8/27/13 Compressor Surging; Anti Surge Control | Comautoment Community novakurniawan.wordpress.com/2010/06/22/compressor-surging-anti-surge-control/ 1/13 Comautoment Community Compressor Surging; Anti Surge Control Posted on June 22, 2010 by novakurniawan I don’t remember where I kept my hand-out about Anti Surge Control System. I got it from Pak Ismail Umar (If I am not wrong, before he was instrument engineer at COPI) when he taught my class on Kapita Selekta, Engineering Physics Dept ITB. What I understood was “surging is a phenomenon on compressor which mechanically compressor could not stand with that”. I mean if compressor has no problem with surging then no need instrument and control engineer to overcome the situation by creating a process control on the discharge of compressor. Nothing else I understand. However when time came, I got a real anti-surge control valves in my job then questions hang on my mind. Why does surging happen on the system? why couldn’t compressor deal with it? I need to find good novels to understand this effect not hand books, but I didn’t. I have a dream someday all technical aspect of engineering shall be explained and described like novels. No more engineering handbooks only novels. Kompressor sentrifugal memiliki tiga parameter operasi yaitu: Speed, Head, dan Flow. Speed adalah kecepatan putar kompressor, Head adalah energi per berat dari kompressor (satuannya feet or meter satuan panjang, jadi bingung :p) untuk menaikkan pressure dari pressure inlet (Pin) menjadi pressure outlet (Pout), Flow adalah aliran fluid yang sedang ditransfer oleh kompressor. Kompressor sentrifugal dapat mencapai kondisi maksimum headnya pada speed tertentu, pada kondisi tersebut akan dilewatkan fluida dengan flow tertentu pula“. Pernyataan di atas disebut sebagai batas kondisi puncak/maksimum stabil dari kompressor. Nah, pada saat Headnya naik (artinya kira-kira Pout membesar) maka flowrate akan turun mengikuti Performance Curve dari kompressor tersebut. P-out membesar bisa jadi karena di pipa yang dialiri oleh discharge kompressor terdapat sumbatan, filternya kotor, atau mungkin juga baju ketinggalan di dalam pipa (ahh nggak mungkin ini), dll. Salah satu contoh Performance Curve dari kompressor adalah sebagai berikut:

Compressor Surging; Anti Surge Control

Embed Size (px)

DESCRIPTION

Compressor

Citation preview

Page 1: Compressor Surging; Anti Surge Control

8/27/13 Compressor Surging; Anti Surge Control | Comautoment Community

novakurniawan.wordpress.com/2010/06/22/compressor-surging-anti-surge-control/ 1/13

Comautoment Community

Compressor Surging; Anti Surge Control

Posted on June 22, 2010 by novakurniawanI don’t remember where I kept my hand-out about Anti Surge Control System. I got it from PakIsmail Umar (If I am not wrong, before he was instrument engineer at COPI) when he taught myclass on Kapita Selekta, Engineering Physics Dept ITB. What I understood was “surging is aphenomenon on compressor which mechanically compressor could not stand with that”. I mean ifcompressor has no problem with surging then no need instrument and control engineer to overcome

the situation by creating a process control on the discharge of compressor. Nothing else Iunderstand. However when time came, I got a real anti-surge control valves in my job thenquestions hang on my mind. Why does surging happen on the system? why couldn’t compressordeal with it? I need to find good novels to understand this effect not hand books, but I didn’t. I havea dream someday all technical aspect of engineering shall be explained and described like novels.No more engineering handbooks only novels.

Kompressor sentrifugal memiliki tiga parameter operasi yaitu: Speed, Head, dan Flow. Speedadalah kecepatan putar kompressor, Head adalah energi per berat dari kompressor (satuannyafeet or meter satuan panjang, jadi bingung :p) untuk menaikkan pressure dari pressure inlet (Pin)menjadi pressure outlet (Pout), Flow adalah aliran fluid yang sedang ditransfer oleh kompressor.

