Conettix Plug-in Communicator Interface B450 en Installation and Operation Guide

Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Conettix Plug-in Communicator InterfaceB450

en Installation and Operation Guide

Page 2: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control
Page 3: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Table of contents

1 Safety 42 Introduction 52.1 About documentation 52.2 Bosch Security Systems, Inc. product manufacturing dates 52.3 Installation workflow 6

3 System overview 73.1 Module overview 83.2 B450 cellular interface compatibility 93.3 Bus address settings overview 9

4 Installation 114.1 Setting the bus address 114.2 Insert the communication module 124.2.1 Insert the B44x communication module (required and available separately) 134.2.2 Insert the B44x communication module with SIM card (required and available

separately)13

4.3 Mount the module in the enclosure 144.3.1 Mount and wire the tamper switch (option for SDI2 bus only) 154.4 Install and mount the plug-in communicator antenna 164.5 Wire to the control panel 164.5.1 Wire to an SDI2 control panel 174.5.2 Wire to an SDI control panel 184.5.3 Wire to an option bus control panel 19

5 Configuration 205.1 Configuration for SDI2 control panels 205.1.1 Configuring and viewing status from RPS 205.2 Use USB to configure the B450 265.2.1 Install a communication program 285.2.2 Log into the USB interface 325.2.3 USB Main menu 345.2.4 USB menu structure 355.2.5 USB menu 365.3 Short Message Service (SMS) configuration 495.3.1 Use SMS to configure the B450 495.4 Firmware Update page 52

6 Maintenance and troubleshooting 566.1 USB menu access disabled 566.2 LED status indicators 566.3 Show the firmware version 606.4 SIM card 606.5 Diagnostic log 606.6 Understanding network polling 616.7 Control panel programming using cellular 61

7 Specifictions and certifications 627.1 Technical specification 627.2 Certifications 64

Conettix Plug-in CommunicatorInterface

Table of Contents | en 3

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 4: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

SafetyESD Precaution

Please note that while the B450 comes in a plastic case, and is protected from ESD, the plug-in cellular communicator (B44x) does not. All plug-in cellular communicator components maypotentially be exposed to finger touches - therefore extra attention must be paid to ESD(electrostatic discharge) precaution. Make sure there is no static interference when using theboard. Appropriate ESD protections must be taken and wearing electrostatic equipment isrecommended, such as anti-static wrist strap.ESD damage can range from subtle performance degradation to complete device failure.Precision integrated circuits may be more susceptible to damage because very smallparametric changes could cause the device not to meet its published specifications.

!

Warning!

Failure to follow these instructions can result in a failure to initiate alarm conditions. Bosch

Security Systems, Inc. is not responsible for improperly installed, tested, or maintained

devices. Follow these instructions to avoid personal injury and damage to the equipment.

Notice!

Inform the operator and the local authority having jurisdiction (AHJ) before installing the

module in an existing system.

Disconnect all power to the control panel before installing the module.

1

4 en | SafetyConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 5: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

IntroductionThis document supports the B450 with firmware version v3.02

About documentationCopyrightThis document is the intellectual property of Bosch Security Systems, Inc. and is protected bycopyright. All rights reserved.

TrademarksAll hardware and software product names used in this document are likely to be registeredtrademarks and must be treated accordingly.

Bosch Security Systems, Inc. product manufacturing datesUse the serial number located on the product label and refer to the Bosch Security Systems,Inc. website at http://www.boschsecurity.com/datecodes/.

2

2.1

2.2

Conettix Plug-in CommunicatorInterface

Introduction | en 5

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 6: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Installation workflowTo install and configure the module, use the workflow below and follow in sequential orderfrom top to bottom, checking off each box as you complete a step.

!

Caution!

Always power down the control panel when connecting a module. To power down the control

panel, unplug the transformer and disconnect the battery.

Plan the installation of the B450 Conettix Plug-in Communicator Interface

Unpack the device contents

Power down the system

Select the bus address value for the compatible control panel (This will automaticallyconfigure the module to work with a compatible control panel. Refer to Setting the busaddress, page 11)

Insert the desired plug-in communicator into the B450 (Refer to Insert the communicationmodule, page 12)

Mount the B450 into the enclosure (Refer to Mount the module in the enclosure, page 14)

Wire the B450 to a compatible control panel (Refer to Wire to the control panel, page 16)

Power up the system

Install a communication program (if required) (Refer to Install a communication program,page 28)

Configure the communication module (non SDI2 control panels)

Verify LED activity

Review signal strength on the cellular communicator. Refer to your cellular communicatorInstallation Guide for more information on signal strength.

Installation is complete

2.3

6 en | IntroductionConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 7: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

System overviewRefer to the graphic below for the complete B450 system configuration.

1

2

7

5

6

3

4

13

12

11

8

14

9

10

B450 system connections overview

Callout ᅳ Description Callout ᅳ Description

1 ᅳ Compatible Bosch control panel 8 ᅳ Ethernet network connectionbetween the host computer Ethernetnetwork interface card (NIC) and theEthernet network

2 ᅳ Data bus connection between the controlpanel and the B450 module

9 ᅳ Host PC running RemoteProgramming Software, Automation, orConettix D6200 Programming/Administration Software

3 ᅳ B450 10 ᅳ Conettix D6100i CommunicationsReceiver/Gateway and/or ConettixD6600 Communications Receiver/Gateway (Conettix D6600Communications Receiver/Gatewayrequires 11, 12, and 13)

4 ᅳ USB direct connection for B450configuration (if required)

11 ᅳ Ethernet network connection tothe Ethernet adapter (D6680/ITS-D6682/ITS-D6686) (ITS-D6682 shown)Ethernet Network Adapter

5 ᅳ B44x Plug-in Cellular Communicator(required and available separately)

12 ᅳ Conettix Ethernet NetworkAdapter (ITS-D6682 shown)

3

Conettix Plug-in CommunicatorInterface

System overview | en 7

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 8: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

6 ᅳ Cellular carrier network 13 ᅳ Connection from ITS-D6682 to theCOM4 Port on the Conettix D6600Communications Receiver/Gateway

7 ᅳ Internet 14 ᅳ Ethernet network connection tothe D6100i Communications Receiver(D6100i/D6100IPv6)

Module overviewThe B450 Conettix Plug-in Communicator Interface (wired to a compatible control panel) is afour-wire powered SDI2, or SDI device that provides two-way communication over commercialcellular networks using a plug-in communicator. The B450 Conettix Plug-in Communicator Interface bus address switch determines the busaddress of the device. When required, configuration of the module is managed through thecontrol panel, a local USB connection, or using SMS.

B450 module overview

1

8 6 2

9

10

37 5 4

TX RX

Figure 3.1: B450 Plug-in Communicator Interface

Callout ᅳ Description

1 ᅳ Tamper switch connector

2 ᅳ Bus address switch

3 ᅳ MODE 2-pin jumper connector (for future use)

4 ᅳ Bus address label

5 ᅳ USB connector (Type A)

6 ᅳ Heartbeat LED

7 ᅳ RX LED (indicates packets received from the wireless network)

3.1

8 en | System overviewConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 9: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

8 ᅳ TX LED (indicates packets transmitted over the wireless network)

9 ᅳ Terminal strip (to control panel)

10 ᅳ Interconnect wiring connectors (to control panel or other compatible modules)

B450 cellular interface compatibilityThe B450 supports multiple bus types. Use the following table to determine the supportedapplications and features by bus type. the following table for supporting compatibilityapplications.

Installed Bus

Function Option/SDI SDI2 Details

IP Event Reporting Y Y TCP communicationis only supported onSDI2

Remote Program(RPS or A-link)

Y Y Requires BoschCellular service orother cellular networkaccess

Configure B450 fromcontrol panel

N Y GV4/B Series requirev2.03+

Personal Notificationvia SMS or Email

N Y Requires compatiblecontrol panel andcellular plan

Remote SecurityControl App

N Y Requires BoschCellular service orother cellular networkaccess

Table 3.1: B450 cellular interface compatibility

Bus address settings overviewThe address switch determines the bus address for the B450 Conettix Plug-in CommunicatorInterface. The control panel uses the address for communications. Use a slotted screwdriverto set the address switch.

Notice!

The B450 reads the bus address switch setting only during power up. If you change the

switch after you apply power to the module, you must cycle the power to the module in order

for the new bus address setting to be used for bus communication.

3.2

3.3

Conettix Plug-in CommunicatorInterface

System overview | en 9

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 10: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Bus address labelUse the bus address label to select the desired setting on the bus address switch, dependingon your control panel.

PANEL ADDRESSES

TX RX

0 1 2 4 5 6 7 8 9

Bus cfg 1 2 88 92 250

Addr SDI2 SDI Option

134 13 14

Figure 3.2: Bus address label

10 en | System overviewConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 11: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

InstallationPerform the following steps to install the B450.

!

Caution!

Remove all power (AC and battery) before making any connections. Failure to do so might

result in personal injury and/or equipment damage.

Setting the bus addressThe B450 Conettix Plug-in Communicator Interface address switch provides the value for themodule's address. The figure below shows the address switch setting for address 1. Refer tothe table below for panel-specific settings.

