COMBINATION OF LOW ENERGY AND MECHANICAL COOLING TECHNOLOGIES FOR BUILDINGS IN CENTRAL EUROPE Miloš Lain 1) , Jan Hensen 2) 1) Department of Environmental Engineering, Faculty of Mechanical Engineering Czech Technical University in Prague Technická 4, 166 07 Prague 6, Czech Republic, e-mail: [email protected] 2) Center for Building & Systems TNO-TU/e, Group FAGO, Technische Universiteit Eindhoven,, The Netherlands SUMMARY This paper discusses options for incorporating low energy cooling technologies combined with standard mechanical cooling in buildings in central Europe. Case studies, design recommendations and role of computer simulation of building and system in the design process are presented. Applicability of night ventilation, evaporative cooling, and cooled ceiling panels will be analyzed. INTRODUCTION In Europe buildings account for approximately 40 to 50% of total primary energy consumption. More and more offices are fully air-conditioned in the Czech Republic. Increasing use of computer and auxiliary equipment has led to an increasing demand for cooling in commercial buildings. Associated impact on greenhouse gas emissions is enhanced by the fact that these cooling systems are usually electrically driven and electricity in the Czech Republic is mostly produced by coal power plants. Based upon the Kyoto Protocol, European countries have agreed to decrease energy consumption in buildings and thus cut down greenhouse gas emissions. One promising way to solve the discrepancy between the increasing demand for thermal comfort and the necessity to reduce CO2 emissions is application of low energy cooling techniques. Low energy technologies are not often able to guarantee thermal comfort for the whole summer; therefore they can be combined with mechanical cooling. LOW ENERGY COOLING TECHNIQUES Low energy cooling techniques aim to reduce energy consumption and peak electricity demand. They do so by making use of low exergy (i.e. low quality) cooling sources such as ambient air and ground or surface water. These technologies are also referred to as passive or hybrid cooling systems. Low energy cooling techniques can be divided into two groups: those, which include a cooling source and those that focus solely on delivery of cooling to the treated space (IEA 1995, Liddament 2000). The first group of systems rely on natural sources of cooling: Night ventilation – lowers the temperature of building thermal mass by night ventilation Evaporative cooling – sensible heat is absorbed as latent heat to evaporate water Ground cooling –air is cooled by the ground via matrix of piping or groundwater (aquifer) cooling The second group of technologies focus on delivering cooling to the treated space in an efficient manner, those technologies work usually well with lower grade sources of cooling. The following systems can be placed in this group: Slab cooling – thermal mass of slab is cooled by air or water Chilled ceilings and beams – ceiling panel or beam is cooled Displacement ventilation – conditioned air is emitted at low level at very low velocity For some of the low energy technologies mechanical cooling (compressor cycle) can be used as a cooling liquid source (slab or ceiling cooling, displacement ventilation), some can

COMBINATION OF LOW ENERGY AND MECHANICAL COOLING ... · COMBINATION OF LOW ENERGY AND MECHANICAL COOLING TECHNOLOGIES FOR BUILDINGS IN CENTRAL EUROPE Miloš Lain1), Jan Hensen2) 1)

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: COMBINATION OF LOW ENERGY AND MECHANICAL COOLING ... · COMBINATION OF LOW ENERGY AND MECHANICAL COOLING TECHNOLOGIES FOR BUILDINGS IN CENTRAL EUROPE Miloš Lain1), Jan Hensen2) 1)

COMBINATION OF LOW ENERGY AND MECHANICAL COOLING TECHNOLOGIES

FOR BUILDINGS IN CENTRAL EUROPE

Miloš Lain1), Jan Hensen2) 1) Department of Environmental Engineering, Faculty of Mechanical Engineering

Czech Technical University in Prague Technická 4, 166 07 Prague 6, Czech Republic, e-mail: [email protected] 2)Center for Building & Systems TNO-TU/e, Group FAGO, Technische Universiteit Eindhoven,, The Netherlands

SUMMARY This paper discusses options for incorporating low energy cooling technologies combined with standard mechanical cooling in buildings in central Europe. Case studies, design recommendations and role of computer simulation of building and system in the design process are presented. Applicability of night ventilation, evaporative cooling, and cooled ceiling panels will be analyzed.

