University of Arkansas, FayettevilleScholarWorks@UARK
Theses and Dissertations
5-2016
Correcting Current Imbalances in Three-PhaseFour-Wire Distribution SystemsVinson Joseph JonesUniversity of Arkansas, Fayetteville
Follow this and additional works at: http://scholarworks.uark.edu/etd
Part of the VLSI and Circuits, Embedded and Hardware Systems Commons
This Thesis is brought to you for free and open access by ScholarWorks@UARK. It has been accepted for inclusion in Theses and Dissertations by anauthorized administrator of ScholarWorks@UARK. For more information, please contact [email protected], [email protected].
Recommended CitationJones, Vinson Joseph, "Correcting Current Imbalances in Three-Phase Four-Wire Distribution Systems" (2016). Theses andDissertations. 1576.http://scholarworks.uark.edu/etd/1576
Correcting Current Imbalances in Three-Phase Four-Wire Distribution Systems
A thesis submitted in partial fulfillment
of the requirements for the degree of
Master of Science in Electrical Engineering
by
Vinson Jones
University of Arkansas
Bachelor of Science in Electrical Engineering, 2014
May 2016
University of Arkansas
This thesis is approved for recommendation to the Graduate Council.
____________________________
Dr. Juan Carlos Balda
Thesis Director
____________________________
Dr. Alan Mantooth
Committee Member
____________________________
Dr. Roy McCann
Committee Member
ABSTRACT
The objective of this thesis is to present the theory, design, construction, and testing of a
proposed solution to unbalanced current loading on three-phase four-wire systems. The
Unbalanced Current Static Compensator is the name of the prototype; herein referred to as the
UCSC. The purpose of this prototype is to redistribute current between the three phases of a
distribution system. Through this redistribution, negative- and zero-sequence currents are
eliminated and a balanced system is seen upstream from the point of installation.
The UCSC consists of three separate single-phase H-bridge inverters that all share the
same dc-link capacitor. Each of these inverters performs independently using a single-phase
rotating reference frame controller. Each either draws or injects current onto the distribution
system lines to balance the active currents and performs power factor correction for voltage
compensation. A 34.5 kV, 6 MVA system was built and simulated in Matlab/Simulink™ to test
the validity of this solution. A scaled-down UCSC prototype was then designed and constructed
to compensate for a 208 V, 10 kVA system. Results from both the simulations and testing of this
UCSC prototype are presented and analyzed.
ACKNOWLEDGEMENTS
Thank you to Dr. Balda for the opportunity to further my knowledge in Electrical
Engineering and the support and advice on this project.
TABLE OF CONTENTS
CHAPTER 1
INTRODUCTION .......................................................................................................................... 1
1.1 Motivations for this Research Work ....................................................................... 1
1.2 Existing Solutions ................................................................................................... 1
1.2.1 Zig-Zag Transformers ............................................................................................. 2
1.2.2 Neutral-Wire Series Compensators......................................................................... 3
1.2.3 Neutral Wire Series Compensator/Zig-Zag Transformer Hybrid ........................... 4
1.2.4 Three-Level Inverter with Neutral Point Clamp (NPC) ......................................... 5
1.2.5 α-β Instantaneous Power Controller ....................................................................... 7
1.3 Proposed UCSC Solution ........................................................................................ 9
1.4 Objectives of Thesis .............................................................................................. 10
1.5 Organization of Thesis .......................................................................................... 11
1.6 References ............................................................................................................. 12
CHAPTER 2
THEORY OF UCSC OPERATION ............................................................................................. 14
2.1 Control of the UCSC ............................................................................................. 14
Reference Current Generator Stage ...................................................................... 15 2.1.1
Voltage Controller Stage....................................................................................... 16 2.1.2
Current Controller ................................................................................................. 17 2.1.3
2.2 ABC to D-Q Transformation ................................................................................ 18
2.3 Second-Order Generalized Integrator (SOGI) ...................................................... 20
2.4 Design of LCL Filters ........................................................................................... 22
2.5 Pulse-Width Modulation Algorithm ..................................................................... 25
2.6 Discretization of the UCSC control system functions .......................................... 26
2.7 Concluding Remarks ............................................................................................. 27
2.8 References ............................................................................................................. 28
CHAPTER 3
SIMULATION PROCESS AND RESULTS ............................................................................... 29
3.1 Introduction ........................................................................................................... 29
3.2 Realized Changes to Previously Suggested Simulation Model ............................ 29
3.2.1 PWM Control Signal Normalization .................................................................... 30
3.2.2 Current Reference Generator ................................................................................ 30
3.3 Modifying the Time-Domain Simulations to Reflect the Prototype
Implementation ......................................................................................................................... 32
3.3.1 Sensing Circuitry .................................................................................................. 33
3.3.2 Inverter Devices and Filter Components .............................................................. 35
3.3.3 Pre-Filtering of d-q Signals ................................................................................... 36
3.3.4 Coupling Transformers ........................................................................................ 37
3.3.5 Discrete Phase-Lock Loop Algorithm .................................................................. 38
3.3.6 Discrete d-q Transformation ................................................................................. 39
3.4 Simulation Results of the New Model .................................................................. 40
3.5 Conclusions ........................................................................................................... 42
3.6 References ............................................................................................................. 43
CHAPTER 4
....................................................... 44 DESIGN OF THE SCALED-DOWN UCSC PROTOTYPE
4.1 Introduction ........................................................................................................... 44
4.2 Design of the Prototype Power Stage ................................................................... 44
4.2.1 Scaling-Down the Case Study .............................................................................. 44
4.2.2 Calculations for the dc Link Capacitor Sizing ...................................................... 45
4.2.3 Design of the Gate Driving Circuit ....................................................................... 46
4.2.4 The Effect of Parasitics on System Performance .................................................. 47
4.2.5 Design of the Printed Circuit Board for the Power Stage ..................................... 49
4.3 Design of the Filter Inductors ............................................................................... 51
4.4 Calculations for the IGBT Heat Sink .................................................................... 63
4.5 Sensors and Measurement Conditioning .............................................................. 65
4.6 Concluding Remarks ............................................................................................. 66
4.7 References ............................................................................................................. 67
CHAPTER 5
IMPLEMENTATION OF THE CONTROL ALGORITHM IN A MICROCONTROLLER ..... 68
5.1 Introduction ........................................................................................................... 68
5.2 Developing a Single-DSP System ........................................................................ 68
5.3 Controller Implementation in the DSP ................................................................. 69
5.4 Start-Up and Shutdown Procedure ........................................................................ 70
5.5 Initializing the DSP Modules ................................................................................ 72
5.5.1 Analog-to-Digital Converter ................................................................................. 72
5.5.2 Pulse-Width Modulator ......................................................................................... 73
5.5.3 CPU Timer ............................................................................................................ 74
5.6 Calculating the Dead Time for the Inverter-Leg Semiconductor Devices ........... 74
5.7 Modifications for EMI Reduction ......................................................................... 76
5.8 Concluding Remarks ............................................................................................. 77
5.9 References ............................................................................................................. 77
CHAPTER 6
TESTING OF THE UCSC PROTOTYPE ................................................................................... 78
6.1 Experimental Setup ............................................................................................... 78
6.2 Testing of the UCSC Prototype ............................................................................ 79
6.2.1 Effect of Increasing the dc-bus Voltage ................................................................ 81
6.2.2 Effect of a Decrease in the Dead Time ................................................................. 81
6.2.3 Effect of Increased Inverter Loading .................................................................... 83
6.3 Causes of Output Voltage Distortion in a Single-Phase Inverter ......................... 83
6.4 Effect of Harmonic Voltage Components ............................................................. 88
6.5 Effect of Improper Measurements ........................................................................ 89
6.6 Conclusions ........................................................................................................... 89
6.7 References ............................................................................................................. 90
CHAPTER 7
CONCLUSIONS AND FUTURE WORK ................................................................................... 92
7.1 Conclusions ........................................................................................................... 92
7.2 Recommendations for Future Work...................................................................... 93
7.2.1 Implement a method for compensating the distortion due to dead time ............... 93
7.2.2 Include of a mechanism for compensating for grid voltage distortion ................. 94
7.2.3 Develop applications for the UCSC in mesh networks ........................................ 94
7.2.4 Apply the UCSC control to different three-phase inverter topologies ................. 94
7.2.5 Augment the UCSC controller to compensate for harmonic currents .................. 94
7.2.6 Add the ability to partially compensate for reactive power .................................. 95
7.3 References ............................................................................................................. 96
APPENDIX A
SNUBBERS FOR SEMICONDUCTOR DEVICES .................................................................... 97
A.1 RCD Snubber ........................................................................................................ 97
A.2 Overvoltage Snubber ............................................................................................ 98
A.3 Turn-On Snubber .................................................................................................. 98
A.4 Undeland Snubber ................................................................................................. 99
A.5 References ........................................................................................................... 100
APPENDIX B
DIGITAL SIGNAL PROCESSOR CODE ................................................................................. 101
B.1 The Main.c File ................................................................................................... 101
LIST OF FIGURES
Figure 1-1. Zig-zag transformer compensation system .................................................................. 2
Figure 1-2. Neutral-wire series compensator system ...................................................................... 3
Figure 1-3. Zig-zag and series compensator hybrid system ........................................................... 4
Figure 1-4. NPC three-phase three-level voltage source inverter ................................................... 5
Figure 1-5. Three-level four-leg voltage source inverter ................................................................ 6
Figure 1-6. Indirect current control block diagram ......................................................................... 8
Figure 1-7. Proposed shoot-through current immune topology ...................................................... 9
Figure 1-8. Connection of the UCSC to the distribution system .................................................. 11
Figure 2-1. The UCSC power topology ........................................................................................ 14
Figure 2-2. UCSC simplified block schematic ............................................................................. 15
Figure 2-3. Simplified current controller block diagram .............................................................. 18
Figure 2-4. Equivalent current controller block diagram .............................................................. 18
Figure 2-5. Frequency response of the SOGI ............................................................................... 21
Figure 2-6. Block diagram for the SOGI-QSG ............................................................................. 22
Figure 2-7. Schematic for an LCL filter ....................................................................................... 23
Figure 2-8. SPWM waveforms (top) and the resulting pulses (bottom) ....................................... 26
Figure 3-1. Matlab/SIMULINK™ UCSC system ........................................................................ 29
Figure 3-2. Substation currents from the previous model in different UCSC operating modes ... 30
Figure 3-3. PWM control signal normalization ............................................................................ 31
Figure 3-4. Previously suggested controller ................................................................................. 32
Figure 3-5. Outputs of the current reference and voltage PI controllers in the previous system.. 33
Figure 3-6. Current reference PI controller output for new system .............................................. 33
Figure 3-7. Reference generator for the current controller ........................................................... 34
Figure 3-8. Effect of the notch filter before (left) and after (right) ............................................... 34
Figure 3-9. Measurement filtering and conditioning used in the simulations .............................. 35
Figure 3-10. Inverter implemented in SIMULINK™ ................................................................... 36
Figure 3-11. Dialog box for the IGBTs and diodes used in the SIMULINK™ simulations ........ 37
Figure 3-12. Discrete phase-lock loop block diagram .................................................................. 38
Figure 3-13. D-Q Transformation ................................................................................................. 39
Figure 3-14. Substation currents from new continuous model in different UCSC operating modes
....................................................................................................................................................... 41
Figure 3-15. Substation currents from the discrete-domain prototype simulation ....................... 42
Figure 4-1. Bottom layer photoplot for the power stage PCB used in the UCSC prototype ........ 50
Figure 4-2. Bottom-middle layer photoplot for the power stage PCB used in the UCSC prototype
....................................................................................................................................................... 50
Figure 4-3. Top-middle layer photoplot for the power stage PCB used in the UCSC prototype . 51
Figure 4-4. Top layer photoplot for the power stage PCB used in the UCSC prototype .............. 51
Figure 4-5. Dimensions of a C core pair ....................................................................................... 55
Figure 4-6. B-H Curve without airgap (solid line) and with airgap (dotted line) ......................... 56
Figure 4-7. Core loss curves for the Hitachi POWERLITE amorphous cores ............................. 60
Figure 4-8. Equivalent thermal circuit for IGBT and antiparallel diode ...................................... 64
Figure 4-9. Thermal circuits for the IGBT and antiparallel diode ................................................ 65
Figure 5-1. Flowchart for the DSP processes ............................................................................... 70
Figure 5-2. Turn-off current waveform for an IGBT .................................................................... 75
Figure 6-1. Experimental setup for testing of the UCSC prototype ............................................. 78
Figure 6-2. Unbalanced load currents (left) and substation current (right) during testing ........... 79
Figure 6-3. Phase Voltage and Current before (left) and during (right) UCSC full operation ..... 80
Figure 6-4. UCSC inverter currents (left) and FFT of the substation neutral current (right) during
full UCSC operation ..................................................................................................................... 80
Figure 6-5. FFT of the substation current ..................................................................................... 81
Figure 6-6. Inverter Currents (left) and FFT of substation neutral current (right) with 300 V dc
bus ................................................................................................................................................. 82
Figure 6-7. Inverter Current (left) and FFT of substation neutral current (right) with 0.833 μs
dead time ....................................................................................................................................... 82
Figure 6-8. Unbalanced load currents during increased load testing ............................................ 83
Figure 6-9. Inverter currents (left) and FFT of the substation neutral current (right) with
increased inverter loading ............................................................................................................. 84
Figure 6-10. FFT of substation current with increased inverter loading. ..................................... 84
Figure 6-11. Unipolar inverter output distortion due to dead time ............................................... 85
Figure 6-12. Voltage (left) and current (right) waveforms produced from the hybrid modulation
scheme........................................................................................................................................... 86
Figure 6-13. FFT of inverter output current with unipolar (left) and hybrid (right) modulation
scheme........................................................................................................................................... 87
Figure 6-14. Substation currents during UCSC operation without (left) and with (right) grid
voltage distortion .......................................................................................................................... 87
Figure 6-15. IGBT Turn on without (left) and with (right) appropriate voltage probes ............... 88
Figure 6-16. IGBT Turn-on Vce without (left) and with (right) appropriate voltage probes ....... 90
Figure 7-1. Shoot-through current immune topology ................................................................... 95
Figure A-1. RCD Snubber Circuit ................................................................................................ 97
Figure A-2. Overvoltage Snubber ................................................................................................. 99
Figure A-3. Undeland Snubber Circuit ....................................................................................... 100
LIST OF TABLES
Table 3-1. Parameters of the prototype IGBTs ............................................................................. 36
Table 4-1. Load power ratings for the case study and scaled-down prototype ............................. 45
Table 4-2. DC Link Capacitor Parameters .................................................................................... 46
Table 4-3. 2.2 mH and 0.5 mH Inductor Design Parameters ........................................................ 52
Table 4-4. Amorphous Core Data ................................................................................................. 54
Table 4-5. Variables for switching and conduction losses in controlled semiconductor devices . 64
Table 5-1. Gate Driver Circuit IC Datasheet Parameters ............................................................. 75
1
CHAPTER 1 1
INTRODUCTION
1.1 Motivations for this Research Work
In an ideal three-phase four-wire distribution system, each of the phases would be
connected to identical customers and the same amount of current would be drawn from each
phase. In practical systems, this is not the case as there is much variation in the type and
connection timing of customers. This situation leads to an unbalance in the currents that run
through each phase. As a result, the currents do no sum to zero at the neutral conductor, which
causes several issues in the power transmission system:
Extra current in the neutral wire of four-wire systems which can result in unsafe
conditions, and in some cases, an incorrectly sized conductor [1].
Electric machine overheating due to negative-sequence currents [2].
Magneto-motive force (MMF) generated by negative-sequence currents interferes
with the positive-sequence MMF. This along with the machine overheating causes
a drop in the efficiency of the system [3].
Zero-sequence fluxes produced in wye-connected ungrounded transformers can
cause overheating [4].
Several different attempts have been made to mitigate the effects of the negative-
sequence and zero-sequence currents. These are described in the next section.
1.2 Existing Solutions
The presented solutions can be classified into two different types of compensators:
passive and active compensators. The passive solutions do not react to changes in the system like
2
the active compensators and, as a result, are often not as effective. However, passive systems are
usually cheaper and do not require complex control techniques and sensing that active systems
do.
1.2.1 Zig-Zag Transformers
To eliminate the zero-sequence current components that would flow through the neutral
in three-phase four-wire systems one proposed method is the introduction of a zig-zag
transformer in parallel with the load [5]. Zig-zag transformers are wound in such a way that they
have very low impedance to zero-sequence currents and very large impedance to positive- and
negative- sequence currents. The system setup is shown in Fig. 1-1 where Zs is the impedance of
the phase conductor between the source and transformer, Zsn is the impedance of the neutral
conductor between the transformer and the source, and ZLn is the neutral conductor impedance
Figure 1-1. Zig-zag transformer compensation system [1]
3
between the load and the transformer. Ideally, this would remove the zero-sequence current
injected into the utility system and thus reduce the stress on the system; however, the impedance
Zsn plays a large part in the performance of this solution. If Zsn is large then the attenuation is
better, though this requires that the transformer is either further away from the utility, thus
compensating less load, or that an inductor be placed in series with the neutral, which adds a
significant cost to the system and can cause abnormal operation of load-side equipment.
Moreover, this solution loses its advantage in unbalanced utility voltage conditions due to the
fundamental-component zero-sequence currents which may cause the transformer to overheat.
These disadvantages suggest the need for another solution, particularly based on power
electronics.
1.2.2 Neutral-Wire Series Compensators
A voltage-source inverter in series with the neutral conductor is applied to reduce the
harmonic currents reaching the utility system [6]. Fig. 1-2 demonstrates a test case. By inducing
a series voltage in the neutral conductor the inverter creates a high impedance path for harmonic
currents in the form of a virtual inductor. The performance of the system improves as
Figure 1-2. Neutral-wire series compensator system [2]
4
the reactance of the inverter increases, but a balance must be achieved between the desired
attenuation of neutral current and the level of voltage distortion that is caused as a result.
1.2.3 Neutral Wire Series Compensator/Zig-Zag Transformer Hybrid
This method combines the two previous solutions. In this system there is a zig-zag
transformer connected in parallel with the load and in addition there is a voltage-source inverter
connected in series with the utility-side neutral conductor [7]. Fig. 1-3 demonstrates the
described system.
The series inverter helps to force the harmonic zero-sequence currents through the
transformer and back to the load by producing a voltage waveform in the neutral that mimics
high impedance. The hybrid systems require less knowledge of the system impedance for them
to be effective and allow for smaller and cheaper zig-zag transformers. This solution is effective,
and reduces current imbalances, but only through mitigating the harmonic currents contribution
to this problem. The fundamental zero-sequence currents still flow back to the utility.
Figure 1-3. Zig-zag and series compensator hybrid system [3]
5
1.2.4 Three-Level Inverter with Neutral Point Clamp (NPC)
This solution uses a NPC three-leg voltage source inverter as shown in Fig. 1-4 where Ls
is the inductance of the conductor from the source to the point of common coupling (PCC), Rc is
the resistance between the output of the inverter and the PCC, and Lc is the inductance between
the output of the inverter and the PCC [8]. This setup allows for better compensation of neutral
currents due to the added control of the output voltage relative to the neutral. To control this
inverter, a switch commutation strategy called space vector modulation is implemented where a
map of all possible switching combinations is constructed [8]. A different set of output voltage or
output vectors is obtained for each of these combinations. Through control in the α-β-0 or other
domain, the amount of time spent at each of these vectors is calculated as well as the order.
Using this technique an averaged output vector can be produced to allow for precise control over
the output voltage.
Figure 1-4. NPC three-phase three-level voltage source inverter [4]
6
This method can be generalized for any number of switching positions and can also be
used to control the four-leg converter in Fig. 1-5Figure 1-5. The fourth leg of this inverter gives
the user better control over neutral currents as there are now more neutral point switching vectors
to choose from; however, it is not only more expensive to add this fourth leg, but the SVM
becomes more complex.
The complexity of using SVM, compared to SPWM (sinusoidal pulse width modulation),
can be a problem due to the extra computation resources required to implement the modulation
technique. Larger computational load can lead to reduction in the frequency at which the
controller can be run when implementing these techniques on digital signal processors [9]. This
disadvantage could be mitigated by delegating the control signal modulation to an FPGA with
parallel computing ability, but integration of an FPGA into the design adds more complexity to
the final solution.
Figure 1-5. Three-level four-leg voltage source inverter [4]
7
1.2.5 α-β Instantaneous Power Controller
This solution keeps the controller in the stationary α-β reference frame. Given that the
filtering and computational delays are properly dealt with, this type of control allows for the
elimination of a phase-lock loop as well as a second transformation into the dq rotating reference
frame. The control in [6] works by calculating the instantaneous power required by the load and,
by normalizing the α and β voltage terms, and a current reference for the inverters is then set
which is proportional to the power needed on each phase. This controller achieves full
compensation of reactive currents required by the load and current balancing. Also, it can
compensate for low-order harmonics present within the distribution system with the use of a low-
pass filter on the instantaneous power calculations.
Two different versions of this controller are used. The direct current controller method
generates the control signal for an active filter directly by calculating the harmonic and reactive
current components that need to be delivered to the load by the filter. The indirect current
controller calculates the fundamental-component current that should be the only one supplied by
the source. The difference between this fundamental component reference and the actual source
current becomes the control signal for the active filter. As a result it provides all current
components but the fundamental one. Fig. 1-6Figure 1-6 contains the block diagram for the
indirect current controller. The iL components are the measured load currents, the vL components
are the voltages of each phase at the PCC, and the isb* components are the generated current
references for the inverters.
Fig. 1-7Figure 1-7 indicates the topology of the inverter used in the testing of the α-β
controller. This topology is convenient because it is not susceptible to the shoot-through current
that
8
normally is a problem in inverters with cascade devices, and thus reduces the need for the dead
time in the switching pulses. This topology has the same number of active switches as a standard
three-phase inverter, but has twice the number of diodes and twice the PCC connecting reactors.
A NPC configuration is also required for proper functionality, which adds to the cost.
