2 MSP OVERLOAD MSP Overloads Contents Motor Starter Protectors Overview 2-2 SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80A Motor Starter Protectors - For Motor Protection 2-5 Motor Starter Protectors - For Motor Protection with Overload Relay Function 2-6 Motor Starter Protectors - For Motor Protection 2-7 Circuit Breakers - For starter combinations for export applications 2-8 Motor Starter Protectors - For Transformer Protection 2-9 Accessories Mountable Accessories 2-10 Busbar Accessories 2-12 Rotary Operating Mechanisms 2-14 Mounting Accessories 2-15 Protection Equipment Overload Relays Overview 2-18 SIRIUS 3RU2 Thermal Overload Relays 2-19 Accessories 2-22 SIRIUS 3RB3 Electronic Overload Relays 2-23 Accessories 2-27 2

Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

2MSP OVERLOAD

MSP Overloads

Contents Motor Starter Protectors Overview 2-2 SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80A Motor Starter Protectors - For Motor Protection 2-5 Motor Starter Protectors - For Motor Protection with Overload Relay Function 2-6 Motor Starter Protectors - For Motor Protection 2-7 Circuit Breakers - For starter combinations for export applications 2-8 Motor Starter Protectors - For Transformer Protection 2-9 Accessories Mountable Accessories 2-10 Busbar Accessories 2-12 Rotary Operating Mechanisms 2-14 Mounting Accessories 2-15 Protection Equipment Overload Relays Overview 2-18 SIRIUS 3RU2 Thermal Overload Relays 2-19 Accessories 2-22 SIRIUS 3RB3 Electronic Overload Relays 2-23 Accessories 2-27

2

Page 2: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 20152-2

2MS

P OV

ERLO

AD

SIRIUS 3RV2 Motor Starter Protector/Circuit Breaker up to 80 AOverview General

Mountable accessoriesa�� Transverse auxiliary switchb�� Lateral auxiliary switch with 2 contactsc�� Lateral auxiliary switch with 4 contactsd�� Shunt release (can not be used with 3RV21

motor starter protectors)e�� Undervoltage release without/with leading contacts (can not be

used with 3RV21 motor starter protectors)f�� Signaling switch (can not be used with 3RV27 and 3RV28

circuit breakers)g�� Isolator module (can not be used with 3RV27 and 3RV28

circuit breakers)h�� Terminal block type E or phase barriers

SIRIUS motor starter protector with spring-type terminals, size S0 (left)

SIRIUS motor starter protector

with screw terminals, size S00 (right)

4

2

6

3

1

5

7

8

Mountable accessories for SIRIUS 3RV2 motor starter protectors/circuit breakers

The new SIRIUS 3RV2 motor starter protectors/circuit breakers are compact, current limiting motor starter protectors/circuit breakers which are optimized for load feeders. The motor starter protectors/circuit breakers are used for switching and protecting three-phase motors of up to 50 HP at 600 V AC and for other loads with rated currents of up to 80 A.

For 3RV1 motor starter protectors/circuit breakers in size S3 up to 100 A.

The new 3RV2 motor starter protectors/circuit breakers are usually approved according to IEC and UL/CSA. According to UL 508/UL 60947-4-1, the 3RV2 motor starter protectors in sizes S00 to S2 are approved as:

b "Manual Motor Controllers"

b "Manual Motor Controllers" for "Group Installations"

b "Manual Motor Controllers Suitable for Tab Conductor Protection in Group Installations"

b "Self-Protected Combination Motor Controllers (Type E)"

Please note that for this approval the 3RV20 motor starter protectors must be equipped with additional infeed terminals or phase barriers.

The 3RV27 and 3RV28 circuit breakers are approved as circuit breakers according to UL 489; they are a special version of the 3RV2 motor starter protectors.

The following illustration shows our 3RV2 motor starter protector/circuit breaker with the accessories which can be mounted for the sizes S00 to S2.

Page 3: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 2015 2-3

2MSP OVERLOAD

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80AOverview Selection

a�� Delivery late 2015.

3RV20 31

FLA AdjustmentRange

Single Phase HP Ratings Three Phase HP Ratings

Instantaneous Overcurrent Release

CSA SCCR kA 400Y/277V

CSA SCCR kA 600Y/347V Order No.115V 230V 200V 230V 460V 575V

A kA kA 3RV20 31

3RV20 31 Size S2

9.5-14 11/2 3 5 5 10 15 208 65 25 3RV20 31-4SA10

12-17 11/2 3 5 71/2 15 15 260 65 25 3RV20 31-4TA10

14-20 11/2 3 71/2 71/2 15 20 260 65 25 3RV20 31-4BA10

18-25 2 5 71/2 10 20 25 325 65 25 3RV20 31-4DA10

22-32 3 5 10 10 25 30 416 65 25 3RV20 31-4EA10

28-36 3 71/2 15 15 30 40 520 65 25 3RV20 31-4PA10

32-40 3 71/2 15 15 30 40 585 65 22 3RV20 31-4UA10

35-45 3 10 15 15 40 50 650 65 22 3RV20 31-4VA10

42-52 5 10 15 20 40 50 741 65 22 3RV20 31-4WA10

49-59 5 15 20 25 50 60 845 — a 3RV20 31-4XA10

54-65 5 15 20 25 50 60 845 — a 3RV20 31-4JA10

62-73 71/2 15 20 25 60 75 949 — a 3RV20 31-4KA10

70-80 71/2 15 20 25 60 75 1040 — a 3RV20 31-4RA10

Illustrations are approximate

Page 4: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 20152-4

2MS

P OV

ERLO

AD

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80AOverview GeneralApplicationOperating conditions

3RV2 motor starter protectors are suitable for use in any climate.They are intended for use in enclosed rooms in which no severe operating conditions (such as dust, caustic vapors, hazardous gases) prevail. When installed in dusty and damp areas, suitable enclosures must be provided.

3RV2 motor starter protectors can optionally be fed from the top or from below.

The permissible ambient temperatures, the maximum switching capacities, the tripping currents and other boundary conditions can be found in the technical specifications and tripping characteristics.

3RV2 motor starter protectors are suitable for operation in IT systems (IT networks). In this case, the different short-circuit breaking capacity in the IT system must be taken into account.

Since operational currents, starting currents and current peaks are different even for motors with identical power ratings due to the inrush current, the motor ratings in the selection tables are only guide values. The specific rated and start-up data of the motor to be protected is always paramount to the choice of the most suitable motor starter protector. This also applies to motor starter protectors for transformer protection.

Possible uses

The 3RV2 motor starter protectors can be used:

b For short-circuit protection

b For motor protection (also with overload relay function)

b For system protection

b For short-circuit protection for starter combinations

b For transformer protection

b As main and EMERGENCY-STOP switches

b For operation in IT systems (IT networks)

b For switching of DC currents

b In areas subject to explosion hazard (ATEX)

Note: The Order No. scheme is presented here merely for information purposes and for better understanding of the logic behind the order numbers.

For your orders, please use the order numbers quoted in the catalogue in the Selection and ordering data section.

Order No. Scheme

Digit of the Order No.1st - 3rd ooo

4th o

5th o

6th o

7tho —

8th o

9th o

10th o

11th o

12th o —

13th o

14th o

15th o

16th o

Motor starter protector 3 R V

SIRIUS 2nd generation 2

Type of motor starter protector o

Size o

Switching capacity o

Setting range for overload release o o

Trip class (CLASS) o

Connection method o

With or without auxiliary switch o

Special versions o o o o

Example 3 R V 2 0 1 1 — 1 A A 1 0

Page 5: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 2015 2-5

2MSP OVERLOAD

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80AMotor Starter Protectors - For Motor Protection SelectionCLASS 10, without Auxiliary Switches

The 3RV20 1 & 3RV20 3 MSP's can be used as components in Group Installation per NEC 430-53(C) to turn motors on and off. Each device has built-in heater elements that provide overload protection and magnetic trip elements to protect the motor. When the 3RV2 is used as a component in Group Installation,

multiple MSP's can be installed below one circuit breaker to protect its own motor. A contactor can be mounted to the MSP to provide a remotely operated starter.

The 3RV20 can also be used as Type E self-protected manual combination starters per CSA 22.2 without the use of an additional type E terminal adapter.

3RV20 31

Ratedcurrent In

Single Phase HP Ratings Three Phase HP Ratings Setting

range for thermaloverload release

Instantaneouselectronicreleases

Short- circuit Breaking Capacity at 480 V AC in Group Installation Icu

Short- circuit Breaking Capacity at 600 V AC in Group Installation

Screw terminals115V 230V 200V 230V 460V 575V

A A A kA kA Order No.

