165
NATIONAL INSTITUTE OF MALERIA RESEARCH (NIMR), Dwarka, New Delhi TENDER FOR Construction of Auditorium, Guest House, Hostel, Electric Substation , AC Plant Room , Under Ground water Tank etc at NIMR, Sector-8, Dwarka New Delhi-110077 HSCC (INDIA) LTD. (CONSULTANTS & ENGINEERS FOR MEGA HOSPITALS & LABORATORIES) E-6(A), sector-1, NOIDA(U.P) 201301 (India) Phone : 0120-2542436-40 Fax : 0120-2542447 VOLUME – V BOQ October' 2016 Tender No. HSCC/NIMR/Phase-II2015

Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

  • Upload
    buidiep

  • View
    227

  • Download
    6

Embed Size (px)

Citation preview

Page 1: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

NATIONAL INSTITUTE OF MALERIA RESEARCH (NIMR), Dwarka, New Delhi

TENDER

FOR

Construction of Auditorium, Guest House, Hostel, Electric Substation , AC Plant Room ,

Under Ground water Tank etc at NIMR, Sector-8, Dwarka New Delhi-110077

HSCC (INDIA) LTD. (CONSULTANTS & ENGINEERS FOR MEGA HOSPITALS & LABORATORIES)

E-6(A), sector-1, NOIDA(U.P) 201301 (India)

Phone : 0120-2542436-40 Fax : 0120-2542447

VOLUME – V

�BOQ

October' 2016

Tender No. HSCC/NIMR/Phase-II2015

Page 2: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

1.00 EARTH WORK

1.01 Earth work in excavation by mechanical means (Hydraulic excavator) /manual means over areas (exceeding 30cm in depth. 1.5 m in width as wellas 10 sqm on plan) including disposal of excavated earth, lead upto 50m andlift upto 1.5m, disposed earth to be levelled and neatly dressed.

a) All kinds of soil 1663.00 Cum

1.02 Earth work in excavation by mechanical means (Hydraulic excavator)/ manualmeans in foundation trenches or drains (not exceeding 1.5 m in width or 10sqm on plan) including dressing of sides and ramming of bottoms, lift up to1.5 m, including getting out the excavated soil and disposal of surplusexcavated soil as directed, within a lead of 50 m.

a) All kinds of soil. 1005.00 Cum

1.03 Filling available excavated earth (excluding rock) in trenches, plinth, sides offoundations etc. in layers not exceeding 20cm in depth, consolidating eachdeposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.

2617.00 Cum

1.04 Extra for every additional lift of 1.5 m or part there of in excavation/bankingexcavated or stacked materials.

a) All kinds of soil.

i) 1.5 to 3.0m 460.04 Cumii) 3.0 to 4.5m 194.36 Cumiii) 4.5 to 6.0m 68.00 Cum

1.05 Supplying and filling in plinth with Zone-V sand under floors including,watering. ramming consolidating and dressing complete.

288.00 Cum

1.06 Extra for disposal of excavated earth for additional lead beyond 50m or partthereof upto 9 such additional leads

a) All kinds of soil 1163.00 Cum

Total of sub-head

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-1

Page 3: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

2.00 CONCRETE WORK

2.01 Providing and laying in position cement concrete of specified grade excludingthe cost of centering and shuttering - All work up to plinth level :

a) 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominalsize). 134.00 Cum

b) 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mmnominal size) 293.00 Cum

2.02 Providing and laying cement concrete in retaining walls, return walls, walls(any thickness) including attached pilasters, columns, piers, abutments,pillars, posts, struts, buttresses, string or lacing courses, parapets, coping,bed blocks, anchor blocks, plain window sills, fillets, sunken floor,etc., up tofloor five level, excluding the cost of centering, shuttering and finishing :

a) 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominalsize) 18.00 Cum

2.03 Providing and laying damp-proof course 40 mm thick with cement concrete1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominalsize). 302.00 Sqm

2.04 Extra for providing and mixing water proofing material in cement concretework in doses by weight of cement as per manufacturer's specification

80.00per 50 kg

cement

2.05 Applying a coat of residual petroleum bitumen of grade of VG-10 of approvedquality using 1.7 kg per square metre on damp proof course after cleaning thesurface with brushes and finally with a piece of cloth lightly soaked inkerosene oil. 302.00 Sqm

Total of sub-head

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-2

Page 4: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

3.00 REINFORCED CEMENT CONCRETE

3.01 Providing and laying in position machine batched and machine mixed designmix M-25 grade cement concrete for reinforced cement concrete work, usingcement content as per approved design mix, including pumping of concrete tosite of laying but excluding the cost of centering, shuttering, finishing andreinforcement, including admixtures in recommended proportions as per IS:9103 to accelerate, retard setting of concrete, improve workability withoutimpairing strength and durability as per direction of Engineer-in-charge.

(Note :- Cement content considered in this item is @ 330 kg/cum.Excess/less cement used as per design mix is payable/recoverableseparately).

a) All works upto plinth level. 1039.00 Cumb) All works above plinth level upto floor V level. 1234.00 Cum

3.02 Providing and laying in position ready mixed M-25 grade concrete forreinforced cement concrete work, using fly ash and cement content as perapproved design mix, and manufactured in fully automatic batching plant andtransported to site of work in transit mixer for all leads, having continuousagitated mixer, manufactured as per mix design of specified grade forreinforced cement concrete work, including pumping of R.M.C.from transitmixer to site of laying, excluding the cost of centering,shuttering, finishing andreinforcement, including cost of admixtures in recommended proportions asper IS : 9103 to accelerate / retard setting of concrete, improve workabilitywithout impairing strength and durability as per direction of the Engineer - in -charge.

NOTE- (1) Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/ recoverable separately.

(2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as partreplacement of OPC as per IS : 456. Uniform blending with cement to beensured in accordance with clauses 5.2 and 5.2.1 of IS:456 -2000 in the itemsof BMC and RMC.

a) All works up to Plinth level. 75.00 Cumb) All works above plinth & up to floor V level. 114.00 Cum

Note :- The above item shall be used judiciously where specified quality of FlyAsh is available for mixing in concrete. Also, the guidelines issued by CDO,CPWD, vide circular no. CDO/SE(RR)/Fly Ash (Main)/102 dated 9th April2009 shall be followed in such cases.

3.03 Extra for providing richer mixes at all floor levels.

Note:- Excess/less cement over the specified cement content used is payable/recoverable separately.

i) Providing M-30 grade concrete instead of M-25 grade BMC/ RMC. (Note:-Cement content considered in M-30 is @ 340 kg/cum) 208.00 Cum

3.04 Centering and shuttering including strutting, propping etc. and removal of formfor :

a) Foundations, footings, bases of columns, etc. for mass concrete750.00 Sqm

b) Walls (any thickness) including attached pilasters, butteresses, plinth andstring courses etc. 592.40 Sqm

c) Suspended floors, roofs, landings, balconies and access platform3455.00 Sqm

d) Shelves (Cast in situ) 29.00 Sqm

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-3

Page 5: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

e) Lintels, beams, plinth beams, girders, bressumers and cantilevers4975.00 Sqm

f) Columns, Pillars, Piers, Abutments, Posts and Struts 3440.00 Sqmg) Stairs, (excluding landings) except spiral-staircases 366.00 Sqmh) Small lintels not exceeding 1.5 m clear span, moulding as in cornices, window

sills, string courses, bands, copings, bed plates, anchor blocks and the like143.00 Sqm

i) Extra for shuttering in circular work for

i) columns 293.00 Sqmii) Beams 227.00 Sqmiii) Slabs 74.00 Sqmj) Weather shade, Chajjas, corbels etc., including edges 223.00 Sqm

3.05 Extra for additional height in centering, shuttering where ever required withadequate bracing, propping etc., including cost of de-shuttering anddecentering at all levels, over a height of 3.5 m, for every additional height of1 metre or part thereof (Plan area to be measured).

a) Suspended floors, roofs, landing, beams and balconies (Plan area to bemeasured) 5210.00 Sqm

3.06 Steel reinforcement for R.C.C. work including straightening, cutting, bending,placing in position and binding all complete at all levels.

a) Thermo-Mechanically Treated bars. 387740.00 kilogram

3.07 Add/deduct for using extra/less cement in the items of design mix over andabove the specified cement content therein. 260.00 Quintal

Total of sub-head

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-4

Page 6: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

4.00 Walls and Partitions

4.01 Brick work with common burnt clay F.P.S. (non modular) bricks of classdesignation 7.5 in foundation and plinth in:

a) Cement mortar 1:6 (1 cement : 6 coarse sand) 285.00 Cum

4.02 Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at everythird course of half brick masonry. 2106.00 Sqm

4.03 Brick work with non modular fly ash bricks conforming to IS:12894, classdesignation 10 average compressive strength in super structure above plinthlevel up to floor V level in:

a) Cement mortar 1:6 (1 cement : 6 Coarse sand) 1592.00 Cum

4.04 Half brick masonry with non modular fly ash bricks of class designation 10,conforming to IS : 12894, in super structure above plinth and upto floor Vlevel.

a) Cement mortar 1 : 4 (1 cement : 4 coarse sand) 2105.00 Sqm

4.05 Brick edging 7cm wide 11.4 cm deep to plinth protection with common burntclay F.P.S. (non modular) bricks of class designation 7.5 including groutingwith cement mortar 1:4 (1 cement : 4 fine sand). 702.00 Metre

Total of sub-head

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-5

Page 7: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

5.00 DOORS & WINDOWS

5.01 Providing and fixing aluminium work for doors, windows, ventilators andpartitions with extruded built up standard tubular sections/ appropriate Zsections and other sections of approved make conforming to IS: 733 and IS:1285, fixing with dash fasteners of required dia and size, including necessaryfilling up the gaps at junctions, i.e. at top, bottom and sides with requiredEPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rustfree, straight, mitred and jointed mechanically wherever required includingcleat angle, Aluminium snap beading for glazing / paneling, C.P. brass /stainless steel screws, all complete as per architectural drawings and thedirections of Engineer-in-charge. (Glazing, paneling and dash fasteners to bepaid for separately) :

a) For fixed portion

i) Polyester Powder coated aluminium (minimum thickness of polyester powdercoating 50 micron) 5789.00 Kg

5.02 For shutters of doors, windows & ventilators including providing and fixinghinges/ pivots and making provision for fixing of fittings wherever requiredincluding the cost of EPDM rubber / neoprene gasket required (Fittings shallbe paid for separately)

a) Polyester Powder coated aluminium (minimum thickness of polyester powdercoating 50 micron) 3081.00 Kg

5.03 Providing and fixing anodised aluminium (anodised transparent or dyed torequired shade according to IS: 1868. Minimum anodic coating of grade AC15) sub frame work for windows and ventilators with extruded built upstandard tubular sections of approved make conforming to IS: 733 and IS :1285 fixed with dash fastener of required dia and size(Dash fastener to bepaid for separately). 932.00 kg

5.04 Providing and fixing glazing in aluminium door, window, ventilator shutters andpartitions etc. with EPDM rubber / neoprene gasket etc. complete as per thearchitectural drawings and the directions of engineer-in-charge . (Cost ofaluminium snap beading shall be paid in basic item):

a) With float glass panes of 5.50 mm thickness 444.00 Sqm

5.05 Providing and fixing double action hydraulic floor spring of approved brandand manufacture conforming to IS : 6315, having brand logo embossed onthe body / plate with double spring mechanism and door weight upto 125 kg,for doors, including cost of cutting floors, embedding in floors as required andmaking good the same matching to the existing floor finishing and coverplates with brass pivot and single piece M.S. sheet outer box with slide plateetc. complete as per the direction of Engineer-in-charge.

a) With brass cover plate minimum 1.25 mm thickness 29.00 Each

5.06 Providing and fixing anodised aluminium grill (anodised transparent or dyed torequired shade according to IS: 1868 with minimum anodic coating of gradeAC 15) of approved design/pattern, with approved standard section and fixedto the existing window frame with C.P. brass/ stainless steel screws @ 200mm centre to centre, including cutting the grill to proper opening size for fixingand operation of handles and fixing approved anodised aluminium standardsection around the opening, all complete as per requirement and direction ofEngineer-in-charge. (Only weight of grill to be measured for payment).

1369.00 kg

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-6

Page 8: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

5.07 Providing and fixing ISI marked flush door shutters conforming to IS : 2202(Part I) non-decorative type, core of block board construction with frame of1st class hard wood and well matched commercial 3 ply veneering withvertical grains or cross bands and face veneers on both faces of shutters:

a) 35 mm thick including ISI marked Stainless Steel butt hinges with necessaryscrews. 262.00 Sqm

5.08 Extra for providing lipping with 2nd class teak wood battens 25 mm minimumdepth on all edges of flush door shutters (over all area of door shutter to bemeasured). 262.00 Sqm

5.09 Extra for providing vision panel not exceeding 0.1 sqm in all type of flushdoors (cost of glass excluded) (overall area of door shutter to be measured) :

a) Rectangular or square. 69.00 Sqm

5.10 Extra for providing frosted glass panes 4 mm thick instead of ordinary floatglass panes 4 mm thick in doors, windows and clerestory window shutters.(Area of opening for glass panes excluding portion inside rebate shall bemeasured). 38.00 Sqm

5.11 Renewing glass panes, with wooden fillets wherever necessary.

a) Float glass panes of thickness 4 mm 7.00 Sqm

5.12 Providing & Fixing decorative high pressure laminated sheet of plain / woodgrain in gloss / matt / suede finish with high density protective surface layerand reverse side of adhesive bonding quality conforming to IS : 2046 Type S,including cost of adhesive of approved quality.

a) 1.0 mm thick. 499.00 Sqm

5.13 Providing and installation of fully insulated wooden fire rated shutter of120min. fire rating conforming to BS: 476 part 22 and IS:3614 Part II as perthe prototype tested and certified by CBRI Roorkee, of minimum 50 mmthickness, comprising of 75mm x 44mm hardwood internal timber frame work,with infill of 96 kg/m3, ceramic fiber blankets, coated with intumuscent coatingon both sides for insulation. The coated insulation shall be sandwichedbetween 12mm thick, Non combustible Boards (Calcium Silicate of approvedquality and manufacture) on both sides (edge to edge on internal Hardwoodframe) and cladded with 3mm thick commercial ply of approved quality &1mm thick laminate of approved brand and manufacture on both sides, with50mm x 14mm 2nd class teak wood lipping all round the shutter.

The shutter is suitable for mounted on the door frame, as per the item givenbelow. Both frame and shutter shall be fitted with fire & smoke intumescentseal of Viper or equivalent make of size 20 x 4mm on all the three sidesexcept bottom. The pasting of the ply/veneer/laminate should be done usingautomatic machine and should be free from any nails or perforations. Theboard shall be Resistant to vermin, mould growth, minor impact, abrasion andshort term water attack. The shutter shall be fixed with the frame with thehelp of SS 304 grade ball bearing hinges of size 100x75x3mm of approvedquality with necessary screws and making cut out for vision panel.Provisions/reinforcement for fixing all fixtures shall be built in on the door priorto the supply. The rate shall include all the materials, labour and T&P for theworks described in the item above.

a) Single/Double Shutter 22.00 Sqm

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-7

Page 9: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

5.14 Providing and fixing door frames as per BS: 476 part 22, IS:3614 Part II asper the prototype certified by CBRI Roorkee made out of 2nd class TeakWood (Ivory Coast)frame of section 120 X 70 mm for fire resistant doors of120 minutes fire rating, with heat activated intumescent fire seal strips of size20 x 4 mm( for smoke sealing) provided in grooves on all three sides of theframe with one coat of approved brand of fire retardant primer including twocoats of fire retardant paint FR 881or equivalent un thinned on cleared hardwood surface of door frames (@3.5 sq.m. per litre per coat) includingpreperation of base surface as per recommendations of manufacturer tomake the surface fire retardant, including fixing the frame with 8 nos. 100 mmlong, 10 mm dia metal dash fastners complete as per directions of theEngineer in charge NOTE:- cost of fire seal strips, dash fastners are includedin the item. Nothing extra shall be paid if size of any component of materialexceeds the limit mentioned in the item.

53.00 Metre

5.15 Providing and fixing of approved quality and manufacture wooden fire cumacoustic door as per BS:476 Part- 20 & 22 & IS 3614 part-1 & part-2 forstability, integrity and thermal insulation. Wooden door confirming to IS 277with the following specification. Recommended fire door shall have doorstested at CBRI for maximum rating of 2hrs tested with or without vision panel.Individual Test certificates should be available for glass used in vision litesconfirming the required fire ratings. Proper label confirming the type of doorand the hourly rating is mandatory.

Door leaf shall be 77mm thick flush door, with or without vision lite, comprising of 100mm x 65mm hardwood internal timber frame work, with infill of 41mmthick fire resistant & accoustic wool insulation of 48 Kg/m3 density coatedwith approved quality FR coating on both sides for insulation. The coatedinsulation shall be sandwiched between 12mm thick Non Combustible(Calcium Silicate) Board of approved brand and manufacture on both sides(edge to edge on internal Hard wood frame and cladded with 6mm thickcommercial ply of approved quality and manufacture & 1mm thick laminate ofapproved brand and manufacture (Any Regular Shade as approved by theengineer), with 77mm x 14mm exposed teak wood beading, 20 x4mm fire &smoke intumescent seal shall be used for shutter & for the frame 02 Nos. X10 x 4mm fire and smoke intumescent seal (For Smoke Sealing). The Frameshall be 140 x 90mm of Teak Wood (Ivory Coast) and cotaed with VIPER Firereatrdent Primer. The rebate shall be of 20mm x 79mm in Door Frame toaccommodate the shutter in frame The board shall be Resistant to vermin,mould growth, minor impact and abrasion

Area of opening shall be measured for payment. Cost of vision glass panel ispayable seperatly. 22.00 Sqm

5.16 Providing and fixing UL listed door Co-ordinator of approved Make forcoordination of double leaf doors, of approved brand and manufacture withminimum one year warrantee. 13.00 Each

5.17 Providing & fixing 11.0 mm thick sandwich clear toughened glass of approvedmake tested upto 2 hours fire rating and complies with BS 476: Part 22 asvision panel including cost of fire rated ceramic tape and moulding/beading allcomplete. 4.00 Sqm

5.18 Providing and fixing aluminium extruded section body tubular type universalhydraulic door closer (having brand logo with ISI, IS : 3564, embossed on thebody, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000mm), with double speed adjustment with necessary accessories and screwsetc. complete. 131.00 Each

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-8

Page 10: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

5.19 Providing and fixing aluminium sliding door bolts, ISI marked anodised(anodic coating not less than grade AC 10 as per IS : 1868), transparent ordyed to required colour or shade, with nuts and screws etc. complete :

a) 250x16 mm 54.00 Each

5.20 Providing and fixing aluminium tower bolts, ISI marked, anodised (anodiccoating not less than grade AC 10 as per IS : 1868 ) transparent or dyed torequired colour or shade, with necessary screws etc. complete :

a) 250x10 mm 525.00 Eachb) 150x10 mm 608.00 Each

5.21 Providing and fixing aluminium handles, ISI marked, anodised (anodic coatingnot less than grade AC 10 as per IS : 1868) transparent or dyed to requiredcolour or shade, with necessary screws etc. complete :

a) 125 mm

357.00 Eachb) 100 mm

65.00 Each

5.22 Providing and fixing aluminium hanging floor door stopper, ISI marked,anodised (anodic coating not less than grade AC 10 as per IS : 1868)transparent or dyed to required colour and shade, with necessary screws etc.complete.

a) Twin rubber stopper 178.00 Each

5.23 Providing and fixing bright finished brass 100 mm mortice latch and lock ISImarked with six levers and a pair of anodised (anodic coating not less thangrade AC 10 as per IS : 1868) aluminium lever handles of approved qualitywith necessary screws etc. complete. 89.00 Each

5.24 Providing and fixing stainless steel (SS 304 grade) adjustable friction windowsstays of approved quality with necessary stainless steel screws etc. to theside hung windows as per direction of Engineer-in-charge complete.

a) 205 X 19 mm 764.00 Each

5.25 Providing and fixing aluminium tubular handle bar 32 mm outer dia, 3.0 mmthick & 2100 mm long with SS screws etc .complete as per direction ofEngineer-in-Charge.

a) Polyester powder coated minimum thickness 50 micron aluminium tubularhandle bar 36.00 Each

5.26 Providing and fixing aluminium casement windows fastener of required lengthfor aluminium windows with necessary screws etc. complete.

a) Polyester powder coated minimum thickness 50 micron aluminium 487.00 Each

5.27 Providing and fixing aluminium round shape handle of outer dia 100mm withSS screws etc. complete as per direction of Engineer-in-charge

a) Polyester Powder coated minimum thickness 50 micron aluminium 21.00 Each

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-9

Page 11: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

5.28 Providing and fixing panic bar / latch (Double point) fitted with a single body,Trim Latch & Lock on back side of the Panic Latch of reputed brand andmanufacture to be approved by the Engineer- in- charge, all complete.

7.00 Nos.

5.29 Providing and fixing of fire rated heavy duty door closer of approved quality for fire door in accordance with BS:476 Part 22 for fire rating) and BS EN 1154with minimum one year warranty. 13.00 Each

5.30 Providing & fixing of SL 7260/ TLH 612 or equivalent approved Mortise LockWith SS Lever Handle of approved Make. 10.00 Each

5.31 Providing and fixing fire rated mortice dead lock tested in accordance withEuropean Standard EN12209 / DIN18251 and 80mm Long cylinder toEN1303 of approved brand and manufacturer having min. 1 yearmanufacturers warranty. 7.00 Each

5.32 Providing and fixing 300 mm long stainless steel grade 304 D type back toback pull handle of approved make with necessary bolts with alen keyarrangement etc complete. 28.00 Each

5.33 Providing and fixing bright finished 100 mm mortice lock with 6 levers withoutpair of handles of approved quality for aluminium door, with necessary screwsetc complete as per direction of Engineer-in-charge.

16.00 Each

5.34 Providing and fixing PVC rigid foam sheet 1 mm thick on existing doorshutters (bathroom and W.C. doors) using synthetic rubber based adhesive

81.00 Sqm

Total of sub-head

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-10

Page 12: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

6.00 STEEL WORK

6.01 Steel work welded in built up sections/ framed work, including cutting,hoisting, fixing in position and applying a priming coat of approved steelprimer using structural steel etc. as required.

a) In gratings, frames, guard bar, ladder, railings, brackets, gates, signage andsimilar works. 3047.00 Kg

6.02 Providing and fixing hand rail of approved size by welding etc. to steel ladderrailing, balcony railing, staircase railing and similar works, including applyingpriming coat of approved steel primer.

a) M.S. tube 481.00 kg

6.03 Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes,channels, plates etc., including welding, grinding, buffing, polishing andmaking curvature (wherever required) and fitting the same with necessarystainless steel nuts and bolts complete, i/c fixing the railing with necessaryaccessories & stainless steel dash fasteners , stainless steel bolts etc., ofrequired size, on the top of the floor or the side of waist slab with suitablearrangement as per approval of Engineer-in-charge, (for payment purposeonly weight of stainless steel members shall be considered excluding fixingaccessories such as nuts, bolts, fasteners etc.).

1057.00 Kg

6.04 Supplying and fixing rolling shutters of approved make, made of required sizeM.S. laths, interlocked together through their entire length and jointed togetherat the end by end locks, mounted on specially designed pipe shaft withbrackets, side guides and arrangements for inside and outside locking withpush and pull operation complete, including the cost of providing and fixingnecessary 27.5 cm long wire springs manufactured from high tensile steelwire of adequate strength conforming to IS: 4454 -part 1 and M.S. top coverof required thickness for rolling shutters.

80x1.25 mm M.S. laths with 1.25 mm thick top cover 52.50 sqm

6.05 Providing and fixing ball bearing for rolling shutters. 12.00 each

6.06 Extra for providing mechanical device chain and crank operation for operatingrolling shutters.

a) Exceeding 10.00 sqm and upto 16.80 sqm in the area 2.00 sqm

6.07 Extra for providing grilled rolling shutters manufactured out of 8 mm dia M.S.bar instead of laths as per design approved by Engineer-in- charge, (area ofgrill to be measured). 27.00 sqm

Total of sub-head

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-11

Page 13: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

7.00 FLOORING

7.01 Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stoneaggregate) finished with a floating coat of neat cement including cementslurry, but excluding the cost of nosing of steps etc. complete.

a) 40mm thick with 20mm nominal size stone aggregate. 797.10 Sqm

7.02 Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1 cement: 3 coarse sand), finished with a floating coat of neat cement.

a) 18 mm thick 63.10 Sqm

7.03 Providing and fixing glass strips in joints of terrazo/ cement concrete floors.

a) 40 mm wide and 4 mm thick. 44.30 Metre

7.04 Marble stone flooring with 18 mm thick marble stone, as per sample of marbleapproved by Engineer-in-charge, over 20 mm (average) thick base of cementmortar 1:4 (1 cement : 4 coarse sand) laid and jointed with grey cementslurry, including rubbing and polishing complete with :

a) Raj Nagar plain 162.20 Sqmb) Udaipur green/Jaiselmer marble 327.40 Sqm

7.05 Providing and fixing machine cut, mirror / eggshell polished , Marble stonework for wall lining (veneer work) including dado, skirting, risers of steps etc.,in required design and pattern wherever required, stones of different finishedsurface texture, on 12 mm (average) thick cement mortar 1:3 (1 cement : 3oarse sand) laid and jointed with white cement slurry @ 3.3 kg/sqm includingpointing with white cement slurry admixed with pigment of matching shade,including rubbing, curing, polishing etc. all complete as per Architecturaldrawings, and as directed by the Engineer-in-Charge.

a) Flamed/polished granite stone slab Jet Black, Cherry Red, Elite Brown, CatEye or equivalent 65.00 Sqm

7.06 Providing and laying flamed finish Granite stone flooring in required designand patterns, in linear as well as curvilinear portions of the building allcomplete as per the architectural drawings with 18 mm thick stone slab over20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand)laid and jointed with cement slurry and pointing with white cement slurryadmixed with pigment of matching shade including rubbing, curing andpolishing etc. all complete as specified and as directed by the Engineerin-Charge :

a) Flamed/polished finish granite stone slab Jet Black, Cherry Red, Elite Brown,Cat Eye or equivalent 645.00 Sqm

7.07 Kota stone slab flooring over 20 mm (average) thick base laid over andjointed with grey cement slurry mixed with pigment to match the shade of theslab including rubbing and polishing complete with base of cement mortar 1 :4 (1 cement : 4 coarse sand) :

a) 25 mm thick. 1228.00 Sqm

7.08 Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laidon 12 mm (average) thick cement mortar 1:3 (1 cement 3 coarse sand) andjointed with grey cement slurry mixed with pigment to match the shade of theslabs, including rubbing and polishing complete. 234.00 Sqm

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-12

Page 14: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

7.09 Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS :15622 (thickness to be specified by the manufacturer ) of approved make inall colours, shades except burgundy, bottle green, black of any size asapproved by Engineer-in-Charge in skirting, risers of steps and dados over 12mm thick bed of cement Mortar 1:3 (1 cement : 3 coarse sand) and jointingwith grey cement slurry @ 3.3kg per sqm including pointing in white cementmixed with pigment of matching shade complete.

786.00 Sqm

7.10 Providing and laying vitrified floor tiles in different sizes (thickness to bespecified by the manufacturer) with water absorption's less than 0.08% andconforming to IS : 15622 of approved make in all colours and shades, laid on20mm thick cement mortar 1:4 (1 cement : 4 coarse sand) including groutingthe joints with white cement and matching pigments etc., complete.

a) Size of Tile 600x600 mm 654.00 Sqm

7.11 Providing and laying Antiskid vitrified floor tiles in different sizes (thickness tobe specified by the manufacturer) with water absorption's less than 0.08% and conforming to IS : 15622 of approved make in all colours and shades, laid on20mm thick cement mortar 1:4 (1 cement : 4 coarse sand) including groutingthe joints with white cement and matching pigments etc., complete.

a) Size of Tile 600x600 mm 112.00 Sqm

7.12 Providing and laying rectified/ antiskid Glazed Ceramic floor tiles 300x300 mmor more (thickness to be specified by the manufacturer) of 1st qualityconforming to IS : 15622 of approved make in all colours, shades, exceptWhite, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4(1 Cement : 4 Coarse sand) including pointing the joints with white cementand matching pigments etc., complete.

126.00 Sqm

7.13 Providing and laying Vitrified tiles in different sizes (thickness to be specifiedby manufacturer) with water absorption less than 0.08 % and conforming toI.S. 15622, of approved make in all colours & shade in skirting, riser of steps,over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand),including grouting the joint with white cement & matching pigments etc.complete.

a) Size of Tile 600x600 mm 377.00 Sqm

7.14 Providing and fixing 18 mm thick gang saw cut, mirror polished, premouldedand prepolished, machine cut for kitchen platforms, vanity counters, windowsills , facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarsesand), joints treated with white cement, mixed with matching pigment, epoxytouch ups, including rubbing, curing, moulding and polishing to edges to givehigh gloss finish etc. complete at all levels

a) Raj Nagar Plain white marble/ Udaipur green marble/ Zebra black marble i Area of slab upto 0.50 sqm 47.00 Sqm

b) Granite of any colour and shade

i Area of slab upto 0.50 sqm 20.00 Sqmii Area of slab over 0.50 sqm. 14.00 Sqm

7.15 Providing edge moulding to 18 mm thick marble stone counters, Vanities etc.,including machine polishing to edge to give high gloss finish etc. complete asper design approved by Engineer-in-Charge.

a) Granite work 42.00 Metre

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-13

Page 15: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

7.16 Extra for fixing marble /granite stone, over and above corresponding basic item, in facia and drops of width upto 150 mm with epoxy resin based adhesive, including cleaning etc. complete.

42.00 Metre

7.17 Extra for providing opening of required size & shape for wash basin/ kitchensink in kitchen platform, vanity counter and similar location inmarble/Granite/stone work, including necessary holes for pillar taps etc.including moulding, rubbing and polishing of cut edges etc. complete.

25.00 Each

7.18 Chequered terrazo tiles 22 mm thick with graded marble chips of size up to 6mm in floors jointed with neat cement slurry mixed with pigment to match theshade of the tiles including rubbing and polishing complete on 20 mm thickbed of cement mortar 1:4 (1 cement :4 coarse sand) :

a) Medium shade using 50%white cement 50% ordinary cement 101.00 Sqm

7.19 38 mm thick wood block flooring of first class teak wood laid over 25 mmthick leveling layer of cement concrete 1:2:4 (1 cement : 2 coarse sand : 4graded stone aggregate 10 mm nominal size) to be paid separately, coatedwith a thin layer of hot bitumen penetration 80/25 (blown type) @ 2.45 kg persqm, including fixing blocks in position after dipping in hot bitumen (blowntype) up to half depth, planed, levelled smooth and finished complete.

7.20 Providing and fixing pure wool cut/ loop pile carpet of approved brand andmanufacture having total pile weight of 1250 Gm per sqm including underlayof 8 mm thick PU foam fixed to existing floor with synthetic adhesive asapproved by the manufacturer, all complete as per specification and directionof engineer in charge.

7.21 Providing and fixing PVC Vinyl Accoustic flooring of approved manufacturehaving total thickness not less than 3.00mm, jointless flooring with suitablewelding and adhesive of approved quality etc all complete as directed byEngineer in charge.The PVC floor should have acoustic impact soundReduction, Acoustical Improvement.

Total of sub-head

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-14

123.00 Sqm

194.00 Sqm

455.00 Sqm

Page 16: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

8.00 ROOFING

8.01 Providing and fixing tiled false ceiling of approved materials of size 595x595mm in true horizontal level, suspended on inter locking metal grid of hotdipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both sideinclusive) consisting of main "T" runner with suitably spaced joints to getrequired length and of size 24x38 mm made from 0.30 mm thick (minimum)sheet, spaced at 1200 mm center to center and cross "T" of size 24x25 mmmade of 0.30 mm thick (minimum) sheet, 1200 mm long spaced betweenmain "T" at 600 mm center to center to form a grid of 1200x600 mm andsecondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mmthick (minimum) sheet to be interlocked at middle of the 1200x600 mm panelto form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and layingfalse ceiling tiles of approved texture in the grid including, requiredcutting/making, opening for services like diffusers, grills, light fittings, fixtures,smoke detectors etc. Main "T" runners to be suspended from ceiling using GIslotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia

and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanisedbutterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center tocenter along main T, bottom exposed width of 24 mm of all T-sections shallbe pre-painted with polyester paint, all complete for all heights as perspecifications, drawings and as directed by Engineer-in-charge.

a) 12.5 mm thick fully Perforated Gypsum Board tile made from plasterboardhaving glass fibre conforming to IS: 2095 part I , of size 595x595 mm, havingperforation of 9.7x9.7 mm at 19.4 mm c/c with center borders of 48 mm andthe side borders of 30 mm, backed with non woven tissue on the back side,having an NRC ( Noise Reduction Coefficient) of 0.79, with 50 mm resinbondedglass wool backing. 407.00 Sqm

8.02 Providing & Fixing of Mineral Fibre Acoustical Suspended Ceiling Systemwith Armstrong/ Anutone/ Topakustik tiles with 15mm Exposed GRID as permanufacturer specification. The tiles should have Humidity Resistance (RH)of 95%, NRC 0.9, Light Reflectance ≥85%, Fire Performance UK Class 0 /Class 1 (BS 476 pt - 6 &7) in module size of 600 x 600 x 15mm. The tile shallbe laid on 38 15 mm wide T - section flanges colour white having rotarystitching on all T sections i.e. the Main Runner, 1200 mm & 600 mm CrossTees with a web height of 38mm and a load carrying capacity of 14 Kgs/M2.The T Sections have a Galvanizing of 90 grams per M2.

INSTALLATION: To comprise main runner spaced at 1200mm centressecurely fixed to the structural soffit using suspension system (as perspecifications) at 1200mm centre to centre. The First/Last suspensionsystem at the end of each main runner should not be greater than 450mmfrom the adjacent wall. Flush fitting 1200mm long cross tees to beinterlocked between main runners at 600mm centre to form 1200 x 600 mmmodule. Cut cross tees longer than 600mm require independent support.600 x 600mm module to be formed by fitting 600mm long flush fitting crosstees centrally between the 1200 mm cross tees. Perimeter trim to be wallangles of size 3000x19x19mm, secured to walls at 450 mm maximumcentres.

