GPM,TYP.
EXISTING FINNEDTUBE, 1.0 GPMEXISTING FINNED
TUBE, 1.0 GPM
HWS&R PIPING LOCATEDWITHIN SOFFIT SHALL
INCLUDE HEAT TRACING,(TYPICAL AT ALL
LOCATIONS).
EXISTING FINNEDTUBE, 0.5 GPM
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
EXISTING FINNEDTUBE, 0.5 GPM
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
11
4
6
7
9
1
A B C D F G H L
12
3
G
4" G(1/4 PSI) DN WITH PLUGVALVE (MAIN BLDG SHUT OFF).FURNISH AND INSTALL PRV(1/2 PSI DN TO 1/4 PSI - 3,125 MBH)
4" G(1/2 PSI) DN WITH PLUG VALVE (EMERGENCYGENERATOR). FURNISH AND INSTALL VALVETAG WITH THE FOLLOWING "EMERGENCYGENERATOR FUEL SUPPLY"
GAS METER(5,151 MBH)
EXIST 2" G DN
M
6" G(1/2 PSI) HEADER
4" G(14") DN
4" G(14") TOEMERGENCYGENERATOR
EMERGENCY GENERATOR,REFER TO ELEC DWG'SFOR EXACT LOC
4" G DN
G (1
/4 PS
I)
4" G UP
CONFP104
RECEPTP106
LOBBYP103
VESTP101
MECHP110 OFFICE
P111
JANP114
CORRP113
OFFICEP115
OFFICEP117
OFFICEP116OFFICE
P109
CORRP108
VAULTP107
VAV-1-33.6 GPM
VAV-1-60.8 GPM VAV-1-7
3.3 GPM
VAV-1-50.8 GPM
VAV-1-42.4 GPM
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M3.1
5-2420
PHASE 2 - PLAZA & MEZZANINEHYDRONIC PIPING PLAN
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"HYDRONIC PIPING PLAN MEZZANINE NORTH
1/8" = 1'-0"HYDRONIC PIPING PLAN PLAZA
DNUPDNUP
DNUPDN
UP
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING PIPE ROUTING WITH DUCTWORKAND ELECTRICAL TRADES.
INSTALL THERMOSTATS/SENSORS AT 48" A.F.F. TO TOP OF THERMOSTATS/ SENSORS, UNLESSNOTED OTHERWISE. ALL THERMOSTATS/SENSORS INSTALLED ON OUTSIDE WALLS SHALL HAVEINSULATED BACKPLATES.
CONTRACTOR SHALL FIELD VERIFY MECHANICAL EQUIPMENT CONDITIONS PRIOR TOFABRICATION AND CONNECTION OF HYDRONIC AND DUCTWORK COMPONENTS. CONTRACTORSHALL BE RESPONSIBLE FOR THE COORDINATION OF PIPE ROUTING WITH DUCTWORK ANDELECTRICAL TRADES. REFER TO DETAIL SHEETS M7.01 AND M7.02 FOR TYPICAL COIL,EQUIPMENT, VALVE AND PIPING INFORMATION.
CORE HOLES IN WALLS AND FLOORS FOR PIPES, PROVIDE SLEEVES, AND FIRE STOP TOMAINTAIN WALL/FLOOR RATING. SEE CODE COMPLIANCE PLANS FOR RATINGS.
ALL PIPING BRANCHES SHALL HAVE ISOLATION VALVES LOCATED ABOVE THE CEILING(INCORRIDORS) OR MECHANICAL ROOMS AND/0R CLOSETS AT AN ACCESSIBLE LOCATION ANDHEIGHT. INTENT OF DESIGN IS FOR ALL DUCTWORK TO BE LOCATED HIGH AS POSSIBLE WHEREPIPING AND DUCTWORK CROSS OR INHABIT SAME LOCATIONS, ALL HYDRONIC PIPING SHALL BELOCATED UNDER DUCTWORK. COORDINATE INSTALLATION WITH MECHANICAL/HVACCONTRACTOR.
PATCH AND REPAIR ALL EXISTING PIPE INSULATION WHERE NEW HOT WATER HEATING SUPPLYAND RETURN PIPING CONNECTS TO EXISTING PIPING, TYPICAL.
COORDINATE PIPING AND THERMOSTATS WITH APPROPRIATE TRADES TO AVOIDINTERFERENCES.
GENERAL HYDRONIC PIPING NOTES:
1.
2.
3.
4.
5.
6.
7.
11
4
6
7
9
A B C D F G H L
12
3
VAV-2-201.9 GPM
VAV-2-223.9 GPM VAV-2-23
3.9 GPM
VAV-2-243.9 GPM
VAV-2-253.9 GPM
VAV-2-400.8 GPM
VAV-2-281.4 GPM
VAV-2-263.9 GPM
VAV-2-272.6 GPM
VAV-2-30
VAV-2-331.5 GPM
VAV-2-290.6 GPM
VAV-2-381.4 GPM
VAV-2-391.4 GPM
VAV-2-375.3 GPM
VAV-2-365.3 GPM
VAV-2-321.9 GPM
VAV-2-313.0 GPM
VAV-2-345.2 GPM
VAV-2-353.9 GPM
CONF328
OFFICE329 OFFICE
330OFFICE
331 OFFICE332 OFFICE
333
OFFICE327
OFFICE326
CONF325
OFFICE301
OFFICE302
OFFICE303 OFFICE
304
OFFICE305
OFFICE306
OFFICE307 OFFICE
308
CORR309
CONF312
STOR313
OFFICE314
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 1.0 GPM
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING FINNEDTUBE, 1.0 GPM
MENS310
MECH311
VESTIBULE-2001-2
FILES322
STOR321
LOBBY319
VAV-2-213.9 GPM
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
3/4"ø HWS (VAV)2 1/2"ø HWR (VAV)
3/4"ø HWS (FT)1 1/2"ø HWR (FT)
3/4"ø HWS (FT)
3/4"ø HWR (FT)3/4"ø HWS (FT)
3/4"ø HWR (FT)
3/4"ø HWS (FT)
3/4"ø HWR (FT)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
1"ø HWS (VAV)1"ø HWS (VAV)1"ø HWR (VAV)
1"ø HWR (VAV)1"ø HWS (VAV)
1"ø HWR (VAV)1"ø HWS (VAV)
3/4"ø HWR (VAV)3/4"ø HWS
2 1/2"ø HWS (VAV)
1"ø HWS (VAV)1"ø HWR (VAV)
1"ø HWS (VAV)1"ø HWR (VAV)
1"ø HWS (VAV)1"ø HWR (VAV) 1"ø HWS (VAV)
1"ø HWR (VAV)1"ø HWS (VAV)1"ø HWR (VAV)
1"ø HWR (VAV)1"ø HWS (VAV)
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
3/4"ø HWR (FT)3/4"ø HWS (FT)
3/4"ø HWR (FT)3/4"ø HWS (FT)
3/4"ø HWR (FT)
3/4"ø HWS (FT)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
1"ø HWS (VAV)1"ø HWR (VAV)
1"ø HWR (VAV)1"ø HWS (VAV)
1"ø HWS (VAV)1"ø HWR (VAV)
1"ø HWS (FT)1 1/4"ø HWR (FT)
2"ø HWS (VAV)
2 1/2"ø HWR (VAV)
2 1/2"ø HWS (VAV)3/4"ø HWR (VAV)
2 1/2"ø HWS (VAV)1 1/4"ø HWR (VAV)
1 1/2"ø HWR (VAV)2 1/2"ø HWS (VAV)
2"ø HWR (VAV)2"ø HWS (VAV)1 1/4"ø HWR (FT)1"ø HWS (FT)
1"ø HWS (FT)1 1/4"ø HWR (FT)
1 1/2"ø HWS (VAV)2 1/2"ø HWR (VAV)
3/4"ø HWS (FT)1 1/2"ø HWR (FT)3/4"ø HWS (VAV)
2 1/2"ø HWR (VAV)
1"ø HWS (VAV)1 1/4"ø HWS (VAV)
1"ø HWS (VAV)1"ø HWR (VAV)
1 1/4"ø HWS (FT)1"ø HWR (FT)
2"ø HWR (VAV)2"ø HWS (VAV)
1 1/2"ø HWS (FT)
1 1/2"ø HWS (FT)3/4"ø HWR (FT)1 1/4"ø HWS (FT)
1"ø HWR (FT)
1 1/4"ø HWS (FT)3/4"ø HWR (FT)
1 1/4"ø HWS (FT)1"ø HWR (FT)
2 1/2"ø HWS (VAV)2"ø HWR (VAV)
11
4
6
7
9
A B C D F G H L
12
3
VAV-2-15.2 GPM VAV-2-3
3.9 GPMVAV-2-43.9 GPM
VAV-2-53.9 GPM
VAV-2-63.9 GPM
VAV-2-98.0 GPM
VAV-2-12
VAV-2-21.5 GPM
VAV-2-130.8 GPM
VAV-2-73.9 GPM
VAV-2-83.9 GPM
VAV-2-185.3 GPM
VAV-2-193.9 GPM
VAV-2-172.4 GPM
VAV-2-110.8 GPM
VAV-2-141.5 GPM
CORR200
CORR.201
MENS202
OFFICE203
OFFICE204 OFFICE
205
OFFICE206
OFFICE207
OFFICE208
OFFICE211
CORR209
OFFICE217
WORK RM215
CONF216
ENTRY214
LOBBY213
OFFICE226
OFFICE227
OFFICE228
OFFICE229
OFFICE230
OFFICE231
CORR225
LIBRARY218
CONF224
CORR223
WOMENS220
JAN222
OFFICE212
MECH219
ELEC221
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 1.0 GPM
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING FINNEDTUBE, 1.0 GPM
EXISTING FINNEDTUBE, 1.0 GPM
1 1/2"ø HWR (FT)
1 1/4"ø HWS (FT)
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
1"ø HWS (VAV)
1"ø HWR (VAV)
1"ø HWR (VAV)
1"ø HWS (VAV)
1 1/4"ø HWR (VAV)2 1/2"ø HWS (VAV)2 1/2"ø HWS (VAV)
1 1/2"ø HWR (VAV)2 1/2"ø HWS (VAV)2 1/2"ø HWR (VAV)
1 1/4"ø HWS (VAV)1 1/4"ø HWR (VAV)
3/4"ø HWR (FT)
3/4"ø HWS (FT)
3/4"ø HWS (FT)3/4"ø HWR (FT)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
VAV-2-162.4 GPM
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
VAV-2-105.2 GPM
VAV-2-155.3 GPM
1"ø HWR (VAV)1"ø HWS (VAV)
1 1/4"ø HWS (VAV)
1"ø HWS (VAV)
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
1 1/4"ø HWS (VAV)
1 1/2"ø HWS (VAV)
2"ø HWS (VAV)
1 1/4"ø HWR (VAV)
2 1/2"ø HWR (VAV)1"ø HWR (FT)
2"ø HWS (VAV)1"ø HWS (FT)
2"ø HWS (VAV)2 1/2"ø HWR (VAV)1"ø HWR (FT)
1"ø HWS (FT)
2 1/2"ø HWR (VAV)2"ø HWS (VAV)
2 1/2"ø HWR (VAV) 2 1/2"ø HWR (VAV)1 1/2"ø HWS (VAV)
2 1/2"ø HWR (VAV)
1 1/2"ø HWR (FT)1 1/4"ø HWS (VAV)
1 1/4"ø HWR (FT)3/4"ø HWS (FT)
2 1/2"ø HWR (VAV)
2 1/2"ø HWS (VAV)ROUTEPIPING THRU
HOLES INBEAMS, TYP.
ROUTEPIPING THRUHOLES INBEAMS, TYP.
ROUTEPIPING THRUHOLES INBEAMS, TYP.
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M3.2
5-2420
PHASE 2 - SECOND & THIRDFLOOR HYDRONIC PIPING
PLAN
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"HYDRONIC PIPING THIRD FLOOR NORTH
1/8" = 1'-0"HYDRONIC PIPING SECOND FLOOR
DNUPDN UP
DNUP
DNUP
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING PIPE ROUTING WITH DUCTWORKAND ELECTRICAL TRADES.
INSTALL THERMOSTATS/SENSORS AT 48" A.F.F. TO TOP OF THERMOSTATS/ SENSORS, UNLESSNOTED OTHERWISE. ALL THERMOSTATS/SENSORS INSTALLED ON OUTSIDE WALLS SHALL HAVEINSULATED BACKPLATES.
CONTRACTOR SHALL FIELD VERIFY MECHANICAL EQUIPMENT CONDITIONS PRIOR TOFABRICATION AND CONNECTION OF HYDRONIC AND DUCTWORK COMPONENTS. CONTRACTORSHALL BE RESPONSIBLE FOR THE COORDINATION OF PIPE ROUTING WITH DUCTWORK ANDELECTRICAL TRADES. REFER TO DETAIL SHEETS M7.01 AND M7.02 FOR TYPICAL COIL,EQUIPMENT, VALVE AND PIPING INFORMATION.
CORE HOLES IN WALLS AND FLOORS FOR PIPES, PROVIDE SLEEVES, AND FIRE STOP TOMAINTAIN WALL/FLOOR RATING. SEE CODE COMPLIANCE PLANS FOR RATINGS.
ALL PIPING BRANCHES SHALL HAVE ISOLATION VALVES LOCATED ABOVE THE CEILING(INCORRIDORS) OR MECHANICAL ROOMS AND/0R CLOSETS AT AN ACCESSIBLE LOCATION ANDHEIGHT. INTENT OF DESIGN IS FOR ALL DUCTWORK TO BE LOCATED HIGH AS POSSIBLE WHEREPIPING AND DUCTWORK CROSS OR INHABIT SAME LOCATIONS, ALL HYDRONIC PIPING SHALL BELOCATED UNDER DUCTWORK. COORDINATE INSTALLATION WITH MECHANICAL/HVACCONTRACTOR.
PATCH AND REPAIR ALL EXISTING PIPE INSULATION WHERE NEW HOT WATER HEATING SUPPLYAND RETURN PIPING CONNECTS TO EXISTING PIPING, TYPICAL.
COORDINATE PIPING AND THERMOSTATS WITH APPROPRIATE TRADES TO AVOIDINTERFERENCES.
GENERAL HYDRONIC PIPING NOTES:
1.
2.
3.
4.
5.
6.
7.
M
11
4
6
7
9
A B C D F G H L
12
3
VAV-3-193.9 GPM
VAV-3-203.9 GPM
VAV-3-552.4 GPM
VAV-3-213.9 GPM
VAV-3-223.9 GPM
VAV-3-231.5 GPM
VAV-3-243.9 GPM
VAV-3-572.6 GPM
VAV-3-561.1 GPM
VAV-3-270.0 GPM
VAV-3-280.8 GPM
VAV-3-296.2 GPM
VAV-3-351.5 GPM
VAV-3-323.9 GPM
VAV-3-333.0 GPM
VAV-3-343.0 GPM
VAV-3-313.1 GPMVAV-3-30
3.6 GPM
VAV-3-261.5 GPM
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
1 1/2"ø HWS (FT)
2 1/2"ø HWS (VAV)3/4"ø HWR (VAV)
1 1/2"ø HWS (FT)3/4"ø HWR (FT)
2 1/2"ø HWS (VAV)3/4"ø HWR (VAV)
3/4"ø HWR (VAV)
3/4"ø HWS (VAV)
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
1"ø HWR (VAV)1"ø HWS (VAV)
1"ø HWR (VAV)1"ø HWS (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
1 1/4"ø HWR (VAV)1 1/4"ø HWS (VAV)
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
3/4"ø HWS (FT)
3/4"ø HWR (FT)
3/4"ø HWS (FT)3/4"ø HWR (FT)
3/4"ø HWS (FT)3/4"ø HWR (FT)
3/4"ø HWS (FT)3/4"ø HWR (FT)
3/4"ø HWS (FT)3/4"ø HWR (FT)
1 1/2"ø HWS (FT)3/4"ø HWR (FT)2 1/2"ø HWS (VAV)
1"ø HWR (VAV)
1 1/4"ø HWS (FT)3/4"ø HWR (FT)
2 1/2"ø HWS (VAV)1"ø HWR (VAV)
1 1/4"ø HWS (FT)3/4"ø HWR (FT)
2 1/2"ø HWS (VAV)1 1/4"ø HWR (VAV)
1 1/4"ø HWS (FT)1"ø HWR (FT)2 1/2"ø HWS (VAV)1 1/2"ø HWR (VAV)
1 1/4"ø HWS (FT)1"ø HWR (FT)
2"ø HWS (VAV)2"ø HWR (VAV)
1 1/4"ø HWS (FT)1"ø HWR (FT)
2"ø HWS (VAV)2"ø HWR (VAV)
1 1/4"ø HWS (FT)1"ø HWR (FT)
2"ø HWS (VAV)2"ø HWR (VAV)
1 1/4"ø HWS (FT)1"ø HWR (FT)
2"ø HWS (VAV)2"ø HWR (VAV)
3/4"ø HWS (FT)3/4"ø HWR (FT)
3/4"ø HWS (FT)3/4"ø HWR (FT)
1"ø HWS (FT)
1"ø HWR (FT)2"ø HWS (VAV)
2"ø HWR (VAV)
1"ø HWS (FT)1"ø HWR (FT)
2"ø HWS (VAV)2"ø HWR (VAV)
1"ø HWS (FT)1"ø HWR (FT)
2"ø HWS (VAV)2"ø HWR (VAV)
1"ø HWS (FT)1 1/4"ø HWR (FT)
2"ø HWS (VAV)2"ø HWR (VAV)
1"ø HWS (FT)1 1/4"ø HWR (FT)
2"ø HWS (VAV)2"ø HWR (VAV)
1"ø HWS (FT)1 1/4"ø HWR (FT)1 1/2"ø HWS (VAV)2 1/2"ø HWR (VAV)
1 1/2"ø HWS (VAV)2 1/2"ø HWR (VAV)
1 1/4"ø HWR (FT)3/4"ø HWS (FT)
3/4"ø HWS (FT)1 1/4"ø HWR (FT)1 1/2"ø HWS (VAV)2 1/2"ø HWR (VAV)
3/4"ø HWS (FT)1 1/4"ø HWR (FT)1 1/2"ø HWS (VAV)2 1/2"ø HWR (VAV)
3/4"ø HWS (FT)1 1/4"ø HWR (FT)
1 1/4"ø HWS (VAV)2 1/2"ø HWR (VAV)
3/4"ø HWS (FT)1 1/4"ø HWR (FT)1"ø HWS (VAV)
2 1/2"ø HWR (VAV)
1 1/2"ø HWR (FT)3/4"ø HWS (VAV)
2 1/2"ø HWR (VAV)
2 1/2"ø HWR (VAV)1 1/2"ø HWR (FT)
2 1/2"ø HWS (VAV)1 1/2"ø HWS (FT)
VAV-3-25350 CFM
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
11
4
6
7
9
A B C D F G H L
12
3
VAV-3-11.9 GPM
VAV-3-23.9 GPM
VAV-3-32.4 GPM
VAV-3-42.4 GPM
VAV-3-55.3 GPM
VAV-3-62.6 GPM
VAV-3-91.7 GPM
VAV-3-611.5 GPM
VAV-3-71.9 GPM VAV-3-11
1.5 GPM
VAV-3-173.9 GPM VAV-3-18
2.2 GPMVAV-3-163.9 GPM
VAV-3-153.9 GPM
VAV-3-143.9 GPM
VAV-3-131.4 GPM
VAV-3-120.8 GPM
VAV-3-100.8 GPM
3/4"ø HWR (FT)
3/4"ø HWS (FT)
3/4"ø HWS (FT)3/4"ø HWR (FT)
1"ø HWR (FT)1"ø HWS (FT)
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 1.0 GPM
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING FINNEDTUBE, 0.75 GPM
EXISTING FINNEDTUBE, 1.0 GPM
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP. 3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
OFFICE401
OFFICE402
OFFICE403
OFFICE404
OFFICE405
OFFICE406
OFFICE410 OFFICE
411
KITCHETTE417
WOMENS414
JAN419
CONF422
OFFICE429OFFICE
428
OFFICE427
OFFICE426OFFICE
425
CONF424
CORR423
WORK RM421OFFICE
420
ENTRY416
LOBBY415
MENS407
Room409
CORR418
TOILET430
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
3/4" HWS&R (FT) UPTO EXISTING FINNED
TUBE, TYP.
HWS&R PIPING LOCATEDWITHIN SOFFIT SHALL
INCLUDE HEAT TRACING,(TYPICAL AT ALL
LOCATIONS).
VAV-3-8
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
1 1/4"ø HWR (FT)
3"ø HWR (VAV)
3/4"ø HWS (FT)
3/4"ø HWR (FT)
3/4"ø HWR (FT)
3/4"ø HWS (FT)
3/4"ø HWS (FT)
3/4"ø HWR (FT)3/4"ø HWR (FT)
3/4"ø HWS (FT)
3/4"ø HWS (VAV)
3/4"ø HWR (VAV)
1 1/4"ø HWR (FT)
3/4"ø HWS (FT)
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
2"ø HWR (VAV)1"ø HWS (VAV)
1 1/4"ø HWR (FT)3/4"ø HWS (FT)
1"ø HWR (VAV)1"ø HWS (VAV)
1"ø HWR (VAV)1"ø HWS (VAV)
1"ø HWR (VAV)1"ø HWS (VAV)
1"ø HWR (VAV)1"ø HWS (VAV)2"ø HWS (VAV)
1"ø HWS (FT)
1"ø HWR (FT)
3/4"ø HWR (VAV)
3/4"ø HWS (VAV)
2"ø HWR (VAV)2"ø HWS (VAV)
1"ø HWR (FT)1"ø HWS (FT)
1"ø HWR (VAV)1"ø HWS (VAV) 3/4"ø HWR (VAV)
3/4"ø HWS (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
1"ø HWS (VAV)1"ø HWR (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
1"ø HWS (VAV)1"ø HWR (VAV)
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
1 1/2"ø HWR (VAV)
2 1/2"ø HWS (VAV)
1 1/4"ø HWS (FT)
3/4"ø HWS (VAV)
3/4"ø HWR (VAV)3/4"ø HWS (VAV)
1 1/4"ø HWR (FT)
3"ø HWR (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
1 1/4"ø HWS (VAV)2"ø HWR (VAV)
2"ø HWR (VAV)2"ø HWS (VAV)
1"ø HWS (FT)
1"ø HWR (FT)
2"ø HWS (VAV)
1 1/4"ø HWR (VAV)
1 1/4"ø HWS (FT)
3/4"ø HWR (FT)
1 1/4"ø HWS (FT)3/4"ø HWR (FT)
1"ø HWR (FT)
1"ø HWS (FT)
1"ø HWR (FT)
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M3.3
5-2420
PHASE 2 - FOURTH & FIFTHFLOOR HYDRONIC PIPING
PLAN
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"HYDRONIC PIPING FIFTH FLOOR NORTH
1/8" = 1'-0"HYDRONIC PIPING FOURTH FLOOR
DNUPDNUP
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING PIPE ROUTING WITH DUCTWORKAND ELECTRICAL TRADES.
INSTALL THERMOSTATS/SENSORS AT 48" A.F.F. TO TOP OF THERMOSTATS/ SENSORS, UNLESSNOTED OTHERWISE. ALL THERMOSTATS/SENSORS INSTALLED ON OUTSIDE WALLS SHALL HAVEINSULATED BACKPLATES.
CONTRACTOR SHALL FIELD VERIFY MECHANICAL EQUIPMENT CONDITIONS PRIOR TOFABRICATION AND CONNECTION OF HYDRONIC AND DUCTWORK COMPONENTS. CONTRACTORSHALL BE RESPONSIBLE FOR THE COORDINATION OF PIPE ROUTING WITH DUCTWORK ANDELECTRICAL TRADES. REFER TO DETAIL SHEETS M7.01 AND M7.02 FOR TYPICAL COIL,EQUIPMENT, VALVE AND PIPING INFORMATION.
CORE HOLES IN WALLS AND FLOORS FOR PIPES, PROVIDE SLEEVES, AND FIRE STOP TOMAINTAIN WALL/FLOOR RATING. SEE CODE COMPLIANCE PLANS FOR RATINGS.
ALL PIPING BRANCHES SHALL HAVE ISOLATION VALVES LOCATED ABOVE THE CEILING(INCORRIDORS) OR MECHANICAL ROOMS AND/0R CLOSETS AT AN ACCESSIBLE LOCATION ANDHEIGHT. INTENT OF DESIGN IS FOR ALL DUCTWORK TO BE LOCATED HIGH AS POSSIBLE WHEREPIPING AND DUCTWORK CROSS OR INHABIT SAME LOCATIONS, ALL HYDRONIC PIPING SHALL BELOCATED UNDER DUCTWORK. COORDINATE INSTALLATION WITH MECHANICAL/HVACCONTRACTOR.
PATCH AND REPAIR ALL EXISTING PIPE INSULATION WHERE NEW HOT WATER HEATING SUPPLYAND RETURN PIPING CONNECTS TO EXISTING PIPING, TYPICAL.
COORDINATE PIPING AND THERMOSTATS WITH APPROPRIATE TRADES TO AVOIDINTERFERENCES.
GENERAL HYDRONIC PIPING NOTES:
1.
2.
3.
4.
5.
6.
7.
M
11
4
6
7
9
A B C D F G H L
12
3
VAV-3-393.0 GPM
VAV-3-362.4 GPM
VAV-3-582.4 GPM VAV-3-37
3.0 GPM
VAV-3-435.2 GPM
VAV-3-383.0 GPM
VAV-3-403.0 GPM
VAV-3-413.0 GPM VAV-3-42
2.4 GPM
VAV-3-591.5 GPM
VAV-3-463.9 GPM
VAV-3-472.6 GPM
VAV-3-453.9 GPM
VAV-3-541.4 GPM
VAV-3-531.5 GPM
VAV-3-521.5 GPM
VAV-3-511.5 GPM
VAV-3-501.5 GPM
VAV-3-491.5 GPM
OFFICE600
OFFICE601
OFFICE602
OFFICE603
OFFICE604
OFFICE605
OFFICE606
OFFICE607A
OFFICE607B
OFFICE611
OFFICE612
OFFICE613
OFFICE617A
LOBBY616
OFFICE620
OFFICE621
OFFICE617B
OFFICE622
CORR618
ELEC614B
CONF.631OFFICE
630
WORK ROOM625
OFFICE626
OFFICE627
OFFICE628
OFFICE629
CORR624
CORR610
MENS608
WOMENS615
OFFICE623
CLOSET619
4"ø Sanitary
4"ø Sanitary
4"ø Sanitary
UP TO F.S.
UP TO F.D.
2 1/2"ø HWS (VAV)
2 1/2"ø HWS (VAV)
3/4"ø HWS (VAV)
2 1/2"ø HWS (VAV)
3/4"ø HWS (VAV)
2 1/2"ø HWS (VAV)
1 1/4"ø HWR (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
2"ø HWS (VAV)
1 1/2"ø HWR (VAV)
1"ø HWS (VAV)1"ø HWR (VAV)
2"ø HWS (VAV)1 1/2"ø HWR (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
2"ø HWS (VAV)1 1/2"ø HWR (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
1"ø HWS (VAV)3/4"ø HWR (VAV)
3/4"ø HWS (VAV)2"ø HWR (VAV)
2"ø HWS (VAV)2"ø HWR (VAV)
2"ø HWS (VAV)2"ø HWR (VAV)
2"ø HWS (VAV)1 1/2"ø HWR (VAV)
2"ø HWS (VAV)2"ø HWR (VAV)
2"ø HWS (VAV)2"ø HWR (VAV)
2"ø HWS (VAV)2"ø HWR (VAV)
1"ø HWS (VAV)1"ø HWR (VAV)
2"ø HWS (VAV)2"ø HWR (VAV)
1"ø HWS (VAV)1"ø HWR (VAV)
2"ø HWS (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
1 1/2"ø HWS (VAV)2"ø HWR (VAV)
1 1/4"ø HWS (VAV)
2"ø HWR (VAV)
1 1/2"ø HWS (VAV)
2"ø HWR (VAV)
1"ø HWS (VAV)1"ø HWR (VAV)
1"ø HWS (VAV)1"ø HWR (VAV)
1"ø HWS (VAV)2"ø HWR (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
1"ø HWS (VAV)2 1/2"ø HWR (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
3/4"ø HWS (VAV)3/4"ø HWR (VAV)
3/4"ø HWS (VAV)2 1/2"ø HWR (VAV)
2 1/2"ø HWR (VAV)
3/4"ø HWR (VAV)
3/4"ø HWR (VAV)
1 1/4"ø HWR (VAV)
3/4"ø HWR (VAV)
2"ø HWS (VAV)
2"ø HWR (VAV)
VAV-3-60
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING CONVECTOR,0.5 GPM
EXISTING FINNEDTUBE, 0.5 GPM,
TYP.
3/4"ø HWS (FT)3/4"ø HWR (FT)
3/4"ø HWS (FT)
3/4"ø HWR (FT)
3/4"ø HWS (FT)3/4"ø HWR (FT)
VAV-3-442.2 GPM
3/4"ø HWR (FT)
3/4"ø HWS (FT)
3/4"ø HWS (FT)
3/4"ø HWR (FT)
VAV-3-48600 CFM
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M3.4
5-2420
PHASE 2 - SIXTH FLOORHYDRONIC PIPING PLAN
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"HYDRONIC PIPING SIXTH FLOOR
DNDN
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING PIPE ROUTING WITH DUCTWORKAND ELECTRICAL TRADES.
INSTALL THERMOSTATS/SENSORS AT 48" A.F.F. TO TOP OF THERMOSTATS/ SENSORS, UNLESSNOTED OTHERWISE. ALL THERMOSTATS/SENSORS INSTALLED ON OUTSIDE WALLS SHALL HAVEINSULATED BACKPLATES.
CONTRACTOR SHALL FIELD VERIFY MECHANICAL EQUIPMENT CONDITIONS PRIOR TOFABRICATION AND CONNECTION OF HYDRONIC AND DUCTWORK COMPONENTS. CONTRACTORSHALL BE RESPONSIBLE FOR THE COORDINATION OF PIPE ROUTING WITH DUCTWORK ANDELECTRICAL TRADES. REFER TO DETAIL SHEETS M7.01 AND M7.02 FOR TYPICAL COIL,EQUIPMENT, VALVE AND PIPING INFORMATION.
CORE HOLES IN WALLS AND FLOORS FOR PIPES, PROVIDE SLEEVES, AND FIRE STOP TOMAINTAIN WALL/FLOOR RATING. SEE CODE COMPLIANCE PLANS FOR RATINGS.
ALL PIPING BRANCHES SHALL HAVE ISOLATION VALVES LOCATED ABOVE THE CEILING(INCORRIDORS) OR MECHANICAL ROOMS AND/0R CLOSETS AT AN ACCESSIBLE LOCATION ANDHEIGHT. INTENT OF DESIGN IS FOR ALL DUCTWORK TO BE LOCATED HIGH AS POSSIBLE WHEREPIPING AND DUCTWORK CROSS OR INHABIT SAME LOCATIONS, ALL HYDRONIC PIPING SHALL BELOCATED UNDER DUCTWORK. COORDINATE INSTALLATION WITH MECHANICAL/HVACCONTRACTOR.
PATCH AND REPAIR ALL EXISTING PIPE INSULATION WHERE NEW HOT WATER HEATING SUPPLYAND RETURN PIPING CONNECTS TO EXISTING PIPING, TYPICAL.
COORDINATE PIPING AND THERMOSTATS WITH APPROPRIATE TRADES TO AVOIDINTERFERENCES.
GENERAL HYDRONIC PIPING NOTES:
1.
2.
3.
4.
5.
6.
7.
M
11
4
6
7
9
A B C D F G H L
12
3
4" G DN
G (1/4 PSI)
G
4" G HEADER
4" G DN TOBOILER, TYP2 PLACES
UH-4
HTG.
COI
L
CLG.
COI
L
1" G DNTO UH
PLUG VALVE,TYP 2 PLACES
BALL VALVE
G (1
/4 PS
I)
4"
1"
EXIST DWH
CONN 1" G INTOEXIST G TO DWH.FIELD VERIFY SIZEAND ACTUAL LOC
F.D.
F.S.2" COND. DRAINW/ TRAP
EXIST. F.D.
EQ-4
EQ-10
B-1 B-2
CHILR-1CHILR-2
P-15
P-14
4"ø CHGR
4"ø CHGS
4"ø HWS
4"ø HWR
SEE SIXTH FLOORHYDRONIC PIPING PLAN FORCONTINUATION DOWN.
4"ø CHGR
4"ø HWS
4"ø CHGS
4"ø HWR
MAINTAIN AHUSERVICE
CLEARANCE
4"ø Hydronic Supply
4"ø CHGS
6"ø CHGR 6"ø CHGS
4"ø CHGR
4"ø CHGS
2.1/2" HEATRECOVERY S&R
P-9P-8P-2P-1
P-6
P-7
P-13
P-10P-5
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M3.5
5-2420
PHASE 2 - ENLARGEDPENTHOUSE HYDRONIC
PIPING PLAN - ADDENDUM
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
1/4" = 1'-0"1 HYDRONIC PIPING PENTHOUSE
PI
PI
MAKE-UPWATER METER
AIRSEPARATOR
1" CW MAKEUP.REFER TO PLUMBINGDRAWINGS FOR CONT.
M
EXPANSION TANK
1"
1" AIR GAP
1"
1/4"
1"
1"
AIR-COOLED CHILLER
GLYCOL FILLSTATION
1"
PIPE TOFLOOR DRAIN
AIR-COOLED CHILLER
4"CHGR 4" CHGR
4" CHGS4" CHGS
6" CHGS
6" CHGR6" CHGR
X" CHGS
6" CHGR6" CHGS
6" CHGR
CHLR-1
MECHANICAL PENTHOUSEROOF
CHLR-2
BOILER BOILER
FLOORDRAIN
x;PIPE BOILER DRAINSINDIVIDUALLY TOFLOOR DRAINS.
6" HWR
60 GPM
2.1/2"
1"
1"
100 GPM
x;4" CONCRETE HOUSEKEEPINGPAD BY MECH. CONTRACTOR,TYPICAL.
100 GPM
3" HWS 3" HWS
NOTE: PIPE BOILERS PER MANUFACTURER'S RECOMMENDATIONS.
6" HWS&R
1. LAYOUT PIPING TO MINIMIZE FITTINGS AND PRESSURE DROP.
X" HWS&R TO FINNED TUBE
X" HWS&R TO VAV BOXES
60 GPM
2.1/2"
EQ-2
P-5
P-3 P-4
NOTES:
B-1 B-2
EQ-6
P-10
FILTER
60 GPM
FILTER
60 GPM
X" CHGS&R BRANCHESTO BUILDING. SEE HYDRONICPLANS FOR CONTINUATION.
