Upload
amit-kumar-singh
View
37
Download
1
Tags:
Embed Size (px)
DESCRIPTION
Cooler data in thermal pant
Citation preview
COOLER DATA
COOLER DATA
H2 COOLEREXCITER COOLERSEAL OIL COOLER (AIR SIDE)SEAL OIL COOLER (H2 SIDE)PRIMARY WATER COOLERDESIGN DATA FOR THE H2 COOLER
TYPE:
2 X KG12-356/29/6/2-NSV-SR20 (4 SECTION, 25% EACH)U NITSMATERIAL & PRESSURE
HYDROGEN PRESSURE4barFINSCu
GAS FLOW33m3/sTUBESCuZn28Sn
HEAT DISSIPIATING CAPACITY4.859GcalTUBESHEETCuZn40
COLD GAS TEMP43OCWATER CHANNELSSTEEL WITH PROTECTIVE COATING
HOT GAS TEMP75OC
GAS PRESSURE DROP6.6mbarPRESSURE
COOLING WATER FLOW150dm3/sPERM. OPERATING 10 bar
MAX. WATER INLET TEMP38OCTEST PRESSURE 15 bar
WATER OUTLET TEMP47OC
WATER PRESSURE DROP200mbar
DESIGN DATA FOR THE EXCITER COOLER
TYPE:
2 X KG11-280/19/10/2-NSV-SR50 (2 SECTION, 50% EACH)
AIR FLOW15.5m3/sTUBESCuZn28Sn
HEAT DISSIPIATING CAPACITY0.43GcalTUBESHEETCuZn40
COLD AIR TEMP43OCWATER CHANNELSSTEEL WITH PROTECTIVE COATING
HOT AIR TEMP71.7OCFINSCu
AIR PRESSURE DROP4.9mbarPRESSURE
COOLING WATER FLOW23.88dm3/sPERM. OPERATING 10 bar
MAX. WATER INLET TEMP38OCTEST PRESSURE 15 bar
WATER OUTLET TEMP43OC
WATER PRESSURE DROP50mbar
DESIGN DATA FOR ONE SEAL OIL COOLER (AIR SIDE)
TYPE:
3C2720-4050-060AD (1 SECTION)
OIL FLOW3.33dm3/sTUBESSoMs71
HEAT DISSIPIATING CAPACITY0.12GcalTUBESHEETMUNTZ METAL
OIL INLET TEMP70OCWATER CHANNELSSTEEL WITH PROTECTIVE COATING
OIL OUTLET TEMP45OC
OIL PRESSURE DROP (app.)0.833barCOOLING WATERS SIDE PRESSURE
COOLING WATER FLOW8.1dm3/sPERM. OPERATING 16 bar
MAX. WATER INLET TEMP38OCTEST PRESSURE 24 bar
WATER OUTLET TEMP42OCOIL SIDE PRESSURES
WATER PRESSURE DROP (appr.)0.440barPERM. OPERATING 16 bar
TEST PRESSURE 24 bar
DESIGN DATA FOR ONE SEAL OIL COOLER (H2 SIDE)
TYPE:
3C2222-4050-050AD (1 SECTION)
OIL FLOW2.17dm3/sTUBESSoMs71
HEAT DISSIPIATING CAPACITY0.069GcalTUBESHEETMUNTZ METAL
OIL INLET TEMP70OCWATER CHANNELSSTEEL WITH PROTECTIVE COATING
OIL OUTLET TEMP45OC
OIL PRESSURE DROP (app.)0.850barCOOLING WATERS SIDE PRESSURE
COOLING WATER FLOW5.43dm3/sPERM. OPERATING 16 bar
MAX. WATER INLET TEMP38OCTEST PRESSURE 24 bar
WATER OUTLET TEMP42OCOIL SIDE PRESSURES
WATER PRESSURE DROP (appr.)0.300barPERM. OPERATING 16 bar
TEST PRESSURE 24 bar
DESIGN DATA FOR PRIMARY WATER COOLER
TYPE:
Ns 35/280/23/14/1.2/1 (2 SECTION)
PRIMARY WATER FLOW18.06dm3/sTUBESSF-Cu
HEAT DISSIPIATING CAPACITY2.15GcalTUBESHEETCuNi10Fe
PRIMARY WATER INLET TEMP81.5OCWATER CHANNELSH II WITH PROTECTIVE COATING
PRIMARY WATER OUTLET TEMP48OCSHELL1.4541
PRIMARY WATER PRESSURE DROP (app.)510mbarPRIMARY WATER SIDE PRESSURE
COOLING WATER FLOW96.4dm3/sPERM. OPERATING 10 bar
MAX. WATER INLET TEMP38OCTEST PRESSURE 15 bar
WATER OUTLET TEMP4.2OCCOOLING WATER SIDE PRESSURES
WATER PRESSURE DROP (appr.)160mbarPERM. OPERATING 16 bar
TEST PRESSURE 24 bar
EXCITATION SYSTEM
A-WHEEL (NEGATIVE POLARITY)
NO./TYPE OF DIODES60 NO. /SSi1 12 120 S3 (SIEMENS)
NO./TYPE OF FUSES30 NO. /3 NC 9 538
RESISTANCE/VOLTAGE/CURRENT PER FUSEAPPROX. 150 micro ohm, 800 V, 800 A
NO. OF RC NETWORK6 NO.