The α-β stationary reference frame controllers are generally easier to implement than d-q
synchronous reference frame controllers. This is because they do not require as many reference
frame transformations or the phase-lock loops required for the transformations. They may also
have better transient behavior as experienced in [7] However, their performance can be severely
diminished by any magnitude or phase error in the measurements or calculations because these
control strategies directly use ac waveforms to construct the current references in the inverter
controller [12].
Figure 1-6. Indirect current control block diagram [5]
9
1.3 Proposed UCSC Solution
A case study is developed to test any possible solutions based on data from a 34.5 kV
distribution feeder. At peak power, the three phase loads were 877 kW + 500 kVAR, 707 kW +
300 kVAR, and 753 kW + 300 kVAR, so these load ratings were chosen for the case study [13].
The topology selected for the UCSC has three single-phase full-bridge inverters. This is
useful for several reasons:
Figure 1-7. Proposed shoot-through current immune topology [5]
10
Each of the inverters can control their respective phases current completely
independent of the other phases.
There is full utilization of the dc bus voltage which is not the case for neutral-
point-clamped inverters.
Control of an H-bridge is relatively simple and does not require more complex
modulation schema as required by four-leg inverter topologies.
The largest flaw with the use of this topology is that 12 switching position are required
and thus 12 IGBTs and 12 diodes are required.
A diagram showing the connection of the UCSC to the distribution system is displayed in
Fig. 1-8Figure 1-8. Each of the inverters shares a single dc-bus capacitor. All three are coupled
to the 34.5 kV distribution system using 480V/19.9kV single-phase distribution transformers that
boost the voltage to the required value as well as provide the necessary isolation required by
industry standards. Not shown in the figure is the line-to-neutral LCL filter at the output of each
of the inverters. The UCSC is to be installed just downstream from the distribution substation to
compensate for as many downstream loads as possible.
1.4 Objectives of Thesis
The main objectives of this thesis are to improve upon the UCSC solution developed in
[9] and then, to validate its performance using a constructed prototype. This will be done in three
main steps:
1) First, the theoretical background behind the operation of the UCSC will be
developed.
2) Second, simulation results will be analyzed for potential improvements.
11
3) Third, the scaled down prototype will be built, tested, and the experimental results
analyzed.
1.5 Organization of Thesis
The theory behind the operation of the UCSC will be presented in Chapter 2. The
simulations of the system will be addressed in Chapter 3. This will include the construction of
the simulation models and any changes from previous model in [13] and the results from those
simulations. The assembly and design of the scaled down prototype is documented in Chapter 4
and the controller implementation is presented in Chapter 5. The measurements and analysis of
the results that come from testing of the prototype are found in Chapter 6. Conclusions and
recommendations for future work are given in Chapter 7.
Figure 1-8. Connection of the UCSC to the distribution system [6]
12
1.6 References
[1] J. Kennedy, C. A. Nucci, A. Borghetti, G. Contaxis A. P. S. Meliopoulos, "Power
distribution practices in USA and Europe: impact on power quality," in Proceedings of the
8th International Conference on Harmonics and Quality of Power, Athens, 1998, pp. 24-29.
[2] R. G. Harley, E.B. Makram, and E.G. Duran, "The effects of unbalanced networks on
synchronous and asynchronous machine transient stability," Electric Power System
Research, vol. 13, no. 2, pp. 119-127, October 1987.
[3] R.H. Salim, R.A. Ramos, and N.G. Bretas, "Analysis of the small signal dynamic
performance of synchronous generators under unbalanced operating conditions," in IEEE
Power and Energy Society General Meeting, 2010, pp. 1-6.
[4] T.A. Short, Electrical Power Distribution Handbook. Boca Raton, FL: CRC Press Taylor &
Taylor Croup, 2004.
[5] Jou Hurng-Liahng, Wu Jinn-Chang, Wu Kuen-Der, Chiang Wen-Jung, and Chen Yi-Hsun,
"Analysis of zig-zag transformer applying tin the three-phase four-wire ditribution power
system," IEEE Transactions on Power Delivery, vol. 20, no. 2, pp. 1168-1173, April 2005.
[6] S Inoue, T. Shimizu, and K. Wada, "Control Methods and Compensation Characteristics of
a Series Active Filter for a Neutral Conductor," Industrial Electronics, IEEE Transactions
on, vol. 54, no. 1, pp. 433-440, February 2007.
[7] Sewan Choi and Minsoo Jang, "Analysis and Control of a Single-Phase-Inverter-Zigzag-
Transformer Hybrid Neutral-Current Suppressor in Three-Phase Four-Wire Systems,"
Industrial Electronics, IEEE Tansactions on, vol. 54, no. 4, pp. 2201-2208, August 2007.
[8] Ning-Yi Dai, Man-Chung Wong, and Ying-Duo Han, "Application of a three-level NPC
inverter as a three-phase four-wire power quality compensator by generalized 3DSVM,"
Power Electronics, IEEE Transactions on, vol. 21, no. 2, pp. 440-449, March 2006.
[9] D. Dujic, M. Jones, and Levi E., "Contrinuous Carrier-Based vs. Space Vector PWM for
Five-Phase VSI," in EUROCON, 2007. The International Conference on Computer as a
Tool, Warsaw, 2007, pp. 1772-1779.
[10] Singh G.N and P Rastgoufard, "A new topology of active filter to correct power-factor,
compensate harmonics, reactive power and unbalance of three-phase four-wire loads," in
Applied Power Electronics Conference and Exposition, Miami Beach, 2003, pp. 141-147.
[11] Matias Diaz and Roberto Cardenas, "Analysis of Synchronous and Stationary Reference
Frame Control Strategies to Fulfill LVRT Requirements in Wind Energy Conversion
Systems," in Ecological Vehicles and Renewable Energies (EVER), 2014 Ninth
13
International Conference on, Monte-Carlo, 2014, pp. 1 - 8.
[12] D. N. Zmood and D. G. Holmes, "Stationary frame current regulation of PWM inverters
with zero steady state error," in Power Electronics Specialists Conference, Charleston,
1999, pp. 1185-1190.
[13] Manuel A. S. Tejada, "Unbalanced Current Static Compensator," Dept. of Elect. Eng., Univ.
of Arkansas, Fayetteville, MS Thesis 2014.
14
CHAPTER 2 2
THEORY OF UCSC OPERATION
2.1 Control of the UCSC
The power topology of the UCSC is displayed in Fig. 2-1 and the control block schematic
for each inverter is shown in Fig. 2-2Figure 2-2. The UCSC’s three single-phase inverters inject
or draw current at the point of common coupling (PCC) to compensate for the load currents in
such a way that the substation currents are balanced. The various subsystems of the controller
will be explained next. The controller first transforms the inverter and load currents along with
phase voltages at the PCC into the d-q synchronously-rotating reference frame using a
Figure 2-1. The UCSC power topology
15
single-phase α-β to d-q transformation [1].
Reference Current Generator Stage 2.1.1
This section of the block schematic is responsible for generating the reference signal for
the current controller. Using the d-axis component of the load current from each phase an
average load current is calculated . The substation currents
are then
compared to the average load current through current summation at the PCC (
)
to develop the respective d-axis current references. The resulting error signal for each phase is
summed with and routed into a PI controller whose output is the d-axis reference current
for the current controller.
Because the three single-phase inverters circulate the currents between the phases, there
is no net current drawn from the grid into the capacitor except the current used to maintain the dc
bus voltage. The PI controller gains ( ) are specified by using the following method
from [2]:
Figure 2-2. UCSC simplified block schematic
16
𝐶 𝑑𝑣 𝑑𝑡
[ (𝑣 𝑣 ) + ∫(𝑣
𝑣 )] (1)
In (1) the capacitor equation relating its current and voltage is used to develop a
relationship between the error signal (𝑣 𝑣 ) and the capacitor voltage. Using the Laplace
transform and solving for
𝑇 (𝑠) in (1) results in:
𝑇 (𝑠) 𝑣
𝑣
𝐶
(𝑠 +
)
(𝑠 + 𝐶
𝑠 + 𝐶
)
(2)
this takes a similar form to the general form of a two-pole transfer function given by:
𝑇(𝑠)
(𝑠 + 𝑠 + ) (3)
Using the theory behind this general form, the response of the reference PI controller can
be determined through the following relationships:
( ) → (𝐶 ) (4)
( ) → (𝐶 )
(5)
A damping factor = √
is used and corresponds to a 5% overshoot given a step change in set
point.
Voltage Controller Stage 2.1.2
The voltage controller regulates the voltage for the dc-link capacitor, common to all three
phases of the UCSC, within a certain band; the specified voltage ripple is 1% of the rated voltage
The controller senses and filters the bus voltage 𝑣 and compares this instantaneous value to a
set reference value 𝑣
. The difference in these values is then processed through a gain to
17
regulate the effect of an error in the dc bus voltage versus an error in the currents. The error
signal , after being modified, is added to the reference current generators error signal.
Current Controller 2.1.3
The d-axis current reference is compared to the inverter d-axis current
. The error
between these two signals is then routed to a PI controller to establish the response
characteristics of the current controller [1]. The d-axis component of the grid voltage 𝑣 is
added to the signal as a feed-forward element to bias the voltage output of the inverter. Also, a
decoupling term is added to take into account the coupling between the q-axis currents and the
inductances of the filter and transformer. The same process is done for the q-axis current
controller; however, the current reference becomes the q-axis component of the load current (this
fully compensates for the reactive power). The feed-forward q-axis grid voltage is assumed to be
0. The decoupling term comes from the interaction between the d-axis current component and
the inductances present. To produce a control signal for the PWM generator the signals are
converted back to the α-β reference frame, where the α component is the output voltage
waveform.
The simplified block diagram for the current controller is shown in Fig. 2-3Figure 2-3.
The first block represents the transfer function for the PI controller and the second one the plant
model for the output filter. The PI controller gains for the current controller ( ) are
specified by using the following method [1]. The transfer function L(s) for the open-loop system
is given by:
(𝑠) ( 𝑠 + )
𝑠 + 𝑠 (
𝑠)
(𝑠 +
)
(𝑠 + )
(6)
18
By choosing the relationship between and appropriately (
), the pole
and zero cancel out. This is useful because this leads to a much simpler closed-loop transfer
function given by:
(𝑠)
(𝑠)
+ (𝑠)
(
) 𝑠 +
(7)
The closed-loop system is drawn in Fig. 2-4Figure 2-4. Using the chosen proportional
and integral gain ratio as given above the PI gains can be selected from:
(8)
2.2 ABC to D-Q Transformation
The control diagram described above requires dc values in order to be stable. This
requires the ac voltages and currents that are sensed by the UCSC to be transformed into dc
Figure 2-3. Simplified current controller block diagram
Figure 2-4. Equivalent current controller block diagram
19
value equivalents in order to be used [3]. This is accomplished through the use of the Park’s
transformation, otherwise known as the d-q-0 transformation, which takes an input vector of the
3 voltage (or current) functions and outputs a vector that consists of dc values in steady state
corresponding to the magnitude of the input ac functions.
The d-q-0 transformation is derived from another vector manipulation method known as
the Clarke’s transformation or the α-β-0 transformation that changes the reference axis that is
used to measure the phasor values in a three-phase system [4]. The new reference axes are called
the α, β, and 0 axis that are rotated such that the zero axis is equidistant from the original a, b,
and c axes. The new values for the three phasors are their reflections upon the new reference
axes. Thus, all the original phasors in a balanced three-phase system cancel out to zero on the
zero axis. This is useful for the control of balanced three-phase systems because it effectively
eliminates a variable. A system defined in the abc reference frame can be fully described by the
variables α and β. The α-β-0 transformation is given by [3]:
[ ] √
[
√
√
]
[ ] (9)
With the system in the αβ0 reference frame, the transformation to the dq0 reference frame
is given by:
[𝑑 ] √
[ ( 𝑡) ( 𝑡) ( 𝑡) ( 𝑡)
] [ ] (10)
This rotates the α and β reference axes around the 0 axis at the same frequency as the
sinusoids that define the phasors. The effect of this rotation is that the periodic signals become
DC values. The full d-q-0 transformation and its inverse are shown below:
20
[𝑑 ] √
[ (
) ( +
)
(
) ( +
)
√
√
√
]
[ ] (11)
[ ] √
[
√
(
) (
)√
( +
) ( +
)√
]
[𝑑 ] (12)
In the case of unbalanced three-phase systems, the three-phase transformations shown
above are not as effective because they do not help to eliminate the number of variables used to
define the system. This is because the 0 axis contains a non-zero value. One approach to deal
with this problem is the use of single-phase d-q transformations [3]. The α-β to d-q transform in
this case is a straightforward modification of the above equation and is given by:
[𝑑 ] [
( 𝑡) ( 𝑡) ( 𝑡) ( 𝑡)
] [ ] (13)
The initial transformation process is different from (9). In order to establish the α- and β-
axis values for a single-phase system the value used for the α axis is the present value of the
function that defines the ac waveform, such as 𝑠 ( 𝑡), and the β axis value is the value of that
same function but lagged for a quarter cycle; that is, 𝑠 ( 𝑡
). This gives the magnitude and
phase information for the ac waveform [3].
2.3 Second-Order Generalized Integrator (SOGI)
A SOGI is actually the transformation of an integrator in the dq reference frame into its
corresponding operation in the stationary αβ reference frame. This is done by transforming
21
+ (
𝑠) ( + ) (14)
into the stationary reference frame [5]. The results of the transformation are:
(𝑠 )+
(𝑠 + )
𝑠
(𝑠 + ) (15)
where and represent the output in the positive and negative sequence rotating
reference frames. The frequency response of this system is illustrated in Fig. 2-5Figure 2-5. This
shows that the SOGI has infinite gain at 60 Hz and -60 Hz. By using negative feedback the SOGI
can be used to track an input signal and as outputs, reproduces the input signal along with a
signal of identical amplitude but lagging 90 degrees.
In Matlab/Simulink™, the creation of an orthogonal signal for use in a single-phase d-q
transformation is as simple as using a delay block with a step of a quarter cycle. The same
operation in the DSP would take up a large amount of space. For a sampling rate of 10 kHz, a
quarter-cycle delay would require the saving of 2500 numbers, which takes up a lot of memory
especially with a word length of 32 bits, so it is not very efficient.
Figure 2-5. Frequency response of the SOGI
22
This is where a second-order generalized integrator quadrature signal generator (SOGI-
QSG) can be used. This configuration of the SOGI takes in a sinusoidal input signal and then
outputs two other sinusoidal signals. One of them is the fundamental frequency sinusoid
component of the input and the other output is fundamental frequency sinusoid component of the
input but delayed by a quarter cycle. The transfer functions for each of these outputs are:
(𝑠)
(𝑠)
𝑠
𝑠 + 𝑠 + (16)
(𝑠)
(𝑠)
𝑠 + 𝑠 + (17)
Where ω0 is the frequency to which the SOGI is tuned. Fig. 2-6Figure 2-6 contains the block
diagram of the SOGI-QSG [5].
2.4 Design of LCL Filters
An LCL filter has become more commonly used in grid interfacing systems due to its
superior current ripple attenuation when compared to the conventional L or LC filters. An L filter
is simple, but only has a -20 dB/dec frequency response for the entire frequency spectrum. The
LCL filter matches the performance of an L filter for lower frequencies, but can achieve a 60
dB/dec attenuation at higher frequencies, allowing for smaller magnetic components.
Figure 2-6. Block diagram for the SOGI-QSG
23
The basic structure of the LCL filter is shown in Fig. 2-7Figure 2-7. Because the design
of this filter is based on the attenuation of harmonics that arise from active grid-connected
devices the value of vg is considered to be zero as the grid voltage is considered to be a pure 60
Hz voltage source. The output of the inverter is a PWM voltage and the filter is used to eliminate
high-frequency current components. This leads to following transfer function [6]:
𝑇 (𝑠)
𝑣
𝐶 𝑠 + ( + )𝑠 (18)
The problem with this response characteristic is that a resonance occurs that might make
the LCL filter actually produce worse current ripple in the output of the inverter. A solution for
eliminating this resonance is the use of the resistor, Rf in series with the shunt capacitor to lessen
the effects of the resonance, but unfortunately results in higher system losses. As a tradeoff for
using a passive damping resistor, the 60 dB/dec attenuation after the resonant frequency reduces
to 40 dB/dec. The transfer function that takes into account the effect of the damping resistor is
given by:
𝑇 (𝑠)
𝑣
𝐶 𝑠 +
𝐶 𝑠 + 𝐶 ( + ) 𝑠 + ( + )𝑠 (19)
In order to avoid significant change in the power factor of the filter, the parallel capacitor is
Figure 2-7. Schematic for an LCL filter [6]
24
limited to a percentage of the base capacitance of the system [6]. This requires knowledge of the
power and voltage ratings of the inverter as follows:
𝐶 ( )
( )𝐶 ( )
(20)
If this capacitor is to be connected in a delta configuration then line-to-line voltage
would be used instead of line-to-ground voltage . This derivation of the LCL, instead of being
designed based on a cutoff frequency to eliminate specified harmonics, is designed to attenuate
the overall ripple current amplitude. The inverter-side inductor is determined from an initial
ripple attenuation, which is a reduction to 20% as follows [6]:
( ) (21)
The value of the grid side inductor is determined once again by using required ripple
current reduction, which is 10%, so resulting attenuation is (20%)(10%) = 2%. Relevant
equations are:
(22)
( )
( )
| + ( 𝐶 ( )( ) )| (23)
Due to the effect of the additional inductor the filter actually has a resonant frequency of
its own at:
√ +
𝐶 (24)
This resonant frequency should be chosen at most to be half of the switching frequency
of the inverter and at least ten times greater than the fundamental frequency [6]. This keeps the
filter from amplifying switching noise as well as the lower order harmonics that are potentially
25
produced in a single-phase inverter. In addition to choosing the appropriate resonant frequency a
resistor is added in series with the parallel capacitor in order to attenuate the resonance. The
value of this resistance is given by:
𝐶 (25)
The factor of 3 in the denominator would be eliminated if the resistor is placed in delta
configuration.
2.5 Pulse-Width Modulation Algorithm
A sinusoidal pulse width modulation (SPWM) is employed in order to produce the
sinusoidal output voltage with an inverter [7]. This technique compares a sinusoidal control
signal which under normal operating conditions has an amplitude of less than 1. This control
signal is compared to a triangular waveform with an amplitude of 1. When the triangular
waveform has a lower value than the control signal then the output of the PWM generator is 1
and when it is higher the output of the PWM generator is 0. When this output of the inverter is
filtered appropriately the resulting output is a sinusoidal voltage with the same frequency
magnitude as the control signal sent to the PWM generator. The frequency of the triangular
waveform corresponds to the switching frequency of the inverter. These signals can be applied to
the full-bridge inverter in many different ways. An example of this is drawn in Fig. 2-8Figure
2-8.
In bipolar PWM switching one set of signals is sent to the top and bottom switches of the
first leg of the inverter and the second leg receives the same signals but inverted. Thus, the
output of the inverter can either be –Vdc or Vdc, where Vdc is the voltage of the dc bus. Unipolar
PWM switching uses a PWM generator for each leg of the inverter; one generator receives the
26
control signal unmodified and the other receives the same control signal but negated. This type
of modulation means that the top two or bottom two switches in the inverter can be on at the
same time, which means that the voltage across the load can be 0 V, VDC, or –VDC. Unipolar
switching doubles the effective switching frequency of the inverter resulting in less harmonic
currents.
2.6 Discretization of the UCSC control system functions
Once the UCSC control system has been verified using continuous-domain techniques,
the system must be transferred to the discrete domain in order to apply it to a real-world
prototype by transforming all control operations into their Z-domain equivalents. The general
method for this application would be the unilateral z-transformation [8]:
( ) { (𝑡)} ∑ ( 𝑇 )
(26)
The continuous function x(t) is broken into discrete parts based on the sampling rate of
the system Ts and z-n
is an operator that when applied to a variable refers to its value “n”
Figure 2-8. SPWM waveforms (top) and the resulting pulses (bottom)
27
sampling periods earlier. As computing an infinite series can be cumbersome and many control
operations are done in the Laplace domain, it is much simpler to make use of s-to-z
approximations. Five examples of Laplace-to-discrete transformations are given below [9]:
Euler Forward: 𝑠
Euler Backward: 𝑠
Tustin (Trapezoidal): 𝑠
Zero-Order Hold: 𝑠 ( ) { ( )
}
Matched Pole-Zero:
2.7 Concluding Remarks
This chapter presented the underlying theory behind the operation and control of the
UCSC. This included the reference frames that the controller relies upon, how the controller
operates, and the process of developing a controller that works in a real-world implementation.
The next chapter will focus on building simulations and resulting results that were used to verify
the performance of the UCSC.
2.8 References
[1] Manuel A. S. Tejada, "Unbalanced Current Static Compensator," Department of Electrical
Engineering, University of Arkansas, Fayetteville, MS Thesis 2014.
[2] M. S. Huertas, "The use of power electonics for emulating power distribution feeders,"
Department of Electrical Engineering, University of Arkansas, Fayetteville, Masters Thesis
2008.
[3] U. A. Miranda, L. G. B. Rolim, and M Aredes, "A DQ synchronous reference frame current
control for signle-phase converters," in IEEE 36th Power Electronics Specialists Conference
PESC'05, Recife, 2005, pp. 1377-1381.
28
[4] P.C. Krause, O. Wasynczuk, and S.D. Sudhoff, Analysis of Electric Machinery and Drive
Systems, 3rd ed. Somerset, United States of America: Wiley, 2013.
[5] C. A. Busada, S. Gomez Jorge, A. E. Leon, and J. A. Solsona, "Current controller based on
reduced order generalized integrators for distributed generation systems," IEEE Transactions
Industrial Electronics, vol. 59, no. 7, pp. 2898-2909, 2012.
[6] A. Reznik, M.G. Simoes, A. Al-Durra, and S.M. Muyeen, "Filter Design and Performance
Analysis for Grid-Interconnected Systems," Industry Applications, IEEE Transactions on,
vol. 50, no. 2, pp. 1225-1232, March-April 2014.
[7] N. Mohan, T. M. Undeland, and W. P. Robbins, Power Electronics: Converters Applications
and Design, 3rd ed. New Jersey, United States of America: JW&S Inc, 2003.