EQ-5
HOT WATER HEATING FLOW DIAGRAM
EQ-1
P-2
EQ-3
P-1
VARIABLE AIR VOLUME BOX HOT WATER LOOP
FINNED TUBE HOT WATER LOOP
EQ-4
P-6
P-7
CHILLED GLYCOL/WATER PIPING SCHEMATIC
P-8 P-9
EQ-7
EQ-9
EQ-10
EQ-8
EQ-11
6" HWR
6" HWS
4" HWSBYMECH.CONT'R
BYPLUMB.CONT'R
1" CW MAKE-UPREFER TOPLUMBINGDWG'S. FOR CONT.
1"
WATER MAKE-UPMETER
3/4" PIPE TOFL. DRAIN
EXPANSION TANK
1"
3/4" PIPE TOFL. DRAIN, TYP.OF EXP.TANKS.
1"
HYDRONIC FLR. PLANS.REFER TO HYDRONICPIPING DRAWINGS FORACTUAL LAYOUT OFPIPING TO EQUIPMENT.
N.T.S.
6" HWS
6" HWS
1"
PI
SD
PI
PI
PI
6"HWS
6" HWR
POT FEEDER
AIR SEPARATOR
MAX 12"
PI
SD
6"HWS
PI
BALL VALVE
TEMPERATURECONTROL VALVE
THERMOMETER
"Y" STRAINER W/BLOWDOWN
B&G CIRCUIT SETTER
PROVIDE PUMPFLOOR SUPPORT.
FLEXCONNECTOR,TYPICAL
PI
BALL VALVE
TEMPERATURECONTROL VALVE
THERMOMETER
"Y" STRAINER W/BLOWDOWN
B&G CIRCUIT SETTERPROVIDE PUMPFLOOR SUPPORT.
FLEXCONNECTOR,TYPICAL
4" HWR
N.T.S.
N.T.S.
6" HWR
3" HWR 3" HWS
6" HWS
N.T.S.
PI
SD
6"CHGR
PI
SD
6"CHGR
PI
POT FEEDER
M
D/P
D/P
D/P
D/P
D/P
D/P D/P
D/P
X" BYPASS
PROVIDE INSULATION & HEAT TAPEON ALL EXTERIOR PIPING, TYPICAL.
PROVIDE INSULATION & HEAT TAPEON ALL EXTERIOR PIPING, TYPICAL.
P-14PI
"Y" STRAINER W/BLOWDOWN
PROVIDE PUMPFLOOR SUPPORT.
FLEXCONNECTOR,TYPICAL
P-15PI
"Y" STRAINER W/BLOWDOWN
FLEXCONNECTOR,TYPICAL
THERMOMETER
46 GPM46 GPM
VFDVFD
VFDVFD
VFD
VFD
PROVIDE PUMPFLOOR SUPPORT.
VFD
VFD
2.1/2"2.1/2"
PIPE TO FLOOR DRAIN, TYP.
12" MAX
3"
TCV-2
TCV-1
TCV-6
TCV-5
TCV-3
TCV-4
TCV-1
TCV-2
TCV-3
TCV-4
TCV-5
TCV-6
CHILLER SHUT-OFF VALVE
CHILLER SHUT-OFF VALVE
FINTUBE LOOP CONTROL VALVE
VAV LOOP CONTROL VALVE
LOW FLOW HTG. BYPASS VALVE
LOW FLOW CLG. BYPASS VALVE
TEMPERATURE CONTROL VALVES
3" HWR 3" HWR
6" HWR
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M4.0
5-2420
PHASE 2 - HOT WATER &CHILLED WATER HYDRONIC
PIPING SCHEMATICS
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
THE FLEXIBLE DUCTWORK CORE SHALL BE CLAMPED(ZIP-STRIPS CAN ALSO BE USED) AND TAPED AT ALLCONNECTIONS. ALSO, THE FLEXIBLE DUCTWORKJACKET/INSULATION SHALL BE TAPED AT ALL CONNECTIONS.TAPE SHALL MEET REQUIREMENTS OF UL181B-FX. REFER TOSPECIFICATIONS FOR ADDITIONAL INFORMATION.
ACCEPTABLE INSTALLATION
ACCEPTABLE INSTALLATION BOTTOM TAKE OFF (ACCEPTABLE)
ACCEPTABLE INSTALLATION
NOTE:
1. FLEXIBLE DUCTWORK SHALL NOT EXCEED 3'-0" IN LENGTH.
2.
SUPPLY AIR DUCT,REFER TO PLANSFOR SIZE (TYP.).
LO-LOSS FITTING (TYP.)
VOLUME DAMPER (TYP.)
LOW PRESSUREFLEXIBLE DUCT (TYP.)
SUPPLY AIR DIFFUSER, REFERTO EQUIPMENT SCHEDULE (TYP.)
PROVIDE DUCT TRANSITION ATDIFFUSER IF REQUIRED. (TYP.)
1.5 DIAMETER BEND RADIUSPREFERRED, BUT 1.0 DIAMETERBEND RADIUS EXCEPTED WHERESPACE RESTRICTIONS EXIST (TYP.)
PROVIDE HANGERS (TYP.)
PROVIDE SADDLESFOR FLEX (TYP.)
UNSUPPORTED AND UNCONSTRAINEDBENDS OR TURNS LESS THAN TWODIAMETERS, OR ALLOWANCE OF ANYSAGGING, IS NOT ACCEPTED.
MIN. OF 2 DUCT DIAMETERS
1.5 DIAMETER BEND RADIUSPREFERRED, BUT 1.0 DIAMETERBEND RADIUS EXCEPTED WHERESPACE RESTRICTIONS EXIST (TYP.)
3. ALL DUCT TAKE-OFFS FROM SUPPLY AND RETURN DUCTMAINS SHALL BE 45" DEGREE LO-LOSS TYPE.
0' - 0 21/32"
45 TEE 90 TEE 45/90 TEE CONICAL 90 TEELO-LOSS90 TEE
REDUCER RECTANGULARDUCT TRANSITION
SHEET METALSCREWS ON MAX.15 DEG. CENTERS
ORIFICE WHERENOTED ON PLANS
SPIRAL DUCT
COLLAR BRUSHED WITHDUCT SEALER BEFOREASSEMBLY
CONTRACTION ANGLE NOTTO EXCEED 45 DEG.
ENLARGEMENT ANGLE NOTTO EXCEED 22.5 DEG.
WYE BRANCH
SPACING PERSPECIFICATIONS
PIPE INSULATIONPER SPECIFICATIONS
PIPE INSULATIONINSERT PER SPECS.
ADJUSTABLE CLEVISHANGER
ROD SIZE AND
PIPE INSULATIONSHIELD PER SPECS.
UNIT
POSITIVE STATIC PRESSURE TRAPPING:
NEGATIVE STATIC PRESSURE TRAPPING:
X
H
TOTALHEIGHTOF TRAP
TO DRAIN
SLOPE DN.
CLEANOUT PLUG
CAPPED TEE FORRENEWING SEAL
X = 1/2 "H"
H = AT LEAST 1 INCH PLUS UNIT STATIC PRESSURE
X = AT LEAST 1 INCH PLUS UNIT STATIC PRESSURE
H = AT LEAST 1 INCH
TOTAL HEIGHT OF TRAP = X + H + (1.1/2 x PIPE DIAMETER)
(AHU, ERU, ETC.)
B & G CIRCUIT SETTER
THERMOSTAT
TEMPERATURE CONTROLVALVE. SELF-CONTAINEDOR CONTROLLED BY WALLTHERMOSTAT. SEE SCHED.
NOTE: DRAIN & VENTS SHALLBE 3/4" BOILER DRAIN COCKSWITH CAPS, TYPICAL.
FINNED ELEMENT
VENT
CONVECTOR HOUSING
BALL VALVE
NOTE: UNIONS SHOWNFOR STEEL PIPE ONLY.
FINNED ELEMENT
DRAIN
VENT
BALL VALVE
DANFOSS SELF-OPERATEDTEMP. CONTROL VALVE
B&G CIRCUIT SETTER PLUSCOMBINATION BALANCE /ISOLATION VALVE
FINTUBE ENCLOSURE(EXISTING)
SUPPLYHOT WATERRETURN
HOT WATER
STRAINER W/ BLOWDOWN VALVE NOTES:1. UNIONS SHOWN FOR STEEL PIPE ONLY.2. DRAIN & VENTS SHALL BE BALL VALVES WITH PLUGS.
SCH. 40 STEEL PIPE SLEEVE.
SUPPORT PIPE OUTSIDEOF WALL CAVITY.
PROVIDE CHROME-PLATED ESCUTCHEONIN FINISHED AREAS.
FILL SPACE W/FIRE-STOP SEALANT,REFER TO SPECIFICATION.
FILL SPACE W/MINERAL WOOL,REFER TO SPECIFICATIONS
PROVIDE CHROME-PLATED ESCUTCHEONIN FINISHED AREAS
SCH.40 STEEL PIPESLEEVE.
SUPPORT PIPE INSIDE &OUTSIDE OF WALL CAVITY
PIPE INSULATION
FIRE-STOP SEALANT,REFER TO SPECIFICATIONS
RATED FLOOR
CLEARANCE: 1/8" PER FOOTOF DAMPER WIDTH OR HEIGHT.MIN. 1/4" & MAX. 1.1/2"
DUCT (SEE PLAN FOR SIZE)
BREAKAWAY CONNECTION PERSMACNA RECOMMENDATIONS
RETAINING ANGLES SHALL BE 16 GAUGESTEEL (MIN.) WITH MIN. 1.1/2" x1.1/2"LEGS, TYP. OF ALL SIDES. ATTACH TOSLEEVE PER MANF. REC., DO NOT ANCHORTO FLOOR. ANGLES SHOULD SANDWISH FLOR.TO ALLOW FOR EXPANSION AND OVERLAPOPENING A MIN. OF 1" + CLEARANCE.
PROVIDE ACCESS DOORSEE SPEC., LOCATE PERDAMPER MFG. REC.
FIRE DAMPER,REFER TO SPEC.
6" MAX. / 3" MIN.,TYPICAL.
DAMPER SLEEVE GAUGE PERMFG. REC., 10 GAUGE, MAX.
HOT WATER RETURN
B&G CIRCUIT SETTER
VENT
UNIT HEATERREFER TOEQUIPMENTSCHEDULE
PIPE REDUCER, TYPICALNOTE: DRAIN & VENTS SHALLBE 3/4" BOILER DRAIN COCKSWITH CAPS, TYPICAL.
HOT WATER SUPPLY
BALL VALVE
THERMOSTAT
T
B&G CIRCUIT SETTER
NOTE: INSTALL VENTSON COIL IF TAPS ARE
AVAILABLE.
BALL VALVE ORBUTTERFLY VALVE
THERMOMETER
THERMOSTAT
TEMP. CNTL. VALVE(VERIFY PORT CONNECTION
W/ MANUFACTURER)
STRAINER WITHBLOWDOWN VALVE
VENT
VENT
DRAIN
DRAIN
HOT OR CHILLED WATER SUPPLY
HOT OR CHILLED WATER RETURN
HEATING ORCOOLING COIL
PI
T
NOTES:1. ALL DRAINS & VENTS SHALL BE BALL VALVES WITH PLUGS.2. UNIONS SHOWN FOR STEEL PIPING ONLY.3. CONTRACTOR TO VERIFY QUANTITY AND SIZE OF COIL CONNECTIONS4. IF PUMP IS BASE MOUNTED TYPE, INCLUDE VALVES AND FITTINGS FOR PUMP PER ZONE PUMP DETAIL.
EQUIPMENT FLASHING
ROOF CURB (SIZEAS REQUIRED FOREQUIPMENT)
OPENING IN ROOF
FLASH CURB INTO ROOF
ROOF STRUCTURE
ROOF OPENINGFRAMING ANGLES (SEEPLANS FOR SIZE)3.1/2"x5"x1/4" MIN.
S
B&G CIRCUIT SETTER
NOTE: DRAIN & VENTS SHALLBE BALL VALVES WITH PLUGS, TYP.
BALL VALVE
HOT WATER RETURN
HOT WATER SUPPLY
TEMPERATURE CONTROLVALVE. SEE MECH. EQUIP.SCHED. FOR VALVE TYPE.
PIPE REDUCER, TYPICAL
SENSOR
LOWPRESSUREFLEXIBLE DUCT(4' MAXIMUM)
DISCHARGE DUCTOR PLENUM BOX
COLLAR W/ BALANCEDAMPER HIGH PRESSURE FLEXIBLE
CONNECTION
MINIMUM 6 DUCTDIAMETERS OF STRAIGHTDUCT AT VAV BOX INLET.
PROVIDEHANGERS
MAIN DUCTV.A.V.
BOX
SUPPLY AIR DIFFUSER
PROVIDE SADDLES
REHEAT COIL
BRANCH DUCT
NOTE: DRAIN & VENTS SHALLBE BALL VALVES WITH PLUGS, TYP.
DUCT, REFER TO PLAN FOR SIZE.
RATED WALL
BREAKAWAY CONNECTION PERSMACNA RECOMMENDATIONS.
CLEARANCE: 1/8" PER FOOTOF DAMPER WIDTH OR HEIGHT,MIN. 1/4" / MAX. 1.1/2".
FIRE DAMPER, REFERTO SPECIFICATIONSFOR TYPE.
NOTE: PROVIDE ACCESS DOOR,REFER TO SPECIFICATIONS.LOCATE DOOR PER DAMPERMFG. RECOMMENDATIONS.
6" MAX./3" MIN., TYPICAL.
DAMPER SLEEVE, GAUGE PER MFG.RECOMMENDATIONS, 10 GAUGE MAX.
RETAINING ANGLES SHALL BE 14 GAUGESTEEL (MIN.) WITH MIN. 1.1/2" X 1.1/2" LEGS,TYPICAL. ATTACH TO SLEEVE PER MFG.RECOMMENDATIONS. DO NOT ANCHOR TOWALL. ANGLES SHOULD SANDWICH WALLTO ALLOW FOR EXPANSION AND OVERLAPOPENING A MIN. OF 1"+ CLEARANCE.
RETAINING ANGLES (10 GAUGE MIN.)
FINNED ELEMENT
DRAIN
DANFOSS SELF-OPERATED,TEMP. CONTROL VALVE
B&G CIRCUIT SETTER PLUSCOMBINATION BALANCE/ISOLATION VALVE
HOT WATERRETURN
NOTES:1. UNIONS SHOWN FOR STEEL PIPE ONLY.2. DRAIN & VENTS SHALL BE BALL VALVES WITH PLUGS.
FINNED ELEMENT
VENT
BALL VALVE
SUPPLYHOT WATER
STRAINER W/ BLOWDOWN VALVE
S
T
OR
OR
VALVE SYMBOLS
GATE VALVE
BALL VALVE
GLOBE VALVE
BUTTERFLY VALVE
SWING CHECK VALVE
TRIPLE-DUTY VALVE
PLUG VALVE
DIAPHRAM VALVE
NEEDLE VALVE
ANGLE VALVE
THREE-WAY VALVE
SELF CONTAINED PRESS. RED'G VALVE
EXT. PRESSURE RED'G VALVE
CHECK VALVE
RELIEF / SAFETY VALVE
SOLENOID VALVE
HOSE BIBB
CIRCUIT SETTER
TEMPERATURE CONTROL VALVE
3-WAY TEMPERATURE CONTROL
SELF OPERATED VALVE
BACKFLOW PREVENTERWITH DRIP PAN
INDICATES VALVE IS FLANGED (TYP)
ABBREVIATIONS
AFFBFWBODBOG
CABOP
CHCONVCOCWDCWDHWDHWREAEFFCOFDFPGHWRHWSOAPIVRECIRCRWR
RARWS
SANSTSASWTODTOGTOPVVDVTRUHWWCOWH
ABOVE FINISHED FLOORBOILER FEED WATERBOTTOM OF DUCTBOTTOM OF GRILLEBOTTOM OF PIPECOMPRESSED AIRCHILLED GLYCOL RETURNCHILLED GLYCOL SUPPLYCABINET HEATERCONVECTORCLEAN-OUT
DOMESTIC COLD WATERDOMESTIC COLD WATER
DOMESTIC HOT WATERDOMESTIC HOT WATER RETURNEXHAUST AIREXHAUST FANFLOOR CLEAN-OUTFLOOR DRAINFIRE PROTECTIONNATURAL GASHOT WATER RETURN (HEATING)HOT WATER SUPPLY (HEATING)OUTSIDE AIRPOST INDICATOR VALVEDOMESTIC HOT WATER RETURNRADIANT WATER RETURN
RETURN AIRSANITARY WASTESTORM WATERSUPPLY AIRSOFTWATERTOP OF DUCTTOP OF GRILLETOP OF PIPEVENTVOLUME DAMPERVENT THRU ROOFUNIT HEATERWASTEWALL CLEAN-OUTWALL HYDRANT
RADIANT WATER SUPPLY
CGRCGS
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M7.0
5-2420
PHASE 2 - MECHANICALDETAILS
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NOT TO SCALEM7.01 CEILING DIFFUSER FLEX CONNECTION
NOT TO SCALEM7.02 HIGH VELOCITY ROUND DUCT FITTINGS
NOT TO SCALEM7.03 CHILLED & HOT WATER HEATING HANGER DETAIL
NOT TO SCALEM7.04 CONDENSATE /DRAIN PAN PIPING DETAIL
NOT TO SCALEM7.05 CONVECTOR PIPING DETAIL
NOT TO SCALEM7.06 FINNED TUBE PIPING DIAGRAM
NOT TO SCALEM7.07 FIRE WALL SLEEVE DETAIL
NOT TO SCALEM7.08 FIRE WALL SLEEVE DETAIL - INSULATED PIPE
NOT TO SCALEM7.09 HORIZONTAL FIRE DAMPER DETAIL
NOT TO SCALEM7.010 HOT WATER UNIT HEATER PIPING DETAIL
NOT TO SCALEM7.011 PUMPED COIL PIPING DIAGRAM
NOT TO SCALEM7.012 ROOF CURB DETAIL
NOT TO SCALEM7.013 TYPICAL VAV BOX WITH REHEAT COIL
NOT TO SCALEM7.014 VERTICAL FIRE DAMPER DETAIL
NOT TO SCALEM7.015 MULTIPLE FINNED ELEMENT PIPING DIAGRAM
MECHANICAL EQUIPMENT SCHEDULEMark
EQ-1
EQ-2
EQ-3
EQ-4
Manufacturer Model Notes
BELL & GOSSET RL-6 Heating Hot Water System Air Separator: 700 GPM capacity, 6" dia. flanged tangential openings and blowdown valve.
UNITED SERIES UFA Heating Hot Water System Filter: Series A Ultra Flow with 2 inch inlet/outlet connections, cover swing bolts, O-ring cover gasket, side drain, upflow design with media inlet at the bottom and clean fluid discharge, ModelUFA-6-2 rated at for 60 gpm with 12 ten inch filter elements, clean pressure drop approx 5-7 psig., BMS monitor DP to change at 20 psig.
WESSELS Heating Hot Water System Pot Feeder: Wessels, Enerco, or equivalent. Refer to Specifications for sizing.
BELL & GOSSET 135 Expansion Tank, Hot Water Heating System: Bell & Gossett model 135, size 24” diameter x 78” length, 135 gallon capacity with ATF-24 Airtrol tank fitting and gauge glass.
EQ-5 Heating Hot Water System Makeup Water Meter: Badger or Carlon, nutating disc water meter with electric contact register, 3/4 inch size, 10 gallons per contact indication.
EQ-6 UNITED SERIES UFA Chilled Glycol/Water System Filter: Series A Ultra Flow with 2 inch inlet/outlet connections, cover swing bolts, O-ring cover gasket, side drain, upflow design with media inlet at the bottom and clean fluid discharge, ModelUFA-6-2 rated at for 60 gpm with 12 ten inch filter elements, clean pressure drop approx 5-7 psig., BMS monitor DP to change at 20 psig.
EQ-7 WESSELS Chilled Glycol/Water System Pot Feeder: Wessels, Enerco, or equivalent. Refer to Specifications for sizing.
EQ-8 Chilled Glycol/Water System Makeup Water Meter: Badger or Carlon, nutating disc water meter with electric contact register, 3/4 inch size, 10 gallons per contact indication.
EQ-9 BELL & GOSSET RL-6 Chilled Glycol/Water System Air Separator: 700 GPM capacity, 6" dia. flanged tangential openings and blowdown valve.
EQ-10 BELL & GOSSET 60 Expansion Tank, Chilled Glycol Water Cooling System: Bell & Gossett model 60, size 16” diameter x 72” length, 60 gallon capacity with ATF-16 Airtrol tank fitting and gauge glass.
EQ-11 ENERCO AGF-1 Geothermal Glycol Fill System, Lower Level North Mechanical Room: Enerco AGF-1 Glycol Feeder with 55 gallon polyethylene solution tank, unit mounted injection pump rated at 1/2 HP, 120/1/60, 8.2 amps,pressure relief valves, pressure switch, pressure gauge, in-line check valve, low level cut-off and alarm, dry contact for remote alarm and unit mounted control panel with H-O-A switch rated for 120/1/60, 5 amps.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\L
ocal
Pro
ject
s\5-
2420
M_C
EN
TRA
L_P
AU
L_B
LAN
CH
AR
D.rv
t
M8.0
5-2420
PHASE 2 - MECHANICALEQUIPMENT SCHEDULE
AB-TM
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
VAV SCHEDULE
Mark ModelMax. Cooling
AirflowMin. Cooling
AirflowHeatingAirflow
Unit LeavingAir
Temperature
HeatingFluid Flow
Rate
HeatingFluid
PressureDrop
APD @CoolingAirflow
CoilHeatingCapacity
MBh NotesVAV-1-1 VCWF12 1000 CFM 350 CFM 500 CFM 90 °F 3.14 GPM 0.6 ftH2O 0.27 in-wg 18.98VAV-1-2 VCWF12 1000 CFM 350 CFM 500 CFM 90 °F 3.14 GPM 0.6 ftH2O 0.27 in-wg 18.98VAV-1-3 VCWF10 800 CFM 250 CFM 450 CFM 90 °F 3.64 GPM 2.1 ftH2O 0.27 in-wg 17.08VAV-1-4 VCWF08 400 CFM 250 CFM 250 CFM 90 °F 2.36 GPM 0.5 ftH2O 0.17 in-wg 9.49VAV-1-5 VCWF05 200 CFM 100 CFM 150 CFM 90 °F 0.77 GPM 0.4 ftH2O 0.09 in-wg 5.69 MBHVAV-1-6 VCWF05 200 CFM 100 CFM 150 CFM 90 °F 0.77 GPM 0.4 ftH2O 0.09 in-wg 5.69 MBHVAV-1-7 VCWF05 350 CFM 100 CFM 250 CFM 90 °F 3.29 GPM 5.4 ftH2O 0.24 in-wg 9.49 MBhVAV-1-8 VCWF10 900 CFM 300 CFM 450 CFM 90 °F 3.64 GPM 2.1 ftH2O 0.32 in-wg 17.08VAV-1-9 VCWF05 250 CFM 100 CFM 150 CFM 90 °F 0.77 GPM 0.4 ftH2O 0.12 in-wg 5.69 MBhVAV-1-10 VCWF05 300 CFM 100 CFM 250 CFM 90 °F 3.29 GPM 5.4 ftH2O 0.24 in-wg 9.49 MBhVAV-1-11 VCWF14 1600 CFM 550 CFM 900 CFM 90 °F 7.32 GPM 2.2 ftH2O 0.25 in-wg 34.16VAV-1-12 VCWF05 375 CFM 125 CFM 150 CFM 90 °F 0.77 GPM 0.4 ftH2O 0.36 in-wg 5.69VAV-1-13 VCWF05 300 CFM 100 CFM 250 CFM 90 °F 3.29 GPM 5.4 ftH2O 0.24 in-wg 9.49VAV-1-14 VCWF08 400 CFM 150 CFM 350 CFM 90 °F 7.32 GPM 3.6 ftH2O 0.17 in-wg 13.29VAV-1-15 VCWF10 875 CFM 875 CFM 875 CFM 90 °F 5.18 GPM 1.9 ftH2O 0.23 in-wg 33.21VAV-1-16 VCCF04 200 CFM 200 CFM 200 CFM 55 °F 0.01 in-wgVAV-1-17 VCWF05 350 CFM 100 CFM 175 CFM 90 °F 1.06 GPM 0.7 ftH2O 0.32 in-wg 6.64VAV-1-18 VCWF05 250 CFM 150 CFM 200 CFM 90 °F 1.49 GPM 1.3 ftH2O 0.12 in-wg 7.59VAV-1-19 VCWF10 800 CFM 250 CFM 500 CFM 90 °F 5.24 GPM 4.1 ftH2O 0.17 in-wg 18.98VAV-1-20 VCWF05 200 CFM 100 CFM 150 CFM 90 °F 0.77 GPM 0.4 ftH2O 0.09 in-wg 5.69VAV-2-1 VCWF10 775 CFM 500 CFM 500 CFM 90 °F 5.24 GPM 4.1 ftH2O 0.16 in-wg 18.98VAV-2-2 VCWF05 350 CFM 150 CFM 200 CFM 90 °F 1.49 GPM 1.3 ftH2O 0.32 in-wg 7.59VAV-2-3 VCWF08 400 CFM 150 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 5.79VAV-2-4 VCWF08 400 CFM 150 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-2-5 VCWF08 400 CFM 150 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-2-6 VCWF08 400 CFM 150 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-2-7 VCWF08 400 CFM 175 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.21 in-wg 11.39VAV-2-8 VCWF08 450 CFM 175 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.21 in-wg 11.39VAV-2-9 VCWF10 700 CFM 550 CFM 550 CFM 90 °F 8.04 GPM 9.2 ftH2O 0.21 in-wg 20.88VAV-2-10 VCWF10 900 CFM 200 CFM 500 CFM 90 °F 5.24 GPM 4.1 ftH2O 0.17 in-wg 18.98VAV-2-11 VCWF05 250 CFM 125 CFM 150 CFM 90 °F 0.77 GPM 0.4 ftH2O 0.17 in-wg 5.69VAV-2-12 VCCF04 200 CFM 200 CFM 200 CFM 55 °F 0.01 in-wg Cooling Only BoxVAV-2-13 VCWF05 225 CFM 100 CFM 150 CFM 90 °F 0.77 GPM 0.4 ftH2O 0.09 in-wg 5.69VAV-2-14 VCWF08 400 CFM 150 CFM 200 CFM 90 °F 1.50 GPM 0.2 ftH2O 0.17 in-wg 7.59VAV-2-15 VCWF08 400 CFM 150 CFM 325 CFM 90 °F 5.27 GPM 2.0 ftH2O 0.17 in-wg 12.34VAV-2-16 VCWF08 400 CFM 150 CFM 250 CFM 90 °F 2.36 GPM 0.5 ftH2O 0.17 in-wg 9.49VAV-2-17 VCWF08 400 CFM 150 CFM 250 CFM 90 °F 2.36 GPM 0.5 ftH2O 0.17 in-wg 9.49VAV-2-18 VCWF08 425 CFM 175 CFM 325 CFM 90 °F 5.27 GPM 2.0 ftH2O 0.19 in-wg 12.34VAV-2-19 VCWF08 425 CFM 175 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.19 in-wg 11.39VAV-2-20 VCWF08 450 CFM 175 CFM 225 CFM 90 °F 1.88 GPM 0.3 ftH2O 0.21 in-wg 8.54VAV-2-21 VCWF08 400 CFM 175 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.21 in-wg 11.39VAV-2-22 VCWF08 400 CFM 150 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-2-23 VCWF08 400 CFM 150 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-2-24 VCWF08 400 CFM 150 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-2-25 VCWF08 400 CFM 150 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-2-26 VCWF08 400 CFM 150 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-2-27 VCWF08 450 CFM 175 CFM 400 CFM 90 °F 2.55 GPM 0.6 ftH2O 0.29 in-wg 15.18VAV-2-28 VCWF10 600 CFM 200 CFM 300 CFM 90 °F 1.44 GPM 0.4 ftH2O 0.17 in-wg 11.39VAV-2-29 VCWF05 200 CFM 200 CFM 125 CFM 90 °F 0.56 GPM 0.2 ftH2O 0.08 in-wg 4.74VAV-2-30 VCCF04 200 CFM 200 CFM 200 CFM 55 °F 0.01 in-wg Cooling Only BoxVAV-2-31 VCWF08 550 CFM 175 CFM 275 CFM 90 °F 3.02 GPM 0.7 ftH2O 0.29 in-wg 10.44VAV-2-32 VCWF10 600 CFM 200 CFM 350 CFM 90 °F 1.92 GPM 0.6 ftH2O 0.17 in-wg 13.29VAV-2-33 VCWF05 325 CFM 325 CFM 200 CFM 90 °F 1.49 GPM 1.3 ftH2O 0.32 in-wg 7.59VAV-2-34 VCWF10 600 CFM 200 CFM 500 CFM 90 °F 5.24 GPM 4.1 ftH2O 0.17 in-wg 18.98VAV-2-35 VCWF08 400 CFM 150 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-2-36 VCWF08 400 CFM 150 CFM 325 CFM 90 °F 5.27 GPM 2.0 ftH2O 0.17 in-wg 12.34VAV-2-37 VCWF08 400 CFM 150 CFM 325 CFM 90 °F 5.27 GPM 2.0 ftH2O 0.17 in-wg 12.34VAV-2-38 VCWF10 600 CFM 200 CFM 300 CFM 90 °F 1.44 GPM 0.4 ftH2O 0.17 in-wg 11.39VAV-2-39 VCWF10 600 CFM 200 CFM 300 CFM 90 °F 1.44 GPM 0.4 ftH2O 0.17 in-wg 11.39VAV-2-40 VCWF05 200 CFM 100 CFM 150 CFM 90 °F 0.77 GPM 0.4 ftH2O 0.09 in-wg 5.69VAV-3-1 VCWF08 450 CFM 150 CFM 225 CFM 90 °F 1.88 GPM 0.3 ftH2O 0.21 in-wg 8.54VAV-3-2 VCWF08 400 CFM 125 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-3-3 VCWF08 400 CFM 125 CFM 250 CFM 90 °F 2.36 GPM 0.5 ftH2O 0.17 in-wg 9.49VAV-3-4 VCWF08 400 CFM 125 CFM 250 CFM 90 °F 2.36 GPM 0.5 ftH2O 0.17 in-wg 9.49VAV-3-5 VCWF08 400 CFM 125 CFM 325 CFM 90 °F 5.27 GPM 2.0 ftH2O 0.17 in-wg 12.34VAV-3-6 VCWF10 600 CFM 400 CFM 400 CFM 90 °F 2.61 GPM 1.1 ftH2O 0.24 in-wg 15.18VAV-3-7 VCWF10 750 CFM 225 CFM 350 CFM 90 °F 1.92 GPM 0.6 ftH2O 0.24 in-wg 13.29VAV-3-8 VCCF04 200 CFM 100 CFM 100 CFM 55 °F 0.01 in-wg Cooling Only BoxVAV-3-9 VCWF10 650 CFM 200 CFM 325 CFM 90 °F 1.66 GPM 0.5 ftH2O 0.19 in-wg 12.34VAV-3-10 VCWF05 250 CFM 100 CFM 150 CFM 90 °F 0.77 GPM 0.4 ftH2O 0.17 in-wg 5.69VAV-3-11 VCWF08 400 CFM 125 CFM 200 CFM 90 °F 1.50 GPM 0.2 ftH2O 0.17 in-wg 7.59VAV-3-12 VCWF05 300 CFM 100 CFM 150 CFM 90 °F 0.77 GPM 0.4 ftH2O 0.24 in-wg 5.69VAV-3-13 VCWF10 600 CFM 200 CFM 300 CFM 90 °F 1.44 GPM 0.4 ftH2O 0.17 in-wg 11.39VAV-3-14 VCWF08 400 CFM 125 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-3-15 VCWF08 400 CFM 125 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-3-16 VCWF08 400 CFM 125 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-3-17 VCWF08 400 CFM 125 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-3-18 VCWF10 675 CFM 200 CFM 375 CFM 90 °F 2.23 GPM 0.9 ftH2O 0.20 in-wg 14.23VAV-3-19 VCWF08 500 CFM 150 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.25 in-wg 11.39VAV-3-20 VCWF08 400 CFM 125 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-3-21 VCWF08 400 CFM 125 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-3-22 VCWF08 400 CFM 125 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-3-23 VCWF08 400 CFM 125 CFM 200 CFM 90 °F 1.50 GPM 0.2 ftH2O 0.17 in-wg 7.59VAV-3-24 VCWF08 400 CFM 125 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-3-25 VCWF05 350 CFM 125 CFM 175 CFM 90 °F 1.06 GPM 0.7 ftH2O 0.32 in-wg 6.64VAV-3-26 VCWF08 400 CFM 150 CFM 300 CFM 90 °F 1.50 GPM 0.2 ftH2O 0.17 in-wg 7.59VAV-3-27 VCCF04 200 CFM 100 CFM 100 CFM 55 °F 0.01 in-wg Cooling Only BoxVAV-3-28 VCWF05 275 CFM 100 CFM 150 CFM 90 °F 0.77 GPM 0.4 ftH2O 0.09 in-wg 5.69VAV-3-29 VCWF12 1260 CFM 400 CFM 650 CFM 90 °F 6.16 GPM 2.0 ftH2O 0.38 in-wg 24.67VAV-3-30 VCWF10 810 CFM 250 CFM 450 CFM 90 °F 3.64 GPM 2.1 ftH2O 0.27 in-wg 17.08VAV-3-31 VCWF10 600 CFM 200 CFM 425 CFM 90 °F 3.07 GPM 1.5 ftH2O 0.17 in-wg 16.13VAV-3-32 VCWF08 400 CFM 150 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.17 in-wg 11.39VAV-3-33 VCWF08 300 CFM 150 CFM 275 CFM 90 °F 3.02 GPM 0.7 ftH2O 0.13 in-wg 10.44VAV-3-34 VCWF08 400 CFM 150 CFM 275 CFM 90 °F 3.02 GPM 0.7 ftH2O 0.17 in-wg 10.44VAV-3-35 VCWF08 400 CFM 150 CFM 200 CFM 90 °F 1.50 GPM 0.2 ftH2O 0.17 in-wg 7.59VAV-3-36 VCWF08 400 CFM 150 CFM 250 CFM 90 °F 2.36 GPM 0.5 ftH2O 0.17 in-wg 9.49VAV-3-37 VCWF08 400 CFM 150 CFM 275 CFM 90 °F 3.02 GPM 0.7 ftH2O 0.17 in-wg 10.44VAV-3-38 VCWF08 400 CFM 150 CFM 275 CFM 90 °F 3.02 GPM 0.7 ftH2O 0.17 in-wg 10.44VAV-3-39 VCWF08 400 CFM 150 CFM 275 CFM 90 °F 3.02 GPM 0.7 ftH2O 0.17 in-wg 10.44VAV-3-40 VCWF08 400 CFM 150 CFM 275 CFM 90 °F 3.02 GPM 0.7 ftH2O 0.17 in-wg 10.44VAV-3-41 VCWF08 400 CFM 150 CFM 275 CFM 90 °F 3.02 GPM 0.7 ftH2O 0.17 in-wg 10.44VAV-3-42 VCWF08 500 CFM 150 CFM 250 CFM 90 °F 2.36 GPM 0.5 ftH2O 0.25 in-wg 9.49VAV-3-43 VCWF10 925 CFM 500 CFM 500 CFM 90 °F 5.24 GPM 4.1 ftH2O 0.34 in-wg 18.98VAV-3-44 VCWF10 600 CFM 375 CFM 375 CFM 90 °F 2.23 GPM 0.9 ftH2O 0.20 in-wg 14.23VAV-3-45 VCWF08 500 CFM 180 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.25 in-wg 11.39VAV-3-46 VCWF08 500 CFM 300 CFM 300 CFM 90 °F 3.94 GPM 1.2 ftH2O 0.25 in-wg 11.39VAV-3-47 VCWF10 700 CFM 400 CFM 400 CFM 90 °F 2.61 GPM 1.1 ftH2O 0.21 in-wg 15.18VAV-3-48 VCWF10 600 CFM 200 CFM 300 CFM 90 °F 1.44 GPM 0.4 ftH2O 0.17 in-wg 11.39VAV-3-49 VCWF08 400 CFM 150 CFM 200 CFM 90 °F 1.50 GPM 0.2 ftH2O 0.34 in-wg 7.59VAV-3-50 VCWF08 400 CFM 150 CFM 200 CFM 90 °F 1.50 GPM 0.2 ftH2O 0.17 in-wg 7.59VAV-3-51 VCWF08 400 CFM 150 CFM 200 CFM 90 °F 1.50 GPM 0.2 ftH2O 0.17 in-wg 7.59VAV-3-52 VCWF08 400 CFM 150 CFM 200 CFM 90 °F 1.50 GPM 0.2 ftH2O 0.17 in-wg 7.59VAV-3-53 VCWF08 400 CFM 150 CFM 200 CFM 90 °F 1.50 GPM 0.2 ftH2O 0.17 in-wg 7.59VAV-3-54 VCWF10 600 CFM 200 CFM 300 CFM 90 °F 1.44 GPM 0.4 ftH2O 0.17 in-wg 11.39VAV-3-55 VCWF08 500 CFM 200 CFM 250 CFM 90 °F 2.36 GPM 0.5 ftH2O 0.25 in-wg 9.49VAV-3-56 VCWF05 350 CFM 125 CFM 175 CFM 90 °F 1.06 GPM 0.7 ftH2O 0.32 in-wg 6.64VAV-3-57 VCWF10 800 CFM 400 CFM 400 CFM 90 °F 2.61 GPM 1.1 ftH2O 0.27 in-wg 15.18VAV-3-58 VCWF08 500 CFM 200 CFM 250 CFM 90 °F 2.36 GPM 0.5 ftH2O 0.25 in-wg 9.49VAV-3-59 VCWF05 300 CFM 125 CFM 200 CFM 90 °F 1.49 GPM 1.3 ftH2O 0.24 in-wg 7.59VAV-3-60 VCCF04 200 CFM 100 CFM 100 CFM 55 °F 0.01 in-wg Cooling Only BoxVAV-3-61 VCWF05 350 CFM 125 CFM 200 CFM 90 °F 1.49 GPM 1.3 ftH2O 0.32 in-wg 7.59
GRAND RAPIDS COMMUNITY COLLEGECOLLEGE PARK PLAZAPHASE 1 – MECHANICAL EQUIPMENT SCHEDULEA/E Project #5-2420GRCC BID #1213-9098
NOTE: THIS IS SHOWN FOR REFERENCE ONLY & REFLECTS UPDATED INFORMATION REQUIRED FOR PHASE 2.