“Kompressor sentrifugal dapat mencapai kondisi maksimum headnya pada speed tertentu, pada kondisitersebut akan dilewatkan fluida dengan flow tertentu pula“. Pernyataan di atas disebut sebagaibatas kondisi puncak/maksimum stabil dari kompressor. Nah, pada saat Headnya naik (artinyakira-kira Pout membesar) maka flowrate akan turun mengikuti Performance Curve darikompressor tersebut. P-out membesar bisa jadi karena di pipa yang dialiri oleh dischargekompressor terdapat sumbatan, filternya kotor, atau mungkin juga baju ketinggalan di dalampipa (ahh nggak mungkin ini), dll. Salah satu contoh Performance Curve dari kompressor adalahsebagai berikut:

Page 2: Compressor Surging; Anti Surge Control

8/27/13 Compressor Surging; Anti Surge Control | Comautoment Community

novakurniawan.wordpress.com/2010/06/22/compressor-surging-anti-surge-control/ 2/13

(http://novakurniawan.files.wordpress.com/2010/06/performance-curve.jpg)

Gambar 1

Performance Curve di atas menghubungkan Isentropic Head vs Flowrate. Anyway karena padagambar di atas menggunkan istilah isentropic dan kata “isentropic” merupakan kata yang sakraldan susah dimengerti oleh orang biasa kaya saya, maka saya harus meninggalkan grafik diatas. Mari kita temukan performance curve yang lain yang serupa tetapi menggunakan hubunganCompression Ratio vs Flowrate (harapannya semoga lebih mudah). Ketemu Performance CurveCompressor seperti di bawah ini:

(http://novakurniawan.files.wordpress.com/2010/06/performance-curve1.jpg)

Gambar 2

Absisnya adalah Q1 (Flowrate) dan Ordinatnya adalah Rho = Pout/Pin. Sedangkan N1 dan N2adalah kecepatan putar dari kompresor (rpm). Nah garis melengkung ke atas itu adalah SurgeLine. Daerah di kanan surge line adalah daerah stabil kompresor, daerah di kiri surge line adalahdaerah tidak stabil. Grafik di atas dapat dibaca sebagai berikut: Ketika kompresor running denganspeed N1 kemudian Rho membesar (misal karena Pout membesar) maka Q1 akan mengecilmengikuti line N1 tersebut. Begitu grafik sampai di surge-line maka kestabilan kompressor akanterganggu. Kalau kestabilan kompressor terganggu apa dampak secara mechanical kepada

Page 3: Compressor Surging; Anti Surge Control

8/27/13 Compressor Surging; Anti Surge Control | Comautoment Community

novakurniawan.wordpress.com/2010/06/22/compressor-surging-anti-surge-control/ 3/13

kompressor? Let’s give it to mechanical engineer to explain, ambil intinya saja mechanical engineertidak ingin kompressornya masuk surging area. The duty of instrument engineer is to ensurethe plot point Rho againts Q1 is not in the surge area atau melintas di kiri surge line. It means

Q1 should not be allowed to dropRho should not be allowed to raise

Flow Q1 jangan sampai jatuh, artinya suction dan discharge harus bisa mengalirkan fluida padajumlah yang berada di kanan surge line-nya. Flow Q1 bisa jatuh karena suctionnya kekuranganflowrate atau juga bisa karena dischargenya kompressor di line downstreamnya ada sumbatanatau bahkan mungkin ada valve nutup. Atau kenapa lagi ya? Helm projek ketinggalan di dalam. Rho-nya (Pout / Pin) jangan sampai naik, gimana caranya? Pressure ini akan berperilaku seiringdan sejalan meski tak serupa dengan flowrate, bukan?. Kalau flowrate lancar tekanan dischargejuga tidak akan naik meninggi. Bayangkan saja kalau flowrate di discharge menjaditerganggu sampai mendekati mampet-pet, maka pressure akan naik dan Rho menjadi membesardan masuk dan melintasi surge line.

Solusinya bagaimana? Cara yang disampaikan oleh Robert C. White dan Rainer Kurz dalamartikel Surge Avoidance for Compressor System adalah schematic berikut:

(http://novakurniawan.files.wordpress.com/2010/06/antisurge.jpg)

Gambar 3

Penambahan pipa by-pass pada discharge compressor setelah cooler dan diumpankan balik kesuction compressor sebelum scrubber dan lajunya diatur oleh anti-surge control valve merupakankonsep pengendalian surge yang diperkenalkan.

