Ill N c MATERIAL COMPLIANCE STATEMENT International MATERIAL COMPLIANCE STATEMENT SHEET FOR: FIRE PUMP SET Ref: No. NGLCTY1-MS-LP-Q021
Revision No. 0 EPIC OF PHASE 1 OF THE NEW NGL SUPPORT CAMPUS AT MESAIEED Date : 13/02/2014
Spec Ref:NGLCTY1-9-14-0003 REV A S-NO Description Compliance
The impeller shall be of cast bronze enclosed double suction type, both statically an hydraulically balanced. The impeller shall be keyed to a shaft. The shaft material shall be steel to the shaft shall be protected by; sleeves with a gasket joint between it. The shaft shall be
2 protected by; sleeves with a gasket joint between it and t he impeller for protection against shaft corrosion. The sleeves will be bronze Noted&Comply.Grease lubricated bearings are used per UL/FM requirements to ASTM 8584-932 or equivalent. The sleeves will be positive drive by means of a key and with an extern sa sleeve nut set screwed to the shaft for a reduction in shaft wear
The shall be equipped with renewable throat bushings, casing rings in bronze to ASTM 8584- and inter stage channel ring to reduce casing wear and maintenance costs. The casing rings and channel ring shall be hold by Anti-rotational pins to permit easy reinstallation and reduce down time, impeller wear rings are optional. The rotating element shall be mounted in (Grease) (Oil) lubricated ball
3 bearings (when temperatures rise above 225"F. Water jackets shall be added). Heavy cast split glands shall be furnished on each Noted&Comply.Grease lubricated bearings are used per UL/FM requirements stuffing box design for easy removal for packing inspection and maintenance. Heavy fabricated steel base to mount the pump and driver shall be furnished. Flexible shaft coupling shall be furnished to connect the driver pump. Coupling shall be installed with coupling guard in accordance w ith section 8 of ANSI 8 15.1, Safety standard for Mechan ical power transmission Apparatus
l-6MOTORS
1 The Motors for Emergency firewater pumps and Training fire water pumps shall comply with NEMA MG-1, Motors and Generators, Comply. IEC type motor manufactured by A88 is provided. shall be marked as complying with NEMA Design 8 standards, and shall be specifically listed for fire pump service
The main pump set shall be provided with a direct drive, totally enclosed fan cooled, 2900 rpm, F class insulation, temperature rise 2 restricted to class 8, IP-55 protection type Standard Motor wound for a 415 volt 3 phase 50 Hz. supply w ith flexible coupling and Comply. IEC type motor manufactured by ABB is provided.
mounted with motor alignment jacking points
The motor shall fully comply with QP standard ES.2.03.0001 (Electrical Engineering Philosophy) ES.2.14.0030 (LV. Cage Induction 3 Motor), ES.2.14.0098 (Electrical Requirement for Package Equipment) NFPA 20 (2013), & NFPA 70[(2011) CONTRACTOR shall ensure Comply_ IEC type motor manufactured by A88 is provided.
compatibility of pump and motor in all aspects
The driver shall be selected in accordance with NFPA 20[(2013) clause 9.5.2 to provide the required power to operate t he pump at 4 rated speed and maximum pump load under any flow condition. All motors shall be rated for continuous duty. The motors shall not Comply. IEC type motor manufactured by A88 is provided.
have a service factor greater than 1.1.5.
l-7 DIESEL ENGINE
ElectricalQACHighlight
ElectricalQACHighlight
ElectricalQACHighlight
ElectricalQACHighlight
ElectricalQACHighlight