Concrete encased electrode 2 0 0 Main 20’ 250.8 NEC “Equipment Grounding Conductors, grounding electrode conductors and bonding jumpers shall be connected by one or more of the following means”. 4 AWG 250.52(A)(3) 15 15 15 15 20 20 20 20 20 15 30 30 20 20 60 60 15 15 2 0 0 Copyright Kenny Clamp LLC January 2014 Improved Kenny Clamp ® Grounding and Bonding Connector 312.5(A) NEC “Openings through which conductors enter shall be closed in an approved manner” Complies with the UL 467 Standard for “Grounding and Bonding Equipment” and the UL White Book requirements Kenny Clamp Phone 410-741-9551 E-mail [email protected] Patent No. 7595455

Concrete encased electrode 200200 Main 20’ 250.8 NEC “Equipment Grounding Conductors, grounding electrode conductors and bonding jumpers shall be connected

Embed Size (px)

Citation preview

Page 1: Concrete encased electrode 200200 Main 20’ 250.8 NEC “Equipment Grounding Conductors, grounding electrode conductors and bonding jumpers shall be connected

Concrete encased electrode

200Main

20’

250.8 NEC “Equipment Grounding Conductors, grounding electrode conductors and bonding jumpers shall be connected by one or more of the following means”.

4 AWG250.52(A)(3)

15 15

15 15

20 20

20 20

20

15

30 30

2020

60 60

1515

200

Copyright Kenny Clamp LLC January 2014

Improved Kenny Clamp®

Grounding and Bonding Connector

312.5(A) NEC “Openings through which conductors enter shall be closed in an approved manner”

Complies with the UL 467 Standard for“Grounding and Bonding Equipment” and the UL White Book requirements

Kenny Clamp

Phone 410-741-9551

E-mail [email protected]

US Patent No. 7595455

Page 2: Concrete encased electrode 200200 Main 20’ 250.8 NEC “Equipment Grounding Conductors, grounding electrode conductors and bonding jumpers shall be connected

Main

15 15

15 15

20 20

20 20 20 15

30 30

2020

60 60

1515

200

[email protected]

H20 pipe

Kenny Clamp® Grounding and Bonding Connector

250.66 NEC®

250.53 (D)(2) 6 AWG

250.52 (A)(1)

310.15(B)(7) &T-310.15 (B)(16)2/0 XHHW CU

6 AWG Improved Kenny Clamp

4 AWG

10’ Direct contact with earth

Ground Rod

312.5(A) NEC “Openings through which conductors enter shall be closed in an approved manner”

Complies with the UL 467 Standard for “Grounding and Bonding Equipment” and the UL White Book requirements

Complies with the UL 486(A) Connector Standard

Phone 410-741-9551Fax 410-741-1240

200

US Patent No. 7595455

Page 3: Concrete encased electrode 200200 Main 20’ 250.8 NEC “Equipment Grounding Conductors, grounding electrode conductors and bonding jumpers shall be connected

33

600 VoltRated

XO H1 H2 H3 X1

X2

X3

75 KVA

Main

Structural Steel

Water pipe

Copyright © 2014 Wayne H. Robinson SeminarsCopyright © 2014 Wayne H. Robinson Seminars

Kenny Clamp®

Selection of the Kenny Clamp ® Grounding and Bonding Connector For Separately Derived Systems

Phone 410-741-9551E-mail [email protected]

US Patent No. 7595455

Improved Kenny Clamp ®2 AWG ConnectorNEC® 250.8, 312.5(A)UL 467 & UL 486(A) Standards

100 Ampere fuses

4/0 CuTHW 750 Cderived phase conductors

225 Ampere Main Breaker Panelboard

3 AWG CuTHW 750Cconductors

250.104 (D)(1)

Fax 410-741-1240

Page 4: Concrete encased electrode 200200 Main 20’ 250.8 NEC “Equipment Grounding Conductors, grounding electrode conductors and bonding jumpers shall be connected

KENNY CLAMP®

Grounded Conductor

C phase

A phase

B phase

Grounding Bar

Water Pipe

3/0 Grounding Electrode Conductor

Patented Improved Kenny Clamp® Connector

1200 ampere Switch Board

250.64 (E)(1)

Labor SavingNo need to installthe 3/0 conductorthru a bond bushing

First 5 feet

Rigid Metal ConduitCopyright © Kenny Clamp LLC January 2014

Phone 410-741-9551Fax 410-741-1240

E-mail [email protected]

US Patent No. 7595455

Page 5: Concrete encased electrode 200200 Main 20’ 250.8 NEC “Equipment Grounding Conductors, grounding electrode conductors and bonding jumpers shall be connected

Fire Pump Connection to Service Rated Fire Pump

Controller

Service Rated Fire Pump Controller

20’

5’

Pressure MaintenanceJockey or Make-up PumpFed from separate source

Meter or CTCabinet

UtilityTransformer

Grounded ConductorBrought to Service

Equipment250.24(C) NEC

GroundingElectrode

Conductors250.52(A)(1)

NEC

250.52(A)(3) NEC

Service Conductors

Fire Pump Room

Kenny ClampGrounding and

Bonding Connector

Branch Circuit Conductors Rated @ 125% of

Fire Pump FLC Rating430.22 NEC

Kenny Clamp® Grounding and Bonding ConnectorPhone 410-741-9551 Fax 410-741-1240

US Patent No. 7595455

E-mail [email protected]

NFPA 20Locked RotorOvercurrentProtection

10.4.4

Page 6: Concrete encased electrode 200200 Main 20’ 250.8 NEC “Equipment Grounding Conductors, grounding electrode conductors and bonding jumpers shall be connected

Main

15 15

20 20

20 20

20 15

30 30

20 20

60 60

15 15

200

[email protected]

H20 pipe

400Ampere

Tran-socket

5’

Water Meter

Kenny Clamp ® Grounding and Bonding

Connector

Kenny Clamp®

600KCMIL

1/0 AWG 250.66 Connector

200 Ampere Fuses

6 AWG

400 ANeutralBuss

1/0 T-250.102(C)(1)Supply-sideBondingJumper

3/0 THW

Phone 410-741-9551Fax 410-741-1240

US Patent No. 7595455

Page 7: Concrete encased electrode 200200 Main 20’ 250.8 NEC “Equipment Grounding Conductors, grounding electrode conductors and bonding jumpers shall be connected

225

22225

Neutral Terminal Block

225

500 KCMIL CU 4/0 CU

225 A OCPD

1/0Supply-Side

Bonding JumperTypical

Main Bonding Jumper2 AWG

225

Copyright © 2014 Wayne H. Robinson SeminarsCopyright © 2014 Wayne H. Robinson Seminars

Kenny Clamp® Grounding and Bonding ConnectorPhone 410-741-9551 Fax 410-741-1240

[email protected]

Page 8: Concrete encased electrode 200200 Main 20’ 250.8 NEC “Equipment Grounding Conductors, grounding electrode conductors and bonding jumpers shall be connected

Concrete encased electrode

20’

MAIN 200

1515

15

2020

15

20 20

3030

5050

KENNY CLAMP ®

GROUNDING AND BONDING CONNECTOR

E-mail [email protected]

2/0 copper310.15(B)(16)& 310.15(B)(7)

4 AWG250.52(A)(3)NEC

Complies withUL 467 Grounding and Bonding Standard

Ph 410-741-9551

Fax 410-741-1240

US Patent No. 7595455

312.5(A) NEC “Openings through which conductors enter shall be closed in an approved manner”

250.8 NEC “Equipment Grounding Conductors, grounding electrode conductors and bonding jumpers shall be connected by one or more of the following means”.