Summary instrumentnya adalah suction compressor harus diketahui Pressure, Temperature, danFlow sedangkan pada discharge compressor harus diketahui Pressure dan Temperature. Ingat thefundamental law of process control is started by measurement. “The quality of process controlobtained can never be better than quality of measurement in which it is based” Bob Connel ProcessInstrumentation and Application Manual. Jadi biar tahu dan bisa mengendalikan denganbaik maka mengukurnya harus benar.

Anti-Surge Process Control menghimpun variabel dari transmitter-transmitter tersebut denganaccurate. Informasi tersebut dibandingkan dengan value normalnya yang bukan pada daerahsurging. Value normalnya adalah Rho-nya kecil dan Flow-nya besar pada titik yang jauh darisurge line. Jadi value normal tersebut adalah set-pointnya. Value dari transmitter harus dibawa

Page 4: Compressor Surging; Anti Surge Control

8/27/13 Compressor Surging; Anti Surge Control | Comautoment Community

novakurniawan.wordpress.com/2010/06/22/compressor-surging-anti-surge-control/ 4/13

menuju value normal dengan memanipulasi variable flowrate pada by-pass line. Ada 5 variabelyang berperan pada sistem anti-surge ini yaitu: pressure suction, temperature suction, pressuredischarge, temperature discharge dan flowrate. Dan hanya ada satu variable yang bisa dimainkanuntuk memuaskan ke-5 nya, yaitu flowrate by-pass line. Ibarat satu pekerja yang harus memenuhikebutuhan ke-5 nya secara bersamaan? bukan gantian. Mana mungkin?

Kita dihadapkan pada pertanyaan yang memerlukan solusi dari seorang I&C Engineer. Ada 5proses variabel, dan hanya ada 1 manipulated variabel, what are you going to do to control themall? what kind of control loops are you going to develope to control them all?

Yang mula-mula pertama adalah menentukan interlock systemnya. Pada saat kapan kompresorharus mati karena kondisi yang sudah tidak terkendali. Interlocknya bisa berasal dari process valueyang 5 di atas itu (dah jelas kan?), bisa juga mekanisme internal dari kompressor, atau suroundingsystem. Mekanisme internal yang saya maksud misalnya karena vibrasi, internal cooling system,dan faktor fueling sistem. Surounding system adalah kondisi lingkungan yang berpengaruh yangberasal dari fire and gas detection system. However, interlock system bukanlah kontrol sistem tapilebih tepat disebut sebagai safety sistem. Tujuannya adalah untuk menyelamatkan.

Kembali ke sistem kontrolnya maka akan ada 2 loops yang didesain untuk mengendalikansurging. Loop pertama disebut anti-surge control loop dan loop ke dua disebut process control loop.Ada 2 loop dengan satu control valve pada by-pass line, bagaimana mengakurkan ke-dua looptersebut? Diakurkan dengan salah satu bisa mengoveride yang lain jika dan hanya jika, selamaoveride berlangsung tidak membahayakan loop yang dioveride. Loop yang dioveride harussemakin aman ketika ditake-over, artinya dibuat tidak berfungsi dalam kondisi aman. Kedua loopakan memerintahkan satu anti-surge control valve untuk beraksi secara bergantian.

Anti Surge Control Valve dipasang pada by-pass line apakah fail-open atau fail-close? Penentuanfail-open atau fail-close control valve berdasarkan pertimbangan sistem harus berada pada kondisilow-energi pada saat ada kejadian fail. Low energy dapat diartikan sebagai kondisi aman.Misalkan kejadian terburuk terjadi yaitu pada downstrean kompresor pipanya tersumbat makapressure discharge akan naik drastis (danger). Kondisi akan aman jika by-pass line terbuka artinyaanti surge control valve terbuka sehingga fluida pada discharge direcycle kembali ke suctionsehingga kompressor tetap aman. Dengan evaluasi ini dapat disimpulkan bahwa kondisi failcontrol valve yang paling aman pada line by-pass adalah fail-open.

