Upload
rselec
View
217
Download
0
Embed Size (px)
Citation preview
8/6/2019 ConexionTransformadoresEnGD
1/7
1
Abstract-- The interconnection of Distributed Generation(DG) into the power distribution system creates many challenges
for utilities. Many of these challenges are related to the type of
interconnection transformer (or lack thereof) and consequently
the grounding used for the DG interconnection. There remains
confusion about the various transformer types for DG
interfacing. This is a critical point because the selection of the
correct interface with the local utility will simplify feasibility
studies; therefore, decreasing the overall cost of the DG
interconnect investigation to benefit all. This paper discusses the
advantages and disadvantages of different interconnectingtransformers. Neutral reactor sizing for grounding transformer
connections is discussed.
Index Termsdistributed generation; grounding; neutral
reactor; isolation transformer
I. INTRODUCTION
ntroducing Distributed Generation (DG) into a distribution
system designed for radial power flow creates many issues
including but not limited to: harmonic concerns, system
overvoltages, fault coordination, increased fault currents,
insulation coordination, and islanding concerns. The addition
of DG may also alter the distribution of fault current affectingthe existing overcurrent protection coordination.
The added DG may expose the existing utility system to
temporary system overvoltages that are damaging to the line-
to-neutral-connected electrical equipment. For example, Fig.
1 illustrates typical phase voltages when a single line-to-
ground (SLG) fault is applied at Phase C. Fig. 1(a) illustrates
the pre-fault condition, (b) illustrates a system that is not
effectively grounded, and (c) illustrates a system that is
effectively grounded. As can be seen in Fig. 1 (b), there are
excessive voltages on the unfaulted phases that will cause
damage to surge arresters and other electrical equipment.
This condition may occur when a DG becomes islanded onthe faulted section.
This issue as well as other conditions yielding overvoltages
on the distribution system may be alleviated by choosing an
appropriate interconnection transformer that maintains an
effectively grounded system at all times. However, this may
R. F. Arritt is with EPRI, Knoxville, TN 37932 USA (email:
R. C. Dugan is with EPRI, Knoxville, TN 37932 USA (email:
change the flow of fault current effecting the existing ground
fault protection. The selection of DG interconnection
transformer will also have an effect on the insulation
coordination and the flow of third harmonics.
V a
V c
V b
V a G N D = 1 p u
V a G N D = 1 . 2 5 t o 1 . 7 3 p u
V a
V c
V b
V a G N D = < 1 . 2 5 p u
V a
V b
V c
P r e - F a u l t C o n d i t i o n
S L G - F a u l t C o n d i t i o n
N o t E f f e c t i v e l y G r o u n d e d S y s t e m
S L G - F a u l t C o n d i t i o n
E f f e c t i v e l y G r o u n d S y s t e m
1 . 2 1
1 . 2 5
1 . 7 3
1 . 7 3
1 . 0
1 . 0
1 . 0
( a )
( b ) ( c )
Fig. 1 Neutral Shift During Single Line to Grounded Fault (SLG) on Phase C
(a) Pre-Fault Condition (b) Not Effectively Grounded System (c) Effectively
Grounded System
II. DIRECT DGCONNECTION
While it is possible to obtain DG rated for the utility
medium voltage (MV) distribution system, there can beconsiderable risks in connecting such equipment directly to
utility distribution system. This is particularly risky for
installations fed by overhead lines. The insulation level of the
machines may not coordinate with the utility system.
Interconnecting DG through a transformer can eliminate many
of the difficulties that may occur with directly-connected DG
installations. Therefore, direct connection is often
discouraged.
Distributed Generation Interconnection Transformer
and Grounding SelectionR. F. Arritt,Member, IEEE, and R. C. Dugan, Fellow, IEEE
I
2008 IEEE.
8/6/2019 ConexionTransformadoresEnGD
2/7
2
III. INTERCONNECTION TRANSFORMER CONFIGURATIONS
Several of the concerns with the interconnection of DG can
be addressed, or at least minimized, through means of an
appropriately-configured interconnection transformer. Three
interconnection transformer winding configurations will be
discussed here along with their advantages and disadvantages
with respect to system protection (overvoltages and fault
current), harmonic alteration, and other general system
considerations. The transformers are assumed to be sized
properly and have an appropriate insulation level for
coordination between the utility and load-side equipment.