B-WHEEL (POSITIVE POLARITY)
NO./TYPE OF DIODES60 NO. /SSi1 13 120 S3 (SIEMENS)
NO./TYPE OF FUSES30 NO. /3 NC 9 538
RESISTANCE/VOLTAGE/CURRENT PER FUSEAPPROX. 150 micro ohm, 800 V, 800 A
NO. OF RC NETWORK6 NO.
STROBOSCOPE
TYPELX5-30/36-2 (BIOCHINGER)
VOLTAGE240 V
FREQUENCY50/60 Hz
NO. OF STOBOSCOPE1
EXCITER AIR DRYER
TYPEM 120 (BERNER INTERNATIONAL GmbH)
VOLTAGE240 V
FREQUENCY50/60 Hz
ADSORPTION AIR FLOW RATE120 m3/h
REGENERATION AIR FLOW RATE35 m3/h
TYPE OF ENCLOSUREIP55
NO. OF DRYER1
ACTUATOR FOR EMERGENCY COOLING DAMPER IN BASE FRAME
TYPEVD6-AG100 (LEWA)
MOTOR1LA3063-2AA92ZK17 (SIEMENS)
RATING0.25 KW
VOLTAGE415 V
FREQUENCY50 Hz
CURRENT0.71 Amp
SPEED50 S-1
TYPE OF ENCLOSUREIP55
NO. OF ACTUATOR2 NOs.
ACTUATOR FOR EMERGENCY COOLING DAMPER IN ENCLOSURE
TYPEVS8-GK350 (LEWA)
MOTOR1LA3063-2AA92ZK17 (SIEMENS)
RATING0.25 KW
VOLTAGE415 V
FREQUENCY50 Hz
CURRENT0.71 Amp
SPEED50 S-1
TYPE OF ENCLOSUREIP55
NO. OF ACTUATOR1 NOs.
GAS SYSTEM
CO2 FLASH EVAPORATOR
RATING18 KW (6 X 3 KW)
VOLTAGE240 V
HEAT TRANSFER LIQUIDMARLOTHERM
VOLUME OF HEAT TRANSFER LIQUID25 dm2
HOLE IN ORIFICE2.8 mm
RELIEF VALVE ON HIGH-PRESSURE SIDE80 bar
RELIEF VALVE ON LOW-PRESSURE SIDE8 bar
NO.1 (FULL CAPACITY)
GAS DRYER
TYPE8.70 (BOLL+ KIRCH)
MOTOR1 LA 3073-2AA93 (SIEMENS)
RATING1.1 KW
VOLTAGE /FRQ415 V, 50 Hz
CURRENT2.5 Amp AT 380 V
SPEED48.5 S-1
TYPE OF ENCLOSUREIP54
VOLUME PF ABSORBENT MATERIAL20 dm3
HEATER RATING2.5 KW
REGENERATION AIR FLOW RATE65 m3/Hr
NO.1 (FULL CAPACITY)
COMPRESSED AIR FILTER
TYPEAH (HUNDT AND WEBER)
VOLUME OF ACTIVATED CARBON13 dm3
SERVICE HOURSAPPROX. 1,500 TO 2,000 Hrs
THROUGHPUT80 m3/hr AT 8 bar
NO.1 FULL CAPACITY
GENERAL
MAKEBHEL
TYPETHDF 115/59
CODEIEC 34-1, VDE 0530
COOLING
STATOR WINDINGDIRECTLY WATER COOLED
STATOR CORE, ROTORDIRECTLY HYDROGEN COOLED
RATING
APPARENT POWER588 MVA
ACTIVE POWER500 MW
POWER FACTOR0.85 (LAG)
TERMINAL VOLTAGE21 KV
PERMISSIBLE VARIATION IN VOLTAGE+/- 5%
SPEED /FREQ RPM/ Hz3000/50
STATOR CURRENT16200 Amps
HYDROGEN PRESSURE Kg/cm24
SHORT CIRCUIT RATIO0.48
FIELD CURRENT (CALCULATED VALUE)4040 Amps
CLASS & TYPE OF INSULATIONMICALASTIC (SIMILAR TO CLASS F)
NO. OF TERMINAL BROUGHT OUT6
RESISTANCE IN OHMS AT 20 OC (UNIT # 6)
STATOR WINDING BETWEEN TERMINALS
U-X0.0014132
V-Y0.0014145
W-Z0.0014132
ROTOR WINDINGF1-F2 0.0672
MAIN EXCITER
ACTIVE POWER3780 KW
CURRENT6300 A
VOLTAGE600V
PILOT EXCITER
APPARENT POWER65 KVA
CURRENT195 A
VOLTAGE220 V (1+/- 10%)
FREQUENCY400 Hz
GENERATOR PROTECTIONGenerators are high quality for securing the best possible continuity of power supply. In addition to a suitable technical design &responsible mode of operation, provision has therefore been made for automatic protection facility. The following protection have been provided in the 500 mw TG.