Figure 4.1: Address switch set to address 1

Control panels Switchposition

Control panelbus address

Bus type Function

USB or SMS configurationsetting

0 N/A Any Change configuration

B5512/B4512/B3512,D9412GV4/D7412GV4/D7212GV4Solution 2000/3000

1 1 SDI2 Automation, Remote Programming, orReporting

D9412GV4/D7412GV4/D7212GV4Solution 2000/3000

2 2 SDI2 Automation, Remote Programming, orReporting

D9412GV4/D7412GV4/D7212GV4, D9412GV3/D7412GV3/D7212GV3,D9412GV2/D7412GV2/7212GV2 v7.06+

4 88 SDI1 Remote Programming or Reporting

D9412GV4/D7412GV4/D7212GV4, D9412GV3/D7412GV3/D7212GV3

5 92 SDI1 Remote Programming or Reporting

AMAX 2000/2100/3000/4000 6 134 Option Remote Programming or Reporting

CMS 6/8, CMS 40 6 134 Option Remote Programming or Reporting

Easy Series v3+ 6 134 Option Remote Programming or Reporting

4

4.1

Conettix Plug-in CommunicatorInterface

Installation | en 11

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 12: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Control panels Switchposition

Control panelbus address

Bus type Function

FPD-7024 9 250 Option Remote Programming or Reporting

1For D9412GV4/D7412GV4/D7212GV4 configurations, SDI2 bus connection is the recommended configurationoption, but SDI bus configuration is also supported.

Table 4.1: B450 address switch settings

Notice!

Address switches 3, 7, and 8 are not supported on the B450.

Insert the communication moduleInsert the desired B44x communication module into the slot of the B450 until you feel themodule “click” into place.

Notice!

Review your communication module prior to insertion into the B450. Depending on the

physical attributes of your communication module, insert your module accordingly using the

supported installation process (Section 4.2.1 without a SIM card, or Section 4.2.2 with a SIM

card).

4.2

12 en | InstallationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 13: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Insert the B44x communication module (required and available separately)

Figure 4.2: Inserting the communication module into the B450

Callout ᅳ Description

1 ᅳ B44x Plug-in Communicator module (available separately)

2 ᅳ B450 Conettix Plug-in Communicator Interface

Insert the B44x communication module with SIM card (required andavailable separately)Insert the desired B44x communication module with supporting SIM card into the slot of theB450 until you feel the module “click” into place.

4.2.1

4.2.2

Conettix Plug-in CommunicatorInterface

Installation | en 13

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 14: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

2

3

1

Figure 4.3: Inserting the communication module with supporting SIM card into the B450

Callout ᅳ Description

1 ᅳ B44x Plug-in Communicator SIM card insertion (required and, available separately)

2 ᅳ B44x Plug-in Communicator module (available separately)

3 ᅳ B450 Conettix Plug-in Communicator Interface

Mount the module in the enclosure

Notice!

If you are not using the interconnect cable, it is recommended to wire the B450 module to

the compatible control panel via the terminal strip prior to mounting the B450 into the

enclosure. Failure to do so will complicate the mounting procedure.

Mount the B450 Conettix Plug-in Communicator Interface using the interior wall of theenclosure’s 3-hole mounting pattern and the supplied mounting screws.

Notice!

UL requirement

Mount the module in the control panel enclosure, or in a UL listed enclosure. For Commercial

Burglary applications, house all communicators in tampered enclosures.

All communicators shall be housed in tampered enclosures. If the unit is used in a commercialburglar environment, and is enclosed in a commercial enclosure, that enclosure must betampered.If the installation is a local or police station connection, then the B450 must be mountedinside an attack resistant enclosure.

4.3

14 en | InstallationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 15: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Figure 4.4: Mounting the module to the exterior wall of the enclosure

Callout ᅳ Description

1 ᅳ B450

2 ᅳ Enclosure (outside wall shown)

3 ᅳ Mounting screws (3 screws included)

Installing in a control panel enclosureInstall the B450 on the inside enclosure wall that also contains the supported control panel.The control panel powers the B450 via the terminal block or bus connection.

Installing in a separate enclosureInstall the B450 on the inside wall of a separate enclosure. The control panel in a nearby,separate enclosure powers the B450 via the terminal block or bus connection.

Installing in a separate enclosure with separate power supplyInstall the B450 on the inside wall of a separate enclosure that also has a separate externalpower supply such as the B520 Auxiliary Power Supply Module.

Mount and wire the tamper switch (option for SDI2 bus only)When the tamper input is shorted, the firmware version flashes, then the B450 LEDs aredisabled to conserve power. To see the troubleshooting LEDs, open the tamper circuit orjumper. You can connect an enclosure door tamper switch for one module in an enclosure.Installing the optional tamper switch for use with a B450:1. Mount the tamper switch into the enclosure’s tamper switch mounting location.2. Plug the tamper switch wire onto the module’s tamper switch connector. For the tamper

switch connector location, refer to Module overview, page 8.3. Verify the B450 module is configured with tamper enabled ON within the SDI2 supported

control panel.

4.3.1

Conettix Plug-in CommunicatorInterface

Installation | en 15

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 16: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Install and mount the plug-in communicator antennaInstalling and mounting the magnetic antenna:1. Place the magnetic antenna on top of the enclosure, or vertically on another metal

surface.

Notice!

If you are experiencing a weak signal, place the antenna on top of a metal surface that has a

radius of 10.16 cm (4 in) for optimal performance.

2. Route the antenna cable through a knock-out in the enclosure wall.3. Connect the antenna cable to the module.4. Secure the antenna cable to the inside of the enclosure.5. Secure the extra antenna cable length inside the enclosure.

1

2

Figure 4.5: Antenna installation

Callout ᅳ Description

1 ᅳ B44x plug-in cellular communicator antenna (routed through any knock-out)

2 ᅳB44x plug-in cellular communicator antenna cable (connected to the module)

Wire to the control panelWhen you wire a module to an SDI, or SDI2 control panel, you can use either the module'sterminal strip labeled R, Y, G, B (PWR, A, B, COM) or the module's interconnect wiringconnectors (wire included). The figure below indicates the location of both the terminal stripand the interconnect wiring connectors on the module.

4.4

4.5

16 en | InstallationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 17: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Notice!

Use either the terminal strip wiring or interconnect cable to wire to the control panel. Do not

use both. When connecting multiple modules, you can combine terminal strip and

interconnect wiring connectors to daisy-chain the modules in series.

Wire to an SDI2 control panelRun the wiring connections from the module to the data bus terminals on the compatiblecontrol panel.

R

Y

G

B

R

Y

G

B

3.7 - 5.0 VDC2.0 - 3.0 VDC0.0 - 1.3 VDC

Open Normal Short

3

R

Y

G

B

1 1

2

42

7 COM 8

COUTPUT

B

1 k End of Line Resistors

Voltage Ranges

ON-BOARD POINTS

3 COM 4 5 COM 61 COM 2

R Y G B

SDI2Device Bus

AUX- 12 V + 7 COM 8

COUTPUT

B

1 k End of Line Resistors

Voltage Ranges

ON-BOARD POINTS

3.7 - 5.0 VDC2.0 - 3.0 VDC0.0 - 1.3 VDC

Open Normal Short

3 COM 4 5 COM 61 COM 2

R Y G B

SDI2Device Bus

AUX- 12 V +T

MP

R

1 COM 2 7 COM 83 COM 4 5 COM 6

RE

SE

T

COM AUX R Y G B

PWR A B COM

B C

OU

TP

UT

TM

PR

1 COM 2 7 COM 83 COM 4 5 COM 6

RE

SE

T

COM AUX R Y G B

PWR A B COM

B C

OU

TP

UT

Figure 4.6: Using terminal strip or interconnect cable wiring on an SDI2 control panel (B Series control panel shown)

Callout ᅳ Description

1 ᅳ Compatible SDI2 control panel (B Series control panel shown)

2 ᅳ B450

3 ᅳ Terminal strip wiring

4 ᅳ Interconnect cable

4.5.1

Conettix Plug-in CommunicatorInterface

Installation | en 17

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 18: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Wire to an SDI control panel

R

Y

G

B

R

Y

G

B

3

R

Y

G

B

1 1 2

4

2

Commercial Protected-Premises Control Panel

D9412GV3 Control Panel is UL Listed For Central Station, Remote Station, Local, Auxiliary, Proprietary, and Household Fire Alarm, and Central Station, Local, Proprietary, Police Station Connect, Household Burglar Alarm and Encrypted Line Security when communicating via a network.

System is intended to be checked by a Qualified Technician at least every 3 years. The types of initiating circuits the control panel has been approved for are A, M, W, SS. The types of signaling the control panel has been approved for are DAC, OT, NC, RevPol.

VOLTAGE RANGESOpen 3.7 - 5.0 VDC Short 0.0 - 1.3 VDCNormal 2.0 - 3.0 VDC

Reset PinDisable all except Battery

Charging and Programming

PERIPHERAL DEVICE CONNECTIONS

RED POWER +

YELLOW DATA BUS A

GREEN DATA BUS B

BLACK COMMON

ZONEX OUT 1

ZONEX IN 1

NFPAStyle 4.0SignalingLineCircuits

This equipment should be installed in accordance with the NFPA 70 (National Electrical Code) and NFPA 72 (National Fire Alarm Code).

D9412GV3

26

25

ZONEX POWER + 24

ZONEX COMMON 23

SDI Connector

ZONEX OUT 2

ZONEX IN 2

Refer to the D9412GV3/D7412GV3 Approved Applications Compliance Guide (P/N: F01U143069) for System Wiring Diagram, Issue A and for compatible smoke detectors. 2-wire Compatible Identifier “A”.

POWER SUPPLY REQUIREMENTSThe Power Supply provides a maximum of 1.4 Amps for the Control Panel and all Accessory Devices. For System Loading, refer to the D9412GV3/D7412GV3 Operation and Installation Guide (P/N: F01U143070).

(P/N: F01U143070) for Power Requirements relating to Terminals 6 and 7 .

All external connections except Terminal 5 (battery positive) are inherently power

limited. Requirements for battery standby time might reduce allowable output.

Battery: Replace every 3 to5 years with one or two Model D126 or D1218 12 V Lead Acid Batteries.