INTRODUCTION In Europe buildings account for approximately 40 to 50% of total primary energy consumption. More and more offices are fully air-conditioned in the Czech Republic. Increasing use of computer and auxiliary equipment has led to an increasing demand for cooling in commercial buildings. Associated impact on greenhouse gas emissions is enhanced by the fact that these cooling systems are usually electrically driven and electricity in the Czech Republic is mostly produced by coal power plants. Based upon the Kyoto Protocol, European countries have agreed to decrease energy consumption in buildings and thus cut down greenhouse gas emissions. One promising way to solve the discrepancy between the increasing demand for thermal comfort and the necessity to reduce CO2 emissions is application of low energy cooling techniques. Low energy technologies are not often able to guarantee thermal comfort for the whole summer; therefore they can be combined with mechanical cooling.

LOW ENERGY COOLING TECHNIQUES Low energy cooling techniques aim to reduce energy consumption and peak electricity demand. They do so by making use of low exergy (i.e. low quality) cooling sources such as ambient air and ground or surface water. These technologies are also referred to as passive or hybrid cooling systems. Low energy cooling techniques can be divided into two groups: those, which include a cooling source and those that focus solely on delivery of cooling to the treated space (IEA 1995, Liddament 2000). The first group of systems rely on natural sources of cooling:

Night ventilation – lowers the temperature of building thermal mass by night ventilation Evaporative cooling – sensible heat is absorbed as latent heat to evaporate water Ground cooling –air is cooled by the ground via matrix of piping or groundwater (aquifer) cooling

The second group of technologies focus on delivering cooling to the treated space in an efficient manner, those technologies work usually well with lower grade sources of cooling. The following systems can be placed in this group:

Slab cooling – thermal mass of slab is cooled by air or water Chilled ceilings and beams – ceiling panel or beam is cooled Displacement ventilation – conditioned air is emitted at low level at very low velocity

For some of the low energy technologies mechanical cooling (compressor cycle) can be used as a cooling liquid source (slab or ceiling cooling, displacement ventilation), some can

Adelya Khayrullina
Text Box
Lain, M. & Hensen, J.L.M. (2004). Combination of low energy and mechanical cooling technologies for buildings in Central Europe. Proceedings of the 5th International IRR Conference Compressors, pp. 1-6. Castá Papiernicka: International Institute of Refrigeration of Paris.
Page 2: COMBINATION OF LOW ENERGY AND MECHANICAL COOLING ... · COMBINATION OF LOW ENERGY AND MECHANICAL COOLING TECHNOLOGIES FOR BUILDINGS IN CENTRAL EUROPE Miloš Lain1), Jan Hensen2) 1)

accommodate additional mechanical cooling as a part of the system (night ventilation, evaporative cooling) and some systems are combined with independent air-conditioning units.

NIGHT VENTILATION The system is based on using low external air temperature during the night and high thermal mass of the building. For mechanical night ventilation it is necessary to optimize the flow rate during the night. Energy consumption of fans can be higher than consumption of mechanical cooling system if the flow rate is overestimated. Whole year computer simulation is one of basic methods to determine optimal night ventilation because of combination of building thermal mass and variable external temperatures and gains. If a building with high thermal mass is equipped with a mechanical all air air-conditioning system a complex system called “top cooling“ allows reducing energy consumption by night ventilation and by proper control of mechanical cooling as well.

THE OFFICE BUILDING IN PRAGUE WITH TOP COOLING The first headquarters building in the Czech Republic to employ night-cooling for most of the office spaces was built in Prague (1998 – 2002). During the initial design process computer simulation was applied to prove the chosen conception. Second stage simulations based on a model calibrated acording to the monitored data are carried out to optimalize the air conditoning system controll.

The thermal mass of the building was increased by using pure concrete ceilings with ribs (no false ceiling) and concrete floors without carpets in all open plan offices. The design of external shading elemens eliminates solar gains from direct radiation on the south facade. A high performance heat recovery sytem in the central unit reduces the heat or cool consumption as well. Building monitoring as well as second stage simulations proved a minimal need for mechanical cooling or heating in the building, especially during late spring or early autumn.

Figure 1: Principle of the shading and night ventilating in the referred building.