BOILERS
B-1, B-2Boiler, Hot Water Heating, Boiler Room: Aerco Low NOx Benchmark Gas Fired Hot Water Boiler, Model BMK1.5LN, 3" inlet and 3” outletwater connections, 1.1/2" natural gas connection, UL/FM/IRI/CSD-1 gas train and CSD1 firing code, 1,500 MBH input, 1,290 - 1,409MBH output, 6 inch dia. intake and vent size for direct vent/sealed combustion with vent and air inlet caps, (contractor will installAL29-4C stainless steel vent and PVC intake piping). Temperature gauges in/out, T/P relief valve, low water cutoff, drain tee, routevent drain to nearest floor drain, 120/1/60, to produce 120 deg. F heating hot water and condensate neutralization kit. Provided withAerco Boiler Management System II system controller to provide sequencing and lead/lag control. Pipe condensate drain and P/Tvalve discharge to floor drain. Refer to specifications for additional features and accessories and alternate manufacturers.
CHILLERS
CHLR-1, CHLR-2Air Cooled Packaged Outdoor Chiller: Trane Model CGAM 80, scroll packaged chilled glycol system, nominal 80 tons, rated 73.7tons, R-410A, tandem scroll compressors (4 total), (2) circuits, 4 step capacity, oversized shell and tube heat exchanger, 95F/76Fdesign outdoor air temperature, 42F leaving evaporator water temperature, 54F entering evaporator water temperature, 155.1 GPM,30% propylene glycol, 14.1 ft. H2O total pressure drop through evaporator and strainer. Refrigerant System Features: Site glassand low ambient control, 5 year compressor warranty, refrigerant monitoring, alarm, ventilation system for service area, halflouvers, and comprehensive acoustic package. Unit shall include heat recovery: 75.8 kW heating capacity, 120F LWT, 110FEWT, 52.31 GPM, and 13.2 ft. H20 pressure drop. Electrical: 460/3/60, 162.2 MCA, 175 amp max over-current protection device.Electrical connection shall be a single point connection. Disconnect shall be provided and installed by Electrical Contractor.BACnet interface to allow for control by the building management system. Chilled water discharge temperature is to be resetBMS/ATC.
Chiller sound power levels by octave band shall not exceed as follows:
1 2 3 4 5 6 7 887 85 88 92 84 80 76 68
AIR HANDLING UNITS
AHU-1Air Handling Unit, serves the Plaza and Mezzanine Levels: Trane Performance Climate Changer, Size 21 for the air handling unitsections with 6" base rail under entire unit. All sections shall be double-wall construction, solid inner liner throughout except atsupply fan and relief fan sections which shall have perforated metal inner liner, IAQ drain pans, pipe connections on same side asfan motor access and integral control panel housing. The air handling unit section shall have all joints sealed air tight. Lengthsof sections are for reference only. Alternate manufacturers shall verify unit will work in space.
Exhaust Fan Section: (2) 20 inch direct drive plenum fan, 10,300 CFM, 1.0" ESP, 1.415“ TSP, 1617 RPM, 3 HP per motor, 460/3/60,with VFD (provided by control contractor as part of Phase 2 package and installed on/in air handling unit by the electrical contractorin accordance with equipment manufacturer's recommendations), perforated double wall with 2" thick 3.0 pound density insulation.Include expanded metal door guard screen to prevent unauthorized entry to the fan, spring isolators and vapor proof lights withswitch/receptacle. Length: 50.1/4"
Exhaust fan discharge sound power levels by octave band shall not exceed as follows:
1 2 3 4 5 6 7 880 70 81 76 73 75 71 62
Medium Access section: Access door, 2" thick double wall with solid inner liner, 3.0 pound density insulation. Length: 14"
Mixing Box: Access door, top return air opening, back exhaust air opening with opposed blade damper, 2" thick double wall withsolid inner liner, 3.0 pound density insulation. Length: 34”
Traq Mixing Box: Access door, top outdoor air opening with Traq damper, back return air opening with opposed blade damper, 2"thick double wall with solid inner liner, 3.0 pound density insulation. Length: 50.3/8”
Filter Section: Access door, 12” deep cartridge MERV-15 filter section with 2” pleated MERV-8 pre-filter, 2" thick double wall with solidinner liner, 3.0 pound density insulation. Manufacturer shall provide (1) set of final filters and (3) sets of pre-filters. Length: 24.5"
Medium Heating Coil: 2" thick double wall with solid inner liner, 3.0 pound density insulation. Heating Coil: coil type UW, 4 row, FinType Delta Flo E, 89 FPF, 10,300 CFM, 55 EDB, 120 EWT, 90 LDB, 391 total MBH, 26.1 GPM, 30^ TD, 0.283" APD, 2.4 ft. WPD, withturbulators. Length: 14”
Medium Large Access section: Access door, 2" thick double wall with solid inner liner, 3.0 pound density insulation. Length:24.1/2"
Medium Large Cooling Coil: 2" thick double wall with solid inner liner, 3.0 pound density insulation. 30% Propylene Glycol CoolingCoil: coil type W, 8 row, Fin Type Prima Flo E, 95 FPF, 10,300 CFM, 79.0 EDB, 66.0 EWB, 52.0 LDB, 51.9 LWB, 432.7 total MBH, 42FEWT, 78.1 GPM, 12^ TR, 0.743" APD, 17.4 ft. WPD, with turbulators. Length: 24.1/2”
Medium Large Access section: Access door, 2" thick double wall with solid inner liner, 3.0 pound density insulation. Length:24.1/2"
Supply Fan Section: (2) 20 inch direct drive plenum fan, 10,300 CFM (2,060 CFM OA Max.), 3.0" ESP, 5.3" TSP, 2216 RPM, 7.5 HPmotor per fan, 460/3/60, with VFD (provided by control contractor as part of Phase 2 package and installed on/in air handling unit bythe electrical contractor in accordance with equipment manufacturer's recommendations), perforated double wall with 2" thick 3.0pound density insulation. Include expanded metal door guard screen to prevent unauthorized entry to the fan, spring isolators andvapor proof lights with switch/receptacle. Length: 50.1/4"
Supply fan discharge sound power levels (without plenum) by octave band shall not exceed as follows:
1 2 3 4 5 6 7 877 69 83 80 79 75 72 66
Contractor will be fabricating a supply air discharge plenum for this unit. More information included in Phase 2 Documents.
AHU-2Air Handling Unit, serves Level Two and Level Three: Trane Performance Climate Changer, Size 35 for the air handling unit sectionswith 6" base rail under entire unit. All sections shall be double-wall construction, solid inner liner throughout except at supply fanand relief fan sections which shall have perforated metal inner liner, IAQ drain pans, pipe connections on same side as fan motoraccess and integral control panel housing. The air handling unit section shall have all joints sealed air tight. Lengths of sectionsare for reference only. Alternate manufacturers shall verify unit will work in space.
Exhaust Fan Section: (2) 24.5 inch direct drive plenum fan, 17,250 CFM, 1.0" ESP, 1.334“ TSP, 1378 RPM, 5 HP per motor, 460/3/60,with VFD (provided by control contractor as part of Phase 2 package and installed on/in air handling unit by the electrical contractorin accordance with equipment manufacturer's recommendations), perforated double wall with 2" thick 3.0 pound density insulation.Include expanded metal door guard screen to prevent unauthorized entry to the fan, spring isolators and vapor proof lights withswitch/receptacle. Length: 55.1/2"
Exhaust fan discharge sound power levels by octave band shall not exceed as follows:
1 2 3 4 5 6 7 881 77 82 77 81 84 80 70
Medium Access section: Access door, 2" thick double wall with solid inner liner, 3.0 pound density insulation. Length: 14"
Mixing Box: Access door, top return air opening, back exhaust air opening with opposed blade damper, 2" thick double wall withsolid inner liner, 3.0 pound density insulation. Length: 48”
Traq Mixing Box: Access door, top outdoor air opening with Traq damper, back return air opening with opposed blade damper, 2"thick double wall with solid inner liner, 3.0 pound density insulation. Length: 48”
Filter Section: Access door, 12” deep cartridge MERV-15 filter section with 2” pleated MERV-8 pre-filter, 2" thick double wall with solidinner liner, 3.0 pound density insulation. Manufacturer shall provide (1) set of final filters and (3) sets of pre-filters. Length: 24.5"
Medium Heating Coil: 2" thick double wall with solid inner liner, 3.0 pound density insulation. Heating Coil: coil type UU, 4 row, FinType Delta Flo E, 96 FPF, 17,250 CFM, 55 EDB, 120 EWT, 90 LDB, 654.8 total MBH, 43.8 GPM, 30^ TD, 0.29" APD, 1.3 ft. WPD, withturbulators. Length: 14”
Medium Large Access section: Access door, 2" thick double wall with solid inner liner, 3.0 pound density insulation. Length:24.1/2"
Medium Large Cooling Coil: 2" thick double wall with solid inner liner, 3.0 pound density insulation. 30% Propylene Glycol CoolingCoil: coil type WD, 8 row, Fin Type Prima Flo E, 115 FPF, 17,250 CFM, 79.0 EDB, 66.0 EWB, 52.0 LDB, 51.9 LWB, 728.0 total MBH, 42FEWT, 131.3 GPM, 12^ TR, 0.807" APD, 7.8 ft. WPD, with turbulators. Length: 24.1/2”
Medium Large Access section: Access door, 2" thick double wall with solid inner liner, 3.0 pound density insulation. Length:24.1/2"
Supply Fan Section: (2) 24.5 inch direct drive plenum fan, 17,250 CFM (3,450 CFM OA Max.), 3.0" ESP, 5.391" TSP, 1857 RPM, 15 HPmotor per fan, 460/3/60, with VFD (provided by control contractor as part of Phase 2 package and installed on/in air handling unit bythe electrical contractor in accordance with equipment manufacturer's recommendations), perforated double wall with 2" thick 3.0pound density insulation. Include expanded metal door guard screen to prevent unauthorized entry to the fan, spring isolators andvapor proof lights with switch/receptacle. Length: 55.1/2"
Supply fan discharge sound power levels (without plenum) by octave band shall not exceed as follows:
1 2 3 4 5 6 7 885 73 88 82 83 84 84 77
Contractor will be fabricating a supply air discharge plenum for this unit. More information included in Phase 2 Documents.
AHU-3 – Modified in Addendum #1Air Handling Unit, serves Level Four, Level Five and Level Six: Trane Performance Climate Changer, Size 57 for the air handling unitsections with 6" base rail under entire unit. All sections shall be double-wall construction, solid inner liner throughout except atsupply fan and relief fan sections which shall have perforated metal inner liner, IAQ drain pans, pipe connections on same side asfan motor access and integral control panel housing. The air handling unit section shall have all joints sealed air tight. Lengthsof sections are for reference only. Alternate manufacturers shall verify unit will work in space.
Exhaust Fan Section: (2) 30 inch direct drive plenum fan, 28,500 CFM, 1.0" ESP, 1.339“ TSP, 1276 RPM, 7.5 HP per motor, 460/3/60,with VFD (provided by control contractor as part of Phase 2 package and installed on/in air handling unit by the electrical contractorin accordance with equipment manufacturer's recommendations), perforated double wall with 2" thick 3.0 pound density insulation.Include expanded metal door guard screen to prevent unauthorized entry to the fan, spring isolators and vapor proof lights withswitch/receptacle. Length: 65.0"
Exhaust fan discharge sound power levels by octave band shall not exceed as follows:
1 2 3 4 5 6 7 888 69 75 71 74 80 77 69
Medium Access section: Access door, 2" thick double wall with solid inner liner, 3.0 pound density insulation. Length: 14"
Mixing Box: Access door, top return air opening, back exhaust air opening with opposed blade damper, 2" thick double wall withsolid inner liner, 3.0 pound density insulation. Length: 48”
Traq Mixing Box: Access door, top outdoor air opening with Traq damper, back return air opening with opposed blade damper, 2"thick double wall with solid inner liner, 3.0 pound density insulation. Length: 48”
Filter Section: Access door, 12” deep cartridge MERV-15 filter section with 2” pleated MERV-8 pre-filter, 2" thick double wall with solidinner liner, 3.0 pound density insulation. Manufacturer shall provide (1) set of final filters and (3) sets of pre-filters. Length: 24.5"
Medium Heating Coil: 2" thick double wall with solid inner liner, 3.0 pound density insulation. Heating Coil: coil type W, 3 row, FinType Prima Flo E, 112 FPF, 28,500 CFM, 55 EDB, 120 EWT, 90 LDB, 1081.8 total MBH, 108.5 GPM, 30^ TD, 0.229" APD, 2.4 ft. WPD,without turbulators. Length: 14”
Medium Large Access section: Access door, 2" thick double wall with solid inner liner, 3.0 pound density insulation. Length:24.1/2"
Medium Large Cooling Coil: 2" thick double wall with solid inner liner, 3.0 pound density insulation. 30% Propylene Glycol CoolingCoil: coil type WD, 8 row, Fin Type Prima Flo E, 102 FPF, 28,500 CFM, 79.0 EDB, 66.0 EWB, 52.0 LDB, 51.9 LWB, 1210.2 total MBH,42F EWT, 218.2 GPM, 12^ TR, 0.738" APD, 11.4 ft. WPD, with turbulators. Length: 24.1/2”
Large Access section: Access door, 2" thick double wall with solid inner liner, 3.0 pound density insulation. Length: 48"
Extended Medium Access section: Access door, 2" thick double wall with solid inner liner, 3.0 pound density insulation. Length:19"
Supply Fan Section: (2) 30 inch direct drive plenum fan, 28,500 CFM (5,700 CFM OA Max.), 3.0" ESP, 6.1" TSP, 1587 RPM, 25 HPmotor per fan, 460/3/60, with VFD (provided by control contractor as part of Phase 2 package and installed on/in air handling unit bythe electrical contractor in accordance with equipment manufacturer's recommendations), perforated double wall with 2" thick 3.0pound density insulation. Include expanded metal door guard screen to prevent unauthorized entry to the fan, spring isolators andvapor proof lights with switch/receptacle. Length: 65"
Supply fan discharge sound power levels (without plenum) by octave band shall not exceed as follows:
1 2 3 4 5 6 7 875 71 74 75 74 73 71 67
Supply Air Discharge Plenum: 2” thick double wall with solid inner liner, 3.0 pound density insulation and field cut bellmouth fitting.Length: 56” (Contractor is responsible for field verifying length of plenum prior to final order of unit.)
EXHAUST FAN SCHEDULE
Mark Manufacturer Description Model Air FlowTotal StaticPressure
InletSones
MotorHP Voltage Phase Comments
EF-1 Greenheck Fan Belt DriveCentrifugal InlineFan
BSQ-90-5 1000 CFM 0.38 in-wg 17.6 0.50 hp 115 V 1 Belt drive, premium efficient motor, disconnect switch, galvanized inlet guard, spring hanging vibration isolators and brackets, 1" acoustical insulated fan housing,extended lubrication lines, gravity backdraft damper and spare belts. Controlled by reverse acting thermostat that is provided and installed by the TemperatureControl Contractor - Fan shall be energized when the temperature in the space exceeds 85F (adjustable), interlock with motorized damper in outdoor air ductwork.
EF-2 Greenheck Fan Direct DriveCentrifugal InlineFan
SQ-85-D 300 CFM 0.42 in-wg 7.5 0.08 hp 115 V 1 Direct drive, premium efficient motor, speed controller, gravity backdraft damper, birdscreen, spring hanging vibration isolators and brackets, and factory installeddisconnect switch. Controlled by reverse acting thermostat that is provided and installed by the Temperature Control Contractor - Fan shall be energized when thetemperature in the space exceeds 85F (adjustable), interlock with motorized damper in outdoor air ductwork.
EF-3 Greenheck Fan Direct DriveCentrifugal InlineFan
SQ-85-D 300 CFM 0.42 in-wg 7.5 0.08 hp 115 V 1 Direct drive, premium efficient motor, speed controller, gravity backdraft damper, birdscreen, spring hanging vibration isolators and brackets, and factory installeddisconnect switch. Controlled by reverse acting thermostat that is provided and installed by the Temperature Control Contractor - Fan shall be energized when thetemperature in the space exceeds 85F (adjustable), interlock with motorized damper in outdoor air ductwork.
LOUVER SCHEDULEMark Manufacturer Model Description Notes
L-1 Ruskin ELF6375DX Extruded Aluminum Drainable Stationary Louver Relief Air Discharge Louver, Mechanical Room 003, 8'-6"W x 7'-6"H x 0'-6"D, aluminum drainable blade louver with 37-1/2 degree blade angle, bird screen, standard recess frame with sill extension, and customcolor to be selected by Architect.
L-2 Ruskin ELF6375DX Extruded Aluminum Drainable Stationary Louver Relief Air Discharge Louver, Storage 005, 2'-8"W x 1'-6"H x 0'-6"D, aluminum drainable blade louver with 37-1/2 degree blade angle, bird screen, standard recess frame with sill extension, and custom color to beselected by Architect.
L-3 Ruskin ELF6375DX Extruded Aluminum Drainable Stationary Louver Relief Air Discharge Louver, Penthouse 702, 6'-8"W x 9'-0"H x 0'-6"D, aluminum drainable blade louver with 37-1/2 degree blade angle, bird screen, standard recess frame with sill extension, and custom color tobe selected by Architect.
INTAKE VENTILATOR SCHEDULEMark Manufacturer Model Air Flow Notes
IV-1 Greenheck WIH 28500 CFM Louvered Gravity Intake associated with AHU-3. 58"W x 100"L throat size, 72"W x 114"L hood size, 12 louvers high, 706 FPM throat velocity, and 0.096" SP. Louvers of extruded aluminum, removable cover(s) with fiberglass insulation,galvanized mesh bird screen, and 1" thick insulation. Unit shall include sloped roof curb. Contractor shall field verify roof slope prior to fabrication. Curb shall be 30" minimum above the roof.
PUMP SCHEDULE
Mark Model Series Pump Type Seal Type Impeller SizeRated Speed
(RPM) Flow RatePump
Head (FT) ElectricalMotorPower Comments
P-1 2.5 AB 1510 Base Mounted EndSuction
Standard 1510 6 7/8" 1750 196.0 GPM 40 460/3/60 50 HP Heating Hot Water System Main Pump. Include flex connectors, triple duty valve, invertor duty premium efficiency motorwith variable frequency drive, and pressure transducer. Include Metraflex Cablesphere flexible connectors and cost to trimthe impeller after test and balance to rebalance pump as necessary. Refer to Specifications for more information.
P-2 2.5 AB 1510 Base Mounted EndSuction
Standard 1510 6 7/8" 1750 196.0 GPM 40 460/3/60 50 HP Heating Hot Water System Main Pump. Include flex connectors, triple duty valve, invertor duty premium efficiency motorwith variable frequency drive, and pressure transducer. Include Metraflex Cablesphere flexible connectors and cost to trimthe impeller after test and balance to rebalance pump as necessary. Refer to Specifications for more information.
P-3 2.5x2.5x7 80 In-Line Mounted Stuffing Box 80 5 3/4" 1750 100.0 GPM 25 460/3/60 2 HP Boiler Circulation Pump. Include premium efficiency motor. Refer to Specifications for more information.P-4 2.5x2.5x7 80 In-Line Mounted Stuffing Box 80 5 3/4" 1750 100.0 GPM 25 460/3/60 2 HP Boiler Circulation Pump. Include premium efficiency motor. Refer to Specifications for more information.P-5 1.5x1.5x9.5 80 In-Line Mounted Standard 80 8 1/8" 1750 60.0 GPM 60 460/3/60 3 HP Hot Water System Side Stream Filter Pump. Refer to Specifications for more information.P-6 5x5x9.5B 80 In-Line Mounted Standard 80 7 5/8" 1750 390.0 GPM 50 460/3/60 10 HP VAV Box Loop Hot Water Pump. Include invertor duty premium efficiency motor with variable frequency drive and pressure
transducer. Include Metraflex Cablesphere flexible connectors and cost to trim the impeller after test and balance torebalance pump as necessary. Refer to Specifications for more information.
P-7 2.5x2.5x7 80 In-Line Mounted Standard 80 5 1/2" 1750 100.0 GPM 30 460/3/60 1.5 HP Finned Tube Hot Water Loop Pump. Include invertor duty premium efficiency motor with variable frequency drive andpressure transducer. Include Metraflex Cablesphere flexible connectors and cost to trim the impeller after test and balanceto rebalance pump as necessary. Refer to Specifications for more information.
P-8 2.5 BB 1510 Base Mounted EndSuction
Stuffing Box 1510 8 3/4" 1750 310.0 GPM 60 460/3/60 10 HP Chilled Glycol System Main Pump. Include flex connectors, triple duty valve, invertor duty premium efficiency motor withvariable frequency drive, and pressure transducer. System includes 30% Propylene Glycol. Refer to Specifications formore information.
P-9 2.5 BB 1510 Base Mounted EndSuction
Stuffing Box 1510 8 3/4" 1750 310.0 GPM 60 460/3/60 10 HP Chilled Glycol System Main Pump. Include flex connectors, triple duty valve, invertor duty premium efficiency motor withvariable frequency drive, and pressure transducer. System includes 30% Propylene Glycol. Refer to Specifications formore information.
P-10 1.5x1.5x9.5 80 In-Line Mounted Standard 80 8 1/8" 1750 60.0 GPM 60 460/3/60 3 HP Hot Water System Side Stream Filter Pump. System includes 30% Propylene Glycol. Refer to Specifications for moreinformation.
P-11 1.25x1.25x5.25 60 In-Line Mounted Standard 4 7/8" 1750 40.0 GPM 20 120/1/60 0.5 HP AHU-1 Hot Water Heating Coil Pump. Refer to Specifications for more information.P-12 2.5x2.5x7 80 In-Line Mounted Standard 80 5 1/2" 1750 105.0 GPM 20 460/3/60 1.5 AHU-2 Hot Water Heating Coil Pump. Refer to Specifications for more information.P-13 2.5x2.5x7 80 In-Line Mounted Stuffing Box 80 5 3/8" 1750 100.0 GPM 20 460/3/60 1 HP AHU-3 Hot Water Heating Coil Pump. Refer to Specifications for more information.P-14 2x2x7 80 In-Line Mounted Stuffing Box 80 5 3/4" 1750 50.0 GPM 30 460/3/60 1.5 HP Chiller Heat Recovery Pumps. Include invertor duty premium efficiency motor with variable frequency drive and pressure
tranducer. Refer to Specifications for more information.P-15 2x2x7 80 In-Line Mounted Stuffing Box 80 5 3/4" 1750 50.0 GPM 30 460/3/60 1.5 HP Chiller Heat Recovery Pumps. Include invertor duty premium efficiency motor with variable frequency drive and pressure
tranducer. Refer to Specifications for more information.
DIFFUSER SCHEDULE
MarkSystem
Classification MANUFACTURER DESCRIPTIONMODULE
SIZE
NECK SIZE NECK SIZE
COLOR REMARKSROUNDNECK
SQUARENECK
L-3 Exhaust Air Ruskin Extruded Aluminum Drainable Stationary Louver 82 x 110 Relief Air Discharge Louver, Penthouse 702, 6'-8"W x 9'-0"H x 0'-6"D, aluminum drainable blade louver with 37-1/2 degree blade angle, bird screen,standard recess frame with sill extension, and custom color to be selected by Architect.
Exhaust Air Ruskin Extruded Aluminum Drainable Stationary Louver 96 x 80S-1 Supply Air Titus Architectural Square Plaque Diffuser 12 x 12 6 Steel - Titus - 26 WhiteS-2 Supply Air Titus Architectural Square Plaque Diffuser 24 x 24 6 Steel - Titus - 26 WhiteS-3 Supply Air Titus Architectural Square Plaque Diffuser 24 x 24 8 Steel - Titus - 26 WhiteS-4 Supply Air Titus Architectural Square Plaque Diffuser 24 x 24 10 Steel - Titus - 26 WhiteS-5 Supply Air Titus Architectural Square Plaque Diffuser 24 x 24 10 Steel - Titus - 26 WhiteS-6 Supply Air Titus Architectural Square Plaque Diffuser 24 x 24 12 Steel - Titus - 26 WhiteS-7 Supply Air Titus High Capacity Adjustable Plenum Slot Diffuser 48 x 12 12 Steel - Titus - Flat BlackS-8 Supply Air Titus Adjustable Supply Grille with Double Deflection 6 x 4 6 x 4 Steel - Titus - 26 WhiteS-9 Supply Air Titus Adjustable Supply Grille with Double Deflection 8 x 18 18 x 8 Steel - Titus - 26 WhiteS-10 Supply Air Titus Adjustable Supply Grille with Double Deflection 20 x 6 20 x 6 Steel - Titus - 26 WhiteS-11 Supply Air Titus Linear Fixed Bar Diffuser 61 x 4 61 x 4 Aluminum - Titus - 26 WhiteS-12 Supply Air Titus High Performance Square Cone Diffuser 12 x 12 6 Steel - Titus - 26 White ExistingS-13 Supply Air Titus High Performance Square Cone Diffuser 24 x 24 6 Steel - Titus - 26 White ExistingS-14 Supply Air Titus High Performance Square Cone Diffuser 24 x 24 8 Steel - Titus - 26 White ExistingS-15 Supply Air Titus High Performance Square Cone Diffuser 24 x 24 10 Steel - Titus - 26 White ExistingR-1 Return Air Titus Perforated Square Ceiling Diffuser 12 x 12 6 x 6 Steel - Titus - 26 WhiteR-2 Return Air Titus Perforated Square Ceiling Diffuser 24 x 24 12 x 12 Steel - Titus - 26 WhiteR-3 Return Air Titus Return Grille with 35 Degree Deflection 6 x 6 6 x 6 Steel - Titus - 26 WhiteR-4 Return Air Titus Return Grille with 35 Degree Deflection 8 x 6 8 x 6 Steel - Titus - 26 WhiteR-5 Return Air Titus Return Grille with 35 Degree Deflection 8 x 8 8 x 8 Steel - Titus - 26 WhiteR-6 Return Air Titus Return Grille with 35 Degree Deflection 9 x 6 9 x 6 Steel - Titus - 26 WhiteR-7 Return Air Titus Return Grille with 35 Degree Deflection 10 x 6 10 x 6 Steel - Titus - 26 WhiteR-8 Return Air Titus Return Grille with 35 Degree Deflection 10 x 10 10 x 10 Steel - Titus - 26 WhiteR-9 Return Air Titus Return Grille with 35 Degree Deflection 12 x 10 12 x 10 Steel - Titus - 26 WhiteR-10 Return Air Titus Return Grille with 35 Degree Deflection 12 x 12 12 x 12 Steel - Titus - 26 WhiteR-11 Return Air Titus Return Grille with 35 Degree Deflection 13 x 4 13 x 4 Steel - Titus - 26 WhiteR-12 Return Air Titus Return Grille with 35 Degree Deflection 14 x 6 14 x 6 Steel - Titus - 26 WhiteR-13 Return Air Titus Return Grille with 35 Degree Deflection 18 x 14 18 x 14 Steel - Titus - 26 WhiteR-14 Return Air Titus Return Grille with 35 Degree Deflection 20 x 14 20 x 14 Steel - Titus - 26 WhiteR-15 Return Air Titus Return Grille with 35 Degree Deflection 24 x 10 24 x 10 Steel - Titus - 26 WhiteR-16 Return Air Titus Linear Fixed Bar Diffuser 61 x 4 61 x 4 Aluminum - Titus - 26 WhiteR-17 Return Air 16 x 8 ExistingE-1 Exhaust Air Titus Return Grille with 35 Degree Deflection 8 x 6 8 x 6 Steel - Titus - 26 WhiteE-1 Return Air Titus Perforated Square Ceiling Diffuser 12 x 12 6 x 6 Steel - Titus - 26 WhiteE-2 Exhaust Air Titus Perforated Square Ceiling Diffuser 12 x 12 6 x 6 Steel - Titus - 26 WhiteE-3 Exhaust Air Titus Perforated Square Ceiling Diffuser 24 x 24 6 x 6 Steel - Titus - 26 WhiteE-4 Exhaust Air Titus Perforated Square Ceiling Diffuser 24 x 24 8 x 8 Steel - Titus - 26 WhiteE-5 Exhaust Air Titus Perforated Square Ceiling Diffuser 24 x 24 10 x 10 Steel - Titus - 26 WhiteE-6 Exhaust Air Titus Perforated Square Ceiling Diffuser 24 x 24 12 x 12 Steel - Titus - 26 WhiteNOTE:
1. IF DIFFUSER /GRILLE IS LOCATED IN A HARD LID CEILING, PROVIDE DAMPER INCORPORATED INTO DIFFUSER/GRILLE.2. ALL GRILLES & DIFFUSERS SHALL BE WHITE, UNLESS NOTED OTHERWISE.
UNIT HEATERSMARK MANUFACTURER MODEL FLOW (GPM) REMARKS
UH-1 TRANE UHSB-084 6.1 GPM 26.2 MBH heating capacity @ 120F EWT, 20F WTD, 1/12 HP, 120/1/60, factory installed disconnect switch and louver fin diffuser, line voltage thermostat provided with the unit and installed/ wired by electrical contractor per plans.UH-2 TRANE UHSB-036 2.7 GPM 11.2 MBH heating capacity @ 120F EWT, 20F WTD, 25 WATTS, 120/1/60, factory installed disconnect switch and louver fin diffuser, line voltage thermostat provided with the unit and installed/ wired by electrical contractor per plans.UH-3 TRANE UHSB-036 2.7 GPM 11.2 MBH heating capacity @ 120F EWT, 20F WTD, 25 WATTS, 120/1/60, factory installed disconnect switch and louver fin diffuser, line voltage thermostat provided with the unit and installed/ wired by electrical contractor per plans.UH-4 TRANE GHND-007 75 MBH maximum input, 60 MBH output, 1/30 HP, shaded pole motor type, 120/1/60, powered vented for horizontal venting with termination kit, with low voltage thermostat furnished by mechanical contractor, installed and wired by electrical contractor per plans.
UP
UP
S
S
S
D DD D
H
H
H
33 34
SB SB
ATS
3
1.5 5 5
15
1/2
1/2
1/2
3/4
1.5
1.5
01
01
01
01
02
03 03 03 03
04
04
04
05
05
05
13
08
0909
0918
12
14
1516
17
VESTIBULE001
LOBBY002
MECHANICAL003
19
COMPRESSSOR
COMPRESSOR PUMP PUMP
AHU
EX FAN
EX FAN
EX FAN
AHU
PUMPEX FAN
01EXISTING ROUND 100W H.I.D. BOLLARD 9" IN DIAMETER AND 42" IN HEIGHT. E.C. SHALL RETROFIT EXISTINGMERCURY VAPOR LAMP AND BALLAST WITH NEW 70W PULSE START METAL HALIDE LAMP AND BALLAST.