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-15

Page 17: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

SUSPENSION SYSTEM accessories consisting of M6 Anchor Fastenerswith Vertical Hangers made of Galvanised steel of size 26 x 26 x 25 x 1.2mmwith a Galvanised Thickness of 80gsm, A pre Straightened Hanger wire of dia2.68 mm of 1.83 m length., thickness of 80gsm and a tensile strength of 344-413 MPa, along with Adjustable hook clips of 0.8mm thick, galvanised springsteel for 2.68 mm with a minimum pull strength of 110 kg. The adjustable clipalso consists of a 3.5 mm aquiline wire to be used with the main runner. (Areaof false ceiling shall be measured for payment)

711.00 Sqm

8.03 Providing & fixing false ceiling at all height including providing & fixing offramework made of special section, power pressed from M.S. sheets andgalvanised with zinc coating of 120 gms/ sqm (both side inclusive) as per IS :277 and consisting of angle cleat of size 25mm wide x 1.6mm thick withflanges of 27mm and 37mm, at 1200mm c/c, one flange fixed to the ceilingwith dash fastener 12.5mm dia x 50mm long with 6mm dia bolts, other flangeof cleat fixed to the angle hangers of 25 x10 x0.50mm of required length withnuts & bolts of required size and other end of angle hanger fixed withintermediate G.I chanels 45 x15 x 0.90mm running at the spacing of

intermediate G.I chanels 45 x15 x 0.90mm running at the spacing of 1200 mmc/c, to which the ceiling section 0.5mm thick bottom wedge of 80mm withtapered flanges of 26 mm each having lips of 10.5mm, at 450mm c/c, shallbe fixed in a direction perpendicular to G.I intermediate channel withconnecting clip made out of 2.64mm dia x 230mm long G.I wire at everyjunction, including fixing perimeter channels 0.50mm thick 27mm high havingflanges of 20mm and 30mm long, the perimeter of ceiling fixed to wall/partitions with the help of Rawl plugs at 450mm centre, with 25mm long drywall screws @ 230mm interval, including fixing of Calcium Silicate Board toceilingsection and perimeter channels with the help of dry wall screws of size 3.5x25mm at 230mm c/c, including jointing & finishing to a flush finish of taperedand square edges of the board with recommended jointing compounds,jointing tapes,finishing with jointing compounds in three layers covering up to150mm on both sides of joints and two coats of primer suitable for boards, allas per manufacture's specification and also including the cost of makingopening for light fittings, grills, diffusers, cut outs made with frame ofperimeter channels suitably fixed, all complete as per drawings, specificatonand direction of the Engineer in charge but excluding the cost of painting with:

a) 8 mm thick Calcium Silicate Board made with Calcareous & Siliceousmaterials reinforced with cellulose fiber manufactured through autoclavingprocess. 228.00 Sqm

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-16

Page 18: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

8.04 Providing and fixing false ceiling at all height including providing and fixing offrame work made of special sections, power pressed from M.S. sheets andgalvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS :277 and consisting of angle cleats of size25 mm wide x 1.6 mm thick withflanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixedto the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm diabolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm ofrequired length with nuts & bolts of required size and other end of anglehanger fixed with intermediate G.I. channels 45x15x0.9 mm running at thespacing of 1200 mm centre to centre, to which the ceiling section 0.5 mmthick bottom wedge of 80 mm with tapered flanges of 26 mm each having lipsof 10.5 mm, at 450 mm centre to centre, shall be fixed in a directionperpendicular to G.I. intermediate channel with connecting clips made out of2.64 mm dia x 230 mm long G.I. wire at every junction, including fixingperimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawlplugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval,including fixing of gypsum board to ceiling section and perimeter channel withthe help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, includingjointing and finishing to a flush finish of tapered and square edges of theboard with recommended jointing compound , jointing

tapes , finishing with jointing compound in 3 layers covering upto 150 mm onboth sides of joint and two coats of primer suitable for board, all as permanufacturer's specification and also including the cost of making openingsfor light fittings, grills, diffusers, cutouts made with frame of perimeterchannels suitably fixed, all complete as per drawings, specification anddirection of the Engineer in Charge but excluding the cost of painting with :

a) 12.5 mm thick tapered edge gypsum plain board conforming to IS: 2095- PartI 72.00 Sqm

8.05 Providing and fixing 10mm thick clear multi wall solar control polycarbonatesheets of approved quality and shade in desired shape in roofing including thecost of EPDM gaskets , sealing tape , aluminium profile and all necessaryaccessories complete as per architectural drawings and as directed byEngineer incharge. The item includes designing the complete system andsupplying & getting approved from client and / or reputed engineering instituelike IIT etc. The detailed shop drawings including supplying structural designcalculations based on relevent codal provisions and carrying out waterpenetration test as per standards followed in India.

a) for Plain Structure 21.00 SqmThe whole work is to be done through reputed and approved vendor havingexperience in polycarbonate work in Commercial/ Govt/ Corporate buildingsas per architectural elevation drawings including filling of joints with siliconsealent and also with masonary/ RCC work, at all heights including doubleheights, straight or curved etc. complete in all respect. ( Surface Area shall bemeasured for the payment) ( M.S. Framing to be paid for seprately )

8.06 Providing and laying water proofing treatment to vertical and horizontalsurfaces of depressed portions of W.C., kitchen and the like consisting of :

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-17

Page 19: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

Ist course of applying cement slurry @ 4.4 kg/sqm mixed with water proofingcompound conforming to IS 2645 in recommended proportions includingrounding off junction of vertical and horizontal surface.

IInd course of 20 mm cement plaster 1:3 (1 cement : 3 coarse sand) mixedwith water proofing compound in recommended proportion including roundingoff junction of vertical and horizontal surface.IIIrd course of applying blown or residual bitumen applied hot at 1.7 kg. persqm of area.IVth course of 400 micron thick PVC sheet. (Overlaps at joints of PVC sheetshould be 100 mm wide and pasted to each other with bitumen @ 1.7kg/sqm). 79.00 Sqm

8.07 Providing and laying integral cement based water proofing treatment includingpreparation of surface as required for treatment of roofs, balconies, terracesetc consisting of following operations: a) Applying a slurry coat of neat cementusing 2.75 kg/sqm. of cement admixed with water proofing compoundconforming to IS. 2645 and approved by Engineer-in-charge over the RCCslab including adjoining walls upto 300mm height including cleaning thesurface before treatment. b) Laying brick bats with mortar using brokenbricks/brick bats 25 mm to 115mm size with 50% of cement mortar 1:5 (1cement : 5 coarse sand) admixed with water proofing compound conformingto IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer ofcement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with waterproofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300mm height including rounding of junctions of walls and slabs c) After two daysof proper curing applying a second coat of cement slurry using 2.75kg/ sqm ofcement admixed with water proofing compound conforming to IS : 2645 andapproved by Engineer-in-charge. d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4(1 cement :4 coarse sand) admixed with water proofing compoundconforming to IS : 2645 and approved by Engineer-in-charge including layingglass fibre cloth of approved quality in top layer of plaster and finally finishingthe surface with trowel with neat cement slurry and making pattern of 300x300mm square 3mm deep. e) The whole terrace so finished shall be flooded withwater for a minimum period of two weeks for curing and for final test. Allabove operations to be done in order and as directed and specified by theEngineer-in-Charge :

a) With average thickness of 120 mm and minimum thickness at khurra as 65mm. 3000.00 Sqm

Total of sub-head

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-18

Page 20: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

9.00 FINISHING

9.01 12 mm cement plaster of mix :

a) 1:6 (1 cement: 6 fine sand) 4585.00 Sqm

9.02 15 mm cement plaster on the rough side of single or half brick wall of mix:

a) 1:4 (1 cement: 4 fine sand) 1233.00 Sqmb) 1:6 (1 cement : 6 fine sand) 6760.00 Sqm

9.03 18 mm cement plaster in two coats under layer 12 mm thick cement plaster1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cementplaster 1:6 (1 cement : 6 fine sand). 6304.00 Sqm

9.04 6 mm cement plaster of mix :

a) 1:3 (1 cement : 3 fine sand) 4223.00 Sqm

9.05 Extra for plastering exterior walls of height more than 10 m from ground levelfor every additional height of 3 m or part thereof. 202.00 Sqm

9.06 Providing and applying plaster of paris putty of 2 mm thickness over plasteredsurface to prepare the surface even and smooth complete. 13767.00 Sqm

9.07 White washing with lime to give an even shade :

a) New work (three or more coats) 688.00 Sqm

9.08 Distempering with 1st quality acrylic distemper, having VOC (Volatile OrganicCompound ) content less than 50 grams/ litre, of approved brand andmanufacture, including applying additional coats wherever required, toachieve even shade and colour.

a) Two Coats 9209.00 Sqm

9.09 Finishing walls with Acrylic Smooth exterior paint of required shade :

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-19

Page 21: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

a) New work (Two or more coat applied @ 1.67 ltr/10 sqm over and includingpriming coat of exterior primer applied @ 2.20 kg/ 10 sqm) 2176.00 Sqm

9.10 Applying priming coats with primer of approved brand and manufacture,having low VOC (Volatile Organic Compound ) content.With ready mixed pink or grey primer on wood work (hard and soft wood)having VOC content less than 50 grams/ litre Sqm

a) With ready mixed red oxide zinc chromatic on steel / iron works having VOCcontent less than 250 grams/ litre 256.00 Sqm

b) With water thinnable cement primer on wall surface having VOC content lessthan 50 grams/litre 15566.00 Sqm

9.11 Finishing walls with textured exterior paint of required shade:

a) New work (Two or more coats applied @ 3.28 Itr/10 sqm) over and includingbase coat of water proofing cement paint applied @ 2.20kg/1 0 sqm.

6304.00 Sqm

9.12 Wall painting with premium acrylic emulsion paint of interior grade, havingVOC (Volatile Organic Compound ) content less than 50 grams/ litre ofapproved brand and manufacture, including applying additional coatswherever required to achieve even shade and colour.

a) Two Coats 6358.00 Sqm

9.13 Painting with synthetic enamel paint, having VOC (Volatile OrganicCompound) content less than 150 grams/ litre, of approved brand andmanufacture, including applying additional coats wherever required to achieveeven shade and colour.

a) Two Coats 256.00 Sqm

9.14 Providing and fixing 150 mm wide, 22 gauge and 18mm square chickenwiremesh at junctions of concrete and brick work and other locations at allheights placed symmetrically on the joint, including cutting to required size,fixing in position with cement and nails etc complete in all respects as perspecifications/drawings and to the entire satisfaction of the Engineer inCharge. 844.00 Sqm

Total of sub-head

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-20

Page 22: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

10.00 MISCELLANEOUS

10.01 Providing and fixing dry cladding upto 10 metre heights with 30 mm thickgang saw cut stone with (machine cut edges) of uniform colour and size upto1mx1m, fixed to structural steel frame work and/ or with the help of cramps,pins etc. and sealing the joints with approved weather sealant as perArchitectural drawing and direction of Engineer-in-charge. (The steel framework, stainless steel cramps and pins etc. shall be paid for separately).Nothing extra is payable for creating grooves in between stones.

a) White sand stone Sqmb) Extra rate if 30 mm thick Gwalior Stone of approved quality is used instead of

white sand stone in item 10.01(a) above Sqm

10.02 Providing and fixing adjustable stainless steel cramps of approved quality,required shape and size, adjustable with stainless steel nuts, bolts andwasher (total weight not less than 260 gms), for dry stone cladding fixed onframe work at suitable location, including making necessary recesses in stoneslab, drilling required holes etc complete as per direction of the Engineer-in-charge. Each

10.01 Making plinth protection 50 mm thick of cement concrete 1:3:6 (1 cement: 3coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mmthick bed of dry brick ballast 40 mm nominal size, well rammed andconsolidated and grouted with fine sand, including finishing the top smooth.

803.00 Sqm

10.02 Providing and supplying aluminium extruded tubular and other aluminiumsections as per the architectural drawings and approved shop drawings , thealuminium quality as per grade 6063 T5 or T6 as per BS 1474,including superdurable powder coating of 60-80 microns conforming to AAMA 2604 ofrequired colour and shade as approved by the Engineer-in-Charge. ( The itemincludes cost of material such as cleats, sleeves, screws etc. necessary forfabrication of extruded aluminium frame work. Nothing extra shall be paid onthis account). 2243.00 Kg

10.03 Designing, fabricating, testing, protection, installing and fixing in position semi(grid) unitized system of structural glazing (with open joints) for linear as wellas curvilinear portions of the building for all heights and all levels, including:

a) Structural analysis & design and preparation of shop drawings for thespecified design loads conforming to IS 875 part III (the system must passedthe proof test at 1.5 times design wind pressure without any failure), includingfunctional design of the aluminum sections for fixing glazing panels of variousthicknesses, aluminium cleats, sleeves and splice plates etc. gaskets,screws, toggles, nuts, bolts, clamps etc., structural and weather siliconesealants, flashings, fire stop (barrier)-cum-smoke seals, microwave curedEPDM gaskets for water tightness, pressure equalisation & drainage andprotection against fire hazard including:

b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminiumalloy of 6005 T5 brackets of required sizes, sections and profiles etc. toaccommodate 3 Dimentional movement for achieving perfect verticality andfixing structural glazing system rigidly to the RCC/ masonry/structural steelframework of building structure using stainless steel anchor fasteners/ bolts,nylon seperator to prevent bimetallic contacts with nuts and washers etc. ofstainless steel grade 316, of the required capacity and in required numbers.

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-21

Page 23: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

c) Providing and filling, two part pump filled, structural silicone sealant andone part weather silicone sealant compatible with the structural siliconesealant of required bite size in a clean and controlled factory / work shopenvironment , including double sided spacer tape, setting blocks and backerrod, all of approved grade, brand and manufacture, as per the approvedsealant design, within and all around the perimeter for holding glass.

d) Providing and fixing in position flashings of solid aluminium sheet 1 mmthick and of sizes, shapes and profiles, as required as per the site conditions,to seal the gap between the building structure and all its interfaces with curtainglazing to make it watertight.e) Making provision for drainage of moisture/ water that enters the curtainglazing system to make it watertight, by incorporating principles of pressureequalization, providing suitable gutter profiles at bottom (if required), makingnecessary holes of required sizes and of required numbers etc. complete.This item includes cost of all inputs of designing, labour for fabricating andinstallation of aluminium grid, installation of glazed units, T&P, scaffolding andother incidental charges including wastages etc., enabling temporarystructures and services, cranes or cradles etc. as described above and asspecified. The item includes the cost of getting all the structural and functionaldesign including shop drawings checked by a structural designer, dullyapproved by Engineer-in-charge. The item also includes the cost of all mockups at site, cost of all samples of the individual components for testing in anapproved laboratory, field tests on the assembled working structural glazingas specified, cleaning and protection till the handing over of the building foroccupation. In the end, the Contractor shall provide a water tight structuralglazing having all the performance characteristics etc. all complete asrequired, as per the Architectural drawings, as per item description, asspecified, as per the approved shop drawings and as directed by the Engineer-in-Charge.

Note:- 1. The cost of providing extruded aluminium frames, shadow boxes,extruded aluminium section capping for fixing in the grooves of the curtainglazing and vermin proof stainless steel wire mesh shall be paid forseparately under relevant items under this sub- head. However, for thepurpose of payment, only the actual area of structural glazing (including widthof grooves ) on the external face shall be measured in sqm. up to two decimalplaces.

Note:-2. The following performance test are to be conducted on structuralglazing system if area of structural glazing exceeds 2500 Sqm from thecertified laboratories accreditated by NABL(National Accreditation Board forTesting and Calibration Laboratories), Department of Science &Technologies, India. Cost of testing is payable separately. The NIT approvingauthority will decide the necessity of testing on the basis of cost of the work,cost of the test and importance of the work. Performance Testing of Structuralglazing system Tests to be conducted in the NBL Certified laboratories

1. Performance Laboratory Test for Air Leakage Test (-50pa to –300pa) &(+50pa to +300pa) as per ASTM E-283-04 testing method for a range oftesting limit 1 to 200 mVhr”2. Static Water Penetration Test. (50pa to 1500pa) as per ASTME-331-09testing method for a range up to 2000 ml.”3. Dynamic Water Penetration (50pa to 1500pa) as per AAMA 501.01-05testing method for a range upto 2000 ml”4. Structural Performance Deflection and deformation by static air pressuretest (1.5 times desing wind pressure without any failure) as per ASTME-330-10 testing method for a range upto 50 mm”5. Seismic Movement Test (upto 30 mm) as per AAMA 501.4-09 testingmethod for Qualitative test” Tests to be conducted on site

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-22

Page 24: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

6. Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa(35psi) upto 2000ml” 345.00 Sqm

10.04 Providing, assembling and supplying vision glass panels (IGUs) comprising ofhermetically-sealed 6-12- 6 mm insulated glass (double glazed) vision panelunits of size and shape as required and specified, comprising of an outer heatstrengthened float glass 6mm thick, of approved colour and shade withreflective soft coating on surface # 2 of approved colour and shade, an innerHeat strengthned clear float glass 6mm thick, spacer tube 12mm wide,dessicants, including primary seal and secondary seal (structural siliconesealant) etc. all complete for the required performances, as per theArchitectural drawings, as per the approved shop drawings, as specified andas directed by the Engineer-in-Charge. The IGUs shall be assembled in thefactory/ workshop of the glass processor. (Payment for fixing of IGU Panels inthe curtain glazing is included in cost of item No.26.2) For payment, only theactual area of glass on face # 1 of the glass panels (excluding the areas ofthe grooves and weather silicone Sealant) provided and fixed in position, shallbe measured in sqm.

(i) Coloured tinted float glass 6mm thick substrate with reflective soft coatingon face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass ofapproved make having properties as visible Light transmittance (VLT) of 25 to35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %,shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc.The properties of performance glass shall be decided by technical sanctioningauthority as per site requirement. 345.00 Sqm

10.05 Extra for openable side / top hung vision glass panels (IGUs) includingproviding and supplying at site all accessories and hardwares for theopenable panels as specified and of the approved make such as heavy dutystainless steel friction hinges, min 4 -point cremone locking sets with stainlesssteel plates, handles, buffers etc. including necessary stainless steel screws/fasteners, nuts, bolts, washers etc. all complete as per the Architecturaldrawings, as per the approved shop drawings, as specified and as directed bythe Engineer- in-Charge. 82.00 Sqm

10.06 Providing and Fixing Armstrong/ Anutone/ Topakustik Channelled Woodworksperforated panels of required width and length and thickness of 15mm, madeof a high density fibre board with minimum 830 Kg/M3 density substrate with alaminated facing / wood veneer as per the approved shade/ species & finishand a melamine balancing layer on the reverse side. The boards shall have aspecial perforation pattern where the visible surface has a “Helmholtz” flutedperforation of required width etc as required. The panels shall provide a firereaction of Class of 1 as per Part 7 of BS 476. The edges of the panels shallbe “tongue-and-grooved” to receive special clips for installation. The back ofthe perforated panel shall have sound absorbing non-woven acoustical fleecehaving NRC of 0.55. The panels shall be mounted on keel made up ofAluminium extrusion of size 18X26X3000 mm.using inside and outsidealuminium border clips of size 45X38X5mm, as per manufacturerspecification and/or approved by Architect/Engineer-in-Chargnd

INSTALLATION: Providing and fixing aluminium extruded keel for channelledwoodworks as per the manufacturer specification over wooden battens of size50mmx50mm or as approved by the Engineer in Charge/ Architect on thesolid wall. (Area of paneling shall be measured for payment. The rate mustinclude all costs involved in labour, all materials, scaffolding and T&P)

248.00 Sqm

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-23

Page 25: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

10.07 Providing and supplying Armstrong (Optra)/ Anutone/ Topakustik AcousticalWall Paneling with square edges made of fibre glass substrate 25mm thickand wrapped on the front side with an acoustically transparent and classifiedfor Fire reaction Class B-s1, d1 as per EN13501, fabric with an option ofcolors , as recommended by Engineer/ Architect of size 600X1200/2100 mm,providing a minimum sound absorption level of 0.90 NRC to be affixed to wallusing Wall panel impalers as per the manufacturer spceification and usingconstruction adhesives as per the instructions laid down by the manufacturer.

INSTALLATION: Wall panel Impalers of size 102mmX77mmX1.2mm GMSZinc Coated both sides with galvanisation of 90 gm/sqm as per manufacturerspecification shall be fixed to the wall surface using self tapping screws. Silicabased construction adhesive to be dabbed on to the projecting elements(spikes) of the impalers. Wall panels shall be pierced through the spikes ofthe impalers ensuring the line and level of the panels are maintained. (Area ofpaneling shall be measured for payment. The rate must include all costsinvolved in labour, all materials, scaffolding and T&P)

298.00 Sqm

10.08 Providing and fixing Auditorium Chairs as per specification given below:

1) Seat rest Assembly: The seat-rest assembly is made up of FR grade 15mm thick Marine or equivalent plywood upholstered with fabric of approvedquality and sample and moulded polyurethane foam with Injection mouldedseat cover. The seat is auto tip-up type and folds when not in use. The seatsize should be 45.0cm. (W) X 48.5cm. (D) X 14.5cm. (T) approx.

2) Back rest Assembly: The backrest assembly is made up of a FR grade 15mm thick Marine or equivalent plywood upholstered with fabric of approvedquality and sample and moulded polyurethane foam with injection mouldedback cover. The back foam is designed with contoured lumbar support forextra comfort. The back size should be 47.5cm. (W) X 80.0cm. (H) X 12.5cm.(T) approx.3) Leg Frame Assembly: The leg frame assembly is fabricated from M.S.tube 6 cm x 4 cm x 14bg (2.0mm) thick welded with grouting member. It isblack powder coated & grouted to the floor using Foundation expansion boltsof approved quality and manufacture.

4) Armrest Assembly: It consists of the following:a) P.U. armrest: The armrest is made up of black integral skin Polyurethanewith 70-80 shore `A ’ hardness and reinforced with M.S. insert fixed with legframe. The armrests are scratch and weather resistant. Armrest may be flatsurface or with cup-holder as per the requirement.b) Armrest cladding: The armrest cladding is made up of 9 mm particle boardof approved quality & upholstered with fabric of approved quality and sample.

5) Powder Coating: All steel components are Epoxy Polyester Powder Coatedof approved quality.

6) PU Foam: The polyurethane foam is moulded with density 48+/-2kgs./cum.7) Upholstery: The fabric must be foam laminated stretchable fire retardant, ofapproved quality, as per the sample approved by the Engineer. A sample ofchair shall be first made and got approval of Engineer/ Client before bulksupply. No. Of chairs shall be counted for payment.

368.00 Each

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-24

Page 26: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

10.09 Providing and laying integral cement based treatment for water proofing onhorizontal surface at all depth below ground level for under ground structuresas directed by Engineer-in-Charge and consisting of : i) Ist layer of 22mm to25mm thick approved and specified rough stone slab over a 25mm thick baseof cement mortar 1:3 (1 cement : 3 coarse sand) mixed with water proofingcompound conforming to IS:2645 in the recommended proportion over theleveling course (leveling course to be paid separately). Joints sealed andgrouted with cement slurry mixed with water proofing compound. ii) 2nd layerof 25mm thick cement mortar 1:3 (1 cement: 3 coarse sand) mixed with waterproofing compound in recommended proportions. iii) Finishing top with stoneaggregate of 10mm to 12mm nominal size spreading @ 8 cudm/sqmthoroughly embedded in the 2nd layer.

a) Using rough kota stone. 93.00 Sqm

10.10 Providing and laying integral cement based treatment for water proofing onthe vertical surface by fixing specified stone slab 22 mm to 25mm thick withcement slurry mixed with water proofing compound conforming to IS:2645 inrecommended proportions with a gap of 20mm (minimum) between stoneslabs and the receiving surfaces and filling the gaps with neat cement slurrymixed with water proofing compound and finishing the exterior of stone slabwith cement mortar 1:3 (1 cement : 3 coarse sand) 20mm thick with neatcement punning mixed with water proofing compound in recommendedproportion complete at all levels and as directed by Engineer-in-charge :

a) Using rough Kota stone 420.00 Sqm

10.11 Manufacturing, supplying and fixing retro reflective overhead signage boardsmade up of 2 mm thick aluminium sheet, face to be fully covered with highintensity and encapsulated lens type heat activated retro reflective sheetingconforming to type - III of ASTM-D-4956-01 as approved by Engineer-in-charge, letters, borders etc. as per IRC : 67-2001 in silver white with bluecolour back ground and with high intensity grade, pasted on substrate bypressure sensitive adhesive backing which shall be activated by applyingpressure conforming to class II ofASTM-D-4956-01 and fixing the same to theplate of structural frame work by means of suitable sized aluminium alloys,rivets or bolts & nuts @ 300 mm centre to centre all along the periphery aswell as in two vertical rows along with theft resistant measures, including thecost of painting with two or more coats of epoxy paint in grey colour on theback side of aluminium sheet including appropriate priming coat.

The rate includes the cost of rounding off the corners, lowering down thestructural frame work from the gantry, fixing and erecting the same in positionall complete as per drawings, specification and direction of the engineer-in-charge.(Structural frame work including M.S. plate to be provided separately.Rectangular area of the sheet only shall be measured for seperately.

a) Overhead informatory road signage 10.00 Sqm

10.12 Providing and applying 2.5 mm thick road marking strips (retro- reflective) ofspecified shade/ colour using hot thermoplastic material by fully/ semiautomatic thermoplastic paint applicator machine fitted with profile shoe, glassbeads dispenser, propane tank heater and profile shoe heater, driven byexperienced operator on road surface including cost of material, labour ,T&P,cleaning the road surface of all dirt, seals, oil, grease and foreign material etc.complete as per direction of Engineer-in-charge and accordance withapplicable specifications.

70.00 each

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-25

Page 27: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

10.13 Providing & fixing of external signages of varying sizes & shapes using GIsheet of atleast 19G, painting the entire board both surfaces with 1 coat ofprimer & 2 coats of synthetic enamel painting, lettering of approved type onboard of any sizes in English / Hindi or Local language complete as pertechnical specifications & directions of Engineer.

150.00 Sqft

10.14 Providing & Fixing Wall Mounted Nonlit Fire Exit 24" x 9" Internal sign ofapproved make & made of 10mm Acrylic with the required text matters stuckon it with plotted self adhesive vinyl & Mounted on 3mm Aluminium CompositPanel bracketed at suitable locations including necessary fittings & fasteningetc. complete & as directed by The Engineer in charge.

30.00 Nos

10.15 Providing & Fixing Wall Mounted Nonlit Utility 6" x 6" Internal sign of approvedmake & made of 10mm Acrylic with the required text matters stuck on it withplotted self adhesive vinyl & Mounted on 3mm Aluminium Composit Panelbracketed at suitable locations including necessary fittings & fastening etc.complete & as directed by The Engineer in charge.

50.00 Nos

10.16 Providing & Fixing Wall Mounted Nonlit Identification sign 18"x5" of approvedmake & made of 10mm Acrylic with the required text matters stuck on it withplotted self adhesive vinyl & Mounted on 3mm Aluminium Composit Panelbracketed at suitable locations including necessary fittings & fastening etc.complete & as directed by The Engineer in charge.

40.00 Nos

10.17 Providing & Fixing Wall Mounted Nonlit Fire Exit 24" x 9" Internal sign ofapproved make & made of 10mm Acrylic with the required text matters stuckon it with plotted self adhesive vinyl & Mounted on 3mm Aluminium CompositPanel bracketed at suitable locations including necessary fittings & fasteningetc. complete & as directed by The Engineer in charge.

30.00 Nos

10.18 Providing & Fixing Wall Mounted Nonlit directory sign 2' x 3' of approvedmake & made of 10mm Acrylic with the required text matters stuck on it withplotted self adhesive vinyl & Mounted on 3mm Aluminium Composit Panelbracketed at suitable locations including necessary fittings & fastening etc.complete & as directed by The Engineer in charge.

20.00 Nos

10.19 Providing & Fixing Wall Mounted Nonlit directory sign 3' x 4' of approvedmake & made of 10mm Acrylic with the required text matters stuck on it withplotted self adhesive vinyl & Mounted on 3mm Aluminium Composit Panelbracketed at suitable locations including necessary fittings & fastening etc.complete & as directed by The Engineer in charge.

20.00 Nos

10.20 Providing & Fixing Wall Mounted Nonlit directory sign 3' x 3.5' of approvedmake & made of 10mm Acrylic with the required text matters stuck on it withplotted self adhesive vinyl & Mounted on 3mm Aluminium Composit Panelbracketed at suitable locations including necessary fittings & fastening etc.complete & as directed by The Engineer in charge.

20.00 Nos

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-26

Page 28: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

10.21 Providing & Fixing Suspended Nonlit sign 48"x9" of approved make & madeof 1" Aluminium framing duly PU painted and 10mm Acrylic element mountedto it from either side with the required text matters stuck on it with plotted SelfAdhesive Vinyl bracketed at suitable locations, including necessary fittings &fastening etc. complete & as directed by The Engineer in charge.

20.00 Nos

10.22 Providing & Fixing Wall Mounted Nonlit directory sign 15' x 11' of approvedmake & made of 10mm Acrylic with the required text matters stuck on it withplotted self adhesive vinyl & Mounted on 3mm Aluminium Composit Panelbracketed at suitable locations including necessary fittings & fastening etc.complete & as directed by The Engineer in charge.

1.00 Nos

Total of sub-head

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-27

Page 29: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

11.00 Road work, Development

11.01 Preparation and consolidation of sub grade with power road roller of 8 to 12tonne capacity after excavating earth to an average of 22.5 cm. depth,dressing to camber and consolidating with road roller including making goodthe undulations etc. and re-rolling the sub grade and disposal of surplus earthlead upto 50 metres. 2500.00 Sqm

11.02 Construction of dry lean cement concrete sub base over a prepared sub-grade with coarse and fine aggregate conforming to IS:383, the size of coarse aggregate not exceeding 25 mm, aggregate cement ratio not to exceed 15:1,aggregate gradation after blending to be as per specifications, cementcontent not to be less than 150 Kg/cum, optimum moisture content to bedetermined during trial length construction, concrete strength not to be lessthan 10 Mpa at 7 days, mixed in a batching plant, transported to site, for allleads & lifts, laid with a mechanical paver, compacting with 8-10 tonnevibratory roller, finishing and curing etc. complete as per direction of Engineer-in- charge.

300.00 Cum

11.03 Providing and laying C.C. pavement of mix M25 with ready mixed concretefrom batching plant. The ready mixed concrete shall be laid and finished withscreed board vibrator, vacuum dewatering process and finally finished byfloating, brooming with wire brush etc. complete as per specifications anddirections of Engineer-in-charge. (The panel shuttering work shall be paid forseparately). 300.00 Cum

11.04 Providing and laying in position bitumen hot sealing compound for expansionjoints etc

a) Using grade 'A' sealing compound.

20000.00

Per cm depth per cm width per m length

11.05 Providing and laying 60mm thick factory made cement concrete interlockingpaver block of M -30 grade made by block making machine with strongvibratory compaction and of approved size and design/ shape laid in requiredcolour and pattern over and including 50mm thick compacted bed of finesand, filling the joints with fine sand etc. all complete as per the direction ofEngineer-in-charge. 500.00 sqm

11.06 Providing and laying at or near ground level factory made kerb stone of M-25

grade cement in position to the required line, level and curvature jointed with

cement mortar 1:3 (1 cement: 3 coarse sand) including making joints with or

without grooves (thickness of joints except at sharp curve shall not to more

than 5mm) including making drainage opening wherever required complete

etc. as per direction of Engineer-in-charge (length of finished kerb edging

shall be measured for payment). (Precast C.C. kerb stone shall be approved

by Engineer-in-charge). 80.00 Cum

11.07 Trenching in ordinary soil upto a depth of 60cm including removal andstacking of serviceable materials and then disposing of surplus soil byspreading and neatly leveling with in a lead of 50m and making up thetrenched area to proper levels by filling with earth or earth mixed with sludgeor/and manure before and after flooding trench with water (excluding cost ofimported earth, sludge or manure). 600.00 Cum

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-28

Page 30: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Total Qty Unit Rate in Figures (Rs.) Rate in Words (Rs.) Amount in Figures (Rs.)

1 2 3 4 5 6 7

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

11.08 Supplying and stacking sludge at site including royalty and carriage up to 1km (sludge measured in stacks will be reduced by 8% for payment).

100.00 Cum

11.09 Supplying and stacking at site dump manure from approved source, includingcarriage up to 1 km (manure measured in stacks will be reduced by 8% forpayment ).

a) Screened through sieve of I.S. designation 16 mm 100.00 Cum

11.10 Rough dressing the trenched ground including breaking clods & Uprootingweeds from the trenched area after 10 to 15 days of its flooding with waterincluding disposal of uprooted vegetation. 2000.00 Sqm

11.11 Fine dressing the ground 2000.00 Sqm

11.12 Spreading of sludge, dump manure or/and good earth in required thicknessincluding mixing earth and sludge or manure in the required proportionspecified or directed by the Officer in Charge (Cost of sludge, dump manureor/ and good earth to be paid separately). 100.00 Cum

11.13 Grassing with selection No.1 grass including watering and maintenance of thelawn for 30 days or more till the grass forms a thick lawn, free from weedsand fit for mowing including supplying good earth, if needed (the good earthshall be paid for separately).

a) With grass turf 2000.00 Sqm.

11.14 Digging holes in ordinary soil and refilling the same with the excavated earthmixed with manure or sludge in the ratio of 2:1 by volume (2 parts of stackedvolume of earth after reduction by 20% : 1part of stacked volume of manureafter reduction by 8%) flooding with water, dressing including removal ofrubbish and surplus earth, if any with all leads and lifts (cost of manure,sludge or extra good earth if needed to be paid for separately):

a) Holes 1.2 m dia and 1.2 m deep. 20.00 Eachb) Holes 60 cm dia, and 60 cm deep. 20.00 Each

Total of sub-head

HSCC/ NIMR Dwaraka Auditorium, Conference Hall, Hostel and VIP Guest House BOQ Page No.C-29

Page 31: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No DESCRIPTION OF WORK Amount (Rs.)1 EARTHWORK2 CONCRTE WORK3 RCC WORK4 WALLS AND PARTITIONS5 DOORS & WINDOWS6 STEEL WORK7 FLOORING8 CEILING & ROOFING9 FINISHING10 MISCELLANEOUS11 Road work, Development

TOTAL

Project Name: Construction of Auditorium, Conference Hall, Hostel, ESS, AC

Plant Room and VIP Guest House at NIMR Dwarka, New Delhi

ABSTRACT OF COST (CIVIL)

ABSTRACT 1

Page 32: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Note: Based on the tender drawing the agency has to prepare the

internal & external plumbing shop drawing and obtain the approval

of the same before execution

1.00 SANITARY FIXTURES

1.01 17.1 Providing&fixing water closet squatting pan( Indian W.C.Pan)with 100mm sand cast iron P or S strap,10 Litre low level white P.V.C flushingcistern with manually controled device(handle lever) conforming toIS:7231 with all fittings&fixture complete including cutting and makinggood the walls & floors whereever required.

a) 17.1.1 White vitreous china orissa pattern W.C. pan of size 580 x 440 mm withintegral type foot rests.

Each 1.0

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

1.02 17.3 Providing and fixing white vitreous china pedestal type water closet(European type) with seat and lid, 10 litre low level white vitreousflushing cistern and C.P. flush bend with fittings & C.I. brackets, 40mmflush bend, overflow arrangement with specials of standard make andmosquito proof coupling of approved municipal design completeincluding painting of fittings and brackets, cutting and making good thewalls and floors wherever required:

a) 17.3.2 W.C. pan with ISI black solid plastic seat & lid. Each 44.0

1.03 17.4 Providing and fixing white vitreous China flat back or wall corner typelipped front urinal basin of 430x260x350 mm and 340x410x265 mmsizes respectively with automatic flushing cistern with standard flush pipeand C.P. brass spreaders with brass unions and G.I. clamps complete,including painting or fittings and brackets, cutting and making good thewalls and floors wherever required.

a) 17.4.3 Range of three urinal basin with10 litre white PVC automatic flushingcistern.

Each 3.0

HSCC PHE- 1 NIMR-Dwarka

Page 33: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

1.04 17.7 Providing and fixing wash basin with C.I. brackets, 15mm C.P. brasspillar taps, 32mm C.P. brass waste of standard pattern, includingpainting of fittings and brackets, cutting and making good the wallswherever required:

a) 17.7.3 White vitreous china wash basin size 550x 400 mm with a pair of15mm C.P. brass pillar tap.