Size S2

14 11/2 3 5 5 10 15 9.5-14 208 65 25 3RV20 31-4SA10

17 11/2 3 5 71/2 15 15 12-17 260 65 25 3RV20 31-4TA10

20 11/2 3 71/2 71/2 15 20 14-20 286 65 25 3RV20 31-4BA10

25 2 5 71/2 10 20 25 18-25 325 65 25 3RV20 31-4DA10

32 3 5 10 10 25 30 22-32 364 65 25 3RV20 31-4EA10

36 3 71/2 15 15 30 40 28-36 400 65 25 3RV20 31-4PA10

40 3 71/2 15 15 30 40 32-40 432 65 22 3RV20 31-4UA10

45 3 10 15 15 50 50 35-45 480 65 22 3RV20 31-4VA10

52 5 10 15 20 40 50 42-52 741 65 22 3RV20 31-4WA10

59 5 15 20 25 50 60 49-59 845 a a 3RV20 31-4XA10

65 5 15 20 25 50 60 59-65 845 a a 3RV20 31-4JA10

73 71/2 15 20 25 60 75 62-73 949 a a 3RV20 31-4KA10

80 71/2 15 20 25 60 75 70-80 1040 a a 3RV20 31-4RA10

Size S2 with increased switching capacity

14 11/2 3 5 5 10 15 9.5-14 208 100 25 3RV20 32-4SA10

17 11/2 3 5 71/2 15 15 12-17 260 100 25 3RV20 32-4TA10

20 11/2 3 71/2 71/2 15 20 14-20 286 100 25 3RV20 32-4BA10

25 2 5 71/2 10 20 25 18-25 325 100 25 3RV20 32-4DA10

32 3 5 10 10 25 30 22-32 364 100 25 3RV20 32-4EA10

36 3 71/2 15 15 30 40 28-36 400 100 25 3RV20 32-4PA10

40 3 71/2 15 15 30 40 32-40 432 100 22 3RV20 32-4UA10

45 3 10 15 15 40 50 35-45 480 100 22 3RV20 32-4VA10

52 5 10 15 20 40 50 42-52 741 65 22 3RV20 32-4WA10

59 5 15 20 25 50 60 49-59 845 a a 3RV20 32-4XA10

65 5 15 20 25 50 60 54-65 845 a a 3RV20 32-4JA10

73 71/2 15 20 25 60 75 62-73 949 a a 3RV20 32-4KA10

80 71/2 15 20 25 60 75 70-80 1040 a a 3RV20 32-4RA10

a�� Availability and data to be announced.

Illustrations are approximate

Page 6: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 20152-6

2MS

P OV

ERLO

AD

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80AMotor Starter Protectors - For Motor Protection with Overload Relay Function SelectionCLASS 10, with Overload Relay Function (automatic RESET), without Auxiliary Switches

3RV21 31-4BA10

3RV21 31-4WB10

Ratedcurrent In

Single Phase HP Ratings Three Phase HP Ratings

Setting range for thermal overload release

Instantaneouselectronic releases

Short-circuitBreaking Capacityat 480 V AC

Short-circuitBreaking Capacityat 600 V ACIcu

Screw terminals115V 230V 200V 230V 460V 575V

A A A kA kA Order No.

Size S2

14 11/2 3 5 5 10 15 9.5 ... 14 208 65 25 3RV21 31-4SA10

17 11/2 3 5 71/2 15 15 12 ... 17 260 65 25 3RV21 31-4TA10

20 11/2 3 71/2 71/2 15 20 14 ... 20 286 65 25 3RV21 31-4BA10

25 2 5 71/2 10 20 25 18 ... 25 325 65 25 3RV21 31-4DA10

32 3 5 10 10 25 30 22 ... 32 364 65 25 3RV21 31-4EA10

36 3 71/2 15 15 30 40 28 ... 36 400 65 25 3RV21 31-4PA10

40 3 71/2 15 15 30 40 32 ... 40 432 65 22 3RV21 31-4UA10

45 3 10 15 15 40 50 35 ... 45 480 65 22 3RV21 31-4VA10

52 5 10 15 20 40 50 42 ... 52 741 65 22 3RV21 31-4WA10

59 5 15 20 25 50 60 49 ... 59 845 a a 3RV21 31-4XA10

65 5 15 20 25 50 60 54 ... 65 845 a a 3RV21 31-4JA10

73 71/2 15 20 25 60 75 62- ... 73 949 a a 3RV21 31-4KA10

80 71/2 15 20 25 60 75 70 ... 80 1040 a a 3RV21 31-4RA10

a�� Availability and data to be announced.

Illustrations are approximate

Page 7: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 2015 2-7

2MSP OVERLOAD

3RV2031-4.B10

3RV2031-4.B10

Ratedcurrent In

Single Phase HP Ratings Three Phase HP Ratings Setting range

for thermal overload release

Instantaneouselectronic releases

Short-circuitBreaking Capacityat 480 V AC

Short-circuitBreaking Capacityat 600 V ACIcu

Screw terminals115V 230V 200V 230V 460V 575V

A A A kA kA Order No.

Size S2

14 11/2 3 5 5 10 15 9.5 ... 14 208 65 25 3RV20 31-4SB10

17 11/2 3 5 71/2 15 15 12 ... 17 260 65 25 3RV20 31-4TB10

20 11/2 3 71/2 71/2 15 20 14 ... 20 286 65 25 3RV20 31-4BB10

25 2 5 71/2 10 20 25 18 ... 25 325 65 25 3RV20 31-4DB10

32 3 5 10 10 25 30 22 ... 32 364 65 25 3RV20 31-4EB10

36 3 71/2 15 15 30 40 28 ... 36 400 65 25 3RV20 31-4PB10

40 3 71/2 15 15 30 40 32 ... 40 432 65 22 3RV20 31-4UB10

45 3 10 15 15 40 50 35 ... 45 480 65 22 3RV20 31-4VB10

52 5 10 15 20 40 50 42 ... 52 741 65 22 3RV20 31-4WB10

59 5 15 20 25 50 60 49 ... 59 845 — — 3RV20 31-4XB10

65 5 15 20 25 50 60 54 ... 65 845 — — 3RV20 31-4JB10

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80AMotor Starter Protectors - For Motor Protection SelectionCLASS 30, without Auxiliary Switchesa

The 3RV30 1 can be used as components in Group Installation per NEC 430-53(C) to turn motors on and off. Each device has built-in heater elements that provide overload protection and magnetic trip elements to protect the motor. When the 3RV2 is used as a component in Group Installation, multiple MSP's can

be installed below one circuit breaker to protect its own motor. A contactor can be mounted to the MSP to provide a remotely operated starter.

The 3RV20 can also be used as Type E self-protected manual combination starters per CSA 22.2 without the use of an additional type E terminal adapter.

a�� The 3RV20 .1-..A.0 motor starter protectors up to 32 A are also available with ring lug terminal connection. The Order No. must be changed in the 11th position to "4": e. g. 3RV20 11-0AA40.

Auxiliary switches can be ordered separately(see "Mountable accessories").

c�� Availability and data to be announced.

Illustrations are approximate

Page 8: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 20152-8

2MS

P OV

ERLO

AD

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80ACircuit Breakers - For starter combinations for export applications SelectionWithout Auxiliary Switches

These Circuit Breakers are designed for export only applications.

a�� Guide value for 4-pole standard motors at AC 50 Hz 400 V. Select MSP by motor full load amps. kW ratings for reference only.

b�� For overload protection of the motors, appropriate overload relays must be used.

c�� Start of delivery on request.d�� Suitable for use with IE3 motors up to a starting

current of 720 A. For higher starting currents we recommend using 3RV1 motor starter protectors size S3.

Auxiliary switches can be ordered separately(see "Mountable accessories").

3RV2331-4.C10

3RV2331-4WC10

3RV2332-4.C10

3RV2332-4WC10

Rated currentIn

Suitable for inductionmotorsa with P

Thermal overload releasesb�

Instantaneouselectronic releases

Short-circuit Breaking Capacity at 480 V AC in Group Installation Icu

Short-circuit Breaking Capacity at 600 V AC in Group Installation

Screw terminals

A kW A A kA Order No.