Comparison of simulation and measurement

0123456789

1011121314151617181920

3-IX

.

4-IX

.

5-IX

.

6-IX

.

7-IX

.

8-IX

.

9-IX

.

10-IX

.

11-IX

.

12-IX

.

13-IX

.

Pow

er [k

W]

17

18

19

20

21

22

23

24

25

26

27

Tem

pera

ture

[°C

]

Cooling power (average, measurements) Cooling power (simulation 26)

Inside temperature of 5th floor (measurements, dataloger) Onside air temperature (simulation 26)

101%

Enhanced heat With system

Figure 2: Comparison of the building measurements and simulation results

Page 3: COMBINATION OF LOW ENERGY AND MECHANICAL COOLING ... · COMBINATION OF LOW ENERGY AND MECHANICAL COOLING TECHNOLOGIES FOR BUILDINGS IN CENTRAL EUROPE Miloš Lain1), Jan Hensen2) 1)

INFLUENCE OF STORED HEAT IN HEAVY CONSTRUCTIONS ON COOLING ENERGY DEMAND One of the main disadvantages of traditional calculating and design methods for HVAC systems is underestimation of the impact of the heat capacity of the building. In the design of new galleries in the historical building of Sovovy Mlýny (watermills) in Prague, computer simulations were used to predict the required capacity of the cooling system. The initial design made by a standard calculation estimated the cooling capacity of about 100 kW. The cooling system was dimensioned accordingly. The simulation showed that for the indoor air temperature of 24°C the cooling capacity of 20 kW would be enough to remove both the external heat load and the internal heat gains from occupants and lights.

The study helped not only to lower investment costs for the cooling system but most of all to minimize changes in the construction of a valuable historical building. The simulation was combined with measurements in the existing building and indoor environment was assessed also for the case without any cooling device. The influence of the number of visitors, the lighting and open or closed shutters was tested.

EVAPORATIVE COOLING Evaporative cooling is a process, which uses the effect of evaporation as natural heat sink. Sensible heat from the air is absorbed as latent heat necessary to evaporate water. The amount of sensible heat absorbed depends on the amount of water that can be evaporated. Evaporative cooling is a very old process, having its origins some thousand years ago in ancient Egypt and Persia. Evaporative cooling was one of the main cooling techniques before refrigerant vapor compression cycle. Evaporative cooling can be direct or indirect. The determinative factor for evaporative cooling is outside air humidity. The evaporative cooling technology can be placed just in central all air air-conditioning system. Analysis of Czech climate shows stand alone direct or indirect evaporative cooling is not able to guarantee thermal comfort in office buildings. That is why direct evaporative cooling is usually combined with other cooling technologies in order to provide comfort thermal conditions for people throughout the whole year. The maximum capacity of chiller does not decrease significantly if such a hybrid system consists of a direct evaporative cooling device and a standard chiller. However, the number of operation hours decreases markedly, as you can see in the following example.

Cooling load time variation

0

5

10

15

20

25

po út st čt pá so ne

Representative week

Coo

ling

load

[kW

]

0

5

10

15

20

25

30A

ir te

mpe

ratu

re [°

C]

Cooling load Heat gains Ventilating air temperature

Figure 6: Cooling load variation during a representative week

Figure 5: The Sovovy Mlyny building

Page 4: COMBINATION OF LOW ENERGY AND MECHANICAL COOLING ... · COMBINATION OF LOW ENERGY AND MECHANICAL COOLING TECHNOLOGIES FOR BUILDINGS IN CENTRAL EUROPE Miloš Lain1), Jan Hensen2) 1)

Figure 3: The ZOO pavilion construction and ESP-r software model

EVAPORATIVE COOLING OF THE INDONESIAN JUNGLE PAVILION Modelling and simulation work was carried out to support the design team of the new "Indonesian Jungle" pavilion in Prague Zoo (Bartak 2001). This pavilion is basically a very large (a surface area of 1900 m2 covering a volume of 14700 m3) transparent dome (see

Figure 3) maintaining warm and humid (20 to 25 °C and 70 to 90 %) jungle-like indoor environment. Problematic issues include very high solar gains in summer, very high heat losses in winter, and potential condensation against the roof at various times throughout the year.