Each 50.0

1.05 17. 10 Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as perIS 13983 with C.I. brackets and stainless steel plug 40 mm includingpainting of fittings and brackets, cutting and making good the wallswherever required:

17.10.1 Kitchen sink with drain board

a) 17.10.1.3 510x1040 mm bowl depth 200mm. Each 4.0

1.06 17. 14 Extra for using coloured W.C. pan instead of white W.C pan

a) 17.14.1 Orissa pattern W.C. pan 580x440 mm Each 1.0

1.07 17. 16 Extra for using coloured pedestal type W.C. pan (European type) withlow level cistern of same colour instead of white vitreous china W.C. panand cistern

Each 43.0

1.08 17. 32 Providing and fixing superior glass (of approved quality) and of requiredshape and size with plastic moulded frame of approved make and shapewith 6 mm thick hard board backing.

a) 17.32.2 Rectangular shape 453x357 mm Each 47.0

1.09 17. 33 Providing and fixing 600x120x5 mm glass shelf with edges round ofsupported and anodised alominium angle frame with C.P. brass bracketsand guard rail complete fixed with 40 mm long screws, rawl plugs etc.,complete.

Each 47.0

1.10 17. 34 Providing and fixing toilet paper holder .

a) 17.34.2 Vitreous china Each 44.0

HSCC PHE- 2 NIMR-Dwarka

Page 34: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

1.11 17. 71 Providing and fixing PTMT liquid soap container 109 mm wide, 125 mmhigh and 112 mm distance from wall of standard shape with bracket ofthe same materials with snap fittings of approved quality and colourweighing not less than 105 gms.

Each 47.0

1.12 NS Providing and fixing health faucet with tube and hook chrome ofapproved make as approved by Engineer-in-charge.

Each 44.0

1.13 NS Providing and fixing soap dish holder with CP brass lid and bracketsfixed to wooden cleats with CP brass screws

Each 30.0

1.14 NS Providing and fixing CP brass towel rail size of 600x20 mm of approvedmake complete with CP brackets fixed to wooden cleats with CP brassscrews.

Each 47.0

1.15 NS Providing and fixing brass coat hook of approved quality and makecomplete with material of fixing

Each 60.0

1.16 NS Extra for providing and fixing white vitreous china oval shape wash basinin place of normal wash basin with CI/MS brackets painted white, 15 mmCP brass pillar taps, 32 mm CP brass waste of standard pattern,including painting of fittings and brackets cutting and making good thewalls wherever required

a) Counter top oval shape wash basin size 550x470 mm with centre taphole, single 15 mm CP brass swan neck type pillar tap

Each 50.0

1.17 NS Extra for providing and fixing white vitreous china wall hung type watercloset (European type) in place of normal pedestal type water closet withwhite solid plastic seat and lid concealed flushing cystern 9 ltrs capacity(min) approximate size(400x300x100)comprising of SS actuating panelwith dual flush with fittings ,specials of standardmake(Viega,ACO,Kohler,Jaquar) and complete including painting ,cutting and making good the walls and floors wherever required:

Each 26.0

1.18 NS Providing and fixing stainless steel grab bar 20mm dia of requiredlength with PVC cleats, C.P. brass screws etc. complete.

Each 2.0

SUB TOTAL( SANITARY FIXTURES)

HSCC PHE- 3 NIMR-Dwarka

Page 35: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

2.00 SOIL, WASTE AND VENT PIPES

2.01 17. 35 Providing and fixing soil, waste and vent pipes.

a) 17.35.1 100 mm dia.

a i) 17.35.1.2 Centrifugally cast (spun) iron socketed pipe as per IS:3989 Metre 930.0

2.02 17. 37 Providing and fixing M.S holder-bat clamps of approved design to SandCast iron/ cast iron (spun) pipe embedded in and including cementconcrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4graded stone aggregate 20mm nominal size) including cost of cuttingholes and making good the walls etc.

a) 17.37.1 for 100 mm dia. pipe Each 61.0

2.03 17. 38 Providing and fixing bend of required degree with access door, insertionrubber washer 3 mm thick, bolts and nuts complete.rubber washer 3 mm thick, bolts and nuts complete.

a) 17.38.1 100 mm

a ii) 17.38.1.2 Sand cast iron S&S as per IS-3989 Each 76.0

2.04 17. 39 Providing and fixing plain bend of required degree.

a) 17.39.1 100 mm

a ii) 17.39.1.2 Sand cast iron S&S as per IS:3989 Each 130.0

2.05 17. 40 Providing and fixing heel rest sanitary bend.

a) 17.40.1 100 mm dia

a.ii) 17.40.1.2 sand cast iron S&S as per IS-3989 Each 25.0

2.06 17. 43 Providing and fixing single equal plain junction of required degree withaccess door, insertion rubber washer 3mm thick, bolts and nutscomplete.

a) 17.43.1 100x100x100mm a.ii) 17.43.1.2 sand cast iron S&S as per IS-3989 Each 47.0

2.07 17. 44 Providing and fixing single equal plain junction of required degree

HSCC PHE- 4 NIMR-Dwarka

Page 36: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

a) 17.44.1 100x100x100mm

a.ii) 17.44.1.2 sand cast iron S&S as per IS-3989 Each 5.0

2.08 17. 55 Providing and fixing door piece, insertion rubber washer 3mm thick, boltsand nuts complete

a) 17.55.1 100 mm

a.ii) 17.55.1.2 sand cast iron S&S as per IS-3989 Each 10.0

2.09 17. 56 Providing and fixing terminal guard.

a) 17.56.1 100 mm Each 25.0

a.ii) 17.56.1.2 sand cast iron S&S as per IS-3989

2.10 17. 57 Providing and fixing collar

a) 17.57.1 100 mm

a.ii) 17.57.1.2 Sand cast iron S&S as per IS-3989 Each 60.0

2.11 17. 58 Providing lead caulked joints to sand cast iron /centrifugally cast (spun)iron pipes and fittings of diameter:

a) 17.58.1 100 mm Each 575.0b) 17.58.2 75 mm Each 245.0

2.12 NS Providing Drip seal joint of approved make for the sand castiron/centrifugaly cast iron pipes where the workability of lead joint can beeffected due to space constraints.

a) 100 mm Each 300.0

2.13 17. 59 Providing and fixing M.S. stays and clamps for sand cast iron /centrifugally cast (spun) iron pipes of diameter :

a) 17.59.1 100 mm Each 25.0

2.14 17. 60 Providing and fixing trap of self cleansing design with screwed downor hinged grating with or without vent arm complete, including cost ofcutting and making good the walls and floors:

a) 17.60.1 100 mm inlet and 100 mm outlet a i) 17.60.1.1 Sand cast iron S&S as per IS-3989 Each 68.0

HSCC PHE- 5 NIMR-Dwarka

Page 37: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

2.15 17. 61 Cutting chases in brick masonary walls for following diameter sand castiron/centrifugally cast (spun) iron pipes and making good the same withcement concrete 1:3:6 (1 cement:3 coarse sand:6 graded stoneaggregate 12.5 mm nominal size) including necessary plaster andpointing in cement mortar 1:4 (1 cement: 4 coarse sand):

a) 17.61.1 100 mm diameter pipe Metre 15.0

2.16 17. 65 Painting sand cast iron / centrifugally cast (spun) iron soil, waste ventpipes and fittings with paint of any colour such as chocolate, grey, orbuff etc. over a coat of primer (of approved quality) for new work:

a) 17.65.1 100 mm diameter pipe Metre 520.0

NS Providing and fixing floor drain points formed out of 65 mm dia GIelbow, including with 75mm dia Stainless Steel grating with frame,embedded in floor, all complete as directed.

Each 43.0

2.18 NS Providing and fixing C.P. brass bottle trap for wash basin including CPwaste fittings complete 32 mm dia complete in all respect of approvedquality.

Each 50.0

2.19 NS Providing and fixing C.P. brass bottle trap for urinals & sinks includingCP waste fittings complete 40 mm dia complete in all respect ofapproved quality.

Each 5.0

2.20 NS Providing and laying cement concrete 1:2:4 (1 cement:2 coarse sand:4graded stone aggregate 20 mm nominal size) 80 mm thick all-round theSCI/centrifugally S&S pipe diameter.

a) 100 mm dia Metre 300.0

2.21 NS Providing and fixing dash fastner made of rust proof plated steel forholding the soil/waste supply pipes complete in all respect

HSCC PHE- 6 NIMR-Dwarka

Page 38: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

a) Dash fastner for pipe more than 25 mm dia to 150 mm dia pipe of size25 mm dia and 75 mm long minimum & shall be capable of taking 6tonnes load and also include the supporting angles 35x35x5 mm/ ofrequired size or MS bars steel structures as per drawing.

Each 150.0

2.22 NS Providing and fixing floor clean out plug consist of CI bend & GI socketheavy class with Brass cap & key for opening male threaded cap etc.including lead caulked to CI pipescomplete in all respects as perdrawing/ sample approved by Engineer -in -ChargeFCO (floor clean outplug shall be flushed with floor finish

100 mm dia Each 10.0

2.23 NS Providing and fixing clean out plug consist of GI socket/nipple heavyclass with threaded pludge for opening male threaded cap etc. includingclass with threaded pludge for opening male threaded cap etc. includinglead caulked to CI pipescomplete in all respects as per drawing/ sampleapproved by Engineer -in -Charge

100 mm dia/150 mm dia Each 10.0

2.24 NS Providing and fixing G.I EXTENSION PIECE for 100 mm dia floor trapformed out of main pipe( Type A) with multiple side inlets, suitable forvarious dia pipes, side connections, including all fixtures and fittings asper site conditions and as per standard details and water tight sealing ofjoints and area surrounding the grating and as directed.

Each 68.0

2.25 18.10 Providing and fixing GI pipes complete with GI fittings and clamps, i/ccutting and making good the walls etc and making good the same forwaste water disposal complete as per direction of engineer incharge.

a) 18.10.4 32 mm dia nominal bore (Wash basin to floor trap/floor drain) Metre 50.0

b) 18.10.5 40 mm dia nominal bore (Sink,Urinal to floor trap) Metre 35.0

c) 18.10.6 50 mm dia nominal bore (Floor Drain to Floor Trap) Metre 35.0

HSCC PHE- 7 NIMR-Dwarka

Page 39: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

2.26 NS Providing & fixing SS floor trap grating 143x143x5mm thickscrewablewith SS fixed frame of 150x150 mm size as per approvedmake & model

Each 80.0

SUB TOTAL(SOIL, WASTE AND VENT PIPES)

HSCC PHE- 8 NIMR-Dwarka

Page 40: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

3.00 WATER SUPPLY

3.01 18.7 Providing and fixing Chlorinated Polyvenyl Chloride(CPVC)pipes havingthermal stability for hot & cold water supply including all CPVC plain&brass threaded fittings i/c fixing the pipe with clamps at 1.0 mspacing.This includes jointing of pipes &fittings with one step CPVCsolvent cement and the cost of cutting chases and making good thesame including testing of joints ciomplete as per direction of Engineer incharge.

Internal work – Exposed on wall

a) 18.7.1 15 mm nominal outer dia pipes (SDR-11) Metre 100.0

b) 18.7.2 20 mm nominal outer dia pipes (SDR-11) Metre 200.0

c) 18.7.3 25 mm nominal outer dia pipes (SDR-11) Metre 300.0

d) 18.7.4 32 mm nominal outer dia pipes (SDR-11) Metre 75.0

e) 18.7.5 40 mm nominal outer dia pipes (SDR-11) Metre 50.0

f) 18.7.5 50 mm nominal outer dia pipes (SDR-11) Metre 40.0

g) NS 62.5 mm nominal outer dia pipes (SDR-11) Metre 10.0

3.02 18. 8 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for hot & cold water supply including all CPVCplain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 mspacing. This includes jointing of pipes & fittings with one step CPVCsolvent cement and the cost of cutting chases and making good thesame including testing of joints complete as per direction of Engineer inCharge.

Concealed work including cutting chases and making good the

walls etc.

a) 18. 8.1 15 mm nominal outer dia pipes (SDR-11) Metre 350.0

b) 18.8.2 20 mm nominal outer dia pipes (SDR-11) Metre 355.0

c) 18. 8.3 25 mm nominal outer dia pipes (SDR-11) Metre 70.0

d) 18. 8.4 32 mm nominal outer dia pipes (SDR-11) Metre 15.0

HSCC PHE- 9 NIMR-Dwarka

Page 41: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

3.03 18. 9 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for hot & cold water supply including all CPVCplain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 mspacing. This includes jointing of pipes & fittings with one step CPVCsolvent cement and the cost of cutting chases and making good thesame including testing of joints complete as per direction of Engineer inCharge.

External Work

a) 18.9.3 25 mm nominal outer dia pipes (SDR-11) Metre 30.0b) 18.9.5 40 mm nominal outer dia pipes (SDR-11) Metre 20.0

3.04 18.10 Providing and fixing G.I. pipes complete with G.I. fittings and clamps,including cutting and making good the walls etc.

Internal Work- Exposed on walls

b) NS 80 mm dia nominal bore Metre 10.0c) NS 100 mm dia nominal bore Metre 10.0c) NS 100 mm dia nominal bore Metre 10.0

3.05 18. 13 Making connection of G.I. distribution branch with G.I. main of followingsizes by providing and fixing tee, including, cutting and threading thepipe etc. commplete including obtaining approval for connection fromDJB/Municipal corporation :

a) 18.13.2 50 to 80 mm nominal bore (SDR-11) Each 4.0

3.06 18. 17 providing and fixing gun metal gate valve with C.I. wheel of approvedquality (screwed end)

a) 18.17.1 25 mm nominal bore Each 28.0

b) 18.17.2 32 mm nominal bore Each 11.0

c) 18.17.3 40 mm nominal bore Each 4.0

d) 18.17.4 50 mm nominal bore Each 2.0

3.07 18. 18 Providing and fixing ball valve (brass) of approved quality, High or lowpressure with plastic floats complete

a) 18.18.2 20mm Each 9.0

3.08 18.20 Providing and fixing brass ferrule with C.I. mouth cover including boringand tapping the main

HSCC PHE- 10 NIMR-Dwarka

Page 42: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

a) 18.20.3 25 mm nominal bore Each 3.0

3.09 18. 21 Providing and fixing unplasticised PVC connection pipe with brassunions:

a) 18.21.2 45 cm lengtha i) 18.21.2.1 15 mm nominal bore Each 250.0

3.10 18. 22 Providing and fixing C.P. brass shower rose with 15 or 20 mm inlet

a) 18.22.2 150 mm diameter Each 27.0

3.11 18. 32 Constructing masonary chamber 30x30x50 cm, inside with 75 classdesignation brick work in cement mortar 1:4 (1 cement: 4 coarse sand)for stop cock, with C.I. surface box 100x100x75 mm (inside) with hingedcover fixed in cement concrete slab 1:2:4 mix (1 cement: 2 coarsesand:4 graded stone aggregate 20 mm nominal size) necessarysand:4 graded stone aggregate 20 mm nominal size) necessaryexcavation foundation concrete 1:5:10 (1 cenment:5 fine sand: 10graded stone aggregate 40 mm nominal size) and inside plastering withcement mortar 1:3 (1 cement :3 coarse sand) 12 mm thick finished witha floating coat of neat cement complete as per standard design

a) 18.32.1 With F.P.s bricks Each 6.0

3.12 18. 38 Painting CPVC/G.I. pipes and fittings with synthetic enamel white paintover a ready mixed priming coat, both of approved quality for new work

a) 18.38.1 15 mm nominal outer dia pipes Metre 75.0b) 18.38.2 20 mm nominal outer dia pipes Metre 175.0c) 18.38.3 25 mm nominal outer dia pipes Metre 255.0d) 18.38.4 32 mm nominal outer dia pipes Metre 255.0e) 18.38.5 40 mm nominal outer dia pipes Metre 125.0f) 18.38.6 50 mm nominal outer dia pipes Metre 30.0

3.13 18. 40 Painting G.I. /CPVC pipes and fittings with two coats of anti-corrosivebitumastic paint of approved quality.

a) 18.40.3 25 mm diameter pipe Metre 30.0

b) 18.40.5 40 mm diameter pipe Metre 20.0

3.14 18. 41 Providing and filling sand of grading zone V or coarser grade all-roundthe G.I./CPVC pipes in external work

a) 18.41.3 25 mm diameter pipe Metre 30.0

HSCC PHE- 11 NIMR-Dwarka

Page 43: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

b) 18.41.5 40 mm diameter pipe Metre 20.0

3.15 18. 48 Providing and placing on terrace (at all floor levels) polyethylene waterstorage tank ISI:12701 marked with cover and suitable lockingarrangement and making necessary holes for inlet, outlet and overflowpipes but without fittings and the base support for tank

a) Treated water Tank and Untreated water tank per litre 37000.0

3.16 18. 49 Providing and fixing C.P brass bib cock of approved quality. a) 18.49.1 15 mm nominal bore Each 50.0

3.17 18. 50 Providing and fixing C.P. brass long nose bib cock of approved qualityconforming to IS standards and weighing not less than 810 gms. (Marck, Jaquar, othello)

a) 18.50.1 15 mm nominal bore Each 70.0

3.18 18. 53 Providing and fixing C.P. brass angle valve for basin mixer andgeyser/cisterns points of approved quality conforming to IS:8931.

a) 18.53.1 15 mm nominal bore Each 250.0

3.19 18.52 Providing and fixing C.P. brass stop cock (concealed) of standard designand of approved make conforming to 18:8931.

a) 18.52.1 15mm nominal bore. Each 60.0

3.20 18. 60 Providing and fixing enclosed type water meter ( bulk type) conforming toIS : 2373 and tested by muncipal board complete with bolts,nuts rubber,insersions etc. ( the tail plases if required will be paid seperatly )

a) 18. 60. 1 80mm dia nominal bore Each 1.0

3.21 18. 62 Providing and fixing PTMT ball cock of approved quality, colour andmake complete with Epoxy coated aluminium rod with L.P./H.P.H.D.plastic ball.

a) 18.62.4 40 mm nominal bore, 206 mm long weighin not less than 690 gms Each 9.0

HSCC PHE- 12 NIMR-Dwarka

Page 44: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

b) 18.62.5 50 mm nominal bore, 242 mm long weighin not less than 1240 gms Each 8.0

3.22 18.76 Cutting holes upto 30x30 cm in walls including making good the same

a) 18.76.1 with F.P.S bricks Each 25.0

3.23 18. 77 Cutting holes up to 15x15 cm in R.C.C. floors and roofs for passing drainpipe etc. and repairing the hole after insertion of drain pipe etc. withcement concrete 1:2:4 (1 cement:2 coarse sand: 4 graded stoneaggregate 20 mm nominal size) including finishing complete so as tomake it leak proof

Each 15.0

3.24 NS Extra for providing wash basin mixer pillar tap in place of normal pillartap

Each 50.0tap

3.25 NS Extra for providing divertor type shower mixer with provision for shower &single tap in place of 2Nos. concealed stop cock & 2 Nos. CP long nosebib cock complete in all respect of approved make & model

Each 26.0

3.26 NS Providing & fixing full way lever operated forged brass ball valve ofbrass body with forged brass hard chrome plated steel ball tested to apressure not less than 10 Kg / sqcm with threaded / flanged jointscomplete with nuts, bolts, gaskets, washers etc.

a) 15 mm diameter Each 8.0b) 20 mm diameter Each 24.0

3.27 NS Providing and fixing mosquito proof coupling of approved Municipaldesign for scour and vent pipes for RCC overhead tanks complete in allrespects

a) 20 mm diameter Each 22.0b) 25 mm diameter Each 14.0c) 32 mm diameter Each 2.0d) 40 mm diameter Each 2.0

3.28 NS Providing and fixing C.P. brass Overhead (Rain Fall) shower (100mm)with arm and wall flange complete including cutting and making good thewalls wherever required.

Each 32.0

HSCC PHE- 13 NIMR-Dwarka

Page 45: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

3.29 NS Providing & fixing 9 mm thick thermal insulation tubing of elastomericflexible material on hot water supply/return pipes having hermeticblistered closed cell structure of expanded synthetic rubber over pipes/fitting as per manufacturer's specifications etc.complete.

a 15 mm to 25 mm diameter Meter 215.0

HSCC PHE- 14 NIMR-Dwarka

Page 46: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

3.30 NS Extra for providing and installing INFRA-RED controlled electricallyoperated (220V, AC mains) automatic flushing system of approved makeinstead of urinals with flushing cistern. The automatic flushing systemshall comprising of :

Light sensing device fixed in recessed metallic box with tamper resistantstainless steel outercase Solenoid valve housed in a recessed metallicbox with openable cover mounted at high level ( at desired height fromfinished floor level) complete with interconnecting control wiring inrecessed PVC conduit between solenoid valve and sensing unit,including cutting and making good the walls & floor complete and allnecessary fittings to make it operational as directed

Each 10.0

NS Providing & fixing solid state fully hygienic no touch hand drier ofapproved make rated for continuous repeat usage with solid state time

Each 10.0approved make rated for continuous repeat usage with solid state timedelay LSF protection, with independent ambient light level & seasonalcontrol temperatures including providing necessary C.I./M.S. bracketspainted with two or three coats of enamel paint of approved shade over acoat of primer, wiring cables from drier to plug, plug tops etc. completeincluding cutting and making good the walls wherever required.

3.32 NS Supplying, fixing, testing and commissioning of storage type waterheater (Geyser) etc. with outer body of ABS, 2 MM Thick Mild Steel innerTank with glass line coating,option of 1/2/3 KW electrically operatedsingle phase 230V, including Glass Lined Double HeatingElement,Digital Display, Multifunction Safety Device, ELCB, Anode RodSystem, and Brackets for fixing on wall with connecting Wire & plug etc.conforming to IS: 2082 and energy efficient star rated model.

a) 25 Litre Capacity Each 27.0b) 35 litre capacity Each 2.0

HSCC PHE- 15 NIMR-Dwarka

Page 47: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

3.33 NS Providing & fixing water storage cooler of approved make and brand withSS body Complete in respects-230V Single Phase

a) minimum flow rate of 20 ltrs. Per hour and storage capacity 40 ltrs. Each 6.0b) minimum flow rate of 40 ltrs. Per hour and storage capacity 80 ltrs. Each 2.0

3.34 NS Providing and fixing approved make & suitable model of R.O. plant 40ltrs. Per hour flow rate having capacity to treat the raw water having TDS1200 ppm and not less than 40%. The treated water should have TDSless than 100 ppm and hardness less than 50 ppm. The operatingvoltage to 230 volt AC +/- 10% alongwith required capacity pump andsolenoid valves, dry run protection of pump, automatic tank level control,inbuilt auto flush timer for periodic flushing of membranes, hydropneumatic tank, over voltage and over current protection with switchmode power supply system antiscaling dosing system complete in allrespects including installation and fittings with the following provisions:(IONIEXCHANGE/ KENT/AQUAPROCESS/Pantair )(IONIEXCHANGE/ KENT/AQUAPROCESS/Pantair )

a) 10 micron polypropylene sediment pre filter

b) 10 micron bacteriostatic activated carbon block on line micron filter with5 micron rating

c) 3 Nos. of reverse osmosis memberane with 0.0001 micron pore sizeenergy saving poly amide type

d) UV lamp of minimum capacity 40 LPM and minimum lamp wattage 9W Each 8.0

3.35 NS Supplying, installing, testing and commissioning vertical online/horizontal centrifugal pumping set with mechanical seal, C.I. Housing, C.I. volute and SS impeller & SS shaft connected to a TEFC induction motor of suitable HP for 415 volts, 3 phase, 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads, base plate wiring upto panel and equipment for water level controller to start and stop the pump automatically at predecided levels of the water in the tank with provision of protection for dry run etc. complete in all respect (The shop drawing or the pumps along with its characteristics curves, model and technical data etc. are to be submitted for approval before purchase of pump).

Domestic water pumps (Treated water transfer&Raw water Transfer

pump to terrace tank)

a) Capacity 50 lpm Head 45M Each 2.0

HSCC PHE- 16 NIMR-Dwarka

Page 48: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

Capacity 35 lpm Head 45M Each 2.0

b) Soft water transfer pump

capacity 105 lpm & Head 45m Each 2.0

SUB TOTAL(Water Supply)

HSCC PHE- 17 NIMR-Dwarka

Page 49: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

4.00 SEWARAGE & DRAINAGE

4.01 19. 1 Providing laying and jointing glazed stoneware pipes grade 'A' with stiffmixture of cement mortar in the pro-portion of 1:1 (1 cement : 1 finesand) including testing of joints etc. complete.

a) 19.1.1 100 mm diameter Metre 38.3

4.02 19. 2 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand :10 graded stone aggregate 40 mm nominal size) all-round S.W. pipesincluding bed concrete as per standard design:

a) 19.2.1 100 mm diameter S.W. pipe/RCC NP2 Metre 38.3

b) 19.2.2 150 mm diameter S.W. pipe/RCC NP2 Metre 275.0

c) 19.2.4 250 mm diameter S.W. pipe/RCC NP2 Metre 200.0

4.03 19. 3 Providing and laying cement concrete 1:5:10 (1 cement:5 coarsesand:10 graded stone aggregate 40 mm nominal size) up to haunches ofS.W. pipes including bed concrete as per standard design:

a) 19.3.2 150 mm diameter S.W.pipe Metre 100.0

b) 19.3.4 250 mm diameter s.W. pipe Metre 350.0

c) 19.3.5 300 mm diameter s.W. pipe Metre 550.0

4.04 19. 4 Providing and fixing square-mouth S.W. gully trap grade ‘A’' completewith C.I. grating, brick masonry chamber with water tight C.I. cover withframe of 300x300 mm size (inside) the weight of cover to be not lessthan 4.50 kg and frame to be not less than 2.70 kg as per standarddesign:.

a) 19.4.2 150x100mm size P type

a.i) 19.4.2.1 F.P.S. Bricks class designation 75 Each 29.0

4.05 19. 6 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipeswith collars jointed with stiff mixture of cement mortar in the proportion of1:2 (1 cement:2 fine sand) including testing of joints etc. complete

a) 19.6.2 150 mm dia R.C.c. pipe Metre 375.0

HSCC PHE- 18 NIMR-Dwarka

Page 50: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

b) 19.6.3 250 mm dia R.C.C. pipe Metre 350.0

c) 19.6.4 300 mm dia R.C.C. pipe Metre 750.0d) 19.6.5 450 mm dia R.C.C. pipe Metre 500.0e) 19.6.7 600 mm dia R.C.C. pipe Metre 100.0

Metre4.06 19. 7 Constructing brick masonry manhole in cement mortar 1:4 (1 cement : 4

coarse sand), R.C.C. top slab with 1:2:4 mix ( 1cement : 2 coarse sand :4graded stone aggregate 20 mm nominal size ), foundation concrete1:4:8 ( 1cement : 4 coarse sand : 8graded stone aggregate 40 mmnominal size ), inside plastering 12mm thick with cement mortar 1:3 (1cement : 3 coarse sand) finished with a floating coat of neat cement,and making necessary channels in cement concrete 1:2:4 (1 cement : 2coarse sand : 4 graded stone aggregate 20mm nominal size) finishedwith a floating coat of neat cement all complete as per standard design.

a) 19.7.1 Inside size 90x80 cm and 45 cm deep including C.I. cover with frame(light duty) 455x610 mm internal dimensions total weight of cover and(light duty) 455x610 mm internal dimensions total weight of cover andframe to be not less than 38 kg (weight of cover 23 kg and weight offrame 15 kg):

a i) 19.7.1.1 With F.P.S. bricks with class designation 75 Each 35.0

4.07 19. 8 Extra depth for manholesa) 19.8.1 Size 90 x 80 cm

a i) 19.8.1.1 With F.P.S. bricks class designation 75 Metre 7.5

4.08 19. 9 Constructing brick masonry circular type manhole 0.91m internal dia atbottom and 0.56m dia at top in cement mortar 1:4 (1 cement :4 coarsesand), in side cement plaster 12 mm thick with cement mortar 1:3 (1cement : 3 coarse sand) finished with a floating coat of neat cement,foundation concrete 1:3:6 mix (1 cement: 3 coarse sand: 6 graded stoneaggregate 40mm nominal size), and making necessary channel incement concrete 1:2:4 (1 cement: 2 coarse sand: 4 graded stoneaggregate 20mm nominal size) finished with a floating coat of neatcement all complete as per standard design:

a) 19.9.1 0.91 m deep with S.F.R.C. cover and frame (heavy duty, HD-20 gradedesignation) 560mm internal diameter conforming to I.S. 12592, totalweight of cover and frame to be not less than 182kg., fixed in cementconcrete 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate 20mm nominal size) including centering shuttering all complete.(Excavation, foot rests and 12mm thick cement plaster at the externalsurface shall be paid for separately) :

HSCC PHE- 19 NIMR-Dwarka

Page 51: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

a i) 19.9.1.1 With F.P.S. bricks class designation 75 Each 33.0

4.09 19. 10 Extra depth for circular type manhole 0.91m dia (at bottom) with beyond0.91m to 1.67 m

a) 19.10.1 With F.P.S. bricks class designation 75 Metre 17.0

4.10 19. 11 Constructing brick masonry circular manhole 1.22 m intenral dia atbottom and 0.56 m dia at top in cement mortar 1:4 ( 1 cement: 4 coarsesand) inside cement plaster 12 mm thick with cement mortar 1:3 (1cement : 3 coarse sand) finished with a floating coat of neat cementfoundation concrete 1:3:6 mix (1 cement :3 coarse sand : 6 graded stoneaggregate 40mm nominal size) and making necessary channel incement concrete 1:2:4 (1 cement :2 coarse sand : 4 graded stoneaggregate 20mm nominalsize) fineished with a floating coat of neatcement complete as per standard design.

a) 19.11.1 1.68 m deep with SFRC cover and frame(heavy duty HD-20 gradea) 19.11.1 1.68 m deep with SFRC cover and frame(heavy duty HD-20 gradedesignation) 560 mm internal diameter conforming to IS: 12592, totalweight of cover and frame to be not less than 182 kg. fixed in cementconcrete 1:2:4 (1 cement :2 coarse sand : 4 graded stone aggregate20mm nominalsize) including centering shuttering all complete.(Excavation, foot rests and 12 mm tick cement plaster at the externalsurface shall be paid for separately)

a.i) 19.11.1.1 With F.P.S. bricks with class designation 75 Each 33.0

4.11 19. 12 Extra depth for circular type manhole 1.22 m internal dia (at bottom) withbeyond 1.68 m to 2.29 m

a) 19.12.1 With F.P.S. bricks with class designation 75 Metre 7.0

4.12 19. 16 Providing and fixing orange colour safety foot rest of minimum 6 mmthick plastic encapsulated as per IS: 10910 on 12 mm dia steel barconforming to IS: 1786 having minimum cross section as 23 mm x 25mm and over all minimum length 263 mm and width as 165 mm withminimum 112 mm space between protruded legs having 2 mm tread ontop surface by ribbing or chequering besides necessary and adequateanchoring projections on tail length on 138 mm as per standarddrawing and suitable to with stand the bend test and chemical resistancetest as per specification mark to be visible even after fixing, includingfixing in manholes with 30x20x15 cm cement concrete block 1:3:6 ( 1cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominalsize) complete as per design.

Each 75.0

HSCC PHE- 20 NIMR-Dwarka

Page 52: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

4.13 19. 21 Making connection of drain or sewer line with existing manhole includingbreking into and making good the walls, floors with cement concrete1:2:4 mix (1 cement:2 coarse sand:4 graded stone aggregate 20 mmnominal size) cement plastered on both sides with cemnet mortar 1:3 (1cement:3 coarse sand) finished with a floating coat of neat cement andmaking necessary channels for the drain etc. complete (includingobtaining approval from DJB/Municipal corporation

a) 19.21.1 For pipes 100 to 230 mm dia Each 3.0

4.14 19. 22 Providing sand cast iron drop connection externally for 60 cm drop frombranch sewer line to main sewer manhole including inspection andcleaning eye with chain and lid sand cast Iron drop pipe and bendencased all-round with cement concrete 1 :5:1 0 (1 cenment:5 fine sand:10 graded stone aggregate 40 mm nominal size) with all centering andshuttering required, cutting holes in walls and making good with brickwork in cement mortar 1:4 (1 cement: 4 coarse sand) plastered withcement mortar 1:3 (1 cement: 3 coarse sand) on, inside of the manholewall lead caulked joints between sand cast iron pipes and fittings, stiffcement mortar 1:1 (1 cement: 1 fine sand) joints between sand cast irontee and S.W. pipe, making required channels complete as per standarddesign and specifications:

a) 19.22.2 150 mm dia. sand cast iron drop connection Each 3.0

4.15 19. 27 Constructing brick masonry road gully chamber 50x45x60 cm with bricksof class designation 75 in cement mortar 1:4 (1 cement:4 coarse sand)including 500x450 mm pre-cast R.C.C. horizontal grating with framecomplete as per standard design:

a) 19.27.1 With F.P.S. bricks Each 40.0

4.16 19. 34 Providing and fixing S.W.intercepting trap in manholes with stiff mixtureof cement mortar 1:1 (1 cement:1 fine sand) including testing of jointsetc. complete

a) 19.34.2 150 mm dia Each 3.0

HSCC PHE- 21 NIMR-Dwarka

Page 53: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

4.17 NS Constructing brick masonry open surface drain including factory madeperforated RCC cover with edge protected with MS plate of 3 mm thickwith bricks of class designation 75 in cement mortar 1:4 (1 cement : 4fine sand) including earth excavation, 10cm thick bed concrete 1:5:10 (1cement: 5 fine sand :10 graded stone aggregate 40mm nominal size)and 25mm thick cement concrete 1:2:4 (1 cement:2 coarse sand:4graded stone aggregate 12.5 mm nominal size) for filling hunchesincluding 12mm cement plaster 1:4 (1 cement:4 coarse sand) with afloating coat of neat cement inside the drain, its top and exposed sideincluding disposal of surplus earth complete as per standard design.

