26b INTUMASTIC HP CORE HOLE APPLICATIONS WITHIN: HEBEL PANEL 90 Minute T&G Single Mesh 75mm Thick Walls FIRE ALARM CABLE BUNDLES AIRCON BUNDLES PEX WATER PIPES HDPE PIPES CPVC SPRINKLER PIPES NBN CAT 5 CABLES IN CONDUIT NBN CAT 6 CABLES IN CONDUIT SIMPLY SQUIRT THE INTUMASTIC HP INTO THE ANNULAR GAP BETWEEN THE OUTSIDE OF THE SERVICE PENETRATION AND THE INSIDE OF THE HOLE. FILL TO THE FULL DEPTH OF THE SUBSTRATE. PHONE: (07) 5411 4209 OR (02) 8004 3333 (Option 2) WEBSITE: tbafirefly.com.au EMAIL: [email protected] TBA FIREFLY

CORE HOLE APPLICATIONS WITHIN: T&G Single Mesh FIREFLY

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: CORE HOLE APPLICATIONS WITHIN: T&G Single Mesh FIREFLY

26bINTUMASTIC HP

CORE HOLE APPLICATIONS WITHIN:

HEBEL PANEL 90 Minute T&G Single Mesh 75mm Thick Walls

FIRE ALARM CABLE BUNDLES AIRCON BUNDLES PEX WATER PIPES

HDPE PIPES CPVC SPRINKLER PIPES NBN CAT 5 CABLES IN CONDUIT

NBN CAT 6 CABLES IN CONDUIT

SIMPLY SQUIRT THE INTUMASTIC HP INTO THE ANNULAR GAP BETWEEN THE OUTSIDE OF THE SERVICE PENETRATION AND THE INSIDE OF THE HOLE. FILL TO THE FULL DEPTH OF THE SUBSTRATE.

PHONE: (07) 5411 4209OR (02) 8004 3333 (Option 2)

WEBSITE: tbafirefly.com.auEMAIL: [email protected]

TBA FIREFLY

Page 2: CORE HOLE APPLICATIONS WITHIN: T&G Single Mesh FIREFLY

FRL -/90/90

FRL -/90/90

FRL -/90/90

FRL -/90/90

Warringtonfire Report No:

FAS190236 RIRSpecific ID No:

V74

BUNDLE OF UP TO 6 FIRE ALARM CABLES

58mm Core Hole. The annular gap around the service is to be filled to the full depth of the substrate using TBA Firefly Intumastic HP

Warringtonfire Report No:

FAS190236 RIRSpecific ID No:

V63a

Warringtonfire Report No:

FAS190236 RIRSpecific ID No:

V63b

Warringtonfire Report No:

FAS190236 RIRSpecific ID No:

V64

AIRCON CLPE FOAM PAIR-COIL + 2 TPS CABLES & WITH OR WITHOUT 18mm FLEXI DRAIN HOSE

70mm Core Hole. The annular gap around the service is to be filled to the full depth of the substrate using TBA Firefly Intumastic HP

AIRCON ARMAFLEX PAIR-COIL + 2 TPS CABLES & WITH OR WITHOUT 18mm FLEXI DRAIN HOSE

70mm Core Hole. The annular gap around the service is to be filled to the full depth of the substrate using TBA Firefly Intumastic HP

Up to 40mm OD PEX PIPE

60mm Core Hole. The annular gap around the service is to be filled to the full depth of the substrate using TBA Firefly Intumastic HP

TBA FIREFLY

Page 3: CORE HOLE APPLICATIONS WITHIN: T&G Single Mesh FIREFLY

FRL -/90/90

FRL -/90/90

FRL -/90/90

FRL -/90/90

Warringtonfire Report No:

FAS190236 RIRSpecific ID No:

V65

Up to 40mm HDPE PIPE

60mm Core Hole. The annular gap around the service is to be filled to the full depth of the substrate using TBA Firefly Intumastic HP

Warringtonfire Report No:

FAS190236 RIRSpecific ID No:

V66

Warringtonfire Report No:

FAS190236 RIRSpecific ID No:

V67

Warringtonfire Report No:

FAS190236 RIRSpecific ID No:

V68

Up to 48mm OD CPVC SPRINKLER PIPE

70mm Core Hole. The annular gap around the service is to be filled to the full depth of the substrate using TBA Firefly Intumastic HP

Up to 26mm PVC CONDUIT FILLED WITH up to 14 x Cat 5 NBN CABLES

46mm Core Hole. The annular gap around the service is to be filled to the full depth of the substrate using TBA Firefly Intumastic HP

Up to 26mm PVC CONDUIT FILLED WITH up to 10 x Cat 6 NBN CABLES

46mm Core Hole. The annular gap around the service is to be filled to the full depth of the substrate using TBA Firefly Intumastic HP

TBA FIREFLY

Page 4: CORE HOLE APPLICATIONS WITHIN: T&G Single Mesh FIREFLY

All service penetrations must be treated in strict accordance with the concise construction details contained within the referenced compliance Reports. These Reports meet Specification A2.3 of NCC2016 Amendment 1 (Including prior versions) & Schedule 5 of NCC2019 (Including amendment 1) for determination of an FRL.