ConexionTransformadoresEnGD

  • Upload
    rselec

  • View
    217

  • Download
    0

Embed Size (px)

Citation preview

  • 8/6/2019 ConexionTransformadoresEnGD

    1/7

    1

    Abstract-- The interconnection of Distributed Generation(DG) into the power distribution system creates many challenges

    for utilities. Many of these challenges are related to the type of

    interconnection transformer (or lack thereof) and consequently

    the grounding used for the DG interconnection. There remains

    confusion about the various transformer types for DG

    interfacing. This is a critical point because the selection of the

    correct interface with the local utility will simplify feasibility

    studies; therefore, decreasing the overall cost of the DG

    interconnect investigation to benefit all. This paper discusses the

    advantages and disadvantages of different interconnectingtransformers. Neutral reactor sizing for grounding transformer

    connections is discussed.

    Index Termsdistributed generation; grounding; neutral

    reactor; isolation transformer

    I. INTRODUCTION

    ntroducing Distributed Generation (DG) into a distribution

    system designed for radial power flow creates many issues

    including but not limited to: harmonic concerns, system

    overvoltages, fault coordination, increased fault currents,

    insulation coordination, and islanding concerns. The addition

    of DG may also alter the distribution of fault current affectingthe existing overcurrent protection coordination.

    The added DG may expose the existing utility system to

    temporary system overvoltages that are damaging to the line-

    to-neutral-connected electrical equipment. For example, Fig.

    1 illustrates typical phase voltages when a single line-to-

    ground (SLG) fault is applied at Phase C. Fig. 1(a) illustrates

    the pre-fault condition, (b) illustrates a system that is not

    effectively grounded, and (c) illustrates a system that is

    effectively grounded. As can be seen in Fig. 1 (b), there are

    excessive voltages on the unfaulted phases that will cause

    damage to surge arresters and other electrical equipment.

    This condition may occur when a DG becomes islanded onthe faulted section.

    This issue as well as other conditions yielding overvoltages

    on the distribution system may be alleviated by choosing an

    appropriate interconnection transformer that maintains an

    effectively grounded system at all times. However, this may

    R. F. Arritt is with EPRI, Knoxville, TN 37932 USA (email:

    [email protected])

    R. C. Dugan is with EPRI, Knoxville, TN 37932 USA (email:

    [email protected]

    change the flow of fault current effecting the existing ground

    fault protection. The selection of DG interconnection

    transformer will also have an effect on the insulation

    coordination and the flow of third harmonics.

    V a

    V c

    V b

    V a G N D = 1 p u

    V a G N D = 1 . 2 5 t o 1 . 7 3 p u

    V a

    V c

    V b

    V a G N D = < 1 . 2 5 p u

    V a

    V b

    V c

    P r e - F a u l t C o n d i t i o n

    S L G - F a u l t C o n d i t i o n

    N o t E f f e c t i v e l y G r o u n d e d S y s t e m

    S L G - F a u l t C o n d i t i o n

    E f f e c t i v e l y G r o u n d S y s t e m

    1 . 2 1

    1 . 2 5

    1 . 7 3

    1 . 7 3

    1 . 0

    1 . 0

    1 . 0

    ( a )

    ( b ) ( c )

    Fig. 1 Neutral Shift During Single Line to Grounded Fault (SLG) on Phase C

    (a) Pre-Fault Condition (b) Not Effectively Grounded System (c) Effectively

    Grounded System

    II. DIRECT DGCONNECTION

    While it is possible to obtain DG rated for the utility

    medium voltage (MV) distribution system, there can beconsiderable risks in connecting such equipment directly to

    utility distribution system. This is particularly risky for

    installations fed by overhead lines. The insulation level of the

    machines may not coordinate with the utility system.

    Interconnecting DG through a transformer can eliminate many

    of the difficulties that may occur with directly-connected DG

    installations. Therefore, direct connection is often

    discouraged.