Loop yang pertama adalah Anti Surge Control Loop; yang merangkai loop flow variable-controller-control valve. Fungsi dari loop ini adalah mengendalikan flowrate yang melalui kompresor agartetap pada normal operasinya. Flow yang semakin lambat menyebabkan aliran makin menujumampet. Aliran mampet pressure discharge jadi tinggi dan lebih tinggi lagi….and then danger.Flow dimainkan dengan mengendalikan by-pass line. Kalau memang pada pipa downstreamsetelah cooler terjadi problem (mampat misalnya) maka dengan mengatur control valve pada by-pass untuk membuka penuh maka aliran akan tetap bersirkulasi. Kompresor aman. Berapa nilaiflow yang aman dan stabil? jawaban mudahnya sesuai dengan Gambar.2 yaitu ketika Q1 disebelah kanan surge line. Nah, nilai normal Q1 bisa menjadi multi-value tergantung nilai Rho-nya.Bagaimana menentukan set-point aman flowrate Q1? Saya tidak tau bagaimana cara praktisnya dilapangan atau manual yang direkomendasikan company.

Berdasarkan teori, intuisi, penerawangan, dan common sense saja bahwa kompresor memilikirange flowrate Max-Min (mmscfd). Dan set-point flowrate diambil value diantara itu (Yaa…jelaslah jreng). Katakanlah set-point X mmscfd. Nah, ketika flowrate jatuh di bawah X mmscfd maka

Page 5: Compressor Surging; Anti Surge Control

8/27/13 Compressor Surging; Anti Surge Control | Comautoment Community

novakurniawan.wordpress.com/2010/06/22/compressor-surging-anti-surge-control/ 5/13

logikanya by-pass line harus membuka. Ketika flow normal di atas X mmscfd maka by-pass lineharus menutup. Jadi line by-pass itu normalnya tertutup, artinya control valve-nya normalnyatertutup. Control Valve membuka ketika kondisi tidak normal. Apakah PID calculation yangdigunakan? yang continuously menghitung perbedaan flow actual dengan set-point X danmemerintahkan aksi ke control valve. Atau menggunakan sistem yang lain yaitu signaling-pulsayaitu kalau flow actual menyentuh nilai minimal N% maka controller memberikan pulsa-signal kecontrol valve untuk membuka M%.

Loop yang ke dua adalah Process Control Loop; yang merangkai loop pressure suction, pressuredischarge-controller-control valve. Jika suction pressure jatuh maka control valve harus membuka,jika suction pressure terlalu tinggi maka nggak apa-apa. Jika discharge pressure terlalu tinggi makacontrol valve mulai membuka mengurangi pressurenya dengan membalikkan fluidanya, jikapressurenya terlalu rendah maka nggak apa-apa.

Apakah ke-dua loop ini tidak bentrok? Pasti bentrok karena variable yang hendak dikontrol adadua (pressure dan flow), sedangkan yang dimanipulasi ada satu (aliran feedback yang dikontrolpakai control valve). Biar gak bentrok maka pakai override control. Loop yang lebih critical meng-overide loop yang tidak kritikal. Caranya? Dua loop itu masing-masing melakukan kalkulasi PIDdan mengeluarkan signal aksi yang dilenearisasikan ke 4-20 mA. Dengan kondisi valve fail-openmaka 4-fully open dan 20 fully closed. Dengan logika bahwa open itu aman maka loop yangmemerintahkan signal “lebih aman” harus diikuti untuk mengoveride signal yang kurang aman.Contoh: Loop antisurge control menghasilkan perhitungan PID dan memberikan signal 10 mA,sedangkan loop proses control menghasilkan perhitungan PID dan memberikan signal 6 mA makaloop ke dua harus mengoveride loop pertama. Karena loop ke-dua lebih kritikal memerlukanbukaan yang lebih lebar. Overide-nya menggunakan tanda “>” atau “<” tergantungprogrammernya.

Selain ke-dua control di atas (anti-surge dan process control), untuk keperluan safety kompressorjuga dilengkapi dengan safety interlock system untuk kondisi kritikal flow low-low, pressure hi-hi,yang langsung terhubungn ke system shutdown yang memutus supply elektrikal power kekompressor. This the last option shall be taken.

just only what i know

Nova Kurniawan

You May Like

1.