Operation Monitor LED Pulses when Normal Flickers when Ringing

GREEN

Point 8, S3 Option

Closed = 1 kΩ EOLNormal Operation

Open =AB-12 ULBell Box 220 kΩ

25

Point 3 Point 4

1614

Point 1 Point 2

11 13

Point 5 Point 6

17 19

Point 7 Point 8

2120 22

Minimum system requirements for Classification in accordance with ANSI/SIA CP-01-2007:UL Listed and Classified control unit Model D9412GV3, D7412GV3, or D7212GV3;UL Listed and Classified keypad Model D1256, D1257, D1260, D1255, D1255R, or D1255RW;UL Listed Local Bell

WARNING!To prevent risk of electric shock, disconnect AC power and telephone lines before servicing.

181512

Not suitable for remote station protected premises services where separate transmission circuitsare required for fire, supervisory (when applicable) and trouble signals when using D185.

Commercial Protected-Premises Control Panel

D9412GV3 Control Panel is UL Listed For Central Station, Remote Station, Local, Auxiliary, Proprietary, and Household Fire Alarm, and Central Station, Local, Proprietary, Police Station Connect, Household Burglar Alarm and Encrypted Line Security when communicating via a network.

System is intended to be checked by a Qualified Technician at least every 3 years. The types of initiating circuits the control panel has been approved for are A, M, W, SS. The types of signaling the control panel has been approved for are DAC, OT, NC, RevPol.

VOLTAGE RANGESOpen 3.7 - 5.0 VDC Short 0.0 - 1.3 VDCNormal 2.0 - 3.0 VDC

Reset PinDisable all except Battery

Charging and Programming

PERIPHERAL DEVICE CONNECTIONS

RED POWER +

YELLOW DATA BUS A

GREEN DATA BUS B

BLACK COMMON

ZONEX OUT 1

ZONEX IN 1

NFPAStyle 4.0SignalingLineCircuits

This equipment should be installed in accordance with the NFPA 70 (National Electrical Code) and NFPA 72 (National Fire Alarm Code).

D9412GV3

26

25

ZONEX POWER + 24

ZONEX COMMON 23

SDI Connector

ZONEX OUT 2

ZONEX IN 2

Refer to the D9412GV3/D7412GV3 Approved Applications Compliance Guide (P/N: F01U143069) for System Wiring Diagram, Issue A and for compatible smoke detectors. 2-wire Compatible Identifier “A”.

POWER SUPPLY REQUIREMENTSThe Power Supply provides a maximum of 1.4 Amps for the Control Panel and all Accessory Devices. For System Loading, refer to the D9412GV3/D7412GV3 Operation and Installation Guide (P/N: F01U143070).

(P/N: F01U143070) for Power Requirements relating to Terminals 6 and 7 .

All external connections except Terminal 5 (battery positive) are inherently power

limited. Requirements for battery standby time might reduce allowable output.

Battery: Replace every 3 to5 years with one or two Model D126 or D1218 12 V Lead Acid Batteries.

Operation Monitor LED Pulses when Normal Flickers when Ringing

GREEN

Point 8, S3 Option

Closed = 1 kΩ EOLNormal Operation

Open =AB-12 ULBell Box 220 kΩ

25

Point 3 Point 4

1614

Point 1 Point 2

11 13

Point 5 Point 6

17 19

Point 7 Point 8

2120 22

Minimum system requirements for Classification in accordance with ANSI/SIA CP-01-2007:UL Listed and Classified control unit Model D9412GV3, D7412GV3, or D7212GV3;UL Listed and Classified keypad Model D1256, D1257, D1260, D1255, D1255R, or D1255RW;UL Listed Local Bell

WARNING!To prevent risk of electric shock, disconnect AC power and telephone lines before servicing.

181512

Not suitable for remote station protected premises services where separate transmission circuitsare required for fire, supervisory (when applicable) and trouble signals when using D185.

Figure 4.7: Using terminal strip or interconnect cable wiring on an SDI control panel (GV3 Series control panel shown)

Callout ᅳ Description

1 ᅳ Compatible SDI control panel (GV3 Series control panel shown)

2 ᅳ B450

3 ᅳTerminal strip wiring

4 ᅳ Interconnect cable

4.5.2

18 en | InstallationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 19: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Wire to an option bus control panelRun the wiring connections from the module to the data bus terminals on the compatiblecontrol panel.

Notice!

When wiring the connections between the option bus terminal strip and the B450, verify the

terminal position of the colored wires as they may be in a different orientation (option bus =

R, B, G, and Y) and (B450 = R, Y, G, and B).

R

Y

G

BR YGB

2

1

3

R

Y

G

B

Figure 4.8: Wiring to an option bus terminal strip (

Callout ᅳ Description

1 ᅳ Compatible control panel (FPD-7024 control panel shown)

2 ᅳ B450

3 ᅳ Terminal strip wiring

For complete wiring instructions, refer to the control panel documentation.

4.5.3

Conettix Plug-in CommunicatorInterface

Installation | en 19

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 20: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Configuration

Notice!

Power up the system prior to the configuration workflows described in this chapter.

You can configure the B450 using one of the methods described in this section for yourcontrol panel type.

Configuration for SDI2 control panelsPerform the following to configure the B450 to supporting SDI2 control panels.

Notice!

By default, when connecting a field replacement B450 to an existing SDI2 control panel, the

control panel overrides some of the module settings such as; TCP/UDP Port Number, AES

Encryption, Tamper, Panel Programming, IPv4 DNS Server IP Address, Alternate IPv4 DNS

Server IP Address, and TCP Keep Alive Time. To keep custom module settings when you

connect a module to a configured control panel, you must disable Panel Programming prior to

connecting to the SDI2 bus. This is accomplished by using either USB, or SMS configuration.

If the SDI2 control panel is not defaulted, the control panel sends the network configuration

parameters to the B450.

Address-only configuration conditionsAn SDI2 control panel automatically configures a newly connected module.1. If the control panel is not at factory default, it transfers the configuration settings in the

control panel to the B450.2. Verify that the address switch is set to the correct address for the control panel (SDI2

control panels use address 1 or 2). If the switch is not set to the correct address, powerdown the system, set the correct address, and then power up the system.

3. Program the control panel communication settings using RPS or the keypad.The control panel stores the module settings and automatically programs a defaulted modulewhen connected. If manual module programming is required, use USB or SMS configuration toset the Panel Programming parameter to Disabled before installing.

Configuring and viewing status from RPSConfigurationFor SDI2 control panels, the networking related parameters in the Networking parameters inRPS table can be configured through the panel or RPS. When cellular specific parameters needto be modified, refer to the USB or SMS configuration sections within this installation andoperation guide for programming workflows and operation. The B450 parameters within RPS can be found under the SDI2 Modules section. Refer to thechart below for RPS selections:

5

5.1

5.1.1

20 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 21: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

If your control panel configuration is a,…. Then use this menu within RPS,…

GV4 Series v1.00 SDI2 Modules B420 Ethernet Communicator

B Series/GV4 Series v2.00+ SDI2 Modules IP Communicator B4501

1B Series and GV4 Series control panels at firmware version 2.03+ with RPS version 5.19+can use the B450 submenu to configure GSM cellular parameters specific to B442 and B443Plug-in Cellular Communicators.

Table 5.1: RPS settings based on control panel firmware versions

Refer to the illustration below to locate the SDI2 Modules parameter within RPS.

Figure 5.1: RPS SDI2 Modules location

Common RPS configuration parametersRefer to the table below for parameters configured in RPS. The parameters listed in thefollowing table support SDI2 control panel versions v2.00 and higher.

Conettix Plug-in CommunicatorInterface

Configuration | en 21

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 22: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Parameter Value Description

Tamper (for GV4 ([v2.0x orhigher] control panels)

0 = Disabled1 = Enabled

When enabled, allows tamperand tamper restoreconditions to be reported toan SDI2 control panel.Notice!Only control panels with aSDI2 bus connection to theB450 can report a tampercondition.

IPv4 DNS Server IP Address IPv4 address format (0.0.0.0) The B450 uses the DNSserver addresses supplied bythe cellular network when thePrimary DNS Server addressoption is configured as0.0.0.0. If the address is notconfigured as 0.0.0.0, theB450 installs the Primary DNSServer address.

Web/USB access enabled Default: Yes Enabling Web/USB access onthe B450 enables the USBmenu, allowing forconfiguration programming.The B450 USB menu isenabled when the Web/USBAccess Enabled parameterremains in the defaultselection of Yes.When disabled, the B450shows a message stating:“Menu access disabled.” Notice! In the B Series andGV4 Series control panels,the default setting forWeb/USB Access Enabled isset to No. USB menu accessis NOT allowed unless theWeb/USB Access Enabledparameter is changed to Yesin the control panelconfiguration.In non-SDI2 control panels,configuration via the controlpanel does not occur.

22 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 23: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Parameter Value Description

Web/USB access password Enter a 4 – 10 characterpassword to access moduleprogramming Do not use thecharacters ; or !

The web access password isused to allow access tomodule programming. For aB450 module, the passwordcontrols configuration fromthe USB menu and SMS text.

TCP/UDP Port Number 1 to 65535 (7700) Sets the source port for theB450.

Alternate IPv4 DNS Server IPAddress

IPv4 address format (0.0.0.0) If the address is notconfigured at 0.0.0.0, theB450 installs the AlternateDNS Server address.

TCP Keep Alive Time 0 – 255 sec (45) This parameter determineshow long to wait betweentransmissions to keep an idleTCP connection to a remotehost from terminating due toinactivity.

IPv4 Test Address IPv4 address format (0.0.0.0) The IPv4 Test Address is usedby the module to ping aninternet address as part ofthe IP diagnostics.

