Comfort Ceiling Fan Coil System INDULVENT ec Draught-free ambient air distribution with cooling capacity up to 2600 W Low sound power levels Only electrical, cooling water and condensate connections required Energy-saving EC technology Stepless power regulation Integrated condensate pump Open BUS architecture NEW

Comfort Ceiling Fan Coil System INDULVENT ec NEW · Comfort Ceiling fan coil system INDULVENT ec A square form with the following functions: Room cooling and dehumidification in recirculation

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Comfort Ceiling Fan Coil System INDULVENT ec

Draught-free ambient air distribution with cooling capacity up to 2600 W

Low sound power levels

Only electrical, cooling water and condensate connections required

Energy-saving EC technology

Stepless power regulation

Integrated condensate pump

Open BUS architecture

NEW

Local ceiling fan coil systems allow the flexible use of available space. For high comfort requirements, INDULVENT ec ensures draught-free ambient air flow with high cooling capacity and low sound power levels. The compact unit employs a fan with energy-saving EC technology. Cooling loads of up to 2600 W can be accommodated. Only electrical, cooling water and condensate connec-tions are required. INDULVENT ec is suitable for the installation in all prevalent modular ceilings.

INDULVENT ec performance features

Compact designFan, heat exchanger, dust protection, ambient air temperature sensor and controller are all integra-ted in a single housing.

Up to 2600 W cooling capacity (sensible + latent) per unit for high cooling loads.

Only a cold water connection and mains voltageare needed for operation.

Draught-free air distributionaccording to DIN EN 13 779, results from the high- induction, integrated, ceiling air diffuser. Average local air velocities of less than 0.15 m/s can be achieved.

Housing with internal insulationusing halogen-free closed-cell insulation material. Fire-resistance classification (BKZ) B2.

Simple operation and maintenanceThe folding hinge fitted as standard to the front panel makes servicing easy.

Easy to clean (VDI 6022)because all internal parts are easily accessible. Just a few simple operations and the housing, ventilator, heat exchanger, condensate dish etc. are accessible for maintenance and cleaning.

Integral cooling regulationadapts the cooling capacity to the load situation in a room by changing the recirculation air flow rate.

Features INDULVENT ec

Vent-BUSis an internal communication system which can connect up to 32 subscribers to a common BUS. Any desired combination of individual units and master / slave groups is possible.

Comfortable operation, parameterisation and monitoringusing a PC or a laptop via the USB socket in the front panel. With the VENT-BUS, any connected unit can be addressed and parameterised from the USB interface of any convenient subscriber.

FlexibleBecause parameterisation is simple, the works control parameters can be changed to individual settings when required. If usage changes, new master / slave groups can be set up at any time.

Comprehensive equipmentThe basic unit includes signal contacts for ope-ration and fault messages. An external control using a 0-10 V DC control voltage is possible. Con- densate pump is fitted as standard to ensure the reliable removal of any condensate for construc-tion height 335 mm.

Accessories Remote switching point with the functions:

OFF – STAGE 1 – STAGE 2 – AUTOMATIC Through valve (¾“) with thermal actuator

to cut off cold water during standstill periods Coupler to incorporate the Vent-BUS in an

inhouse BUS system

Function and Measurement

Air flow path Construction

Simple to operate and easy to maintain

The compact unit contains a fan, Cu-Al heat ex- changer with hydrophobically-coated vanes, ambient air temperature sensor, filter fleece, con-densate pump and an electronic controller. The folding hinge fitted as standard makes installa-tion and servicing especially easy. After undoing the quick-action fastener, the front panel can be swung open. All components are readily accessi-ble, and easy to clean and maintain (VDI 6022).

Master-slave operation with Vent-BUS

Using the Vent-BUS, it is possible to operate units that belong together in parallel. Up to 32 sub- scribers can be connected in such a group. Communication is by means of twisted-pair cable that must be installed by the customer. It con-nects all units that belong to the data BUS in series. Within a hard-wired VENT-BUS, groups can be set up as required at any time and confi-gured to operate in parallel. The parameterisation software is used for this purpose.