Filed under: Engineering

About these ads (http://en.wordpress.com/about-these-ads/)

Page 6: Compressor Surging; Anti Surge Control

8/27/13 Compressor Surging; Anti Surge Control | Comautoment Community

novakurniawan.wordpress.com/2010/06/22/compressor-surging-anti-surge-control/ 6/13

« Motor Control; Electrical or Instrument It is a Head; Go A Head »

25 Responses

ikhsan anugrah, on June 24, 2010 at 11:17 pm said:th atas share nya ttg antisurge

mas nova, pada performance curve ratio specific head tu apa? perbandingan pressure dischargedengan suction nya?

jadi yang dipake untuk performance curve itu sebenarnya ratio Pd/Ps terhadah flow suctionatau Head isentropic (pressure suction?) terhadap flow suction???

Reply

novakurniawan, on June 29, 2010 at 12:23 am said:Mas Anugrah,

Specific Heat maksutnya? Menurut pendapat saya, itu Cp/Cv dari fluid yang dikompresyang besarnya 1.255. Data yang di atas tabel itu data untuk case fluid yang dijadikan acuanperformance curve.

Performance Curve menggunakan Isentropic Head thd Flow accross (btw flow suction =flow discharge continuity mass law. Kalau nggak sama flownya dibuang ke mana?)

“Isentropic head is defined as the energy per mass unit accumulated by the fluid subsequentto a reversible (and thus isentropic) adiabatic transformation between states 1 and 2″.

Sepertinya perlu saya pelajari and tulis special ttg Head.

Reply

ikhsan anugrah, on June 25, 2010 at 10:47 pm said:waah hand out nya tentang anti surge control system nya menarik tuh, dibeli dimana mashehe..

Reply

novakurniawan, on June 29, 2010 at 1:37 am said:Hand-out kuliah… dari yang ngajar. Tapi sudah hilang…

Reply

ikhsan anugrah, on June 29, 2010 at 5:03 pm said:wahhh benar mas nova.. mungkin perlu nulis tentang head juga. hehe ::D

Page 7: Compressor Surging; Anti Surge Control

8/27/13 Compressor Surging; Anti Surge Control | Comautoment Community

novakurniawan.wordpress.com/2010/06/22/compressor-surging-anti-surge-control/ 7/13

Reply

juare97, on July 23, 2010 at 12:48 am said:nov,Untuk yang surge pake yang gambar ke-2.untuk compressor solar turbine yang menggunakan HMI TT2000/TT4000 ada tampilan graphicXY plotnya.Ada 3 garis yang tergambar di XY Plot tsb yaitu Surge Line, Control Line dan Deadband Line.Dan ada semacam XY Plot berbentuk Tanda “+” merepresentasikan Suction Flow DP (Sb-X) &Compressor DP (Sb-Y).Yang paling bagus bila Plot ini ada disebelah kanan.

Kalau terjadi Surge maka dampaknya Compressornya akan rusak. Karena akan ada pressurebalik dari Discharge menuju Suction yang tidak bisa dilawan Compressor. Bisa vibrasi dan bisamenyebabkan kerusakan di compressornya. CMMIW.

Sehingga untuk mengantisipasi dipasang Control Valve Anti surge. Untuk lebih detailnya,kalau punya manual Solar Compressor Centaur 40 bisa tuh dibaca-baca.

Selain itu ada proteksi Vibrasi. Kalau sempat compressor bergetar melebih set pointShutdownnya maka compressor akan shutdown juga.

berikut yang saya cuplik dari manualnya Solar Turbines Centaur 40 yang kami punya(kebetulan masih belajar juga mengenai AntiSurge ini):

Gas Compressor Surge———————————Certain operating conditions may lead to gas compressor surge. Indications of surge vary fromminor compressor speed fluctuations to severe compressor speed oscillations with noise andvibration of station piping.

Compressor surge may occur with the unit operating at an intermediate power level because of apipeline condition change such as a reduced flow to the compressor or increased pressure ratioacross the compressor.

Antisurge Control System———————————-The antisurge control system prevents compressor surge by recycling process gas, reducing headand increasing flow through the compressor.