Table 5.2: B450 networking parameters configurable in RPS

B450 IP Communicator settingsThe parameters listed below are configurable on control panels with firmware version 2.03+.Use the following settings to configure your cellular module parameters under the SDI2 IPCommunicator B450 option (applicable for control panels with firmware version 2.03+).

Conettix Plug-in CommunicatorInterface

Configuration | en 23

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 24: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Figure 5.2: B450 parameters

Notice!

Cellular configuration programming under the IP Communicator – B450 section is not available

in RPS with control panels using firmware version v1.00 - v2.02. Cellular configuration for

control panels with firmware version 1.00 – 2.02 can only be done through the USB interface

connected to the B450. Use RPS settings on Module 1 only. Module 2 must be configured

through from the B450 through the USB menu.

DiagnosticsInformation about the B450 such as it's Status, IP Address, Bus Voltage and the assignedphone number of the plug-in module can be found on the RPS Diagnostics screen. Dependingon the firmware version of your control panel, you will see the following screens.

24 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 25: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

B450 status with version 2.03+ firmware

Figure 5.3: B450 status shown in RPS Diagnostics with B Series/GV4 Series version 2.03+

B450 status with version 2.00 – 2.02B450 status as shown as Ethernet Communicator in RPS Diagnostics with GV4 version 2.00 –2.02.The following Diagnostic screen shown below is applicable to both B Series and GV4 Seriescontrol panels:

Conettix Plug-in CommunicatorInterface

Configuration | en 25

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 26: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

B450 status with version 1.00B450 status as shown as Ethernet Communicator in RPS Diagnostics with GV4 v1.00. Theplug-in communicator's phone number (if available) displays in the "Hostname" field. Refer tothe illustration below.

Figure 5.4: B450 status shown as Ethernet Communicator in RPS Diagnostics with GV4 version 1.00

RPS Diagnostics is not available when the module’s connected to SDI or Option bus controlpanels.

Use USB to configure the B450You can use a USB connection from a laptop PC to the B450 to configure the B450 on-site.The supported USB cable used to establish connection is a Male A to Male A cable.

Notice!

It is recommended to use a Bosch supported USB cable such as the B99 cable (F01U278853).

Failure to do so may result in communication failures between the B450 and your computer.

Notice!

USB connection is for configuration or diagnostics only. Disconnect when done.

Before you can access the USB user interface, you must install the RBUS1CP.inf file, or haveRPS version 5.16 or greater installed, and USB driver on the target PC or laptop. TheRBUS1CP.inf file and USB driver are available on the supplied CD‑ROM. You need to installthis file only once on the target PC or laptop.

5.2

26 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 27: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Notice!

If you currently have RPS version 5.16 or greater, you do not have to install USB driver

(RBUS1CP.inf) as described below.

If the B450 CD-ROM is not available:1. From your Internet browser, go to: http://www.boschsecurity.com to open the Bosch

Web site.2. Select the web site for your region and country.3. In the Online Catalogs section on the left, click the Intrusion Alarm Systems link.4. Under the Intrusion Alarm Systems Products heading, scroll to the Conettix -

Information Transport Solutions section. Click the Show product section link.5. Click the Conettix IP link.6. Scroll to the B450 Plug-in Communicator Interface section. Click the section title to

open the product page.7. Under the product image, click the Software tab.8. Click OK to accept the license agreement.9. To the right of the B450, click on the language link (for example, en).

The File Download dialog box opens.10. Click Save to save the file to the target PC or laptop. Perform this task to download both

the USB driver file, and the RBUS1CP.inf file.11. Supply power to the B450.12. Connect the B450 to the target PC or laptop, using a USB Type A to A cable. A New

Hardware Found window appears on the computer.13. Install the RBUS1CP.inf file onto your PC or laptop. Verify through the device manager

that the appropriate .inf installs properly, and is listed under the Ports (COMM & LPT)section. The correct .inf file is B450 Config Interface.

14. Install a communication program to configure the B450.

Conettix Plug-in CommunicatorInterface

Configuration | en 27

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 28: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Figure 5.5: RBUS1CP.inf installed inside Device Manager

Install a communication programTo use USB connection from a computer to the B450 to configure the B450, you must use acommunication program.– Windows XP. The Microsoft Windows XP installation automatically installs HyperTerminal,

a Microsoft communication program, when Windows installs. If HyperTerminal is notinstalled, install it from the Windows XP installation disc, or install Tera Term from theB450 CD.

– Windows Vista and Windows 7/8 installations no longer include a communicationprogram when the operating system installs. Install Tera Term from the B450 CD.

Install the communication program that supports your configuration (Hyper Terminal or TeraTerm), depending on your laptop or PC’s operating system.

Notice!

Tera Term is preferred in all applications as its operation is understood by Bosch Technical

Support if assistance is required.

Installing Tera TermWhen you perform the Tera Term installation, follow the prompts in the installation wizard,but on the Select Components page of the wizard, select Compact installation from the drop-down list. Refer to the figure below.

5.2.1

28 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 29: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Figure 5.6: Setup - Tera Term wizard's Select Components window

Tera Term version interfaceAfter installing the latest Tera Term version, double-click on Tera Term to launch the program.The Tera Term window opens. Refer to the illustrations below to set up Tera Term defaults.Setting up Tera Term defaults:1. Launch the application.2. Select Setup => Terminal as shown below.

Conettix Plug-in CommunicatorInterface

Configuration | en 29

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 30: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Figure 5.7: Selecting the Terminal Setup window

3. Change the default setting of CR to LF from the Receive pull-down menu and press OK.

Figure 5.8: Changing the Receive: option to LF

4. Select Save setup.

30 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 31: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Figure 5.9: Saving the setup

5. Select Save to overwrite the existing TERETERM.INI file. This stores the new setting, andallows you to have the correct display settings when you launch Tera Term in futuresessions.

6. Select the correct port option in the Port: pull-down menu for the B450.

Figure 5.10: Tera Term Pro window shown

Conettix Plug-in CommunicatorInterface

Configuration | en 31

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 32: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Log into the USB interface

Notice!

To allow for USB configuration, address switch must be set to 0. Powering down the module

after changing the bus address switch for programming is not required.

1. Ensure that the USB-Type A male-to-male cable is connected to the B450 and the targetPC or laptop.

2. From Windows, start a terminal session by launching Hyper Terminal on Windows XP orearlier, or launching Tera Term on Windows Vista/Windows 7/Windows 8.

3. Set up a connection on the new virtual serial COM port (for example, Port: COM7: B450[COM7]). If the B450 is not connected to the computer, or the USB driver is not installed,the B450 does not appear in the list.

4. After the connection is established, press [Enter]. The B450 USB login window opens.

Figure 5.11: B450 USB login window

5. Enter the password to log on. The default password is B450.The user interface allows three attempts to enter the password correctly. After threefailed attempts, the B450 shows a Too many attempts error message, and the USBinterface enters into an idle state for 30 sec. Repeat Steps 3 through 6. at the conclusionof 30 sec.

6. Press [Enter] to continue. The USB main menu opens.

5.2.2

32 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 33: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Notice!

The default password is case-sensitive. Verify the password for case-sensitivity when

entering.

Menu access disabled error messageRefer to USB menu access disabled, page 56 if you receive the following error message whenaccessing the USB menu.

Figure 5.12: USB menu access disabled error window

Conettix Plug-in CommunicatorInterface

Configuration | en 33

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 34: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

USB Main menu

:

1

2

3

4

Figure 5.13: USB Main Menu

Callout Description

1 Installed device

2 Current device status

3 Current access level

4 Main menu options

The USB main menu appears:– after a user enters a password successfully– every time the user presses [Enter] without first selecting an option from the main screen– upon returning from a sub-menu. The following table describes the USB Main Menu parameters found within callouts 1-3 in thegraphic above.:

Parameter Description

B44x This field displays one of the following parameters:– B44x Cellular Communicator– Plug-in not connected– Detecting plug-in module

5.2.3

34 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 35: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Link Status This field displays the connection status to the cellular network. Theoptions include:– OK– Error

Bus Status This option includes:– On Line– Not Connected

Module Status This option includes:– Normal– Trouble

Tamper This option includes:– Yes– No– Disabled (through configuration)

Access Level This option includes:– Restricted– Full

Table 5.3: USB Menu parameters

USB menu structureThe following illustration depicts the B450 menu structure.

5.2.4

Conettix Plug-in CommunicatorInterface

Configuration | en 35

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 36: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Advanced

Configuration

Change

Passcode

Status

(Starts with

Basic Status)

Reset Statistics1

Signal Strength

3

4

2

Main Menu

Reset to

Factory Defaults

5

Exit

Go to Main Menu

Go to Basic Status Menu1

0

Go to Advanced Status Menu

5

Go to Main Menu

Modify diagnostic settings

Re-print all console messages

Enable console messages

1

2

3

0 Go to Diagnostic Log Menu

1 Cellular Modem Verbose Mode

2 Bus Communication Verbose Mode

2

Product Versions

Diagnostic Log*

Basic

Configuration

Firmware

Update7

8

0

3 Network Communications Verbose Mode

4 Network Operations Verbose Mode

5 Module Operations Verbose Mode

6 All Verbose Modes Off

0 Go to Main Menu

1

2

5

Set Modem Reset Count

6

Set Reporting Delay for no towers

Set Reporting Delay for single tower

Set TCP Keepalive Time

4

0 Go to Main Menu

4 Panel Programming Enabled

5 Inbound SMS Enabled

6 Reporting Delay for Low Signal Strength

7 GSM/GPRS Configuration

3

6

* The Diagnostic Log option is used in troubleshooting communication issues with the B450. Use of the Diagnostic Log option is to be used

only at the direction of TECHNICAL SUPPORT.

