Upload
others
View
4
Download
0
Embed Size (px)
Citation preview
construction details
EQUITONE with face fixings on timber support frame
New Zealand
Table of contents
General information 3
Ventilation 4
Components 5
EQUITONE facade system with flexible air barrier 9
EQUITONE facade system with rigid air barrier 26
2
General information
This document provides generic construction details for EQUITONE façade systems to assist with the design ofEQUITONE façade.
Construction details in this document have been independently certified for the purpose of compliance withClause E2, External moisture, of the New Zealand Building Code within the scope of E2/VM1 and E2/VM2 forEQUITONE façade systems with the recommended pliable and rigid weather barrier, respectively, as described inthe ‘General components’.
The weatherproofing performance of any project specific detail or application that is different from or not includedin the construction details of this document shall be evaluated by the project engineer or consultant.
It is the responsibility of the project designer, architect and engineer to ensure that the information andconstruction details provided in this document are appropriate for the intended application.
Cladding support frame and its connection to substructure shall be designed by the project engineer inaccordance with the relevant standards. The support frame maximum deflection under the influence of load shallbe limited to Span/250.
The support frame, fixings, flashings and the like shall be of adequate corrosion resistance appropriate to thecorrosivity category of the project location.
Flashings and capping shall be designed with respect to project wind loading, relevant standards and regulations.
This document is not designed to serve as an installation guide, and is intended to be used in conjunction withother relevant technical and installation documents.
Construction details contained in this document are not to a specific scale, and are for illustration purposes only.
The information in this document is correct at the time of issuing. However, due to our committed program ofcontinuous material and system development we reserve the right to amend or alter the information containedtherein without prior notice. Please contact your local EQUITONE sales organisation to ensure you have the mostcurrent version.
This document is supplied in good faith and no liability can be accepted for any loss or damage resulting from itsuse. All the content of this document is © Copyright of Etex Group. All rights reserved.
This document is protected by International copyright laws. Reproduction and distribution in whole or in partwithout prior written permission is strictly prohibited. Cedral and logos are trademarks of Etex NV or an affiliatethereof. Any use without authorisation is strictly prohibited and may violate trademark laws.
3
Ventilation
A ventilated façade is a kind of two stage construction, an inner structurewith a protective outer skin, and the cladding panel or rainscreen. Aventilated façade consists of an insulated and weathertight structure, aventilated cavity formed with a cladding support frame, and the claddingpanel.
Allowance for adequate ventilation is paramount in ensuring a successfulEQUITONE façade. Ventilated façades provide a number of added benefitsto the building and its occupants. These may include but are not limited tothe following:
- Positive contribution to energy savings- Minimises thermal bridges- Assists with condensation management- Reduces thermal movement of the structure and cladding support
frame- Dissipates radiant heat- Increases acoustic performance of the external wall- Provides an effective drainage path for any moisture passing the
cladding skin- Eliminates the need for exposed caulking and sealant, therefore
reducing maintenance requirements- Assists with Keeping the weather barrier dry and healthy- Architectural design freedom- Provides opportunities for concealing external services such as
downpipes within the cavity- Proven to be a more sustainable and healthier façade construction
Air must be allowed to enter the cavity from bottom of the façade, windowhead, soffit, slab junctions, and the like, and exit from top of the façade,capping, window sill, slab and soffit interfaces, and the like.
All air inlets and outlets are protected against entry of birds and vermininto the cavity with a corrosion resistant perforated profile (angle).
The perforated angle should be of maximum 0.9mm in thickness, whereplaced between the cladding panel and support frame, and be of aminimum 50% open area with aperture size of maximum 3mm to 5mm.The perforations must be kept open and unobstructed to maintaindrainage and ventilation of the cavity. The perforated angle shall bepositioned to allow an adequate drip edge to the cladding panel.
4
Components
Material
Maximum available panel sizes
EQUITONE [tectiva] 8 mm thickEQUITONE [lines] 10 mm thick
EQUITONE [natura] 8 and 12 mm thickEQUITONE [natura] PRO 8 and 12 mm thickEQUITONE [pictura] 8 and 12 mm thick
Panel fixingsUNI Screw
Colour coded and available in the following materials and grades:
Stainless Steel 304 (A2)Available with additional protective coating for NZ exposure zone E (Very High) as defined in NZS 3604:2011
Stainless Steel 316 (A4)
EQUITONE [tectiva] EQUITONE [lines] EQUITONE [natura] EQUITONE [pictura]
1250
2500
1250
3100
2500
1220
3050
NotesFor EQUITONE [natura] PRO and [pictura] UNI Screw Stainless Steel protective collarshould be used with UNI Screw.Panel hole size is 7mm, drilled with 7mm EQUITONE drill bit.Each panel thickness has its own corresponding UNI screw.UNI Screw panel edge distance:
From the edge parallel to support frame: 30 – 100 mm (Recommended: 40 mm)From the edge perpendicular to support frame: 70 – 100 mm (Recommended: 80 mm)
12
20
5
Components
Compressible EPDM gasketTesa® 61102
A compressible closed-cell EPDM gasket used for sealing interfaces withflashings and the like.
Minimum width:9mm where a narrow strip is required as specified on theconstruction details48mm where located on vertical joints as specified on theconstruction details
Expanding foam gasketpro clima CONTEGA® FIDEN EXO
A pre-compressed sealing tape used to seal interfaces with windowjoineries and the like as specified on the construction details.