[8] H. A. Helm, "The Z transformation," The Bell System Technical Journal, vol. 38, no. 1, pp.
177-196, January 1959.
[9] F. J. Rodriguez et al., "Discrete-time implementation of second order generalized integrators
for grid converters," in Proceedings 34th Annual Conference IEEE Industrial Electronics,
2008, pp. 176-181.
29
CHAPTER 3 3
SIMULATION PROCESS AND RESULTS
3.1 Introduction
The system shown in Fig. 3-1 was implemented and tested in Matlab/SIMULINK™ in
order to establish the plausibility of the proposed solution. This system is based upon the 6
MVA, 34.5 kV radial feeder case study described in Chapter 1 [1]. The inverters are rated 480
VL-N, and have a current rating of 2048 A, giving each a 1 MVA rating.
Fig. 3-2 shows the simulation results of the case study from the model proposed in [1].
The UCSC is in 3 different modes of operation. In the first mode from 0.03 s to 0.15 s,
the UCSC is compensating for the unbalanced loads. From 0.15 s to 0.60 s, the UCSC is
fully operational. At 0.40 s, there is a step increase of 30% in one of the phase loads.
3.2 Realized Changes to Previously Suggested Simulation Model
Several changes were made to the original model proposed in [1] either to improve its
performance or to reduce its computational load. These changes are addressed below.
Figure 3-1. Matlab/SIMULINK™ UCSC system
30
3.2.1 PWM Control Signal Normalization
The previous model in [1] and the change made to it are shown in Fig. 3-3. If the control
signal is normalized as in Fig. 3-3 (a), then the resulting control signal will contain the same 2nd
harmonic component that is present in the dc bus voltage. This will result in a 3rd
harmonic
voltage component being produced in the output of the inverter because of the rotating reference
frame. The control signal is now normalized using the instantaneous dc bus voltage to avoid this
harmonic as in Fig. 3-3 (b).
3.2.2 Current Reference Generator
In the original model, displayed in Fig. 3-3, a reference current from the dc-bus voltage
controller was added to the error between the d-axis inverter current, igad, and the d-axis current
reference, i*
gad. The result of this scheme was a “wind-up” of the PI controllers for the reference
current and the voltage controller. An example of this is shown in Fig. 3-5 where the output of PI
controllers continues to rise even when the UCSC is in steady-state operation.
Figure 3-2. Substation currents from the previous model in different UCSC operating
modes
31
By adding now directly the dc-bus voltage error to the reference current error; this “wind-
up” and extra DSP calculations were avoided. The PI controller for the voltage error was
eliminated. The resulting output from the current reference PI controller now has the form
illustrated in Fig. 3-6. The new system is shown in Fig. 3-7.
In addition to moving the voltage error, a notch filter at 120 Hz was added to the Vdc
measurement used to compare to the reference. The elimination of the 2nd
harmonic voltage
ripple in the control system is desirable because (a) PI controllers are meant to work upon dc
values and because (b) 2nd
harmonics in the d-q reference frame become 3rd
harmonic
components in the control waveforms sent to the PWM generator. This results in a 3rd
harmonic
component in the output voltage of the single-phase inverters used in the UCSC. The voltage
measurement before and after the notch filter is shown in Fig. 3-8.
Another change within the reference current generator refers to the sourcing of the
Figure 3-3. PWM control signal normalization
32
current measurements. Instead of measuring all the substation, load and inverter currents, as done
previously, the model now just computes the inverter and loads current and uses KCL at the PCC
to determine the substation currents. This saves computational time for the DSP to perform the
SOGI and d-q transforms (associated with sampling these currents) that make up most of the
DSP’s calculations.
3.3 Modifying the Time-Domain Simulations to Reflect the Prototype Implementation
To better emulate the behavior of the prototype, the controller was modeled as it is
implemented in the DSP and the start-up procedure is modified to be indicative of the laboratory
testing. The sections below describe the realized changes.
Figure 3-4. Previously suggested controller [1]
33
3.3.1 Sensing Circuitry
Fig. 3-9 is the block diagram that emulates the current and voltage measurements as
implemented in the actual system. The first gain is the conversion ratio between the actual
current or voltage being measured by the sensors and its output, followed by the voltage output
of the conditioning circuits that are connected to the sensor’s output. The filter after this first
gain is analog filtering as a result of the feedback capacitor in the operational amplifier based
conditioning circuit. The second gain is the compensation due to any loss in gain from the effects
Time(s)
Figure 3-5. Outputs of the current reference and voltage PI controllers in the previous
system
Figure 3-6. Current reference PI controller output for new system
34
of the analog filtering.
The uniform random number block generates noise to mimic the noise experienced in the
actual ADC measurements. The quantizer block mimics the ADC characteristics of the DSP
where the ADC module can only detect 4096 different discrete voltage values between the digital
ground and supply voltage (3.0 V). The last block is the digital filter used to eliminate high-
frequency noises from the ADC measurements. This digital filter averages the last two samples.
This is the discrete domain equivalent to a single-pole continuous transfer function with a cutoff
frequency at half of the sampling frequency.
Figure 3-7. Reference generator for the current controller
Figure 3-8. Effect of the notch filter before (left) and after (right)
35
3.3.2 Inverter Devices and Filter Components
When validating the control of the system, semiconductor devices near to ideal are used
in the simulations. But to get the appropriate behavior of the inverters, IGBT and diode models
that better describe the behavior of the actual IGBT and antiparallel diode co-package found in
the prototype are used as shown in Fig. 3-10. The most important parameters are the minimum
voltage drop across the IGBT , the on-state resistance of the IGBT , the minimum voltage
drop across the antiparallel diode , and the on-state resistance of the antiparallel diode .
Though the models used also allow for package inductances, turn-off and tail current times, and
parasitic snubber, these are not as important for a full system simulation as the time step required
to witness the phenomenon that these parameters cause is too small to efficiently test the model.
These are important when looking at the effects of parasitics, which will be described later.
The prototype IGBTs are the FGH20N60SFDTU from Fairchild Semiconductor whose
main parameters are listed in Table 3-1. Fig. 3-11 shows the dialog box for the IGBT and
antiparallel diodes used in the simulations. It is also important to use accurate values for the
inductances and resistances in the filter because of the decoupling terms required in the current
controller for each phase. This includes finding the actual inductances and winding
Figure 3-9. Measurement filtering and conditioning used in the simulations
36
resistances of the filter inductors. There is a slight variation in the inductance between each of
the inductors because the inductors were handmade; an impedance meter was used to test the
inductance of each of the inductors.
3.3.3 Pre-Filtering of d-q Signals
In [1], the output of the d-q transformations were first filtered through single-pole transfer
functions such as
. This introduced an additional measurement delay on the signals used in
Figure 3-10. Inverter implemented in SIMULINK™
Table 3-1. Parameters of the prototype IGBTs
Property Value
VCE Breakdown Voltage 600 V
Rated Collector Current @ 25°C 40 A
Maximum Power @ 25°C 165 W
Operating Temperature -55°C to +150°C
37
the control algorithm. These filters that can slow down the settling and the response times for
any changes in the load currents were removed to avoid these affects.
3.3.4 Coupling Transformers
The transformers in the simulations were characterized using the short-circuit and dc
resistance test on the transformers used in the lab testing. The short-circuit test consisted of
shorting the low-voltage side of transformer and then increasing the high-side voltage until the
rated current. Then, the leakage reactance can be calculated using the current and voltage on the
high side. The winding resistance is found by applying a dc voltage to both sides of the
transformer and calculating the dc resistance based on the current that flows. The resistance of
Figure 3-11. Dialog box for the IGBTs and diodes used in the SIMULINK™ simulations
38
the windings for a 60 Hz waveform can be approximated by the dc resistance because the skin
effect is negligible at low frequencies unless the conductors used have a very large cross-
sectional area.
3.3.5 Discrete Phase-Lock Loop Algorithm
The phase-lock loop algorithm implemented in the DSP is summarized in Fig. 3-12,
where a normalized grid voltage is the input. Then, a single-phase d-q transformation is
performed based on the previously estimated grid angle. If the grid angle estimation is correct,
then the d-q transformation will result in a null q component and the d component is the peak
magnitude of the grid voltage. Assuming that the estimated grid angle is wrong, the q component
has a non-zero value and becomes an error signal. This error signal is processed through a PI
controller that acts as a low-pass filter (LPF) to eliminate any measurement noise [2]. The
transfer function for the LPF is given by:
( )
(
) (
)
(1)
Figure 3-12. Discrete phase-lock loop block diagram
39
where is the proportional gain, is the integral gain, and is the sampling period.
This filtered error signal is added to the nominal grid value to either increase or decrease
the rate of change of the estimated phase angle. This causes the derivative of the phase angle to
increase or decrease in order to eliminate the q component. The most recently calculated sine and
cosine values are used in the next cycle of the algorithm [2]. The sine and cosine functions in the
DSP are actually computed using a lookup table (LUT) that includes 512 values to define each
quarter of the sine and cosine functions; so, it is assumed that there is a negligible amount of
error between the actual function and the values used by the DSP.
3.3.6 Discrete d-q Transformation
The d-q transformation as performed in the DSP is illustrated in Fig. 3-13. A SOGI-QSG
is used to produce a quadrature signal for the single-phase transformation [2]. The outputs of the
SOGI-QSG are used along with the sine and cosine of the grid voltage angle to produce the d-
and q-axis outputs. The discrete transfer functions from the Tustin approximation for both
outputs of the SOGI-QSG are:
( )
( )
(2)
Figure 3-13. D-Q Transformation
40
( )
( )
(3)
where, , , , , , , , and are constant that are specified in:
( )
( ) (4)
( )
( )
( )
(5)
( ) (6)
( ) (7)
using the fundamental frequency , sampling period , and the forward gain .
3.4 Simulation Results of the New Model
The substations currents from the new model in the continuous domain are shown in Fig.
3-14. This includes most of the changes mentioned above; however, it excludes all discretization
modifications. As in Fig. 3-2 the waveforms encompass three different operating
modes of the UCSC. From 0.00 s to 0.15 s, the UCSC is not operational. From 0.15
s to 0.25 s, the UCSC is compensating for the reactive power of the load. From 0.25 s to
0.60 s ,the UCSC is fully operational. At 0.40 s there is a step increase of 30% in one of
the phase loads. The substation currents in steady state are brought to a UBF of 0.497%, where
UBF is calculated using:
(8)
Using the rated currents and voltages for which the UCSC prototype was designed,
discrete-domain simulations were run to predict the system performance. Demonstrating
41
the predicted prototype performance in the same operating modes as the case-study simulations,
the substation currents are shown in Fig. 3-15. From 0.20 s to 0.30 s, the UCSC is not
operational. From 0.30 s to 0.45 s, the UCSC is compensating for the reactive power of
the load. And from 0.45 s to 0.80 s, the UCSC is fully operational. Some neutral current
Figure 3-14. Substation currents from new continuous model in different UCSC operating
modes
Figure 3-15. Substation currents from the discrete-domain prototype simulation
42
exists due to the non-idealities that were introduced into the model. The most significant
component of this neutral current is the third harmonic produced from dead time effect in the
output of the UCSC inverters. In steady state, these simulations yielded an average UBF of
0.37%, down from an UBF of 18.2% when the UCSC is not operational.
3.4.1 Effect of Incorrect Decoupling Terms
Within the current controller as described in Chapter 2 there are decoupling terms that
allow for separate control of the d-axis and q-axis currents. Fig. 3-16(a) and Fig. 3-16(b) show
the substation currents from the laboratory prototype simulations with and without the
decoupling terms, respectively, during a large load change on one phase. Though they both
perform as expected in steady-state, the simulation with the decoupling terms shows better
transient response. The absence of the decoupling terms is an extreme case, but a diminished
transient performance can also be caused by incorrect assumption about filter inductance values.
3.5 Conclusions
Improvements made upon the UCSC controller improved its dynamic response and made
it more stable. Through several other modifications, such as the discretization of the controller
Figure 3-16. Transient reponse of UCSC with (a) and without (b) decoupling terms
43
and the inclusion of dead time, a model that was more indicative of a real implementation of the
UCSC was created. This model showed the compensator was still effective at reducing the
negative- and zero-sequence fundamental current components as seen by the substation.
With the viability of the proposed solution confirmed by simulations the next step is the
construction of a prototype that can be tested in a laboratory setting. Determining the effect of
different component choices on the performance of the UCSC becomes easier with a simulation
that emulates the non-ideal behavior of an actual prototype. The simulation can help to validate
component choices before they are installed on the prototype.
3.6 References
[1] Manuel A. S. Tejada, "Unbalanced Current Static Compensator," Department of Electrical
Engineering, University of Arkansas, Fayetteville, Masters Thesis 2014.
[2] Texas Instruments, C28x Solar Library Module User's Guide, 2014.
44
CHAPTER 4 4
DESIGN OF THE SCALED-DOWN UCSC PROTOTYPE
4.1 Introduction
The objective of this chapter is to explain the process for designing and constructing the
UCSC scaled-down prototype based on the 34.5 kV, 6 MVA case study. Thus, this chapter
begins with the procedure used for scaling down the case study introduced in Chapter 1, and
includes component selections as well as the printed circuit board layout. A comprehensive
design process for AC inductors is also included because the required inductors are not
commercially available.
4.2 Design of the Prototype Power Stage
4.2.1 Scaling-Down the Case Study
A per-unit scaling is used to reduce the power rating of the case study in Chapter 1 to a
level that can be produced in a laboratory environment. A base power 6 MVA along
with a base voltage 34.5 kV are used to convert the case study parameters to their per
unit equivalents. A base power 10 kVA and a base voltage 208 V were
chosen based on the power delivery and voltage capabilities in the lab. These base values are
then used to convert the per unit values from the case study into the real laboratory system
values. The power rating for each of the UCSC prototype inverters is chosen based on the active
and reactive power demand of the calculated loads. A summary of the results from these
calculations is presented in Table 4-1. From these power ratings, each inverter was designed for
1 kVA at a voltage of 120 VL-N.
45
4.2.2 Calculations for the dc Link Capacitor Sizing
Though the UCSC is effectively a three-phase inverter, due to the unbalance in the loads
and the varying phase shifts between the three phases, the ( ) voltage ripple in the dc bus is
still an issue. For a single-phase inverter, the dc capacitor current has a dc component as well as
a ( ) component [1]. In the case of the UCSC, the dc current component is small, flowing into
the capacitor to maintain its voltage because there is no power generation on the dc bus.
An assumption made for the UCSC system is that each phase compensate for
approximately the same reactive power. Thus, the imbalance between the inverter currents will
come from the active current component differences between each phase. Using data from the
case study in [2], it is assumed that the active current between phase differs at most by 0.15 pu
which results in 4.0A for the scaled-down laboratory system. The worst case scenario for ripple
current on the dc bus is when one inverter is producing a current of 0.15 pu more than the other
two. The equivalent current ripple of the dc bus is that of a single-phase inverter with an output
current of 0.15 pu given by:
(1)
Table 4-1. Load power ratings for the case study and scaled-down prototype
Parameter Cast Study Laboratory
PLoad1 (kW) 877 1.461
QLoad1 (kVAR) 500 0.833
PLoad2 (kW) 707 1.178
QLoad2 (kVAR) 300 0.500
PLoad3 (kW) 753 1.255
QLoad4 (kVAR) 300 0.666
46
where is the peak of the sinusoidal output voltage of the inverter, is the peak output current
of the inverter, and is the dc-bus voltage applied to the inverter. The capacitance is
calculated using:
| | (2)
where and is chosen as the desired voltage ripple. The UCSC dc-bus capacitor parameters are
given in Table 4-2.
4.2.3 Design of the Gate Driving Circuit
Each IGBT in the UCSC is driven with a bipolar power supply of +17 V and -8.7 V. So
+17 V is applied to the gate of the IGBT during turn-on and -8.7 V at turn-off. This, along with a
gate driving IC with relatively large current capability, is required to charge and discharge the
gate capacitance quickly; translating into faster turn-on and turn-off times. For each IGBT used
in the prototype, the CUI Inc VQA-S15-D17-SIP power supply and the Silicon Labs
SI8261BCC-C-IS isolated gate driver was used. An isolated gate driver was chosen to reduce the
part count and reduce the propagation delay.
The gate driver IC can source up 1.8 A and sink up to 4.0 A from the same output pin. To
utilize the larger current sinking ability from the same output pin two separate gate resistors (20
Ω and 6.8 Ω) were used in series with diodes. During turn-on the gate of the IGBT will be driven
through a 20 Ω resistor while the current through the 6.8 Ω resistor is blocked by a reverse-
Table 4-2. DC Link Capacitor Parameters
Parameter Value
Maximum Peak Ripple Current 4 A
Desired Peak Voltage Ripple 1% of rated bus
Capacitance 2200 μF
dc-bus voltage rating 250 V
47
biased diode. At turn-off the gate driver sinks current through the 6.8 Ω resistor while the current
through the 20 Ω resistor is blocked by a reverse-biased diode.
Capacitors rated 25 V and 100 uF were used at the input of the power supply as well as at
both outputs. This was done to provide an additional source of charge to compensate for the
large currents drawn by the gate driver IC. Additional ceramic capacitors with values of 1.0 μF,
0.1 μF and 0.01 μF were added as close to the gate driver IC as possible to provide compensation
for high frequency voltage oscillations experienced during switching transitions. Bleeding
resistors that draw 1% of the rated current were also added from supply to ground at the output
of the power supply to help with no-load voltage regulation of the power supply.
Voltage protection at the gate is important because exceeding the voltage rating of the
gate oxide used in the IGBT (±20 V relative to the emitter) can cause catastrophic device failure.
Between gate and emitter of the IGBT two zener diodes are placed in series with a common
cathode configuration. One zener has a breakdown voltage of 18 V for over-voltage protection
during the on-time of the IGBT and the other has a breakdown voltage of 9 V to protection
against undervoltages during the off-time. The diodes are in parallel with a 50 kΩ bleeding
resistor placed to help drain charge from the gate capacitance during turn-off as well as protect
the IGBT from false triggering due to current oscillations at the gate.
4.2.4 The Effect of Parasitics on System Performance
Connecting components on a PCB or with cables introduces parasitic between the two
points of contact. This can be in the form of a capacitance, such as the overlapping of traces
between layers or crosstalk between two parallel traces on the same layer. It can also be
inductance caused by the orientation of the trace itself or the self-inductance present in all
conductors [1].
48
Another source of these parasitic inductances and capacitances comes from the devices
and the packages in which they are held. The IGBTs used in the UCSC prototype have parasitic
inductances from the leads that solder to the board and from the wire bonds used to connect these
leads to the metallization on the substrate. In addition there are parasitic capacitances between
the leads due to the characteristics of the semiconductor. When these are taken into account in
the simulations they become the source of current and voltage oscillations or “ringing” present in
the circuit. The next two subsections highlight the importance of reducing these parasitics
through careful system packaging and printed circuit board design.
Power Stage Parasitics
A major concern is the voltage across the semiconductor devices used in the legs of the
inverters in the UCSC. The IGBTs have a maximum rated voltage of 600 V that they can handle
without breaking down. While the dc-bus voltage used in the prototype is only 250 V, the
parasitic inductances can cause very large voltage spikes if countermeasures are not taken. These
spikes come from energy stored in the parasitic inductances and the rate of change of the current
[1]. A large voltage is developed at the collector terminal due to the abrupt change in current at
the IGBT turn-off. If the inductance can be minimized then these effects might be negligible, but
in many cases there is an unavoidable amount of parasitic inductance from the traces due to size
constraints and technologies used. Appendix A explains some of the passive solutions used to
mitigate this ringing.
Gate Driver Circuit Parasitics
Because of the short turn-on and turn-off times associated with IGBTs, gate driver
circuits have unavoidably large changes in current that can lead to oscillations in the voltage
applied to the gate of the IGBT [1]. There are two major sources of voltage spikes at the gate.
49
One is the inductance of the small section of conductor shared by the power stage and the gate
driver. During the reverse recovery time of the antiparallel diode there is a significant change in
current. This
across the emitter inductance can cause an oscillation in the voltage applied to
the gate [3]. The other source are the oscillations that occur due to the interaction between the
trace inductance and the Miller capacitance of the IGBT, . During the turn-on transient some
of the current from the gate-driver IC goes into the as it discharges through the conduction
channel of the IGBT. If the gate driver injects too much current too quickly the IGBT cannot
respond quickly enough and large voltage swings will result.
Relative to the emitter terminal, most IGBTs can only handle ±20V before the gate oxide
begins to breakdown. Devices are normally driven close to these maximum voltages in order to
decrease their turn-on and turn-off times and because of this the voltage oscillations at the gate
need to be minimized; otherwise, devices failure may occur.
4.2.5 Design of the Printed Circuit Board for the Power Stage
A four-layer printed circuit board (PCB) was designed in order to more easily integrate
the gate drivers and IGBTs on the same board. Fig. 4-1 to Fig. 4-4 display the positive photoplots
(in color) used for each of the layer of the PCB. These were created using Cadence® Allegro
®
PCB Designer software.
The bottom layer, shown in Fig. 4-1, contains the positive rail of the dc bus and the
midpoints of each leg (outlined in green). The traces were made very wide in order to reduce the
parasitic inductances between the dc-bus capacitor and each of three inverters. The negative rail
of the dc bus is contained in the bottom-middle layer displayed in Fig. 4-2. This layer is almost
all copper to shield the top and top-middle layers from EMI generated by the current in the
bottom layer [4]. The plane used is split so that the return current to the capacitor does not
50
flow in the outside portions of the plane. By doing this, these portions of the plane only act as
shields and do not transfer any switching related EMI to the upper layers.
The traces drawn for the gate driving circuitry can be found in Fig. 4-3 and Fig. 4-4. The
ICs mentioned in section 4.2.6, which are represented by the footprints within the indicated are
in Fig. 4-3 and Fig. 4-4, are placed near the IGBT to reduce the length of the current loop used to
charge the gate capacitor. This along with the use of wide traces reduces the parasitic
inductances. Overlapping the power and ground traces for the gate charging loop also
Figure 4-1. Bottom layer photoplot for the power stage PCB used in the UCSC prototype
Figure 4-2. Bottom-middle layer photoplot for the power stage PCB used in the UCSC
prototype
51
help to reduce the inductance by partial cancellation of the self-inductance of each of the traces
using the mutual inductance between them [5]. This overlapping also creates a deliberate
parasitic capacitance between the power rails which helps to filter the unwanted higher
frequency currents that are generated in the gate driving path.