1 TCP/UDP port

2 AES Encryption

3 Tamper Enabled

3

Set Primary DNS Server Address

4

Set Alternate DNS Server Address

0 Basic Configuration Menu

1 Network Access Point Name (APN)

2 Network Access Point User Name

3 Network Access Point Password

4 SIM PIN

5 Session Keep Alive Period (min)

6 Inactivity Timeout (min)

8 Email Server Configuration 0 Basic Configuration Menu

1 Email Server Name/Address

2 Email Server Port Number

3 Email Server Authentication/Encryption

4 Authentication User Name

5 Authentication Password

7 Set TLS Automation Security

Figure 5.14: USB menu structure

Notice!

Changes or edits to programming are discarded if you select the Exit option, and exit the

menu. If you make changes or edits, select the Save and Exit option to ensure programming

changes are saved.

USB menuFor a description of the USB menu options, refer to the tables in the following sections.To go to a specific menu option, enter the appropriate menu option number.

Notice!

Any and all changes that were not saved will be lost if no keys are pressed within 5 minutes.

The USB menu will automatically logout.

Using the Escape (Esc) keyPress the Escape (Esc) key without making any programming changes will return you to theprevious menu.

USB Main MenuPressing the Escape key after entering data will clear data entered.

5.2.5

36 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 37: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Option PresstoSelect

Description

1. Status (Startswith BasicStatus)

1 To access and view the link, modem, and bus statusFor additional menu descriptions, refer to the USB Status sub-menu parameters tablebelow for more information.

2. ChangePasscode

2 To change the login passcode, enter the new passcode twice. The second entryconfirms the new passcode.Passcodes must be 4-10 characters long, and are case-sensitive.0-9, A-Z, a-z, and special characters are allowed.Notice!If SMS configuration is used, do not use semicolon (;) or exclaimation mark (!) aspart of the passcode.

3. BasicConfiguration

3 Select to program Basic Configuration options. Press 0 to return to the Main menu.To change a basic parameter, select the option to change, and then enter in the newvalue.

4. AdvancedConfiguration

4 Select to program Advanced Configuration options. Press 0 to return to the Mainmenu.To change an advanced parameter, select the option to change, and then enter in thenew value.

5. Reset toFactory Defaults

5 Select to reset all factory default values. All fields are cleared and the factory defaultvalues are restored.Notice!A non-defaulted SDI2 control panel will overwrite the default settings if connected tothe defaulted module.

6. Diagnostic Log 6 Select to review the Diagnostic log.

7. FirmwareUpdate

7 Select this option to update the firmware in the B450.Notice!Download your update file from the Bosch website prior to performing an update.For more information on Firmware update workflows, refer to Firmware Update page,page 52.

8. Exit 8 Select to exit the menu and log out. You must enter the passcode to log back in.Notice!If configuration changes have been made but not saved, you will be prompted to saveor discard them.

Table 5.4: USB Main Menu parameters

Basic Status MenuThe following section describes the description of the Basic Status menu parameters.

Conettix Plug-in CommunicatorInterface

Configuration | en 37

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 38: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Figure 5.15: Basic Status screen

Parameter Description

Link Status

IP Address This field displays the current Cellular Network IP Address. An IPaddress of 0.0.0.0 is listed when no IP address is found.

Link Status This field displays the connection status to the cellular network. Thisfield displays either OK, or Error.

Encryption This field displays either Normal, or Trouble:

Socket xx: PortNumber

This field displays the current open Port Numbers and Data Types (up to32).

Modem Status – The information below displays in the appropriate fields. If no modemstatus is detected, the following message appears: Modem status is not available.

Telephone Number This field displays the cellular phone number if available. A phonenumber of 000-000-0000 is listed when there is no phone number.

Electrical Serial #(ESN)

This field displays the B44x radio modem serial number.

38 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 39: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Data Status This field displays one of the following; Disconnected, Connecting, orConnected.

Signal Strength This field displays the current signal strength. One of the followingappears; Very good, Good, Marginal, Unacceptable, or Unavailable.

Bus Status

Bus Type This field displays the current bus type. One of the following appears;SDI2, SDI, Option, or None.

Bus Address This field displays the current bus address. One of the followingappears; 1, 2, 88, 92, 134, or 250.

Bus Voltage This field displays the current voltage. One of the following appears;Good, or Low.

Module Status – This status displays only if there is a trouble condition.– B44x Plug-in Missing– Detecting Plug-in

– B44x Plug-in Missing– B44x Plug-in Invalid– No IP Address– Detecting Plug-in– Signal Strength Low– Too Few Towers– No Towers– B44x Not Active– B44x Failure– Configuration Failure– Low Bus Voltage– No Bus Communication– Switch in Position 0– Firmware Checksum Error– Configuration Checksum Error– SIM Missing– SIM PIN Wrong– SIM PIN Lockout– Invalid Access Point

– No IP Address

Advanced Status MenuThe following section describes the description of the Advanced Status menu parameters.

Conettix Plug-in CommunicatorInterface

Configuration | en 39

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 40: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Figure 5.16: Advanced Status screen

Parameter Description

Advanced Link Status

Internet (ping) This field displays one of the following; OK, Error, No Status (no pinghas been performed).

IPv4 DNS Server IPAddress

This field displays the current IP sddress.

Alternate IPv4 DNSServer IP Address

This field displays an alternate IP address.

DNS Status This field displays one of the following; OK, Error, No Status (no DNSlookup (has been performed).

UDP PacketsTransmitted

This field displays from power up, or Option 3 (Reset Status)

UDP PacketsReceived

This field displays from power up, or Option 3 (Reset Status)

40 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 41: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Advanced Modem Status

Transceiver Modelnumber

This field displays one of the following; DE910-DUAL, CE910-DUAL,GE910-QUAD

Carrier Name This field displays the carrier network providing service.

Data Status This field displays one of the following; Disconnected, Connecting, orConnected.

Signal Strength This field displays the current signal strength in dbm.

Towers Available This field displays the number of towers that can be detected by themodule

Base Station ID This field displays information about the tower you are currentlyconnected to.

Current Band This field displays the current band frequency

Data Class This field displays one of the following; 1xRTT, 3G, GPRS, EDGE,WCDMA, HSPA

Temperature This field displays the internal temperature of the radio transceiver (inCelsius)

Advanced Bus Status

Bus Voltage This field displays the voltage measured at the input to the module

Bus Commandsreceived

This is a running total of the number of valid bus messages that themodule has received. If the module is on the bus and operating thisnumber will change when refreshed.

For a description of the Status sub-menu parameters, refer to the table below.To go to a specific Status menu option (Reset Status, Signal Strength, and Product Versions),perform the following;1. Enter the B450 passcode2. Press [1] Status (Starts With Basic Status).3. Select the desired parameter (Basic Status, Advanced Status, Reset Status, Signal

Strength, and Product Versions) from the table below.

Option PresstoSelect

Description

1. Basic StatusMenu

1 This option displays the current IP address, link status, modem status, bus status,and module status.

2. AdvancedStatus Menu

2 This option displays various parameters related to the cellular device such as UDPpackets transmitted and received, the carrier name, available towers, and data class,just to name a few.

3. Reset Status 3 The status display shows several items that are counts of activities, such as UDPpackets transmitted. When reset status is selected, all counts are returned to zero.This is not required for normal operation.

Conettix Plug-in CommunicatorInterface

Configuration | en 41

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 42: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Option PresstoSelect

Description

4. SignalStrength

4 The current signal strength records every 15 minutes for up to 48 hours worth ofdata. When signal strength is selected, up to 192 values are displayed representingthe signal strength values over the last 48 hours. If the B450 has been powered upless than 48 hours, the list shows only the samples taken so far. If it has been lessthan 15 minutes, you will see “Not Available” listed.The screen shot below is an example of what you might see in the signal strengthhistory.

5. ProductVersions

5 This option displays the software version of all entities in the B450. The following listis an example of the versions displayed:*** Product Versions ***B450 Product ID: 88096.16041400007B450 Application: V 3.01.032B450 Boot Loader: V 1.05.001B450 Hardware: V 1.00.000RTOS: V 3.03.600Fusion Stack: V 8.07.5603Cellular Manager: V 2.00.3203UPKI Encryption: V 3.03.002AES Lib: V 01.00.000Modem Firmware: V 15.00.021

Table 5.5: Status sub-menu parameters

Basic Configuration sub-menu parameters – TCP/UDP Port NumberThis option sets the source port for the B450.To go to TCP/UDP Port Number, perform the following:1. Enter the B450 passcode2. Press [3] Basic Configuration.3. Press [1] TCP/UDP Port Number.4. Enter the desired port number value.

Basic Configuration sub-menu parameters – AES EncryptionThis option allows each receiver path to be configured with a unique AES encryption key.Refer to the graphic below for entering in the encryption key.

42 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 43: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Figure 5.17: Entering the encryption key

Notice!

Enter in your 32 digit encryption key. Verify your 32 digit key does not exceed the arrow

prompt as viewed in the graphic above. The module says "Invalid Entry: Incorrect key length",

if you enter more or less then the required key length. It also detects that you entered hex

values 0-9 and A-F. Any other hex values result in an error.

To go to AES Encryption, perform the following:1. Enter the B450 passcode2. Press [3] Basic Configuration.3. Press [2] AES Encryption.4. Enter the desired option:– 0 = Go to Basic Configuration Menu– 1 = Disabled– 2 = 128 Bits– 3 = 192 Bits– 4 = 256 Bits

Basic Configuration sub-menu parameters – Module Enclosure TamperThis option sets the enclosure tamper indication of a particular SDI2 device when enabled.To go to Module Enclosure Tamper, perform the following:1. Enter the B450 passcode2. Press [3] Basic Configuration.3. Press [3] Module Enclosure Tamper.4. Enter the desired option.