The required tape size depends on the gap which needs to be sealed.Refer to pro clima CONTEGA® FIDEN EXO datasheet to determine therequired tape size.
Baffle
Black coated aluminium baffle used to close and form expressed panel horizontal joint.
Weather resistive barrier option 1Flexible air barrier (pliable membrane)
EQUITONE façade systems have been certified with pro clima SOLITEXEXTASANA® pliable membrane to E2/VM1 for the purpose of compliance with Clause E2 of the NZBC for the following scope:
Serviceability wind pressure: Up to ±1515PaUltimate wind pressure: Up to ±2500PaBuilding height: Up to 10m
pro clima SOLITEX EXTASANA® shall be applied in accordance with proclima SOLITEX EXTASANA® installation guidelines and relevant standards.
EPDM gasket strip0.75mm EPDM strip 100mm wide
Applied on timber cavity battens for moisture protectionas specified on the construction details
6
Components
Flashing tapepro clima TESCON EXTORA®
A pressure sensitive adhesive tape for overlaps and end laps used withboth weather resistive barrier options.
Sill tapepro clima TESCON EXTOSEAL®
A flexible tape for use around window and door openings, used with bothweather resistive barrier options.
Sealing tapepro clima TESCON® NAIDECK mono patch
A single-sided adhesive nail or screw sealing adhesive used with bothweather resistive barrier options.
Foil tapepro clima TESCON® ADHISO WS
A pure aluminium tape for wet seal connections to TESCONEXTOSEAL® and EXTORA® and SOLITEX EXTASANA®..
Grommetpro clima ROFLEX and KALFEX
pro clima ROFLEX is used to seal pipe and pro clima KAFLEX for cablepenetrations. pro clima ROFLEX and KALFEX are used with both weatherresistive barrier options.
Weather resistive barrier option 2Rigid air barrier
Where a rigid air barrier is required the ADHERO version of pro climaSOLITEX EXTASANA® may be used with 6mm Kalsi (RigidBacker) fibrecement sheeting.EQUITONE façade systems have been certified with pro clima SOLITEXEXTASANA® AHERO and Kalsi to E2/VM2 for the purpose of compliancewith Clause E2 of the NZBC for the following scope:
Serviceability wind pressure: Up to ±2250PaBuilding height: Up to 25m
pro clima SOLITEX EXTASANA® ADHERO shall be applied in accordancewith pro clima SOLITEX EXTASANA® ADHERO installation guidelines andrelevant standards.
7
Support frame
EQUITONE may be fixed to vertical timber battens with minimum depth of35mm and width of 70mm (35 x 70 mm).
Timber battens shall be of minimum preservative treatment of H3.1, andof minimum structural grade of SG6 as per the relevant standards.
Maximum deflection of support framing must be limited to Span/250.
Timber shall be seasoned or have reached an equilibrium moisturecontent of 16% or less at the time of installation. Unseasoned timber isnot recommended.
Structure and support frame shall be designed to relevant standardsincluding, but not limited to, the following:
• AS/NZS 4600 – Cold-formed steel structures • NZS 3404 – Steel structures• NZS 3604 – Timber framed buildings
8
EQUITONE system
flexible air barrier (pliable membrane)timber batten construction
9
Drawings index
Detail Figure Page
Baffled horizontal joint 1 11Baffled horizontal joint junction with vertical joint - Elevation 2 11Vertical joint - Detail 1 3 12Vertical joint - Detail 2 4 12Vertical joint - Detail 3 5 12Intermediate panel fixings connection 6 12Horizontal control joint 7 13EPDM gasket support over control joint or the like 8 13Vertical control joint 9 13Flush window - Head and sill 10 14Flush window - Jamb 11 14Recessed window - Head and sill 12 15Recessed window jamb - Option 1 13 15Recessed window jamb - Option 2 14 15Meter box - Section 15 16Meter box - Plan view - Detail 1 16 16Meter box - Plan view - Detail 2 17 16Isometric view of window/meter box opening - Tape application 18 17Soffit junction 19 17Base detail 20 18Base detail - Covered area 21 18Base detail - Balcony 22 18Junction with other materials - flush detail 23 19Junction with other materials, eaves or the like - recessed detail 24 19Exposed concrete slab or beam - Cladding flush 25 20Exposed concrete slab or beam - Cladding recessed 26 20External corner - Detail 1 27 21External corner - Detail 2 28 21Internal corner 29 22Abutment 30 22Pipe penetration - Plan view 31 23Pipe penetration - Elevation 32 23Pipe penetration - Section 33 23Capping - Detail 1 34 24Capping - Detail 2 35 24Parapet junction - Section 36 24Parapet junction - Plan view 37 25Corrosion resistant saddle flashing 38 25
10
8 - 12 mm
Outline of baffle
EPDM or aluminium strip
EPDM strip
Max. 0.9mm baffle
5 mm
Timber batten
EQUITONE
EQUITONE
Min. cavity width: 35 mm
UHB double sided tape or sealant
EPDM compressible gasket
Figure 1: Baffled horizontal joint(Not suitable for EQUITONE [materia])
Figure 2: Baffled horizontal jointjunction with vertical joint - Elevation
Notes1) Depending on the project requirements max. 0.9mm (powder) coated aluminium strip may be used in lieu of EPDM strip on vertical jointsfor higher UV resistance.