4.3 Design of the Filter Inductors
The design process given below was used to design and build the filter inductors that
were used in the prototype. The process that comes from [6] can be applied to any ac inductor.
Figure 4-3. Top-middle layer photoplot for the power stage PCB used in the UCSC prototype
Figure 4-4. Top layer photoplot for the power stage PCB used in the UCSC prototype
52
After each step, the results for each inductor are in bold. The quantities in Table 4-3 were
determined before the process can begin with the inductance values determined using the process
outlined in section 2.4.
The sinusoidal voltage across the inductor is determined based on its reactance and the
rated current through it. The current density is chosen within a normal range of 150-250 A/cm2
which changes based on the core material. Flux density is determined from the maximum
operating flux density of the material that is chosen for the core. Window utilization refers to the
percentage of the area that is enclosed by the inductor core that is filled with the wire and its
insulation. Waveform factor is a scaling term used in several of the equations which reflects the
shape of the applied ac waveform; for a square waveform 4.0, and for a pure sinusoidal
4.44. The temperature rise goal refers to the inductor temperature with respect to room
temperature which is considered to be 40 °C,
Step 1 – Power Rating:
Determine the inductor power rating using its voltage and current:
(3)
resulting in:
Table 4-3. 2.2 mH and 0.5 mH Inductor Design Parameters
Parameter 2.2 mH 0.5 mH Unit
Voltage across inductor, 𝑉𝐿 8.29 1.884954 V
Line Current, 𝐼𝐿 10 10 A
Line Frequency, 𝑓 60 60 Hz
Current Density, 𝐽 200 200 A/cm^2
Efficiency Goal, 𝜇 90 90 %
Flux Density, 𝐵𝑎𝑐 1.5 1.5 T
Window Utilization, 𝐾𝑢 0.4 0.4
Waveform Factor, 𝐾𝑓 4.44 4.44
Temperature Rise Goal, 𝑇𝑟 20 20 °C
Desired Inductance, 𝐿 0.0022 1.884954 H
53
2.2 mH: S = 83 VA
0.5 mH: S = 19 VA
Step 2 – Area Product:
The area product is determined based on:
(4)
yielding:
2.2 mH: = 17.30 cm4
0.5 mH: = 3.93 cm4
This term determines the minimum size core that is required.
Step 3 – Core Selection:
There are many different core shapes as well as materials from which to choose. Each
one has specific advantages over the others. For application in this inverter, size was the largest
concern, therefore, a core with a large operating flux density is the most helpful. The large
capacity for flux means that less core volume is required for the same excitation level. An
amorphous core was chosen in this case, because of its maximum operating flux density of 1.6 T.
The operating flux density shown in Table 4-3 was chosen as 1.5 T to have a safety margin.
Currently, this type of core is mostly limited to C shapes, so that was the chosen shape. The
selected cores based on AP were:
2.2 mH: AMCC0040
0.5 mH: AMCC06R3
Table 4-4 shows data from Hitachi Metals for POWERLITE® amorphous cores [7].
is the abbreviation for mean length of turn, which is the average length of wire needed to wrap
around the leg of the core which can be estimated using values and Fig. 4-5. is the
54
core sectional area of the core (A x D), WA is the area contained within the core computed using
B x C, and AP refers to the same value calculated in Step 2, however this value for the core is the
product of AC and WA. At is the core surface area.
Step 4 – Wire Turns:
The number of wire turns is calculated by:
(5)
yielding:
2.2 mH: N = 56 turns
0.5 mH: N = 29 turns
Table 4-4. Amorphous Core Data [5]
𝑨
(cm)
𝑩
(cm)
𝑪
(cm)
𝑫
(cm)
𝑬
(cm)
𝑭
(cm)
AMCC06R3 1.0 1.1 3.3 2.0 3.1 5.3
AMCC0040 1.3 1.5 5.6 3.5 4.1 8.2
Mass
(g)
𝑴𝑳𝑻
(cm)
𝑨𝒄 (cm
2)
𝑾𝒂
(cm2)
𝑨𝒑
(cm4)
𝑨𝒕 (cm
2)
AMCC06R3 154 6.0 1.64 3.63 5.95 59.20
AMCC0040 530 9.6 3.73 8.40 31.33 136.54
Figure 4-5. Dimensions of a C core pair [5]
55
Step 5 – Air Gap Calculation:
This is a deliberate gap between the two halves of the C cores that increases the
reluctance of the core’s flux path. A larger excitation current or magnetic field strength is
required to achieve the same flux density because of the increase in reluctance. Though this
reduces the effectiveness of the inductor as a whole, this gap prevents the core from saturating as
quickly by extending the linear operating region of the core material. Fig. 4-6 demonstrates the
effect of the air gap using the B-H curve that is used widely in magnetics [6]. The solid line is
the core characteristic without an air gap and the dotted line is with an air gap given by:
(6)
yielding:
2.2 mH: = 0.066 cm
0.5 mH: = 0.034 cm
Figure 4-6. B-H Curve without airgap (solid line) and with airgap (dotted line)
56
Step 6 – Fringing Flux Factor:
The fringing flux factor is a unitless correction term to account for the fringing flux that
arises from the air gap. The larger the air gap, the larger the fringing flux, which can cause
localized heating around the air gap, also cause the material to saturate prematurely, and is
calculated as follows:
(
⁄ )
√
(7)
resulting in:
2.2 mH: = 1.16
0.5 mH: = 1.14
Step 7 – New Number of Turns:
A new number of turns is determined taking into account the fringing flux to avoid any
problems that it might cause as follows:
(8)
yielding:
2.2 mH: = 52 turns
0.5 mH: = 27 turns
Step 8 – Core Verification:
After determining a new number of turns it is necessary to check whether the core is still
suitable for operating at a flux density appropriate for the material. This is done using:
57
(9)
which yields:
2.2 mH: = 1.61 T
0.5 mH: = 1.60 T
These values are still appropriate for the materials chosen, though they are at the material
maximum flux density; however the designed inductors have a larger current rating than that of
the UCSC so they should never experience the above flux densities.
Step 9 – Bare Wire Area:
The area of the required wire based on the rated current of the inductor and the desired
current density for the wire. The calculation is done per:
(10)
resulting in:
2.2 mH: = 0.05 cm2
0.5 mH: = 0.05 cm2
The current density may vary based on the operating temperature of the inductor and the
available space.
Step 10 – Wire Size:
The next step is to select a wire size based upon the previously calculated bare wire area.
The conductor chosen should have a bare wire are as large as . A table of AWG conductor
areas is easily available from many sources [8]. Taking in account the above yields:
2.2 mH: 10 AWG
0.5 mH: 10 AWG
58
Step 11 – Winding Resistance:
The winding resistance is determined as follows:
(11)
where is the wire resistance per centimeter. If the resistivity is not known, it can be calculated
from the specific resistance, of the wire material and the bare wire area. For the selected wire
size and number of turns, (11) results in:
2.2 mH: 0.0079 Ω
0.5 mH: 0.0211 Ω
Step 12 – Winding Losses:
The winding losses are now determined using:
(12)
which yields:
2.2 mH: 0.79 W
0.5 mH: 2.11 W
Step 13 – Hysteresis Losses:
Some of the applied flux actually is cancelled out due to the residual magnetic field that
is held by ferromagnetic materials from past applied fluxes. This interaction causes losses in the
core that are referred to as hysteresis losses [6]. Eddy currents also produce losses; these are
currents within the core that are induced in order to oppose the change in flux. These currents
flowing within the material cause losses. Some cores are built using insulated laminations to
minimize the eddy currents by limiting the length of the current loop that can develop
perpendicular to the travel of flux [6].
59
These losses that are determined empirically by the core manufacturer depend on the
properties of the material and the applied frequency. Usually they are estimated using graphs like
the one in Fig. 4-7. The core losses incurred are determined as follows:
(13)
where
are calculated per:
(
⁄ )
(
⁄ )
(14)
(
⁄ )
(
⁄ )
(15)
(16)
The subscripts A, B, and C represent the value of the variables they operate on at arbitrary points
A, B, and C in Fig. 4-7 above. However, points A and B must have the same frequency, but
differ from the frequency of point C and points B and C must share the same flux density, but
differ from the flux density of point A.
In Fig. 4-7, the manufacturer provides the following values for :
60
Step 14 – Total Core Losses:
Core losses are calculated as a function of mass, so the total core losses are given by:
Figure 4-7. Core loss curves for the Hitachi POWERLITE amorphous cores
61
(17)
where is the mass of the core. For the selected cores, the total core losses are:
2.2 mH: 0.113 W
0.5 mH: 0.032 W
Step 15 – Loss Power Density:
The temperature analysis begins once the core has been selected. Losses in the core and
in the windings have only a limited surface area from which that heat can escape. The power loss
per surface area is calculated as follows:
(18)
resulting in:
2.2 mH: 0.0163 W
0.5 mH: 0.0139 W
Step 16 – Core Temperature Rise:
The temperature rise of the core is dependent upon the surface area power density and the
properties of the material. This equation is used for iron based ferrites [6]:
(19)
The design is satisfactory if this temperature rise is acceptable; otherwise a new core with a
larger surface area per unit volume or a larger wire should be chosen. For the selected cores:
2.2 mH: 15 K rise
0.5 mH: 13.2 K rise
which is an acceptable temperature rise. The inductors will not require external cooling and will
not overheat adjacent components.
62
Step 17 – Window Utilization:
The window utilization is computed in order to determine if the goals from Table 4-3
were met. The window utilization is given by:
(20)
The constants used in the denominator of (20) are used to modify the bare wire area to
compensate for the inefficiencies in the wire winding process. The maximum space usage of a
plane by identical circles is around 90%. A significant amount of the resulting diameter of a wire
comes from the insulation. In this case it was assumed that the actual copper only accounts for
75% of the diameter of each winding. For the selected cores, this yields:
2.2 mH: 0.48
0.5 mH: 0.58
The window utilization of the inductors wound for this project are larger than the goal because
an oversized wire was chosen.
Step 18 – Continuous Wire Length:
Lastly, the continuous length of wire needed to wind the inductor is specified. Using the
MLT from the inductor might not be an accurate representation of the average length of the
turns; in particular, this is the case when there will be more than one layer of turns used. The
wire continuous length is calculated as follows:
(21)
yielding:
2.2 mH: 695 cm
0.5 mH: 260 cm
63
4.4 Calculations for the IGBT Heat Sink
Due to the modulation of the duty cycle in unipolar switching, an estimation method for
the losses incurred in the IGBT and antiparallel diode must take into account a non-constant duty
cycle. The equations below from [9] use parameters given in the datasheet as well as an average
operating point of the switch to estimate the losses. The assumption made in these equations is
that the operating point used by the manufacturer to specify values in the datasheet is similar to
the actual operating point of the IGBT so linear extrapolation of values is valid; that is:
( )
(22)
(23)
(
)
(
) (24)
(
)
(
) (25)
where the definitions of the variables used and their values are given in Table 4-5. The
equivalent thermal circuit can be solved using these losses, the desired maximum operating
temperature and thermal-electric analogies [1]. Fig. 4-8 shows this circuit, where is the
junction-to-case thermal resistance is the case-to-sink thermal resistance and is the
sink-to-ambient resistance. Given the power dissipation of the IGBT and the antiparallel diode, a
thermal pad/grease ( ) and heat sink ( ) must be chosen so that the power dissipation,
analogous to current, does not cause a larger temperature rise, analogous to a voltage rise, than is
allowed. This circuit must be solved for the IGBT and the diode separately as they do not have
the same .
64
The circuits solved for the prototype are shown in Fig. 4-9. A thermal pad with a thermal
resistance of 1.5 °C/W is the chosen isolating material between the IGBT package and the heat
sink, so the required is determined and a heat sink must be chosen accordingly. An
ambient temperature of 40 °C is chosen to represent a worst case scenario. To limit the
maximum junction temperature in either device to 85 °C, the maximum is 2.55 °C/W. A
Table 4-5. Variables for switching and conduction losses in controlled semiconductor devices
Parameter Explanation Prototype Value
𝑓𝑠𝑤 Switching frequency of inverter 10 kHz
𝐸𝑜𝑛 Turn-on energy of IGBT from datasheet 0.63 mJ
𝐸𝑜𝑓𝑓 Turn-off energy of IGBT from datasheet 1.39 mJ
𝑉𝐷𝐶 Actual dc bus voltage 250 V
𝑉𝑟𝑒𝑓 Test dc bus voltage from datasheet 480 V
𝐿 Peak line current 11.5 A
𝑖𝑟𝑒𝑓 Test line current from datasheet 17 A
𝑀 Nominal modulation index 0.7
𝑝𝑓 Power factor of inverter 1.0
𝑉𝐶𝐸 On-state voltage of IGBT 1.8 V
𝑟𝐶𝐸 On-state resistance of IGBT 0.129 Ω
𝑉𝐹 On-state voltage of diode 1.8 V
𝑟𝑓 On-state resistance of diode 0.04 Ω
Figure 4-8. Equivalent thermal circuit for IGBT and antiparallel diode
65
heat sink with a thermal resistance of 2.55 °C/W or less must be chosen. The heat sink that was
chosen has a = 2.2 °C/W, but only with a forced convection of at least 300 ft/min parallel
to the blades. A fan was chosen with an air flow of 17.5 CFM and an output area of
approximately 0.0341 ft2. Using
(
)
(26)
results in an air speed of 513 ft/min, which is adequate.
4.5 Sensors and Measurement Conditioning
Isolated hall-effect sensors were used for measurement of the currents and voltages
needed for the control of the UCSC. The LEM HY-10P current sensor was used to measure all
currents and the LEM LV-20P to measure voltages. Isolated sensors are useful because they
decouple the measurement from any noise that exists in the ground of the power stage and reduce
the requirements of the PCB ground design. The sensors are also located away from the IGBTs
and LCL filter to reduce the EMI that they experience. The outputs of these sensors become the
input to the operational amplifier (op-amp) based conditioning circuits that modify the outputs of
the sensor to the appropriate voltage levels for use by the DSP. The op-amp used for the
Figure 4-9. Thermal circuits for the IGBT and antiparallel diode
66
prototype is the Tl081a from Texas Instruments and is fed by the same +15 V/-15 V supply rails
that supply the sensors which allow this 30 V range at each stage of the conditioning circuit. The
first stage of the conditioning circuit scales the voltage output from the sensor while the second
stage shifts the dc offset of the signal to 1.5 V, which corresponds to the half of the maximum
voltage (3.0 V) allowed by the analog-to-digital converter used by the digital controller. The
conditioning circuits for the current measurements also contained a phase-lagging third stage that
if utilized could replace the digital SOGI implemented in the digital signal processor and save
computation resources.
4.6 Concluding Remarks
The methods for designing the scaled-down UCSC prototype were disclosed addressed in
this chapter. This included the per-unit scaling process used to reduce the 6 MVA case study to a
10 kVA laboratory system and the selection of components in addition to dead time selection. A
synopsis of the effects of parasitics on the power stage provided the motivation for the design of
the PCB presented in subsection 4.2.8. Almost all the components used in the scaled-down
prototype were over-designed by 15 % to increase the robustness and flexibility of the prototype.
Reliability is important because device failures can be costly and repairs may require long period
of down time.
An appropriate implementation of the control in a digital signal processor is also
important for reliability. Using an appropriate start-up and shutdown procedures as well as
overcurrent protection can increase the lifetime of the devices that are used. Achieving the
necessary performance from a digital controller is the topic of the next chapter.
67
4.7 References
[1] N. Mohan, T. M. Undeland, and W. P. Robbins, Power Electronics: Converters Applications
and Design, 3rd ed. New Jersey, United States of America: JW&S Inc, 2003.
[2] Manuel A. S. Tejada, "Unbalanced Current Static Compensator," Dept. of Elect. Eng., Univ.
of Arkansas, Fayetteville, MS Thesis 2014.
[3] Semikron, "High-Frequency Oscillations due to Driver Coupling," Power Electronics
Europe, no. 6, pp. 2-4, 2013.
[4] Texas Instruments Incorporated, PCB Design Guiudelines for Reduced EMI, 1999.
[5] Richard K. Ulrich and William D. Brown, Advanced Electronic Packaging, 2nd ed.: Wiley-
IEEE Press, 2006.
[6] Colonel Wm. T. McLyman, Transformer and Inductor Design Handbook, 4th ed. United
States of America: CRC Press, 2004.
[7] Hitachi Metals America Ltd. (2011) Hitachi Metals Web Site. [Online].
http://www.elnamagnetics.com/wp-content/uploads/catalogs/metglas/powerlite.pdf
[8] PowerStream Technology. (2016, March) Wire Gauge and Current Limits Including Skin
Depth and Strength. [Online]. http://www.powerstream.com/Wire_Size.htm
[9] W.-T. Franke, M. Mohr, and F.W. Fuchs, "Comparison of a Z-source inverter and a voltage-
source inverter linked with a DC/DC-boost-converter for wind turbines concerning their
efficiency and installed semiconductor power," in Power Electronics Specialists Conference,
2008, 2008, pp. 1814-1820.
68
CHAPTER 5 5
IMPLEMENTATION OF THE CONTROL ALGORITHM IN A MICROCONTROLLER
5.1 Introduction
The objective of this chapter is to present the methods used to implement the controller
presented in Chapter 2 in the Texas Instruments TMS320F28335 Digital Signal Processor (DSP);
a 32-bit floating-point microcontroller. The computational load of the presented controller is
large due to the single-phase d-q transformations, so the initial implementation used three DSPs
to iterate through the discrete controller at the desired rate of 10 kHz. Each DSP controlled an
inverter and the necessary d-axis load current and voltage bus data was exchanged between these
three using the SCI serial communication ability on board each DSP. This separation of
computational load made debugging very inefficient and any auxiliary functions, such as
protection and operating mode changes, difficult to implement. A different solution using only
one DSP was desired; the newly devised system is the subject of this chapter.
5.2 Developing a Single-DSP System
A single-DSP solution was developed after further experience, significant reading, and
consultation from individuals more experienced on DSPs. The problem with the original
implementation is the location of the program used to implement the controller inside the DSP.
The program must be assigned to a non-volatile memory location to run the DSP in stand-alone
mode because volatile memory loses its data when the power is removed. The drawback of this
non-volatile memory, called FLASH memory, is that it requires many more CPU cycles to
access it for each instruction than it would for the same code stored in RAM; a volatile memory.
The key to running the code all in one DSP, but also in stand-alone mode, is to store the program
69
in FLASH, but copy the program to RAM at run-time. In this way the DSP does not require a
computer connection or suffers from the speed penalties that come from running the program out
of FLASH memory. With the above modifications it is now possible to run the entire program
used to control the UCSC at a rate of 20 kHz.
5.3 Controller Implementation in the DSP
The DSP implements all of the control functions presented in Chapter 2 as illustrated in
Fig. 5-1. The auxiliary processes performed outside the DSP controller code are shown inside the
red section in Fig. 5-1. These actions, that occur as fast as the DSP can perform them, include the
polling of the current controller flag bit ‘ccbit’ for proper timing of the current controller,
checking for overcurrent, and polling a PWM disable input. When an overcurrent or the PWM
disable input is detected, the PWM module on the DSP drives all gate outputs to 0 shutting down
the system.
The CPU timer interrupt that can transpire at any step within the red section normally
occurs every 0.00005 s (period of a 20 kHz signal). This interrupt sets ‘ccbit’ so that the current
controller will run at the same frequency as the interrupt. The timing of the current controller is
crucial because the accuracies of the z-domain functions used to implement the controller
operations are dependent upon the frequency at which they are run.
The blue section in Fig. 5-1 has the current controller operations. The controller starts by
sampling all of the required current and voltage signals and then, calculates the phase-lock loop
and the d-q transformations for the currents. The next action depends on the mode selected by
the user. The inverter has three modes: (1) only dc-bus voltage regulation, (2) compensation for
load reactive power and dc-bus voltage regulation, and (3) full current balancing operation. The
errors processed by the PI controllers will change depending on the operating mode.
70
Then, the controller must perform the inverse d-q transformations of the output voltage
and develop a control signal for to the PWM module which produces the gate signals for the
IGBT in the three single-phase inverters.
5.4 Start-Up and Shutdown Procedure
The controller in section 5.3 defines the behavior of the DSP during steady-state
operation, but the DSP and user behavior must change during start-up to avoid large inrush
Figure 5-1. Flowchart for the DSP processes
71
currents that might damage the semiconductor devices used in the power stage. To soft start the
UCSC scaled-down prototype, the follow procedure is used:
1) Adjust the autotransformer that acts as the system voltage source to lower the grid
voltage down to 0 V.
2) Close the breaker that isolates the UCSC from the grid to connect it to the grid.
3) Increase the system voltage is until the UCSC experiences a dc-bus voltage of 10 V.
4) Turn-on the DSP. The DSP forces the PWM module to shut off the gate signals while
it runs the phase-lock loop for 0.5 s. After this time the DSP enables the PWM gate
signals and the rest of the controller for each inverter when the corresponding grid
voltage is at the zero crossover point.
5) Then, the dc-bus reference voltage in the voltage controller ramps from 10 V to 250
V at a rate of 20 V/s, forcing the UCSC to raise the voltage of the dc-bus to 250 V.
Increase the grid voltage linearly by adjusting the autotransformer to follow the now
rising dc-bus voltage while keeping the peak value of the grid voltage below the dc-
bus voltage.
6) With the dc-bus at 250 V and the grid voltage at 110 VL-N, pull the first input pin low
to enable reactive current compensation mode inside the controller. The DSP will
ramp the reactive current reference from 0 to 100% of the full value linearly in 2.0 s
to avoid a large step change in the reference.
7) After the UCSC has compensated for all of the reactive current, pull the second input
pin low to force the UCSC into full compensation mode. Again, the DSP ramps the
current reference value from 0 to 100 % linearly over 2.0 s.
The following procedure is used to shut down the system:
72
1) When data acquisition for the run test is complete, pull the shutdown input pin low to
shut off the PWM module.