Two-wire BUS cable

A special feature of Vent-BUS is that the parame-terisation of any subscriber can be carried out from any desired INDULVENT ec connected to the BUS. This offers the advantage that, for example, sensitive rooms do not have to be entered for setting up operations.

The temperature of the ambient air entering the unit is recorded by an internal temperature sen-sor. The integrated electronic controller reacts to this measured temperature or to an external control signal. By changing the speed of rotation, and so changing the recirculation air flow rate, the cooling capacity is continually adapted to the cooling load of a room.

INDULVENT ec 1Master

INDULVENT ec 2Slave

INDULVENT ec 32Slave

Example of parameter setting

A USB socket and signal diodes for monitoring and parameterisation of the unit are integrated into the front panel. This allows the current ope-rating state to be read from within the room. In addition the ceiling fan coil has an operation and fault-signal relay.

Outlet recirculation air Outlet recirculation airInlet ambient air

Heat exchanger EC motor Fan rotor

Air guide vane Inlet grille / Filter fleece Condensate dish

Side view cold water connections

Technical data – Dimensions

Side view cold water and condensate connections

Section

Soffit from room (front plate)

Side view electrical connections

All dimensions in mm*335 mm with condensate pump*375 mm with free condensate drain

571

85 400 85Ø

9Ø9

282 233

184

43Soffit from room (front plate)

Side view cold water connections

Side view electrical connections

Siede view cold water and condensate connections Section

*335 mm with condensate pump

*375 mm with free condensate drain All dimensions in mm

569

84,5 84,558

~43

400

~85

15

6

33

5 (

37

5)*

12

Ø9 Ø9

598

598

Technical data - Dimensions (size 600)

Front panel

Temperature sensor Filter fleece

Condensate dish

Controller / Electricalconnection box

Ceilingpanel

Cold waterconnection

Attachementpoint

Attachementpoint

Fan unit

Heat exchanger

569

84,5 84,5

Ø9Ø9

400

40

Ø9Ø3/4"

Ø9

56

25

3

170

50

110

86

166

57

Ø3/4"

70

179

VL

RL

Overview

Technical data – Operating range and properties

Operating temperature range as indoor unit ° C + 5 bis + 40Recirculation air flow rate m3 / h 100 - 470Power supply V / Hz 230 / 50Degree of protection IP X0Nominal electrical power requirement of fan1 Watt 39Standby power consumption Watt 4Operating medium WaterOperating limits for water temperature ° C + 5 bis + 65 ° CHeat exchanger test pressure bar 10Nominal heat exchanger water requirement l / h 450Nominal pressure loss kPa 9Water connection, supply / return Zoll ¾“ External threadWater volume l 1.8Electrical power requirement of condensate pump Watt 11Condensate connection (free discharge) mm 10 x 1.0Condensate connection (pressure line) mm 6 x 1.5Condensate pump, delivery head / flow rate m / l / h 3,5 / 2Dimensions of housing without front panelHeight / Width / Depth mm 335 / 596 / 594Dimensions of front panelHeight / Width / Depth mm 12 / 623 / 623Operating weight kg 31

Recirculation air flow rate [m3 / h] Cold water supply temperature6 ° C 8 ° C 10 ° C 12 ° C 14 ° C

Total cooling capacity [Watt]150 1270 1050 840 650 490200 1480 1220 980 760 570250 1690 1390 1110 870 650300 1890 1560 1250 980 740350 2080 1720 1380 1080 820400 2290 18880 1510 1190 890450 2470 2040 1650 1280 970470 2600 2100 1690 1330 1000

Cooling capacity2

1 Power requirement Vmax = 470 m³ / h

2 Ambient air conditions: 26 ° C / 60 % rel. humidity, dew point: 17,6 ° C

.