11
8 - 12mmEPDM strip
5 mm
EQUITONE
Timber batten
EPDM compressible gasket
EPDM strip
Max. 0.9mm corrosionresistant metal strip
8 - 12mm
5 mm
Timber batten
EQUITONE
EPDM compressiblegasket
EPDM strip
5 mm
Timber batten
EQUITONE
EPDM compressiblegasket
Max. 0.9mm corrosionresistant metal strip
EQUITONE10 - 12mm
EPDM strip
Timber batten
5 mm
EPDM compressiblegasket
Figure 3: Vertical joint - Detail 1
Figure 4: Vertical joint - Detail 2
Figure 6: Intermediate panel fixings connection
Notes1) Depending on the project requirements max. 0.9mm (powder) coated aluminium strip may be used in lieu of EPDM strip on vertical jointsfor higher UV resistance.2) In Figure 6 & 7, the metal strip should be fixed ONLY to one of the battens (either left or right) where allowance for horizontal and/or verticalmovement of the cladding frame is required.
Figure 5: Vertical joint - Detail 3
12
Min. 10 mm or larger as specified by project engineer
Min. 40 mm
10 mm
Corrosion resistant flashing with min. 15 degree slope
Min. 10 mm
60mm flashing tape
EPDM strip
EPDM compressible gasket
Min. 100 mm10 - 15 mm drip edge
or as required20 mmEPDM strip Max. 150 mm
20 mm or as required
EPDM compressible gasket
Figure 7: Horizontal control joint - Detail 1
Notes1) Support frame profiles must NOT be fixed crossing over a control joint.2) Allowance for movement at the location of any control joint must be made in the cladding and its support frame design andinstallation. Panel must NOT be fixed bridging over any control joint.3) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be ofmin. 50% open area with aperture size of 3-5mm.
Figure 8: EPDM gasket support over control joint or the like
Figure 9: Vertical control joint
13
0.9mm corrosionresistant jamb flashing
Expanding foam gasket
Outline of head flashing
EPDM strip
Air seal option 1Backing rod & sealant
Air seal option 2Min. 60mm flashing tape
Foil tape over sill tapeand membrane for wetsealing (sealant)
Min. 20 mm8 - 12 mm
Outline of sill flashingEPDM compressible gasket
30 - 50 mm
Corrosion resistant head flashing with min. 15mmupstand each end, and min. 15 degree slope
Sill tape
Foil tape over sill tape andmembrane for wet sealing(sealant)
Air seal option 1Backing rod & sealant
60mm flashing tape
Min. 10 mm
EPDM strip
Min. 100 mm
Air seal option 2Min. 60mm flashing tape
Sealant for Very High andExtra High wind zones
Min. 10 mm
10 - 15 mm
Min. 40 mm
10 - 15 mm
Corrosion resistantperforated angle
Corrosion resistantperforated angle
Sill support bar with drainage hole
Corrosion resistant sillflashing
Air seal option 2Min. 60mm flashingtape
Air seal option 1Backing rod & sealant
EPDM compressible gasket
10 - 15 mm drip edge
Figure 10: Flush window - Head and sill
Figure 11: Flush window - Jamb
Notes1) ONLY sealant compatible with the foil tape should be used. Should any sealant be intended to be used directly on the flashing and/or silltape it must be confirmed with its manufacturer to ensure compatibitlity with these tapes in accordence with the relavent standards.2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min.50% open area with aperture size of 3-5mm.
14
Min. 50 mm
Outline of jamb flashing
Min.50 mm
Corrosion resistantperforated angle
Sill tape
Corrosion resistant sill flashing with min.15mm upstand each end passing behindjamb flashing, and min. 15 degree slope
60mm flashing tape
Corrosion resistant head flashing with min. 15mmupstand each end, and min. 15 degree slope
EPDM strip
Min. 8 mm cover
Min. 35 mm cover
Min. 10 mm
Corrosion resistant sillflashing with min. 15mmupstand each end
10 - 15 mm
Min 40 mm
10 - 15 mm
Air seal option 1Backing rod & sealant
Air seal option 2Min. 60mm flashing tape
Foil tape over sill tapeand membrane for wetsealing (sealant)
Min. 10 mm cover
Corrosion resistantperforated angle
Air seal option 2Min. 60mm flashing tape
Air seal option 1Backing rod & sealant
EPDM compressible gasket
Sealant for Very High andExtra High wind zones
5 mm
Min. 100 mm
Corrosion resistant jambflashing option 2
EPDM compressible gasket
Outline of sill flashing EPDM strip
Bond breaker & sealant
Air seal option 1Backing rod & sealant
Air seal option 2Min. 60mm flashing tape
Foil tape over sill tapeand membrane for wetsealing (sealant)
Max. 0.9mm corrosion resistantjamb flashing option 1
Outline of sill flashingEPDM strip
Bond breaker & sealant
Air seal option 1Backing rod & sealant
Air seal option 2Min. 60mm flashing tape
Foil tape over sill tapeand membrane for wetsealing (sealant)
Min. 10 mm cover
Outline of head flashingOutline of head flashing
EPDM compressible gasket EPDM compressible gasket
Figure 12: Recessed window - Head and sill
Figure 13: Recessed window jamb - Option 1 Figure 14: Recessed window jamb - Option 2
Notes1) ONLY sealant compatible with the foil tape should be used. Should any sealant be intended to be used directly on the flashing and/or silltape it must be confirmed with its manufacturer to ensure compatibitlity with these tapes in accordence with the relavent standards.2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min.50% open area with aperture size of 3-5mm.