2) Adjust of the autotransformer to 0 V and open the breaker that connects the UCSC to
the grid. The charge in the dc-bus capacitor will dissipate through a bleeding resistor.
For installation on a distribution system, this method would not be acceptable as the
system voltage cannot be controlled in the same manner. In this case, a strategy that allows for
direct connection to an energized system would need to be employed.
5.5 Initializing the DSP Modules
Each of the hardware modules in the DSP requires register initializations that dictate how
a particular module will act when activated. The proceeding subsections describe the
initialization settings for the hardware modules used in the DSP.
5.5.1 Analog-to-Digital Converter
The analog-to-digital converter (ADC) converts the continuous-time signals from the
current and voltage sensors into series of discrete samples. For the scaled-down prototype the
ADC is initialized to sample at the fastest available sampling rate of 12.5 million samples per
second (MSPS) and was set to sample ten measurements continuously as follows:
1. Phase A inverter current
2. Phase A load current
3. Phase A grid voltage
4. dc-bus voltage
5. Phase B inverter current
6. Phase B load current
7. Phase B grid voltage
8. Phase C inverter current
9. Phase C load current
10. Phase C grid voltage
73
As a result the present values of each current and voltage sensors are always available in the
ADC conversion result register. Because the ADC module actually consists of two separate
eight-input multiplexors, ADCA and ADCB, they were initialized into cascade mode where they
can act as one sixteen-input multiplexor.
5.5.2 Pulse-Width Modulator
The pulse-width modulation hardware module, known as the ePWM module in the DSP
documentation, works on the same principle as described in section 2.6. The time-based counter
or timer that is used to emulate the carrier waveform in sinusoidal PWM is set to the up_down
count mode. This creates a symmetrical triangular waveform as opposed to up or down count
modes, which produce asymmetrical sawtooth carrier waveforms that in turn would produce
asymmetrical gate pulses. The period of the timer is set to ½ the period of the desired carrier
signal measured in clock cycles or 1500010.
Of the six ePWM modules used for the scaled-down prototype, ePWM1 is used as the
master module and dictates the timing of the remaining ePWM modules so that all six modules
count up and down in unison. When the timer is equal to zero, the value of the calculated control
signal for that switching cycle is loaded into the module and the pulses are generated directly by
the hardware without any further software intervention.
The “dead-band” sub-module within each ePWM module is initialized to automatically
insert a dead time between any gate signal transitions. Active-high complementary mode is used
so that the signals sent to the top and bottom IGBT of each half bridge in the UCSC are always
opposites. A dead band of 15010 clock cycles is also specified which translates to a dead time of
1.0 μs.
74
The “trip-zone” sub-module also resides within the PWM module and allows the user to
specify the behavior of the ePWM module during software or hardware events. The trip-zone
sub-module for each of the ePWM modules is configured to force all gate signals low when an
input pin is pulled low or action is triggered by software.
5.5.3 CPU Timer
A CPU Timer is a timer module with the DSP that waits for a specified amount of time
and then generates an interrupt. This was used in the UCSC to give the appropriate timing for the
discrete controller. The period value for CPU TIMER 0 was chosen as 750010 to generate an
interrupt at a rate of 20 kHz based on a clock frequency of 150 MHz.
5.6 Calculating the Dead Time for the Inverter-Leg Semiconductor Devices
A non-ideal transistor does not transition from on to off and vice versa instantaneously;
there is a specific time [1]. In gate controlled transistors like the MOSFET and IGBT, there is a
certain amount of charge stored in the gate that must be injected or removed in order to turn the
device on and off, respectively. The time to fully charge or discharge this gate-emitter
capacitance is a period of time when the transistor is still on or off even though the gate
signal coming from the controller is indicating the opposite should be true. For IGBTs after the
initial MOSFET action there is an additional amount of charge that must be depleted from within
the device itself adding to the turn-off time. This charge is in the form of minority carriers that
build up in the device [2]. An IGBT will still conduct a current while these carriers exist. This
extra current component is known as the “tail current” due to the shape it forms in a switching
diagram like the one shown in Fig. 5-2.
The IGBT itself has a turn-off delay, , as well as a current fall time, .
Another concern is the delay of the gate driver circuitry. The isolator and gate driver ICs used
75
have a range of delay times and , as well as fall times, and . These added
together are the minimum dead time to be used. This is summarized in:
(1)
These values can be taken from the manufacturer’s datasheet for each IC and are
displayed in Table 5-1. For driving the IGBTs in the scaled-down prototype a single chip
(Silicon Labs SI8261BCC-C-IS) was used for isolation and driving so the isolator delays are left
blank. To account for any variation in the performance among the ICs due to age, operating
conditions, temperature, and circuit damage, a safety margin of 15%-50% is added to the
minimum dead time. For the UCSC the dead time value is established as 1 μs.
Figure 5-2. Turn-off current waveform for an IGBT [2]
Table 5-1. Gate Driver Circuit IC Datasheet Parameters
Parameter Value (ns)
Maximum gate driver delay time 200
Maximum isolator delay time *
Maximum isolator fall time *
Maximum gate driver fall time 80
Maximum IGBT delay time 350
Maximum IGBT fall time 230 * isolator delay included in the gate driver delay
76
5.7 Modifications for EMI Reduction
The low voltages used in the DSP make it more susceptible to any interference from the
switching action of power electronic converters and the
from the gate signals that it triggers
[3]. These effects can cause false triggering of inputs and corrupted ADC measurements at
higher current and voltage levels. Internal pull-up resistors inside the DSP help to mitigate false
triggering in low EMI environments, but they are not sufficient at higher interference levels.
Placing a relatively small pull-up resistor (1-10 kΩ) external to the DSP input pin will
“strengthen” that input pin against a noisy environment because a larger current is required to
drive the pin low.
As suggested in [3], an RC filter with a high cut-off frequency was placed near the input
of each ADC pin. The capacitor near the input acts a charge bank for the sample-and-hold circuit
used in the ADC. This counteracts the voltage drop from any series inductance between the
signal conditioning circuits and the ADC input while also helping to eliminate high-frequency
noise.
At the ePWM output pins, an IC is used to boost the current and voltage output from the
4 mA and 3.3 V that can be produced by the DSP to 20 mA and 5.0 V. This reduces the stress on
the ePWM outputs and also drives the isolating IC in the gate driver circuitry with more current,
helping to increase the ratio of signal to common-mode noise that it experiences. In addition to
this twisted pair ribbon cables were used to help compensate for the relatively long distance that
the gate and sensor signals must travel. This helps to cancel out the inductive coupling that
causes noise in single wires [4]
77
5.8 Concluding Remarks
An overview of the controller as implemented in a DSP has been presented including
separate start-up and shutdown procedures because this was not addressed in the simulations.
The highlights for initializing each module used in the DSP were summarized and a complete
copy of the C program is given in Appendix B. With the controller defined in this chapter and
the prototype designed in Chapter 4, the prototype system was tested and the results are
presented in Chapter 6.
5.9 References
[1] Infineon Technologies AG, "How to calculate and minimize the dead time requirement for
IGBTs properly," Appl. Note AN2007-04 2007.
[2] N. Mohan, T. M. Undeland, and W. P. Robbins, Power Electronics: Converters Applications
and Design, 3rd ed. New Jersey, United States of America: JW&S Inc, 2003.
[3] Texas Instruments, "Hardware Design Guidelines for TMS320F28xx and TMS320F28xxx
DSCs," Application Note SPRAAS1C 2015.
[4] C. R. Paul and J. W. McKnight, "Prediction of Crosstalk Involving Twisted Pairs of Wires -
Part I: A Transmission-Line Model for Twisted-Wire Pairs," IEEE Transactions on
Electromagnetic Compatability, vol. EMC-21, no. 2, pp. 92-105, May 1979.
78
CHAPTER 6 6
TESTING OF THE UCSC PROTOTYPE
6.1 Experimental Setup
The experimental setup used to test the UCSC prototype is depicted in Fig. 6-1. The
system consists of:
A variable ac source with a maximum value of 208 VL-L that acts as the substation.
The load is represented by high-amperage three-phase line reactors with a cumulative
value of 3.0 mH in series with an unbalanced resistive load with equivalent resistance
values of 20, 30, and 40 Ω.
Figure 6-1. Experimental setup for testing of the UCSC prototype
79
Connected in parallel with the load immediately after the ac source is the UCSC which is
connected to the PCC through three 1:1 isolation transformers.
For protection of the system, the isolation transformers are connected via a 15 A fuse and
a 15 A breaker.
6.2 Testing of the UCSC Prototype
Displayed in Fig. 6-2 on the left side are the unbalanced currents that the UCSC has to
compensate which correspond to a UBF of 8.8%. The resulting substation currents during full
operation of the UCSC prototype are shown in Fig. 6-2 on the right side. The phase currents in
each of the figures are displayed in red, blue, and green, with the neutral current in blank. In Fig.
6-3 the phase shift between the phase voltage (blue) and current (black) before and after
compensation is shown. There is an improvement in power factor from 0.92 without compensate
to 0.999 with compensation.
The UCSC is effective at reducing the fundamental neutral current at the substation and
brings the system UBF to approximately 0.7%; however, some neutral current remains. These
Figure 6-2. Unbalanced load currents (left) and substation current (right) during testing
80
currents are produced by the inverters due to dead time distortion that occurs in a standard
unipolar switching scheme [1]. This distortion is easily seen in Fig. 6-4, which shows the phase
inverter currents during full operation and the FFT of the substation neutral current. The FFT
shows that the peak fundamental current component in the neutral has been reduced to 0.15 A
from 4.0 A, but a 3rd
harmonic peak current of 0.8 A is present. An FFT of one of the
Figure 6-3. Phase Voltage and Current before (left) and during (right) UCSC full operation
Figure 6-4. UCSC inverter currents (left) and FFT of the substation neutral current (right) during
full UCSC operation
81
substation phase currents is presented in Fig. 6-5 has a 6.0 % 3rd
harmonic current component;
the fundamental component is 4.0 A peak.
In an attempt to improve the performance of the UCSC several different tests were run to
decrease the effect of the zero-crossover distortion and thus the harmonic current output of the
UCSC inverters. The following sections describe the differences between these tests and their
effects.
6.2.1 Effect of Increasing the dc-bus Voltage
The dc bus was raised from 250 V to 300 V to test the performance of the inverter. The
resulting inverter currents are shown in Fig. 6-6 together with an FFT of the substation neutral
current. There is no significant change in the harmonic performance of the inverters.
6.2.2 Effect of a Decrease in the Dead Time
The dead time used during the transitions between the high and low switches was
decreased from 1.0 μs to 0.833 μs. An improvement is expected because the dead time is the
cause of distortion at the output of the inverters [1]. Fig. 6-7 shows the inverter current
Figure 6-5. FFT of the substation current
82
waveforms in addition to an FFT of the substation neutral current for this test. There is no
significant change in the harmonic content.
This could be due to the fact that the reduction in dead time was not large enough to
affect much change, or that other effects which are discussed in section 6.3 are responsible.
Figure 6-6. Inverter Currents (left) and FFT of substation neutral current (right) with 300 V
dc bus
Figure 6-7. Inverter Current (left) and FFT of substation neutral current (right) with 0.833
μs dead time
83
6.2.3 Effect of Increased Inverter Loading
A large induction motor with no shaft load is used to increase the reactive power
compensation requirement for the UCSC. The induction motor draws current at a power factor of
0.12 lagging which results in 2.0 A of inductive current. The load currents for which the UCSC
has to compensate are shown in Fig. 6-8, which still has a UBF of 8.8% because the additional
load is balanced. An FFT of the neutral current and the inverter currents from this test are shown
in Fig. 6-9. The magnitude of the 3rd
harmonic current is approximately 0.65 Apeak down from the
0.8 Apeak in the initial testing. This reduction is due to the change in phase shift between the
inverter phase currents, which causes some of the 3rd
harmonics to cancel out. A significant 3rd
harmonic still flows back to the substation as shown in Fig. 6-10.
6.3 Causes of Output Voltage Distortion in a Single-Phase Inverter
As mentioned previously in section 5.6, a dead time must be included in the transition
between the top and bottom switches conduction to avoid shorting the dc bus when using a half-
bridge configuration. When neither IGBT is conducting in the presence of an inductive load, the
Figure 6-8. Unbalanced load currents during increased load testing
84
voltage distortion that results is dependent upon the direction of the load current [2]. When
current is flowing towards the load, the freewheeling diode paired with the bottom switch
conducts during the off-time of the top switch, clamping the output voltage to the negative dc-
bus voltage. This results in a lower output voltage than is dictated by the control waveform sent
to the PWM generator. The output voltage is higher when the current is flowing towards the half-
bridge.
Figure 6-9. Inverter currents (left) and FFT of the substation neutral current (right) with
increased inverter loading
Figure 6-10. FFT of substation current with increased inverter loading
85
A solution for this current based distortion is suggested in [3] where a square waveform
is added to the sinusoidal output voltage. The square waveform is in phase with the output
current and has a magnitude given by:
(1)
where is the dead time, is the period of the carrier waveform, and is the dc-bus voltage.
Around the zero-crossing point of the voltage waveform, the PWM pulses are very small
and close to the width of the dead time band. This may result in the total elimination of a pulse,
or a pulse that is so short that the IGBTs cannot respond fast enough and thus lost. This paired
with the non-zero minimum voltage drop across the IGBT during conduction (on-state) results in
a distorted voltage at the output. Fig. 6-11 is an oscilloscope capture of the output voltage
(yellow) and the output current (blue) from one the inverters used in the UCSC. The load was
purely resistive in this case so the current and voltage distortion (encircled in red) looks identical,
but the current distortion will not appear at the zero-crossover point in the case of a leading or
lagging load power factor.
A potential solution for the voltage distortion based on [1] is a hybrid unipolar and
bipolar switching scheme. The inverter switches using unipolar modulation, but the inverter
Figure 6-11. Unipolar inverter output distortion due to dead time
86
changes to bipolar modulation near the zero-voltage crossover points. A simulation is run to
compare this modulation scheme to unipolar switching and the resulting voltage waveforms at
the output of the LCL filter are shown in Fig. 6-12. In the figure, bipolar modulation is used in a
30 degree band centered on either of the zero crossover points.
The effect on the magnitude of the harmonic current components produced is shown in
Fig. 6-13. The magnitude of the odd-integer current harmonics that are produced by the inverter
are reduced significantly in the hybrid scheme when compared to the pure unipolar switching
but, there is no significant change in the total THD. This is likely due to the higher harmonic
content that comes from bipolar switching. If this hybrid modulation scheme were used a more
effective output filter would need to be considered.
Fig. 6-14 shows several FFT of the neutral current from simulations a UCSC inverter to
demonstrate the benefits of compensating for these effect. Fig. 6-14(a) contains the FFT of the
system with dead time and device voltage drops, Fig. 6-14(b) if the FFT when there is no dead
time, Fig. 6-14(c) is the FFT when there is no device voltage drop and Fig. 6-14(d) shows the
FFT with neither dead time nor device voltage drop. The 3rd
harmonic component drop from 0.6
A to 0.18 A with dead time, 0.35 A with no device voltage drop and 0.01 A when neither are
Figure 6-12. Voltage (left) and current (right) waveforms produced from the hybrid
modulation scheme
87
Figure 6-13. FFT of inverter output current with unipolar (left) and hybrid (right)
modulation scheme
(a) (b)
(c) (d)
Figure 6-14. Simulation FFTs of substation neutral current under different operating
conditions
88
present.
6.4 Effect of Harmonic Voltage Components
The voltage in the power outlet in the testing lab contains a 3rd
harmonic component. This
voltage distortion is caused by harmonic currents produced by non-linear equipment in the
building (e.g., computers). This can cause issues with grid-connected inverters if there is no
compensation method for these harmonic voltages. This is evident in Fig. 6-15 below which
shows the UCSC working at the same operating point with and without a 5% 3rd
harmonic grid
voltage component. The compensator is working as intended in both instances but the waveforms
on the right show a significant 3rd
harmonic current that flows from the source and into the
UCSC. This is because there is no mechanism in this version of the UCSC controller that
compensates for harmonics present in the grid voltage.
An isolation transformer connected in a delta-wye configuration was used at the source to
eliminate this problem associated with this version of the UCSC. Because the 3rd
harmonic
voltage component in three-phase balanced systems has the same phase angle in each of the
Figure 6-15. Substation currents during UCSC operation without (left) and with (right)
grid voltage distortion
89
three-phases, the resulting line-to-line voltages that the delta-connected side of the isolation
transformer experiences is not affected by the distortion due to triplen harmonics [4]. This means
that the wye-grounded side of the isolation transformer at the source no longer has the 3rd
harmonic voltage component, so it is eliminated from the system used to test the UCSC.
Obviously, this represents a more ideal system, and thus less indicative of a real-world system,
but it enables the testing of this UCSC version which was not designed to compensate for
harmonic voltage distortion.
6.5 Effect of Improper Measurements
Using improper probes or testing points can lead to misleading current and voltage
measurements. Ideally, the probes used to measure voltage would have unlimited impedance and
have no effect on oscilloscope readings. However, actual probes have an impedance network that
interacts with parasitics that exist in the circuit being measured. The length of the probe
contributes to its parasitic inductance and this along with its effective capacitance can make it
unsuitable for high-frequency signals.
The turn-on gate-to-emitter voltage measurement of an IGBT as taken by an
unnecessarily long probe is shown in Fig. 6-16 on the left side. There is a significant amount of
voltage oscillation in the waveform, which suggests a problem with the gate drive circuitry. The
same measurement was taken on the right side, but using a probe that has much shorter leads.
The oscillations are no longer present, confirming that the gate driver circuit is preforming as
expected.
6.6 Conclusions
The scaled-down UCSC prototype was used to compensate for system currents that had a
UBF of 8.8% and a peak fundamental neutral current of 4.0 A. During steady-state operation the
90
UCSC was able to reduce the UBF of the system to 0.7% and the peak fundamental neutral
current to 0.15 A while achieving near unity power factor at the PCC. This proved that the
UCSC was effective at compensating for the fundamental negative- and zero-sequence current
components produced by unbalanced loads. A 3rd
harmonic current of 0.57 A was produced in
the neutral conductor due to distortion in the voltage output of the inverters. Three more tests
were conducted in an attempt to reduce this output voltage distortion. An increase in the dc-bus
voltage from 250 V to 300 V had no effect on the THD of the inverter output current and neither
did a small reduction of the dead time from 1.0 μs to 0.833 μs or an increase in the loading of the
inverter. It is important to note that results from tests with a distorted grid voltage showed that
without the ability to compensate for the 3rd
harmonic voltage, 3rd
harmonic currents can be
expected in the output of the UCSC.
6.7 References
[1] N. Mohan, T. M. Undeland, and W. P. Robbins, Power Electronics: Converters Applications
and Design, 3rd ed. New Jersey, United States of America: JW&S Inc, 2003.
Figure 6-16. IGBT Turn-on Vce without (left) and with (right) appropriate voltage probes
91
[2] Seung-Gi Jeong and Min-Ho Park, "The Analysis and Compensation of Dead-Time Effects
in PWM Inverters," IEEE Transaction on Inducstrial Electronics, vol. 38, no. 2, pp. 108-114,
April 1991.
[3] T. F. Wu, C. L. Kuo, K. H. Sun, and H. C. Hsieh, "Combined Unipolar and Bipolar PWM for
Current Distortion Improvement During Power Compensation," IEEE Transactions on Power
Electronics, vol. 29, no. 4, pp. 1702-1709, October 2013.
[4] Roger C. Dugan, Mark F. McGranaghan, Surya Santoso, and H. Wayne Beaty, Electrical
Power Systems Quality, 3rd ed.: McGraw-Hill, 2012.
92
CHAPTER 7 7
CONCLUSIONS AND FUTURE WORK
7.1 Conclusions
As elaborated in Chapter 1, several adverse effects can arise from unbalanced loading on
a distribution feeder. These include: potential overcurrent on the neutral conductor [1], electric
machine overheating [2], negative-sequence MMF interference with positive-sequence MMF [3],
and overheating of wye-ungrounded transformers [4]. An overview of existing solutions for
these issues was presented followed by a description of the solution developed in this paper, the
Unbalanced Current Static Compensator which is installed just downstream of the distribution
power transformer. It consists of three single-phase inverters coupled to grid using readily
available and low-cost distribution transformers.
The principles behind the operation of each part of the UCSC as well as a thorough
description of the controller used to run the system was shown in Chapter 2. This was followed
by the application of those control principles to develop Matlab/Simulink™-based simulations in
Chapter 3 that were indicative of the real-world implementation. With the viability of the
proposed solution confirmed through the simulation results, the construction of a scaled-down
prototype was addressed in Chapter 4. The constructed prototype was built to fully compensate
for a 10 kVA, 208 VL-L system and consisted of three single-phase inverters each rated 1 kVA,
120 VL-N coupled to the system through 1:1 isolation transformers.
The discrete controller implemented in the DSP was presented in Chapter 5. An
explanation of the steps taken to reduce the susceptibility of the DSP to EMI was given in
addition to a procedure for soft-starting the compensator and an orderly shutdown procedure to
93
avoid large currents. Using these techniques, testing data from the laboratory prototype were
captured and analyzed in Chapter 6. The UCSC was found to be effective at reducing the peak
fundamental current component in the neutral from 4.0 A to 0.15 A and the UBF of the system
from 8.8 % to approximately 0.7 % with power factor of 0.999 at the PCC. Unfortunately, there
was a third harmonic current of 0.57 A that flowed through the neutral conductor because of
distortion caused by the dead time used between gate pulses. A dc bus voltage increase from 250
V to 300 V, a dead time reduction from 1.0 μs to 0.833 μs, and an increase in the loading of the
inverter were all ineffective for reducing the distortion caused by the dead time.
The UCSC developed for the case study required three 1 MVA inverters to compensate a
6 MVA system in the case study. Rating each inverter in the compensator at nearly 17 % of the
rated power for the system is not economical. The installation of power factor correction
capacitors close to the UCSC could be a less expensive method for full power factor correction at
the substation.