Size S2

14 5.5 Without 208 65 25 3RV23 31-4SC10

17 7.5 Without 260 65 25 3RV23 31-4TC10

20 7.5 Without 260 65 25 3RV23 31-4BC10

25 11 Without 325 65 25 3RV23 31-4DC10

32 15 Without 416 65 25 3RV23 31-4EC10

36 18.5 Without 520 65 25 3RV23 31-4PC10

40 18.5 Without 585 65 22 3RV23 31-4UC10

45 22 Without 650 65 22 3RV23 31-4VC10

52 22 Without 741 65 22 3RV23 31-4WC10

59c 30 Without 845 a a 3RV23 31-4XC10

65c 30 Without 845 a a 3RV23 31-4JC10

73c 37 Without 949 a a 3RV23 31-4KC10

80cd 37 Without 1 040 a a 3RV23 31-4RC10

Size S2, with increased switching capacity

14 5.5 Without 208 100 25 3RV23 32-4SC10

17 7.5 Without 260 100 25 3RV23 32-4TC10

20 7.5 Without 260 100 25 3RV23 32-4BC10

25 11 Without 325 100 25 3RV23 32-4DC10

32 15 Without 416 100 25 3RV23 32-4EC10

36 18.5 Without 520 100 25 3RV23 32-4PC10

40 18.5 Without 585 100 22 3RV23 32-4UC10

45 22 Without 650 100 22 3RV23 32-4VC10

52 22 Without 741 100 22 3RV23 32-4WC10

59c 30 Without 845 a a 3RV23 32-4XC10

65c 30 Without 845 a a 3RV23 32-4JC10

73c 37 Without 949 a a 3RV23 32-4KC10

80cd 37 Without 1 040 a a 3RV23 32-4RC10

Illustrations are approximate

Page 9: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 2015 2-9

2MSP OVERLOAD

Illustrations are approximate

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80AMotor Starter Protectors - For Transformer Protection SelectionCLASS 10, without Auxiliary Switches

Motor starter protectors for the protection of transformers with high inrush current.

a�� The setting range of the thermal overload releases has been extended.

Auxiliary switches can be ordered separately(see "Mountable accessories").

3RV2411-0AA10

3RV2411-0AA20

3RV2421-4AA10

3RV2421-4AA20

3RV2431-4.A10

3RV2421-4WA10

Rated currentIn

Setting range thermal overload releases �

Instantaneous electronic releases Short-circuit

Breaking Capacity at 480 V AC

Short-circuit Breaking Capacity at 600 V AC

Screw terminals

A A A kA kA Order No.

Size S2

14 9.5 ... 14 328 10 10 3RV2431-4SA10

17 12 ... 17 410 10 10 3RV2431-4TA10

20 14 ... 20 410 10 10 3RV2431-4BA10

25 18 ... 25 512 10 10 3RV2431-4DA10

32 22 ... 32 656 10 10 3RV2431-4EA10

36 28 ... 36 820 10 10 3RV2431-4PA10

40 32 ... 40 820 10 10 3RV2431-4UA10

45 35 ... 45 922 10 10 3RV2431-4VA10

52 42 ... 52 1 025 10 10 3RV2431-4WA10

59a 49 ... 59 1 332 10 10 3RV2431-4XA10

65a 54 ... 65 1 332 10 10 3RV2431-4JA10

Page 10: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 20152-10

2MS

P OV

ERLO

AD

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80AMountable Accessories Accessories

Signaling Switchesc

3RV29 21-1M

3RV29 21-2M

VersionFor motorstarter protectors

Screw terminals

Spring-type terminals

Size Order No. Order No.

Signaling switchesb One signaling switch ca be mounted on the left per motor starter protector.

Separate tripped and short-circuit alarms, 1 NO + 1 NC each

S00 ... S2 3RV29 21-1M 3RV29 21-2M

Isolator modulesc

3RV29 28-1A

3RV2938-1A

VersionFor motorstarter protectors

Screw terminals

Spring-type terminals

Size Order No. Order No.

Isolator modulesd Visible isolating distance for isolating indi-vidual motor starter protectors from the network, lockable in disconnected position

S0, S00S2d

3RV2928-1A3RV2938-1A

——

a�� Each motor starter protector/circuit breaker can be fitted with one transverse and one lateral auxiliary switch. The lateral auxiliary switch with 2 NO + 2 NC is used without a transverse auxiliary switch.

b�� The 3RV29 auxiliary and signaling switches with 1 NO + 1 NC are also available with ring terminal lug connection. The Article No. must be changed in the 8th digit to "4": e.g. 3RV2901-4E.

c�� This accessory cannot be used for the 3RV27 and 3RV28 circuit breakers.

d�� The isolator module for size S2 can be used only with 3RV2 motor starter protectors/circuit breakers up to max. 65 A. Similarly, it cannot be usedwith the transverse auxiliary switch..

Illustrations are approximate

Auxiliary switchesa

3RV29 01-1E

3RV29 01-2E

3RV29 01-1G

3RV29 01-0H

VersionFor motorstarter protectors

Screw terminals

Spring-type terminals

Size Order No. Order No.

Transverse auxiliary switches for front mounting 1 CO1 NO + 1 NCb

2 NO

S00 ... S2 3RV29 01-1D 3RV29 01-1E 3RV29 01-1F

—3RV29 01-2E3RV29 01-2F

Electronic compatible transverse auxil-iary switches Mountable on the front, for operation in dusty atmosphere and in electronic circuits with low operating currents

1 CO S00 ... S2 3RV29 01-1G —

Covers for transverse auxiliary switch (PKG* = 10 units)

S00 ... S2 3RV29 01-0H —

3RV29 01-1A

3RV29 01-2A

Lateral auxiliary switches mountable on the left 1 NO + 1 NCb

2 NO 2 NC2 NO + 2 NC

S00 ... S2

3RV29 01-1A 3RV29 01-1B 3RV29 01-1C 3RV29 01-1J

3RV29 01-2A 3RV29 01-2B 3RV29 01-2C —

Page 11: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 2015 2-11

2MSP OVERLOAD

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80AMountable Accessories AccessoriesAuxiliary releasesc

3RV29 02-1AV0

3RV29 02-2AV0

3RV29 22-1CP0

3RV29 02-2DB0

Rated control supply voltage Us

For motorstarter protectors

Screw terminals

Spring-type terminals PS*

AC 50 Hz

AC 60 Hz

AC 50/60 Hz 100 % ON perioda

AC/DC 50/60Hz, DC5 s ON periodb DC

V V V V V Size Order No. Order No.

Undervoltage releases

Shunt releases

— — — — 24 S00 ... S2 3RV29 02-1AB4 — 1 unit

24 — — — — S00 ... S2 3RV29 02-1AB0 — 1 unit

110 120 — — — S00 ... S2 3RV29 02-1AF0 — 1 unit

— 208 — — — S00 ... S2 3RV29 02-1AM1 — 1 unit

230 240 — — — S00 ... S2d 3RV29 02-1AP0 3RV29 02-2AP0 1 unit

400 440 — — — S00 ... S2d 3RV29 02-1AV0 3RV29 02-2AV0 1 unit

415 480 — — — S00 ... S2 3RV29 02-1AV1 — 1 unit

500 600 — — — S00 ... S2 3RV29 02-1AS0 — 1 unit

Undervoltage releases with leading auxiliary contacts 2 NO

230 240 — — — S00 ... S2 3RV29 22-1CP0 3RV29 22-2CP0 1 unit

400 440 — — — S00 ... S2 3RV29 22-1CV0 3RV29 22-2CV0 1 unit

415 480 — — — S00 ... S2d 3RV29 22-1CV1 3RV29 22-2CV1 1 unit

Shunt releases

— — 20 ... 24 20 ... 70 — S00 ... S2 3RV29 02-1DB0 3RV29 02-2DB0 1 unit

— — 90 ... 110 70 ... 190 — S00 ... S2d 3RV29 02-1DF0 3RV29 02-2DF0 1 unit

— — 210 ... 240 190 ... 330 — S00 ... S2d 3RV29 02-1DP0 3RV29 02-2DP0 1 unit

— — 350 ... 415 330 ... 500 — S00 ... S2 3RV29 02-1DV0 — 1 unit

— — 500 500 — S00 ... S2 3RV29 02-1DS0 — 1 unit

a�� The voltage range is valid for 100 % (infinite) ON period. The response voltage lies at 0.9 of the lower limit of the voltage range.

b�� The voltage range is valid for 5 s ON period at AC 50/60Hz and DC. The response voltage lies at 0.85 of the lower limit of the voltage range.

c�� One auxiliary release can be mounted on the right per motor starter protector (does not apply to 3RV21 motor starter protectors with overload relay function).

d�� The 3RV29 auxiliary releases are also available with ring lug terminal connection. The Order No. must be changed in the 8th position to "4": e. g. 3RV29 02-4AP0.