Basic Configuration sub-menu parameters – Panel ProgrammingThis option sets the enables/disabled configuration of the B450 by the control panel.To go to Panel Programming, perform the following:

Conettix Plug-in CommunicatorInterface

Configuration | en 43

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 44: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

1. Enter the B450 passcode2. Press [3] Basic Configuration.3. Press [4] Panel Programming.4. Enter the desired option.

Basic Configuration sub-menu parameters – Inbound SMSThis option allows the B450 to be configured via SMS configuration.To go to Inbound SMS, perform the following:1. Enter the B450 passcode2. Press [3] Basic Configuration.3. Press [5] Inbound SMS.4. Enter the desired option.

Basic Configuration sub-menu parameters – Reporting Delay for Low Signal StrengthThis option sets the duration of time when the B450’s signal strength is measured.To go to Reporting Delay for Low Signal Strength, perform the following:1. Enter the B450 passcode2. Press [3] Basic Configuration.3. Press [6] Reporting Delay for Low Signal Strength.4. Enter the desired option. The range is from 0 to 3600.5. Then press Enter.

Basic Configuration sub-menu parameters – GSM/GPRS ConfigurationFor a description of the Basic Configuration sub-menu parameters (Access Point Name, AccessPoint Login Name, Access Point Login Password, or SIM PIN), refer to the table below.To go to a specific Basic Configuration menu option – GSM/GPRS Configuration (Access PointName, Access Point Login Name, Access Point Login Password, or SIM PIN), perform thefollowing:1. Enter the B450 passcode2. Press [3] Basic Configuration.3. Press [7] GSM/GPRS Configuration.4. Select the desired parameter (Network Access Point Name, Network Access Point User

Name, Network Access Point Password, or SIM PIN) from the table below.

Option PresstoSelect

Description

1.Network AccessPoint Name (APN)

1 The Network Access Point Name is required for modems that use a SIM card suchas the B442 or B443.The Network Access Point Name must be 0-99 characters long, and is casesensitive.The default is: wyless.apn

2. NetworkAccess Point UserName

2 The Network Access Point User Name is used on the B442 and B443.The Network Access Point User Name allows users to connect to the access point.The Network Access Point User Name must be 0-30 characters long, and is casesensitive.The default is: None

44 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 45: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Option PresstoSelect

Description

3. NetworkAccess PointPassword

3 The Network Access Point Password is used on the B442 and B443Some carriers require a password to access the Access point. The Network AccessPoint Password must be 0-30 characters long, and is case sensitive.The default is: None

4. SIM PIN 4 To set the PIN in the B450 to match the SIM card pin in the cellular communicatormodule (for B442 and B443 only)Notice! To erase text, you must type in the word None to erase the previous text.This is NOT case-sensitive.The default is None:

5. Session KeepAlive Period (min)

5 This parameter sets the length of time in minutes between session keep alivereports to verify that an idle connection is still active. Leave the default value.The default is: 0The range is 0 to 1000 minutes

6. InactivityTimeout

6 This parameter specifies the time before the control panel will disconnect a sessionwith no data traffic. Leave the default value.When enabled, the control panel verifies an active connection exists with themodule.When disabled, the control panel does not verify the connection is active.The default is: 0The range is 0 to 1000 minutes

Basic Configuration sub-menu parameters – Email Server ConfigurationFor a description of the Basic Configuration sub-menu parameters – Email ServerConfiguration (Email Server Name/Address, Email Server Port Number, Email ServerAuthentication/Encryption, Authentication User Name, or Authentication Password), refer tothe table below.To go to a specific Basic Configuration menu option (Email Server Name/Address, EmailServer Port Number, Email Server Authentication/Encryption, Authentication User Name, orAuthentication Password), perform the following:1. Enter the B450 passcode2. Press [3] Basic Configuration.3. Press [8] Email Server Configuration.4. Select the desired parameter (Email Server Name/Address, Email Server Port Number,

Email Server Authentication/Encryption, Authentication User Name, or AuthenticationPassword from the table below.

Conettix Plug-in CommunicatorInterface

Configuration | en 45

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 46: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Option PresstoSelect

Description

1. Email ServerName/Address

1 This parameter specifies either the name or the address of the SMTP (Simple MailTransfer Protocol) for the email server chosen to transfer event messages from thecontrol panel to a designated email address. (Example:smtp.gmail.com)

2. Email ServerPort Number

2 This parameter specifies the port number for the email server.The default is: 25

3. Email ServerAuthentication/Encryption

3 Use this parameter to set the security level required by the email server to receivemessages from the control panel.Authentication means that the email server requires an authentication usernameand authentication password. This is sometimes referred to as SMTP-AUTH.The Encryption used is Transport Layer Security (TLS)The default is: Authenticate

4. AuthenticationUser Name

4 This parameter specifies the user name for the email account that is set up toreceive messages from the SMPT server sent by the control panel.The default is: NoneRange is: 0 – 255 ASCII printable characters

5. AuthenticationPassword

5 This parameter sets the password that the SMPT server uses to send emails to thePersonal Notification destinations.The default is: NoneRange is: 0 – 49 ASCII printable characters

Diagnostic Log sub-menu parametersFor a description of the Diagnostic Log sub-menu parameters (Modify Diagnostic Settings, Re-print All Console Messages, and Enable Console Messages), refer to the table below.

Notice!

The Diagnostic Log option is used in troubleshooting communication issues with the B450 .

Use of the Diagnostic Log option is to be used only at the direction of TECHNICAL SUPPORT.

Refer to Diagnostic log, page 60 for more information.

To go to a specific Diagnostic Log menu option (Modify Diagnostic Settings, Re-print AllConsole Messages, and Enable Console Messages), perform the following:1. Enter the B450 passcode2. Press [6] Diagnostic Log.3. Sect the desired parameter (Modify Diagnostic Settings, Re-print All Console Messages,

and Enable Console Messages) from the table below.

46 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 47: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Option PresstoSelect

Description

1. ModifyDiagnosticSettings

1 The Diagnostic logging is intended for use only under Bosch direction. Diagnosticsettings determine which types of messages to display.

2. Re-print SavedConsole Message

2 The Re-Print Saved option prints any diagnostic messages that have already occurredand are stored in the B450’s buffer. This can print what just happened if an issueoccurs.

3. Enable LiveConsoleMessages

3 Enable live console messages provides real time output of diagnostic messages. Thisallows the PC running TeraTerm to log what is occurring in the module and can logfor longer periods of time.

Table 5.6: Diagnostic Log sub-menu parameters

SMS and USB configuration parameters

Notice!

The table below shows all parameters available through SMS or USB configuration. Values in

bold are default settings.

ID Parameter Values Description

1 Current Password 4 to 10 characters (B450) Mandatory and case sensitive.Notice!Make sure you record and record your password.

2 New Password 4 to 10 characters New password, as desired. Case sensitive.

13 TCP/UDP PortNumber

1 to 65535 (7700) Sets the source port for the B450.

15 AES Encryption 0 = Disabled1 = 128 bit, 2 = 192 bit, 3 = 256bit

Security encryption on or off. The setting mustmatch the encryption settings in the receiver.Notice!This setting applies to SDI, and GV4 v1.0.x controlpanels only.

16 AES Encryption Key 32, 48, or 64 digits max.0-9, A-F, a-f allowed0102030405060708091011121314151601020304050607080910111213141516

The AES Encryption Key must match the encryptionkey in the receiver.Notice!This setting applies to SDI, and GV4 v1.0.x controlpanels only.

19 Module EnclosureTamper (for GV4v1.0.x controlpanels)

0 = Disabled1 = Enabled

When enabled, allows tamper and tamper restoreconditions to be reported to an SDI2 control panel.Notice!Only control panels with a SDI2 bus connection tothe B450 can report a tamper condition.

Conettix Plug-in CommunicatorInterface

Configuration | en 47

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 48: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

ID Parameter Values Description

20 Inbound SMS 0 = Disabled1 = Enabled

Allows the B450 to be configured via SMSconfiguration.Notice! When this option is set to Disabled, noinbound SMS text messages are processed.

65 IPv4 DNS Server IPAddress

IPv4 address format (0.0.0.0) The B450 uses the DNS server addresses suppliedby the cellular network when the Primary DNSServer address option is configured as 0.0.0.0. Ifthe address is not configured as 0.0.0.0, the B450installs the Primary DNS Server address.

66 Alternate IPv4 DNSServer IP Address

IPv4 address format (0.0.0.0) If the address is not configured at 0.0.0.0, the B450installs the Alternate DNS Server address.

67 Panel Programming 0 = Disabled1 = Enabled

Select to enable or disable control panelprogramming. This enables/disabled configurationof the B450 by the control panel.

68 Reporting Delay forLow SignalStrength

0 – 3600 sec. (1800) Sets the duration of time when the B450’s signalstrength is measured. The value selecteddetermines how long the signal strength must be ata low condition before reporting as low, or howlong the signal strength must be normal beforereporting as normal.

69 Reporting Delay forNo Towers

0 – 3600 sec. (1800) Amount of delay before the module reports atrouble for not being able to receive signals from acell tower.

70 Reporting Delay forSingle Tower

0 – 3600 sec. (0) Amount of time delay before module reports atrouble due to getting signals from only one towerinstead of multiple towers.

71 Modem ResetCount

0 – 99 communication attempts(5)

This parameter determines how many times apacket of data must be sent without a reply beforethe cell module modem is reset to attemptrestoring communications.Note: When connected to a B5512/B4512 orD9412GV4/D7412GV4 control panel at v2.03 orhigher, the default is zero and controlled by theabove mentioned control panel, unless controlpanel programming is disabled.