A. Grounded-Wye (Utility) Grounded-Wye (DG)
This is a common connection applied in North American
distribution systems for three-phase loads. It is applied
because of its reduced susceptibility to ferroresonance on
cable-fed loads and fewer operating restrictions while being
switched for maintenance. It is also generally well-behaved
with respect to DG applications; however, a few issues do
exist. A summary of advantages and disadvantages are listed
below:
Advantages:
General
1) Less concern for ferroresonance in cable-fed
installations; some core designs may be more prone
than others if there is sufficient capacitance.
2) More economical than other connections in some
applications, particularly at 25 and 35 kV class
voltages.
3) More economic fusing than similarly-rated delta
connected primary winding. This may also translate
to a smaller-sized padmounted transformer.
System Protection4) No phase shift in system voltages (relaying); can
detect primary side voltages with low-voltage
relays.
Disadvantages:
General
1) DG sees same imbalance that utility system sees.
Harmonics
2) Will directly pass zero-sequence harmonic currents
(such as the 3rd harmonic).
System Protection
3) DG may feed into any type of fault that is on the
utility system.4) Utility will supply fault current for internal
generator ground faults, increasing fault damage.
5) Does not necessarily provide an effectively
grounded source when islanded despite the fact that
both windings are solidly grounded. Ground
reference will be provided by the generator and/or
load.
Because of the fact that this type of connection allows the
DG to feed into all fault types and also does not inhibit the
flow of zero-sequence harmonics, it may be difficult to
operate some generators in parallel with the utility system
using this transformer connection. Synchronous generators
may produce third harmonic voltage distortion, depending on
its winding pitch. This connection provides a very low
impedance path for the third harmonics when paralleled to the
utility system. This decreased impedance path may add or
sink neutral harmonic current, damaging the generator or
simply adding unwanted harmonic currents to the utilitysystem. A neutral reactor may be added to limit the flow of
zero-sequence harmonics and fault currents. Care must be
taken when sizing the reactor (see following paragraph). The
interconnection diagram shown in Fig. 2 shows a typical
grounded-wye/grounded-wye installation.
Despite the fact that both windings of the grounded-
wye/grounded-wye transformer are grounded, this connection
may not provide an effectively-grounded source to the utility
system when the DG becomes islanded. This is brought about
by the fact that some generators are not themselves effectively
grounded.
For example, the ground fault current from a solidlygrounded synchronous generator is typically larger than the
three-phase fault current due to the fact that the neutral zero-
sequence impedance of a synchronous generator is typically
smaller than the sub-transient positive-sequence reactance.
Therefore, a common approach to limiting the ground fault
current is to ground the synchronous generator through an
impedance between the neutral point and ground. This added
impedance may result in the DG not being effectively
grounded while in an islanded condition. Fig. 3 uses the
sequence diagram for the SLG fault situation to illustrate the
flow of zero-sequence current through an islanded DG with a
grounded-wye/grounded-wye transformer and a grounding
reactor.
Also, inverters used to connect such generation as
microturbines and photovoltaics need isolation and will
generally not be grounded at all. Likewise, induction
generators seldom have a connection to ground. Thus, DG
relying on these technologies will not provide an effectively-
grounded source to the utility when interconnected with a
grounded-wye/grounded-wye transformer. The characteristics
with respect to many power system faults and other
disturbance events are similar to the delta/wye connection
(discussed below).
Fig. 2. Grounded Wye/Wye Interconnection Transformer
8/6/2019 ConexionTransformadoresEnGD
3/7
3
Z t r a n s f o r m e r + Z p o s g e n
Z e q u i v a l e n t
Z e q u i v a l e n t
Z e q u i v a l e n t
3 x Z N
D G S i d e
U t i l i t y S i d e
P o i n t o f C o m m o n
C o u p l i n g
Z t r a n s f o r m e r + Z n e g g e n
Z t r a n s f o r m e r + Z z e r o g e n
S y s t e m N e u t r a l R e f e r e n c e
a f t e r I s l a n d i n g
P o s i t i v e S e q u e n c e
N e g a t i v e S e q u e n c e
Z e r o S e q u e n c e
Fig. 3. Grounded Wye/Wye Interconnection Transformer Sequence Diagram
B. Delta (Utility) Grounded-Wye (DG) Interconnection
Transformer
This is another common connection for three-phase loads
in North America, and the most common connection in
European-style systems. It would probably be favored for
serving loads in most cases if it were not for the susceptibility
of the connection to ferroresonance in the types of cable-fed
systems common in North America. A summary of
advantages and disadvantages are listed below:
Advantages:
Harmonics
1) Triplen harmonics from the DG do not reach the
utility system.