* You can order this quantity or a multiple thereof.Illustrations are approximate

Page 12: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 20152-12

2MS

P OV

ERLO

AD

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80ABusbar Accessories AccessoriesThree-phase Busbarsa

3RV19 15-1AB

3RV19 15-1BB

3RV19 15-1CB

3RV19 15-1DB

Modularspacing

Number of motor starter protectors that can be connected

Rated currentIn at 690 V

For motorstarter protector Order No. PS*

Without lateralaccessories

With lateralauxiliary switch

With auxiliaryrelease

mm A Size

For feeding several motor starter protectors with screw terminals, mounted side by side on standard mounting rails, insulated, with touch protection.

45c 2345

————

— — — —

63 63 63 63

S00, S0b S00, S0b S00, S0b S00, S0b

3RV19 15-1AB 3RV19 15-1BB 3RV19 15-1CB 3RV19 15-1DB

1 unit 1 unit 1 unit 1 unit

55d ————2 3 4

2345— — —

— — —————

63 63 63 63 108 108 108

S00, S0b S00, S0b S00, S0b S00, S0b

S2 S2 S2

3RV19 15-2AB 3RV19 15-2BB 3RV19 15-2CB 3RV19 15-2DB3RV19 35-1A 3RV19 35-1B 3RV19 35-1C

1 unit 1 unit 1 unit 1 unit 1 unit 1 unit 1 unit

63e — —

— —

24

63 63

S00, S0b S00, S0b

3RV19 15-3AB 3RV19 15-3CB

1 unit 1 unit

75e — ——

2 3 4

23 4

108 108 108

S2 S2 S2

3RV19 35-3A3RV19 35-3B3RV19 35-3C

1 unit 1 unit 1 unit

Three-phase Infeed Terminals

3RV29 25-5AB

3RV29 35-5A

Conductor cross-section

Tighteningtorque

For motor starter protector Order No. PS*

Solid or approx.stranded

Finely strandedwith end sleeve

AWG cables,solid or stranded

mm2 mm2 AWG Nm Size

Connection from top

2.5 ... 16 2 x (2.5 ... 50)f,1 x (2.5 ... 70)f

2.5 ... 16 2 x (2.5 ... 50)f, 1 x (2.5 ... 70)f

10 ... 4 2 x (10 ... 1/0)f, 1 x (10 ... 2/0)f

3 ... 44 ... 6

S00, S0 S2

3RV29 25-5AB 3RV29 35-5A

1 unit 1 unit

Three-phase Infeed Terminals for constructing "Type E Starters"

3RV29 25-5EB

3RV29 35-5E

Conductor cross-section

Tighteningtorque

For motor starter protector Order No. PS*

Solid or approx.stranded

Finely strandedwith end sleeve

AWG cables,solid or stranded

mm2 mm2 AWG Nm Size

Connection from top

2.5 ... 162 x (2.5 ... 50)f, 1 x (2.5 ... 70)f

2.5 ... 16 2 x (2.5 ... 35)f, 1 x (2.5 ... 50)f

10 ... 4 2 x (10 ... 1/0)f, 1 x (10 ... 2/0)f

3 ... 4 4 ... 6

S00, S0 S2

3RV29 25-5EB 3RV29 35-5E

1 unit 1 unit

Covers for Connection Tags

3RV19 15-6AB

VersionFor motorstarter protector Order No.

PS*

Size

Touch protection for empty positions S00, S0S2

3RV19 15-6AB3RV19 35-6A

10 Units 5 Units

* You can order this quantity or a multiple thereof.Illustrations are approximate

a�� Not suitable for 3RV21 motor starter protectors for motor protection with overload relay function and for 3RV27 and 3RV28 circuit breakers according to UL 489/ CSA C22.2 No. 5.

b�� Approved for motor starter protectors size S0 with In ≤ 32 A.

c�� For 3RV2 motor starter protectors without accessories mounted on the side.

d�� For 3RV2 motor starter protectors with auxiliary switches with 1 NO + 1 NC, 2 NO and 2 NC mounted on the left (9 mm wide).

e�� For 3RV2 motor starter protectors with mounted accessories (18 mm wide). Auxiliary switches with 2 NO + 2 NC or signaling switch (mounted on the

left) or with auxiliary release (mounted on the right).

f�� If two different conductor cross-sections are connected to one clamping point, both cross-sections must be in the range specified.

Page 13: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 2015 2-13

2MSP OVERLOAD

a�� For the assembly of feeders for reversing starters comprising a motor starter protector and two contactors.

For additional busbar adapters, see Catalog LV 10 "Low-Voltage Power Distribution and Electrical Installation Technology".

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80ABusbar Accessories AccessoriesBusbar Adapters

8US12 51-5DS10

8US12 51-5DT11

8US12 50-5AS10

8US12 50-5AT10

For motor starterprotectors/circuit breakers

Ratedcurrent

Connectingcable

Adapterlength

Adapterwidth

Rated voltage Order No. PS*

Size A AWG mm mm V

Busbar adapters for 60 mm systems

For flat copper profiles according to DIN 46433 Width: 12 mm and 30 mm Thickness: 5 mm and 10 mm also for T and double-T special profilesb For motor starter protectors/circuit breakers with screw terminals Screw terminals S00, S0S0S2S2S2a

2532808080

1210444

200260200260260

45455555118

690690690690690

8US12 51-5DS108US12 51-5NT108US12 61-5MS138US12 61-6MT108US12 11-6MT10

1 Unit 1 Unit1 Unit 1 Unit1 Unit

b For motor starter protectors/circuit breakers with spring-type terminals Spring-type terminals

S00, S0S00, S0S0

252532

121210

200260260

454545

690690690

8US12 51-5DS118US12 51-5DT118US12 51-5NT11

1 Unit 1 Unit 1 Unit

Accessories

Device holdersFor lateral mounting tobusbar adapters

——

——

200 260

45 45

——

8US12 50-5AS10 8US12 50-5AT10

1 Unit 1 Unit

Side modulesFor widening of busbar adapters

— — 200 9 — 8US19 98-1BA10 10 Units

SpacersFor fixing the load feeder onto the busbar adapter

— — — — — 8US19 98-1BA10 50 Units

Vibration and shock kitsFor high vibration andshock loadsS00/S0S2

— —

— —

— —

— —

— 8US19 98-1CA108US19 98-1DA10

2 Units1 Unit

* You can order this quantity or a multiple thereof.Illustrations are approximate

Page 14: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 20152-14

2MS

P OV

ERLO

AD

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80ARotary Operating Mechanisms Accessories

Selection

3RV29 26-0K Door-coupling Rotary Operating Mechanism

Door-coupling Rotary Operating Mechanisms

Motor starter protectors/circuit breakers with a rotary operating mechanism can be mounted in a control cabinet and operated externally by means of a door-coupling rotary operating mechanism. When the cabinet door with motor starter protector/circuit breaker is closed, the operating mechanism is coupled.

When the motor starter protector/circuit breaker closes, the coupling is locked which prevents the door from being opened unintentionally. This interlock can be defeated by the maintenance personnel. In the OPEN position, the rotary operating mechanism can be secured against reclosing with up to three padlocks. Inadvertent opening of the door is not possible in this case either.

3RV29 26-2B Door-coupling Rotary Operating Mechanism for arduous conditions

Door-coupling Rotary Operating Mechanisms

3RV29 26-0B

Version Color of handleVersion of extension shaft

For motor starter protector Order No. PS*

mm Size

The door-coupling rotary operating mechanisms consist of a knob, a coupling driver and a 130/330 mm long extension shaft (6 mm x 6 mm).

The door-coupling rotary operating mechanisms are designed to degree of protection IP64. The door locking device prevents accidental opening of the control cabinet door in the ON position of the motor starter protector/circuit breaker.The OFF position can be locked with up to three padlocks.