Direct evaporative cooling by spraying water in the pavilion interior was considered in order to cool the air adiabatically and thus reduce summertime cooling energy consumption and lower the maximum cooling loads. This was considered an interesting option since the Czech Republic has a relatively dry summer climate while the jungle pavilion requires high levels of relative humidity; i.e. in the range of 70% to 90%. As can be seen in Figure 4 the

simulation results indicate about 50 kW or 25% reduction in maximum cooling load due to evaporative cooling. The amount of time the cooling system is in use will be reduced from 2000 hrs to about 1000 hrs per year. The number of operating hours with high cooling loads, e.g. loads over 120 kW, will reach 80 hours per year only. In terms of cooling energy demand the differences are even bigger. Without direct evaporative cooling the cooling energy demand over a typical summer amounts to 89 MWh. With direct evaporative cooling and the maximum indoor relative humidity of 70% the demand is reduced to 41 MWh (54% reduction). With the maximum relative humidity of 90% the cooling energy demand reduces to 13 MWh (85% reduction).

CEILING SLAB COOLING Slab cooling is a radiant cooled ceiling with high thermal mass. Sensible room heat gains are dissipated by large-area massive water-cooled ceiling panels. The cooling water temperature is usually close to 20°C. Therefore this system is suitable for high temperature (low potential) cooling sources. The maximal performance of cooled ceilings is approximately 50 W/m2.

Cooling load - representative week

0

50

100

150

200

250

7.7

8.7

9.7

10.7

11.7

12.7

13.7

14.7

15.7

16.7

17.7

18.7

19.7

Coo

ling

load

[kW

]

Sensible cooling load Cooling load with evaporative humidication

Indoor air temperature 25/21°C

Relative humidity 90%

Figure 4: Cooling loads during a representative week

Page 5: COMBINATION OF LOW ENERGY AND MECHANICAL COOLING ... · COMBINATION OF LOW ENERGY AND MECHANICAL COOLING TECHNOLOGIES FOR BUILDINGS IN CENTRAL EUROPE Miloš Lain1), Jan Hensen2) 1)

Figure 5: Office model in ESP-r software

15

20

25

30

35

40

45

9.VIII 11.VIII 13.VIII 15.VIII 17.VIII 19.VIII 21.VIII 23.VIIIdate

t o[°

C]

Clear float - v1s1c1

Antisun bronze - v1s2c1

Internal blind - v1s3c1

v1s1c1v1s2c1v1s3c1

15

20

25

30

35

40

45

9.VIII 11.VIII 13.VIII 15.VIII 17.VIII 19.VIII 21.VIII 23.VIIIdate

t o[°

C]

Clear float - v1s1c0Antisun bronze - v1s2c0Internal blind - v1s3c0

v1s1c0

v1s2c0

v1s3c0

Figure 6: Operative temperature during two summer weeks assuming infiltration only, different glazing types, without (left) and with ceiling cooling.

APPLICABILITY OF LOW ENERGY COOLING TECHNOLOGIES FOR RETROFIT OF MECH. ENG. FACULTY BUILDING Computer simulations for a typical office room in the building were carried out. There are two south-east facing windows resulting in 55% glazing of one of the walls. Model of the office is shown in Figure 1. Internal heat gains representing three occupants (3 x 62 W) each with PC (3 x 40 W) and monitor (3 x 58 W) are incorporated in the model. Two passive cooling methods (shading, natural ventilation) for improving thermal comfort in a not air-conditioned office in summer were tested. : decreasing solar heat gains by shading or reflection and natural ventilation strategies. All cases have been simulated without slab cooling and with slab cooling. According to the simulation results all three low energy cooling strategies help to improve indoor thermal comfort in the office. It is recommended to use antisun glassing with blinds especially if there is not other cooling technology. Operative temperature was decreased by 10 K if just infiltration was used and by 5 K for night ventilation.

Ceiling cooling was approved as the only system, which can fully guarantee thermal comfort in the office. The effect of ceiling cooling was much stronger that other considered technologies. The simulation results even show occasional overcooling of the office (Figure 6.). The question of the optimal ceiling (cooling water) temperature and the control of the slab cooling system remains for future research.