ELECTRICAL DEMOLITION KEYED NOTES: (ALL NOTES MAY NOT BE USED ON THIS SHEET)
GENERAL ELECTRICAL DEMOLITION NOTES:
GRAND RAPIDS COMMUNITY COLLEGE RESERVES THE RIGHT OF FIRST REFUSAL IN OWNERSHIPOF ANY EQUIPMENT ITEMS AND MATERIAL TO BE REMOVED FROM THE BUILDING ANDSITE.
DEMOLITION OF AN ITEM SHALL INCLUDE REMOVAL OF ALL RELATED CONTROLDEVICES, WIRING, CONDUIT, SUPPORTS, ACCESSORIES IN THEIR ENTIRETY.
ALL ELECTRICAL EQUIPMENT SHOWN IN DASHED / BOLD PRINT SHALL BE REMOVEDIN ITS ENTIRETY UNLESS OTHERWISE NOTED. PROTECT EXISTING WORK WHICHIS TO REMAIN IN PLACE FOR RE-USE WITH TEMPORARY COVERS, SHORING, BRACING,AND SUPPORTS. VERIFY LOCATIONS OF AND PROTECT EXISTING INTERIORELECTRICAL AND MECHANICAL UTILITIES AND SERVICES; EXCEPT WHERE INDICATEDOTHERWISE. ALL MATERIALS AND EQUIPMENT REMOVED, AND NOT RE-USEDSHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVEDFROM THE OWNERS PROPERTY. THE OWNER RESERVES THE RIGHT TO SALVAGEPARTS FROM ALL THE MECHANICAL AND ELECTRICAL EQUIPMENT BEFORE REMOVALFROM THE SITE. ALL MATERIALS & EQUIPMENT REQUIRING REMOVAL ANDRE-LOCATION FOR RE-USE SHALL BE CAREFULLY REMOVED AND STORED TOPREVENT DAMAGE AND RE-INSTALLED AS THE WORK PROGRESSES.
IF ASBESTOS MATERIAL IS ENCOUNTERED IT WILL BE REMOVED BY THE OWNER.
CONTRACTOR SHALL PROTECT ALL WALLS, CEILINGS, FLOORS, LIGHTS, AND OTHERFINISHED SURFACES THAT ARE NOT TO BE REMOVED. IF DAMAGED, CONTRACTORSHALL REPAIR TO MATCH EXISTING CONDITIONS AT NO ADDITIONAL COST TOTHE OWNER.
ITEMS SHOWN IN FADED PRINT ARE EXISTING DEVICES INTENDED TO REMAIN.CONTRACTOR SHALL MAKE ANY NECESSARY PROVISIONS TO RE-FEED DEVICESDE-ENERGIZED DUE TO CONSTRUCTION.
1.
2.
3.
4.
5.
6.
02DISCONNECT AND REMOVE (3) EXISTING ROUND BOLLARDS, 14.5" IN DIAMETER, (1) 82" IN HEIGHT, (1) 70" INHEIGHT AND (1) 58" IN HEIGHT.
03DEMOLISH EXISTING BOLLARD CONCRETE BASE AND ASSOCIATED CONDUIT AND WIRING IN IT'S ENTIRETY.
04DEMOLISH EXISTING IN-GRADE FLAGPOLE LIGHT. RE-USE EXISTING CONDUIT TO FEED NEW FLAG-POLELIGHTS. REPLACE WIRING IN IT'S ENTIRETY. REFER TO NEW LIGHTING PLANS.
05DISCONNECT EXISTING FIXTURE. SAVE AND STORE FOR RE-USE.
06RETROFIT EXISTING FIXTURE WITH NEW T8 LAMP, BALLAST, AND SOCKETS. FURNISH LONG LIFE, MIN. CRI 85LAMPS AND AN ELECTRONIC PROGRAMMED RAPID START BALLAST PER SPEC'S.
07EXISTING UTILITY TRANSFORMER AND SWITCH TO BE DISCONNECTED AND REPLACED WITH NEW. E.C. SHALLCOORDINATE WITH UTILITY COMPANY.
08DISCONNECT AND REMOVE EXISTING CHILLER FEED AND ASSOCIATED CONDUIT AND DISCONNECT TO ALLOWFOR REMOVAL.
09DISCONNECT AND REMOVE EXISTING MOTOR STARTER / DISCONNECT AND ASSOCIATED CONDUIT FOR MECH.EQUIPMENT SLATED FOR DEMOLITION.
10EXISTING MAIN FIRE ALARM PANEL. DISCONNECT AND UPGRADE SYSTEM PER SPECIFICATIONS.
11DISCONNECT AND DEMOLISH EXISTING FIRE ALARM CONTROL PANEL IN IT'S ENTIRERY. REPLACE WITH NEWCONTROL PANEL PER SPECIFICATIONS.
12DEMOLISH EXISTING IN / OUT / CLEARANCE SIGNAGE AND ASSOCIATED CONDUIT, WIRING, AND LIGHTFIXTURES.
13DISCONNECT AND REMOVE EXISTING DIESEL GENERATOR AND ASSOCIATED AUTOMATIC TRANSFER SWITCH
14DEMOLISH EXISTING KEYLESS LAMPHOLDER IN THIS SPACE AND REPLACE WITH NEW LIGHT FIXTURE PERLIGHTING PLAN.
15EXISTING FIRE ALARM DEVICE - REPLACE WITH NEW DEVICE TO BE COMPATIBLE WITH NEW FIRE ALARMSYSTEM.
16EXISTING ELEVATOR SMOKE DETECTOR TO REMAIN.
17DISCONNECT AND REMOVE EXISTING METER (CUSTOMER OWNER) - REFER TO ONE-LINE DIAGRAM.
18EXISTING SECURITY / FIRE ALARM MONITORING PANEL AND ELEVATOR SMOKE DETECTOR POWER SUPPLIES.UPGRADE AS REQUIRED FOR NEW FIRE ALARM SYSTEM.
19INTERCEPT EXISTING SERVICE ENTRANCE CONDUITS AND RE-ROUTE TO NEW UTILITY TRANSFORMER.CONTRACTOR SHALL INSTALL ALL NEW CONDUCTORS AND COORDINATE SWITCHOVER WITH UTILITY COMPANYAND CONSTRUCUTION MANAGER.
20REMOVE EXTG INCANDESCENT A-LAMP FROM KEYLESS LAMPHOLDER AND REPLACE WITH NEW 13WSELF-BALLASTED CFL LAMP. MOVE LAMPHOLDER AS REQUIRED TO ALLOW FOR NEW DUCTWORKINSTALLATION.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E0.0
5-2420
PHASE 2 - RAMP ELECTRICALDEMOLITION PLAN
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NORTH
1/8" = 1'-0"ELECTRICAL DEMOLITION - RAMP LEVEL
DN
UP
UP
UP
DN
F
F
F
AV
AV
V
VV
V
V
V
V
VV
V
AV
F
V
H H
3
S
S
S
DN
DNUPDN
UP
F
F
AV
AV
AV
VV
AV
H H
S
SSM M
MM
12
05
10
07
07
08
06
14
20
15
15
16
15
15
15
VESTP101
MECHP102
LOBBYP103
CONFP104
WORK ROOMP105
RECEPTP106
VAULTP107
CORRP108
OFFICEP109
MECHP110
OFFICEP111
T.P112
CORRP113
JANP114
OFFICEP115
OFFICEP116
OFFICEP117
STAIRS-3
06
20
1406
15
15
15
15
14
14
OFFICEM101
CORRM102
MECHM103
JANM104
LOBBYM105
OFFICEM106 OFFICE
M107
OPEN OFFICEM108
STORM109
OFFICEM110
OFFICEM111
OFFICEM112
WORK ROOMM113
ELECM114
MENSM115
LOUNGEM118
WOMENSM117
MECHM116
01EXISTING ROUND 100W H.I.D. BOLLARD 9" IN DIAMETER AND 42" IN HEIGHT. E.C. SHALL RETROFIT EXISTINGMERCURY VAPOR LAMP AND BALLAST WITH NEW 70W PULSE START METAL HALIDE LAMP AND BALLAST.
ELECTRICAL DEMOLITION KEYED NOTES: (ALL NOTES MAY NOT BE USED ON THIS SHEET)
GENERAL ELECTRICAL DEMOLITION NOTES:
GRAND RAPIDS COMMUNITY COLLEGE RESERVES THE RIGHT OF FIRST REFUSAL IN OWNERSHIPOF ANY EQUIPMENT ITEMS AND MATERIAL TO BE REMOVED FROM THE BUILDING ANDSITE.
DEMOLITION OF AN ITEM SHALL INCLUDE REMOVAL OF ALL RELATED CONTROLDEVICES, WIRING, CONDUIT, SUPPORTS, ACCESSORIES IN THEIR ENTIRETY.
ALL ELECTRICAL EQUIPMENT SHOWN IN DASHED / BOLD PRINT SHALL BE REMOVEDIN ITS ENTIRETY UNLESS OTHERWISE NOTED. PROTECT EXISTING WORK WHICHIS TO REMAIN IN PLACE FOR RE-USE WITH TEMPORARY COVERS, SHORING, BRACING,AND SUPPORTS. VERIFY LOCATIONS OF AND PROTECT EXISTING INTERIORELECTRICAL AND MECHANICAL UTILITIES AND SERVICES; EXCEPT WHERE INDICATEDOTHERWISE. ALL MATERIALS AND EQUIPMENT REMOVED, AND NOT RE-USEDSHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVEDFROM THE OWNERS PROPERTY. THE OWNER RESERVES THE RIGHT TO SALVAGEPARTS FROM ALL THE MECHANICAL AND ELECTRICAL EQUIPMENT BEFORE REMOVALFROM THE SITE. ALL MATERIALS & EQUIPMENT REQUIRING REMOVAL ANDRE-LOCATION FOR RE-USE SHALL BE CAREFULLY REMOVED AND STORED TOPREVENT DAMAGE AND RE-INSTALLED AS THE WORK PROGRESSES.
IF ASBESTOS MATERIAL IS ENCOUNTERED IT WILL BE REMOVED BY THE OWNER.
CONTRACTOR SHALL PROTECT ALL WALLS, CEILINGS, FLOORS, LIGHTS, AND OTHERFINISHED SURFACES THAT ARE NOT TO BE REMOVED. IF DAMAGED, CONTRACTORSHALL REPAIR TO MATCH EXISTING CONDITIONS AT NO ADDITIONAL COST TOTHE OWNER.
ITEMS SHOWN IN FADED PRINT ARE EXISTING DEVICES INTENDED TO REMAIN.CONTRACTOR SHALL MAKE ANY NECESSARY PROVISIONS TO RE-FEED DEVICESDE-ENERGIZED DUE TO CONSTRUCTION.
1.
2.
3.
4.
5.
6.
02DISCONNECT AND REMOVE (3) EXISTING ROUND BOLLARDS, 14.5" IN DIAMETER, (1) 82" IN HEIGHT, (1) 70" INHEIGHT AND (1) 58" IN HEIGHT.
03DEMOLISH EXISTING BOLLARD CONCRETE BASE AND ASSOCIATED CONDUIT AND WIRING IN IT'S ENTIRETY.
04DEMOLISH EXISTING IN-GRADE FLAGPOLE LIGHT. RE-USE EXISTING CONDUIT TO FEED NEW FLAG-POLELIGHTS. REPLACE WIRING IN IT'S ENTIRETY. REFER TO NEW LIGHTING PLANS.
05DISCONNECT EXISTING FIXTURE. SAVE AND STORE FOR RE-USE.
06RETROFIT EXISTING FIXTURE WITH NEW T8 LAMP, BALLAST, AND SOCKETS. FURNISH LONG LIFE, MIN. CRI 85LAMPS AND AN ELECTRONIC PROGRAMMED RAPID START BALLAST PER SPEC'S.
07EXISTING UTILITY TRANSFORMER AND SWITCH TO BE DISCONNECTED AND REPLACED WITH NEW. E.C. SHALLCOORDINATE WITH UTILITY COMPANY.
08DISCONNECT AND REMOVE EXISTING CHILLER FEED AND ASSOCIATED CONDUIT AND DISCONNECT TO ALLOWFOR REMOVAL.
09DISCONNECT AND REMOVE EXISTING MOTOR STARTER / DISCONNECT AND ASSOCIATED CONDUIT FOR MECH.EQUIPMENT SLATED FOR DEMOLITION.
10EXISTING MAIN FIRE ALARM PANEL. DISCONNECT AND UPGRADE SYSTEM PER SPECIFICATIONS.
11DISCONNECT AND DEMOLISH EXISTING FIRE ALARM CONTROL PANEL IN IT'S ENTIRERY. REPLACE WITH NEWCONTROL PANEL PER SPECIFICATIONS.
12DEMOLISH EXISTING IN / OUT / CLEARANCE SIGNAGE AND ASSOCIATED CONDUIT, WIRING, AND LIGHTFIXTURES.
13DISCONNECT AND REMOVE EXISTING DIESEL GENERATOR AND ASSOCIATED AUTOMATIC TRANSFER SWITCH
14DEMOLISH EXISTING KEYLESS LAMPHOLDER IN THIS SPACE AND REPLACE WITH NEW LIGHT FIXTURE PERLIGHTING PLAN.
15EXISTING FIRE ALARM DEVICE - REPLACE WITH NEW DEVICE TO BE COMPATIBLE WITH NEW FIRE ALARMSYSTEM.
16EXISTING ELEVATOR SMOKE DETECTOR TO REMAIN.
17DISCONNECT AND REMOVE EXISTING METER (CUSTOMER OWNER) - REFER TO ONE-LINE DIAGRAM.
18EXISTING SECURITY / FIRE ALARM MONITORING PANEL AND ELEVATOR SMOKE DETECTOR POWER SUPPLIES.UPGRADE AS REQUIRED FOR NEW FIRE ALARM SYSTEM.
19INTERCEPT EXISTING SERVICE ENTRANCE CONDUITS AND RE-ROUTE TO NEW UTILITY TRANSFORMER.CONTRACTOR SHALL INSTALL ALL NEW CONDUCTORS AND COORDINATE SWITCHOVER WITH UTILITY COMPANYAND CONSTRUCUTION MANAGER.
20REMOVE EXTG INCANDESCENT A-LAMP FROM KEYLESS LAMPHOLDER AND REPLACE WITH NEW 13WSELF-BALLASTED CFL LAMP. MOVE LAMPHOLDER AS REQUIRED TO ALLOW FOR NEW DUCTWORKINSTALLATION.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E0.1
5-2420
PHASE 2 - PLAZA & MEZZANINEELECTRICAL DEMOLITION
PLAN
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
10.22.12 OWNER REVIEW
NORTH
1/8" = 1'-0"ELECTRICAL DEMOLITION - PLAZA LEVEL
NORTH
1/8" = 1'-0"ELECTRICAL DEMOLITION - MEZZANINE LEVEL
DNUPDN
UP
F
F
F
F
AV
AV
AV
AV
AV
AV
V
S
S
S
V
M
M
H
3
3
3
3
3
3
3
4
3 3
3
3
H
DNUPDNUP
V
V
F F
AV
AV
AV
AVAV
S
S
S
H
AV
3
33
3
3
14 14
14
15
15
15
15
15
16
CORR.201
MENS202
OFFICE203
OFFICE204
OFFICE205
OFFICE206
OFFICE207
OFFICE208
CORR209
MECH210
OFFICE211
OFFICE212
LOBBY213
ENTRY214
WORK RM215
CONF216
OFFICE217
LIBRARY218
MECH219
WOMENS220
ELEC221
JAN222
CORR223
CONF224
CORR225
OFFICE226
OFFICE227
OFFICE228
OFFICE229
OFFICE230
OFFICE231
CORR200
16
14 14
14
15
15
15
15
15 01EXISTING ROUND 100W H.I.D. BOLLARD 9" IN DIAMETER AND 42" IN HEIGHT. E.C. SHALL RETROFIT EXISTINGMERCURY VAPOR LAMP AND BALLAST WITH NEW 70W PULSE START METAL HALIDE LAMP AND BALLAST.
ELECTRICAL DEMOLITION KEYED NOTES: (ALL NOTES MAY NOT BE USED ON THIS SHEET)
GENERAL ELECTRICAL DEMOLITION NOTES:
GRAND RAPIDS COMMUNITY COLLEGE RESERVES THE RIGHT OF FIRST REFUSAL IN OWNERSHIPOF ANY EQUIPMENT ITEMS AND MATERIAL TO BE REMOVED FROM THE BUILDING ANDSITE.
DEMOLITION OF AN ITEM SHALL INCLUDE REMOVAL OF ALL RELATED CONTROLDEVICES, WIRING, CONDUIT, SUPPORTS, ACCESSORIES IN THEIR ENTIRETY.
ALL ELECTRICAL EQUIPMENT SHOWN IN DASHED / BOLD PRINT SHALL BE REMOVEDIN ITS ENTIRETY UNLESS OTHERWISE NOTED. PROTECT EXISTING WORK WHICHIS TO REMAIN IN PLACE FOR RE-USE WITH TEMPORARY COVERS, SHORING, BRACING,AND SUPPORTS. VERIFY LOCATIONS OF AND PROTECT EXISTING INTERIORELECTRICAL AND MECHANICAL UTILITIES AND SERVICES; EXCEPT WHERE INDICATEDOTHERWISE. ALL MATERIALS AND EQUIPMENT REMOVED, AND NOT RE-USEDSHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVEDFROM THE OWNERS PROPERTY. THE OWNER RESERVES THE RIGHT TO SALVAGEPARTS FROM ALL THE MECHANICAL AND ELECTRICAL EQUIPMENT BEFORE REMOVALFROM THE SITE. ALL MATERIALS & EQUIPMENT REQUIRING REMOVAL ANDRE-LOCATION FOR RE-USE SHALL BE CAREFULLY REMOVED AND STORED TOPREVENT DAMAGE AND RE-INSTALLED AS THE WORK PROGRESSES.
IF ASBESTOS MATERIAL IS ENCOUNTERED IT WILL BE REMOVED BY THE OWNER.
CONTRACTOR SHALL PROTECT ALL WALLS, CEILINGS, FLOORS, LIGHTS, AND OTHERFINISHED SURFACES THAT ARE NOT TO BE REMOVED. IF DAMAGED, CONTRACTORSHALL REPAIR TO MATCH EXISTING CONDITIONS AT NO ADDITIONAL COST TOTHE OWNER.
ITEMS SHOWN IN FADED PRINT ARE EXISTING DEVICES INTENDED TO REMAIN.CONTRACTOR SHALL MAKE ANY NECESSARY PROVISIONS TO RE-FEED DEVICESDE-ENERGIZED DUE TO CONSTRUCTION.
1.
2.
3.
4.
5.
6.
02DISCONNECT AND REMOVE (3) EXISTING ROUND BOLLARDS, 14.5" IN DIAMETER, (1) 82" IN HEIGHT, (1) 70" INHEIGHT AND (1) 58" IN HEIGHT.
03DEMOLISH EXISTING BOLLARD CONCRETE BASE AND ASSOCIATED CONDUIT AND WIRING IN IT'S ENTIRETY.
04DEMOLISH EXISTING IN-GRADE FLAGPOLE LIGHT. RE-USE EXISTING CONDUIT TO FEED NEW FLAG-POLELIGHTS. REPLACE WIRING IN IT'S ENTIRETY. REFER TO NEW LIGHTING PLANS.
05DISCONNECT EXISTING FIXTURE. SAVE AND STORE FOR RE-USE.
06RETROFIT EXISTING FIXTURE WITH NEW T8 LAMP, BALLAST, AND SOCKETS. FURNISH LONG LIFE, MIN. CRI 85LAMPS AND AN ELECTRONIC PROGRAMMED RAPID START BALLAST PER SPEC'S.
07EXISTING UTILITY TRANSFORMER AND SWITCH TO BE DISCONNECTED AND REPLACED WITH NEW. E.C. SHALLCOORDINATE WITH UTILITY COMPANY.
08DISCONNECT AND REMOVE EXISTING CHILLER FEED AND ASSOCIATED CONDUIT AND DISCONNECT TO ALLOWFOR REMOVAL.
09DISCONNECT AND REMOVE EXISTING MOTOR STARTER / DISCONNECT AND ASSOCIATED CONDUIT FOR MECH.EQUIPMENT SLATED FOR DEMOLITION.
10EXISTING MAIN FIRE ALARM PANEL. DISCONNECT AND UPGRADE SYSTEM PER SPECIFICATIONS.
11DISCONNECT AND DEMOLISH EXISTING FIRE ALARM CONTROL PANEL IN IT'S ENTIRERY. REPLACE WITH NEWCONTROL PANEL PER SPECIFICATIONS.
12DEMOLISH EXISTING IN / OUT / CLEARANCE SIGNAGE AND ASSOCIATED CONDUIT, WIRING, AND LIGHTFIXTURES.
13DISCONNECT AND REMOVE EXISTING DIESEL GENERATOR AND ASSOCIATED AUTOMATIC TRANSFER SWITCH
14DEMOLISH EXISTING KEYLESS LAMPHOLDER IN THIS SPACE AND REPLACE WITH NEW LIGHT FIXTURE PERLIGHTING PLAN.
15EXISTING FIRE ALARM DEVICE - REPLACE WITH NEW DEVICE TO BE COMPATIBLE WITH NEW FIRE ALARMSYSTEM.
16EXISTING ELEVATOR SMOKE DETECTOR TO REMAIN.
17DISCONNECT AND REMOVE EXISTING METER (CUSTOMER OWNER) - REFER TO ONE-LINE DIAGRAM.
18EXISTING SECURITY / FIRE ALARM MONITORING PANEL AND ELEVATOR SMOKE DETECTOR POWER SUPPLIES.UPGRADE AS REQUIRED FOR NEW FIRE ALARM SYSTEM.
19INTERCEPT EXISTING SERVICE ENTRANCE CONDUITS AND RE-ROUTE TO NEW UTILITY TRANSFORMER.CONTRACTOR SHALL INSTALL ALL NEW CONDUCTORS AND COORDINATE SWITCHOVER WITH UTILITY COMPANYAND CONSTRUCUTION MANAGER.
20REMOVE EXTG INCANDESCENT A-LAMP FROM KEYLESS LAMPHOLDER AND REPLACE WITH NEW 13WSELF-BALLASTED CFL LAMP. MOVE LAMPHOLDER AS REQUIRED TO ALLOW FOR NEW DUCTWORKINSTALLATION.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E0.2
5-2420
PHASE 2 - SECOND & THIRDFLOOR ELECTRICALDEMOLITION PLAN
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
10.22.12 OWNER REVIEW
NORTH
1/8" = 1'-0"ELECTRICAL DEMOLITION - 2ND FLOORNORTH
1/8" = 1'-0"ELECTRICAL DEMOLITION - 3RD FLOOR
DNUP
DNUP
V
V
AVAV
AV
AV
AV
F
F
HH
S
S
S
AV
3
3 3
33
3
3 3
3
DNUPDN UP
AV
AV
AV
V
F F
AV
V
S
S
S3
3
3
3
15
15
15
14
14
16
14 14
14
15
15
15
16
E.C. TO REMOVE (3) EXISTING CUSTOMER METERSAND VERIFY WHAT THE 12 SPACE LOAD CENTER FEEDS
01EXISTING ROUND 100W H.I.D. BOLLARD 9" IN DIAMETER AND 42" IN HEIGHT. E.C. SHALL RETROFIT EXISTINGMERCURY VAPOR LAMP AND BALLAST WITH NEW 70W PULSE START METAL HALIDE LAMP AND BALLAST.
ELECTRICAL DEMOLITION KEYED NOTES: (ALL NOTES MAY NOT BE USED ON THIS SHEET)
GENERAL ELECTRICAL DEMOLITION NOTES:
GRAND RAPIDS COMMUNITY COLLEGE RESERVES THE RIGHT OF FIRST REFUSAL IN OWNERSHIPOF ANY EQUIPMENT ITEMS AND MATERIAL TO BE REMOVED FROM THE BUILDING ANDSITE.
DEMOLITION OF AN ITEM SHALL INCLUDE REMOVAL OF ALL RELATED CONTROLDEVICES, WIRING, CONDUIT, SUPPORTS, ACCESSORIES IN THEIR ENTIRETY.
ALL ELECTRICAL EQUIPMENT SHOWN IN DASHED / BOLD PRINT SHALL BE REMOVEDIN ITS ENTIRETY UNLESS OTHERWISE NOTED. PROTECT EXISTING WORK WHICHIS TO REMAIN IN PLACE FOR RE-USE WITH TEMPORARY COVERS, SHORING, BRACING,AND SUPPORTS. VERIFY LOCATIONS OF AND PROTECT EXISTING INTERIORELECTRICAL AND MECHANICAL UTILITIES AND SERVICES; EXCEPT WHERE INDICATEDOTHERWISE. ALL MATERIALS AND EQUIPMENT REMOVED, AND NOT RE-USEDSHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVEDFROM THE OWNERS PROPERTY. THE OWNER RESERVES THE RIGHT TO SALVAGEPARTS FROM ALL THE MECHANICAL AND ELECTRICAL EQUIPMENT BEFORE REMOVALFROM THE SITE. ALL MATERIALS & EQUIPMENT REQUIRING REMOVAL ANDRE-LOCATION FOR RE-USE SHALL BE CAREFULLY REMOVED AND STORED TOPREVENT DAMAGE AND RE-INSTALLED AS THE WORK PROGRESSES.
IF ASBESTOS MATERIAL IS ENCOUNTERED IT WILL BE REMOVED BY THE OWNER.
CONTRACTOR SHALL PROTECT ALL WALLS, CEILINGS, FLOORS, LIGHTS, AND OTHERFINISHED SURFACES THAT ARE NOT TO BE REMOVED. IF DAMAGED, CONTRACTORSHALL REPAIR TO MATCH EXISTING CONDITIONS AT NO ADDITIONAL COST TOTHE OWNER.
ITEMS SHOWN IN FADED PRINT ARE EXISTING DEVICES INTENDED TO REMAIN.CONTRACTOR SHALL MAKE ANY NECESSARY PROVISIONS TO RE-FEED DEVICESDE-ENERGIZED DUE TO CONSTRUCTION.
1.
2.
3.
4.
5.
6.
02DISCONNECT AND REMOVE (3) EXISTING ROUND BOLLARDS, 14.5" IN DIAMETER, (1) 82" IN HEIGHT, (1) 70" INHEIGHT AND (1) 58" IN HEIGHT.
03DEMOLISH EXISTING BOLLARD CONCRETE BASE AND ASSOCIATED CONDUIT AND WIRING IN IT'S ENTIRETY.
04DEMOLISH EXISTING IN-GRADE FLAGPOLE LIGHT. RE-USE EXISTING CONDUIT TO FEED NEW FLAG-POLELIGHTS. REPLACE WIRING IN IT'S ENTIRETY. REFER TO NEW LIGHTING PLANS.
05DISCONNECT EXISTING FIXTURE. SAVE AND STORE FOR RE-USE.
06RETROFIT EXISTING FIXTURE WITH NEW T8 LAMP, BALLAST, AND SOCKETS. FURNISH LONG LIFE, MIN. CRI 85LAMPS AND AN ELECTRONIC PROGRAMMED RAPID START BALLAST PER SPEC'S.
07EXISTING UTILITY TRANSFORMER AND SWITCH TO BE DISCONNECTED AND REPLACED WITH NEW. E.C. SHALLCOORDINATE WITH UTILITY COMPANY.
08DISCONNECT AND REMOVE EXISTING CHILLER FEED AND ASSOCIATED CONDUIT AND DISCONNECT TO ALLOWFOR REMOVAL.
09DISCONNECT AND REMOVE EXISTING MOTOR STARTER / DISCONNECT AND ASSOCIATED CONDUIT FOR MECH.EQUIPMENT SLATED FOR DEMOLITION.
10EXISTING MAIN FIRE ALARM PANEL. DISCONNECT AND UPGRADE SYSTEM PER SPECIFICATIONS.
11DISCONNECT AND DEMOLISH EXISTING FIRE ALARM CONTROL PANEL IN IT'S ENTIRERY. REPLACE WITH NEWCONTROL PANEL PER SPECIFICATIONS.
12DEMOLISH EXISTING IN / OUT / CLEARANCE SIGNAGE AND ASSOCIATED CONDUIT, WIRING, AND LIGHTFIXTURES.
13DISCONNECT AND REMOVE EXISTING DIESEL GENERATOR AND ASSOCIATED AUTOMATIC TRANSFER SWITCH
14DEMOLISH EXISTING KEYLESS LAMPHOLDER IN THIS SPACE AND REPLACE WITH NEW LIGHT FIXTURE PERLIGHTING PLAN.
15EXISTING FIRE ALARM DEVICE - REPLACE WITH NEW DEVICE TO BE COMPATIBLE WITH NEW FIRE ALARMSYSTEM.
16EXISTING ELEVATOR SMOKE DETECTOR TO REMAIN.
17DISCONNECT AND REMOVE EXISTING METER (CUSTOMER OWNER) - REFER TO ONE-LINE DIAGRAM.
18EXISTING SECURITY / FIRE ALARM MONITORING PANEL AND ELEVATOR SMOKE DETECTOR POWER SUPPLIES.UPGRADE AS REQUIRED FOR NEW FIRE ALARM SYSTEM.
19INTERCEPT EXISTING SERVICE ENTRANCE CONDUITS AND RE-ROUTE TO NEW UTILITY TRANSFORMER.CONTRACTOR SHALL INSTALL ALL NEW CONDUCTORS AND COORDINATE SWITCHOVER WITH UTILITY COMPANYAND CONSTRUCUTION MANAGER.
20REMOVE EXTG INCANDESCENT A-LAMP FROM KEYLESS LAMPHOLDER AND REPLACE WITH NEW 13WSELF-BALLASTED CFL LAMP. MOVE LAMPHOLDER AS REQUIRED TO ALLOW FOR NEW DUCTWORKINSTALLATION.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E0.3
5-2420
PHASE 2 - FOURTH & FIFTHFLOOR ELECTRICALDEMOLITION PLAN
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
10.22.12 OWNER REVIEW
NORTH
1/8" = 1'-0"ELECTRICAL DEMOLITION - 4TH FLOORNORTH
1/8" = 1'-0"ELECTRICAL DEMOLITION - 5TH FLOOR
DNUPDNUP
F
F
AV
AV
V
AV
V
AV
V
V
V
S
S
S
VV
V V V V V
V
V
V
V
V
V
VV
V V V V V
V
3
3
DNDN
FF
AV
AV
AV F
D
D
D
D
H
H
H
H
15
10
1.5
1.5
1/2
1/2
1/21/3
1/4
16
14 14
14
14
14 15 15
1515
15
15
1515
1515
15
15
15
15
15
15
05
05
05
0505
0505
05
05
PB-7L
15
EX FAN
HUMIDIFIER
AHU-1
AHU-2
BOILER
CIRC PUMPS
BOILER
EX FAN
EX FAN
EX FAN
CIRC PUMP
01EXISTING ROUND 100W H.I.D. BOLLARD 9" IN DIAMETER AND 42" IN HEIGHT. E.C. SHALL RETROFIT EXISTINGMERCURY VAPOR LAMP AND BALLAST WITH NEW 70W PULSE START METAL HALIDE LAMP AND BALLAST.
ELECTRICAL DEMOLITION KEYED NOTES: (ALL NOTES MAY NOT BE USED ON THIS SHEET)
GENERAL ELECTRICAL DEMOLITION NOTES:
GRAND RAPIDS COMMUNITY COLLEGE RESERVES THE RIGHT OF FIRST REFUSAL IN OWNERSHIPOF ANY EQUIPMENT ITEMS AND MATERIAL TO BE REMOVED FROM THE BUILDING ANDSITE.
DEMOLITION OF AN ITEM SHALL INCLUDE REMOVAL OF ALL RELATED CONTROLDEVICES, WIRING, CONDUIT, SUPPORTS, ACCESSORIES IN THEIR ENTIRETY.
ALL ELECTRICAL EQUIPMENT SHOWN IN DASHED / BOLD PRINT SHALL BE REMOVEDIN ITS ENTIRETY UNLESS OTHERWISE NOTED. PROTECT EXISTING WORK WHICHIS TO REMAIN IN PLACE FOR RE-USE WITH TEMPORARY COVERS, SHORING, BRACING,AND SUPPORTS. VERIFY LOCATIONS OF AND PROTECT EXISTING INTERIORELECTRICAL AND MECHANICAL UTILITIES AND SERVICES; EXCEPT WHERE INDICATEDOTHERWISE. ALL MATERIALS AND EQUIPMENT REMOVED, AND NOT RE-USEDSHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVEDFROM THE OWNERS PROPERTY. THE OWNER RESERVES THE RIGHT TO SALVAGEPARTS FROM ALL THE MECHANICAL AND ELECTRICAL EQUIPMENT BEFORE REMOVALFROM THE SITE. ALL MATERIALS & EQUIPMENT REQUIRING REMOVAL ANDRE-LOCATION FOR RE-USE SHALL BE CAREFULLY REMOVED AND STORED TOPREVENT DAMAGE AND RE-INSTALLED AS THE WORK PROGRESSES.
IF ASBESTOS MATERIAL IS ENCOUNTERED IT WILL BE REMOVED BY THE OWNER.
CONTRACTOR SHALL PROTECT ALL WALLS, CEILINGS, FLOORS, LIGHTS, AND OTHERFINISHED SURFACES THAT ARE NOT TO BE REMOVED. IF DAMAGED, CONTRACTORSHALL REPAIR TO MATCH EXISTING CONDITIONS AT NO ADDITIONAL COST TOTHE OWNER.
ITEMS SHOWN IN FADED PRINT ARE EXISTING DEVICES INTENDED TO REMAIN.CONTRACTOR SHALL MAKE ANY NECESSARY PROVISIONS TO RE-FEED DEVICESDE-ENERGIZED DUE TO CONSTRUCTION.
1.
2.
3.
4.
5.
6.
02DISCONNECT AND REMOVE (3) EXISTING ROUND BOLLARDS, 14.5" IN DIAMETER, (1) 82" IN HEIGHT, (1) 70" INHEIGHT AND (1) 58" IN HEIGHT.
03DEMOLISH EXISTING BOLLARD CONCRETE BASE AND ASSOCIATED CONDUIT AND WIRING IN IT'S ENTIRETY.
04DEMOLISH EXISTING IN-GRADE FLAGPOLE LIGHT. RE-USE EXISTING CONDUIT TO FEED NEW FLAG-POLELIGHTS. REPLACE WIRING IN IT'S ENTIRETY. REFER TO NEW LIGHTING PLANS.