Door-coupling Rotary Operating Mechanisms

Black 130 330

S00 ... S2S00 ... S2

3RV29 26-0B 3RV29 26-0K

1 Unit 1 Unit

EMERGENCYSTOPDoor-coupling Rotary Operating Mechanisms

Red/Yellow 130 330

S00 ... S2S00 ... S2

3RV29 26-0C 3RV29 26-0L

1 Unit 1 Unit

Door-coupling Rotary Operating Mechanisms for arduous conditions

3RV29 26-2B

3RV29 26-2B

Version Color of handleVersion of extension shaft

For motor starter protector Order No. PS*

mm Size

The door-coupling rotary operating mechanisms consist of a knob, a coupling driver, an extension shaft of 300 mm in length (8 mm x 8 mm), a spacer and two metal brackets, into which the motor starter protector is inserted.

The door-coupling rotary operating mechanisms are designed to degree of protection IP65. The door interlocking reliably prevents opening of the control cabinet door in the ON position of the motor starter protector. The OFF position can be locked with up to 3 padlocks.

Laterally mountable auxiliary releases and two-pole auxiliary switches can be used. The door-coupling rotary operating mechanisms thus meet the requirements for isolating functions according to IEC 60947-2.

Door-coupling Rotary Operating Mechanisms

Gray 300 S00, S0S2

3RV29 26-2B3RV29 36-2B

1 Unit 1 Unit

EMERGENCYSTOPDoor-coupling Rotary Operating Mechanisms

Red/Yellow 300 S00, S0S2

3RV29 26-2C3RV29 36-2C

1 Unit 1 Unit

* You can order this quantity or a multiple thereof.Illustrations are approximate

Page 15: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 2015 2-15

2MSP OVERLOAD

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80AMounting Accessories AccessoriesAccessories for "Self-Protected Combination Motor Controllers (Type E)" according to UL 508/UL 60947-4-1

The 3RV20 motor starter protectors with screw terminals are approved according to UL 508/UL 60947-4-1 as "Self-Protected Combination Motor Controllers (Type E)".

This requires increased clearance and creepage distances (1 inch and 2 inches respectively) at the input side of the device, which are achieved by mounting a terminal block or a phase barrier.

SIRIUS 3RV2928-1H Terminal Block

SIRIUS 3RV2938-1K Phase Barrier

Motor starterprotectors/circuit breakers Size

Essential accessoriesfor "Self-Protected CombinationMotor Controllers (Type E)" accordingto UL 508/UL 60947-4-1

3RV201., 3RV202. S00/S0 3RV2928-1H terminal block or3RV2928-1K phase barrier

3RV2031-4B1.,3RV2031-4D.1.,3RV2031-4E1.,3RV2031-4P.1.,3RV2031-4S.1.,3RV2031-4T.1.,3RV2031-4U.1.,3RV2031-4V.1.

S2 — —

3RV2031-4J.1., 3RV2031-4K.1., 3RV2031-4R.1., 3RV2031-4W.1., 3RV2031-4X.1., 3RV2032

S2 3RV2938-1K phase barrier

— — No accessories needed

Special three-phase infeed terminals are required for constructing "Type E Starters" with an insulated three-phase busbar system.

The 3RV29 infeed system also enables the assembly of "Type E Starters".

Note: According to CSA, these terminal blocks and the phase barriers can be omitted when the device is used as a "Self-Protected Combination Motor Controller (Type E)".

Link Modules

Feeders can be easily assembled from single devices with the help of the link modules. The following table shows the different combination options for devices with screw or spring-type terminals.

Combinationdevice

3RV2motorstarterprotectors/circuitbreakersSize

3RT2 contactors;3RW30, 3RW40soft starters;3RF34 solid-statecontactorsSize

Link modules

Screw terminals

Spring-type

terminals

Link modules for connecting switching devices to 3RV2 motor starter protectors/circuit breakersa

3RT2 contactorswith AC orDC coil

S00 S003RA19 21-1DA00 3RA29 11-2AA00

S0 S00

S2 S2 3RA2931-1AA00 — —

3RT2 contactorswith AC coil

S0 S03RA29 21-1AA00 3RA29 21-2AA00

S00 S0

3RT2 contactorswith DC coil

S0 S03RA29 21-1BA00 3RA29 21-2AA00

S00 S0

3RW30 softstarters

S00 S03RA29 21-1BA00 3RA29 11-2GA00

S00 S00

3RW30/3RW40soft starters

S0 S003RA29 21-1BA00 3RA29 21-2GA00

S0 S0

S2b S2b 3RA2931-1AA00 — —

3RF34 solidstatecontactors

S00 S03RA29 21-1BA00 — —

S00/S0 S00

Hybrid link modules for connecting contactors with spring-type terminals to 3RV2 motor starter protectors/circuit breakers with screw terminalsc

3RT2 contactorswith AC orDC coil

S00 S00 3RA29 11-2FA00 — —

3RT2 contactorswith AC orDC coil

S0 S0 3RA29 21-2FA00 — —

— — Version not possible

Note:

b Link modules can be used in

- Sizes S00 and S0: up to max. 32 A - Size S2: up to max. 65 A

b Hybrid link modules can be used in

- Sizes S00 and S0: up to max. 32 A

a�� The link modules cannot be used for the 3RV2.21-4PA1., 3RV2.21-4FA1., 3RV2.31-4K.1., 3RV2.31-4R.1., 3RV2.32-4K.1., 3RV2.32-4R.1., 3RV27 and 3RV28 motor starter protectors/circuit breakers.

b�� To assemble the feeder between a motor starter protector and a soft starter in size S2, the 3RA2932-1AC00 standard mounting rail adapter must be used.

c�� The motor starter protector to contactor hybrid link modules cannot be used for the 3RV2.21-4PA1., 3RV2.21-4FA1., 3RV27 and 3RV28 motor starter protectors/circuit breakers. They are only suitable for constructing direct-on-line starters.

Page 16: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 20152-16

2MS

P OV

ERLO

AD

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80AMounting Accessories Accessories

Tools for opening spring-type terminals

3RA29 08-1A

Version For motor starter protector Spring-type terminals PS*Size Order No.

Screwdriversfor all SIRIUS devices with spring-type terminals

Length approx. 200 mm,3.0 mm x 0.5 mm,titanium gray/black,partially insulated

S00 ... S2 3RA29 08-1A 1 Unit

Terminal blocks and phase barriers for "Self-Protected Combination Motor Controllers (Type E)" according to UL 508/UL 60947-4-1

3RV29 28-1H

3RV29 28-1K

3RV29 38-1K

VersionFor motor starter protector Order No. PS*Size

Note: UL 508/UL 60947-4-1 approval demands 1-inch clearance and 2-inch creepage distance for "Self-Protected Combination Motor Controllers (Type E)". The following terminal blocks or phase barriers must be used for the 3RV20 motor starter protectors with screw terminals. The construction of 3RV20 motor starter protectors with spring-type terminals with the 3RV29 infeed system is also approved as "Self-Protected Combination Motor Controllers (Type E)" according to UL 508/UL 60947-4-1.

The terminal block or phase barriers cannot be used in combination with the 3RV19.5 three-phase busbars.For construction with three-phase busbars, see "Busbar Accessories" page 7/34 onwards.

Terminal Blocks Type EFor extended clearance andcreepage distances (1 and 2 inch)

S00, S0 3RV29 28-1H 1 Unit

Phase BarriersFor extended clearance andcreepage distances (1 and 2 inch)

S00, S0 S2

3RV29 28-1K 3RV29 38-1K

1 Unit 1 Unit

a�� The link modules for motor starter protector to contactor cannot be used for the 3RV2. 21-4PA1., 3RV2. 21-4FA1., 3RV27 and 3RV28 motor starter

protectors.

b�� A spacer for height compensation on AC contactors size S0 is optionally available.

Note: Link modules can be used up to max. 32 A.

Covers

3RV29 08-0P

3RT29 36-4EA2

Version For motor starter protector Order No. PS*

Size

Scale coversSealable, for covering the set current scale

3RV20, 3RV21, 3RV24:S00 ... S2

3RV29 08-0P 10 Unit

Covers for devices with screwterminals (box terminals)Additional touch protection for fasteningto the box terminals(2 units required per device)

b Main current level

S2

Screw terminals

1 Unit3RT2936-4EA2

* You can order this quantity or a multiple thereof.Illustrations are approximate

Page 17: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 2015 2-17

2MSP OVERLOAD

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80AMounting Accessories AccessoriesLink modules for motor starter protector to contactora

3RA29 21-1AA00

3RA29 11-2AA00

Actuating voltage ofcontactor

SizeOrder No. PS*3RT2 contactors 3RV2 motor starter protectors

For mechanical and electrical connection between motor starter protector and contactor with screw terminals Screw terminals Single-unit packagingAC/DCACDCAC/DC

Multi-unit packagingAC/DCACDCAC/DC

S00S0S0S2

S00S0S0S2

S00/S0S00/S0S00/S0S2

S00/S0S00/S0S00/S0S2

3RA19 21-1DA003RA29 21-1AA003RA29 21-1BA003RA29 31-1AA00

3RA19 21-1D3RA29 21-1A3RA29 21-1B3RA29 31-1A

1 Unit 1 Unit 1 Unit 1 Unit

10 Units10 Units10 Units5 Units

a�� The link modules from motor starter protector to contactor cannot be used for the 3RV2.21-4PA1., 3RV2.21-4FA1., 3RV2.31-4K.1., 3RV2.31-4R.1.,

3RV2.32-4K.1., 3RV2.32-4R.1., 3RV27 and 3RV28 motor starter protectors/circuit breakers.

