Upload
prasanna-kumar
View
224
Download
1
Embed Size (px)
Citation preview
8/9/2019 Control of Hvdc
1/38
CONTROL OF HVDC
CONVERTERS AND SYSTEMS
8/9/2019 Control of Hvdc
2/38
8/9/2019 Control of Hvdc
3/38
8/9/2019 Control of Hvdc
4/38
BASIS FOR SELECTION OF CONTROL
Following considerations influence the selection ofcontrol characteristics:
Prevention of large fluctuation in DC voltage/current
due to variation in AC side voltage
Maintaining direct voltage near rated value
Power factor at the receiving and sending ends
should be as high as possible
8/9/2019 Control of Hvdc
5/38
CONTROL IMPLEMENTATION
8/9/2019 Control of Hvdc
6/38
CONTROL IMPLEMENTATION
Tap changer control It is used to keep the converter firing angles (and ) within the
desired range
They are sized to allow for minimum and maximum steady statevoltage variation
Current limits: Maximum short circuit current is limited to 1.2 to 1.3 times
normal full load current to avoid thermal damage to
equipment
Minimum current limit is set to avoid ripple in the current
that may cause it to be discontinuous or intermittent
Minimum firing angle limit:
In case of a DC fault, the inverter station may switch to
rectification mode. This would result in reversal of power flow
To prevent this, the a minimum value for firing angle is set
8/9/2019 Control of Hvdc
7/38
CONTROL IMPLEMENTATION
Power control To transmit a scheduled power, the corresponding
current order is determined by:
Iord=Po/Vd
Bridge/converter unit control Determines firing angles and
sets their limits
Pole control
It coordinates the conversionof current order to a firing
angle order, tap changer
control and other protection
sequences
8/9/2019 Control of Hvdc
8/38
LIMITATIONS OF MANUAL CONTROL
The DC voltage at either end of transmission line may vary in asudden, unexpected and undesired manner because of
Short circuits or other disturbances on ac system
Faults in converters
It necessitates the rapid grid control to maintain or restore the
desired conditions on the DC side with available range of control
Fig. Shows ideal control characteristics of Rectifier and Inverter,
it is draw by viewing the transmission line from mid point : thegraph of voltage versus current and half line on each side.
Both characteristics are straight lines
8/9/2019 Control of Hvdc
9/38
Left hand (rectifier) side
Internal voltage = Vd01Cos
Slope = - (Rc1+ Rl/2)
Right hand (Inverter) side Internal voltage = Vd02Cos
Slope = + (Rc1+ Rl/2)
Nominal operating point : N where
rated current and voltage is Idn& Vdn
Note: Slopes of the lines are drawn on the assumption that at rated current the
voltage drop due to commutation is 8 % and line drop is 9 % of rated voltage and
hence
slope = 8 + 9/2 = 12.5 %
8/9/2019 Control of Hvdc
10/38
Let ac voltage at inverter drops by 12.5 % of Vdnthen
Intersection point with rectifier characteristics moves to point Acorresponding to 1.5 Idn
Further voltage drop of 12.5 % moves to point B and increase in currentto 2 Idn
If ac voltage at rectifier drops by 12.5 % of Vdn
while the inverter isnormal
Intersection point with inverter characteristics moves to point Ccorresponding to 0.5 Idn
Further voltage drop of 12.5 % moves to point D and decrease incurrent to nil.
In this Example, dip in ac voltage produces % change in dc current of4 times % change of voltage, such large fluctuations of current cannot be tolerated
The high over currents are undesirable, they lead to arcbacks in
rectifier and commutation failure in inverter
8/9/2019 Control of Hvdc
11/38
DESIRED FEATURES OF CONTROL
8/9/2019 Control of Hvdc
12/38
CONTROL CHARACTERISTICS
The control characteristics of theconvertor are the plots of thevariation of the direct voltage againstthe direct current.