System Protection
2) Provides some isolation from voltage sags due to
utility-side single line-ground (SLG) faults, allowing
the DG to better ride through voltage sags.
3) Does not feed directly into utility-side SLG faults (it
can contribute through other ground sources on the
utility system).
Disadvantages:
General
1) Very prone to ferroresonance in cable-fed
installations, especially during open conductor fault
conditions.
Harmonics
2) Depending on generator neutral grounding, 3rd
harmonics in the DG may cause excessive current in
the DG-side neutral.
System Protection
3) Cannot provide an effectively grounded system
during islanding or open conductor conditions i.e. If
islanded on SLG fault, can subject utility arresters
to overvoltages.
4) Difficult to detect some utility-side SLG faults from
the generator side by voltage relaying alone. The
delta winding tends to hold the generator side
voltage magnitudes up and in the proper phase
relationship. Primary-side relaying is often requiredto ensure rapid detection.
5) Due to the susceptibility to ferroresonance,
instantaneous overvoltage relaying (59I) is often
required to ensure prompt detection of this
condition.
This type of connection is not alone in being prone to
ferroresonance and subjecting arresters and loads to
overvoltages during single-line-to-ground faults. This concern
is shared with all transformers that have an ungrounded
primary connection.
While this type of connection prevents most third harmonic
currents that might emanate from the DG from reaching theutility, it does not prevent their flow on the DG side. As
discussed in the previous section, a neutral reactor is typically
used to limit the third harmonic current flow if the generator
is not of 2/3 pitch design which minimizes the 3rd
harmonic.
While the winding connection can be beneficial to the load
in reducing the impact of voltage sags due to SLG faults, it
also makes some SLG faults on the utility system more
difficult to detect. This increases the likelihood of islanding
because it will delay fault detection until the utility breaker
operates for many faults. As with all ungrounded primary
connections, there is danger in being islanded on a SLG fault
with very light load even briefly because this can result in asevere resonant condition.
Therefore, it is common to add other relaying functions to
aid in the early detection of utility-side faults when this
connection is used. A negative sequence relay can make the
detection more reliable and will also help detect single-
phasing conditions in which a fuse has blown. While the
voltage magnitudes seen on the secondary may not change
sufficiently, they will become unbalanced, resulting in
detectable negative sequence voltages and currents. Care must
be taken not to set these relays too sensitive, resulting in
nuisance generator tripping.
A common approach to more sensitive utility-side fault
protection is to add relaying on the primary side of the
transformer, such as a ground overvoltage (59N or 59G) relay
that can detect the presence of the SLG fault. This is
implemented by installing potential transformers (PTs) on the
primary system and then placing a voltage relay in the corner
of the delta winding on the instrumentation transformer. The
interconnection diagram shown in Fig. 4 shows a typical
delta/grounded-wye installation.
8/6/2019 ConexionTransformadoresEnGD
4/7
4
Fig. 4. Delta/Grounded Wye Interconnection Transformer Connection
C. Grounded-wye (Utility) Delta (DG) Interconnection
Transformer
This connection is rarely used on utility power distribution
systems to serve loads, but is considered by many as the best
way to interconnect large three-phase DG. This transformer
connection is often referred to as a grounding bank and has
a number of special characteristics that must be considered in
its application on utility power systems. A summary of
advantages and disadvantages are listed below:
Advantages:
General
1) Protection schemes are well understood by both
vendors of larger DG equipment and utility
protection engineers.
Harmonics
2) Triplen harmonic currents that might be produced
by the generator are blocked by the delta winding
and cannot flow on the generator side and,
therefore, are not passed on to the utility power
system.
System Protection3) Utility-side faults are generally more readily
detected by the DG system protection because the
transformer itself actually participates in all ground
faults. This generally allows the DG to disconnect
more quickly. (This connection is also known as a
grounding transformer or a ground source.)
4) Should the DG become isolated from the utility
source (islanded), this connection helps the DG
system to present an effectively grounded source to
the utility distribution system and avoid the
resonance and overvoltage issues of other
connections.
Disadvantages:
Harmonics
1) Triplen harmonic currents already present in the
utility system from other sources will tend to flow
into transformers with this winding connection,
contributing to transformer heating.