1. GENERATOR DIFFERENTIAL PROTECTION (87G)
2. GENERATOR LOW FORWARD POWER PROTECTION (37G)
3. NEGATIVE PHASE SEQUENCE PROTECTION (46G)
4. POLE SLIPPING PROTECTION (98G)
5. UNDER FREQUENCY PROTECTION (81G)
6. LBB PROTECTION (50Z)
7. GEN. FIELD FAILURE PROTECTION (40G)
8. STATOR EARTH FAULT PROTECTION (64G1 & 64G2)
9. INTER TURN FAULT PROTECTION (95G)
10. OVER LOAD PROTECTION (51G)
11. OVER VOLTAGE PROTECTION (59G)
12. GEN. BACK UP IMPEDANCE PROTECTION (21G)
FIRE IN AIR PRE HEATER
AIR PRE HEATER FIRE FIGHTING PROCEDURE
_ Air heater fire alarm will appear. As IRDS is not effective this
alarm has been derived from excessive rise in air heater exit
flue gas temperature
_ Air heater rotor stopped.
_ Rapid and abnormal increase in air heater flue gas exit
temperature.
ACTIONS
a. Instruct boiler operator to start air heater soot blowing of the affected APH.
b. Try to assess extent of fire by visual inspection ( through inspection
window)
c. Continue air heater soot blowing and inform shift charge Engineer.
d. If temperature come normal stop soot blowing and observe for
further rise in temperature.
e. In case of reappearance of fire alarm again start air heater soot
blowing.
f. In case air heater fire alarm does not disappear or temperature of air
heater does not come down seek permission for boiler outage.
g. Trip the boiler.
h. After furnace is purged trip the F.D. Fan also. Keeping all air
heaters running (even the air heater which has caught fire).
i. Isolate the effected air heater from gas side (by closing its gas
outlet damper from control room).
j. Observe air heater temperature or sign of hot spot (from inspection
window).
k. In case temperature does not come down or any hot spot visual fire)
is observed DELUGE the air heater with copious amount of water.
l. Continue water spray till rotor is cooled.
m. Keep air heater running and remove inspection doors when it is safe
to examine.
n. Assess extent of damage and decide further course of action.
[ NOTE]:
(a) DO NOT HESITATE TO PUT WATER IN CASE CLEAR SYMPTOMS OF AIR
HEATER FIRE IS OBSERVED.
(b) If the fire has progressed to involve the metal the temperature inside the air
heater will be from 1100 C to 2200 C. Hence use of large quantity of water is
always recommended.
(c) While water quenching is on please ensure that :-
i) Air heater is running
ii) Water is getting drained is not accumulation of water in duct.
iii) Keep the air motor healthy by taking help of maintenance persons.
(d) While opening the fire water valve heavy cracking may be observed.
Steam with escape from leaky print and air heater chamber may get
pressurized.
(e) Do not use foam, chemical or steam for fire tightening because they will
not be effective.NTPC/SINGRAULI
DC SUPPLY SYSTEM FAILURE
220 V D.C POWER FAILURE IN STAGE -I (5X200MW)
INDICATIONS & CONSEQUENCES:
1. Annunciation of LOSS of 220 V DC supply will appear.
1. 220 V DC Voltmeters reading at generator panel & DCDB will show ZERO V.
2. MFR, TLR & UTR will not actuate, however,
a. All coal feeders will TRIP.
b. All Hot air gates will CLOSE.
c. All HONV will CLOSE.
d. HOTV & HORV will not OPERATE from UCB.
e. Generator and Turbine will continue to RUN
f. PSW pumps will TRIP.
g. Speeder Gear motor will become INOPERATIVE from UCB.
h. Field breaker status indication will DISAPPEAR. However breaker will continue to
be in CLOSED CONDITION.
3. 6.6 KV auxiliaries will continue to run, however,
a. Their Interlocks & protection will not work.
b. Their indicating lamps will NOT GLOW but ammeters will show the current.
c. Scoop position of all BFPs will come down to MINIMUM. & recirculation valve will
open.
NTPC/SINGRAULI
2
INSTRUCTIONS FOR SAFE SHUT DOWN OF UNIT
1. On DC failure PSW pump will trip. Immediately rush to Start PSW pump motor by
switching on overhead switch provided inside the PSW/SSW panel at 0 meter.
2. Gradually reduce load locally by manual operation of speeder gear hand wheel up to 5 to
10 MW.
3. As a parallel action, inform SCE /ASCE on station paging.
4. Inform unit # 1 UCE to start DG set
5. In case of abnormalities Such as :
Main steam temperature less than 465 Dec C
Stator slot temp. more than 90 Dec C
Drum level high-high.
Following action to be taken:
_ Hand trip the Turbine from local.
_ Trip Generator breaker.
_ Mechanically trip field breaker
_ Open the vacuum breaker.
_ Mechanically trip UATs A and B incomer breakers.
_ Mechanically Charge EMCC by closing DG set incomer after
mechanically tripping the incomer breaker from USS.
_ Start AC lube oil pump from ATRS panel
_ Start AC seal oil pump by operating over ride switch in local panel,
_ Start PSW pump motor by switching on overhead switch provided inside
the PSW/SSW panel at 0 meter.