25cm drain 30cm average depth

a) With F.P.S bricks Metre 320.0

45cm drain 75cm average depth

b) With F.P.S bricks Metre 130.0b) With F.P.S bricks Metre 130.0

SUB TOTAL(SEWERAGE AND DRAINAGE)

HSCC PHE- 22 NIMR-Dwarka

Page 54: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

5.00 EARTH WORK

5. 01 2. 6 Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth,1.5 m in width aswell as 10 sqm on plan) including disposal of excavated earth, lead up to50 m and lift up to 1.5 m , disposed earth to be levelled and neatlydressed.

a) 2.6.1 All kinds of soil cum 105.0

5. 02 2. 10 Excavating trenches of required width for pipes, cables, etc includingexcavation for sockets, and dressing of sides, ramming of bottoms,depth up to 1.5 m including getting out the excavated soil, and thenreturning the soil as required, in layers not exceeding 20 cm in depthincluding consolidating each deposited layer by ramming, watering, etc.and disposing of surplus excavated soil as directed, within a lead of 50m:m:

a) 2.10.1 All kinds of soila.ii) 2.10.1.2 Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia metre 1170.0

5. 03 2. 25 Filling available excavated earth (excluding rock) in trenches, plinth,sides of foundations etc. in layers not exceeding 20 cm in depth,consolidating each deposited layer by ramming and watering, lead up to50 m and lift up to 1.5 m

cum 37.0

SUB TOTAL(EARTH WORK)

HSCC PHE- 23 NIMR-Dwarka

Page 55: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

6.00 EXTERNAL WATER SUPPLY

6. 01 18. 17 Providing and fixing gun metal gate valve with CI wheel of approvequality ( screwed end )

a) 18. 17.6 80 mm dia nominal bore each 4.00

6.02 18. 19 Providing and fixing gun metal non-return valve of approved quality(screwed end)

a) 18.19.5 65 mm nominal bore

a.i) 18.19.5.1 Horizontal each 2.00

b) 18.19.6 80 mm nominal bore

b.i) 18.19.6.1 Horizontal each 6.00

6.03 18. 31 Providing and fixing C.I. sluice valves (with cap) complete with bolts,nuts, rubber insertions etc. (the tail pieces if required will be paidseparately):separately):

a) 18.31.1 100 mm diameter

a.i) 18.31.1.1 Class I each 6.00

6.04 18. 33 Constructing masonary chamber 60x60x75 cm, inside with 75 classdesignation brick work in cement mortar 1:4 (1 cement: 4 coarse sand)for sluice valve, with C.I. surface box 100mm top diameter, 160 mmbottom diameter and 180 mm deep (inside) with chained lid and RCCtop slab 1:2:4 mix (1 cement: 2 coarse sand:4 graded stone aggregate20 mm nominal size) necessary excavation foundation concrete 1:5:10(1 cenment:5 fine sand: 10 graded stone aggregate 40 mm nominalsize) and inside plastering with cement mortar 1:3 (1 cement :3 coarsesand) 12 mm thick finished with a floating coat of neat cement completeas per standard design

a) 18.33.1 With F.P.S. bricks each 7.00

HSCC PHE- 24 NIMR-Dwarka

Page 56: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

6.05 18. 34 Constructing masonary chamber90x90x100 cm, inside with 75 classdesignation brick work in cement mortar 1:4 (1 cement: 4 coarse sand)for sluice valve, with C.I. surface box 100mm top diameter, 160 mmbottom diameter and 180 mm deep (inside) with chained lid and RCCtop slab 1:2:4 mix (1 cement: 2 coarse sand:4 graded stone aggregate20 mm nominal size) necessary excavation foundation concrete 1:5:10(1 cenment:5 fine sand: 10 graded stone aggregate 40 mm nominalsize) and inside plastering with cement mortar 1:3 (1 cement :3 coarsesand) 12 mm thick finished with a floating coat of neat cement completeas per standard design

a) 18.34.1 With F.P.S.bricks each 2.00

6.06 18. 59 Providing and fixing C.I. double acting air valve of approved quality withbolts, nuts, rubber insertions etc. complete (The tail pieces, tapers etc. ifrequired will be paid separately):required will be paid separately):

a) 18.59.1 50 mm dia each 4.00

b) 18.59.2 80 mm dia each 2.00

6.07 18. 68 Providing and laying D.I. specials of class k-12 suitable for push-onjointing as per IS:9523

a) 18.68.1 Upto 600 mm dia quintal 25.00

6.08 18. 70 Providing push-on-joints to Centrifugally (Spun) Cast Iron pipes orDuctile Iron Pipes including testing of joints and including the cost ofrubber gasket

a) 18.70.1 100mm dia pipes joint 195.00

b) 18.70.2 150 mm dia pipes joint 20.00

c) 18.70.3 200 mm dia pipes joint

d) 18.70.4 250 mm dia pipes joint

6.09 18. 72 Providing and laying S&S Centrifugally Cast (Spun)/Ductile Iron pipesconfirming to is:8329:

a) 18.72.1 100 mm dia Ductile Iron Class k-7 pipes metre 450.00

b) 18.72.2 150 mm dia Ductile Iron Class k-7 pipes 40.00

c) 18.72.3 200 mm dia Ductile Iron Class k-7 pipes

d) 18.72.4 250 mm dia Ductile Iron Class k-7 pipes

HSCC PHE- 25 NIMR-Dwarka

Page 57: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

6.10 18. 80 Disinfecting C.I./D.I. water mains by flushing with water containingbleaching powder at 0.5 gms per litre of water and cleaning the samewith freash water, operation to be reaeated three times including gettingthe sample of water from the disinfected main tested in the municipallaboratory

a) 18.80.2 100 mm diameter C.I./D.I. pipe metre 4.50

18.80.4 150 mm diameter C.I./D.I. pipe metre 0.50

6.11 NS Providing and fixing puddle flanged including 40 cm long GI pipe piecewelded/threaded with MS plates 450x450x6 mm thick with both endscrewed/flanged.

a) For 80 mm dia pipe Each 2.00

b) For 100 mm dia pipe Each 4.00

c) For 150 mm dia pipe Each 2.00

6.12 NS Providing and fixing double seal type D.I. Manhole cover of 560 mm Each 6.006.12 NS Providing and fixing double seal type D.I. Manhole cover of 560 mmclear internal diameter of over all heavy duty with locking arrangementcomplete in all respects.

Each 6.00

6.13 NS Providing and fixing gun metal foot valve with stainer of approvedquality/model complete in all respect

a) 80 mm dia each 4.00

b) 100 mm dia each 2.00

SUBTOTAL (EXTERNAL WATER SUPPLY)

HSCC PHE- 26 NIMR-Dwarka

Page 58: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

7.00 RAIN WATER PIPING

7.01 12. 44 Providing and fixing to the inlet mouth of rain water pipe cast iron grating15 cm diameter and weighing not less than 440 grams

Each 43.0

7.02 Providing and fixing rain water ,soil, waste and vent pipes.

a) 100 mm dia.

a i) 17.35.1.2 Centrifugally cast (spun) iron socketed pipe as per IS:3989 Metre 311.0

c) NS 150 mm dia pipe as per IS:3989 Metre 114.0

7.03 17. 37 Providing and fixing M.S holder-bat clamps of approved design to SandCast iron/ cast iron (spun) pipe embedded in and including cementconcrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4graded stone aggregate 20mm nominal size) including cost of cuttingholes and making good the walls etc.holes and making good the walls etc.

a) 17.37.1 for 100 mm dia. pipe Each 79.0

c) NS for 150 mm dia pipe Each 39.0

7.04 17.39 Providing and fixing plain bend of required degree.

a) 100 mm

a ii) 17.39.1.2 Sand cast iron S&S as per IS:3989 Each 36.0

c) NS 150 mm Each 7.0

7.05 17.40 Providing and fixing heel rest sanitary bend.

a) 17.40.1 100 mm dia

a.ii) 17.40.1.2 sand cast iron S&S as per IS-3989 Each 36.0

c) NS 150 mm dia Each 7.0

7.06 17.57 Providing and fixing collar

a) 17.57.1 100 mm

a.ii) 17.57.1.2 Sand cast iron S&S as per IS-3989 Each 74.0

c) NS 150 mm Each 39.0

7.07 17.58 Providing lead caulked joints to sand cast iron /centrifugally cast (spun)iron pipes and fittings of diameter:

a) 17.58.1 100 mm Each 192.0

c) NS 150 mm Each 48.0

HSCC PHE- 27 NIMR-Dwarka

Page 59: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

7.08 17. 65 Painting sand cast iron / centrifugally cast (spun) iron soil, waste ventpipes and fittings with paint of any colour such as chocolate, grey, orbuff etc. over a coat of primer (of approved quality) for new work:

a) 17.65.1 100 mm diameter pipe Metre 311.0c) NS 150 mm diameter pipe Metre 114.0

SUB TOTAL(Rain Water pipe & fitting)

HSCC PHE- 28 NIMR-Dwarka

Page 60: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

8.00 BOREWELL(2 No)

8.01 NS Drilling by suitable rig as per IS : 2800-1979 (percussion or combinationrig ) or Reverse Rotary to suit site condition from ground level in all kindof soils and weathered rock including boulders (excluding rock )diameter of bore 450mm including carry out hydrological survey reportbefore boring & getting the approval based on Hydrogeological surveybefore start of the work.Also getting approval from local authority if anyrequired

a) 0-30m metre 30.0b) 30-60m metre 30.0c) 60-90m metre 30.0d) 90-120 m metre 30.0

8.02 NS Extra additional for drilling in Ordinary Rock if any found metre 25.0

8.03 NS Extra additional for drilling in Hard Rock if any found metre 25.0

8.04 NS Providing and lowering uPVC casing/housing pipe 200mm dia. with wall thickness 10 mm conforming to IS :12818 including sockets of standarddesign.

metre 240.0

8.05 NS Providing & fixing uPVC screen/slotted pipe with 1.5 mm to 3mm (slotsas per strata condition) including sockets of standard design as per IS:12818/1992.

a) 200 mm dia uPVC socketed pipe with wall thickness 10.0 mm metre 80.0

8.06 NS Providing and fixing in position threaded iron cap with lockingarrangement of approved design to prevent foreign matters getting intothe bore-hole as required.

Each 1.0

8.07 NS Providing and laying rounded pea gravel washed & served 3 to 6mm nominal boreas per relevant ISI code.

Cum 16.0

8.08 NS Providing and laying cement concrete 1:2:4 mix for sanitary sealing ofwell at top.

Cum 1.0

8.09 NS Supplying, lowering and fixing in position reducer ,PVC bail plug with"U" hooks as per IS:2800-1964.

Each 1.0

HSCC PHE- 29 NIMR-Dwarka

Page 61: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

8.10 NS Development of Tubewell including testing of yield depression & qualityof water (for all parameters of potable water), contractor to obtaincertificate for quality for water from Competent Authority approved byclient or Engineer- In -Charge.

i)a) Development of Tube well by high capacity air compressor till the clear

water discharge but not more than 100 hours.per hour 80.0

b) Additional development of Tube well by high an over pumping unit tillcomplete development of tube well does not clear by maximum 100hours air compressor

per hour 50.0

8.11 NS Tranportation, mobilisation and demobilisation or drilling equipment andancillary equipment to site including clearing and cleaning the site aftercompletion of work.

set 1.0

8.12 NS Providing and fixing brass full way valve with C.I. wheel of approved8.12 NS Providing and fixing brass full way valve with C.I. wheel of approvedmake, tested to a pressure of 21 kg/sqcm.

a) 100 mm dia Each 1.08.13 NS Providing and fixing gunmetal non return valve of approved make tested

to a pressure of 21kg/sqcm.a) 100 mm dia Each 1.0

8.14 NS Providing & fixing G.I. pipes (heavy class)confirming to IS with specialfittings in external works including earthwork ,excavationin all kinds ofsoil including ordinary rock,refilling, painting pipes & fitting complete inalll respects.

a) 100 mm dia Metre 100.0

8.15 NS Providing & filling sand of grading zone V or coarser grade all around GIpipe in external work

. a) 100 mm dia Metre 100.0

8.16 NS Submersible pumps

HSCC PHE- 30 NIMR-Dwarka

Page 62: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

Providing and installing submersible pump and electrical panel suitablefor 8" dia casing of bore with SS impeller, high tensile SS shaft, copperwound squirrel cage wet type induction motor 2880 rpm, 415 V, 50 Hz,3phase A.C. supply, conforming to ISS: 8034-1976, capacity 500 litre perminute at 70-120 m head/ or suitable as per the hydrological surveyreport along with a directly coupled submersible type squirrel cage

electric induction 5 H.P(minimum). motor suitable for operation on 400V, 3 phase, 50 c.p.s. A.C. supply, water lubricated bearings and providedwith pivoted segment type thrust bearings to withstand non-vertical leadwith minimum wear and tear and duly fitted with device to take up theexpansion of water with heating of motor, including supply, testing andcommissioning of elctrical panel from the same manufacturer, completewith all accessories in all respects. The contractor to obtain approval formodel and make of pumpset & suitable Electrical panel after havingyield report of fully developed tube well and submite actual bore stratachart.

including supplying laying and fixing water proof PVC insulated flatsubmersible cable 3x10 sqmm with end termination with its accessories.complete in all respect as required.

set 10.0

8.17 Carrying out Electrical logging of Borewell before lowering of pipe foranalysiing of water quality including Electrical logging report, calculationetc.

Job 1.0

SUBTOTAL (BOREWELL)

HSCC PHE- 31 NIMR-Dwarka

Page 63: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

9.00 RAIN WATER HARVESTING(5 NOS.)

9.01 NS Designing and Constructing of percolation pit cum perforated well3000mm. dia upto 4000mm deep, 230 mm thick brick masonry workalround upto 1.5 m deep with 75 class brick in cement mortar 1:4, 200mm foundation concrete in 1:4:8 mix below brick work only, 150 mmthick precast removable RCC top slab with required steel reinforcementin cement concrete 1:2:4 mix, filled with coarse aggregate, SFRCcovers, river pebbles of requisite size stone as shown in the drawingincluding centering and shuttering, as shown complete as per detaileddrawings complete.

Each 5.0

9.02 NS Drilling as per IS : 2800-1964 ( with percussion or combination rig ) fromground level in all kind of soils including boulders (excluding rock )diameter of bore 450mm.diameter of bore 450mm.

a) 0-50m Metre 100.0

9.03 NS Extra for drilling in Ordinary Rock Metre 20.0

9.04 NS Extra for drilling in Hard Rock Metre 20.0

9.05 NS Providing and lowering of 200 mm dia uPVC blank/ slotted pipe withribs, special fittings, jointing conforming to IS 12818 - 1992.

Metre 100.0

HSCC PHE- 32 NIMR-Dwarka

Page 64: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

9.06 NS Constructing bar screen / settling tank, of sizes 4500x2500 with suitabledepth up to 2.0 m in 1: 4 Cement Mortar (one cement : 4 coarse sand)height as per site requirement, in brick masonry 350mm thick walls uptowater level and 230mm thick walls above water level & upto groundlevel, including all excavation, 20 cm thick bed concrete in 1:4:8 (onecement 4 fine sand 8 stone aggregate 40 mm), cement plaster 1:3 (onecement :3 coarse sand) with a floating coat of neat cement as insidefinish , top slab in RCC 1:2:4, including centring, shuttering and steelwork, also providing and fixing D.I. manhole cover & frame of size605mm x 450mm of weight not less than 38 kg (frame + cover) and costof 100mm dia C.I. vent pipe with C.I. Ventilating Cowl and suitable wiremesh provision for inlet, 115mm baffle walls extending 2/3 the widthspaced@500mm c/c including finishing with 1:3 cement plaster 15mmthick with floating coat of neat cement slurry , all complete in everyrespect as per drawing and as directed to suit site condition.

Each 5.0

SUBTOTAL (RAIN WATER HARVESTING)

HSCC PHE- 33 NIMR-Dwarka

Page 65: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

10.00 NS WATER SUPPLY PUMP PANEL

10.01 Supply, installation, testing and commissioning of following M.V.

cubicle type totally enclosed, powder coated, Free standing type, dust,

damp and vermin proof, indoor type Distribution Board/Panel

complete with busbars, M.V. danger notice plate, interconnections with

suitable capacity aluminium leads/solid aluminium strips/rods,

connection of incoming and outgoing cables with thimbles, and having

following incoming and outgoing switchgears complete as technical

specification & as required.

Note :

All MCCBs shall have Ics=Icu =100%

ii

INCOMER :

125 Amp 415 volts, 35 KA (Ics=Icu), FP MCCB Thermal magnetic release

based, with variable current settings.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB

"ON" ,"OFF" and "TRIP" LED indicating lamp and 6A control SP MCBs

Extended rotary operating mechanism with door interlock with defeat

feature and padlock facility. MCCB should have spreader links & phase

barriers.

1 no. Digital voltmeter with selector switch

1 no Digital ammeter with selector switch with one set of suitable C.T. s

BUSBARS :

300 Amp TPN busbars of aluminium

OUTGOINGS :

HSCC PHE- 34 NIMR-Dwarka

Page 66: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

i6 Sets of following (treated water transfer pump to terrace tank,Raw

water transfer pump, Filter feed pump for WTP)

32 Amp. 415 volts, 35 KA (Ics=Icu), TPN MCCB, with Thermal magnetic

release having variable current settings. .

Extended rotary operating mechanism with door interlock with defeat

feature and padlock facility. MCCB should have spreader links & phase

barriers.

1No. 3 Phase, DOL starter of 1 HP with thermal overload relay with

inbuilt single phase preventor , contactor, Push Buttons and Switches

etc complete as required.

LED indicating Lamps for "ON" , "OFF" & "TRIP".

ii 2 Sets of following (Softener feed pump)

ii 2 Sets of following (Softener feed pump)

32 Amp. 415 volts, 35 KA (Ics=Icu), TPN MCCB, with Thermal magnetic

release having variable current settings. .

Extended rotary operating mechanism with door interlock with defeat

feature and padlock facility. MCCB should have spreader links & phase

barriers.

1No. 3 Phase, DOL starter of 2 HP with thermal overload relay with

inbuilt single phase preventor , contactor, Push Buttons and Switches

etc complete as required.

LED indicating Lamps for "ON" , "OFF" & "TRIP".

iii 2 Sets of following (Soft water transfer pump)

32 Amp. 415 volts, 35 KA (Ics=Icu), TPN MCCB, with Thermal magnetic

release having variable current settings. .

Extended rotary operating mechanism with door interlock with defeat

feature and padlock facility. MCCB should have spreader links & phase

barriers.1No. 3 Phase, DOL starter of 2.5 HP with thermal overload relay with

inbuilt single phase preventor , contactor, Push Buttons and Switches

etc complete as required. LED indicating Lamps for "ON" , "OFF" & "TRIP".

iv 2 Sets of following (Tube Well Pump 10 HP)

HSCC PHE- 35 NIMR-Dwarka

Page 67: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl. No. DSR-2014

No.

Description of Item Unit Total Qty. Rate In Figure

(Rs)

Rate In Words(Rs.) Rate In Amount

(Rs.)

1 2 3 4 5 6 7 8

Name of Work: BOQ of Plumbing work of proposed buildings at NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank etc )

32 Amp. 415 volts, 35 KA (Ics=Icu), TPN MCCB, with Thermal magnetic

release having variable current settings. .

Extended rotary operating mechanism with door interlock with defeat

feature and padlock facility. MCCB should have spreader links & phase

barriers.

Digital ammeter with selector switch with one set of suitable CT,s.

LED indicating Lamps for "ON" , "OFF" & "TRIP".

v 2 Sets of following (Spare)

32 Amp. 415 volts, 35 KA (Ics=Icu), TPN MCCB, with Thermal magnetic

release having variable current settings. .

Extended rotary operating mechanism with door interlock with defeat

feature and padlock facility. MCCB should have spreader links & phase

barriers.

LED indicating Lamps for "ON" , "OFF" & "TRIP".LED indicating Lamps for "ON" , "OFF" & "TRIP".

WATER SUPPLY PUMP PANEL in pump room as above Set 1.00

1.01 Starter for Tubewell

3 Phase, fully automatic star Delta starter of 10HP with thermal

overload relay with inbuilt/separate single phase preventer , contactor,

Timer, Push Buttons and Auto-manual selector switch etc including its

mounting on the wall and control cables for starting of the motor

complete as required.each

2.00

Subtotal(Water supply Pump Panel)

HSCC PHE- 36 NIMR-Dwarka

Page 68: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. DESCRIPTION Rate in Figure (Rs.)

A INTERNAL PLUMBING , 1. 00 SANITARY FIXTURES2. 00 SOIL, WASTE AND VENT PIPES3. 00 WATER SUPPLY 4. 00 SEWERAGE AND DRAINAGE5. 00 EARTH WORK

B EXTERNAL PLUMBING ,6.00 EXTERNAL WATER SUPPLY7.00 RAIN WATER PIPING

8.00 BOREWELL

9.00 RAIN WATER HARVESTING

10.00 WATER SUPPLY ELECTRICAL PANEL TOTAL

ABSTRACT

Name of Work: BOQ of Plumbing work of proposed buildings at

NIMR,Dwarka(Hostel,Auditorium,VIP Guest house, A/c plant room, UG Tank

etc )

Page 69: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Unit Total Qty. Rate In Figures

(Rs).

Rate In Words (Rs). Amount In Figures (Rs).

1 2 3 4.00

1.00 FIRE FIGHTING SYSTEM

1. 01 Providing and laying S&S Centrifugally Cast (Spun) / Ductile Iron Pipes conforming

to IS : 8329 :

1.01.1 150 mm dia Ductile Iron Double Flanged Metre 425.0

1.02 Providing and laying D.I. specials of class K-12 suitable for push-on jointing as per IS

: 9523

1.02.1 Upto 600 mm dia quintal 19.0

1.03 Providing push-on-joints to Centrifugally (Spun) Cast Iron Pipes or Ductile Iron Pipes

including testing of joints and including the cost of

rubber gasket :

1.03.1 150 mm dia pipes joints 183.0

Project Name construction of Audiorium, Conference Hall, Hostel ,ESS AC Plant Room and VIP Guest House,UG Tank at NIMR Dwarika New Delhi Sector -08 New Delhi

Name of Works: Estimate of Fire Fighting Works

1.04 Excavating trenches of required width for pipes, cables etc including excavation for

sockets, and dressing of sides, ramming of bottoms, depth upto 1.5m including

getting out the excavated soil, and then returning the soil as required, inlayers not

exceeding 20 cm in depth including consolidating each deposited layer by ramming,

watering, etc. and disposing of surplus excavated soil as directed within a lead of 50

m

1.04.1 Pipes, cables etc exceeding 80 mm dia but not excedding 300 mm dia Metre 425.0

1.05 Providing, fixing joiting and testing of Heavy (class -C) G.I. pipes as per relevant IS

:1239/4736 with special accessories like tees, elbow, gesket, flanges, flanged joints,

rubber insertion nuts and bolts including earth work excavatin and trenching,

wrapping pipekot 4mm thick 500mm width tar based plymaric corrosion protection

tape or equivalent suitable to GI/ MS pipe line including applying uniform coat of cold

pipekot primer complete 1 m below the ground level, refillling in layers not exeeding

20 cm in depth consolidated each deposited layer by ramming & watering complete

in all respect as pe IS : 1022 (Under ground )

a) 150 mm dia G.I. Pipe with flange joints (5.4 mm wall thickness) Metre 30.0

b) 80 mm dia G.I. Pipe with flange joints Metre 25.0

1.06 Heavy class G.I. pipes conforming to IS with accessories like tees, elbows, flanged

joints, rubber insertion, nuts, bolts or welded joints including fixing the pipe with

suitable flat iron strip clamps/brackets, structural members, dash fastener , cutting

hole and chases in walls, floor, R.C.C. slab etc. and making good the same,

including painting pipes and fittings with a primer coat of steel primer and two coats

of postal red enamel paint etc. complete as required. (All the fitting i.e. tee /elbow,

Valve shall be joint the pumps will flanged joints)

a) 150 mm dia (with Flanged joints) Metre 50.0

b) 100 mm dia (with Flanged joints) Metre 145.0

c) 80 mm dia Metre 20.0

NIMR-Dwarka 11 Estimate-Fire Fighting

Page 70: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Unit Total Qty. Rate In Figures

(Rs).

Rate In Words (Rs). Amount In Figures (Rs).

d) 65 mm dia Metre 5.0

e) 50 mm dia Metre 10.0

f) 40 mm dia Metre 45.0

g) 32 mm dia Metre 50.0

h) 25 mm dia Metre 135.0

1.07 Providing and fixing Single headed hydrants flanged inlet with 63 mm female

instantaneous outlet of gunmetal complete with male blank caps, chains conforming

to IS:5290 type A with stainless steel orifice plate (if required) to keep the pressure

not more than 3.5 kg/sq.cm at any point. Each 28.0

1.08 Providing 63mm dia 15 m long reinforced rubber lined hose pipe conforming to IS:

636-1992 Part-II with gunmetal male & female coupling wire wound with pipe as

required. Each 18.0

1.09 Providing and fixing 63mm dia 15 m long canvas hose pipe complete with gunmetal

male & female coupling wire wound with the pipe The pipe shall confirm to IS: 4927. Each 38.0

1. 10 Providing and fixing Gunmetal branch pipe with 20mm dia nozzle conforming to

IS:903. suitable for installation connections to hose coupling etc. as required. Each 28.0

1.11 Providing and fixing Four way fire brigade connection housed in steel cabinet of size

900mm x 750mm x 400mm fabricated from 1.5mm thick M.S. sheet having lockable

arrangement, openable glazed door with 4mm thick glass, including painting a coat

of steel primer and two coats of postal red enamel paint, with necessary supports for

the cabinet etc. with 150 mm dia. non return and butterfly valves complete in all

respects.

a) 4 Way - 150mm dia Each 3.0

1.12 Providing and fixing Set of "Siamese" quadraplet instantaneous fire brigade

connections comprising of two gunmetal instantaneous male inlet coupling 63mm

dia with plug and cap, chain bends, tees etc for inlet to the static tank. Each 3.0

1.13 Providing & Fixing 150 mm dia, 4 way suction coupling for firebrigade withdrawal of

water from the fire tank Each 3.0

1.14 Providing and fixing glazed door shutter and frame for Fire hose cabinet with hold

fasts ( frame fabricated from 40 x 40 x 5mm and shutter from angle) 2100 mm high x

1200 mm wide x 600mm deep with locking arrangement, 4mm thick glass with M.S.

flats including all accessories, painting with one coat of steel primer and two coats of

postal red enamel paint complete as per drawing and as directed. The words “ hose

cabinet” to be painted on the box complete in all respects.Each 9.0

1.15 Providing and fixing Weather proof standard stand post type hose cabinet (900mm x

750 mm x 400 mm) out door type made of 1.5mm thick M.S. sheet having central

opening glazed door with 4mm thick glass suitable for accommodating hydrants, 2

Nos. canvas hose pipe and branch pipe including necessary locking arrangements,

painting one coat of primer and two coats of postal red enamel paint.. The shutters

are to be lockable type. The words “ hose cabinet” to be painted on the box.Each 19.0

NIMR-Dwarka 11 Estimate-Fire Fighting

Page 71: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Unit Total Qty. Rate In Figures

(Rs).

Rate In Words (Rs). Amount In Figures (Rs).

1.16 Providing and fixing cast iron body IS: 210 FG 220 and double flange gear simple

operation type butterfly valve conforming to IS: 13095 with SS304 disc and shaft

NITNLE rubber replaceable seat of the following size complete with bolts, nuts,

washers and rubber insertions as per specification.a) 150 mm dia Each 15.0

b) 80 mm dia Each 2.0

c) 50 mm dia Each 3.0

1.17 Supplying, testing, installation & commissioning of pressure switches for pumps

including necessary wiring upto the control panel. Each 19.0

1.18 Constructing masonry chamber 90x90x100 cm, inside with 75 class designation

brick work in cement mortar 1:4 (1 cement: 4 fine sand) for sluice valve, with C.I.

surface box 100mm top diameter, 160mm bottom diameter and 180mm deep

(inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4

graded stone aggregate 20 mm nominal size) necessary excavation foundation

concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal

size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12

mm thick finished with a floating coat of neat cement complete as per standard

design.with F.P.S. bricks Each 4.0

1.19 Supplying and Fixing First Aid Hose Reel, wall mounting swinging type complete1.19 Supplying and Fixing First Aid Hose Reel, wall mounting swinging type complete

with drum & bracket of MS construction, spray painted in Post office Red, confirming

to IS 884/1995 with upto date amendments, complete with the following as required.

36 Meter long 20 mm dia water hose Thermoplastic (Textile reinforced) Type - 2 as

per IS : 12585 20 mm dia gun metal ball valve & nozzle.

Drum and brackets for fixing the equimpments on wall.

Connection from riser with stop valve (gun metal) & M.S. Pipe Each 9.0

1. 20 Providing and fixing C.I. sluice valves (With cap) of approved quality complete with

bolts, nuts, rubber insertions etc. ( the tail pieces if required will be paid separately )

Class IIa) 200 mm dia Each 1.0

b) 150 mm dia Each 3.0

1.21 Supply, Installation, Testing and Commissioning of 100 mm dia Bourden type,

Stainless Steel dial type Pressure Gauge including brass isolation valve and siphon

pipe having caliberation of 0 - 16 Kg / cm2 . Each 15.0

1.22 Supplying and Fixing of Fire Man's axe with heavy insulated rubber as per standard

conforming to IS 926

Each 9.0

1.23 Supplying and Fixing vane type waterflow switch with contacts suitable for installation

on 50 mm to 150 mm dia pipeline for a service pressure upto 20 Kg/sq.cm.Each 15.0

NIMR-Dwarka 11 Estimate-Fire Fighting

Page 72: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Unit Total Qty. Rate In Figures

(Rs).

Rate In Words (Rs). Amount In Figures (Rs).

1.24 Providing, Fixing, Testing and Commissioning of Sprinkler Installation Control

Valve of Cast iron body and brass / bronze working parts comprising of water motor,

alarm, bronze seat clapper and clapper arm, hydraulically driven mechanical gong

bell to sound continuous alarm when the Sprinkler system activates, pressure

gauges, emergency releases, strainer, pressure switch, cock valve complete with

drain valve and bypass, test control box, ball valves, MS pipe of required size,

flanges, orifice plate, gasket etc. of size 200/150 mm dia, as required.Each 1.0

1.25 Supplying, Installation, Testing & Commissioning modular construction master

control annciation panel for sprinkler with provision for requider No. of Zone (30%

additional spares),eachsprinkler hydrant will have atleast 2 zone on each floor as

approved by engineer.The panel shall have but not limited to the following

arrangment.

a) Indication of Zone sprinkler

b) Indication of zone fault

c) Fire/fault hooter

d) Alarm cancel for fire/fault

e) Battery for emergency back up of 4 Hrs. Set 1.0

1.26 Providing and Fixing 15 mm dia gunmetal / brass quartzoid type Sprinkler Head

with quartz bulb and set to operate at specified temperature.

a) Pendent / Upright type, 68 C, Chrome plated a) Pendent / Upright type, 68 C, Chrome plated Each 20.0

b) Side wall extended throw 20 mm dia 68 C, Chrome plated Each 50.0

1.27 Fabricating, Supplying, Installation, Testing and Commissioning Air Vessel of

continuous welded construction with flanged discharge header on the top of each

riser fabricated out of 10 mm thick dished ends and 8 mm thick MS sheet, Air

Release Valve complete with suitable drain arrangement with 25 mm dia gun metal

wheel valve complete with all accessories etc. as required of the following sizes

a) 1.2 Metre high and 250 mm dia Each 4.0

1.28 Providing and fixing of C.I. 'Y' type strainer flanged with SS 304 perforated screen

including nuts, bolts and rubber insertions etcb) 150 mm dia Each 1.0

1.29 Providing and fixing of single arc expansion joints (rubber below) of following size

complete with nuts, bolts and washers etc. a) 150 mm dia Each 2.0

b) 80 mm dia Each 1.0

1.30 Providing and fixing of foot valve complete with including M.S. flange nuts, bolts,

washers, gaskets insertions etc.a) 150 mm dia Each 1.0

1.31 Supply, Installation, Testing and Commissioning External Yard Hydrant Stand Post

comprising of GI pipe 80 mm dia (heavy duty C class) from existing ringmain to

about 1 meter above ground level and Single Headed Yard Hydrant Valve with 80

mm dia flanged inlet, intantanneous gunmetal coupling of 63 mm dia with cast iron

wheel ISI marked, conforming to IS : 5290 (Type A), with ABS cap and chain

etc.complete with all accessroies as required. Each 15.0

NIMR-Dwarka 11 Estimate-Fire Fighting

Page 73: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Unit Total Qty. Rate In Figures

(Rs).

Rate In Words (Rs). Amount In Figures (Rs).

1.32 Providing and placing on terrace polyethylene water storage tank ISI : 12701

MARKED indicating the BIS license No with cover and suitable locking arrangement

and making necessary holes for inlet, outlet and overflow pipes but without fittings

and the base support for tank. Ltrs 15000.0

NIMR-Dwarka 11 Estimate-Fire Fighting

Page 74: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Unit Total Qty. Rate In Figures

(Rs).

Rate In Words (Rs). Amount In Figures (Rs).

1.33 Supply, erection, testing & commissioning of exit glow sign board of size 200mm x

350 mm wall mounting signage consisting of photo luminescent coating on acrylic

cover

Each 12.0

1.34 Providing and fixing fire extinguisher of carbon dioxide type consisting of brand new

high pressure steel cylinder bearing IS: 7285 mark and having the approval of

controller of explosives Nagpur, wheel type valve bearing IS:3224 mark internal

discharge tube, 1 meter long high pressure discharge hose, non conducting horn,

suspension bracket, fully charged bearing IS: making fixed to wall as directed.

a) 4.5kg capacity cylinder Each 17.0

1.35 Providing and fixing 9 liters capacity fire extinguisher water type gas pressure

conforming to IS marking, fixed to wall. Each 17.0

1.36 Providing and fixing ABC type fire extinguishers complete in all respects.conforming

to IS marking, fixed to wall. a) Capacity 6.0 Kg. Each 17.0

1.37 Providing and fixing ABC type automatic modular ceiling mounted type extinguisher

with body powder coated 10 lts. Capacity min. 300 mm dia 68 degree centigrade bul

temperature complete in all respect of approved make and modeltemperature complete in all respect of approved make and model

Each 2.0

1.38 Automatic Fire Detection and Suppression system with NOVEC 1230 GAS

A) Trace Tube System

1) Supply, fixing, testing and commissioning of Automatic Linear pneumatic Tube

Detection based NOVEC 1230 / System for Electrical Panels (consisting of the

following components:

(a) 2 Kg Novec 1230, DLP Assembly with automatic valve, push in connector for tube, 2

Kg Novec 1230 gas, mounting bracket, End of Line adopter and low pressure

switch for monitoring system activation of LT Panel size(7.79x5.71x0.9)

Nos. 4.0

(b) 4 Kg Novec 1230, DLP Assembly with automatic valve, push in connector for tube, 4

Kg Novec 1230 gas, mounting bracket, End of Line adopter and low pressure

switch for monitoring system activation of HT Panel size(5.65x5.71x0.9)

Nos. 3.0

(c) Linear pneumatic heat Detection Tube with all necessary fittings & supports.

Mtr 300.0

(d) Master Control Unit with Audio Visual Alarm with wiring to make complete system

operational. The Control Panel should have provision for integration with Fire

Alarm/SCADA/BMS System.

Nos. 7.0

NIMR-Dwarka 11 Estimate-Fire Fighting

Page 75: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Unit Total Qty. Rate In Figures

(Rs).

Rate In Words (Rs). Amount In Figures (Rs).

1.39 Fabricating, Supplying, Installation, Testing and Commissioning Air Vessel of

continuous welded construction with flanged discharge header in pump house

fabricated out of 10 mm thick dished ends and 8 mm thick MS sheet, Air Release

Valve, complete with drain arrangement with 25 mm dia gun metal wheel valve

complete with all accessories etc. as required of the following sizes

a) 2 Metre high and 450 mm dia suitable to operate Jockey Pump, Main Fire Pump &

Diesel Engine Driven Fire Pump Each 1.0

1.4 Providing and fixing C.I. non-return valve complete with gunmetal seat, bolts, nuts

washer & rubber insertions as required conforming to IS:5312.a) 150 mm dia Each 4.0

b) 80 mm dia Each 4.0

NIMR-Dwarka 11 Estimate-Fire Fighting

Page 76: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Unit Total Qty. Rate In Figures

(Rs).

Rate In Words (Rs). Amount In Figures (Rs).

1.41 Supplying, installing, testing and commissioning of electric driven fire pump

suitable for automatic operation consisting of the following (as per CPWD

specification Part V-1985 for Fire Fighting and its amendments) (For Hydrant system

& Sprinkler system).

a) Fire pump with SS/bronze impeller, CI casing, SS shaft & mechanical seal shall be

horizontal split casing centrifugal suction type multistage having following capacity

and head so as to ensure a minimum pressure of 3.0 kg per square cm. at the

highest and farthest out let at the specified flow complete with necessary strainer /

foot valve suction side and pressure gauge on the delivery side including by pass

arrangement for periodical testing of the working of the pumping set as required. The

pump shall be provided with mechanical seals.

b) Squirrel cage type TEFC motor suitable for operation on 415V, 10%, 3 phases 50

Hz. system of suitable HP for the above pump with synchronous speed of 1500

RPM and flexible coupling. The pump motor should conform to IS: 325-1978.

c) Common bed plate fabricated from mild steel channel or cast iron type.

d) Suitable cement concrete pump foundation & vibration damping arrangement with

cushy foot mounting as required.