2) The flow pattern for triplen harmonic currents on
the distribution system is altered, which could be
either beneficial or detrimental to
telecommunications interference and neutral-to-
ground voltages depending on the path taken by the
currents. This is difficult to predict prior to
construction and can require mitigation after
commissioning should complaints arise from
customers.
System Protection
3) Contributes strongly to all ground faults, which can
increase damage due to high fault currents.
4) The connection contributes to sympathetic trippingof the feeder breaker for faults on other feeders.
The transformer supplies current to other feeders
connected to the same substation bus. Ground trip
pickup levels must be increased to maintain
coordination, which results in less sensitive fault
protection.
5) Utilities may have to change relaying depending on
whether a transformer of this type is connected or
disconnected. This requires expensive
communications and control equipment that might
not be needed for the other connections.
6) The transformer itself is subject to short-circuit
failure when the fault occurs. This is particularlytrue for smaller transformer banks with impedances
less than 4-5%. A special transformer must
generally be ordered.
The fact that this transformer acts as a ground source is
undesirable on many distribution systems and few utilities will
allow this connection on the distribution system without
special study. Implementing this connection often implies
changes to the feeder overcurrent protection scheme that are
costly either in terms of having to replace equipment or of
inconvenience to other customers on the feeder.
Fig. 5 shows how the connection contributes to a SLG fault
on a 4-wire, multi-grounded neutral distribution system, the
most common in the U.S. Fig. 5(a) illustrates a ground fault
when the DG transformer is not connected. Fig. 5(b)
illustrates a ground fault when the DG transformer is
connected. The arrows show the paths of the current from the
grounded-wye/delta DG interconnection transformer. The
currents flow back through the solidly-grounded substation
transformer and contribute additional current to the fault. The
amount contributed would depend on the size and impedance
of the transformer.
Fig. 7 shows the sequence network to illustrate this
increased ground fault contribution from this transformer
configuration. When this Figure is compared to Fig. 6, it canbe seen that the zero-sequence current is divided between the
utility and DG connection. This increases the overall ground
fault contribution but reduces the ground fault current seen
at the substation.
Note: The DG contribution in Fig. 5 will be dependent on
the capability of the DG to supply fault current. In many
ground fault cases, the contribution due to the transformer
alone will be larger. The connection of the DG device (delta,
grounded-wye, or ungrounded-wye) is irrelevant for faults on
the utility side of the interconnection.
8/6/2019 ConexionTransformadoresEnGD
5/7
5
S u b s t a t i o n
T r a n s f o r m e r
S e c o n d a r y
D G
* F a u l t c u r r e n t i s
a p p r o x i m a t e l y e q u a l t o t h e
c u r r e n t t h r o u g h t h e
s u b s t a t i o n n e u t r a l r e a c t a n c e .
S u b s t a t i o n
T r a n s f o r m e r
S e c o n d a r y
* * T h e g r o u n d e d - w y e
D G t r a n s f o r m e r
d e c r e a s e s t h e z e r o -
s e q u e n c e i m p e d a n c e
w h i c h i n c r e a s e s t h e
t o t a l f a u l t c u r r e n t
c o m p a r e d t o t h e
e x a m p l e w i t h o u t t h e
g r o u n d e d - w y e D G
t r a n s f o r m e r .
F a u l t *
F a u l t * *
( a )
( b ) Fig. 5. Grounded-wye/delta transformer for DG interconnection can feed ground
faults on 4-wire multi-grounded neutral systems, introducing additional fault
stresses and interfering with utility-side protective relaying (a) Without
Transformer Connection (b) With Transformer Connection
Fig. 6. Sequence Diagram for SLG Fault in system without any Ground
Wye/Delta Transformer Connection
Fig. 7. Sequence Diagram for SLG Fault with Grounded-Wye/DeltaTransformer Connected
If this connection is to be used on a typical North
American distribution system, some of the options for better
accommodating it are:
1. Ground the transformer through a neutralreactance of sufficient size to limit the fault
current contribution and the amount of
unbalanced load current the transformer would
have to absorb. (Discussed in next section.)
2. Increase ground trip pickup settings on feederbreakers and line reclosers.
Since this connection is unusual for distribution systems,
but has some clear advantages for interconnecting DG, the
remainder of this paper will be devoted to issues related to
implementing it with a neutral grounding reactor.