15
Min. 20 mmMin. 20 mm
Line of head flashing
Line of sill flashing
Max. 0.9mm corrosionresistant metal angle
Supporting angle, bondbreaker & sealant
Line of sill flashingLine of head flashing
EPDM strip
5 - 10 mm 5 - 10 mm
Backing rod & sealant
Foil tape over sill tapeand membrane for wetsealing (sealant)
Backing rod & sealant
Foil tape over sill tapeand membrane for wetsealing (sealant)
EPDM compressible gasket
Min. 10 mm
Min. 10 mm
10 - 15 mm
Corrosion resistant flashing with min. 15mmupstand on each end, and min. 15 degree slope
Corrosion resistant flashing
Sill tape
Min. 50 mm
Backing rod & sealant
EPDM strip
60mm flashing tape
Foil tape over sill tapeand membrane for wetsealing (sealant)
Min. 40 mm
Min. 10 mm
Corrosion resistantperforated angle
Corrosion resistantperforated angle
EPDM compressible gasket
Sealant
Min. 100 mm10 - 15 mm drip edge
Figure 16: Meter box - Plan view - Detail 1 Figure 17: Meter box - Plan view - Detail 2
Figure 15: Meter box - Section
Notes1) ONLY sealant compatible with the foil tape should be used. Should any sealant be intended to be used directly on the flashing and/or silltape it must be confirmed with its manufacturer to ensure compatibitlity with these tapes in accordence with the relavent standards.2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min.50% open area with aperture size of 3-5mm.
16
10 mm
Min. 20 mm
Min. 10 mm
Corrosion resistantperforated angle
Corrosion resistantperforated angle
Corrosion resistant flashing,and min. 15 degree slope
60mm flashing tape
Min. 10 mm
EPDM tape
Min. 5 mm
EPDM compressible gasket
Max. 150 mm
Min. 15 mm
Min. 100 mm
Min. 100 mm
Min. 100 mm
Figure 19: Soffit junction
Figure 18: Isometric view of window/meter box opening - Tape application
Sill tape to the sill reveal with min. 50mmcover onto membrane (Applied first)
Sill tape to the top corners with min. 50mmcover onto membrane (Applied second)
Foil tape between sealant and sill tape, andmembrane (Applied last); only applies whenusing sealant (wet seal)
Notes1) ONLY sealant compatible with the foil tape should be used. Should any sealant be intended to be used directly on the flashing and/or silltape it must be confirmed with its manufacturer to ensure compatibitlity with these tapes in accordence with the relavent standards.2) Support frame profiles must NOT be fixed crossing over a control joint.3) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min.50% open area with aperture size of 3-5mm.
17
Corrosion resistantperforated angle
100mm flashing tape
Min. 150 mm ground clearance or larger to regulatory requirements
Min. 50 mm cover
EPDM compressible gasket
EPDM strip
10 - 15 mm drip edge
Corrosion resistantperforated angle
100mm flashing tape
Min. 20 mm or larger to regulatory requirements
EPDM compressible gasket
Min. 50 mm cover
EPDM strip
10 - 15 mm drip edge
Corrosion resistantperforated angle
100mm flashing tape
Min. 35 mm or larger to regulatory requirements
EPDM compressible gasket
Min. 50 mm cover
Min. 12 mm
EPDM strip
10 - 15 mm drip edge
Figure 20: Base detail
Figure 21: Base detail - Covered area
Figure 22: Base detail - Balcony
Notes1) For EQUITONE [materia], minimum ground clearance is 300mm.2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50%open area with aperture size of 3-5mm.
18
Min. 40 mm
10 mm
Corrosion resistant flashing with min. 15 degree slope
Corrosion resistantperforated angle
60mm flashing tape
Corrosion resistant flashing with min. 15degree slope
Min. 15 mm
EPDM strip
Min. 10 mm
Min. 35 mm
Min. 100 mm
Corrosion resistantperforated angle
EPDM compressible gasket
10 - 15 mm drip edge
Min. 150 mm
Min. 40 mm
10 mm
Corrosion resistant flashing
Corrosion resistantperforated angle
60mm flashing tape
Corrosion resistant flashing with min. 15degree slope
Min. 15 mm
Soffit lining
EPDM strip
Min. 35 mm
Corrosion resistant perforatedangle fixed only to soffit
EPDM compressible gasket
Min. 10 mm
10 - 15 mm drip edge
Min. 150 mm
Figure 23: Junction with other materials - flush detail
Figure 24: Junction with other materials, eaves or the like - recessed detail
Notes1) Support frame profiles must NOT be fixed crossing over a control joint.2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% openarea with aperture size of 3-5mm.
19
Min. 15 mm
Min. 35 mm
Sealant
Corrosion resistant flashing
Corrosion resistantperforated angle
60mm flashing tape
Corrosion resistant flashing, with min.15 degree slope
EPDM strip
Corrosion resistantperforated anglefixed only to soffit
60mm flashing tape
Min. 10 mm
Min. 40 mm
10 - 15 mm
EPDM compressible gasket
10 - 15 mm drip edge
60mm flashing tape
Min. 150 mm
Min. 15 mm
Min. 35 mm
Min. 10 mm
Min. 40 mm
10 - 15 mm
Sealant
Corrosion resistant flashing
Corrosion resistantperforated angle
60mm flashing tape
Corrosion resistant flashing,with min. 15 degree slope
EPDM strip
Corrosion resistantperforated anglefixed only to soffit
60mm flashing tape
EPDM compressible gasket
10 - 15 mm drip edge
60mm flashing tape
Min. 150 mm
Figure 25: Exposed concrete slab or beam - Cladding flush
Figure 26: Exposed concrete slab or beam - Cladding recessed
Note1) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% openarea with aperture size of 3-5mm.