I) Capacity 2280 LPM and Head 55 Metres Each 1.0

1.42 Supplying, installing, testing and commissioning of diesel engine driven fire pump

suitable for automatic operation consisting of the following (as per CPWD

specifications PartV 1985.) (For Hydrant system & Sprinkler system).

a) Horizontal centrifugal type multi-stage, fire pump with stainless steel impeller CI

casing, SS shaft & mechanical seal complete of following capacity and Head so as

to ensure a minimum pressure of 3.0 kg per sq.cm. at the highest & farthest outlet at

the specified flow, complete with necessary strainer pressure gauge on the delivery

side etc. including by pass arrangement for periodical testing of the working of the

pump set as required. The pump shall be provided with mechanical seals.

b) Water cooled cold starting type multi cylinder 4 stroke diesel engine, developing

suitable BHP at 1500 RPM for the above pump set with automatic starting

mechanism, cooling system shall be with radial cool engine, maintenance free

batteries, battery charge unit, flexible coupling with the pump, common bed plate for

mounting diesel engine fuel day tank fuel piping and pump and vibration damping

arrangement by cushy foot mounting as required complete in all respects.

c) The engine shall be capable to drive the pump at 150% rated discharge at 65%

head and shall be suitable for 10% overload capacity for one hour in any period of

12 hrs. continuous run.

d) Common bed plate fabricated from mild steel channel or cast iron type.

e) Isolation Valve

NIMR-Dwarka 11 Estimate-Fire Fighting

Page 77: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Unit Total Qty. Rate In Figures

(Rs).

Rate In Words (Rs). Amount In Figures (Rs).

f) Suitable cement concrete pump foundation & vibration damping arrangement with

cushy foot mounting as required.

NIMR-Dwarka 11 Estimate-Fire Fighting

Page 78: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Unit Total Qty. Rate In Figures

(Rs).

Rate In Words (Rs). Amount In Figures (Rs).

I) Capacity 2280 LPM and Head 55Metres Each 1.0

1.43 Supplying, installation, testing and periodic commissioning of electric motor driven

automatic pressurization pump set consisting of the following (as per specification)

(For Hydrant system & Sprinkler system).

a) Centrifugal pump of 180 LPM capacity capable of building up pressure lost in any

leakage in the system against atotal head (mentioned as under) complete with C.I.

casing stainless steel impellor ; mechanical seal & S.S. shaft necessary strainer,

pressure gauge on delivery side etc. including by-pass arrangement for testing of the

working of the pumping set as required .

b) Squirrel cage A.C. induction motor suitable for operation on 415 V, 10% 3 phase 50

Hz. A.C. supply and of minimum 7.5 HP,1500 RPM, for the above pump with flexible

coupling as per specification and conforming to IS: 325/ 1978 and shall be TEFC

type only.

c) Common bed plate fabricated from mild steel channel or cast iron type.

d) Suitable cement concrete pump foundation with vibration damping arrangement

with cushy foot or similar mounting as per required.I) Head - 55 Metres Each 1.0

1.44 Providing & fixing puddle flanged including 40 cm long GI pipe piece welded /

threaded with MS plates 450x450x6mm thick with both end screwed / flangeda) For 80 mm dia pipe Each 2.0

b) for 150 mm dia pipe Each 4.0

c) for 200 mm dia pipe Each 2.0

1.45 Supplying, installing, testing and commissioning of electric motor driven type

automatic pressurisation, pump set suitable for automatic operation of terrace

down comer and consisting of the following (as per CPWD specifications Part V-

1985) for fire fighting and its amendmendts).

NIMR-Dwarka 11 Estimate-Fire Fighting

Page 79: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Unit Total Qty. Rate In Figures

(Rs).

Rate In Words (Rs). Amount In Figures (Rs).

a Fire pump with stainless steel impeller CI casing, SS shaft shall be horizontal end

suction centrifugally type having a capacity of 450 LPM against a total head of 25m

so as to ensure a minimum pressure of 3.0 kg/sqm at the highest and farthest out at

the specified flow complete with necessary strainer with foot valve in suction side

and pressure gauge on the delivery side including bypass arrangement for periodic

testing of the working of the pumping set as required. The pump shall be provided

with mechamical seals.(Including taking necessary approval of complete fire fighting

scheme from local fire authority before and after start of work) {Agency also has to

submit characterstic curve of the pumps, model & other technical data for approval

before placing the order}

b Squirrel cage AC induction motor suitable fot operation of 415 V ,+/-10%, 3 phase 50

HZ, AC supply and of minimum 7.5 HP,1500 RPM for the above pump with flexible

coupling as per spwcification and conforming to IS 325-1978 and shall be TEFC type

onlyc Common base plate fabricated from mild steel channel ot castiron type

d 1 No. 3 Phase, DOL starter type - II of 5 HP with thermal overload relay, contactor,

Push Buttons, Single Phase Preventer and Switches etc complete as required.

e Suitable cement concrete pump foundation with vibration damping arrangememnt

with cushy foot mounting as required and having provision of suitable weather

protection cover. set 3.0

2.00 Fire Panel (Electrical)

2.01

Supply, installation, testing and commissioning of following M.V. cubicle type totally

enclosed, powder coated, free standing type, dust, damp and vermin proof, indoor

type Panel complete with busbars, M.V. danger notice plate, interconnections with

suitable capacity aluminium leads/solid aluminium strips/rods, connection of

incoming and outgoing cables with thimbles, and having following incoming and

outgoing switchgears complete as technical specification & as required.

Note :

ii All MCCBs shall have Ics=Icu =100%

INCOMER :

320 Amp 415 volts, 35 KA (Ics=Icu), FP MCCB microprocessor based, with O/L,

S/C & E/F protection.R,Y&B phase indicating lamp (LED type) with 6A control SP MCB

"ON" ,"OFF" and "TRIP" LED indicating lamp and 6A control SP MCBs

Extended rotary operating mechanism with door interlock with defeat feature and

padlock facility. MCCB should have spreader links & phase barriers.

1 no. Digital voltmeter with selector switch

1 no Digital ammeter with selector switch with one set of suitable C.T. s

BUSBARS :

500 Amp TPN busbars of aluminium

OUTGOINGS :

NIMR-Dwarka 11 Estimate-Fire Fighting

Page 80: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Unit Total Qty. Rate In Figures

(Rs).

Rate In Words (Rs). Amount In Figures (Rs).

i

2 Sets of following (Main electric pump)

160 Amp. 415 volts, 35 KA (Ics=Icu), TPN MCCB, with Thermal magnetic release

having variable current settings. .

Extended rotary operating mechanism with door interlock with defeat feature and

padlock facility. MCCB should have spreader links & phase barriers.

1 No. 3 Phase, fully automatic Star Delta starter of 60 HP with thermal overload

relay with inbuilt/separate single phase preventer , contactor, Timer, Push Buttons

and Auto-manual selector switch etc complete as required.

Digital ammeter with selector switch with one set of suitable CT,s.

LED indicating Lamps for "ON" , "OFF" & "TRIP" .

ii

2 Sets of following (Jockey Pump)

NIMR-Dwarka 11 Estimate-Fire Fighting

Page 81: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No Description Of Item Unit Total Qty. Rate In Figures

(Rs).

Rate In Words (Rs). Amount In Figures (Rs).

32 Amp. 415 volts, 35 KA (Ics=Icu), TPN MCCB, with Thermal magnetic release

having variable current settings. .

Extended rotary operating mechanism with door interlock with defeat feature and

padlock facility. MCCB should have spreader links & phase barriers.

1No. 3 Phase, DOL starter of 5 HP with thermal overload relay with inbuilt single

phase preventor , contactor, Push Buttons and Switches etc complete as required.

LED indicating Lamps for "ON" , "OFF" & "TRIP" .

iii 2 Sets of following (Spare)

32 Amp. 415 volts, 35 KA (Ics=Icu), TPN MCCB, with Thermal magnetic release

having variable current settings. .Extended rotary operating mechanism with door interlock with defeat feature and

padlock facility. MCCB should have spreader links & phase barriers.

LED indicating Lamps for "ON" , "OFF" & "TRIP" .

iv 1 Set of following in a separate cubicle (Diesel engine auto starting kit)

One no. Diesel engine auto starting kit with all necessary relay, controls, wiring etc to

start 70 HP diesel engine when electrical driven fire pump fail to start including one

no rectifier circuit, battery charger, batteries, DC Voltmeter, DC Ammeter and its

interconnection with control cables etc complete in ready to use condition.

Fire PANEL in pump room as above set 1.0

2.02 Starter For Terrace Pump (Audi, Hostel, Guest House)

1No. 3 Phase, DOL starter of 5 HP with thermal overload relay with inbuilt single

phase preventor , contactor, Push Buttons and Switches etc complete as required. set 3.0

FIRE PUMP Panel as mentioned above

Subtotal (Fire fighting)

NIMR-Dwarka 11 Estimate-Fire Fighting

Page 82: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No DESCRIPTION OF WORK Rate In figure (Rs.)

1 FIRE FIGHTING

Sub Total(Fire Fighting work)

Cost of DSR based works

Value of market rate based items

GRAND TOTAL

PROJECT NAME: Proposed Buildings at BOQ NIMR,Dwarka (Auditorium,VIP Guest

House, Hostel, AC Plant Room, Substation & UG Tank)

ABSTRACT OF COST (BOQ)

SUMMARY FIRE

Page 83: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

1 2 3 4 5 6 7

SUBHEAD 1: H.T. SUB STATION.

1.01HT Panel

Supply, erection, testing and commissioning of 3 panel, 630 A ,11 kV, 3 Phase, 50 Hz., metal clad, dead

front, 350 MVA rupturing capacity Vacuum Circuit Breaker Incoming & Outgoings as per the detailed

specifications and drawings including connections etc. including door interlocking and expendable as

required.

A. INCOMER :

i) 1 No. VCB having following

BOQ OF ELECTRICAL WORKS FOR CONSTRUCTION OF GUEST HOUSE, AUDITORIUM BLOCK, HOSTEL BLOCK, SUBSTATION & AC PLANT ROOM AT NIMR, DWARKA, NEW DELHI

i) 1 No. VCB having following

1 No.630A, 11kV, 3 Phase, 50Hz., metal clad, dead front, 350 MVA rupturing capacity, Fully Draw out type,

Vacuum Circuit Breaker (VCB)

1 set of 11kV/110V Potential Transformers with HRC fuses for metering & protection.

1 Set of Phase indicating lamps with HRC fuses

1 No. Digital voltmeter .

1 set of indicating lamps to indicate OPEN, CLOSE, TRIP, SPRING CHARGED, TRIP CIRCUIT

HEALTHY

Push button for ON, OFF,TRIP&TRIP circuit healthy

1 set of 150/5-5A Current Transformer for metering and protection.

1 No.digital Ammeter.

1 Set of CDG 61 (2 No. O/C, 1 No. E/F) relay

Digital frequency meter,Digital Tri vector meter.

I Set of undervoltage relay and Overvoltage relay

Trip circuit supervision relay,Auxiliary relays with shunt trip coil (WTI & Door open trip)

I No. Master Trip relay

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 1_R5

Page 84: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

1 No. Digital Power factor meter

8 window annuciator with Hooter

1 no. Phase reversal Relay

B. BUSBARS :

11kV, 350 MVA, 630 Amps Three Phase busbars of copper.

C. OUTGOINGS :

2 No. VCB each having following2 No. VCB each having following

1 No. 630A, 11kV, 3 Phase, 50Hz., metal clad, dead front, 350 MVA rupturing capacity, Fully Drawout type,

Vacuum Circuit Breaker (VCB)

1 set of 11kV/110V Potential Transformers with HRC fuses for metering & protection

1 Set of Phase indicating lamps with HRC fuses

1 No. Digital voltmeter .

1 set of indicating lamps to indicate OPEN, CLOSE, TRIP, SPRING CHARGED, TRIP CIRCUIT

HEALTHY

Push button for ON, OFF,TRIP&TRIP circuit healthy

1 No.Digital ammeter with selector switch and one set of C.T 75/5-5 A. For measurement & protection.

1 Set of CDG 61 (2 No. O/C, 1 No. E/F) relay

Digital frequency meter,Digital Tri vector meter.

I Set of undervoltage relay and Overvoltage relay

Trip circuit supervision relay,Auxiliary relays with shunt trip coil

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 2_R5

Page 85: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

I No. Master Trip relay

1 No. Digital Power factor meter

8 window annuciator with Hooter

HT Panel as mentioned aboveSet 1

1.01 AAdapter Box

Supply, erection, testing and commissioning of adaptor box of 11KV fabricated out of powder coated 2.0

mm MS Sheet of suitable size including copper bus bar insulation & connections etc. including expendable as

required.

Set 1

1.02TRANSFORMER :

Supply, installation, testing and commissioning of 1250 KVA, 11/0.433 kV, 3 Phase, 4 wire, 50 Hz., ON-AN

Transformer Vector group copper bound Class F insulation On load tap changer on HV Side range -15% ,0,

+5% in the steps of 1.25% per step, type transformer with RTCC+AVR inclusive of all control cable . Cable

box connection at primary and secondary end (LT side) shall be connected through Bus Duct, complete with

all accessories including first filling of oil, double float buchholz relay protection, high winding temperature,

oil temperture sensors and gauges etc. confirming to IS 2026 (Part -1 & Part -2 ) including its

interconnection with control cables, as per detailed technical specifications and as required.

Each 2

1.03

BATTERY CHARGER PANEL

Supply, erection, testing and commissioning of battery charger panel with 24 V DC continuous out put for

control supply of HT panel complete with battery, control cabling etc. as required. Capacity of battery

charger panel should be suitable for above mentioned H.T. Panels.

2 numbers battery of minimum 180 AH ampere hour capacity.

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 3_R5

Page 86: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

Boost and Trickle charger suitable for above items.

1 No. AC Voltmeter (0-500Volt)

I No. DC Voltmeter

I No. DC Ammeter

1 set of AC and DC indicating lamps

1 No. DC Battery charging position indicator

DC distribution board suitable for above application to incoming & outgoing MCBs include tripping, closing

and indication etc.

Control cabling between DC Distribution panel to the HT panel of the Substation with suitable core 1.5

sqmm copper cableEach 1

1.04

BUS DUCTS :

i) Supply, Installation, testing and commissioning of 2000 phase and neutral , 415 V, 3 Phase, 4 Wire, sandwich

construction Aluminium Bus Duct including bends, flexible joints, earth bus (2 runs of aluminum strips),

supports for installation, supporting arrangements, etc.outdoor /indoor duty type complete as per technical

specifications and as requirment. . Note- for outdoor installtion canopy will be mounted on bus duct for

protection.

Mtrs. 50

1.05

H.T. CABLE

Supply of following sizes of 11 kV grade multicore aluminum conductor XLPE armoured power cable as per

IS : 7098.

i) 3 Core, 240 sq mm

Mtrs. 150

1.06

Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following

size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc

as required.

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 4_R5

Page 87: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

i) upto 240 Sq mm

Meter 80

1.07

Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following

size in the existing RCC/ HUME/ METAL pipe as required.

i) upto 240 Sq mmMetre 20

1.08

Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following

size in the existing masonry open duct /cable tray as required.

i) upto 240 Sq mm

Metre 50

1.09

Supplying and making end termination with heat shrinkable jointing kit complete with all accessories

including lugs suitable for following size 3 Core, XLPE aluminium conductor cable of 11kV grade as

required.

i) 240 sqmm 3 core (Heat Shrunk Type ) Indoor Type

Each 4

ii) 240 sqmm 3 core (Heat Shrunk Type ) Outdoor Type

Each 2

1.10

Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC

collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and

refilling etc as required.

i) 300 mm dia

Metre 100

1.11

Cable Route Marker

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 5_R5

Page 88: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there

on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as

required.each 10

1.12

Providing & Fixing of Safety Equipmet

i) Providing and fixing H.T. (11kV) danger notice plate of 250mmX150mm made of mild steel, atleast 2mm

thick and vitreous enameled white on both sides and with inscription in signal red colour on front side as

required.

Each 2

ii) Providing and fixing M.V. danger notice plate of 200mmX150mm made of mild steel, atleast 2mm thick and

vitreous enammelled white on both sides and with inscription in signal red colour on front side as required.

Each 6

iii) Supply & erection of the following Safetyand testing Equipment including miscellanoes items like Clamps,

nuts & Bolts , rawl plugs etc at suib;e laces in the Substation building as required.

a) G.I buckets of 4 nos of 5 Litres Capacity duly painted white inside and red oxide paint out side and witten

'FIRE' with white paint & Filled with Dry sand and mounted on M.S angel iron bracket of Size 50x50x6mm

thick and 1200mm long including grounting in walll /floor etc as required .

Each 2

b) Supplying, storing, handling and fixing in position First Aid Medical Box complete as per technical

specifications as required.Each 1

c) Shock Treatment Chart duly glazed mounted on Aluminum Frame with Sheet Glass as required.

Each 1

d) Supplying and laying of 12kV grade 1 metre wide anti skid chequered type rubber mat.

Metre 20

e) Supplying and laying of 1.1kV grade 1 metre wide anti skid chequered type rubber mat.

Metre 30

f) Supply rubber hand gloves 11kV grade as per I.S. Code.

set 1

d) Supplying of digital Earth Tester complete with probes etc as required

Set 1

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 6_R5

Page 89: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

e) Supplying of Telesscopic folding Aluminium ladder folding double with sitting stand 6 M etc as required

Each 1

1.13

Providing and fixing of M.S Slotted angle iron with fixing materials and painting for cable racks in trenches

/on wall etc. as required KG 100

1.14

Providing and fixing of M.S Slotted angle 'C' channel /Ladder type rack /tray including fixing material

grouted in wall or haning with M.S rod hanger from ceiling including 2 coat synthetic enamel painting over 1

coat of res oxide primer etc. as required

KG 100

1.15 Fabrication and Installing following size of preforted M.S Cable tray including Horizontal and vertical bends,

reducers,tee, crossmember and other accessories as required and duly Suspended from the ceiling with M.S

12mm rod suspenders and including painting etc. as required.

i) 150mmwidth x 50mm depth x1.6mm thickness Metre 200

ii) 300mmwidth x 50mm depth x1.6 mm thickness Metre 150

iii) 450mmwidth x 62.5mm depth x2.0mm thickness Metre 100

1.16 Fabrication and Installing following size of Ladder type M.S Cable tray including Horizontal and vertical

bends, reducers,tee, crossmember and other accessories as required and duly Suspended from the ceiling with

M.S 12mm rod suspenders and including painting etc. as required.

i) 450mmwidth x 62.5mm depth x2.0mm thickness Metre 200

TOTAL SUBHEAD 1: H.T. SUB STATION AS MENTIONED ABOVE

2.00 SUBHEAD 2: MAIN LT PANEL.

2.00 MAIN L.T. PANEL

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 7_R5

Page 90: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

Supply, installation, testing and commissioning of expandable type LT Panel, Totally Typed Tested

Assembaly (TTA) cubicle type, totally enclosed, free standing type, dust, damp and vermin proof Panel made

up of CRCA sheet , complete with aluminium busbars, danger notice plate, interconnections with suitable

capacity aluminum leads/solid aluminum strips/rods, necessary interlocking,cable alley in front, powder

coated and having incoming and outgoing switchgears as mentioned below and complete as per technical

specifications and as required.

Note :

1. All ACBs shall have spare contacts & as required.

2. All relays to operate at 240Volts, Single phase, 50Hz.,

3. UPS of 2 KVA ,UPS is the part of supply of LT Panel

A INCOMER:

i) 2 No. ACB Panels each having following:

2000 A, 415/500V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker with

microprocessor based overload, short circuit & earth Fault trip including under voltage release and lockable

trip push button. ACB should have Icw=Ics = 50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB

Push button to CLOSE the ACB.

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs

1 No. 0 to 500 V Digital voltmeter with selector switch.

Digital Ampere Metre with ASS and Digital Energy meter with suitable set of CT's

Digital multi function meter with one set of suitable CTs

One set of dual core dual ratio CT of 2000/1000/5/5A for capacitor panel.day night selector switch.

B. BUSBARS :

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 8_R5

Page 91: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

2000 Amps TPN busbars of aluminum with an ambient temperature of 45 degree Centigrade and 50 degree

Centigrade rise in the over and above ambient temperature.

C. BUS COUPLER :

i) 1 No. ACB Panels each having following:

2000 A, 415/500V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker with

microprocessor based overload, short circuit, Instantenous & earth Fault trip including under voltage release

and lockable trip push button. The ACB should have Icw =Ics= 50KA for 1 sec.

1 set of indicating lamps to indicate OPEN, CLOSE, TRIP.

Push button to CLOSE the ACB.

1 Set of Ampere meter with ASS and CTs.

D. OUTGOING.

i) 1 No. ACB Panels each having following:

1250A, 415/500V, Fully Motorised, Fully Drawout type (EDO), TPN, Air Circuit Breaker with

microprocessor based overload, short circuit, instantanious & earth Fault trip including under voltage release

and loackable trip push button. ACB should have Icw=Ics= 50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB

Push button to CLOSE the ACB

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs

Digital Ampere Metre of suitable range with suitable set of CT's and ASS.

Digital energy metre with CT

i) 4 No. ACB Panels each having following:

1000A, 415/500V, Fully Motorised, Fully Drawout type (EDO), TPN, Air Circuit Breaker with

microprocessor based overload, short circuit, instantanious & earth Fault trip including under voltage release

and loackable trip push button. ACB should have Icw=Ics= 50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 9_R5

Page 92: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

Push button to CLOSE the ACB

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs

Digital Ampere Metre of suitable range with suitable set of CT's and ASS.

Digital energy metre with CT

ii) 2 No. ACB Panels each having following:

800 A, 415/500V, Fully Motorised, Fully Drawout type (EDO), TPN, Air Circuit Breaker with

microprocessor based overload, short circuit, instantanious & earth Fault trip including under voltage release

and loackable trip push button. ACB should have Icw=Ics= 50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB

Push button to CLOSE the ACBPush button to CLOSE the ACB

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs

Digital Ampere Metre of suitable range with suitable set of CT's and ASS.

Digital energy metre with CT

iii) 2 Nos. MCCB FEEDER as per following details/ specifications:

630Amp 415 volts, 50 KA ( Ics) TP+NL MCCB with variable current settings and having microprocessor

based O/L, S/C & E/F protection release.

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP .

Digital Ampere Metre of suitable range with suitable set of CT's and ASS.

Digital Energy meter

v) 1 Nos. MCCB FEEDER as per following details/ specifications:

400Amp 415 volts, 50 KA ( Ics) TP+NL MCCB with variable current settings and having microprocessor

based O/L, S/C & E/F protection release.

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 10_R5

Page 93: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP .

Digital Ampere Metre of suitable range with suitable set of CT's and ASS.

Digital Energy meter

v) 1 Nos. MCCB FEEDER as per following details/ specifications:

250Amp 415 volts, 50 KA ( Ics) TP+NL MCCB with variable current settings and having microprocessor

based O/L, S/C & E/F protection release.

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP .

Digital Ampere Metre of suitable range with suitable set of CT's and ASS.

Digital Energy meterDigital Energy meter

vi) 2 Nos. MCCB FEEDER as per following details/ specifications:

200 Amp 415 volts, 50 KA ( Ics) TP+NL MCCB with thermal magnetic release having variable current

settings of 0.8 to 1.0 In .

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP .

Digital Ampere Metre of suitable range with suitable set of CT's and ASS.

Digital Energy meter

vi) 2 Nos. MCCB FEEDER as per following details/ specifications:

160 Amp 415 volts, 50 KA ( Ics) TP+NL MCCB with thermal magnetic release having variable current

settings of 0.8 to 1.0 In .

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP .

Digital Ampere Metre of suitable range with suitable set of CT's and ASS.

Digital Energy meter

vii) 3 Nos. MCCB FEEDER as per following details/ specifications:

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 11_R5

Page 94: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

100Amp 415 volts, 50 KA (Isc), TP+NL MCCB with thermal magnetic release having variable current

settings of 0.8 to 1.0 In .

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP .

Digital Ampere Metre of suitable range with suitable set of CT's and ASS.

Digital Energy meter

viii) 2 Nos. MCCB as per following details/ specifications:

63 Amp 415 volts, 50 KA (Isc), TP+NL MCCB with thermal magnetic release having variable current

settingsof 0.8 to 1.0 In .

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP .

Digital Ampere Metre of suitable range with suitable set of CT's and ASS.

Digital Energy meter

Main LT Panel as mentioned above. Set1

2.02 CAPACITOR PANEL FOR ESS- 1 (500 KVAR Capactoir Panel )

Supply, installation, testing and commissioning of M.V. cubicle type totally enclosed free standing type,

powder coated, dust, damp and vermin proof Capacitor Panel complete with busbars, M.V. danger notice

plate, ammeter, ammeter selector switch, indicating lamps, CT's, Ultra heavy duty, APP type Capacitors

suitable for non linear loads upto 20% with operating losses of capacitor shall not more than 0.45 W /

KVAR, Power contactors suitable for capacitor switching or Capacitor duty with current limiting contactor

circuit to suppress switching inrush current interconnections with suitable capacity aluminium leads/solid

aluminium strips, rods, connection of incoming and outgoing cables with thimbles, and having following

incoming and outgoing switchgears complete as per techinical Specification as required.

A. INCOMER :

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 12_R5

Page 95: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

1 No. 1000A, 415/500V, Motorised, Fully Drawout type (EDO), Three Pole, Air Circuit Breaker with

microprocessor based overload, short circuit & earth Fault trip including under voltage release and lockable

trip push button. ACB should have Icw=Ics=Icu=65 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP.

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs

Day & Night mode selector switch

14 steps Intelligent microprocessor based Automatic Power factor Correction relay having measurment

sensitivity of 1 % or better.

Extension of incoming busbars for connection of multicore armoured aluminium cables.

B. METERING :

1 set of digital Amp. Meter, digital Power factor meter and Digital voltmeter

C. BUSBARS :

1250 Amp TPN busbars of aluminum

D. OUTGOINGS :

i) 2 Nos . MCCB as per following details/ specification:

200 Amps, 415 volts, TP, Power Contactor suitable for capacitive switching including current limiting

contactor circuit to supress switching inrush current.

ON/ OFF delay timers for switching capacitor circuit.

"ON" and "OFF" LED indicating lamp and 2A control SP MCBs

Push button for CLOSE and TRIP

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

100 kVAR extra heavy duty APP type Capacitors suitable for non linear loads upto 20%, operating losses not

more than 0.45 W per KVAR .

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 13_R5

Page 96: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

ii) 4 Nos . MCCB as per following details/ specification:

100 Amps, 415 volts, 25 KA, TP, Power Contactor suitable for capacitive switching including current

limiting contactor circuit to supress switching inrush current

ON/ OFF delay timers for switching capacitor circuit.

"ON" and "OFF" LED indicating lamp and 2A control SP MCBs

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

50 kVAR Ultra heavy duty APP type Capacitors suitable for non linear loads upto 20%, operating losses not

more than 0.45 W per KVAR .

iii) 4 Nos . MCCB as per following details/ specification:iii) 4 Nos . MCCB as per following details/ specification:

63 Amps, 415 volts, 25 KA, TP, Power Contactor suitable for capacitive switching including current limiting

contactor circuit to supress switching inrush current

ON/ OFF delay timers for switching capacitor circuit.

"ON" and "OFF" LED indicating lamp and 2A control SP MCBs

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

25 kVAR Ultra heavy duty APP type Capacitors suitable for non linear loads upto 20%, operating losses not

more than 0.45 W per KVAR .

Capacitor panel as mentioned above.Set 1

TOTAL SUBHEAD 2: LT PANEL AS MENTIONED ABOVE.

SUB HEAD 3: DG SET & ACCESSORIES

3 SOUND PROOF DG SET OF 380 KVA (FOR AUDI BLOCKS)

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 14_R5

Page 97: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

Supply, installation, testing and commissioning of sound proof (silent type) Diesel Generating set having 380

KVA Prime Power Ratings , 415 volt at 1500 RPM, 0.8 power factor suitable for 50 Hz, 3 phase system ,

suitable bhp, Air cooled Radiator type diesel engine- alternator set mounted on common base frame, return

fuel cooler, battery & battery charger, Anti Vibration mounting pads, Engine alternator safeties, electronic

governor including all accessories, their wiring and control cable between DG set and panel etc. is also in

the scope of supply, including its connections etc. complete as per technical specification. This includes the

following:

- Supplying and fixing of suitable sizes Heavy class MS pipe for DG exhaust complete with bends, elbow,

flanges etc including silencer and catalytic convertor exhaust pipe chimney as per CPCB norms for exhaust of

DG sets.

- Supply and fixing of 50mm thick compressed mineral wool insulation (Rock wool) for D.G. exhaust pipe

with 24 gauge aluminium sheet cladding etc. as required for the under mentioned dia pipe.

- Supply, installation, testing and commissioning of suitable size fuel pipe for connecting diesel engine to- Supply, installation, testing and commissioning of suitable size fuel pipe for connecting diesel engine to

individual day service tank including supply and fixing of required valves & filters etc. as required.

- Fabrication of supports for exhaust pipe, fuel pipe or for any other purpose out of suitable M.S. structural

steel including supplying and applying of enamel paint of approved shade after one coat of steel primer of

reputed company.

- Supplying and fixing of suitable capacity cable adapter box for alternator. (if required)

- Providing and fixing oil tank of 990 litres capacity complete with suitable M.S. fabricated MS stand oil level

indicator gauge tank and stand duly painted, complete with float switches etc. as required.

Supply of sutibale hand manual pump with 20 Meter Hard PVC pipe for filling the Oil from drum in D.G set

First filling of Full capacity of Disel in D.G set after complete testing of D.G set at site. For commissioning of

D.G set Disel will provided by the contractor.

Intial Supply as well as first replacement of lube oil , fuel for 8 hrs for full load test run would be provided by

vendor before handling over D.G Set to the Client.

- Factory assembled Sound proof Canopy as per pollution control board requirement to achieve noise level

desired during night condition, with base frame, doors, inspection window, fresh air supply fans etc

- Any other item required for completion of system above (D.G. set).

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 15_R5

Page 98: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

A. DG AMF PANEL

Supply, installation, testing and commissioning of AMF Panel for above 380 KVA DG Set cubicle type,

totally enclosed, free standing type, dust, damp and vermin proof Panel made up of 14/ 16SWG CRCA sheet,

(load bearing members 14 SWG and doors 16 SWG) ,complete with aluminum busbars, M.V. danger notice

plate, interconnections with suitable capacity aluminum leads/solid aluminum strips/rods, powder coated and

having capacity to change over Main power and DG supply .

DG should start automatically and will have automatic change over at LT panel through auto change over

arrangement of suitable capacity.

Indicating lamps with 6A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB

Push button to CLOSE the ACB.

1 set of suitable set of CT for measurement and protection.

R, Y & B Phase indicating lamps (LED type) with 6A control SP MCBs

1 set of Digital multi function meter with LCD display and measurement of parameters like voltages,

currents, p.f, frequency, active and reactive power and energies etc

B. AMF panel should have following protection and AMF components for above mentioned DG set.

- Auto/manual/test/off selector switch

- 2 Nos over voltage relay, 2 nos. reverse power relay and 2 nos. under voltage relay.

- 3 sets of current transformers 15 P 10 accuracy for protection and 15 VA class -1 for metering

- Energy analyzer unit to indicate current voltage frequency power factor and KWH

- Indicating lamps for load on mains and load on set.

- Fuse for instruments.

- Battery charger, complete with transformer/rectifier, DC voltmeter and ammeter, selector switch for trickle,

off and boost the current adjustment.

- Main supply failure monitor.

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 16_R5

Page 99: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

- Restoration timer.

- Control unit with three impulse automatic engine start / stop and failure to start lockout.

- Impulse counter with locking and reset facility.

- On/Off/ Control circuit switch with indicator.

- Audio/ Video annunciation for :

a) High winding temperature.

b) Low lubricating oil pressure

c) Engine over speed

d) Engine fails to startd) Engine fails to start

e) Full load/ maximum load warning.

C. ENCLOSURE :

Fabrication, PVC Sleeving, Control/Power Wiring and necessary electrical/ mechanical interlocking etc any

other item required for proper functioning of the system complete as required.

DG SET WITH AMF PANEL AS MENTIONED ABOVESet 1

3.01 SOUND PROOF DG SET OF 82.5 KVA including AMF PANEL ( GUEST HOUSE)

Supply, installation, testing and commissioning of sound proof (silent type) Diesel Generating set having

82.5 KVA Prime Power Ratings , 415 volt at 1500 RPM, 0.8 power factor suitable for 50 Hz, 3 phase system

, suitable bhp, air cooled Radiator type diesel engine- alternator set mounted on common base frame, return

fuel cooler, battery & battery charger, Anti Vibration mounting pads, Engine alternator safeties, electronic

governor including all accessories, their wiring and control cable between DG set and panel etc. is also in

the scope of supply, including its connections etc. complete as per technical specification This includes the

following:

- Supplying and fixing of suitable sizes Heavy class MS pipe for DG exhaust complete with bends, elbow,

flanges etc including silencer and catalytic convertor exhaust pipe chimney as per CPCB norms for exhaust of

DG sets.

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 17_R5

Page 100: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

- Supply and fixing of 50mm thick compressed mineral wool insulation (Rock wool) for D.G. exhaust pipe

with 24 gauge aluminium sheet cladding etc. as required for the under mentioned dia pipe.

- Supply, installation, testing and commissioning of suitable size fuel pipe for connecting diesel engine to

individual day service tank including supply and fixing of required valves & filters etc. as required.

- Fabrication of supports for exhaust pipe, fuel pipe or for any other purpose out of suitable M.S. structural

steel including supplying and applying of enamel paint of approved shade after one coat of steel primer of

reputed company.

- Supplying and fixing of suitable capacity cable adapter box for alternator. (if required)

- Providing and fixing oil tank of 990 litres capacity complete with suitable M.S. fabricated MS stand oil level

indicator gauge tank and stand duly painted, complete with float switches etc. as required.

- Factory assembled Sound proof Canopy as per pollution control board requirement to achieve noise level

desired during night condition, with base frame, doors, inspection window, fresh air supply fans etc

-Supply of sutibale hand manual pump with 20 Meter Hard PVC pipe for filling the Oil from drum in D.G

set

-First filling of Full capacity of Disel in D.G set after complete testing of D.G set at site. For commissioning

of D.G set Disel will provided by the contractor.

- Intial Supply as well as first replacement of lube oil , fuel for 8 hrs for full load test run would be provided

by vendor before handling over D.G Set to the Client.

- Any other item required for completion of system above (D.G. set)

C. ENCLOSURE :

Fabrication, PVC Sleeving, Control/Power Wiring and necessary electrical/ mechanical interlocking etc any

other item required for proper functioning of the system complete as required.

DG SET WITH AMF Panel as mentioned above Set 1

TOTAL SUB HEAD 3: DG SET & ACCESSORIES AS MENTIONED ABOVE

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 18_R5

Page 101: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

4.00 SUB HEAD 4 :MV PANELS

Supply, installation, testing and commissioning of following M.V. cubicle type totally enclosed, wall

mounted/Free standing type, powder coated, dust, damp and vermin proof, indoor type Distribution

Board/Panel complete with busbars, M.V. danger notice plate, interconnections with suitable capacity

aluminium leads/solid aluminium strips/rods, connection of incoming and outgoing cables with thimbles, and

having following incoming and outgoing switchgears complete as per techinical specification and as required.