    Distributed Generation Interconnection Transformer

    and Grounding SelectionR. F. Arritt,Member, IEEE, and R. C. Dugan, Fellow, IEEE

    I

    2008 IEEE.

  • 8/6/2019 ConexionTransformadoresEnGD

    2/7

    2

    III. INTERCONNECTION TRANSFORMER CONFIGURATIONS

    Several of the concerns with the interconnection of DG can

    be addressed, or at least minimized, through means of an

    appropriately-configured interconnection transformer. Three

    interconnection transformer winding configurations will be

    discussed here along with their advantages and disadvantages

    with respect to system protection (overvoltages and fault

    current), harmonic alteration, and other general system

    considerations. The transformers are assumed to be sized

    properly and have an appropriate insulation level for

    coordination between the utility and load-side equipment.

    A. Grounded-Wye (Utility) Grounded-Wye (DG)

    This is a common connection applied in North American

    distribution systems for three-phase loads. It is applied

    because of its reduced susceptibility to ferroresonance on

    cable-fed loads and fewer operating restrictions while being

    switched for maintenance. It is also generally well-behaved

    with respect to DG applications; however, a few issues do

    exist. A summary of advantages and disadvantages are listed

    below:

    Advantages:

    General

    1) Less concern for ferroresonance in cable-fed

    installations; some core designs may be more prone

    than others if there is sufficient capacitance.

    2) More economical than other connections in some

    applications, particularly at 25 and 35 kV class

    voltages.

    3) More economic fusing than similarly-rated delta

    connected primary winding. This may also translate

    to a smaller-sized padmounted transformer.

    System Protection4) No phase shift in system voltages (relaying); can

    detect primary side voltages with low-voltage

    relays.

    Disadvantages:

    General

    1) DG sees same imbalance that utility system sees.

    Harmonics

    2) Will directly pass zero-sequence harmonic currents

    (such as the 3rd harmonic).

    System Protection

    3) DG may feed into any type of fault that is on the

    utility system.4) Utility will supply fault current for internal

    generator ground faults, increasing fault damage.

    5) Does not necessarily provide an effectively

    grounded source when islanded despite the fact that

    both windings are solidly grounded. Ground

    reference will be provided by the generator and/or

    load.

    Because of the fact that this type of connection allows the

    DG to feed into all fault types and also does not inhibit the

    flow of zero-sequence harmonics, it may be difficult to

    operate some generators in parallel with the utility system

    using this transformer connection. Synchronous generators

    may produce third harmonic voltage distortion, depending on

    its winding pitch. This connection provides a very low

    impedance path for the third harmonics when paralleled to the

    utility system. This decreased impedance path may add or

    sink neutral harmonic current, damaging the generator or

    simply adding unwanted harmonic currents to the utilitysystem. A neutral reactor may be added to limit the flow of

    zero-sequence harmonics and fault currents. Care must be

    taken when sizing the reactor (see following paragraph). The

    interconnection diagram shown in Fig. 2 shows a typical

    grounded-wye/grounded-wye installation.

    Despite the fact that both windings of the grounded-

    wye/grounded-wye transformer are grounded, this connection

    may not provide an effectively-grounded source to the utility

    system when the DG becomes islanded. This is brought about

    by the fact that some generators are not themselves effectively

    grounded.

    For example, the ground fault current from a solidlygrounded synchronous generator is typically larger than the

    three-phase fault current due to the fact that the neutral zero-

    sequence impedance of a synchronous generator is typically

    smaller than the sub-transient positive-sequence reactance.

    Therefore, a common approach to limiting the ground fault

    current is to ground the synchronous generator through an

    impedance between the neutral point and ground. This added

    impedance may result in the DG not being effectively

    grounded while in an islanded condition. Fig. 3 uses the

    sequence diagram for the SLG fault situation to illustrate the

    flow of zero-sequence current through an islanded DG with a

    grounded-wye/grounded-wye transformer and a grounding

    reactor.