7.2 Recommendations for Future Work
The ensuing subsections contain recommendations for future research based on the
existing solutions, the economics of the proposed solution, and the performance of the laboratory
prototype.
7.2.1 Implement a method for compensating the distortion due to dead time
To deploy the UCSC in the field the THD that it produces is dictated by standards for
grid connected equipment [5]. The performance of this UCSC prototype would not meet these
standards for grid connection and requires a dead time compensation method such as those
presented in [6] and [7].
94
7.2.2 Include of a mechanism for compensating for grid voltage distortion
The same argument as above applies to the inability of the controller to compensate for
grid voltage distortion. Without this capability the current drawn from the grid by the inverter
will contain the same harmonic content that exists in the grid voltage.
7.2.3 Develop applications for the UCSC in mesh networks
The proposed solution is only suited for power flow in one direction along a radial feeder.
With the higher penetration of distributed generation, bi-directional power flow may become
much more common. An area of research could be finding the appropriate position for the UCSC
in this type of system and giving the device the ability to compensate in either direction.
7.2.4 Apply the UCSC control to different three-phase inverter topologies
The proposed solution requires 12 IGBTs and 12 diodes compared to a three-phase four-
leg inverter which only requires 8 IGBTs and 8 diodes. Obviously, the four-leg topology is
cheaper, but it more complex to control. A performance comparison of these two topologies as
well as others such as in Fig. 7-1 can be done.
7.2.5 Augment the UCSC controller to compensate for harmonic currents
Elimination of harmonic currents from the source will improve system efficiency and has
some of the same effect as eliminating the fundamental negative- and zero-sequence current
components. Because the power electronics provide full control over output voltages, the
addition of this ability to the UCSCs controller does not require a redesign of the system.
95
7.2.6 Add the ability to partially compensate for reactive power
The majority of the current rating for the UCSC comes from the requirement for full
reactive power compensation. The ability to control the power factor at the PCC at a non-unity
value would be useful, because it could reduce the power rating required for the UCSC
solution and allow the UCSC to maintain its balancing capabilities even when the current limits
for the inverters have been reached. Implement a stationary reference frame controller for
comparison
Stationary reference frame controllers can be less computationally taxing than
synchronous frame controllers because neither a phase-lock loop nor a d-q transformation is
Figure 7-1. Shoot-through current immune topology [9]
96
required and they may have better a transient response as a result [8]. A comparison between an
instantaneous power controller in the stationary reference frame such as in [9], and the proposed
controller could provide insight into advantages and disadvantages of either method.
7.3 References
[1] J. Kennedy, C. A. Nucci, A. Borghetti, G. Contaxis A. P. S. Meliopoulos, "Power distribution
practices in USA and Europe: impact on power quality," in Proceedings of the 8th
International Conference on Harmonics and Quality of Power, Athens, 1998, pp. 24-29.
[2] R. G. Harley, E.B. Makram, and E.G. Duran, "The effects of unbalanced networks on
synchronous and asynchronous machine transient stability," Electric Power System Research,
vol. 13, no. 2, pp. 119-127, October 1987.
[3] R.H. Salim, R.A. Ramos, and N.G. Bretas, "Analysis of the small signal dynamic
performance of synchronous generators under unbalanced operating conditions," in IEEE
Power and Energy Society General Meeting, 2010, pp. 1-6.
[4] T.A. Short, Electrical Power Distribution Handbook. Boca Raton, FL: CRC Press Taylor &
Taylor Croup, 2004.
[5] Roger C. Dugan, Mark F. McGranaghan, Surya Santoso, and H. Wayne Beaty, Electrical
Power Systems Quality, 3rd ed.: McGraw-Hill, 2012.
[6] Seung-Gi Jeong and Min-Ho Park, "The Analysis and Compensation of Dead-Time Effects
in PWM Inverters," IEEE Transaction on Inducstrial Electronics, vol. 38, no. 2, pp. 108-114,
April 1991.
[7] T. F. Wu, C. L. Kuo, K. H. Sun, and H. C. Hsieh, "Combined Unipolar and Bipolar PWM for
Current Distortion Improvement During Power Compensation," IEEE Transactions on Power
Electronics, vol. 29, no. 4, pp. 1702-1709, October 2013.
[8] Matias Diaz and Roberto Cardenas, "Analysis of Synchronous and Stationary Reference
Frame Control Strategies to Fulfill LVRT Requirements in Wind Energy Conversion
Systems," in Ecological Vehicles and Renewable Energies (EVER), 2014 Ninth International
Conference on, Monte-Carlo, 2014, pp. 1 - 8.
[9] Singh G.N and P Rastgoufard, "A new topology of active filter to correct power-factor,
compensate harmonics, reactive power and unbalance of three-phase four-wire loads," in
Applied Power Electronics Conference and Exposition, Miami Beach, 2003, pp. 141-147.
97
APPENDIX A
SNUBBERS FOR SEMICONDUCTOR DEVICES
A.1 RCD Snubber
One solution to the problem of the oscillations is the use of a snubber circuit in parallel
with the IBGTs. Snubber circuits absorb the stored energy from the inductances and then
disperse that energy in a non-destructive way. Several different snubber topologies exist. One of
the basics is the RCD snubber used to absorb energy from the turn-off of a transistor. Fig. A-1
shows this snubber structure.
During the IGBT turn-off, the diode conducts the current that the parasitic inductances
are trying to maintain [1]. This results in the snubber capacitor being charged up to the applied
voltage level. When the IGBT turns on again the voltage across the capacitor drops dramatically
and it’s is drained through the snubber resistor. As a result, the resistor must dissipate this
Figure A-1. RCD Snubber Circuit
98
energy, but this is easier to manage than extra turn-on losses that would result in the IGBT
otherwise.
A.2 Overvoltage Snubber
Another form of protection is an overvoltage snubber that acts much like the turn-off
snubber, but the capacitor is connected across the dc-bus instead of the IGBT, and remains
charged to the bus value [1]. The diode conducts and charges the capacitor when the voltage of
the bus becomes larger than that of the capacitor like when there are oscillations. The excess
energy in the capacitor is drained through a resistor back to the dc bus. The circuit for this is
displayed in Fig. A-2.
A.3 Turn-On Snubber
In some cases, such as in half-bridge circuits, there are adverse effects that come from the
use of turn-off snubbers like the one mentioned above. This is due to the charging currents that
the snubber capacitors draw each switch cycle [1]. The bottom IGBT takes the load current when
turning on, but there is an extra current component flowing through the bottom switch because
the top switch’s snubber capacitor is charging. Because this extra current occurs during the turn-
on of the bottom switch, when both the voltage and current are non-zero, it can cause a
significant increase in switching losses for the bottom switch. To mitigate the extra losses that
might arise from this arrangement a turn-on snubber can be employed. One type of turn-on
snubber uses an inductor in series with the switch. This inductor, due to the changing current
during the turn-on of a device, takes some of the voltage that would normally be experienced
completely by the switch. At turn-off, the energy stored in the inductor is bled through a series
diode and resistor branch that is in parallel with the inductor. This avoids voltage oscillations
99
across the switch. A drawback to using this solution is the complexity it adds to the circuit.
A.4 Undeland Snubber
Employing all three of these snubbers on a half bridge circuit can be expensive and
requires significant space on the PCB, which can be a problem from a power density perspective.
The Undeland snubber combines all three of these snubbers into a hybrid snubber with a reduced
footprint and amount of components [1]. Fig. A-3 shows an implementation of this snubber.
Figure A-2. Overvoltage snubber
100
A.5 References
[1] N. Mohan, T. M. Undeland, and W. P. Robbins, Power Electronics: Converters Applications
and Design, 3rd ed. New Jersey, United States of America: JW&S Inc, 2003.
Figure A-3. Undeland Snubber Circuit
101
APPENDIX B
DIGITAL SIGNAL PROCESSOR CODE
Written in C below is the main.c file that is uploaded to the DSP. This contains the
register initialization presented in chapter 5 and the code used to implement the controller.
B.1 The Main.c File
#include "DSP28x_Project.h" // Device Headerfile and Examples Include File #include "Solar_F.h" #include "UCSC_Functions.h" #include "Phase.h" #include "SPLL_1ph_SOGI_MOD.h" #define PI 3.141592654 #define TWO_PI 6.283185308 #define Grid_freq 60.0 // control signal frequency of 60 Hz #define VoltagePeakMax 220.0 // Maximum instantaneous voltage measured by the voltage sensors #define dcbusref 250.0 // Reference level for the DC bus #define omegaLcoup 12.02 // 2*pi*60*Lcoup*CurrentMax ( 0.85 * 10 * sqrt(2) ), accounts for scaling #define FilterR 0.048 #define FilterL 0.00226 #define CurrentMax 14.14 // the maximum instantaneous current measured by the current sensors #define PWM1_TIMER_TBPRD 15000 // 15000 = 5 kHz, 7500 = 10 kHz, 18750 = 4 kHz, Configure the period for ePWM Time-Based Counter #define rc_freq 10.0 #define cc_freq 2000.0 #define deadtimecycles 150 #define FLASH_SELECT 1 ///////////////////////////////////////////////////////////////////////////////////// // If you change this you must change the discrete filter constants.///////// #define MEASUREFREQ 20000.0 //frequency at which values are sampled//////////////////////////////// ///////////////////////////////////////////////////////////////////////////////////// #pragma CODE_SECTION(CurrentControl, "UserFuncs"); #pragma CODE_SECTION(ReferenceGenerator, "UserFuncs"); #pragma CODE_SECTION(OverCurrentProtection, "UserFuncs"); #pragma CODE_SECTION(cpu_timer0_isr, "UserFuncs"); // Prototype statements for functions found within this file. // void AdcInitialize(void); // ADC initializing function interrupt void cpu_timer0_isr(void); //
102
void InitEPwm1Timer(void); // ePWM modules void InitEPwm2Timer(void); void InitEPwm3Timer(void); void InitEPwm4Timer(void); void InitEPwm5Timer(void); void InitEPwm6Timer(void); void CurrentControl(void); // current controller function void ReferenceGenerator(void); // PI error generator function void OverCurrentProtection(void); //Variables to update the PWM registers float control_a = 0.0, control_b = 0.0, control_c = 0.0; int ccbit = 0; // Class objects for sampling ADC ADC VaADC, IainvADC, IaLADC, VbADC, IbinvADC, IbLADC, VcADC, IcinvADC, IcLADC, VbusADC; // Class objects for PI controllers PI_controller Curr_Cont_Da, Curr_Cont_Qa, Curr_Cont_Refa, Curr_Cont_Db, Curr_Cont_Qb, Curr_Cont_Refb, Curr_Cont_Dc, Curr_Cont_Qc, Curr_Cont_Refc; // Class objects for OSG and d-q transformations SPLL_1ph_SOGI_F PARKS_Ia_inv, PARKS_Ia_L, VaPLL, PARKS_Ib_inv, PARKS_Ib_L, VbPLL, PARKS_Ic_inv, PARKS_Ic_L, VcPLL; // Class objects for notch filters NotchFilter VbusNotch; int i = 0, j = 0, ocdelay = 0; int ClearTrip = 0, RunControl = 0, EnablePWM = 1; float gain_a = 0.0, alpha_a = 0.0, gain_b = 0.0, alpha_b = 0.0, gain_c = 0.0, alpha_c = 0.0; float DaxisMag_a = 0.0, QaxisMag_a = 0.0, DaxisMag_b = 0.0, QaxisMag_b = 0.0, DaxisMag_c = 0.0, QaxisMag_c = 0.0; float dead_comp_a = 0.0, dead_comp_b = 0.0, dead_comp_c = 0.0; //static float radian_a = 0, radian_b = 0, radian_c = 0, Ts = TWO_PI*Grid_freq/MEASUREFREQ; float PhALegA = 0.0, PhALegB = 0.0, PhBLegA = 0.0, PhBLegB = 0.0, PhCLegA = 0.0, PhCLegB = 0.0; float ia = 0.0,ib = 0.0,ic = 0.0; void main(void) { #if FLASH_SELECT // This function is found in the MemCopy.c file and is required for stand-alone mode MemCopy(&RamfuncsLoadStart, &RamfuncsLoadEnd, &RamfuncsRunStart); MemCopy(&fastRTS_LoadStart, &fastRTS_LoadEnd, &fastRTS_RunStart); MemCopy(&UserFuncsLoadStart, &UserFuncsLoadEnd, &UserFuncsRunStart);
103
InitFlash(); #endif // PLL, WatchDog, enable Peripheral Clocks // This example function is found in the DSP2833x_SysCtrl.c file. InitSysCtrl(); // Initialize PIE control registers to their default state. // The default state is all PIE interrupts disabled and flags // are cleared. // This function is found in the DSP2833x_PieCtrl.c file. InitPieCtrl(); // Initialize the PIE vector table with pointers to the shell Interrupt // Service Routines (ISR). // This will populate the entire table, even if the interrupt // is not used in this example. This is useful for debug purposes. // The shell ISR routines are found in DSP2833x_DefaultIsr.c. // This function is found in DSP2833x_PieVect.c. InitPieVectTable(); // Step 3. Clear all interrupts and initialize PIE vector table: DINT; // Disable CPU interrupts // Disable CPU interrupts and clear all CPU interrupt flags: IER = 0x0000; IFR = 0x0000; //------ Populate the Interrupt vector addresses -------// EALLOW; PieVectTable.TINT0 = &cpu_timer0_isr; EDIS; SPLL_1ph_SOGI_F_init(Grid_freq,((float)(1.0/(MEASUREFREQ))),&VaPLL); SPLL_1ph_SOGI_F_coeff_update(((float)(1.0/(MEASUREFREQ))),(float)(2*PI*Grid_freq),&VaPLL); SPLL_1ph_SOGI_F_init(Grid_freq,((float)(1.0/(MEASUREFREQ))),&PARKS_Ia_inv); SPLL_1ph_SOGI_F_coeff_update(((float)(1.0/(MEASUREFREQ))),(float)(2*PI*Grid_freq),&PARKS_Ia_inv); SPLL_1ph_SOGI_F_init(Grid_freq,((float)(1.0/(MEASUREFREQ))),&PARKS_Ia_L); SPLL_1ph_SOGI_F_coeff_update(((float)(1.0/(MEASUREFREQ))),(float)(2*PI*Grid_freq),&PARKS_Ia_L); SPLL_1ph_SOGI_F_init(Grid_freq,((float)(1.0/(MEASUREFREQ))),&VbPLL); SPLL_1ph_SOGI_F_coeff_update(((float)(1.0/(MEASUREFREQ))),(float)(2*PI*Grid_freq),&VbPLL); SPLL_1ph_SOGI_F_init(Grid_freq,((float)(1.0/(MEASUREFREQ))),&PARKS_Ib_inv); SPLL_1ph_SOGI_F_coeff_update(((float)(1.0/(MEASUREFREQ))),(float)(2*PI*Grid_freq),&PARKS_Ib_inv);
104
SPLL_1ph_SOGI_F_init(Grid_freq,((float)(1.0/(MEASUREFREQ))),&PARKS_Ib_L); SPLL_1ph_SOGI_F_coeff_update(((float)(1.0/(MEASUREFREQ))),(float)(2*PI*Grid_freq),&PARKS_Ib_L); SPLL_1ph_SOGI_F_init(Grid_freq,((float)(1.0/(MEASUREFREQ))),&VcPLL); SPLL_1ph_SOGI_F_coeff_update(((float)(1.0/(MEASUREFREQ))),(float)(2*PI*Grid_freq),&VcPLL); SPLL_1ph_SOGI_F_init(Grid_freq,((float)(1.0/(MEASUREFREQ))),&PARKS_Ic_inv); SPLL_1ph_SOGI_F_coeff_update(((float)(1.0/(MEASUREFREQ))),(float)(2*PI*Grid_freq),&PARKS_Ic_inv); SPLL_1ph_SOGI_F_init(Grid_freq,((float)(1.0/(MEASUREFREQ))),&PARKS_Ic_L); SPLL_1ph_SOGI_F_coeff_update(((float)(1.0/(MEASUREFREQ))),(float)(2*PI*Grid_freq),&PARKS_Ic_L); //----------- PI Controller Initialization -------------// Curr_Cont_Da.Ts = (float)(1.0/(MEASUREFREQ)); //Period of Current controller Curr_Cont_Da.Ki = FilterR * cc_freq * CurrentMax; //Define the PI constants for Current Controller Curr_Cont_Da.Kp = FilterL * cc_freq * CurrentMax; PI_controller_init(&Curr_Cont_Da); Curr_Cont_Qa.Ts = (float)(1.0/(MEASUREFREQ)); Curr_Cont_Qa.Ki = FilterR * cc_freq * CurrentMax; Curr_Cont_Qa.Kp = FilterL * cc_freq * CurrentMax; PI_controller_init(&Curr_Cont_Qa); Curr_Cont_Refa.Ts = (float)(1.0/(MEASUREFREQ)); Curr_Cont_Refa.Ki = ( TWO_PI * rc_freq ) * ( TWO_PI * rc_freq ) * 0.0022; // / 3.0; //0.08 * 1.5; Curr_Cont_Refa.Kp = sqrt(2) * TWO_PI * rc_freq * 0.0022; //0.05 * 1.5; PI_controller_init(&Curr_Cont_Refa); Curr_Cont_Db.Ts = (float)(1.0/(MEASUREFREQ)); //Period of Current controller Curr_Cont_Db.Ki = FilterR * cc_freq * CurrentMax; //Define the PI constants for Current Controller Curr_Cont_Db.Kp = FilterL * cc_freq * CurrentMax; PI_controller_init(&Curr_Cont_Db); Curr_Cont_Qb.Ts = (float)(1.0/(MEASUREFREQ)); Curr_Cont_Qb.Ki = FilterR * cc_freq * CurrentMax; Curr_Cont_Qb.Kp = FilterL * cc_freq * CurrentMax; PI_controller_init(&Curr_Cont_Qb); Curr_Cont_Refb.Ts = (float)(1.0/(MEASUREFREQ)); Curr_Cont_Refb.Ki = ( TWO_PI * rc_freq ) * ( TWO_PI * rc_freq ) * 0.0022; // / 3.0; //0.08 * 1.5; Curr_Cont_Refb.Kp = sqrt(2) * TWO_PI * rc_freq * 0.0022; //0.05 * 1.5; PI_controller_init(&Curr_Cont_Refb); Curr_Cont_Dc.Ts = (float)(1.0/(MEASUREFREQ)); //Period of Current controller Curr_Cont_Dc.Ki = FilterR * cc_freq * CurrentMax; //Define the PI constants for Current Controller Curr_Cont_Dc.Kp = FilterL * cc_freq * CurrentMax; PI_controller_init(&Curr_Cont_Dc); Curr_Cont_Qc.Ts = (float)(1.0/(MEASUREFREQ));
105