Note:

b Link modules can be used in

- Sizes S00 and S0 up to max. 32 A - Size S2: up to max. 65 A

* You can order this quantity or a multiple thereof.Illustrations are approximate

Page 18: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 20152-18

2MS

P OV

ERLO

AD

Protection EquipmentOverload Relays Introduction

3RU21

3RB30

3RB31

Type 3RU21 3RB30 3RB31

SIRIUS overload relays up to 40A

Applications

System protection 4a 4a 4a

Motor protection 4 4 4

Alternating current, three-phase 4 4 4

Alternating current, single-phase 4 — — — —

Direct current 4 — — — —

Size of contactor S00, S0, S2 S00, S0, S2 S00, S0, S2

Rated operational current IeSize S00Size S0Size S2

AAA

Up to 16Up to 40Up to 80

Up to 16Up to 40Up to 80

Up to 16Up to 40Up to 80

Rated operational voltage Ue V 690 AC 690 AC 690 AC

Rated frequency Hz 50/60 50/60 50/60

Trip class CLASS 10, 10A CLASS 10E, 20E CLASS 5E, 10E, 20E, 30E (adjustable)

Thermaloverload release

AA

0.11 ... 0.16 up to 70 ... 80 — — — —

Electronic overload releases

AA — — 0.1 ... 0.4 up to

20 ... 800.1 ... 0.4 up to 20 ... 80

Accessories

For sizes S00 S0 S2 S00 S0 S2 S00 S0 S2

Terminal brackets for stand-alone installation 4 4 4 4 4 4 4 4 4

Mechanical RESET 4 4 4 4 4 4 4 4 4

Cable releases for RESET 4 4 4 4 4 4 4 4 4

Electrical remote RESET 4 4 4 — — — — — — Integrated in the unit

Terminal coversRing lug connectionsFor box terminals

4b

— —4b

— —— —4

— —— —

— —— —

— —4

— —— —

— —— —

— —4

Sealable covers for setting knobs 4 4 4 4 4 4 4 4 4

a�� The units are responsible in the main circuit for overload protection of the assigned electrical loads (e.g. motors), feeder cable, and other switching and protection devices in the respective load feeder.

b Terminal covers for ensuring finger-safe touch protection are available for 3RU21 overload relays with ring terminal lug connections for mounting onto contactors.

4 Has this function or can use this accessory— — Does not have this function or cannot use

this accessory

* You can order this quantity or a multiple thereof.Illustrations are approximate

Page 19: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 2015 2-19

2MSP OVERLOAD

Overload RelaysSIRIUS 3RU2 Thermal Overload Relays Overview

Order No. Scheme

Digit of the Order No.1st - 3rd ooo

4th o

5th o

6th o

7tho —

8th o

9th o

10th o

11th o

Thermal overload relays 3 R U

SIRIUS 2nd generation 2

Device series o

Size, rated operational current and power o o

Setting range of the overload release o o

Connection method o

Installation type o

Example 3 R U 2 1 1 6 — 0 A B 0

6

2

15

4

3

SIRIUS 3RU2136-4.B0 Thermal Overload Relay

a�� Switch position indicator and TEST function of the wiring: Indicates a trip and enables the wiring test.

b�� Motor current setting: Setting the device to the rated motor current is easy with the large rotary knob.

c�� Connecting terminals: Depending on the device version, the connecting terminals for screw, spring-type or ring terminal lug connection are configured for the main and auxiliary circuit.

d�� STOP button: If the STOP button is pressed, the NC contact is opened. This switches off the contactor downstream. The NC contact is closed again when the button is released.

e�� Selector switch for manual/automatic RESET and RESET button: With this switch you can choose between manual and automatic RESET. A device set to manual RESET can be reset locally by pressing the RESET button. A remote RESET is possible using the RESET modules (accessories), which are independent of size.

f�� Connection for mounting onto contactors: Optimally adapted in electrical, mechanical and design terms to the contactors. The overload relay can be connected directly to the contactor using these pins. Stand-alone installation is possible as an alternative (in conjunction with a terminal bracket for stand-alone installation).

A sealable transparent cover can be optionally mounted (accessory). It secures the motor current setting against adjustment.

The 3RU21 thermal overload relays up to 80 A have been designed for inverse-time delayed protection of loads with normal starting (for "Function", see manual

"SIRIUS Innovations – SIRIUS 3RU2/3RB3 Overload Relays", http://support.automation.siemens.com/WW/view/en/60298164) against excessive temperature rises due to overload or phase failure.

An overload or phase failure results in an increase of the motor current beyond the set rated motor current. Via heating elements, this current rise heats up the bimetal strips inside the device which then bend and as a result trigger the auxiliary contacts by means of a tripping mechanism. The auxiliary contacts then switch off the load by means of a contactor. The break time depends on the ratio between the tripping current and current setting Ie and is stored in the form of a long-term stable tripping characteristic (see "Characteristic Curves" http://support.automation.siemens.com/WW/view/en/ 34291410/134300).

The "tripped" status is signaled by means of a switch position indicator. Resetting takes place either manually or automatically after a recovery time has elapsed (for "Function", see manual "SIRIUS Innovations – SIRIUS 3RU2/3RB3 Overload Relays", http://support.automation.siemens.com/WW/view/en/60298164).

The 3RU2 thermal overload relays are suitable for operation with frequency converters. Please follow the instructions in the manual "SIRIUS Innovations – 3RU2/3RB3 Overload Relays", see http://support.automation.siemens.com/WW/view/en/60298164.

The devices are manufactured in accordance with environmental guidelines and contain environmentally friendly and reusable materials. They comply with all important worldwide standards and approvals.

3RU11 overload relays for currents over 80 A in size S3.

Use in hazardous areas

The 3RU21 thermal overload relays are suitable for the protection of motors with "Flameproof enclosure d" or "Increased safety e" types of protection.

EC type test certificate for Category (2) G/D exists. It has the number DMT 98 ATEX G001.

Note: The Order No. scheme is presented here merely for information purposes and for better understanding of the logic behind the order numbers.

For your orders, please use the order numbers quoted in the catalogue in the Selection and ordering data section.

Page 20: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 20152-20

2MS

P OV

ERLO

AD

Overload RelaysSIRIUS 3RU2 Thermal Overload Relays Selection3RU21 thermal overload relays for mounting onto contactora

Features and Technical Specifications:b Connection methods

- Main circuit: Screw terminals with box terminal - Auxiliary circuit: Either screw or spring-type terminals

b Overload and phase failure protection

b Auxiliary contacts 1 NO + 1 NC

b Manual and automatic RESET

b Switch position indicators

b TEST function

b STOP button

b Sealable covers (optional accessory)

3RU2136-4.B0

3RU2136-4.D0

Size contactor Trip ClassCurrent setting value of the inverse-time delayed overload release

Short-circuit protection with fuse, type of coordination "2", operational class gGb

Screw terminals

Spring-type terminals

Class A A Order No. Order No.

Size S2

S2 10101010

11 ... 1614 ... 2018 ... 2522 ... 32

40 506380

3RU2136-4AB03RU2136-4BB03RU2136-4DB03RU2136-4EB0

3RU2136-4AD03RU2136-4BD03RU2136-4DD03RU2136-4ED0

1010101010

28 ... 4036 ... 4540 ... 5047 ... 5754 ... 65

80100100100125

3RU2136-4FB03RU2136-4GB03RU2136-4HB03RU2136-4QB03RU2136-4JB0

3RU2136-4FD03RU2136-4GD03RU2136-4HD03RU2136-4QD03RU2136-4JD0

10A10A

62 ... 7370 ... 80

160160

3RU2136-4KB03RU2136-4RB0

3RU2136-4KD03RU2136-4RD0

a�� With the suitable terminal supports (see "Accessories", page 7/103), the 3RU2 overload relays for mounting on contactors can also be installed as stand-alone units.

b�� Maximum protection by fuse only for overload relay, type of coordination "2".