05DISCONNECT EXISTING FIXTURE. SAVE AND STORE FOR RE-USE.
06RETROFIT EXISTING FIXTURE WITH NEW T8 LAMP, BALLAST, AND SOCKETS. FURNISH LONG LIFE, MIN. CRI 85LAMPS AND AN ELECTRONIC PROGRAMMED RAPID START BALLAST PER SPEC'S.
07EXISTING UTILITY TRANSFORMER AND SWITCH TO BE DISCONNECTED AND REPLACED WITH NEW. E.C. SHALLCOORDINATE WITH UTILITY COMPANY.
08DISCONNECT AND REMOVE EXISTING CHILLER FEED AND ASSOCIATED CONDUIT AND DISCONNECT TO ALLOWFOR REMOVAL.
09DISCONNECT AND REMOVE EXISTING MOTOR STARTER / DISCONNECT AND ASSOCIATED CONDUIT FOR MECH.EQUIPMENT SLATED FOR DEMOLITION.
10EXISTING MAIN FIRE ALARM PANEL. DISCONNECT AND UPGRADE SYSTEM PER SPECIFICATIONS.
11DISCONNECT AND DEMOLISH EXISTING FIRE ALARM CONTROL PANEL IN IT'S ENTIRERY. REPLACE WITH NEWCONTROL PANEL PER SPECIFICATIONS.
12DEMOLISH EXISTING IN / OUT / CLEARANCE SIGNAGE AND ASSOCIATED CONDUIT, WIRING, AND LIGHTFIXTURES.
13DISCONNECT AND REMOVE EXISTING DIESEL GENERATOR AND ASSOCIATED AUTOMATIC TRANSFER SWITCH
14DEMOLISH EXISTING KEYLESS LAMPHOLDER IN THIS SPACE AND REPLACE WITH NEW LIGHT FIXTURE PERLIGHTING PLAN.
15EXISTING FIRE ALARM DEVICE - REPLACE WITH NEW DEVICE TO BE COMPATIBLE WITH NEW FIRE ALARMSYSTEM.
16EXISTING ELEVATOR SMOKE DETECTOR TO REMAIN.
17DISCONNECT AND REMOVE EXISTING METER (CUSTOMER OWNER) - REFER TO ONE-LINE DIAGRAM.
18EXISTING SECURITY / FIRE ALARM MONITORING PANEL AND ELEVATOR SMOKE DETECTOR POWER SUPPLIES.UPGRADE AS REQUIRED FOR NEW FIRE ALARM SYSTEM.
19INTERCEPT EXISTING SERVICE ENTRANCE CONDUITS AND RE-ROUTE TO NEW UTILITY TRANSFORMER.CONTRACTOR SHALL INSTALL ALL NEW CONDUCTORS AND COORDINATE SWITCHOVER WITH UTILITY COMPANYAND CONSTRUCUTION MANAGER.
20REMOVE EXTG INCANDESCENT A-LAMP FROM KEYLESS LAMPHOLDER AND REPLACE WITH NEW 13WSELF-BALLASTED CFL LAMP. MOVE LAMPHOLDER AS REQUIRED TO ALLOW FOR NEW DUCTWORKINSTALLATION.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E0.4
5-2420
PHASE 2 - SIXTH FLOOR &PENTHOUSE ELECTRICAL
DEMOLITION PLAN
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
10.22.12 OWNER REVIEW
NORTH
1/8" = 1'-0"ELECTRICAL DEMOLITION - 6TH FLOORNORTH
1/8" = 1'-0"ELECTRICAL DEMOLITION - PENTHOUSE LEVEL
UP
UP
S
S
S
F
F
AV
AV
F
SB SB
AV
V
ATS
AV
AV
TSTS TS TSTS TS TS
FSFS
TS TS
5
5
7.5
7.5
3
3
15
15
S
D
D
S
ATS
D
D
PB-RPPB-EMPB-EMR
TR-EM
TR-PBRR
PB-RL
PB-RR
01 02
03
04
05
06
JOCKEYPUMP
CONTROLLER
FIREPUMP
CONTROLLERWITHATS
FIRE ALARMANNUNCIATOR PANEL
FP
FP
07
07
EMERGENCYGENERATORON PLAZA LEVEL
UTILITYXFMRON PLAZA LEVEL
UTILITYSWITCH ON PLAZA LEVEL
WLGFCI
PBRR-6
PBRR-4
PBRR-2
PBRR-5
08
08
09
PB-SB
ATS-SB ATS-EM
VFD
PB-SBR
TR-SB
PBSBR-1
REFER TOLIGHTING PLAN
13
13
14
14
VESTIBULE001
LOBBY002
MECHANICAL003
FIRE PUMP004
STORAGE005
UH-2
UH-3
UH-1
AHU-1
AHU-2
EF-2
EF-3
PBRR-8
AHU SERVICELIGHTS/RECEPT
MSB
EF-1
PBRP-2,4,6
P-11
VFD VFD
VFD
14
14
P-12
PBRP-3,5,7
PBRP-8,10,12 PBRP-9,11,13
PBRP-3,5,7
PBRP-14,16,18
PBRP-15,17,19
PBRR-9
PBRR-11 PBRR-7
PBRR-9
PBRR-3
01CONTRACTOR SHALL FURNISH AND INSTALL NEW SQUARE D POWERLOGIC METERING ON EXISTINGSWITCHBOARD MAINS. REFER TO SPECIFICATIONS
02CONTRACTOR SHALL FURNISH AND INSTALL SURGE PROTECTION DEVICE ON EXISTING SWITCHBOARD. REFERTO SPECIFICATIONS.
03CONTRACTOR SHALL INSTALL NEW CONDUIT RISER TO PENTHOUSE FOR NEW PANELBOARD PB-7L - REFER TOONE-LINE DIAGRAM
04CONDUITS SHALL BE INSTALLED IN A MINIMUM OF 2" CONCRETE ENCASEMENT TO AUTOMATIC TRANSFERSWITCH
05FIRE PUMP AUTOMATIC TRANSFER SWICH AND PUMP CONTROLLER BY TRADES, INSTALLED BY ELECTRICALCONTRACTOR
ELECTRICAL POWER KEYED NOTES:
06CUT AND PATCH THE EXISTING PAVEMENT AS REQUIRED TO FACILITATE THE INSTALLATION OF NEWUNDERGROUND CONDUITS FOR THE GENERATOR AND FIRE PUMP SERVICE ENTRANCE
07EXISTING ELEVATOR SYSTEM SMOKE DETECTOR TO REMAIN
08REPLACE EXTG RECEPTACLE WITH GFCI AND FURNISH METAL WET LOCATION IN-USE COVER
09NOT ALL REQUIRED CONDUIT RUNS ARE SHOWN. REFER TO MANUFACTURER'S SUBMITTALS ANDINSTALLATION INSTRUCTIONS.
10EVERY ATTEMPT SHALL BE MADE TO FISH THE EXTG WALL AND RECESS MOUNT THE OUTLET INTO THE WALL.NOTIFY PROJECT ENGINEER IN THE EVENT THAT THIS IS NOT POSSIBLE.
11CONDUIT ROUTED TO CHILLERS SHALL BE RIGID GALVANIZED UTILIZING COOPER B-LINE DURA-BLOK ROOF TOPSUPPORTS (OR SIMILAR). FINAL CONNECTION TO CHILLER SHALL BE MADE WITH LIQUID TIGHT FLEXIBLECONDUIT
12BOILER EMERGENCY E-STOP. CONTRACTOR SHALL FURNISH WITH CLEAR POLY-CARB PROTECTIVE COVERAND LABLED ACCORDINGLY. TIE INTO SHUNT-TRIP CIRCUIT BREAKER FEEDING BOILER CIRCUITS.
13REPLACE EXTG RECEPTACLE WITH NEW GFCI DEVICE AND RE-FEED FROM NEW PANEL PB-SBR (STANDBYPOWER). PIT LIGHTS AND RECEPTS SHALL BE ON THE SAME CIRCUIT.
14CONTRACTOR TO MOUNT DRIVE TO STRUCTURAL SUPPORT OR PROVIDE INDEPENDENT STRUT SUPPORT FORDRIVE. DO NOT MOUNT ON HVAC EQUIPMENT.
15CONTRACTOR TO INSTAL (1) 1 1/4" CONDUIT FROM PANEL PB-SB (RAMP LEVEL) TO THE ELEVATOR MACHINEROOMS FOR FUTURE STANDBY POWER CONNECTION TO THE ELEVATORS. INSTALL A JUNCTION BOX IN EACHROOM WITH A LABLED COVER PLATE "FUTURE ELEVATOR STANDBY POWER"
GENERAL ELECTRICAL POWER NOTES:
1. REFER TO SHEET E5.0 FOR EQUIPMENT CONNECTION SCHEDULE
2. CONTRACTOR SHALL REVIEW MECHANICAL DRAWINGS AND EQUIPMENT SCHEDULE FOR ADDITIONALINFORMATION AND COORDINATION.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E2.0
5-2420
PHASE 2 - RAMP ELECTRICALPLAN
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
10.22.12 OWNER REVIEW
NORTH
1/8" = 1'-0"POWER RAMP
DN
UP
UP
UP
DN
F
F
F
AV
AV
V
VV
V
V
V
V
VV
V
AV
F
S
V
V
AV
DD
SS
V
V
AV
S
S
S
E
F
AV
SD
S D
DN
DNUPDN
UP
F
F
AV
AV
VV
AV
AV
V
AV
V
AV
S
SS
SS
D D
AV
V
V
V
V
V
D S
S D
S D
UTILITYXFMR
EMERGENCYGENERATOR
PB-PR
UTILITYSWITCH
WLGFCI
FP
FP
FP
07
07
03
PBRR-12 PBRR-10
PBRR-1
BATT. CHARGERBLOCK HEATER
VESTP101
MECHP102
LOBBYP103
CONFP104
WORK ROOMP105RECEPT
P106
VAULTP107
CORRP108
OFFICEP109
MECHP110
OFFICEP111
T.P112
CORRP113
JANP114
OFFICEP115
OFFICEP116
OFFICEP117
1010
EXTERIOR A/V DEVICE FURNISHEDAND INSTALLED BY FIREPROTECTION CONTRACTOR
GENERATOR E-STOP SURFACE MOUNTED TO EXISTING WALL.FURNISH WITH WEATHER PROOF ENCLOSURE.
F.A.C.P. / EM VOICEALARM
GENERATORANNUNCIATOR PANEL
FIRE PUMP ANNUNCIATOR PANEL.REFER TO FIRE PROTECTION PLANS
PB-MR
FP
FPFP
07
07
03
10
10
10
OFFICEM101
CORRM102
MECHM103
JANM104
LOBBYM105
OFFICEM106 OFFICE
M107
OPEN OFFICEM108
STORM109
OFFICEM110
OFFICEM111
OFFICEM112
WORK ROOMM113
ELECM114
MENSM115
LOUNGEM118
WOMENSM117
MECHM116
HEAT TRACEPBRP-1
HEAT TRACEMECHANICALPIPING - REFER TOMECHANICALDWG'S AND SPECS.
01CONTRACTOR SHALL FURNISH AND INSTALL NEW SQUARE D POWERLOGIC METERING ON EXISTINGSWITCHBOARD MAINS. REFER TO SPECIFICATIONS
02CONTRACTOR SHALL FURNISH AND INSTALL SURGE PROTECTION DEVICE ON EXISTING SWITCHBOARD. REFERTO SPECIFICATIONS.
03CONTRACTOR SHALL INSTALL NEW CONDUIT RISER TO PENTHOUSE FOR NEW PANELBOARD PB-7L - REFER TOONE-LINE DIAGRAM
04CONDUITS SHALL BE INSTALLED IN A MINIMUM OF 2" CONCRETE ENCASEMENT TO AUTOMATIC TRANSFERSWITCH
05FIRE PUMP AUTOMATIC TRANSFER SWICH AND PUMP CONTROLLER BY TRADES, INSTALLED BY ELECTRICALCONTRACTOR
ELECTRICAL POWER KEYED NOTES:
06CUT AND PATCH THE EXISTING PAVEMENT AS REQUIRED TO FACILITATE THE INSTALLATION OF NEWUNDERGROUND CONDUITS FOR THE GENERATOR AND FIRE PUMP SERVICE ENTRANCE
07EXISTING ELEVATOR SYSTEM SMOKE DETECTOR TO REMAIN
08REPLACE EXTG RECEPTACLE WITH GFCI AND FURNISH METAL WET LOCATION IN-USE COVER
09NOT ALL REQUIRED CONDUIT RUNS ARE SHOWN. REFER TO MANUFACTURER'S SUBMITTALS ANDINSTALLATION INSTRUCTIONS.
10EVERY ATTEMPT SHALL BE MADE TO FISH THE EXTG WALL AND RECESS MOUNT THE OUTLET INTO THE WALL.NOTIFY PROJECT ENGINEER IN THE EVENT THAT THIS IS NOT POSSIBLE.
11CONDUIT ROUTED TO CHILLERS SHALL BE RIGID GALVANIZED UTILIZING COOPER B-LINE DURA-BLOK ROOF TOPSUPPORTS (OR SIMILAR). FINAL CONNECTION TO CHILLER SHALL BE MADE WITH LIQUID TIGHT FLEXIBLECONDUIT
12BOILER EMERGENCY E-STOP. CONTRACTOR SHALL FURNISH WITH CLEAR POLY-CARB PROTECTIVE COVERAND LABLED ACCORDINGLY. TIE INTO SHUNT-TRIP CIRCUIT BREAKER FEEDING BOILER CIRCUITS.
13REPLACE EXTG RECEPTACLE WITH NEW GFCI DEVICE AND RE-FEED FROM NEW PANEL PB-SBR (STANDBYPOWER). PIT LIGHTS AND RECEPTS SHALL BE ON THE SAME CIRCUIT.
14CONTRACTOR TO MOUNT DRIVE TO STRUCTURAL SUPPORT OR PROVIDE INDEPENDENT STRUT SUPPORT FORDRIVE. DO NOT MOUNT ON HVAC EQUIPMENT.
15CONTRACTOR TO INSTAL (1) 1 1/4" CONDUIT FROM PANEL PB-SB (RAMP LEVEL) TO THE ELEVATOR MACHINEROOMS FOR FUTURE STANDBY POWER CONNECTION TO THE ELEVATORS. INSTALL A JUNCTION BOX IN EACHROOM WITH A LABLED COVER PLATE "FUTURE ELEVATOR STANDBY POWER"
GENERAL ELECTRICAL POWER NOTES:
1. REFER TO SHEET E5.0 FOR EQUIPMENT CONNECTION SCHEDULE
2. CONTRACTOR SHALL REVIEW MECHANICAL DRAWINGS AND EQUIPMENT SCHEDULE FOR ADDITIONALINFORMATION AND COORDINATION.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E2.1
5-2420
PHASE 2 - PLAZA & MEZZANINEELECTRICAL PLAN
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
10.22.12 OWNER REVIEW
NORTH
1/8" = 1'-0"POWER PLAZA
NORTH
1/8" = 1'-0"POWER MEZZANINE
DNUPDN
UP
F
F
F
F
AV
AV
AV
AV
V
S
S
S
V
M
M
SS
V V
AV
V
VV V
V
V
V
V
V
AVAV
AV
AV AV
AV
AV
AV
AV
D
D
S
S
VV
VVVV
AV
V
AVV
AV
AV
S
S
D
D
S
D
DNUPDNUP
V
V
F F
AV
AV
S
S
S
VV
V
V
V
V
V
V
VV
V
AV
AV
AV
AV
AVS
SDD
T
AV
AV
VVV
V
V V V V V V
AV
AV
S
D
SD
PB-2RPB-2L
TR-2RA TR-2R
FPFP
FP
07
07
03
10
1010
CORR.201
MENS202
OFFICE203
OFFICE204
OFFICE205
OFFICE206
OFFICE207
OFFICE208
CORR209
MECH210 OFFICE
211
OFFICE212
LOBBY213
ENTRY214
WORK RM215
CONF216
OFFICE217
LIBRARY218
MECH219
WOMENS220
ELEC221 JAN
222
CORR223
CONF224
CORR225
OFFICE226
OFFICE227
OFFICE228
OFFICE229
OFFICE230
OFFICE231
CORR200
PB-2RA
PB-3L
TR-3R
PB-3R
FPFP
FP
07
07
03
10
10
10
OFFICE301
OFFICE302
OFFICE303
OFFICE304
OFFICE305
OFFICE306
OFFICE307
OFFICE308
CORR309
MENS310
MECH311
CONF312
STOR313
OFFICE314 MECH
315
WOMENS316
ELEC317
JAN.318
LOBBY319
CORR320
STOR321
FILES322
CORR323
STOR324
CONF325OFFICE
326OFFICE
327
CONF328 OFFICE
329OFFICE
330OFFICE
331OFFICE
332
OFFICE333
INSTALL (1) 4"METALLIC CONDUITSLEEVE WITHPLASTIC BUSHINGSBETWEEN THE 4THAND 5TH FLOORSFOR IT CABLINGCHASE.COORDINATE FINALLOCATION WITHOWNER.
01CONTRACTOR SHALL FURNISH AND INSTALL NEW SQUARE D POWERLOGIC METERING ON EXISTINGSWITCHBOARD MAINS. REFER TO SPECIFICATIONS
02CONTRACTOR SHALL FURNISH AND INSTALL SURGE PROTECTION DEVICE ON EXISTING SWITCHBOARD. REFERTO SPECIFICATIONS.
03CONTRACTOR SHALL INSTALL NEW CONDUIT RISER TO PENTHOUSE FOR NEW PANELBOARD PB-7L - REFER TOONE-LINE DIAGRAM
04CONDUITS SHALL BE INSTALLED IN A MINIMUM OF 2" CONCRETE ENCASEMENT TO AUTOMATIC TRANSFERSWITCH
05FIRE PUMP AUTOMATIC TRANSFER SWICH AND PUMP CONTROLLER BY TRADES, INSTALLED BY ELECTRICALCONTRACTOR
ELECTRICAL POWER KEYED NOTES:
06CUT AND PATCH THE EXISTING PAVEMENT AS REQUIRED TO FACILITATE THE INSTALLATION OF NEWUNDERGROUND CONDUITS FOR THE GENERATOR AND FIRE PUMP SERVICE ENTRANCE
07EXISTING ELEVATOR SYSTEM SMOKE DETECTOR TO REMAIN
08REPLACE EXTG RECEPTACLE WITH GFCI AND FURNISH METAL WET LOCATION IN-USE COVER
09NOT ALL REQUIRED CONDUIT RUNS ARE SHOWN. REFER TO MANUFACTURER'S SUBMITTALS ANDINSTALLATION INSTRUCTIONS.
10EVERY ATTEMPT SHALL BE MADE TO FISH THE EXTG WALL AND RECESS MOUNT THE OUTLET INTO THE WALL.NOTIFY PROJECT ENGINEER IN THE EVENT THAT THIS IS NOT POSSIBLE.
11CONDUIT ROUTED TO CHILLERS SHALL BE RIGID GALVANIZED UTILIZING COOPER B-LINE DURA-BLOK ROOF TOPSUPPORTS (OR SIMILAR). FINAL CONNECTION TO CHILLER SHALL BE MADE WITH LIQUID TIGHT FLEXIBLECONDUIT
12BOILER EMERGENCY E-STOP. CONTRACTOR SHALL FURNISH WITH CLEAR POLY-CARB PROTECTIVE COVERAND LABLED ACCORDINGLY. TIE INTO SHUNT-TRIP CIRCUIT BREAKER FEEDING BOILER CIRCUITS.
13REPLACE EXTG RECEPTACLE WITH NEW GFCI DEVICE AND RE-FEED FROM NEW PANEL PB-SBR (STANDBYPOWER). PIT LIGHTS AND RECEPTS SHALL BE ON THE SAME CIRCUIT.
14CONTRACTOR TO MOUNT DRIVE TO STRUCTURAL SUPPORT OR PROVIDE INDEPENDENT STRUT SUPPORT FORDRIVE. DO NOT MOUNT ON HVAC EQUIPMENT.
15CONTRACTOR TO INSTAL (1) 1 1/4" CONDUIT FROM PANEL PB-SB (RAMP LEVEL) TO THE ELEVATOR MACHINEROOMS FOR FUTURE STANDBY POWER CONNECTION TO THE ELEVATORS. INSTALL A JUNCTION BOX IN EACHROOM WITH A LABLED COVER PLATE "FUTURE ELEVATOR STANDBY POWER"
GENERAL ELECTRICAL POWER NOTES:
1. REFER TO SHEET E5.0 FOR EQUIPMENT CONNECTION SCHEDULE
2. CONTRACTOR SHALL REVIEW MECHANICAL DRAWINGS AND EQUIPMENT SCHEDULE FOR ADDITIONALINFORMATION AND COORDINATION.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E2.2
5-2420
PHASE 2 - SECOND & THIRDFLOOR ELECTRICAL PLAN
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
10.22.12 OWNER REVIEW
NORTH
1/8" = 1'-0"POWER 2FNORTH
1/8" = 1'-0"POWER 3F
DNUP
DNUP
V
V
AV
AV
F
F
S
S
S
V
VV
VV
V
V
V
V
V
V
V
AV
AV
AV
AV
DS
V V V
VVVV
AV
AV
AV
SD
DNUPDN UP
AV
AV
V
F F
AV
V
S
S
S
AV
AV
AV
V
V
V
AVV
V
AV AV
AV
S
V
V
V V V V
AV
V
D
DD
S
S
PB-4LPB-4R
TR-4R
FPFP
FP
07
07
03
10
10
10
INSTALL (1) 4"METALLIC CONDUITSLEEVE WITHPLASTIC BUSHINGSBETWEEN THE 4THAND 5TH FLOORSFOR IT CABLINGCHASE.COORDINATE FINALLOCATION WITHOWNER.
OFFICE401
OFFICE402
OFFICE403
OFFICE404
OFFICE405 OFFICE
406
MENS407
MECH408
CORR409
OFFICE410
OFFICE411
STOR412
ELEC413B
WOMENS414
LOBBY415
ENTRY416
KITCHETTE417
CORR418
JAN419
OFFICE420
WORK RM421
CONF422
CORR423
CONF424
OFFICE425
OFFICE426
OFFICE427
OFFICE428
OFFICE429
TOILET430
MECH413A
PB-5L
PB-5RTR-5R
FPFP
FP
07
07
03
10
10
10
OFFICE501
OFFICE502
OFFICE503
OFFICE504
OFFICE505 OFFICE
506STOR507
BREAK509OFFICE
510 CORR511
MENS512
MECH513
FILES514
CONF515
OPEN OFFICE516
MECH517
ELEC518
WOMENS519
JAN520
CORR521
OFFICE522
CONF523
OPEN OFFICE524
OPEN OFFICE525
OFFICE526
OFFICE527
OFFICE528
OFFICE529
OFFICE530
STOR508
01CONTRACTOR SHALL FURNISH AND INSTALL NEW SQUARE D POWERLOGIC METERING ON EXISTINGSWITCHBOARD MAINS. REFER TO SPECIFICATIONS
02CONTRACTOR SHALL FURNISH AND INSTALL SURGE PROTECTION DEVICE ON EXISTING SWITCHBOARD. REFERTO SPECIFICATIONS.
03CONTRACTOR SHALL INSTALL NEW CONDUIT RISER TO PENTHOUSE FOR NEW PANELBOARD PB-7L - REFER TOONE-LINE DIAGRAM
04CONDUITS SHALL BE INSTALLED IN A MINIMUM OF 2" CONCRETE ENCASEMENT TO AUTOMATIC TRANSFERSWITCH
05FIRE PUMP AUTOMATIC TRANSFER SWICH AND PUMP CONTROLLER BY TRADES, INSTALLED BY ELECTRICALCONTRACTOR
ELECTRICAL POWER KEYED NOTES:
06CUT AND PATCH THE EXISTING PAVEMENT AS REQUIRED TO FACILITATE THE INSTALLATION OF NEWUNDERGROUND CONDUITS FOR THE GENERATOR AND FIRE PUMP SERVICE ENTRANCE
07EXISTING ELEVATOR SYSTEM SMOKE DETECTOR TO REMAIN
08REPLACE EXTG RECEPTACLE WITH GFCI AND FURNISH METAL WET LOCATION IN-USE COVER
09NOT ALL REQUIRED CONDUIT RUNS ARE SHOWN. REFER TO MANUFACTURER'S SUBMITTALS ANDINSTALLATION INSTRUCTIONS.
10EVERY ATTEMPT SHALL BE MADE TO FISH THE EXTG WALL AND RECESS MOUNT THE OUTLET INTO THE WALL.NOTIFY PROJECT ENGINEER IN THE EVENT THAT THIS IS NOT POSSIBLE.
11CONDUIT ROUTED TO CHILLERS SHALL BE RIGID GALVANIZED UTILIZING COOPER B-LINE DURA-BLOK ROOF TOPSUPPORTS (OR SIMILAR). FINAL CONNECTION TO CHILLER SHALL BE MADE WITH LIQUID TIGHT FLEXIBLECONDUIT
12BOILER EMERGENCY E-STOP. CONTRACTOR SHALL FURNISH WITH CLEAR POLY-CARB PROTECTIVE COVERAND LABLED ACCORDINGLY. TIE INTO SHUNT-TRIP CIRCUIT BREAKER FEEDING BOILER CIRCUITS.
13REPLACE EXTG RECEPTACLE WITH NEW GFCI DEVICE AND RE-FEED FROM NEW PANEL PB-SBR (STANDBYPOWER). PIT LIGHTS AND RECEPTS SHALL BE ON THE SAME CIRCUIT.
14CONTRACTOR TO MOUNT DRIVE TO STRUCTURAL SUPPORT OR PROVIDE INDEPENDENT STRUT SUPPORT FORDRIVE. DO NOT MOUNT ON HVAC EQUIPMENT.
15CONTRACTOR TO INSTAL (1) 1 1/4" CONDUIT FROM PANEL PB-SB (RAMP LEVEL) TO THE ELEVATOR MACHINEROOMS FOR FUTURE STANDBY POWER CONNECTION TO THE ELEVATORS. INSTALL A JUNCTION BOX IN EACHROOM WITH A LABLED COVER PLATE "FUTURE ELEVATOR STANDBY POWER"
GENERAL ELECTRICAL POWER NOTES:
1. REFER TO SHEET E5.0 FOR EQUIPMENT CONNECTION SCHEDULE
2. CONTRACTOR SHALL REVIEW MECHANICAL DRAWINGS AND EQUIPMENT SCHEDULE FOR ADDITIONALINFORMATION AND COORDINATION.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E2.3
5-2420
PHASE 2 - FOURTH & FIFTHFLOOR ELECTRICAL PLAN
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
10.22.12 OWNER REVIEW
NORTH
1/8" = 1'-0"POWER 4FNORTH
1/8" = 1'-0"POWER 5F
DNUPDNUP
F
F
AV
V
AV
V
V
V
S
S
SS
VV
V V V V V
V
V
V
V
V
V
VV
V V V V V
V
AV
AV
AV AV
D S
AV
AV
AV
DNDN
AV F
7.5
7.5
25
25
E
E
F
AV
S
S
D
AV
J
J
AV
AV
D
22
PB-6LPB-6R
03
FPFP
FP
07
07
10
10
10
OFFICE600
OFFICE602
OFFICE603
OFFICE604
OFFICE605
OFFICE606
OFFICE607A
MENS608
MECH609
CORR610
OFFICE611
OFFICE612
OFFICE613
ELEC614B
WOMENS615
LOBBY616
OFFICE617B
CORR618
OFFICE620
OFFICE621
OFFICE622
OFFICE623
CORR624
WORK ROOM625
OFFICE626
OFFICE627
OFFICE628
OFFICE629
OFFICE630
CONF.631
OFFICE601
OFFICE607B
CLOSET619
OFFICE617A
MECH614A
TR-6R
PB-7P
TR-7RPB-7R
03
FPFP1010
11
12
12
AHU SERVICELIGHTS/RECEPT
WPGFCI
WPGFCI
GFCI
GFCI
GFCI
PBSBR-3
REFER TOLIGHTING PLANS
PBSB-2,4,6
15
15
MECH701
PENTHOUSE702
EQUIPMENT703ELEV. RM
704
ELEV. RM705
CHILR-2CHILR-1
UH-4 236 235
P-9P-8P-2P-1
AHU-3
VFD
VFD
PB7P-43,45,47
PB7P-38,40,42
PB7R-3
PB7P-32,34,36
PB7R-2
PB7R-1
P-7P-6
P-3 P-4
P-13
P-15
P-14P-10P-5
PB7P-7,9,11PB7P-8,10,12PB7P-19,21,23
PB7P-13,15,17PB7P-20,22,24
PB7P-25,27,29VFD VFD VFD VFD VFD
VFD
VFD
VFD
PB7P-13,15,17
PB7P-14,16,18
PB7P-13,15,17
PB7P-37,39,41
PB7P-2,4,6
PB7P-13,15,17 PB7P-2,4,6
PB7R-4
EF-5 EF-4
EF-6
01CONTRACTOR SHALL FURNISH AND INSTALL NEW SQUARE D POWERLOGIC METERING ON EXISTINGSWITCHBOARD MAINS. REFER TO SPECIFICATIONS
02CONTRACTOR SHALL FURNISH AND INSTALL SURGE PROTECTION DEVICE ON EXISTING SWITCHBOARD. REFERTO SPECIFICATIONS.
03CONTRACTOR SHALL INSTALL NEW CONDUIT RISER TO PENTHOUSE FOR NEW PANELBOARD PB-7L - REFER TOONE-LINE DIAGRAM
04CONDUITS SHALL BE INSTALLED IN A MINIMUM OF 2" CONCRETE ENCASEMENT TO AUTOMATIC TRANSFERSWITCH
05FIRE PUMP AUTOMATIC TRANSFER SWICH AND PUMP CONTROLLER BY TRADES, INSTALLED BY ELECTRICALCONTRACTOR
ELECTRICAL POWER KEYED NOTES:
06CUT AND PATCH THE EXISTING PAVEMENT AS REQUIRED TO FACILITATE THE INSTALLATION OF NEWUNDERGROUND CONDUITS FOR THE GENERATOR AND FIRE PUMP SERVICE ENTRANCE
07EXISTING ELEVATOR SYSTEM SMOKE DETECTOR TO REMAIN
08REPLACE EXTG RECEPTACLE WITH GFCI AND FURNISH METAL WET LOCATION IN-USE COVER
09NOT ALL REQUIRED CONDUIT RUNS ARE SHOWN. REFER TO MANUFACTURER'S SUBMITTALS ANDINSTALLATION INSTRUCTIONS.
10EVERY ATTEMPT SHALL BE MADE TO FISH THE EXTG WALL AND RECESS MOUNT THE OUTLET INTO THE WALL.NOTIFY PROJECT ENGINEER IN THE EVENT THAT THIS IS NOT POSSIBLE.
11CONDUIT ROUTED TO CHILLERS SHALL BE RIGID GALVANIZED UTILIZING COOPER B-LINE DURA-BLOK ROOF TOPSUPPORTS (OR SIMILAR). FINAL CONNECTION TO CHILLER SHALL BE MADE WITH LIQUID TIGHT FLEXIBLECONDUIT
12BOILER EMERGENCY E-STOP. CONTRACTOR SHALL FURNISH WITH CLEAR POLY-CARB PROTECTIVE COVERAND LABLED ACCORDINGLY. TIE INTO SHUNT-TRIP CIRCUIT BREAKER FEEDING BOILER CIRCUITS.
13REPLACE EXTG RECEPTACLE WITH NEW GFCI DEVICE AND RE-FEED FROM NEW PANEL PB-SBR (STANDBYPOWER). PIT LIGHTS AND RECEPTS SHALL BE ON THE SAME CIRCUIT.
14CONTRACTOR TO MOUNT DRIVE TO STRUCTURAL SUPPORT OR PROVIDE INDEPENDENT STRUT SUPPORT FORDRIVE. DO NOT MOUNT ON HVAC EQUIPMENT.
15CONTRACTOR TO INSTAL (1) 1 1/4" CONDUIT FROM PANEL PB-SB (RAMP LEVEL) TO THE ELEVATOR MACHINEROOMS FOR FUTURE STANDBY POWER CONNECTION TO THE ELEVATORS. INSTALL A JUNCTION BOX IN EACHROOM WITH A LABLED COVER PLATE "FUTURE ELEVATOR STANDBY POWER"
GENERAL ELECTRICAL POWER NOTES:
1. REFER TO SHEET E5.0 FOR EQUIPMENT CONNECTION SCHEDULE
2. CONTRACTOR SHALL REVIEW MECHANICAL DRAWINGS AND EQUIPMENT SCHEDULE FOR ADDITIONALINFORMATION AND COORDINATION.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E2.4
5-2420
PHASE 2 - SIXTH FLOOR &PENTHOUSE ELECTRICAL
PLAN
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
10.22.12 OWNER REVIEW
NORTH
1/8" = 1'-0"POWER 6FNORTH
1/8" = 1'-0"POWER PENTHOUSE
UP
UP
33 3
4
M
LCLC
OS
SASA SA
SASA
SB SB SB
SBSBSB
SB SB SB
SA
SD
SD
D2
D2EM
D2
D2EM
D2
D2D2EM
BEMB
BB
B
B
HEMH HH
HEM
H
H
H
HEM
HEMHEM
H
DEM DEM
01
02
SC
SC
SC
SC
SG2
H HEM
H
H
EM
EMPBEM-1PBEM-1
PBEM-1
PBRL-1
PBRL-1 PBRL-1
PBRL-1
PBRL-1PBRL-1
PBRL-1
PBRL-1
N.L.
N.L.N.L.
PBRL-1
THRU LC-2
THRU LC-1
PBEM-1
THRU LC-1
TO EXTG STEPLIGHTS ABOVE
07
PBEM-1
PBRL-3
PBRL-1
THRU LC-2
LC-1LC-2
H H PBRL-1
VESTIBULE001
LOBBY002
MECHANICAL003
FIRE PUMP004
STORAGE005
MOUNT FIXTURE HORIZONTALLYAS HIGH AS POSSIBLE
SGEMN.L.
SA
GENERAL LIGHTING NOTES:
THE EXISTING LOCAL LIGHTING CIRCUITS SHALL BE UTILIZED FOR ALL NEW LIGHT FIXTURE LOCATIONS.THE ELECTRICAL CONTRACTOR SHALL NOTE CIRCUIT NUMBERS ON RECORD AS-BUILTS. FIELD VERIFYPANELBOARD SCHEDULE AND PROVIDE A NEW TYPE-WRITTEN DIRECTORY FOR EACH LIGHTING PANELAT PROJECT COMPLETION.