    Also, inverters used to connect such generation as

    microturbines and photovoltaics need isolation and will

    generally not be grounded at all. Likewise, induction

    generators seldom have a connection to ground. Thus, DG

    relying on these technologies will not provide an effectively-

    grounded source to the utility when interconnected with a

    grounded-wye/grounded-wye transformer. The characteristics

    with respect to many power system faults and other

    disturbance events are similar to the delta/wye connection

    (discussed below).

    Fig. 2. Grounded Wye/Wye Interconnection Transformer

  • 8/6/2019 ConexionTransformadoresEnGD

    3/7

    3

    Z t r a n s f o r m e r + Z p o s g e n

    Z e q u i v a l e n t

    Z e q u i v a l e n t

    Z e q u i v a l e n t

    3 x Z N

    D G S i d e

    U t i l i t y S i d e

    P o i n t o f C o m m o n

    C o u p l i n g

    Z t r a n s f o r m e r + Z n e g g e n

    Z t r a n s f o r m e r + Z z e r o g e n

    S y s t e m N e u t r a l R e f e r e n c e

    a f t e r I s l a n d i n g

    P o s i t i v e S e q u e n c e

    N e g a t i v e S e q u e n c e

    Z e r o S e q u e n c e

    Fig. 3. Grounded Wye/Wye Interconnection Transformer Sequence Diagram

    B. Delta (Utility) Grounded-Wye (DG) Interconnection

    Transformer

    This is another common connection for three-phase loads

    in North America, and the most common connection in

    European-style systems. It would probably be favored for

    serving loads in most cases if it were not for the susceptibility

    of the connection to ferroresonance in the types of cable-fed

    systems common in North America. A summary of

    advantages and disadvantages are listed below:

    Advantages:

    Harmonics

    1) Triplen harmonics from the DG do not reach the

    utility system.

    System Protection

    2) Provides some isolation from voltage sags due to

    utility-side single line-ground (SLG) faults, allowing

    the DG to better ride through voltage sags.

    3) Does not feed directly into utility-side SLG faults (it

    can contribute through other ground sources on the

    utility system).

    Disadvantages:

    General

    1) Very prone to ferroresonance in cable-fed

    installations, especially during open conductor fault

    conditions.

    Harmonics

    2) Depending on generator neutral grounding, 3rd

    harmonics in the DG may cause excessive current in

    the DG-side neutral.

    System Protection

    3) Cannot provide an effectively grounded system

    during islanding or open conductor conditions i.e. If

    islanded on SLG fault, can subject utility arresters

    to overvoltages.

    4) Difficult to detect some utility-side SLG faults from

    the generator side by voltage relaying alone. The

    delta winding tends to hold the generator side

    voltage magnitudes up and in the proper phase

    relationship. Primary-side relaying is often requiredto ensure rapid detection.

    5) Due to the susceptibility to ferroresonance,

    instantaneous overvoltage relaying (59I) is often

    required to ensure prompt detection of this

    condition.

    This type of connection is not alone in being prone to

    ferroresonance and subjecting arresters and loads to

    overvoltages during single-line-to-ground faults. This concern

    is shared with all transformers that have an ungrounded

    primary connection.

    While this type of connection prevents most third harmonic

    currents that might emanate from the DG from reaching theutility, it does not prevent their flow on the DG side. As

    discussed in the previous section, a neutral reactor is typically

    used to limit the third harmonic current flow if the generator

    is not of 2/3 pitch design which minimizes the 3rd

    harmonic.

    While the winding connection can be beneficial to the load

    in reducing the impact of voltage sags due to SLG faults, it

    also makes some SLG faults on the utility system more

    difficult to detect. This increases the likelihood of islanding

    because it will delay fault detection until the utility breaker

    operates for many faults. As with all ungrounded primary

    connections, there is danger in being islanded on a SLG fault

    with very light load even briefly because this can result in asevere resonant condition.

    Therefore, it is common to add other relaying functions to

    aid in the early detection of utility-side faults when this

    connection is used. A negative sequence relay can make the

    detection more reliable and will also help detect single-

    phasing conditions in which a fuse has blown. While the

    voltage magnitudes seen on the secondary may not change

    sufficiently, they will become unbalanced, resulting in

    detectable negative sequence voltages and currents. Care must

    be taken not to set these relays too sensitive, resulting in

    nuisance generator tripping.