IV. GROUNDED-WYE (UTILITY)DELTA (DG)
INTERCONNECTION TRANSFORMER WITH A GROUNDING
REACTOR
As discussed in the previous section, a neutral reactor may
be added to this connection to make it more compatible with
typical distribution system design by limiting fault currents,unbalance currents, and harmonic currents. If the neutral
reactor is sized properly, the grounded-wye/delta transformer
connection can provide an effectively grounded DG interface
under all circumstances without excessive interference with
system operation and other utility customers on the system.
The interconnection diagram shown in Fig. 8 shows a typical
grounded-wye/delta installation with a neutral impedance.
Fig. 9 shows the sequence network for a SLG fault
condition to illustrate the effect of the added neutral reactor.
When compared to Fig. 7, the added reactor increases the
8/6/2019 ConexionTransformadoresEnGD
6/7
6
effective zero-sequence impedance, decreasing the overall
ground fault contribution of the transformer. Not only does it
reduce the total ground fault current when compared to Fig. 7,
but when the zero-sequence current is divided between the
utility and the DG connection, more current will flow through
the utility connection allowing the ground fault protection to
work closer to its original ground fault settings.
With the addition of this neutral reactor, a neutral shift is
introduced. When sizing the neutral reactor, one design goal isto not expose the distribution system to line-to-ground
voltages during a ground fault during an islanding condition
that greatly exceed the voltages under the same conditions
with the utility source alone.
The selection of the grounding reactor size is a trade-off
that minimizes the risks associated with harmonics, ground
fault currents and overvoltages. However there is one caveat:
the addition of future DG with this transformer connection
may alter the optimal size of this neutral reactor, complicating
reactor sizing. The design must leave a certain amount of
margin for future DG addition.
Fig. 8. Grounded-Wye/Delta Transformer with Added Neutral Reactor
Z t r a n s f o r m e r
Z e q u i v a l e n t
Z e q u i v a l e n t
Z e q u i v a l e n t
3 x Z N
D G S i d e
U t i l i t y S i d e
P o i n t o f C o m m o n
C o u p l i n g
P o s i t i v e S e q u e n c e
N e g a t i v e S e q u e n c e
Z e r o S e q u e n c e
Z p o s g e n
Z t r a n s f o r m e r
Z n e g g e n
Z t r a n s f o r m e r
Z z e r o g e n
A d d e d N e u t r a l
R e a c t o r
Fig. 9. Grounded-Wye/Delta Transformer Sequence Diagram for SLG Fault
with Added Neutral Reactor
A. Neutral Grounding Reactor Sizing
The proper sizing of a neutral grounding reactor on a
grounded-wye/delta interconnection transformer is a
compromise of three (3) conflicting goals. The impedance
must be:
1. High enough to limit the maximum fault currentcontribution to a value acceptable to utility to
which the proposed DG is to be connected, and
to prevent failure of the grounding bank itself
due to high fault currents flowing repeatedly in
its windings.
2. High enough to limit circulating currentssufficiently for continuous operation in
unbalanced conditions.
3. Low enough to maintain an effectivelygrounded system on the utility should the DG
become separated from the utility system while
the DG is operating.
In order to be low enough to maintain an effectivelygrounded system the following criteria must be met [2]:
3/ 10 XX and 1/ 10 XR
Therefore, to keep the system effectively grounded during
a possible islanding condition the reactor size needs to be
limited to the value calculated below [1]:
3/011 TGTN XXXX +
where
=NX neutral reactance
=0TX transformer zero-sequence reactance
=1TX transformer positive-sequence reactance
=1GX generator (DG) positive-sequence reactance
The above calculation only guarantees effective grounding
for the interconnection point. For faults at other locations on
the feeder the zero- and positive-sequence impedances
between the ground fault location and the DG need to be
added toXT0 andXT1. The resistance portion has been ignored
because of the small resistance values associated on
transformers and generators; however, they may need to beincluded with the addition of feeder [7].
Reference [4] states a typical ohmic value of a neutral
reactor to be within 1.0 to 1.5 times the transformer zero-
sequence reactance. This typical range of values is on a
system that limits temporary overvoltages during line-to-
ground faults to 122% and permits only a 5% reduction in
feeder ground protection sensitivity from a case with no DG
connected [4] . The authors have worked on cases where
values between 4 and 5 ohms have been used on 15-kV class
distribution systems for 5MW DG interconnects. This gives
8/6/2019 ConexionTransformadoresEnGD
7/7
7
the reader some idea of the ranges of values necessary for
acceptable operation.