NEW OCCUPANCY SENSORS SHALL BE INSTALLED ON THE LINE SIDE OF ALL LOCAL SWITCHING DEVICESAND SHALL BE LOCATED PER MANUFACTURERS RECOMMENDATIONS. KEEP A MINIMUM OF 6'-0" CLEAR OFALL HVAC DIFFUSERS.
REVISE ALL EMERGENCY LIGHTING CIRCUITS AS SHOWN ON THE NEW LIGHTING PLANS.INSTALL AN EMERGENCY LIGHTING CIRCUIT CONDUIT RISER AND INSTALL A JUNCTION BOXLOCATED ON EACH FLOOR IN THE ELECTRICAL CLOSET FOR CONNECTION TO NEWEMERGENCY AND/OR NIGHT LIGHT FIXTURES.
LIGHTING KEYED NOTES:
1.
2.
3.
01CUT CONCRETE TO ALLOW FOR EXISTING IN-GRADE FIXTURE REMOVAL AND TO INTERCEPT THE EXISTINGCONDUIT. EXTEND CONDUIT TO NEW LIGHT FIXTURE CONCRETE BASES AND PATCH AND REPAIR CONCRETESURFACE AS REQUIRED. REFER TO DETAIL ON SHEET E7.0
02INSTALL NEW LIGHT FIXTURE OVER EXISTING ROUGH-IN BOX.
03UTILIZE EXTG CONDUIT AND ROUGH-IN BOX TO INSTALL AN ADDITIONAL SWITCH LEG TO ACCOMPLISH DUALLEVEL SWITCHING.
04REMOVE AND/OR REPAIR EXISTING SOFFIT TO ALLOW FOR NEW LIGHT FIXTURE INSTALLATION
05CONTRACTOR SHALL FURNISH AND INSTALL A CUSTOM ORDERED RETROFIT KIT TO REPLACE THE EXISTINGDOWNLIGHT. CONTRACTOR SHALL PROVIDE ACCURATE DIMENSIONS TO MANUFACTURER PRIOR TO FIXTUREAPPROVAL.
06CONTRACTOR SHALL FISH EXISTING WALL TO INSTALL NEW SWITCH - SURFACE RACEWAY WILL NOT BEACCEPTABLE.
07INTERCEPT EXISTING CONDUIT AND INSTALL NEW CONDUCTORS IF POSSIBLE.
08E.C. TO UTILIZE EXTG CIRCUIT. RECORD DRAWINGS INDICATE FIXTURES ARE FED FROM PANEL BOARD PB-2LVIA A TIME CLOCK. REMOVE TIME CLOCK AND TIE INTO NEW SINGLE POLE (277V) RELAY FURNISHED BY TEMP.CONTROLS CONTRACTOR.
THE INTENT OF THE LIGHTING REVISIONS IS AS FOLLOWS:A. REMOVE AND REPLACE ALL EXISTING T12 FLUORESCENT
AND MERCURY VAPOR LIGHT FIXTURES WITH NEW, MORE EFFICIENT, LUMINAIRES.
B. ADD OCCUPANCY SENSOR CONTROL TO ALL SPACES (WITH THE EXCEPTION OF MECHANICAL EQUIPMENT AND ELECTRICAL SPACES)
C. PROVIDE ALL OFFICES AND SIMILAR SPACES WITH DUAL LIGHT LEVEL CONTROL. IN MOST CASES THIS WILL REQUIRE THE CONTRACTOR TO INSTALL ADDITIONAL SWITCH LEGS EITHER BY FISHING THE EXISTING WALL OR UTILIZING THE EXISTING
CONDUIT SYSTEM.
4.
09CONNECT EXISTING FIXTURE TO NIGHT LIGHT / EMERGENCY CIRCUIT AS SHOWN. ADJACENT FIXTURES TOREMAIN SWITCHED AS-IS.
10CUT-IN NEW SWITCH(ES) AS SHOWN. CONTRACTOR SHALL MAKE EVERY ATTEMP TO FISH THE EXISTING WALL.NOTIFY PROJECT ENGINEER IN THE EVENT THIS IS NOT POSSIBLE.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E3.0
5-2420
PHASE 2 - RAMP LIGHTINGPLAN
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
10.22.12 OWNER REVIEW
NORTH
1/8" = 1'-0"LIGHTING - RAMP LEVEL
DN
UP
UP
UP
DN
3
M
MM
OS
OSD
OS OSD
OS
M
OSD
LC LC
DN
DNUPDN
UP
M
M
M
MM
M
M
M
OSD OSD
OSD
OS
OS
OSDOSD
OS
3
3
M
3
M
M M M
MM
3
M
GEMN.L.
SF SFSD
SD
A2
A2
A2
A
A
A2
A2
A2
A2
BEM B
HEM
JEM
J
F
F
BEM
B
BEM
D2EM
HEM
GEMN.L.
D2EM
D
H
03
03
02
02 02 02
SG
SG SGEM
SGEM
D2EM
GEMN.L.
D2EM
N.L.
N.L.
N.L.
N.L.
N.L.
N.L.
PBEMR-1
EM
EM
EM
03
LOCAL 'HOT'
LOCAL 'HOT'
THRU R-1
TO NIGHT LTS ONMEZZANINE LEVEL
LOCAL 'HOT' LEG
N.L.
N.L.
N.L.
TO EXTGSTEP LTS BELOW
VESTP101
MECHP102
LOBBYP103
CONFP104
WORK ROOMP105
RECEPTP106
VAULTP107
CORRP108
OFFICEP109
MECHP110
OFFICEP111T.
P112
CORRP113
JANP114
OFFICEP115
OFFICEP116
OFFICEP117
04
THRU R-2
PBPR-1TO LIGHTSABOVE
TO LIGHTSABOVE
RELAYS R-1 & R-2 FURNISHED BYTEMP. CONTROLS CONTRACTOR.'HIGH VOLTAGE' WIRING BY E.C.
09
09
09
09
09
09
09
09
PBEMR-1
PBPR-1
SA SA
SA
GEMN.L.
GEMN.L.
GEMN.L.
A2 A2 A2
A2 A2 A2
A2
A2
A2
A2
A2
A3 A3 A3 A3 A3EM
A2
A2
A2
A2
A2
A2
A2
A2
DDDEMDDDDDEMDDDEM
DDEM
D
D
A3
A3EM
A3
JEM
JEM
J
D
D
D D D
SA2
SA2
SA2SA2
J
DEM
BEM
B
GEMN.L.
HEM
H
H
A3EM
GEMN.L.
GEMN.L.
DEM
06
03030303
03
04
N.L.
N.L.
N.L.N.L.
N.L.
N.L.
N.L.
N.L.
N.L.
N.L.N.L.
EM
EM
EM
D
D
D
LOCAL 'HOT' LEG
LOCAL 'HOT' LEG
LOCAL 'HOT' LEG
PBEMR-3
PBPR-1TIE INTO DOWNLIGHTSON PLAZA LEVEL
PBEMR-1TIE INTO DOWNLIGHTSON PLAZA LEVEL
K
OFFICEM101
CORRM102
MECHM103
JANM104
LOBBYM105
OFFICEM106 OFFICE
M107OPEN OFFICE
M108
STORM109
OFFICEM110
OFFICEM111
OFFICEM112
WORK ROOMM113
ELECM114 MENS
M115
LOUNGEM118
WOMENSM117
MECHM116
CONTRACTOR SHALL RE-INSTALL EXISTING LIGHTFIXTURES AS SHOWN IN THIS AREA - EXTGCIRCUITING TO REMAIN
10
GENERAL LIGHTING NOTES:
THE EXISTING LOCAL LIGHTING CIRCUITS SHALL BE UTILIZED FOR ALL NEW LIGHT FIXTURE LOCATIONS.THE ELECTRICAL CONTRACTOR SHALL NOTE CIRCUIT NUMBERS ON RECORD AS-BUILTS. FIELD VERIFYPANELBOARD SCHEDULE AND PROVIDE A NEW TYPE-WRITTEN DIRECTORY FOR EACH LIGHTING PANELAT PROJECT COMPLETION.
NEW OCCUPANCY SENSORS SHALL BE INSTALLED ON THE LINE SIDE OF ALL LOCAL SWITCHING DEVICESAND SHALL BE LOCATED PER MANUFACTURERS RECOMMENDATIONS. KEEP A MINIMUM OF 6'-0" CLEAR OFALL HVAC DIFFUSERS.
REVISE ALL EMERGENCY LIGHTING CIRCUITS AS SHOWN ON THE NEW LIGHTING PLANS.INSTALL AN EMERGENCY LIGHTING CIRCUIT CONDUIT RISER AND INSTALL A JUNCTION BOXLOCATED ON EACH FLOOR IN THE ELECTRICAL CLOSET FOR CONNECTION TO NEWEMERGENCY AND/OR NIGHT LIGHT FIXTURES.
LIGHTING KEYED NOTES:
1.
2.
3.
01CUT CONCRETE TO ALLOW FOR EXISTING IN-GRADE FIXTURE REMOVAL AND TO INTERCEPT THE EXISTINGCONDUIT. EXTEND CONDUIT TO NEW LIGHT FIXTURE CONCRETE BASES AND PATCH AND REPAIR CONCRETESURFACE AS REQUIRED. REFER TO DETAIL ON SHEET E7.0
02INSTALL NEW LIGHT FIXTURE OVER EXISTING ROUGH-IN BOX.
03UTILIZE EXTG CONDUIT AND ROUGH-IN BOX TO INSTALL AN ADDITIONAL SWITCH LEG TO ACCOMPLISH DUALLEVEL SWITCHING.
04REMOVE AND/OR REPAIR EXISTING SOFFIT TO ALLOW FOR NEW LIGHT FIXTURE INSTALLATION
05CONTRACTOR SHALL FURNISH AND INSTALL A CUSTOM ORDERED RETROFIT KIT TO REPLACE THE EXISTINGDOWNLIGHT. CONTRACTOR SHALL PROVIDE ACCURATE DIMENSIONS TO MANUFACTURER PRIOR TO FIXTUREAPPROVAL.
06CONTRACTOR SHALL FISH EXISTING WALL TO INSTALL NEW SWITCH - SURFACE RACEWAY WILL NOT BEACCEPTABLE.
07INTERCEPT EXISTING CONDUIT AND INSTALL NEW CONDUCTORS IF POSSIBLE.
08E.C. TO UTILIZE EXTG CIRCUIT. RECORD DRAWINGS INDICATE FIXTURES ARE FED FROM PANEL BOARD PB-2LVIA A TIME CLOCK. REMOVE TIME CLOCK AND TIE INTO NEW SINGLE POLE (277V) RELAY FURNISHED BY TEMP.CONTROLS CONTRACTOR.
THE INTENT OF THE LIGHTING REVISIONS IS AS FOLLOWS:A. REMOVE AND REPLACE ALL EXISTING T12 FLUORESCENT
AND MERCURY VAPOR LIGHT FIXTURES WITH NEW, MORE EFFICIENT, LUMINAIRES.
B. ADD OCCUPANCY SENSOR CONTROL TO ALL SPACES (WITH THE EXCEPTION OF MECHANICAL EQUIPMENT AND ELECTRICAL SPACES)
C. PROVIDE ALL OFFICES AND SIMILAR SPACES WITH DUAL LIGHT LEVEL CONTROL. IN MOST CASES THIS WILL REQUIRE THE CONTRACTOR TO INSTALL ADDITIONAL SWITCH LEGS EITHER BY FISHING THE EXISTING WALL OR UTILIZING THE EXISTING
CONDUIT SYSTEM.
4.
09CONNECT EXISTING FIXTURE TO NIGHT LIGHT / EMERGENCY CIRCUIT AS SHOWN. ADJACENT FIXTURES TOREMAIN SWITCHED AS-IS.
10CUT-IN NEW SWITCH(ES) AS SHOWN. CONTRACTOR SHALL MAKE EVERY ATTEMP TO FISH THE EXISTING WALL.NOTIFY PROJECT ENGINEER IN THE EVENT THIS IS NOT POSSIBLE.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E3.1
5-2420
PHASE 2 - PLAZA & MEZZANINELIGHTING PLAN
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
10.22.12 OWNER REVIEW
NORTH
1/8" = 1'-0"LIGHTING - PLAZA LEVEL
NORTH
1/8" = 1'-0"LIGHTING - MEZZANINE LEVEL
DNUPDN
UP
3
3
3
4
3 3
3
3
M
M
M
M
M
M
M
M
M M
M
M
M
M
M
OSD OSD OSD OSD OSD
OSD
OSD
OSD
OS
OSD
OSD OSD OSD
OSD
OS
OSD
OS
OSD
M
M
M
M
3
3
3
LC
3
DNUPDNUP
3
3
3
3
M
M
M
M
M
M
M
M
M M
MM
M
M
M
OSD OSD OSD OSD OSDOSD
OSD
OSD
OS
OSD
OSD
OS
OSD
OSDOSDOSD
OS
OSD
M
M
3
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A3EM
A2
A2 A2
A2
A2 A2
A2 A2
A2 A2 A2
A2 A2 A A
A2
A A
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A3EM
A3
A3
BEM
BEMB B B
BEM
B
B
B
B
BEM
B
B
BEMBBBEMBBBEM
BEM
A3EM
B
D
DEM
B
B
B
B
B
A2 A2
A2 A2
GEMN.L.
HH
HEM J
JEM
J
GEMN.L.
GEMN.L.
GEMN.L.
A2
A2
A2
B
B
B
BEM
A3
A3EM A3
A3
A3EM
HEM
03 03 03 03 03
03
03
03
0303
03
0303
03
03
SH2 SH2 SH2 SH2
05 05
C
C
B
PBEM-7
03
EM
EM
EM
EM
S4EMS4EMN.L. N.L.
LOCAL 'HOT' LEG
LOCAL 'HOT' LEG
LOCAL 'HOT' LEG
LOCAL 'HOT' LEG
LOCAL SWITCH LEG
N.L.
N.L.
N.L.
N.L.
N.L.
N.L.
N.L.
N.L.
N.L.
N.L.
N.L. N.L. N.L.
08
CORR.201
MENS202
OFFICE203
OFFICE204
OFFICE205
OFFICE206
OFFICE207
OFFICE208
CORR209
MECH210
OFFICE211
OFFICE212
LOBBY213
ENTRY214
WORK RM215
CONF216
OFFICE217
LIBRARY218
MECH219
WOMENS220
ELEC221
JAN222
CORR223
CONF224
CORR225
OFFICE226
OFFICE227 OFFICE
228OFFICE
229
OFFICE230
OFFICE231
CORR200
THRU R-3
RELAY (R-3) FURNISHED BYTEMP. CONTROLS CONTRACTORFOR EXTERIOR SOFFIT LIGHTS
03
TO THREE-WAY SWITCHAT BOTTOM OF STAIR
S7'
S7'
S8'-7"S8'-7"
K
GEMN.L.
GEMN.L.
GEMN.L.
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2 A2 A2 A2
A2A2A3
A2
A2 A2
A2 A2
A2 A2
A2 A2
A2
A2
A2
A2
A2
A2
A2
A2 A2
A2A2 A2 A2
A2
A2
B
BEM
B BBEM
BBEM
B
B
B
BEM
BBEM
B
B
B
J
JEM
BEMBBBEMB
BEM
J
JEM
BEMB
D DEM
H H
HEM
BEM
B
A2 A2
A2 A2
A2 A2
GEMN.L. D DEM
DD
S4EMS4EM
03 03 0303 03 03
03
03
03
03
03
03
030303
EM
EM
EM
N.L.
N.L.
N.L.
N.L.N.L.
N.L.
N.L.N.L.
N.L.
N.L. N.L. N.L.
LOCAL 'HOT' LEG
C
K
N.L.
LOCAL 'HOT' LEG
LOCAL 'HOT' LEG
PBEM-4
OFFICE301
OFFICE302
OFFICE303
OFFICE304
OFFICE305
OFFICE306
OFFICE307
OFFICE308
CORR309
MENS310
MECH311
CONF312
STOR313 OFFICE
314
MECH315 WOMENS
316ELEC317
JAN.318
LOBBY319
CORR320
STOR321
FILES322
CORR323
STOR324
CONF325
OFFICE326
OFFICE327
CONF328 OFFICE
329OFFICE
330OFFICE
331OFFICE
332
OFFICE333
1010
10
10
S7'
S7'
S8'-7"S8'-7"
GENERAL LIGHTING NOTES:
THE EXISTING LOCAL LIGHTING CIRCUITS SHALL BE UTILIZED FOR ALL NEW LIGHT FIXTURE LOCATIONS.THE ELECTRICAL CONTRACTOR SHALL NOTE CIRCUIT NUMBERS ON RECORD AS-BUILTS. FIELD VERIFYPANELBOARD SCHEDULE AND PROVIDE A NEW TYPE-WRITTEN DIRECTORY FOR EACH LIGHTING PANELAT PROJECT COMPLETION.
NEW OCCUPANCY SENSORS SHALL BE INSTALLED ON THE LINE SIDE OF ALL LOCAL SWITCHING DEVICESAND SHALL BE LOCATED PER MANUFACTURERS RECOMMENDATIONS. KEEP A MINIMUM OF 6'-0" CLEAR OFALL HVAC DIFFUSERS.
REVISE ALL EMERGENCY LIGHTING CIRCUITS AS SHOWN ON THE NEW LIGHTING PLANS.INSTALL AN EMERGENCY LIGHTING CIRCUIT CONDUIT RISER AND INSTALL A JUNCTION BOXLOCATED ON EACH FLOOR IN THE ELECTRICAL CLOSET FOR CONNECTION TO NEWEMERGENCY AND/OR NIGHT LIGHT FIXTURES.
LIGHTING KEYED NOTES:
1.
2.
3.
01CUT CONCRETE TO ALLOW FOR EXISTING IN-GRADE FIXTURE REMOVAL AND TO INTERCEPT THE EXISTINGCONDUIT. EXTEND CONDUIT TO NEW LIGHT FIXTURE CONCRETE BASES AND PATCH AND REPAIR CONCRETESURFACE AS REQUIRED. REFER TO DETAIL ON SHEET E7.0
02INSTALL NEW LIGHT FIXTURE OVER EXISTING ROUGH-IN BOX.
03UTILIZE EXTG CONDUIT AND ROUGH-IN BOX TO INSTALL AN ADDITIONAL SWITCH LEG TO ACCOMPLISH DUALLEVEL SWITCHING.
04REMOVE AND/OR REPAIR EXISTING SOFFIT TO ALLOW FOR NEW LIGHT FIXTURE INSTALLATION
05CONTRACTOR SHALL FURNISH AND INSTALL A CUSTOM ORDERED RETROFIT KIT TO REPLACE THE EXISTINGDOWNLIGHT. CONTRACTOR SHALL PROVIDE ACCURATE DIMENSIONS TO MANUFACTURER PRIOR TO FIXTUREAPPROVAL.
06CONTRACTOR SHALL FISH EXISTING WALL TO INSTALL NEW SWITCH - SURFACE RACEWAY WILL NOT BEACCEPTABLE.
07INTERCEPT EXISTING CONDUIT AND INSTALL NEW CONDUCTORS IF POSSIBLE.
08E.C. TO UTILIZE EXTG CIRCUIT. RECORD DRAWINGS INDICATE FIXTURES ARE FED FROM PANEL BOARD PB-2LVIA A TIME CLOCK. REMOVE TIME CLOCK AND TIE INTO NEW SINGLE POLE (277V) RELAY FURNISHED BY TEMP.CONTROLS CONTRACTOR.
THE INTENT OF THE LIGHTING REVISIONS IS AS FOLLOWS:A. REMOVE AND REPLACE ALL EXISTING T12 FLUORESCENT
AND MERCURY VAPOR LIGHT FIXTURES WITH NEW, MORE EFFICIENT, LUMINAIRES.
B. ADD OCCUPANCY SENSOR CONTROL TO ALL SPACES (WITH THE EXCEPTION OF MECHANICAL EQUIPMENT AND ELECTRICAL SPACES)
C. PROVIDE ALL OFFICES AND SIMILAR SPACES WITH DUAL LIGHT LEVEL CONTROL. IN MOST CASES THIS WILL REQUIRE THE CONTRACTOR TO INSTALL ADDITIONAL SWITCH LEGS EITHER BY FISHING THE EXISTING WALL OR UTILIZING THE EXISTING
CONDUIT SYSTEM.
4.
09CONNECT EXISTING FIXTURE TO NIGHT LIGHT / EMERGENCY CIRCUIT AS SHOWN. ADJACENT FIXTURES TOREMAIN SWITCHED AS-IS.
10CUT-IN NEW SWITCH(ES) AS SHOWN. CONTRACTOR SHALL MAKE EVERY ATTEMP TO FISH THE EXISTING WALL.NOTIFY PROJECT ENGINEER IN THE EVENT THIS IS NOT POSSIBLE.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E3.2
5-2420
PHASE 2 - SECOND & THIRDFLOOR LIGHTING PLAN
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
10.22.12 OWNER REVIEW
NORTH
1/8" = 1'-0"LIGHTING - 2ND FLOORNORTH
1/8" = 1'-0"LIGHTING - 3RD FLOOR
DNUP
DNUP
3
3
3
M
M M
M
M
M
M
M
M
MM
M M
M
M
OSD OSD
OSD
OSD OSD OSD OSD
OSDOSD
OSD
OS
OS
OS
M
M
M
3
3
3
DNUPDN UP
3
3
M
M
M
M
M
M M
M
M
M
M
OSD
OSD
OSD
OSD
OSD
OS
OS
OSD
OSD OSD OSD
OSD
OSD
OS
OS
OSD
OS
M
OSD
M
M
3
3 3
3
GEMN.L.
GEMN.L.
GEMN.L.
A2 A2
A2A2
A2 A2
A2A2
A2 A2
A2A2
A2 A2
A2A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A3
A3
A3
A3
A2
A2
A2
BEM
B B BEM B
BEM
B
BEM B
B
B
BEMBBBEMBB
BEM
B
BEM
JEM
J
JHEM
HH
D DEM
J
JEM
B
A3
S4EMS4EMGEMN.L.
S4EM
S4EM
D
D
D
D
03 03
03
03 03 03 03
0303
03
05 05
SH1 SH1 SH1 SH1
TO LOCAL 'HOT' LEG
EM
EM
N.L.
N.L.
N.L.
N.L.
N.L.
N.L.
N.L.
N.L.
N.L.N.L.
C
C
N.L.
N.L. TO LOCAL 'HOT' LEG
TO LOCAL 'HOT' LEG
08
OFFICE401
OFFICE402
OFFICE403
OFFICE404
OFFICE405 OFFICE
406
MENS407
MECH408
OFFICE410
OFFICE411
STOR412
ELEC413B
WOMENS414
LOBBY415
ENTRY416 KITCHETTE
417
CORR418
JAN419
OFFICE420
WORK RM421
CONF422
CORR423
CONF424
OFFICE429
TOILET430
MECH413A
THRU R-3
S7'
S7'
S8'-7" S8'-7"
S18'S18'
S8'
S8'
10 10
10
10
PBEM-6
OFFICE425
OFFICE426
OFFICE427
OFFICE428
D
GEMN.L.
GEMN.L.GEM
N.L.
A2 A2 A2
A2 A2A3
A
A
A
A
A
A
A
A
A
A
A3
A3
A
A
A2
A2A
A2
A2
A2
A2 A2
A2
A2
A2
A2
A2
A2
A2
A2A2
A2B
A3
A3
A3
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2 A2
A2 A2 A2
A2
B2
B2
BBEM
B BBEM
B B
BEM
J
JJEM
J
JEM
D DEM
D
HH
HEM
B B B B B
B
GEMN.L.
S4EMS4EM
03
03
03 03 03 03
03
03
03
0303
03
PBEM-5
EM
EMC
EM
C
LOCAL 'HOT' LEG
N.L. N.L.
N.L.
N.L.
N.L.
LOCAL 'HOT' LEG
LOCAL 'HOT' LEG
B
DDD
D
D
03
10
03
S7'
S7'
S8'-7"S8'-7"
OFFICE501
OFFICE502
OFFICE503
OFFICE504
OFFICE505
OFFICE506
STOR507
BREAK509
OFFICE510
CORR511
MENS512
MECH513
FILES514
CONF515 OPEN OFFICE
516
MECH517ELEC
518 WOMENS519
JAN520
CORR521
OFFICE522
CONF523 OPEN OFFICE
524
OPEN OFFICE525 OFFICE
526OFFICE
527OFFICE
528
OFFICE529
OFFICE530
STOR508
10
GENERAL LIGHTING NOTES:
THE EXISTING LOCAL LIGHTING CIRCUITS SHALL BE UTILIZED FOR ALL NEW LIGHT FIXTURE LOCATIONS.THE ELECTRICAL CONTRACTOR SHALL NOTE CIRCUIT NUMBERS ON RECORD AS-BUILTS. FIELD VERIFYPANELBOARD SCHEDULE AND PROVIDE A NEW TYPE-WRITTEN DIRECTORY FOR EACH LIGHTING PANELAT PROJECT COMPLETION.
NEW OCCUPANCY SENSORS SHALL BE INSTALLED ON THE LINE SIDE OF ALL LOCAL SWITCHING DEVICESAND SHALL BE LOCATED PER MANUFACTURERS RECOMMENDATIONS. KEEP A MINIMUM OF 6'-0" CLEAR OFALL HVAC DIFFUSERS.
REVISE ALL EMERGENCY LIGHTING CIRCUITS AS SHOWN ON THE NEW LIGHTING PLANS.INSTALL AN EMERGENCY LIGHTING CIRCUIT CONDUIT RISER AND INSTALL A JUNCTION BOXLOCATED ON EACH FLOOR IN THE ELECTRICAL CLOSET FOR CONNECTION TO NEWEMERGENCY AND/OR NIGHT LIGHT FIXTURES.
LIGHTING KEYED NOTES:
1.
2.
3.
01CUT CONCRETE TO ALLOW FOR EXISTING IN-GRADE FIXTURE REMOVAL AND TO INTERCEPT THE EXISTINGCONDUIT. EXTEND CONDUIT TO NEW LIGHT FIXTURE CONCRETE BASES AND PATCH AND REPAIR CONCRETESURFACE AS REQUIRED. REFER TO DETAIL ON SHEET E7.0
02INSTALL NEW LIGHT FIXTURE OVER EXISTING ROUGH-IN BOX.
03UTILIZE EXTG CONDUIT AND ROUGH-IN BOX TO INSTALL AN ADDITIONAL SWITCH LEG TO ACCOMPLISH DUALLEVEL SWITCHING.
04REMOVE AND/OR REPAIR EXISTING SOFFIT TO ALLOW FOR NEW LIGHT FIXTURE INSTALLATION
05CONTRACTOR SHALL FURNISH AND INSTALL A CUSTOM ORDERED RETROFIT KIT TO REPLACE THE EXISTINGDOWNLIGHT. CONTRACTOR SHALL PROVIDE ACCURATE DIMENSIONS TO MANUFACTURER PRIOR TO FIXTUREAPPROVAL.
06CONTRACTOR SHALL FISH EXISTING WALL TO INSTALL NEW SWITCH - SURFACE RACEWAY WILL NOT BEACCEPTABLE.
07INTERCEPT EXISTING CONDUIT AND INSTALL NEW CONDUCTORS IF POSSIBLE.
08E.C. TO UTILIZE EXTG CIRCUIT. RECORD DRAWINGS INDICATE FIXTURES ARE FED FROM PANEL BOARD PB-2LVIA A TIME CLOCK. REMOVE TIME CLOCK AND TIE INTO NEW SINGLE POLE (277V) RELAY FURNISHED BY TEMP.CONTROLS CONTRACTOR.
THE INTENT OF THE LIGHTING REVISIONS IS AS FOLLOWS:A. REMOVE AND REPLACE ALL EXISTING T12 FLUORESCENT
AND MERCURY VAPOR LIGHT FIXTURES WITH NEW, MORE EFFICIENT, LUMINAIRES.
B. ADD OCCUPANCY SENSOR CONTROL TO ALL SPACES (WITH THE EXCEPTION OF MECHANICAL EQUIPMENT AND ELECTRICAL SPACES)
C. PROVIDE ALL OFFICES AND SIMILAR SPACES WITH DUAL LIGHT LEVEL CONTROL. IN MOST CASES THIS WILL REQUIRE THE CONTRACTOR TO INSTALL ADDITIONAL SWITCH LEGS EITHER BY FISHING THE EXISTING WALL OR UTILIZING THE EXISTING
CONDUIT SYSTEM.
4.
09CONNECT EXISTING FIXTURE TO NIGHT LIGHT / EMERGENCY CIRCUIT AS SHOWN. ADJACENT FIXTURES TOREMAIN SWITCHED AS-IS.
10CUT-IN NEW SWITCH(ES) AS SHOWN. CONTRACTOR SHALL MAKE EVERY ATTEMP TO FISH THE EXISTING WALL.NOTIFY PROJECT ENGINEER IN THE EVENT THIS IS NOT POSSIBLE.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E3.3
5-2420
PHASE 2 - FOURTH & FIFTHFLOOR LIGHTING PLAN
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
10.22.12 OWNER REVIEW
NORTH
1/8" = 1'-0"LIGHTING - 4TH FLOORNORTH
1/8" = 1'-0"LIGHTING - 5TH FLOOR
DNUPDNUP
3
M M M M M
M
M
M
M
M
MMMMMMM
M M
M
M
M
M M
M
M
M M
M
MMM
M
M
OSD
OS
OSD
3
3
3
DNDN
3
3
T
T
GEMN.L.
GEMN.L.
GEMN.L.
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2A2
A2 A2
A2
A2
A2 A2
A2
A2
A2
A2
A2
A2
A
A
A
A
AA A A
A2A2
A2A2 A
A
A
A
A
A
A2 A2
A2A2
A2
A2
A2 A2
A2
A2
A2A2
A2
A2
A2
A2
BEM
BEM
B B B B BEM B
B
B
BEMB
BEM
B
B
BEM BBBBBEMB
BEM
B
H
HEM
H
D D
B
B
B
BEMJ
GEMN.L.
JEM
J
J
J
JEM
J
PBEM-3
LOCAL 'HOT' LEG
LOCAL 'HOT' LEG
LOCAL 'HOT' LEG
N.L.
N.L.
N.L.
N.L.
N.L.N.L.
N.L.
N.L.
N.L.
EM
EM
EM
CC
03
03
OFFICE600 OFFICE
602OFFICE
603OFFICE
604OFFICE
605OFFICE
606
OFFICE607A
MENS608
MECH609
CORR610
OFFICE611
OFFICE612
OFFICE613
ELEC614B
WOMENS615
LOBBY616
OFFICE617B CORR
618
OFFICE620
OFFICE621
OFFICE622
OFFICE623
CORR624
WORK ROOM625
OFFICE626
OFFICE627
OFFICE628
OFFICE629
OFFICE630
CONF.631
OFFICE601
OFFICE607B
CLOSET619
OFFICE617A
MECH614A
10
GEMN.L.
GEMN.L.
GEMN.L.
GEMN.L.
HEM H
H HEM
HHEM
HEM
HEM
HEM
HH
H
H
H
HEM
SD
SD
H
HEM
H
H
H
EM
EM
EM
PBEM-2
PBSBR-3
PB6L-1
PB6L-1
PB6L-1
PB6L-1
PB6L-1
MECH701
PENTHOUSE702
EQUIPMENT703
ELEV. RM704
ELEV. RM705
GENERAL LIGHTING NOTES:
THE EXISTING LOCAL LIGHTING CIRCUITS SHALL BE UTILIZED FOR ALL NEW LIGHT FIXTURE LOCATIONS.THE ELECTRICAL CONTRACTOR SHALL NOTE CIRCUIT NUMBERS ON RECORD AS-BUILTS. FIELD VERIFYPANELBOARD SCHEDULE AND PROVIDE A NEW TYPE-WRITTEN DIRECTORY FOR EACH LIGHTING PANELAT PROJECT COMPLETION.
NEW OCCUPANCY SENSORS SHALL BE INSTALLED ON THE LINE SIDE OF ALL LOCAL SWITCHING DEVICESAND SHALL BE LOCATED PER MANUFACTURERS RECOMMENDATIONS. KEEP A MINIMUM OF 6'-0" CLEAR OFALL HVAC DIFFUSERS.
REVISE ALL EMERGENCY LIGHTING CIRCUITS AS SHOWN ON THE NEW LIGHTING PLANS.INSTALL AN EMERGENCY LIGHTING CIRCUIT CONDUIT RISER AND INSTALL A JUNCTION BOXLOCATED ON EACH FLOOR IN THE ELECTRICAL CLOSET FOR CONNECTION TO NEWEMERGENCY AND/OR NIGHT LIGHT FIXTURES.
LIGHTING KEYED NOTES:
1.
2.
3.
01CUT CONCRETE TO ALLOW FOR EXISTING IN-GRADE FIXTURE REMOVAL AND TO INTERCEPT THE EXISTINGCONDUIT. EXTEND CONDUIT TO NEW LIGHT FIXTURE CONCRETE BASES AND PATCH AND REPAIR CONCRETESURFACE AS REQUIRED. REFER TO DETAIL ON SHEET E7.0
02INSTALL NEW LIGHT FIXTURE OVER EXISTING ROUGH-IN BOX.
03UTILIZE EXTG CONDUIT AND ROUGH-IN BOX TO INSTALL AN ADDITIONAL SWITCH LEG TO ACCOMPLISH DUALLEVEL SWITCHING.
04REMOVE AND/OR REPAIR EXISTING SOFFIT TO ALLOW FOR NEW LIGHT FIXTURE INSTALLATION
05CONTRACTOR SHALL FURNISH AND INSTALL A CUSTOM ORDERED RETROFIT KIT TO REPLACE THE EXISTINGDOWNLIGHT. CONTRACTOR SHALL PROVIDE ACCURATE DIMENSIONS TO MANUFACTURER PRIOR TO FIXTUREAPPROVAL.
06CONTRACTOR SHALL FISH EXISTING WALL TO INSTALL NEW SWITCH - SURFACE RACEWAY WILL NOT BEACCEPTABLE.
07INTERCEPT EXISTING CONDUIT AND INSTALL NEW CONDUCTORS IF POSSIBLE.
08E.C. TO UTILIZE EXTG CIRCUIT. RECORD DRAWINGS INDICATE FIXTURES ARE FED FROM PANEL BOARD PB-2LVIA A TIME CLOCK. REMOVE TIME CLOCK AND TIE INTO NEW SINGLE POLE (277V) RELAY FURNISHED BY TEMP.CONTROLS CONTRACTOR.
THE INTENT OF THE LIGHTING REVISIONS IS AS FOLLOWS:A. REMOVE AND REPLACE ALL EXISTING T12 FLUORESCENT
AND MERCURY VAPOR LIGHT FIXTURES WITH NEW, MORE EFFICIENT, LUMINAIRES.