_ Voltage and frequency of DG set should be watched closely
_ Ensure lube oil and seal oil system is normal. Put the Turbine on barring
gear.
_ In case of seal oil failure, purge out H2 gas and fill CO2 & Inform all the
concerned.
_ Trip all HT motor breakers manually
NTPC/SINGRAULI
3
6.2.0 220V DC POWER FAILURE IN STAGE II(2X500MW)
INDICATIONS & CONSEQUENCES:
- Annunciation of LOSS of 220 V DC supply will appear.
- 220 V DC Voltmeters reading at generator panel & DCDB will show ZERO V.
- All coal feeders will TRIP.
- 6.6 KV auxiliaries indicating lamps will NOT GLOW. However ammeters will show the
running status.
- 0.4 KV auxiliaries indicating lamps will NOT GLOW. However ammeters will show the
running status.
- Boiler will trip on loss of 220V DC power. HOTV will not get closed, however, HONV
will get close through MFR.
- Turbine will trip (as +/-24V DC supply is available).
- Interlock & protection of C&I system will remain out.
- Generator will not trip and as turbine has tripped Motoring will take place.
- Air side SOP will continue to run. H2 side SOP will trip. No alarm /annunciation will be
available at CXW 01 panel only ammeter will indicate whether motor is running or not.
- 50% protections of generator on DC 1 from same unit will be out and remaining 50%
protection on DC 2 from other unit will be in service.
INSTRUCTIONS FOR SAFE SHUT DOWN OF UNIT
1. Run the DG set from control room. Ensure correct selection of DC source at local
control panel of DG set.
2. Charge the EMCC after Mechanically opening incomer breaker from USS-A. In case
of non-availability of DG set, charge the Emergency MCC from the other Unit
after Mechanically tripping the incomers from USS-A and DG set
3. Hand Trip Generator Breaker from control room. Then trip field control breaker
manually in equipment control room CJN 1 panel.
4. Run AOP from ATRS panel and SOP from CXW panel after charging EMCC. Ensure
SOP running, failing which H2 purging should be initiated.
5. Trip the 6.6KV breaker of UAT-A and UAT-B manually from local. Unit bus will be
dead as tie will not come in service due to DC failure.
6. Run the standby air compressors from healthy units.
7. Put the Machine on barring gear.
8. Keep a close watch on Turbine, Boiler and Generator parameters.
NTPC/SINGRAULI
4
Loss of DC to UPS (5x200 MW Stage-I & 2x500 MW stage-II)
Two numbers inverters and three numbers UPS chargers, with batteries banks, are provided
for individual units. In case of Loss of UPS DC supply, UPS supply will change over to
standby alternate AC source and unregulated AC supply will remain available for C&I system
since AC supply is available.
Indication/Consequences
Following annunciations will appear on loss of DC to inverters.
- UPS charger A/B/C trouble &/or
- UPS Inverter A/Static switch A trouble &/or
- UPS inverter B/Static switch B trouble.
ACTION:-
- Inform HOD (C&I), HOD (Opn.) and Shift Charge Engineer.
- Check for any abnormalities in UPS charger room as well as battery room.
- After removal of fault take inverter back into service with the help of C&I Engineer.
Loss of 24 volt D.C. (5x200 MW Stage-I)
SOP, ACLOP, DCLOP, Speeder gear, valves etc on ATRS panel will not operate either on
auto or manual from ATRS panel. However DC LOP can be started from the direct on/off
switch on UCB. In the same way AC LOP can also be started from direct on/off switch in unit
number 1 & 3 (for other units the switch is being provided in shutdown).
NTPC/SINGRAULI
5
Loss of 24 volt D.C. (2x500 MW Stage-II)
Two Numbers (+)24V and two Numbers (-)24V battery chargers along with (+)24V battery
bank of 1500 AH & (-) 24V battery bank of 600 AH are provided to each 500MW Units.
Indication/Status
- Loss of + 24 volt D.C. Power supply fail alarm will appear on AN D 010 fascia window
- ATRS panel indication will not glow
- Turbine trip will not get actuated.
- Loss of excitation & GCB trip
- All controllers output of ATRS will become ZERO.
- Turbine control through ATRS will remain out.
ACTION:-
- Inform SCE.
- Take necessary action for early & safe shut down of unit.
- Run DC seal oil p/p from local.
- Run DC Lube oil p/p from local.
- Station one responsible person in the MOT room who will start JOP at TG speed < 500 rpm
on instruction of control engineer.
- Hand trip the turbine from local.
- Trip the generator breaker and boiler in case they do not trip on protection.
- Identify the fault and restore the system.
NOTE:-1. Do not take chance to run the unit on loss of 24V DC.
2. Try to take shut down of unit before 24V DC voltage falls to Zero.
NTPC/SINGRAULI
6
Switchyard DC Supply (For Protection & Control system) failure
There are two sets of Batteries for 400/132 KV Switch yard.
Main - 1 Batteries: 300AH/220 volts (110 cells) batteries
Main - 2 Batteries: 300AH/220 volts (110 cells) batteries
Both Main-I/Main-II remain in the service for Indication, Control, Protection and Emergency light in
control room, charger room, Compressor room and cable galleries.
Indication/status when 220 volts DC Supply Main 1 fails.