Technical data - Operating range an properties (size 600)

Operating temperature range as indoor unit °C +5 to +40

Recirculation air flow rate m³/h 100 - 470

Power supply V/ Hz 230/50

Degree of protection IP X0

Nominal electrical power requirement of fan1 Watt 39

Standby power consumption Watt 4

Operating medium Water

Operating limits for water temperature °C +5 to +65°C

Heat exchanger test pressure bar 10

Nominal heat exchanger water requirement l/h 450

Nominal pressure loss kPa 9

Water connection, supply / return Zoll 3/4" External thread

Water volume l 1,8

Electrical power requirement of condensate pump Watt 11

Condensate connection (free discharge) mm 10 x 1,0

Condensate connection (pressure line) mm 6 x 1,5

Condensate pump, delivery head / flow rate m / l/h 3,5 / 2

Dimensions of housing without front panel

Height mm 375

Width mm 571

Depth mm 569

Dimensions of front panel

Height mm 12

Width mm 598

Depth mm 598

Operating weight kg 31

Overview

1 Power requirement Vmax = 470m³/h

Cooling capacity2

Recirculation air flow rate [m³/h] Cold water supply temperature

6°C 8°C 10°C 12°C 14°C

Total cooling capacity [Watt]

150 1270 1050 840 650 490

200 1480 1220 980 760 570

250 1690 1390 1110 870 650

300 1890 1560 1250 980 740

350 2080 1720 1380 1080 820

400 2290 1880 1510 1190 890

450 2470 2040 1650 1280 970

470 2600 2100 1690 1330 1000

2 Ambient air conditions: 26° C / 60 % rel. humidity, dew point: 17.6° C

Sound power levels and electrical power requirements

Technical data – Sound power level and requirement

Recirculation air flow rate [m³/h]

Sound power level [dB (A)]

Electrical power requirement [Watt]

150 29 8200 33 10250 37 13300 41 17350 45 23400 48 29450 51 37

470 (max.) 52 39

Water side pressure loss

Water volume [l / h]

Pressure loss [kPa]

300 (minimum water volume) 3.9350 5.3400 7.0

450 (nominal water volume) 8.8500 10.9550 13.2

The cooling capacity depends principally on:

Parameter settings Fan speed selected by the control system or

manually Ambient air temperature and humidity Cold water supply temperature and cold water

mass flow

Determination of the cooling capacity using graphs or formulas is therefore laborious and prone to error. The speed of rotation of the fan changes continually according to the ambient air temperature, as does the cooling capacity during condensing operation.

We recommend:

Due to the numerous parameters, please contact our Technical Sales for a concrete design proposal.

Specification Text

Comfort Ceiling fan coil system INDULVENT ecA square form with the following functions: Room cooling and dehumidification in recirculation mode with a highly inductive, swirl air diffuser

for the greatest possible comfort in accordance with DIN EN 13779 and DIN ISO 7730 Suitable for installation in all popular modular ceilings Unit is easy to clean according to VDI 6022 Speed regulation or control of fan unit depending on ambient air temperature, an external control

voltage, a remote switch or Vent-BUS Potential-free changeover contacts for operation and fault signals Operation, monitoring and parameterisation using a laptop (customer to supply) via a USB socket

in the front panel

Type: INDULVENT ec consisting of: Housing made from zinc-plated steel sheet, thermally insulated, with 8 attachment points Ø 9 mm Front panel, finish colour RAL 9010, with black or light grey (similar to RAL 7035) air guide vanes Front panel with folding hinge is easy to open for servicing and cleaning EC radial fan with backwards-curved guide vanes, stable characteristic, low noise level and

electrical power requirement Heat exchanger with high thermal performance made of copper tubing with press-fitted,

hydrophobically-coated, aluminium lamellae for optimum condensate removal. Water connections: ¾‘‘ male threads.

Electronic controller with ambient air temperature sensor and USB socket Condensate dish made from flame-retarded ABS with external condensate-discharge nozzle Condensate pump with float control and safety cut-off integrated into the unit Easy-to-change G 2 filter fleece Plug 3-pole for power supply consisting of plug fitting and cable housing Operating weight: ca. 31 kg External dimensions:Nominal size of front panel: 623 mm x 623 mm Housing dimensions: 596 mm x 594 mm x 335 mm (without front panel)Type INDULVENT ec / Manufacturer: Kiefer Luft- und KlimatechnikPos. Quantity Type Price per piece

Additional charge front panel coated in RAL colour of your choice, air guide vanes black or light grey (similar to RAL 7035)

