Cooling Load for House Design

Embed Size (px)

Citation preview

  • 8/2/2019 Cooling Load for House Design

    1/18

    TABLE OF CONTENTS

    INTRODUCTION................................................................................................................ 1

    Calculations of Cooling Load for Given House Design ........................................ 2

    PROPOSALS...................................................................................................................... 11

    Calculations of Cooling Load for Proposed House Design .............................. 12

    CONCLUSION .................................................................................................................. 17

  • 8/2/2019 Cooling Load for House Design

    2/18

    1

    INTRODUCTION

    In this assignment, we were given a detailed worked example which calculates the

    building cooling load for an air-conditioning system. Using this work example as a reference,

    we were to calculate the building cooling load for given design of a house.

    After the cooling load has been calculated, we then come up with a proposal for a new

    design of the house that could reduce the cooling load for the air-conditioning system.

    Calculations of the cooling load for the original house design are presented in this report.

    Proposals to reduce the cooling load are presented later in this report.

  • 8/2/2019 Cooling Load for House Design

    3/18

    2

    CALCULATIONS OF COOLING LOAD FOR GIVEN HOUSE DESIGN

    1.

    2.

    3.

    4.

    5.

  • 8/2/2019 Cooling Load for House Design

    4/18

    3

    6.

    7.

    8.

    9.

    10.

    11.

  • 8/2/2019 Cooling Load for House Design

    5/18

    4

    12.

    13.

    14.

    15. GLF

    16.

  • 8/2/2019 Cooling Load for House Design

    6/18

    5

    17.

    18.

    19.

    20.

    21.

    22.

  • 8/2/2019 Cooling Load for House Design

    7/18

    6

    23.

    24.

    25.

    26.

    27.

    28.

  • 8/2/2019 Cooling Load for House Design

    8/18

    7

    29.

  • 8/2/2019 Cooling Load for House Design

    9/18

    8

    Given cooling load

    1. External

    (a) Heat gain through opaque surfaces (walls, roofs and doors)

    for each exterior wall

    for each door

    (b) Heat gain through translucent surfaces (windows and skylights)

    for each window and skylight

  • 8/2/2019 Cooling Load for House Design

    10/18

    9

    (c) Heat gain due to infiltration of outside air through leaks

    2. Internal

    (a) Heat gain due to occupants

    for each occupant

    for each occupant

    (b) Heat gain due to artificial lighting

    for each lamp

  • 8/2/2019 Cooling Load for House Design

    11/18

    10

    (c) Heat gain due to electrical appliances

    for each appliances

    Cooling Load of Given Design

  • 8/2/2019 Cooling Load for House Design

    12/18

    11

    PROPOSALS

    In order to reduce the cooling load of the air-conditioning system of the house, a new

    design of the house is proposed. There are few methods that could be used to reduce the

    cooling load and one of them is to reduce the overall perimeter of the house which will

    decrease the floor area of the house and therefore greatly decreasing the cooling load.

    However this method is not used because we do not want to sacrifice the floor area of the

    house as this would affect the market value of the house. Besides, the savings from the

    reduced cooling load could hardly cover the inconvenience caused.

    The other method that could be used is to reduce the cooling load factors such as

    CLTD and CLF, however this method is not used because the procedure to reduce the cooling

    load factors is complicated and references are needed to support the changes (insufficient

    acquired knowledge).

    The method which we used to reduce the cooling load is to decrease the internal and

    external heat gained by the house, and the only way we could do that is to come up with a

    proposal for a new design of the house. The new design of the house will have the following

    changes:

    1. The Width of the Door is decreased from 1m to 0.8m.

    2. The size of the North & South Windows is decreased from (2m 2m) to (1.5m 1.5m).

    3. The amount of Windows in the East & West is decreased from 4 to 3.

    4. The % of electrical appliances operating is reduced from 30% to 25%.

    By reducing the sizes of doors and window at North and South, heat gained by the

    house can be reduced because the entrance of sun rays into the house can be limited.

    Although the size reduction of the doors will increase the heat gained by opaque walls (qw)

    due to increased area of exterior wall (Aw), the heat gained is insignificant compared to the

    cooling load that is reduced because the heat gain through translucent surfaces (qG) is greatly

    reduced. The reduction ofqG is caused by reduction ofAG in all four directions of the house

    and AGS at east and west. All the calculations of the design of new cooling load will be

    presented in this report.

  • 8/2/2019 Cooling Load for House Design

    13/18

    12

    We also proposed that the % of electrical appliance operating could be reduced from

    30% to 25% so that HA can be reduced to decrease heat gain due to electrical appliances (qA).

    To achieve this, the occupants of the house should turn off unnecessary power usage

    whenever possible so that the cooling load can be minimized.

    CALCULATIONS OF COOLING LOAD FOR PROPOSED HOUSE DESIGN

    1.

    2.

    3.

  • 8/2/2019 Cooling Load for House Design

    14/18

    13

    4.

    5.

    Proposed cooling load

    1. External

    (a) Heat gain through opaque surfaces (walls, roofs and doors)

    for each exterior wall

  • 8/2/2019 Cooling Load for House Design

    15/18

    14

    for each door

    (b) Heat gain through translucent surfaces (windows and skylights)

    for each window and skylight

    (c) Heat gain due to infiltration of outside air through leaks

  • 8/2/2019 Cooling Load for House Design

    16/18

    15

    2. Internal

    (a) Heat gain due to occupants

    for each occupant

    for each occupant

    (b) Heat gain due to artificial lighting

    for each lamp

    (c) Heat gain due to electrical appliances

    for each appliances

  • 8/2/2019 Cooling Load for House Design

    17/18

    16

    Cooling load of proposed design

    Daily difference in qDES

    Yearly Difference in qDES

    Percentage of Cooling Load Reduced

  • 8/2/2019 Cooling Load for House Design

    18/18

    17

    CONCLUSION

    In conclusion, reduction in heat gain through doors and translucent object such as window

    will greatly reduce the cooling load of the air conditioning system of the house. With the

    proposal of a new design of the house, it is calculated that approximately 923.77w of cooling

    load can be reduced daily and this is equivalent to reduction of377.18 kW in cooling load

    per year. The proposal of the new design of the house could reduce the cooling load of the

    air-conditioning system by 10.96%. Although the percentage of reduced cooling load is not

    much, but our objective is achieved, which is to propose a new design of house having lower

    cooling load.