- DC Supply Failed annunciation will appear
- Trip coil 1 faulty flag on all 400 kV CB & trip coil faulty flag on all 132 kV panels will come
- 220V DC Voltmeter of DC1 mounted on top of 400 kV control panel and at float charger
panel will show Zero
- Indicating lamps of 400/132KV breakers and isolators will not glow in control room and in
yard local control panel.
- All breakers/Isolator ON or OFF status will remain same. However Ammeters will show
current
- Hand tripping operation of any feeder will not be possible.
- Protection tripping from DC1 will fail but from DC2 will remain in service for 400 kV feeders
- All protection tripping for 132 kV feeders will fail.
Indication/status when 220 volts DC Supply Main 2 fails.
- TC-2 Faulty annunciation will appear on 400 kV breakers
- 220V DC Voltmeter of DC 2 mounted on top of 400 kV control panel and at float charger
panel will show Zero
- Hand tripping as well as protection trip of feeders through DC 1 will be in service for all 400
kV panel as well as 132 kV panel
- Protection tripping from DC 2 will be out of service for 400 kV feeders.
Instructions when DC Supply Main 1 fails
- Change annunciation /supply to DC-2 at Bus section panel.
- If restoration of Main - 1 DC is not possible within 2 to 3 hours, decision to shut down by
initiating protection trip to be taken for 400KV feeders.
- No protection/tripping will be possible for 132KV feeders. However 132 kV will be dead after
tripping all 400 kV feeders.
NTPC/SINGRAULI
7
Instructions when DC Supply Main 2 fails
- Efforts for restoration of DC II supply to be taken up. If same is not possible within 5 to 6
hours decision to shut down through hand trip is to be taken for 400KV feeders.
- 132KV Feeders will be healthy and available for 132KV panels only DC-1 has been provided.
(For 132 kV panel DC-2 is also from same DC DB. This will be connected in due course).
Instructions when both DC Supply Main-1 & Main-2 fail simultaneously
- Efforts to be made to restore at least one of DC-1 or DC-II after which selective tripping can
be taken p as may be decided.
- Using a 220V DC + emergency source tripping of all units one by one can be initiated.
- In extreme cases, emergency trip provided on ABCBs, MOCBs and unit 4/5 Generator CBs
can be actuated to isolate units 1 to 5 Unit 6 & 7 having SF6 CB will not be possible to be
isolated.
- The lines can be got tripped from other end as required.
Switchyard 50 Volts PLCC DC supply failure
PLCC battery, 500 AH 50 volts (24cells) battery. In case of 50 volts PLCC D.C. Supply failure:
Indication/Status.
- Annunciation of Carriers protection fail will appear 50V DC Voltmeter reading : Zero volt
(on PLCC DCDB)
- PLCC will fail & there will be no speech communication from other stations.
- Protection system will fail though PLCC however on unit basis protection system will remain
in service there will be no tripping through PLCC i.e. No feeder tripping will take place in case
of tripping from other end.
Instructions
- Immediate action to be taken for normalization of D.C. supply to PLCC.
- Operator should rush to PLCC D.C.D.B. battery room / battery charger room to check if any
fire has taken place/fuses blown.
- At least portable battery charger/temporary supply should be taken in service with the help of
Electrical Maint.
NTPC/SINGRAULI
8
C.W. System D.C. Power Supply System
CW has two sets of 50 volt battery each having 24 cells and 1000 Ah capacity.
- 50 Volts DC supply have been used for all 6.6 kV & 0.4 kV breaker ON/OFF indication, their
control panel indication and their protection and control system.
- For relay panel/control panel.
- For emergency light in CW pump house and CW switchgear.
- For emergency closure of 2 x 500MW CW pump discharge valve.
Indications in case of DC supply failure.
- 50 Volts DC volt meter will show zero reading at DCDB
- None of the indicating lamps on 6.6KV CW buses, control panel of both CW pumps houses
as well as Relay panel in switchgear will glow.
- All pumps running status will remain same and pump running status can be known by their
ammeter reading. However for emergency trip operation breaker can be tripped through
mechanical trip at breaker.
- In stage-I, CW discharge valve status will remain same as it was prior to DC failure. The
valve operations should be done manually.
- In stage-II, CW discharge valve will close on DC supply failure, thus loss of DC supply is
detrimental to Stage-II CW pumps as pumps
INSTRUCTIONS:
On 6.6 kV buses DC selection is provided in Bus VT panel. On failure of DC, go to switch
board & put above selection from DC1 to DC 2 or vice versa
Condition 1: Only DC 1 fails
a) Put selector switch of DC at bus VT panels of 6.6KV to DC 2.
b) Put selector switch at Bus coupler of LTMCC stage-I to DC 2.
c) Transformer protection is out. Trip transformer from 132KV yard manually if
required. (For 6.6KV Bus A & Bus B only DC 1 is provided. Provision of DC2
through selector switch yet to be made available.)
d) Put off DC 1 and switch on DC 2 at dist board located at Auxiliary Pump house.
Try restoration of DC 1.