As stated previously, the addition of future DG with the
same transformer connection on the feeder may require the
neutral reactor size be altered in order to meet the above
design criteria. The technical solution may be straightforward,
but the commercial solution is often contentious.
V. CONCLUSIONS
Connecting DG with a grounded-wye/delta, or grounding
bank, transformer connection has advantages over other
common connections used for loads by maintaining an
effectively grounded system even when the DG becomes
islanded. However, this connection cannot exist on many
distribution systems without an appropriately-sized neutral
reactor to limit zero-sequence currents. The proper sizing of
the neutral grounding reactor is a compromise between
conflicting objectives and must be done with careful study.
The neutral reactor size may need to change to accommodate
future DG on the system in order to maintain the ground-fault
contribution and overvoltages to acceptable levelsThe implementation of this transformer (as with all
interface transformers) with the appropriate insulation level
will provide proper insulation coordination between utility
and load-side equipment.
VI. REFERENCES
[1] EPRI 1000419, Engineering Guide for Integration of DistributedGeneration and Storage into Power Distribution, Electric Power
Research Institute, Palo Alto, CA 2002.
[2] IEEE Guide for the Application of Neutral Grounding in ElectricalUtility SystemsPart I: Introduction, IEEE Standard C62.92.1-2000,
Sept. 2000.
[3] IEEE Guide for the Application of Neutral Grounding in ElectricalUtility Systems, Part IV Distribution, IEEE Standard C62.92.4-1991,
Jul. 1992.
[4] Nagpal, Plumptre, Fulton, and Martinich, Dispersed Generation-UtilityPerspective, IEEE Transactions on Industry Applications, May/June
2006, Volume 42 No. 3, Page(s):864 872.
[5] R.C. Dugan, On The Necessity Of Three-Phase Feeder Models For DgPlanning Analysis, IEEE Power Engineering Society Summer Meeting
Conference Proceedings, 2002, Volume 1, Page(s):438 441.
[6] R.C. Dugan, M.F. McGranaghan, S. Santoso, H.W. Beaty, ElectricalPower Systems Quality 2nd Edition. New York: McGraw-Hill, 2002, pp.
373-435.
[7] T.A. Short, Electric Power Distribution Handbook. New York: CRCPress, 2000, p. 651-748.
VII. BIOGRAPHIES
Robert F. Arritt (M96) is a Power Systems
Engineer for EPRI in Knoxville, TN. He holds a
BSEE degree from West Virginia Institute of
Technology, Montgomery, WV (2000) and an
MSEE degree from Worcester Polytechnic Institute
in Worcester, MA (2005).
His employment experience included Raytheon in
Sudbury, MA where he worked in the Power and
Electronic Systems Department. At Raytheon he was awarded the 2006
Raytheon Technical Honors Award for Peer and Leadership Recognition for
Outstanding Individual Technical Contribution and also received a 2005
Raytheon Authors Award for work on Phase-Shifted Transformers for
Harmonic Reduction.
Mr. Arritt has spent most of his career designing and modeling power
systems from the electronics level to ac generation. Recently, Mr. Arritt has
been actively involved in distributed generation impact studies.
Roger C. Dugan (M74SM81F00) is Sr.
Technical Executive for EPRI in Knoxville, TN. He
holds the BSEE degree from Ohio University, Athens,
OH (1972) and the MEEPE degree from Rensselaer
Polytechnic Institute, Troy, NY (1973).
From 1992-2004, he served as Sr. Consultant forElectrotek Concepts, Knoxville, TN. From 1973
1992 he held various positions in the Systems
Engineering department of Cooper Power Systems in
Canonsburg, PA and Franksville, WI. Roger has worked on many diverse
aspects of power engineering over his career because of his interests in applying
computer methods to power system simulation. The focus of his career has been
on utility distribution systems. He has been particularly active in developing
advanced methods for analysis of distribution systems with distributed
generation. He was elected an IEEE Fellow in 2000 for his contributions in
harmonics and transients analysis. He is coauthor of Electrical Power Systems
Quality published by McGraw-Hill, 2nd edition. He is currently Chair of the
IEEE PES Power Systems Analysis, Computing, and Economics Committee. He
was the 2005 recipient if the IEEE Excellence in Distribution Engineering
Award.