20
Max. 0.9mm corrosionresistant angle
8 - 12 mm30 - 100 mm
EPDM strip
EPDM compressible gasket
30 - 100 mm
Max. 250 mm
Min. 1.1mm corrosionresistant metal angle
EPDM compressible gasket
8 - 12 mm
EPDM strip
EQUITONE UNI rivet
Figure 27: External corner - Detail 1
Figure 28: External corner - Detail 2
21
EPDM strip
Max. 0.9mm corrosionresistant angle
EPDM compressible gasket
EPDM compressible gasket
Backing rod & sealant
Max. 0.9mm corrosionresistant angle
60mm flashing tape
10 mm
EPDM strip
Figure 29: Internal corner
Figure 30: Abutment
22
Grommet
60mm flashing tape
Supporting collar,backing rod &sealant
Grommet60mm flashing tape
Supporting collar,backing rod &sealant
60mm flashing tape
Grommet
Once the grommet isinstalled, first apply thistape, and then continue anti-clockwise with the others
Figure 31: Pipe penetration - Plan view
Figure 32: Pipe penetration - Elevation Figure 33: Pipe penetration - Section
23
15 mm
Min. 15 mm
Min. 50 mm or to regulatory req uirements
Sill or sealing tape
Roof or gutterflashing ormembrane
Corrosion resistantperforated angle
60mm flashing tape
EPDM strip
EPDM compressible gasket
To regulatory requirements
Suitable capping structural supportMin. 5 degree slope
60mm flashing tape
Sill or sealing tape
15 mm
Min. 15 mm
Min. 50 mm or larger to regulatory requirements
Air
Non-continuous packer
Roof or gutterflashing ormembrane
Corrosion resistantperforated angle
EPDM compressible gasket
EPDM strip
Min. 50 mm or larger to regulatory requirements
Suitable capping structural support
Min. 5 degree slope
Sill tape
Capping with two rows of sealantto saddle flashing
Capping support
Corrosion resistant Saddleflashing with two rows ofsealant to capping support
Min. 50mm
60mm flashing tape
Supportingangle, backingrod & sealant
Min. 100 mm
Figure 34: Capping - Detail 1
Figure 35: Capping - Detail 2(Not suitable for EQUITONE [materia])
Figure 36: Parapet junction - Section
Notes1) For EQUITONE [materia], the following capping dimensions should be followed.
- A minimum 20mm between panel face and rear of the capping- A minimum 50mm overlap with the panel for building up to 8m or larger to regulatory requirements- A minimum 80mm overlap with the panel for building up to 20m or larger to regulatory requirements- A minimum 100mm overlap with the panel for building over 20m or larger to regulatory requirements
2) Any face fixings of capping shall be through an over sized hole (by min 5mm) in the capping as well as the panel.3) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min.50% open area with aperture size of 3-5mm.4) Capping shall be designed and engineered accordingly to provide adequate allowance for ventilation as shown in Figures 36 & 37.
24
Outline of saddleflashing
EPDM strip
EPDM compressible gasket
Min. 70 mm
Min. 50 mm
Min. 50 mm
Min.50 mm
Min. 150 mm
Min. 20 mm
Min. 50 mm
Min. 100 mm
Min. 5 degree slope
Figure 37: Parapet junction - Plan view
Figure 38: Corrosion resistant saddle flashing
25
EQUITONE system
rigid air barriertimber batten construction
26
Drawings index
Detail Figure Page
Baffled horizontal joint 1 28Baffled horizontal joint junction with vertical joint - Elevation 2 28Open horizontal joint 3 28Open horizontal joint junction with vertical joint - Elevation 4 28Vertical joint - Detail 1 5 29Vertical joint - Detail 2 6 29Vertical joint - Detail 3 7 29Intermediate panel fixings connection 8 29Horizontal control joint 9 30EPDM gasket support over control joint or the like 10 30Vertical control joint 11 30Flush window - Head and sill 12 31Flush window - Jamb 13 31Recessed window - Head and sill 14 32Recessed window jamb - Option 1 15 32Recessed window jamb - Option 2 16 32Meter box - Section 17 33Meter box - Plan view - Detail 1 18 33Meter box - Plan view - Detail 2 19 33Isometric view of window/meter box opening - Tape application 20 34Soffit junction 21 34Base detail 22 35Base detail - Covered area 23 35Base detail - Balcony 24 35Junction with other materials - flush detail 25 36Junction with other materials, eaves or the like - recessed detail 26 36Exposed concrete slab or beam - Cladding flush 27 37Exposed concrete slab or beam - Cladding recessed 28 37External corner - Detail 1 29 38External corner - Detail 2 30 38Internal corner 31 39Abutment 32 39Pipe penetration - Plan view 33 40Pipe penetration - Elevation 34 40Pipe penetration - Section 35 40Capping - Detail 1 36 41Capping - Detail 2 37 41Parapet junction - Section 38 41Parapet junction - Plan view 39 42Corrosion resistant saddle flashing 40 42
27
8 - 12 mm
Outline of baffleEPDM strip
Max. 0.9mm baffle
5 mm
Timber batten
EQUITONE
EQUITONE
Min. cavity width: 35 mm
UHB double sided tape or sealant
EPDM compressible gasket
EPDM or aluminium strip
Min. 6 mm
EPDM strip
EPDM or aluminium strip
Timber batten
EQUITONE
EQUITONE
Min. cavity width: 35 mm
EPDM compressible gasket
Figure 1: Baffled horizontal joint(Not suitable for EQUITONE [materia])
Figure 2: Baffled horizontal jointjunction with vertical joint - Elevation
Figure 3: Open horizontal joint Figure 4: Open horizontal joint junctionwith vertical joint - Elevation
Notes1) Horizontal open joint detail (Figure 3 & 4) requires project engineer's evaluation and approval, and the selection of appropriate UV resistantweather resistive barrier (membrane).2) In Figure 4, visible part of the support frame (battens) and weather barrier may be coated black with suitable paint.3) Depending on the project requirements max. 0.9mm (powder) coated aluminium strip may be used in lieu of EPDM strip on vertical joints forhigher UV resistance.