B. ADD OCCUPANCY SENSOR CONTROL TO ALL SPACES (WITH THE EXCEPTION OF MECHANICAL EQUIPMENT AND ELECTRICAL SPACES)
C. PROVIDE ALL OFFICES AND SIMILAR SPACES WITH DUAL LIGHT LEVEL CONTROL. IN MOST CASES THIS WILL REQUIRE THE CONTRACTOR TO INSTALL ADDITIONAL SWITCH LEGS EITHER BY FISHING THE EXISTING WALL OR UTILIZING THE EXISTING
CONDUIT SYSTEM.
4.
09CONNECT EXISTING FIXTURE TO NIGHT LIGHT / EMERGENCY CIRCUIT AS SHOWN. ADJACENT FIXTURES TOREMAIN SWITCHED AS-IS.
10CUT-IN NEW SWITCH(ES) AS SHOWN. CONTRACTOR SHALL MAKE EVERY ATTEMP TO FISH THE EXISTING WALL.NOTIFY PROJECT ENGINEER IN THE EVENT THIS IS NOT POSSIBLE.
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E3.4
5-2420
PHASE 2 - SIXTH FLOOR &PENTHOUSE LIGHTING PLAN
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
10.22.12 OWNER REVIEW
NORTH
1/8" = 1'-0"LIGHTING - 6TH FLOORNORTH
1/8" = 1'-0"LIGHTING - PENTHOUSE LEVEL
01
KEYNOTES
02
03
03
02
03
01
GFI
TVSS
M
N.C.
M
M
M
M
M
LOAD CALCEXISTING HISTORIC DEMAND 207.00 KWASSUMED POWER FACTOR 0.70 PF
TOTAL EXISTING LOAD 295.71 KVA
125% PER NEC 220.87 369.64 KVA
DEMOLISHED CONNECTED LOAD -267.79 KVA
NEW CONNECTED LOAD 468.78 KVATOTAL DESIGN LOAD (KVA) 570.64 KVA
TOTAL DESIGN LOAD (AMPS) 686.38 A
EXISTING SERVICE CAPACITY IS 1,000A AND THEREFORE IS SUFFICIENT
M
PB-SB480Y/277V 3PH 4W100A M.L.O.SQUARE D NF
250A/3
250A/3
LOCATED IN RAMPMECH. ROOM ADJACENTTO PANEL PB-RP x;EXTG
ATS
REMOVE EXTGMETER
REMOVE EXTGMETER
REMOVE EXTGMETER
REMOVE EXTGMETER
PB-PB-7P480Y/277V 3PH 4W250A M.L.O.SQUARE D NH1B
255NG
480Y/277V-3P-4W
EXTG 15KWEM GENERATOR
T-2R30 KVA XFMR480V x 208Y/120V
T-2RA30 KVA XFMR480V x 208Y/120V
T-RR75 KVA XFMR480V x 208Y/120V
T-6R30 KVA XFMR480V x 208Y/120V
T-3R30 KVA XFMR480V x 208Y/120V
T-4R30 KVA XFMR480V x 208Y/120V
T-5R30 KVA XFMR480V x 208Y/120V
T-7R30 KVA XFMR480V x 208Y/120V
EXTG LIGHTINGLOADS
#3/0 AWG GROUND GRIDWITH 3 - 10' GROUND RODS
PB-6L480Y/277V 3PH 4W125A M.L.O.SQUARE D NH1B
PB-6R120/208Y 3P 4W125A M.B.42 SPACESQUARE D NQO
PB-7R120/208Y 3P 4W125A M.B.42 SPACESQUARE D NQO
PB-RP480Y/277V 3PH 4W125A M.L.O.SQUARE D NH1B
PB-RL480Y/277V 3PH 4W125A M.L.O.SQUARE D NH1B
PB-RR120/208Y 3P 4W225A M.B.42 SPACE
PB-PR120/208Y 3P 4W100A M.L.O.
12 SPACE120/240VLOAD CENTER
PB-MR120/208Y 3P 4W100A M.L.O.
PB-2RA120/208Y 3P 4W125A M.B.42 SPACESQUARE D NQOW/ SHUNT TRIP CONTACTOR
PB-2R120/208Y 3P 4W125A M.B.42 SPACESQUARE D NQO
PB-3R120/208Y 3P 4W125A M.B.42 SPACESQUARE D NQO
PB-2L480Y/277V 3PH 4W125A M.L.O.SQUARE D NH1B
PB-3L480Y/277V 3PH 4W125A M.L.O.SQUARE D NH1B
PB-4L480Y/277V 3PH 4W125A M.L.O.SQUARE D NH1B
PB-4R120/208Y 3P 4W125A M.B.42 SPACESQUARE D NQO
PB-5L480Y/277V 3PH 4W125A M.L.O.SQUARE D NH1B
PB-5R120/208Y 3P 4W125A M.B.42 SPACESQUARE D NQO
12 SPACE120/240VLOAD CENTER
PB-EM-R208Y/120V 3PH 4W30A M.B.100A BUSSQUARE D
T-EMR9KVA480 X 208Y/120V
PB-EM480Y/277V 3PH 4W30A M.B.100A BUSSQUARE D NH1B
BUILDINGSTEEL
WATERMETER
SWITCHBOARD MSB1,000A MAIN BOLT-LOCFUSED SWITCH480Y/277V 3PH-4WSQUARE DTYPE POWER STYLE SWITCHBOARDLOCATED: RAMP MECHANICAL ROOM
EXISTINGCHILLER
x;CLASS: L,TYPE: KRP-C-SP
GNDS/N
1000A /3
30A/3
125A/3
125A/3
125A/3
125A/3125A/3
125A/3
125A/3
TO NEAREST METALLIC COLD WATER PIPEOR STRUCTURAL STEEL USING MINIMUMNEC SIZE BARE OR GREEN INSULATEDCOPPER CONDUCTOR.
ENCLOSUREBOND
01E4.01
TRANSFORMER BONDING SCHEMATIC
GENERAL ONE-LINE NOTES:
115G
130G
150G
175G
200G
230G
255G
310G
380G
420G
500G
600G
800G
25NG
35NG
50NG
65NG
85NG
1000NG
1200NG
1600NG
2000NG
25G
35G
50G
65G
85G
100G
1000G
1200G
1600G
2000G
115NG
130NG
150NG
175NG
200NG
230NG
255NG
310NG
380NG
420NG
500NG
600NG
800NG
3 PHASE, 3 WIRE WITH GROUND 3 PHASE, 4 WIRE WITH GROUND
TAG TAG
(4)#8 + (1)#10 GRD. IN 1"C
(4)#4 + (1)#8 GRD. IN 1%%130"C
(4)#3 + (1)#8 GRD. IN 1%%130"C
(4)#2 + (1)#6 GRD. IN 1%%129"C
(4)#3/0 + (1)#6 GRD. IN 2%%129"C
(4)#4/0 + (1)#4 GRD. IN 2%%129"C
(3)#8 + (1)#10 GRD. IN %%131"C
(3)#6 + (1)#8 GRD. IN 1"C
(3)#4 + (1)#8 GRD. IN 1%%130"C
(3)#3 + (1)#8 GRD. IN 1%%130"C
(3)#2 + (1)#6 GRD. IN 1%%130"C
(3)#1 + (1)#6 GRD. IN 1%%129"C
(3)#1/0 + (1)#6 GRD. IN 1%%129"C
(4)#12 + (1)#10 GRD. IN %%131"C
(4)#10 + (1)#10 GRD. IN %%131"C
(4)#1 + (1)#6 GRD. IN 2"C
(4)#1/0 + (1)#6 GRD. IN 2"C
(4)#2/0 + (1)#6 GRD. IN 2"C
(3)#12 + (1)#10 GRD. IN %%131"C
(3)#10 + (1)#10 GRD. IN %%131"C
(3)#2/0 + (1)#6 GRD. IN 2"C
(3)#3/0 + (1)#6 GRD. IN 2"C
(3)#4/0 + (1)#4 GRD. IN 2"C
100NG
(4)#6 + (1)#8 GRD. IN 1%%130"C
CONDUIT FILL CONDUIT FILL
2500G 2500NG
(4)#250 KC ML + (1)#4 GRD. IN 2%%129"C
(4)#500 KC ML + (1)#3 GRD. IN 3%%129"C
(4)#600 KC ML + (1)#2 GRD. IN 3%%129"C
2@[(4)#250 KC ML + (1)#2 GRD. IN 2%%129"C]
2@[(4)#600 KC ML + (1)#1/0 GRD. IN 4 "C]
3@[(4)#500 KC ML + (1)#2/0 GRD. IN 3%%129"C]
4@[(4)#600 KC ML + (1)#4/0 GRD. IN 4 "C]
5@[(4)#600 KC ML + (1)#250 KC ML GRD. IN 4 "C]
2@[(4)#350 KC ML + (1)#1 GRD. IN 3"C]
(3)#350 KC ML + (1)#3 GRD. IN 2%%129"C
2@[(3)#250 KC ML + (1)#2 GRD. IN 2%%129"C]
(4)#350 KC ML + (1)#3 GRD. IN 3"C
3@[(4)#600 KC ML + (1)#3/0 GRD. IN 4"C]
(3)#250 KC ML + (1)#4 GRD. IN 2"C
(3)#500 KC ML + (1)#3 GRD. IN 3"C
(3)#600 KC ML + (1)#2 GRD. IN 3"C
2@[(3)#350 KC ML + (1)#1 GRD. IN 2%%129"C]
2@[(3)#500 KC ML + (1)#1/0 GRD. IN 3"C]
3@[(3)#500 KC ML + (1)#2/0 GRD. IN 3"C]
4@[(3)#600 KC ML + (1)#4/0 GRD. IN 4"C]
3@[(3)#600 KC ML + (1)#3/0 GRD. IN 4"C]
5@[(3)#600 KC ML + (1)#250 KC ML GRD. IN 4"C]
6@[(3)#600 KC ML + (1)#250 KC ML GRD. IN 4"C] 6@[(4)#600 KC ML + (1)#250 KC ML GRD. IN 4 "C]
SCALE:
GROUND LUG
N
G
C
B
A
H3H2
H1
X3
X0
X2X1
GBNC
AABCG
A
B
C
G
NEUTRAL-GROUND BONDING CONDUCTOR(SIZED PER NEC ARTICLE 250)
GROUNDING ELECTRODE CONDUCTOR(SIZED PER NEC ARTICLE 250-66)
EQUIPMENT GROUNDING CONDUCTOR(SIZED PER NEC TABLE 250-122)
CONDUITBUSHING
TRANSFORMERENCLOSURE
SECONDARY CONDUIT(FMT OR LIQUID-TITE)
CONDUITBUSHING
PRIMARY CONDUIT(FMT OR LIQUID-TITE)
x;FIRE PUMP40 H.P.
G
NEW PAD MOUNTM.V. SWITCHGEARBY UTILITY COMPANYCONCRETE PAD BY G.C.
NEW SPD DEVICEPER SPECS800A/3
LSIG
E.C. SHALL COORDINATE WITHUTILITY AND FURNISH ANDINSTALL 4" CONDUIT SLEEVE.CABLING AND TERMINATIONS BY UTILITY.
ALL ITEMS SHOWN IN FADED PRINT REPRESENT EXISTING ELECTRICALEQUIPMENT TO REMAIN. ITEMS SHOWN IN BOLD DASHED PRINTREPRESENT EQUIPMENT TO BE DEMOLISHED. ITEMS SHOWN INBOLD PRINT REPRESENT NEW EQUIPMENT TO BE FURNISHED ANDINSTALLED BY THE E.C. (U.O.N.)
1.
x;ATS-EM100A-4P480V
REMOVE EXTG 30AMAIN BREAKER
100A/3
PROVIDE NEW ELECTRONIC TRIP C.B.
INSTALL (1) 1 1/4" CONDUIT W/PULL STRING TO ELEVATORMACHINE ROOMS FOR FUTURECONNECTION TO ELEVATOR
ENCASED IN MIN. 2" OF CONCRETEWHERE RUN THROUGH BUILDING
E.C. TO INSTALL NEWCONCRETE ENCASED ELECTRODE20'-0" MIN. LENGTH REBAR IN NEW SLAB POUR
15A-3P
30A-3P
PB-7P480Y/277V 3PH 4W800A M.L.O.SQUARE D I-LINE
65G T-SBR9KVA480 X 208Y/120VWALL MOUNT
PB-SB-R208Y/120V 3PH 4W30A M.B.100A BUSSQUARE D NQ
FIRE PUMPCONTROLLERW/ INTEGRALTRANSFER SWITCHPROVIDED BY OTHERSWIRED BY E.C.
100NG
CONCRETE PAD BYGENERAL CONTRACTOR
480Y/277V-3P-4W
NEW 150KW GENERATORBY ELECTRICAL CONTRACTOR
35NG 100NG
#3/0
EXTEND EXISTING (3) 3" CONDUITS TO NEW TRANSFORMER LOCATIONINSTALL NEW SETS OF (4) #500 KCMIL BACK TO MAIN SWITCHBOARD - DO NOT SPLICE.
NEW PAD MTD.TRANSFORMER BY UTILITYCONCRETE PAD BY G.C.480Y/277V-3P-4W (SEC)
#3/0 AWGBARE CU GRD.
100NG
30A-3P
100A-3P
100A-3P
x;ATS-EM30A-4P480V
100NG 100NG
25G
35G
800G
100G
NEW CUSTOMERMETERING W/ ETHERNETCOMMUNICATIONS CARDPER SPECS
FEEDER SCHEDULE
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E4.0
5-2420
PHASE 2 – ONE-LINE DIAGRAM
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
10.22.12 OWNER REVIEW
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E5.0
5-2420
PHASE 2 - SCHEDULES
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
10.22.12 OWNER REVIEW
EXTG PANEL TO REMAIN - E.C. TO REMOVE EXTG MAIN BREAKER (REFER TO ONE-LINE). FURNISH NEW CIRCUIT BREAKERS AS REQUIRED.Notes:
Legend:Total... 8 A 8 A 9 A
Total Load: 2275 VA 2296 VA 2471 VAPBEM-41 PBEM-42PBEM-39 PBEM-40PBEM-37 PBEM-38PBEM-35 PBEM-36PBEM-33 PBEM-34PBEM-31 PBEM-32PBEM-29 PBEM-30PBEM-27 PBEM-28PBEM-25 PBEM-26PBEM-23 PBEM-24PBEM-21 PBEM-22PBEM-19 PBEM-20PBEM-17 PBEM-18PBEM-15 PBEM-16PBEM-13 -- -- -- 0 VA PBEM-14PBEM-11 -- -- -- 990 VA PBEM-12PBEM-9 TR-EM 20 A 3 763 VA PBEM-10PBEM-7 EM LTG - 2ND FLOOR 20 A 1 1143... PBEM-8PBEM-5 EM LTG - 5TH FLOOR 20 A 1 590 VA 891 VA 1 20 A EM LTG - 4TH FLOOR PBEM-6PBEM-3 EM LTG - 6TH FLOOR 20 A 1 670 VA 864 VA 1 20 A EM LTG - 3RD FLOOR PBEM-4PBEM-1 EM LTG - RAMP LEVEL 20 A 1 600 VA 532 VA 1 20 A EM LTG - PENTHOUSE PBEM-2
CKT Circuit Description TripPole
s A B CPole
s Trip Circuit Description CKT
Provide with the following:
Enclosure: MCB Rating: 30 AMounting: Wires: 4 Mains Rating: 100 A
Supply From: Phases: 3 Mains Type: MAIN BREAKERLocation: MECHANICAL 003 Volts: 480/277 Wye A.I.C. Rating:
Branch Panel: PB-EM
EXTG PANEL TO REMAIN - E.C. TO FURNISH NEW CIRCUIT BREAKERS AS REQUIREDNotes:
Legend:Total... 7 A 9 A 0 A
Total Load: 763 VA 990 VA 0 VAPBEMR-41 PBEMR-42PBEMR-39 PBEMR-40PBEMR-37 PBEMR-38PBEMR-35 PBEMR-36PBEMR-33 PBEMR-34PBEMR-31 PBEMR-32PBEMR-29 PBEMR-30PBEMR-27 PBEMR-28PBEMR-25 PBEMR-26PBEMR-23 PBEMR-24PBEMR-21 PBEMR-22PBEMR-19 PBEMR-20PBEMR-17 PBEMR-18PBEMR-15 PBEMR-16PBEMR-13 PBEMR-14PBEMR-11 PBEMR-12PBEMR-9 PBEMR-10PBEMR-7 PBEMR-8PBEMR-5 PBEMR-6PBEMR-3 EM LTG - MEZZANINE LEVEL 20 A 1 990 VA PBEMR-4PBEMR-1 EM LTG - PLAZA LEVEL 20 A 1 763 VA PBEMR-2
CKT Circuit Description TripPole
s A B CPole
s Trip Circuit Description CKT
Provide with the following:
Enclosure: MCB Rating:Mounting: Wires: 4 Mains Rating: 30 A
Supply From: TR-EM Phases: 3 Mains Type: MAIN BREAKERLocation: MECHANICAL 003 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: PB-EMR
NEW PANEL FURNISHED AND INSTALLED BY E.C.Notes:
Legend:Total... 2 A 3 A 0 A
Total Load: 360 VA 714 VA 0 VAPBSB-41 PBSB-42PBSB-39 PBSB-40PBSB-37 PBSB-38PBSB-35 PBSB-36PBSB-33 PBSB-34PBSB-31 PBSB-32PBSB-29 PBSB-30PBSB-27 PBSB-28PBSB-25 PBSB-26PBSB-23 PBSB-24PBSB-21 PBSB-22PBSB-19 PBSB-20PBSB-17 PBSB-18PBSB-15 PBSB-16PBSB-13 PBSB-14PBSB-11 PBSB-12PBSB-9 PBSB-10PBSB-7 PBSB-8PBSB-5 -- -- -- 0 VA 0 VA -- -- -- PBSB-6PBSB-3 -- -- -- 714 VA 0 VA -- -- -- PBSB-4PBSB-1 TR-SB 20 A 3 360 VA 0 VA 3 100 A FUTURE - ELEVATOR PBSB-2
CKT Circuit Description TripPole
s A B CPole
s Trip Circuit Description CKT
Provide with the following:
Enclosure: MCB Rating: 250 AMounting: Wires: 4 Mains Rating: 100 A
Supply From: Phases: 3 Mains Type: MAIN LUG ONLYLocation: MECHANICAL 003 Volts: 480/277 Wye A.I.C. Rating:
Branch Panel: PB-SB
NEW PANEL FURNISHED AND INSTALLED BY E.C.Notes:
Legend:Total... 3 A 6 A 0 A
Total Load: 360 VA 714 VA 0 VAPBSBR-41 PBSBR-42PBSBR-39 PBSBR-40PBSBR-37 PBSBR-38PBSBR-35 PBSBR-36PBSBR-33 PBSBR-34PBSBR-31 PBSBR-32PBSBR-29 PBSBR-30PBSBR-27 PBSBR-28PBSBR-25 PBSBR-26PBSBR-23 PBSBR-24PBSBR-21 PBSBR-22PBSBR-19 PBSBR-20PBSBR-17 PBSBR-18PBSBR-15 PBSBR-16PBSBR-13 PBSBR-14PBSBR-11 PBSBR-12PBSBR-9 PBSBR-10PBSBR-7 PBSBR-8PBSBR-5 PBSBR-6PBSBR-3 RECEPTS - ELEVATOR... 20 A 1 714 VA PBSBR-4PBSBR-1 RECEPTS - ELEVATOR PIT,... 20 A 1 360 VA PBSBR-2
CKT Circuit Description TripPole
s A B CPole
s Trip Circuit Description CKT
(5) SPARE 20A-1P CIRCUIT BREAKERSProvide with the following:
Enclosure: MCB Rating: 30 AMounting: Wires: 4 Mains Rating: 100 A
Supply From: TR-SB Phases: 3 Mains Type: MAIN BREAKERLocation: MECHANICAL 003 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: PB-SBR
EXTG PANEL TO REMAIN. E.C. TO FURNISH AND INSTALL NEW CIRCUIT BREAKERS AS INDICATED IN THIS SCHEDULE. PROVIDE BLANK 'FILLERS' ASREQUIRED.
Notes:
Legend:Total Amps: 97 A 92 A 92 ATotal Load: 26859 VA 25359 VA 25359 VA
PBRP-41 PBRP-42PBRP-39 PBRP-40PBRP-37 PBRP-38PBRP-35 PBRP-36PBRP-33 PBRP-34PBRP-31 PBRP-32PBRP-29 PBRP-30PBRP-27 PBRP-28PBRP-25 PBRP-26PBRP-23 PBRP-24PBRP-21 PBRP-22PBRP-19 -- -- -- 110... PBRP-20PBRP-17 -- -- -- 110... 581... -- -- -- PBRP-18PBRP-15 AHU-2 SUPPLY 80 A 3 110... 581... -- -- -- PBRP-16PBRP-13 -- -- -- 387... 581... 3 40 A AHU-1 SUPPLY PBRP-14PBRP-11 -- -- -- 387... 265... -- -- -- PBRP-12PBRP-9 AHU-2 RETURN 25 A 3 387... 265... -- -- -- PBRP-10PBRP-7 -- -- -- 138... 265... 3 20 A AHU-1 RETURN PBRP-8PBRP-5 -- -- -- 138... 558... -- -- -- PBRP-6PBRP-3 P-11, P-12 20 A 3 138... 558... -- -- -- PBRP-4PBRP-1 HEAT TRACE (30mA GFCI) 20 A 1 150... 558... 3 15 A JOCKEY PUMP PBRP-2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Provide with the following: (2) 20A-3P, (2) 60A-3P SPARE CIRCUIT BREAKERS
Enclosure: MCB Rating: 250 AMounting: Wires: 4 Mains Rating: 250 A
Supply From: Phases: 3 Mains Type: MAIN LUG ONLYLocation: MECHANICAL 003 Volts: 480/277 Wye A.I.C. Rating:
Branch Panel: PB-RP
EXTG PANEL TO REMAIN - E.C. TO PROVIDE NEW CIRCUIT BREAKERS AS REQUIRED. UTILIZE EXTG CIRCUIT BREAKERS WHEREVER POSSIBLE.Notes:
Legend:Total... 28 A 28 A 28 ATotal... 3414 VA 3404 VA 3387 VA
PBRR-41 PBRR-42PBRR-39 PBRR-40PBRR-37 PBRR-38PBRR-35 PBRR-36PBRR-33 PBRR-34PBRR-31 PBRR-32PBRR-29 PBRR-30PBRR-27 PBRR-28PBRR-25 PBRR-26PBRR-23 PBRR-24PBRR-21 PBRR-22PBRR-19 PBRR-20PBRR-17 PBRR-18PBRR-15 PBRR-16PBRR-13 PBRR-14PBRR-11 EF-3 20 A 1 1127... 1000... 1 20 A GENERATOR BATT. CHARGER PBRR-12PBRR-9 EF-2, UH-1 20 A 1 1794... 1000... 1 20 A GENERATOR BLOCK HEATER PBRR-10PBRR-7 UH-2, UH-3 20 A 1 1334... 1000... 1 20 A AHU SERVICE RECEPTS & LTS PBRR-8PBRR-5 RECEPTS - MECH. ROOM 20 A 1 540... 720... 1 20 A RECEPTS - MECH. ROOM PBRR-6PBRR-3 EF-1 20 A 1 250 VA 360 VA 1 20 A RECEPTS - FIRE PUMP ROOM PBRR-4PBRR-1 RECEPT - GENERATOR SERVICE 20 A 1 180... 900... 1 20 A RECEPTS - RAMP PBRR-2
CKT Circuit Description TripPoles A B C
Poles Trip Circuit Description CKT
Provide with the following:
Enclosure: MCB Rating:Mounting: Wires: 4 Mains Rating: 225 A
Supply From: TR-PBRR Phases: 3 Mains Type: MAIN BREAKERLocation: MECHANICAL 003 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: PB-RR
FIXTURE SCHEDULETAG LUMINAIRE VOLTAGE BALLAST LAMP
FINISHMOUNTING
DESCRIPTION MANUFACTURER/CATALOG NUMBER QUANTITY TYPE
A x;5,000 LUMEN 2' X 4 ' RECESSED LED ARCHITECTURAL TROFFERWITH STEP DIMMING CAPABILITY
x;CREE: CR24-50L-40K-SLITHONIA: 2RTL4-48L-D49-LP840-BLDOR APPROVED EQUAL
120/277V N/A
x;5,000 LUMEN4000K L.E.D. WHITE
RECESSED IN CEILING
A2/A2EM x;4,000 LUMEN 2' X 4 ' RECESSED LED ARCHITECTURAL TROFFERWITH STEP DIMMING CAPABILITY
x;CREE: CR24-40L-40K-SLITHONIA: 2RTL4-40L-D40-LP840-BLDOR APPROVED EQUAL
120/277V N/A
x;4,000 LUMEN4000K L.E.D. WHITE
RECESSED IN CEILING
A3/A3EM 2' X 4' FLUORESCENT RECESSED VOLUMETRIC TROFFER
x;LITHONIA: 2RT8S-232-MVOLT-GEB10PS-L835HT8COLUMBIA: EPC24-232G-SH-EPU-FOH841METALUX: 2AC-232-UNV-HR81OR APPROVED EQUAL
120/277Vx;ELECTRONIC
PROGRAM RAPIDSTART <10% THD
2
x;SYLVANIA F32W T84100K, 85+ CRI
3100 LUMEN, LONG LIFE WHITE
RECESSED IN CEILING
B/BEM 2' X 2' RECESSED FLUORESCENT VOLUMETRIC TROFFER
x;LITHONIA: 2RT8S-217-MVOLT-GEB10PS-L835HT8COLUMBIA: EPC22-217G-SH-EPU-FOH841METALUX: 2AC-217-UNV-HR81-UOR APPROVED EQUAL
120/277Vx;ELECTRONIC
PROGRAM RAPIDSTART <10% THD
2
x;SYLVANIA F17W T84100K, 85+ CRI
1400 LUMEN, LONG LIFE WHITE
RECESSED IN CEILING
C WALL MOUNT FLUORESCENT
x;LITHONIA: W-2-32-MVOLT-GEB10RS-MWCOLUMBIA: WPM4-232-EPUMETALUX: BAU-232-UNV-HR81OR APPROVED EQUAL
120/277Vx;ELECTRONIC
PROGRAM RAPIDSTART <10% THD
2
x;SYLVANIA F32W T84100K, 85+ CRI
3100 LUMEN, LONG LIFE WHITE
x;WALL MOUNT OVER EXTGJ-BOX
D/DEM 1,500 LUMEN WIDE DISTRIBUTION DOWNLIGHT
x;PORTFOLIO: LD6-15-D010-ERW6-835-6LWI-HFOCAL POINT: FL4D-13LED-L4-RO-DN-CD-NPGOTHAM: ALED-41/14-6AR-MVOLTOR APPROVED EQUAL
120/277V N/A
4100K L.E.D. HAZE REFLECTOR
RECESSED IN CEILING
D2/D2EM 1,000 LUMEN WIDE DISTRIBUTION DOWNLIGHT
x;PORTFOLIO: LD6-10-D010-ERW6-835-6LWI-HFOCAL POINT: FL4D-11LED-L4-RO-DN-CD-NPGOTHAM: ALED-41/1000-6AR-MVOLTOR APPROVED EQUAL
120/277V N/A
4100K L.E.D. HAZE REFLECTOR
RECESSED IN CEILING
F 2-LAMP FLUORESCENT WRAP
x;LITHONIA: ST8-232-MVOLT-GEB10RSLIGHTING ALTERNATIVES: TRI-.75X4-2L-T832-PUNVFAIL-SAFE: HVL8-232-UNV-O-ER81-SOR APPROVED EQUAL
120/277Vx;ELECTRONIC
PROGRAM RAPIDSTART <10% THD
2
x;SYLVANIA F32W T84100K, 85+ CRI
3100 LUMEN, LONG LIFE WHITE
x;SURFACE MOUNT TOCEILING
G/GEMx;1 ' X 4' SURFACE MOUNT VANDAL RESISTANT FLUORESCENT W/INTEGRAL OCCUPANCY SENSOR AND (2) BALLASTS - (1) FOR NIGHTLIGHT AND (1) FOR OCCUPANCY SENSOR CONTROLLED LAMP
x;TERON: TRN48232E-277E-TW-MS2BLITHONIA: WT8-232-MVOLT-BSNP-NESPDT7-DIM50LUMINAIRE: TSL94-2F32T8-2B-120/277(PRS)-OP-WHTOR APPROVED EQUAL
120/277Vx;ELECTRONIC
PROGRAM RAPIDSTART <10% THD
2
x;SYLVANIA F32W T84100K, 85+ CRI
3100 LUMEN, LONG LIFE WHITE
x;SURFACE MOUNT TOCEILING
H/HEM FLUORESCENT INDUSTRIAL TOURRETT W/ 10% UPLIGHT
x;LITHONIA: 'AF' SERIESCOLUMBIA: KL4-232-U-EPU-KHCMETALUX: DMFN-232-UNV-ER81OR APPROVED EQUAL
120/277Vx;ELECTRONIC
PROGRAM RAPIDSTART <10% THD
2
x;SYLVANIA F32W T84100K, 85+ CRI
3100 LUMEN, LONG LIFE WHITE
x;CHAIN HUNG APPROX. 10'-0"AFF OR AS HIGH AS
POSSIBLE - CORRDINATELOCATIONS W/ DUCTWORK
J/JEM 2' X 2' RECESSED FLUORESCENT LENSED TROFFERx;LITHONIA: 2SP8-G-217-12125-MVOLT-GEBPRSCOLUMBIA: ST822-217-G-FS-A12.125-EP-U-PAFMETALUX: 2GC8-217-A125-UNV-HER81-PAF
120/277Vx;ELECTRONIC
PROGRAM RAPIDSTART <10% THD
2
x;SYLVANIA F17W T84100K, 85+ CRI
1400 LUMEN, LONG LIFE WHITE
RECESSED IN CEILING
K 4'-0" UNDERCABINET LIGHTx;COLOR KENETICS: 'eW PROFILE POWERCORE' SERIESNORA: 'LEDUC' SERIESOR APPROVED EQUAL
120/277V N/A4100K L.E.D. WHITE
SURFACE MOUNT]
SX' / SXEM
x;SLIDING ADJUSTABLE STAGGERED STIP LIGHT. PROVIDE LENGTHCONFIGURATIONS BASED ON TOAL LENGTH OF COVE (REFER TODRAWINGS). LAYOUT SHALL LIMIT LAMP TYPES TO 3' -0" AND 4'-0"LENGTHS AS BEST POSSIBLE
x;BIRCHWOOD: WP-T8-1ST-SAS-120/277-EB-XX' -HRWOR APPROVED EQUAL 120/277V
x;ELECTRONICPROGRAM RAPIDSTART <10% THD
1
x;SYLVANIA F25W/F32WT8
4100K, 85+ CRILONG LIFE WHITE
SURFACE MOUNT IN COVE
X x;AC ONLY OPERATION DIE-CAST ALUMINUM EXIT SIGN, SIDES,ARROWS AND MOUNTING AS SHOWN ON DRAWINGS.
x;LITHONIA: 'LE' SERIESSURE-LITES: 'CX' SERIESDUAL-LITE: 'SE' SERIESOR APPROVED EQUAL
120/277V N/A
L.E.D.x;BRUSHED ALUMINUM WITH
RED LETTERING
x;CEILING / WALL MOUNTED -REFER TO DRAWINGS.
SA x;RECESSED CANOPY LED FIXTURE WITH IC RATING, STEP DIMMINGCAPABILITY AND INTEGRAL OCCUPANCY SENSOR
x;CREE: SFT-304-5S-RM-04-D-UL-WH-350-IC-40K-MLOR APPROVED EQUAL 120/277V N/A
4100K L.E.D. WHITE
x;RECESSED IN INSULATEDSUSPENDED CEILING
SA2 x;RECESSED CANOPY LED FIXTURE WITH IC RATING, STEP DIMMINGCAPABILITY AND INTEGRAL OCCUPANCY SENSOR
x;CREE: SFT-304-PS-RM-04-D-UL-WH-350-IC-40K-MLOR APPROVED EQUAL 120/277V N/A
4100K L.E.D. WHITE
x;RECESSED IN INSULATEDSUSPENDED CEILING
SB x;SURFACE MOUNT CANOPY LED FIXTURE WITH INTEGRALOCCUPANCY SENSOR AND STEP DIM CAPABILITY
x;CREE: CAN-EDG-5S-DM-04-D-UL-WH-350-4OK-MLMCGRAW-EDISON:VPL-B02-LED-E1-SQ-WH-LCF-OSX-MOD(MULTI-LEVEL)OR APPROVED EQUAL
120/277V N/A
4100K L.E.D. WHITE
x;SURFACE MOUNT OVEREXTG J-BOX
SC x;FLAGPOLE FLOODLIGHT WITH SPOT DISTRIBUTION, AND DUALTENON MOUNTING AND FULL CUT-OFF VISOR
x;LITHONIA: DSXF3LED-8-A530/40K-NSP-MVOLT-THK-SF-FV-DDBXDBEACON: AL-U-72NB-170-2X2-UNV-SF3-FL-BZOR APPROVED EQUAL
120/277V N/A
4100K L.E.D. BRONZE
x;DOUBLE TENON(BULL-HORN) MOUNT -REFER TO DETAIL ON
SHEET E7.0
SD x;EXTERIOR LED WALLMOUNT FIXTURE WITH TYPE 2 OPTICS ANDBACK LIGHT CONTROL
x;MCGRAW-EDISON: IST-B01-LED-E1-BL2-BZ-LCFHUBBELL: TRP-40L8-5K-WT-BZ (4000K)LITHONIA: WSTLED-1-10A700/40K-SR2-MVOLT-DDBXOR APPROVED EQUAL
120/277V N/A
4100K L.E.D. BRONZE
x;SURFACE MOUNT OVEREXTG J-BOX
SF x;EXTERIOR LED WALLMOUNT FIXTURE WITH TYPE 4 OPTICS ANDBACK LIGHT CONTROL
x;MCGRAW-EDISON: IST-B01-LED-E1-BL4-BZ-LCFLITHONIA: WSTLED-1-10A700/40K-SR4-MVOLT-DDBXOR APPROVED EQUAL
120/277V N/A4100K L.E.D. BRONZE
x;SURFACE MOUNT OVEREXTG J-BOX
SG x;EXTERIOR 2' -0" VANDAL RESISTANT ADA COMPLIANT LEDWALLMOUNT FIXTURE
x;KENALL: MLA826-PAN-PP-DB-1940KLUMINAIRE: VPF2-14W HP-4000K-120/277-OP-BRZ-WET-ST/SCOR APPROVED EQUAL
120/277V N/A
4100K L.E.D. BRONZE
x;SURFACE MOUNTVERTICALLY OVER EXTG
J-BOX
SG2 EXTERIOR 4'-0" VANDAL RESISTANT LED WALLMOUNT FIXTUREx;KENALL: MLAS850-PAN-PP-MW-32L40K277VLUMINAIRE: VPF4-128W HP-4000K-120/277-OP-WHT-WET-ST/SCOR APPROVED EQUAL
120/277V N/A
4100K L.E.D. WHITE
x;SURFACE MOUNTHORIZONTALLY AS HIGH AS
POSSIBLE
SH1 EXTERIOR 2,000 LUMEN LED DOWNLIGHT - RETROFIT IN SOFFIT x;GOTHAM: ICO-40/20-6AR-LD-20-MVOLT-RFD-124579OR APPROVED EQUAL 120/277V N/A
4100K L.E.D. BRONZE
x;RETROFIT IN EXISTING 10.5"X 12" CYLINDRICAL HOLE INSOFFIT - CONTRACTOR TO
PROVIDE HARD DIMENTIONS
SH2 EXTERIOR 4,000 LUMEN LED DOWNLIGHT - RETROFIT IN SOFFIT x;GOTHAM: ICO-40/40-6AR-LD-20-MVOLT-RFD-124579OR APPROVED EQUAL 120/277V N/A
4100K L.E.D. BRONZE
x;RETROFIT IN EXISTING 10.5"X 12" CYLINDRICAL HOLE INSOFFIT - CONTRACTOR TO
PROVIDE HARD DIMENTIONS
GENERAL NOTES:1 MODEL NUMBERS GIVEN IN THIS SCHEDULE MAY NOT INCLUDE ALL REQUIRED OPTIONS AND ACCESSORIES TO MEET THE REQUIREMENTS OF THE DESCRIPTION AND SPECIFICATIONS.