ROLE OF COMPUTER SIMULATIONS As you can se from previous case studies the use of computer modelling and simulation for the design and/ or evaluation of buildings and HVAC is quickly moving from the research and development stage into everyday engineering practice. In contrast to the traditional simplified calculating methods (not considering the system dynamics), computer based modelling approaches reality much closer. Especially for low energy and hybrid system design the role of computer modelling and simulation is more important. Dynamic interactions of the building, climate and plant system play the crucial role for most low energy cooling technologies. Computer simulations demand more input information and data processing than ordinary design work. On the other hand, once the model is prepared, simulation techniques allow

Page 6: COMBINATION OF LOW ENERGY AND MECHANICAL COOLING ... · COMBINATION OF LOW ENERGY AND MECHANICAL COOLING TECHNOLOGIES FOR BUILDINGS IN CENTRAL EUROPE Miloš Lain1), Jan Hensen2) 1)

quick and detailed analysis of various solutions for the building geometry and construction as well as for the design and operation of HVAC systems. The aim of computer modelling is to optimize the design of a building and its service system according to the requirements for indoor air quality while keeping energy consumption at minimum levels. All presented simulations were done with integrated building performance modelling and simulation environment ESP-r.

CONCLUSIONS If thermal comfort for the whole summer is required in most office buildings low energy cooling technology has to be combined with mechanical cooling. Design and maintenance of such hybrid systems is usually very difficult but if it is done well energy savings can be considerable. Passive cooling reduces especially the operating costs (energy consumption) of hybrid systems, but in some cases the initial investments can be reduced as well. Computer simulation and modelling play the crucial role for the design and optimalization of such hybrid systems.

REFERENCES [1] Banks, J. and R.R. Gibson. 1997. "Simulation Modelling – Some Programming

Required". IIE Solutions. Feb. 1997. [2] Barnard, N., Jaunzens, D., 2001, Low Energy Cooling – Technology Selection and Early

Design Guidance, Building Research Establishment Ltd, London, 109 p. [3] Barták, M., Drkal, F., Hensen, J., Lain, M.: Design Suport Simulations for The Prague

Zoo Indonesian Jungle Pavilion In: Building Simulation 2001. Kyoto: IBPSA, 2001, vol. 1, p. 841-845. ISBN 85-901939-3-4.

[4] Clarke, J.A. 1985. Energy Simulation for Building Design. Adam Hilger Ltd., Bristol. [5] Dvorak, J., 2002, Hlavni sprava CEZ: nocni chlazeni, Proc. Simulace budov a techniky

prostredi 2002, IBPSA-CZ, p. 15 to 17 (in Czech). [6] Heap, R.D., 2001, Refrigeration and air conditioning – the response to climate change,

Bulletin of the IIR - No 2001-5. [7] IEA, 1995, Review of Low Energy Cooling Technologies, Natural resources Canada,

Ottawa, Canada, 88 p. [8] Lain, M., 2002, Pocitacove simulace pri reseni alternativnich zpusobu chlazeni budov,

Proc. Simulace budov a techniky prostredi 2002, IBPSA-CZ, p. 93 to 96 (in Czech). [9] Lain, M. - Barták, M. - Drkal, F. - Hensen, J.: Simulation in Engineering the Ventilation

and Air-Conditioning of a New Art Galery in Sovovy Mlýny In: Sustainable Building & Solar Energy 2001. Brno: Brno University, 2001, vol. 1, p. 80-83. (in Czech

[10] Lain, M., Drkal, F., Hensen, J., Zmrhal, V.: Low Energy Cooling Techniques for Retrofitted Office Buildings in Central Europe. AIVC conference 2004 Prague, not published yet.

[11] Liddament, M.W., 2000, Low energy cooling, ESSU, Coventry, U.K., 32 p. [12] Loveday, D.L., Parsons, K.C., Taki, A.H., Hodder, S.G., Jeal, L.D., Displacement

ventilation environments with chilled ceilings: thermal comfort design within the context of the BS EN ISO7730 versus adaptive debate. Energy and Buildings 34, 2002, p. 573 – 579.

[13] Santamouris, M., Asimakopoulos, D., 1996, Passive Cooling of Buildings, James&James Ltd., London, U.K., 472 p.