    A common approach to more sensitive utility-side fault

    protection is to add relaying on the primary side of the

    transformer, such as a ground overvoltage (59N or 59G) relay

    that can detect the presence of the SLG fault. This is

    implemented by installing potential transformers (PTs) on the

    primary system and then placing a voltage relay in the corner

    of the delta winding on the instrumentation transformer. The

    interconnection diagram shown in Fig. 4 shows a typical

    delta/grounded-wye installation.

  • 8/6/2019 ConexionTransformadoresEnGD

    4/7

    4

    Fig. 4. Delta/Grounded Wye Interconnection Transformer Connection

    C. Grounded-wye (Utility) Delta (DG) Interconnection

    Transformer

    This connection is rarely used on utility power distribution

    systems to serve loads, but is considered by many as the best

    way to interconnect large three-phase DG. This transformer

    connection is often referred to as a grounding bank and has

    a number of special characteristics that must be considered in

    its application on utility power systems. A summary of

    advantages and disadvantages are listed below:

    Advantages:

    General

    1) Protection schemes are well understood by both

    vendors of larger DG equipment and utility

    protection engineers.

    Harmonics

    2) Triplen harmonic currents that might be produced

    by the generator are blocked by the delta winding

    and cannot flow on the generator side and,

    therefore, are not passed on to the utility power

    system.

    System Protection3) Utility-side faults are generally more readily

    detected by the DG system protection because the

    transformer itself actually participates in all ground

    faults. This generally allows the DG to disconnect

    more quickly. (This connection is also known as a

    grounding transformer or a ground source.)

    4) Should the DG become isolated from the utility

    source (islanded), this connection helps the DG

    system to present an effectively grounded source to

    the utility distribution system and avoid the

    resonance and overvoltage issues of other

    connections.

    Disadvantages:

    Harmonics

    1) Triplen harmonic currents already present in the

    utility system from other sources will tend to flow

    into transformers with this winding connection,

    contributing to transformer heating.

    2) The flow pattern for triplen harmonic currents on

    the distribution system is altered, which could be

    either beneficial or detrimental to

    telecommunications interference and neutral-to-

    ground voltages depending on the path taken by the

    currents. This is difficult to predict prior to

    construction and can require mitigation after

    commissioning should complaints arise from

    customers.

    System Protection

    3) Contributes strongly to all ground faults, which can

    increase damage due to high fault currents.

    4) The connection contributes to sympathetic trippingof the feeder breaker for faults on other feeders.

    The transformer supplies current to other feeders

    connected to the same substation bus. Ground trip

    pickup levels must be increased to maintain

    coordination, which results in less sensitive fault

    protection.

    5) Utilities may have to change relaying depending on

    whether a transformer of this type is connected or

    disconnected. This requires expensive

    communications and control equipment that might

    not be needed for the other connections.

    6) The transformer itself is subject to short-circuit

    failure when the fault occurs. This is particularlytrue for smaller transformer banks with impedances

    less than 4-5%. A special transformer must

    generally be ordered.

    The fact that this transformer acts as a ground source is

    undesirable on many distribution systems and few utilities will

    allow this connection on the distribution system without

    special study. Implementing this connection often implies

    changes to the feeder overcurrent protection scheme that are

    costly either in terms of having to replace equipment or of

    inconvenience to other customers on the feeder.

    Fig. 5 shows how the connection contributes to a SLG fault

    on a 4-wire, multi-grounded neutral distribution system, the

    most common in the U.S. Fig. 5(a) illustrates a ground fault

    when the DG transformer is not connected. Fig. 5(b)

    illustrates a ground fault when the DG transformer is

    connected. The arrows show the paths of the current from the

    grounded-wye/delta DG interconnection transformer. The

    currents flow back through the solidly-grounded substation

    transformer and contribute additional current to the fault. The

    amount contributed would depend on the size and impedance

    of the transformer.