2 PROVIDE ALL NECESSARY MOUNTING HARDWARE FOR EACH FIXTURE TYPE
3 PROVIDE 277 X 120 STEP DOWN TRANSFORMERS FOR ALL FIXTURE TYPES REQUIREING 120V CONNECTION ONLY
4 UNLESS OTHERWISE NOTED ALL FINISHES SHALL BE CHOSEN FROM THE STANDARD MANUFACTURER'S COLORS
5 ALL FLUORESCENT LAMP CCT SHALL BE 4100K UNLESS OTHERWISE NOTED
EQUIPMENT CONNECTION SCHEDULE
FED FROM TAG DESCRIPTIONLOAD
VOLT Ø
x;DISCONNECT /CONTROLLER Ampacity WIRING RACEWAY
x;SEENOTES
VALUE UNITS SIZE POLE TYPE NO SIZE GND TYPE SIZE
x;PB
-RP
(RAM
P)
AHU-1 EXHAUST FAN (2) 3HP FANS 6 HP 460 3 VFD BY CONTROLS CONTRCTOR, INSTALLED BY E.C 20 3 THWN 3 12 12 EMT 1/2 4AHU-1 SUPPLY FAN (2) 7.5 HP FANS 15 HP 460 3 VFD BY CONTROLS CONTRCTOR, INSTALLED BY E.C 40 3 THWN 3 8 10 EMT 3/4 4
AHU-2 EXHAUST FAN (2) 5HP FANS 10 HP 460 3 VFD BY CONTROLS CONTRCTOR, INSTALLED BY E.C 25 3 THWN 3 10 10 EMT 1/2 4
AHU-2 SUPPLY FAN (2) 15 HP FANS 30 HP 460 3 VFD BY CONTROLS CONTRCTOR, INSTALLED BY E.C 80 3 THWN 3 4 8 EMT 1 4, 5P-11 AHU-1 HEATING COIL CIRC. PUMP 1/2 HP 460 3 F.V.N.R. BY E.C. 2 3 THWN 3 12 12 EMT 1/2 2P-12 AHU-2 HEATING COIL CIRC. PUMP 1 1/2 HP 460 3 F.V.N.R. BY E.C. 5.6 3 THWN 3 12 12 EMT 1/2 2
x;PB
-7P
(PEN
THO
USE)
AHU-3 EXHAUST FAN (2) 7.5 HP FANS 15 HP 460 3 VFD BY CONTROLS CONTRCTOR, INSTALLED BY E.C 40 3 THWN 3 8 10 EMT 3/4 4
AHU-3 SUPPLY FAN (2) 25 HP FANS 50 HP 460 3 VFD BY CONTROLS CONTRCTOR, INSTALLED BY E.C 100 3 THWN 3 3 8 EMT 1 4, 5
CHLR-1 AIR COOLED OUTDOOR CHILLER 140 A 460 3 NEMA 3R DISCONNECT BY E.C. 175 3 THWN 3 2/0 6 EMT 1 1/2 1
CHLR-2 AIR COOLED OUTDOOR CHILLER 140 A 460 3 NEMA 3R DISCONNECT BY E.C. 175 3 THWN 3 2/0 6 EMT 1 1/2 1
EL-V EAST ELEVATOR (EXISTING) 30 HP 460 3 EXTG CONTROLS TO REMAIN 70 3 THWN 3 4 8 EMT 1
EL-2 WEST ELEVATOR (EXISTING) 30 HP 460 3 EXTG CONTROLS TO REMAIN 70 3 THWN 3 4 8 EMT 1
TR-7R XFMR SERVING PANELBOARD PB-7R (EXISTING) 30 KVA 460 3 EXTG CIRCUIT BREAKER TO REMAIN 50 3 THWN 3 8 10 EMT 3/4
P-1 HEATING / HOT WATER PUMP (PRIME) 5 HP 460 3 VFD BY CONTROLS CONTRCTOR, INSTALLED BY E.C 15 3 THWN 3 12 12 EMT 1/2
P-2 HEATING / HOT WATER PUMP (STANDBY) 5 HP 460 3 VFD BY CONTROLS CONTRCTOR, INSTALLED BY E.C 15 3 THWN 3 12 12 EMT 1/2
P-3 BOILER CIRC. PUMP 2 HP 460 3 F.V.N.R. BY E.C. 6.25 3 THWN 3 12 12 EMT 1/2 2P-4 BOILER CIRC. PUMP 2 HP 460 3 F.V.N.R. BY E.C. 6.25 3 THWN 3 12 12 EMT 1/2 2P-5 HOT WATER FILTER PUMP 3 HP 460 3 F.V.N.R. BY E.C. 8 3 THWN 3 12 12 EMT 1/2 2
P-6 VAV HOT WATER CIR. PUMP 10 HP 460 3 VFD BY CONTROLS CONTRCTOR, INSTALLED BY E.C 25 3 THWN 3 10 10 EMT 1/2
P-7 TERMINAL HEATING CIRC. PUMP 1 1/2 HP 460 3 VFD BY CONTROLS CONTRCTOR, INSTALLED BY E.C 5.6 3 THWN 3 12 12 EMT 1/2 2
P-8 CHILLED WATER PUMP (PRIME) 10 HP 460 3 VFD BY CONTROLS CONTRCTOR, INSTALLED BY E.C 25 3 THWN 3 10 10 EMT 1/2
P-9 CHILLED WATER PUMP (STANDBY) 10 HP 460 3 VFD BY CONTROLS CONTRCTOR, INSTALLED BY E.C 25 3 THWN 3 10 10 EMT 1/2
P-10 CHILLED WATER FILTER PUMP 3 HP 460 3 F.V.N.R. BY E.C. 8 3 THWN 3 12 12 EMT 1/2 2
P-14 HEAT RECOVERY PUMP 1 1/2 HP 460 3 VFD BY CONTROLS CONTRCTOR, INSTALLED BY E.C 5.6 3 THWN 3 12 12 EMT 1/2 2P-13 AHU-3 HEATING COIL CIRC. PUMP 1 HP 460 3 F.V.N.R. BY E.C. 4 3 THWN 3 12 12 EMT 1/2 2P-15 HEAT RECOVERY PUMP 1 1/2 HP 460 3 VFD BY CONTROLS CONTRCTOR, INSTALLED BY E.C 5.6 3 THWN 3 12 12 EMT 1/2 2
EF-4 BUILDING EX FAN 2 HP 460 3 F.V.N.R. BY E.C. 6.25 3 THWN 3 12 12 EMT 1/2 2
EF-5 BUILDING EX FAN 2 HP 460 3 F.V.N.R. BY E.C. 6.25 3 THWN 3 12 12 EMT 1/2 2
x;LO
CAL
208Y
/120
VRE
CEPT
ACLE
PANE
L
B-1 & B-2 BOILERS (GAS FIRED) 1/4 HP 115 1 DISCONNECTS, E-STOP AND SHUNT TRIP C.B. BY E.C. 9 1 THWN 2 12 12 EMT 1/2 2EF-1 RAMP MECH. ROOM EX FAN 1/2 HP 115 1 DISCONNECT BY EQM 20 1 THWN 2 12 12 EMT 1/2EF-2 RAMP FIRE PROTECTION ROOM EX FAN 1/4 HP 115 1 DISCONNECT BY EQM 9 1 THWN 2 12 12 EMT 1/2 2EF-3 RAMP STORAGE ROOM EX FAN 1/2 HP 115 1 DISCONNECT BY EQM 20 1 THWN 2 12 12 EMT 1/2EF-6 PENTHOUSE MECH EX FAN 1/4 HP 115 1 DISCONNECT BY EQM, SSY BY E.C. 9 1 THWN 2 12 12 EMT 1/2 2P-11 AHU-1 HEATING COIL CIRC. PUMP 1/2 HP 115 1 F.V.N.R. BY E.C. 20 1 THWN 2 12 12 EMT 1/2UH-1 RAMP MECH. ROOM UNIT HEATER 1/4 HP 115 1 DISCONNECT BY EQM, SSY BY E.C. 9 1 THWN 2 12 12 EMT 1/2 2UH-2 FIRE PUMP ROOM UNIT HEATER 1/4 HP 115 1 DISCONNECT BY EQM, SSY BY E.C. 9 1 THWN 2 12 12 EMT 1/2 2UH-3 STORAGE ROOM UNIT HEATER 1/4 HP 115 1 DISCONNECT BY EQM, SSY BY E.C. 9 1 THWN 2 12 12 EMT 1/2 2UH-4 PENTHOUSE UNIT HEATER 1/4 HP 115 1 DISCONNECT BY EQM, SSY BY E.C. 9 1 THWN 2 12 12 EMT 1/2 2
NOTES:
1. SINGLE POINT CONNECTION TO ROOF TOP EQUIPMENT.
2. MULTIPLE MOTORS / EQUIPMENT FED FROM SAME BRANCH CIRCUIT. INSTALLATION SHALL COMPLY WITH NEC TAP RULES. REFER TO PANELBOARD SCHEDULES FOR MORE INFORMATION. AMPACITY SIZE SHOWN IS REFERING TO THE RECOMMENDED FUSE SIZE IN THE CORRESPONDING DISCONNECT / CONTROLLER
3. PROVIDE W/ SHUNT TRIP CIRCUIT BREAKER AND HEAVY DUTY LOCKABLE DISCONNECT SWITCH FOR EMERGENCY BOILER SHUT-DOWN
4. MULTIPLE MOTORS CONTROLLED FROM A SINGLE DRIVE SHALL BE PROVIDED WITH A LOAD SIDE REACTOR
5 VFD SHALL BE PROVIDED WITH A LINE SIDE REACTOR FOR LOADS OVER 20 HP
CONTROLLER DISCONNECT KEY: MCC VFD = VFD IN MCC, BY EQM=SUPPLIED BY EQUIPMENT MANUFACTURER, BY EC=PROVIDED AND INSTALLED BY THE ELECTRICAL CONTRACTOR, F.V.N.R. = FULL VOLTAGE NON-REVERSING MOTOR STARTER
CONDUIT KEY: RMC: RIGID STEEL CONDUIT, EMT= ELECTRICAL METALLIC TUBING, SST=STAINLESS STEEL TUBING, LFMC=LIQUID TIGHT FLEXIBLE METALIC CONDUIT
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E5.1
5-2420
PHASE 2 - SCHEDULES
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
NEW PANEL FURNISHED AND INSTALLED BY E.C.Notes:
Legend:Total Amps: 488 A 491 A 491 ATotal Load: 135354 VA 135994 VA 135888 VA
PB7P-71 PB7P-72PB7P-69 PB7P-70PB7P-67 PB7P-68PB7P-65 PB7P-66PB7P-63 PB7P-64PB7P-61 PB7P-62PB7P-59 PB7P-60PB7P-57 PB7P-58PB7P-55 PB7P-56PB7P-53 PB7P-54PB7P-51 PB7P-52PB7P-49 PB7P-50PB7P-47 -- -- -- 37181... PB7P-48PB7P-45 -- -- -- 37181... PB7P-46PB7P-43 CHILLER-2 175 A 3 37181... PB7P-44PB7P-41 -- -- -- 18822... 37181... -- -- -- PB7P-42PB7P-39 -- -- -- 18822... 37181... -- -- -- PB7P-40PB7P-37 AHU-3 SUPPLY 100 A 3 18822... 37181... 3 175 A CHILLER-1 PB7P-38PB7P-35 -- -- -- 5577... 6090... -- -- -- PB7P-36PB7P-33 -- -- -- 5577... 6090... -- -- -- PB7P-34PB7P-31 ELEVATOR (EXTG) 70 A 3 5577... 6090... 3 40 A AHU-3 RETURN PB7P-32PB7P-29 -- -- -- 3875... 5577... -- -- -- PB7P-30PB7P-27 -- -- -- 3875... 5577... -- -- -- PB7P-28PB7P-25 P-9 25 A 3 3875... 5577... 3 70 A ELEVATOR (EXTG) PB7P-26PB7P-23 -- -- -- 3875... 3875... -- -- -- PB7P-24PB7P-21 -- -- -- 3875... 3875... -- -- -- PB7P-22PB7P-19 P-6 25 A 3 3875... 3875... 3 25 A P-8 PB7P-20PB7P-17 -- -- -- 2740... 3211... -- -- -- PB7P-18PB7P-15 -- -- -- 2740... 3211... -- -- -- PB7P-16PB7P-13 P-7, P-10, P-13, P-14, P-15 30 A 3 2740... 3211... 3 20 A P-3, P-4, P-5 PB7P-14PB7P-11 -- -- -- 2104... 2104... -- -- -- PB7P-12PB7P-9 -- -- -- 2104... 2104... -- -- -- PB7P-10PB7P-7 P-1 20 A 3 2104... 2104... 3 20 A P-2 PB7P-8PB7P-5 -- -- -- 1794... 1882... -- -- -- PB7P-6PB7P-3 -- -- -- 1900... 1882... -- -- -- PB7P-4PB7P-1 TR-7R 50 A 3 1260... 1882... 3 20 A EF-4, EF-5 PB7P-2
CKT Circuit Description Trip PolesA B C
Poles Trip Circuit Description CKT
(2) 100A-3P, (2) 60A-3P, (2) 20A-3P SPARE CIRCUIT BREAKERSProvide with the following:
Enclosure: NEMA 1 MCB Rating: 800 AMounting: Wires: 3 Mains Rating: 800 A
Supply From: Phases: 3 Mains Type: MAIN LUG ONLYLocation: PENTHOUSE 702 Volts: 480 Delta A.I.C. Rating:
Branch Panel: PB-7P
OS3
4
LC
M
SF
SH
TSFSE
M
V
D
AV
V
AV
1/20
1/20
GFCI
MM
ATS
OSD
RED
WHITE
YELLOW
BLUE
NON-EMERGENCY POWER
EMERGENCY POWER
EMERGENCY NEUTRAL
x;CONNECTION SCHEMATICS ARE SHOWN FOR REFERENCE ONLY.VERIFY WITH MANUFACTURER'S DIAGRAMS PRIOR TO INSTALLATION.
EMERGENCY LIGHT(S) WHITE/BLUE
NORMAL LIGHT(S)NON-EMERGENCY NEUTRAL
SWITCHING MEANS
2.
NOTES:1.
x;TYPICAL WIRING. VERIFY WITHEQUIPMENT MANUFACTURER.x;VERIFY VOLTAGE (120 OR 277)AT ALL REQUIRED LOCATIONSPRIOR TO ORDERING.
ORANGE-277V (BLACK -120V)EM
CONCRETE REBAR
x;CHAMFER EDGE AT45 DEGREES
SQUARE POLE
GLARE SHIELD
3'-0"
1'-6"
x;SONOTUBE FORMEDCONCRETE BASE
x;1" PVC SCHED. 40UNLESS NOTED.
2'-0"
x;4'-0" DOUBLE TENON(BULLHORN) MOUNT
R
R
x;EMERGENCY LIGHTINGPANEL PB-EM
x;NORMAL LIGHTINGPANEL PB-RL
LC-1
LC-2
OPERATION:
SPARE
SPARE
SPARE
SPARE
N.O.
N.C.
AUX.CONTACTS
N.O.
N.C.
AUX.CONTACTS
FROM BMS
RIB RELAY(0R EQUAL)BY TEMP. CONTROLS
FROM BMS
RIB RELAY(0R EQUAL)BY TEMP. CONTROLS
RAMP LEVEL EMERGENCY LIGHTS
FLAGPOLE LIGHTS
RAMP LEVEL EM & FLAGPOLE LTS
RAMP PARKING LIGHTS
WALK WAY BOLLARDS
PARKING AREA LTS
LC-1: DUSK TO DAWN OR WHEN BMS PHOTO-EYE FALLS BELOW 1 FC
LC-2: PROGRAMMED SCHEDULED PER OWNER DIRECTION
x;277V, 30A, 4 POLE ELECTRICALLY HELD CONTACTORWITH 277V COIL, HAND OFF AUTO SELECTOR SWITCHRED LED PILOT LIGHT IN A NEMA 1 ENCLOSURE.PROVIDE ENGRAVED NAMEPLATE INDICATING FUNCTION.
x;277V, 30A, 4 POLE ELECTRICALLY HELD CONTACTORWITH 277V COIL, HAND OFF AUTO SELECTOR SWITCHRED LED PILOT LIGHT IN A NEMA 1 ENCLOSURE.PROVIDE ENGRAVED NAMEPLATE INDICATING FUNCTION.
HAND
AUTO
OFF
HAND
AUTO
OFF
EM
NEUTRAL
NEUTRAL
DS
S S
BV
F F
S SS
A/Vx;HORN/STROBE& VISUAL ONLYDEVICES.SEE SPECS.
x;ALL WATER FLOW VALVES & TAMPERSWITCHES REQUIRED FOR CODE. REVIEWMECHANICAL DRAWINGS AND COORDINATEWITH M.C. IN FIELD.
x;NAC PANELS.SEE SPECS.
x;PROVIDE SMOKE DETECTORFOR EACH PANEL LOCATION
M
H
ALL CONTROL &SIGNAL WIRINGBY FIRE ALARMCONTRACTOR.
M
MAGNETICDOOR HOLDSEE SPECS.
AHUFAN
DUCT DETECTOR &MOTOR SHUT-DOWNBY F.A. CONT'R.SEE SPECS.
HEAT DETECTORSEE SPEC'S.
MANUAL PULLSTATIONS,SEE SPECS.
ROOM SMOKEDETECTORS,SEE SPEC'S.
EXTERIOR, WALLMOUNTED, ALARMBELL, SEE SPEC'S.
120V POWER BYELECTRICAL CONT'RCONN. TO F.A.PANEL
REMOTEANNUNCIATORSSEE SPEC'S.
CONDUIT & BOXES INTHE WALL SHALL BEPROVIDED BY E.C..CONDUIT TO RUN TOABOVE ACCESSIBLECEILING AND CONTAINPULL WIRE.COORDINATE BETWEENFIRE ALARM CONT'RAND ELECT. CONT'R.
FIRE FLYDOOR RELEASE
REQUIRED.
USE WHENFUSIBLE LINKSHUTTERS ARE
120V
x;FOR DOOR HOLDOPEN MAGNETS.
DEDICATED PHONE LINES
x;INTELLIGENTADDRESSABLEFIRE ALARMPANEL. SEESPEC'S
x;SMOKE DETECTORSWITH RELAY BASES
TO ADDITIONAL SENSORSPER DRAWINGS
x;CONNECTION SCHEMATICS ARE SHOWN FOR REFERENCE ONLY.VERIFY WITH MANUFACTURER'S DIAGRAMS PRIOR TO INSTALLATION.
Ylw
Blk
Brn
Hot
Neutral
Blk/Brn
Wht
SwitchOff
Load
PowerPack
*
BluRed
Control Output
Common
+24VDC
OUTPUT
+24 VDC
COMMON
CONTROL
OCCUPANCYSENSOR
Line Voltage Wiring
Provide Cover LabledWith Type of Lighting Controlledi.e. "Corridor Ltg", "Exterior Ltg", etc.
Low Voltage Wiring
LoadSwitch
LocalOff
Junction Box
Local
Power Pack / Relay
EMERGENCY LIGHT
LIGHTING SYMBOLOGY
POWER SYMBOLOGY FIRE ALARM SYMBOLOGY
2' X 4' RECESSED LIGHT FIXTURE
2' X 4' SURFACE MOUNT LIGHT FIXTURE
1' X 4' RECESSED LIGHT FIXTURE
1' X 4' SURFACE MOUNT LIGHT FIXTURE
2' X 2' RECESSED LIGHT FIXTURE
2' X 2' SURFACE MOUNT LIGHT FIXTURE
WALL MOUNT LIGHT FIXTURE
STRIP LIGHT OR UNDERCABINET LIGHT FIXTURE
KNUCKLE MOUNTED FLOOD LIGHT FIXTURE
BOLLARD LIGHT FIXTURE
EXIT LIGHT FIXTURE - ARROWS, MOUNTING, ANDNUMBER OF FACES AS SHOWN ON DRAWINGS
EMERGENCY BATTERY BACK-UP LIGHT FIXTURE ("FROG-EYE")
EMERGENCY / NIGHT LIGHT
N.L.
RECESSED DOWNLIGHT - REFER TO FIXTURE SCHEDULE FOR DIAMETER
WALL SWITCH OCCUPANCY SENSOR - LOCATED 44" AFFTO BOTTOM OF THE DEVICE BOX
DUAL LEVEL WALL SWITCH OCCUPANCY SENSOR - LOCATED44" AFF TO THE BOTTOM OF THE DEVICE BOX
SINGLE POLE LIGHT SWITCH - LOCATED 44" AFF TO THE BOTTOMOF THE DEVICE BOX.
THREE-WAY LIGHT SWITCH - LOCATED 44" AFF TO THE BOTTOMOF THE DEVICE BOX.
FOUR-WAY LIGHT SWITCH - LOCATED 44" AFF TO THE BOTTOMEOF THE DEVICE BOX.
LIGHTING CONTACTOR - REFER TO DRAWINGS FOR SIZE AND TYPE
DUAL TECHNOLOGY CEILING MOUNTED OCCUPANCY SENSOR WITH360 DEGREE COVERAGE PATTERN - REFER TO SPECIFICATIONS
DUAL TECHNOLOGY CEILING MOUNTED OCCUPANCY SENSOR WITH180 DEGREE COVERAGE PATTERN - REFER TO SPECIFICATIONS
ULTRASONIC TECHNOLOGY CEILING MOUNTED OCCUPANCY SENSOR - REFER TO SPECIFICATIONS
2
3
HEAVY DUTY IN-LINE DISCONNECT SWITCH
HEAVY DUTY IN-LINE FUSED DISCONNECT SWITCH
HEAVY DUTY IN-LINE COMBINATION MOTOR STARTER / DISCONNECT
THREE PHASE MOTOR (1/20 HP)
SINGLE PHASE MOTOR (1/20 HP)
RECEPTACLE PANELBOARD
LIGHTING PANELBOARD
DRY TYPE TRANSFORMER
SINGLE RECEPTACLE - LOCATED 16" AFF TO BOTTOM OF THEDEVICE BOX
QUADRAPLEX RECEPTACLE - LOCATED 16" AFF TO THE BOTTOM OFTHE DEVICE BOX
MULTI-PHASE RECEPTACLE - TYPE AS REQUIRED. MOUNT AT 16" AFF TOTHE BOTTOM OF THE DEVICE BOX UNLESS OTHERWISE NOTED
DUPLEX RECEPTACLE - LOCATED 16" AFF TO THE BOTTOM OFTHE DEVICE BOX
GROUND FAULT CIRCUIT INTERUPTER RECEPTACLE - LOCATED 16" AFFTO THE BOTTOM OF THE DEVICE BOX
GENERATOR AUTOMATIC TRANSFER SWITCH - TYPE AS REQUIRED
EMERGENCY PUSH-BUTTON STATION - LOCATED 44" TO THEBOTTOM OF THE DEVICE BOX
PB-XR
PB-XL
FIRE ALARM ANNUNCIATOR PANEL
F.A.C.P.FIRE ALARM CONTROL PANEL
MANUAL PULL STATION
WALL MOUNTED VISUAL NOTIFICATION DEVICE. CANDELA RATINGS SHALL BE DETERMINEDBY QUALIFIED FIRE ALARM CONTRACTOR TO MEET CODE COMPLIANCE.
WALL MOUNTED SPEAKER / STROBE NOTIFICATION DEVICE. CANDELA RATINGS SHALL BE DETERMINEDBY QUALIFIED FIRE ALARM CONTRACTOR TO MEET CODE COMPLIANCE.
CEILING MOUNTED VISUAL NOTIFICATION DEVICE. CANDELA RATINGS SHALL BE DETERMINEDBY QUALIFIED FIRE ALARM CONTRACTOR TO MEET CODE COMPLIANCE.
CEILING MOUNTED SPEAKER / STROBE NOTIFICATION DEVICE. CANDELA RATINGS SHALL BE DETERMINEDBY QUALIFIED FIRE ALARM CONTRACTOR TO MEET CODE COMPLIANCE.
CEILING MOUNT SMOKE DETECTOR
DUCT SMOKE DETECTOR
MAGNETIC DOOR HOLD
CEILING MOUNTED HEAT DETECTOR
TAMPER SWITCH
FLOW SWITCH
MOTORIZED SMOKE DAMPER
F.A.A.P.
FPFIREMAN'S PHONE JACK
ITEM 1ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR REVIEWING AND PROVIDING ITEMSLISTED IN MECHANICAL EQUIPMENT LIST SUCH AS DISCONNECTS, STARTERS, TIMERS,SWITCHES, VARIABLE FREQUENCY DRIVES, ETC.
ITEM 2ELECTRICAL CONTRACTOR IS TO REFER TO ARCHITECTURAL REFLECTED CEILINGPLANS FOR ADDITIONAL LUMINAIRE INFORMATION AND MOUNTING LOCATIONS.
ITEM 3ELECTRICAL CONTRACTOR SHALL VERIFY COLOR OF DEVICES, SURFACE RACEWAY,AND/OR PLUGMOLD WITH ARCHITECT/ENGINEER.
ITEM 4ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR LOCATION OF THE EXHAUST FANSLISTED IN THE MECHANICAL EQUIPMENT LIST BY REFERRING TO MECHANICAL/HVACPLANS.
ITEM 5FEEDERS ON DRAWINGS ARE SCHEMATIC ONLY. CONDUIT RUNS SHALL COMPLY WITHCONDUIT SPECIFICATIONS AND CONTAIN BENDS THAT ARE NO GREATER THAN 90DEGREES. CONDUITS ABOVE GRADE SHALL BE RUN PARALLEL TO OR PERPENDICULARWITH BUILDING STEEL AND/OR ARCHITECTURAL LINES.
ITEM 6ADJUST LUMINAIRE LOCATIONS IN MECHANICAL ROOMS TO ACCOMMODATE MECHANICALEQUIPMENT AND FIELD CONDITIONS.
ITEM 7ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO REVIEW INTERIOR ELEVATIONSHEETS FOR PLACEMENT OF DEVICE BOXES. COORDINATE LOCATIONS SO THAT NODEVICES ARE BE INSTALLED BEHIND MARKERBOARDS, MIRRORS, TACKBAORDS, ETC..
ITEM 8ELECTRICAL CONTRACTOR IS RESPONSIBLE TO ROUGH-IN SINGLE GANG BOXES FORHVAC/TEMPERATURE CONTROLS SENSORS IN ALL OCCUPIED ROOMS. IN ADDITIONTO THE BOXES, INSTALL 1/2" CONDUIT FROM BOX TO CONTROLLED DEVICE ASREQUIRED, COORDINATE WITH MECH. CONTRACTOR AND MECH. DRAWINGS.
ITEM 9CABINET HEATERS MAY HAVE LINE VOLTAGE THERMOSTATS SUPPLIED BYMECHANICAL CONTRACTOR AND INSTALLED BY THE ELECTRICAL CONTRACTOR.REFER TO MECHANICAL EQUIPMENT SCHEDULE.
ITEM 10SEE MECHANICAL EQUIPMENT LIST FOR DETAILED INFORMATION ON EQUIPMENT ANDCONTROL. ELECTRICAL CONTRACTOR SHALL PROVIDE ITEMS AS NOTED ONMECHANICAL EQUIPMENT LIST.
ITEM 11SEE ROOF PLANS FOR EXACT LOCATIONS OF ROOF-TOP MECHANICAL EQUIPMENT.
ITEM 12FOR TELECOMM SLEEVES INTO ROOMS FOR WHICH SIZES ARE NOT CALLED OUT,E.C. SHALL SUPPLY (2) 2" CONDUIT SLEEVES WITH APPROPRIATE BUSHINGS.
ITEM 13ELECTRICAL CONTRACTOR SHALL COORDINATE WITH PLUMBING CONTRACTOR ANDTHE ELECTRIC WATER COOLER SHOP DRAWINGS FOR MOUNTING HEIGHT OF EWCPOWER CONNECTIONS.
ITEM 14ELECTRICAL CONTRACTOR SHALL REVIEW TOILET EQUIPMENT SHOP DRAWINGS FORCORRECT DEVICE BOX ROUGH-IN LOCATION OF HAND DRYERS.
ITEM 15ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR INSTALLING ANY LOOSE VARIABLEFREQUENCY DRIVES PROVIDED BY THE MECHANICAL CONTRACTOR.
ITEM 16METAL CLAD CABLE MAY BE USED FOR FIXTURE WHIPS IN LENGTHS OF 6 FEET ORLESS ABOVE AN ACCESSIBLE LAY-IN CEILING SYSTEM ONLY. OTHERWISE, METALCLAD OR OTHER CABLE TYPES SHALL NOT BE USED UNLESS SPECIFICALLYAUTHORIZED BY THE ENGINEER. IT IS THE INTENT OF THESE CONSTRUCTIONDOCUMENTS THAT ALL INSTALLED BRANCH CIRCUITS CONSIST OF SEPARATERACEWAY AND CONDUCTORS ALLOWING REMOVAL AND REPLACEMENT OF WIRINGAS REQUIRED FOR FUTURE UPGRADES. REFER TO CONDUIT SPECIFICATIONS.
ITEM 17CIRCUIT WIRING FOR THE EMERGENCY SYSTEMS SHALL BE INSTALLED IN SEPARATECONDUIT/RACEWAY AND BE KEPT ENTIRELY INDEPENDENT OF ALL OTHER WIRINGAND EQUIPMENT PER N.E.C.
ITEM 18ALL FEEDER AND BRANCH CIRCUITS TO PANELS, MOTORS, LIGHTS, RECEPTACLES,EQUIPMENT, GENERAL DISTRIBUTION, ETC. SHALL CONTAIN AN EQUIPMENT GROUNDINGCONDUCTOR SIZED ACCORDING TO THE N.E.C. THE CONDUIT SYSTEM SHALL NOTBE CONSIDERED AN ACCEPTABLE GROUND.
ITEM 19ALL "LOW-VOLTAGE" TELECOMMUNICATIONS AND CONTROL CABLING MAY BEINSTALLED WITHOUT CONDUIT, RACEWAY, OR CABLE TRAY ONLY WHERECONCEALED ABOVE AN LAY-IN CEILING SYSTEM AND ACCESSIBLE FOR FUTUREMAINTENANCE. OTHERWISE, ALL CABLING ASSOCIATED WITH BMS/ATC,OCCUPANCY SENSOR OR LV SWITCH LIGHTING CONTROLS, FIRE ALARM SYSTEM,VOICE/DATA/VIDEO SYSTEMS, CLOCK SYSTEM, AUDIO SYSTEMS, ETC. MUST BEINSTALLED IN AN APPROVED CONDUIT OR SURFACE RACEWAY.
ITEM 20ALL NEW ITEMS SHOWN ON EXISTING WALLS IN FINISHED AREAS SHALL BE FLUSH-MOUNTED EXCEPT WHERE NOTED. CONTRACTOR SHALL CUT IN NEW DEVICE BOX,FISH WALL WITH FLEXIBLE METALLIC CONDUIT, ETC. SURFACE RACEWAY SHALL BEUSED ONLY WHERE WALL IS UNABLE TO BE FISHED, OR TO MATCH EXISTINGCONDITIONS. COORDINATE EXCEPTIONS WITH ENGINEER. EXAMPLES OF UNFINISHEDAREAS, WHERE EXPOSED SURFACE RACEWAY OR CONDUIT ARE ACCEPTABLE INCLUDESTORAGE ROOMS, MECHANICAL/ELECTRICAL ROOMS, ETC.
GENERAL NOTES
PROJECT NO.
Site / CivilArchitectureInteriorStructureMechanicalElectrical
GMB
No part of this drawing may be used orreproduced in any form or by any means,
or stored in a database or retrieval system,without prior written permission of
Copyright 2012 All Rights Reservedc
ARCHITECTURE + ENGINEERING
85 East Eighth Street, Suite 200
P. 616.796.0200 F. 616-796-0201
Holland, Michigan 49423
www.gmb.com
GRCC PROJECT NO. 1213-11034
11.05.12 BIDS & CONSTRUCTION
C:\U
sers
\nat
hand
\Des
ktop
\5-2
420E
_CE
NTR
AL.
rvt
E7.0
5-2420
PHASE 2 – SYMBOL LEGEND &NOTES
ND
CO
LLE
GE
PA
RK
PLA
ZA
GR
AN
D R
AP
IDS
CO
MM
UN
ITY
CO
LLE
GE
GR
AN
D R
AP
IDS
, MIC
HIG
AN
E7.0 1/8" = 1'-0"
1 EMERGENCY TRANSFER DEVICE WIRING DETAIL
E7.0 1/8" = 1'-0"
2 FLAGPOLE LIGHT FIXTURE MOUNTING DETAILE7.0 1/8" = 1'-0"
3 LIGHTING CONTACTOR LC-1 & LC-2 DETAIL
E7.0 1/8" = 1'-0"
4 FIRE ALARM RISER DETAILE7.0 1/8" = 1'-0"
5 TYPICAL OCCUPANCY SENSOR WIRING DETAIL