Fuse values in connection with contactors, see Configuration Manual "Configuring SIRIUS

Innovations – Selection Data for Fuseless and Fused Load Feeders", http://support.automation.siemens.com/WW/view/en/50250599.

Illustrations are approximate

Page 21: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 2015 2-21

2MSP OVERLOAD

Overload RelaysSIRIUS 3RU2 Thermal Overload Relays Selection

Features and Technical Specifications:b Connection methods

- Sizes S00 and S0: Main and auxiliary circuit: Either screw or spring-type terminals

- Size S2: Main circuit: Screw terminals with box terminal Main circuit: Either screw or spring-type terminals

b Auxiliary contacts 1 NO + 1 NC

b Manual and automatic RESET

b Switch position indicators

b TEST function

b STOP button

b Sealable covers (optional accessory)

3RU2136-4.B1

3RU2136-4.D1

Size contactor Trip ClassCurrent setting value of the inverse-time delayed overload release

Short-circuit protection with fuse, type of coordination "2", operational class gGa

Screw terminals

Spring-type terminals

Class A A Order No. Order No.

Size S2

S2 101010

22 ... 3228 ... 4036 ... 45

8080100

3RU2136-4EB13RU2136-4FB13RU2136-4GB1

3RU2136-4ED13RU2136-4FD13RU2136-4GD1

101010

40 ... 5047 ... 5754 ... 65

100100125

3RU2136-4HB13RU2136-4QB13RU2136-4JB1

3RU2136-4HD13RU2136-4QD13RU2136-4JD1

10A10A

62 ... 7370 ... 80

160160

3RU2136-4KB13RU2136-4RB1

3RU2136-4KD13RU2136-4RD1

a�� Maximum protection by fuse only for overload relay, type of coordination "2".

Fuse values in connection with contactors, see

Configuration Manual "Configuring SIRIUS Innovations – Selection Data for Fuseless and Fused Load Feeders", http://support.automation.siemens.com/WW/view/en/50250599.

3RU21 thermal overload relays for stand-alone installation, size S2, CLASS 10

Illustrations are approximate

Page 22: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 20152-22

2MS

P OV

ERLO

AD

Overload RelaysSIRIUS 3RU2 Thermal Overload Relays Accessories

* You can order this quantity or a multiple thereof.Illustrations are approximate

Overload relays for standard applications

Features and Technical Specifications:b Connection methods

- Main circuit: Screw terminals with box terminal - Auxiliary circuit: Either screw or spring-type terminals

b Overload and phase failure protection

b Auxiliary contacts 1 NO + 1 NC

b Manual and automatic RESET

b Switch position indicators

b TEST function

b STOP button

b Sealable covers (optional accessory)

Terminal Brackets for Stand-alone Installation

3RU2916-3AA01

Version Size Screw terminals PS*

Order No.

Terminal supports for overload relays with screw terminals

For separate mounting of the overload relays; screw and snap-on mounting onto standard mounting rail

S00S0S2

3RU2916-3AA013RU2926-3AA013RU2936-3AA01

1 unit1 unit1 unit

Terminal Covers

3RT29 36-4EA2

Version Size Screw terminals PS*

Order No.

Covers for devices with screw terminals (box terminals)

Additional touch protection for fastening to the box terminalsb Main current level S2 3RT29 36-4EA2 1 unit

Mechanical RESET

3RU29 00-1A

with pushbutton andextension plunger

Version Size Order No. PS*

Resetting plungers, holders and formers S00 ... S2 3RU29 00-1A 1 unit

Pushbuttons with extended stroke(12 mm), IP65, Ø 22 mm S00 ... S2 3SB30 00-0EA11 1 unit

Extension plungersFor compensation of the distance between the pushbutton and the unlatching button of the relay

S00 ... S2 3SX1 335 1 unit

Cable Releases with holder for RESET

3RU29 00-1.

Version Size Order No. PS*

For Ø 6.5 mm hole in the control panel; max. control panel thickness 8 mm

b Length 400 mm

b Length 600 mmS00 ... S2

S00 ... S2

3RU29 00-1B

3RU29 00-1C

1 unit 1 unit

Modules for Remote RESET, Electrical

3RU19 00-2A.71

Version Size Order No. PS*

Operating range 0.85 ... 1.1 x Us, power consumption AC 80 VA, DC 70 W, ON period 0.2 ... 4 s, switching frequency 60/hb 24 ... 30 V AC/DC

b 110 ... 127 V AC/DC

b 220 ... 250 V AC/DC

S00 ... S2

S00 ... S2

S00 ... S2

3RU19 00-2AB71

3RU19 00-2AF71

3RU19 00-2AM71

1 unit

1 unit

1 unit

Sealable Covers

3RV29 08-0P

Version Size Order No. PS*

For covering the setting knobs S00 ... S2 3RV29 08-0P 1 unit

Page 23: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 2015 2-23

2MSP OVERLOAD

Overload RelaysSIRIUS 3RB3 Electronic Overload Relays Overview

8

5

6

71

4

3

2

SIRIUS 3RU3133-4.B0 Electronic Overload Relay

a�� Switch position indicator and TEST function of the wiring: Indicates a trip and enables the wiring test.

b�� Trip class setting/internal ground-fault detection (only 3RB31): Using the rotary switch you can set the required trip class and activate the internal ground-fault detection dependent on the start-up conditions.

c�� Solid-state test (device test): Enables a test of all important device components and functions.

d�� Connecting terminals (removable joint block for auxiliary circuits): Depending on the device version, the terminals for screw and spring-type connection are configured for the main and auxiliary circuit.

e�� Selector switch for manual/automatic RESET: With the slide switch you can choose between manual and automatic RESET.

f�� Motor current setting: Setting the device to the rated motor current is easy with the large rotary knob.

g�� A device set to manual RESET can be reset locally by pressing the RESET button. On 3RB31 overload relays an electrical remote RESET is integrated.

h�� Connection for mounting onto contactors: Optimally adapted in electrical, mechanical and design terms to the contactors 3RT2. The overload relay can be connected directly using these connection pins. Stand-alone installation is possible as an alternative (in conjunction with a terminal support for stand-alone installation).

A sealable transparent cover can be optionally mounted (accessory). It secures the motor current setting against adjustment.

The 3RB30/3RB31 electronic overload relays up to 80 A with internal power supply have been designed for inverse-time delayed protection of loads with normal and heavy starting (for "Function", see the manual "SIRIUS Innovations – SIRIUS 3RU2/3RB3 Overload Relays", http://support.automation.siemens.com/WW/view/en/60298164) against excessive temperature rises due to overload, phase unbalance or phase failure. An overload, phase unbalance or phase failure result in an increase of the motor current beyond the set rated motor current. This current rise is detected by the current transformers integrated into the devices and evaluated by corresponding solid-state circuits which then output a pulse to the auxiliary contacts. The auxiliary contacts then switch off the load by means of a contactor. The break time depends on the ratio between the tripping current and current setting Ie and is stored in the form of a long-term stable tripping characteristic (see "Characteristic Curves" http://support.automation.siemens.com/WW/view/en/34290881/134300).

In addition to inverse-time delayed protection of loads against excessive temperature rises due to overload, phase unbalance and phase failure, the 3RB31 electronic overload relays also allow internal ground-fault detection (not possible in conjunction with contactor assemblies for wye-delta starting). This provides protection of loads against high-resistance short circuits due to damage to the insulation material, moisture, condensed water etc.

The "tripped" status is signaled by means of a switch position indicator. Resetting takes place either manually or automatically after the recovery time has elapsed ("Function", see manual "SIRIUS Innovations – SIRIUS 3RU2/3RB3 Overload Relays", http://support.automation.siemens.com/WW/view/en/60298164).

The 3RB3 electronic overload relays are suitable for operation with frequency converters. Please follow the instructions in the manual "SIRIUS Innovations – 3RU2/3RB3 Overload Relays", see http://support.automation.siemens.com/WW/view/en/60298164.

The devices are manufactured in accordance with environmental guidelines and contain environmentally friendly and reusable materials. They comply with all important worldwide standards and approvals.

3RB20 and 3RB21 overload relays in sizes S2 to S10/S12.