    Fig. 7 shows the sequence network to illustrate this

    increased ground fault contribution from this transformer

    configuration. When this Figure is compared to Fig. 6, it canbe seen that the zero-sequence current is divided between the

    utility and DG connection. This increases the overall ground

    fault contribution but reduces the ground fault current seen

    at the substation.

    Note: The DG contribution in Fig. 5 will be dependent on

    the capability of the DG to supply fault current. In many

    ground fault cases, the contribution due to the transformer

    alone will be larger. The connection of the DG device (delta,

    grounded-wye, or ungrounded-wye) is irrelevant for faults on

    the utility side of the interconnection.

  • 8/6/2019 ConexionTransformadoresEnGD

    5/7

    5

    S u b s t a t i o n

    T r a n s f o r m e r

    S e c o n d a r y

    D G

    * F a u l t c u r r e n t i s

    a p p r o x i m a t e l y e q u a l t o t h e

    c u r r e n t t h r o u g h t h e

    s u b s t a t i o n n e u t r a l r e a c t a n c e .

    S u b s t a t i o n

    T r a n s f o r m e r

    S e c o n d a r y

    * * T h e g r o u n d e d - w y e

    D G t r a n s f o r m e r

    d e c r e a s e s t h e z e r o -

    s e q u e n c e i m p e d a n c e

    w h i c h i n c r e a s e s t h e

    t o t a l f a u l t c u r r e n t

    c o m p a r e d t o t h e

    e x a m p l e w i t h o u t t h e

    g r o u n d e d - w y e D G

    t r a n s f o r m e r .

    F a u l t *

    F a u l t * *

    ( a )

    ( b ) Fig. 5. Grounded-wye/delta transformer for DG interconnection can feed ground

    faults on 4-wire multi-grounded neutral systems, introducing additional fault

    stresses and interfering with utility-side protective relaying (a) Without

    Transformer Connection (b) With Transformer Connection

    Fig. 6. Sequence Diagram for SLG Fault in system without any Ground

    Wye/Delta Transformer Connection

    Fig. 7. Sequence Diagram for SLG Fault with Grounded-Wye/DeltaTransformer Connected

    If this connection is to be used on a typical North

    American distribution system, some of the options for better

    accommodating it are:

    1. Ground the transformer through a neutralreactance of sufficient size to limit the fault

    current contribution and the amount of

    unbalanced load current the transformer would

    have to absorb. (Discussed in next section.)

    2. Increase ground trip pickup settings on feederbreakers and line reclosers.

    Since this connection is unusual for distribution systems,

    but has some clear advantages for interconnecting DG, the

    remainder of this paper will be devoted to issues related to

    implementing it with a neutral grounding reactor.

    IV. GROUNDED-WYE (UTILITY)DELTA (DG)

    INTERCONNECTION TRANSFORMER WITH A GROUNDING

    REACTOR

    As discussed in the previous section, a neutral reactor may

    be added to this connection to make it more compatible with

    typical distribution system design by limiting fault currents,unbalance currents, and harmonic currents. If the neutral

    reactor is sized properly, the grounded-wye/delta transformer

    connection can provide an effectively grounded DG interface

    under all circumstances without excessive interference with

    system operation and other utility customers on the system.

    The interconnection diagram shown in Fig. 8 shows a typical

    grounded-wye/delta installation with a neutral impedance.

    Fig. 9 shows the sequence network for a SLG fault

    condition to illustrate the effect of the added neutral reactor.

    When compared to Fig. 7, the added reactor increases the

  • 8/6/2019 ConexionTransformadoresEnGD

    6/7

    6

    effective zero-sequence impedance, decreasing the overall

    ground fault contribution of the transformer. Not only does it

    reduce the total ground fault current when compared to Fig. 7,

    but when the zero-sequence current is divided between the

    utility and the DG connection, more current will flow through

    the utility connection allowing the ground fault protection to

    work closer to its original ground fault settings.