28
8 - 12mmEPDM strip
5 mm
EQUITONE
Timber batten
EPDM compressible gasket
EPDM strip
Max. 0.9mm corrosionresistant metal strip
8 - 12mm
5 mm
Timber batten
EQUITONE
EPDM compressiblegasket
EPDM strip
5 mm
Timber batten
EQUITONE
EPDM compressiblegasket
Max. 0.9mm corrosionresistant metal strip
EQUITONE10 - 12mm
EPDM strip
Timber batten
5 mm
EPDM compressiblegasket
Figure 5: Vertical joint - Detail 1
Figure 6: Vertical joint - Detail 2
Figure 8: Intermediate panel fixings connection
Notes1) Depending on the project requirements max. 0.9mm (powder) coated aluminium strip may be used in lieu of EPDM strip on vertical jointsfor higher UV resistance.2) In Figure 6 & 7, the metal strip should be fixed ONLY to one of the battens (either left or right) where allowance for horizontal and/or verticalmovement of the cladding frame is required.
Figure 7: Vertical joint - Detail 3
29
Min. 10 mm or larger as specified by project engineer
Min. 40 mm
10 mm
Corrosion resistant flashing with min. 15 degree slope
Min. 10 mm
60mm flashing tape
EPDM strip
Min. 15 mm or larger as specified by project engineer
EPDM compressible gasket
Min. 100 mm 10 - 15 mm drip edge
or as required20 mmEPDM strip Max. 150 mm
20 mm or as required
EPDM compressible gasket
Figure 9: Horizontal control joint
Notes1) Support frame (batten) and Kalsi RigidBacker must NOT be fixed crossing over a control joint.2) Allowance for movement at the location of any control joint must be made in the cladding and its support frame design and installation.Panel must NOT be fixed bridging over any control joint.3) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min.50% open area with aperture size of 3-5mm.
Figure 10: EPDM gasket support over control joint or the like
Figure 11: Vertical control joint
30
0.9mm corrosion resistantjamb flashing
Expanding foam gasket
Outline of head flashing
EPDM strip
Air seal option 1Backing rod & sealant
Air seal option 2Min. 60mm flashing tape
Foil tape over sill tapeand membrane for wetsealing (sealant)
Min. 20 mm8 - 12 mm
Outline of sill flashingEPDM compressible gasket
30 - 50 mm
Corrosion resistant head flashing with min. 15mmupstand each end, and min. 15 degree slope
Sill tape
Foil tape over sill tape andmembrane for wet sealing(sealant)
Air seal option 1Backing rod & sealant
60mm flashing tape
Min. 10 mm
EPDM strip
Min. 100 mm
Air seal option 2Min. 60mm flashing tape
Sealant for Very High andExtra High wind zones
Min. 10 mm
10 - 15 mm
Min. 40 mm
10 - 15 mm
Corrosion resistantperforated angle
Corrosion resistant perforated angle
Sill support bar with drainage hole
Corrosion resistant sillflashing
Air seal option 2Min. 60mm flashingtape
Air seal option 1Backing rod & sealant
EPDM compressible gasket
10 - 15 mm drip edge
Figure 12: Flush window - Head and sill
Figure 13: Flush window - Jamb
Notes1) ONLY sealant compatible with the foil tape should be used. Should any sealant be intended to be used directly on the flashing and/or silltape it must be confirmed with its manufacturer to ensure compatibitlity with these tapes in accordence with the relavent standards.2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min.50% open area with aperture size of 3-5mm.