Curr_Cont_Qc.Ki = FilterR * cc_freq * CurrentMax; Curr_Cont_Qc.Kp = FilterL * cc_freq * CurrentMax; PI_controller_init(&Curr_Cont_Qc); Curr_Cont_Refc.Ts = (float)(1.0/(MEASUREFREQ)); Curr_Cont_Refc.Ki = ( TWO_PI * rc_freq ) * ( TWO_PI * rc_freq ) * 0.0022; // / 3.0; //0.08 * 1.5; Curr_Cont_Refc.Kp = sqrt(2) * TWO_PI * rc_freq * 0.0022; //0.05 * 1.5; PI_controller_init(&Curr_Cont_Refc); //-------------- Initialize Notch Filter ---------------// Notch_Init(((float)(1.0/(MEASUREFREQ))),(float)(2*PI*Grid_freq),(float)0.00001,(float)0.1,&VbusNotch); //--------- ADC Read Function Initialization -----------// VaADC.midpoint = 2062; IainvADC.midpoint = 2044; IaLADC.midpoint = 2042; VbADC.midpoint = 2061; IbinvADC.midpoint = 2042; IbLADC.midpoint = 2055; VcADC.midpoint = 2063; IcinvADC.midpoint = 2044; IcLADC.midpoint = 2035; VbusADC.midpoint = 0; //----------- Initialize Device Peripherals ------------// InitEPwm1Timer(); // Initialize ePWMs InitEPwm2Timer(); InitEPwm3Timer(); InitEPwm4Timer(); InitEPwm5Timer(); InitEPwm6Timer(); EPwm1Regs.TZCLR.bit.OST = 1; EPwm2Regs.TZCLR.bit.OST = 1; EPwm3Regs.TZCLR.bit.OST = 1; EPwm4Regs.TZCLR.bit.OST = 1; EPwm5Regs.TZCLR.bit.OST = 1; EPwm6Regs.TZCLR.bit.OST = 1; EALLOW; EPwm1Regs.TZFRC.bit.OST = 1; EPwm2Regs.TZFRC.bit.OST = 1; EPwm3Regs.TZFRC.bit.OST = 1; EPwm4Regs.TZFRC.bit.OST = 1; EPwm5Regs.TZFRC.bit.OST = 1; EPwm6Regs.TZFRC.bit.OST = 1; EDIS; InitAdc(); // Init the ADC as far as turning it on, enabling clock, calibration AdcInitialize(); // Init the ADC for program specific settings
106
InitCpuTimers(); ConfigCpuTimer(&CpuTimer0, 150, (1/MEASUREFREQ)*1000000); // Configure the period for the CPU TIMER0 CpuTimer0Regs.TCR.all = 0x4001; // write to the entire register to make sure everything is set correctly after the InitCpuTimers() and ConfigCpuTimer() functions //--------------- Define GPIO pins used ----------------// EALLOW; // Inputs GpioCtrlRegs.GPAMUX2.bit.GPIO31 = 0; // '0' means general purpose use. otherwise it is used by a peripheral GpioCtrlRegs.GPADIR.bit.GPIO31 = 0; // 0 = input, 1 = output GpioCtrlRegs.GPAMUX2.bit.GPIO29 = 0; GpioCtrlRegs.GPADIR.bit.GPIO29 = 0; GpioCtrlRegs.GPBMUX1.bit.GPIO34 = 0; GpioCtrlRegs.GPBDIR.bit.GPIO34 = 0; GpioCtrlRegs.GPBMUX1.bit.GPIO32 = 0; GpioCtrlRegs.GPBDIR.bit.GPIO32 = 0; GpioCtrlRegs.GPAMUX2.bit.GPIO30 = 0; GpioCtrlRegs.GPADIR.bit.GPIO30 = 0; GpioCtrlRegs.GPAPUD.bit.GPIO30 = 0; // Outputs EDIS; AdcRegs.ADCTRL2.bit.SOC_SEQ1 = 1; // Start of conversion bit for sequence 1 //-------------- Turn on/Enable Interrupts -------------// PieCtrlRegs.PIEIER1.bit.INTx7 = 1; // Enable the CPUTIMER0 INTn in the PIE IER |= M_INT1; // Enable CPU INT1 which is connected to TINT0 EINT; // Enable Global interrupt INTM ERTM; // Enable Global realtime interrupt DBGM EALLOW; SysCtrlRegs.PCLKCR0.bit.TBCLKSYNC = 1; // Start all the timers sync'd EDIS; for(;;) { OverCurrentProtection(); CurrentControl(); } } void AdcInitialize(void) {
107
// Specific ADC setup for this example: AdcRegs.ADCTRL1.bit.ACQ_PS = 3; // Determine the number of clock cycles the Sample and Hold circuit holds the charge. AdcRegs.ADCTRL3.bit.ADCCLKPS = 3; // Determine the clock speed of the ADC. // ADCCLK = HSPCLK / (ADCCLKPS*2) / (CPS+1) // ADC module clock = 75.0MHz / (3*2) / (1+1) = 6.25MHz AdcRegs.ADCTRL1.bit.CPS = 1; // Clock prescalar. 0 = (clock/1) , 1 = (clock/2) AdcRegs.ADCREFSEL.bit.REF_SEL = 0x0; // Selects the internal voltage reference, which should be 3 V AdcRegs.ADCTRL3.bit.SMODE_SEL = 0; // Sets the mode of operation. 1 = simultaneous, 0 = sequential AdcRegs.ADCMAXCONV.all = 0x0009; // Sets the maximum number of auto conversions. There will be ADCMAXCONV + 1 conversions AdcRegs.ADCTRL1.bit.SEQ_CASC = 1; // 1 Cascaded mode. So both sequencers are acting as one. AdcRegs.ADCCHSELSEQ1.bit.CONV00 = 0x0; // Sets up a conversion from ADCINA0; which samples Iainv AdcRegs.ADCCHSELSEQ1.bit.CONV01 = 0x1; // ADCINA1; IaL AdcRegs.ADCCHSELSEQ1.bit.CONV02 = 0x2; // ADCINA2; Va AdcRegs.ADCCHSELSEQ1.bit.CONV03 = 0x3; // ADCINA3; Vbus AdcRegs.ADCCHSELSEQ2.bit.CONV04 = 0x4; // ADCINA4; Ibinv AdcRegs.ADCCHSELSEQ2.bit.CONV05 = 0x5; // ADCINA5; IbL AdcRegs.ADCCHSELSEQ2.bit.CONV06 = 0x6; // ADCINA6; Vb AdcRegs.ADCCHSELSEQ2.bit.CONV07 = 0x7; // ADCINA7; Icinv AdcRegs.ADCCHSELSEQ3.bit.CONV08 = 0x8; // ADCINB0; IcL AdcRegs.ADCCHSELSEQ3.bit.CONV09 = 0x9; // ADCINB1; Vc AdcRegs.ADCTRL1.bit.CONT_RUN = 1; // Setup whether or not it is in continuous run mode. '0' means not. /// Setup the offset register. Refer to page 31 of the ADC documentation. AdcRegs.ADCOFFTRIM.bit.OFFSET_TRIM = 0x000; // The format is 2's complement which allows negative offset correction. Only 9 bits. } void InitEPwm1Timer() { EALLOW; SysCtrlRegs.PCLKCR0.bit.TBCLKSYNC = 0; // Stop all the TB clocks EDIS; /// Initialize the Ports (GPIO Pins) InitEPwm1Gpio(); // enables pull-ups on ePWM1's output pins and select ePWM1's output pins /// Determine the Clock Prescalar EPwm1Regs.TBCTL.bit.HSPCLKDIV = 0; // Corresponds to a scalar of 1. This sets the clock to be 150 MHz. (T = 6.666667 ns) /// Determine the Timer Clock Prescalar EPwm1Regs.TBCTL.bit.CLKDIV = 0; // Corresponds to a scalar of of 1. This keeps the clock at 150 Mhz. /// Period of Timer
108
EPwm1Regs.TBPRD = PWM1_TIMER_TBPRD; /// Phase Shift- EPwm1Regs.TBPHS.half.TBPHS = 0; // Upon phase syncing. The counter resets to this value. // This is also the starting phase shift of the module. If it is ignoring phase synching then this just the starting point. /// Counting Mode of Timer EPwm1Regs.TBCTL.bit.CTRMODE = TB_COUNT_UPDOWN; // Count up to TBPRD and the immediately count back down to 0. Allows for symmetrical PWM signal. /// Allow each timer to be sync'ed EPwm1Regs.TBCTL.bit.PHSEN = TB_DISABLE; // This bit determines whether or not the ePWM module acknowledges the phase synch. Right now it's the 'Master Module'. /// Determine the use of Shadow Period Load Register EPwm1Regs.TBCTL.bit.PRDLD = TB_SHADOW; // Loads the TBPRD register when the timer counts to 0. This is good for changing periods, which is not the case here. /// Setup Sync EPwm1Regs.TBCTL.bit.SYNCOSEL = TB_CTR_ZERO; // This determines how the module deals with phase synching. This has all down-stream modules synced with PWM1. /// Determine use of Shadow Counter-Compare Registers (A and B) EPwm1Regs.CMPCTL.bit.SHDWAMODE = CC_SHADOW; // This uses the shadow register. This is good when counter-compare values are constantly changing like in PWM. EPwm1Regs.CMPCTL.bit.SHDWBMODE = CC_SHADOW; // see line above. This is for the counter value B. /// Determine when Counter-Compare Module is loaded EPwm1Regs.CMPCTL.bit.LOADAMODE = CC_CTR_ZERO_PRD; // This loads the values for register A at counter = 0. EPwm1Regs.CMPCTL.bit.LOADBMODE = CC_CTR_ZERO_PRD; // This loads the values for register B at counter = 0. /// Determines PWM action for counter = counter-compare EPwm1Regs.AQCTLA.bit.CAU = AQ_SET; // set on up count EPwm1Regs.AQCTLA.bit.CAD = AQ_CLEAR; // clears on down count // only A is set because B is complement unless specified otherwise in POLSEL register. Need CAU and CAD because of UPDOWN count. /// Enable the Dead-Band Module EPwm1Regs.DBCTL.bit.OUT_MODE = DB_FULL_ENABLE; // enables output dead-band for EPWM1A and EPWM1B. Necessary for avoiding shoot-through current. /// Determine the relationship between A and B EPwm1Regs.DBCTL.bit.POLSEL = DB_ACTV_HIC; //Active High Complementary Mode. B is opposite of A. /// Determine the Dead-Band length EPwm1Regs.DBRED = deadtimecycles; // Number of clock cycles for rise. (50 * 6.666667ns) EPwm1Regs.DBFED = deadtimecycles; // NUmber of clock cycles for fall. EALLOW; // Trip zone 1 used for ePWM1 EPwm1Regs.TZSEL.bit.OSHT1 = 1; EPwm1Regs.TZSEL.bit.CBC1 = 1; // What do we want the TZ1 to do? EPwm1Regs.TZCTL.bit.TZA = TZ_FORCE_LO; EPwm1Regs.TZCTL.bit.TZB = TZ_FORCE_LO; // Enable TZ interrupt EPwm1Regs.TZEINT.bit.OST = 1; EPwm1Regs.TZEINT.bit.CBC = 1; EDIS;
109
} void InitEPwm2Timer() { EALLOW; SysCtrlRegs.PCLKCR0.bit.TBCLKSYNC = 0; // Stop all the TB clocks EDIS; /// Initialize the Ports (GPIO Pins) InitEPwm2Gpio(); // enables pull-ups on ePWM1's output pins and select ePWM1's output pins /// Determine the Clock Prescalar EPwm2Regs.TBCTL.bit.HSPCLKDIV = 0; // Corresponds to a scalar of 1. This sets the clock to be 150 MHz. (T = 6.666667 ns) /// Determine the Timer Clock Prescalar EPwm2Regs.TBCTL.bit.CLKDIV = 0; // Corresponds to a scalar of 1. This keeps the clock at 150 Mhz. /// Period of Timer EPwm2Regs.TBPRD = PWM1_TIMER_TBPRD; /// Phase Shift- EPwm2Regs.TBPHS.half.TBPHS = 0; // Upon phase syncing. The counter resets to this value. // This is also the starting phase shift of the module. If it is ignoring phase synching then this just the starting point. /// Counting Mode of Timer EPwm2Regs.TBCTL.bit.CTRMODE = TB_COUNT_UPDOWN; // Count up to TBPRD and the immediately count back down to 0. Allows for symmetrical PWM signal. /// Allow each timer to be sync'ed EPwm2Regs.TBCTL.bit.PHSEN = TB_ENABLE; // This bit determines whether or not the ePWM module acknowledges the phase synch. Right now it's a 'Slave Module'. /// Determine the use of Shadow Period Load Register EPwm2Regs.TBCTL.bit.PRDLD = TB_SHADOW; // Loads the TBPRD register when the timer counts to 0. This is good for changing periods, which is not the case here. /// Setup Sync EPwm2Regs.TBCTL.bit.SYNCOSEL = TB_SYNC_IN; // This determines how the module deals with phase synching. This takes in a sync signal from upstream. /// Determine use of Shadow Counter-Compare Registers (A and B) EPwm2Regs.CMPCTL.bit.SHDWAMODE = CC_SHADOW; // This uses the shadow register. This is good when counter-compare values are constantly changing like in PWM. EPwm2Regs.CMPCTL.bit.SHDWBMODE = CC_SHADOW; // see line above. This is for the counter value B. /// Determine when Counter-Compare Module is loaded EPwm2Regs.CMPCTL.bit.LOADAMODE = CC_CTR_ZERO; // This loads the values for register A at counter = 0. EPwm2Regs.CMPCTL.bit.LOADBMODE = CC_CTR_ZERO; // This loads the values for register B at counter = 0. /// Determines PWM action for counter = counter-compare EPwm2Regs.AQCTLA.bit.CAU = AQ_SET; // toggles output for up-count EPwm2Regs.AQCTLA.bit.CAD = AQ_CLEAR; // does nothing for down-count // only A is set because B is complement unless specified otherwise in POLSEL register. Need CAU and CAD because of UPDOWN count. /// Enable the Dead-Band Module EPwm2Regs.DBCTL.bit.OUT_MODE = DB_FULL_ENABLE; // enables output dead-band for EPWM1A and EPWM1B. Necessary for avoiding shoot-through current.
110
/// Determine the relationship between A and B EPwm2Regs.DBCTL.bit.POLSEL = DB_ACTV_HIC; //Active High Complementary Mode. B is opposite of A. /// Determine the Dead-Band length EPwm2Regs.DBRED = deadtimecycles; // Number of clock cycles for rise. (50 * 6.666667ns) EPwm2Regs.DBFED = deadtimecycles; // NUmber of clock cycles for fall. EPwm2Regs.ETSEL.bit.INTSEL = ET_CTR_ZERO; // Select INT on Zero event EPwm2Regs.ETSEL.bit.INTEN = 0; // Enable INT EPwm2Regs.ETPS.bit.INTPRD = ET_1ST; // Generate INT on 1st event, can also do 2nd and 3rd EALLOW; // Trip Zone 1 used for ePWM2 EPwm2Regs.TZSEL.bit.OSHT1 = 1; EPwm2Regs.TZSEL.bit.CBC1 = 1; // What do we want the TZ1 to do? EPwm2Regs.TZCTL.bit.TZA = TZ_FORCE_LO; EPwm2Regs.TZCTL.bit.TZB = TZ_FORCE_LO; // Enable TZ interrupt EPwm2Regs.TZEINT.bit.OST = 1; EPwm2Regs.TZEINT.bit.CBC = 1; EDIS; } void InitEPwm3Timer() { EALLOW; SysCtrlRegs.PCLKCR0.bit.TBCLKSYNC = 0; // Stop all the TB clocks EDIS; /// Initialize the Ports (GPIO Pins) InitEPwm3Gpio(); // enables pull-ups on ePWM1's output pins and select ePWM1's output pins /// Determine the Clock Prescalar EPwm3Regs.TBCTL.bit.HSPCLKDIV = 0; // Corresponds to a scalar of 1. This sets the clock to be 150 MHz. (T = 6.666667 ns) /// Determine the Timer Clock Prescalar EPwm3Regs.TBCTL.bit.CLKDIV = 0; // Corresponds to a scalar of of 1. This keeps the clock at 150 Mhz. /// Period of Timer EPwm3Regs.TBPRD = PWM1_TIMER_TBPRD; /// Phase Shift- EPwm3Regs.TBPHS.half.TBPHS = 0; // Upon phase syncing. The counter resets to this value. // This is also the starting phase shift of the module. If it is ignoring phase synching then this just the starting point. /// Counting Mode of Timer EPwm3Regs.TBCTL.bit.CTRMODE = TB_COUNT_UPDOWN; // Count up to TBPRD and the immediately count back down to 0. Allows for symmetrical PWM signal. /// Allow each timer to be sync'ed EPwm3Regs.TBCTL.bit.PHSEN = TB_ENABLE; // This bit determines whether or not
111
the ePWM module acknowledges the phase synch. Right now it's a 'Slave Module'. /// Determine the use of Shadow Period Load Register EPwm3Regs.TBCTL.bit.PRDLD = TB_SHADOW; // Loads the TBPRD register when the timer counts to 0. This is good for changing periods, which is not the case here. /// Setup Sync EPwm3Regs.TBCTL.bit.SYNCOSEL = TB_SYNC_IN; // This determines how the module deals with phase synching. This takes in a sync signal from upstream. /// Determine use of Shadow Counter-Compare Registers (A and B) EPwm3Regs.CMPCTL.bit.SHDWAMODE = CC_SHADOW; // This uses the shadow register. This is good when counter-compare values are constantly changing like in PWM. EPwm3Regs.CMPCTL.bit.SHDWBMODE = CC_SHADOW; // see line above. This is for the counter value B. /// Determine when Counter-Compare Module is loaded EPwm3Regs.CMPCTL.bit.LOADAMODE = CC_CTR_ZERO; // This loads the values for register A at counter = 0. EPwm3Regs.CMPCTL.bit.LOADBMODE = CC_CTR_ZERO; // This loads the values for register B at counter = 0. /// Determines PWM action for counter = counter-compare EPwm3Regs.AQCTLA.bit.CAU = AQ_SET; // toggles output for up-count EPwm3Regs.AQCTLA.bit.CAD = AQ_CLEAR; // does nothing for down-count // only A is set because B is complement unless specified otherwise in POLSEL register. Need CAU and CAD because of UPDOWN count. /// Enable the Dead-Band Module EPwm3Regs.DBCTL.bit.OUT_MODE = DB_FULL_ENABLE; // enables output dead-band for EPWM1A and EPWM1B. Necessary for avoiding shoot-through current. /// Determine the relationship between A and B EPwm3Regs.DBCTL.bit.POLSEL = DB_ACTV_HIC; //Active High Complementary Mode. B is opposite of A. /// Determine the Dead-Band length EPwm3Regs.DBRED = deadtimecycles; // Number of clock cycles for rise. (50 * 6.666667ns) EPwm3Regs.DBFED = deadtimecycles; // NUmber of clock cycles for fall. EPwm3Regs.ETSEL.bit.INTSEL = ET_CTR_ZERO; // Select INT on Zero event EPwm3Regs.ETSEL.bit.INTEN = 0; // Enable INT EPwm3Regs.ETPS.bit.INTPRD = ET_1ST; // Generate INT on 1st event, can also do 2nd and 3rd EALLOW; // Trip Zone 1 used for ePwm3 EPwm3Regs.TZSEL.bit.OSHT1 = 1; EPwm3Regs.TZSEL.bit.CBC1 = 1; // What do we want the TZ1 to do? EPwm3Regs.TZCTL.bit.TZA = TZ_FORCE_LO; EPwm3Regs.TZCTL.bit.TZB = TZ_FORCE_LO; // Enable TZ interrupt EPwm3Regs.TZEINT.bit.OST = 1; EPwm3Regs.TZEINT.bit.CBC = 1; EDIS; } void InitEPwm4Timer() {
112
EALLOW; SysCtrlRegs.PCLKCR0.bit.TBCLKSYNC = 0; // Stop all the TB clocks EDIS; /// Initialize the Ports (GPIO Pins) InitEPwm4Gpio(); // enables pull-ups on ePWM1's output pins and select ePWM1's output pins /// Determine the Clock Prescalar EPwm4Regs.TBCTL.bit.HSPCLKDIV = 0; // Corresponds to a scalar of 1. This sets the clock to be 150 MHz. (T = 6.666667 ns) /// Determine the Timer Clock Prescalar EPwm4Regs.TBCTL.bit.CLKDIV = 0; // Corresponds to a scalar of of 1. This keeps the clock at 150 Mhz. /// Period of Timer EPwm4Regs.TBPRD = PWM1_TIMER_TBPRD; /// Phase Shift- EPwm4Regs.TBPHS.half.TBPHS = 0; // Upon phase syncing. The counter resets to this value. // This is also the starting phase shift of the module. If it is ignoring phase synching then this just the starting point. /// Counting Mode of Timer EPwm4Regs.TBCTL.bit.CTRMODE = TB_COUNT_UPDOWN; // Count up to TBPRD and the immediately count back down to 0. Allows for symmetrical PWM signal. /// Allow each timer to be sync'ed EPwm4Regs.TBCTL.bit.PHSEN = TB_ENABLE; // This bit determines whether or not the ePWM module acknowledges the phase synch. Right now it's a 'Slave Module'. /// Determine the use of Shadow Period Load Register EPwm4Regs.TBCTL.bit.PRDLD = TB_SHADOW; // Loads the TBPRD register when the timer counts to 0. This is good for changing periods, which is not the case here. /// Setup Sync EPwm4Regs.TBCTL.bit.SYNCOSEL = TB_SYNC_IN; // This determines how the module deals with phase synching. This takes in a sync signal from upstream. /// Determine use of Shadow Counter-Compare Registers (A and B) EPwm4Regs.CMPCTL.bit.SHDWAMODE = CC_SHADOW; // This uses the shadow register. This is good when counter-compare values are constantly changing like in PWM. EPwm4Regs.CMPCTL.bit.SHDWBMODE = CC_SHADOW; // see line above. This is for the counter value B. /// Determine when Counter-Compare Module is loaded EPwm4Regs.CMPCTL.bit.LOADAMODE = CC_CTR_ZERO; // This loads the values for register A at counter = 0. EPwm4Regs.CMPCTL.bit.LOADBMODE = CC_CTR_ZERO; // This loads the values for register B at counter = 0. /// Determines PWM action for counter = counter-compare EPwm4Regs.AQCTLA.bit.CAU = AQ_SET; // toggles output for up-count EPwm4Regs.AQCTLA.bit.CAD = AQ_CLEAR; // does nothing for down-count // only A is set because B is complement unless specified otherwise in POLSEL register. Need CAU and CAD because of UPDOWN count. /// Enable the Dead-Band Module EPwm4Regs.DBCTL.bit.OUT_MODE = DB_FULL_ENABLE; // enables output dead-band for EPWM1A and EPWM1B. Necessary for avoiding shoot-through current. /// Determine the relationship between A and B EPwm4Regs.DBCTL.bit.POLSEL = DB_ACTV_HIC; //Active High Complementary Mode. B is opposite of A. /// Determine the Dead-Band length EPwm4Regs.DBRED = deadtimecycles; // Number of clock cycles for rise. (50 *
113