The antisurge control system consists of pressure transmitters and temperature detectors at thesuction and discharge sides of the compressor, a flow transmitter across the suction line orifice,an algorithm in the control system, and a recycle control valve with accessories.

When conditions fall below the surge protection margin, the control system opens the recyclevalve. When conditions return to greater than the surge protection margin, the control systemcloses the recycle valve.

The antisurge system monitors:

Page 8: Compressor Surging; Anti Surge Control

8/27/13 Compressor Surging; Anti Surge Control | Comautoment Community

novakurniawan.wordpress.com/2010/06/22/compressor-surging-anti-surge-control/ 8/13

The antisurge system monitors:- Pressure drop across a flow measuring element (hw)- Suction and discharge pressures (P2 and P1)- Suction and discharge temperatures (T2 and T1)

SURGE DETECTOR—————————The surge detector operates as part of the antisurge system. The differential pressure across theflow orifice is used to compute the rate-of-decrease of flow through the compressor and iscompared to a preset value. If the maximum value exceeds the minimum value by a presetamount (typically 25 percent), one pulse is counted, and the recycle valve is opened 20 percent. Iffive pulses occur within ten seconds, the engine is shut down and a message indicating that thecompressor is in surge appears on the display terminal.

SYSTEM OPERATION——————————The antisurge control loop is disabled until engine speed is greater than a preset value. Below thisvalue, the recycle control valve is fully open to allow maximum gas flow through thecompressor.

Above loading speed, the antisurge control system is enabled and the recycle valve can be closed.Pressures and temperatures in the suction and discharge lines are measured and head across thecompressor is calculated. Flow through the compressor is determined by measuring pressuredrop across an orifice in the suction line, discharge line, or compressor impeller eye. Signals fromthese transmitters are processed by the control system. If the surge margin falls below a presetvalue, the signal to the recycle valve is reduced. The recycle valve opens a fraction proportionalto the signal value. With the valve opened, a portion of the gas from the discharge side of thecompressor is routed back to the suction side, and flow through the compressor increases. Whenthe condition that caused the antisurge action disappears, the recycle control valve closes and thecompressor resumes normal operation.

DISPLAY————This section describes the techniques typically used to construct the antisurge control displayscreen.

On the left of the screen, operating mode, operating conditions, setpoint, valve position andengine speed are displayed.

On the right of the screen is an X:Y plot showing surge limits and operating point. For display, Xand Y values are converted to percentages. A white cross defining a point, X, Y, shows theoperating point. Plus and minus one (1) are added to the operating point Y, providing Y′ and Y′′. X′ and X′′ are then calculated using the polynomial equation providing Y′ and Y′′. X′ Y′ and X′′, Y′′are two points at the surge limit.

The displayed surge limit takes the form:

Y = MX + B

where

Page 9: Compressor Surging; Anti Surge Control

8/27/13 Compressor Surging; Anti Surge Control | Comautoment Community

novakurniawan.wordpress.com/2010/06/22/compressor-surging-anti-surge-control/ 9/13

where(X′ – X′′)/(Y′ – Y′′) = MB = Y’ – MX’M = KSL = slope of the surge lineB = SLB = Y intercept for KSL, KCL, AND KDB

The following three lines are displayed on the screen:

KSL = slope of surge limit, SURGE LINE,KCL = slope of the control line, CONTROL LINE,KDB = slope of the deadband line, DEADBAND LINE,

whereKCL = KSL times 1 plus desired protection marginKDB = KCL times 1 plus desired deadband width

PROCESS CONTROL WITH ANTISURGE VALVE CONTROLLER——————————————————————–Antisurge valve control consists of two loops: antisurge and process control.

Under antisurge control, the compressor flow variable value is compared to the compressor linesetpoint. If the flow factor is less than the setpoint, the antisurge valve is quickly opened until theflow is greater than the control line setpoint. If the flow factor is greater than the setpoint, theantisurge valve is slowly closed until it reaches the fully closed position, or until the operatingpoint contacts the deadband line at which point the valve holds its position.

Under process control, if the compressor suction pressures drop below their setpoints minus anoffset, or if the compressor discharge pressure exceeds its setpoint plus an offset, the antisurgevalve opens. This action increases the suction pressure and reduces the discharge pressure so thatthe unit does not shut down because of low suction pressure or high discharge pressure. Theoffsets are adjustable through the program constants display.