NOTE:

i All MCCBs shall have Ics=Icu=100%

ii MCB Should be connected throught terminal Strip of suitable rating

4.01 MV PANEL ANIMAL HOUSE4.01 MV PANEL ANIMAL HOUSE

A INCOMER:

i) 1 No. ACB Panels each having following:

1250 A, 415/500V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker with

microprocessor based overload, short circuit & earth Fault trip including under voltage release and lockable

trip push button. ACB should have Icw=Ics = 50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB

Push button to CLOSE the ACB.

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs

1 No. 0 to 500 V Digital voltmeter with selector switch.

Digital Ampere Metre with ASS with suitable set of CT's

Digital Volt meter with one set of suitable CTs

B. BUSBARS :

1600 Amps TPN busbars of aluminum.

C. OUTGOING.

i) 1 No. ACB Panels each having following:

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 19_R5

Page 102: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

1000A, 415/500V, Fully Motorised, Fully Drawout type (EDO), TPN, Air Circuit Breaker with

microprocessor based overload, short circuit, instantanious & earth Fault trip including under voltage release

and loackable trip push button. ACB should have Icw=Ics= 50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB

Push button to CLOSE the ACB

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs

Digital Ampere Metre of suitable range with suitable set of CT's and ASS.

ii) 2 No. ACB Panels each having following:

800A, 415/500V, Fully Motorised, Fully Drawout type (EDO), TPN, Air Circuit Breaker with

microprocessor based overload, short circuit, instantanious & earth Fault trip including under voltage release

and loackable trip push button. ACB should have Icw=Ics= 50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB

Push button to CLOSE the ACB

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs

Digital Ampere Metre of suitable range with suitable set of CT's and ASS.

iii) 1 Nos. MCCB FEEDER as per following details/ specifications:

400Amp 415 volts, 50 KA ( Ics) TP+NL MCCB with variable current settings and having microprocessor

based O/L, S/C & E/F protection release.

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP .

Digital Ampere Metre of suitable range with suitable set of CT's and ASS.

iv) 1 Nos. MCCB FEEDER as per following details/ specifications:

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 20_R5

Page 103: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

200 Amp 415 volts, 50 KA ( Ics) TP+NL MCCB with thermal magnetic release having variable current

settings

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP .

Digital Ampere Metre of suitable range with suitable set of CT's and ASS.

v) 2 Nos. MCCB FEEDER as per following details/ specifications:

100Amp 415 volts, 50 KA (Isc), TP+NL MCCB with thermal magnetic release having variable current

settings

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP .

Digital Ampere Metre of suitable range with suitable set of CT's and ASS.

vi) 2 Nos. MCCB as per following details/ specifications:

63 Amp 415 volts, 50 KA (Isc), TP+NL MCCB with thermal magnetic release having variable current

settings

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP .

Digital Ampere Metre of suitable range with suitable set of CT's and ASS.

MV Panel Animal House as mentioned above. Set1

4.02 MV PANEL (NORMAL) Auditoirum

a) INCOMER:

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 21_R5

Page 104: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

800 Amp 415 volts, 35 KA FP MCCB with variable current settings and having microprocessor based O/L,

S/C & E/F protection release.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB

ON, OFF, TRIP indication (LED Type)

Extended rotary operating mechanism with door interlocking with defeat feature and padlock facility. MCCB

should have spreader links & phase barriers.

1 No. 0 to 500 V Digital voltmeter with selector switch.

Digital ammeter with selector switch with one set Suitable C.Ts.

b) BUSBARS:

1000 Amp TPN Aluminium busbars

c) OUTGOING:

i) 2 Nos. MCCB as per following details/ specifications:

400 Amp 415 volts, 35 KA TP+NL MCCB with variable current settings and having microprocessor based

O/L, S/C & E/F protection release.

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

ON, OFF, TRIP indication (LED Type).

ii) 2 Nos. MCCB as per following details/ specifications:

250 Amp 415 volts, 35 KA TP+NL MCCB with variable current settings and having microprocessor based

O/L, S/C & E/F protection release.

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

ON, OFF, TRIP indication (LED Type).

iii) 2 Nos. MCCB as per following details/ specifications:

63 Amp 415 volts, 35 KA TP+NL MCCB with thermal magnetic release having variable current settings.

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 22_R5

Page 105: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

ON, OFF, TRIP indication (LED Type).

iv) 6 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker.

MV PANEL (NORMAL) AUDI as mentioned above

Set 1

4.03 SUB MV PANEL (NORMAL) Conference Hall

a) INCOMER:

250 Amp 415 volts, 35 KA FP MCCB with variable current settings and having microprocessor based O/L,

S/C & E/F protection release.S/C & E/F protection release.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB

ON, OFF, TRIP indication (LED Type)

Extended rotary operating mechanism with door interlocking with defeat feature and padlock facility. MCCB

should have spreader links & phase barriers.

1 No. 0 to 500 V Digital voltmeter with selector switch.

Digital ammeter with selector switch with one set Suitable C.Ts.

b) BUSBARS:

400 Amp TPN Aluminium busbars

c) OUTGOING:

i) 1 Nos. MCCB as per following details/ specifications:

63 Amp 415 volts, 35 KA TP+NL MCCB with thermal magnetic release having variable current settings.

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 23_R5

Page 106: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

ON, OFF, TRIP indication (LED Type).

ii) 2 no. 100 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker.

iii) 6 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker.

MV PANEL (NORMAL) Confernce Hall as mentioned above

Set 1

4.04 Main MV PANEL (Normal) Hostel Block

a) INCOMER:

200 Amp 415 volts, 35 KA , FP MCCB with thermal magnetic release having variable current settings.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB

ON, OFF, TRIP indication (LED Type)

Extended rotary operating mechanism with door interlocking with defeat feature and padlock facility. MCCB

should have spreader links & phase barriers.

1 No. 0 to 500 V Digital voltmeter with selector switch.

Digital ammeter with selector switch with one set Suitable C.Ts.

b) BUSBARS:

400 Amp TPN Aluminium busbars

c) OUTGOING:

i) 1 Nos. MCCB as per following details/ specifications:

100 Amp 415 volts, 35 KA TP+NL MCCB with thermal magnetic release having variable current settings.

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

ON, OFF, TRIP indication (LED Type).

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 24_R5

Page 107: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

ii) 3 Nos. MCCB as per following details/ specifications:

63 Amp 415 volts, 35 KA TP+NL MCCB with thermal magnetic release having variable current settings.

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

ON, OFF, TRIP indication (LED Type).

iii) 2 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker.

iv) 6 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker.

Main MV PANEL (Normal) Hostel Block as mentioned above

Set 1

4.05 SUB MV PANEL (NORMAL) Hostel Part- B

a) INCOMER:

100 Amp 415 volts, 35 KA , FP MCCB with thermal magnetic release having variable current settings.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB

ON, OFF, TRIP indication (LED Type)

Extended rotary operating mechanism with door interlocking with defeat feature and padlock facility. MCCB

should have spreader links & phase barriers.

1 No. 0 to 500 V Digital voltmeter with selector switch.

Digital ammeter with selector switch with one set Suitable C.Ts.

b) BUSBARS:

300 Amp TPN Aluminium busbars

c) OUTGOING:

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 25_R5

Page 108: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

i) 6 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker.

MV PANEL (NORMAL) Hostel Part- B as mentioned above

Set 1

4.06 MV PANEL (NORMAL) Guest House

a) INCOMER:

200 Amp 415 volts, 35 KA , FP MCCB with thermal magnetic release having variable current settings.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB R,Y&B phase indicating lamp (LED type) with 6A control SP MCB

ON, OFF, TRIP indication (LED Type)

Extended rotary operating mechanism with door interlocking with defeat feature and padlock facility. MCCB

should have spreader links & phase barriers.

1 No. 0 to 500 V Digital voltmeter with selector switch.

Digital ammeter with selector switch with one set Suitable C.Ts.

b) BUSBARS:

400 Amp TPN Aluminium busbars

c) OUTGOING:

i) 4 Nos. MCCB as per following details/ specifications:

63 Amp 415 volts, 35 KA TP+NL MCCB with thermal magnetic release having variable current settings.

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB

should be with spreader link and phase barriers.

ON, OFF, TRIP indication (LED Type).

ii) 2 no. 63Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker.

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 26_R5

Page 109: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

iii) 6 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker.

MV PANEL (NORMAL) Guest House as mentioned aboveSet 1

TOTAL SUB HEAD 4 : MV PANEL AS MENTIONED ABOVE

5.00 SUB HEAD- 5: MCB DISTRIBUTION BOARDS.

MCB DISTRIBUTION BOARD

5.01 Supplying & fixing following way, three pole and neutral sheet steel, MCB distribution board, 415 volts,on

recess/surface complete with loose wire box, terminal blocks, tinned copper busbar, neutral link, earth bar,din

bar, detachable gland plate, interconnections, phosphatized and powder coated including earthing connection

bolt etc. as per technical specifications and as required.(but without MCB & RCCB).

i 4 way (8+12), Double door Each 9

ii 6 way (8+18) Double door Each 15

iii 8 way (8+24), Double door Each 2

5.02 Supplying & fixing following way, single pole and neutral,sheet steel, MCB distribution board, 240 volts,on

recess/surface complete with loose wire box, terminal blocks, tinned copper busbar, neutral link, earth bar,din

bar, detachable gland plate, interconnections, phosphatized and powder painted including earthing etc.Before

procurement of DB the contractor has to take approval of DB schedule/ drawing of each DB from the

Electrical Engineer, HSCC, as per technical specifications and as required.(but without MCB & RCCB),

5.03 Supplying & fixing 6 Amps to 32 Amps rating, 240 volts,'B' series, miniature circuit breaker suitable for

lighting & other loads of following poles in the existing MCB DB complete with connections, testing &

commissioning etc. as per technical specifications & as required.

i Single poleEach 426

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 27_R5

Page 110: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

5.04 Supplying & fixing following rating, four pole, 415 volts, Miniature Circuit Breaker (MCB),in the existing

MCB DB complete with connections, testing & commissioning etc. as per technical specifications and as

required.

i 25 Amps Each 9

ii 40 Amps Each 4

iii 63 Amps Each 13

5.05 Supplying & fixing following rating, four pole, 415 volts, Residual Current Circuit Breaker (RCCB) having a

sensitivity current upto 300 mA in the existing MCB DB complete with connections, testing &

commissioning etc. as per technical specifications and as required.

i 25 Amps Each 9

ii 40 Amps Each 4

iii 63 Amps Each 13

5.06 Supplying and fixing following rating, Double Pole, 240 volts, MCB (B/C/D/ Curve) in the existing MCB DB

complete with connections, testing and commissioning etc. as required.

i 40 amp Each 1

5.07 Supplying & fixing following rating, Double pole, 240 volts, Residual Current Circuit Breaker (RCCB)

having a sensitivity current upto 300 mA in the existing MCB DB complete with connections, testing &

commissioning etc. as per technical specifications and as required.

i 40 amp Each 1

5.08 Supplying and fixing Single pole Blanking plate in the existing MCB DB complete as required.

Each 40

TOTAL SUB HEAD-5 : MCB DISTRIBUTION BOARDS AS MENTIONED ABOVE

SUB HEAD 6: WIRING

6.00 WIRING

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 28_R5

Page 111: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

6.01 i Wiring for light point/fanpoint/ exhaust fan point/call bell point with 1.5 sq.mm. PVC insulated, fire retardant

low smoke (FRLS) copper conductor cable, single core/ multi strand, in steel conduit (Including supplying &

recess laying of MS conduit and accessories) including the following and complete as required.

ii Supplying and Fixing Modular type switches (modular Bell push in case of call bell points) in suitable size

modular metal boxes, base plate & modular cover plates, space for fixing electronic fan regulator in case of

fan point wiring & space for fixing 5A socket on the board etc.

iii Supplying and fixing Hexagonal fan Boxes with 3 mm thick hylem sheet covers in case of Fan Points

iv Supplying & Fixing Ceiling Rose in case of Exhaust Fan Points etc.

Note :Note :

i) Unless otherwise specified all the conduiting work to be done in recess

Point wiring as mentioned above Group B Point 550

Point wiring as mentioned above Group CPoint 515

6.02 i Wiring for twin control light points with 1.5 sq.mm. PVC insulated, FRLS copper conductor cable in MS

conduit (including supplying and recess laying of MS conduit) including the following and complete as

required.

ii Supplying and Fixing Modular type two numbers 2 Way switches in suitable size modular metal boxes, base

plate & modular cover plates etc.

Note :

i) Unless otherwise specified all the conduiting work to be done in recess

Wiring for twin control light points as mentioned above Point 94

6.03 Wiring for Submain/ circuit wiring with following size of PVC insulated FRLS copper conductor single

core/multi strand cable in recessed steel conduit (including supply & laying of recessed conduit) as required.

i 2X1.5 Sqmm with 1 No. 1.5 sqmm PVC FRLS insulated, copper conductor for earthing.Metre 1530

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 29_R5

Page 112: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

ii 2X2.5 Sqmm with 1 No. 2.5 sqmm PVC FRLS insulated, copper conductor for earthing.

Metre 2369.00

iii 2X4 Sqmm with 1 No. 4 sqmm PVC insulated FRLS copper conductor for earthingMetre 1710

iv 2X6 Sqmm with 1 No. 6 sqmm PVC insulated FRLS copper conductor for earthingMetre 440

v 2X10 Sqmm with 1 No. 10 sqmm PVC insulated FRLS copper conductor for earthingMetre 50

vi 4X4 Sqmm with 2 No. 4 sqmm PVC insulated FRLS copper conductor for earthingMetre 180

vii 4X6 Sqmm with 2 No. 6 sqmm PVC insulated FRLS copper conductor for earthingMetre 375

viii 4X10 Sqmm with 2 No. 10 sqmm PVC insulated FRLS copper conductor for earthingMetre 100

ix 4X16 Sqmm with 2 nos 16 sq mm PVC insulated FRLS copper conductor for earthing.

Metre 50

6.04 Supplying and fixing suitable Module GI box on surface or in recess including providing and fixing 3 pin 5/66.04 Supplying and fixing suitable Module GI box on surface or in recess including providing and fixing 3 pin 5/6

amps. modular socket outlet with shutters and 5/6 amps. modular type switch with indicator type, base plate,

modular cover plate, connections etc. and all civil works 'complete as required.

Each 135

6.05 Supplying and fixing suitable modular GI box on surface or in recess including providing and fixing 13/6 A

international Socket Plus modular socket outlet with shutters and 13/6 A modular switch with indicator,

base plate, modular cover plate, connections, etc. and all civil works complete as required.

Each 10

6.06 Supplying and fixing suitable modular GI box on surface or in recess including providing and fixing 6 pin

15/16 A modular socket outlet with shutters and 15/16 A modular switch with indicator, base plate, modular

cover plate, connections, etc. and all civil works complete as required.

Each 114

6.07 Supplying and fixing suitable Modular metal box on surface or in recess including providing and fixing three

nos 3 pin 5/6 amps. modular socket outlet with shutters and one no. 10 amps. modular type switch, base

plate, modular cover plate, connections etc. and all civil works 'complete as required. ( For computer

Points)

Each 26

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 30_R5

Page 113: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

6.08 Supplying and fixing suitable Modular metal box surface or in recess including providing and fixing two

nos 3 pin 5/6 amps. modular socket outlet with shutters and one no. 5 amps. modular type switch, base plate,

modular cover plate, connections etc. and all civil works 'complete as required. ( COMBO POINT2 )

Each 18

6.09 Supplying and fixing suitable module modular GI box on surface or in recess including providing and fixing

3 pin 20 A modular socket outlet with shutters and 20 AMP SP MCB, base plate, modular cover plate, etc.

on surface or recess complete with all accessories including connections, testing and commissioning etc. as

required.

Each 20

6.10 Supply and fixing following 20 Amps, 240 volts, 2P+E, Industrial Socket Outlet (with plugs) in a metal box

with 20 SP MCB in a sheet steel cover on surface or recess complete with all accessories including

connections, testing and commissioning etc. as required.

Each 10Each 10

6.11 Supply and fixing following 32 Amps, 240 volts, 2P+E, Industrial Socket Outlet (with plugs) in a metal box

with 32 DP MCB in a sheet steel cover on surface or recess complete with all accessories including

connections, testing and commissioning etc. as required.

Each 2

6.12 Supply and fixing following 63 Amps, 240 volts, TPN , Industrial Socket Outlet (with plugs) in a metal box

with 63 FP MCB in a sheet steel cover on surface or recess complete with all accessories including

connections, testing and commissioning etc. as required.

Each 4

Supplying, providing & fixing cordless musical bell with batteries etc of approved make complete as

required.

Each 11

6.13

Supply and fixing following FP MCCB, 415 volts, 35 KA (Isc), Four Pole with thermal magnetic release

having variable current setting (0.8 to 1.0 In) with Extended rotary operating mechanism including door

interlocking with defeat feature and padlock facility in a sheet steel enclosure on surface complete with all

accessories including , connections, testing and commissioning etc. as required.

6.14 i 63 Amp Each 1

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 31_R5

Page 114: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

6.15 Supplying and fixing suitable Modular metal box surface or in recess including providing and fixing one

no.32A DPmains switch with one no. key ring modular type switch, base plate, modular cover plate,

connections etc. and all civil works 'complete as required. Anchor 21770,20868 or approved equivalent) (key

lock)Each 10

6.16 Supply, installation, testing and commissioning of 16 Amp. IP 66/56 power switch and socket in suitable

enclosure consisting of the following as per technical specifications and as required.

Switch:

Single pole, 250 V, 16 amp without enclosure similar to Schneider Electric-Clipsal model no. 56SW116LE-

GY or approved equivalent.

Socket

16 amp, 3 round pin socket out let, Indian standard, without enclosure similar to Schneider Electric-Clipsal

model no. 56SO116RP-LE-GY-EX or approved equivalent.

Angle Plug

16 amp, 3 pin, 250 V, Indian Standard similar to Schneider Electric-Clipsal model no. 56PA316RP-GY-EX

or approved equivalent.

Mounting Enclosure

Mounting enclosure for the above mentioned switch and sockets as supplied by Schneider Electric- Clipsal

model no. 56E2 GY or approved equivalent

Supply , installation, testing and commissioning of above mentioned power switch and socket.

point

6.17 Light Control Box

Supply, installation, testing and commissioning of light control box for animal room's light and dark cycle in

suitable enclosure consisting of the following as per technical specifications and as required.

Incomer:

6-32 A, DP, 10 KA C curve MCB

Power Contactor

3 pole , 9 amp AC3 duty , wide band 220 V coil

Time Switch

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 32_R5

Page 115: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

Digital time switch suitable for daily and weekly application, having minimum 8 ON/OFF function and 4

mode manual over ride and LED indication for relay status with a battery backup of 1500 hours and shortest

switching time 1 minute. Similar to L&T-GIC Crono 62DDT0 or approved equivalent.

Mounting Enclosure

Mounting enclosure in powder coated MS for the above mentioned items

Supply , installation, testing and commissioning of above light control box. Nos.

TOTAL SUBHEAD: 6- WIRING AS MENTIONED ABOVE

SUB HEAD 7: LIGHT FIXTURE AND FANS

7.00 LIGHT FIXTURES AND FANS

7.01 Supply of following light fixture with high efficiency electronic ballast, starter, tubes/lamps, capacitor,

reflector, diffuser, MS body/housing holder etc. complete with all fixing accessories as required.

i 1X28 watt box type fluorescent light fixture (Philips Mirolta Slim T5 TMS540 HF or approved equivalent)

(136bw )Each 52

ii 1X36 watt surface mounted type fluorescent light fixture with opal acrylic diffuser (Philips TCS019 1XTL-

D36W EBT or approved equivalent) (136AC1)Each 32

iii 2X36 watt surface mounted type fluorescent light fixture with opal acrylic diffuser (Philips TCS019 2XTL-

D36W EBT or approved equivalent) (236AC1)

Each 26

iv 1X 36 watt Surface / Recess Mounted flourscent light fixture (Philips TCS 306 1XTL-36W EBE or approved

equivalent). (136 SMO1)Each 29

v 1XTL-5 28 watt box type fluorescent light fixture without reflector(Philips TMS 122M 1XTL5 28 W EBT

or approved equivalent) (136b/136w)Each 48

vi 1XTL-5 28 watt box type fluorescent light fixture with reflector(Philips TMS 122M 1XTL5 28 W EBT or

approved equivalent) (136b/136w)Each 45

vii 4 X 14 /2x28 watt Recess Mounted flourscent light fixture (Philips TBS 088 4XTL5 -14 W EBP M2 or

approved equivalent). (236 RMSQ1)Each 35

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 33_R5

Page 116: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

viii 4 X 14/2x28 watt Recess Mounted flourscent light fixture (Philips TBS 869 4XTL5 -14 W EBP D8 /TBS

869 2XTL5 -28 W EBP D8 or approved equivalent). (236 RMO1)Each 63

ix 2X28 watt box type flourescent light fixture with reflector (Philips TMS 122M2XTL528 W EBT or

approved equivalent) (236b)Each 109

x 2X 36 watt recess mounted clean room flourscent light fixture with bottom opening and Clear

acrylic version (Philips TBS 670 2X36W TLD FOP GT or approved equivalent).Each 50

xi 4X 14 watt recess mounted clean room flourscent light fixture with bottom opening and Clear

acrylic version (Philips TBS651 4 XTL5 -14 W EB CR FOP GT or approved equivalent).

Each 40

xii 2X 28 watt surface mounted clean room flourscent light fixture with Clear acrylic version (Philips

TCS 450 2 x TL5 -28 W EBT or approved equivalent).Each 30

7.02 Supply of following compact fluorescent light fixture with electronic ballast, starter, capacitor, yellow light7.02 Supply of following compact fluorescent light fixture with electronic ballast, starter, capacitor, yellow light

lamps, reflector, diffuser, MS body/housing holder etc. complete with all fixing accessories as required.

i 1x9 watt Bulk Head light fixture (Philips FXC 101 1XPL-S/2P11 W AC GR or approved equivalent) BH

Each 25

ii 2X13 watt Mirror top with frosted glass (Decon 05CZ 06 or approved equivalent) (w toilet)

Each 49

iii Surface mounted Batten holder (Plastic) with 13 watt CFL

Each 4

iv 2 X 18 watt surface mounted down light frosted glass (DECON:PL-2X18 W 03NBG 01 or approved

equivalent) (DL1)Each 32

v 2 x9 W recessed flush mounted light fixture (Anchor 92586 or approved equivalent ) (NLWM)

Each 12

vi LED Surface mounted down light fixture (Philips DN170C LED 10S -6500PSU WH or approved

equivalent ) DL1Each 220

vii LED recessed flush mounted down light fixture (Philips DN194B LED 15S -4000PSU WH or approved

equivalent ) dl2Each 40

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 34_R5

Page 117: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

viii Exit light of pendant mounted maintained type 'EXIT' LED light with inbuilt battery pack for one hour

duration.(Crompton greaves EXL/S/1/SE/H/DD or aproved equivalent)Each 4

ix 2x13 watt non louvered path light with frosted glass of green colour. ( Decon 54 OP 08 or approved

equivalent )Each 46

x 2X18 W recessed flush mounted down light fixture (Philips FBS 075 2X18 PL-C HFB or approved

equivalent ) Each 65

xi 2 X 18 watt surface mounted down light clear glass (DECON:PL-2X18 W 03NBS 01 or approved

equivalent) (DL0)Each 10

7.03 Supply of following ceiling fans (Crompton Greaves High Breeze or approved equivalent) complete with

double ball bearing, motor, blades, downrod, canopies, capacitor, modular type electronic fan regulator,

suitable for operation on 230 volts, 50 Hz., 1 phase, AC supply complete as required.suitable for operation on 230 volts, 50 Hz., 1 phase, AC supply complete as required.

i 1200 mm sweep Each 207

ii 900mm Sweep Each 5

7.04 Supply of 900 RPM, 300 mm (Crompton Greaves Trans Air or approved equivalent) exhaust fan suitable for

single phase 230 volts, 50 Hz., AC supply complete with motor, louvers/shutters etc. complete as required.

Each 66

7.05 Supply of 400 mm sweep, Crompton greaves model high flow 16'' wall mounted fan complete with double

ball bearing, motor, blades, capacitor etc suitable for single phase 230 volts, 50 Hz., AC supply, complete as

required.

Each 4

7.06 Installation, testing and commissioning of prewired, fluorescent fittings of all types, complete with all

accessories and tube etc. directly on ceiling/wall, including connections with 1.5 sq.mm. PVC insulated,

FRLS copper conductor, single core/ multi strand cable etc. as required.

Each 342

7.07 Installation, testing and commissioning of prewired, compact fluorescent lamp fixture (CFL fixtures)of all

types, complete with all accessories and lamp etc. directly on ceiling/wall, including connections with 1.5

sq.mm. PVC insulated, FRLS copper conductor, single core/ multi strand cable etc. as required.

Each 505

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 35_R5

Page 118: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

7.08 Installation, testing and commissioning of ceiling fan and modular type electronic fan regulator(Electronic

regulator to be fixed in switch board) including wiring the down rod and connection with 1.5 sqmm FR PVC

insulated, copper conductor single core/multi strand cable including providing & fixing phenolic laminated

sheet cover on the fan box, etc. as required.

Each 192

7.09 Installation, testing and commissioning of exhaust fan up to 400 mm sweep in the opening, including

making the hole to suit the size of the above fan including , fixing of louvers/ shutters with frame making

good the damages etc. as required.

Each 66

7.10 Installation, testing and commissioning of wall mounted fan up to 400 mm sweep including supply and fixing

wall bracket arrangement complete as required.

Each 4

7.11 Supplying,installation, testing and commissioning of Passive Infrared(PIR) technology based occupancy7.11 Supplying,installation, testing and commissioning of Passive Infrared(PIR) technology based occupancy

sensor having high preformance, non regulating programmable type, suitable for connected load upto 10Amp

, for mounting height up to 2.8 mtr and for 5 m diameter coverage area along with necessary fixing

arrangements i/c programming at site etc. complete as required.

Each 342

TOTAL SUBHEAD 7 : LIGHT FIXTURE & FANS AS MENTIONED ABOVE

SUB HEAD 8: TELEPHONE SYSTEM

8.00 TELEPHONE SYSTEM

8.01 Supplying drawing, connecting and testing of 0.5mm dia annealed copper conductor PVC

insulated PVC sheathed telephone Wire/cables in Existing M.S/ PVC conduit or a racks as required.

i 2 pair Telephone cable. (0.5 sq mm)

Meter 745

8.02 Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including

painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit

as required.

i 20 mm Metre 755

ii 25 mm Metre 145

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 36_R5

Page 119: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

8.03 Supply, fixing, connecting and testing of telephone modular sockets modular plate anodised MS box

and blanking plate in surface / recessed including connectionetc as required.

i Telephone socket outlet (RJ-11 telephone Jack Single with Shutter)Each 26

ii Telephone socket outlet (RJ- 11 telephone Jack double with Shutter) Each 5

8.04 Supplying, Installation, testing and commissioning of following sizes of telephone distribution board in M.S.

hinged type lockable box duly painted complete with Krone type tag block etc. including terminations of

cable as required.

i 20 Pair Each 1

ii 10 Pair Each 4

8.05 Supplying and drawing of following pairs 0.5mm dia annealed bare copper conductor Polythene insulated,

core twisted into pairs armoured telephone cable on surface/tray with saddels including termination of cablescore twisted into pairs armoured telephone cable on surface/tray with saddels including termination of cables

at both sides in Krone Tag Block etc. complete as required.

i 20 Pair Metre 10

ii 10 Pair Metre 90

8.06 Supplying and drawing of following pairs 0.5 mm dia annealed bare copper conductor Polythene insulated,

core twisted into pairs armoured jelly filled telephone cable in the existing trench/ hume pipe/ GI pipe etc

with saddels etc. including terniation of cables in both sides at krone tag block complete as required.

i 50 Pair Metre 50

ii 30 Pair Meter 20

TOTAL SUBHEAD 8: TELEPHONE SYSTEM & EPABX AS MENTIONED ABOVE

SUBHEAD 9:CONDUITING FOR COMPUTER SYSTEM .

9.00 CONDUITING FOR COMPUTER SYSTEM .

9.01 Supply and fixing of following sizes of MS conduit along with the accessories in surface/recess including

painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit

as required

i 20 mm dia Metre 700

ii 25 mm dia Metre 200

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 37_R5

Page 120: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

9.02 Supplying and fixing two module modular plate in recess flush mounted with clear acrylic cover (suitable for

RJ-45 computer socket) with GI box complete as required.

Each 34

TOTAL SUBHEAD 9: CONDUITING FOR COMPUTER SYSTEM AS MENTIONED ABOVE

SUB HEAD 10: CONDUTING FOR TV OUTLETS

10.00 CONDUITING FOR TV OUTLETS

10.01 Supply and fixing of following sizes of MS conduit along with the accessories in surface/recess including

painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit

as required

i 20 mm dia Metre 425

ii 25 mm dia Metre 20

10.02 Supplying and fixing 2 module modular metal box in recess flush mounted with clear acrylic cover with

modular cover plate including fixing 1 no. coaxial TV outlet connection and all accessories complete as

requiredEach 17

10.03 Supply and drawing Coaxial TV Cable RG - 6 grade, 0.7 mm solid copper conductor PE insulated, shielded

with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC

conduit as required.Metre 510

TOTAL SUB HEAD 10: CONDUTING FOR TV OUTLETS AS MENTIONED ABOVE

11.00 SUBHEAD 11: ADDRESSABLE FIRE AND P.A SYSTEM

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 38_R5

Page 121: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

11.01 Supply, installation, testing and commissioning of Networkable Microprocessor based multiloop

capacity,Networkable analogue addressable type fire alarm control panel with minimum 640 character LCD

display / Touch Screen Display. The panel should be equipped with sufficient numbers of loop with 15%

Spare capacity in each loop. The panel shall be capable of taking atleast 200 analog addressable devices in

one loop in any combuination quantities of the Detectors and Devices.Four access levels, flash EPROM

sufficient numbers of programmable relay controls for controlling AHUs, pressurization fans, ventilation fans

at fire pump room, monitoring of fire sprinkler and fire hydrant pump, 240 volts AC power supply, automatic

battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then be

capable of operating the system for 2 hours during an emergency conditions as required. The Panel shall be

compatiable for backnet card for BMS interfacing. (UL/ VDS / EN Approved)

i 1 Loop Capacity Nos. 1

11.02 Supply, installation, testing and commissioning of Networkable & Microprocessor based 640 ‐ characters11.02 Supply, installation, testing and commissioning of Networkable & Microprocessor based 640 ‐ characters

LCD / Touch Screen LCD Display Network Repeator panel. The LCD shall Display all events / detectors,

devices status of complete systems in the networked, The repeator shall be equipped with Mounting options

etc. (UL/ VDS / EN Approved)

Nos. 1

11.03 Supply, installation, testing and commissioning of Automatic Analog addressable Photo - Thermal

multicriteria detector with mounting Base, alarm LED . The Detector shall have automatic Electronic / dip

switch addressing feature & each of these shall be equipped with fault Isolator/ External Fault Isolator

complete with the GI Mounting Box and the hardware etc. as required.(UL/ VDS / EN Approved)

Nos. 12

11.04 Supply, installation, testing and commissioning of Automatic Analog addressable Photoelectric smoke

detector with mounting Base,alarm LED . The Detector shall have automatic Electronic /dip switch

addressing feature & each of these shall be equipped with fault Isolator/ External Fault Isolator complete

with the GI Mounting Box and the hardware etc. as required. (UL / EN Approved).

Nos. 12

11.05 Supply, installation, testing and commissioning of Automatic Analog addressable Fixed Temperature cum

rate of Rise type Heat detector with mounting Base, alarm LED . The Detector shall have automatic

Electronic / dip switch addressing feature & each of these shall be equipped with fault Isolator/ External

Fault Isolator complete with the GI Mounting Box and the hardware etc. as required.(UL/ VDS / EN

Approved)

Nos. 1

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 39_R5

Page 122: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

11.06 Supply, installation, testing and commissioning of Automatic Analog addressable Beam Detector unit

complete with Transmitter & Receiver Units of the suitable range. The Detector shall have automatic

Electronic dip switch addressing feature & each of these shall be equipped with fault Isolator/ External Fault

Isolator complete with the GI Mounting Box and the hardware etc. as required.(UL/ VDS / EN Approved)

Nos 3

11.07 Supply, installation, testing and commissioning of Automatic Analog addressable Duct Detector with Duct

Housing and Duct probe tubes complete with Photoelectric Smoke Detector with mounting Base, alarm LED

.The Detector shall have automatic Electronic/ dip switch addressing feature & each of these shall be

equipped with fault Isolator/ External Fault Isolator complete with the GI Mounting Box and the hardware

etc. as required.(UL/ VDS / EN Approved)

Nos. 1

11.08 Supply, installation, testing and commissioning of Automatic Addressable control module for AHU & Stair

Pressurization fan, The Module shall have automatic Electronic addressing feature & each of these shall be

equipped with fault Isolator complete with the GI Mounting Box and the hardware etc. as required. (UL /

EN Approved).

Nos. 3

11.09 Supply, installation, testing and commissioning of Automatic Addressable Monitor module for Flow Switch

Monitoring etc. The Module shall have automatic Electronic/ dip switch addressing feature & each of these

shall be equipped with fault Isolator/ external fault complete with the GI Mounting Box and the hardware

etc. as required.(UL/ VDS / EN Approved)

Nos. 1

11.10 Supply, installation, testing and commissioning of Dual LED Response indicator for indicating the activation

of the Remotely located Detector.Nos. 5

11.11 Supply, installation, testing and commissioning of Addressable Manual call Station. The Call Point shall

have automatic Electronic / dip Swich addressing feature & each of these shall be equipped with fault

Isolator / external fault isolator complete with the Mounting Box and the hardware etc. as required.(UL/

VDS / EN Approved) Nos. 2

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 40_R5

Page 123: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

11.12 Supply, installation, testing and commissioning of Liscenced GRAPHICAL alarm monitoring and

management Software to pin point the location of the Fire. The software shall identify the alarm events in the

System and shall graphically indicate the pin point area in the Floor Plans.

(At Control Room).

Nos. 1

11.13 Supply, installation, testing and commissioning of Networked PC BASED GRAPHICAL FACILITIES

MONITORING SYSTEM with Dual Core 2.0 GHz Pentium® IV processor with 512 MBytes of RAM with

22" flat‐screen LCD monitor, sound card. It shall and speakers, and 500 Giga Byte hard disk. It shall operate

under Microsoft® Windows® XP Professional / Windows Software, complete with ethernet port, DVD

Drive, 4 GB RAM, multimedia Speakers, Multimedia Keyboard, Optical wireless Mouse, 650 VA UPS etc.

complete as required. (At Control Room)

Nos. 1

11.14 Supply and laying of following size of M.S, Conduit pipe in recess including all accessories MS pull/junction

boxes, GI fish wire of 6 SWG, fixing hardware etc., including cutting, chasing

the walls/floor and plastering the chased portion and making good the damages etc., complete as required.

i 25 mm diaMeter 1500

ii 32 mm diaMeter 250

11.15 Supply and drawing of 2 C x 1.5 Sq.mm. Sheathed anneled flexible copper Conductor FRLS cablein existing

M. S. Conduit, Complete with termination and testing as per requirement.

Meter 2000

11.16 Supply and drawing of 4 C x 1.5 Sq.mm. anneled flexible copper Conductor, Copper breaded shielding and

overall Sheathed FRLS cable in existing M. S. Conduit, Complete with termination and testing as per

requirement.