31
Min. 50 mm
Outline of jamb flashing
Min.50 mm
Corrosion resistantperforated angle
Sill tape
Corrosion resistant sill flashing with min.15mm upstand each end passing behindjamb flashing, and min. 15 degree slope
60mm flashing tape
Corrosion resistant head flashingwith min. 15mm upstand eachend, and min. 15 degree slope
EPDM strip
Min. 8 mm cover
Min. 35 mm cover
Corrosion resistant sillflashing with min. 15mmupstand each end
10 - 15 mm
Min 40 mm
10 - 15 mm
Air seal option 1Backing rod & sealant
Air seal option 2Min. 60mm flashing tape
Foil tape over sill tapeand membrane for wetsealing (sealant)
Min. 10 mm cover
Corrosion resistantperforated angle
Air seal option 2Min. 60mm flashing tape
Air seal option 1Backing rod & sealant
EPDM compressible gasket
Sealant for Very High andExtra High wind zones
5 mm
Min. 10 mm
Min. 100 mm
Corrosion resistant jambflashing option 2
EPDM compressible gasket
Outline of sill flashing EPDM strip
Bond breaker & sealant
Air seal option 1Backing rod & sealant
Air seal option 2Min. 60mm flashing tape
Foil tape over sill tapeand membrane for wetsealing (sealant)
Max. 0.9mm corrosion resistantjamb flashing option 1
Outline of sill flashingEPDM strip
Bond breaker & sealant
Air seal option 1Backing rod & sealant
Air seal option 2Min. 60mm flashing tape
Foil tape over sill tapeand membrane for wetsealing (sealant)
Min. 10 mm cover
Outline of head flashingOutline of head flashing
EPDM compressible gasket EPDM compressible gasket
Figure 14: Recessed window - Head and sill
Figure 15: Recessed window jamb - Option 1 Figure 16: Recessed window jamb - Option 2
Notes1) ONLY sealant compatible with the foil tape should be used. Should any sealant be intended to be used directly on the flashing and/or silltape it must be confirmed with its manufacturer to ensure compatibitlity with these tapes in accordence with the relavent standards.2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min.50% open area with aperture size of 3-5mm.
32
Min. 20 mmMin. 20 mm
Line of head flashing
Line of sill flashing
Max. 0.9mm corrosionresistant metal angle
Supporting angle, bondbreaker & sealant
Line of sill flashingLine of head flashing
EPDM strip
5 - 10 mm
5 - 10 mm
Backing rod & sealant
Foil tape over sill tapeand membrane for wetsealing (sealant)
Backing rod & sealant
Foil tape over sill tapeand membrane for wetsealing (sealant)
EPDM compressible gasket
Min. 10 mm
Min. 10 mm
10 - 15 mm
Corrosion resistant flashing withmin. 15mm upstand on each end,and min. 15 degree slope
Corrosion resistant flashing
Sill tape
Min. 50 mm
Backing rod & sealant
EPDM strip
60mm flashing tape
Min. 100 mm
Foil tape over sill tapeand membrane for wetsealing (sealant)
Min. 40 mm
Min. 10 mm
Corrosion resistantperforated angle
Corrosion resistantperforated angle
EPDM compressible gasket
Sealant
10 - 15 mm drip edge
Figure 18: Meter box - Plan view - Detail 1 Figure 19: Meter box - Plan view - Detail 2
Figure 17: Meter box - Section
Notes1) ONLY sealant compatible with the foil tape should be used. Should any sealant be intended to be used directly on the flashing and/or silltape it must be confirmed with its manufacturer to ensure compatibitlity with these tapes in accordence with the relavent standards.2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min.50% open area with aperture size of 3-5mm.
33
10 mm
Min. 20 mm
Min. 10 mm
Corrosion resistantperforated angle Min. 15 mm
Corrosion resistantperforated angle
Corrosion resistant flashing,and min. 15 degree slope
60mm flashing tape
Min. 10 mm
EPDM tape
Min. 5 mm
EPDM compressible gasket
Max. 150 mm
Min. 100 mm
Min. 100 mm
Min. 100 mm
Figure 21: Soffit junction
Figure 20: Isometric view of window/meter box opening - Tape application
Notes1) ONLY sealant compatible with the foil tape should be used. Should any sealant be intended to be used directly on the flashing and/or silltape it must be confirmed with its manufacturer to ensure compatibitlity with these tapes in accordence with the relavent standards.2) Support frame (batten) and Kalsi RigidBacker must NOT be fixed crossing over a control joint.3) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min.50% open area with aperture size of 3-5mm.
Sill tape to the sill reveal with min. 50mmcover onto membrane (Applied first)
Sill tape to the top corners with min. 50mmcover onto membrane (Applied second)
Foil tape between sealant and sill tape, andmembrane (Applied last); only applies whenusing sealant (wet seal)
34
Corrosion resistant perforated angle
100mm flashing tape
Min. 150 mm ground clearance or larger to regulatory requirements
Min. 50 mm cover
EPDM compressible gasket
EPDM strip
10 - 15 mm drip edge
Corrosion resistantperforated angle
100mm flashing tape
Min. 20 mm or larger to regulatory requirements
EPDM compressible gasket
Min. 50 mm cover
EPDM strip
10 - 15 mm drip edge
Corrosion resistantperforated angle
100mm flashing tape
Min. 35 mm or larger to regulatory requirements
EPDM compressible gasket
Min. 50 mm cover
Min. 12 mm
EPDM strip
10 - 15 mm drip edge
Figure 22: Base detail
Figure 23: Base detail - Covered area
Figure 24: Base detail - Balcony
Notes1) For EQUITONE [materia], minimum ground clearance is 300mm.2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50%open area with aperture size of 3-5mm.
35
Min. 40 mm
10 mm
Corrosion resistant flashing with min. 15 degree slope
Corrosion resistantperforated angle
60mm flashing tape
Corrosion resistant flashing with min. 15degree slope
Min. 15 mm
EPDM strip
Min. 10 mm
Min. 35 mm
Min. 150 mm
Min. 100 mm
Corrosion resistantperforated angle
EPDM compressible gasket
10 - 15 mm drip edge
Min. 40 mm
10 mm
Corrosion resistant flashing
Corrosion resistantperforated angle
60mm flashing tape
Corrosion resistant flashing with min.15 degree slope
Min. 15 mm
Soffit lining
EPDM strip
Min. 35 mm
Min. 150 mm
Corrosion resistant perforatedangle fixed only to soffit
EPDM compressible gasket
Min. 10 mm
10 - 15 mm drip edge
Figure 25: Junction with other materials - flush detail
Figure 26: Junction with other materials, eaves or the like - recessed detail
Notes1) Support frame (batten)s and Kalsi RigidBacker must NOT be fixed crossing over a control joint.2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% openarea with aperture size of 3-5mm.