Pos. Quantity RAL Price per piece Additional charge remote switch for operating a unit from the room Surface mounting Pos. Quantity Price per piece Flush-mounting Pos. Quantity Price per piece

Additional charge through valve (¾”) with thermal actuator to cut off cold water during standstill periods (supplied loose)

Pos. Quantity Price per piece

Additional charge for plug fitting consisting of: 1 x plug 3-pole for fault message 1 x plug 3-pole for operation notification 1 x plug 12-pole for connection for remote switch, external control voltage and Vent-BUS

Pos. Quantity Price per piece

Additional charge for parameterisation of the offered INDULVENT units on site by Kiefer according to our installation charge rates

Pos. Quantity Estimated price

Specification Text (size 600)

Comfort Ceiling fan coil system INDULVENT ec

A square form with the following functions:

Room cooling and dehumidification in recirculation mode with a highly inductive, swirl air diffuser for the greatest possible comfort in accordance with DIN EN 13779 and DIN ISO 7730

Suitable for installation in all popular modular ceilings.

Unit is easy to clean according to VDI 6022

Speed regulation or control of fan unit depending on ambient air temperature, an external control voltage, a remote switch or Vent-BUS

Potential-free changeover contacts for operation and fault signals

Operation, monitoring and parameterisation using a laptop (customer to supply) via a USB socket in the front panel

Type: INDULVENT ec consisting of:

Housing made from zinc-plated steel sheet, thermally insulated, with 8 attachment points Ø 9 mm

Front panel, finish colour RAL 9010, with black or light grey (similar to RAL 7035) air guide vanes

Front panel with folding hinge is easy to open for servicing and cleaning

EC radial fan with backwards-curved guide vanes, stable characteristic, low noise level and electrical power requirement

Heat exchanger with high thermal performance made of copper tubing with press-fitted, hydrophobically-coated, aluminium lamellae for optimum condensate removal (water connections: ¾‘‘ male threads).

Electronic controller with ambient air temperature sensor and USB socket

Condensate dish made from flame-retarded ABS with external condensate-discharge nozzle

Condensate pump with float control and safety cut-off integrated into the unit

Easy-to-change G 2 filter fleece

Plug 3-pole for power supply consisting of plug fitting and cable housing

Operating weight: ca. 31 kg

External dimensions:

Nominal size of front panel: 598 mm x 598 mm

Housing dimensions: 571 mm x 569 mm x 335 mm (without front panel)

Height: 335 mm (with condensate pump) 375 mm (without condensate pump)

Type: INDULVENT ec / Manufacturer: Kiefer Luft- und Klimatechnik

Pos.___________ Quantity_________ Type______ Price per piece___________

Additional charge front panel coated in RAL colour of your choice, air guide vanes black or light grey

(similar to RAL 7035)

Pos.___________ Quantity_________ RAL______ Price per piece___________

Additional charge remote switch for operating a unit from the room

Surface mounting Pos.__________ Quantity________ Price per piece___________

Flush-mounting Pos.__________ Quantity________ Price per piece___________

Additional charge through valve (¾”) with thermal actuator to cut off cold water during standstill periods

(supplied loose) Pos.__________ Quantity_________ Price per piece___________

Additional charge for plug fitting consisting of:

1 x plug 3-pole for fault message

1 x plug 3-pole for operation notification

1 x plug 12-pole for connection for remote switch, external control voltage and Vent-BUS

Pos.__________ Quantity_________ Costs___________

Additional charge for parameterisation of the offered INDULVENT units on site by Kiefer according to our installation charge rates.

Pos.__________ Quantity_________ Estimated price___________

Experts for air conditioning

Development and testing laboratory

Consulting and planning for ventilation

and air conditioning systems

Linear diffusers

Chilled ceilings

Concrete core cooling with air

System construction comfort air conditioning

System construction industrial air conditioning

Building management

Maintenance service

Asbestos decontamination

Maschinenfabrik Gg. Kiefer GmbH Tel.: +49 (0)711 8109-0 Fax: -205

Heilbronner Straße 380 – 396 E-Mail: [email protected]

70469 Stuttgart, Germany Internet: www.kieferklima.de

E30

42-0

4/12

You will find further information about our products and services on our website: www.kieferklima.de