Meter 300

11.17 Supply and drawing of two pair, 0.71 sq. mm ATC Copper conductor cable in existing M. S. Conduit,

Complete with termination and testing as per requirement.

Meter 150

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 41_R5

Page 124: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

11.18 Supply, installation, testing and commissioning of 12 U, 19" Equipment Rack with power coated finish with

front lockable Door with M. S. Framed translucent Acrylic material, 2 Nos of fans for heat exhaust, Top &

Bottom entry knock outs, back side lockable Door , inbuilt MCB, Power Points, raceways and partitions, one

no. sliding Tray etc. complete as required to house the PC and other Equipment.

Nos. 1

11.19 CONVENTIONAL FIRE DETECTION AND ALARM SYSTEM (MICROPROCESSOR BASED

SYSTEM) For Residential Complex

i) Supply, Installation, Testing & Commissioning of Main fire alarm panel of 4 Zone microcontroller based with

its own fire detection zone interface card for initiating and indicating devices , power supply & Batteryits own fire detection zone interface card for initiating and indicating devices , power supply & Battery

Charger. with LED for fault / isolate / fire alarm condition, short, open condition The batteries shall be

sufficient for 30 Mins. in alarm Condition and 48 Mins in normal condition.

Nos. 2

11.20 Supply, installation, testing & commissioning of MANUAL CALL POINT complete with UPVC box duly

painted in red colour including connections etc.

Nos. 12

11.21 Supply, Installation, testing & commissioning of Hooter Cum Speaker with 24 volt circuit complete as

required

Nos. 12

11.22 Supply, Installation, testing & commissioning of Optical smoke detector with mounting base complete as

requiredNos. 2

TOTAL SUB HEAD 11 :ADDRESSABLE FIRE AND P.A SYSTEM

12.00 SUB HEAD 12: SOLAR PHOTVOLTAIC POWER GENERATION

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 42_R5

Page 125: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

12.01 Supply, installation, testing and commissioning of grid interactive roof top solar photovoltaic power

generation system of following grid interactive solar inverters, Data logger with temperature and irriadance

sensor, AC Distribution Board,Cables, interconnections, chemical earthing, GI Strip(25mmx5mm) etc.

complete as required.

i 5KWpset 1

12.02 Extra for providing space frame for above 5KWp solar system. set 1

TOTAL SUB HEAD 12: SOLAR PHOTVOLTAIC POWER GENERATION AS MENTIONED

ABOVE

SUB HEAD 13: LT CABLES

13.00 LT CABLES13.00 LT CABLES

13.01 Supply of following sizes of 1.1 kV grade multicore aluminium conductor PVC sheathed armoured XLPE

cable as per IS 7098.

i 3.5 Core 25 Sqmm. Metre 400

ii 3.5 Core 50 Sqmm. Metre 300

iii 3.5 Core 70 Sqmm. Metre 120

iv 3.5 Core 95 Sqmm. Meter 100

v 3.5 Core 120 Sqmm. Mter 300

vi 3.5 Core 150 Sqmm. Meter 230

vii 3.5 Core 185Sqmm. Metre 150

viii 3.5 Core 240 Sqmm. Metre 100

ix 3.5 Core 300 Sqmm. Metre 750

x 4 Core 16 Sq mm Metre 250

xi 4 Core 10Sq mm Metre 200

xii 4 Core 6 Sq mm Meter 100

xiii 3 Core 6 Sqmm. Meter 100

xiv 3 Core 4 Sqmm. Meter 100

xv 2 Core 10 Sq mm Metre 500

xvi 2 Core 16 Sq mm Meter 1000

13.02 Laying of one number PVC insulated and PVC sheathed power cable 1.1kV grade direct in ground including

excavation, sand cushioning, protective covering and refilling the trench etc. as required

i Up to 35 sq.mm Metre 1855

ii Above 35 Sq mm and upto 95 Sq mm Metre 294

iii Above 95 Sq mm and up to 185 Sq mm Metre 476

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 43_R5

Page 126: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

iv Above 185 Sq mm and up to 400 Sq mm Metre 700

13.03 Laying of one number PVC insulated and PVC sheathed power cable 1.1kV grade direct in the existing RCC/

Hume/Stoneware/Metal pipe as required

i Up to 35 sq.mm Metre 398

ii Above 35 Sq mm and upto 95 Sq mm Metre 63

iii Above 95 Sq mm and up to 185 Sq mm Metre 103

iv Above 185 Sq mm and up to 400 Sq mm Metre 151

13.04 Laying of one number PVC insulated and PVC sheathed power cable 1.1kV grade on surface or on existing

cable tray complete as required.

i Up to 35 sq.mm Metre 398

ii Above 35 Sq mm and upto 95 Sq mm Metre 63

iii Above 95 Sq mm and up to 185 Sq mm Metre 103

iv Above 185 Sq mm and up to 400 Sq mm Metre 151iv Above 185 Sq mm and up to 400 Sq mm Metre 151

13.05 Supplying and making end termination with suitable size aluminium lugs including double compression

glands of following sizes of 1.1. kv grade multicore aluminium conductor PVC insulated and PVC sheathed

i 3.5 Core 25 Sqmm. Each 20

ii 3.5 Core 50 Sqmm. Each 10

iii 3.5 Core 70 Sqmm. Each 10

iv 3.5 Core 95 Sqmm. Each 6

v 3.5 Core 120 Sqmm. Each 12

vi 3.5 Core 150 Sqmm. Each 14

vii 3.5 Core 185Sqmm. Each 14

viii 3.5 Core 240 Sqmm. Each 4

ix 3.5 Core 300 Sqmm. Each 18

x 4 Core 16 Sq mm Each 26

xi 4 Core 10Sq mm Each 18

xii 4 Core 6 Sq mm Each 6

xiii 3 Core 6 Sqmm. Each 10

xiv 3 Core 4 Sqmm. Each 10

xv 2 Core 10 Sq mm Each 80

xvi 2 Core 16 Sq mm Each 30

TOTAL SUBHEAD 13: LT CABLES AS MENTIONED ABOVE

SUBHEAD 14: EARTHING

14.00 EARTHING

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 44_R5

Page 127: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

14.01 Earthing with copper plate 600mmX600mmX3mm thick including accessories, and providing masonary

enclosure with cover plate having locking arrangement and watering pipe etc., including charcoal or coke

and salt complete as required.Set 12

14.02 Earthing with GI plate 600mmX600mmX6mm thick including accessories, and providing masonary

enclosure with cover plate having locking arrangement and watering pipe etc., including charcoal or coke

and salt complete as required.

Set 24

14.03 Supplying and laying 25mmX5mm GI strip at 0.5m below ground level as strip earth electrode, including

soldering etc. as required.Metre 100

14.04 Providing and fixing 25mmX5mm GI strip on surface/on existing cable trench/RCC pipe/GI pipe or in recess

for earth electrode as required. Metre 350

14.05 Supplying and laying 50mmX6mm GI strip at 0.5m below ground level as strip earth electrode, including

soldering etc. as required.Metre 50

14.06 Providing and fixing 50mmX6mm GI strip on surface/on existing cable trench/RCC pipe/GI pipe or in recess

for earth electrode as required.Metre 100

14.07 Providing and fixing25mmX5mm Copper strip on surface/on existing cable trench/RCC pipe/GI pipe or in

recess for earth electrode as required.Metre 100

14.08 Supplying and laying 25mmX5mm Copper strip at 0.5m below ground level as strip earth electrode, including

soldering etc. as required.Metre 20

14.09 Supplying and laying 50mmX6mm Copper strip at 0.5m below ground level as strip earth electrode, including

soldering etc. as required.Metre 50

14.10 Providing and fixing 50mmX6mm Copper strip on surface/on existing cable trench/RCC pipe/GI pipe or in

recess for earth electrode as required.Metre 100

14.11 Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I.pipe from earth electrode including

connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required

Metre 30

14.12 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including

connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.

Metre 100

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 45_R5

Page 128: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

14.13 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.

Metre 500

14.14 Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC

collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and

refilling etc as required.

i) 300 mm diaMetre 100

ii) 150 mm diaMetre 200

TOTAL SUBHEAD 14: EARTHING AS MENTIONED ABOVE

SUBHEAD 15: LIGHTNING PROTECTION

15.00 LIGHTENING PROTECTION

15.01 Earthing with 600 mm X 600 mm X 6 mm thick GI plate including accessories, and providing masonary

enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal or coke and salt

complete as required. Set 16

15.02 Providing and fixing of lightening conductor finial, made of 25mm. dia. 300mm., long GI tube, having single

prong at top, with 85 mm. dia. 6 mm. thick GI base plate including holes etc. complete as required.

Each 12

15.03 Providing and fixing GI tape 20mm X 3 mm thick on parapet or surface of wall for lightning conductor as

required. (For horizontal runs).Metre 600

15.04 Providing and and fixing GI tape 20mm X 3 mm thick on parapet or surface of wall for lightning conductor

as required. (For vertical runs).Metre 300

15.05 Providing and fixing testing joint, made of 20mmX3mm thick GI strip, 125 mm. long, with 4 no.'s of GI

bolts, nuts, check nuts, bar shaddles, and spring washers etc. complete as required.

Each 16

15.06 Providing and laying GI tape, 32 mm X 6 mm thick, from test joint upto earth electrode directly in ground as

required. Metre 320

TOTAL SUBHEAD 15: LIGHTENING PROTECTION AS MENTIONED ABOVE

16.00SUB HEAD : 16 AUDITORIUM SOUND SYSTEM:

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 46_R5

Page 129: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

AUDITORIUM SOUND SYSTEM:

16.01

Supply Installation Testing & Commissioning of flying ,Line arrayble Full Size 12''/15", 2 Way, bi-ampable

speaker . The speaker cabinet must have frequency range of 60Hz-17kHz(-10dB), sensitivity (1W/1m)101

dB SPL or more, delviering Max SPL of 134dB or more with power handling pk 2000W or more. The

speaker should have a nominal impedance of 8 ohm .The speaker cabinet should have a horizontal coverage

angle of 60 and 90 degrees for better far and near field experiance.Speaker must have 8 or more suspension

points for permanenet installation.

Approved makes :Electro-Voice, Martin Audio, Renkus Heinz

Nos 4

16.02

Supply Installation Testing & Commissioning of OEM array frame

Nos 2

Supply Installation Testing & Commissioningof Powered 18" subwoofer with Freq. Range(-10 dB): 35 Hz -

16.03

Supply Installation Testing & Commissioningof Powered 18" subwoofer with Freq. Range(-10 dB): 35 Hz -

130Hz., delivering a Max. Calculated SPL of 130 dB or more.The loudspeaker should have Class D inbuilt

amplifier of 1800W or more

Approved makes :Electro-Voice, Renkus-Heinz,Martin AudioNos 2

16.04

Supply Installation Testing & Commissioning of 15" two way powered stage monitor Loudspeaker with

frequency response of 60Hz - 20kHz (-10dB), delivering Max SPL 125dB SPL Wideband.It should have

horizontal and vertical coverage angle of 90° and 50° degree or better. The loudspeaker should have inbuilt

amplfier of class D delivering a power of 800W or more.It should have integrated monitor angle on the

enclosure for use floor monitor

Approved makes :Electro-Voice, Martin Audio, Renkus Heinz pairs 2

16.05

Supply Installation Testing & Commissioning of dual 5''/4" LF or better two-way wall mounted loudspeaker

with frequency range of 65Hz-20kHz,with a sensitivity of 86dB(1W/1m) or more delivering a max SPL of

110dB or more.The louspeaker should have a horizontal coverage angle of 95 degree or more and vertical

coverage angle of 120 degree or more.It should have a power handling pk of 300W or more with nominal

impedance of 8 ohms.The loudspeaker should have integrated mounting bracket for permanent installation.

Transformer taps(100V/70V),30W,15W,7.5W

Approved makes :Electro-Voice, Martin Audio, Renkus Heinz

Nos 2

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 47_R5

Page 130: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

16.06

SITC of Class I/Class TD/Class H Dual channel power amplifier with specification as below or BETTER to

suit the power requirement of proposed speakers;

Max Midband Output Power:1150W @ 4 ohms,1750W @ 2 ohms,Max Bridged Output Power:3500W @ 4

ohms,Frequency Response:20Hz - 20 KHz,THD:<0.05%,Max input level:+21dBu,input

impedence:20kohm,signal to noise ratio : >110dB ,with built in protection such as Audio Limiters,

Temperature, DC, HF Short Circuit, Peak Current Limiters

Approved makes: EV, Camco,Powersoft

Nos 1

Supply Installation Testing & Commissioning of Dual channel power amplifier with specification as below

or BETTER to suit the power requirement of proposed speakers;

Max Midband Output Power:450W @ 4 ohms,650W @ 2 ohms,Max Bridged Output Power:1300W @ 4

ohms,Frequency Response:10Hz - 40 KHz,THD:<0.03%,IMD<0.1%,Max input

level:+21dBu,Crosstalk<80dB,input impedence:20kohm,signal to noise ratio : >105dB ,with built in

protection such as Audio Limiters, Temperature, DC, HF Short Circuit, Peak Current Limiters

Approved Makes: EV,Camco,Powersoft

16.07

Approved Makes: EV,Camco,Powersoft

Nos 1

16.08

Supply Installation Testing & Commissioning of 15W loudspeaker with inbulid transformer ( green Room &

Control Room)

Approved Makes : Bosh , Martin Audio, Renkus Heinz Nos 2

16.09

Supply Installation Testing & Commissioning of Power Amplifier with 120Watt at 70V/100V

Approved Makes : Bosh , Camco, Powersoft Nos 1

16.10

Supply Installation Testing & Commissioning of Digital Signal Processor with 2 x XLR IN, electronically

balanced audio input,6 x XLR OUT, electronically balanced audio output with 2 x XLR Thru out ,and 1x

XLR AES/EBU IN digital input,with Nominal Input Voltage:1.23V / +4 dBu, maximum input voltage:8.7V /

+21 dBu,input impedence :10k Ohm,CMR:-80dB@1kHz,A/D &D/A coversion :24 bit sigma delta,THD+N

<0.01% Approved make:EV,Martin Audio,

Bi-ampNos 1

16.11

Supply Installation Testing & Commissioning of 16 channel Mixer with 4 or more Auxiallary Outputs

Approved Makes: Yamaha, Bheringer,Allen Heath

Nos 1

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 48_R5

Page 131: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

16.12

SITC of Corded Vocal Microphone with Dynamic Neodymium Magnet microphone element,with frequency

response 80Hz-16kHz,Super-Cardioid polar pattern,sensitivity of 2.2mV/Pa and output impedence 600 ohm

Approved makes:EV, Sennhieiser, Shure

Nos 2

16.13

SITC of Corded Instrument Microphone with Self Biased condensor microphone element ,with frequency

response of 55Hz-16kHz ,Cardioid polar pattern,sensitivity of 5.5mV/Pa ,rated impedence of 200 ohm

,maximum spl :130dB SPL and dynamic range ;107dB Approved makes:EV, Sennhieser, Shure

Nos 2

Supply Installation Testing & Commissioning of Handheld Wireless Mic system that has a min of 14-hour

battery life from two AA alkaline batteries. Cardiod polar pattern,Dynamic microphone ,frequency response

16.14

battery life from two AA alkaline batteries. Cardiod polar pattern,Dynamic microphone ,frequency response

83Hz-18kHz,RF sensitivity < 1.0 Uv,Image rejection>55dB,Dyanmic range >95dB and receiver having 30

channels possible,S/N ratio >100dB A,dynamic range >95db B,distortion <1 %,frequency band:618-

634MHz,modulation:+/-40kHz

Approved Makes: EV, Sennhieser, Shure

Nos 2

16.15

Supply Installation Testing & Commissioning of Lapel Wireless Mic system that has a min of 14-hour battery

life from two AA alkaline batteries. uni-directional polar pattern,condensor microphone ,frequency response

83Hz-18kHz,RF sensitivity < 1.0 Uv,Image rejection>55dB,Dyanmic range >95dB and receiver having 30

channels possible,S/N ratio >100dB A,dynamic range >95db B,distortion <1 %,frequency band:618-

634MHz,modulation:+/-40kHz

Approved Makes: EV, Sennhieser, Shure

Nos 2

16.16

Supply Installation Testing & Commissioning of Freestanding Gooseneck Mic with base for podium having

back electret condensor microphone element ,Hyper Cardioid polar pattern,LED status display and with

programmable button for Push to Talk or Push to Mute functions having ,frequency response 50Hz-20kHz

,sensitivity 5.5mV/Pa,clipping level >130dB SPL ,output impendence 200 ohm

Approved makes:EV, Sennhieiser, Shure

Nos 1

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 49_R5

Page 132: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

16.17

Supply Installation Testing & Commissioningof DVD/CD player with USB input.

Approved makes :Philips,Sony,PanasonicNos 1

16.18

Supply Installation Testing & Commissioning of 30 W volume control for Speakers at Green room and

control .

Approved Makes: Bosch,Atlas,Ahuja Nos 2

16.19

INSTALLATION EQUIPMENT

i

Supply and installation of Speaker cable - 2 core 2.5 Sq.mm for loudspeakers .

Approved Makes :Finolex, Beldon, Sommer

Mtrs 200

Supply and installation of 2 core shielded Microphone Cable.

ii

Supply and installation of 2 core shielded Microphone Cable.

Approved Makes :Finolex, Beldon, Sommer

Mtrs 125

iii

Supply and Installation of Microphone Stand(3 big +3 small) with base

Nos 6

iv

Equipment Rack with lockable and front perforated doors. Approved

Makes :President,RittalNo's 1

v

Supply and Installation of XLR Socket / Connector with Suitable Accessories

Approved makes:Neutrik

Nos 1

TOTAL SUB HEAD : 16 AUDITORIUM SOUND SYSTEM AS MENTIONED ABOVE

17.00SUB HEAD : 17 AUDITORIUM LIGHTING SYSTEM:

AUDITORIUM LIGHTING SYSTEM:

17.01

Supply Installation Testing & Commissioning LED downlighter 18W , 1600 lumen , DALI Dimmbale same

as Philips cat no: DN 394B LED16S-4000 PSD WH or approved equivalent.

Nos 60

17.02

Supply Installation Testing & Commissioning of Led downlighter 24W , 2000 lumen , DALI Dimmbale

same as Philips cat no: DN 395B LED20S-4000 PSD WH . Approved makes :Philips or approved

equivalent.

Nos 120

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 50_R5

Page 133: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

17.03

Supply Installation Testing & Commissioning of HF Ballast Controller 12-Ch with all necessary Accessories

required same as Philips cat no: DDBC1200 or approved equivalent.

Nos 2

17.04

Supply Installation Testing & Commissioning of Dyn 12x20A Relay control with all necessary Accessories

required same as Philips cat no: (FR) DDRC1220FR-GL or approved equivalent.

Nos 2

17.05

Supply Installation Testing & Commissioning of Dyn Euro 10 Butt Config Panel same as Philips cat no:

DLPE9100 or approved equivalent.Nos 2

wiring for light point with 5X1. Sq.Mm. pvc insulated copper conductor FRLS cable in MS Conduit in recess

17.06

/ Surface including make good the surface , painting etc . As required ( 2nos wires shall run in separte

conduit )

Points 30

TOTAL SUB HEAD : 17 AUDITORIUM LIGHTING SYSTEM AS MENTIONED ABOVE

18.00SUB HEAD : 18 STAGE CURTAIN

Stage Curtain

18.01

Main curtain made out of velvet curtain cloth with horizontal sliding arrangement complete with fixing rails,

brackets, sliding arrangement and motorised operation complete with runners, master runners, pullies, 3mm

steel wire rope, motor of required capacity with 2 Nos. air breaker contactors, 2 nos. micro switches for auto

stop, 3 nos. push buttons for forward, reverse and stop positions. The curtain should be draped to half area

when in closed position. Min. overlap at centre should be 900mm and should be stitched in double gathering.

Set 1

18.02

Providing and fixing cloth wings made out of black glazed cotton cloth fixed on 6mm thick commercial

plywood fixed on one side of MS 50x25x16G pipe welded frame work. The pipe framework shall be made

out of 25x50mm pipe fixed at 900mm c/c with overhead pivot track complete with duly painted framework.

Set 1

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 51_R5

Page 134: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

18.03

Providing and fixing average frills made out of double gathering glazed cotton fabric to be installed above

stage with 25mm dia. GI pipe.

Set 2

TOTAL SUB HEAD : 18 STAGE CURTAIN AS MENTIONED ABOVE

19.00SUB HEAD 19: STAGE LIGHTING

STAGE LIGHTING

19.01

Supply, Installation, Testing and commissioning of 1000W 150mm double plano-convex lens profile spot

light complete with T-11 or equiv. lamps, barn door, filter frame, C-clamp, 1.5M 3x2.5 sq.mm. copper cable,

plug top etc. complete. Each 6

Supply, Installation, Testing and commissioning of 1000W Solar Fresnel spot light complete with all

19.02

accessories and T-11 lamp or equiv. lamps with imported glass, side/bottom sliding knob, 1.5M 3x2.5 sq.mm.

copper cable, plug top etc. as required.

Each 6

19.03

Supply, Installation, Testing and commissioning of 1000W Flood light complete with 1000W 189mm

halogen tube and other accessories and 1.5 m. 3x2.5 sq.mm. copper cable, plug top, etc. weather proof

complete. Each 6

19.04

Providing and fixing 3 Section telescopic stands made of steel tube for stage lighting mentioned above.

Each 4

TOTAL SUB HEAD -19 :STAGE LIGHTING AS MENTIONED ABOVE

SUBHEAD 20: OUT DOOR LIGHTING

20.00 OUT DOOR LIGHTING

20.01 Supply, erection, testing and commissioning of external swaged steel tubular pole with following

specifications & items :

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 52_R5

Page 135: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

i 9.0 Mtrs. high swaged steel tubular pole with arm length around 1.5 Metre, the construction of the pole shall

be as per IS:2713 - 1980 410 SP-30 with base plate 450mmX450mmX6mm complete as per requirement

with two coats of spray paints of approved shade.

ii 1X150 watts street light fixture with 150watts high pressure sodium vapour (HPSV) lamp complete with

control gear, acrylic cover cover etc. similar to Philips SRP 051/ 150 W or approved equivalent including its

wiring with 2X4 sq.mm. PVC insulated, FRLS copper conductor and 1.5 sqmm PVC insulated, FRLS

copper earth wire from control box complete as required.

iii Suitable size 32 A DP MS Control box with 2 no. incoming and outgoing terminals and 2 nos. tap-out

terminal with 6A DP MCB complete as required - 1 Set

iv Suitable number(s) 40mm dia Class-B GI Pipe(s) from above control box to upto 0.5 metre below ground

level for power cable entry

v Providing foundation including excavation, shuttering, alingment of poles, casting etc. including lean

concrete at the bottom as per CPWD/ BIS specifications.

vi The above installations shall be completed as CPWD specifications and as required

a. Steel Tubular Poles(9M) Single Arm as mention above Set 50

b. Steel Tubular Poles (9M) same as above but for Double Arm as mention above Set 16

20.02 Supply, installation, testing and commissioning of external post top lantern with following accessories and

complete as required :

i 4m high (3.3m above ground) 80mm dia GI pole as approved, adopting socket at top for fixture mentioned

below, base plate 300 x 300 x 6mm and provision for mounting junction box etc. - 1 set.

ii 1 x 70 W Post top lantern with 70W HPSV lamp (Philips SPC 101 x SON 70 W E or equivalent) and its

wiring with 2 x 2.5 sq.mm PVC insulated copper wire and 1.5 sqmm PVC insulated copper earth wire from

control box .

iii Suitable size 20A DP MS Control box with 2 no. incoming and outgoings terminals and 2 nos. tap-out

terminal with 1 nos. 5A HRC fuses complete 1 set.

iv Suitable number(s) 40mm dia Class-B GI Pipe(s) from above control box to upto 0.5 metre below ground

level for power cable entry

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 53_R5

Page 136: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

v Providing 400x400x1000mm deep 1:3:6 ratio cement concrete including excavation shuttering alignment of

poles casting etc. including 100mm thick lean concrete shall be provided at the bottom

Supply, installation, testing and commissioning of external post top lantern as mentioned above

Set 51

20.03 Supply, installation, testing and commissioning of Post top lantern with 70W SON lamp ( (Philips SPC 101 x

SON 70 W E or equivalent) and its wiring with 2 x 2.5 sq.mm PVC insulated copper wire and 1.5 sqmm

PVC insulated copper earth wire from control box - 1 set

set 8

20.04 Supply, installation, testing and commissioning of bollard lamps 1X18 watts CFL (Philips HCS360 1XPL-

C/2P 18W GR Sonara bollard in gree color or equivalent) control box - 1 set.

Each 28

20.05 Road Lighting Panel

Supply, installation, testing and commissioning of following outdoor type with canopy, IP-54 protected M.V.

cubicle type totally enclosed, free standing type, dust, damp and vermin proof, MV Panel, busbars, M.V.

danger notice plate, interconnections with suitable capacity aluminium leads/solid aluminium strips/rods,

connection of incoming and outgoing cables with thimbles, stove enamelled painted and having following

incoming and outgoing switchgears complete as required.

1 INCOMER:

100 Amps,415 volts, TP+NL, 35 KA Moulded Case Circuit Breaker with thermal magnetic release having

variable current settings .

R,Y&B phase indicating lamp (LED type) with 2A control SP MCB ,ON, OFF , TRIP for MCCB

Extended rotary operating mechanism with door interlocking with defeat feature and padlock facility. MCCB

should have spreader links & phase barriers.

1 Set of timer switch & 100A TP contactor with nuetral link (for street lights control) .

BUSBARS:

300 Amp TPN Aluminium busbars

OUTGOING:

i 30 Nos. 16 Amp 415 volts, DP MCB

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 54_R5

Page 137: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. Description. Unit.Total

QTY

Rate in Figures

(in Rs.)Rate in Words (in Rs.)

Amount

(in Rs.)

Feeder Pillar as mention above Set 5

20.06 Spiral earthing made out of 6 SWG GI wire , 50mm Dia, 115 turns closely wound ,1.5 mtr below ground,

earth pit of 350 Dia., 1.5 mtr depth including providing charcoal and salt for earthing at alternate layers of

300 mm depth (total 3 layers),connections etc. complete as required.

Set 84

TOTAL SUBHEAD 20: OUTDOOR LIGHTING AS MENTIONED ABOVE

HSCC_NIMR/ DWARKA/PHASE-II BOQ-E 55_R5

Page 138: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. DESCRIPTION Amount in Figures (in Rs.)

1SUBHEAD 1: H.T. SUB STATION.

2SUBHEAD 2: MAIN LT PANEL.

3 SUB HEAD 3: DG SET & ACCESSORIES

4SUB HEAD 4 :MV PANELS

5SUB HEAD- 5: MCB DISTRIBUTION BOARDS.

6SUB HEAD 6: WIRING

7SUB HEAD 7: LIGHT FIXTURE AND FANS

8SUB HEAD 8: TELEPHONE SYSTEM

9SUBHEAD 9:CONDUITING FOR COMPUTER SYSTEM .

10SUB HEAD 10: CONDUTING FOR TV OUTLETS

11SUBHEAD 11: ADDRESSABLE FIRE AND P.A SYSTEM

12 SUB HEAD 12: SOLAR PHOTVOLTAIC POWER GENERATION

13SUB HEAD 13: LT CABLES

14SUBHEAD 14: EARTHING

15SUBHEAD 15: LIGHTNING PROTECTION

BOQ OF ELECTRICAL WORKS FOR CONSTRUCTION OF GUEST HOUSE, AUDITORIUM BLOCK, HOSTEL BLOCK,

SUBSTATION & AC PLANT ROOM AT NIMR, DWARKA, NEW DELHI

HSCC_NIMR_Dwarka_Phase-II BOQ-E 62_R5

Page 139: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

S.No. DESCRIPTION Amount in Figures (in Rs.)

BOQ OF ELECTRICAL WORKS FOR CONSTRUCTION OF GUEST HOUSE, AUDITORIUM BLOCK, HOSTEL BLOCK,

SUBSTATION & AC PLANT ROOM AT NIMR, DWARKA, NEW DELHI

16SUB HEAD : 16 AUDITORIUM SOUND SYSTEM:

17SUB HEAD : 17 AUDITORIUM LIGHTING SYSTEM:

18SUB HEAD : 18 STAGE CURTAIN

19SUB HEAD 19: STAGE LIGHTING

20SUBHEAD 20: OUT DOOR LIGHTING

TOTAL FOR ALL ELECTRICAL WORKS

GRAND TOTAL FOR ALL ELECTRICAL WORKS (RS)

HSCC_NIMR_Dwarka_Phase-II BOQ-E 62_R5

Page 140: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

A) EQUIPMENTS

1.0 NDSR WATER CHILLING UNITS.

1.1

Supply, installation, testing & commissioning of 100 TR

(actual) capacity water cooled water chilling units as

specified and shown in equipment schedule complete as per

specifications with.a. Screw Compressor with motor.b. Drive package.c. Mounting frames for all componentsd. Water cooled condenser with accessories. e. Chiller with accessories.f. Refrigerant piping, fittings, accessories and valves etc.g. Insulation of chiller and suction line.h. First charge of refrigerant and oil.i. Base frame with Vibration isolatorsj. Automatic capacity control arrangement.k. Lot Safety controls, flow switches, pressure gauge,

thermometer etc. as per specifications. l. Suitable capacity motor with necessary insulation , soft

starter panel complete with all necessary switchgears and

control complete as requiredm. Necessary water drain &air purge valves wherever

requiredn. Necessary lubrication device as per specifications complete.

o.Microprocessor based control panel complete with

accessories as per specifications.

Chilled Water Leaving temp. 44 deg. FChilled Water Entering temp. 54 deg. FChiller fouling factor = 0.0005 (FPS units)

Condenser Water Leaving Temp. 97.5 deg FCondenser Water Entering Temp. 90 deg FCondenser fouling factor = 0.001 (FPS units)

Complete water chilling machine as above. 2 Nos

2.0 NDSR WATER CIRCULATION PUMPS

BOQ of HVAC Works for Guest House, Director's Bungalow, Auditorium & Conference, Substation & AC Plant Room at NIMR-Dwarka , New Delhi.

The prices are to be quoted in the below mentioned form and shall include the supply, installation, testing & commissioning at site of all the equipments, ancillary materials as specified and all such items what so ever which may be

required to fulfill the intent and purpose as laid down in the specifications and or the drawings.

The tenderer shall quote rates in figures and in words under column 6&7 and extend amount to column 8

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC1

Page 141: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

2.1 Chilled Water Pumps

Supply, installation, testing and commissioning of vertical

split casing end suction type centrifugal chilled water pump

sets factory assembled and tested for rated efficiency

mounted on a common base frame etc each capable of

delivering specified flow rate complete with following as per

specifications & schedule of equipments.

a. Pump with IP 55 TEFC induction motor with class F

insulationb. Channel base with vibration isolators, coupling, coupling

guard etc.c. Cladded insulation and anti corrosive coating inside and

outside casing etc. of chilled water pump.d. 2 Nos.- 150 mm dia dial type pressure gaugee. Pumps shall be suitable foroperation on 415+/- 10% Volts/

3ph / 50 Hz/AC power supply.The pump characteristic shall be as follows:

Water flow rate=240 USGPMHead = 20 Metre WC

Chilled water pumps as described above. 2 Nos

2.3 Condenser water Pumps

Supply, installation, testing and commissioning of vertical

split casing end suction type centrifugal pump sets factory

assembled and tested for rated efficiency mounted on a

common base frame etc each capable of delivering specified

flow rate complete with following as per specifications &

schedule of equipments.a. Pump with IP 55 TEFC induction motor with class F

insulationb. Channel base with vibration isolators, coupling, coupling

guard etc.c. Cladded insulation and anti corrosive coating inside and

outside casing etc. of chilled water pump.d. 2 Nos.- 150 mm dia dial type pressure gaugee. Pumps shall be suitable foroperation on 415+/- 10% Volts/

3ph / 50 Hz/AC power supply.The pump characteristic shall be as follows:

Water flow rate=400 USGPMHead = 18 Metre WC

Condenser water pumps as described above. 2 Nos.

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC2

Page 142: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

2.4 Hot water Pumps

Supply, installation, testing and commissioning of vertical

split casing type centrifugal hot water recirculation pump sets

factory assembled and tested for rated efficiency mounted on

a common base etc each capable of delivering specified flow

rate complete with following as per specifications & schedule

of equipments.

a. Pump with IP 55 TEFC induction motor with class F

insulationb. Channel base with vibration isolators, coupling, coupling

guard etc.c. Cladded insulation and anti corrosive coating/cathodic

electro deposit (CED) type coating inside and outside casing

etc. of hot water pump, etc.d. 2 Nos.- 150 mm dia dial type pressure gaugee. Pumps shall be suitable foroperation on 415+/- 10% Volts/

3ph / 50 Hz/AC power supply.The pump characteristic shall be as follows:

Water flow rate=70 USGPM

Head = 20 Metre WC

Hot water pumps as described above. ( 1W+1S) 2 Nos

3.0 NDSR COOLING TOWER

Supply, installation, testing and commissioning of induced

draft FRP type cooling towers for air conditioning system.

Each tower shall be complete with distribution system, filling,

louvers, steel ladder, fan and motor. Motor shall be IP 55

suitable for outdoor installation, 415±10% volts, 50 Hz, 3

phase power supply. Isolator enclosed in weather proof panel

complete with earthing shall be included. Tower shall be

selected on basis of water temperature 97.5 -90 degree F,

ambient wet bulb 83 deg F and water flow rate 400 US gpm.

Cooling tower fan motor shall be compatible for working with

BMS. Capacity shall be as follows:-

378000kcal/hr capacity

Cooling Tower as described above. 2 Nos.

4.0 NDSR Hot Water Generator

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC3

Page 143: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

Supply, installation, testing & commissioning of Electric Hot

Water Generator for winter heating/monsoon reheating

system.Hot water shall be with IP 55 protection and

compatible with controls, sensors,controll cabling,piping and

fittings,thermal insulation, BMS compatible, base frame etc. as

per specifications.

4.1 Capacity : 40 KWStatus : 1(W) USGPM: 70

Temp IN/OUT : 46.6/48.8 Deg C 1 Nos.

6.0 NDSR AIR HANDLING UNITS

AHUs for Auditorium

6.1 NDSR

Supply, installation, testing and commissioning of draw

through type Air Handling Units (double skin type) of

horizontal /vertical type as specified & shown in schedule of

equipment complete with the following :-

a. Fan Section and canvas connection,Mixing Box, Thermal

break profile. (double skin type)b. Centrifugal blowerc. Coil section with cooling coil/s as per specifications.d. Pre filters with filter section as required in all AHUs.e. Fine and hepa filters with filter section wherever

specifically specified as per AHU schedule .Wherever

fine/hepa filters are specified, item shall include factory

fabricated double skin plenum of same specifications as AHU

panels and complete with filter frameworks.Fine/hepa filter

section along with discharge plenum shall be part of AHU in

upper tier.f. Drain pan, drain connection.g. Squirrel cage induction IP 55 TEFC drive motor, drive

arrangement, guard etc.All AHU motors shall be compatible

for working with VFD.h. Necessary vibration isolators & supporting arrangement.

i. Fresh air intake arrangement, necessary water drain & air

purge valves wherever required etc.

j. Canvass connections,necessary foundations, 2 nos pressure

gauge, 2 nos thermometer etc

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC4

Page 144: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

k Controls for AHUs comprising of a set of pressure

independent type 2 Way Modulating Flow Control valve with

integrated 2 way modulating control of required size having

manual override facility alongwith proportional thermostat &

wiring for interconnection with 1.5 sq. mm Cu Conductor

multicore armoured complete as required.The valve actuator

shall be capable of accepting 2-10 volt DC, 4-20 mA electric

signal and shall provide similar transduced feedback output

signal to control system. The minimum closeoff pressure of

valve must be 1.5 times shut OFF head of pump.