NTPC/SINGRAULI
9
Condition 2: Only DC 2 fails
a) Put selector switch of DC at bus VT panels of 6.6KV to DC 1.
b) Put selector switch at Bus coupler of LTMCC stage-I to DC 1.
c) Transformer protection is out. Trip transformer from 132KV yard manually if
required. (For 6.6KV Bus A & Bus B only DC 1 is provided. Provision of DC2
through selector switch yet to be made available.)
d) Put off DC 2 and switch on DC 1 at dist board located at Auxiliary Pump house.
Try restoration of DC 2
Condition 3: Both DC sources fail
a) Immediately trip 500MW CW pumps by tripping transformer C and D from 132 KV
switchyard Control room.
b) Stage-I will remain in operation without protection and control DC try restoration of at
least one DC. If not possible trip entire stage-I from 132KV C.R
(Loss of DC Supply is detrimental to 2X500MW CW Pumps because pumps will keep on
running on shut off head)
NTPC/ SINGRAULI UPS FAILURE (STAGE-1) ________
SAFE LANDING OF UNITS DUE IN CASE OF UPS FAILURE ( STAGE-I )
Date: 09/12/2004 Page No. 01 Revision No. 0
UNIT
HAPPENING DUE TO UPS FAILURE ACTION TO BE TAKEN
U #1 to 5 Alternate supply will come automatically
from USS-B through change over switch
in case of Inverter failure. But if auto
change over fails followings will happen:
Inform C&I Maintenances
to Restore back the
Inverter
BOILER SIDE:-
All scanners power supply fail and
MFR will act within 2sec.on Flame
Failure and Turbine & Generator will
trip.
HONV will remains at its last position
( * If any oil gun is in service then
HONV & HOTV will remains at its
last position )
( * If no oil gun in service then HOTV
will close )
ID Fan IGV will full open
FD Fan Blade pitch will full close
F W Hi range & Lo range control
valve will close
Hydra-step supply will be off ( No
Indication in UCB)
SADC will full open
R-37, S-102 and all Spray Control
valves Will close
Ensure Turbine & Gen
Trip
---------------
Close HOTV & HONV
Manual V/V
Ensure HOTV closing,
otherwise close HOTV
Manual V/V
Stop both ID & FD Fans
---------------
----------------
----------------
Ensure R-37, S-102
closed and close all
spray Manual Isolating
valves
U # 1to 5 Common :-
UCB indications, recorders will be off
DAS will fail including annunciation
-----------------
-----------------
NTPC/ SINGRAULI UPS FAILURE (STAGE-1) ________
SAFE LANDING OF UNITS DUE IN CASE OF UPS FAILURE ( STAGE-I )
Date: 09/12/2004 Page No. 02 Revision No. 0
UNIT HAPPENING DUE TO UPS FAILURE
ACTION TO BE TAKEN
U #1 to 5 Alternate supply will come automatically
from USS-B through change over switch
in case of Inverter failure. But if auto
change over fails followings will happen
:
Inform C&I Maintenances
to Restore back the
Inverter
TURBINE SIDE :-
ATRS supply will remain for at
least next six hours for U # 1,3 & 4
only because 24 Volts battery
back up provided ( U # 2 & 5 NO
battery back up ) But if battery
supply fails followings will
happen :-
Turbine motorized actuators in
ATRS will be in operative & will
remain in its last position
AC / DC LOP will not start from
ATRS
Starting Oil P/p will not start
PSW Conductivity hi-hi to UTR trip
will be out of service
Exp. Tank level lo lo- to PSW p/p trip
will be out of service
For U # 2 & 5 only PSW flow lo- lo to
UTR trip will be out of service
-------------------
-------------------
Start AC / DC LOP from
Panel and keep watch
L.O.Pr from local
Start AC / DC SOP and
keep watch S.O.Pr / Seal
oil DP / Thrust Oil Pr / H2
Pr from local
-----------------
-----------------
-----------------
NTPC/ SINGRAULI UPS FAILURE (STAGE-1) ________
SAFE LANDING OF UNITS DUE IN CASE OF UPS FAILURE ( STAGE-I )
Date: 09/12/2004 Page No. 02 Revision No. 0
UNIT
HAPPENING DUE TO UPS FAILURE ACTION TO BE TAKEN
U# 1to 5 TURBINE SIDE :-
BFP C will trip
Lead/ lag Auto starting for BFP &
CEP will not act.
MC-36 will full open and become
Inoperative
BFP-A & B Scoop will be
minimum and Recirculation will
full open.
( But DT Protection will be out
of
service and no indication will
be
available for Recirculation
valve )
CA-21,22 & MC-39,57 will remain
in its last position and become
Inoperative
HPBP Steam pr control valve
may open due to HPBP Oil P/p
failure by entrapped steam pr.