    With the addition of this neutral reactor, a neutral shift is

    introduced. When sizing the neutral reactor, one design goal isto not expose the distribution system to line-to-ground

    voltages during a ground fault during an islanding condition

    that greatly exceed the voltages under the same conditions

    with the utility source alone.

    The selection of the grounding reactor size is a trade-off

    that minimizes the risks associated with harmonics, ground

    fault currents and overvoltages. However there is one caveat:

    the addition of future DG with this transformer connection

    may alter the optimal size of this neutral reactor, complicating

    reactor sizing. The design must leave a certain amount of

    margin for future DG addition.

    Fig. 8. Grounded-Wye/Delta Transformer with Added Neutral Reactor

    Z t r a n s f o r m e r

    Z e q u i v a l e n t

    Z e q u i v a l e n t

    Z e q u i v a l e n t

    3 x Z N

    D G S i d e

    U t i l i t y S i d e

    P o i n t o f C o m m o n

    C o u p l i n g

    P o s i t i v e S e q u e n c e

    N e g a t i v e S e q u e n c e

    Z e r o S e q u e n c e

    Z p o s g e n

    Z t r a n s f o r m e r

    Z n e g g e n

    Z t r a n s f o r m e r

    Z z e r o g e n

    A d d e d N e u t r a l

    R e a c t o r

    Fig. 9. Grounded-Wye/Delta Transformer Sequence Diagram for SLG Fault

    with Added Neutral Reactor

    A. Neutral Grounding Reactor Sizing

    The proper sizing of a neutral grounding reactor on a

    grounded-wye/delta interconnection transformer is a

    compromise of three (3) conflicting goals. The impedance

    must be:

    1. High enough to limit the maximum fault currentcontribution to a value acceptable to utility to

    which the proposed DG is to be connected, and

    to prevent failure of the grounding bank itself

    due to high fault currents flowing repeatedly in

    its windings.

    2. High enough to limit circulating currentssufficiently for continuous operation in

    unbalanced conditions.

    3. Low enough to maintain an effectivelygrounded system on the utility should the DG

    become separated from the utility system while

    the DG is operating.

    In order to be low enough to maintain an effectivelygrounded system the following criteria must be met [2]:

    3/ 10 XX and 1/ 10 XR

    Therefore, to keep the system effectively grounded during

    a possible islanding condition the reactor size needs to be

    limited to the value calculated below [1]:

    3/011 TGTN XXXX +

    where

    =NX neutral reactance

    =0TX transformer zero-sequence reactance

    =1TX transformer positive-sequence reactance

    =1GX generator (DG) positive-sequence reactance

    The above calculation only guarantees effective grounding

    for the interconnection point. For faults at other locations on

    the feeder the zero- and positive-sequence impedances

    between the ground fault location and the DG need to be

    added toXT0 andXT1. The resistance portion has been ignored

    because of the small resistance values associated on

    transformers and generators; however, they may need to beincluded with the addition of feeder [7].

    Reference [4] states a typical ohmic value of a neutral

    reactor to be within 1.0 to 1.5 times the transformer zero-

    sequence reactance. This typical range of values is on a

    system that limits temporary overvoltages during line-to-

    ground faults to 122% and permits only a 5% reduction in

    feeder ground protection sensitivity from a case with no DG

    connected [4] . The authors have worked on cases where

    values between 4 and 5 ohms have been used on 15-kV class

    distribution systems for 5MW DG interconnects. This gives

  • 8/6/2019 ConexionTransformadoresEnGD

    7/7

    7

    the reader some idea of the ranges of values necessary for

    acceptable operation.

    As stated previously, the addition of future DG with the

    same transformer connection on the feeder may require the

    neutral reactor size be altered in order to meet the above

    design criteria. The technical solution may be straightforward,

    but the commercial solution is often contentious.