6.1.1AH-GF-1 & AH-GF-2 - 8500cfm/ 4RD Cooling Coil/2 RD

Heating coil /50 mm static 2 Nos.

6.1.2AH-FF-1 - 16500cfm/ 4RD Cooling Coil/ 2 RD Heating

coil/50 mm static 1 Nos.

8.0 NDSR

Supply , installation , testing and commisioning of air cooled

Ductable split air conditioner with scroll compressors

suitable for 3 Phase 50 Hz AC supply comprising of the

following.

a) Outdoor condensing Units

b) Indoor Evaporative Unitsc) Interconnecting Refrigerant and drain piping with

insulation wherever required, refrigerant and oil. The unit

shall include refrigerant piping, power cabling and drain

piping as required.

d) Safety and operational controls

e) The unit shall have advanced microcomputer controller

with run time equalization, auto restart after power failure,

fuzzy logic, self fault diagnostics .

The controller shall have 2 digit 7 segment LED display, LED

indicators and touch key pad. The controller shall have faults

and alarm dispay and it shall be mounted in fire retardant

box.

The equipment shall be equiped with humidity control.

8.1 Capacity :17 TR 2 Nos.

8.2 Capacity : 8.5 TR 2 Nos.

9.0 NDSR SPLIT AIR CONDITIONERSSupply , installation , testing and commisioning of HI wall

split air conditioner comprising of the following.

a) Outdoor condensing Units

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC5

Page 145: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

b) Indoor Evaporative Unitsc) Interconnecting Refrigerant and drain piping with

insulation wherever required, refrigerant and oil. The unit

shall include refrigerant piping, power cabling and drain

piping.

c) Safety and operational controlse) Hiwall splits shall be suitable for single phase power supply

and complete with voltage stablizer. f) Mounting arrangement and structural supports for outdoor

unit are included.g) The units should have atleast 3 star rating from BEE.

9.1 Capacity : 1.5 TR 8 Nos.

9.2 Capacity : 2 TR 10 Nos.

9.3 Capacity : 2.5 TR 4 Nos.

10.0 NDSR HEAT RECLAIM VENTILATION UNIT

Supply, installation , testing and commissioning of heat

reclaim ventilation with inlet and exhaust blower with fan

(Inlet & exhaust) desiccant absorption material non contact

seal, modular design with Aluminium supports of extruded

section, galvanized steel plate casing, self extinguishable

polyurethene foam insulation, multi-directional fibrous fleeces

air filter including electric panel with cabling & earthing

complete as per requirements.

75% efficiency

(F/A - 2500 cfm & R/A 2500 cfm) 2 Nos.

11.0 NDSR Air Washer Unit

Supply, installation, testing and commissioning of air washer

units for air cooling work constructed as per detailed

specifications and drawings, complete with 50mm thick

prefilter, minimum 200mm deep celldeck pad, water

circulating pump, DIDW centrifugal forward

curved/backward curved fan, TEFC squirrel cage induction

motor V-belt & drive set vibration isolators, internal piping

with class 'B' piping, quick fill, make up drain, overflow

connection float value etc. complete with all respects.

Mounting frame of angle iron for floor / wall mounting. Price

must include starter panel, cabling, control wiring, earthing

etc.

11.1 3000 CFM with 50mm static pressure 1 No.

12.0 NDSR Inline Fans/ Propeller Fans

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC6

Page 146: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

12.1

Supply, installation, testing and commissioning of Inline Fans

as shown in drawings and as per equipment schedule .Each

fan shall be complete with centrifugal blowers, totally

enclosed fan cooled motor. Fan motor shall be suitable for

single phase, 220 +/- 6% V, 50 Hz AC supply. Item shall be

complete with starter & cabling.

Duty Toilet Exhaust:

12.1.1 Air Quantity :600 CFM 2 Nos.

Static Pressure :15 mm wg

12.1.2 Air Quantity : 400 CFM 2 Nos.

Static Pressure :15 mm wg

12.1.3 Air Quantity : 350 CFM 1 Nos.

Static Pressure :15 mm wg

12.2

Supplying, installing, testing and commissioning of direct

driven Propeller fan for exhaust air as shown in drawings.

Each fan shall be complete with permanent split capacitor or

shaded pole motor, mounting plate, accessories like wire

guard, bird screen and fixed louvers for weather protection as

required. Fan selection arrangement and Electrical

characteristics shall be as follows:

12.2.1150 mm dia 900 RPM fan suitable for 220 +/- 10% volts, 50

Cycles, 1 Phase AC Supply 2 Nos

13.0 NDSR Tube Axial Fans (Fire rated)

Supply, installation,testing and commisioning of tube axial

flow fans as shown in drawings, Each fan shall be direct

driven.. Fan motor shall be suitable for 3 Phase, 415+/- 10% V,

50Hz AC supply . Fan shall be complete with gravity louvers.

Fan shall be 250 deg C, 2hrs fire rated.

13.1 Duty: Auditorium exhaust

Air Quantity : 5100 CFM, 20 mm st. pr. 4 Nos.

13.2 Duty: Plant room ventilation

Air Quantity : 3750 CFM, 25 mm st. pr. 2 Nos.

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC7

Page 147: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

13.3 Duty: Substation ventilation

Air Quantity : 1000 CFM, 20 mm st. pr. 5 Nos.

13.4 Duty: Substation ventilation

Air Quantity : 1500 CFM, 25 mm st. pr. 2 Nos.

15.0 NDSR EXPANSION TANK

Supply, installation, testing and commissioning of pressurised

PVC, expansion tank of following capacities made of PVC 2

layer sheet complete with 50 mm thick fire retardant type 32

kg/mt cu density TF quality expanded polystyrene insulation

finished with two layers of sand cement plaster and painted

complete with vent, drain connections , float valve, quick fill

connection, manhole cover etc as specified. (Of double layered

Sintex or equivalent make).

15.1 1000 ltrs. (for chilled water circuit) 1 No.

16.0 NDSR AIR OZONE SYSTEM

Supply, Installation , testing , commissioning and handing

over of the imported Air Ozone System for maintaining

indoor Air Quality. The components of the system must be in

strict conformity with the specifications.and shall be including

freight from Delhi Airport to site ,Insurance,Lifting,Shifting

etc.as required . Single phase power supply for the Ozone

Generators will be provided near the controller by others. The

prices to include all connected wiring between the duct

mounted ozone generator, VOC sensor / Controller. The

power supply to the Ozone monitor will be provided near the

respective equipment by others . But the wiring between the

ozone moniter / switch and controller will be included in the

scope. also shall be inclided the supply installation , Testing &

commisioning of Motorised Fresh air Damper.

Duct mounted ozone generators suitable for the following

floor area mentioned in the basis of design .

16.1 Auditorium Hall

8500 CFM 2 Set

TOTAL

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC8

Page 148: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

B) PIPING

17.0 DSR CONDENSER WATER PIPING & VALVES

16.10.1

Supplying, fixing, testing and commissioning of condenser

water pipes of following sizes of MS 'C' class along with

necessary clamps, vibration isolators and fittings such as

bends,tees etc.but excluding valves, strainers, gauges etc.

adequately supported on rigid supports duly painted/buried

in ground excavation and refilling etc. as per specification and

as required complete in all respect.

Note:-The Pipes size 150mm & below shall be M.S. 'C' class as

per IS : 1239 and pipes size above 150mm shall be welded

black steel pipe heavy class as per IS: 3589, from minimum

6.35mm thick M.S. Sheet for pipes upto 350 mm dia. And

from minimum 7mm thick MS sheet for pipes of 400 mm dia

and above.

17.1 16.10.1.4 150 mm dia 150 RM

18.0 Valves without insulation

16.11

Supplying, fixing, testing and commissioning of following

valves, gauges and strainers for condenser water circulation as

per specifications.

18.1 16.11.1Butterfly valves (manual) : with C I body SS disc nitrile

sheet & O - ring & PN 16 pressure rating as specified.

18.1.1 16.11.1.2 150 mm dia. 13 Nos

18.1.2 16.11.1.7 50 mm dia. 2 Nos

18.1.3 16.11.1.8 40 mm dia. 2 Nos

18.2 NDSR Balancing valves :

18.2.1 150 mm dia. 2 Nos

18.3 16.11.2

Non return/Check valves : with dual plate of CI body SS

plates vuicanized NBR seal flanged end & PN 16 pressure

rating as specified.

18.3.1 16.11.2.2 150 mm dia. 2 Nos

18.4 NDSR Pot strainer with drain valve

18.4.1 150 mm dia. 1 Nos

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC9

Page 149: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

18.5 NDSR Y- strainer with drain valve

18.5.1 150mm dia. 2 Nos

19.0 DSR INSULATED CHILLED WATER PIPING

19.1 16.2

Supplying, laying/ fixing, testing and commissioning of

following nominal sizes of chilled water piping inside the

building (with necessary clamps, vibration isolators and

fittings but excluding valves, strainers, gauges etc.) duly

insulated with following closed cell elastometric nitrile rubber

of class 'O' insulation applied by adhesive confirming to

standard specifications and finally applying 0.63mm

aluminium sheet cladding complete with type3 , grade 1

roofing feltstrip(as per IS:1322 as amended up to date ) at

joints and repairing of damage to building etc. as per

specifications and as required complete in all respect.

Note:-The Pipes of sizes 150mm & below shall be M.S. 'C'

class as per IS : 1239 and pipes size above 150mm shall be

welded black steel pipe heavy class as per IS: 3589, from

minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm

dia. and from minimum 7mm thick MS sheet for pipes of 400

mm dia and above.

19.1.1 16.2.7 125 mm dia 120 RM

19.1.2 16.2.8 100 mm dia 20 RM

19.1.3 16.2.9 80 mm dia 100 RM

19.2 NDSR

Supply, Installation, Testing and Commissioning of following

nominal sizes of Chilled water piping Outside the building

burried in ground (with necessary clamps, vibration isolators

and fitttings but excluding valves, strainers, gauges)

adequately supported on rigid supports and duly insulated

with fire retardant quality expanded polysterene molded pipe

sections of density not less than 20 kg/cu.m after a thick coat

of cold setting adhesive (CPRX compound) wrapping with

500 gm polythene faced hessain and secured with

0.5mmx20mm G.I wire mesh and two coats of cement plaster

(each layer not less than 10mm) as per specifications including

digging and refilling the trenches and providing suitable

thichness 1:2:4 cement concrete pads at 3 m intervals complete

as per specifications and as required.

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC10

Page 150: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

19.2.1 125 mm dia 25 RM

20.0 DSR INSULATED VALVES & STRAINERS

Supplying, fixing, testing and commissioning of following

valves, strainers, gauges in the chilled water plumbing duly

insulated to the same specifications as the connected piping

and adequately supported as per specifications.

20.1 16.7.1

Butterfly valves (Manual) :

with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16

pressure rating for chilled water/ hot water circulation as

specified

20.1.1 16.7.1.3 125 mm dia. 13 Nos

20.1.2 16.7.1.5 80 mm dia. 17 Nos

20.2 16.7.2

Balancing valves :

with C I body flanged construction with EPDM coated disc

with long pitch with protected out pipe insulation & PN 16

pressure rating for chilled / hot water circulation as specified.

20.2.1 16.7.2.3 125 mm dia. 4 Nos

20.2.2 16.7.2.5 80 mm dia. 3 Nos

20.3 16.7.3

Non return/Check valves :

with duel plate of C I body SS plates vulcanized NBR seal

flanged end & PN 16 pressure rating for chilled / hot water

circulation including insulation as specified.

20.3.1 16.7.3.3 125 mm dia. 2 Nos

20.3.2 16.7.3.5 80 mm dia. 2 Nos

20.4 16.7.4

Y- strainers of Ductile CI Body flanged ends with stainless

steel strainer for chilled / hot water circulation including

insulation as specified.

20.4.1 16.7.4.3 125 mm dia. 2 Nos

20.4.2 16.7.4.5 80 mm dia. 5 Nos

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC11

Page 151: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

20.5 NDSRProviding and fixing in position the following Gate Valves

duly insulated as per specifications:

20.5.1 50 mm dia Valves 2 Nos.

20.5.2 40 mm dia Valves 2 Nos.

20.5.3 32 mm dia Valves 2 Nos.

21.0 NDSR DRAIN PIPING

21.1

Supply, laying/fixing, testing and commissioning of G.I.

medium class ERW piping confirming to IS:l239 with

necessary clamps, supports, anti vibration mountings, hangers

and fittings such as bends, tees, reducers etc. duly insulated

and painted as per specifications for condensate drain from air

handling units and chillers etc.

21.1.1 50 mm dia 20 RM

21.1.2 40 mm dia 20 RM

21.1.3 32 mm dia 20 RM

21.1.4 25 mm dia 20 RM

22.0 On-line non-chemical water treatment system

Supply, Installation, Testing and Commissioning of On line,

Non-Chemical Water Treatment Scale Preventor System : for

100 TR AC Chiller, having flow rate 400 USGPM 2 Nos.

TOTAL

C) AIR DISTRIBUTION

23.0 DSR GSS DUCTING

16.12.1

Supply, installation, balancing and commissioning of factory

fabricated GSS sheet metal rectangular/round ducting

complete with neoprene rubber gaskets, elbows, splitter

dampers, vanes, hangers, supports etc. as per approved

drawings and specifications of following sheet thickness

complete as required.

23.1 16.12.1.1 Thickness 0.63 mm (24 G) GSS 1150 Sqm.

23.2 16.12.1.2 Thickness 0.80 mm (22 G) GSS 1450 Sqm.

23.3 16.12.1.3 Thickness 1.0 mm (20 G ) GSS 462 Sqm.

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC12

Page 152: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

23.4 16.12.1.4 Thickness 1.25 mm(l8 G) GSS 190 Sqm.

24.0 DSR FIRE DAMPERS

16.20

Supplying, Fixing,testing and commissioning of fire dampers

in supply air duct/main branch and return air path as and

where required of required sizes i/c control wiring,the

damper shall be motorized and spring return so as to close the

damper in the event of power failure automatically and open

the same in case of power being restored. The spring return

action shall be inbuilt mechanism and not externally mounted.

The damper shall also be closed in the event of fire signal

complete as required and as per specifications.

24.1 16.20.1 Fire/smoke Damper 5 Sqm

24.2 16.20.2 Actuator 6 Nos.

25.0 DSR VOLUME CONTROL DAMPERS

16.13

Supply, installation, testing and commissioning of GI volume

control duct damper complete with neoprene rubber gaskets,

nuts, bolts, screws linkages, flanges etc, as per specifications.

8 Sqm.

27.0 DSR CEILING DIFFUSERS

27.1 16.17

Supplying, fixing testing commissioning of supply air

diffusers of powder coated aluminium with aluminium

volume control dampers with anti smudge ring & removable

core. 20 Sqm.

27.2 16.18

Supplying, fixing testing commissioning of Return air

diffusers of powder coated aluminium without volume

control dampers with anti smudge ring & removable core. 9 Sqm.

28.0 GRILLES

28.1 DSR

Supply, installation, testing and balancing of supply/return

air grilles with/without volume control dampers of powder

coated aluminium construction suitable for installation in

walls, false ceiling boxing etc as per specifications and

drawings.

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC13

Page 153: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

28.1.1 16.15

Supplying & fixing of powder coated extruded aluminium

Supply Air Grills with aluminium volume control dampers as

per specifications. 8 Sqm.

28.1.2 16.16

Supplying & fixing of powder coated extruded aluminium

Return Air Grills with louvers but without volume control

dampers complete as required. 11 Sqm.

28.2 NDSR

Supply, installation, testing and balancing of powder coated

extruded M.S. Air Grilles with / without volume control

dampers.

28.2.1Supply air grilles in single louvers with volume control

dampers. 2 Sqm.

28.2.2Exhaust air grilles in single louvers without volume control

dampers. 8 Sqm.

29.0 NDSR LINEAR GRILLES

Supply, installation,testing and balancing of air linear grilles

of powder coated aluminium construction suitable for

installation in walls/false ceiling, boxing etc as per

specifications and drawings. 5 Sqm.

30.0 NDSR GRILLE DAMPERS

Supply, installation and balancing of aluminium construction

volume control dampers for linear grills. 5 Sqm.

31.0 NDSR FRESH AIR GRILLES with bird screen

31.1

Supply, installation, testing, commissioning and balancing of

fresh air opening comprising of powder coated extruded

aluminium louvers with bird screen, projection with frame

and volume control damper with lever mounting

arrangement etc. as per specifications and drawings. 3 Sqm.

31.2

Supply, installation,testing and balancing of extruded

aluminium exhaust air grilles with louvers and bird screen as

per specification and drawings. 3 Sqm.

32.0 NDSR Pan type Humidifier

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC14

Page 154: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

Supply, installation, testing and commissioning of electric pan

type humidifiers in each Air Handling Rooms to provide

humidification during winter months heating operation. The

humidifier shall evaporate 12 liters water per hour and

complete with all required water valves incoming MCB,

humidistat and ,electrical & control wiring and earthing as

required.

32.1 9 KW 1 Sets

32.2 6 KW 2 Sets

33.0 DUCT INSULATION

Supplying and fixing of following thickness aluminium foil

faced resin bonded fibre glass insulation (on duct ) of density

24 kg/cu.m after applying two coats of cold setting adhesive

(CPRX compound) sealing all joints with self adhesive

aluminium tape & covering with 0.63mmx19mm GI wire

mesh netting butting all joints and laced with GI wire

complete as per specifications and as required. (for indoor

applications).

33.1 16.24 50 mm thick insulation ( For duct in Non AC area) 400 Sqm.

33.2 NDSR 25 mm thick insulation ( For duct in AC area) 2650 Sqm.

33.3 16.25

Supplying and fixing 50mm thick aluminium foil faced resin

bonded fibre glass insulation (on duct) of density 24 kg/cu.m

after applying two coats of cold setting adhesive (CPRX

compound) sealing all joints with self adhesive aluminium

tape & covering with 0.63mmx19mm GI wire mesh netting &

butting all joints and laced with GI wire complete and finally

covered with one layer of tar felt stuck with hot bitumen as

per specifications and as required. (for outdoor applications)

250 Sqm.

34.0 ACOUSTIC

34.1 DSR Duct lining

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC15

Page 155: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

16.21

Supply and fixing of acoustic lining of supply air duct and

plenum with 25 mm thick resin bonded glass wool having

density of 32 kg/m³, with 25 mm X 25 mm GI section of 1.25

mm thick, at 600 mm centre to centre covered with Reinforced

Plastic tissue paper and 0.5 mm thick perforated aluminum

sheet fixed to inside surface of ducts with cadmium plated

nuts, bolts, stick pins, CPRX compound etc. complete as

required and as per specifications.2910 Sqm.

34.2 NDSR Duct Silencer

Supply, installation, testing, commissioning and balancing of

duct silencer in both supply & return air ducting with heavy

gauge GI sheet with acoustic insulation material, inside GI

perforated sheet all complete as per specifications & shop

drawings etc. 20 Sqm

34.3 DSR Plant room accoustic Insulation

16.22

Supplying, fixing acoustic lining on wall and ceiling of AC

Plant room with 50mm thick, density 32 kg/cu.m resin

bonded glass fiber insulation friction fixed in 610mm x 610

mm frame work made of 25 X 50 X50 X 50 X 25 mm made out

of 0.6mm thick GI sheet U shaped channel and covered with

reinforced fiber glass tissue and finished with 0.80 mm

perforated aluminium sheet etc. complete as required and as

per specifications 500 Sqm.

TOTAL

D) ELECTRICAL

35.0 AIR- CONDITIONING PANELS

All bill of items are to be read in conjuction with

specifications and drawings.

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC16

Page 156: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

Supply, installation, testing and commissioning of A/C panels

suitable for 415 V, 3 phase, 4 wires, 50 Hz power distribution

system. The panel shall be cubicle non draw out type free

standing floor mounting sheet metal enclosed flush front with

aluminium busbars, separate earth bus bars to be provided

throughout the length of the panel. The incoming & outgoing

feeder breakers, fuses, indicating lamps etc. shall be

accomodated in a modular multitier arrangement. The

painting shall be done as per relavant IS codes as specified in

the specifications. Adequate size cable alley shall be provided

all round the panel and in the back for each cable bending and

termination. The outgoing feeders inside the panel shall be

connected through solid bus bar. Flexible cable links are not

acceptable. Bus bars shall be provided with sleeves or heat

resistant insulated paint. The panel shall be suitable for cable

entry from top. The panel shall be fabricated after the

approval of fabrication drawings.All the panels shall have

minimum 20%spare capacity.

i)All doors to have pad locking and shrouding arrangement.

ii)All switches to be heavy duty type base mounted having

operating handle.iii) BMS compatible with BACnet protocal

35.1Main/ Emergency Air-conditioning MCC in plant room (for

Audi)

INCOMER

2 nos 400 Amp 415 volts, 35 KA (Isc), FP MCCB with thermal

magnetic release having variable current settings of 0.8 to 1.0

ln.Extended rotary operating mechanism with door interlock

with defeat feature and padlock facility. MCCB should be

with spreader link and phase barriers.Indicating lamps with

2A protection MCBs to indicate OPEN, CLOSE, TRIP for

MCCB.Ampere Metre of suitable range with suitable set of

CT's and ASS.For hot water genetators.(2W)

1 set of indicating lamps to indicate OPEN, CLOSE, TRIP.

Push button to CLOSE the ACB.

1 Set of A meter with ASS and CTs.All ACBs should be computer compatible.

BUSBARS :500 TPN

Bus Coupler

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC17

Page 157: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

1 nos 400 Amp 415 volts, 35 KA (Isc), FP MCCB with thermal

magnetic release having variable current settings of 0.8 to 1.0

ln.Extended rotary operating mechanism with door interlock

with defeat feature and padlock facility. MCCB should be

with spreader link and phase barriers.Indicating lamps with

2A protection MCBs to indicate OPEN, CLOSE, TRIP for

MCCB.Ampere Metre of suitable range with suitable set of

CT's and ASS.For hot water genetators.(1W)

1 set of indicating lamps to indicate OPEN, CLOSE, TRIP.

Push button to CLOSE the ACB.1 Set of A meter with ASS and CTs.All ACBs should be computer compatible.

OUTGOING

2 nos 250 Amp 415 volts, 35 KA (Isc), FP MCCB with thermal

magnetic release having variable current settings of 0.8 to 1.0

ln.Extended rotary operating mechanism with door interlock

with defeat feature and padlock facility. MCCB should be

with spreader link and phase barriers.Indicating lamps with

2A protection MCBs to indicate OPEN, CLOSE, TRIP for

MCCB.Ampere Metre of suitable range with suitable set of

CT's and ASS. For water chilling machines.

2 nos 160 Amp 415 volts, 35 KA (Isc), FP MCCB with thermal

magnetic release having variable current settings of 0.8 to 1.0

ln.Extended rotary operating mechanism with door interlock

with defeat feature and padlock facility. MCCB should be

with spreader link and phase barriers.Indicating lamps with

2A protection MCBs to indicate OPEN, CLOSE, TRIP for

MCCB.Ampere Metre of suitable range with suitable set of

CT's and ASS.For hot water genetators and AHP1.

2 Nos. 63 Amp 415 volts, 35 KA (Isc), FP MCCB with thermal

magnetic release having variable current settings of 0.8 to 1.0

ln.Extended rotary operating mechanism with door interlock

with defeat feature and padlock facility. MCCB should be

with spreader link and phase barriers.Indicating lamps with

2A protection MCBs to indicate OPEN, CLOSE, TRIP for

MCCB.Ampere Metre of suitable range with suitable set of

CT's and ASS with fully automatic star delta starter suitable

for 15 hp Chilled water pumps.(1W+1S)

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC18

Page 158: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

3 Nos. 16 Amp 415 volts, 35 KA (Isc), FP MCCB with thermal

magnetic release having variable current settings of 0.8 to 1.0

ln.Extended rotary operating mechanism with door interlock

with defeat feature and padlock facility. MCCB should be

with spreader link and phase barriers.Indicating lamps with

2A protection MCBs to indicate OPEN, CLOSE, TRIP for

MCCB.Ampere Metre of suitable range with suitable set of

CT's and ASS with fully automatic dol starter suitable for 2 hp

hot water pumps.

3 Nos. 63 Amp 415 volts, 35 KA (Isc), FP MCCB with thermal

magnetic release having variable current settings of 0.8 to 1.0

ln.Extended rotary operating mechanism with door interlock

with defeat feature and padlock facility. MCCB should be

with spreader link and phase barriers.Indicating lamps with

2A protection MCBs to indicate OPEN, CLOSE, TRIP for

MCCB.Ampere Metre of suitable range with suitable set of

CT's and ASS with fully automatic star delta starter suitable

for 20 hp Condenser water pumps.

6 Nos. 32 Amp 415 volts, 35 KA (Isc), FP MCCB with thermal

magnetic release having variable current settings of 0.8 to 1.0

ln.Extended rotary operating mechanism with door interlock

with defeat feature and padlock facility. MCCB should be

with spreader link and phase barriers.Indicating lamps with

2A protection MCBs to indicate OPEN, CLOSE, TRIP for

MCCB.Ampere Metre of suitable range with suitable set of

CT's and ASS with fully automatic star delta starter suitable

for 5 hp cooling towers.

4 No. 16 Amps MCCB 10 KA for 5 HP Motor with suitable

Starters for motor with thermal overload protection,single

phase preventor,spare NO_NC contacts for interlocking, ON-

OFF indication lamps with push button,ammeter with ASS

and CTs for ventilation fan motors.

Complete panel as above 1 Panel

35.3 AHU MAIN DISTRIBUTION PANEL

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC19

Page 159: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

Supply, installation, testing and commissioning of A/C panels

suitable for 415 V, 3 phase, 4 wires, 50 Hz power distribution

system. The panel shall be cubicle non draw out type free

standing floor mounting sheet metal enclosed flush front with

aluminium busbars, separate earth bus bars to be provided

throughout the length of the panel. The incoming & outgoing

feeder breakers, fuses, indicating lamps etc. shall be

accomodated in a modular multitier arrangement. The

painting shall be done as per relavant IS codes as specified in

the specifications. Adequate size cable alley shall be provided

all round the panel and in the back for each cable bending and

termination. The outgoing feeders inside the panel shall be

connected through solid bus bar. Flexible cable links are not

acceptable. Bus bars shall be provided with sleeves or heat

resistant insulated paint. The panel shall be suitable for cable

entry from top. The panel shall be fabricated after the

approval of fabrication drawings.

35.3.1 AHU Distribution Panel (AHP-1)

INCOMER :1 nos 160 Amp 415 volts, 35 KA (Isc), FP MCCB with thermal

magnetic release having variable current settings of 0.8 to 1.0

ln.Extended rotary operating mechanism with door interlock

with defeat feature and padlock facility. MCCB should be

with spreader link and phase barriers.Indicating lamps with

2A protection MCBs to indicate OPEN, CLOSE, TRIP for

MCCB.Ampere Metre of suitable range with suitable set of

CT's and ASS.

Bus Bar

200 A TPN Aluminium bus bar 415V , 50 Hz.

OUTGOINGS :

5 set - 63 A, 415 V MCCB 15 KA, ON-OFF indication lamps .

2 set - 32 A, 415 V MCCB 15 KA, contactors of suitable rating

for each bank , ON-OFF indication lamps.

3 set - 16 A, 415 V MCCB 15 KA, contactors of suitable rating

for each bank , ON-OFF indication lamps.

Complete panel as above 1 Panel

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC20

Page 160: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

35.4 AHU STARTER PANELS (AHSP)

Supply, installation, testing and commissioning of cubicle

type totally enclosed wall/floor mounted free standing type,

dust, damp and vermin proof for AHU made of 2mm thick

CRCA sheet steel in compartmentalized design as per

specification and drawings. These distribution boards shall be

mounted on 50x50x6 MS angle frame work grouted to

floor/walls of recessed. The rate includes the angle iron

frame, support, painting, numbering, earthing etc. as required.

35.5 AHU/ FAN STARTER PANEL

OUTGOING :

1 No. 63 Amps MCCB 10 KA for 12.5 HP Motor with suitable

Starters for motor with thermal overload protection,single

phase preventor,spare NO_NC contacts for interlocking, ON-

OFF indication lamps with push button,ammeter with ASS

and CTs for AHU/Fan motor as required.

1 Nos.

35.6 AHU/FAN STARTER PANEL

OUTGOING :

1 No. 32 Amps MCCB 10 KA for 1.5/2/7.5 HP Motor with

suitable Starters for motor with thermal overload

protection,single phase preventor,spare NO_NC contacts for

interlocking, ON-OFF indication lamps with push

button,ammeter with ASS and CTs for AHU/Fan motor as

required. 1 Nos.

35.7 AHU/FAN STARTER PANEL

OUTGOING :

1 No. 16 Amps MCCB 10 KA for 2 HP Motor with suitable

Starters for motor with thermal overload protection,single

phase preventor,spare NO_NC contacts for interlocking, ON-

OFF indication lamps with push button,ammeter with ASS

and CTs for AHU/Fan motor as required.

5 Nos.

35.8 AHU/FAN STARTER PANEL

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC21

Page 161: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

OUTGOING :

1 No. 16 Amps MCCB 10 KA for 1/0.75/0.5 HP Motor with

suitable Starters for motor with thermal overload

protection,single phase preventor,spare NO_NC contacts for

interlocking, ON-OFF indication lamps with push

button,ammeter with ASS and CTs for AHU/Fan motor as

required. 6 Nos.

36.0 CABLING

Supplying, laying, effecting proper connections, testing &

commissioning of following size of 1.1 kv PVC insulated

aluminium conducting armoured cables as per IS 1554 Part-

1laid underground/cable tray/on surface of wall/hume pipe

etc. & termination with aluminium cable lugs & brass

compression glands as required.

36.1 3.5C x 150 sq.mm cable 150 Mtr

36.2 3.5C x 95 sq.mm cable 100 Mtr

36.3 3.5C x 35 sq.mm cable 20 Mtr

36.4 4Cx 25 sq.mm Cable 20 Mtr

36.5 4 C X 16 sq. mm. Cable 150 Mtr

36.6 4 C X10 sq. mm. Cable 80 Mtr

36.7 4 C X 6 sq. mm. Cable 300 Mtr

36.8 4 C X 4 sq. mm. Cable 250 Mtr

37.0 CABLE TRAYS

Supply & installation of following sizes of perforated MS

cable trays including horizontal & vertical bends, reducers,

tees, cross members and other accessories as required and

duly supported from the ceiling/wall/floor with MS

suspenders/supports and including painting etc. as required

37.1 200 mm widthx50 mm deep x1.6 mmthickness 100 Mtr

37.2 150 mm widthx50 mm deep x1.6 mmthickness 80 Mtr

37.3 100 mm widthx50 mm deep x1.6 mmthickness 120 Mtr

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC22

Page 162: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

38.0 EARTHING

38.1

Earth pits with GI earth plate of size 600mmx600mmx6mm

thick including all accessories , down watering GI pipes 40mm

dia and providing masonry enclosure with cover plate having

interlocking arrangement and watering pipe etc. with

charcoal of or coke and salt) complete as required 2 Set

38.2Providing & fixing GI earth strip 40mm x 6mm on surface or

in recess for earth connections etc. as required. 70 Mtr

38.3Providing and fixing GI earth strip on walls/ trenches

complete as per specifications and as required.

38.3.1 40mmx 6mm 100 Mtr

38.3.2 25mm x 3mm 120 Mtr

38.4Providing and fixing GI earth wire of complete as per

specifications as required.

38.4.1 6 SWG wire 100 Mtr

38.4.2 8 SWG wire 200 Mtr

39.0 CONTROL CABLING

Supply, laying, effecting proper connections, testing &

commissioning of 1.5 sq.mm. PVC insulated copper multicore

cables from AHU's and AC equipments to central control

console

39.1 14 core cable 300 Mtr

39.2 10 core cable 100 Mtr

39.3 8 core cable 200 Mtr

39.4 6 core cable 200 Mtr

39.5 3 core cable 150 Mtr

39.6 2 core cable 120 Mtr

40.0 CONTROL CONSOLE /DESK

40.1 In Plant Room for Audi and conference

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC23

Page 163: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Item No.

1

DSR/

NDSR

2

Description

3

Total

Qty

4

Unit

5

Rate In Rs ( in

Figure)

6

Rate in Rs (in Words)

7

Amount (Rs.)

8

Supplying, installation, testing & commissioning of floor

mounted desk type control console cum indicating panel in

the A.C. plant room containing various indications and

controls for the complete air-conditioning system comprising

chilling units, chilled/ Hot/ condenser water pumps, cooling

towers and AHUs/ Ex. blower/ Fans etc , Hot water boiler

with test push button facility. The panel shall be fabricated

from minimum 1.6mm thick M.S. powder coated sheet of

approved design. The air-conditioning module of the central

control cum indicating panel shall contain the following

accessories.

Status indication (ON, OFF & fault) of each compressor for

each chilling machine, hot water boiler etc.

Push buttons and indicating lamps for remote start & stop and

status indication for every nos of the water circulating pumps,

Air Handling Units, Ex blower, Fans etc.

Push buttons and indication lamps for remote start & stop and

status indication (On, Off & Fault) for every nos. cooling

tower motors and low water level indication for every Nos.

cooling towers.

Hooter and flashing lamp to indicate operation of any safety/

shut down with necessary contactors, accept, reset and test

push buttons.

COMPLETE PANEL AS ABOVE 1 Set

TOTAL

Complete wiring with copper conductor PVC insulated

multicore 2.5 sq.mm stranded cable (including supply of

cable, tray, clamps etc) from various equipments in the A.C.

plant room, AHU’s Terrace plant room and cooling towers etc

to the control console panel as required.

HSCC-NIMR,Dwarka,New Delhi BOQ R2-AC24

Page 164: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

SUMMARY SHEET FOR HVAC WORKS

SECTION DESCRIPTION OF WORK AMOUNT(Rs.)

A EQUIPMENTS

B PIPING

C AIR DISTRIBUTION

D ELECTRICAL

GRAND TOTAL

Guest House, Director's Bungalow, Auditorium & Conference, Substation & AC Plant Room at

NIMR-Dwarka , New Delhi.

Page 165: Construction of Auditorium, Guest House, Hostel, Electric ... · Excess/less cement used as per design mix is payable/recoverable ... 456 -2000 in the items ... corbels etc., including

Sl.No. Name of the Head

Total Quoted amount(in indian

Rupees) Discount If Any(%) Discounted Value Value After Discount

1 Civil Works0.00 0 0.00

2

Public Health

Engineering Works

0.00 0 0.00

3

Fire Fighting

Works

0.00 0 0.00

4 Electrical Works0.00 0 0.00

5 HVAC Works0.00 0 0.00

Total Amount in

Figure(Rs)0.00

0.00

Guest House, Director's Bungalow, Auditorium & Conference, Substation & AC Plant Room at NIMR-Dwarka , New Delhi.

Name of the Firm