--------------
-----------------
Stop All CEPs and
Close
LPH-4 O/L Valve
Trip all BFPs
Open CA-21,22 from
MCC room
Close MS-1 & 5
PRIMARY WATER SYSTEM
PRIMARY WATER PUMPS 1 & 2SS11 D001/SS11 D002
KIND OF PUMPCENTRIFUGAL PUMP
TYPECPK Cm 65-250 (KSB)
SPEED47 S-1
CAPACITY19 dm3/s
DISCHARGE HEAD80 m
PUMP MOTOR TYPE1LA4207-2AA90 (SIEMENS)
RATING37 KW
VOLTAGE /FREQ415 ,3 PHSAE AC / 50 Hz
SPEED47 S-1
TYPE OF ENCLOSUREIP54
NO.2 (FULL CAPACITY)
MAIN FILTERSS11 N531
KIND OF FILTERSTRAINER TYPE FILTER WITH MAGNETIC BARS
TYPE1.53.1 (Boll + Kirch)
VOLUMETRIC FLOW RATE25 dm3/s (max)
DEGREE OF FILTRATION150 microns
PRESSURE DROP ACROSS FILTER0.1 bar WITH CLEAN FILTER & 1.2 bar WITH 100% FOULING
NO.1 NO. FULL CAPACITY
FINE FILTER
KIND OF FILTER1 PLUG, 1 CARTRIDGE
TYPE1.55.1 (Boll + Kirch)
VOLUMETRIC FLOW RATE0.42 dm3/s (max)
PRESSURE DROP ACROSS FILTER0.15 bar WITH CLEAN FILTER & 1.2 bar WITH 100% FOULING
NO.1 NO. FULL CAPACITY
ION EXCHANGERSS11 N520
VOLUME83 LITERS (BISCHOFF)
RESINLEWATIT
RESIN VOLUME56 LITERS (45 KG)
NO.1 FULL CAPACITY
SEAL OIL SYSEM
SEALOIL PUMP 1and 2, AIR SIDE
KIND OF PUMPSREW PUMP
TYPESNH 210-R46 (ALLWEILER)
CAPACITY3.3 dm3/s
DISCHARGE PRESSURE15 bar
PUMP MOTOR- TYPEILA3 133-4AA90 (SIEMENS)
RATING7.5 KW
VOLTAGE/FREQUENCY415V, 50 Hz
CURENT14.1 A
SPEED24.17 S-1
TYPE OF ENCLOSUREIP54
NO.2 NO. FULL CAPACITY
SEAL OIL PUMP 3 AIR SIDE (DC SOP)
KIND OF PUMPREW PUMP
TYPESNH 210-R46 (ALLWEILER)
CAPACITY3.3 dm3/s
DISCHARGE PRESSURE15 bar
PUMP MOTOR- TYPEIHA4165-5JL20 (SIEMENS)
RATING8.5 KW
VOLTAGE220 DC
CURENT51 A
SPEED24.17 S-1
TYPE OF ENCLOSUREIP54
NO.1 NO. FULL CAPACITY
SEAL OIL PUMP H2 SIDE
KIND OF PUMPSREW PUMP
TYPESNH 210-R46 (ALLWEILER)
CAPACITY2.17 dm3/s
DISCHARGE PRESSURE15 bar
PUMP MOTOR- TYPEILA3 133-6AA90 (SIEMENS)
RATING4 KW
VOLTAGE415V, 50 Hz
CURENT7.2 A
SPEED15.8 S-1
TYPE OF ENCLOSUREIP54
NO.1 NO. FULL CAPACITY
SEAL OIL FILTER UNIT, AIR SIDE & H2 SIDE
KIND OF FILTERSTRAINER TYPE FILTER
TYPE2.62.9 Ma (Boll + Kirch)
VOLUMETRIC FLOW RATE3.3 dm3/s
DEGREE OF FILTRATION100 microns
PRESSURE DROP ACROSS FILTER0.3 bar WITH CLEAN FILTER & 1.2 bar WITH 100% FOULING
NO. OF AIR SIDE2 NO. FULL CAPACITY
NO. OF H2 SIDE2 NO. FULL CAPACITY
SPECIFICATION OF TRANSFORMERS
GENERATOR TRANSFORMER
MANUFACTURERBHEL
NO. OF UNITS3
RATING HV & LV (MVA)200 MVA
NO LOAD VOLTAGE, HV400 / 3 KV
NO LOAD VOLTAGE, LV21 / 3 KV
RATED CURRENT, HV866.0 Amp
RATED CURRENT, L9523.8 Amp
NO. OF PHASES1
FREQUENCY50 Hz
TYPE OF COOLINGFORCED OIL & FORCED WATER
CONNECTION SYMBOL WHEN FORMED A BANKYN 11
IMPEDANCE AT PRINCIPLE TAP15% MAX
ON LOAD TAP CHANGERTAPPING IN 12 EQUAL ATEPS OF 1.25% EACH PROVIDED ONHV WINDING TO GIVE (+) 10% TO (-) 5%
TEMPRATURE RISESVARIATION OF HIGH VOLTAGES
i) OIL BY THERMOMETER50 OC
ii) WINDING BY RESISTANCE60 OC
OTI & WTI, AUXILIARY CONTACTS SETTINGS
i) OTI ALARM85 OC
TRIP90 OC
ii) WTI ALARM105 OC
TRIP115 OC
STATION TRANSFORMER
MANUFACTURERNGEF
NO. OF UNITS2
CAPACITY20/35/50 MVA