    V. CONCLUSIONS

    Connecting DG with a grounded-wye/delta, or grounding

    bank, transformer connection has advantages over other

    common connections used for loads by maintaining an

    effectively grounded system even when the DG becomes

    islanded. However, this connection cannot exist on many

    distribution systems without an appropriately-sized neutral

    reactor to limit zero-sequence currents. The proper sizing of

    the neutral grounding reactor is a compromise between

    conflicting objectives and must be done with careful study.

    The neutral reactor size may need to change to accommodate

    future DG on the system in order to maintain the ground-fault

    contribution and overvoltages to acceptable levelsThe implementation of this transformer (as with all

    interface transformers) with the appropriate insulation level

    will provide proper insulation coordination between utility

    and load-side equipment.

    VI. REFERENCES

    [1] EPRI 1000419, Engineering Guide for Integration of DistributedGeneration and Storage into Power Distribution, Electric Power

    Research Institute, Palo Alto, CA 2002.

    [2] IEEE Guide for the Application of Neutral Grounding in ElectricalUtility SystemsPart I: Introduction, IEEE Standard C62.92.1-2000,

    Sept. 2000.

    [3] IEEE Guide for the Application of Neutral Grounding in ElectricalUtility Systems, Part IV Distribution, IEEE Standard C62.92.4-1991,

    Jul. 1992.

    [4] Nagpal, Plumptre, Fulton, and Martinich, Dispersed Generation-UtilityPerspective, IEEE Transactions on Industry Applications, May/June

    2006, Volume 42 No. 3, Page(s):864 872.

    [5] R.C. Dugan, On The Necessity Of Three-Phase Feeder Models For DgPlanning Analysis, IEEE Power Engineering Society Summer Meeting

    Conference Proceedings, 2002, Volume 1, Page(s):438 441.

    [6] R.C. Dugan, M.F. McGranaghan, S. Santoso, H.W. Beaty, ElectricalPower Systems Quality 2nd Edition. New York: McGraw-Hill, 2002, pp.

    373-435.

    [7] T.A. Short, Electric Power Distribution Handbook. New York: CRCPress, 2000, p. 651-748.

    VII. BIOGRAPHIES

    Robert F. Arritt (M96) is a Power Systems

    Engineer for EPRI in Knoxville, TN. He holds a

    BSEE degree from West Virginia Institute of

    Technology, Montgomery, WV (2000) and an

    MSEE degree from Worcester Polytechnic Institute

    in Worcester, MA (2005).

    His employment experience included Raytheon in

    Sudbury, MA where he worked in the Power and

    Electronic Systems Department. At Raytheon he was awarded the 2006

    Raytheon Technical Honors Award for Peer and Leadership Recognition for

    Outstanding Individual Technical Contribution and also received a 2005

    Raytheon Authors Award for work on Phase-Shifted Transformers for

    Harmonic Reduction.

    Mr. Arritt has spent most of his career designing and modeling power

    systems from the electronics level to ac generation. Recently, Mr. Arritt has

    been actively involved in distributed generation impact studies.

    Roger C. Dugan (M74SM81F00) is Sr.

    Technical Executive for EPRI in Knoxville, TN. He

    holds the BSEE degree from Ohio University, Athens,

    OH (1972) and the MEEPE degree from Rensselaer

    Polytechnic Institute, Troy, NY (1973).

    From 1992-2004, he served as Sr. Consultant forElectrotek Concepts, Knoxville, TN. From 1973

    1992 he held various positions in the Systems

    Engineering department of Cooper Power Systems in

    Canonsburg, PA and Franksville, WI. Roger has worked on many diverse

    aspects of power engineering over his career because of his interests in applying

    computer methods to power system simulation. The focus of his career has been

    on utility distribution systems. He has been particularly active in developing

    advanced methods for analysis of distribution systems with distributed

    generation. He was elected an IEEE Fellow in 2000 for his contributions in

    harmonics and transients analysis. He is coauthor of Electrical Power Systems

    Quality published by McGraw-Hill, 2nd edition. He is currently Chair of the

    IEEE PES Power Systems Analysis, Computing, and Economics Committee. He

    was the 2005 recipient if the IEEE Excellence in Distribution Engineering

    Award.