The antisurge valve is normally controlled by the surge margin control loop. However, if theprocess control loop demands the valve be open more than the surge margin control loop,process control overrides the surge margin loop. The control loop requiring the more open valveposition controls the valve position.

Reply

novakurniawan, on July 24, 2010 at 12:15 am said:Mantab Jun, tapi agak pusing untuk menafsirkan manual di atas menjadi novel kalau tanpamelihat schematic dan grafik yang dimaksud. Kirim dong Schematic P&ID-nya dan Grafikyang memuat semua simbol di atas pakai email. Thanks

Reply

juare97, on July 27, 2010 at 11:21 pm said:

sama nov .. gw lihatnya juga pusing … pa lagi lihat program laddernya …. masih belum

Page 10: Compressor Surging; Anti Surge Control

8/27/13 Compressor Surging; Anti Surge Control | Comautoment Community

novakurniawan.wordpress.com/2010/06/22/compressor-surging-anti-surge-control/ 10/13

sama nov .. gw lihatnya juga pusing … pa lagi lihat program laddernya …. masih belumintensive belajarnya ….insyaAllah nanti gw kirimin gambarnya deh ….tapi sih peraturannya kalau mau publish tempat umum (blog) apakah perlu ditambahincourtesy solar turbine gitu kah soalnya ada hak ciptanya tuh.

ikhsan anugrah, on July 24, 2010 at 3:54 am said:mas juare 97, kelihatannya artikelnya bagus, tapi saya kurang paham ketika memasukipertengahan, hehe..mungkin perlu gambar skematik yang jelas seperti kata mas [email protected]

Reply

juare97, on July 27, 2010 at 11:59 pm said:nanti biar mas nova saja yang publish yah …

Reply

ikhsan anugrah, on July 24, 2010 at 3:56 am said:mas nova, dari artikel mas,HEAD punya satuan dalam meter, how it can, katanya head itu energi atau gaya..mumeng ki, hehe

Reply

novakurniawan, on July 28, 2010 at 3:26 am said:Ntar gambarnya gw bikin sendiri dengan perubahan, karena kalo manual seharusnya rahasiaperusahaan dong. Lha wong dia yang nyiptain sistemnya.

Reply

ikhsan anugrah, on July 29, 2010 at 2:05 pm said:Mas, sewaktu sy kerja praktek, sering banget denger kata2 kompensasi flowrate d topik antisurge kompresor. Sebenerny kompensasi flowrate itu apaan sih. Thx.

Reply

al, on March 6, 2011 at 12:58 pm said:Try include nos as an example for the compression ratio/flow on the performance curve forbetter understanding.

Reply

Page 11: Compressor Surging; Anti Surge Control

8/27/13 Compressor Surging; Anti Surge Control | Comautoment Community

novakurniawan.wordpress.com/2010/06/22/compressor-surging-anti-surge-control/ 11/13

Andy Odank, on January 5, 2012 at 8:09 am said:ada tidak hubungannya antara rpm engine (power) dengan anti surge control valve. Bisa gakkalau kita ingin supaya control valve menutup penuh, maka kita harus setting suction pressureagar control valve fully closed.

Reply

juare97, on January 13, 2012 at 11:30 pm said:kalau di Compressor Solar ada tuh, Anti Surge Control Valve akan terus membuka 100%sampai tercapai NGP Speed > 85% dan NPT Speed > 50%. Setelah ini maka Sistem AntiSurge Control akan bekerja.

Anti Surge Control bekerja berdasarkan parameter berikut:- Suction Press. (P1)- Discharge Press.(P2)- Suction Temp. (T1)- Discharge Temp. (T2)- Flow (DP / Hx)

Jadi tidak hanya melihat Suction Pressure saja.