VOLTAGE RATIO132/6.9/6.9 KV
VECTOR GROUPY/Yno/Yno
COOLINGFORCED OIL & FORCED AIR
UNIT AUXILIARY TRANSFORMER
MANUFACTURERNGEF
NO. OF UNITS4
CAPACITY25 MVA
VOLTAGE RATIO21/6.9 KV
VECTOR GROUPDYN
COOLINGNATURAL OIL & FORCED AIR
PERCENTAGE IMPEDANCE7.8%
CW TRNSFORMER
MANUFACTURERNGEF
NO. OF UNITS1
CAPACITY25 MVA
VOLTAGE RATIO132/6.9 KV
VECTOR GROUPY/Yn
COOLINGONAF
PERCENTAGE IMPEDANCE0.135 +/- 10%
ESP TRNSFORMER
NO. OF UNITS4
CAPACITY2000 KVA
VOLTAGE RATIO6.6 KV / 0.433 KV
VECTOR GROUPDYn1
ASH SLURRY TRNSFORMER
NO. OF UNITS3
CAPACITY1600 KVA
VOLTAGE RATIO6.6 KV / 433 V
PERCENTAGE IMPEDANCE0.08 +/- 10%
STATION SERVICE TRNSFORMER
NO. OF UNITS4
CAPACITY1600 KVA
VOLTAGE RATIO6.6 KV / 0.433 KV
VECTOR GROUPDYO1
PERCENTAGE IMPEDANCE0.08 +/- 10%
WTP SERVICE TRNSFORMER
NO. OF UNITS2
CAPACITY1000 KVA
VOLTAGE RATIO6.6 KV / 0.433 KV
VECTOR GROUPDYO1
PERCENTAGE IMPEDANCE0.05 +/- 10%
CHP TRNSFORMER
NO. OF UNITS4
CAPACITY1600 KVA
VOLTAGE RATIO6.6 KV / 433 V
UNIT SERVICE TRNSFORMER
NO. OF UNITS4
CAPACITY1600 KVA
VOLTAGE RATIO6.6 KV / 0.433 KV
VECTOR GROUPDY1
PERCENTAGE IMPEDANCE0.08 +/- 10%
CW PUMP HOUSE SERVICE TRNSFORMER
NO. OF UNITS2
CAPACITY630 KVA
VOLTAGE RATIO6.6 KV / 0.433 KV
VECTOR GROUPDYn1
PERCENTAGE IMPEDANCE0.05 +/- 10%
VOLTAGE REGULATING SYSTEM
TYPETHYRISIAM 04-2
MAX OUTPUT VOLTAGE250 V
OUTPUT CURRENT FOR FIELD FORCING152 A
OUTPUT CURRENT FOR RATED GENERATOR LOAD88 A
AUXILIARY VOLTAGES FROM PILOT EXCITER FOR THYRISTOR SETSTHREE PHASE SUPPLY, 220 V, 400 Hz
DC VOLTAGE FROM STATION BATTERY FOR CONTACTORS & DRIVES220 V
POWER INPUT CONTINUOUSLY< 0.1 KW
POWER INPUT, SHORT TIME< 1 KW
DC VOLTAGE FROM STATION BATTERY FOR 2 X 24 V FOR CONTROL & REGULATIONMAX. 15 A POSITIVE
MAX. 6 A NEGATIVE
RATED SECONDARY VOLTAGE120 V
POWER INPUT OF VOLTAGE TRANFORMER PER PHASE2 VA
RATED SECONDARY CURRENT5 A
POWER INPUT OF CURRENT TRANFORMER PER PHASE6.5 VA (PLUS LOSSES IN CONNECTING LEADS)
ACCURACY OF CONTROLBETTER THAN +/- 0.5%
SETING RANGE OF VOLTAGE SET POINT POTENTIO METER+5% - 15% OF NOMINAL GENERATOE VOLTAGE
SETTING RANGE OF DROOP COMPENSATION OR COMPOUNDIND+/- 0-10% DEPENDANT ON THE SETTING OF POTENTIO METER & PROPOTIONAL TO REACTIVE CURRENT (direction of reactive current compensation depend on the phase relation which is determined by connection of CTs to TVR terminals.
TORQUE, CRITICAL SPEEDS
MAX SHORT CIRCUIT TORQUE OF STATOR AT LINE TO LINE SINGLE PHASE SHORT CIRCUIT1488 kpm
MOMENT OF INERTIA OF GENERATOR SHAFT10,000 Kgm2
CRITICAL SPEED (CALCULATED)
nk114.4 S-1 (V-GEN)
nk230.1 S-1 (V-EXC)
nk339.8 S-1 (S-GEN)
GENERATOR VOLUME & FILLING QUANTITIES
GENERATOR VOLUME (GAS VOLUME)80 M3
CO2 FILLING QUANTITY160 M3
H2 FILLING QUANTITY520 M3
WASTE GAS SYSTEM
BEARING VAPOUR EXHAUSTER
TYPE4036 Mx 80112 (ANTON PILLER KG)
MOTOREm 80-2
RATING0.75 KW
VOLTAGE /FREQ415 / 50 Hz
CURRENT1.65 Amp
SPEED49 S-1
TYPE OF ENCLOSUREIP54
TYPE OF EXHAUSTERSRADIAL FLOW
VOLUMETRIC FLOW RATE380 m3/h AT 10 m BAR
NO.2 (FULL CAPACITY)