Use in hazardous areas

The 3RB30/3RB31 electronic overload relays are suitable for the overload protection of motors with the following types of protection:

b II (2) G [Ex e] [Ex d] [Ex px]

b II (2) D [Ex t] [Ex p]

EC type test certificate for Group II, Category (2) G/D exists. It has the number PTB 09 ATEX 3001.

Illustrations are approximate

Page 24: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 20152-24

2MS

P OV

ERLO

AD

Overload RelaysSIRIUS 3RB3 Electronic Overload Relays Selection

3RB3036-1.B0

3RB3036-1.W1

3RB3036-1.D0

3RB3036-1.X1

Size contactor Trip ClassCurrent setting value of the inverse-time delayed overload release

Short-circuit protection with fuse, type of coordination "2", operational class gGa

Screw terminals

Spring-type terminals

Class A A Order No. Order No.

Size S2

S2 Devices with screw terminals (main current side) and for mounting onto contactorb

10 10

12 ... 5020 ... 80

250250

3RB3036-1UB03RB3036-1WB0

3RB3036-1UD03RB3036-1WD0

Devices with straight-through transformer for stand-alone installation

10E 10E

12 ... 5020 ... 80

250250

3RB3036-1UW13RB3036-1WW1

3RB3036-1UX13RB3036-1WX1

Overload relays for standard applications

Features and Technical Specifications:b Connection methods

- Sizes S00 and S0: Main and auxiliary circuit: Either screw or spring-type terminals - Size S2: Main circuit: Screw terminals with box terminal or as straight through transformer Auxiliary circuit: Either screw or spring-type terminals

b Overload protection, phase failure protection and unbalance protection

b Internal power supply

b Auxiliary contacts 1 NO + 1 NC

b Manual and automatic RESET

b Switch position indicators

b TEST function and self-monitoring

b Sealable covers (optional accessory)

a�� Maximum protection by fuse only for overload relay, type of coordination "2". Fuse values in connection with contactors, see Configuration Manual

"Configuring SIRIUS Innovations – Selection Data for Fuseless and Fused Load Feeders"http://support. automation.siemens.com/WW/view/en/39714188.

b�� With the appropriate terminal supports, these overload relays can also be installed as stand-alone units.

Illustrations are approximate

Page 25: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 2015 2-25

2MSP OVERLOAD

Overload RelaysSIRIUS 3RB3 Electronic Overload Relays Selection

3RB3036-1.B0

3RB3036-1.W1

3RB3036-1.D0

3RB3036-1.X1

Size contactor Trip ClassCurrent setting value of the inverse-time delayed overload release

Short-circuit protection with fuse, type of coordination "2", operational class gGa

Screw terminals

Spring-type terminals

Class A A Order No. Order No.

Size S2

S2 Devices with screw terminals (main current side) and for mounting onto contactorb

20E 20E

12 ... 5020 ... 80

250250

3RB3036-2UB03RB3036-2WB0

3RB3036-2UD03RB3036-2WD0

Devices with straight-through transformer for stand-alone installation

20E 20E

12 ... 5020 ... 80

250250

3RB3036-2UW13RB3036-2WW1

3RB3036-2UX13RB3036-2WX1

3RB30 electronic overload relays, CLASS 20E

Features and Technical Specifications:b Connection methods

- Sizes S00 and S0: Main and auxiliary circuit: Either screw or spring-type terminals - Size S2: Main circuit: Screw terminals with box terminal or as straight through transformer Auxiliary circuit: Either screw or spring-type terminals

b Overload protection, phase failure protection and unbalance protection

b Internal power supply

b Auxiliary contacts 1 NO + 1 NC

b Manual and automatic RESET

b Switch position indicators

b TEST function and self-monitoring

b Sealable covers (optional accessory)

a�� Maximum protection by fuse only for overload relay, type of coordination "2". Fuse values in connection with contactors, see Configuration Manual

"Configuring SIRIUS Innovations – Selection Data for Fuseless and Fused Load Feeders"http://support. automation.siemens.com/WW/view/en/39714188.

b�� With the appropriate terminal supports, these overload relays can also be installed as stand-alone units.

Illustrations are approximate

Page 26: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 20152-26

2MS

P OV

ERLO

AD

Overload RelaysSIRIUS 3RB3 Electronic Overload Relays Selection

3RB3133-4.B0

3RB3133-4.W1

3RB3133-4.D0

3RB3133-4.X1

Size contactor Trip ClassCurrent setting value of the inverse-time delayed overload release

Short-circuit protection with fuse, type of coordination "2", operational class gGa

Screw terminals

Spring-type terminals

Class A A Order No. Order No.

Size S2

S2 Devices with screw terminals (main current side) and for mounting onto contactorb

5E, 10E, 20E or 30E adjustable

12 ... 5020 ... 80

250250

3RB3133-4UB03RB3133-4WB0

3RB3133-4UD03RB3133-4WD0

Devices with straight-through transformer for stand-alone installation

5E, 10E, 20E or 30E adjustable

12 ... 5020 ... 80

250250

3RB3133-4UW13RB3133-4WW1

3RB3133-4UX13RB3133-4WX1

Features and Technical Specifications:b Connection methods

- Sizes S00 and S0: Main and auxiliary circuit: Either screw or spring-type terminals - Size S2: Main circuit: Screw terminals with box terminal or as straight through transformer Auxiliary circuit: Either screw or spring-type terminals

b Overload protection, phase failure protection and unbalance protection

b Internal ground-fault detection (activatable)

b Internal power supply

b Auxiliary contacts 1 NO + 1 NC

b Manual and automatic RESET

b Switch position indicators

b TEST function and self-monitoring

b Sealable covers (optional accessory)

a�� Maximum protection by fuse only for overload relay, type of coordination "2". Fuse values in connection with contactors, see Configuration Manual

"Configuring SIRIUS Innovations – Selection Data for Fuseless and Fused Load Feeders"http://support. automation.siemens.com/WW/view/en/39714188.

b�� With the appropriate terminal supports, these overload relays can also be installed as stand-alone units.

3RB31 electronic overload relays, CLASS 5E, 10E, 20E or 30E (adjustable)

Illustrations are approximate

Page 27: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 2015 2-27

2MSP OVERLOAD

Overload RelaysSIRIUS 3RB3 Electronic Overload Relays AccessoriesOverload relays for standard applications

The following optional accessories are available for the 3RB30/3RB31 electronic overload relays:

b Size-specific terminal support for stand-alone installation, in sizes S00 and S0 also with spring-type terminals

b Manual and automatic RESET

More Information

Manuals

The following optional accessories are available for the 3RB30/3RB31 electronic overload relays:

b System Manual "SIRIUS Innovations – System Overview" http://support.automation.siemens.com/WW/view/en/60311318

b Manual "SIRIUS Innovations – SIRIUS 3RU2/3RB3 Overload Relays" http://support.automation.siemens.com/WW/view/en/60298164

b Cable release for resetting devices which are difficult to access (for all sizes)

b Sealable covers (optional accessory)

Terminal Brackets for Stand-alone Installation

3RU2916-3AA01

Version Size Screw terminals PS*

Order No.

Terminal supports for overload relays with screw terminals

For separate mounting of the overload relays; screw and snap-on mounting onto standard mounting rail

S00S0S2

3RU2916-3AA013RU2926-3AA013RU2936-3AA01

1 unit1 unit1 unit

Mechanical RESET

3RU29 00-1A

with pushbutton andextension plunger

Version Size Order No. PS*

Resetting plungers, holders and formers S00 ... S2 3RU29 00-1A 1 unit

Pushbuttons with extended stroke(12 mm), IP65, Ø 22 mm S00 ... S2 3SB30 00-0EA11 1 unit

Extension plungersFor compensation of the distance between the pushbutton and the unlatching button of the relay

S00 ... S2 3SX1 335 1 unit

Cable Releases with holder for RESET

3RU29 00-1.

Version Size Order No. PS*

For Ø 6.5 mm hole in the control panel; max. control panel thickness 8 mm

b Length 400 mm

b Length 600 mmS00 ... S2

S00 ... S2

3RU29 00-1B

3RU29 00-1C

1 unit 1 unit

* You can order this quantity or a multiple thereof.Illustrations are approximate

Page 28: Contents · 2017-07-04 · Contents Motor Starter Protectors Overview 2-2 ... 12th o — 13th o 14th o 15th o ... Type of motor starter protector o Size o Switching capacity o Setting

Siemens Industrial Control Products Catalogue Additions 20152-28

2MS

P OV

ERLO

AD

Notes