Reply

basori, on March 18, 2012 at 12:30 am said:selamat pagi bos…aq ingin tanya tentang kompressor yg pake system ES 100..kami pake atlascopco..instrument air 2 paket..kami sering dpt masalh comprsr yg leading sering jd lagging..njug sering terjdi 1 comprsr isolated sendiri…es100 merpkn alat yg dipake utk sequence aja..aqtunggu infonya bos…thanks…

Reply

novakurniawan, on March 19, 2012 at 1:14 am said:Lead and Lag dimanage oleh control system. Pelajari dulu logic-nya ES100 itu. Berupa apaitu ES100? kalau PLC, kawan saya Juni Ardi Irawan yg comment di atas itu insyaAllah bisabantu.

Reply

basori, on March 18, 2012 at 1:27 am said:tambahan bos…kami disini pake komprssr screw…bukan sentrfgl…

Reply

iman kustaman, on November 13, 2012 at 7:07 am said:terima kasih saya saja yang lagi nyari tentang anti surge (buat bahan interview) langsung adagambaran, thanks a lot.Anyway, saya setuju untuk dibuatkan novel instrumentation, malah saya punya ide untuk buat

Page 12: Compressor Surging; Anti Surge Control

8/27/13 Compressor Surging; Anti Surge Control | Comautoment Community

novakurniawan.wordpress.com/2010/06/22/compressor-surging-anti-surge-control/ 12/13

komik instrument seperti komik fisika yang sudah ada.

Reply

weni nuraeni, on January 12, 2013 at 10:13 am said:maaf pak……cara membuat kurva surge limit nya gimana ya pak? kita dapatkan data2nya dari mana?mksh pak

Reply

novakurniawan, on January 22, 2013 at 12:05 am said:manufacture yang provide data surge limitnya. cara bikinnya mungkin lebih baik tanya kevendor compressor ya

Reply

Hardy Ferrysian, on March 3, 2013 at 7:18 am said:mas Nova kurniawan, artikel yang sangat menarik terimaksih sudah mau berbagi.waktu saya kerja praktek di industri migas, anti-surge controlnya masih berupa control local(lupa nama vendornya) belum terinterasi dengan kendali terpusat seperti DCS, padahal semuakomponen diplant sudah integrasi dengan DCS.apakah anti-surge controller tidak bisa ditangani dengan DCS ?misal DCS centum CS3000 dari yokogawa.

mohon bantuannya.salam.

Reply

Adi Wicaksono, on June 20, 2013 at 3:24 am said:Mas Ferry,Sedikit membantu saja, kadang di suatu plant memang terdiri dari beberapa subsistem.Dan dari beberapa subsistem ini ada beberapa yang rumit (sehingga diperlukan localcontrol yang biasanya kita serahkan ke Vendor paketnya masing2 untuk membuat controllogicnya) dan ada subsistem yang mudah dan bisa dikontrol langsung dari DCS. Nahuntuk antisurge control yang biasanya digunakan untuk memproteksi paket compressor,dibutuhkan teori dan pemahaman yang detail tentang surge characteristic compressortersebut dan ini hanya dikuasai oleh si Vendor compressor. Oleh karenanya antisurgecontrolnya biasanya dikerjakan oleh si Vendor langsung, namun kita bisa mita agar siVendor memberikan link supaya DCS masih bisa menerima reading input dari pakettersebut.

Reply

juare97, on July 16, 2013 at 12:22 am said:setuju sama mas Adi …

Page 13: Compressor Surging; Anti Surge Control

8/27/13 Compressor Surging; Anti Surge Control | Comautoment Community

novakurniawan.wordpress.com/2010/06/22/compressor-surging-anti-surge-control/ 13/13

sediit menambahkan…

kalau dipaksakan dimasukkan ke DCS saya kurang yakin DCS bisa handle Anti SurgeControl .. butuh aksinya dalam milisecond .. apabila terjadi surge harus cepat aksinya.Sedangkan DCS kan handle process control dengan banyak sekali Input Output (I/O)nya.. .

Anti Surge Control mengontrol Control Valvenya dengan mempertimbangkanperubahan nilai P1, P2, T1, T2, FT terhadap kurva surge compressor itu sendiri.Detailnya bisa dilihat di user manual Compressor tsb. Untuk Solar Turbine Compressormanualnya lengkap. Dan kalau punya HMI TT4000 nya bisa dilihat kurvanya danbagaimana plot XY nya (Flow dan Head) bekerja di surge map tsb.Kalau mau lihat logicnya bisa buka program PLC nya.