72 TCP Keep AliveTime

0 – 255 sec (45) This parameter determines how long to waitbetween transmissions to keep an idle TCPconnection to a remote host from terminating dueto inactivity.

Table 5.7: SMS and USB configuration parameters

48 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 49: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Short Message Service (SMS) configurationThe B450 supports configuration by SMS connection. When enabled via the Inbound SMSparameter, the Short Message Service feature allows an installer to configure the B450through the use of a mobile phone, or any other service that sends compatible SMS textmessages.

Notice!

SMS text messages are not processed when the Inbound SMS parameter is set to: Disabled.

The default setting is Enabled.

Use SMS to configure the B450The SMS string follows a specific format. If the configuration message exceeds 160characters, you must send multiple messages. Refer to Compose the Configuration SMS formore details.When the B450 receives the final valid part of an SMS message, it accepts the configuration.

Notice!

To allow the receipt of SMS data, the bus address switch must be set at position 0. Refer to

the tables in this section for LED activity.

If the bus address switch is not set to 0, incoming SMS data is discarded.

Enter CONFIG MODEEnsure that the bus address switch is set to 0.

Compose the Inbound SMSUse the appropriate SMS template for the selected mode of operation, and compose theconfiguration SMS message on your mobile phone. SMS can contain only 160 characters.Refer to Multiple SMS Messages (for Messages Longer than 160 Characters) for instructionsfor sending a multiple SMS configuration. The information in the tables below contain only the essential configuration IDs. For additionalconfiguration IDs, refer to the SMS configuration parameters. To configure a B450 parameterusing SMS text, format the text as follows : %1;1=B450;19=1;!The configuration message must begin with the sequence number (%1) and must include thecurrent B450 configuration password (default = B450) followed by the ID number and thevalue you want to set.

Notice!

Separate each ID or value pair with a semi-colon ; (for example, %1;1=B450;19=1;!). To allow

spanning of configuration across multiple messages, each SMS starts with the sequence

number followed by the command line separator.

Use the ! character to signal the end of the configuration data. Refer to your cellular phone’s

documentation for available characters. You must include the current SMS configuration

passcode in the SMS text message to allow the module to save the new configuration data.

5.3

5.3.1

Conettix Plug-in CommunicatorInterface

Configuration | en 49

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 50: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Removing parameter textIn order to remove text from an SMS message, you must use the word None, or ;. Forinstance, if you want to remove a SIM PIN using SMS, you would include either:4=None or 4=; in the text message.

Notice!

The word None is NOT case sensitive.

SMS configuration parameters

ID Description

1= Current passcode (4 to 10 characters); default = B450

2= New passcode (4 to 10 characters)

4= SIM PIN (4 to 8 characters)

Basic parameters

10= Network Access Point Name (APN): Text characters thatcan fit in a single text message

11= Network Access Point User Name (up to 30 characters)

12= Network Access Point Password (up to 30 characters)

13= TCP/UDP port number: 7700 (1 to 65535)

15= AES encryption– 0 = disable– 1 = 128 bit– 2 = 192 bit– 3 = 256 bit

16= AES encryption key (0 to 9, A-F, a-f, based on key size,none, 32, 48, or 64 digits)

19= Module Enclosure Tamper (V1.0.x control panels on SDI2bus)– 0 = disable– 1 = enabled

20= Inbound SMS– 0 = disabled– 1 = enabled

Advanced parameters

57= Session Keep Alive (0 to 1000 min)

58= Inactivity timeout (0 to 1000 min)

65= IPv4 DNS Server IP Address

50 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 51: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

ID Description

66= Alternate IPv4 DNS Server IP Address

67= Panel programming– 0 = disabled– 1 = enabled

68= Reporting delay for low signal strength (0 - 3600 sec)

69= Reporting delay for no towers (0 - 3600 sec)

71= Modem reset count (0 – 99)

72= TCP keep alive time (0 – 255 sec)

Table 5.8: SMS configuration parameters

Multiple SMS Messages (for Messages Longer than 160 Characters)

ID Description Sample SMS1

%1; SMS sequence number 1 %1;1=B450;2=secret123;15=3;

16=010203040506070809101112131

41516;1=B450; Current password

2=secret123; New password (case sensitive)

15=3; Enable AES encryption

16=01020304050607080910111213141516;

Sample AES key

1As you enter in the various ID’s into your cell phone, do notpress the return key. Doing so will cause the B450 to ignorethe programming request.

Table 5.9: Double SMS example, part 1

ID Description Sample SMS2

%2; SMS sequence number%2;19=1;!

19=1; Tamper enabled

! End of configuration

2When you end the configuration programming with theexclamation mark, do not enter any values. Doing so maycause the B450 to ignore the programming request.

Table 5.10: Double SMS example, part 2

Send the Inbound SMS1. Send the configuration SMS to the B44x module’s phone number. The transmission might

take several minutes. Because the bus address switch is set to 0, the B450 waits for anSMS until a message is received.

Conettix Plug-in CommunicatorInterface

Configuration | en 51

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 52: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

2. Observe the LEDs on the B450. When the Transmit (TX) and Receive (RX) LEDs will flashin unison at a 1 second interval indicating a successful SMS was received. If the SMS wasreceived but was not valid the Transmit (TX) and Receive (RX) LEDs will alternate flashingat 1/2 second interval. Both flashing patterns will continue until the bus address switch ismoved from position "0.”

Notice!

If the LEDs indicate an invalid SMS, repeat the steps in Enter CONFIG MODE.

Refer to the tables in Maintenance and troubleshooting, page 56 section for more information

on LED descriptions. Ensure that your configuration SMS contains the correct information, as

well as sending the SMS to the correct phone number for the module, or use the USB

connection to configure the B450

Exit from CONFIG MODE1. Change the bus address switch to the desired value, depending on the supported control

panel. Changes to the B450 configuration are accepted.2. Check the signal strength and Heartbeat LED for status.

Firmware Update pageFirmware updates are performed through the USB interface via a communication programsuch as Hyper Terminal or Tera Term.

Notice!

When performing a firmware update, verify that the update software file to be downloaded is

the most current software update version. No changes to the firmware occur if the firmware

update version is the same version as the current version installed on the B450.

1. Ensure that the USB cable is connected to the B450 and the target PC or laptop.2. From Windows, start a terminal session by launching Hyper Terminal on Windows XP or

earlier, or launching Tera Term on Windows Vista/Windows 7/Windows 8.3. Log into the USB interface as described in Log into the USB interface, page 32, starting at

step 3, and continuing through to step 6. The B450 USB login window appears, listing thecurrent software version and build.

5.4

52 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 53: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Figure 5.18: B450 USB login window

4. Select option 7 Firmware Update and press [Enter].

Notice!

Once the Firmware Update menu item is selected, the B450 begins a 90 sec timer as it waits

for the firmware File>Transfer>XMODEM>Send process to begin. If the transfer process

takes longer than 90 sec to locate the file and begin the send process, the menu times out,

and the user must begin the update process again.

1. From the Tera Term main menu, select File>Transfer>XMODEM>Send.

Conettix Plug-in CommunicatorInterface

Configuration | en 53

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 54: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Figure 5.19: Firmware update send window

2. In the XMODEM Send dialog window, navigate to the folder location and select thefirmware update software you downloaded. The file ends in *.kfw extension.

Figure 5.20: File navigation

54 en | ConfigurationConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 55: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

3. Click Open to start the firmware update. The Tera Term: XMODEM Send dialog box opensand indicates the update process.

Figure 5.21: Tera Term XMODEM Send dialog box

4. When the file transfer completes, the Tera Term: XMODEM Send dialog box closesautomatically. Within the Tera Term window an updating to firmware version “x.xx.xxx”message displays, and the B450 automatically reboots.

5. Close the Tera Term session, and re-launch Tera Term.6. Log back into Tera Term as described previously to re-establish communication from your

laptop, to the B450.Communication between the control panel and B450 is restored.

Conettix Plug-in CommunicatorInterface

Configuration | en 55

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 56: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Maintenance and troubleshootingRefer to the following for maintenance and troubleshooting information

USB menu access disabledA Menu access disabled error message occurs when the Web/USB Access Enabled feature inRPS is set to No when connected to a GV4 Series v2.03+ or B Series v2.03+ control panel.Perform the following to enable the feature:1. Launch your session of RPS.2. Login to RPS.3. Select the correct control panel.4. Select SDI2 MODULES.5. Select IP Communicator.6. Double-click on Web/USB Access Enable, and select Yes. This allows you to view or

change information from the B450 USB menu.

Figure 6.1: USB access enable

LED status indicators

Notice!

When the tamper input is shorted, the firmware version flashes, then the B450 LEDs are

disabled to conserve power. To see the troubleshooting LEDs, open the tamper circuit or

jumper

The B450 includes the following on-board LEDs to assist with troubleshooting:– Heartbeat (system status).– RX (receive).– TX (transmit).The plug-in module also includes LEDs for troubleshooting and status.

6

6.1

6.2

56 en | Maintenance and troubleshootingConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 57: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Flash pattern Function

Flashesonce every 1 sec

Normal state. Indicates normal operation.

3 quick flashes every 1 sec

Communication error state. Indicates a buscommunication error with the control panel.

On Steady

Trouble state. Indicates a trouble conditionexists. Examine the other LEDs to determinethe trouble condition.

Off

LED trouble state. Indicates the module isnot powered up, or there is a failure in themodule. Check for proper installation.

Table 6.1: Heartbeat LED descriptions

Flash pattern Function

RX (Receive)

Flashing

Occurs every time a packet is received on-air.