The Natural Voltage Characteristiccorresponds to zero delay angle, =0. It as characteristic equation
Vd= Vd0Cos (3Lc/) Id
Constant Ignition Angle control
C.I.A.):
It is a similar characteristic which isparallel to the NV characteristic witha controllable intercept is Vd0Cos
8/9/2019 Control of Hvdc
13/38
Constant extinction angle control :
The Inverter is usually operated at constant extinction angle.This has the characteristic equation given by
Vd
= Vd0
Cos (3Lc
/) Id
8/9/2019 Control of Hvdc
14/38
Constant Current Control CC) :
In a d.c. link it is common practice to operate the link at constant
current rather than at constant voltage. (constant current means
that current is held nearly constant and not exactly constant)
In constant current control,
the power is varied by varying
the voltage. There is an
allowed range of current settings
within which the current varies.
8/9/2019 Control of Hvdc
15/38
Actual Control Characteristics :
8/9/2019 Control of Hvdc
16/38
Combined Characteristics :
8/9/2019 Control of Hvdc
17/38
The margin setting Idmbetween the current setting Ids for theinverter and for the rectifier is usually kept at about 10% to20% of the current setting.
The setting of the convertor operating as rectifier is kept higher
than the setting of that as inverter by the margin setting Idm
The usual operating point for power transfer is the intersectionof the CC control of the rectifier and the CEA control of theinverter.
It also be ensured by proper tap changing that the N.V.characteristic of the convertor operating in the rectificationmode is higher than the C.E.A. characteristic of the inverter, asVdoof the two ends are not necessarily equal
8/9/2019 Control of Hvdc
18/38
With convertor A operating as rectifier, and convertor Boperating as inverter, the steady state current under allcircumstances will remain within the upper limit (Ids+ Idm) andthe lower limit Ids.
i.e, the system direct current will not change by more than Idmunder all operating conditions.
By reversing the margin setting Idm, that is making the setting ofconvertor B to exceed that of A, power flow can be
automatically reversed.
Convertor B will then operate as a rectifier and A as an inverter.The reversal of power occurs as a result of the reversal ofpolarity of the voltage.
8/9/2019 Control of Hvdc
19/38
8/9/2019 Control of Hvdc
20/38
CONVERTER CONTROL
8/9/2019 Control of Hvdc
21/38
The ideal control system for an HVDC converter should meet the following
requirements Symmetrical firing of the valves under steady-state conditions.
Instant of firing to be decided with regard to permissible values ofcommutation voltage (rectifier) and commutation margin (inverter).
Minimal reactive-power consumption in the converters, subject to the
condition that it is achieved without an unacceptable risk of commutationfailure.
Insensitivity to normal variations in voltage and frequency of the AC supplynetwork.
Some degree of prediction of the optimum instant of firing in the inverters,
based on actual network voltage and direct current, subject to the conditionthat it is achieved without an unacceptable risk of commutation failure.
Current-control characteristics with sufficient speed and stability margin tocope with changing reference values and disturbances.
Continuous operating range from full rectification to full inversion.
8/9/2019 Control of Hvdc
22/38
FIRING ANGLE CONTROL :
The firing instant for all the valves are determined at ground
potential and the firing signals sent to individual thyristors
by light signals through fibreoptic cables.
While a signal pulse is adequate to turn on a thyristor, thegate pulse generator must send a pulse whenever required ,
if the particular valve is to be kept in a conducting state.
There are two basic firing schemes,
Individual phase control (IPC).
Equidistant pulse control (EPC).
8/9/2019 Control of Hvdc
23/38
INDIVIDUAL PHASE CONTROL
The firing instants are determined individually for each valve. In which constant delay (or extinction) angle is maintained for all the
valves in the steady state with respect to the earliest firing instant(i.e. the voltage crossing).
Phase control is a process in which forward current conduction ismaintained in a valve by varying the time period of cycle for shortperiod.
The generation of pulses at a valve is determined or known from thezero crossing of commutation voltage.
In rectification the constant delay angle is normally determined froma negative-feedback control loop, involving the set current and theactual monitored current.
8/9/2019 Control of Hvdc
24/38
To maintain safe inverter operation with minimum reactivepower requirements the individual firings require:
a continuous calculation of the available voltage integral for
commutation
a continuous calculation of the required voltage integral for safecommutation.
Optimum firing is achieved when the results of these two
coincide.
The relationship governing the commutation process relies on
the fact that the time integral of the commutating voltage,
i.e. the voltage integral, is equal to the overall voltage
change produced by the commutating current, ic.