6.666667ns) EPwm4Regs.DBFED = deadtimecycles; // NUmber of clock cycles for fall. EPwm4Regs.ETSEL.bit.INTSEL = ET_CTR_ZERO; // Select INT on Zero event EPwm4Regs.ETSEL.bit.INTEN = 0; // Enable INT EPwm4Regs.ETPS.bit.INTPRD = ET_1ST; // Generate INT on 1st event, can also do 2nd and 3rd EALLOW; // Trip Zone 1 used for ePwm4 EPwm4Regs.TZSEL.bit.OSHT1 = 1; EPwm4Regs.TZSEL.bit.CBC1 = 1; // What do we want the TZ1 to do? EPwm4Regs.TZCTL.bit.TZA = TZ_FORCE_LO; EPwm4Regs.TZCTL.bit.TZB = TZ_FORCE_LO; // Enable TZ interrupt EPwm4Regs.TZEINT.bit.OST = 1; EPwm4Regs.TZEINT.bit.CBC = 1; EDIS; } void InitEPwm5Timer() { EALLOW; SysCtrlRegs.PCLKCR0.bit.TBCLKSYNC = 0; // Stop all the TB clocks EDIS; /// Initialize the Ports (GPIO Pins) InitEPwm5Gpio(); // enables pull-ups on ePWM1's output pins and select ePWM1's output pins /// Determine the Clock Prescalar EPwm5Regs.TBCTL.bit.HSPCLKDIV = 0; // Corresponds to a scalar of 1. This sets the clock to be 150 MHz. (T = 6.666667 ns) /// Determine the Timer Clock Prescalar EPwm5Regs.TBCTL.bit.CLKDIV = 0; // Corresponds to a scalar of of 1. This keeps the clock at 150 Mhz. /// Period of Timer EPwm5Regs.TBPRD = PWM1_TIMER_TBPRD; /// Phase Shift- EPwm5Regs.TBPHS.half.TBPHS = 0; // Upon phase syncing. The counter resets to this value. // This is also the starting phase shift of the module. If it is ignoring phase synching then this just the starting point. /// Counting Mode of Timer EPwm5Regs.TBCTL.bit.CTRMODE = TB_COUNT_UPDOWN; // Count up to TBPRD and the immediately count back down to 0. Allows for symmetrical PWM signal. /// Allow each timer to be sync'ed EPwm5Regs.TBCTL.bit.PHSEN = TB_ENABLE; // This bit determines whether or not the ePWM module acknowledges the phase synch. Right now it's a 'Slave Module'. /// Determine the use of Shadow Period Load Register EPwm5Regs.TBCTL.bit.PRDLD = TB_SHADOW; // Loads the TBPRD register when the timer counts to 0. This is good for changing periods, which is not the case here. /// Setup Sync
114
EPwm5Regs.TBCTL.bit.SYNCOSEL = TB_SYNC_IN; // This determines how the module deals with phase synching. This takes in a sync signal from upstream. /// Determine use of Shadow Counter-Compare Registers (A and B) EPwm5Regs.CMPCTL.bit.SHDWAMODE = CC_SHADOW; // This uses the shadow register. This is good when counter-compare values are constantly changing like in PWM. EPwm5Regs.CMPCTL.bit.SHDWBMODE = CC_SHADOW; // see line above. This is for the counter value B. /// Determine when Counter-Compare Module is loaded EPwm5Regs.CMPCTL.bit.LOADAMODE = CC_CTR_ZERO; // This loads the values for register A at counter = 0. EPwm5Regs.CMPCTL.bit.LOADBMODE = CC_CTR_ZERO; // This loads the values for register B at counter = 0. /// Determines PWM action for counter = counter-compare EPwm5Regs.AQCTLA.bit.CAU = AQ_SET; // toggles output for up-count EPwm5Regs.AQCTLA.bit.CAD = AQ_CLEAR; // does nothing for down-count // only A is set because B is complement unless specified otherwise in POLSEL register. Need CAU and CAD because of UPDOWN count. /// Enable the Dead-Band Module EPwm5Regs.DBCTL.bit.OUT_MODE = DB_FULL_ENABLE; // enables output dead-band for EPWM1A and EPWM1B. Necessary for avoiding shoot-through current. /// Determine the relationship between A and B EPwm5Regs.DBCTL.bit.POLSEL = DB_ACTV_HIC; //Active High Complementary Mode. B is opposite of A. /// Determine the Dead-Band length EPwm5Regs.DBRED = deadtimecycles; // Number of clock cycles for rise. (50 * 6.666667ns) EPwm5Regs.DBFED = deadtimecycles; // NUmber of clock cycles for fall. EPwm5Regs.ETSEL.bit.INTSEL = ET_CTR_ZERO; // Select INT on Zero event EPwm5Regs.ETSEL.bit.INTEN = 0; // Enable INT EPwm5Regs.ETPS.bit.INTPRD = ET_1ST; // Generate INT on 1st event, can also do 2nd and 3rd EALLOW; // Trip Zone 1 used for ePwm5 EPwm5Regs.TZSEL.bit.OSHT1 = 1; EPwm5Regs.TZSEL.bit.CBC1 = 1; // What do we want the TZ1 to do? EPwm5Regs.TZCTL.bit.TZA = TZ_FORCE_LO; EPwm5Regs.TZCTL.bit.TZB = TZ_FORCE_LO; // Enable TZ interrupt EPwm5Regs.TZEINT.bit.OST = 1; EPwm5Regs.TZEINT.bit.CBC = 1; EDIS; } void InitEPwm6Timer() { EALLOW; SysCtrlRegs.PCLKCR0.bit.TBCLKSYNC = 0; // Stop all the TB clocks EDIS; /// Initialize the Ports (GPIO Pins)
115
InitEPwm6Gpio(); // enables pull-ups on ePWM1's output pins and select ePWM1's output pins /// Determine the Clock Prescalar EPwm6Regs.TBCTL.bit.HSPCLKDIV = 0; // Corresponds to a scalar of 1. This sets the clock to be 150 MHz. (T = 6.666667 ns) /// Determine the Timer Clock Prescalar EPwm6Regs.TBCTL.bit.CLKDIV = 0; // Corresponds to a scalar of of 1. This keeps the clock at 150 Mhz. /// Period of Timer EPwm6Regs.TBPRD = PWM1_TIMER_TBPRD; /// Phase Shift- EPwm6Regs.TBPHS.half.TBPHS = 0; // Upon phase syncing. The counter resets to this value. // This is also the starting phase shift of the module. If it is ignoring phase synching then this just the starting point. /// Counting Mode of Timer EPwm6Regs.TBCTL.bit.CTRMODE = TB_COUNT_UPDOWN; // Count up to TBPRD and the immediately count back down to 0. Allows for symmetrical PWM signal. /// Allow each timer to be sync'ed EPwm6Regs.TBCTL.bit.PHSEN = TB_ENABLE; // This bit determines whether or not the ePWM module acknowledges the phase synch. Right now it's a 'Slave Module'. /// Determine the use of Shadow Period Load Register EPwm6Regs.TBCTL.bit.PRDLD = TB_SHADOW; // Loads the TBPRD register when the timer counts to 0. This is good for changing periods, which is not the case here. /// Setup Sync EPwm6Regs.TBCTL.bit.SYNCOSEL = TB_SYNC_IN; // This determines how the module deals with phase synching. This takes in a sync signal from upstream. /// Determine use of Shadow Counter-Compare Registers (A and B) EPwm6Regs.CMPCTL.bit.SHDWAMODE = CC_SHADOW; // This uses the shadow register. This is good when counter-compare values are constantly changing like in PWM. EPwm6Regs.CMPCTL.bit.SHDWBMODE = CC_SHADOW; // see line above. This is for the counter value B. /// Determine when Counter-Compare Module is loaded EPwm6Regs.CMPCTL.bit.LOADAMODE = CC_CTR_ZERO; // This loads the values for register A at counter = 0. EPwm6Regs.CMPCTL.bit.LOADBMODE = CC_CTR_ZERO; // This loads the values for register B at counter = 0. /// Determines PWM action for counter = counter-compare EPwm6Regs.AQCTLA.bit.CAU = AQ_SET; // toggles output for up-count EPwm6Regs.AQCTLA.bit.CAD = AQ_CLEAR; // does nothing for down-count // only A is set because B is complement unless specified otherwise in POLSEL register. Need CAU and CAD because of UPDOWN count. /// Enable the Dead-Band Module EPwm6Regs.DBCTL.bit.OUT_MODE = DB_FULL_ENABLE; // enables output dead-band for EPWM1A and EPWM1B. Necessary for avoiding shoot-through current. /// Determine the relationship between A and B EPwm6Regs.DBCTL.bit.POLSEL = DB_ACTV_HIC; //Active High Complementary Mode. B is opposite of A. /// Determine the Dead-Band length EPwm6Regs.DBRED = deadtimecycles; // Number of clock cycles for rise. (50 * 6.666667ns) EPwm6Regs.DBFED = deadtimecycles; // NUmber of clock cycles for fall. EPwm6Regs.ETSEL.bit.INTSEL = ET_CTR_ZERO; // Select INT on Zero event EPwm6Regs.ETSEL.bit.INTEN = 0; // Enable INT
116
EPwm6Regs.ETPS.bit.INTPRD = ET_1ST; // Generate INT on 1st event, can also do 2nd and 3rd EALLOW; // Trip Zone 1 used for ePwm6 EPwm6Regs.TZSEL.bit.OSHT1 = 1; EPwm6Regs.TZSEL.bit.CBC1 = 1; // What do we want the TZ1 to do? EPwm6Regs.TZCTL.bit.TZA = TZ_FORCE_LO; EPwm6Regs.TZCTL.bit.TZB = TZ_FORCE_LO; // Enable TZ interrupt EPwm6Regs.TZEINT.bit.OST = 1; EPwm6Regs.TZEINT.bit.CBC = 1; EDIS; } interrupt void cpu_timer0_isr(void) { ccbit = 1; // Turn on this bit to allow the current controller to be run // CurrentControl(); CpuTimer0Regs.TCR.bit.TIF = 1; CpuTimer0Regs.TCR.bit.TSS = 0; CpuTimer0Regs.TCR.bit.TRB = 1; PieCtrlRegs.PIEACK.all = PIEACK_GROUP1;// Acknowledge this interrupt to receive more interrupts from group 1 } void ReferenceGenerator() { float average, vbus_err; static float Vref = 10.0; static float k = 0.0, m = 0.0; average = (PARKS_Ia_L.u_D[0] + PARKS_Ib_L.u_D[0] + PARKS_Ic_L.u_D[0]) / 3.0; vbus_err = (VbusNotch.y[0] - Vref) * 0.0707; if(!GpioDataRegs.GPADAT.bit.GPIO31) // go into reactive-power-compensation/dc-bus mode { if(!GpioDataRegs.GPBDAT.bit.GPIO34) // go into current balancing/reactive-power-compensation/dc-bus mode { if (m < 1.0) { m += 0.00001; }
117
Curr_Cont_Refa.err = vbus_err - (PARKS_Ia_L.u_D[0] - PARKS_Ia_inv.u_D[0] - average) * m; Curr_Cont_Refb.err = vbus_err - (PARKS_Ib_L.u_D[0] - PARKS_Ib_inv.u_D[0] - average) * m; Curr_Cont_Refc.err = vbus_err - (PARKS_Ic_L.u_D[0] - PARKS_Ic_inv.u_D[0] - average) * m; } else // stay in reactive-power-compensation/dc-bus mode { Curr_Cont_Refa.err = vbus_err; Curr_Cont_Refb.err = vbus_err; Curr_Cont_Refc.err = vbus_err; } if (k < 1.0) { k += 0.00001; } Curr_Cont_Qa.err = PARKS_Ia_L.u_Q[0] * k - PARKS_Ia_inv.u_Q[0]; // update the q-axis current PI controller Curr_Cont_Qb.err = PARKS_Ib_L.u_Q[0] * k - PARKS_Ib_inv.u_Q[0]; // update the q-axis current PI controller Curr_Cont_Qc.err = PARKS_Ic_L.u_Q[0] * k - PARKS_Ic_inv.u_Q[0]; // update the q-axis current PI controller } else // This is the starting mode, just maintains the dc-bus voltage { Curr_Cont_Refa.err = vbus_err; Curr_Cont_Refb.err = vbus_err; Curr_Cont_Refc.err = vbus_err; Curr_Cont_Qa.err = 0.0 - PARKS_Ia_inv.u_Q[0]; Curr_Cont_Qb.err = 0.0 - PARKS_Ib_inv.u_Q[0]; Curr_Cont_Qc.err = 0.0 - PARKS_Ic_inv.u_Q[0]; } PI_controller_FUNC(&Curr_Cont_Refa); // run the reference generator PI controller PI_controller_FUNC(&Curr_Cont_Refb); // run the reference generator PI controller PI_controller_FUNC(&Curr_Cont_Refc); // run the reference generator PI controller if(Vref < dcbusref) // Soft start the first inverter { Vref += 0.0005; // Curr_Cont_Da.Ki = 0.1; if(Curr_Cont_Refa.U < -0.25){Curr_Cont_Refa.U = -0.25; Curr_Cont_Refa.U_1 = -0.25;} if(Curr_Cont_Refb.U < -0.25){Curr_Cont_Refb.U = -0.25; Curr_Cont_Refb.U_1 = -0.25;} if(Curr_Cont_Refc.U < -0.25){Curr_Cont_Refc.U = -0.25; Curr_Cont_Refc.U_1 = -0.25;} }
118
} void CurrentControl() { if (ccbit == 1) // This bit switched in PWM interrupt to time the current controller { float norm_denom; // static float DaxisMag_a_prev = 0.0, QaxisMag_a_prev = 0.0, DaxisMag_b_prev = 0.0, QaxisMag_b_prev = 0.0, DaxisMag_c_prev = 0.0, QaxisMag_c_prev = 0.0; // static float Iainv_prev = 0.0, Ibinv_prev = 0.0, Icinv_prev = 0.0, Vbus_prev = 9.0; if(j < 10000) { j++; ClearTrip = 0; } else{ClearTrip = 1;} //---------- ADC Sample Collection and Conditioning ------------// ADC_Read(&IainvADC, AdcMirror.ADCRESULT0); ADC_Read(&IbinvADC, AdcMirror.ADCRESULT4); ADC_Read(&IcinvADC, AdcMirror.ADCRESULT7); ADC_Read(&IaLADC, AdcMirror.ADCRESULT1); ADC_Read(&IbLADC, AdcMirror.ADCRESULT5); ADC_Read(&IcLADC, AdcMirror.ADCRESULT8); ADC_Read(&VaADC, AdcMirror.ADCRESULT2); ADC_Read(&VbADC, AdcMirror.ADCRESULT6); ADC_Read(&VcADC, AdcMirror.ADCRESULT9); ADC_Read(&VbusADC, AdcMirror.ADCRESULT3); VbusADC.out *= 225; // 175 = 350Vmax/2 Notch_Filter_Func(&VbusNotch, VbusADC.out); //----------------- PLL and Magnitude -------------------// VaPLL.u[0] = VaADC.out; SPLL_1ph_SOGI_F_FUNC(&VaPLL); VbPLL.u[0] = VbADC.out; SPLL_1ph_SOGI_F_FUNC(&VbPLL); VcPLL.u[0] = VcADC.out; SPLL_1ph_SOGI_F_FUNC(&VcPLL); //----------- Park's Transformations ----------------//
119
PARKS_Ia_inv.u[0] = IainvADC.out; SPLL_1ph_SOGI_F_FUNC_SOGIPARK(&PARKS_Ia_inv, VaPLL.sin, VaPLL.cos); // Outputs: -PARKS_Ia_inv.u_D[0], PARKS_Ia_inv.u_Q[0], for some reason D-axis is neg; PARKS_Ia_L.u[0] = IaLADC.out; SPLL_1ph_SOGI_F_FUNC_SOGIPARK(&PARKS_Ia_L, VaPLL.sin, VaPLL.cos); PARKS_Ib_inv.u[0] = IbinvADC.out; SPLL_1ph_SOGI_F_FUNC_SOGIPARK(&PARKS_Ib_inv, VbPLL.sin, VbPLL.cos); PARKS_Ib_L.u[0] = IbLADC.out; SPLL_1ph_SOGI_F_FUNC_SOGIPARK(&PARKS_Ib_L, VbPLL.sin, VbPLL.cos); PARKS_Ic_inv.u[0] = IcinvADC.out; SPLL_1ph_SOGI_F_FUNC_SOGIPARK(&PARKS_Ic_inv, VcPLL.sin, VcPLL.cos); // Outputs: -PARKS_Ia_inv.u_D[0], PARKS_Ia_inv.u_Q[0], for some reason D-axis is neg PARKS_Ic_L.u[0] = IcLADC.out; SPLL_1ph_SOGI_F_FUNC_SOGIPARK(&PARKS_Ic_L, VcPLL.sin, VcPLL.cos); /////////////////////////////////////////////////////////// //---------------- Current Controller -------------------// /////////////////////////////////////////////////////////// if(RunControl == 1) { ReferenceGenerator(); Curr_Cont_Da.err = Curr_Cont_Refa.U + PARKS_Ia_inv.u_D[0]; // update the d-axis current PI controller PI_controller_FUNC(&Curr_Cont_Da); // run the d- and q- axis current PI controllers PI_controller_FUNC(&Curr_Cont_Qa); Curr_Cont_Db.err = Curr_Cont_Refb.U + PARKS_Ib_inv.u_D[0]; // update the d-axis current PI controller PI_controller_FUNC(&Curr_Cont_Db); // run the d- and q- axis current PI controllers PI_controller_FUNC(&Curr_Cont_Qb); Curr_Cont_Dc.err = Curr_Cont_Refc.U + PARKS_Ic_inv.u_D[0]; // update the d-axis current PI controller PI_controller_FUNC(&Curr_Cont_Dc); // run the d- and q- axis current PI controllers PI_controller_FUNC(&Curr_Cont_Qc); // Determine the d- and q- axis component of the voltage output DaxisMag_a = Curr_Cont_Da.U - ( omegaLcoup * PARKS_Ia_inv.u_Q[0] ) + VaPLL.u_D[0] * VoltagePeakMax; QaxisMag_a = Curr_Cont_Qa.U - ( omegaLcoup * PARKS_Ia_inv.u_D[0] );
120
DaxisMag_b = Curr_Cont_Db.U - ( omegaLcoup * PARKS_Ib_inv.u_Q[0] ) + VbPLL.u_D[0] * VoltagePeakMax; QaxisMag_b = Curr_Cont_Qb.U - ( omegaLcoup * PARKS_Ib_inv.u_D[0] ); DaxisMag_c = Curr_Cont_Dc.U - ( omegaLcoup * PARKS_Ic_inv.u_Q[0] ) + VcPLL.u_D[0] * VoltagePeakMax; QaxisMag_c = Curr_Cont_Qc.U - ( omegaLcoup * PARKS_Ic_inv.u_D[0] ); //----- Find control waveform function and its mag ------// //|Asin(x) + Bcos(x)| = sqrt( A^2 + B^2 ) gain_a = sqrt(DaxisMag_a * DaxisMag_a + QaxisMag_a * QaxisMag_a); alpha_a = DaxisMag_a * VaPLL.sin + QaxisMag_a * VaPLL.cos; gain_b = sqrt(DaxisMag_b * DaxisMag_b + QaxisMag_b * QaxisMag_b); alpha_b = DaxisMag_b * VbPLL.sin + QaxisMag_b * VbPLL.cos; gain_c = sqrt(DaxisMag_c * DaxisMag_c + QaxisMag_c * QaxisMag_c); alpha_c = DaxisMag_c * VcPLL.sin + QaxisMag_c * VcPLL.cos; //---------- Normalize the control waveform -------------// norm_denom = 2.0*VbusADC.out*VbusADC.out; control_a = gain_a / (norm_denom) * alpha_a + 0.5; control_b = gain_b / (norm_denom) * alpha_b + 0.5; control_c = gain_c / (norm_denom) * alpha_c + 0.5; ia = IainvADC.out; ib = IbinvADC.out; ic = IcinvADC.out; if(ia > 0.0){PhALegA = control_a + 0.0; PhALegB = control_a - 0.0;} if(ia < 0.0){PhALegA = control_a - 0.0; PhALegB = control_a + 0.0;} if(ib > 0.0){PhBLegA = control_b + 0.0; PhBLegB = control_b - 0.0;} if(ib < 0.0){PhBLegA = control_b - 0.0; PhBLegB = control_b + 0.0;} if(ic > 0.0){PhCLegA = control_c + 0.0; PhCLegB = control_c - 0.0;} if(ic < 0.0){PhCLegA = control_c - 0.0; PhCLegB = control_c + 0.0;} //-----------------Update the PWM Module -------------------// EPwm1Regs.CMPA.half.CMPA = PWM1_TIMER_TBPRD * ( 1.0 - PhALegA ); // Counter Compare value updated for Phase A, Leg 1 EPwm2Regs.CMPA.half.CMPA = PWM1_TIMER_TBPRD * ( PhALegB ); // Counter Compare value updated for Phase A, Leg 2
121
EPwm3Regs.CMPA.half.CMPA = PWM1_TIMER_TBPRD * ( 1.0 - PhBLegA ); // Counter Compare value updated for Phase B, Leg 1 EPwm4Regs.CMPA.half.CMPA = PWM1_TIMER_TBPRD * ( PhBLegB ); // Counter Compare value updated for Phase B, Leg 2 EPwm5Regs.CMPA.half.CMPA = PWM1_TIMER_TBPRD * ( 1.0 - PhCLegA ); // Counter Compare value updated for Phase C, Leg 1 EPwm6Regs.CMPA.half.CMPA = PWM1_TIMER_TBPRD * ( PhCLegB ); // Counter Compare value updated for Phase C, Leg 2 } // end bracket for controller ON/OFF flag ccbit = 0; // turn off this bit till the next CPUTIMER0 interrupt, so that the controller doesn't continuously run. } // ccbit if statement end bracket } void OverCurrentProtection() { if(ocdelay == 2000) { if (AdcMirror.ADCRESULT0 > 3789 || AdcMirror.ADCRESULT0 < 307) //--- overcurrent trip protection, turns off inverter if d-axis current is too big { EALLOW; EPwm1Regs.TZFRC.bit.OST = 1; EPwm2Regs.TZFRC.bit.OST = 1; EDIS; EnablePWM = 0; } else { if(ClearTrip == 1 && VaPLL.ZCD == 1 && EnablePWM == 1) { RunControl = 1; EALLOW; EPwm1Regs.TZCLR.bit.OST = 1; EPwm2Regs.TZCLR.bit.OST = 1; EDIS; } } if (AdcMirror.ADCRESULT4 > 3789 || AdcMirror.ADCRESULT4 < 307) //--- overcurrent trip protection, turns off inverter if d-axis current is too big { EALLOW; EPwm3Regs.TZFRC.bit.OST = 1; EPwm4Regs.TZFRC.bit.OST = 1; EDIS; EnablePWM = 0;
122
} else { if(ClearTrip == 1 && VbPLL.ZCD == 1 && EnablePWM == 1) { RunControl = 1; EALLOW; EPwm3Regs.TZCLR.bit.OST = 1; EPwm4Regs.TZCLR.bit.OST = 1; EDIS; } } if (AdcMirror.ADCRESULT7 > 3789 || AdcMirror.ADCRESULT7 < 307) //--- overcurrent trip protection, turns off inverter if d-axis current is too big { EALLOW; EPwm5Regs.TZFRC.bit.OST = 1; EPwm6Regs.TZFRC.bit.OST = 1; EDIS; EnablePWM = 0; } else { if(ClearTrip == 1 && VcPLL.ZCD == 1 && EnablePWM == 1) { RunControl = 1; EALLOW; EPwm5Regs.TZCLR.bit.OST = 1; EPwm6Regs.TZCLR.bit.OST = 1; EDIS; } } } // oc end bracket else{ocdelay++;} if(!GpioDataRegs.GPADAT.bit.GPIO30) { EALLOW; EPwm1Regs.TZFRC.bit.OST = 1; EPwm2Regs.TZFRC.bit.OST = 1; EPwm3Regs.TZFRC.bit.OST = 1; EPwm4Regs.TZFRC.bit.OST = 1; EPwm5Regs.TZFRC.bit.OST = 1; EPwm6Regs.TZFRC.bit.OST = 1; EDIS; RunControl = 0; ClearTrip = 0; EnablePWM = 0; } } //===========================================================================
123
// No more. //===========================================================================