36
Min. 15 mm
Min. 150 mm
Min. 35 mm
Sealant
Corrosion resistant flashing
Corrosion resistantperforated angle
60mm flashing tape
Corrosion resistant flashing withmin. 15 degree slope
EPDM strip
Corrosion resistantperforated anglefixed only to soffit
60mm flashing tape
Min. 10 mm
Min. 40 mm
10 - 15 mm
EPDM compressible gasket
10 - 15 mm drip edge
60mm flashing tape
Min. 15 mm
Min. 150 mm
Min. 35 mm
Min. 10 mm
Min. 40 mm
10 - 15 mm
Sealant
Corrosion resistant flashing
Corrosion resistantperforated angle
60mm flashing tape
Corrosion resistant flashingwith min. 15 degree slope
EPDM strip
Corrosion resistantperforated anglefixed only to soffit
60mm flashing tape
EPDM compressible gasket
60mm flashing tape
10 - 15 mm drip edge
Figure 27: Exposed concrete slab or beam - Cladding flush
Figure 28: Exposed concrete slab or beam - Cladding recessed
Notes1) Support frame (batten)s and Kalsi RigidBacker must NOT be fixed crossing over a control joint.2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% openarea with aperture size of 3-5mm.
37
30 - 100 mm
Max. 250 mm
Min. 1.1mm corrosionresistant metal angle
EPDM compressible gasket
8 - 12 mm
EPDM strip
EQUITONE UNI rivet
Max. 0.9mm corrosionresistant angle
8 - 12 mm30 - 100 mm
EPDM strip
EPDM compressible gasket
Figure 29: External corner - Detail 1
Figure 30: External corner - Detail 2
38
EPDM strip
Max. 0.9mm corrosionresistant angle
EPDM compressible gasket
EPDM compressible gasket
Backing rod & sealant
Max. 0.9mm corrosionresistant angle
60mm flashing tape
10 mm
EPDM strip
Figure 31: Internal corner
Figure 32: Abutment
39
Grommet
60mm flashing tape
Supporting collar,backing rod &sealant
Grommet60mm flashing tape
Supporting collar,backing rod &sealant
60mm flashing tape
Grommet
Once the grommet isinstalled, first apply thistape, and then continue anti-clockwise with the others
Figure 33: Pipe penetration - Plan view
Figure 34: Pipe penetration - Elevation Figure 35: Pipe penetration - Section
40
15 mm
Min. 15 mm
Min. 50 mm or larger to regulatory requirements
Sill or sealing tape
Roof or gutterflashing ormembrane
Corrosion resistantperforated angle
60mm flashing tape
EPDM strip
EPDM compressible gasket
To regulatory requirements
Suitable capping structural support
Min. 5 degree slope
60mm flashing tape
Sill or sealing tape
15 mm
Min. 15 mm
Min. 50 mm or larger to regulatory requirements
Air
Non-continuous packer
Roof or gutterflashing ormembrane
Corrosion resistantperforated angle
EPDM compressible gasket
EPDM strip
Min. 50 mm or larger to regulatory requirements
Suitable capping structural support
Min. 5 degree slope
Sill tape
Capping with two rows of sealantto saddle flashing
Capping support
Corrosion resistant Saddleflashing with two rows ofsealant to capping support
Min. 50mm
60mm flashing tape
Supportingangle, backingrod & sealant
Min. 100 mm
Figure 36: Capping - Detail 1
Figure 37: Capping - Detail 2(Not suitable for EQUITONE [materia])
Figure 38: Parapet junction - Section
Notes1) For EQUITONE [materia], the following capping dimensions should be followed.
- A minimum 20mm between panel face and rear of the capping- A minimum 50mm overlap with the panel for building up to 8m or larger to regulatory requirements.- A minimum 80mm overlap with the panel for building up to 20m or larger to regulatory requirements.- A minimum 100mm overlap with the panel for building over 20m or larger to regulatory requirements.
2) Any face fixings of capping shall be through an over sized hole (by min 5mm) in the capping as well as the panel.3) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min.50% open area with aperture size of 3-5mm.4) Capping shall be designed and engineered accordingly to provide adequate allowance for ventilation as shown in Figures 36 & 37.
41
Outline of saddleflashing
EPDM strip
EPDM compressible gasket
Min. 70 mm
Min. 50 mm
Min. 50 mm
Min.50 mm
Min. 150 mm
Min. 20 mm
Min. 50 mm
Min. 100 mm
Min. 5 degree slope
Figure 39: Parapet junction - Plan view
Figure 40: Corrosion resistant saddle flashing
42
Etex Exteriors ANZSuite 201198 Harbour EsplanadeDocklands VIC 3008Australia
+61 (03) 9988 [email protected]
Ed. 1 NOV2020
1. Cover page2. Table of contents3. General information4. Ventilation5. Components6. Support frame7. EQUITONE system with flexible air barrier & timber batten construction8. EQUITONE system with rigid air barrier & timber batten construction9. Contact details