TX (Transmit)

Flashing

Occurs every time a packet is transmitted on-air.

Table 6.2: RX and TX LED descriptions

Plug-in communicator LEDsFor communicator LED information, refer to the compatible communicator documentation.

Trouble condition LEDs

Condition B450 Heartbeat B450 Transmit(TX)

B450 Receive(RX)

Plug-in modulestatus

Module tamper Not indicated

Plug-in modulemissing

OnSteady

Off

1 quick flash,repeating

N/A

Conettix Plug-in CommunicatorInterface

Maintenance and troubleshooting | en 57

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 58: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Condition B450 Heartbeat B450 Transmit(TX)

B450 Receive(RX)

Plug-in modulestatus

SIM card missing

OnSteady

Off

2 quick flashes,repeating

Off

Plug-in modulenot recognized

OnSteady

Off

3 quick flashes,repeating

Off

Low bus voltage

OnSteady

Off

4 quick flashes,repeating

Off

Cellular modemfailure

OnSteady

Off

5 quick flashes,repeating

Off

Switch positiontrouble

OnSteady

Off

6 quick flashes,repeating

1 Hz Heartbeat

Configurationfailure

OnSteady

Off

7 quick flashes,repeating

Invalid SIM PIN

OnSteady

Off

8 quick flashes,repeating

Off

SIM PUKrequired

OnSteady

Off

9 quick flashes,repeating

Off

Table 6.3: B450 module related trouble conditions

58 en | Maintenance and troubleshootingConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 59: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Condition B450 Heartbeat B450 Transmit(TX)

B450 Receive(RX)

Plug-in modulestatus

No IP address

OnSteady

Off Off

2 quick flashes,repeating

Cellular numbernot activated

OnSteady

Off Off

3 quick flashes,repeating

Not enoughtowers (singletower) On

Steady

Off Off

4 quick flashes,repeating

Invalid accesspoint

OnSteady

Off Off

5 quick flashes,repeating

Low signalstrength

OnSteady

Off Off

1 Hz Heartbeat

No towers

OnSteady

Off Off OnSteady

Detecting plug-inmodule type

OnSteady

OnSteady

OnSteady

Off

Table 6.4: Plug-in module related trouble conditions

SMS configuring LEDs

Condition B450Heartbeat

B450 Transmit(TX)

B450 Receive(RX)

Plug-in modulestatus

Invalid SMS messagereceived

1 sec flash The Transmit (TX) and Receive (RX)LEDs will alternate flashing at 1/2second interval

1 sec flash

SMS configurationcomplete

1 sec flash The Transmit (TX) and Receive (RX)LEDs will flash in unison at a 1second interval

1 sec flash

Conettix Plug-in CommunicatorInterface

Maintenance and troubleshooting | en 59

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 60: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Show the firmware versionTo show the firmware version using an LED flash pattern:– If the optional tamper switch is installed:

With the enclosure door open, activate the tamper switch.– If the optional tamper switch is NOT installed:

Momentarily short the tamper pins.When the tamper switch is activated (open to closed), the heartbeat LED stays Off for 3 secbefore indicating the firmware version. The LED pulses the major, minor, and micro digits ofthe firmware version, with a 1 sec pause after each digit.The following is an example: The version 1.4.3 would show as LED flashes:[3 second pause] *__****__*** [3 second pause, then normal operation].

Figure 6.2: Firmware LED flash patterns example

SIM card

Notice!

Section 6.3 SIM card is applicable to cellular communicators that have a SIM card.

Review the following suggestions if you are experiencing problems with the SIM card. This isapplicable to cellular communicators that have SIM cards.– Check for the presence of a SIM in the holder.– SIM card must be installed at power up in order to be recognized.– Check for damage to the SIM card holder.– Remove and reseat the SIM card in the holder, checking for worn contacts or looseness

between the holder and the SIM card.– Reboot the system.– If the problem persists after rebooting the system, replace the SIM card. A new SIM card

might require the B450 to be reconfigured to the new card’s parameters (if using adifferent carrier or provider).

Diagnostic logThe Diagnostic Log option is used in the event of an intermittent service outage, orcommunication error, in which a diagnostic log can be generated from the B450 menu options.The generated diagnostic log file is used by TECHNICAL SUPPORT to determine how often apersistent problem occurs, as well as detailed network configuration settings associated tothe module during the time of the reported problem.Generate the diagnostic log only when directed by TECHNICAL SUPPORT.

6.3

6.4

6.5

60 en | Maintenance and troubleshootingConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 61: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Understanding network pollingPlan carefully when programming the control panel poll time, ACK wait times, retries, andD6x00 Receiver poll and supervision time. Having the wrong or improper control panelsettings could cause trouble conditions when the network carrier performs maintenance, andincreased data volumes that could effect your monthly cost. Your settings for theseparameters determine how the system works, but depend on the security level needed.For more information regarding proper data plans and installation parameters related tonetwork polling, refer to Bosch Cellular Service User Guide (P/N: F01U273558).

Control panel programming using cellularFor more information regarding proper planning and installation parameters related to VPNsetup for control panel programming, refer to Bosch Cellular Service User Guide (P/N:F01U273558).

6.6

6.7

Conettix Plug-in CommunicatorInterface

Maintenance and troubleshooting | en 61

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 62: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Specifictions and certificationsRefer to the following for specification and certification information.

Technical specificationEnvironmental considerations

Relative humidity Up to 93% non-condensing

Temperature (operating) 0゚ - +49゚C (+32゚ - 120゚F)

Properties

Dimensions (HxWxD) 79 mm x 128 mm x 38 mm (3.11 in x 5.03 in x 1.50 in)

Power requirements

Current Standby: B450 with B440/B441/B442/B443 = 75 mAAlarm: B450 with B440/B441/B442/B443 = 180 mA

Voltage (B450 bus operation): 12 VDC nominal

Wiring

Bus wire gauge 12 AWG to 22 AWG

Bus wire length Maximum distance – Wire size :22 AWG (0.65 mm) --> 12 m (40 ft)18 AWG (1.0 mm) --> 30 m (100 ft)16 AWG (1.3 mm) --> 48 m (158 ft)12 AWG (2.0 mm) --> 122 m (400 ft) Using a separate UL listed power supply, such as the B520Auxiliary Power Supply Module, connected to the B450 withinthe specification listed above, the wire distance can beextended up to 300 m (1000 ft)

USB cable Type A male-to-male (It is recommended to use a Boschsupported USB cable such as the B99 cable (F01U278853).

Compatible enclosures

B10 ᅳ 35.6 cm x 31.8 cm x 7.6 cm (14 in x 12.5 in x 3 in)

B11 ᅳ 27.8 cm x 25.9 cm x 8.32 cm (10.9 in x 10.2 in x 3.3 in)

D8103 ᅳ 41 cm x 41 cm x 9 cm (16 in x 16 in x 3.5 in)

D203 ᅳ 19.68 cm x 13.05 cm x 6.35 cm (7.75 in x 5.14 in x 2.50 in)

Notice!

Temporary loss of communication may be caused by static when using anyone of the above

enclosures.

7

7.1

62 en | Specifictions and certificationsConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 63: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Compatible control panels

B5512/B4512/B3512

B5512E/B4512E/B3512E

D9412GV4/D7412GV4 (v2.xx+)

D9412GV4/D7412GV4 (v1.xx+)

D9412GV3/D7412GV3/D7212GV3

D9412GV2/D7412GV2/7212GV2 (v7.07+)

FPD-7024 (v1.03+)

AMAX 2000/2100/3000/4000

CMS 6/8, CMS 40

Easy Series v3+

Solution 2000/3000

Compatible cellular modules

B440 Conettix Plug-in Communicator, Cellular (3G)

B441 Conettix Plug-in CDMA Cellular Communicator

B442 Conettix Plug-in GPRS Cellular Communicator (SIM card required)

B443 Conettix Plug-in HSPA+ Cellular Communicator (SIM card required)

Conettix Plug-in CommunicatorInterface

Specifictions and certifications | en 63

Bosch Security Systems, Inc. Installation and Operation Guide 2014.10 | 05 | F.01U.300.740

Page 64: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control

Certifications

Region Certification

US NIST FIPS 197 AES Certification (IP Communications)

FCC Part 15 Class B

UL 365 – Police Station Connected Burglar Alarm Units and Systems

UL 636 – Hold Up Alarm Units and Systems

UL 864 – Control Units and Accessories for Fire Alarm Systems

UL 985 – Household Fire Warning System Units

UL 1023 – Household Burglar Alarm System Units

UL 1076 – Proprietary Burglar Alarm Units and Systems

UL 1610 – Central Station Burglar Alarm Units

SIA CP-01:2010 False Alarm Reduction

California State Fire Marshall (CSFM)

Fire Department of New York (FDNY) - Certified

Canada CAN/ULC S303 - Local Burglar Alarm Units and Systems

CAN/ULC S304 - Signal Receiving Centre and Premise Alarm Control Units

ULC-ORD C1023 - Household Burglar Alarm System Units

ULC-ORD C1076 - Proprietary Burglar Alarm Units and Systems

ICES-003 - Digital Apparatus

Europe CE - EMC Directive 2004/108/EC

Australia A-Tick Certified

7.2

64 en | Specifictions and certificationsConettix Plug-in Communicator

Interface

2014.10 | 05 | F.01U.300.740 Installation and Operation Guide Bosch Security Systems, Inc.

Page 65: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control
Page 66: Conettix Plug-in Communicator Interfaceresource.boschsecurity.us/documents/B450_IOG... · 2014-12-15 · The B450 Conettix Plug-in Communicator Interface (wired to a compatible control