8/9/2019 Control of Hvdc
25/38
This can be achieved as follows:
under commutation
In the integration such a relationship can be expressed as
From above equation the integral of voltage lies betweent1=
and t2 = - and hence phase control of system can be
achieved
8/9/2019 Control of Hvdc
26/38
The pulses in individual phase control can be generated by two
methodsConstantcontrol
Inverse cosine control
Constant control Method :
This method also called delay control method
The firing pulses are obtained individually by determining thezero crossing of the commutation voltage.
The commutation voltages are produced or generated by usingvoltage transformers
In this scheme the gate pulses are generated at same delaytime
8/9/2019 Control of Hvdc
27/38
The value ofis minimum at the instant when zero crossing of
commutation voltage.
The delay angle can be controlled by controlling the voltage.
The delay angle at rectifier is generally determined with
negative-feedback control loop, involving the set current and
the actual monitored current.
In inverter the delay angel is controlled with minimum reactive
power requirements for safe operation.
The schematic diagram of Constantcontrol is as follows:
8/9/2019 Control of Hvdc
28/38
8/9/2019 Control of Hvdc
29/38
Inverse Cosine control :
In this method the commutation voltages obtained are phase
shifted by 900
The zero crossings of sum of two voltages gives the firing
pulses for a particular valve that is considered
The delay angle depends on ac system voltage amplitude and
shape and is also proportional to inverse cosine of voltage.
The voltage across the bridge varies linearly with controlvoltage Vc
The essential requirement in this scheme is the maintenance
of phase shift by 900. The schematic diagram is as follows:
8/9/2019 Control of Hvdc
30/38
8/9/2019 Control of Hvdc
31/38
EQUIDISTANT PULSE CONTROL
In this system the pulses are generated at regular intervals of time byusing phase-lock oscillator.
The main components in this system are voltage controlled oscillatorand a ring counter.
The pulses of a particular frequency proportional to control voltageare passed to the ring counter from a voltage controlled oscillator.
The train of pulses is fed to a six-stage ring counter in which only onestage is on at a time, the ON stage is stepped cyclically frompositions 1 to 6 by the oscillator pulses.
As each ring-counter stage turns on, it produces a short pulse at theoutput (once per cycle).
Therefore the complete set of six output pulses normally occurs atsuccessive intervals of 60
8/9/2019 Control of Hvdc
32/38
The STOP pulses are also obtained from the ring counter but
two stages later (e.g. the START pulse for valve 1 is from stage1 and the STOP pulse for valve 1 is from stage 3, normally
120 later).
One oscillator and one ring counter per bridge constitute the
basic control hardware.
The various control modes only differ in the type of control loop
which provides the oscillator control voltage, Vc.
There are three methods in equidistant pulse control
pulse frequency control
pulse phase control
pulse period control
8/9/2019 Control of Hvdc
33/38
8/9/2019 Control of Hvdc
34/38
Pulse Frequency Control :
In this method, the frequency is determined by the control voltage Vcwhich is related to error in the quantity (current, extinction angle ordc voltage) being regulated.
The frequency in steady state operation is equal to pfo m
where ppulse number fo is nominal frequency
PFC system has integral characteristic and hence it is used infeedback mode for stabilization.
At firing instant tn of the pulse is determined from the following
equation:
Where V1bias voltage V3proportional to system period
8/9/2019 Control of Hvdc
35/38
In steady state
and
since
in steady state the gain K1can be chosen as
8/9/2019 Control of Hvdc
36/38
It does not has frequency correction, Ainsworth proposedfrequency correction according to the following block diagram
8/9/2019 Control of Hvdc
37/38
Pulse Period Control :
This is similar to PFC, in which VCis summed with V3instead ofV1. The firing instant tnof the pulse is determined from thefollowing equation:
The frequency correction scheme is obtained by eitherupdating V1in response to the system frequency variation orincluding another integrator in CC or CEA controller
8/9/2019 Control of Hvdc
38/38
Pulse Phase Control :
Firing pulses generated according to the following equation
For Proportional current control, the steady state can bereached when the error or Vcis constant.
To reduce the error to zero it is recommended that a slowalpha
control with feed back signal taken from the measured delayangle.
This signal in addition to the signal derived from the frequencyerror is used to control the voltage V1